This file contains drawings and bid documents for a federal contract solicitation to replace air handling units at a Veterans Affairs medical facility. The solicitation number is 36C24824R0010 to replace AHUs 22 and 23 under project 673-21-152 at the Veterans Integrated Service Network 8 facility. Responses are due by small businesses for this project, which involves replacing two air handling units to improve heating, ventilation and air conditioning systems. The contract award is expected before the end of the current fiscal year.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
T43
T33
T34
T34a
T49
T78 T77
37?
G001
Department of Veterans Affairs
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437
COA: FL #29758
AKEA Project No. AD204-22
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
A
U.S. Department of Veterans Affairs
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
321 4 5 6 7 8 10
A/E REPLACE AHUs 22 AND 23
TAMPA, FLORIDA
673-21-152
APRIL 14, 2023Revisions: Date:
Office of Construction and Facilities Management
ARCHITECT / ENGINEER OF RECORDCONSULTANT
A
B
C
D
E
F
JAMES A. HALEY VA HOSPITAL
BUILDING #30
13000 BRUCE B. DOWNS BLVD.
FINAL DESIGN
APPROVED FOR CONSTRUCTION
TITLE PAGE, LOCATION MAP,
AND INDEX OF DRAWINGS
William Rodriguez-Arroyo
2023.04.12 12:08:17 -04'00'
A-101 DETAIL NUMBER
SHEET WHERE DRAWN
DETAIL REFERENCE
SIM
A
NEW GRID
IDENTIFICATION
LAYOUT GRID LINES
A102
ELEVATION NUMBER AND
DIRECTION OF VIEW
SHEET WHERE DRAWN
INTERIOR ELEVATION REFERENCE
101 ROOM NUMBER
ROOM NAME
ROOM TAG
ROOM NUMBER
ROOM FINISH
BASE FINISH
WALL FINISH
ROOM NAME
FINISH PLAN ROOM TAG
SECTION NUMBER
SHEET WHERE DRAWN
DIRECTION OF VIEW
A-101
SIM
SECTION
A-101
SIM
ELEVATION NUMBER
AND DIRECTION
SHEET WHERE DRAWN
SECTION DETAIL REFERENCE
B3B PARTITION SYMBOL
SEE SHEET A-620
PARTITION TYPE IDENTIFICATION MARK
A
EXISTING GRID
IDENTIFICATION
ELEVATION NUMBER
DIRECTION OF VIEW1
A-101
SIM
EXTERIOR ELEVATION
SHEET WHERE DRAWN
SCALE: 1/8" = 1'-0"
BASIC DRAWING
TITLE
DRAWING TITLE SYMBOLS
VIEW NAME
INDICATES HEIGHT
ABOVE PROJECT DATUM
+10'-0"
SECOND LEVEL
NAME OF LEVEL
LEVEL LINE
SEE CORRESPONDING
NUMBERED KEY NOTE ON SHEET
WHERE REFERENCE OCCURS
KEYED NOTE MARKED
REVISION NUMBER - SEE
REVISION HISTORY ON THE TITLE
BLOCK OF EACH SHEET
EXTENT OF CURRENT
REVISION
REVISION NUMBER AND EXTENT
CEILING TYPE TAG
CEILING TYPE TAG WITH
CEILING HEIGHT. HEIGHT
INDICATED IS AFF
2'X2' RECESSED LIGHT
FIXTURE
2'X4' RECESSED
LIGHT FIXTURE
FIRE PROTECTION-
SPRINKLER HEAD
F FIRE PROTECTION-
FIRE ALARM DEVICE
GYPSUM BOARD
CEILING OR SOFFIT
GWB
APC CEILING - 2X2 OR 2X4
AS INDICATED ON CEILING PLAN
APC-X
COVE LIGHT (NOT ALL
INDICATED)
RECESSED LINEAR
LIGHT FIXTURE
PENDANT/SUSPENDED
LIGHT FIXTURE
PENDANT/SUSPENDED
LIGHT FIXTURE
EXIT SIGN,
SINGLE-SIDED EXIT SIGN,
DOUBLE-SIDED
HVAC SUPPLY
GRILLE
HVAC RETURN
GRILLE
HVAC SWITCHED
EXHAUST GRILLE
HVAC SUPPLY/RETURN
LINEAR DIFFUSER
ACCESS PANEL
ARCHITECTURAL REFERENCE SYMBOLS REFLECTED CEILING PLAN SYMBOLS
FLOOR PLAN SYMBOLS ARCHITECTURAL MATERIAL INDICATIONS
EARTH RIGID INSULATION
STEEL
PLYWOOD
GYPSUM WALL BOARD
ASPHALT
SAND
GROUT
DIMENSIONAL LUMBER
CONTINUOUS WOOD
FRAMING
DIMENSIONAL LUMBER
WOOD BLOCKING
CONCRETE MASONRY
UNIT
PRECAST CONCRETE
BRICK
CONCRETE
ALUMINUM
FINISH LUMBER
GRAVEL
GRANULAR DRAINAGE
MATERIAL
STONE
BATT INSULATION
ONE HOUR FIRE
RATED PARTITION
TWO HOUR FIRE
RATED PARTITION
THREE HOUR FIRE
RATED PARTITION
DOOR OPENING
OVERHEAD
ROLLING DOOR
INTERIOR GLAZED
WINDOW
WINDOW TYPE
EQUIPMENT TYPE1i
7' - 0"
DIMENSION SYMBOL
BASE CABINETS
BASE AND WALL
CABINETS
WALL CABINETS
TOILET PARTITION
AND DOOR
HANDRAIL
BUMPER GUARD
CORNER GUARD
CGC
G
OVERHEAD ITEMS
UNDER-COUNTER ITEMS
NOT-IN-CONTRACT ITEMSNIC
FEC
FIRE EXTINGUISHER
CABINET
FE
FIRE EXTINGUISHER
(MOUNT 3'-6" AFF)
URINAL
LAVATORY -
COUNTERTOP
LAVATORY -
PEDESTAL/WALL HUNG
UTILITY SINK
FLOOR FINISH
TRANSITION SYMBOL
XXX-X
XXX-X
JANITOR'S
RECEPTOR
SHOWER
FLOOR DRAIN IN
SLOPING FLOOR
FD
FLOOR JUNCTION
BOX
ROOF SAFETY TIE-
BACK
ROOF DRAIN
RD
OVER FLOW ROOF
DRAIN
ORD
DOOR OPENING MARK
SINGLE OPENING DOOR
DOUBLE ACTING DOOR
PAIR DOORS -
EQUAL SIZES
PAIR DOORS -
UNEQUAL SIZES
PAIR DOORS -
DOUBLE EGRESS
SLIDING DOOR -
BETWEEN JAMBS
DOOR WITH SIDE LIGHT
PAIR - BI FOLD DOOR
@ AT
A AIR
AB AIR BARRIER
AB ANCHOR BOLT
AC AIR CONDITIONING
ACC ACCESSIBLE
ADD ADDENDUM
ADDL ADDITIONAL
ADJ ADJACENT
ADMIN ADMINISTRATIVE
AESS ARCHITECTURAL EXPOSED
STRUCTURAL STEEL
AFF ABOVE FINISHED FLOOR
AGGR AGGREGATE
AHJ AUTHORITIES HAVING JURISDICTION
AHU AIR HANDLING UNIT
AIC AMP INTERRUPTING CAPACITY
ALT ALTERNATE
ALUM ALUMINUM
AMP AMPERE
AMPC ACOUSTICAL METAL PAN CEILING
AOR AREA OF REFUGE
AP ACCESS PANEL
APC ACOUSTICAL PANEL CEILING
