N400857241766 Replace Rooftop Units Building 87
Solicitation number
N400857241766
Issued by

About this file

This is a set of architectural and engineering design documents for a naval facilities project to replace rooftop HVAC equipment at Building 87 in Marine Corps Air Station Cherry Point, North Carolina. The project involves replacing two existing rooftop air handling units (RTU-1 and RTU-2) with new units that have similar specifications. The new rooftop units will have cooling capacities of 492,200 Btu/h and 612,900 Btu/h, respectively, with 9.3 and 9.1 EER ratings. Each unit will have variable frequency drives, 20 hp motors, and use R-454B refrigerant. The electrical design includes connecting the new units to the existing Main Distribution Panel (MDP), with minimal changes to the electrical infrastructure. The project is being executed by Naval Facilities Engineering Systems Command (NAVFAC) Mid-Atlantic, with a project date of April 30, 2025, and a project number of 7242175.

The comprehensive design documents include mechanical, electrical, and control system details across multiple sheets, covering demolition plans, new equipment placement, electrical riser diagrams, panel schedules, and control sequences. Key design considerations include maintaining existing building systems, ensuring proper ventilation and cooling, integrating with the existing building management system, and providing appropriate electrical connections. The new HVAC units will be connected to existing ductwork, with careful attention to maintaining proper airflow, static pressure, and building pressurization. The project also includes provisions for wind restraint, condensate drainage, and compatibility with the existing Johnson Controls Metasys control system.

View the file

Other files

File Type Posted
Amendment 0001 7241766.pdf PDF
7242175 SpecsAsOne.pdf PDF
7241766 RFP.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

MAXIMO WORKORDER NO:

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

PROJECT NO:

D E

P

AR

TM

E

N T

O F

TH

E

N A

VY

N

A

VA

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S

YS

TE

M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D

M

ID

-A

TL

AN

TI

C

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CL

AS

SI

FI

ED

SIGNED FINAL

DEPARTMENT OF THE NAVY

NAVAL FACILITIES ENGINEERING SYSTEMS COMMAND ~ MID-ATLANTIC

NICHOLAS A. HALL

NICHOLAS A. HALL

PATRICK FAULKNER

EE

__ ___ ___ ___ ___ ____ ___ ___ ___ ___ __A

B C D E F G H JA-430C1

G-001

CO

VE

R

SH

EE

T

AN

D

DR

AW

IN

G

IN

DE

X

DB

TWM TWM

APRIL 30, 2025

199.26

7242175

CH

ER

RY

P

OI

NT

, N

OR

TH

C

AR

OL

IN

A

MA

RI

NE

C

OR

PS

A

IR

S

TA

TI

ON

N

AV

FA

C

S

YS

C O

M M

ID

-A

TL

AN

TI

C

FR

C

-E , M

A R

IN

E

C O

R

PS

A

IR

S

TA

TI

O

N

REPLACE ROOFTOP HVAC EQUIPMENT

BUILDING 87

R E

P

LA

C E

R O

O

FT

O P

H V

A C

E Q

U

IP

M E

N T

B U

IL

D

IN

G

CHERRY POINT, NORTH CAROLINA

SIGNED FINAL

7242175

APRIL 30, 2025

12913246

SHEET LIST

NAVFAC NUMBER SHEET NUMBER SHEET NAME

GENERAL

12913246 G-001 COVER SHEET AND DRAWING INDEX

MECHANICAL

12913247 M-001 ABBREVIATIONS, LEGEND AND GENERAL NOTES

12913248 MD111 MECHANICAL ROOF PLAN -DEMOLITION

12913249 M-111 MECHANICAL ROOF PLAN - NEW WORK

12913250 M-501 DETAILS

12913251 M-601 SCHEDULES

12913252 M-701 CONTROLS

12913253 M-702 CONTROLS

ELECTRICAL

12913254 E-001 LEGEND AND ABBREVIATIONS

12913255 E-002 GENERAL NOTES

12913256 ED130 ELECTRICAL ROOF PLAN - DEMOLITION

12913257 EP110 LEVEL 1 - POWER PLAN

12913258 EP130 ELECTRICAL ROOF PLAN

12913259 EP410 ENLARGED PLANS

12913260 EP601 ELECTRICAL RISER DIAGRAMS

12913261 EP701 PANEL SCHEDULES

VICINITY PLAN LOCATION PLAN

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

PR

04/30/2025

DUCT SECTION, RECTANGULAR SUPPLY AIR

DUCT SECTION, RECTANGULAR RETURN

AIR OR OUTSIDE AIR

DUCT SECTION, RECTANGULAR EXHAUST

AIR OR RELIEF AIR

RECTANGULAR DUCT SIZE

ROUND DUCT SIZE

20x10

14Ø

POINT OF DISCONNECT

POINT OF CONNECTION

LINETYPE REPRESENTS NEW WORK TO BE

INSTALLED

LINETYPE REPRESENTS EXISTING WORK

TO REMAIN

LINETYPE REPRESENTS DEMO WORK TO

BE REMOVED

SUPPLY AIR FLOW DIRECTION

RETURN/EXHAUST AIR FLOW DIRECTION

1. PROJECT SUMMARY

THE PROJECT INVOLVES THE REPLACEMENT OF TWO PACKAGED ROOFTOP AIR HANDLING UNITS.

