7348665 DrawingsAsOne SIGNED.pdf

PDF 4 MB Posted

Attached to
Replace Fuel Tanks and Piping, Building 4075
Solicitation number
N400857348665
Issued by

About this file

This is a set of architectural and engineering drawings for a fuel tank and piping replacement project at Marine Corps Air Station Cherry Point in North Carolina. The project (Work Order #7348665) involves demolishing existing aboveground fuel storage infrastructure and installing new fuel storage systems for diesel and motor gasoline (MOGAS). Key details include:

The project scope includes removing two existing 2,000-gallon aboveground storage tanks (ASTs), associated fuel pumps, dispensers, piping, and related electrical systems. New infrastructure will be installed in the same location, featuring two new 2,000-gallon double-wall steel tanks with leak detection, emergency vents, and updated fuel pumps. The replacement will maintain the existing underground piping network. Electrical work involves reconnecting existing circuitry, replacing Veeder-Root monitoring systems, and updating emergency shutoff controls. The project is being executed for the Naval Facilities Engineering Command Mid-Atlantic, with design drawings prepared by NRW Engineering, dated 06/14/24.

View the file

Other files

File Type Posted
Amendment 0008 7348665.pdf PDF
Amendment 0007 7348665.pdf PDF
Amendment 0006 7348665.pdf PDF
Amendment 0005 7348665.pdf PDF
Amendment 0004 7348665.pdf PDF
Amendment 0004 7348665.pdf PDF
Amendment 0003 7348665.pdf PDF
Amendment 0002 7348665.pdf PDF
Amendment 0001 7348665.pdf PDF
7348665 SpecsAsOne SIGNED.pdf PDF
7348665 RFP.pdf PDF
Show all 11

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Digitally signed by John K Avolis

7/11/2024

Digitally signed by John K Avolis

GENERAL NOTES

DEMOLITION

EXISTING PIPING AND EQUIPMENT SHOWN IS BASED ON EXISTING PLANS AND FIELD

OBSERVATION WITHOUT DEMOLITION. AFTER DEMOLITION, ANY CLARIFICATION REQUIRED

TO DETERMINE SCOPE OF WORK SHALL BE BROUGHT TO THE ATTENTION OF THE COTR.

THE CONTRACTOR MUST VISIT THE JOB SITE AND THOROUGHLY FAMILIARIZE HIMSELF WITH

THE EXISTING CONDITIONS, DEMOLITION, AND NEW WORK REQUIREMENTS PRIOR TO

PERFORMING ANY WORK.

DRAWINGS DO NOT SHOW EVERY EXISTING PIPE, CONDUIT, DUCT, ETC. CONTRACTOR SHALL

TAKE CARE TO REMOVE ONLY ITEMS REQUIRED TO BE REMOVED AND VERIFY PIPES, PUMPS,

ETC. BEFORE REMOVAL.

REMOVAL OF ITEMS SHALL INCLUDE ASSOCIATED HANGERS, ANCHOR BOLTS AND OTHER

APPURTENANCES. WHERE SUCH REMOVAL RESULTS IN OPEN HOLES, VOIDS OR EXPOSURE

OF DAMAGED SURFACES, THE CONTRACTOR IS RESPONSIBLE FOR REPAIRING AND

FINISHING THE SURFACE TO MATCH ADJACENT CONDITIONS.

REMOVE EXISTING ABOVE GRADE PIPING NOT TO BE REUSED.

ALL MATERIALS REMOVED UNDER DEMOLITION, NOT TO BE RELOCATED OR DESIGNATED TO

BE TURNED OVER TO THE GOVERNMENT, SHALL BECOME THE PROPERTY OF THE

CONTRACTOR, UNLESS OTHERWISE NOTED, AND SHALL BE REMOVED COMPLETELY FROM

THE SITE.

GENERAL ITEMS

GENERAL NOTES ON THIS DRAWING ARE APPLICABLE TO EACH MECHANICAL DRAWING OF

THIS SET. SEE EACH DRAWING FOR SPECIFIC NOTES APPLICABLE TO THAT DRAWING.

ARRANGE PIPING AS REQUIRED TO CLEAR STRUCTURE, CONDUITS, ETC. ALLOWING SPACE

FOR PIPE HANGERS AND ACCESS TO VALVES, FILTERS, AND MAINTENANCE OF EQUIPMENT.

COORDINATE LOCATION AND INSTALLATION OF EQUIPMENT WITH OTHER TRADES.

DO NOT SCALE DRAWINGS.

VALVES AND SPECIALTIES SHALL BE LINE SIZE UNLESS NOTED OTHERWISE.

NO PIPING SHALL BE SMALLER THAN 3/4" UNLESS OTHERWISE NOTED.

