This file contains drawings and bid documents for a federal contract solicitation to replace air handling units at a Veterans Affairs medical facility. The solicitation number is 36C24824R0010 to replace AHUs 22 and 23 under project 673-21-152 at the Veterans Integrated Service Network 8 facility. Responses are due by small businesses for this project, which involves replacing two air handling units to improve heating, ventilation and air conditioning systems. The contract award is expected before the end of the current fiscal year.

View the file

Other files

Show all 13

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

T43

T33

T34

T34a

T49

T78 T77

37?

G001

Department of Veterans Affairs

3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437

COA: FL #29758

AKEA Project No. AD204-22

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

A

U.S. Department of Veterans Affairs

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

321 4 5 6 7 8 10

A/E REPLACE AHUs 22 AND 23

TAMPA, FLORIDA

673-21-152

APRIL 14, 2023Revisions: Date:

Office of Construction and Facilities Management

ARCHITECT / ENGINEER OF RECORDCONSULTANT

A

B

C

D

E

F

JAMES A. HALEY VA HOSPITAL

BUILDING #30

13000 BRUCE B. DOWNS BLVD.

FINAL DESIGN

APPROVED FOR CONSTRUCTION

TITLE PAGE, LOCATION MAP,

AND INDEX OF DRAWINGS

William Rodriguez-Arroyo

2023.04.12 12:08:17 -04'00'

A-101 DETAIL NUMBER

SHEET WHERE DRAWN

DETAIL REFERENCE

SIM

A

NEW GRID

IDENTIFICATION

LAYOUT GRID LINES

A102

ELEVATION NUMBER AND

DIRECTION OF VIEW

SHEET WHERE DRAWN

INTERIOR ELEVATION REFERENCE

101 ROOM NUMBER

ROOM NAME

ROOM TAG

ROOM NUMBER

ROOM FINISH

BASE FINISH

WALL FINISH

ROOM NAME

FINISH PLAN ROOM TAG

SECTION NUMBER

SHEET WHERE DRAWN

DIRECTION OF VIEW

A-101

SIM

SECTION

A-101

SIM

ELEVATION NUMBER

AND DIRECTION

SHEET WHERE DRAWN

SECTION DETAIL REFERENCE

B3B PARTITION SYMBOL

SEE SHEET A-620

PARTITION TYPE IDENTIFICATION MARK

A

EXISTING GRID

IDENTIFICATION

ELEVATION NUMBER

DIRECTION OF VIEW1

A-101

SIM

EXTERIOR ELEVATION

SHEET WHERE DRAWN

SCALE: 1/8" = 1'-0"

BASIC DRAWING

TITLE

DRAWING TITLE SYMBOLS

VIEW NAME

INDICATES HEIGHT

ABOVE PROJECT DATUM

+10'-0"

SECOND LEVEL

NAME OF LEVEL

LEVEL LINE

SEE CORRESPONDING

NUMBERED KEY NOTE ON SHEET

WHERE REFERENCE OCCURS

KEYED NOTE MARKED

REVISION NUMBER - SEE

REVISION HISTORY ON THE TITLE

BLOCK OF EACH SHEET

EXTENT OF CURRENT

REVISION

REVISION NUMBER AND EXTENT

CEILING TYPE TAG

CEILING TYPE TAG WITH

CEILING HEIGHT. HEIGHT

INDICATED IS AFF

2'X2' RECESSED LIGHT

FIXTURE

2'X4' RECESSED

LIGHT FIXTURE

FIRE PROTECTION-

SPRINKLER HEAD

F FIRE PROTECTION-

FIRE ALARM DEVICE

GYPSUM BOARD

CEILING OR SOFFIT

GWB

APC CEILING - 2X2 OR 2X4

AS INDICATED ON CEILING PLAN

APC-X

COVE LIGHT (NOT ALL

INDICATED)

RECESSED LINEAR

LIGHT FIXTURE

PENDANT/SUSPENDED

LIGHT FIXTURE

PENDANT/SUSPENDED

LIGHT FIXTURE

EXIT SIGN,

SINGLE-SIDED EXIT SIGN,

DOUBLE-SIDED

HVAC SUPPLY

GRILLE

HVAC RETURN

GRILLE

HVAC SWITCHED

EXHAUST GRILLE

HVAC SUPPLY/RETURN

LINEAR DIFFUSER

ACCESS PANEL

ARCHITECTURAL REFERENCE SYMBOLS REFLECTED CEILING PLAN SYMBOLS

FLOOR PLAN SYMBOLS ARCHITECTURAL MATERIAL INDICATIONS

EARTH RIGID INSULATION

STEEL

PLYWOOD

GYPSUM WALL BOARD

ASPHALT

SAND

GROUT

DIMENSIONAL LUMBER

CONTINUOUS WOOD

FRAMING

DIMENSIONAL LUMBER

WOOD BLOCKING

CONCRETE MASONRY

UNIT

PRECAST CONCRETE

BRICK

CONCRETE

ALUMINUM

FINISH LUMBER

GRAVEL

GRANULAR DRAINAGE

MATERIAL

STONE

BATT INSULATION

ONE HOUR FIRE

RATED PARTITION

TWO HOUR FIRE

RATED PARTITION

THREE HOUR FIRE

RATED PARTITION

DOOR OPENING

OVERHEAD

ROLLING DOOR

INTERIOR GLAZED

WINDOW

WINDOW TYPE

EQUIPMENT TYPE1i

7' - 0"

DIMENSION SYMBOL

BASE CABINETS

BASE AND WALL

CABINETS

WALL CABINETS

TOILET PARTITION

AND DOOR

HANDRAIL

BUMPER GUARD

CORNER GUARD

CGC

G

OVERHEAD ITEMS

UNDER-COUNTER ITEMS

NOT-IN-CONTRACT ITEMSNIC

FEC

FIRE EXTINGUISHER

CABINET

FE

FIRE EXTINGUISHER

(MOUNT 3'-6" AFF)