2. INTENT OF THE DRAWINGS

THE DRAWINGS ARE DIAGRAMMATIC AND SHOW THE GENERAL LOCATION OF DUCTWORK, PIPING, AND EQUIPMENT. THE DRAWINGS DO NOT SHOW ALL NECESSARY OFFSETS, TRANSITIONS, AND ADJUSTMENTS NECESSITATED BY COORDINATION WITH OTHER TRADES. THE COST OF ALL OFFSETS, TRANSITIONS, AND ADJUSTMENTS NECESSITATED BY

COORDINATION WITH OTHER TRADES SHALL BE INCLUDED IN THE CONTRACTOR'S BID.

3. COORDINATION WITH OTHER TRADES

EXAMINE AND REVIEW THE CONTRACT DOCUMENTS OF ALL DIVISIONS IN ORDER TO COORDINATE THE INSTALLATION OF

WORK.

USE FIELD MEASUREMENTS TO VERIFY DIMENSIONS WHERE AREAS ARE CONGESTED, AS EXACT LOCATION IS CRITICAL

TO ASSURE PROPER INSTALLATION.

COORDINATION SHALL INCLUDE, BUT SHALL NOT BE LIMITED TO, VERIFYING THE LOCATION AND SIZE OF OPENINGS IN CEILINGS AND ROOFS WITH THE INSTALLING TRADES; ALLOCATION OF SPACE WITH OTHER TRADES INSTALLING WORK IN CEILING INTERSTITIAL SPACES; AND THE PHASING OF INSTALLATION WORK WITH THAT OF OTHER TRADES.

WHERE A PRODUCT IS SUBMITTED THAT IS NOT THE BASIS OF DESIGN (WHETHER STATED IN THE DOCUMENTS OR NOT), COORDINATE THE DIFFERENCES IN THE PRODUCT THAT IMPACT OTHER TRADES WITH THE AFFECTED TRADES. THE COST IMPACT ON OTHER TRADES RESULTING FROM A PRODUCT SUBMITTAL THAT IS NOT THE BASIS OF DESIGN SHALL BE

INCLUDED IN THE CONTRACTOR'S PRICE AND SHALL NOT BE PASSED ON TO THE OWNER.

4. WORKMANSHIP

PERFORM ALL WORK IN A WORKMANLIKE MANNER TO PROVIDE A FIRST CLASS COMPLETE INSTALLATION. REMOVE, CORRECT AND REPLACE ANY WORK DEEMED UNACCEPTABLE AT THE DISCRETION OF THE CONTRACTING OFFICER.

5. EXISTING WORK

EXISTING WORK TO REMAIN IS SHOWN ON DRAWINGS AS SOLID, LIGHT LINES; EXISTING WORK TO BE REMOVED IS SHOWN

AS HEAVY DASHED LINES.

THE EXTENT OF DEMOLITION REQUIRED IS SHOWN ON DRAWINGS AS A GENERAL GUIDE. ADDITIONAL DEMOLITION MAY BE

REQUIRED.

SCHEDULE AND COORDINATE ANY TEMPORARY OR PERMANENT SHUTDOWNS OF EXISTING SYSTEMS, OR ANY PORTION THEREOF IN ADVANCE, AND INITIATE SHUTDOWN ONLY WITH THE CONCURRENCE OF THE OWNER.

ARRANGE DEMOLITION OF EXISTING WORK, NEW CONNECTIONS TO, OR MODIFICATION OF EXISTING WORK TO KEEP THE NUMBER OF SHUTDOWNS TO A MINIMUM, AND MINIMIZE THE DURATION OF EACH SHUTDOWN. SCHEDULE SHUTDOWNS FOR NIGHTS OR WEEKENDS, UNLESS APPROVED OTHERWISE BY ARCHITECT/ENGINEER AND OWNERS REPRESENTATIVE.

EXISTING DUCTWORK AND PIPING LOCATIONS AND SIZES SHOWN ARE APPROXIMATE, ARE SHOWN FOR REFERENCE ONLY, AND ARE NOT INTENDED TO BE EXACT. FIELD VERIFY EXISTING SIZES AND LOCATIONS PRIOR TO FABRICATING ANY NEW WORK. DUCTWORK BRANCH OPENINGS LEFT AFTER REMOVAL OF DUCTS SHALL BE CUT TO THE NEAREST DIVIDED FLOW FITTING, CAPPED AND SEALED AIRTIGHT (SEAL CLASS A). PIPE ENDS LEFT OPEN AFTER REMOVAL OF PIPING OR EQUIPMENT SHALL BE REMOVED BACK TO THE NEAREST DIVIDED FLOW FITTING AND CAPPED WATERTIGHT.

