This is a mechanical engineering bid set for interior renovations at Atlantic Cape Community College's Atlantic City Campus, located at 1535 Bacharach Boulevard in Atlantic City, New Jersey. The project, identified as Bid No. 1883 - Atlantic City One Stop, encompasses mechanical, electrical, and plumbing work designed by consulting engineer Richard L. Delp, P.E. (New Jersey Professional Engineer No. GE45368). The scope includes mechanical ductwork demolition on the first and second floors, mechanical piping demolition on the first floor, and new mechanical ductwork and piping installation on both floors. The bid set contains detailed floor plans at 1/8"=1'-0" scale showing partial layouts for both stories, along with a comprehensive ventilation schedule detailing 48 distinct spaces across the facility. The ventilation schedule specifies room classifications per IMC 2021 standards, room dimensions, outdoor air rates, occupancy densities, and CFM (cubic feet per minute) requirements for each space, ranging from storage areas and corridors to classrooms, offices, testing areas, and restroom facilities. Bidders are required to submit all required bid forms, bid security, certifications, subcontractor documentation, and supporting materials electronically through the College's Bonfire eProcurement Portal by the specified deadline.
The mechanical design utilizes existing RTU-1 (rooftop unit) equipment to serve the various zones throughout the facility. All spaces have been calculated with zone air distribution effectiveness factors and zone outdoor airflow rates to ensure compliance with ventilation standards. The project includes fan coil unit control diagrams and detailed mechanical systems documentation to support the bidding and construction process. No specific pricing terms, award dates, contract duration, or renewal options are detailed within this engineering bid set document.
View the file
Other files
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
M0.1
Consulting M/E/P Engineers
RICHARD L. DELP, P.E.
New Jersey Professional Engineer
NO. GE45368
DM1.1
RICHARD L. DELP, P.E.
New Jersey Professional Engineer
NO. GE45368
1/8"=1'-0"
MECHANICAL DUCTWORK DEMOLITION PARTIAL FIRST FLOOR PLAN
DM1.2
RICHARD L. DELP, P.E.
New Jersey Professional Engineer
NO. GE45368
1/8"=1'-0"
MECHANICAL DUCTWORK DEMOLITION PARTIAL SECOND FLOOR PLAN
DM2.1
RICHARD L. DELP, P.E.
New Jersey Professional Engineer
NO. GE45368
1/8"=1'-0"
MECHANICAL PIPING DEMOLITION PARTIAL FIRST FLOOR PLAN
M1.1
RICHARD L. DELP, P.E.
New Jersey Professional Engineer
NO. GE45368
1/8"=1'-0"
MECHANICAL DUCTWORK NEW WORK PARTIAL FIRST FLOOR PLAN
M1.2
1/8"=1'-0"
MECHANICAL DUCTWORK NEW WORK PARTIAL SECOND FLOOR PLAN
Consulting M/E/P Engineers
