751-25468.JLM - Drwg File 4 of 4 - 2026 06 15.pdf
PDF 2 MB Posted
- Solicitation number
- RFQ 171 260000000356 3
- Issued by
- Allegan County, Michigan
About this file
This is a drawing file (Drawing File 4 of 4) for the Saugatuck Dunes State Park Storage Building project located in Laketown Township, Allegan County, Michigan, prepared for the State of Michigan Department of Technology, Management and Budget, State Facilities Administration, Design and Construction Division. The project file number is 751/25468.JLM, issued for bid and construction on June 15, 2026. The drawings include comprehensive plumbing, mechanical, and electrical systems for a new storage building facility. The plumbing plans show a complete system including water supply (via well system), hot and cold water distribution, sanitary and storm drainage, with fixtures including one water closet (ADA compliant), one lavatory, one service sink, and one floor drain. The mechanical plans detail HVAC systems including two wall-mounted ductless cooling units (Daikin), one air-source heat pump, toilet exhaust ventilation, electric baseboard heating, and a radiant ceiling heating panel. The electrical plans specify a 150-amp, single-phase service panel with 27 branch circuits, exterior and interior lighting with LED fixtures, emergency lighting, receptacles throughout the facility, and connections for all mechanical equipment.
The project documentation establishes detailed specifications for materials and equipment selections, including acceptable manufacturers and equivalents for all fixtures and equipment. Plumbing equipment includes an A.O. Smith water heater (1650 watts, 8 GPH), Zurn water closet and fixtures, and Elkay sink with specific valve requirements. Mechanical equipment incorporates Daikin ductless units with SEER2 ratings of 21 and Greenheck exhaust fans. Electrical specifications require compliance with local, state, and national codes, with particular attention to grounding requirements (25-ohm resistance or less), surge protection, and emergency battery lighting systems. The contractor must coordinate all trades to avoid conflicts between ductwork, piping, electrical conduit, and structural elements, verify field conditions prior to rough-in, submit detailed shop drawings, and perform testing and balancing. General notes emphasize compliance with Michigan codes, field coordination of actual conditions versus diagrammatic layouts, and that the contractor is responsible for determining equipment lead times and ensuring timely delivery to meet project deadlines.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2x4 V.T.R.
MEZZANINE
GARAGE BELOW
WC-1
L-1
S-1
FD-1 FD-1
2" V
1" CW
¾" COLD WATER ABOVE
¾" HOT WATER PIPING
2" V UP
SC-1
FCO
2" V
2" V
2" V
1" DOMESTIC
WATER SERVICE
WELL SYSTEM
BY OTHER
1"
GARAGE
BREAK ROOM
OFFICE
CLO.
ADA/BF UNISEX TLT.
WH
SEE CIVIL FOR
CONTINUATION
SEE CIVIL FOR
CONTINUATION
1"
4" SAN
4" SAN
4" SAN
4" SAN
4" SAN
1" CW UP
1" INCOMING
WATER SERVICE
9 6
1"
GARAGE
BREAK ROOM
OFFICE
CLO.
3ADA/BF UNISEX TLT.
DRAIN DOWN - SEE
SHEET P2.0 FOR DETAIL
P L
U R
I B
U E
S U
N U
M
C I
R C
U M
S P
I C
E
S I
Q U
E R
E I
S P
E N
I N
S U
L A
M A
M
OE
N A
M
9711 Valparaiso Drive
221 N. LaSalle Street
(219)924-8400
Munster, IN 46321
Chicago, IL 60601 www.milliesengineeringgroup.com
MILLIES
ENGINEERING GROUP
820 Monroe Ave NW Grand Rapids, MI 49503
Copyright © 2026 Millies Engineering Group
S th S tr e e t, P O
B o x
O s h te m o
M
I
(2
-8
S N
A N
O -1
F
IL
E N
O
.J
L M
S H
E E
T
ID
E N
T
IF
IC
A
T
IO
N N
O
IS
S
U E
D F
O R
D A
T E
C o p y ri g h t
S c h le y N el so n A rc h it e ct s, I n c.
C O
N S
T R
U C
T
IO
N
F
IN
A L
R E
C O
R D
P R
E L
IM
R
E V
IE
W
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N t h
A v e
S a u g a t u c k
D u n e s M I
S a u ga tu ck
D u n es
S ta te
P a r k
S to r a ge
B u il d in g
D ep a r tm en t o f N a tu r a l R es o u r ce s
L a k e t o w n
T o w n s h ip A ll e g a n
C o u n t y M ic h ig a n
P1.0
-1
-2
F O
R B
ID
C O
N S
T R
1/4" = 1'-0"
MEZZANINE PLAN - PLUMBING
1/4" = 1'-0"
FLOOR PLAN - PLUMBING
1/4" = 1'-0"
UNDERFLOOR PLAN - PLUMBING
1. ½" COLD WATER AND 1½" VENT DOWN AND ½"
HOT WATER UP TO LAVATORY.
2. ½" COLD WATER AND 2" VENT DOWN TO
WATER CLOSET.
3. ½" COLD WATER AND 1½" VENT DOWN AND ½"
HOT WATER UP TO SINK.
4. 1½" SANITARY UP TO LAVATORY.
5. 4" SANITARY UP TO WATER CLOSET.
6. 2" SANITARY UP TO SINK.
7. 4" SANITARY UP TO FLOOR DRAIN.
8. ¾" COLD WATER DOWN TO SILL COCK.
9. 4" SANITARY UP TO FLOOR CLEANOUT.
SHEET NOTES
A. WORK SHALL COMPLY WITH LOCAL, MUNICIPAL, AND STATE PLUMBING CODES.
B. THE SCOPE OF WORK SPECIFIED HEREIN AND IN THE SPECIFICATIONS SHALL BE COORDINATED
WITH THE CONSTRUCTION MANAGER - REFER TO THE SCOPE OF WORK FOR EACH TRADE. ANY
DISCREPANCIES BETWEEN THE CONSTRUCTION DOCUMENTS AND CONSTRUCTION MANAGERS
SCOPE SHALL BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER FOR
CLARIFICATION. THE ARCHITECT/ENGINEER'S DECISION SHALL BE FINAL.
C. LAYOUT IS DIAGRAMMATIC. INSTALL PIPING AND EQUIPMENT TO MEET ACTUAL FIELD
CONDITIONS. REVIEW PROJECT SPECIFICATIONS BEFORE STARTING ANY WORK. SUBMIT SHOP
DRAWINGS OF WORK AS PER SPECIFICATIONS.
D. LAYOUT WORK TO AVOID CONFLICTS BETWEEN DUCTWORK, LIGHTING, CEILINGS, PIPING AND
BUILDING STRUCTURE.
E. VERIFY LOCATION AND ELEVATION OF PLUMBING EQUIPMENT, FIXTURES, PIPING, PANELS, ETC.
EXPOSED WITHIN OCCUPIED SPACES BEFORE THE START OF ANY ROUGH-IN OR INSTALLATION.
F. COORDINATE EQUIPMENT ELECTRICAL REQUIREMENTS (VOLTAGES, PHASE, LOAD, ETC.)
BEFORE ORDERING ANY EQUIPMENT.
G. COORDINATE VENT THROUGH ROOF LOCATIONS WITH OUTDOOR AIR INTAKE LOCATIONS TO
MAINTAIN A MINIMUM SEPARATION OF TEN FEET.
H. PROVIDE A WATERTIGHT SHEET METAL DRIP PAN OVER ELECTRICAL EQUIPMENT INSTALLED
UNDER OR NEAR PIPING SYSTEMS. DRIP PAN TO EXTEND MINIMUM 3" OVER FRONT AND SIDES
OF ELECTRICAL EQUIPMENT AND BE PITCHED AT A MINIMUM 30° ANGLE. SEAL DRIP PAN
WATERTIGHT TO WALL.
I. PROVIDE ROUGH-IN AND FINAL CONNECTIONS TO PLUMBING EQUIPMENT AND FIXTURES. SET FIXTURES/EQUIPMENT AND FURNISH AND INSTALL NECESSARY FITTINGS, TRAPS, STOPS, ETC.
AS REQUIRED.
J. PROVIDE ALL ROUGH-IN AND FINAL SERVICES AND CONNECT ALL WATER LINES, WASTE LINES, INDIRECT PIPING, ETC. FOR FIXTURES. PROVIDE ALL VALVES, STOPS, TRAPS, AND PRESSURE
REGULATORS NECESSARY TO CONNECT LINES.
K. PLUMBING PIPING ROUTING TO BE FIELD COORDINATED WITH NEW HVAC DUCTWORK, HVAC
PIPING, ELECTRICAL AND STRUCTURE TO ENSURE NO CONFLICTS WILL OCCUR DUE TO
INTERFERENCE.
L. PIPING, EQUIPMENT, ETC. SHALL NOT BE SUPPORTED FROM THE BOTTOM CHORD OF
ENGINEERED JOISTS WITHOUT WRITTEN APPROVAL FROM THE STRUCTURAL ENGINEER.
M. INVERT ELEVATIONS SHALL BE FIELD COORDINATED WITH FINAL GRADING PLANS TO ENSURE
PROPER INSTALLATION.
N. REFER TO ARCHITECTURAL INTERIOR ELEVATIONS FOR FINAL MOUNTING HEIGHTS OF
PLUMBING FIXTURES.
O. PROTECT NEW AND EXISTING DRAIN OPENINGS AND SANITARY LINES DURING CONSTRUCTION
TO PREVENT BLOCKAGE. ROD-OUT EXISTING SANITARY PIPING. PIPING SHALL BE FREE OF
BLOCKAGE.
P. REPAIR AND/OR REPLACE DAMAGED PIPE INSULATION THAT OCCURS AS THE RESULT OF THIS
CONSTRUCTION.
Q. PRIME AND PAINT EXPOSED PIPING IN FINISHED AREAS IN COLOR AS SELECTED BY OWNERS
REPRESENTATIVE.