APPROX APPROXIMATE
AR ARGON
ARCH ARCHITECTURAL/ARCHITECT
PCC PRECAST CONCRETE
ASPH ASPHALT
ASSY ASSEMBLY
AT AIR TERMINAL DEVICE
AUTO AUTOMATIC
AV AUDIO VISUAL
AVE AVENUE
AVG AVERAGE
AVTR ACID VENT THROUGH ROOF
AW ACID WASTE
AWC ACOUSTIC WOOD CEILING
AWP ACOUSTICAL WALL PANEL
BD BOARD
BITUM BITUMINOUS
BL BORROWED LIGHT
BLDG BUILDING
BLKG BLOCKING/BLOCK
BLKT BLANKET
BM BENCH MARK
BOD BASIS OF DESIGN
BOS BOTTOM OF STEEL
BPL BASE PLATE
BRG BEARING
BRK BRICK
BSL BIO SAFETY LEVEL
BSMT BASEMENT
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
BTWN BETWEEN
BUR BUILT-UP ROOFING
C CHANNEL
C/C CENTER TO ROOFING
CAB CABINET
CAP CAPACITY
CB CATCH BASIN
CC CUBICAL CURTAIN
CFCI CONTRACTOR FURNISHED CONTRACTOR
INSTALLED
CFMF COLD FORM METAL FRAMING
CFOI CONTRACTOR FURNISHED OWNER
INSTALLED
CH BD CHALKBOARD
CHWS/R CHILLED WATER SUPPLY/RETURN
CI CAST IRON
CIP CAST IN PLACE CONCRETE
CIRC CIRCULATE/CIRCULATING
CJ CONTROL JOINT
CK CORK FLOORING
CL CENTERLINE
CLG CEILING
CLO CLOSET
CLR CLEAR
CM CONSTRUCTION MANAGER
CMU CONCRETE MASONRY UNIT
CO CARBON MONOXIDE
CO CLEANOUT
CO2 CARBON DIOXIDE
COL COLUMN
COMB COMBINATION/COMBINED
COMP COMPOSITE
CONC CONCRETE
COND CONDENSATE
CONF CONFERENCE
CONN CONNECTION/CONNECT
CONSTR CONSTRUCTION
CONT CONTINUOUS/CONNECT
CONTR CONTRACT(OR)
CONV CONVECTOR
CORP CORRIDOR
CP CONTROL PANEL
CPT CARPET
CR CARD READER
CS CUP SINK
CSK COUNTERSINK
CT CERAMIC TILE
CTR CENTER
CU CUBIC
CU FT CUBIC FEET
CU FT CUBIC FEET
CU YD CUBIC YARD(S)
CUH CABINET UNIT HEATER
CW COLD WATER
CW CURTAIN WALL
D DEPTH
DBL DOUBLE
DEPT DEPARTMENT
DH DOUBLE HUNG
DIA DIAMETER
DIAG DIAGONAL
DIFF DIFFERENCE
DIFF DIFFUSER
DIM DIMENSION
DIR DIRECTION
DISP DISPENSER
DISTR PNL DISTRIBUTION PANEL
DIV DIVISION
DL DEAD LOAD
DL DIVIDED LITES
DN DOWN
DO DOOR OPERATOR
DPTN DEMOUNTABLE PARTITION
DR DOOR
DS DOWNSPOUT
DTL DETAIL
ARCHITECTURAL ABBREVIATIONS
DW DISHWASHER
DWG DRAWING
DWR DRAWER
DWTR DUMBWAITER
E EAST
EA EACH
EC ELECTRICAL CONTRACTOR
ED EMERGENCY DEPARTMENT
EEW EMERGENCY EYE WASH
EF EXHAUST FAN
EFG ENTRANCE FLOOR GRILL
EFM ENTRANCE FLOOR MAT
EH EXHAUST HOOD
EIFS EXTERIOR FINISH INSULATION SYSTEM
EL ELEVATION
ELEC ELECTRIC (ELECTRICAL)
ELEV ELEVATOR
EMBED EMBEDDED
EMER EMERGENCY
EMT ELECTRICAL METALLIC TUBING
ENCL ENCLOSURE
ENTR ENTRANCE
EP ELECTRICAL PANEL
EPO EMERGENCY POWER OUTLET
EPT EPOXY PAINT
EPX EPOXY
EQ EQUAL
EQUIP EQUIPMENT
ES EMERGENCY SHOWER
ESR ELASOMETRIC SHEET ROOFING
ETR EXISTING GTO REMAIN
EWC ELECTRIC WATER COOLER
EWS EMERGENCY SHOWER AND EYE WASH
EXC EXCAVATE(D)
EXH EXHAUST
EXIST EXISTING
EXP EXPOSED
EXT EXTERIOR
F FAHRENHEIT
FA FIRE ALARM
FB FLOOR BOX
FCU FAN COIL UNIT
FD FLOOR DRAIN
FDC FIRE DEPT CONNECTION
FDTN FOUNDATION
FDV FIRE DEPT VALVE
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FF FINISHED FLOOR
FH FIRE HYDRANT
FHC FIRE HOSE CABINET
FHR FIRE HOSE RACK
FIN FINISH (ED)
FIXT FIXTURE
FLEX FLEXIBLE
FLR FLOOR
FP FIRE PROTECTION
FPM FEET PER MINUTE
FPS FEET PER SECOND
FR FIRE RETARDANT/RESISTANT
FRP FIBERGLASS REINFORCED
PANEL/POLYESTER/PLASTIC
FRT FIRE RESISTANT TREATED
FRZ FREEZER
FT FEET
FTG FOOTING
GA GAGE (GAUGE)
GAL GALLON(S)
GALV GALVANIZED
GC GENERAL CONTRACTOR
GEN GENERAL
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GFRC GLASS FIBER REINFORMCENT
CONCRETE
GFRP GLASS FIBER REINFORCED PLASTER
GL GLASS
GPC GROUND POLISHED CONCRETE
GRT GROUT
GWB GYPSUM WALL BOARD
HB HOSE BIBB
HD HEAD
HD HUB DRAIN
HDWD HARDWOOD
HDWE HARDWARE
HE HELIUM
HEX HEXAGON
HM HOLLOW METAL
HO ELECTROMAGNETIC HOLD OPEN
HOLD HOLD DIMENSION
HORIZ HORIZONTAL
HP HIGH POINT
HP HORSEPOWER
HPC HIGH PERFORMANCE COATING
HR HOUR
HSKPG HOUSEKEEPING
HSS HOLLOW STRUCTURAL SHAPE
HT HEIGHT
HVAC HEATING, VENTILATING & AIR
CONDITIONING
HW HOT WATER
HWS HEAD WELDED STUD
HYD HYDROGEN
ID INSIDE DIAMETER/DIMENSION
IMP INSULATED METAL PANEL
IN INCH(ES)
INCL INCLUDE
INFO INFORMATION
INSUL INSULATION/INSULATED
INT INTEGRAL
INV INVERT
INV EL INVERT ELEVATION
JAN JANITOR
JAN CLO JANITOR CLOSET
J-BOX JUNCTION BOX
JST JOIST
JT JOINT
K KIP (1000 LB)
KO KNEE SPACE OPENING
KPL KICK PLATE
KV KILOVOLT
KW KILOWATTS
KWH KILOWATT HOUR
L ANGLE
L LENGTH/LONG
LAB LABORATORY
LAN LOCAL AREA NETWORK
LAV LAVATORY
LBS POUND(S) / LBS
LEV LEVEL
LF LINEAR FOOT
LFG LAB FURNISHINGS CONTRACTOR
LH LEFT HAND
LINO LINOLEUM
LKR LOCKER
LL LIVE LOAD
LN2 LIQUID NITROGEN
LNDG LANDING
LOC LOCATION (LOCATE)
LONG LONGITUDINAL
LPT LOW POINT
LT GA LIGHT GAGE
LTG LIGHTING
LTG PNL LIGHTING PANEL
LVR LOUVER
LW LIGHTWEIGHT
M METER
MACH MACHINE
MAN MANUAL
MATL MATERIAL
MAX MAXIMUM
MB MARKER BOARD
MC MECHANICAL CONTRACTOR
MCC MOTOR CONTROL CENTER
MDO MEDIUM DENSITY OVERLAY
MECH MECHANICAL
MECH RM MECHANICAL EQUIPMENT ROOM
MED MEDICINE/MEDICAL