PROVIDE UNION OR FLANGED CONNECTIONS AT EACH PIECE OF EQUIPMENT AND ON BOTH

SIDES OF CONTROL VALVES AND PRESSURE REGULATING VALVES. PROVIDE SHUT-OFF

VALVES ON BOTH SIDES OF AUTOMATIC VALVES.

PIPING SHALL BE SUPPORTED IN ACCORDANCE WITH THE SPECIFICATIONS. ADDITIONAL

SUPPORTS OR HANGERS SHALL BE INSTALLED ADJACENT TO ELBOWS TO PREVENT WEIGHT

OF PIPING BEING PLACED ON THE EQUIPMENT.

CORRECT SETTING ON BALANCING FITTINGS SHALL BE PERMANENTLY MARKED.

FOR LOCATION OF MOTOR STARTERS, SEE ELECTRICAL DRAWINGS.

MAINTENANCE

PROVIDE ACCESS TO ANY INSPECTION OR MAINTAINABLE DEVICE, EQUIPMENT, ETC. -

ACCESS OR ACCESS DOOR SHALL BE OF ADEQUATE SIZE TO WORK ON DEVICE.

EXAMINE MANUFACTURER'S LITERATURE TO DETERMINE RECOMMENDED CLEARANCES.

THESE CLEARANCES, IN ADDITION TO MINIMUM CLEARANCES REQUIRED BY THE NATIONAL

ELECTRICAL CODE, SHALL BE ESTABLISHED AND MAINTAINED. THIS APPLIES TO NEW AND

EXISTING EQUIPMENT IMPACTED BY THIS PROJECT. THE CONTRACTOR IS RESPONSIBLE FOR

COORDINATING THESE REQUIREMENTS WITH ALL OTHER TRADES.

INTERDISCIPLINARY COORDINATION

IF THIS CONTRACTOR SHOULD ELECT TO PROPOSE ANY EQUIPMENT THAT HAS DIFFERENT

PHYSICAL OR ELECTRICAL CHARACTERISTICS, ETC. WHEN COMPARED TO THE BASIS OF

DESIGN EQUIPMENT, THIS CONTRACTOR IS RESPONSIBLE FOR COORDINATING THESE

CHANGES WITH THE OTHER TRADES PRIOR TO BID AND AGAIN BEFORE ORDERING OF

EQUIPMENT. IF THERE SHOULD BE ANY ADDITIONAL WORK INCURRED BY THE OTHER

TRADES AS A RESULT OF THIS CONTRACTOR'S EQUIPMENT SELECTION, ALL COSTS

ASSOCIATED WITH THE ADDITIONAL WORK SHALL BE BORNE BY THIS CONTRACTOR.

ABOVEGROUND STORAGE TANK DESIGNATIONAST-1

POINT OF DEMOLITION LIMIT

POINT OF CONNECTION NEW TO EXISTING

WORK NOTE DESIGNATION

LEGEND AND ABBREVIATIONS

SHEET WHERE SHOWN/CUT

DETAIL/RISER/ENLARGED PLAN

REVOLUTIONS PER MINUTE

PIPE TURNING DOWN

FUEL PIPINGG

RPM

PIPE TURNING UP

HP

GAL

GPM

HORSEPOWER

GALLON

GALLONS PER MINUTE

FT FEET

PSIG POUND PER SQUARE INCH GAUGE

NO NUMBER

FUEL PUMP DESIGNATIONP-1

COTR CONTRACTING OFFICER'S TECHNICAL REPRESENTATIVE

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

C

OM

MA

ND

M

ID

AT

LA

NT

IC

RE

PL

AC

E

FU

EL

T

AN

KS

/P

IP

IN

G

MA

LS

, B

Structural Consultants 748 Lord Dunmore Drive, Suite 101 Virginia Beach, VA 23464 Phone 757-474-0612 Fax 757-474-0919

NRWENGINEERING

TNH CML JAK

12908193

GE

NE

RA

L N

OT

ES

, L

EG

EN

D, A

ND

A

BB

RE

VI

AT

IO

NS

AS NOTED

M-001

06/14/24

ABOVEGROUND STORAGE TANK SCHEDULE

CAPACITY TANK DIMENSIONS

TAG GAL SERVICE MATERIAL LENGTH WIDTH HEIGHT REMARKS

AST-1 2,000 DIESEL INSULATED DOUBLEWALL STEEL 11' 3" 6' 10" 4' 7" SEE NOTES

AST-2 2,000 MOGAS INSULATED DOUBLEWALL STEEL 11' 3" 6' 10" 4' 7" SEE NOTES

NOTES:

1. TANK DIMENSIONS VARY WITH MANUFACTURER. MODIFY FOUNDATION, PADS, BOLLARDS, ETC. AS REQUIRED TO MEET MANUFACTURER'S REQUIREMENTS.