REPAIR ALL DAMAGED FINISHES, SURFACES, ETC.

6. EQUIPMENT

INSTALL ALL EQUIPMENT IN ACCORDANCE WITH THE MANUFACTURER'S PRINTED INSTALLATION INSTRUCTIONS, THE

SPECIFICATIONS, AND APPROVED SHOP DRAWINGS.

MAINTAIN SERVICE AND OPERATING CLEARANCES AROUND ALL SIDES OF EACH PIECE OF EQUIPMENT IN ACCORDANCE

WITH THE MANUFACTURER'S PRINTED REQUIREMENTS AND RECOMMENDATIONS.

7. DUCTWORK

DUCTWORK SIZES INDICATED ON CONTRACT DOCUMENTS ARE AIR SIZE ONLY AND DO NOT INCLUDE AN ALLOWANCE FOR

LINER.

8. WIND RESTRAINT

ROOF MOUNTED EQUIPMENT, BOTH VIBRATION ISOLATED AND NON-ISOLATED, MUST HAVE SUPPORT MEMBERS DESIGNED AND ANCHORED TO BUILDING STRUCTURAL STEEL OR CONCRETE AS REQUIRED FOR WIND LOADS.

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

MAXIMO WORKORDER NO:

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

PROJECT NO:

D E

P

AR

TM

E

N T

O F

TH

E

N A

VY

N

A

VA

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S

YS

TE

M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D

M

ID

-A

TL

AN

TI

C

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CL

AS

SI

FI

ED

SIGNED FINAL

NICHOLAS A. HALL

NICHOLAS A. HALL

PATRICK FAULKNER

EE

__ ___ ___ ___ ___ ____ ___ ___ ___ ___ __A

B C D E F G H JA-430C1

M-001

AB

BR

EV

IA

TI

O

NS

, L

EG

EN

D

AN

D G

EN

ER

AL

N

O

TE

S

MCM

AJL RVG

APRIL 30, 2025

199.26

7242175

CH

ER

RY

P

OI

NT

, N

OR

TH

C

AR

OL

IN

A

MA

RI

NE

C

OR

PS

A

IR

S

TA

TI

ON

N

AV

FA

C

S

YS

C O

M M

ID

-A

TL

AN

TI

C

FR

C

-E , M

A R

IN

E

C O

R

PS

A

IR

S

TA

TI

O

N

R E

P

LA

C E

R O

O

FT

O P

H V

A C

E Q

U

IP

M E

N T

B U

IL

D

IN

G

12913247

(E) EXISTING TO REMAIN

A AMPERE

AFMS AIR FLOW MEASURING STATION

AO ANALOG OUTPUT

APD AIR PRESSURE DROP

BTU/H BRITISH THERMAL UNITS PER

HOUR

CFM CUBIC FEET PER MINUTE

CLG COOLING OR CEILING

DB DECIBEL

DN DOWN

EA EACH

EC ELECTRONICALLY COMMUTATED

EER ENERGY EFFICIENCY RATIO

EX EXISTING

F FARENHEIT

FLA FULL LOAD AMPS

FPM FEET PER MINUTE

GA GAUGE

HP HORSEPOWER

Hz HERTZ

IN INCHES

LBM POUNDS

LF LINEAR FEET

MCA MAXIMUM CIRCUIT AMPS

MERV MINIMUM EFFECTIVENESS

REPORTING VALUE

MOCP MAXIMUM OVERCURRENT

PROTECTION

N NORTH

NO NUMBER

NTS NOT TO SCALE

RA RETURN AIR

RPM REVOLUTIONS PER MINUTE

RTU ROOFTOP UNIT

SA SUPPLY AIR

TYP TYPICAL

V VOLT

VFD VARIABLE FREQUENCY DRIVE

WG WATER GAUGE

ABBREVIATIONS LEGEND GENERAL NOTES

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

EX RTU-1

EX RTU-2

(E) 69x34 RA DN

(E) 68x27 SA DN

(E) 69x42 RA DN

B C D E F G H J

(E)1 1/2"CD1

(E) 68x27 SA DN

(E)1 1/2"CD

THRU ROOF

THRU ROOF

THRU ROOF

THRU ROOF

(E) ROOF CURB

EXISTING UNIT

OPENINGS

EXISTING UNIT

OPENINGS

(E) ROOF CURB

04'8' 16' 24'8'

GRAPHIC SCALE: 1/8"GRAPHIC SCALE: = 1'-0"

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

MAXIMO WORKORDER NO:

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

PROJECT NO:

D E

P

AR

TM

E

N T

O F

TH

E

N A

VY

N

A

VA

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S

YS

TE

M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D

M

ID

-A

TL

AN

TI

C

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CL

AS

SI

FI

ED

SIGNED FINAL

NICHOLAS A. HALL

NICHOLAS A. HALL

PATRICK FAULKNER

EE

__ ___ ___ ___ ___ ____ ___ ___ ___ ___ __A

B C D E F G H JA-430C1

MD111

M

EC

HA

NI

CA

L

RO

O

F

PL

AN

-D

EM

O

LI

TI

O N

MCM

AJL RVG

APRIL 30, 2025

199.26

7242175

CH

ER

RY

P

OI

NT

, N

OR

TH

C

AR

OL

IN

A

MA

RI

NE

C

OR

PS

A

IR

S

TA

TI

ON

N

AV

FA

C

S

YS

C O

M M

ID

-A

TL

AN

TI

C

FR

C

-E , M

A R

IN

E

C O

R

PS

A

IR

S

TA

TI

O

N

R E

P

LA

C E

R O

O

FT

O P

H V

A C

E Q

U

IP

M E

N T

B U

IL

D

IN

G

12913248

GENERAL SHEET NOTES

1 TEMPORARILY CAP WEATHERTIGHT AND PROTECT SUPPLY

AND RETURN DUCT CONNECTIONS DURING DEMOLITION

FOR RE-CONNECTION. PRESERVE CONDENSATE DRAIN

PIPING FOR RE-CONNECTION. REMOVE ELECTRICAL

CONNECTION BACK TO PANELBOARD. TEMPORARILY

COVER AND PRESERVE EXISTING ROOF CURB FOR

ADAPTER FOR CONSTRUCTION.

SCALE: 1/8" = 1'-0"MD111

MECHANICAL ROOF PLAN - DEMOLITIONA1

SHEET KEYNOTES

1 DEMOLISH EQUIPMENT SUPPORT.

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

RTU-1

RTU-2

B C D E F G H J

(E)1 1/2"CD

(E) ROOF CURB

(E) ROOF CURB(E) 68x27 SA DN

(E) 69x42 RA DN

THRU ROOF

THRU ROOF

(E) 69x34 RA DN

(E) 68x27 SA DN

(E)1 1/2"CD

THRU ROOF

THRU ROOF

65x46 SA 91x25 RA

65x46 SA

91x25 RA

OPENING OPENING

OPENING

OPENING

04'8' 16' 24'8'

GRAPHIC SCALE: 1/8"GRAPHIC SCALE: = 1'-0"

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

MAXIMO WORKORDER NO:

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

PROJECT NO:

D E

P

AR

TM

E

N T

O F

TH

E

N A

VY

N

A

VA

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S

YS

TE

M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D

M

ID

-A

TL

AN

TI

C

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CL

AS

SI

FI

ED

SIGNED FINAL

NICHOLAS A. HALL

NICHOLAS A. HALL

PATRICK FAULKNER

EE

__ ___ ___ ___ ___ ____ ___ ___ ___ ___ __A

B C D E F G H JA-430C1

M-111

M

EC

HA

NI

CA

L

RO

O

F

PL

AN

NE

W

W O

RK

MCM

AJL RVG

APRIL 30, 2025

199.26

7242175

CH

ER

RY

P

OI

NT

, N

OR

TH

C

AR

OL

IN

A

MA

RI

NE

C

OR

PS

A

IR

S

TA

TI

ON

N

AV

FA

C

S

YS

C O

M M

ID

-A

TL

AN

TI

C

FR

C

-E , M

A R

IN

E

C O

R

PS

A

IR

S

TA

TI

O

N

R E

P

LA

C E

R O

O

FT

O P

H V

A C

E Q

U

IP

M E

N T

B U

IL

D

IN

G

12913249

GENERAL SHEET NOTES

1 CONNECT NEW CONDENSATE DRAINS TO EXISTING

CONDENSATE PIPING, MAINTAINING 1/8" PER FOOT SLOPE.

2 PROVIDE SPECIFIED CURB ADAPTORS TO EXISTING ROOF

CURBS.

3 CONTRACTOR TO VERIFY THE EXISTING TIMBER ROOF

TRUSS MEMBERS FOR DETERIORATION. SEE SCHEDULE

FOR EXACT UNIT WEIGHTS.

SCALE: 1/8" = 1'-0"M-111

MECHANICAL ROOF PLANA1

SHEET KEYNOTES

1 CONNECT RTU SUPPLY TO EXISTING 69x34 SUPPLY AIR

DUCT AND RTU RETURN TO EXISTING 68x27 RETURN AIR

DUCT. FIELD ADJUST DUCTWORK TO CONNECT TO NEW

RTU. TEST DUCTWORK CONNECTION FOR LEAKAGE

2 CONNECT RTU SUPPLY TO EXISTING 68x27 SUPPLY AIR DUCT AND RTU RETURN TO EXISTING 69x42 RETURN AIR

DUCT. FIELD ADJUST DUCTWORK TO CONNECT TO NEW

RTU. TEST DUCTWORK CONNECTION FOR LEAKAGE.

3 REMOVE SUPPLY DUCT SMOKE DETECTORS AND REPLACE

LIKE-IN-KIND. RECONNECT AS REQUIRED TO EXSITING

FIRE ALARM AND DDC CONTROLS.