URINAL

LAVATORY -

COUNTERTOP

LAVATORY -

PEDESTAL/WALL HUNG

UTILITY SINK

FLOOR FINISH

TRANSITION SYMBOL

XXX-X

XXX-X

JANITOR'S

RECEPTOR

SHOWER

FLOOR DRAIN IN

SLOPING FLOOR

FD

FLOOR JUNCTION

BOX

ROOF SAFETY TIE-

BACK

ROOF DRAIN

RD

OVER FLOW ROOF

DRAIN

ORD

DOOR OPENING MARK

SINGLE OPENING DOOR

DOUBLE ACTING DOOR

PAIR DOORS -

EQUAL SIZES

PAIR DOORS -

UNEQUAL SIZES

PAIR DOORS -

DOUBLE EGRESS

SLIDING DOOR -

BETWEEN JAMBS

DOOR WITH SIDE LIGHT

PAIR - BI FOLD DOOR

@ AT

A AIR

AB AIR BARRIER

AB ANCHOR BOLT

AC AIR CONDITIONING

ACC ACCESSIBLE

ADD ADDENDUM

ADDL ADDITIONAL

ADJ ADJACENT

ADMIN ADMINISTRATIVE

AESS ARCHITECTURAL EXPOSED

STRUCTURAL STEEL

AFF ABOVE FINISHED FLOOR

AGGR AGGREGATE

AHJ AUTHORITIES HAVING JURISDICTION

AHU AIR HANDLING UNIT

AIC AMP INTERRUPTING CAPACITY

ALT ALTERNATE

ALUM ALUMINUM

AMP AMPERE

AMPC ACOUSTICAL METAL PAN CEILING

AOR AREA OF REFUGE

AP ACCESS PANEL

APC ACOUSTICAL PANEL CEILING

APPROX APPROXIMATE

AR ARGON

ARCH ARCHITECTURAL/ARCHITECT

PCC PRECAST CONCRETE

ASPH ASPHALT

ASSY ASSEMBLY

AT AIR TERMINAL DEVICE

AUTO AUTOMATIC

AV AUDIO VISUAL

AVE AVENUE

AVG AVERAGE

AVTR ACID VENT THROUGH ROOF

AW ACID WASTE

AWC ACOUSTIC WOOD CEILING

AWP ACOUSTICAL WALL PANEL

BD BOARD

BITUM BITUMINOUS

BL BORROWED LIGHT

BLDG BUILDING

BLKG BLOCKING/BLOCK

BLKT BLANKET

BM BENCH MARK

BOD BASIS OF DESIGN

BOS BOTTOM OF STEEL

BPL BASE PLATE

BRG BEARING

BRK BRICK

BSL BIO SAFETY LEVEL

BSMT BASEMENT

BTU BRITISH THERMAL UNIT

BTUH BRITISH THERMAL UNIT PER HOUR

BTWN BETWEEN

BUR BUILT-UP ROOFING

C CHANNEL

C/C CENTER TO ROOFING

CAB CABINET

CAP CAPACITY

CB CATCH BASIN

CC CUBICAL CURTAIN

CFCI CONTRACTOR FURNISHED CONTRACTOR

INSTALLED

CFMF COLD FORM METAL FRAMING

CFOI CONTRACTOR FURNISHED OWNER

INSTALLED

CH BD CHALKBOARD

CHWS/R CHILLED WATER SUPPLY/RETURN

CI CAST IRON

CIP CAST IN PLACE CONCRETE

CIRC CIRCULATE/CIRCULATING

CJ CONTROL JOINT

CK CORK FLOORING

CL CENTERLINE

CLG CEILING

CLO CLOSET

CLR CLEAR

CM CONSTRUCTION MANAGER

CMU CONCRETE MASONRY UNIT

CO CARBON MONOXIDE

CO CLEANOUT

CO2 CARBON DIOXIDE

COL COLUMN

COMB COMBINATION/COMBINED

COMP COMPOSITE

CONC CONCRETE

COND CONDENSATE

CONF CONFERENCE

CONN CONNECTION/CONNECT

CONSTR CONSTRUCTION

CONT CONTINUOUS/CONNECT

CONTR CONTRACT(OR)

CONV CONVECTOR

CORP CORRIDOR

CP CONTROL PANEL

CPT CARPET

CR CARD READER

CS CUP SINK

CSK COUNTERSINK

CT CERAMIC TILE

CTR CENTER

CU CUBIC

CU FT CUBIC FEET

CU FT CUBIC FEET

CU YD CUBIC YARD(S)

CUH CABINET UNIT HEATER

CW COLD WATER

CW CURTAIN WALL

D DEPTH

DBL DOUBLE

DEPT DEPARTMENT

DH DOUBLE HUNG

DIA DIAMETER

DIAG DIAGONAL

DIFF DIFFERENCE

DIFF DIFFUSER

DIM DIMENSION

DIR DIRECTION

DISP DISPENSER

DISTR PNL DISTRIBUTION PANEL

DIV DIVISION

DL DEAD LOAD

DL DIVIDED LITES

DN DOWN

DO DOOR OPERATOR

DPTN DEMOUNTABLE PARTITION

DR DOOR

DS DOWNSPOUT

DTL DETAIL

ARCHITECTURAL ABBREVIATIONS

DW DISHWASHER

DWG DRAWING

DWR DRAWER

DWTR DUMBWAITER

E EAST

EA EACH

EC ELECTRICAL CONTRACTOR

ED EMERGENCY DEPARTMENT

EEW EMERGENCY EYE WASH

EF EXHAUST FAN

EFG ENTRANCE FLOOR GRILL

EFM ENTRANCE FLOOR MAT

EH EXHAUST HOOD

EIFS EXTERIOR FINISH INSULATION SYSTEM

EL ELEVATION

ELEC ELECTRIC (ELECTRICAL)

ELEV ELEVATOR

EMBED EMBEDDED

EMER EMERGENCY

EMT ELECTRICAL METALLIC TUBING

ENCL ENCLOSURE

ENTR ENTRANCE

EP ELECTRICAL PANEL

EPO EMERGENCY POWER OUTLET

EPT EPOXY PAINT

EPX EPOXY

EQ EQUAL

EQUIP EQUIPMENT

ES EMERGENCY SHOWER

ESR ELASOMETRIC SHEET ROOFING

ETR EXISTING GTO REMAIN

EWC ELECTRIC WATER COOLER

EWS EMERGENCY SHOWER AND EYE WASH

EXC EXCAVATE(D)

EXH EXHAUST

EXIST EXISTING

EXP EXPOSED

EXT EXTERIOR

F FAHRENHEIT

FA FIRE ALARM

FB FLOOR BOX

FCU FAN COIL UNIT

FD FLOOR DRAIN

FDC FIRE DEPT CONNECTION

FDTN FOUNDATION

FDV FIRE DEPT VALVE

FE FIRE EXTINGUISHER

FEC FIRE EXTINGUISHER CABINET

FF FINISHED FLOOR

FH FIRE HYDRANT

FHC FIRE HOSE CABINET

FHR FIRE HOSE RACK

FIN FINISH (ED)

FIXT FIXTURE

FLEX FLEXIBLE

FLR FLOOR

FP FIRE PROTECTION

FPM FEET PER MINUTE

FPS FEET PER SECOND

FR FIRE RETARDANT/RESISTANT

FRP FIBERGLASS REINFORCED

PANEL/POLYESTER/PLASTIC

FRT FIRE RESISTANT TREATED

FRZ FREEZER

FT FEET

FTG FOOTING

GA GAGE (GAUGE)

GAL GALLON(S)

GALV GALVANIZED

GC GENERAL CONTRACTOR

GEN GENERAL

GFCI GROUND FAULT CIRCUIT INTERRUPTER

GFRC GLASS FIBER REINFORMCENT

CONCRETE

GFRP GLASS FIBER REINFORCED PLASTER

GL GLASS

GPC GROUND POLISHED CONCRETE

GRT GROUT

GWB GYPSUM WALL BOARD

HB HOSE BIBB

HD HEAD

HD HUB DRAIN

HDWD HARDWOOD

HDWE HARDWARE

HE HELIUM

HEX HEXAGON

HM HOLLOW METAL

HO ELECTROMAGNETIC HOLD OPEN

HOLD HOLD DIMENSION

HORIZ HORIZONTAL

HP HIGH POINT

HP HORSEPOWER

HPC HIGH PERFORMANCE COATING

HR HOUR

HSKPG HOUSEKEEPING

HSS HOLLOW STRUCTURAL SHAPE

HT HEIGHT

HVAC HEATING, VENTILATING & AIR

CONDITIONING

HW HOT WATER

HWS HEAD WELDED STUD

HYD HYDROGEN

ID INSIDE DIAMETER/DIMENSION

IMP INSULATED METAL PANEL

IN INCH(ES)

INCL INCLUDE

INFO INFORMATION

INSUL INSULATION/INSULATED

INT INTEGRAL

INV INVERT

INV EL INVERT ELEVATION

JAN JANITOR

JAN CLO JANITOR CLOSET

J-BOX JUNCTION BOX

JST JOIST

JT JOINT

K KIP (1000 LB)

KO KNEE SPACE OPENING

KPL KICK PLATE

KV KILOVOLT

KW KILOWATTS

KWH KILOWATT HOUR

L ANGLE

L LENGTH/LONG

LAB LABORATORY

LAN LOCAL AREA NETWORK

LAV LAVATORY

LBS POUND(S) / LBS

LEV LEVEL

LF LINEAR FOOT

LFG LAB FURNISHINGS CONTRACTOR

LH LEFT HAND

LINO LINOLEUM

LKR LOCKER

LL LIVE LOAD

LN2 LIQUID NITROGEN

LNDG LANDING

LOC LOCATION (LOCATE)