2. TANKS SHALL COMPLY WITH UL 2085.

3. PROVIDE WITH MANUFACTURER'S STAIRS TO SUPPORT READY ACCESS TO TOP OF TANK.

4. SELECTION BASED ON FIREGUARD HIGHLAND TANK

FUEL PUMP SCHEDULE

G.P.M. AT

DISPENSER

ELECTRICAL DATA

TAG SERVICE FUEL TYPE H.P. VOLTS PHASE R.P.M. REMARKS

P-1 AST-1 DIESEL 10 VANE ROTARY WITH AIR SEPARATOR 22.0 1 120 1 3450 SEE NOTES

P-2 AST-2 MOGAS 10 VANE ROTARY WITH AIR SEPARATOR 22.0 1 120 1 3450 SEE NOTES

NOTES:

1. PROVIDE FACTORY INTAKE FILTER SCREEN, PRESSURE RELIEF CHECK VALVE, AIR ELIMINATOR, AND MOTOR CONTROLLER.

2. SELECTION BASED ON GASBOY.

DIESEL

MOGAS

JP-5

DIESEL

JP-52

MOGAS2

BOLLARD, ETR (TYP)

BLDG 4075

CONCRETE ISLAND, ETR

EX. HVAC

EX. TRANSFORMER

EX. VEEDER-ROOT CONTROL PANEL

EX. CONCRETE

EX. CONCRETE

EX. CONCRETE

CONCRETE ISLAND, ETR

EX. CONCRETE

FENCE, ETR

GRAPHIC SCALE:

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

C

OM

MA

ND

M

ID

AT

LA

NT

IC

RE

PL

AC

E

FU

EL

T

AN

KS

/P

IP

IN

G

MA

LS

, B

Structural Consultants 748 Lord Dunmore Drive, Suite 101 Virginia Beach, VA 23464 Phone 757-474-0612 Fax 757-474-0919

NRWENGINEERING

TN

PN

MECHANICAL SITE PLAN - DEMOLITION

SCALE: 1" = 10'

DEMOLITION NOTES

REMOVE ABOVEGROUND CONCRETE FUEL STORAGE TANK. REMOVE ALL SENSORS AND

ASSOCIATED APPURTENANCES COMPLETE. REMOVE ALL REMAINING FUEL AND TURN OVER

TO GOVERNMENT. GOVERNMENT SHALL REMOVE MOST OF THE FUEL FROM THE TANKS AND

TRIPLE RINSE. CONTRACTOR SHALL REMOVE RESIDUAL FUEL. EACH FUEL TYPE SHALL BE

STORED IN CONTRACTOR PROVIDED SEPARATE CONTAINERS AND TURNED OVER TO THE

GOVERNMENT.

REMOVE FUEL PUMP, DISPENSER, AND ASSOCIATED APPURTENANCES COMPLETE.

REMOVE FUEL PIPING, SUPPORTS, VALVES, AND ASSOCIATED APPURTENANCES COMPLETE

TO LIMIT INDICATED. UNDERGROUND PIPING SHALL REMAIN IN PLACE, AND MUST BE REUSED

UNDER NEW WORK PHASE.

1" = 10'-0" 10' 5' 0' 10' 20' 30'

TNH CML JAK

12908194

SI

TE

P

LA

N

- D

EM

OL

ITI

ON

AS NOTED

MD101

06/14/24

CONTRACTOR MUST PROTECT EXISTING BOLLARDS AND

CONCRETE PAD. IF THESE ITEMS ARE DAMAGED, THEY SHALL BE

REPLACED AT NO COST TO THE GOVERNMENT.

BOLLARD AND SLAB PROTECTION:

AST-1

AST-2

P-1

P-22

BLDG 4075

CONCRETE ISLAND, ETR

EX. HVAC

EX. TRANSFORMER

EX. VEEDER-ROOT CONTROL PANEL,

SEE ELECTRICAL

EX. CONCRETE

EX. CONCRETE

EX. CONCRETE

CONCRETE ISLAND, ETR

EX. CONCRETE

BOLLARD, ETR (TYP)

FENCE, ETR

GRAPHIC SCALE:

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

C

OM

MA

ND

M

ID

AT

LA

NT

IC

RE

PL

AC

E

FU

EL

T

AN

KS

/P

IP

IN

G

MA

LS

, B

Structural Consultants 748 Lord Dunmore Drive, Suite 101 Virginia Beach, VA 23464 Phone 757-474-0612 Fax 757-474-0919

NRWENGINEERING

TN

PN

MECHANICAL SITE PLAN - NEW WORK

SCALE: 1" = 10'

WORK NOTES

PROVIDE ABOVEGROUND FUEL STORAGE TANK, SENSORS, AND ASSOCIATED

APPURTENANCES COMPLETE.

