7242175 DrawingsAsOne.pdf
PDF 719 KB Posted
- Attached to
- N400857241766 Replace Rooftop Units Building 87
- Solicitation number
- N400857241766
About this file
This is a set of architectural and engineering design documents for a naval facilities project to replace rooftop HVAC equipment at Building 87 in Marine Corps Air Station Cherry Point, North Carolina. The project involves replacing two existing rooftop air handling units (RTU-1 and RTU-2) with new units that have similar specifications. The new rooftop units will have cooling capacities of 492,200 Btu/h and 612,900 Btu/h, respectively, with 9.3 and 9.1 EER ratings. Each unit will have variable frequency drives, 20 hp motors, and use R-454B refrigerant. The electrical design includes connecting the new units to the existing Main Distribution Panel (MDP), with minimal changes to the electrical infrastructure. The project is being executed by Naval Facilities Engineering Systems Command (NAVFAC) Mid-Atlantic, with a project date of April 30, 2025, and a project number of 7242175.
The comprehensive design documents include mechanical, electrical, and control system details across multiple sheets, covering demolition plans, new equipment placement, electrical riser diagrams, panel schedules, and control sequences. Key design considerations include maintaining existing building systems, ensuring proper ventilation and cooling, integrating with the existing building management system, and providing appropriate electrical connections. The new HVAC units will be connected to existing ductwork, with careful attention to maintaining proper airflow, static pressure, and building pressurization. The project also includes provisions for wind restraint, condensate drainage, and compatibility with the existing Johnson Controls Metasys control system.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Amendment 0001 7241766.pdf | ||
| 7242175 SpecsAsOne.pdf | ||
| 7241766 RFP.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
MAXIMO WORKORDER NO:
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
PROJECT NO:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S
YS
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
UN
CL
AS
SI
FI
ED
SIGNED FINAL
DEPARTMENT OF THE NAVY
NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND ~ MID-ATLANTIC
NICHOLAS A. HALL
NICHOLAS A. HALL
PATRICK FAULKNER
EE
__ ___ ___ ___ ___ ____ ___ ___ ___ ___ __A
B C D E F G H JA-430C1
G-001
CO
VE
R
SH
EE
T
AN
D
DR
AW
IN
G
IN
DE
X
DB
TWM TWM
APRIL 30, 2025
199.26
7242175
CH
ER
RY
P
OI
NT
, N
OR
TH
C
AR
OL
IN
A
MA
RI
NE
C
OR
PS
A
IR
S
TA
TI
ON
N
AV
FA
C
S
YS
C O
M M
ID
-A
TL
AN
TI
C
FR
C
-E , M
A R
IN
E
C O
R
PS
A
IR
S
TA
TI
O
N
REPLACE ROOFTOP HVAC EQUIPMENT
BUILDING 87
R E
P
LA
C E
R O
O
FT
O P
H V
A C
E Q
U
IP
M E
N T
B U
IL
D
IN
G
CHERRY POINT, NORTH CAROLINA
SIGNED FINAL
7242175
APRIL 30, 2025
12913246
SHEET LIST
NAVFAC NUMBER SHEET NUMBER SHEET NAME
GENERAL
12913246 G-001 COVER SHEET AND DRAWING INDEX
MECHANICAL
12913247 M-001 ABBREVIATIONS, LEGEND AND GENERAL NOTES
12913248 MD111 MECHANICAL ROOF PLAN -DEMOLITION
12913249 M-111 MECHANICAL ROOF PLAN - NEW WORK
12913250 M-501 DETAILS
12913251 M-601 SCHEDULES
12913252 M-701 CONTROLS
12913253 M-702 CONTROLS
ELECTRICAL
12913254 E-001 LEGEND AND ABBREVIATIONS
12913255 E-002 GENERAL NOTES
12913256 ED130 ELECTRICAL ROOF PLAN - DEMOLITION
12913257 EP110 LEVEL 1 - POWER PLAN
12913258 EP130 ELECTRICAL ROOF PLAN
12913259 EP410 ENLARGED PLANS
12913260 EP601 ELECTRICAL RISER DIAGRAMS
12913261 EP701 PANEL SCHEDULES
VICINITY PLAN LOCATION PLAN
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
PR
04/30/2025
DUCT SECTION, RECTANGULAR SUPPLY AIR
DUCT SECTION, RECTANGULAR RETURN
AIR OR OUTSIDE AIR
DUCT SECTION, RECTANGULAR EXHAUST
AIR OR RELIEF AIR
RECTANGULAR DUCT SIZE
ROUND DUCT SIZE
20x10
14Ø
POINT OF DISCONNECT
POINT OF CONNECTION
LINETYPE REPRESENTS NEW WORK TO BE
INSTALLED
LINETYPE REPRESENTS EXISTING WORK
TO REMAIN
LINETYPE REPRESENTS DEMO WORK TO
BE REMOVED
SUPPLY AIR FLOW DIRECTION
RETURN/EXHAUST AIR FLOW DIRECTION
1. PROJECT SUMMARY
THE PROJECT INVOLVES THE REPLACEMENT OF TWO PACKAGED ROOFTOP AIR HANDLING UNITS.
2. INTENT OF THE DRAWINGS
THE DRAWINGS ARE DIAGRAMMATIC AND SHOW THE GENERAL LOCATION OF DUCTWORK, PIPING, AND EQUIPMENT. THE DRAWINGS DO NOT SHOW ALL NECESSARY OFFSETS, TRANSITIONS, AND ADJUSTMENTS NECESSITATED BY COORDINATION WITH OTHER TRADES. THE COST OF ALL OFFSETS, TRANSITIONS, AND ADJUSTMENTS NECESSITATED BY
COORDINATION WITH OTHER TRADES SHALL BE INCLUDED IN THE CONTRACTOR'S BID.
3. COORDINATION WITH OTHER TRADES
EXAMINE AND REVIEW THE CONTRACT DOCUMENTS OF ALL DIVISIONS IN ORDER TO COORDINATE THE INSTALLATION OF
WORK.
USE FIELD MEASUREMENTS TO VERIFY DIMENSIONS WHERE AREAS ARE CONGESTED, AS EXACT LOCATION IS CRITICAL
TO ASSURE PROPER INSTALLATION.
COORDINATION SHALL INCLUDE, BUT SHALL NOT BE LIMITED TO, VERIFYING THE LOCATION AND SIZE OF OPENINGS IN CEILINGS AND ROOFS WITH THE INSTALLING TRADES; ALLOCATION OF SPACE WITH OTHER TRADES INSTALLING WORK IN CEILING INTERSTITIAL SPACES; AND THE PHASING OF INSTALLATION WORK WITH THAT OF OTHER TRADES.
WHERE A PRODUCT IS SUBMITTED THAT IS NOT THE BASIS OF DESIGN (WHETHER STATED IN THE DOCUMENTS OR NOT), COORDINATE THE DIFFERENCES IN THE PRODUCT THAT IMPACT OTHER TRADES WITH THE AFFECTED TRADES. THE COST IMPACT ON OTHER TRADES RESULTING FROM A PRODUCT SUBMITTAL THAT IS NOT THE BASIS OF DESIGN SHALL BE
INCLUDED IN THE CONTRACTOR'S PRICE AND SHALL NOT BE PASSED ON TO THE OWNER.
4. WORKMANSHIP
PERFORM ALL WORK IN A WORKMANLIKE MANNER TO PROVIDE A FIRST CLASS COMPLETE INSTALLATION. REMOVE, CORRECT AND REPLACE ANY WORK DEEMED UNACCEPTABLE AT THE DISCRETION OF THE CONTRACTING OFFICER.
5. EXISTING WORK
EXISTING WORK TO REMAIN IS SHOWN ON DRAWINGS AS SOLID, LIGHT LINES; EXISTING WORK TO BE REMOVED IS SHOWN
AS HEAVY DASHED LINES.
THE EXTENT OF DEMOLITION REQUIRED IS SHOWN ON DRAWINGS AS A GENERAL GUIDE. ADDITIONAL DEMOLITION MAY BE
REQUIRED.
SCHEDULE AND COORDINATE ANY TEMPORARY OR PERMANENT SHUTDOWNS OF EXISTING SYSTEMS, OR ANY PORTION THEREOF IN ADVANCE, AND INITIATE SHUTDOWN ONLY WITH THE CONCURRENCE OF THE OWNER.
ARRANGE DEMOLITION OF EXISTING WORK, NEW CONNECTIONS TO, OR MODIFICATION OF EXISTING WORK TO KEEP THE NUMBER OF SHUTDOWNS TO A MINIMUM, AND MINIMIZE THE DURATION OF EACH SHUTDOWN. SCHEDULE SHUTDOWNS FOR NIGHTS OR WEEKENDS, UNLESS APPROVED OTHERWISE BY ARCHITECT/ENGINEER AND OWNERS REPRESENTATIVE.
EXISTING DUCTWORK AND PIPING LOCATIONS AND SIZES SHOWN ARE APPROXIMATE, ARE SHOWN FOR REFERENCE ONLY, AND ARE NOT INTENDED TO BE EXACT. FIELD VERIFY EXISTING SIZES AND LOCATIONS PRIOR TO FABRICATING ANY NEW WORK. DUCTWORK BRANCH OPENINGS LEFT AFTER REMOVAL OF DUCTS SHALL BE CUT TO THE NEAREST DIVIDED FLOW FITTING, CAPPED AND SEALED AIRTIGHT (SEAL CLASS A). PIPE ENDS LEFT OPEN AFTER REMOVAL OF PIPING OR EQUIPMENT SHALL BE REMOVED BACK TO THE NEAREST DIVIDED FLOW FITTING AND CAPPED WATERTIGHT.
REPAIR ALL DAMAGED FINISHES, SURFACES, ETC.
6. EQUIPMENT
INSTALL ALL EQUIPMENT IN ACCORDANCE WITH THE MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS, THE
SPECIFICATIONS, AND APPROVED SHOP DRAWINGS.
MAINTAIN SERVICE AND OPERATING CLEARANCES AROUND ALL SIDES OF EACH PIECE OF EQUIPMENT IN ACCORDANCE
WITH THE MANUFACTURER'S PRINTED REQUIREMENTS AND RECOMMENDATIONS.