LONG LONGITUDINAL

LPT LOW POINT

LT GA LIGHT GAGE

LTG LIGHTING

LTG PNL LIGHTING PANEL

LVR LOUVER

LW LIGHTWEIGHT

M METER

MACH MACHINE

MAN MANUAL

MATL MATERIAL

MAX MAXIMUM

MB MARKER BOARD

MC MECHANICAL CONTRACTOR

MCC MOTOR CONTROL CENTER

MDO MEDIUM DENSITY OVERLAY

MECH MECHANICAL

MECH RM MECHANICAL EQUIPMENT ROOM

MED MEDICINE/MEDICAL

MED MEDIUM

MEMB MEMBRANE

MEP MECHANICAL, ELECTRICAL, PLUMBING

MEZZ MEZZANINE

MFR MANUFACTURER

MGR MANAGER

MH MANHOLE

MIC MOBILE INSTRUMENT CART

MICRO MICROWAVE

MIN MINIMUM

MIN MINUTE

MIR MIRROR

MISC MISCELLANEOUS

MLDG MOLDING/MOULDING

mm MILLIMETER

MO MASONRY OPENING

MPH MILES PER HOUR

MTD MOUNTED

MTG MOUNTING

MTL METAL

N NORTH

N2 NITROGEN, PIPED GAS

NA NOT APPLICABLE

NG NATURAL GAS

NIC NOT IN CONTRACT

NO NUMBER

NOM NOMINAL

NTS NOT IN SCALE

NW NORMAL WEIGHT

O OXYGEN, PIPED GAS

OA OUTSIDE AIR

OA OVERALL

OC ON CENTER

OCC OCCUPANCY/OCCUPATION/OCCUPY

OD DRAIN (OVERFLOW)

OD OUTSIDE DIAMETER

OFCI OWNER FURNISHED, CONTRACTOR

INSTALLED

OFF OFFICE/OFFICER

OFOI OWNER FURNISHED,OWNER INSTALLED

OH OPPOSITE

OHSC OVER HEAD SERVICE CARRIER

OPNG OPENING

OPP OPPOSITE

OR OPERATING ROOM

OSHA OCCUPATIONAL SAFETY AND HEALTH

ASSOCIATION

OZ OUNCE

PCC PRECAST CONCRETE - STRUCTURAL

PCF POUNDS PER CUBIC FOOT

PERF PERFORATED

PH PHASE

PL PLATE

PLAM PLASTIC LAMINATE

PLAS PLASTER

PLBG PLUMBING

PLF POUNDS PER LINEAR FOOT

PLYWD PLYWOOD

PNL PANEL/PANELING

PR PAIR

PREFAB PREFABRICATED

PREFIN PREFINISHED

PREP PREPARATION

PS PROJECTION SCREEN

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PT PAINT

P-TYPE PARTITION TYPE

PVC POLYVINYL CHLORIDE

PVMT PAVEMENT / PAVING

PW POLISHED WATER

QT QUARRY TILE

QTY QUANTITY

R RADIUS

R RISER

RA RETURN AIR

RB RESILIENT BASE

RCP REFLECTED CEILING PLAN

RD ROOF DRAIN

REC RECESSED

RECPT RECEPTACLE

REF REFERENCE

REF REFRIGERATOR

REINF REINFORCED/REINFORCEMENT

REQ REQUIRED

RET RETURN

REV REVISION

RF RESINOUS FLOORING

RH RELATIVE HUMIDITY

RH RIGHT HAND

RM ROOM

RO REVERSE OSMOSIS

RO ROUGH OPENING

RPM REVOLUTION PER MINUTE

RUB RUBBER FLOORING

RV ROOF VENT

S SOUTH

SA SUPPLY AIR

SAN SANITARY

SC SEALED CONCRETE

SCF STATIC CONTROL FLOORING

SCHED SCHEDULE

SECT SECTION

SF SQUARE FOOT

SGL SINGLE

SHT SHEET

SHT MTL SHEET METAL

SHWR SHOWER

SIM SIMILAR

SOG SLAB ON GRADE

SPEC SPECIFICATION

SPKR SPEAKER

SPP SOLID PHENOLIC PANELS

SQ IN SQUARE INCHES

SQ YD SQUARE YARD

SS STAINLESS STEEL

SSM SOLID SURFACE MATERIAL

ST STONE

ST STREET

STD STANDARD

STL STEEL

STOR STORAGE

STRUC STRUCTURAL /STRUCTURE

SUSP SUSPENDED

SV SHEET VINYL

SVT SOLID VINYL TILE

SW SWITCH

T TREAD

T&B TOP AND BOTTOM

T&G TONGUE AND GROOVE

TA TOILET ACCESSORIES

TB TACKBOARD

TBB TILE BACKER BOARD

TBD TO BE DETERMINED

TD TRENCH DRAIN

TEL TELEPHONE

TEMP TEMPERATURE/TEMPERED

THK THICK/THICKNESS

TLT TOILET

TO TOP OF

TPO THERMOPLASTIC OLEFIN

TR TELECOM ROOM

TRDT TREATED

TS TUBE STEEL

TSTAT THERMOSTAT

TV TELEVISION

TYP TYPICAL

TZ TERRAZZO

UC UNDER COUNTER

UL UNDERWRITERS LABORATORY

UNO UNLESS NOTED OTHERWISE

UPH UPHOLSTERY

UPS UNINTERRUPTED POWER SUPPLY

UTIL UTILITY

UV ULTRAVIOLET

VAR VARIES

VAV VARIABLE AIR VOLUME

VCT VINYL COMPOSITION TILE

VERT VERTICAL

VEST VESTIBULE

VFD VARIABLE FREQUENCY DRIVE

VIF VERIFY IN FIELD

VOL VOLUME

VR VAPOR RETARDER

VTR VENT THRU ROOF

W WEST

W WIDTH

W/ WITH

W/O WITHOUT

WC WALL COVERING

WD WOOD

WF WIDE FLANGE STEEL BEAM

WP WALL PROTECTION

WP WORKING POINT

WT WINDOW TREATMENTS

WT WEIGHT

WTR WATER

WHEEL CHAIR

CLEARANCE

CENTERLINE

ø 5' - 0

1i CEILING TYPE

? KEYNOTE SYMBOL

101 DOOR TYPE TAG

Ref

ELEVATION NUMBER

SYMBOL

EXIT SIGN SYMBOL

ACT-?

ACT-?

NORTH ARROW

SYMBOL

X WALL TAG SYMBOL

1t

Zone Name ZONE TAG SYMBOL

BREAK LINE SYMBOL

DEMO APC CEILING - 2X2 OR 2X4

AS INDICATED ON CEILING PLAN

APC-X

3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437

COA: FL #29758

AKEA Project No. AD204-22

Design, Inc.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT / ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

A/E REPLACE AHUs 22 AND 23 673-21-152

TAMPA, FLORIDA

OF

ARCHITECT - OF - RECORD FL. REG. NO.

APPROVED FOR CONSTRUCTION

This item has been electronically signed and sealed by the individual named at right.

Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.

FINAL DESIGN

JAMES A. HALEY VA HOSPITAL

BUILDING #30

13000 BRUCE B. DOWNS BLVD.

FINAL DESIGN

APPROVED FOR CONSTRUCTION

-0 4-

2:

:0

JRF RAL

JENNIFER R. FONG AR97191

AG001

ARCHITECTURAL ABBREVIATIONS

AND SYMBOLS

2 41APRIL 14, 2023Revisions: Date:

Digitally signed by Jennifer R Fong Date: 2023.04.12 16:24:12-04'00'

A D

AE101

MECHANICAL

30-011A

MECHANICAL

30-011

AE101

EXISTING LOUVER AND

FRAMING TO REMAIN

DEMOLISH EXISTING BLOCK AND

BRICK FOR NEW TEMPORARY

OPENING.REINFORCE PER

STRUCTURAL AND PERMANANTLY

INFILL AFTER TEMPORARY

CONDITIONS ARE COMPLETED.