PROVIDE FUEL PUMP, DISPENSER, AND ASSOCIATED APPURTENANCES COMPLETE.

PROVIDE FUEL PIPING, SUPPORTS, VALVES, PRESSURE RELIEF, AND ASSOCIATED

APPURTENANCES COMPLETE TO LIMIT INDICATED. PIPING SHALL BE SUPPORTED TO MAINTAIN

A MINIMUM OF 18" ABOVE GRADE. UNDERGROUND PIPING MUST BE REUSED.

PROVIDE ENDCAP ON JP-5 PIPING AND SEAL WATER TIGHT.

1" = 10'-0" 10' 5' 0' 10' 20' 30'

TNH CML JAK

12908195

SI

TE

P

LA

N

- N

EW

W

OR

K

AS NOTED

M-101

06/14/24

ABOVEGROUND STORAGE TANK DETAIL

SUCTION LINE TO FUEL

PUMP. PROVIDE UNION

AT TANK CONNECTION

2" VENT WITH PRESSURE/VACUUM CAP

EMERGENCY VENT

THRU TANK

LEAK DETECTOR

4" DROP TUBE WITH

OVERFILL PREVENTION

VALVE. CLOSES FILL

PIPE AT 90%-95%

CAPACITY

SUCTION TUBE

STEEL TANK

SUPPORT SADDLE

(TYP.)

FLOAT

TANK GAUGE

2" NIPPLE

INNER STEEL TANK

PADLOCK HASP

OVER FILL

4" FILL NIPPLE

DRAIN VALVE

THERMAL

INSULATION

2"Ø THRU TANK LEAK

DETECTION TUBE

2" NIPPLE

PUMP CONNECTION

4" NIPPLE

EMERGENCY VENT

VENT WITH PRESS CAP,

2" NIPPLE

NO SCALE

OUTER STEEL TANK

INSULATION

FUEL TANK

(2000 GALLON)

RELIEF VALVE (TYP)

2-1/2" MOGAS / DIESEL LINE

FIRE EMERGENCY

SHUTOFF VALVE

120 VOLT SHUTOFF

VALVE CONNECTED TO

CONTROL PANEL

TO FUEL PUMP

RELIEF VALVE SET

TO 1.1 TIMES

PRESSURE OF FUEL

PUMP DEAD HEAD

PRESSURE

3/4" PRESSURE RELIEF LINE

UNION (TYP.)

SCHEMATIC FLOW DIAGRAM

NO SCALE

CONTRACTOR MUST PROTECT EXISTING BOLLARDS AND

CONCRETE PAD. IF THESE ITEMS ARE DAMAGED, THEY SHALL BE

REPLACED AT NO COST TO THE GOVERNMENT.

BOLLARD AND SLAB PROTECTION:

EXISTING PRODUCT SUPPLY PIPING.

SUMP MOUNTING FRAME - ATTACH

TO CONCRETE ISLAND

PROVIDE EMERGENCY SHUT-OFF

VALVE IN PRODUCT PIPE

NOTE: PROVIDE SHEAR

SECTION IN VAPOR PIPING

(NOT SHOWN)

PROVIDE 12" MIN. EACH

SIDE (CENTER DISPENSER

ON THE ISLAND)

EXTEND CONDUIT TO TANK

MONITORING CONTROL

PANEL.

PROVIDE WATERTIGHT DISPENSER

SUMP WITH ELECTRONIC LIQUID

SENSOR, FOR BOTH MOGAS/

DIESEL SUMPS.

FIN. GRADE

PROVIDE STABILIZING BAR

AND MOUNTING BRACKET

DISPENSER BASE COLUMN

MOGAS/DIESEL DISPENSER SUMP BASIN DETAIL

NO SCALE

STEEL ISLAND FORM

ANTI-SIPHON VALVE

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

C

OM

MA

ND

M

ID

AT

LA

NT

IC

RE

PL

AC

E

FU

EL

T

AN

KS

/P

IP

IN

G

MA

LS

, B

Structural Consultants 748 Lord Dunmore Drive, Suite 101 Virginia Beach, VA 23464 Phone 757-474-0612 Fax 757-474-0919

NRWENGINEERING

MIN MIN RTW

12908196

GE

NE

RA

L N

OT

ES

, L

EG

EN

D, A

ND

A

BB

RE

VI

AT

IO

NS

AS NOTED

E-001

06.14.24

EXISTING AREA SITE LIGHTING FIXTURE

EQUIPMENT CONNECTION

SAFETY SWITCH, 60A-3P, FU @ 30A, 3R

LIGHTING

POWER

GENERAL

WORK NOTE SYMBOL

GENERAL ELECTRICAL NOTES ELECTRICAL LEGEND

SWITCH RATING

NUMBER OF POLES

FUSE RATING (NF INDICATES NON-FUSED)

NEMA ENCLOSURE IF OTHER THAN NEMA 1

E

GENERAL: UNLESS SPECIFICALLY INDICATED OTHERWISE, ALL WORK

SHOWN ON ELECTRICAL DRAWINGS IS NEW WORK TO BE PROVIDED

UNDER THIS CONTRACT.