GENERAL NOTES
ABBREVIATIONS LIST
A AIR
AD AREA DRAIN
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
CB CATCH BASIN
CI CAST IRON
CO CLEANOUT
CTE CONNECT TO EXISTING
CW COLD WATER
DBP DOMESTIC BOOSTER PUMP
DI DUR-IRON
DN DOWN
DS DOWNSPOUT
DT DRAIN TILE
EX. EXISTING
FCO FLOOR CLEANOUT
FD FLOOR DRAIN
FIN. FL. FINISHED FLOOR
FIN, GR. FINISHED GRADE
HB HOSE BIBB
HW HOT WATER
IM ICEMAKER VALVE BOX
INV. EL. INVERT ELEVATION
IWH INSTANTANEOUS WATER HEATER
L LAVATORY
MB MOP BASIN
NIC NOT IN CONTRACT
OSD OPEN SITE DRAIN
PRV PRESSURE REDUCING VALVE
PS PLUMBING STACK
S SINK
SC SILL COCK
TW TEMPERED WATER
V VENT
VIT VITRIFIED HUB TILE
VTR VENT THROUGH ROOF
WC WATER CLOSET
WCO WALL CLEANOUT
WH WATER HEATER
WS WATER SOFTENER
YCO YARD CLEANOUT
YH YARD HYDRANT
SYMBOL LIST
DESCRIPTIONSYMBOL
PIPE PITCHED DOWN IN DIRECTION OF FLOW
CHECK VALVE
DIRECTION OF FLOW
SHUT-OFF VALVE
RELIEF VALVE
HOSE BIBB/SILL COCK
SHEET NOTE TAG
MECHANICAL EQUIPMENT TAG
DRAIN TILE PIPING
TEMPERED WATER PIPING
COMPRESSED AIR PIPINGCA
TW
DT
VENT PIPING
UNDERGROUND STORM SEWER
HOT WATER PIPING
COLD WATER PIPING
HOT WATER RECIRCULATION PIPING
UNDERGROUND SANITARY SEWER
OVERHEAD STORM PIPING
OVERHEAD SANITARY PIPING
ST
T THERMOMETER
P PRESSURE GAUGE
BALANCING COCK/ MANUAL
FLOW CONTROL VALVE
PIPE DOWN
PIPE UP
SAN
V
ST
SAN
NEW PIPING
SHUT-OFF VALVE
TEMPERED WATER VALVE
DIAGRAM
FAUCET
⅜" CW PIPING
⅜"x½" VALVE
⅜" CW PIPING⅜" HW PIPING
TEMPERED
WATER VALVE-
COMPLY WITH
ASSE 1070
⅜" HW PIPING
⅜"x½" VALVE
⅜"
NTS
LAVATORY TEMPERED WATER
VALVE DIAGRAM
NTS
⅜"
FAUCET
⅜" CW PIPING
⅜"x½" VALVE
⅜" CW PIPING⅜" HW PIPING
TEMPERED
WATER VALVE-
COMPLY WITH
ASSE 1070
⅜" HW PIPING
⅜"x½" VALVE
FIRST FLOOR
FLOOR
MEZZANINE
FLOOR
MEZZANINE
ROOF
FIRST FLOOR
FLOOR
MEZZANINE
FLOOR
MEZZANINE
ROOF
RISER DIAGRAM
F C
O
S -1
L -1
F D
-1
F D
-1
W C
-1
W C
-1
L -1
S -1
4"
2"
1½"
1½"
4"
2"
4"
2"
4"
2"
2x4 INCR VTR
2" 2" 2"
2"
WELL SYSTEM
BY OTHERS
¾"
¾"
¾"
½"½"
1"
1" ¾"
1"1"
¾"
¾"½"
½" ½"
½"
WATER HEATER
- SEE DETAIL ON
SHEET P2.0
S C
-1
1½"
SEE CIVIL FOR
CONTINUATION
SEE CIVIL FOR
CONTINUATION
DRAIN DOWN
VALVE - NC
TO FD
TO FD
COMPRESSED AIR
BLOW DOWN VALVE
FOR WINTER DRAIN
DOWN
COMPRESSED AIR BLOW
DOWN VALVE FOR
WINTER DRAIN DOWN
WH-1
WATER HEATER DIAGRAM
THERMOMETER
DRAIN VALVE-ROUTE TO FLOOR DRAIN
RELIEF PIPE-FULL SIZE OF DISCHARGE
OPENING - ROUTE TO FLOOR DRAIN
A.S.M.E. APPROVED TEMPERATURE &
PRESSURE RELIEF VALVE
AMTROL #ST-5 THERM-X-TROL
THERMAL EXPANSION TANK
HOT WATER
COLD WATER
WATER HEATER TO BE MOUNTED
ON "HOLDRITE #40-SWHP-WM"
SHELF LOCATED AS HIGH AS
POSSIBLE ABOVE FLOOR
WALL
ROUTE PIPING FROM PAN DRAIN
DOWN TO FLOOR DRAIN
VACUUM RELIEF VALVE
HEAT TRAP
HEAT TRAP
EXTERIOR DRAIN DOWN DETAIL
BUTT WELD
BUILDING SHUT-OFF
& CURB BOX (BRASS)
NEW UNDERGROUND
WATER SERVICE
MINIMUM 5' COVER
WALL ANCHOR AND THRUST
RESTRAINT REQUIRED AT
ALL BUILDING CONNECTIONS
FINISH GRADE LINE
CONCRETE PAD
9"x21"x4" THICK
½" COPPER CAPPED AIR BLOW-OFF
LINE WITH AIR SNIFTER.
VALVE IN 5¼" C.I. UPPER SECTION.
VALVE BOX WITH COVER.
CURB BOX
EXTERIOR
BUILDING WALL
P L
U R
I B
U E
S U
N U
M
C I
R C
U M
S P
I C
E
S I
Q U
E R
E I
S P
E N
I N
S U
L A
M A
M
OE
N A
M
9711 Valparaiso Drive
221 N. LaSalle Street
(219)924-8400
Munster, IN 46321
Chicago, IL 60601 www.milliesengineeringgroup.com
MILLIES
ENGINEERING GROUP
820 Monroe Ave NW Grand Rapids, MI 49503
Copyright © 2026 Millies Engineering Group
S th S tr e e t, P O
B o x
O s h te m o
M
I
(2
-8
S N
A N
O -1
F
IL
E N
O
.J
L M
S H
E E
T
ID
E N
T
IF
IC
A
T
IO
N N
O
IS
S
U E
D F
O R
D A
T E
C o p y ri g h t
S c h le y N el so n A rc h it e ct s, I n c.
C O
N S
T R
U C
T
IO
N
F
IN
A L
R E
C O
R D
P R
E L
IM
R
E V
IE
W
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N t h
A v e
S a u g a t u c k
D u n e s M I
S a u ga tu ck
D u n es
S ta te
P a r k
S to r a ge
B u il d in g
D ep a r tm en t o f N a tu r a l R es o u r ce s
L a k e t o w n
T o w n s h ip A ll e g a n
C o u n t y M ic h ig a n
P2.0
-1
-2
F O
R B
ID
C O
N S
T R
PLUMBING EQUIPMENT SCHEDULE
TAG TYPE DESCRIPTION MANUFACTURER MODEL NO. ACCEPTABLE MANUF. ACCESSORIES/REMARKS (SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION)
ELECTRICAL DATA
LOAD
VOLT PHASE HZ HP MCA FLA MOCP
WH-1 WATER HEATER 1650 WATT, 8 GPH @ 90F., 6 GAL. STORAGE A.O. SMITH EJC-6 NOTE #1 TEMP. RELIEF VALVE, DRAIN VALVE PIPED TO SERVICE SINK 13.75 120 V 1 60 Hz
PLUMBING FIXTURE SCHEDULE
TAG
FIXTURE / EQUIPMENT
TYPE
FIXTURE / EQUIPMENT FIXTURE / EQUIPMENT DATA FIXTURE VALVE / FAUCET DATA TEMPERED WATER VALVES
ACCESSORIES/REMARKS (SEE SPECIFICATIONS FOR ADDITIONAL INFORMATION)DESCRIPTION MANUFACTURER AND MODEL NO. ACCEPTABLE MANUF. TYPE MANUFACTURER AND MODEL NO. ACCEPTABLE MANUF. MANUFACTURER AND MODEL NO. ACCEPTABLE MANUF.
WC-1
WATER CLOSET VITREOUS CHINA, FLOOR MOUNTED, TANK TYPE, ADA, 1.6 GPF ZURN Z5551-K NOTE #1 - - - - BEMIS 1500EC-000
L-1 LAVATORY VITREOUS CHINA, WALL MOUNTED, 20"x18" ADA ZURN Z5344 NOTE #1 0.5 GPM-SINGLE LEVER HANDLE, 4"
CENTERS
ZURN Z7440-XL-FC NOTE #4 BRADLEY S59-4000A NOTE #6 MCGUIRE PW2150WC 1-1/2" PROWRAP, MCQUIRE LFH2167CCLK , LAVATORY CHAIR
CARRIER EQUIVILENT TO ZURN Z1231EZ
S-1 SINK 1-COMPARTMENT STAINLESS STEEL SINK, 15"x15"x6-1/8" ELKAY BLR 15601 NOTE #2 TWO HANDLE, 4" GOOSENECK, 1.5
GPM
ELKAY LK406GN04T4 NOTE #5 BRADLEY S59-4000A NOTE #6 ELKAY LK35 STRAINER, MCGUIRE B8912CSDF P-TRAP, MCGUIRE LFH2167CCLK
FD-1
FLOOR DRAIN CAST IRON BODY, ADJUSTABLE 6"x6" NICKEL BRONZE TOP ZURN Z415S-VP NOTE #3 - - - - VANDALPROOF SCREWS, ZURN Z1072 BARRIER TRAP SEAL
NOTE 1: AMERICAN STANDARD, KOHLER, ZURN, SLOAN, TOTO
NOTE 2: ELKAY, JUST, KOHLER, ACORN, FRANKE
NOTE 3: ZURN, JOSAM, J.R. SMITH, MIFAB, WADE, WATTS
NOTE 4: ZURN, DELTA, SLOAN, CHICAGO FAUCET CO., AMERICAN STANDARD, KOHLER, T&S BRASS
NOTE 5: ELKAY, ZURN, DELTA, SLOAN, CHICAGO FAUCET CO., AMERICAN STANDARD, KOHLER, T&S BRASS
NOTE 6: LEONARD, POWERS, LAWLER, BRADLEY, SYMMONS
NOTE 1: STATE, LOCHINVAR, A.O. SMITH, BOCK, BRADFORD WHITE
T
T
T
T
T
MOUNTED ON WALL
MIN. 24" A.F.G.
TERMINATE ¾" PVC
CD IN FLOOR DRAIN
6"ø EXH
6"/6" EXH DN.
EBB
EBB
RCP
1TEF
BJA
UD
GARAGE
BREAK ROOM
OFFICE
ADA/BF UNISEX TLT.
CLO.
REFRIGERANT PIPING THRU
WALL 7'-2" A.F.F. SLEEVE AND
SEAL WALL PENETRATION
WEATHERTIGHT.