±4'-0" ±1'-4"

±6'-4 2' - 6"

DEMOLISH EXISTING BLOCK

AND BRICK FOR NEW OPENING.

REINFORCE PER STRUCTURAL -

SEE MECHANICAL

AE101 3

DEMOLISH EXISTING BLOCK AND

BRICK FOR NEW TEMPORARY

OPENING. REINFORCE PER

STRUCTURAL AND PERMANENTLY

INFILL AFTER TEMPORARY

CONDITIONS ARE COMPLETED.

6'

9" 4'

0"

±6'-0"

EXISTING 1

HOUR

RATED

AE101

Sim

AE101

Sim

AE101

Sim

TEMPORARY MECH DUCTS,

REFER TO MECH DRAWINGS

TEMPORARY DUCT SLEEVE,

REFER TO MECH.

TEMPORARY SELANT AND

CAULK AROUND THE OPENING

EXISTING FACE BRICK

EXISTING AIR GAP

TEMPORARY DUCT SLEEVE,

REFER TO MECHANICAL

EXISTING FACE BRICK

EXISTING AIR GAP EXISTING CONCRETE

BOND BEAM

EXISTING CMU OR

CONCRETE WALL

TEMPORARY PLYWOOD SHEATHING

INFILL, REFER TO STRUCTURAL

DRAWINGS FOR FINAL INFILL

TEMPORARY PLYWOOD OR

OTHER REMOVABLE SHEATHING

OVER AIR GAP, TYP.

NEW LINTEL PER

STRUCTURAL

EXISTING AIR GAP

EXISTING FACE BRICK

TEMPORARY METAL STUD

FRAMING

TEMPORARY METAL

SLEEVE, REFER TO

MECHANICAL

TEMPORARY PLYWOOD

SHEATHING INFILL, REFER

TO STRUCTURAL DRAWINGS

FOR FINAL INFILL

TEMPORARY MECHANICAL

DUCTS AND PIPING AS

APPLICABLE, REFER TO

MECHANICAL DRAWINGS

EXISTING CMU OR

CONCRETE WALL

SEE PLAN FOR OPENING WIDTH

TEMPORARY PLYWOOD

OTHER REMOVABLE

SHEATHING OVER AIR

GAP, TYP.

AE101

Sim

EXISTING FACE BRICK

EXISTING AIR GAP EXISTING CMU WALL

BRICK TIES AT 16" O.C.

VERTICALLY AND

HORIZONTALLY,TYP.

VAPOR BARRIER TO MATCH

EXISTING. IF FILM EXISTS,

OVERLAP FOR PROPER

MOISTURE DRAINAGE

FACE BRICK INFILL TO MATCH

EXISTING. PAINT TO MATCH

EXISTING COLOR IF EXACT

MATCH IS NOT AVAILABLE

BLOCK INFILL TO

MATCH EXISTING

EXISTING CONCRETE

BOND BEAMEXISTING FACE BRICK

EXISTING AIR GAP

EXISTING LINTEL

Ground Floor 43' - 9"

AD

Bldg. 30 Roof Lvl 58' - 3"

EXISTING LOUVER AND

FRAME TO REMAIN

TEMPORARY FRAMING

PER STRUCTURAL

TEMPORARY OPENING

FOR MECHANICAL

EXISTING WALL TO REMAIN

PE

R

M

EC

H

AN

IC

AL

±3

0"

3'

6"

3' - 10 9/16"

PERMANENT OPENING

FOR PERMANENT DUCTS

PER MECHANICAL

Level 3 48' - 7"

2' - 6"

2'

0"

EXISTING

RETAINING

WALL

EXISTING

SLOPED

CURB AND

DRIVEWAY,

GRADE

VARIES,

FIELD VERIFY

PE

R

M

EC

H

AN

IC

AL

±6

FIELD VERIFY

FIELD VERIFY

Ground Floor 43' - 9"

Bldg. 30 Roof Lvl 58' - 3"

Level 3 48' - 7"

TEMPORARY OPENING FOR

TEMPORARY PIPING AND

DUCT PER MECHANICAL

TEMPORARY

FRAMING PER

STRUCTURAL

EXISTING WALL

TO REMAIN

EXISTING

RETAINING WALL EXISTING SLOPED

CURB AND

DRIVEWAY, GRADE

VARIES, FIELD VERIFY

4' - 0"

1'

6"

FIELD VERIFY

EXISTING FACE BRICK

R-19 MIN.

THERMAL INSULATION

BRICK TIES AT 16" O.C.

VERTICALLY AND

HORIZONTALLY, TYP.

DENSGLASS OR EQUAL

FACE BRICK INFILL TO MATCH

EXISTING, PAINT TO MATCH

EXISTING COLOR IF EXACT

MATCH IS NOT AVAILABLE

METAL STUD INFILL - BUILD UP TO

FULL DEPTH OF WALL WITH

SHEATHING

EXISTING LINTEL

SEAL EDGE, SKIM COAT AND

SAND SMOOTH FLUSH WITH

EXISTING. PAINT TO MATCH

ADJACENT.

CEMENTOUS BOARD

SHEATHING

SEAL PERIMETER EDGE

EXISTING CONCRETE

BOND BEAM

EXISTING CONCRETE WALL

EXISTING AIR GAP

EXISTING FACE BRICK

EXISTING AIR GAP

RUNNER CHANNEL

3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437

COA: FL #29758

AKEA Project No. AD204-22

Design, Inc.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT / ENGINEER OF RECORDCONSULTANT

321 4 5 6 7 8 9 10

A/E REPLACE AHUs 22 AND 23 673-21-152

TAMPA, FLORIDA

OF

ARCHITECT - OF - RECORD FL. REG. NO.

APPROVED FOR CONSTRUCTION

This item has been electronically signed and sealed by the individual named at right.

Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.

FINAL DESIGN

JAMES A. HALEY VA HOSPITAL

BUILDING #30

13000 BRUCE B. DOWNS BLVD.

FINAL DESIGN

APPROVED FOR CONSTRUCTION

-0 4-

1:

:1

JRF RAL

JENNIFER R. FONG AR97191

AE101

PLAN, ELEVATIONS AND

WALL OPENING DETAILS

3 41APRIL 14, 2023

3/8" = 1'-0"1 GROUND LEVEL FLOOR PLAN

1 1/2" = 1'-0"5 TEMPORARY WALL OPENING SECTION

1 1/2" = 1'-0"4 TEMPORARY WALL OPENING - PLAN VIEW

1 1/2" = 1'-0"6 FINAL INFILL WALL OPENING - AT EXISTING CAVITY WALL

3/8" = 1'-0"2 NORTH ELEVATION

3/8" = 1'-0"3 WEST ELEVATION

1 1/2" = 1'-0"7 FINAL INFILL WALL OPENING - AT EXISTING RETAINING WALL

Revisions: Date:

Date: 2023.04.13 18:45:22-04'00'

System No. C-AJ-1044 June 15, 2005

F Ratings - 2,3, and 4 Hr T Rating - 0 Hr

L Rating At Ambient - 2 CFM/sq ft L Rating At 400 F - less than 1 CFM/sq ft

W Rating - Class I

SE

CT

IO

N

SECTION A-A

A

A

2 4 1

REFER TO UL DIRECTORY, FIRE RESISTANCE (VOLUME 2) AND MANUFACTURER'S LITERATURE FOR

COMPLETE DETAILING.