COORDINATION: COORDINATE AND COOPERATE WITH ALL TRADES ON

THE PROJECT. THE CONTRACTOR MUST REVIEW ALL CONTRACT

DOCUMENTS INCLUDING CIVIL AND MECHANICAL DRAWINGS AND

SPECIFICATIONS. CONTRACTOR MUST COORDINATE AND ADJUST

ACCORDINGLY AS DIRECTED BY THE CONTRACTING OFFICER.

AS-BUILT DRAWINGS: SECURE AN EXTRA SET OF ELECTRICAL DRAWINGS

TO BE KEPT ON SITE AND MARK, DAILY, THE DRAWINGS IN RED AS THE

PROJECT PROGRESSES IN ORDER TO KEEP AN ACCURATE RECORD OF

ALL DEVIATIONS BETWEEN THE WORK SHOWN ON THE DRAWINGS AND

THE WORK WHICH IS ACTUALLY INSTALLED. THESE MARKED DRAWINGS

MUST REFLECT ANY AND ALL CHANGES AND REVISIONS TO THE ORIGINAL

DESIGN WHICH EXISTS IN THE COMPLETED WORK. DELIVER THE MARKED

DRAWINGS TO THE OWNER AT PROJECT CLOSE-OUT.

TESTS: TEST ALL WIRING FOR CONTINUITY AND GROUNDS BEFORE

CONNECTING ANY FIXTURES OR DEVICES.

INSPECTIONS: ARRANGE ALL NECESSARY INSPECTIONS. DELIVER ALL

REQUIRED INSPECTION CERTIFICATES TO THE CONTRACTING OFFICER.

GROUNDING: PROVIDE GROUNDING IN ACCORDANCE WITH THE NEC FOR

THE ELECTRICAL SYSTEM INCLUDING EQUIPMENT FRAMES CONDUITS,

SWITCHES, CONTROLLERS, WIRE-WAYS, NEUTRAL CONDUCTORS, AND

OTHER EQUIPMENT. PROVIDE A GROUNDING CONDUCTOR IN ALL POWER

CONDUITS.

LABELS: PROVIDE LABELS FOR ALL CABINETS, SAFETY SWITCHES,

MOTOR-DISCONNECT SWITCHES, AND MOTOR CONTROLLERS. LABELS

MUST BE MACHINE ENGRAVED, LAMINATED PLASTIC, PERMANENTLY

ATTACHED WITH SELF-TAPPING SCREWS OR RIVETS. DO NOT USE

SELF-ADHESIVE LABELS. LABEL MUST INDICATE EQUIPMENT DESIGNATION

AND ASSOCIATED PANEL AND CIRCUIT THAT SERVES IT.

J-BOX LABELING: LABEL ALL JUNCTION BOXES WITH PERMANENT

MARKER IDENTIFYING CIRCUIT NUMBER AND PANELBOARD OF CIRCUITS

WITHIN.

WIRING DEVICES: LABEL ALL WIRING DEVICES WITH PANELBOARD AND

CIRCUIT DESIGNATION PERMANENTLY ATTACHED WITH BLACK TYPED

DESIGNATION ON CLEAR TAPE.

PANEL DIRECTORY: PROVIDE UPDATED TYPEWRITTEN PANELBOARD

DIRECTORY CARD IN EACH PANELBOARD MODIFIED WITH CIRCUIT LOAD

INFORMATION AND ROOM NUMBER CLEARLY IDENTIFIED. USE ACTUAL

ROOM NUMBERS IN THE BUILDING, NOT THE ROOM NUMBERS SHOWN ON

THE CONTRACT DRAWINGS, AS THEY ARE OFTEN DIFFERENT.