RICHARD L. DELP, P.E.
UP
M2.1
Consulting M/E/P Engineers
RICHARD L. DELP, P.E.
New Jersey Professional Engineer
NO. GE45368
1/8"=1'-0"
MECHANICAL PIPING NEW WORK PARTIAL SECOND FLOOR PLAN
1/8"=1'-0"
MECHANICAL DUCTWORK NEW WORK PARTIAL FIRST FLOOR PLAN
ROOM NAME
IMC 2021 OCCUPANCY
CLASSIFICATION
AREA (FT2)
Az
ROOM
HEIGHT (FT)
NUMBER OF
FIXTURES
IMC 2021 EXHAUST
CFM PER FIXTURE
IMC 2021
CFM PER
SQUARE
FOOT
TOTAL
ZONE
EXHAUST
CFM /
PERSON Rp
AREA
OUTDOOR
AIR RATE Ra
OCCUPANT
DENSITY
PER 1000
FT2
BREATHING SINGLE
ZONE OUTDOOR
AIR FLOW RATE
Voz=Vbz
ZONE AIR
DISTRIBUTION
EFFECTIVENESS
Ez
ZONE
POPULATION Pz
ZONE OUTDOOR
AIRFLOW CFM
Voz (SINGLE
ZONE)
ACTUAL OA CFM
PROVIDED TO
SPACE
(EXISTING)
SERVED BY REMARKS
1ST FLOOR
WAITING/RECEPTION AREA 134 RECEPTION AREAS 881 9.5 0 0 0 0 5 0.06 30 116 0.8 8 120 120 (E)RTU-1
CASHIER 134A OFFICE SPACES 89 9.5 0 0 0 0 5 0.06 5 13 0.8 1 15 20 (E)RTU-1
WORK SPACE 134C OFFICE SPACES 162 9.5 0 0 0 0 5 0.06 5 18 0.8 1 20 20 (E)RTU-1
CORRIDOR 134D OFFICE SPACES 1,095 9.5 0 0 0 0 5 0.06 5 120 0.8 6 120 120 (E)RTU-1
BREAKROOM 135 OFFICE SPACES 112 9.5 0 0 0 0 5 0.06 5 15 0.8 1 15 80 (E)RTU-1
OFFICE 139 OFFICE SPACES 131 9.5 0 0 0 0 5 0.06 5 16 0.8 1 20 20 (E)RTU-1
OFFICE 140 OFFICE SPACES 150 9.5 0 0 0 0 5 0.06 5 18 0.8 1 20 20 (E)RTU-1
HUDDLE 142 CONFERENCE ROOMS 83 9.5 0 0 0 0 5 0.06 50 37 0.8 5 40 40 (E)RTU-1
HUDDLE 143 CONFERENCE ROOMS 88 9.5 0 0 0 0 5 0.06 50 38 0.8 5 40 40 (E)RTU-1
HUDDLE 144 CONFERENCE ROOMS 83 9.5 0 0 0 0 5 0.06 50 37 0.8 5 40 40 (E)RTU-1
HUDDLE 145 CONFERENCE ROOMS 88 9.5 0 0 0 0 5 0.06 50 38 0.8 5 40 40 (E)RTU-1
CONFERENCE 146 CONFERENCE ROOMS 159 9.5 0 0 0 0 5 0.06 50 62 0.8 8 65 75 (E)RTU-1
STORAGE 147 STORAGE ROOMS 102 9.5 0 0 0 0 0 0.12 0 15 0.8 0 20 20 (E)RTU-1
TESTING WAITING AREA 148 RECEPTION AREAS 435 9.5 1 0 0 0 5 0.06 30 95 0.8 10 100 100 (E)RTU-1
FACULTY 148 OFFICE SPACES 139 9.5 0 0 0 0 5 0.06 5 17 0.8 1 20 50 (E)RTU-1
TESTING 149 CLASSROOMS (9 PLUS) 580 9.5 0 0 0 0 10 0.12 35 400 0.8 25 400 400 (E)RTU-1
STORAGE 150 STORAGE ROOMS 102 9.5 0 0 0 0 0 0.12 0 15 0.8 10 20 20 (E)RTU-1
PROCOTOR 151 OFFICE SPACES 151 9.5 0 0 0 0 5 0.06 5 18 0.8 1 20 20 (E)RTU-1
IT CLOSET 152 CORRIDORS & UTILITIES 197 9.5 0 0 0 0 0 0.06 0 15 0.8 0 15 20 (E)RTU-1
PRIVATE TESTING ROOM 153 OFFICE SPACES 103 9.5 0 0 0 0 5 0.06 5 14 0.8 1 15 20 (E)RTU-1 CFA RESOURCE ROOM 154 CLASSROOMS (9 PLUS) 369 9.5 0 0 0 0 10 0.12 35 143 0.8 7 145 150 (E)RTU-1
ACCESSIBLE TOILET ROOM 180 TOILET/JANITOR CLOSET (PUBLIC) 80 9.5 1 70 0 70 0 0 0 0 0.8 0 0 75 (E)RTU-1 CORRIDOR 100 CORRIDORS & UTILITIES 649 9.5 0 0 0 0 0 0.06 0 49 0.8 0 50 300 (E)RTU-1
MEN'S 126 TOILET/JANITOR CLOSET (PUBLIC) 9.5 2 70 0 140 0 0 0 0 0.8 0 0 150 (E)RTU-1 WOMEN'S 127 TOILET/JANITOR CLOSET (PUBLIC) 9.5 2 70 0 140 0 0 0 0 0.8 0 0 150 (E)RTU-1