MED MEDIUM
MEMB MEMBRANE
MEP MECHANICAL, ELECTRICAL, PLUMBING
MEZZ MEZZANINE
MFR MANUFACTURER
MGR MANAGER
MH MANHOLE
MIC MOBILE INSTRUMENT CART
MICRO MICROWAVE
MIN MINIMUM
MIN MINUTE
MIR MIRROR
MISC MISCELLANEOUS
MLDG MOLDING/MOULDING
mm MILLIMETER
MO MASONRY OPENING
MPH MILES PER HOUR
MTD MOUNTED
MTG MOUNTING
MTL METAL
N NORTH
N2 NITROGEN, PIPED GAS
NA NOT APPLICABLE
NG NATURAL GAS
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NTS NOT IN SCALE
NW NORMAL WEIGHT
O OXYGEN, PIPED GAS
OA OUTSIDE AIR
OA OVERALL
OC ON CENTER
OCC OCCUPANCY/OCCUPATION/OCCUPY
OD DRAIN (OVERFLOW)
OD OUTSIDE DIAMETER
OFCI OWNER FURNISHED, CONTRACTOR
INSTALLED
OFF OFFICE/OFFICER
OFOI OWNER FURNISHED,OWNER INSTALLED
OH OPPOSITE
OHSC OVER HEAD SERVICE CARRIER
OPNG OPENING
OPP OPPOSITE
OR OPERATING ROOM
OSHA OCCUPATIONAL SAFETY AND HEALTH
ASSOCIATION
OZ OUNCE
PCC PRECAST CONCRETE - STRUCTURAL
PCF POUNDS PER CUBIC FOOT
PERF PERFORATED
PH PHASE
PL PLATE
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLBG PLUMBING
PLF POUNDS PER LINEAR FOOT
PLYWD PLYWOOD
PNL PANEL/PANELING
PR PAIR
PREFAB PREFABRICATED
PREFIN PREFINISHED
PREP PREPARATION
PS PROJECTION SCREEN
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT PAINT
P-TYPE PARTITION TYPE
PVC POLYVINYL CHLORIDE
PVMT PAVEMENT / PAVING
PW POLISHED WATER
QT QUARRY TILE
QTY QUANTITY
R RADIUS
R RISER
RA RETURN AIR
RB RESILIENT BASE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REC RECESSED
RECPT RECEPTACLE
REF REFERENCE
REF REFRIGERATOR
REINF REINFORCED/REINFORCEMENT
REQ REQUIRED
RET RETURN
REV REVISION
RF RESINOUS FLOORING
RH RELATIVE HUMIDITY
RH RIGHT HAND
RM ROOM
RO REVERSE OSMOSIS
RO ROUGH OPENING
RPM REVOLUTION PER MINUTE
RUB RUBBER FLOORING
RV ROOF VENT
S SOUTH
SA SUPPLY AIR
SAN SANITARY
SC SEALED CONCRETE
SCF STATIC CONTROL FLOORING
SCHED SCHEDULE
SECT SECTION
SF SQUARE FOOT
SGL SINGLE
SHT SHEET
SHT MTL SHEET METAL
SHWR SHOWER
SIM SIMILAR
SOG SLAB ON GRADE
SPEC SPECIFICATION
SPKR SPEAKER
SPP SOLID PHENOLIC PANELS
SQ IN SQUARE INCHES
SQ YD SQUARE YARD
SS STAINLESS STEEL
SSM SOLID SURFACE MATERIAL
ST STONE
ST STREET
STD STANDARD
STL STEEL
STOR STORAGE
STRUC STRUCTURAL /STRUCTURE
SUSP SUSPENDED
SV SHEET VINYL
SVT SOLID VINYL TILE
SW SWITCH
T TREAD
T&B TOP AND BOTTOM
T&G TONGUE AND GROOVE
TA TOILET ACCESSORIES
TB TACKBOARD
TBB TILE BACKER BOARD
TBD TO BE DETERMINED
TD TRENCH DRAIN
TEL TELEPHONE
TEMP TEMPERATURE/TEMPERED
THK THICK/THICKNESS
TLT TOILET
TO TOP OF
TPO THERMOPLASTIC OLEFIN
TR TELECOM ROOM
TRDT TREATED
TS TUBE STEEL
TSTAT THERMOSTAT
TV TELEVISION
TYP TYPICAL
TZ TERRAZZO
UC UNDER COUNTER
UL UNDERWRITERS LABORATORY
UNO UNLESS NOTED OTHERWISE
UPH UPHOLSTERY
UPS UNINTERRUPTED POWER SUPPLY
UTIL UTILITY
UV ULTRAVIOLET
VAR VARIES
VAV VARIABLE AIR VOLUME
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
VFD VARIABLE FREQUENCY DRIVE
VIF VERIFY IN FIELD
VOL VOLUME
VR VAPOR RETARDER
VTR VENT THRU ROOF
W WEST
W WIDTH
W/ WITH
W/O WITHOUT
WC WALL COVERING
WD WOOD
WF WIDE FLANGE STEEL BEAM
WP WALL PROTECTION
WP WORKING POINT
WT WINDOW TREATMENTS
WT WEIGHT
WTR WATER
WHEEL CHAIR
CLEARANCE
CENTERLINE
ø 5' - 0
1i CEILING TYPE
? KEYNOTE SYMBOL
101 DOOR TYPE TAG
Ref
ELEVATION NUMBER
SYMBOL
EXIT SIGN SYMBOL
ACT-?
ACT-?
NORTH ARROW
SYMBOL
X WALL TAG SYMBOL
1t
Zone Name ZONE TAG SYMBOL
BREAK LINE SYMBOL
DEMO APC CEILING - 2X2 OR 2X4
AS INDICATED ON CEILING PLAN
APC-X
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437
COA: FL #29758
AKEA Project No. AD204-22
Design, Inc.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT / ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
A/E REPLACE AHUs 22 AND 23 673-21-152
TAMPA, FLORIDA
OF
ARCHITECT - OF - RECORD FL. REG. NO.
APPROVED FOR CONSTRUCTION
This item has been electronically signed and sealed by the individual named at right.
Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
FINAL DESIGN
JAMES A. HALEY VA HOSPITAL
BUILDING #30
13000 BRUCE B. DOWNS BLVD.
FINAL DESIGN
APPROVED FOR CONSTRUCTION
-0 4-
2:
:0
JRF RAL
JENNIFER R. FONG AR97191
AG001
ARCHITECTURAL ABBREVIATIONS
AND SYMBOLS
2 41APRIL 14, 2023Revisions: Date:
Digitally signed by Jennifer R Fong Date: 2023.04.12 16:24:12-04'00'
A D
AE101
MECHANICAL
30-011A
MECHANICAL
30-011
AE101
EXISTING LOUVER AND
FRAMING TO REMAIN
DEMOLISH EXISTING BLOCK AND
BRICK FOR NEW TEMPORARY
OPENING.REINFORCE PER
STRUCTURAL AND PERMANANTLY
INFILL AFTER TEMPORARY
CONDITIONS ARE COMPLETED.
±4'-0" ±1'-4"
±6'-4 2' - 6"
DEMOLISH EXISTING BLOCK
AND BRICK FOR NEW OPENING.
REINFORCE PER STRUCTURAL -
SEE MECHANICAL
AE101 3
DEMOLISH EXISTING BLOCK AND
BRICK FOR NEW TEMPORARY
OPENING. REINFORCE PER
STRUCTURAL AND PERMANENTLY
INFILL AFTER TEMPORARY
CONDITIONS ARE COMPLETED.