CONDUCTORS AND MATCHING LUGS: IN SITUATIONS WHERE CONDUCTOR

SIZES AND/OR QUANTITIES OF PARALLEL SETS HAVE BEEN INCREASED

DUE TO VOLTAGE DROP OR FOR OTHER REASONS, CONTRACTOR MUST

PROVIDE THE APPROPRIATE LUG SIZES/QUANTITIES WITHIN THE

EQUIPMENT CONNECTED (SWITCHBOARD, PANELBOARD, DISCONNECT

SWITCH, TRANSFER SWITCH ETC.) TO PERMIT SATISFACTORY

CONNECTION OF THE INDICATED CONDUCTORS. WHERE SUFFICIENT LUG

SIZES AND/OR QUANTITIES CANNOT BE PROVIDED TO ACCOMMODATE THE

CONDUCTORS INDICATED, THEN PROVIDE REDUCING ADAPTERS, PIN

TERMINALS, OR A JUNCTION BOX TO SPLICE LARGER CONDUCTORS TO

APPROPRIATELY SIZED SMALLER CONDUCTORS TO FIT INTO THE LUGS

PROVIDED. ALL CONDUCTORS MUST BE SIZED IN ACCORDANCE WITH THE

NEC.

MOTOR COORDINATION: MOTORS, MOTOR STARTERS, CONTROLLERS,

INTEGRAL DISCONNECT SWITCHES, AND CONTACTORS MUST BE

PROVIDED WITH THEIR RESPECTIVE PIECES OF EQUIPMENT BY THE

EQUIPMENT SUPPLIER. COMMUNICATE WITH THE TRADES PROVIDING THE

EQUIPMENT, VERIFYING ALL REQUIREMENTS, PROVIDE ALL ELECTRICAL

CONNECTIONS REQUIRED THEREIN, AND INSTALL MOTOR STARTERS.

MOTOR DISCONNECTS: ALL MOTORS MUST HAVE DISCONNECTING MEANS.

MOTOR FUSE PROTECTION: WHERE FUSE PROTECTION IS SPECIFICALLY

REQUIRED BY THE EQUIPMENT MANUFACTURER, PROVIDE FUSED

SWITCHES IN LIEU OF NON-FUSED SWITCHES OR IN LIEU OF ENCLOSED

CIRCUIT BREAKERS, OR OTHER DEVICES INDICATED.

CONNECTION DETAILS: SECURE APPROVED SHOP DRAWINGS SHOWING

WIRING DIAGRAMS, ROUGH-IN AND HOOK UP DETAILS FROM OTHER

INVOLVED CONTRACTORS FOR EQUIPMENT WHICH MUST BE CONNECTED

ELECTRICALLY.

COORDINATION DETAILS: MECHANICAL EQUIPMENT WILL BE FURNISHED

AND INSTALLED BY THE MECHANICAL CONTRACTOR. THE LOCATIONS

SHOWN ON THE ELECTRICAL DRAWINGS ARE APPROXIMATE. COORDINATE

WITH THE MECHANICAL CONTRACTOR TO DETERMINE THE EXACT

LOCATION OF EACH PIECE OF EQUIPMENT AND DETERMINE THE EXACT

ROUGH-IN AND CONNECTION REQUIREMENTS.

WORKING CLEARANCE: COORDINATE FINAL LOCATIONS OF ELECTRICAL

EQUIPMENT WITH MECHANICAL DUCTWORK, PIPING ETC. AND ENSURE

WORKING CLEARANCE REQUIRED BY NEC WILL BE MET. SUFFICIENT

ACCESS AND WORKING SPACE MUST BE PROVIDED AND MAINTAINED

AROUND ELECTRICAL EQUIPMENT AS REQUIRED BY THE NATIONAL

ELECTRICAL CODE. CONTRACTOR MUST COORDINATE FINAL LOCATION OF

EQUIPMENT PROVIDED AND INSTALLED BY OTHER TRADES.

MOUNTING HEIGHTS: MOUNTING HEIGHTS INDICATED ARE FROM THE

FINISHED FLOOR TO THE CENTERLINE OF THE WIRING DEVICE UNLESS

OTHERWISE NOTED.

FIRE STOPPING: FOR ANY WALL OR FLOOR PENETRATIONS THROUGH

FIRE-RATED STRUCTURES PROVIDE FIRE-STOPPING TO SEAL ALL THE

PENETRATIONS AFTER THE CONDUIT HAS BEEN INSTALLED. FIRE

STOPPING FOR PENETRATIONS MUST BE UL APPROVED PER THE

PENETRATION MADE IN ORDER TO MAINTAIN FIRE-RATED INTEGRITY OF

THE STRUCTURE.

CLEAN UP: ON PROJECT CLOSE-OUT CLEAN ALL ELECTRICAL DEVICES,

LIGHTING FIXTURES, LENSES, AND REMOVE ALL PAINT SPATTERS FROM

DEVICES, FIXTURES AND PLATES.

