This document provides details for a federal solicitation notice seeking construction services. The Indian Health Service is soliciting proposals for a project to design and construct a 50,000 gallon elevated steel water storage tank, decommission an existing tank, and install associated piping and valves in Dustin, Oklahoma. The performance period is 270 calendar days from notice to proceed. The anticipated contract value is between $500,000 and $1,000,000. A site visit was scheduled for May 17, 2022 and the solicitation will utilize request for proposal procedures with lowest price technically acceptable evaluation. The solicitation is a 100% small business set aside with preference given to Indian Economic Enterprises. The resulting contract will be firm fixed price. The NAICS code is 237110 and interested parties should register in SAM to receive notifications and access the full solicitation.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
05/20/2022 Addendum #1 – Page 1 of 3 Dustin Water Storage Tank, 75H70122R00037
ADDENDUM NO. 1
To The
Drawings and Technical Specifications For
Elevated Steel Water Storage Tank For The
Town of Dustin, OK Solicitation Number: 75H70122R0037
Developed by the Indian Health Service
Division of Sanitation Facilities Construction 701 Market Drive
Oklahoma City, Oklahoma 73114
May 20, 2022
05/20/2022 Addendum #1 – Page 2 of 3
I. The following changes shall be made to the project drawings and specifications titled:
Elevated Steel Water Storage Tank
The Muscogee (Creek) Nation Town of Dustin
Hughes County, Oklahoma Project No. OK-18-V41
A. Plan sheet 2 of 11, General Notes, Existing Elevated Steel Tank, Paragraph 3:
1. Remove paragraph 3 in its entirety and replace with: “The existing elevated storage tank is coated with paint containing lead. Containment and disposal of all loose paint during demolition procedures is required by the contractor.”
B. Plan sheet 5 of 11, Tank Demolition Sequencing, Paragraph 4:
1. Remove Paragraph 4 in its entirety and replace with: “Decommission and dismantle existing water storage tank. Tank demolition plan must be submitted for approval prior to work beginning.”
C. Section 33 16 16.0001 Multi-Column Elevated Water Storage Tank Demolition:
1. Remove in its entirety the following from Section 1.02 “Measurement and
Payment” subsection A 2 b 1:
b. Lead-based paint abatement:
1) Contractor shall provide certified abatement specialist and approved lead abatement remediation and abatement plan to Owner.
D. Section 33 16 16.0001 Multi-Column Elevated Water Storage Tank Demolition:
1. Remove in its entirety the following from Section 1.04 “Submittals” subsection(s) A.4 and A.5:
4. Name and contact information of certified abatement specialist.
5. Written lead abatement remediation plan for the containment of loose, lead-based paint.
E. Section 33 16 16.0001 Multi-Column Elevated Water Storage Tank Demolition:
05/20/2022 Addendum #1 – Page 3 of 3
1. Remove in its entirety Section 3.04 C and replace with: Existing water tower coatings contain lead. The Contractor is responsible for loose paint containment and proper disposal of structure.
F. Section 33 16 16.0001 Multi-Column Elevated Water Storage Tank Demolition:
1. Remove in its entirety Section 3.04 D and replace with: At no time shall loose paint be deposited and left on the existing ground surface, adjacent structures, and/or other objects. Paint shall be contained by using a tarp collection system. The collection system shall be applied on the surface of the ground or any other objects that require protection during cutting and dismantling operations. Collection system shall prevent paint particles from becoming airborne and escaping the jobsite.
G. Section 33 16 16.0001 Multi-Column Elevated Water Storage Tank Demolition:
2. Remove in its entirety Section 3.04 E and replace with: Remove and dispose of any loose paint from the site as a result of the demolition operations.