TERMINATE 6"Ø EXH DUCT
WITH GREENHECK MODEL#
WC-6 HOODED WALL CAP
OR EQUIVALENT
6"ø
EXH
HP
1AC
AC
EBB
3/4"
REFRIGERANT AND ¾" CD
PIPING TO AC-1
3/4"
CD
C D
REFRIGERANT AND ¾" CD
PIPING TO AC-2
L /S
L/S
P L
U R
I B
U E
S U
N U
M
C I
R C
U M
S P
I C
E
S I
Q U
E R
E I
S P
E N
I N
S U
L A
M A
M
OE
N A
M
9711 Valparaiso Drive
221 N. LaSalle Street
(219)924-8400
Munster, IN 46321
Chicago, IL 60601 www.milliesengineeringgroup.com
MILLIES
ENGINEERING GROUP
820 Monroe Ave NW Grand Rapids, MI 49503
Copyright © 2026 Millies Engineering Group
S th S tr e e t, P O
B o x
O s h te m o
M
I
(2
-8
S N
A N
O -1
F
IL
E N
O
.J
L M
S H
E E
T
ID
E N
T
IF
IC
A
T
IO
N N
O
IS
S
U E
D F
O R
D A
T E
C o p y ri g h t
S c h le y N el so n A rc h it e ct s, I n c.
C O
N S
T R
U C
T
IO
N
F
IN
A L
R E
C O
R D
P R
E L
IM
R
E V
IE
W
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N t h
A v e
S a u g a t u c k
D u n e s M I
S a u ga tu ck
D u n es
S ta te
P a r k
S to r a ge
B u il d in g
D ep a r tm en t o f N a tu r a l R es o u r ce s
L a k e t o w n
T o w n s h ip A ll e g a n
C o u n t y M ic h ig a n
M1.0
-1
-2
F O
R B
ID
C O
N S
T R
1/4" = 1'-0"
FLOOR PLAN - MECHANICAL HVAC
NOTE:
NATURAL VENTILATION - MINIMUM OPERABLE WINDOW
AREA IN BREAKROOM: 5.68 SQ.FT.
NATURAL VENTILATION - MINIMUM OPERABLE WINDOW
AREAMINIMUM WINDOW AREA IN OFFICE: 2 SQ.FT.
A. WORK SHALL COMPLY WITH LOCAL, MUNICIPAL, AND STATE HVAC CODES.
B. LAYOUT IS DIAGRAMMATIC AND CONTRACTOR SHALL INSTALL DUCTWORK, PIPING AND
EQUIPMENT TO MEET ACTUAL FIELD CONDITIONS. REVIEW PROJECT SPECIFICATIONS
BEFORE STARTING ANY WORK. SUBMIT SHOP DRAWINGS OF WORK AS PER
SPECIFICATIONS.
C. LAYOUT WORK TO AVOID CONFLICTS BETWEEN DUCTWORK, LIGHTING, CEILINGS, PIPING
AND BUILDING STRUCTURE.
D. COORDINATE EQUIPMENT ELECTRICAL REQUIREMENTS (VOLTAGES, PHASE, LOAD, ETC.)
BEFORE ORDERING ANY EQUIPMENT.
E. COORDINATE EXACT LOCATION OF CEILING REGISTERS, GRILLES AND DIFFUSERS WITH
LIGHTING LAYOUT, SPRINKLER HEADS, AND CEILING GRID. SEE ARCHITECTURAL
REFLECTED CEILING PLAN. VERIFY EXACT LOCATION IN FIELD PRIOR TO INSTALLATION.
VERIFY CEILING STYLES AND TYPES BEFORE ORDERING REGISTERS, GRILLES AND
DIFFUSERS. PROVIDE APPROPRIATE FRAME STYLES AS REQUIRED TO MATCH CEILING
STYLE AND TYPES. SET ADJUSTABLE BLADES AS REQUIRED FOR OPTIMUM AIR PATTERN
AND TO PREVENT DRAFTS. THE MINIMUM DISTANCE BETWEEN SUPPLY
DIFFUSERS/REGISTERS AND SMOKE OR HEAT DETECTORS IS TO BE A MINIMUM OF 3‘.
COORDINATE WITH FIRE ALARM SYSTEM AS REQUIRED.
F. ROUTE DUCTWORK AS HIGH AS POSSIBLE TO AVOID CONFLICTS WITH OTHER TRADES.
ROUTE DUCTWORK BETWEEN AND THROUGH JOIST SPACES AND BETWEEN LIGHT
FIXTURES AS REQUIRED. VERIFY CONDITIONS AND DUCTWORK ROUTING IN FIELD PRIOR
TO INSTALLATION.
G. DUCTWORK, PIPING, EQUIPMENT, ETC. SHALL NOT BE SUPPORTED FROM THE BOTTOM
CHORD OF ENGINEERED JOISTS WITHOUT WRITTEN APPROVAL FROM THE STRUCTURAL
ENGINEER.
H. PROVIDE MANUAL BALANCING DAMPERS AT EACH LOW PRESSURE SUPPLY AIR, RETURN
AIR AND EXHAUST DUCTWORK TAKE-OFF INCLUDING TAKEOFFS TO EACH AIR
DISTRIBUTION DEVICE. DAMPERS SHALL HAVE LOCKING QUADRANT REGULATORS WITH
SPRING LOADED END BEARING. INSTALLATION SHALL BE RATTLE FREE. BE
RESPONSIBLE FOR LOCATING BALANCING DEVICES AND COORDINATE LOCATIONS FOR
TESTING AND BALANCING.
I. BAROMETRIC RELIEF DAMPERS TO BE EQUIVALENT TO AMERICAN WARMING MODEL
BD-52 LOW LEAKAGE DAMPERS SET AT 0.05” SP.
L. VERIFY EXACT THERMOSTAT AND SENSOR LOCATIONS IN FIELD PRIOR TO ROUGH-IN OR
INSTALLATION. CONTROL WIRING TO BE ROUTED IN CONDUIT.
M. REFRIGERANT PIPING INSTALLATION INCLUDING SIZING IS TO BE AS PER
MANUFACTURER'S RECOMMENDATIONS FOR THE ACTUAL FIELD ROUTING AND FOR THE
EQUIPMENT PROVIDED. PROVIDE ALL SUCTION LINE TRAPS, SOLENOID VALVES, SIGHT
GLASSES AND FILTER/DRIERS AS PER EQUIPMENT MANUFACTURER'S
RECOMMENDATIONS.
N. REPAIR AND/OR REPLACE DAMAGED PIPE INSULATION THAT OCCURS AS THE RESULT
OF THIS CONSTRUCTION.
O. PROVIDE CONCRETE EQUIPMENT PADS FOR EQUIPMENT INDICATED ON DRAWINGS.
COORDINATE LOCATIONS BEFORE INSTALLATION. PADS ARE TO BE DESIGNED WITH
REINFORCEMENT TO HANDLE THE WEIGHT OF THE EQUIPMENT BEING SUPPORTED.
EXTERIOR CONCRETE PADS TO BE PROVIDED WITH FROST WALLS (MINIMUM OF 48”
BELOW GRADE).
P. PROVIDE CONDENSATE PUMPS, RECEIVERS, PIPING AND ELECTRICAL CONNECTIONS AS
REQUIRED AT EQUIPMENT WHERE EQUIPMENT DRAINS CANNOT BE DRAINED BY
GRAVITY DUE TO FIELD CONDITIONS.
Q. PROVIDE APPURTENANCES (I.E. EXPANSION COMPENSATORS, FLEXIBLE CONNECTIONS,
EXPANSION LOOPS, JUNCTION BOXES, ETC.) NECESSARY TO CROSS EXPANSION JOINTS
IN BUILDING CONSTRUCTION WITH CONDUIT, PIPING, DUCTWORK, ETC. REFER TO
ARCHITECTURAL DRAWINGS FOR LOCATION AND QUANTITY OF EXPANSION JOINTS.
R. PROVIDE RELIEF VENT PIPING FOR REFRIGERATION EQUIPMENT. PIPING TO BE ROUTED
TO THE EXTERIOR OF BUILDING AS REQUIRED. MULTIPLE RELIEFS ARE TO BE PIPED
INDIVIDUALLY, NOT GROUPED TOGETHER IN A COMMON HEADER. THE PIPING IS TO BE
SAME SIZE AS RELIEF CONNECTION TO EQUIPMENT. TERMINATION LOCATION TO MEET
CODE REQUIREMENTS AND BE APPROVED BY ARCHITECT.
S. PIPING ENCLOSURES SHALL BE PROVIDED FOR HVAC PIPING (INCLUDING CONDENSATE)
THAT IS TO BE MOUNTED BELOW 9'-0" ABOVE FINISHED FLOOR. SUBMIT DETAILED SHOP
DRAWINGS PRIOR TO FABRICATION. ENCLOSURES TO BE ONE (1) PIECE 14 GAUGE
STEEL WITH ONE (1) PRIME COAT AND TWO (2) FINISH COATS OF ENAMEL; CUSTOM
COLOR AS SELECTED BY ARCHITECT. PROPERLY SECURE TO EXISTING CONSTRUCTION
WITH CONCEALED FASTENERS AS REQUIRED TO PROVIDE A COMPLETE AND PROPER
FINISHED INSTALLATION. ENCLOSURES SHALL BE REMOVABLE.