ABBREVIATIONS

A AMPERE

AFF ABOVE FINISHED FLOOR

AFG ABOVE FINISHED GRADE

AIC AMPERE INTERRUPTING CAPACITY

AWG AMERICAN WIRE GAUGE

BFG BELOW FINISHED GRADE

C CONDUIT

CAT CATEGORY

CB CIRCUIT BREAKER

CKT CIRCUIT

DE DOMINION ENERGY

EC EMPTY CONDUIT

EF EXHAUST FAN

EQUIP EQUIPMENT

ETR EXISTING TO REMAIN

EXIST EXISTING

FHP FRACTIONAL AC HORSEPOWER

FLA FULL LOAD AMPS

GFI GROUND FAULT INTERRUPTER

GND GROUND

HP HORSE POWER/HEAT PUMP

IBC INTERNATIONAL BUILDING CODE

KAIC THOUSAND AMPERE

INTERRUPTING CAPACITY

KVA KILO-VOLT-AMPERES

KW KILO-WATTS

LF LINEAR FEET

MCA MINIMUM CIRCUIT AMPS

MCB MAIN CIRCUIT BREAKER

MFR MANUFACTURER

MIN MINIMUM

MLO MAIN LUGS ONLY

MOCP MAXIMUM OVER-CURRENT

PROTECTION

MTD MOUNTED

N NORMAL

NEC NATIONAL ELECTRICAL CODE

NF NON-FUSED

NFPA NATIONAL FIRE PROTECTION

ASSOCIATION

NIC NOT IN CONTRACT

NTS NOT TO SCALE

OC ON CENTER

P POLE

PCP PUMP CONTROL PANEL

PF POWER FACTOR

PNL PANEL

Ø PHASE

PRI PRIMARY

RU RACK UNIT

SCH SCHEDULE

SEC SECONDARY

TYP TYPICAL

UFC UNIFIED FACILITIES CRITERIA

UON UNLESS OTHERWISE NOTED

UTP UNSHIELDED TWISTED PAIR

V VOLT

VAV VARIABLE AIR VOLUME

W WATTS/WIRE

WP WEATHERPROOF

E

E

E

E

BLDG 4075

APPROXIMATE LOCATION

OF PANELBOARDS

SERVING FUEL PUMPS

E

E

E

E

E

BLDG 4075

GRAPHIC SCALE:

NA

VA

L F

AC

ILI

TI

ES

E

NG

IN

EE

RI

NG

C

OM

MA

ND

M

ID

AT

LA

NT

IC

RE

PL

AC

E

FU

EL

T

AN

KS

/P

IP

IN

G

MA

LS

, B

Structural Consultants 748 Lord Dunmore Drive, Suite 101 Virginia Beach, VA 23464 Phone 757-474-0612 Fax 757-474-0919

NRWENGINEERING

TN

PN

SITE PLAN - NEW WORK

SCALE: 1" = 10'

1" = 10'-0" 10' 5' 0' 10' 20' 30'

MIN MIN RTW

12908197

SI

TE

P

LA

N

- D

EM

OL

ITI

ON

A

ND

N

EW

W

OR

K

AS NOTED

E-101

06.14.24

TN

PN

SITE PLAN - EXISTING CONDITIONS AND DEMOLITION

SCALE: 1" = 10'

ELECTRICAL DEMOLITION NOTES

GENERAL: DEMOLITION DRAWINGS ARE BASED ON EXISTING PLANS AND

FIELD INVESTIGATION PRIOR TO DEMOLITION. VISIT THE EXISTING

BUILDING PRIOR TO BID IN ORDER TO BECOME FAMILIAR WITH THE

EXISTING CONDITIONS AND IN ORDER TO AVOID CONFLICTS.

DASHED ITEMS: ALL ITEMS SHOWN DASHED ON DEMOLITION PLANS ARE

EXISTING AND SHALL BE REMOVED.

SOLID ITEMS: ALL ITEMS SHOWN SOLID ON DEMOLITION PLANS ARE

EXISTING TO REMAIN.

CIRCUITING TO REMAIN: EXISTING CIRCUITING TO REMAIN SHALL BE

REROUTED OR RECONNECTED, AS REQUIRED, WHERE AFFECTED BY NEW

WORK IN ORDER TO MAINTAIN CONTINUITY OF THE CIRCUIT.

REUSE OF EXISTING CIRCUITRY: EXISTING CIRCUITRY SERVING LIGHTING

FIXTURES AND/OR EQUIPMENT FOR A GIVEN AREA SHALL BE REUSED

WHERE INDICATED TO SERVE THE NEW LAYOUT. PROVIDE CIRCUIT

MODIFICATIONS INDICATED OR AS OTHERWISE REQUIRED TO MAINTAIN

THE CONTINUITY OF EXISTING CIRCUITS THAT REMAIN.