1. Floor or Wall Assembly - Lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Except as noted in complete system detail, min thickness of solid concrete floor or wall assembly is 4-1/2 in. (114 mm). Floor may also be constructed of any min 6 in. (152 mm) thick UL Classified hollow core Precast Concrete Units*. When floor is constructed of hollow core precast concrete units, packing material (Item 3) and caulk fill material (Item 4) to be installed symmetrically on both sides of floor, flush with floor surface. Wall assembly may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is in solid lightweight or normal weight concrete. Floor is 32 in. (813 mm). Max diam of opening in floor constructed of hollow-core precast concrete units is 7 in. (178 mm).

1A. Steel Sleeve (Not shown) - Max 15 in. (381 mm) ID (or smaller) Schedule 10 (or heavier) steel sleeve cast or grouted into floor or wall assembly. Sleeve may extend a max of 2 in. (51 mm) above top of floor or beyond either surface of wall. Max 16 in. (406 mm) ID (or smaller) min 0.028 (0.71 mm) wall thickness (or heavier) galvanized steel sleeve cast or grouted into floor or wall assembly. Sleeve may extend a max of 1/2 in. (13 mm) beyond either surface of floor or wall.

2. Through Penetrants - One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the firestop system. Max annular space between pipe, conduit or tubing and edge of through opening or sleeve is dependent on the parameters shown in Item 4. Min annular space between pipe or conduit and edge of through opening is 0 in. (0 mm) (point contact). Pipe conduit or tubing to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used:

A. Steel Pipe - Nom 30 in. (762 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.

B. Iron Pipe - Nom 30 in. (762 mm) diam (or smaller) cast or ductile iron pipe.

C. Conduit - Nom 6 in. (152 mm) diam (or smaller) rigid steel conduit.

D. Conduit - Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing.

E. Copper - Tubing Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tube.

F. Copper Pipe - Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe.

3. Packing Material - Polyethylene backer rod or nom 1 in. (25 mm) thickness of tightly-packed mineral wool batt or glass fiber insulation firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of caulk fill material (Item 4).

4. Fill,Void or Cavity Material* - Caulk or Sealant - Applied to fill the annular space flush with top surface of floor. In wall assemblies, required caulk thickness to be installed symmetrically on both sides of wall, flush with wall surface.

At point contact location between penetrant and sleeve or between penetrant and concrete, a min 1/4 in. (6 mm) diam bead of caulk shall be applied at top surface of floor and at both surfaces of wall. The hourly F Ratings and the min required caulk thicknesses are dependent upon a number of parameters, as shown in the complete system detail.

3M COMPANY - CP 25WB+ caulk or FB-3000 WT sealant.

SINGLE METALLIC PIPE

CONCRETE

System No. C-AJ-5024 May 19, 2005

F Ratings - 2 and 3 Hr T Ratings - 1 and 1-1/2 Hr

L Rating At Ambient - 2 CFM/sq ft L Rating At 400 F - less than 1 CFM/sq ft

SE

CT

IO

N

SECTION A-A

A

A

REFER TO UL DIRECTORY, FIRE RESISTANCE (VOLUME 2) AND MANUFACTURER'S LITERATURE FOR

COMPLETE DETAILING.

1. Floor or Wall Assembly - Min 4-1/2 in. (114 mm) thick lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of circular through opening is 21 in. (533 mm).

1A. Steel Sleeve (Not shown) - Nom 21 in. (533 mm) (or smaller) Schedule 10 (or heavier) steel sleeve cast or grouted into floor or wall assembly. Sleeve may extend a max of 2 in. (51 mm) above top of floor or beyond either surface of wall. Sleeve may be used only when floor or wall assembly is min 4-1/2 in. (114 mm) thick.

2. Through Penetrants - One metallic pipe or tubing to be installed either concentrically or eccentrically within the firestop. Pipe or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes or tubing may be used:

A. Steel Pipe - Nom 10 in. (254 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.

B. Copper Tubing - Nom 4 in. (102 mm) diam (or smaller) Type L (or heavier) copper tubing.

C. Copper Pipe - Nom 4 in. (102 mm) diam (or smaller) Regular (or heavier) copper pipe.

3. Pipe Covering* - Nom 1, 2 or 3 in. (25, 51 or 76 mm) thick hollow cylindrical heavy density (min 3.5 pcf or 56 kg/m3) glass fiber units jacketed on the outside with an all service jacket. Longitudinal joints sealed with metal fasteners or factory-applied selfsealing lap tape. Transverse joints secured with metal fasteners or with butt strip tape supplied with the product.

4A. Fill,Void or Cavity Materials* - Wrap Strip - Nom 1/4 in. (6 mm) thick intumescent elastomeric material faced on one side with aluminum foil, supplied in nom 2 in. (51 mm) wide strips. Nom 2 in. (51 mm) wide strip tightly-wrapped around pipe covering material (foil side exposed), secured with a steel wire tie and slid into annular space. In floors, the wrap strip layer is to be installed with its top edge recessed 1/8 to 1/2 in. (3.2 mm to 13 mm) from the top surface of the floor. In walls, the wrap strip layer is to be installed in the same manner used for floors but it shall be installed symmetrically on both sides of the wall assembly. The min number of wrap strip layers required is dependent upon the pipe covering material thickness, as shown in the complete system detail.

3M COMPANY - FS-195+.

4B. Packing Material - When an annular space is present between the wrap strip and the periphery, mineral wool batt insulation shall be tightly-packed into the annular space. In floors, the top surface of the packing material is to be recessed min 1 in. (25 mm) from the top surface of the floor. In walls, the packing material is to be installed in the same manner used for floors but it shall be installed symmetrically on both sides of the wall assembly.

4C. Fill,Void or Cavity Materials* - Caulk or Sealant - Installed to fill annular space to a min depth of 1 in. (25 mm), flush with top surface of floor or both surfaces of wall, such that exposed edge of wrap strip layer is covered with a 1/8 to 1/2 in. (3.2 mm to 13 mm) thickness.

3M COMPANY - CP 25WB+, IC 15WB+ caulk or FB-3000 WT sealant.

4C 2

4A

4B 4A

4C

SINGLE INSULATED METALLIC PIPE

CONCRETE

System No. C-AJ-2228 November 20, 2009

F Ratings - 2 and 3 Hr T Ratings - 0, 2 and 3 Hr

W Rating - Class I

SE

CT

IO

N

SECTION A-A

A

A

REFER TO UL DIRECTORY, FIRE RESISTANCE (VOLUME 2) AND MANUFACTURER'S LITERATURE

FOR COMPLETE DETAILING.

1. Floor or Wall Assembly — Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600 - 2400 kg/m3) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*.

Diam of opening shall be 1 in. (25 mm) larger than nom pipe diam.

2. Steel Sleeve — Nom 4 in. (102 mm) diam (or smaller) Schedule 10 (or heavier) steel sleeve cast or grouted into floor or wall assembly.

T Rating is 0 Hr when sleeve is used.

3. Through Penetrants — One nonmetallic pipe or conduit to be installed within opening. The annular space between pipe or conduit and periphery of opening or sleeve and the T Ratings for the pipes when no sleeve is used are dependent on the type of pipe and nom pipe sizes as shown in the complete system detail. Pipe or conduit to be rigidly supported on both sides of the floor or wall assembly. The following types and sizes of nonmetallic pipes may be used:

A. Polyvinyl Chloride (PVC) Pipe — Nom 3 in. (76 mm) diam (or smaller) Schedule 40 solid core or cellular core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems.

B. Rigid Nonmetallic Conduit++ — Nom 3 in. (76 mm) diam (or smaller) Schedule 40 PVC conduit installed in accordance with Article 347 of the National Electrical Code (NFPA No. 70).

C. Chlorinated Polyvinyl Chloride (CPVC) Pipe — Nom 3 in. (76 mm) diam (or smaller) SDR13.5 CPVC pipe for use in closed (process or supply) piping systems.

