This solicitation requests proposals for construction services to renovate the dental, pharmacy, and medical records departments at the Lodge Grass Health Clinic in Lodge Grass, Montana. The project involves remodeling approximately 3,200 total square feet across the three departments. Key details include a 300-day period of performance, anticipated construction value between $1,000,000 to $5,000,000, and award of a firm fixed price contract using lowest price technically acceptable evaluation. Offerors must register in SAM and check for amendments on the website, as hard copy documents will not be provided.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

IHS LODGE GRASS DENTAL, HIM, AND PHARMACY

RENOVATION

RADIATION PROTECTION

CONSTRUCTION DOCUMENTS 134900 - 1

SECTION 134900

RADIATION PROTECTION

PART 1 - GENERAL

1.1 SUMMARY

A. Section Includes:

1. Lead-lined gypsum board.

2. Informational signs.

1.2 DEFINITIONS

A. Lead Equivalence: The thickness of lead that provides the same attenuation (reduction of radiation passing through) as the material in question under the specified conditions.

1. Lead equivalence specified for materials used in diagnostic x-ray rooms is as measured at 100 kV unless otherwise indicated.

1.3 PREINSTALLATION MEETINGS

A. Preinstallation Conference: Conduct conference at Project site.

1.4 ACTION SUBMITTALS

A. Product Data: For each type of product.

1. Doors and Frames: Include construction details, material descriptions, core descriptions, fire-resistance ratings, temperature-rise ratings, and finishes.

B. Shop Drawings: Show layout of radiation-protected areas, indicating lead thickness or lead equivalence of components. Show components and installation conditions not fully dimensioned or detailed in product data.

1. Show ducts, pipes, conduit, and other objects that penetrate radiation protection; include details of penetrations.

2. Show details of joints between radiation protection materials.

3. Show details of securing lead bricks to structure.

4. Include door details, including elevations, frame dimensions and profile, and clearances and undercuts.

C. Samples: For units with factory-applied finishes.

1.5 INFORMATIONAL SUBMITTALS

A. Sample Warranty: For warranty.

RADIATION PROTECTION

CONSTRUCTION DOCUMENTS 134900 - 2

1.6 QUALITY ASSURANCE

A. Installer Qualifications: Fabricator of products.

PART 2 - PRODUCTS

2.1 SOURCE LIMITATIONS

A. Obtain each type of radiation protection product from single source from single manufacturer.

2.2 PERFORMANCE REQUIREMENTS

A. Provide materials and workmanship, including joints and fasteners, that maintain continuity of radiation protection at all points and in all directions equivalent to materials specified in thicknesses and locations indicated.

B. Materials, thicknesses, and configurations of radiation protection products indicated are based on radiation protection design prepared by Owner's radiation health physicist. This design is available to Contractor upon request. Response to Bidders’s Questions.

C. Lead-Lined Assemblies: Unless otherwise indicated, provide lead thickness in lead-lined assemblies of not less than lead thickness indicated for assemblies in which they are installed.

2.3 L EAD-LINED GYPSUM BOARD

A. 5/8-inch-thick gypsum board complying with Section 092900 "Gypsum Board," of width and length required for support spacing and to prevent cracking during handling, and with a single sheet of lead laminated to the back of the board.

1. Manufacturers and Products:

a. Mars Metal Group Inc.: Marshield Lead Lined Drywall.

b. RPP Radiation Protection Products Inc.: Lead Lined Gypsum Drywall.

c. Pitts Little Radiation Shielding: Lead Lined Drywall.

2. Lead Sheet Lining: Full width and length of board. Extend lead sheet lining 1 inch beyond one vertical edge of board.

3. Furnish 2-inch-wide lead strips for backing joints.

4. Furnish finishing materials, accessories, and trim for lead-lined gypsum board complying with Section 092900 "Gypsum Board."

2.4 INFORMATIONAL SIGNS

A. Panel Signs:

1. Color: As selected by Architect from manufacturer's full range of colors.

2. Provide copy indicated or as directed.

3. Indicate lead equivalence in millimeters and heights of radiation protection in inches.

RADIATION PROTECTION

CONSTRUCTION DOCUMENTS 134900 - 3

B. High-Pressure-Laminate Signs: High-pressure laminate engraving stock with contrasting face and core, machine engraved from master templates for accurately formed letters, numbers, and symbols.