GENERAL NOTES
AD AUTOMATIC (MOTORIZED) DAMPER
AC AIR CONDITIONING
AFF ABOVE FINISHED FLOOR
AH AIR HANDLING UNIT
BJA BETWEEN JOIST ABOVE
BO BLANK OFF
BRD BAROMETRIC RELIEF DAMPER
CAI COMBUSTION AIR INTAKE
CAT CONDENSING AIR TEMPERATURE
CD CONDENSATE DRAIN
CH CABINET HEATER
CTE CONNECT TO EXISTING
CU CONDENSING UNIT
CW COLD WATER
DN. DOWN
DS DISCONNECT SWITCH
DV DRAIN VALVE
DX DIRECT EXPANSION
EAT ENTERING AIR TEMPERATURE
EC ELECTRICAL CONTRACTOR
EDB ENTERING DRY BULB TEMPERATURE
ESP EXTERNAL STATIC PRESSURE
EWB ENTERING WET BULB TEMPERATURE
EWT ENTERING WATER TEMPERATURE
EX EXISTING
EXH EXHAUST
F FURNACE
FC FLEXIBLE CONNECTION
FD FIRE DAMPER
FPM FEET PER MINUTE
FMS FACILITY MANAGEMENT SYSTEM
FVNR FULL VOLTAGE, NON-REVERSING STARTER
G NATURAL GAS
GPM GALLONS PER MINUTE
HP HORSE POWER
HZ HERTZ
IH OUTSIDE AIR INTAKE HOOD
L LIQUID
LAT LEAVING AIR TEMPERATURE
LB/HR POUNDS PER HOUR
LDB LEAVING DRY BULB TEMPERATURE
LV LOUVER
LWB LEAVING WET BULB TEMPERATURE
LWT LEAVING WATER TEMPERATURE
M/A MIXED AIR
MBH 1,000 BTU/HOUR
MC MECHANICAL CONTRACTOR
MD MANUAL DAMPER
MOD MODULATING
MV MANUAL AIR VENT
NC NORMALLY CLOSED
NK NECK
NO NORMALLY OPEN
NTS NOT TO SCALE
O/A OUTSIDE AIR
OAI OUTSIDE AIR INTAKE
OBD OPPOSED BLADE DAMPER
PC PLUMBING CONTRACTOR
PS PRESSURE SENSOR
PSI POUNDS PER SQUARE INCH
R/A RETURN AIR
RH RELATIVE HUMIDITY
RPM REVOLUTIONS PER MINUTE
S SUCTION
S/A SUPPLY AIR
SFD SMOKE-FIRE DAMPER
SHC SENSIBLE HEAT CAPACITY
SM SMOKE
TC TEMPERATURE CONTROL
TEF TOILET EXHAUST FAN
TJA THRU JOIST ABOVE
TSP TOTAL STATIC PRESSURE
TYP TYPICAL
UD UNDERCUT DOOR
UH UNIT HEATER
V VENT
VAV VARIABLE AIR VOLUME
VFD VARIABLE FREQUENCY DRIVE
WC WATER COLUMN
WPD WATER PRESSURE DROP
ABBREVIATIONS LISTSYMBOL LIST
DESCRIPTIONSYMBOL
UNION
PIPE TURNED DOWN
PIPE TURNED UP
SHUT-OFF VALVE
PIPING SLOPED DOWN
COLD WATER
CONDENSATE DRAINCD
CW
DESCRIPTIONSYMBOL
PIPE EXPANSION ANCHOR
AN
PIPE EXPANSION GUIDE
EC
REFRIGERANT PIPE
RETURN OR EXHAUST REGISTER
SUPPLY AIR DIFFUSER
SUPPLY OR OUTSIDE AIR DUCT DOWN
SUPPLY OR OUTSIDE AIR DUCT UP
RETURN OR EXHAUST OR RELIEF DUCT DOWN
RETURN OR EXHAUST OR RELIEF DUCT UP
AUTOMATIC (MOTORIZED) DAMPER
DUCT TRANSITION
NEW DUCTWORK
SQUARE TO ROUND TRANSITION
FLEXIBLE DUCTWORK
FIRE DAMPER
SMOKE DAMPER
FIRE/SMOKE DAMPER
FD
L/S
DUCTWORK INSULATION
DUCTWORK LINING
SM
SFD
AD
FLEXIBLE CONNECTION
SUPPLY AIR DIFFUSER
(SHADING INDICATES BLANK-OFF SIDE)
SHEET NOTE
SEE SCHEDULES
MOTOR STARTERMS
THERMOSTAT - ADJUSTABLET
P L
U R
I B
U E
S U
N U
M
C I
R C
U M
S P
I C
E
S I
Q U
E R
E I
S P
E N
I N
S U
L A
M A
M
OE
N A
M
9711 Valparaiso Drive
221 N. LaSalle Street
(219)924-8400
Munster, IN 46321
Chicago, IL 60601 www.milliesengineeringgroup.com
MILLIES
ENGINEERING GROUP
820 Monroe Ave NW Grand Rapids, MI 49503
Copyright © 2026 Millies Engineering Group
S th S tr e e t, P O
B o x
O s h te m o
M
I
(2
-8
S N
A N
O -1
F
IL
E N
O
.J
L M
S H
E E
T
ID
E N
T
IF
IC
A
T
IO
N N
O
IS
S
U E
D F
O R
D A
T E
C o p y ri g h t
S c h le y N el so n A rc h it e ct s, I n c.
C O
N S
T R
U C
T
IO
N
F
IN
A L
R E
C O
R D
P R
E L
IM
R
E V
IE
W
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H R
A D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N t h
A v e
S a u g a t u c k
D u n e s M I
S a u ga tu ck
D u n es
S ta te
P a r k
S to r a ge
B u il d in g
D ep a r tm en t o f N a tu r a l R es o u r ce s
L a k e t o w n
T o w n s h ip A ll e g a n
C o u n t y M ic h ig a n
M2.0
-1
-2
F O
R B
ID
C O
N S
T R
MECHANICAL EQUIPMENT SCHEDULE
TAG MANUFACTURER MODEL DESCRIPTION EFFICIENCY
FAN MOTOR DATA EXHAUST FANS DX COOLING EQUIPMENT/COIL DATA DX HEATING DATA ELECTRIC HEATING EQUIP./COIL DATA ELECTRICAL DATA
UNITS
CONTROLLED BY
EQUIPMENT
WEIGHT REMARKSCFM
MIN.
OAI
TSP ESP BHP HP RPM CFM ESP BHP HP RPM MBH SHC EDB EWB LDB LWB CAT STAGES MBH EDB STAGES MBH KW EAT LAT STEPS
LOAD
VOLT PHASE HZ
DISCONNECT SWITCH:
CFM HP MCA FLA MOCP
PROV. BY:
M.C. E.C.
AC-1 DAIKIN CTXV07AVJU9 WALL MOUNTED DUCTLESS UNIT
330 7
X WALL MTD
TSTAT
25 NOTE #1
AC-2 DAIKIN
FTXV09/12AVJ
U9
WALL MOUNTED DUCTLESS UNIT
385 9
X WALL MTD
TSTAT
25 NOTE #1
HP-1 DAIKIN 2MXT18AVJU9
WALL MOUNTED AIR SOURCE
HEAT PUMP
21 SEER2 17.2 95 MOD
18 MOD
18.7 20 240 1 60 X INTERLOCK W/
AC-1 & AC-2
150 NOTE #2
TEF-1 GREENHECK SP-A390-VG
CEILING MOUNTED TOILET
EXHAUST FAN
110 0.36 0.01 939 0.29 120 1 60 X OCC. SENSOR 25 NOTE #3
EBB-1 QMARK QMKC2513W ELECTRIC BASE BOARD
2.56 0.75 6.25 15 120 1 60 X INTEGRAL
TSTAT
10 NOTE #5
EBB-2 QMARK QMKC2513W ELECTRIC BASE BOARD
2.56 0.75 6.25 15 120 1 60 X INTEGRAL
TSTAT
10 NOTE #5
EBB-3 QMARK QMKC2546W ELECTRIC BASE BOARD
5.12 1.5 6.3 15 240 1 60 X INTEGRAL
TSTAT
10 NOTE #5
RCP-1 QMARK CP251
24x24 ELECTRIC RADIANT
HEATING PANEL
0.853 0.25 2.08 15 120 1 60 X WALL MTD
TSTAT
20 NOTE #4
NOTE 1:
PROVIDE WITH:
• WIRED THERMOSTAT
• CONDENSATE PUMP
SEE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
NOTE 2:
PROVIDE WITH:
• NON-FUSED DISCONNECT
• INVERTER SCROLL COMPRESSOR
• WALL MOUNT HARDWARE
SEE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
NOTE 3:
PROVIDE WITH:
• BUILT-IN BACKDRAFT DAMPER
• INTEGRAL METAL GRILLE
• VIBRATION ISOLATION HANGERS
SEE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
NOTE 4:
PROVIDE WITH:
• MOUNTING HARDWARE
• BATT INSULATION
• THERMOSTAT
SEE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
NOTE 5:
PROVIDE WITH:
• INTEGRAL THERMOSTAT
SEE SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
E
N '5 "W
.6
S '5 "E
.7 1'
M= N88°40'13"W 200.00'
N '5
"W
.0
M
N '5
"W
.0
M= N88°40'13"W 1116.29'
CP#50
CP#51
CP#52
CP#53
CP#54
J
EXISTING TICKET
BOOTH
NEW MAINTENANCE
FACILITY
NEW UTILITY
POLE-MOUNTED
TRANSFORMER
UNDERGROUND
POWER FEEDER
UNDERGROUND
TELEPHONE CONDUIT
WELL PUMP
ELECTRICAL
FEED
EXISTING UTILITY
METER
27,29
P L
U R
I B
U E
S U
N U
M
C I
R C
U M
S P
I C
E
S I
Q U
E R
E I
S P
E N
I N
S U
L A
M A
M
OE
N A
M
9711 Valparaiso Drive
221 N. LaSalle Street
(219)924-8400
Munster, IN 46321
Chicago, IL 60601 www.milliesengineeringgroup.com
MILLIES
ENGINEERING GROUP
820 Monroe Ave NW Grand Rapids, MI 49503
Copyright © 2026 Millies Engineering Group
S th S tr e e t, P O
B o x
O s h te m o
M
I
(2
-8
S N
A N
O -1
F
IL
E N
O
.J
L M
S H
E E
T
ID
E N
T
IF
IC
A
T
IO
N N
O
IS
S
U E
D F
O R
D A
T E
C o p y ri g h t
S c h le y N el so n A rc h it e ct s, I n c.
C O
N S
T R
U C
T
IO
N
F
IN
A L
R E
C O
R D
P R
E L
IM
R
E V
IE
W
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H
R A
D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N t h
A v e
S a u g a t u c k
D u n e s M I
S a u ga tu ck
D u n es
S ta te
P a r k
S to r a ge
B u il d in g
D ep a r tm en t o f N a tu r a l R es o u r ce s
L a k e t o w n
T o w n s h ip A ll e g a n
C o u n t y M ic h ig a n
E0.0
-1
-2
F O
R B
ID
C O
N S
T R
1" = 40'-0"
SITE PLAN - ELECTRICAL
M3
H
M3
H
W P
M2
M1
3 3
WP WP
D O
D O
D O
PC
M
M
MEZZANINE
GARAGE BELOW
IB1 IB1 IB1 IB1
IB1IB1IB1IB1
7b
7a 7b
7b 7b
7b 7b
7b
IB1
IB1
7b
7b a,b a,b
ALT. 1
GARAGE
ADA/BF UNISEX TLT.
OFFICE
CLO.
BREAK ROOM
EBB
RCP
MICROWAVE
RECEPTACLE
EBB
COFFEE MAKER
RECEPTACLE
REFRIG.
RECEPTACLE
TEF
b a a
WA1
BA2
BA2
BA2
XCEM
EM1
EM1
EM
EM
EM1
EM
11 11
21 21
19 15
14 16 18
7f
7c
7c c d
7d f
WH
G1
IA1
7e e
G1
9PANEL P-1
HP
EBB
T.T.B.