7. DUCTWORK
DUCTWORK SIZES INDICATED ON CONTRACT DOCUMENTS ARE AIR SIZE ONLY AND DO NOT INCLUDE AN ALLOWANCE FOR
LINER.
8. WIND RESTRAINT
ROOF MOUNTED EQUIPMENT, BOTH VIBRATION ISOLATED AND NON-ISOLATED, MUST HAVE SUPPORT MEMBERS DESIGNED AND ANCHORED TO BUILDING STRUCTURAL STEEL OR CONCRETE AS REQUIRED FOR WIND LOADS.
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
MAXIMO WORKORDER NO:
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
PROJECT NO:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S
YS
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
UN
CL
AS
SI
FI
ED
SIGNED FINAL
NICHOLAS A. HALL
NICHOLAS A. HALL
PATRICK FAULKNER
EE
__ ___ ___ ___ ___ ____ ___ ___ ___ ___ __A
B C D E F G H JA-430C1
M-001
AB
BR
EV
IA
TI
O
NS
, L
EG
EN
D
AN
D G
EN
ER
AL
N
O
TE
S
MCM
AJL RVG
APRIL 30, 2025
199.26
7242175
CH
ER
RY
P
OI
NT
, N
OR
TH
C
AR
OL
IN
A
MA
RI
NE
C
OR
PS
A
IR
S
TA
TI
ON
N
AV
FA
C
S
YS
C O
M M
ID
-A
TL
AN
TI
C
FR
C
-E , M
A R
IN
E
C O
R
PS
A
IR
S
TA
TI
O
N
R E
P
LA
C E
R O
O
FT
O P
H V
A C
E Q
U
IP
M E
N T
B U
IL
D
IN
G
12913247
(E) EXISTING TO REMAIN
A AMPERE
AFMS AIR FLOW MEASURING STATION
AO ANALOG OUTPUT
APD AIR PRESSURE DROP
BTU/H BRITISH THERMAL UNITS PER
HOUR
CFM CUBIC FEET PER MINUTE
CLG COOLING OR CEILING
DB DECIBEL
DN DOWN
EA EACH
EC ELECTRONICALLY COMMUTATED
EER ENERGY EFFICIENCY RATIO
EX EXISTING
F FARENHEIT
FLA FULL LOAD AMPS
FPM FEET PER MINUTE
GA GAUGE
HP HORSEPOWER
Hz HERTZ
IN INCHES
LBM POUNDS
LF LINEAR FEET
MCA MAXIMUM CIRCUIT AMPS
MERV MINIMUM EFFECTIVENESS
REPORTING VALUE
MOCP MAXIMUM OVERCURRENT
PROTECTION
N NORTH
NO NUMBER
NTS NOT TO SCALE
RA RETURN AIR
RPM REVOLUTIONS PER MINUTE
RTU ROOFTOP UNIT
SA SUPPLY AIR
TYP TYPICAL
V VOLT
VFD VARIABLE FREQUENCY DRIVE
WG WATER GAUGE
ABBREVIATIONS LEGEND GENERAL NOTES
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
EX RTU-1
EX RTU-2
(E) 69x34 RA DN
(E) 68x27 SA DN
(E) 69x42 RA DN
B C D E F G H J
(E)1 1/2"CD1
(E) 68x27 SA DN
(E)1 1/2"CD
THRU ROOF
THRU ROOF
THRU ROOF
THRU ROOF
(E) ROOF CURB
EXISTING UNIT
OPENINGS
EXISTING UNIT
OPENINGS
(E) ROOF CURB
04'8' 16' 24'8'
GRAPHIC SCALE: 1/8"GRAPHIC SCALE: = 1'-0"
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
MAXIMO WORKORDER NO:
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
PROJECT NO:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S
YS
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
UN
CL
AS
SI
FI
ED
SIGNED FINAL
NICHOLAS A. HALL
NICHOLAS A. HALL
PATRICK FAULKNER
EE
__ ___ ___ ___ ___ ____ ___ ___ ___ ___ __A
B C D E F G H JA-430C1
MD111
M
EC
HA
NI
CA
L
RO
O
F
PL
AN
-D
EM
O
LI
TI
O N
MCM
AJL RVG
APRIL 30, 2025
199.26
7242175
CH
ER
RY
P
OI
NT
, N
OR
TH
C
AR
OL
IN
A
MA
RI
NE
C
OR
PS
A
IR
S
TA
TI
ON
N
AV
FA
C
S
YS
C O
M M
ID
-A
TL
AN
TI
C
FR
C
-E , M
A R
IN
E
C O
R
PS
A
IR
S
TA
TI
O
N
R E
P
LA
C E
R O
O
FT
O P
H V
A C
E Q
U
IP
M E
N T
B U
IL
D
IN
G
12913248
GENERAL SHEET NOTES
1 TEMPORARILY CAP WEATHERTIGHT AND PROTECT SUPPLY
AND RETURN DUCT CONNECTIONS DURING DEMOLITION
FOR RE-CONNECTION. PRESERVE CONDENSATE DRAIN
PIPING FOR RE-CONNECTION. REMOVE ELECTRICAL
CONNECTION BACK TO PANELBOARD. TEMPORARILY
COVER AND PRESERVE EXISTING ROOF CURB FOR
ADAPTER FOR CONSTRUCTION.
SCALE: 1/8" = 1'-0"MD111
MECHANICAL ROOF PLAN - DEMOLITIONA1
SHEET KEYNOTES
1 DEMOLISH EQUIPMENT SUPPORT.
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
RTU-1
RTU-2
B C D E F G H J
(E)1 1/2"CD
(E) ROOF CURB
(E) ROOF CURB(E) 68x27 SA DN
(E) 69x42 RA DN
THRU ROOF
THRU ROOF
(E) 69x34 RA DN
(E) 68x27 SA DN
(E)1 1/2"CD
THRU ROOF
THRU ROOF
65x46 SA 91x25 RA
65x46 SA
91x25 RA
OPENING OPENING
OPENING
OPENING
04'8' 16' 24'8'
GRAPHIC SCALE: 1/8"GRAPHIC SCALE: = 1'-0"
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
MAXIMO WORKORDER NO:
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
PROJECT NO:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S
YS
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
UN
CL
AS
SI
FI
ED
SIGNED FINAL
NICHOLAS A. HALL
NICHOLAS A. HALL
PATRICK FAULKNER
EE
__ ___ ___ ___ ___ ____ ___ ___ ___ ___ __A
B C D E F G H JA-430C1
M-111
M
EC
HA
NI
CA
L
RO
O
F
PL
AN
NE
W
W O
RK
MCM
AJL RVG
APRIL 30, 2025
199.26
7242175
CH
ER
RY
P
OI
NT
, N
OR
TH
C
AR
OL
IN
A
MA
RI
NE
C
OR
PS
A
IR
S
TA
TI
ON
N
AV
FA
C
S
YS
C O
M M
ID
-A
TL
AN
TI
C
FR
C
-E , M
A R
IN
E
C O
R
PS
A
IR
S
TA
TI
O
N
R E
P
LA
C E
R O
O
FT
O P
H V
A C
E Q
U
IP
M E
N T
B U
IL
D
IN
G
12913249
GENERAL SHEET NOTES
1 CONNECT NEW CONDENSATE DRAINS TO EXISTING
CONDENSATE PIPING, MAINTAINING 1/8" PER FOOT SLOPE.
2 PROVIDE SPECIFIED CURB ADAPTORS TO EXISTING ROOF
CURBS.
3 CONTRACTOR TO VERIFY THE EXISTING TIMBER ROOF
TRUSS MEMBERS FOR DETERIORATION. SEE SCHEDULE
FOR EXACT UNIT WEIGHTS.
SCALE: 1/8" = 1'-0"M-111
MECHANICAL ROOF PLANA1
SHEET KEYNOTES
1 CONNECT RTU SUPPLY TO EXISTING 69x34 SUPPLY AIR
DUCT AND RTU RETURN TO EXISTING 68x27 RETURN AIR
DUCT. FIELD ADJUST DUCTWORK TO CONNECT TO NEW
RTU. TEST DUCTWORK CONNECTION FOR LEAKAGE
2 CONNECT RTU SUPPLY TO EXISTING 68x27 SUPPLY AIR DUCT AND RTU RETURN TO EXISTING 69x42 RETURN AIR
DUCT. FIELD ADJUST DUCTWORK TO CONNECT TO NEW
RTU. TEST DUCTWORK CONNECTION FOR LEAKAGE.
3 REMOVE SUPPLY DUCT SMOKE DETECTORS AND REPLACE
LIKE-IN-KIND. RECONNECT AS REQUIRED TO EXSITING
FIRE ALARM AND DDC CONTROLS.
4 DURING INSTALLATION AND ALIGNMENT OF NEW
EQUIPMENT ON EXISTING PAD, ENSURE THE EDGE OF THE
EQUIPMENT IS A MINIMUM OF 10'-0" FROM THE EDGE OF
THE BUILDING ROOF.
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
UNIT DRAIN PAN
AT COIL OUTLET
UNIT DRAIN CONNECTION
H + (1")
NOTE: CONDENSATE DRAIN PIPE SIZE SHALL BE SIZED TO MATCH
OUTLET DRAIN CONNECTION SIZE (MINIMUM 1").