6'
9" 4'
0"
±6'-0"
EXISTING 1
HOUR
RATED
AE101
Sim
AE101
Sim
AE101
Sim
TEMPORARY MECH DUCTS,
REFER TO MECH DRAWINGS
TEMPORARY DUCT SLEEVE,
REFER TO MECH.
TEMPORARY SELANT AND
CAULK AROUND THE OPENING
EXISTING FACE BRICK
EXISTING AIR GAP
TEMPORARY DUCT SLEEVE,
REFER TO MECHANICAL
EXISTING FACE BRICK
EXISTING AIR GAP EXISTING CONCRETE
BOND BEAM
EXISTING CMU OR
CONCRETE WALL
TEMPORARY PLYWOOD SHEATHING
INFILL, REFER TO STRUCTURAL
DRAWINGS FOR FINAL INFILL
TEMPORARY PLYWOOD OR
OTHER REMOVABLE SHEATHING
OVER AIR GAP, TYP.
NEW LINTEL PER
STRUCTURAL
EXISTING AIR GAP
EXISTING FACE BRICK
TEMPORARY METAL STUD
FRAMING
TEMPORARY METAL
SLEEVE, REFER TO
MECHANICAL
TEMPORARY PLYWOOD
SHEATHING INFILL, REFER
TO STRUCTURAL DRAWINGS
FOR FINAL INFILL
TEMPORARY MECHANICAL
DUCTS AND PIPING AS
APPLICABLE, REFER TO
MECHANICAL DRAWINGS
EXISTING CMU OR
CONCRETE WALL
SEE PLAN FOR OPENING WIDTH
TEMPORARY PLYWOOD
OTHER REMOVABLE
SHEATHING OVER AIR
GAP, TYP.
AE101
Sim
EXISTING FACE BRICK
EXISTING AIR GAP EXISTING CMU WALL
BRICK TIES AT 16" O.C.
VERTICALLY AND
HORIZONTALLY,TYP.
VAPOR BARRIER TO MATCH
EXISTING. IF FILM EXISTS,
OVERLAP FOR PROPER
MOISTURE DRAINAGE
FACE BRICK INFILL TO MATCH
EXISTING. PAINT TO MATCH
EXISTING COLOR IF EXACT
MATCH IS NOT AVAILABLE
BLOCK INFILL TO
MATCH EXISTING
EXISTING CONCRETE
BOND BEAMEXISTING FACE BRICK
EXISTING AIR GAP
EXISTING LINTEL
Ground Floor 43' - 9"
AD
Bldg. 30 Roof Lvl 58' - 3"
EXISTING LOUVER AND
FRAME TO REMAIN
TEMPORARY FRAMING
PER STRUCTURAL
TEMPORARY OPENING
FOR MECHANICAL
EXISTING WALL TO REMAIN
PE
R
M
EC
H
AN
IC
AL
±3
0"
3'
6"
3' - 10 9/16"
PERMANENT OPENING
FOR PERMANENT DUCTS
PER MECHANICAL
Level 3 48' - 7"
2' - 6"
2'
0"
EXISTING
RETAINING
WALL
EXISTING
SLOPED
CURB AND
DRIVEWAY,
GRADE
VARIES,
FIELD VERIFY
PE
R
M
EC
H
AN
IC
AL
±6
FIELD VERIFY
FIELD VERIFY
Ground Floor 43' - 9"
Bldg. 30 Roof Lvl 58' - 3"
Level 3 48' - 7"
TEMPORARY OPENING FOR
TEMPORARY PIPING AND
DUCT PER MECHANICAL
TEMPORARY
FRAMING PER
STRUCTURAL
EXISTING WALL
TO REMAIN
EXISTING
RETAINING WALL EXISTING SLOPED
CURB AND
DRIVEWAY, GRADE
VARIES, FIELD VERIFY
4' - 0"
1'
6"
FIELD VERIFY
EXISTING FACE BRICK
R-19 MIN.
THERMAL INSULATION
BRICK TIES AT 16" O.C.
VERTICALLY AND
HORIZONTALLY, TYP.
DENSGLASS OR EQUAL
FACE BRICK INFILL TO MATCH
EXISTING, PAINT TO MATCH
EXISTING COLOR IF EXACT
MATCH IS NOT AVAILABLE
METAL STUD INFILL - BUILD UP TO
FULL DEPTH OF WALL WITH
SHEATHING
EXISTING LINTEL
SEAL EDGE, SKIM COAT AND
SAND SMOOTH FLUSH WITH
EXISTING. PAINT TO MATCH
ADJACENT.
CEMENTOUS BOARD
SHEATHING
SEAL PERIMETER EDGE
EXISTING CONCRETE
BOND BEAM
EXISTING CONCRETE WALL
EXISTING AIR GAP
EXISTING FACE BRICK
EXISTING AIR GAP
RUNNER CHANNEL
3603 NW 98th Street, Suite B Gainesville, FL 32606 Phone: (352) 474-6124 Fax: (352) 553-4437
COA: FL #29758
AKEA Project No. AD204-22
Design, Inc.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT / ENGINEER OF RECORDCONSULTANT
321 4 5 6 7 8 9 10
A/E REPLACE AHUs 22 AND 23 673-21-152
TAMPA, FLORIDA
OF
ARCHITECT - OF - RECORD FL. REG. NO.
APPROVED FOR CONSTRUCTION
This item has been electronically signed and sealed by the individual named at right.
Printed copies of this document are not considered signed and sealed and the signature must be verified on any electronic copies.
FINAL DESIGN
JAMES A. HALEY VA HOSPITAL
BUILDING #30
13000 BRUCE B. DOWNS BLVD.
FINAL DESIGN
APPROVED FOR CONSTRUCTION
-0 4-
1:
:1
JRF RAL
JENNIFER R. FONG AR97191
AE101
PLAN, ELEVATIONS AND
WALL OPENING DETAILS
3 41APRIL 14, 2023
3/8" = 1'-0"1 GROUND LEVEL FLOOR PLAN
1 1/2" = 1'-0"5 TEMPORARY WALL OPENING SECTION
1 1/2" = 1'-0"4 TEMPORARY WALL OPENING - PLAN VIEW
1 1/2" = 1'-0"6 FINAL INFILL WALL OPENING - AT EXISTING CAVITY WALL
3/8" = 1'-0"2 NORTH ELEVATION
3/8" = 1'-0"3 WEST ELEVATION
1 1/2" = 1'-0"7 FINAL INFILL WALL OPENING - AT EXISTING RETAINING WALL
Revisions: Date:
Date: 2023.04.13 18:45:22-04'00'
System No. C-AJ-1044 June 15, 2005
F Ratings - 2,3, and 4 Hr T Rating - 0 Hr
L Rating At Ambient - 2 CFM/sq ft L Rating At 400 F - less than 1 CFM/sq ft
W Rating - Class I
SE
CT
IO
N
SECTION A-A
A
A
2 4 1
REFER TO UL DIRECTORY, FIRE RESISTANCE (VOLUME 2) AND MANUFACTURER'S LITERATURE FOR
COMPLETE DETAILING.
1. Floor or Wall Assembly - Lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Except as noted in complete system detail, min thickness of solid concrete floor or wall assembly is 4-1/2 in. (114 mm). Floor may also be constructed of any min 6 in. (152 mm) thick UL Classified hollow core Precast Concrete Units*. When floor is constructed of hollow core precast concrete units, packing material (Item 3) and caulk fill material (Item 4) to be installed symmetrically on both sides of floor, flush with floor surface. Wall assembly may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is in solid lightweight or normal weight concrete. Floor is 32 in. (813 mm). Max diam of opening in floor constructed of hollow-core precast concrete units is 7 in. (178 mm).