2ND FLOOR
LANGUAGE LAB 249 CLASSROOMS (9 PLUS) 806 9.5 0 0 0 0 10 0.12 35 483 0.8 29 485 600 (E)RTU-1
CLASSROOM 251 OFFICE SPACES 295 9.5 0 0 0 0 5 0.06 5 35 0.8 2 35 80 (E)RTU-1
OFFICE 252 OFFICE SPACES 244 9.5 0 0 0 0 5 0.06 5 31 0.8 2 35 40 (E)RTU-1
OFFICE 254 OFFICE SPACES 131 9.5 0 0 0 0 5 0.06 5 16 0.8 1 20 80 (E)RTU-1
OFFICE 255 OFFICE SPACES 160 9.5 0 0 0 0 5 0.06 5 18 0.8 1 20 80 (E)RTU-1
CLASSROOM 256 CLASSROOMS (9 PLUS) 692 9.5 0 0 0 0 10 0.12 35 416 0.8 25 420 600 (E)RTU-1
OFFICE 259 OFFICE SPACES 155 9.5 0 0 0 0 5 0.06 5 18 0.8 1 20 220 (E)RTU-1
WOMEN TOILET 261 TOILET/JANITOR CLOSET (PUBLIC) 228 9.5 4 70 0 280 0 0 0 0 0.8 0 300 300 (E)RTU-1
OFFICE 264 OFFICE SPACES 235 9.5 0 0 0 0 5 0.06 5 30 0.8 2 35 80 (E)RTU-1
CLASSROOM 266 CLASSROOMS (9 PLUS) 328 9.5 0 0 0 0 10 0.12 35 199 0.8 12 200 270 (E)RTU-1 MEN TOILET 271 TOILET/JANITOR CLOSET (PUBLIC) 403 9.5 9 70 0 630 0 0 0 0 0.8 0 650 650 (E)RTU-1
CLASSROOM 274 CLASSROOMS (9 PLUS) 711 9.5 0 0 0 0 10 0.12 35 419 0.8 25 420 420 (E)RTU-1 CLASSROOM 275 CLASSROOMS (9 PLUS) 350 9.5 0 0 0 0 10 0.12 35 215 0.8 13 215 270 (E)RTU-1
CASINO 276 CLASSROOMS (9 PLUS) 3,070 9.5 0 0 0 0 10 0.12 35 1336 0.8 70 1,340 1,460 (E)RTU-1 1
OFFICE 277 OFFICE SPACES 202 9.5 0 0 0 0 5 0.06 5 28 0.8 2 30 220 (E)RTU-1
CLASSROOM 278 CLASSROOMS (9 PLUS) 379 9.5 0 0 0 0 10 0.12 35 232 0.8 14 235 250 (E)RTU-1 CLASSROOM 282 CLASSROOMS (9 PLUS) 489 9.5 0 0 0 0 10 0.12 35 298 0.8 18 300 300 (E)RTU-1 CLASSROOM 284 CLASSROOMS (9 PLUS) 350 9.5 0 0 0 0 10 0.12 35 215 0.8 13 215 270 (E)RTU-1
COMPUTER LAB 287 COMPUTER LAB 1,124 9.5 0 0 0 0 10 0.12 25 531 0.8 29 535 540 (E)RTU-1 DISTANCE EDUCATION 288 CLASSROOMS (9 PLUS) 746 9.5 0 0 0 0 10 0.12 35 449 0.8 27 450 450 (E)RTU-1
CLASSROOM 291 CLASSROOMS (9 PLUS) 370 9.5 0 0 0 0 10 0.12 35 218 0.8 13 220 225 (E)RTU-1 CLASSROOM 294 CLASSROOMS (9 PLUS) 422 9.5 0 0 0 0 10 0.12 35 251 0.8 15 255 270 (E)RTU-1
OFFICE 295 OFFICE SPACES 297 9.5 0 0 0 0 5 0.06 5 35 0.8 2 35 40 (E)RTU-1
CASINO 296 CLASSROOMS (9 PLUS) 1,132 9.5 0 0 0 0 10 0.12 35 570 0.8 32 570 630 (E)RTU-1 1
CLASSROOM 297 CLASSROOMS (9 PLUS) 1,311 9.5 0 0 0 0 10 0.12 35 597 0.8 32 600 630 (E)RTU-1 1
OFFICE 299 OFFICE SPACES 147 9.5 0 0 0 0 5 0.06 5 17 0.8 1 20 20 (E)RTU-1
OFFICE 303 OFFICE SPACES 971 9.5 0 0 0 0 5 0.06 5 104 0.8 5 105 120 (E)RTU-1
NOTES:
1. ACTUAL EXISTING OCCUPANCY USED FOR OUTSIDE AIR CALCULATIONS.
VENTILATION SCHEDULE - ATLANTIC CAPE COMMUNITY COLLEGE
Consulting M/E/P Engineers
RICHARD L. DELP, P.E.
New Jersey Professional Engineer
M3.1
NOT TO SCALE
FAN COIL UNIT CONTROL DIAGRAM
M4.1
Consulting M/E/P Engineers
RICHARD L. DELP, P.E.
M5.1
RICHARD L. DELP, P.E.
M5.2
RICHARD L. DELP, P.E.