1. Color: As selected by Architect from manufacturer's full range of colors.

2. Provide copy indicated or as directed.

3. Indicate lead equivalence in millimeters and heights of radiation protection in inches.

C. Rooms Where the Level of Protection Is Uniform Throughout: Provide one sign for each room indicating lead equivalence of partitions, ceilings, floors, doors, and other portions of radiation protection enclosure. Indicate height of radiation protection above floor, or indicate that partitions are radiation protected to full height.

D. Rooms Where the Level of Protection Is Not Uniform Throughout: Provide one sign for each room with different lead equivalences in different locations. Indicate, in tabular form, lead equivalence of each wall, partition, ceiling, floor, door, and window. Indicate height of radiation protection above floor, or indicate that partitions are radiation protected to full height. Indicate where lead equivalence changes or is not continuous.

E. Rooms Where Some Partitions Are without Radiation Protection: Provide one sign for each partition that contains radiation protection, and indicate its lead equivalence. Indicate height of radiation protection above floor, or indicate that partitions are radiation protected to full height.

F. Rooms Where Only the Door Has Radiation Protection: Provide one sign for each door indicating its lead equivalence.

G. Mounting: Provide manufacturer's standard two-faced tape.

2.5 MISCELLANEOUS MATERIALS

A. Glazing Compounds, Gaskets, and Accessories: Comply with requirements in Section 088000 "Glazing."

B. Accessories and Fasteners: Manufacturer's standard fasteners and accessories as required for installation, maintaining same lead equivalence as rest of system.

C. Asphalt Coating: Cold-applied asphalt emulsion complying with ASTM D1187/D1187M.

D. Asphalt Felt: ASTM D226/D226M.

PART 3 - EXECUTION

3.1 INSTALLATION OF LEAD-LINED GYPSUM BOARD

A. Install and finish lead-lined gypsum board in accordance with Section 092900 "Gypsum Board."

B. Install lead-lined gypsum board panels with long edge parallel to supports and lead lining facing supports. Provide blocking at end joints. Install per manufacture’s written instructions. NCRP Report No. 147 does not require additional shielding for nails or screws.

C. Install lead-lined gypsum board panels in sequence, so lead lining that extends beyond edge of gypsum board is covered by next panel installed.

RADIATION PROTECTION

CONSTRUCTION DOCUMENTS 134900 - 4

D. At joints where lead lining does not extend beyond edge of gypsum board panels, install lead strips 2 inches wide and same thickness as lead lining to face of framing and blocking. Secure lead strips with construction adhesive.

E. Provide shims at face of supports and blocking, where lead lining does not overlap, to provide a uniform plane across panel surfaces.

F. Fasten lead-lined gypsum board to framing, with steel drill screws spaced as recommended in writing by lead-lined gypsum board manufacturer.

G. Two-Layer System: Apply a facing sheet of gypsum board vertically over base sheet, using laminating adhesive recommended in writing by gypsum board manufacturer. Offset joints in finish layer from joints in base layer, and fasten at top and bottom of sheet to support finish panel until adhesive has set.

H. Openings: Extend lead-lined gypsum board into frames of openings, lapping lead lining with lead frames or frame linings at least 1 inch. Arrange board around openings, so neither horizontal nor vertical joints occur at corners of openings.

I. Install control and expansion joints where indicated, with appropriate trim accessories. Install lead strip on face of framing, extending across joint, and lap with lead lining of gypsum board.

3.2 INSTALLATION OF PENETRATING ITEMS

A. At penetrations of lead linings, provide lead shields to maintain continuity of protection.

B. Provide lead linings, sleeves, shields, and other protection in thickness of not less than that required in assembly being penetrated.

C. Secure shields at penetrations using adhesive or wire ties but not penetrating fasteners unless indicated on Drawings.

D. Outlet Boxes and Conduit: Cover or line with lead sheet lapped over adjacent lead lining at least 1 inch. Wrap conduit with lead sheet for a distance of not less than 10 inches from box.