D. Acrylonitrile Butadiene Styrene (ABS) Pipe — Nom 3 in. (76 mm) diam (or smaller) Schedule 40 solid core or cellular ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems.

E. Fire Retardant Polypropylene (FRPP) Pipe — Nom 3 in. (76 mm) diam (or smaller) Schedule 40 FRPP pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems.

4. Firestop System — The firestop system shall consist of the following:

A. Fill, Void or Cavity Materials* — Wrap Strip — Nom 1/8 in. (3.2 mm) thick intumescent material supplied in 2 in. (51 mm) wide strips. Wrap strip tightly wrapped around nonmetallic pipe with continuous layers and secured with two 1/4 in. (6 mm) wide bands of filament tape placed 1/2 in. (13 mm) from bottom and top of wrap strip. The layers of wrap strip and its position within the opening are dependent on the pipe size. For nom 2 in. (51 mm) diam (or smaller) pipes, one layer is required, recessed within the opening 2-1/4 in. (57 mm) from the bottom surface of the floor or both surfaces of the wall. For nom 2-1/2 and 3 in. (64 and 76 mm) diam pipes, two layers are required, recessed within the opening 1-1/2 in. (38 mm) from the bottom surface of the floor or both surfaces of the wall.

3M COMPANY — Ultra GS B. Fill, Void or Cavity Materials* — Caulk or Sealant (Optional, Not Shown) — Min 1/4 in. (6 mm) thickness of caulk or sealant applied within annular space, flush with top of floor .

3M COMPANY — CP 25WB+ caulk, FB-3000 WT Sealant, FB-1000 NS sealant, IC 15WB+ caulk or FireDam 150+ caulk. (CP 25WB+ and FireDam 150+ not suitable for use with CPVC pipes.)

(Note - W Rating applies only when FB-3000 WT or FB- 1000 NS is used.)

4B

4B

4A

SINGLE NON-METALLIC PIPE

CONCRETE

System No. W-L-1001 June 15, 2005

F Ratings - 1,2,3, and 4 Hr T Ratings - 0, 1, 2, 3, and 4 Hr

L Rating At Ambient - less than 1 CFM/sq ft L Rating At 400 F - less than 1 CFM/sq ft

SE

CT

IO

N

SECTION A-A

A

A

REFER TO UL DIRECTORY, FIRE RESISTANCE (VOLUME 2) AND MANUFACTURER'S LITERATURE FOR

COMPLETE DETAILING.

1. Wall Assembly - The 1, 2, 3 or 4 hr fire-rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner described in the individual U300 or U400 Series Wall or Partition Designs in the UL Fire Resistance Directory and shall include the following construction features:

A. Studs - Wall framing may consist of either wood studs (max 2 hr fire rated assemblies) or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC with nom 2 by 4 in. (51 by 102 mm) lumber end plates and cross braces. Steel studs to be min 3-5/8 in. (92 mm) wide by 1-3/8 in. (35 mm) deep channels spaced max 24 in. (610 mm) OC.

B. Gypsum Board* - Nom 1/2 or 5/8 in. (13 or 16 mm) thick, 4 ft. (122 cm) wide with square or tapered edges. The gypsum wallboard type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the UL Fire Resistance Directory. Max diam of opening is 26 in. (660 mm).

2. Through Penetrant - One metallic pipe, conduit or tubing installed either concentrically or eccentrically within the firestop system. The annular space between pipe, conduit or tubing and periphery of opening shall be min of 0 in. (0 mm) (point contact) to max 2 in. (51 mm). Pipe, conduit or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used:

A. Steel Pipe - Nom 24 in. (610 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.

B. Iron Pipe - Nom 24 in. (610 mm) diam (or smaller) service weight (or heavier) cast iron soil pipe, nom 12 in. (305 mm) diam (or smaller) or Class 50 (or heavier) ductile iron pressure pipe.

C. Conduit - Nom 6 in. (152 mm) diam (or smaller) steel conduit or nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing D. Copper Tubing - Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing E. Copper Pipe - Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe.

F. Through Penetrating Product* - Flexible Metal Piping - The following types of steel flexible metal gas piping may be used:

1. Nom 2 in. (51 mm) diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removed on both sides of floor or wall assembly. OMEGA FLEX INC

2. Nom 1 in. (25 mm) diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removed on both sides of floor or wall assembly. TITEFLEX CORP, A BUNDY CO

3. Nom 1 in. (25 mm) diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removed on both sides of floor or wall assembly. WARD MFG INC

3. Fill,Void or Cavity Material* - Caulk or Sealant - Min 5/8. 1-1/4,1-7/8 and 2-1/2 in. (16, 32, 48 and 64 mm) thickness of caulk for 1, 2, 3 and 4 hr rated assemblies, respectively, applied within annulus, flush with both surfaces of wall. Min 1/4 in.

(6 mm) diam bead of caulk applied to gypsum board/penetrant interface at point contact location on both sides of wall.

The hourly F and T Rating of the firestop system is dependent upon the type or size of the pipe or conduit and the hourly fire rating of the wall assembly in which it is installed, as shown in the complete system detail.

+When copper pipe is used, T Rating is 0 hr.

3M COMPANY - CP 25WB+ caulk or FB-3000 WT sealant, 1A

1B

SINGLE METALLIC PIPE

GYPSUM

System No. W-L-5001 May 19, 2005

F Ratings - 1 and 2 Hr T Ratings - 3/4, 1 and 1-1/2 Hr

L Rating At Ambient - 2 CFM/sq ft L Rating At 400 F - less than 1 CFM/sq ft

SE

CT

IO

N

SECTION A-A

A

A

REFER TO UL DIRECTORY, FIRE RESISTANCE (VOLUME 2) AND MANUFACTURER'S LITERATURE

FOR COMPLETE DETAILING.

1. Wall Assembly - The 1 or 2 hr fire-rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner described in the individual U300, U400 or V400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features:

A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 in. by 4 in. (25 mm by 102 mm) lumber spaced 16 in. (406 mm) OC with nom 2 by 4 in. lumber end plates and cross braces. Steel studs to be min 3-5/8 in. (92 mm) wide by 1-3/8 in. (35 mm) deep channels spaced max 24 in. (610 mm) OC.

B. Gypsum Board* - Nom 5/8 in. (16 mm) thick, 4 ft (122 cm) wide with square or tapered edges. The gypsum wallboard type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the UL Fire Resistance Directory. Max diam of opening is 14-1/2 in (368 mm) for wood stud walls and 18 in. (457 mm) for steel stud walls.

The hourly F Rating of the firestop system is 1 hr when installed in a 1 hr fire rated wall and 2 hr when installed in a 2 hr fire rated wall.

2. Through Penetrants - One metallic pipe or tubing to be centered within the firestop system. Pipe or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes or tubing may be used:

A. Steel Pipe - Nom 12 in. (305 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.

B. Copper Tubing - Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing.

C. Copper Pipe - Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe.

3. Pipe Covering* - Nom 1 in. or 2 in. (25 mm or 51 mm) thick hollow cylindrical heavy density glass fiber units jacketed on the outside with an all service jacket. Longitudinal joints sealed with metal fasteners or factory-applied self-sealing lap tape. Transverse joints sealed with metal fasteners or with butt strip tape supplied with the product. When nom 1 in. (25 mm) thick pipe covering is used, the annular space between the pipe covering and the circular cutout in the gypsum wallboard layers on each side of the wall shall be min 1/4 in. to max 3/8 in. (6 mm to max 10 mm). When nom 2 in. (51 mm) thick pipe covering is used, the annular space between the pipe covering and the circular cutout in the gypsum wallboard layers on each side of the wall shall be min 1/2 in. to max 3/4 in. (13 mm to max 19 mm).