1A. Steel Sleeve (Not shown) - Max 15 in. (381 mm) ID (or smaller) Schedule 10 (or heavier) steel sleeve cast or grouted into floor or wall assembly. Sleeve may extend a max of 2 in. (51 mm) above top of floor or beyond either surface of wall. Max 16 in. (406 mm) ID (or smaller) min 0.028 (0.71 mm) wall thickness (or heavier) galvanized steel sleeve cast or grouted into floor or wall assembly. Sleeve may extend a max of 1/2 in. (13 mm) beyond either surface of floor or wall.
2. Through Penetrants - One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the firestop system. Max annular space between pipe, conduit or tubing and edge of through opening or sleeve is dependent on the parameters shown in Item 4. Min annular space between pipe or conduit and edge of through opening is 0 in. (0 mm) (point contact). Pipe conduit or tubing to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used:
A. Steel Pipe - Nom 30 in. (762 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe - Nom 30 in. (762 mm) diam (or smaller) cast or ductile iron pipe.
C. Conduit - Nom 6 in. (152 mm) diam (or smaller) rigid steel conduit.
D. Conduit - Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing.
E. Copper - Tubing Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tube.
F. Copper Pipe - Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe.
3. Packing Material - Polyethylene backer rod or nom 1 in. (25 mm) thickness of tightly-packed mineral wool batt or glass fiber insulation firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of caulk fill material (Item 4).
4. Fill,Void or Cavity Material* - Caulk or Sealant - Applied to fill the annular space flush with top surface of floor. In wall assemblies, required caulk thickness to be installed symmetrically on both sides of wall, flush with wall surface.
At point contact location between penetrant and sleeve or between penetrant and concrete, a min 1/4 in. (6 mm) diam bead of caulk shall be applied at top surface of floor and at both surfaces of wall. The hourly F Ratings and the min required caulk thicknesses are dependent upon a number of parameters, as shown in the complete system detail.
3M COMPANY - CP 25WB+ caulk or FB-3000 WT sealant.
SINGLE METALLIC PIPE
CONCRETE
System No. C-AJ-5024 May 19, 2005
F Ratings - 2 and 3 Hr T Ratings - 1 and 1-1/2 Hr
L Rating At Ambient - 2 CFM/sq ft L Rating At 400 F - less than 1 CFM/sq ft
SE
CT
IO
N
SECTION A-A
A
A
REFER TO UL DIRECTORY, FIRE RESISTANCE (VOLUME 2) AND MANUFACTURER'S LITERATURE FOR
COMPLETE DETAILING.
1. Floor or Wall Assembly - Min 4-1/2 in. (114 mm) thick lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of circular through opening is 21 in. (533 mm).
1A. Steel Sleeve (Not shown) - Nom 21 in. (533 mm) (or smaller) Schedule 10 (or heavier) steel sleeve cast or grouted into floor or wall assembly. Sleeve may extend a max of 2 in. (51 mm) above top of floor or beyond either surface of wall. Sleeve may be used only when floor or wall assembly is min 4-1/2 in. (114 mm) thick.
2. Through Penetrants - One metallic pipe or tubing to be installed either concentrically or eccentrically within the firestop. Pipe or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes or tubing may be used:
A. Steel Pipe - Nom 10 in. (254 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Copper Tubing - Nom 4 in. (102 mm) diam (or smaller) Type L (or heavier) copper tubing.
C. Copper Pipe - Nom 4 in. (102 mm) diam (or smaller) Regular (or heavier) copper pipe.
3. Pipe Covering* - Nom 1, 2 or 3 in. (25, 51 or 76 mm) thick hollow cylindrical heavy density (min 3.5 pcf or 56 kg/m3) glass fiber units jacketed on the outside with an all service jacket. Longitudinal joints sealed with metal fasteners or factory-applied selfsealing lap tape. Transverse joints secured with metal fasteners or with butt strip tape supplied with the product.
4A. Fill,Void or Cavity Materials* - Wrap Strip - Nom 1/4 in. (6 mm) thick intumescent elastomeric material faced on one side with aluminum foil, supplied in nom 2 in. (51 mm) wide strips. Nom 2 in. (51 mm) wide strip tightly-wrapped around pipe covering material (foil side exposed), secured with a steel wire tie and slid into annular space. In floors, the wrap strip layer is to be installed with its top edge recessed 1/8 to 1/2 in. (3.2 mm to 13 mm) from the top surface of the floor. In walls, the wrap strip layer is to be installed in the same manner used for floors but it shall be installed symmetrically on both sides of the wall assembly. The min number of wrap strip layers required is dependent upon the pipe covering material thickness, as shown in the complete system detail.
3M COMPANY - FS-195+.
4B. Packing Material - When an annular space is present between the wrap strip and the periphery, mineral wool batt insulation shall be tightly-packed into the annular space. In floors, the top surface of the packing material is to be recessed min 1 in. (25 mm) from the top surface of the floor. In walls, the packing material is to be installed in the same manner used for floors but it shall be installed symmetrically on both sides of the wall assembly.
4C. Fill,Void or Cavity Materials* - Caulk or Sealant - Installed to fill annular space to a min depth of 1 in. (25 mm), flush with top surface of floor or both surfaces of wall, such that exposed edge of wrap strip layer is covered with a 1/8 to 1/2 in. (3.2 mm to 13 mm) thickness.
3M COMPANY - CP 25WB+, IC 15WB+ caulk or FB-3000 WT sealant.
4C 2
4A
4B 4A
4C
SINGLE INSULATED METALLIC PIPE
CONCRETE
System No. C-AJ-2228 November 20, 2009
F Ratings - 2 and 3 Hr T Ratings - 0, 2 and 3 Hr
W Rating - Class I
SE
CT
IO
N
SECTION A-A
A
A
REFER TO UL DIRECTORY, FIRE RESISTANCE (VOLUME 2) AND MANUFACTURER'S LITERATURE
FOR COMPLETE DETAILING.
1. Floor or Wall Assembly — Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600 - 2400 kg/m3) concrete. Wall may also be constructed of any UL Classified Concrete Blocks*.
Diam of opening shall be 1 in. (25 mm) larger than nom pipe diam.
2. Steel Sleeve — Nom 4 in. (102 mm) diam (or smaller) Schedule 10 (or heavier) steel sleeve cast or grouted into floor or wall assembly.
T Rating is 0 Hr when sleeve is used.
3. Through Penetrants — One nonmetallic pipe or conduit to be installed within opening. The annular space between pipe or conduit and periphery of opening or sleeve and the T Ratings for the pipes when no sleeve is used are dependent on the type of pipe and nom pipe sizes as shown in the complete system detail. Pipe or conduit to be rigidly supported on both sides of the floor or wall assembly. The following types and sizes of nonmetallic pipes may be used:
A. Polyvinyl Chloride (PVC) Pipe — Nom 3 in. (76 mm) diam (or smaller) Schedule 40 solid core or cellular core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems.
B. Rigid Nonmetallic Conduit++ — Nom 3 in. (76 mm) diam (or smaller) Schedule 40 PVC conduit installed in accordance with Article 347 of the National Electrical Code (NFPA No. 70).
C. Chlorinated Polyvinyl Chloride (CPVC) Pipe — Nom 3 in. (76 mm) diam (or smaller) SDR13.5 CPVC pipe for use in closed (process or supply) piping systems.
D. Acrylonitrile Butadiene Styrene (ABS) Pipe — Nom 3 in. (76 mm) diam (or smaller) Schedule 40 solid core or cellular ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems.
E. Fire Retardant Polypropylene (FRPP) Pipe — Nom 3 in. (76 mm) diam (or smaller) Schedule 40 FRPP pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems.