4 DURING INSTALLATION AND ALIGNMENT OF NEW

EQUIPMENT ON EXISTING PAD, ENSURE THE EDGE OF THE

EQUIPMENT IS A MINIMUM OF 10'-0" FROM THE EDGE OF

THE BUILDING ROOF.

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

UNIT DRAIN PAN

AT COIL OUTLET

UNIT DRAIN CONNECTION

H + (1")

NOTE: CONDENSATE DRAIN PIPE SIZE SHALL BE SIZED TO MATCH

OUTLET DRAIN CONNECTION SIZE (MINIMUM 1").

SQUARE HEAD PLUGS (HAND TIGHT)

H

X = 1/2 "H"

H = MIN. 1" PLUS CASING

STATIC PRESSURE

X

TOTAL

HEIGHT OF

TRAP

TOTAL HEIGHT OF TRAP = X + H + (1 - 1/2 x PIPE DIAMETER)

(WITHOUT INSULATION)

COILS

POWER EXHAUST

BLOWER

RELIEF DAMPER

(BOTH SIDES)

SUPPLY

BLOWER FILTERS ECON

CONDENSATE DRAIN

(BOTH SIDES)

OUTSIDE AIR

RETURNSUPPLY

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

MAXIMO WORKORDER NO:

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

PROJECT NO:

D E

P

AR

TM

E

N T

O F

TH

E

N A

VY

N

A

VA

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S

YS

TE

M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D

M

ID

-A

TL

AN

TI

C

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CL

AS

SI

FI

ED

SIGNED FINAL

NICHOLAS A. HALL

NICHOLAS A. HALL

PATRICK FAULKNER

EE

__ ___ ___ ___ ___ ____ ___ ___ ___ ___ __A

B C D E F G H JA-430C1

M-501

DE

TA

IL

S

MCM

AJL RVG

APRIL 30, 2025

199.26

7242175

CH

ER

RY

P

OI

NT

, N

OR

TH

C

AR

OL

IN

A

MA

RI

NE

C

OR

PS

A

IR

S

TA

TI

ON

N

AV

FA

C

S

YS

C O

M M

ID

-A

TL

AN

TI

C

FR

C

-E , M

A R

IN

E

C O

R

PS

A

IR

S

TA

TI

O

N

R E

P

LA

C E

R O

O

FT

O P

H V

A C

E Q

U

IP

M E

N T

B U

IL

D

IN

G

12913250

SCALE: NTSM-501

ROOFTOP UNIT (RTU) DRAINB3

SCALE: NTSM-501

ROOFTOP UNIT (RTU) DETAILB1

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

MAXIMO WORKORDER NO:

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

PROJECT NO:

D E

P

AR

TM

E

N T

O F

TH

E

N A

VY

N

A

VA

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S

YS

TE

M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D

M

ID

-A

TL

AN

TI

C

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CL

AS

SI

FI

ED

SIGNED FINAL

NICHOLAS A. HALL

NICHOLAS A. HALL

PATRICK FAULKNER

EE

__ ___ ___ ___ ___ ____ ___ ___ ___ ___ __A

B C D E F G H JA-430C1

M-601

SC

HE

DU

LE

S

MCM

AJL RVG

APRIL 30, 2025

199.26

7242175

CH

ER

RY

P

OI

NT

, N

OR

TH

C

AR

OL

IN

A

MA

RI

NE

C

OR

PS

A

IR

S

TA

TI

ON

N

AV

FA

C

S

YS

C O

M M

ID

-A

TL

AN

TI

C

FR

C

-E , M

A R

IN

E

C O

R

PS

A

IR

S

TA

TI

O

N

R E

P

LA

C E

R O

O

FT

O P

H V

A C

E Q

U

IP

M E

N T

B U

IL

D

IN

G

12913251

PACKAGED ROOFTOP UNIT SCHEDULE (1 OF 5)

GENERAL ID INFO UNIT DATA FAN DATA

UNIT

No. LOCATION

NOMINAL

COOLING

CAPACITY EER

SOUND

POWER

LEVEL(dB)

SUMMER DESIGN

AMBIENT

TEMPERATURE (db)

WINTER DESIGN

AMBIENT

TEMPERATURE (db)

SUPPLY FAN DATA

REGULAR

AIRFLOW

MINIMUM

AIRFLOW

OUTSIDE AIR

AIRFLOW

TOTAL STATIC

PRESSURE

EXTERNAL

STATIC

PRESSURE

MAXIMUM

FAN SPEED

(rpm) DRIVE FAN TYPE

WHEEL

DIAMETER

AIR VOLUME

CONTROL

TYPE

NUMBER

OF

MOTORS

MOTOR

SIZE

MOTOR

SPEED

(rpm)

RTU-1 ROOF 492200 Btu/h 9.3 86 90 °F 27 °F 12100 CFM 4000 CFM 1200 CFM 3.78 in-wg 2.50 in-wg 1596 DIRECT BACKWARD CURVED PLENUM 2' - 3 13/32" VFD 1 20 hp 1760 RTU-2 ROOF 612900 Btu/h 9.1 88 90 °F 27 °F 14800 CFM 5000 CFM 1200 CFM 3.93 in-wg 2.50 in-wg 1578 DIRECT BACKWARD CURVED PLENUM 2' - 6" VFD 1 20 hp 1760

PACKAGED ROOFTOP UNIT SCHEDULE (2 OF 5)

UNIT No.