SQUARE HEAD PLUGS (HAND TIGHT)
H
X = 1/2 "H"
H = MIN. 1" PLUS CASING
STATIC PRESSURE
X
TOTAL
HEIGHT OF
TRAP
TOTAL HEIGHT OF TRAP = X + H + (1 - 1/2 x PIPE DIAMETER)
(WITHOUT INSULATION)
COILS
POWER EXHAUST
BLOWER
RELIEF DAMPER
(BOTH SIDES)
SUPPLY
BLOWER FILTERS ECON
CONDENSATE DRAIN
(BOTH SIDES)
OUTSIDE AIR
RETURNSUPPLY
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
MAXIMO WORKORDER NO:
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
PROJECT NO:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S
YS
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
UN
CL
AS
SI
FI
ED
SIGNED FINAL
NICHOLAS A. HALL
NICHOLAS A. HALL
PATRICK FAULKNER
EE
__ ___ ___ ___ ___ ____ ___ ___ ___ ___ __A
B C D E F G H JA-430C1
M-501
DE
TA
IL
S
MCM
AJL RVG
APRIL 30, 2025
199.26
7242175
CH
ER
RY
P
OI
NT
, N
OR
TH
C
AR
OL
IN
A
MA
RI
NE
C
OR
PS
A
IR
S
TA
TI
ON
N
AV
FA
C
S
YS
C O
M M
ID
-A
TL
AN
TI
C
FR
C
-E , M
A R
IN
E
C O
R
PS
A
IR
S
TA
TI
O
N
R E
P
LA
C E
R O
O
FT
O P
H V
A C
E Q
U
IP
M E
N T
B U
IL
D
IN
G
12913250
SCALE: NTSM-501
ROOFTOP UNIT (RTU) DRAINB3
SCALE: NTSM-501
ROOFTOP UNIT (RTU) DETAILB1
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
MAXIMO WORKORDER NO:
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
PROJECT NO:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S
YS
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
UN
CL
AS
SI
FI
ED
SIGNED FINAL
NICHOLAS A. HALL
NICHOLAS A. HALL
PATRICK FAULKNER
EE
__ ___ ___ ___ ___ ____ ___ ___ ___ ___ __A
B C D E F G H JA-430C1
M-601
SC
HE
DU
LE
S
MCM
AJL RVG
APRIL 30, 2025
199.26
7242175
CH
ER
RY
P
OI
NT
, N
OR
TH
C
AR
OL
IN
A
MA
RI
NE
C
OR
PS
A
IR
S
TA
TI
ON
N
AV
FA
C
S
YS
C O
M M
ID
-A
TL
AN
TI
C
FR
C
-E , M
A R
IN
E
C O
R
PS
A
IR
S
TA
TI
O
N
R E
P
LA
C E
R O
O
FT
O P
H V
A C
E Q
U
IP
M E
N T
B U
IL
D
IN
G
12913251
PACKAGED ROOFTOP UNIT SCHEDULE (1 OF 5)
GENERAL ID INFO UNIT DATA FAN DATA
UNIT
No. LOCATION
NOMINAL
COOLING
CAPACITY EER
SOUND
POWER
LEVEL(dB)
SUMMER DESIGN
AMBIENT
TEMPERATURE (db)
WINTER DESIGN
AMBIENT
TEMPERATURE (db)
SUPPLY FAN DATA
REGULAR
AIRFLOW
MINIMUM
AIRFLOW
OUTSIDE AIR
AIRFLOW
TOTAL STATIC
PRESSURE
EXTERNAL
STATIC
PRESSURE
MAXIMUM
FAN SPEED
(rpm) DRIVE FAN TYPE
WHEEL
DIAMETER
AIR VOLUME
CONTROL
TYPE
NUMBER
OF
MOTORS
MOTOR
SIZE
MOTOR
SPEED
(rpm)
RTU-1 ROOF 492200 Btu/h 9.3 86 90 °F 27 °F 12100 CFM 4000 CFM 1200 CFM 3.78 in-wg 2.50 in-wg 1596 DIRECT BACKWARD CURVED PLENUM 2' - 3 13/32" VFD 1 20 hp 1760 RTU-2 ROOF 612900 Btu/h 9.1 88 90 °F 27 °F 14800 CFM 5000 CFM 1200 CFM 3.93 in-wg 2.50 in-wg 1578 DIRECT BACKWARD CURVED PLENUM 2' - 6" VFD 1 20 hp 1760
PACKAGED ROOFTOP UNIT SCHEDULE (2 OF 5)
UNIT No.
FAN DATA
RELIEF/EXHAUST FAN DATA
REGULAR
AIRFLOW
TOTAL STATIC
PRESSURE
EXTERNAL STATIC
PRESSURE
MAXIMUM FAN
SPEED (rpm) DRIVE FAN TYPE
WHEEL
DIAMETER
AIR VOLUME
CONTROL TYPE
NUMBER OF
MOTORS MOTOR SIZE MOTOR SPEED (rpm)
RTU-1 10900 CFM 1.24 in-wg 1.00 in-wg 1447 DIRECT AXIAL 2' - 11 1/2" VFD 1 5 hp 1760 RTU-2 13600 CFM 1.31 in-wg 1.00 in-wg 1629 DIRECT AXIAL 2' - 11 1/2" VFD 1 5 hp 1760
PACKAGED ROOFTOP UNIT SCHEDULE (3 OF 5)
UNIT No.
COMPRESSOR DATA AIR CONDENSER DATA
REFRIGERANT TYPE TYPE QUANTITY No. OF CIRCUITS FAN TYPE FAN QUANTITY MOTOR SIZE MOTOR SPEED (rpm)
RTU-1 R-454B SCROLL 4 2 VFD 6 1 hp 1100 RTU-2 R-454B SCROLL 4 2 VFD 6 1 hp 1100
PACKAGED ROOFTOP UNIT SCHEDULE (4 OF 5)
UNIT No.
EVAPORATOR COIL DATA
AIRFLOW EAT(db) EAT(wb) LAT(db) LAT(wb) TOTAL CAPACITY SENSIBLE CAPACITY APD FACE VELOCITY
RTU-1 12100 CFM 80.0 °F 67.0 °F 52.1 °F 52.1 °F 492200 Btu/h 325400 Btu/h 0.32 in-wg 268.9 FPM RTU-2 14800 CFM 80.0 °F 67.0 °F 51.8 °F 51.7 °F 612900 Btu/h 401000 Btu/h 0.46 in-wg 328.9 FPM
PACKAGED ROOFTOP UNIT SCHEDULE (5 OF 5)
UNIT No.
FILTER DATA UNIT ELECTRICAL DATA
OPERATING WEIGHT
PRE-FILTER FINAL FILTER
VOLTS PHASE HERTZ FLA MCA MOCPMERV RATING DEPTH MID-LIFE APD MERV RATING DEPTH MID-LIFE APD RTU-1 MERV 8 0' - 2" 0.50 in-wg MERV 13 0' - 4" 0.83 in-wg 208 V 3 60 Hz 249 A 264 A 300 A 7024 lbm RTU-2 MERV 8 0' - 2" 0.50 in-wg MERV 13 0' - 4" 1.01 in-wg 208 V 3 60 Hz 302 A 317 A 350 A 6821 lbm
REMARKS:
1. SINGLE POINT ELECTRICAL CONNECTION
2. HINGED ACCESS DOORS
3. COASTAL ENVIRONMENT COATING ON COILS
5. FACTORY PROVIDED VARIABLE FREQUENCY DRIVES
6. STAINLESS STEEL DRAIN PAN
7. BACNET COMMUNICATIONS INTERFACE
8. 110 V CONVENIENCE OUTLET
10. ELECTRICAL ACCESS THROUGH BASE
11. PROVIDE CURB ADAPTORS
12. MODULATING ECONOMIZER DAMPERS
13. ENTHALPHY CONTROL FOR ECONOMIZER
14. ULTRA LOW LEAK ECONOMIZER DAMPERS
15. RTU-1 COOLING STAGING, 1 VARIABLE SPEED COMPRESSOR AND 1 TWO STEP COMPRESSOR
16. RTU-2 COOLING STAGING, 2 VARIABLE SPEED COMPRESSORS AND 2 TWO STEP COMPRESSORS
17. 2" DEFLECTION NEOPRENE PADS ON COMPRESSORS AND FANS
DESIGN CONDITIONS SCHEDULE
WINTER SUMMER
INDOOR
DB
OUTDOOR INDOOR OUTDOOR
DB WB DB RH DB WB
68°F 27°F 27°F 78°F 50% 90°F 77°F
RTU-1 OUTDOOR AIR SCHEDULE
ZONE NAME
ROOM
NUMBER
NUMBER OF
OCCUPANTS OUTDOOR AIRFLOW
VESTIBULE 101 0 5 CFM
ENTRY 102 0 12 CFM
CONFERENCE 103 20.6 128 CFM
CONFERENCE 104 11.1 69 CFM
ADMIN 105 0.9 16 CFM
KITCHENETTE 107 2.9 21 CFM
WOMEN 108 0 0 CFM
MEN 109 0 0 CFM
SHOWER 109.5 0 0 CFM
PWD ADMIN GOOCH 110 1 17 CFM
PWD FILZEN 111 1.8 31 CFM
TOILET 112 0 0 CFM
PWD CO JAYNE 113 1.4 23 CFM
TOILET 114 0 0 CFM
CORRIDOR 115 0 25 CFM
CORRIDOR 116 0 17 CFM
CORRIDOR 117 0 25 CFM
OFFICE DOYLE 119 0.7 12 CFM
CONFERENCE 121 18.3 113 CFM
SHOWER 122 0 0 CFM
WOMEN 123 0 0 CFM
VESTIBULE 124 0 4 CFM
SHOWER 125 0 0 CFM
MEN 126 0 0 CFM
MESS 128 4.6 34 CFM
CORRIDOR 129 0 21 CFM
PWD CLERKS 130 1.4 24 CFM
PWD RUFFIN 131 0.7 13 CFM
PWD FONVILLE 132 0.7 12 CFM
FSSO/UMAC 1 133 2.9 49 CFM
FSSO/UMAC 2 133 1.9 32 CFM
FSSO RIVERS 133A 0.7 12 CFM
PWD OFFICE BEASLEY 136 0.7 13 CFM
CONST. HEAD RHODES 150 0.7 13 CFM
FEAD DEPUTY NEWTON 151 0.8 13 CFM
FEAD DIRECTOR HEADLEE 152 0.9 15 CFM
CONFERENCE 153 10.2 63 CFM
ENERGY MANAGEMENT (VACANT) 154 0.6 11 CFM
CONSTR. GUTHRIE 155 0.6 11 CFM
SCM (VACANT) 156 0.5 8 CFM
OFFICE AREA A 1 167 0.9 15 CFM
OFFICE AREA A 4 167 0.4 7 CFM
MEETING 169 0.6 10 CFM
VESTIBULE 170 0 4 CFM
NOTE: NUMBER OF OCCUPANTS IS SHOWN FOR INFORMATION ONLY.