4. Firestop System — The firestop system shall consist of the following:
A. Fill, Void or Cavity Materials* — Wrap Strip — Nom 1/8 in. (3.2 mm) thick intumescent material supplied in 2 in. (51 mm) wide strips. Wrap strip tightly wrapped around nonmetallic pipe with continuous layers and secured with two 1/4 in. (6 mm) wide bands of filament tape placed 1/2 in. (13 mm) from bottom and top of wrap strip. The layers of wrap strip and its position within the opening are dependent on the pipe size. For nom 2 in. (51 mm) diam (or smaller) pipes, one layer is required, recessed within the opening 2-1/4 in. (57 mm) from the bottom surface of the floor or both surfaces of the wall. For nom 2-1/2 and 3 in. (64 and 76 mm) diam pipes, two layers are required, recessed within the opening 1-1/2 in. (38 mm) from the bottom surface of the floor or both surfaces of the wall.
3M COMPANY — Ultra GS B. Fill, Void or Cavity Materials* — Caulk or Sealant (Optional, Not Shown) — Min 1/4 in. (6 mm) thickness of caulk or sealant applied within annular space, flush with top of floor .
3M COMPANY — CP 25WB+ caulk, FB-3000 WT Sealant, FB-1000 NS sealant, IC 15WB+ caulk or FireDam 150+ caulk. (CP 25WB+ and FireDam 150+ not suitable for use with CPVC pipes.)
(Note - W Rating applies only when FB-3000 WT or FB- 1000 NS is used.)
4B
4B
4A
SINGLE NON-METALLIC PIPE
CONCRETE
System No. W-L-1001 June 15, 2005
F Ratings - 1,2,3, and 4 Hr T Ratings - 0, 1, 2, 3, and 4 Hr
L Rating At Ambient - less than 1 CFM/sq ft L Rating At 400 F - less than 1 CFM/sq ft
SE
CT
IO
N
SECTION A-A
A
A
REFER TO UL DIRECTORY, FIRE RESISTANCE (VOLUME 2) AND MANUFACTURER'S LITERATURE FOR
COMPLETE DETAILING.
1. Wall Assembly - The 1, 2, 3 or 4 hr fire-rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner described in the individual U300 or U400 Series Wall or Partition Designs in the UL Fire Resistance Directory and shall include the following construction features:
A. Studs - Wall framing may consist of either wood studs (max 2 hr fire rated assemblies) or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC with nom 2 by 4 in. (51 by 102 mm) lumber end plates and cross braces. Steel studs to be min 3-5/8 in. (92 mm) wide by 1-3/8 in. (35 mm) deep channels spaced max 24 in. (610 mm) OC.
B. Gypsum Board* - Nom 1/2 or 5/8 in. (13 or 16 mm) thick, 4 ft. (122 cm) wide with square or tapered edges. The gypsum wallboard type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the UL Fire Resistance Directory. Max diam of opening is 26 in. (660 mm).
2. Through Penetrant - One metallic pipe, conduit or tubing installed either concentrically or eccentrically within the firestop system. The annular space between pipe, conduit or tubing and periphery of opening shall be min of 0 in. (0 mm) (point contact) to max 2 in. (51 mm). Pipe, conduit or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used:
A. Steel Pipe - Nom 24 in. (610 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe - Nom 24 in. (610 mm) diam (or smaller) service weight (or heavier) cast iron soil pipe, nom 12 in. (305 mm) diam (or smaller) or Class 50 (or heavier) ductile iron pressure pipe.
C. Conduit - Nom 6 in. (152 mm) diam (or smaller) steel conduit or nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing D. Copper Tubing - Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing E. Copper Pipe - Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe.
F. Through Penetrating Product* - Flexible Metal Piping - The following types of steel flexible metal gas piping may be used:
1. Nom 2 in. (51 mm) diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removed on both sides of floor or wall assembly. OMEGA FLEX INC
2. Nom 1 in. (25 mm) diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removed on both sides of floor or wall assembly. TITEFLEX CORP, A BUNDY CO
3. Nom 1 in. (25 mm) diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removed on both sides of floor or wall assembly. WARD MFG INC
3. Fill,Void or Cavity Material* - Caulk or Sealant - Min 5/8. 1-1/4,1-7/8 and 2-1/2 in. (16, 32, 48 and 64 mm) thickness of caulk for 1, 2, 3 and 4 hr rated assemblies, respectively, applied within annulus, flush with both surfaces of wall. Min 1/4 in.
(6 mm) diam bead of caulk applied to gypsum board/penetrant interface at point contact location on both sides of wall.
The hourly F and T Rating of the firestop system is dependent upon the type or size of the pipe or conduit and the hourly fire rating of the wall assembly in which it is installed, as shown in the complete system detail.
+When copper pipe is used, T Rating is 0 hr.
3M COMPANY - CP 25WB+ caulk or FB-3000 WT sealant, 1A
1B
SINGLE METALLIC PIPE
GYPSUM
System No. W-L-5001 May 19, 2005
F Ratings - 1 and 2 Hr T Ratings - 3/4, 1 and 1-1/2 Hr
L Rating At Ambient - 2 CFM/sq ft L Rating At 400 F - less than 1 CFM/sq ft
SE
CT
IO
N
SECTION A-A
A
A
REFER TO UL DIRECTORY, FIRE RESISTANCE (VOLUME 2) AND MANUFACTURER'S LITERATURE
FOR COMPLETE DETAILING.
1. Wall Assembly - The 1 or 2 hr fire-rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner described in the individual U300, U400 or V400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features:
A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 in. by 4 in. (25 mm by 102 mm) lumber spaced 16 in. (406 mm) OC with nom 2 by 4 in. lumber end plates and cross braces. Steel studs to be min 3-5/8 in. (92 mm) wide by 1-3/8 in. (35 mm) deep channels spaced max 24 in. (610 mm) OC.
B. Gypsum Board* - Nom 5/8 in. (16 mm) thick, 4 ft (122 cm) wide with square or tapered edges. The gypsum wallboard type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the UL Fire Resistance Directory. Max diam of opening is 14-1/2 in (368 mm) for wood stud walls and 18 in. (457 mm) for steel stud walls.
The hourly F Rating of the firestop system is 1 hr when installed in a 1 hr fire rated wall and 2 hr when installed in a 2 hr fire rated wall.
2. Through Penetrants - One metallic pipe or tubing to be centered within the firestop system. Pipe or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes or tubing may be used:
A. Steel Pipe - Nom 12 in. (305 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Copper Tubing - Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing.
C. Copper Pipe - Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe.
3. Pipe Covering* - Nom 1 in. or 2 in. (25 mm or 51 mm) thick hollow cylindrical heavy density glass fiber units jacketed on the outside with an all service jacket. Longitudinal joints sealed with metal fasteners or factory-applied self-sealing lap tape. Transverse joints sealed with metal fasteners or with butt strip tape supplied with the product. When nom 1 in. (25 mm) thick pipe covering is used, the annular space between the pipe covering and the circular cutout in the gypsum wallboard layers on each side of the wall shall be min 1/4 in. to max 3/8 in. (6 mm to max 10 mm). When nom 2 in. (51 mm) thick pipe covering is used, the annular space between the pipe covering and the circular cutout in the gypsum wallboard layers on each side of the wall shall be min 1/2 in. to max 3/4 in. (13 mm to max 19 mm).
4. Firestop System - Installed symmetrically on both sides of wall assembly. The details of the firestop system shall be as follows:
A. Fill,Void or Cavity Materials* - Wrap Strip - Nom 1/4 in. (6 mm) thick intumescent elastomeric material faced on one side with aluminum foil, supplied in 2 in. (51 mm) wide strips. Nom 2 in. (51 mm) wide strip tightly wrapped around pipe covering (foil side out) with seam butted. Wrap strip layer securely bound with steel wire or aluminum foil tape and slid into annular space approx 1-1/4 in. (32 mm) such that approx 3/4 in.