20'-0" AFG
P L
U R
I B
U E
S U
N U
M
C I
R C
U M
S P
I C
E
S I
Q U
E R
E I
S P
E N
I N
S U
L A
M A
M
OE
N A
M
9711 Valparaiso Drive
221 N. LaSalle Street
(219)924-8400
Munster, IN 46321
Chicago, IL 60601 www.milliesengineeringgroup.com
MILLIES
ENGINEERING GROUP
820 Monroe Ave NW Grand Rapids, MI 49503
Copyright © 2026 Millies Engineering Group
S th S tr e e t, P O
B o x
O s h te m o
M
I
(2
-8
S N
A N
O -1
F
IL
E N
O
.J
L M
S H
E E
T
ID
E N
T
IF
IC
A
T
IO
N N
O
IS
S
U E
D F
O R
D A
T E
C o p y ri g h t
S c h le y N el so n A rc h it e ct s, I n c.
C O
N S
T R
U C
T
IO
N
F
IN
A L
R E
C O
R D
P R
E L
IM
R
E V
IE
W
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H
R A
D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N t h
A v e
S a u g a t u c k
D u n e s M I
S a u ga tu ck
D u n es
S ta te
P a r k
S to r a ge
B u il d in g
D ep a r tm en t o f N a tu r a l R es o u r ce s
L a k e t o w n
T o w n s h ip A ll e g a n
C o u n t y M ic h ig a n
E1.0
-1
-2
F O
R B
ID
C O
N S
T R
1/4" = 1'-0"
MEZZANINE PLAN - ELECTRICAL LIGHTING & POWER
1/4" = 1'-0"
FLOOR PLAN - ELECTRICAL LIGHTING & POWER
REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION TOTAL CONNECTED AMPS: 117.9 A
TOTAL CONNECTED LOAD: 28300 VA
TOTAL CONNECTED LOAD PHASE C: 0 VA
TOTAL CONNECTED LOAD PHASE B: 14352 VA
TOTAL CONNECTED LOAD PHASE A: 13948 VA
PANEL TOTALS
GC = PROVIDE GFI CIRCUIT BREAKER
ST = PROVIDE SHUNT TRIP BREAKER
LO = PROVIDE LOCKABLE DEVICE
EX = EXISTING CIRCUIT BREAKER
LEGEND:
41 42
39 40
37 38
35 36
33 34
31 32
29 1248 30
WELL PUMP 20 A 2
1248 28
25 LOW VOLTAGE POWER 20 A 1 1000 1500 1 20 A MICROWAVE RECEP 26
23 COFFEE MAKER RECEP 20 A 1 1400 800 1 20 A GC FRIDGE RECEP 24
21 RECEPS SE GARAGE 20 A 1 600 400 1 20 A BENCH RECEPS, AC S RECEP 22
19 SHOP VAC. & GEN RECEP. 20 A 1 1700 1000 1 20 A RECEPS GEN. BREAK, TLT. 20
17 BENCH AC WEST RECEPS 20 A 1 600 1200 1 20 A OH DOOR EAST 18
15 AIR COMPRESSOR & GEN RECEPS 20 A 1 1900 1200 1 20 A OH DOOR CENTER 16
13 RECEPS MEZZANINE 20 A 1 400 1200 1 20 A OH DOOR WEST 14
11 EXTERIOR RECEPS 20 A 1 600 800 1 20 A RECEPS OFFICE, CLOSET 12
9 EXTERIOR LIGHTING 20 A 1 34 1650 1 20 A WATER HEATER CLOSET 10
7 INTERIOR LIGHTING 20 A 1 840 250 1 15 A RADIANT CEILING PANEL RCP-1 8
5 BASEBOARD HEAT EBB-2 BTHRM 15 A 1 750 750 1 15 A BASEBOARD HEAT EBB-1 BTHRM 6
3 2244 756 4
HEAT PUMP 20 A 2
2244 756
2 15 A BASEBOARD HEAT EBB-3 BREAK
CKT CIRCUIT DESCRIPTION LEG. TRIP POLES A B A B POLES TRIP LEG. CIRCUIT DESCRIPTION CKT
NOTES:
A.I.C. RATING: 22000 A BUSSING: COPPER
ENCLOSURE: NEMA-1 MAIN RATING: 150 A
MOUNTING: SURFACE MAINS TYPE: MCB
SUPPLY FROM: PHASES: 1
LOCATION: GARAGE 5 VOLTS: 120/240 Single
PANEL P-1
SYMBOL LIST
RN
REMOVE EXISTING DEVICE AND PROVIDE NEW AS INDICATED IN EXISTING BACK BOX, JUNCTION BOX, ETC. VERIFY EXACT LOCATION AND CONDITIONS IN FIELD. MODIFY EXISTING BACK BOX, JUNCTION BOX, ETC. PROVIDE TRIM PLATES, EXTENSION RINGS, ETC. AS REQUIRED TO MOUNT
NEW DEVICE AS INDICATED.
DO
NI
EMERGENCY BATTERY LIGHT MOUNTED 7'-6" AF (OR AS NOTED)
F&I NEW DEVICE AS INDICATED.
LIGHTING SEQUENCE SCHEME TAG REFERENCE TO LIGHTING CONTROL SEQUENCE OF OPERATIONS
PC EXTERIOR LIGHTING CONTROL PHOTOCELL
ELECTRIC MOTOR CONNECTION - PROVIDE LOCAL DISCONNECT SWITCH PER NATIONAL ELECTRIC CODE - CONNECT MISCELLANEOUS ACCESSORIES SUCH AS BACK DRAFT DAMPERS, ETC. COMPLETE
AS REQUIRED.
J
LP-A1 #1
120V-20A SPECIFICATION GRADE DUPLEX RECEPTACLE - (MOUNTED 42" A.F.F. OR 2" ABOVE
BACKSPLASH IF LOCATED ABOVE COUNTER) (HUBBELL #5362 OR EQUAL)
120V-20A SPECIFICATION GRADE GROUNDED DUPLEX RECEPTACLE WITH G.F.I. PROTECTION -
(MOUNTED 18" A.F.F. OR AS NOTED) (HUBBELL #GF20 OR EQUAL)
120V-20A SPECIFICATION GRADE GROUNDED DUPLEX RECEPTACLE WITH G.F.I. PROTECTION
(MOUNTED 42" A.F.F. OR 2" ABOVE BACKSPLASH IF LOCATED ABOVE COUNTER) (HUBBELL #GF20 OR
EQUAL)
120V-20A SPECIFICATION GRADE DUPLEX RECEPTACLE - (MOUNTED AT SPECIAL HEIGHT -
COORDINATE IN FIELD) (HUBBELL #5362 OR EQUAL)
TWO DEVICE MOUNTED UNDER COMMON COVER. WHERE LOW VOLTAGE DEVICES ARE
MOUNTED UNDER COMMON COVER, COMBINE CONDUIT STUBS MAINTAINING THE EQUIVALENT
FREE AREA FOR THE LOW VOLTAGE CABLING.
HOMERUN TO PANEL INDICATING PANEL AND CIRCUIT BREAKER NUMBER WITHIN THE PANEL.
ELLIPSE TAG REFERENCE TO SHEET NOTES
HEXAGON TAG REFERENCE TO EQUIPMENT CONNECTION SCHEDULE
JUNCTION BOX - SIZE AND TYPE AS REQUIRED.
OVERHEAD DOOR PUSHBUTTON CONTROL STATION OUTLET BOX - CONTRACTOR SHALL FURNISH
CONDUIT BETWEEN ALL OVERHEAD DOOR DEVICES AS REQUIRED FOR A COMPLETE AND PROPERLY
OPERATING SYSTEM.
120V-20A SPECIFICATION GRADE SIMPLEX RECEPTACLE - (MOUNTED 18" A.F.F. OR AS NOTED)
(HUBBELL #5251 OR EQUAL)
FURNISH AND INSTALL WALL SWITCH SINGLE BUTTON DUAL TECHNOLOGY OCCUPANCY SENSOR WITH MANUAL ON OPERATION MTD 42" AFF: SENSORSWITCH #WSX-PDT OR APPROVED EQUAL BY COOPER
OR HUBBELL CONTROLS.
FURNISH AND INSTALL WALL SWITCH DUAL TECHNOLOGY OCCUPANCY SENSOR CAPABLE OF
DIMMING WITH MANUAL ON OPERATION MTD 42" AFF: SENSORSWITCH #WSX-PDT-D OR APPROVED EQUAL
BY COOPER OR HUBBELL CONTROLS.
M1
M3
FURNISH AND INSTALL CEILING MOUNTED DUAL TECHNOLOGY OCCUPANCY SENSOR WITH POWER
PACK. MANUFACTURERS: SENSORSWITCH #CM-PDT-10-MP-20 (WITH MICROPHONICS) OR APPROVED
EQUAL BY COOPER OR HUBBELL CONTROLS. SENSOR SHALL BE PROGRAMMED FOR MANUAL ON
UNLESS OTHERWISE NOTED.
M2
120V-20A SPECIFICATION GRADE DUPLEX RECEPTACLE - (MOUNTED 18" A.F.F. OR AS NOTED)
(HUBBELL #5362 OR EQUAL).
SPECIAL PURPOSE OUTLET (AS NOTED ON PLAN OR SPECIFICATIONS).
ELECTRIC PANELBOARDS.
DISCONNECT SWITCH SIZE AND TYPE AS REQUIRED - COORDINATE AMPERE RATING WITH
EQUIPMENT SUPPLIER
DOOR OPERATOR FOR OVERHEAD DOORS
FURNISH AND INSTALL TWO BUTTON ON/OFF SWITCH MTD 42" AFF: SENSORSWITCH #SPODM OR
APPROVED EQUAL BY COOPER OR HUBBELL CONTROLS. PROVIDE WITH POWER PACK AS REQUIRED
FOR CONTROL OF FIXTURES.
FURNISH AND INSTALL TWO BUTTON ON/OFF 3-WAY SWITCH MTD 42" AFF: SENSORSWITCH #SPODM OR APPROVED EQUAL BY COOPER OR HUBBELL CONTROLS. PROVIDE WITH POWER PACK AS REQUIRED
FOR CONTROL OF FIXTURES.
X X
LIGHTING
SWITCHING
EQUIPMENT AND WIRING
SHEET SYMBOLS
RECEPTACLES
120V-20A SPECIFICATION GRADE HALF-CONTROLLED DUPLEX RECEPTACLE - (MOUNTED 18" A.F.F. OR AS NOTED) (HUBBELL BR20C1 OR EQUAL). PROVIDE MANUFACTURER MARK FOR CONTROLLED FACE.
120V-20A SPECIFICATION GRADE HALF-CONTROLLED DUPLEX RECEPTACLE - (MOUNTED 42" A.F.F. OR AS NOTED) (HUBBELL BR20C1 OR EQUAL). PROVIDE MANUFACTURER MARK FOR CONTROLLED FACE.