EXISTING CONDUIT: ALL EXISTING CONDUITS AND WIRING THAT WILL NOT

BE REUSED SHALL BE REMOVED WHERE THEY WILL BE EXPOSED UPON

COMPLETION OF NEW WORK. EXISTING CONDUIT TO REMAIN CONCEALED

IN WALLS SHALL BE ABANDONED. EXISTING CONDUIT TO REMAIN BELOW

FLOOR SLAB SHALL BE CUT OFF ONE INCH BELOW ROUGH FLOOR AND

GROUTED FLUSH. ALL EXISTING WIRING IN CONDUITS TO BE ABANDONED

SHALL BE DISCONNECTED FROM POWER SOURCE AND REMOVED.

REPAIR DAMAGE: EXERCISE CARE IN REMOVAL OF DEMOLITION ITEMS.

REPAIR, AT NO ADDITIONAL COST TO THE OWNER, ANY DAMAGE CAUSED

TO EXISTING CONSTRUCTION AND/OR EQUIPMENT TO REMAIN.

ASSOCIATED APPURTENANCES: REMOVE ALL ELECTRICAL

APPURTENANCES (DISCONNECTS, STARTERS, WIRING, CONDUIT, ETC.)

ASSOCIATED WITH ITEMS TO BE REMOVED INCLUDING EQUIPMENT TO BE

REMOVED BY OTHERS.

KNOCKOUT PLUGS AND COVERS: ALL CONDUIT REMOVED SHALL BE

REMOVED IN ITS ENTIRETY, INCLUDING FITTINGS, MOUNTING DEVICES,

MOUNTING HARDWARE, ETC. PROVIDE CONDUIT PLUGS AND BLANKS FOR

ALL OPENINGS CREATED BY THE REMOVAL OF CONDUIT. PROVIDE BLANK

COVER PLATES FOR ALL OPENED OUTLET BOXES CREATED BY THE

REMOVAL OF EQUIPMENT AND/OR DEVICES

DEMOLISHED MATERIALS: ALL MATERIALS REMOVED UNDER DEMOLITION,

NOT TO BE RELOCATED OR DESIGNATED TO BE TURNED OVER TO THE

OWNER, SHALL BECOME THE PROPERTY OF THE CONTRACTOR AND

SHALL BE REMOVED COMPLETELY FROM THE SITE.

SCHEDULE OUTAGES: ALL WORK AND ALL POWER OUTAGES IN THE

EXISTING BUILDING SHALL BE SCHEDULED AT TIMES CONVENIENT TO THE

OWNER.

NOTIFICATION: NOTIFY THE OWNER PRIOR TO TURNING OFF ANY

CIRCUITS.

ABANDONED COMMUNICATIONS CABLING: ABANDONED

COMMUNICATIONS CABLING (TELEPHONE OR DATA) ABOVE THE CEILING

SHALL BE REMOVED PER NEC ARTICLE 645.

WORK NOTES

REMOVE EXISTING VEEDER-ROOT PANEL, RETAIN CIRCUITING FOR REUSE IN NEW WORK.

REMOVE ALL PROBE WIRING ASSOCIATED WITH JP-5 FUEL TANK.

EXISTING WIREWAY, CONTRACTOR TO REPLACE GASKET TO ENSURE WIREWAY IS

WEATHERPROOF.

REMOVE EXISTING VEEDER-ROOT ALARM PANEL AND EMERGENCY SHUTOFF. RETAIN

CONDUIT AND WIRE FOR REUSE IN NEW WORK.

DISCONNECT EXISTING FUEL PUMP CIRCUIT AND RETAIN CONDUIT AND WIRE FOR REUSE.

DISCONNECT AND REMOVE EXISTING 30A-2P FUEL PUMP DISCONNECT SWITCHES.

DISCONNECT AND REMOVE EXISTING FUEL PUMP ELECTRICAL CIRCUIT COMPLETE.

CONTRACTOR TO PROVIDE VEEDER-ROOT TLS-350 AND REWIRE EXISTING SENSORS AND

PROBES TO SUPPORT A COMPLETE AND OPERABLE SYSTEM. ENSURE SYSTEM IS

REPROGRAMMED TO ORIGINAL SETTINGS. CONNECT TO EXISTING CIRCUITING RETAINED

DURING DEMOLITION.

30A-2P, FU@25A, 4X FOR FUEL PUMPS. REPLACE EXISTING DISCONNECT IN-KIND AND REWIRE.

PROVIDE VEEDER-ROOT ALARM PANEL AND EMERGENCY SHUTOFF TO MATCH EXISTING.

CONNECT TO CIRCUITING RETAINED DURING DEMOLITION.

FUEL PUMP CONNECTION, 120V. CONNECT TO EXISTING CIRCUIT RETAINED DURING

DEMOLITION.

12908190
12908191
12908192
12908193
12908194
12908195
12908196
12908197