(19 mm) of the wrap strip width protrudes from the wall surface. One layer of wrap strip is required when nom 1 in. (25 mm) thick pipe covering is used. Two layers of wrap strip are required when nom 2 in. (51
mm) thick pipe covering is used.
3M COMPANY - FS-195+
B. Fill,Void or Cavity Materials* - Caulk or Sealant - Min 1/4 in. (6 mm) diam continuous bead applied to the wrap strip/wall interface and to the exposed edge of the wrap strip layer approx 3/4 in. (19 mm) from the wall surface. 3M COMPANY - CP 25WB+, IC 15WB+, FireDam 150+ caulk or FB-3000 WT sealant
4B
4A
2 3
4A
1A 1B
4B
SINGLE INSULATED METALLIC PIPE
GYPSUM
System No. W-L-2003 November 20, 2009
F Ratings - 1 and 2 Hr T Ratings - 1 and 2 Hr
L Rating At Ambient - 7 CFM/sq ft L Rating At 400 F - less than 1 CFM/sq ft
SE
CT
IO
N
SECTION A-A
A
A
REFER TO UL DIRECTORY, FIRE RESISTANCE (VOLUME 2) AND MANUFACTURER'S LITERATURE FOR COMPLETE
DETAILING.
1. Wall Assembly — The 1 or 2 hr fire-rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner described in the individual U300, U400 or V400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features:
A. Studs — Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in.
(51 by 102 mm) lumber spaced 16 in. (406 mm) OC with nom 2 by 4 in. (51 by 102 mm) lumber end plates and cross braces. Steel studs to be min 3-5/8 in. (92 mm) wide by 1-3/8 in. (35 mm) deep channels spaced max 24 in. (610 mm) OC.
B. Gypsum Board* — 5/8 in. (16 mm) thick, 4 ft (122 cm) wide with square or tapered edges. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300, U400 or V400 Series Design in the UL Fire Resistance Directory. Max diam of opening is 3-1/8 in. (79 mm).
2. Through Penetrants — One nonmetallic pipe or conduit to be centered in the through opening. The annular space between pipe or conduit and periphery of opening shall be min 1/4 in. (6 mm) and max 3/8 in. (10 mm). Pipe or conduit to be rigidly supported on both sides of the floor-ceiling assembly. The following types and sizes of nonmetallic pipes or conduits may be used:
A. Polyvinyl Chloride (PVC) Pipe — Nom 2 in. (51 mm) diam (or smaller) Schedule 40 solid core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping system.
B. Rigid Nonmetallic Conduit++ — Nom 2 in. (51 mm) diam (or smaller)(Schedule 40 or 80) PVC conduit installed in accordance with the National electric Code (NFPA No. 70).
C. Chlorinated Polyvinyl Chloride (CPVC) Pipe — Nom 2 in. (51 mm) diam (or smaller) SDR13.5 CPVC pipe for use in closed (process or supply) piping systems.
D. Cellular Core Polyvinyl Chloride (ccPVC) Pipe — Nom 2 in. (51 mm) diam (or smaller) Schedule 40 cellular core PVC pipe for use in closed (process or supply) or vented (drain, waste or vent) piping system.
E. Acrylonitrile Butadiene Styrene (ABS) Pipe — Nom 2 in. (51 mm) diam (or smaller) Schedule 40 solid core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems.
F. Cellular Core Acrylonitrile Butadiene Styrene (ccABS) Pipe — Nom 2 in. (51 mm) diam (or smaller) Schedule 40 cellular core ABS pipe for use in closed (process or supply) or vented (drain, waste or vent) piping systems.
3. Firestop System — Installed symmetrically on both sides of wall assembly. The hourly F and T Ratings for the firestop system are equal to the hourly fire rating of the wall assembly in which it is installed. The details of the firestop system shall be as follows.
A. Fill, Void or Cavity Materials* — Wrap Strip — Nom 1/4 in. (6 mm) thick intumescent elastomeric material faced on one side with aluminum foil, supplied in 2 in. (51 mm) wide strips. Nom 2 in. (51 mm) wide strip tightly wrapped around nonmetallic pipe (foil side out) with seam butted. Wrap strip layer securely bound with steel wire or aluminum foil tape and slid into annular space approx 1-1/4 in. (32 mm) such that approx 3/4 in. (19 mm) of the wrap strip protrudes from the wall surface. 3M COMPANY — FS-195+ B. Fill, Void or Cavity Materials* — Caulk, Sealant or Putty — Min 5/8 in. (16 mm) thickness of caulk or putty applied into annular space between wrap strip and periphery of opening. A nom 1/4 in. (6 mm) diam bead of caulk or putty to be applied to the wrap strip/wall interface and to the exposed edge of the wrap strip layers approx 3/4 in. (19 mm) from the wall surface.
3M COMPANY — CP 25WB+ caulk or MP+ Stix putty, IC 15WB+ caulk, FireDam 150+ caulk or FB-3000 WT sealant. (Note:
L Ratings apply only when Type CP 25WB+ caulk or FB-3000 WT sealant is used. CP 25WB+ and FireDam 150+ not suitable for use with CPVC pipes.)
C. Foil Tape — (not shown) — Nom 4 in. (102 mm) wide, 3 mil thick aluminum tape wrapped around pipe prior to the installation of the wrap strip (Item 3A). Min of one wrap, flush with both sides of wall and proceeding outward. Tape is not required for pipes shown in Items 2A, 2B and 2C.
3B
3A
1A
3A
1B
3B
SINGLE NON-METALLIC PIPE
GYPSUM
System No. C-AJ-1429 May 18, 2005
F Rating - 2 Hr T Rating - 0 Hr
W Rating - Class I
SE
CT
IO
N
SECTION A-A
A A
REFER TO UL DIRECTORY, FIRE RESISTANCE (VOLUME 2) AND MANUFACTURER'S LITERATURE FOR
COMPLETE DETAILING.
1. Floor or Wall Assembly - Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Floor assembly may also be constructed of any min 6 in. (152 mm) thick UL Classified hollow-core Precast Concrete Units*. Wall may also be constructed of any UL Classified Concrete Blocks*. Max area of opening 240 sq in. (1548 sq cm) with a max dimension of 30 in. (762 mm).Max area of opening in floors constructed of hollow-core concrete is 49 sq in. (316 sq cm) with a max dimension of 7 in.
(178 mm).
See Concrete Blocks (CAZT) and Precast Concrete Units (CFTV) categories in Fire Resistance Directory for names of manufacturers.
2. Through Penetrant - One or more metallic pipes, conduits, tubes or flexible metal pipes installed concentrically or eccentrically within opening. Annular space between penetrants and periphery of opening shall be min of 0 in. (point contact) to max 2 in. (0 mm to max 51 mm) Space between penetrants shall be min of 1/4
in. to max 2 in. (6 mm to max 51 mm). Penetrants to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of penetrants may be used:
A. Steel Pipe - Nom 6 in. (152 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe - Nom 6 in. (152 mm) diam (or smaller) cast or ductile iron pipe.
C. Conduit - Nom 6 in. (152 mm) diam (or smaller) steel conduit or nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing.
D. Copper Tubing - Nom 3 in. (76 mm) diam (or smaller) Type L (or heavier) copper tubing.
E. Copper Pipe - Nom 3 in. (76 mm) diam (or smaller) Regular (or heavier) copper pipe.
F. Through Penetrating Product* - Flexible Metal Piping - The following types of steel flexible metal gas piping may be used:
1. Nom 2 in. (51 mm) diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removed on both sides of floor or wall assembly. OMEGA FLEX INC.
2. Nom 1 in. (25 mm) diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removed on both sides of floor or wall assembly. TITEFLEX CORP, A BUNDY CO.