FAN DATA

RELIEF/EXHAUST FAN DATA

REGULAR

AIRFLOW

TOTAL STATIC

PRESSURE

EXTERNAL STATIC

PRESSURE

MAXIMUM FAN

SPEED (rpm) DRIVE FAN TYPE

WHEEL

DIAMETER

AIR VOLUME

CONTROL TYPE

NUMBER OF

MOTORS MOTOR SIZE MOTOR SPEED (rpm)

RTU-1 10900 CFM 1.24 in-wg 1.00 in-wg 1447 DIRECT AXIAL 2' - 11 1/2" VFD 1 5 hp 1760 RTU-2 13600 CFM 1.31 in-wg 1.00 in-wg 1629 DIRECT AXIAL 2' - 11 1/2" VFD 1 5 hp 1760

PACKAGED ROOFTOP UNIT SCHEDULE (3 OF 5)

UNIT No.

COMPRESSOR DATA AIR CONDENSER DATA

REFRIGERANT TYPE TYPE QUANTITY No. OF CIRCUITS FAN TYPE FAN QUANTITY MOTOR SIZE MOTOR SPEED (rpm)

RTU-1 R-454B SCROLL 4 2 VFD 6 1 hp 1100 RTU-2 R-454B SCROLL 4 2 VFD 6 1 hp 1100

PACKAGED ROOFTOP UNIT SCHEDULE (4 OF 5)

UNIT No.

EVAPORATOR COIL DATA

AIRFLOW EAT(db) EAT(wb) LAT(db) LAT(wb) TOTAL CAPACITY SENSIBLE CAPACITY APD FACE VELOCITY

RTU-1 12100 CFM 80.0 °F 67.0 °F 52.1 °F 52.1 °F 492200 Btu/h 325400 Btu/h 0.32 in-wg 268.9 FPM RTU-2 14800 CFM 80.0 °F 67.0 °F 51.8 °F 51.7 °F 612900 Btu/h 401000 Btu/h 0.46 in-wg 328.9 FPM

PACKAGED ROOFTOP UNIT SCHEDULE (5 OF 5)

UNIT No.

FILTER DATA UNIT ELECTRICAL DATA

OPERATING WEIGHT

PRE-FILTER FINAL FILTER

VOLTS PHASE HERTZ FLA MCA MOCPMERV RATING DEPTH MID-LIFE APD MERV RATING DEPTH MID-LIFE APD RTU-1 MERV 8 0' - 2" 0.50 in-wg MERV 13 0' - 4" 0.83 in-wg 208 V 3 60 Hz 249 A 264 A 300 A 7024 lbm RTU-2 MERV 8 0' - 2" 0.50 in-wg MERV 13 0' - 4" 1.01 in-wg 208 V 3 60 Hz 302 A 317 A 350 A 6821 lbm

REMARKS:

1. SINGLE POINT ELECTRICAL CONNECTION

2. HINGED ACCESS DOORS

3. COASTAL ENVIRONMENT COATING ON COILS

5. FACTORY PROVIDED VARIABLE FREQUENCY DRIVES

6. STAINLESS STEEL DRAIN PAN

7. BACNET COMMUNICATIONS INTERFACE

8. 110 V CONVENIENCE OUTLET

10. ELECTRICAL ACCESS THROUGH BASE

11. PROVIDE CURB ADAPTORS

12. MODULATING ECONOMIZER DAMPERS

13. ENTHALPHY CONTROL FOR ECONOMIZER

14. ULTRA LOW LEAK ECONOMIZER DAMPERS

15. RTU-1 COOLING STAGING, 1 VARIABLE SPEED COMPRESSOR AND 1 TWO STEP COMPRESSOR

16. RTU-2 COOLING STAGING, 2 VARIABLE SPEED COMPRESSORS AND 2 TWO STEP COMPRESSORS

17. 2" DEFLECTION NEOPRENE PADS ON COMPRESSORS AND FANS

DESIGN CONDITIONS SCHEDULE

WINTER SUMMER

INDOOR

DB

OUTDOOR INDOOR OUTDOOR

DB WB DB RH DB WB

68°F 27°F 27°F 78°F 50% 90°F 77°F

RTU-1 OUTDOOR AIR SCHEDULE

ZONE NAME

ROOM

NUMBER

NUMBER OF

OCCUPANTS OUTDOOR AIRFLOW

VESTIBULE 101 0 5 CFM

ENTRY 102 0 12 CFM

CONFERENCE 103 20.6 128 CFM

CONFERENCE 104 11.1 69 CFM

ADMIN 105 0.9 16 CFM

KITCHENETTE 107 2.9 21 CFM

WOMEN 108 0 0 CFM

MEN 109 0 0 CFM

SHOWER 109.5 0 0 CFM

PWD ADMIN GOOCH 110 1 17 CFM

PWD FILZEN 111 1.8 31 CFM

TOILET 112 0 0 CFM

PWD CO JAYNE 113 1.4 23 CFM

TOILET 114 0 0 CFM

CORRIDOR 115 0 25 CFM

CORRIDOR 116 0 17 CFM

CORRIDOR 117 0 25 CFM

OFFICE DOYLE 119 0.7 12 CFM

CONFERENCE 121 18.3 113 CFM

SHOWER 122 0 0 CFM

WOMEN 123 0 0 CFM

VESTIBULE 124 0 4 CFM

SHOWER 125 0 0 CFM

MEN 126 0 0 CFM

MESS 128 4.6 34 CFM

CORRIDOR 129 0 21 CFM

PWD CLERKS 130 1.4 24 CFM

PWD RUFFIN 131 0.7 13 CFM

PWD FONVILLE 132 0.7 12 CFM

FSSO/UMAC 1 133 2.9 49 CFM

FSSO/UMAC 2 133 1.9 32 CFM

FSSO RIVERS 133A 0.7 12 CFM

PWD OFFICE BEASLEY 136 0.7 13 CFM

CONST. HEAD RHODES 150 0.7 13 CFM

FEAD DEPUTY NEWTON 151 0.8 13 CFM

FEAD DIRECTOR HEADLEE 152 0.9 15 CFM

CONFERENCE 153 10.2 63 CFM

ENERGY MANAGEMENT (VACANT) 154 0.6 11 CFM

CONSTR. GUTHRIE 155 0.6 11 CFM

SCM (VACANT) 156 0.5 8 CFM

OFFICE AREA A 1 167 0.9 15 CFM

OFFICE AREA A 4 167 0.4 7 CFM

MEETING 169 0.6 10 CFM

VESTIBULE 170 0 4 CFM

NOTE: NUMBER OF OCCUPANTS IS SHOWN FOR INFORMATION ONLY.

RTU-2 OUTDOOR AIR SCHEDULE

ZONE NAME

ROOM

NUMBERS

NUMBER OF

OCCUPANTS OUTDOOR AIRFLOW

ROLLING FILES 0.7 12 CFM

KITCHENETTE 137 3.3 24 CFM

ARCH SAMUEL 138 0.8 14 CFM

CIVIL SACYNSKI 139 0.8 14 CFM

MECH FAULKNER 140 0.8 14 CFM

STORAGE 141 0 5 CFM

CONFERENCE 142 11.1 69 CFM

OFFICE AREA C1 144 2.4 41 CFM

OFFICE AREA C2 144 10.5 178 CFM

OFFICE AREA C3 144 12.5 213 CFM

ASSET MGT SARGENT 145 0.8 13 CFM

ASSET MGT FRAZIER 146 0.8 13 CFM

ASSET MGT HEAD ELLIOTT 147 0.8 14 CFM

KITCHENETTE 148 3.1 23 CFM

AQ HEAD BISHOP 149 0.8 13 CFM

FSC HEAD BLANCHARD 157 0.6 11 CFM

PWD LAWERENCE 158 0.6 11 CFM

VESTIBULE 159 0 5 CFM

OFFICE AREA B 160 10.8 184 CFM

OFFICE UNASSIGNED 161 0.6 10 CFM

CONFERENCE 162 15.4 96 CFM

VESTIBULE 164 0 4 CFM

SUPPLY 166 0 5 CFM

OFFICE AREA A 2 167 10.5 178 CFM

OFFICE AREA A 3 167 10.1 172 CFM

OFFICE AREA A 5 167 0.5 9 CFM

NOTE: NUMBER OF OCCUPANTS IS SHOWN FOR INFORMATION ONLY.

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

RETURN AIR

SUPPLY

FAN

FILTER

DPS

C

DX

FLT-P-HL

SA-T

SA-T-SP SA-FLOW

SF-SS

SF-S

SF-C

VFDOA-T

OUTSIDE

AIR

RA-RH-SP

RA-RH

MRA-D-C

M

OA-D-C

RA-T

SA-P-HLMA-T-LLOA-AFMS CLG-C

RELIEF

FAN

RF-SS

RF-S

RF-C

VFD

RELIEF AIR

M

RF-D-C

ES-BUT

EMERGENCY

SHUTDOWN

SWITCH

(EXISTING,

REUSE)

RST-BUT

EMERGENCY

RESTART

BUTTON

(EXISTING,

REUSE)

SPACE-T

SPACE-T-LL

SPACE-T-HL

SPACE

TEMPERATURE

SENSOR

(EXISTING,

REUSE)

SYS-OCC

OCCUPANCY

SCHEDULE

(EXISTING,

REUSE)

LOCATED IN ENTRY 102.

NEW RTUS MUST TIE INTO

THESE EXISTING CONTROLS.