E. Duct Openings: Unless otherwise indicated, line or wrap ducts with lead sheet for distance from partition/ceiling equal to 3 times the largest opening dimension. Lap lead sheet with adjacent lead lining at least 1 inch.

F. Piping: Unless otherwise indicated, wrap piping with lead sheet for a distance of not less than 10 inches from point of penetration.

3.3 FIELD QUALITY CONTROL

A. Testing Agency: Owner will engage a qualified testing agency to perform tests and inspections after radiology equipment has been installed and placed in operating condition.

B. Correct deficiencies in or remove and replace radiation protection that inspection reports indicate does not comply with specified requirements.

END OF SECTION 134900

PART 1 - GENERAL
1.1 SUMMARY
A. Section Includes:
1. Lead-lined gypsum board.
2. Informational signs.
1.2 DEFINITIONS
A. Lead Equivalence: The thickness of lead that provides the same attenuation (reduction of radiation passing through) as the material in question under the specified conditions.
1. Lead equivalence specified for materials used in diagnostic x-ray rooms is as measured at 100 kV unless otherwise indicated.
1.3 PREINSTALLATION MEETINGS
A. Preinstallation Conference: Conduct conference at Project site.
1.4 ACTION SUBMITTALS
A. Product Data: For each type of product.
1. Doors and Frames: Include construction details, material descriptions, core descriptions, fire-resistance ratings, temperature-rise ratings, and finishes.
B. Shop Drawings: Show layout of radiation-protected areas, indicating lead thickness or lead equivalence of components. Show components and installation conditions not fully dimensioned or detailed in product data.
1. Show ducts, pipes, conduit, and other objects that penetrate radiation protection; include details of penetrations.
2. Show details of joints between radiation protection materials.
3. Show details of securing lead bricks to structure.
4. Include door details, including elevations, frame dimensions and profile, and clearances and undercuts.