RTU-2 OUTDOOR AIR SCHEDULE
ZONE NAME
ROOM
NUMBERS
NUMBER OF
OCCUPANTS OUTDOOR AIRFLOW
ROLLING FILES 0.7 12 CFM
KITCHENETTE 137 3.3 24 CFM
ARCH SAMUEL 138 0.8 14 CFM
CIVIL SACYNSKI 139 0.8 14 CFM
MECH FAULKNER 140 0.8 14 CFM
STORAGE 141 0 5 CFM
CONFERENCE 142 11.1 69 CFM
OFFICE AREA C1 144 2.4 41 CFM
OFFICE AREA C2 144 10.5 178 CFM
OFFICE AREA C3 144 12.5 213 CFM
ASSET MGT SARGENT 145 0.8 13 CFM
ASSET MGT FRAZIER 146 0.8 13 CFM
ASSET MGT HEAD ELLIOTT 147 0.8 14 CFM
KITCHENETTE 148 3.1 23 CFM
AQ HEAD BISHOP 149 0.8 13 CFM
FSC HEAD BLANCHARD 157 0.6 11 CFM
PWD LAWERENCE 158 0.6 11 CFM
VESTIBULE 159 0 5 CFM
OFFICE AREA B 160 10.8 184 CFM
OFFICE UNASSIGNED 161 0.6 10 CFM
CONFERENCE 162 15.4 96 CFM
VESTIBULE 164 0 4 CFM
SUPPLY 166 0 5 CFM
OFFICE AREA A 2 167 10.5 178 CFM
OFFICE AREA A 3 167 10.1 172 CFM
OFFICE AREA A 5 167 0.5 9 CFM
NOTE: NUMBER OF OCCUPANTS IS SHOWN FOR INFORMATION ONLY.
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
RETURN AIR
SUPPLY
FAN
FILTER
DPS
C
DX
FLT-P-HL
SA-T
SA-T-SP SA-FLOW
SF-SS
SF-S
SF-C
VFDOA-T
OUTSIDE
AIR
RA-RH-SP
RA-RH
MRA-D-C
M
OA-D-C
RA-T
SA-P-HLMA-T-LLOA-AFMS CLG-C
RELIEF
FAN
RF-SS
RF-S
RF-C
VFD
RELIEF AIR
M
RF-D-C
ES-BUT
EMERGENCY
SHUTDOWN
SWITCH
(EXISTING,
REUSE)
RST-BUT
EMERGENCY
RESTART
BUTTON
(EXISTING,
REUSE)
SPACE-T
SPACE-T-LL
SPACE-T-HL
SPACE
TEMPERATURE
SENSOR
(EXISTING,
REUSE)
SYS-OCC
OCCUPANCY
SCHEDULE
(EXISTING,
REUSE)
LOCATED IN ENTRY 102.
NEW RTUS MUST TIE INTO
THESE EXISTING CONTROLS.
FRZ
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
MAXIMO WORKORDER NO:
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
PROJECT NO:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S
YS
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
UN
CL
AS
SI
FI
ED
SIGNED FINAL
NICHOLAS A. HALL
NICHOLAS A. HALL
PATRICK FAULKNER
EE
__ ___ ___ ___ ___ ____ ___ ___ ___ ___ __A
B C D E F G H JA-430C1
M-701
CO
NT
RO
LS
MCM
RVG RVG
APRIL 30, 2025
199.26
7242175
CH
ER
RY
P
OI
NT
, N
OR
TH
C
AR
OL
IN
A
MA
RI
NE
C
OR
PS
A
IR
S
TA
TI
ON
N
AV
FA
C
S
YS
C O
M M
ID
-A
TL
AN
TI
C
FR
C
-E , M
A R
IN
E
C O
R
PS
A
IR
S
TA
TI
O
N
R E
P
LA
C E
R O
O
FT
O P
H V
A C
E Q
U
IP
M E
N T
B U
IL
D
IN
G
12913252
ROOFTOP AIR HANDLING UNIT SEQUENCE OF OPERATION (RTU-1,2)
RTU-1 AND -2 ARE CONTROLLED VIA PACKAGED CONTROLS. PACKAGED CONTROLLER
MUST REPORT BACK TO BUILDING BAS. CONTROLLERS MUST BE COMPATABLE WITH JCI
METASYS PROGRAM AND SYSTEMS, AND MUST TIE INTO EXISTING SNE UNIT.
NOTE: ALL CONTROL POINTS SHOWN WITHIN THE SCHEMATIC BOUNDARY ARE
INTENDED TO BE PROVIDED AS PART OF THE PACKAGED CONTROL SYSTEM WITH THE
RTU. IF THE CONTRACTOR'S PACKAGED SYSTEM DOES NOT CONTAIN ALL POINTS, THE
CONTRACTOR MUST COORDINATE WITH THE BAS VENDOR TO PROVIDE ALL
POINTS/EQUIPMENT.
OCCUPIED MODE:
THE AIR HANDLING UNIT SUPPLY FAN MUST BE STARTED AND STOPPED BY THE
ENERGY MANAGEMENT SYSTEM UNDER A TIME OF DAY SCHEDULE. THIS SCHEDULE
MUST BE MODIFIED BY A START STOP OPTIMIZATION PROGRAM DURING PULL DOWN /
WARM UP OPERATION, THE FAN MUST START AT THIS OPTIMIZED TIME, RAMP THE FAN
TO 100%, OPEN THE APPROPRIATE AHU COIL TO 100% UNTIL ALL ZONES REPORT
OCCUPIED SETPOINT HAS BEEN ACHIEVED.
UPON STARTUP ,THE SUPPLY FAN MUST RAMP UP TO SETPOlNT AND MAlNTAlN STATlC PRESSURE SETPOlNT AT THE lNDlCATED DUCT STATlC PRESSURE SENSOR. THE RELIEF
FAN SHALL TRACK THE SUPPLY FAN IN ORDER TO MAINTAIN THE BUILDING
PRESSURIZATION. THE SYSTEM MUST RUN IN THIS CONDlTON FOR 5 MlNUTES (ADJ) TO ESTABLlSH SYSTEM AND SPACE BALANCE.
NORMAL OCCUPIED OPERATION: OUTDOOR AIR DAMPER MUST OPEN, THE SUPPLY FAN
MUST MODULATE TO MAINTAIN DUCT PRESSURE, AND THE OUTSIDE AIR DAMPER MUST
MODULATE TO MAINTAIN OA CFM SETPOINT.
THE SUPPLY AIR TEMPERATURE MUST BE RESET FROM 55° F TO 65° F AS THE OUTDOOR
TEMPERATURE CHANGES FROM 70° F TO 45° F. THE DX COMPRESSORS MUST BE
SEQUENCED VIA INTERNAL CONTROL TO ACHIEVE SUPPLY AIR SETPOINT.
THE STATIC PRESSURE SENSOR IN THE SUPPLY DUCT MUST MODULATE THE VARIABLE
FREQUENCY DRIVE TO MAINTAIN THE SETPOINT ESTABLISHED DURING FINAL TESTING
AND BALANCING. MONITOR THE SUPPLY FAN HIGH STATIC AND ON INDICATION OF DUCT
STATIC PRESSURE IN EXCESS OF 3.0” WG (ADJ), STOP THE FAN, CLOSE THE OUTSIDE AIR
DAMPER AND ALARM.
ECONOMIZER
PROVIDE ECONOMIZER SEQUENCE FOR OUTDOOR AIR TEMPERATURES BETWEEN 55F
(ADJ) AND 65F (ADJ). ECONOMIZER SHALL BE EQUIPPED WITH AN AUTOMATIC LOCKOUT
WHEN THE OUTDOOR HIGH AMBIENT TEMPERATURE IS TOO HIGH FOR PROPER COOLING.
MINIMUM POSITION CONTROL SHALL BE STANDARD AND ADJUSTABLE THROUGH THE
BUILDING MANAGEMENT SYSTEM. A SPRING RETURN MOTOR SHALL ENSURE CLOSURE
OF OA DAMPERS DURING UNIT SHUTDOWN OR POWER INTERRUPTION. MECHANICAL
COOLING SHALL BE AVAILABLE TO AID THE ECONOMIZER MODE AT ANY AMBIENT.
SMOKE DETECTION & AHU SHUTDOWN:
MONITOR THE SUPPLY AIR DUCT SMOKE DETECTOR, IN COORDINATION WITH THE FIRE
ALARM SYSTEM, AND INDICATE WHEN IN ALARM.
THE BUILDING FIRE ALARM SYSTEM MUST PROVIDE AN AHU SHUT DOWN SIGNAL,
HARDWIRED TO THE AHU.
THE BUILDING FIRE ALARM SYSTEM MUST PROVIDE ONE DIGITAL OUTPUT TO THE BAS TO
INDICATE ALARM CONDITION. WIRING FOR THIS ALARM POINT MUST BE PROVIDED BY
THE BAS SUBCONTRACTOR. UPON RECEIPT OF THIS ALARM, THE BAS MUST SHUT
DOWN ALL AIR MOVING EQUIPMENT IN THE BUILDING.
HUMIDITY CONTROL
UPON A RISE IN HUMIDITY LEVEL ABOVE 55% R.H., AS SENSED BY THE RETURN DUCT
HUMIDITY SENSOR, THE SUPPLY AIR DISCHARGE TEMPERATURE SHALL RESET TO 55°F
UNTIL THE RETURN R.H. FALLS BELOW 50% THE DX COMPRESSORS MUST BE INDEXED
TO 100% BY THE BAS AND ALL VAV BOX HEATING COILS MUST BE MODULATED TO
MAINTAIN SPACE TEMPERATURE 1° F LOWER THAN THE COOLING SETPOINT.
FILTER BANKS: PROVIDE PRESSURE DIFFERENTIAL SWITCHES ACROSS ALL FILTER
BANKS AND INDICATE DIRTY FILTER STATUS BASED ON MANUFACTURERS FILTER
PRESSURE DROP DATA.
UNOCCUPIED MODE:
WHEN THE TEMPERATURE DROPS BELOW THE UNOCCUPIED LOW LIMIT SETPOINT OR
RISES ABOVE THE UNOCCUPIED HIGH LIMIT OR IF TWO OR MORE ZONES HAVE FALLEN
BELOW 50°F, THE UNIT MUST OPERATE IN PREPARATORY MODE.
WHEN THE UNIT IS DISABLED, THE SUPPLY FAN MUST RAMP DOWN AND TURN OFF. THE
DX COMPRESSORS ARE INDEXED OFF. THE OUTDOOR AIR DAMPER IS CLOSED. THE
RETURN AIR DAMPER IS OPEN.