X
A. WORK SHALL COMPLY WITH LOCAL, STATE AND NATIONAL ELECTRIC CODES, AMERICANS WITH DISABILITIES ACT (or MICHIGAN ACCESSIBILITY CODE AND MICHIGAN LIFE SAFETY CODE FOR
SCHOOLS).
B. THE PANEL SCHEDULES ARE PROVIDED FOR ASSISTANCE ONLY IN UNDERSTANDING THE
LOADING ON THE VARIOUS CIRCUITS AND THE CIRCUIT DESIGNATIONS DESIRED FOR THE
PANEL DIRECTORIES. THE PANEL SCHEDULES MUST BE BALANCED UPON COMPLETION OF THE
PROJECT TO COMPLY WITH CODE. IN ADDITION, THE PANEL SCHEDULES DO NOT IDENTIFY THE TYPES OF CIRCUIT BREAKERS TO BE USED (SUCH AS GFCI, HACR, SHUNT TRIP UNITS, ETC.) NOR DO THE SCHEDULES IDENTIFY CIRCUIT BREAKERS REQUIRED. (SUCH AS C/B'S FEEDING SURGE
PROTECTION UNITS). REFER TO THE REST OF THE DRAWINGS AND THE SPECIFICATIONS FOR
ADDITIONAL REQUIREMENTS AND DETAILED INFORMATION.
C. COORDINATE EQUIPMENT ELECTRICAL REQUIREMENTS (VOLTAGES, PHASE, LOAD, ETC.) TO
AVOID CONFLICTS.
D. REFER TO ARCHITECTURAL PLANS AND ELEVATIONS FOR ADDITIONAL ELECTRICAL
INFORMATION AND REQUIREMENTS. IN ALL CASES DEVICE MOUNTING HEIGHTS AND LOCATIONS
SHALL CONFORM TO THE LATEST AMERICANS WITH DISABILITIES FEDERAL STANDARDS.
E. EXCAVATION NECESSARY FOR COMPLETION OF WORK SHALL BE PROVIDED. COORDINATE
WITH ONE ANOTHER TO SHARE TRENCHES WHEREVER POSSIBLE.
F. REFER TO THE PLANS FOR ADDITIONAL ELECTRICAL WORK AND REQUIREMENTS. FURNISH,
INSTALL AND LOCATE DISCONNECT SWITCHES AT EQUIPMENT/MOTOR LOCATION, AS
REQUIRED, AND IN ACCORDANCE WITH CODE. IF THE WORK OF OTHER TRADES CAUSES A LOSS
OF CONTINUITY OF THE EXISTING ELECTRICAL DISTRIBUTION, GROUNDING SYSTEM OR
CIRCUITRY, IT SHALL BE RECONNECTED OR REPAIRED AT NO ADDITIONAL COST.
G. SCHEDULE WORK TO AVOID FACILITY (TICKET BOOTH) DOWNTIME AND INCONVENIENCE TO
OWNER. OWNER'S EXISTING FACILITY (TICKET BOOTH) SHALL REMAIN IN OPERATION AT ALL
TIMES. REQUIRED SHUTDOWN OF EXISTING FACILITY UTILITIES SHALL BE SCHEDULED WITH
OWNER'S OPERATING PERSONNEL.
H. LAYOUT IS DIAGRAMMATIC AND INSTALL DEVICES, CONDUIT AND EQUIPMENT TO MEET ACTUAL
FIELD CONDITIONS. REVIEW PROJECT SPECIFICATIONS BEFORE STARTING WORK AND SUBMIT
COMPLETE SHOP DRAWINGS AS PER SPECIFICATIONS.
I. VISIT SITE PRIOR TO BID TO DETERMINE AND VERIFY EXISTING INTERIOR AND EXTERIOR
ELECTRICAL SYSTEMS TO VERIFY QUANTITIES AND LOCATIONS OF EXISTING SYSTEMS TO
DETERMINE FULL EXTENT OF WORK. INCLUDE THE NECESSARY MODIFICATIONS TO THE
EXISTING CONDITIONS (INCLUDING CEILINGS, WALLS, FLOORS, PIPES, CONDUIT, ROOF WORK, ETC.) AS REQUIRED, TO ALLOW FOR PROPER INSTALLATION OF WORK. ADJUST INSTALLATIONS
TO MEET FIELD CONDITIONS AS REQUIRED FOR A COMPLETE AND PROPER INSTALLATION. NO
EXTRAS WILL BE ALLOWED AFTER BIDDING FOR ANY REWORK OF EXISTING FIELD CONDITIONS
TO RESOLVE CONFLICTS OR NOT FULLY UNDERSTANDING THE SCOPE OF THE WORK
REQUIRED. EXISTING EQUIPMENT, CONDUIT, PIPING, ETC. SHALL BE REMOVED AS NOTED ON
DRAWINGS AND AS REQUIRED TO MEET NEW SCOPE OF WORK.
J. HIDDEN CONDITIONS IDENTIFIED THROUGH THE COURSE OF CONSTRUCTION SHALL BE
IMMEDIATELY BROUGHT TO ATTENTION IN WRITTEN FORM FOR REVIEW AND DIRECTION.
FAILURE TO DO SO SHALL REQUIRE THE CHANGES AND COSTS TO CORRECT SAID HIDDEN
CONDITION TO BE COMPLETED AT NO COST. EXISTING EQUIPMENT NOT IDENTIFIED SHALL BE
BROUGHT TO ATTENTION FOR REVIEW AS TO WHETHER THE EQUIPMENT SHALL REMAIN AND
BE RECONNECTED TO THE NEW SERVICES, BE RELOCATED, BE ABANDONED, ETC.
K. WIRE FIXTURES IN TANDEM AS REQUIRED TO ACCOMPLISH THE SWITCHING ARRANGEMENT AS
INDICATED ON DRAWINGS.
L. VERIFY CEILING STYLES/FRAMES AND TYPES BEFORE ORDERING FIXTURES AND CEILING
MOUNTED DEVICES. PROVIDE APPROPRIATE STYLES/FRAMES AS REQUIRED TO MATCH
CEILING STYLE AND TYPES.
M. COORDINATE LIGHTING LAYOUTS WITH CEILING REGISTERS, GRILLES, DIFFUSERS, SPRINKLER HEADS AND CEILING GRID (SEE ARCHITECTURAL REFLECTED CEILING PLAN.) VERIFY LOCATION
WITH OWNER'S REPRESENTATIVE IN FIELD PRIOR TO INSTALLATION.
N. WHERE INDICATED ON THE DRAWINGS IN UNFINISHED SPACES, RUN EXPOSED RACEWAYS
PARALLEL WITH OR AT RIGHT ANGLES TO WALL.
O. NO RACEWAYS SHALL BE INSTALLED WITHIN 6" OF STEAM, HOT WATER PIPES OR SIMILAR HEAT
PRODUCING APPLIANCES.
P. PROVIDE PULL WIRE IN EACH RACEWAY IN WHICH WIRING IS NOT INSTALLED.
Q. COVERS OF JUNCTION OR PULL BOXES SHALL BE ACCESSIBLE AND IDENTIFIED PER
SPECIFICATIONS. FIRE ALARM JUNCTION BOXES SHALL BE PAINTED RED. JUNCTION OR PULL
BOXES AND THE LIKE SHALL BE INDEPENDENTLY SUPPORTED TO BUILDING STRUCTURE WITH
NO WEIGHT BEARING ON RACEWAYS.
R. WIRE COLOR CODING SHALL BE COORDINATED THROUGHOUT THE ENTIRE PROJECT/BUILDING
FOR NEW AND EXISTING SYSTEMS.
S. IF MORE THAN THREE (3) PHASE (UNGROUNDED) CONDUCTORS ARE RUN IN THE SAME
RACEWAY, CONDUCTOR AMPACITY SHALL BE DERATED IN ACCORDANCE WITH NEC ARTICLE
310.
T. CONDUIT, LIGHTING, EQUIPMENT, ETC. SHALL NOT BE SUPPORTED FROM THE BOTTOM CHORD
OF ENGINEERED JOISTS WITHOUT WRITTEN APPROVAL FROM THE STRUCTURAL ENGINEER.
CONDUITS, ROUTED THROUGH AREAS WITH NO CEILING, SHALL BE ROUTED WITHIN THE
WEBBING OF THE JOISTS AND SHALL NOT BE ROUTED BELOW THE BOTTOM CHORD OF THE
JOIST.
U. SMOKE OR HEAT DETECTORS SHALL BE SURFACE MOUNTED TO CEILING, ROOF DECK
MATERIALS, ETC. IN LIEU OF MOUNTING TO BOTTOM CHORD OF ENGINEERED JOIST OR ANY
OTHER COMPONENTS NOT AN INTEGRAL PART OF THE HORIZONTAL CEILING.
V. WIRING DEVICES SHOWN BACK-TO-BACK IN WALLS SHALL BE SEPARATED BY 8" MINIMUM.
W. UNLESS OTHERWISE NOTED, DEVICE ELEVATIONS REFER TO CENTER LINE OF JUNCTION BOX.
VERIFY JUNCTION BOX LOCATIONS WITH FINAL EQUIPMENT LAYOUT PRIOR TO ROUGHING IN
SAME.
X. FURNISH AND INSTALL A GREEN GROUND WIRE IN POWER CONDUITS (NOT LIGHTING). ALL
DEVICES, EQUIPMENT, FIXTURES AND THE LIKE, MUST BE GROUNDED.
MECHANICAL/ELECTRICAL BONDS OF THE METALLIC RACEWAY SYSTEM SHALL BE MAINTAINED.
Y. PROVIDE CONDUIT AND WIRE AND MAKE FINAL POWER CONNECTIONS AS REQUIRED TO
EXHAUST FANS AND MISCELLANEOUS EQUIPMENT FURNISHED WITH MOTORIZED BACKDRAFT
DAMPERS. DAMPERS SHALL BE CONNECTED TO EQUIPMENT 120 VOLT POWER CIRCUIT SO AS
TO INTERLOCK THE MOTORIZED DAMPER WITH THE EXHAUST FAN. FOR THREE PHASE
MOTORS, PROVIDE AN ADDITIONAL 120 VOLT CIRCUIT ROUTED THROUGH AN AUXILIARY
CONTACT IN THE MOTOR STARTER.
Z. AT NEW WATER METER LOCATION PROVIDE CONDUIT AS REQUIRED TO REMOTE READER
LOCATION. REFER TO PLUMBING DRAWINGS FOR METER LOCATIONS. COORDINATE READER
LOCATION WITH UTILITY COMPANY PRIOR TO ROUGH-IN.
AA. SINGLE POLE CIRCUITS SHALL HAVE SEPARATE INDEPENDENT NEUTRAL CONDUCTORS (NON-
NETWORKED), WHICH (PER CODE) ARE CONSIDERED CURRENT CARRYING CONDUCTORS.