C. Samples: For units with factory-applied finishes.

1.5 INFORMATIONAL SUBMITTALS
A. Sample Warranty: For warranty.
1.6 QUALITY ASSURANCE
A. Installer Qualifications: Fabricator of products.
PART 2 - PRODUCTS
2.1 SOURCE LIMITATIONS
A. Obtain each type of radiation protection product from single source from single manufacturer.
2.2 PERFORMANCE REQUIREMENTS
A. Provide materials and workmanship, including joints and fasteners, that maintain continuity of radiation protection at all points and in all directions equivalent to materials specified in thicknesses and locations indicated.
B. Materials, thicknesses, and configurations of radiation protection products indicated are based on radiation protection design prepared by Owner's radiation health physicist. This design is available to Contractor upon request. Response to Bidders...
C. Lead-Lined Assemblies: Unless otherwise indicated, provide lead thickness in lead-lined assemblies of not less than lead thickness indicated for assemblies in which they are installed.
2.3 L EAD-LINED GYPSUM BOARD
A. 5/8-inch-thick gypsum board complying with Section 092900 "Gypsum Board," of width and length required for support spacing and to prevent cracking during handling, and with a single sheet of lead laminated to the back of the board.
1. Manufacturers and Products:
a. Mars Metal Group Inc.: Marshield Lead Lined Drywall.
b. RPP Radiation Protection Products Inc.: Lead Lined Gypsum Drywall.
c. Pitts Little Radiation Shielding: Lead Lined Drywall.
2. Lead Sheet Lining: Full width and length of board. Extend lead sheet lining 1 inch beyond one vertical edge of board.
3. Furnish 2-inch-wide lead strips for backing joints.
4. Furnish finishing materials, accessories, and trim for lead-lined gypsum board complying with Section 092900 "Gypsum Board."
2.4 INFORMATIONAL SIGNS
A. Panel Signs:
1. Color: As selected by Architect from manufacturer's full range of colors.
2. Provide copy indicated or as directed.
3. Indicate lead equivalence in millimeters and heights of radiation protection in inches.
B. High-Pressure-Laminate Signs: High-pressure laminate engraving stock with contrasting face and core, machine engraved from master templates for accurately formed letters, numbers, and symbols.
1. Color: As selected by Architect from manufacturer's full range of colors.
2. Provide copy indicated or as directed.
3. Indicate lead equivalence in millimeters and heights of radiation protection in inches.
C. Rooms Where the Level of Protection Is Uniform Throughout: Provide one sign for each room indicating lead equivalence of partitions, ceilings, floors, doors, and other portions of radiation protection enclosure. Indicate height of radiation protect...
D. Rooms Where the Level of Protection Is Not Uniform Throughout: Provide one sign for each room with different lead equivalences in different locations. Indicate, in tabular form, lead equivalence of each wall, partition, ceiling, floor, door, and wi...
E. Rooms Where Some Partitions Are without Radiation Protection: Provide one sign for each partition that contains radiation protection, and indicate its lead equivalence. Indicate height of radiation protection above floor, or indicate that partition...
F. Rooms Where Only the Door Has Radiation Protection: Provide one sign for each door indicating its lead equivalence.
G. Mounting: Provide manufacturer's standard two-faced tape.
2.5 MISCELLANEOUS MATERIALS
A. Glazing Compounds, Gaskets, and Accessories: Comply with requirements in Section 088000 "Glazing."
B. Accessories and Fasteners: Manufacturer's standard fasteners and accessories as required for installation, maintaining same lead equivalence as rest of system.
C. Asphalt Coating: Cold-applied asphalt emulsion complying with ASTM D1187/D1187M.
D. Asphalt Felt: ASTM D226/D226M.
PART 3 - EXECUTION
3.1 INSTALLATION OF LEAD-LINED GYPSUM BOARD
A. Install and finish lead-lined gypsum board in accordance with Section 092900 "Gypsum Board."
B. Install lead-lined gypsum board panels with long edge parallel to supports and lead lining facing supports. Provide blocking at end joints. Install per manufacture’s written instructions. NCRP Report No. 147 does not require additional shielding fo...
C. Install lead-lined gypsum board panels in sequence, so lead lining that extends beyond edge of gypsum board is covered by next panel installed.
D. At joints where lead lining does not extend beyond edge of gypsum board panels, install lead strips 2 inches wide and same thickness as lead lining to face of framing and blocking. Secure lead strips with construction adhesive.
E. Provide shims at face of supports and blocking, where lead lining does not overlap, to provide a uniform plane across panel surfaces.
F. Fasten lead-lined gypsum board to framing, with steel drill screws spaced as recommended in writing by lead-lined gypsum board manufacturer.
G. Two-Layer System: Apply a facing sheet of gypsum board vertically over base sheet, using laminating adhesive recommended in writing by gypsum board manufacturer. Offset joints in finish layer from joints in base layer, and fasten at top and bottom ...
H. Openings: Extend lead-lined gypsum board into frames of openings, lapping lead lining with lead frames or frame linings at least 1 inch. Arrange board around openings, so neither horizontal nor vertical joints occur at corners of openings.
I. Install control and expansion joints where indicated, with appropriate trim accessories. Install lead strip on face of framing, extending across joint, and lap with lead lining of gypsum board.
3.2 INSTALLATION OF PENETRATING ITEMS
A. At penetrations of lead linings, provide lead shields to maintain continuity of protection.
B. Provide lead linings, sleeves, shields, and other protection in thickness of not less than that required in assembly being penetrated.
C. Secure shields at penetrations using adhesive or wire ties but not penetrating fasteners unless indicated on Drawings.
D. Outlet Boxes and Conduit: Cover or line with lead sheet lapped over adjacent lead lining at least 1 inch. Wrap conduit with lead sheet for a distance of not less than 10 inches from box.
E. Duct Openings: Unless otherwise indicated, line or wrap ducts with lead sheet for distance from partition/ceiling equal to 3 times the largest opening dimension. Lap lead sheet with adjacent lead lining at least 1 inch.
F. Piping: Unless otherwise indicated, wrap piping with lead sheet for a distance of not less than 10 inches from point of penetration.
3.3 FIELD QUALITY CONTROL
A. Testing Agency: Owner will engage a qualified testing agency to perform tests and inspections after radiology equipment has been installed and placed in operating condition.
B. Correct deficiencies in or remove and replace radiation protection that inspection reports indicate does not comply with specified requirements.

File details come from the government source that posted it. Updated .