MORNING WARM UP:
DURING MORNING WARMUP,AT A TIME DETERMINED BY OWNER AND PROGRAMMED AT
INSTALLATION, THE SUPPLY FAN SHALL OPERATE AT LOW SPEED TO CIRCULATE AIR AND
GRADUALLY INCREASE SPACE TEMPERATURE. SUPPLY TEMPERATURE SHALL BE
MONITORED, AND FAN SPEED AND COMPRESSOR SETTINGS SHALL ADJUST AS NEEDED
TO CONTINUE TEMPERATURE INCREASE. ONCE THE DESIGN TEMPERATURE LEVEL IS
REACHED, THE FAN SPEED AND COMPRESSOR SETTINGS SHALL MAINTAIN THOSE
LEVELS.
FREEZESTAT:
SHOULD THE FREEZESTAT DETECT THE OUTSIDE AIR TEMPERATURE IS AT A LEVEL THAT
WOULD HARM THE UNIT, THE SUPPLY FAN SHALL SHUT OFF, THE OUTSIDE AIR INTAKE
DAMPER SHALL CLOSE, THE COMPRESSOR SHALL SWITCH TO HEATING MODE, AND AN
ALARM SHALL BE SENT TO THE BAS. ONCE THE OUTDOOR AIR CONDITIONS ARE
VERIFIED ACCEPTABLE, THE SEQUENCE SHALL REVERSE.
ROOFTOP AIR HANDLING UNIT CONTROLS SCHEMATIC (RTU-1, -2)
NOTES:
1) COORDINATE CONTROLS WITH EXISTING INFRASTRUCTURE, INCLUDING BUT NOT LIMITED TO EMERGENCY SHUTDOWN, DUCT STATIC PRESSURE, DUCT SMOKE DETECTORS, ETC.
2) ROOFTOP MANUFACTURER SHALL PROVIDE TURN-KEY SOLUTION PACKAGE CONTROLS.
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
MAXIMO WORKORDER NO:
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
PROJECT NO:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S
YS
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
UN
CL
AS
SI
FI
ED
SIGNED FINAL
NICHOLAS A. HALL
NICHOLAS A. HALL
PATRICK FAULKNER
EE
__ ___ ___ ___ ___ ____ ___ ___ ___ ___ __A
B C D E F G H JA-430C1
M-702
CO
NT
RO
LS
MCM
RVG RVG
APRIL 30, 2025
199.26
7242175
CH
ER
RY
P
OI
NT
, N
OR
TH
C
AR
OL
IN
A
MA
RI
NE
C
OR
PS
A
IR
S
TA
TI
ON
N
AV
FA
C
S
YS
C O
M M
ID
-A
TL
AN
TI
C
FR
C
-E , M
A R
IN
E
C O
R
PS
A
IR
S
TA
TI
O
N
R E
P
LA
C E
R O
O
FT
O P
H V
A C
E Q
U
IP
M E
N T
B U
IL
D
IN
G
12913253
6) THE HVAC (ATFP) EMERGENCY SHUTOFF SWITCH IS FOUND IN ENTRY 102 AS SHOWN ON NAVFAC DRAWING 12782579 RD AND DETAIL D2 ON NAVFAC DRAWING 12782597. THE NEW HVAC EQUIPMENT NEEDS TO TIE INTO THE EXISTING EMERGENCY SHUTOFF SWITCH.
5) UNIT STATUS: SERVES AS A MONITORED POINT AT THE M&C SOFTWARE (FRONT-END) AND AS A COOLING REQUEST
4) ALARM CONDITIONS MARKED WITH AN ASTERISK (*) SHALL BE ACTIVE ONLY WHEN THE SYSTEM IS IN OCCUPIED MODE AND HAS BEEN IN OCCUPIED MODE FOR MORE THAN: * = 5 MINUTES ** = 30 MINUTES
3) SYS-OCC: AS DESCRIBED IN THE POINTS SCHEDULE INSTRUCTIONS, OVERRIDE OF SYS-OCC IS ACCOMPLISHED THROUGH THE SYSTEM SCHEDULER.
2) UNIT MANUFACTURERS PROOFS AND SAFETIES: THE CONTRACTOR SHALL SHOW EACH PROOF AND SAFETY AS A SEPARATE ROW.
1) THE CONTRACTOR SHALL COMPLETE THE POINTS SCHEDULE AS SPECIFIED AND AS DESCRIBED IN THE POINTS SCHEDULE INSTRUCTIONS DRAWING.
Notes:
OTHER POINTS FLT-P-HL MIXED AIR FILTER PRESSURE HIGH LIMIT SWITCH <___> ALM/NORMAL <___> BI ~ ~ ~ X ~ ~ TRUE crit <___>
RA-D-C RETURN AIR DAMPER COMMAND ~ <0-100%> <___> AO ~ X X X ~ X ~ ~ ~
RA-RH-SP RETURN AIR HUMIDITY SETPOINT SEE SCHED 20%-60% <___> AI ~ ~ X ~ ~ X ~ ~ ~
RA-RH RETURN AIR RELATIVE HUMIDITY ~ <___> <___> AI ~ ~ X X ~ ~ ~ ~ ~
RA-T RETURN AIR TEMPERATURE ~ <___> <___> AI ~ X X X ~ ~ ~ ~ ~
RETURN AIR
RF-C RELIEF FAN COMMAND ~ ON/OFF <___> <___> ~ X X X ~ X ~ ~ ~
CLG-C COOLING COMMAND ~ ON/OFF <___> <___> ~ X X X ~ X ~ ~ ~
SA-T-SP SUPPLY AIR TEMPERATURE SETPOINT 53 DEG F ~ <___> ~ ~ X X ~ ~ X ~ ~ ~
SA-T SUPPLY AIR TEMPERATURE ~ <___> <___> AI ~ X X X ~ ~ *SA-T MORE THAN 10 DEG F ABOVE OR BELOW SETPOINT crit <___>SUPPLY AIR
SF-C SUPPLY FAN COMMAND ~ ON/OFF <___> <___> ~ X X X ~ X ~ ~ ~
RF-D-C RELIEF AIR DAMPER COMMAND ~ <0-100%> <___> AO ~ X X X ~ X ~ ~ ~
FRZ FREEZESTAT ~ <___> <___> AI ~ X X X ~ ~ OUTSIDE AIR TEMPERATURE LOWER THAN MINIMUM crit <___> OA-AFMS OUTSIDE AIR AIR FLOW MEASURING STATION ~ <___> <___> AI ~ X X X ~ ~ INFO INFO ~
OA-D-C OUTSIDE AIR DAMPER COMMAND ~ <0-100%> <___> AO ~ X X X ~ X ~ ~ ~MIXED AIR
TEMPERATURE
CONTROL
OA-T OUTSIDE AIR TEMPERATURE ~ <___> <___> AI ~ X X X ~ ~ ~ ~ ~
SPACE-T SPACE TEMPERATURE (EXISTING) ~ <___> <___> AI ~ X X X ~ ~ ~ ~ ~
RF-SS RETURN FAN START/STOP ~ ON/OFF <___> <___> ~ X X X ~ X ~ ~ ~
SF-SS SUPPLY FAN START/STOP ~ ON/OFF <___> <___> ~ X X X ~ X ~ ~ ~
SYS-OCC OCCUPANCY INPUT (FROM SYSTEM SCHEDULER) (EXISTING) <___> <___> NVI ~ X X ~ ~ X ~ ~ ~ SPACE-T-HL SPACE TEMPERATURE HIGH LIMIT SETPOINT (EXISTING) 82 DEG F ~ <___> ~ ~ ~ X ~ ~ X ~ ~ ~
START/STOP
SPACE-T-LL SPACE TEMPERATURE LOW LIMIT SETPOINT (EXISTING) 62 DEG F ~ <___> ~ ~ ~ X ~ ~ X ~ ~ ~
RST-BUT SYSTEM RESET BUTTON (EXISTING) ~ ~ <___> <__> ~ ~ ~ ~ ~ ~ ~ ~ ~
ES-BUT EMERGENCY SHUTDOWN (EXISTING) ~ ALM/NORMAL <___> <___> ~ ~ ~ ~ ~ ~ ALM crit <___> MA-T-LL MIXED AIR TEMPERATURE LOW LIMIT (FREEZESTAT) 35 DEG F ALM/NORMAL <___> BI ~ ~ ~ X ~ ~ ALM crit <___> SA-P-HL SUPPLY AIR PRESSURE HIGH LIMIT 3 "WC ALM/NORMAL <___> BI ~ ~ ~ X ~ ~ ALM crit <___> RF-S RELIEF FAN STATUS ~ ON/OFF <___> BI ~ X X X ~ ~ RETURN FAN PROOF FAILED crit <___>
PROOFS
SAFETIES
SF-S SUPPLY FAN STATUS ~ ON/OFF <___> BI ~ X X X ~ ~ SUPPLY FAN PROOF FAILED crit <___>
FUNCTION NAME DESCRIPTION
SETTING
(WITH UNITS)
RANGE
(WITH UNITS)
nci/CPT
NAME
IO
TYPE HOA REQ'D
DISP
REQ'D
TREND
REQ'D
NODE ID: <___> LDP
VIEW
REQ'D
M&C LDP
OVRD
REQ'D
M&C
OVRD
REQ'D
ALARM CONDITION
(SEE NOTES)
ALARM
PRIORITY
M&C
ROUTING
NODE ADDRESS: Domain = <___>, Subnet = <___>, Node = <___> LDP AND M&C DISPLAY OVERRIDES ALARMS
NODE LOCATION: <___>
NODE: <DDC##>
ROOFTOP UNIT CONTROL POINTS (RTU-1, -2)
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
SYMBOL DESCRIPTION
SAFETY SWITCH
NEMA ENCLOSURE RATING
SWITCH RATING 30A-3P,15A, 3R
FUSE AMP RATING
(NF INDICATES NON-FUSED TYPE)
PANELBOARDH2R1PANEL NAME
ELECTRICAL EQUIPMENT / MOTOR
CONNECTIONS
X
X-XXX
X
X-XXX
DETAIL
NOT TO SCALE
DETAIL IDENTIFICATION
NUMBER
NUMBER OF SHEET ON
WHICH DETAIL IS DRAWN
SHEET NOTE1
REVISION NOTE INDICATOR1
CROSS REFERENCING SYMBOL
POINT OF DISCONNECT
POINT OF CONNECTION
MISCELLANEOUS SYMBOLS
SYMBOL DESCRIPTION
NUMBER OF SHEET ON
WHICH DETAIL IS INDICATED
DETAIL IDENTIFICATION
NUMBER
SYMBOL WHERE DETAIL IS TAKEN
LINETYPES
LINETYPE DESCRIPTION
LINETYPE REPRESENTS NEW WORK TO BE INSTALLED
LINETYPE REPRESENTS EXISTING WORK TO REMAIN
LINETYPE REPRESENTS DEMOLITION WORK TO BE REMOVED
NUMBER OF POLES
MISCELLANEOUS EQUIPMENT
CONNECTION
E
ELECTRICAL ABBREVIATIONS
A, AMP
AF
AFF
AFG
AHU
AIC
AT
ATS
C
CB
DISC
DN
EA
EC
EMT
FLA
FU
GFCI
GND
GRS
JB
KCMIL
LTG
MAX
MCB
MCM
MDP
MIN
MLO
MT
MTD
NEC
NEMA
NF
NIC
NTS
P
PB
P/BD
PH
PNL
RCPT
REQD
REV
RGS
RM
RMC
SP
SPD
SPEC
SW
TYP
UGND
U.N.O.