THEREFORE, IF MORE THAN THREE (3) CURRENT CARRYING CONDUCTORS ARE RUN IN THE
SAME RACEWAY, CONDUCTOR AMPACITY SHALL BE DERATED IN ACCORDANCE WITH NEC
ARTICLE 310. AS SUCH, MULTIPLE BRANCH CIRCUIT HOME RUNS SHALL, AT A MINIMUM, UTILIZE
#10 AWG CONDUCTORS TO COMPLY WITH REQUIREMENTS HEREIN. COORDINATE
REQUIREMENTS IN FIELD WITH SPECIFIC HOME RUN CONFIGURATION AND NEC 2008.
BB. CONTRACTOR SHALL OBTAIN AVAILABLE FAULT CURRENT, UTILITY TRANSFORMER SIZE AND
IMPEDANCE WITHIN 14 DAYS OF CONTRACT AWARD. ELECTRICAL PANEL AND GEAR SHOP
DRAWINGS SHALL BE SUBMITTED ALONG WITH COORDINATION/ARC FLASH STUDY WITH 30
DAYS OF CONTRACT AWARD FOR REVIEW. ALL GEAR SHALL BE RATED TO PROPERLY
WITHSTAND AVAILABLE FAULT CURRENT.
GENERAL NOTES
1. INTERIOR FIXTURES, EXTERIOR FIXTURES AND COLORS TO BE SELECTED BY ARCHITECT.
2. LED FIXTURES (LESS THAN 10000 LUMENS) SHALL BE PROVIDED WITH FACTORY INSTALLED
INTEGRAL EMERGENCY BATTERY UNITS BATTERY UNITS SHALL PROVIDE A MINIMUM OF 1400
LUMENS.
3. FIXTURES THAT CANNOT BE PROVIDED WITH EMERGENCY BALLASTS OR FIXTURES WITH
GREATER THAN 10000 LUMENS SHALL BE PROVIDED WITH EMERGENCY INVERTER (MYERS #LV
SERIES OR APPROVED EQUAL) WITH SUITABLE CAPACITY TO POWER FIXTURE FOR A MINIMUM
OF 90 MINUTES PER CODE. VERIFY SIZING AND REQUIREMENTS WITH CONTRACT DOCUMENTS
PRIOR TO ORDERING.
4. SHADED FIXTURES SHALL HAVE AN EMERGENCY SOURCE OF POWER AS SPECIFIED.
5. FIXTURES WITH EMERGENCY BATTERIES SHALL BE PROVIDED WITH CONSTANT HOT SENSING
WIRE SO THAT FIXTURE CAN BE SWITCHED ON AND OFF WITHOUT ACTIVATING EMERGENCY
BALLAST. UPON LOSS OF POWER, THE FIXTURE SHALL BE ILLUMINATED FOR A MINIMUM OF 90
MINUTES REGARDLESS OF THE LIGHT SWITCH POSITION. PROVIDE TEST SWITCH AND
CHARGING INDICATOR FOR EMERGENCY BATTERY
AS SPECIFIED.
6. ALL INTEGRAL EMERGENCY BATTERIES USED IN EXTERIOR APPLICATIONS SHALL HAVE A
MINIMUM STARTING TEMPERATURE OF -20 DEGREES F UNLESS OTHERWISE SPECIFIED.
7. CAREFULLY COORDINATE MOUNTING REQUIREMENTS FOR FIXTURES WITH CONTRACT
DOCUMENTS AND FIXTURE MANUFACTURER. PROVIDE APPROPRIATE MOUNTING FRAMES FOR
LAY-IN OR GYPSUM CEILINGS. VERIFY CEILING REQUIREMENTS WITH FINAL ARCHITECTURAL
REFLECTED CEILING PLAN.
8. COMPLETE PHOTOMETRICS OF THE INTERIOR AND EXTERIOR LIGHTING SHALL BE SUBMITTED
ALONG WITH THE LIGHTING SHOP DRAWINGS FOR REVIEW. FOR FINISHED SPACES, 80/50/20
REFLECTANCES SHALL BE UTILIZED. FOR UNFINISHED SPACES 50/50/20 REFLECTANCE SHALL BE UTILIZED. THE LLD VALUE THAT SHALL BE UTILIZED FOR LED IS .9. EXTERIOR CALCULATIONS
SHALL ACCOUNT FOR HOUSE SIDE SHIELDING AND SHALL CONFORM TO LOCAL
REQUIREMENTS.
9. VERIFY FIXTURE MOUNTING HEIGHTS WITH ARCHITECT PRIOR TO ROUGH-IN.
10. COORDINATE LOCATIONS OF INTERIOR AND EXTERIOR LIGHTING FIXTURES WITH FINAL
ARCHITECTURAL DRAWINGS. FIXTURES THAT ARE NOT INSTALLED IN THE CORRECT LOCATION
SHALL BE RELOCATED AND REINSTALLED IN THE CORRECT LOCATION AT NO ADDITIONAL
CHARGE.
11. FIXTURES SHALL BE CAREFULLY COORDINATED WITH MANUFACTURER TO DELIVER THE
SPECIFIED PRODUCT IN SUFFICIENT TIME TO MEET PROJECT DEADLINES. EQUIPMENT DELIVERY
LEAD TIME SHALL NOT BE HELD AS A VALID REASON FOR REQUESTING LUMINAIRE
SUBSTITUTION UNLESS LUMINAIRE LEAD TIME FROM SPECIFIED MANUFACTURER IS IN EXCESS
OF 14 WEEKS. IT SHALL BE THE SOLE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO
DETERMINE NECESSARY EQUIPMENT LEAD TIMES, DELIVER SUBMITTALS FOR REVIEW IN A
TIMELY FASHION, AND PLACE ORDERS ACCORDINGLY TO ENSURE TIMELY DELIVERY.
12. EVALUATION OF APPROVED EQUALS SHALL BE AT THE SOLE DISCRETION OF THE ARCHITECT
AND ENGINEER. IF THE PRODUCT SUBMITTED DURING THE REVIEW PROCESS IS NOT JUDGED
AS AN EQUAL BY THE REVIEWING ENGINEER, THE CONTRACTOR SHALL PROVIDE THE PRODUCT
SPECIFIED.
13. CAREFULLY COORDINATE VOLTAGES OF FIXTURES PRIOR TO ORDERING FIXTURES.
14. CAREFULLY VERIFY COLOR TEMPERATURE OF FIXTURES WITH ARCHITECT PRIOR TO
ORDERING.
FIXTURE GENERAL NOTES
P L
U R
I B
U E
S U
N U
M
C I
R C
U M
S P
I C
E
S I
Q U
E R
E I
S P
E N
I N
S U
L A
M A
M
OE
N A
M
9711 Valparaiso Drive
221 N. LaSalle Street
(219)924-8400
Munster, IN 46321
Chicago, IL 60601 www.milliesengineeringgroup.com
MILLIES
ENGINEERING GROUP
820 Monroe Ave NW Grand Rapids, MI 49503
Copyright © 2026 Millies Engineering Group
S th S tr e e t, P O
B o x
O s h te m o
M
I
(2
-8
S N
A N
O -1
F
IL
E N
O
.J
L M
S H
E E
T
ID
E N
T
IF
IC
A
T
IO
N N
O
IS
S
U E
D F
O R
D A
T E
C o p y ri g h t
S c h le y N el so n A rc h it e ct s, I n c.
C O
N S
T R
U C
T
IO
N
F
IN
A L
R E
C O
R D
P R
E L
IM
R
E V
IE
W
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H
R A
D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N t h
A v e
S a u g a t u c k
D u n e s M I
S a u ga tu ck
D u n es
S ta te
P a r k
S to r a ge
B u il d in g
D ep a r tm en t o f N a tu r a l R es o u r ce s
L a k e t o w n
T o w n s h ip A ll e g a n
C o u n t y M ic h ig a n
E2.0
-1
-2
F O
R B
ID
C O
N S
T R
ELECTRICAL ONE-LINE SCHEMATIC DIAGRAM
120/240V POLE MOUNTED
TRANSFORMER BY UTILITY
NEW PANEL P-1
120/240V, 1PH, 3W, 150A
REUSE EXISTING C/T
FOR UTILITY METER
OVERHEAD
SECONDARY
FEED BY UTILITY
UNDERGROUND
POWER FEEDER
3 #1/0 & 1 #6 GRD.
1-1/2" C.
EXTERIOR LIGHTING CONTROL DIAGRAM
PHOTOCELL (TORK #2100)
CONTACTOR 'A'
R
P-1 #9
CKT.
ON OFF
'A'
R
NEUTRAL
CP
EXTERIOR LIGHTING
TIME CLOCK (TORK
#T920L-2 CKT.)
TO SECURITY
LTG. - BLDG.
EXTERIOR LIGHTING CONTACTOR 20A.
2P. IN NEMA 1 ENCLOSURE (ALLEN
BRADLEY #500LP-AAD9)
NOTE: TIME CLOCK FUNCTION IS FOR CONTROL OF CIRCUIT 'A' -
PHOTOCELL ON-TIME CLOCK OFF
TO PNL. 'P-1'
CKT. 9
NEUTRAL BUS
SURGE ARRESTOR
1. CONTRACTOR SHALL FOLLOW THIS DETAIL FOR PROPER GROUNDING CONNECTIONS, INCLUDING FURNISH AND INSTALL ALL CONDUCTORS AND EQUIPMENT SUCH AS GROUND RODS, SURGE ARRESTOR, GROUND BUS, ETC.
TO PROPERLY GROUND/BOND ALL EQUIPMENT.
2. GROUNDING ELECTRODE RESISTANCE SHALL BE 25 OHMS OR LESS. SHOULD THE MEASURED RESISTANCE BE HIGHER THAN 25 OHMS, ADDITIONAL SUPPLEMENTAL ELECTRODES SHALL BE PROVIDED AS REQUIRED TO
REACH A RESISTANCE TO EARTH OF 25 OHMS OR LESS.
3. IN ADDITION TO THE ABOVE DEPICTED CONNECTIONS, CONTRACTOR SHALL PROVIDE ALL GROUND RODS, GROUND GRIDS, AND OTHER GROUNDING ELECTRODES AS REQUIRED BY THE UTILITY COMPANY AND MAKE
CONNECTIONS TO UTILITY EQUIPMENT PER UTILITY COMPANY STANDARDS.
NOTES:
3/0 CU
3/0 CU
3/0 CU
3/0 CU
COLD WATER PIPE
3/0 CU. SHUNT AROUND
WATER METER
WATER METER
3/0 CU
CONNECT TO COLD
WATER SYSTEM
(NTS.)
SYSTEM BONDING
JUMPER
(TYP. FOR 3 OR 4
ROD GROUNDING
FIELD.)