4. Firestop System - Installed symmetrically on both sides of wall assembly. The details of the firestop system shall be as follows:

A. Fill,Void or Cavity Materials* - Wrap Strip - Nom 1/4 in. (6 mm) thick intumescent elastomeric material faced on one side with aluminum foil, supplied in 2 in. (51 mm) wide strips. Nom 2 in. (51 mm) wide strip tightly wrapped around pipe covering (foil side out) with seam butted. Wrap strip layer securely bound with steel wire or aluminum foil tape and slid into annular space approx 1-1/4 in. (32 mm) such that approx 3/4 in.

(19 mm) of the wrap strip width protrudes from the wall surface. One layer of wrap strip is required when nom 1 in. (25 mm) thick pipe covering is used. Two layers of wrap strip are required when nom 2 in. (51

mm) thick pipe covering is used.

3M COMPANY - FS-195+

B. Fill,Void or Cavity Materials* - Caulk or Sealant - Min 1/4 in. (6 mm) diam continuous bead applied to the wrap strip/wall interface and to the exposed edge of the wrap strip layer approx 3/4 in. (19 mm) from the wall surface. 3M COMPANY - CP 25WB+, IC 15WB+, FireDam 150+ caulk or FB-3000 WT sealant

4B

4A

2 3

4A

1A 1B

4B

SINGLE INSULATED METALLIC PIPE

GYPSUM

System No. W-L-2003 November 20, 2009

F Ratings - 1 and 2 Hr T Ratings - 1 and 2 Hr

L Rating At Ambient - 7 CFM/sq ft L Rating At 400 F - less than 1 CFM/sq ft

SE

CT

IO

N

SECTION A-A

A

A

REFER TO UL DIRECTORY, FIRE RESISTANCE (VOLUME 2) AND MANUFACTURER'S LITERATURE FOR COMPLETE

DETAILING.

1. Wall Assembly — The 1 or 2 hr fire-rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner described in the individual U300, U400 or V400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features:

A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in.

(51 by 102 mm) lumber spaced 16 in. (406 mm) OC with nom 2 by 4 in. (51 by 102 mm) lumber end plates and cross braces. Steel studs to be min 3-5/8 in. (92 mm) wide by 1-3/8 in. (35 mm) deep channels spaced max 24 in. (610 mm) OC.

B. Gypsum Board* — 5/8 in. (16 mm) thick, 4 ft (122 cm) wide with square or tapered edges. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300, U400 or V400 Series Design in the UL Fire Resistance Directory. Max diam of opening is 3-1/8 in. (79 mm).

2. Through Penetrants — One nonmetallic pipe or conduit to be centered in the through opening. The annular space between pipe or conduit and periphery of opening shall be min 1/4 in. (6 mm) and max 3/8 in. (10 mm). Pipe or conduit to be rigidly supported on both sides of the floor-ceiling assembly. The following types and sizes of nonmetallic pipes or conduits may be used:

A. Polyvinyl Chloride (PVC) Pipe — Nom 2 in. (51 mm) diam (or smaller) Schedule 40 solid core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping system.

B. Rigid Nonmetallic Conduit++ — Nom 2 in. (51 mm) diam (or smaller)(Schedule 40 or 80) PVC conduit installed in accordance with the National electric Code (NFPA No. 70).

C. Chlorinated Polyvinyl Chloride (CPVC) Pipe — Nom 2 in. (51 mm) diam (or smaller) SDR13.5 CPVC pipe for use in closed (process or supply) piping systems.

D. Cellular Core Polyvinyl Chloride (ccPVC) Pipe — Nom 2 in. (51 mm) diam (or smaller) Schedule 40 cellular core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping system.

E. Acrylonitrile Butadiene Styrene (ABS) Pipe — Nom 2 in. (51 mm) diam (or smaller) Schedule 40 solid core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems.

F. Cellular Core Acrylonitrile Butadiene Styrene (ccABS) Pipe — Nom 2 in. (51 mm) diam (or smaller) Schedule 40 cellular core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems.

3. Firestop System — Installed symmetrically on both sides of wall assembly. The hourly F and T Ratings for the firestop system are equal to the hourly fire rating of the wall assembly in which it is installed. The details of the firestop system shall be as follows.

A. Fill, Void or Cavity Materials* — Wrap Strip — Nom 1/4 in. (6 mm) thick intumescent elastomeric material faced on one side with aluminum foil, supplied in 2 in. (51 mm) wide strips. Nom 2 in. (51 mm) wide strip tightly wrapped around nonmetallic pipe (foil side out) with seam butted. Wrap strip layer securely bound with steel wire or aluminum foil tape and slid into annular space approx 1-1/4 in. (32 mm) such that approx 3/4 in. (19 mm) of the wrap strip protrudes from the wall surface. 3M COMPANY — FS-195+ B. Fill, Void or Cavity Materials* — Caulk, Sealant or Putty — Min 5/8 in. (16 mm) thickness of caulk or putty applied into annular space between wrap strip and periphery of opening. A nom 1/4 in. (6 mm) diam bead of caulk or putty to be applied to the wrap strip/wall interface and to the exposed edge of the wrap strip layers approx 3/4 in. (19 mm) from the wall surface.

3M COMPANY — CP 25WB+ caulk or MP+ Stix putty, IC 15WB+ caulk, FireDam 150+ caulk or FB-3000 WT sealant. (Note:

L Ratings apply only when Type CP 25WB+ caulk or FB-3000 WT sealant is used. CP 25WB+ and FireDam 150+ not suitable for use with CPVC pipes.)

C. Foil Tape — (not shown) — Nom 4 in. (102 mm) wide, 3 mil thick aluminum tape wrapped around pipe prior to the installation of the wrap strip (Item 3A). Min of one wrap, flush with both sides of wall and proceeding outward. Tape is not required for pipes shown in Items 2A, 2B and 2C.

3B

3A

1A

3A

1B

3B

SINGLE NON-METALLIC PIPE

GYPSUM

System No. C-AJ-1429 May 18, 2005

F Rating - 2 Hr T Rating - 0 Hr

W Rating - Class I

SE

CT

IO

N

SECTION A-A

A A

REFER TO UL DIRECTORY, FIRE RESISTANCE (VOLUME 2) AND MANUFACTURER'S LITERATURE FOR

COMPLETE DETAILING.

1. Floor or Wall Assembly - Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Floor assembly may also be constructed of any min 6 in. (152 mm) thick UL Classified hollow-core Precast Concrete Units*. Wall may also be constructed of any UL Classified Concrete Blocks*. Max area of opening 240 sq in. (1548 sq cm) with a max dimension of 30 in. (762 mm).Max area of opening in floors constructed of hollow-core concrete is 49 sq in. (316 sq cm) with a max dimension of 7 in.

(178 mm).

See Concrete Blocks (CAZT) and Precast Concrete Units (CFTV) categories in Fire Resistance Directory for names of manufacturers.

2. Through Penetrant - One or more metallic pipes, conduits, tubes or flexible metal pipes installed concentrically or eccentrically within opening. Annular space between penetrants and periphery of opening shall be min of 0 in. (point contact) to max 2 in. (0 mm to max 51 mm) Space between penetrants shall be min of 1/4

in. to max 2 in. (6 mm to max 51 mm). Penetrants to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of penetrants may be used:

A. Steel Pipe - Nom 6 in. (152 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.

B. Iron Pipe - Nom 6 in. (152 mm) diam (or smaller) cast or ductile iron pipe.

C. Conduit - Nom 6 in. (152 mm) diam (or smaller) steel conduit or nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing.

D. Copper Tubing - Nom 3 in. (76 mm) diam (or smaller) Type L (or heavier) copper tubing.

E. Copper Pipe - Nom 3 in. (76 mm) diam (or smaller) Regular (or heavier) copper pipe.

F. Through Penetrating Product* - Flexible Metal Piping - The following types of steel flexible metal gas piping may be used:

1. Nom 2 in. (51 mm) diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removed on both sides of floor or wall assembly. OMEGA FLEX INC.