UTIL
V
WP
XFMR
AMPERE
AMPERE FRAME
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
AIR HANDLING UNIT
AMPERE INTERRUPTING CURRENT
AMPERE TRIP
AUTOMATIC TRANSFER SWITCH
CONDUIT
CIRCUIT BREAKER
DISCONNECT
DOWN
EACH
EMPTY CONDUIT
ELECTRICAL METALLIC TUBING
FULL LOAD AMPERES
FUSE, FUSED
GROUND FAULT CIRCUIT INTERRUPTER
GROUND
GALVANIZED RIGID STEEL
JUNCTION BOX
1000 CIRCULAR MILS
LIGHTING
MAXIMUM
MAIN CIRCUIT BREAKER
THOUSAND CIRCULAR MILS
MAIN DISTRIBUTION PANEL
MINIMUM, MIN
MAIN LUGS ONLY
MOUNT
MOUNTED
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION
NON-FUSED
NOT IN CONTRACT
NOT TO SCALE
POLE
PULL BOX, PUSH BUTTON
PANEL BOARD
PHASE
PANEL
RECEPTACLE
REQUIRED
REVISION
RIGID GALVANIZED STEEL
ROOM
RIGID METAL CONDUIT
SINGLE POLE
SURGE PROTECTION DEVICE (TVSS)
SPECIFICATION
SWITCH
TYPICAL
UNDERGROUND
UNLESS NOTED OTHERWISE
UTILITY
VOLT(S)
WEATHER PROOF
TRANSFORMER
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
MAXIMO WORKORDER NO:
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
PROJECT NO:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S
YS
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
UN
CL
AS
SI
FI
ED
SIGNED FINAL
NICHOLAS A. HALL
NICHOLAS A. HALL
PATRICK FAULKNER
EE
__ ___ ___ ___ ___ ____ ___ ___ ___ ___ __A
B C D E F G H JA-430C1
E-001
LE
G
EN
D
AN
D
AB
BR
EV
IA
TI
O
NS
JMW
KEA KEA
APRIL 30, 2025
199.26
7242175
CH
ER
RY
P
OI
NT
, N
OR
TH
C
AR
OL
IN
A
MA
RI
NE
C
OR
PS
A
IR
S
TA
TI
ON
N
AV
FA
C
S
YS
C O
M M
ID
-A
TL
AN
TI
C
FR
C
-E , M
A R
IN
E
C O
R
PS
A
IR
S
TA
TI
O
N
R E
P
LA
C E
R O
O
FT
O P
H V
A C
E Q
U
IP
M E
N T
B U
IL
D
IN
G
12913254
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
BUILDING GENERAL NOTES
1. CONTRACTOR SHALL VERIFY DEVICE LOCATIONS IN THE FIELD PRIOR TO ROUGH–IN.
2. ALL CONDUITS SHALL BE DE-BURRED AND PROVIDED WITH BUSHINGS TO PREVENT CABLE
DAMAGE. CONDUIT FITTINGS SHALL HAVE INSULATED THROATS.
3. ALL SPARE CONDUITS SHALL BE PROVIDED WITH PULL WIRE.
4. CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING AND SCHEDULING THE DEMOLITION
AND RELOCATION OF EXISTING ELECTRICAL SYSTEMS WITH USERS AND THE CONTRACTING
OFFICER. DOWN TIMES SHALL BE SCHEDULED IN ADVANCE TO AVOID INTERRUPTION OF
SYSTEMS. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ANY TEMPORARY SERVICES
REQUIRED FOR ALL SYSTEMS DURING DEMOLITION AND RELOCATION.
1. DEMOLITION DRAWINGS ARE BASED ON EXISTING PLANS AND FIELD INVESTIGATION. PRIOR TO DEMOLITION. VISIT THE EXISTING BUILDING PRIOR TO BID IN ORDER TO BECOME FAMILIAR WITH
THE EXISTING CONDITIONS AND IN ORDER TO AVOID CONFLICTS.
2. DASHED ITEMS: ITEMS SHOWN DASHED ON DEMOLITION PLANS ARE EXISTING AND MUST BE
REMOVED COMPLETE, INCLUDING BOXES, CONDUIT, WIRE, FASTENERS, AND ASSOCIATED
APPURTENANCES, U.N.O.
3. SOLID ITEMS: ITEMS SHOWN SOLID ON DEMOLITION PLANS ARE EXISTING TO REMAIN.
4. CIRCUITING TO REMAIN: EXISTING CIRCUITING TO REMAIN MUST BE REROUTED OR
RECONNECTED, AS REQUIRED, WHERE AFFECTED BY NEW WORK IN ORDER TO MAINTAIN
CONTINUITY OF CIRCUIT. ENSURE THAT THE CIRCUITRY THAT REMAINS IS SAFE AND CODE
COMPLIANT.
5. EXISTING CONDUIT: EXISTING CONDUITS AND WIRING THAT WILL NOT BE REUSED MUST BE
REMOVED WHERE THEY WILL BE EXPOSED UPON COMPLETION OF NEW WORK. EXISTING
CONDUIT TO REMAIN CONCEALED IN WALLS MUST BE ABANDONED.
6. REPAIR DAMAGE: EXERCISE CARE IN REMOVAL OF DEMOLITION ITEMS. REPAIR, AT NO
ADDITIONAL COST TO OWNER, ANY DAMAGE CAUSED TO EXISTING CONSTRUCTION AND/OR
EQUIPMENT TO REMAIN.
7. ASSOCIATED APPURTENANCES: REMOVE ELECTRICAL APPURTENANCES (DISCONNECTS,
STARTERS, WIRING, CONDUIT, ETC.) ASSOCIATED WITH EQUIPMENT TO BE REMOVED BY
OTHERS.
8. KNOCKOUT PLUGS AND COVERS: CONDUIT REMOVED MUST BE REMOVED IN ITS ENTIRETY,
INCLUDING FITTINGS, MOUNTING DEVICES, MOUNTING HARDWARE, ETC. PROVIDE CONDUIT
PLUGS AND BLANKS FOR OPENINGS CREATED BY THE REMOVAL OF CONDUIT. PROVIDE BLANK
COVER PLATES FOR OPENED OUTLET BOXES CREATED BY THE REMOVAL OF THE EQUIPMENT
AND/OR DEVICES.
9. DEMOLISHED MATERIALS: MATERIALS REMOVED UNDER DEMOLITION, NOT TO BE RELOCATED OR
DESIGNATED TO BE TURNED OVER TO THE OWNER, WILL BECOME PROPERTY OF THE
CONTRACTOR AND MUST BE REMOVED COMPLETELY FROM THE SITE.
10. SCHEDULE OUTAGES: WORK AND POWER OUTAGES IN THE EXISTING BUILDING MUST BE
SCHEDULED AT TIMES CONVENIENT TO THE OWNER.
11. NOTIFICATION: NOTIFY THE OWNER PRIOR TO TURNING OFF ANY CIRCUITS.
12. EXISTING CIRCUITS: IF DURING THE COURSE OF CONSTRUCTION, IT IS DETERMINED BY THE
CONTRACTOR THAT AN EXISTING CIRCUIT BECOMES SPARE, THE CONTRACTOR MUST UPDATE
THE PANELBOARD DIRECTORY TO INDICATE SUCH, EVEN IF IT IS NOT EXPLICITLY MARKED ON
THE ELECTRICAL PLANS.
POWER GENERAL NOTES
1. BRANCH CIRCUIT CONDUCTOR SIZES SHOWN ON PLANS AND PANEL SCHEDULES ARE BASED ON
VOLTAGE DROP CALCULATIONS USING APPROXIMATE CIRCUIT ROUTING PATHS. WHEN FIELD
INSTALLED BRANCH CIRCUIT CONDUCTORS FOR 120 VOLT BRANCH CIRCUITS EXCEED 100 FEET, CONDUCTORS SHALL BE NO SMALLER THAN #10 AWG. WHEN PLANS OR PANEL SCHEDULES
SHOW BRANCH CIRCUIT CONDUCTORS LARGER THAN #10 AWG, USE THE LARGER CONDUCTOR.
2. DISCONNECTING DEVICES, STARTERS, AND/OR CONTROLLERS FOR ALL MECHANICAL
EQUIPMENT SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR/VENDOR. THE ELECTRICAL
CONTRACTOR SHALL PROVIDE AND INSTALL BREAKERS, CONDUIT AND WIRE TO THE
MECHANICAL EQUIPMENT DISCONNECTING MEANS. SIZES SHOWN ON THE ELECTRICAL PLANS
ARE BASED ON DESIGN EQUIPMENT. CONTRACTOR SHALL VERIFY ACTUAL SIZES PROVIDED AND
MAKE ALL NECESSARY ADJUSTMENTS AT NO COST TO THE GOVERNMENT.