(3) 3/4" COPPERWELD
10' LONG GROUND RODS
EQUIPMENT
GROUND BUS AT MAIN
PANEL (P-1)
TO RE-STEEL IN CONCRETE
FOUNDATION
3/0 CU
10' MIN.
GROUNDING DETAIL
LOW VOLTAGE SERVICE ENTRANCE DIAGRAM
WALL
FLOOR LINE
WALL
(NTS.)
4' WIDE X 4' X 3/4" THICK PLYWOOD
TELEPHONE TERMINAL BOARD
(T.T.B.) - 2 COATS FIRE RESISTANT
GRAY PAINT
TELEPHONE WIRE
TERMINATION BLOCKS/
STRIPS, ETC. SEE SPECS
FOR ADDITIONAL
INFORMATION
PROVIDE INLINE
SURGE SUPPRESION
PROVIDE IN-LINE SURGE
SUPPRESSION ON
INCOMING CATV &
TELEPHONE FEEDERS.
QUAD
RECEPTACLE
P-1 #25
(1) 3" PVC CONDUIT WITH TWO (2) NYLON PULL CORDS ROUTED
MINIMUM 36" BELOW GRADE (WITH CONTINUOUS YELLOW WARNING TAPE
18" ABOVE) TO PROPERTY LINE FOR TELEPHONE UTILITY
SERVICES. COORDINATE TERMINATION POINT WITH UTILITIES PRIOR TO
INSTALLING SAME. VERIFY FIELD CONDITIONS . TRENCH AND BACKFILL
AS REQUIRED, PER SPECIFICATIONS. COORDINATE WITH LOCAL
UTILITIES, FOR SERVICE ENTRANCE LOCATIONS, AND ADDITIONAL
REQUIREMENTS.
LIGHTING FIXTURE SCHEDULE
TYPE DESCRIPTION MANUFACTURER SERIES OR CATALOG NUMBER LAMP
COLOR
TEMP MIN LUMENS MAX WATTS VOLTS CONTROL MOUNTING TYPE
MOUNTING
HEIGHT REMARKS
BA2
2'X4' SURFACE MOUNTED FLAT PANEL LED FIXTURE
W/ SURFACE MOUNT KIT
LITHONIA
METALUX
COLUMBIA
CPX-2X4-5000LM-80CRI-35K-SWL-MIN1-ZT-MVOLT / 2X4SMKSH
24CGTX-55-L835-HCD / SMK-24-W
SRP24-35MLG-ED1U / PSMK-24
LED 3500K 5000 LM 40 W 120/277V 0-10V SURFACE ---
EM1
UNIT BATTERY EMERGENCY LIGHTING FIXTURE
WITH 90 MINUTE CAPACITY AND SELF DIAGNOSTICS
LITHONIA
MULE
DUAL LITE
ELM6L-UVOLT-LTP-SDRT
TSR-HO-W-SD
EVHC12I-06L
LED --- --- 5 W 120/277V ---
WALL
SURFACE
IA1
2' WALL MOUNTED LED INDUSTRIAL FIXTURE WITH
FLAT DIFFUSE LENS AND WHITE FINISH
LITHONIA
METALUX
WILLIAMS
DAY-BRITE
CLX-L24-1500LM-SEF-FDL-MVOLT-GZ1-35K-80CRI-WH
2SNX-19SL-FDL-UNV-L835-HCD1
75S-2-L15-835
FLP-2-20L-835-Q-UNV-DIM
LED 3500K 1500LM 11 W 120/277V 0-10V WALL ---
COORDINATE LOCATIONS
WITH DUCTWORK AND PIPING
IB1
8' SUSPENDED LED INDUSTRIAL FIXTURE WITH FLAT
DIFFUSE LENS, WHITE FINISH, WIREGUARD, AND
SAFETY CHAINS
LITHONIA
METALUX
COLUMBIA
CLX-L96-10000LM-SEF-FDL-MVOLT-GZ1-35K-80CRI-WH- HC36M12-WGCLX48
8SNX-10SL-FDL-UNV-L835-HCD1-AYC-CHAIN/SET-U-WG-SNX/SN-4FT-B
MPS8-35HL-FW-ED1U-CSHC-MPSWG4
LED 3500K 10000 LM 64 W 120/277V 0-10V
'Y' CHAIN
SUSPENDED
16'-0" A.F.F.
COORDINATE LOCATIONS
WITH DUCTWORK AND PIPING
WA1
24" LONG SQUARE LED VANITY FIXTURE WITH
WHITE DIFFUSER AND BRUSHED NICKEL HOUSING
LITHONIA
ABRA
OXYGEN
FMVCSLS-24IN-MVOLT-30K-90CRI
20017WV-XX
3-537-XX
LED 3500K 1300 LM 18 W 120/277V 0-10V WALL
MOUNTED
ABOVE
MIRROR
VERIFY MOUNTING HEIGHT
AND FINISH WITH ARCHITECT
XC
LED DIE-CAST ALUMINUM SINGLE FACE EXIT SIGN,
RED LETTERING, BRUSHED ALUMINUM, NICAD
BATTERY, SELF-DIAGNOSTICS
LITHONIA
SURELITES
DUAL LITE
LE-S-1-R-ELN-SD
CX71SD
SESRWEI
LED --- --- 1 W 120/277V --- WALL/CEILING ---
ENGINEER - CONFIRM LETTER
COLOR, FINISH, BATTERY VS
AC ONLY
G1
EXTERIOR GOOSE NECK FIXTURE W/ INTEGRATED
PHOTOCELL
SPECTRUM
BARN LIGHT
AFX
SW1509GV-15L-27K-EX-TF2-CP104-SP9012-MWI-WLKA
BLE-G-ASFC14-XX-XX-G17-XX-NA-NA-CLR-NA-NA-LED16.8-3500K
GILW1210LAJENBK
LED 3500K 1500LM 10 W 120/277V ---
WALL
MOUNTED
MOUNTED
ABOVE DOOR
EM
FIXTURE ON EMERGENCY CIRCUIT WITH 90 MINUTE,
HIGH OUTPUT (MIN 1400LM) BATTERY UNIT OR
INVERTER
BODINE FACTORY INSTALLED BATTERY, OR, AT CONTRACTOR'S DISCRETION,
MYERS LV SERIES INVERTER (SIZE AND QUANTITY AS REQUIRED)
0 W 120/277V ---
- PROVIDE TEST SWITCH AND
CHARGING INDICATOR
- INTEGRAL BATTERIES NOT
ALLOWED IN FIXTURES WITH
GREATER THAN 10000
LUMENS
MECHANICAL EQUIPMENT CONNECTION SCHEDULE
TAG DESCRIPTION
LOAD
MOCP VOLT PHASE PANEL CKT. NO.
FEEDER DISCONNECT SWITCH STARTER
REMARKSWATTS HP MCA FLA CABLE CONDUIT SIZE FUSE
PROV. BY
TYPE
PROV. BY:
M.C./P.C. E.C. M.C./P.C. E.C.
EBB-1 ELECTRIC BASEBOARD HEATER 750 6.25 15 120 1 PANEL P-1 6 2 #12 & 1 #12 GRD. 3/4" 15A X
EBB-2 ELECTRIC BASEBOARD HEATER 750 6.25 15 120 1 PANEL P-1 5 2 #12 & 1 #12 GRD. 3/4" 15A X
EBB-3 ELECTRIC BASEBOARD HEATER 1512 6.3 15 240 1 PANEL P-1 2,4 3 #12 & 1 #12 GRD. 3/4" 30A X
HP-1 HEAT PUMP 4488 18.7 20 240 1 PANEL P-1 1,3 3 #10 & 1 #10 GRD. 3/4" 15A X
RCP-1 RADIANT CEILING PANEL 249.6 2.08 15 120 1 PANEL P-1 8 2 #12 & 1 #12 GRD. 3/4" 15A X
TEF-1 TOILET EXHAUST FAN 34.8 0.29 120 1 PANEL P-1 7 2 #12 & 1 #12 GRD. 3/4" 15A X
WH-1 WATER HEATER 1650 13.75 120 1 PANEL P-1 10 2 #12 & 1 #12 GRD. 3/4" 30A
P L
U R
I B
U E
S U
N U
M
C I
R C
U M
S P
I C
E
S I
Q U
E R
E I
S P
E N
I N
S U
L A
M A
M
OE
N A
M
9711 Valparaiso Drive
221 N. LaSalle Street
(219)924-8400
Munster, IN 46321
Chicago, IL 60601 www.milliesengineeringgroup.com
MILLIES
ENGINEERING GROUP
820 Monroe Ave NW Grand Rapids, MI 49503
Copyright © 2026 Millies Engineering Group
S th S tr e e t, P O
B o x
O s h te m o
M
I
(2
-8
S N
A N
O -1
F
IL
E N
O
.J
L M
S H
E E
T
ID
E N
T
IF
IC
A
T
IO
N N
O
IS
S
U E
D F
O R
D A
T E
C o p y ri g h t
S c h le y N el so n A rc h it e ct s, I n c.
C O
N S
T R
U C
T
IO
N
F
IN
A L
R E
C O
R D
P R
E L
IM
R
E V
IE
W
D E
P A
R T
M E
N T
O F
T E
C H
N O
L O
G Y
M
A N
A G
E M
E N
T A
N D
B U
D G
E T
S T
A T
E O
F M
IC
H
IG
A
N
A D
A M
P L
A C
H
R A
D
IR
E
C T
O R
S T
A T
E F
A C
IL
IT
IE
S
A D
M
IN
IS
T
R A
T
IO
N
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N t h
A v e
S a u g a t u c k
D u n e s M I
S a u ga tu ck
D u n es
S ta te
P a r k
S to r a ge
B u il d in g
D ep a r tm en t o f N a tu r a l R es o u r ce s
L a k e t o w n
T o w n s h ip A ll e g a n
C o u n t y M ic h ig a n
E2.1
-1
-2
F O
R B
ID
C O
N S
T R
| 014 2603048 Plumbing 2026-06-15 |
| P1.0 - MEZZANINE & FLOOR PLANS - PLUMBING |
| P2.0 - PLUMBING DETAILS |
| 015 2603048 Mechanical 2026-06-15 |
| M1.0 - MEZZANINE & FLOOR PLANS - MECHANICAL |
| M2.0 - MECHANICAL DETAILS |
| 016 2603048 Electrical 2026-06-15 |
| E0.0 - SITE PLAN - ELECTRICAL |
| E1.0 - MEZZANINE & FLOOR PLANS - ELECTRICAL |
| E2.0 - ELECTRICAL NOTES & SYMBOLS |
| E2.1 - ELECTRICAL DETAILS & SCHEDULES |