2. Nom 1 in. (25 mm) diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removed on both sides of floor or wall assembly. TITEFLEX CORP, A BUNDY CO.

3. Nom 1 in. (25 mm) diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removed on both sides of floor or wall assembly. WARD MFG INC.

3. Firestop System - The details of the firestop system shall be as follows:

A. Packing Material - Min 3 in. (76 mm) thickness of min 4 pcf (64 kg/m3) mineral wool batt insulation firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of fill material. In floors constructed of hollow-core concrete, packing material to be recessed from top and bottom surfaces of floor as required to accommodate the required thickness of fill material.

B. Fill,Void or Cavity Materials* - Caulk or Sealant - Min 1/2 in. (13 mm) thickness of caulk applied within the annulus, flush with top surface of floor or with both surfaces of wall. In floors constructed of hollow-core concrete, min 1/2 in. (13 mm) thickness of caulk applied within the annulus, flush with top and bottom surfaces of floor. Min 1/4 in. (6 mm) diam bead of caulk applied to the penetrant/concrete interface at the point contact location on the top surface of floor or both surfaces of wall or hollow-core concrete.

3M COMPANY - IC 15WB+, CP 25WB+ caulk or FB-3000 WT sealant.

(Note: W Rating applies only when FB-3000 WT is used.)

MULTIPLE METALLIC PIPE

CONCRETE - 2 HOUR

3B

3B

3A

System No. W-L-3306 F Ratings - 1 and 2 Hr

T Ratings - 0, 1/2, 3/4, 1, 1-1/2 and 2 Hr L Rating At Ambient - less than 1, 2.3, 6.2, 6.7 or 7.4 CFM/Device Module

L Rating At 400 F - less than 1, 2.3, 4.5, 5 or 6.7 CFM/Device Module

SE

CT

IO

N

SECTION A-A

A

A

REFER TO UL DIRECTORY, FIRE RESISTANCE (VOLUME 2) AND MANUFACTURER'S LITERATURE FOR

COMPLETE DETAILING.

1. Wall Assembly - The 1 or 2 hr fire rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner described within the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall incorporate the following construction features:

A. Studs - Wall framing shall consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced max 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC.

B. Gypsum Board* - Thickness, type, number of layers and fasteners as specified in the individual Wall and Partition Design. Opening in gypsum board to be max 1/4 in. (6 mm) larger then width and height dimensions of firestop device(s).

2. Firestop Device* - One, two, three, four or five firestop device modules ganged together and secured by means of integral hook and eye window attachment. Each firestop device module consists of a 4 by 4-5/8 by 14

in. (102 by 118 by 356 mm) long galv steel tube with an intumescent material lining. Series 44 device modules have spring loaded steel retainer plates. Firestop device modules to be installed in accordance with the accompanying installation instructions. The space between the firestop device module(s) and the periphery of the opening shall be min 0 in. ( 0 mm, point contact) to max 1/8 in. (3.2 mm).

SPECIFIED TECHNOLOGIES INC - EZ PATH Series 44 or Series 44+ Fire Rated Pathway

3. Cables - Within the loading area for each firestop device module, the loose or grouped cables may represent a 0 to 100 percent visual fill. Cables to be rigidly supported on both sides of the wall assembly. Any combination of the following types of cables may be used:

A. Max 400 pair No. 24 AWG (or smaller) copper conductor telecommunication cable with polyvinyl chloride (PVC) or plenum-rated jacketing and insulation.

B. Max 750 kcmil single copper conductor power cable with XLPE jacket and insulation.

C. Max 7/C No. 12 AWG copper conductor control cable with PVC or XLPE jacket and insulation.

D. Max 3/C No. 2/0 AWG metal clad or armored cable with steel or aluminum jacket.

E. Max 3/C No. 8 AWG NM cable (Romex) with PVC insulation and jacket.

F. Max four pair No. 22 AWG (or smaller) copper conductor data cable with PVC or plenum rated jacketing and insulation.

G. Coaxial cable with fluorinated ethylene or PVC insulation and jacketing having a max diam of 5/8 in. (16 mm).

H. Optical fiber cable with PVC or polyethylene (PE) jacket and insulation and having a max diam of 5/8 in.

(16 mm).

I. Optical Fiber Raceway+ - Max 1-1/2 in. (38 mm) diam (or smaller) optical fiber raceway ("innerduct") formed of either PVC or polyvinylidene fluoride (PVDF) with optical fiber cable fill. Raceways installed in accordance with the National Electrical Code (NFPA 70).

4. Fill, Void or Cavity Material* - Sealant or Putty - (Not Shown) - As an alternate to gypsum joint compound, the gap between the firestop device module and the cutout in the gypsum board may be sealed with fill material on each side of the wall assembly when four- and seven-gang steel wall plates are installed directly against the wood or steel studs.

SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant, SpecSeal LCI Sealant, SpecSeal Putty

EZ-PATH

GYPSUM

3 2

1A 1B

System No. W-L-8010 May 19, 2005

F Ratings - 1 & 2 Hr T Ratings - 1/4, 3/4, 1, 1-1/2 and 1-3/4 Hr

SE

CT

IO

N

SECTION A-A

A

A

REFER TO UL DIRECTORY, FIRE RESISTANCE (VOLUME 2) AND MANUFACTURER'S LITERATURE

FOR COMPLETE DETAILING.

1. Wall Assembly - The 1 or 2 hr fire-rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features:

A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 in. by 4 in. (51 mm to max 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-5/8

in. (92 mm) wide and spaced max 24 in. (610 mm) OC.

B. Gypsum Board* - Nom 5/8 in. (16 mm) thick gypsum wallboard, as specified in the individual Wall and Partition Design. Max area of opening is 65-1/4 sq in. (421 cm2) with max dimension of 14-1/2 in. (368 mm).

The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly.

2. Through Penetrants - A max of four pipes, conduits or tubing to be installed within the opening. The space between pipes, conduits or tubing shall be min 1/2 in to max 1-5/16 in. (13 mm to max 33 mm). The space between pipes, conduits or tubing and periphery of opening shall be min 1-3/16 in. (30 mm) for uninsulated copper tubes and copper pipes (Items 2C and 2D) and 0 in. (point contact) for insulated copper tubes and copper pipes and uninsulated steel pipes and conduit (Item 2B). The space between pipes, conduits or tubing and periphery of opening shall be max 1-5/16 in. (33 mm). Pipe, conduit or tubing to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used:

A. Steel Pipe - Nom 2 in. (51 mm) diam (or smaller) Schedule 5 (or heavier) steel pipe.

B. Conduit - Nom 2 in. (51 mm) diam (or smaller) steel electrical metallic tubing or steel conduit.

C. Copper Tubing - Nom 2 in. (51 mm) diam (or smaller) Type L (or heavier) copper tubing.

D. Copper Pipe - Nom 2 in. (51 mm) diam (or smaller) Regular (or heavier) copper pipe.

When uninsulated steel pipe or conduit is used,T Rating is 3/4 hr and 1-1/2 hr for 1 and 2 hr rated assemblies, respectively. When uninsulated copper tubing or pipe is used,T Rating is 1/4 hr for both 1 and 2 hr rated assemblies.

3A. Pipe Covering* (Optional) - Nom 1 in. (25 mm) hollow cylindrical heavy density glass fiber units jacketed on the outside with an all service jacket. Longitudinal joints sealed with metal fasteners or factory-applied self-sealing lap tape. Transverse joints secured with metal fasteners or with butt tape supplied with the product. When pipe covering is used on all through penetrants,T Rating is 1 hr and 1-3/4 hr for 1 and 2 hr rated assemblies, respectively.

3B. Tube Insulation - Plastics# (Optional) - Nom 3/4 in.