3. ALL 120 VOLT SINGLE PHASE CIRCUITS SHALL HAVE A DEDICATED NEUTRAL. MULTI-WIRE
BRANCH CIRCUITS ARE NOT ALLOWED UNLESS SPECIFICALLY NOTED OTHERWISE.
4. PLANS SHOW A SEPARATE CONDUIT FOR EACH CIRCUIT. FOR 120 VOLT SINGLE PHASE BRANCH CIRCUITS, UP TO THREE HOME RUN CIRCUITS CAN BE COMBINED IN A SINGLE CONDUIT BACK TO THE PANEL. THE AMPACITY OF EACH CONDUCTOR SHALL BE REDUCED, AND THE CONDUIT SHALL
BE SIZED PER NEC REQUIREMENTS. SIZE CONDUIT TO PROVIDE SPARE CAPACITY FOR ONE
ADDITIONAL 20 AMP CIRCUIT IN EACH CONDUIT.
5. AN EQUIPMENT GROUNDING CONDUCTOR SHALL BE INSTALLED IN EACH CONDUIT. IT SHALL BE
SIZED PER THE NEC FOR THE LARGEST OVERCURRENT DEVICE PROTECTING CONDUCTORS IN
THE CONDUIT.
POWER DEMOLITION NOTES
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
MAXIMO WORKORDER NO:
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
PROJECT NO:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S
YS
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
UN
CL
AS
SI
FI
ED
SIGNED FINAL
NICHOLAS A. HALL
NICHOLAS A. HALL
PATRICK FAULKNER
EE
__ ___ ___ ___ ___ ____ ___ ___ ___ ___ __A
B C D E F G H JA-430C1
E-002
G
EN
ER
AL
N O
TE
S
JMW
KEA KEA
APRIL 30, 2025
199.26
7242175
CH
ER
RY
P
OI
NT
, N
OR
TH
C
AR
OL
IN
A
MA
RI
NE
C
OR
PS
A
IR
S
TA
TI
ON
N
AV
FA
C
S
YS
C O
M M
ID
-A
TL
AN
TI
C
FR
C
-E , M
A R
IN
E
C O
R
PS
A
IR
S
TA
TI
O
N
R E
P
LA
C E
R O
O
FT
O P
H V
A C
E Q
U
IP
M E
N T
B U
IL
D
IN
G
12913255
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
EX RTU-1
EX RTU-2
D E F G
04'8' 16' 24'8'
GRAPHIC SCALE: 1/8"GRAPHIC SCALE: = 1'-0"
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
MAXIMO WORKORDER NO:
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
PROJECT NO:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S
YS
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
UN
CL
AS
SI
FI
ED
SIGNED FINAL
NICHOLAS A. HALL
NICHOLAS A. HALL
PATRICK FAULKNER
EE
__ ___ ___ ___ ___ ____ ___ ___ ___ ___ __A
B C D E F G H JA-430C1
ED130
EL
EC
TR
IC
AL
R
O O
F
PL
AN
DE
M
O
LI
TI
O
N
JMW
KEA KEA
APRIL 30, 2025
199.26
7242175
CH
ER
RY
P
OI
NT
, N
OR
TH
C
AR
OL
IN
A
MA
RI
NE
C
OR
PS
A
IR
S
TA
TI
ON
N
AV
FA
C
S
YS
C O
M M
ID
-A
TL
AN
TI
C
FR
C
-E , M
A R
IN
E
C O
R
PS
A
IR
S
TA
TI
O
N
R E
P
LA
C E
R O
O
FT
O P
H V
A C
E Q
U
IP
M E
N T
B U
IL
D
IN
G
12913256SCALE: 1/8" = 1'-0"ED130
ELECTRICAL ROOF PLAN - DEMOLITION1
SHEET KEYNOTES
1 REMOVE EXISTING CONDUITS AND EXISTING HOMERUN
CIRCUIT BACK TO PANEL ‘MDP’. REFER TO EP601 FOR
ADDITIONAL INFORMATION.
GENERAL SHEET NOTES
1 REFER TO SHEETS E-001 AND E-002 FOR ELECTRICAL
LEGEND, ELECTRICAL GENERAL NOTES, AND ELECTRICAL
ABBREVIATIONS.
2 REFER TO MECHANICAL DRAWINGS FOR MECHANICAL
EQUIPMENT TO BE DEMOLISHED.
3 CONTRACTOR SHALL FIELD VERIFY AND UPDATE PANEL
MDP SCHEDULE BEFORE THE COMMENCEMENT OF
DEMOLITION.
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
WOMAN
109.5
SHOWER
MEN
Room
PWD
TOILET
TOILET
113A
PWD CO
CORRIDOR
OFFICE
MECHANICAL
CONFERENCE
SHOWER
WOMEN
VEST
SHOWER
MEN
VENDING
ELECT
MESS
JAN
CORRIDOR
PWD OFFICE
KITCHENETTE
FEAD DIRECTOR
CONFERENCE
FEED DEPUTY
ENERGY MGR155
CONSTR.
CORRIDOR
OFFICE AREA A
CONST. HEAD
AQ HEAD
KITCHENETTE
ASSET MGT HEAD
VESTIBULE 146
ASSET MGT
ASSET MGT
156A
KITCHENETTE
PWD
OFFICE AREA C
FSC HEAD
160A
ROLLING FILES
SCM
OFFICE AERA B
CONFERENCE
OFFICE
VESTIBULE
SUPPLY
MEETING
VESTIBULE
ENTRY
CONFERENCE
PWD
PWD
133A Room
IT/COMM
EP410
D E F G
04'8' 16' 24'8'
GRAPHIC SCALE: 1/8"GRAPHIC SCALE: = 1'-0"
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
MAXIMO WORKORDER NO:
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
PROJECT NO:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S
YS
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
UN
CL
AS
SI
FI
ED
SIGNED FINAL
NICHOLAS A. HALL
NICHOLAS A. HALL
PATRICK FAULKNER
EE
__ ___ ___ ___ ___ ____ ___ ___ ___ ___ __A
B C D E F G H JA-430C1
EP110
LE
VE
L
-P O
W
ER
P
LA
N
JMW
KEA KEA
APRIL 30, 2025
199.26
7242175
CH
ER
RY
P
OI
NT
, N
OR
TH
C
AR
OL
IN
A
MA
RI
NE
C
OR
PS
A
IR
S
TA
TI
ON
N
AV
FA
C
S
YS
C O
M M
ID
-A
TL
AN
TI
C
FR
C
-E , M
A R
IN
E
C O
R
PS
A
IR
S
TA
TI
O
N
R E
P
LA
C E
R O
O
FT
O P
H V
A C
E Q
U
IP
M E
N T
B U
IL
D
IN
G
12913257
SCALE: 1/8" = 1'-0"EP110
LEVEL 1 - POWER PLAN1
GENERAL SHEET NOTES
1 REFER TO SHEETS E-001 AND E-002 FOR ELECTRICAL
LEGEND, ELECTRICAL GENERAL NOTES, AND ELECTRICAL
ABBREVIATIONS.
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
E
E
A
RTU-1
RTU-2
D E F G
MDP-50,52,54
MDP-34,36,38
04'8' 16' 24'8'
GRAPHIC SCALE: 1/8"GRAPHIC SCALE: = 1'-0"
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
MAXIMO WORKORDER NO:
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
PROJECT NO:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S
YS
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
UN
CL
AS
SI
FI
ED
SIGNED FINAL
NICHOLAS A. HALL
NICHOLAS A. HALL
PATRICK FAULKNER
EE
__ ___ ___ ___ ___ ____ ___ ___ ___ ___ __A
B C D E F G H JA-430C1
EP130
EL
EC
TR
IC
AL
R
O O
F
PL
AN
JMW
KEA KEA
APRIL 30, 2025
199.26
7242175
CH
ER
RY
P
OI
NT
, N
OR
TH
C
AR
OL
IN
A
MA
RI
NE
C
OR
PS
A
IR
S
TA
TI
ON
N
AV
FA
C
S
YS
C O
M M
ID
-A
TL
AN
TI
C
FR
C
-E , M
A R
IN
E
C O
R
PS
A
IR
S
TA
TI
O
N
R E
P
LA
C E
R O
O
FT
O P
H V
A C
E Q
U
IP
M E
N T
B U
IL
D
IN
G
12913258
SCALE: 1/8" = 1'-0"EP130
ELECTRICAL ROOF PLAN1
SHEET KEYNOTES
1 DISCONNECTING MEANS PROVIDED WITH MECHANICAL
UNIT.
2 REFER TO ELECTRICAL RISER DIAGRAM ON SHEET EP601
FOR MECHANICAL EQUIPMENT FEEDER SIZE.
GENERAL SHEET NOTES
1 REFER TO SHEETS E-001 AND E-002 FOR ELECTRICAL
LEGEND, ELECTRICAL GENERAL NOTES, AND ELECTRICAL
ABBREVIATIONS.
2 CONVENIENCE OUTLET PROVIDED WITH MECHANICAL
UNIT. REFER TO MECHANICAL DRAWINGS FOR ADDITIONAL
INFORMATION.
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
MECHANICAL
MDP1
F
4' 02' 8' 12'4'
GRAPHIC SCALE: 1/4"GRAPHIC SCALE: = 1'-0"
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
MAXIMO WORKORDER NO:
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
PROJECT NO:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S
YS
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
UN
CL
AS
SI
FI
ED
SIGNED FINAL
NICHOLAS A. HALL
NICHOLAS A. HALL
PATRICK FAULKNER
EE
__ ___ ___ ___ ___ ____ ___ ___ ___ ___ __A
B C D E F G H JA-430C1
EP410
EN
LA
RG
ED
P
LA
NS
JMW
KEA KEA
APRIL 30, 2025
199.26
7242175
CH
ER
RY
P
OI
NT
, N
OR
TH
C
AR
OL
IN
A
MA
RI
NE
C
OR
PS
A
IR
S
TA
TI
ON
N
AV
FA
C
S
YS
C O
M M
ID
-A
TL
AN
TI
C
FR
C
-E , M
A R
IN
E
C O
R
PS
A
IR
S
TA
TI
O
N
R E
P
LA
C E
R O
O
FT
O P
H V
A C
E Q
U
IP
M E
N T
B U
IL
D
IN
G
12913259
SHEET KEYNOTES
1 EXISTING PANEL TO REMAIN. CONTRACTOR SHALL
MAINTAIN CONTINUITY OF ALL EXISTING CIRCUITS TO
REMAIN.