3. Nom 1 in. (25 mm) diam (or smaller) steel flexible metal gas piping. Plastic covering on piping may or may not be removed on both sides of floor or wall assembly. WARD MFG INC.
3. Firestop System - The details of the firestop system shall be as follows:
A. Packing Material - Min 3 in. (76 mm) thickness of min 4 pcf (64 kg/m3) mineral wool batt insulation firmly packed into opening as a permanent form. Packing material to be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of fill material. In floors constructed of hollow-core concrete, packing material to be recessed from top and bottom surfaces of floor as required to accommodate the required thickness of fill material.
B. Fill,Void or Cavity Materials* - Caulk or Sealant - Min 1/2 in. (13 mm) thickness of caulk applied within the annulus, flush with top surface of floor or with both surfaces of wall. In floors constructed of hollow-core concrete, min 1/2 in. (13 mm) thickness of caulk applied within the annulus, flush with top and bottom surfaces of floor. Min 1/4 in. (6 mm) diam bead of caulk applied to the penetrant/concrete interface at the point contact location on the top surface of floor or both surfaces of wall or hollow-core concrete.
3M COMPANY - IC 15WB+, CP 25WB+ caulk or FB-3000 WT sealant.
(Note: W Rating applies only when FB-3000 WT is used.)
MULTIPLE METALLIC PIPE
CONCRETE - 2 HOUR
3B
3B
3A
System No. W-L-3306 F Ratings - 1 and 2 Hr
T Ratings - 0, 1/2, 3/4, 1, 1-1/2 and 2 Hr L Rating At Ambient - less than 1, 2.3, 6.2, 6.7 or 7.4 CFM/Device Module
L Rating At 400 F - less than 1, 2.3, 4.5, 5 or 6.7 CFM/Device Module
SE
CT
IO
N
SECTION A-A
A
A
REFER TO UL DIRECTORY, FIRE RESISTANCE (VOLUME 2) AND MANUFACTURER'S LITERATURE FOR
COMPLETE DETAILING.
1. Wall Assembly - The 1 or 2 hr fire rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner described within the individual U300 or U400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall incorporate the following construction features:
A. Studs - Wall framing shall consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced max 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC.
B. Gypsum Board* - Thickness, type, number of layers and fasteners as specified in the individual Wall and Partition Design. Opening in gypsum board to be max 1/4 in. (6 mm) larger then width and height dimensions of firestop device(s).
2. Firestop Device* - One, two, three, four or five firestop device modules ganged together and secured by means of integral hook and eye window attachment. Each firestop device module consists of a 4 by 4-5/8 by 14
in. (102 by 118 by 356 mm) long galv steel tube with an intumescent material lining. Series 44 device modules have spring loaded steel retainer plates. Firestop device modules to be installed in accordance with the accompanying installation instructions. The space between the firestop device module(s) and the periphery of the opening shall be min 0 in. ( 0 mm, point contact) to max 1/8 in. (3.2 mm).
SPECIFIED TECHNOLOGIES INC - EZ PATH Series 44 or Series 44+ Fire Rated Pathway
3. Cables - Within the loading area for each firestop device module, the loose or grouped cables may represent a 0 to 100 percent visual fill. Cables to be rigidly supported on both sides of the wall assembly. Any combination of the following types of cables may be used:
A. Max 400 pair No. 24 AWG (or smaller) copper conductor telecommunication cable with polyvinyl chloride (PVC) or plenum-rated jacketing and insulation.
B. Max 750 kcmil single copper conductor power cable with XLPE jacket and insulation.
C. Max 7/C No. 12 AWG copper conductor control cable with PVC or XLPE jacket and insulation.
D. Max 3/C No. 2/0 AWG metal clad or armored cable with steel or aluminum jacket.
E. Max 3/C No. 8 AWG NM cable (Romex) with PVC insulation and jacket.
F. Max four pair No. 22 AWG (or smaller) copper conductor data cable with PVC or plenum rated jacketing and insulation.
G. Coaxial cable with fluorinated ethylene or PVC insulation and jacketing having a max diam of 5/8 in. (16 mm).
H. Optical fiber cable with PVC or polyethylene (PE) jacket and insulation and having a max diam of 5/8 in.
(16 mm).
I. Optical Fiber Raceway+ - Max 1-1/2 in. (38 mm) diam (or smaller) optical fiber raceway ("innerduct") formed of either PVC or polyvinylidene fluoride (PVDF) with optical fiber cable fill. Raceways installed in accordance with the National Electrical Code (NFPA 70).
4. Fill, Void or Cavity Material* - Sealant or Putty - (Not Shown) - As an alternate to gypsum joint compound, the gap between the firestop device module and the cutout in the gypsum board may be sealed with fill material on each side of the wall assembly when four- and seven-gang steel wall plates are installed directly against the wood or steel studs.
SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant, SpecSeal LCI Sealant, SpecSeal Putty
EZ-PATH
GYPSUM
3 2
1A 1B
System No. W-L-8010 May 19, 2005
F Ratings - 1 & 2 Hr T Ratings - 1/4, 3/4, 1, 1-1/2 and 1-3/4 Hr
SE
CT
IO
N
SECTION A-A
A
A
REFER TO UL DIRECTORY, FIRE RESISTANCE (VOLUME 2) AND MANUFACTURER'S LITERATURE
FOR COMPLETE DETAILING.
1. Wall Assembly - The 1 or 2 hr fire-rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner specified in the individual U300, U400 or V400 Series Wall and Partition Designs in the UL Fire Resistance Directory and shall include the following construction features:
A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 in. by 4 in. (51 mm to max 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-5/8
in. (92 mm) wide and spaced max 24 in. (610 mm) OC.
B. Gypsum Board* - Nom 5/8 in. (16 mm) thick gypsum wallboard, as specified in the individual Wall and Partition Design. Max area of opening is 65-1/4 sq in. (421 cm2) with max dimension of 14-1/2 in. (368 mm).
The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly.
2. Through Penetrants - A max of four pipes, conduits or tubing to be installed within the opening. The space between pipes, conduits or tubing shall be min 1/2 in to max 1-5/16 in. (13 mm to max 33 mm). The space between pipes, conduits or tubing and periphery of opening shall be min 1-3/16 in. (30 mm) for uninsulated copper tubes and copper pipes (Items 2C and 2D) and 0 in. (point contact) for insulated copper tubes and copper pipes and uninsulated steel pipes and conduit (Item 2B). The space between pipes, conduits or tubing and periphery of opening shall be max 1-5/16 in. (33 mm). Pipe, conduit or tubing to be rigidly supported on both sides of floor or wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used:
A. Steel Pipe - Nom 2 in. (51 mm) diam (or smaller) Schedule 5 (or heavier) steel pipe.
B. Conduit - Nom 2 in. (51 mm) diam (or smaller) steel electrical metallic tubing or steel conduit.
C. Copper Tubing - Nom 2 in. (51 mm) diam (or smaller) Type L (or heavier) copper tubing.
D. Copper Pipe - Nom 2 in. (51 mm) diam (or smaller) Regular (or heavier) copper pipe.
When uninsulated steel pipe or conduit is used,T Rating is 3/4 hr and 1-1/2 hr for 1 and 2 hr rated assemblies, respectively. When uninsulated copper tubing or pipe is used,T Rating is 1/4 hr for both 1 and 2 hr rated assemblies.
3A. Pipe Covering* (Optional) - Nom 1 in. (25 mm) hollow cylindrical heavy density glass fiber units jacketed on the outside with an all service jacket. Longitudinal joints sealed with metal fasteners or factory-applied self-sealing lap tape. Transverse joints secured with metal fasteners or with butt tape supplied with the product. When pipe covering is used on all through penetrants,T Rating is 1 hr and 1-3/4 hr for 1 and 2 hr rated assemblies, respectively.
3B. Tube Insulation - Plastics# (Optional) - Nom 3/4 in.