GENERAL SHEET NOTES
1 REFER TO SHEETS E-001 AND E-002 FOR ELECTRICAL
LEGEND, ELECTRICAL GENERAL NOTES, AND ELECTRICAL
ABBREVIATIONS.
SCALE: 1/4" = 1'-0"EP410
ENLARGED PLAN - MECHANICAL ROOM1
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
500 KVA
PAD-MTD.
TRANSFORMER
MDP
1200A MLO
208V,3PH,4W
(E)
ATS
1200/3
(E)
EXISTING 350 KW
GENERATOR
(OPTIONAL STANDBY)
1200/3 300A MLO 150A MLO 150A MLO 150A MLO 150A MLO 150A MLO 150A MLO 150A MLO 100A MB 100A MB
(E) M
(E) A
(E) B
(E) C
(E) D
(E) F
(E) G
(E) H
(E) T1
(E) T2M
(E)
SPD
(E)
SPD
(E)
SPD
(E) (E)
EXT RTU-2EXT RTU-1
500 KVA
PAD-MTD.
TRANSFORMER
(E) MDP
1200A MLO
208V,3PH,4W
(E)
ATS
1200/3
(E)
EXISTING 350 KW
GENERATOR
(OPTIONAL STANDBY)
1200/3 300A MLO 150A MLO 150A MLO 150A MLO 150A MLO 150A MLO 150A MLO 150A MLO 100A MB 100A MB
(E) M
(E) A
(E) B
(E) C
(E) D
(E) F
(E) G
(E) H
(E) T1
(E) T2M
(E)
SPD
(E)
SPD
(E)
SPD
(E) (E)
RTU-2RTU-1
3 F4-350
F4-300
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
MAXIMO WORKORDER NO:
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
PROJECT NO:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S
YS
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
UN
CL
AS
SI
FI
ED
SIGNED FINAL
NICHOLAS A. HALL
NICHOLAS A. HALL
PATRICK FAULKNER
EE
__ ___ ___ ___ ___ ____ ___ ___ ___ ___ __A
B C D E F G H JA-430C1
EP601
EL
EC
TR
IC
AL
R
IS
ER
D
IA
G
RA
M S
JMW
KEA KEA
APRIL 30, 2025
199.26
7242175
CH
ER
RY
P
OI
NT
, N
OR
TH
C
AR
OL
IN
A
MA
RI
NE
C
OR
PS
A
IR
S
TA
TI
ON
N
AV
FA
C
S
YS
C O
M M
ID
-A
TL
AN
TI
C
FR
C
-E , M
A R
IN
E
C O
R
PS
A
IR
S
TA
TI
O
N
R E
P
LA
C E
R O
O
FT
O P
H V
A C
E Q
U
IP
M E
N T
B U
IL
D
IN
G
12913260
SCALE: NTSEP601
DEMOLITION ELECTRICAL RISER DIAGRAM1
SCALE: NTSEP601
NEW ELECTRICAL RISER DIAGRAM2
SHEET KEYNOTES
1 CONTRACTOR SHALL FIELD VERIFY AND UPDATE PANEL
SCHEDULE BEFORE THE COMMENCEMENT OF
DEMOLITION.
2 REMOVE EXISTING CONDUITS AND EXISTING FEEDER BACK
TO PANEL ‘MDP’.
3 DISCONNECTING MEANS PROVIDED WITH MECHANICAL
UNIT. REFER TO MECHANICAL DRAWINGS AND
SPECIFICATIONS FOR ADDITIONAL INFORMATION.
BRANCH CIRCUIT AND FEEDER SCHEDULE
MARK FEEDER SIZE_I RATINGS
F4-300 4#350kcmil & 1#4G - 3"C 300A (3 PHASE - 4 WIRE + GROUND) F4-350 4#500kcmil & 1#3G -3-1/2"C 350A (3 PHASE - 4 WIRE + GROUND)
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
EXISTING LOAD NEW LOAD
470.6A
EQUIPMENT LOAD SUMMARY
195A
LOAD
RTU - 1
RTU - 2
TOTAL LOAD
264A
275.6A 317A
581A
EXISTING
DEMAND LOAD
PROVIDED BY
CLIENT
120KVA * 1.25 = 150KVA
SERVICE SIZE 1200A * 1.732 * 208V * 0.8 = 345.845 KVA
NET LOAD
+69A
+41.4A
+110.4A
70.25KVA
99.29KVA
169.54KVA
95.11KVA
114.2KVA
209.31KVA
+24.86KVA
+14.77KVA
+39.63KVA
SATISFACTORY TO DATE
APPROVED
ACTIVITY
FOR COMMANDER NAVFAC
SEAL
A/E INFO
A
B
C
D
1 2 3 4 5
1 2 3 4 5
A
B
C
D
SCALE:
MAXIMO WORKORDER NO:
SHEET
NAVFAC DRAWING NO.
DES DRW CHK
OF
PROJECT NO:
D E
P
AR
TM
E
N T
O F
TH
E
N A
VY
N
A
VA
L
FA
C
IL
IT
IE
S E
N G
IN
E
E R
IN
G
S
YS
TE
M
S C
O M
M A
N D
DRAWFORM REVISION: 25 AUGUST 2020
PM/DM
BRANCH MANAGER
CHIEF ENG/ARCH
FIRE PROTECTION
NA
VA
L
FA
CI
LI
TI
ES
E
NG
IN
EE
RI
NG
S
YS
TE
M
S
CO
M M
AN
D
M
ID
-A
TL
AN
TI
C
AS NOTED
UNCLASSIFIED
UNCLASSIFIED
UN
CL
AS
SI
FI
ED
SIGNED FINAL
NICHOLAS A. HALL
NICHOLAS A. HALL
PATRICK FAULKNER
EE
__ ___ ___ ___ ___ ____ ___ ___ ___ ___ __A
B C D E F G H JA-430C1
EP701
PA
NE
L
SC
HE
DU
LE
S
JMW
KEA KEA
APRIL 30, 2025
199.26
7242175
CH
ER
RY
P
OI
NT
, N
OR
TH
C
AR
OL
IN
A
MA
RI
NE
C
OR
PS
A
IR
S
TA
TI
ON
N
AV
FA
C
S
YS
C O
M M
ID
-A
TL
AN
TI
C
FR
C
-E , M
A R
IN
E
C O
R
PS
A
IR
S
TA
TI
O
N
R E
P
LA
C E
R O
O
FT
O P
H V
A C
E Q
U
IP
M E
N T
B U
IL
D
IN
G
12913261
1. PROVIDE A NEW 350A BREAKER.
2. CONNECT RTU-1 TO EXISTING 300A BREAKER MADE AVAILABLE DURING DEMOLITION PHASE.
3. CLEARLY MARK THE EXISTING 250A BREAKER MADE AVAILABLE DURING DEMOLITION PHASE AS “SPARE”.
Notes:
Total Est. Demand Current: 1081 A Total Conn. Current: 1081 A
Total Est. Demand: 389364 VA Total Conn. Load: 389364 VA
Power 389364 VA 100.00% 389364 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Legend:
Total Amps: 1089 A 1089 A 1070 A Total Load: 130455 VA 130455 VA 128455 VA
59 1667... 2343... 60 57 1667... 2343... 58
PANEL H 150 A 3
1667... 2343...
3 250 A SPARE
53 1667... 3733... 54 51 1667... 3733... 52
PANEL F 150 A 3
1667... 3733...
3 300 A RTU-1
47 2833... 2833... 48 45 2833... 2833... 46
PANEL D 150 A 3
2833... 2833...
3 250 A PANEL M
41 2000... -- 1 -- SPACE 42
39 2000... -- 1 -- SPACE 40
PANEL C 150 A 3
2000... 4533... 38
35 2117... 4533... 36 33 2117... 4533...
3 350 A RTU-2
PANEL B 150 A 3
2117... -- 1 -- SPACE 32
29 2100... -- 1 -- SPACE 30
27 2100... 2000... 28
PANEL A 150 A 3
2100... 2000...
2 80 A D-WH-4
23 1100... 1261... 24 21 1100... 1261... 22
PANEL T2 100 A 3
1100... 1261...
3 15 A HWP-2
17 1100... -- 1 -- SPACE 18
15 1100... -- 1 -- SPACE 16
PANEL T1 100 A 3
1100... -- 1 -- SPACE 14
11 2000... -- 1 -- SPACE 12
9 2000... -- 1 -- SPACE 10
HWP-1 15 A 3
2000... -- 1 -- SPACE 8
5 0 VA 1677... 6
3 0 VA 1677... 4
SPD 60 A 3
0 VA 1677...
3 60 A EX. PANEL DP
CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT
Notes:
Enclosure: NEMA 1 MCB Rating: 1200 A Mounting: SURFACE Wires: 4 Mains Rating: 1200 A
Supply From: Phases: 3 Mains Type: MLO Location: MECHANICAL 120 Volts: 208/120 A.I.C. Rating: 22000
Branch Panel: MDP
(E) ATS
(E) ATS
SY
M
DE
SC
RI
PT
IO
N
DA
TE
AP
| 100_G-001 COVER SHEET AND DRAWING INDEX |
| 551_M-001 ABBREVIATIONS, LEGEND AND GENERAL NOTES |
| 552_MD111 MECHANICAL ROOF PLAN -DEMOLITION |
| 553_M-111 MECHANICAL ROOF PLAN - NEW WORK |
| 557_M-501 DETAILS |
| 557_M-601 SCHEDULES |
| 557_M-701 CONTROLS |
| 557_M-702 CONTROLS |
| 601_E-001 LEGEND AND ABBREVIATIONS |
| 601_E-002 GENERAL NOTES |
| 602_ED130 ELECTRICAL ROOF PLAN - DEMOLITION |
| 604_EP110 LEVEL 1 - POWER PLAN |
| 604_EP130 ELECTRICAL ROOF PLAN |
| 604_EP410 ENLARGED PLANS |
| 604_EP601 ELECTRICAL RISER DIAGRAMS |
| 604_EP701 PANEL SCHEDULES |
| 2025-06-25T21:50:11-0400 | |
| PERRY.HEATHER.MELYNN.1388599614 |
File details come from the government source that posted it. Updated .