FRZ

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

MAXIMO WORKORDER NO:

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

PROJECT NO:

D E

P

AR

TM

E

N T

O F

TH

E

N A

VY

N

A

VA

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S

YS

TE

M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D

M

ID

-A

TL

AN

TI

C

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CL

AS

SI

FI

ED

SIGNED FINAL

NICHOLAS A. HALL

NICHOLAS A. HALL

PATRICK FAULKNER

EE

__ ___ ___ ___ ___ ____ ___ ___ ___ ___ __A

B C D E F G H JA-430C1

M-701

CO

NT

RO

LS

MCM

RVG RVG

APRIL 30, 2025

199.26

7242175

CH

ER

RY

P

OI

NT

, N

OR

TH

C

AR

OL

IN

A

MA

RI

NE

C

OR

PS

A

IR

S

TA

TI

ON

N

AV

FA

C

S

YS

C O

M M

ID

-A

TL

AN

TI

C

FR

C

-E , M

A R

IN

E

C O

R

PS

A

IR

S

TA

TI

O

N

R E

P

LA

C E

R O

O

FT

O P

H V

A C

E Q

U

IP

M E

N T

B U

IL

D

IN

G

12913252

ROOFTOP AIR HANDLING UNIT SEQUENCE OF OPERATION (RTU-1,2)

RTU-1 AND -2 ARE CONTROLLED VIA PACKAGED CONTROLS. PACKAGED CONTROLLER

MUST REPORT BACK TO BUILDING BAS. CONTROLLERS MUST BE COMPATABLE WITH JCI

METASYS PROGRAM AND SYSTEMS, AND MUST TIE INTO EXISTING SNE UNIT.

NOTE: ALL CONTROL POINTS SHOWN WITHIN THE SCHEMATIC BOUNDARY ARE

INTENDED TO BE PROVIDED AS PART OF THE PACKAGED CONTROL SYSTEM WITH THE

RTU. IF THE CONTRACTOR'S PACKAGED SYSTEM DOES NOT CONTAIN ALL POINTS, THE

CONTRACTOR MUST COORDINATE WITH THE BAS VENDOR TO PROVIDE ALL

POINTS/EQUIPMENT.

OCCUPIED MODE:

THE AIR HANDLING UNIT SUPPLY FAN MUST BE STARTED AND STOPPED BY THE

ENERGY MANAGEMENT SYSTEM UNDER A TIME OF DAY SCHEDULE. THIS SCHEDULE

MUST BE MODIFIED BY A START STOP OPTIMIZATION PROGRAM DURING PULL DOWN /

WARM UP OPERATION, THE FAN MUST START AT THIS OPTIMIZED TIME, RAMP THE FAN

TO 100%, OPEN THE APPROPRIATE AHU COIL TO 100% UNTIL ALL ZONES REPORT

OCCUPIED SETPOINT HAS BEEN ACHIEVED.

UPON STARTUP ,THE SUPPLY FAN MUST RAMP UP TO SETPOlNT AND MAlNTAlN STATlC PRESSURE SETPOlNT AT THE lNDlCATED DUCT STATlC PRESSURE SENSOR. THE RELIEF

FAN SHALL TRACK THE SUPPLY FAN IN ORDER TO MAINTAIN THE BUILDING

PRESSURIZATION. THE SYSTEM MUST RUN IN THIS CONDlTON FOR 5 MlNUTES (ADJ) TO ESTABLlSH SYSTEM AND SPACE BALANCE.

NORMAL OCCUPIED OPERATION: OUTDOOR AIR DAMPER MUST OPEN, THE SUPPLY FAN

MUST MODULATE TO MAINTAIN DUCT PRESSURE, AND THE OUTSIDE AIR DAMPER MUST

MODULATE TO MAINTAIN OA CFM SETPOINT.

THE SUPPLY AIR TEMPERATURE MUST BE RESET FROM 55° F TO 65° F AS THE OUTDOOR

TEMPERATURE CHANGES FROM 70° F TO 45° F. THE DX COMPRESSORS MUST BE

SEQUENCED VIA INTERNAL CONTROL TO ACHIEVE SUPPLY AIR SETPOINT.

THE STATIC PRESSURE SENSOR IN THE SUPPLY DUCT MUST MODULATE THE VARIABLE

FREQUENCY DRIVE TO MAINTAIN THE SETPOINT ESTABLISHED DURING FINAL TESTING

AND BALANCING. MONITOR THE SUPPLY FAN HIGH STATIC AND ON INDICATION OF DUCT

STATIC PRESSURE IN EXCESS OF 3.0” WG (ADJ), STOP THE FAN, CLOSE THE OUTSIDE AIR

DAMPER AND ALARM.

ECONOMIZER

PROVIDE ECONOMIZER SEQUENCE FOR OUTDOOR AIR TEMPERATURES BETWEEN 55F

(ADJ) AND 65F (ADJ). ECONOMIZER SHALL BE EQUIPPED WITH AN AUTOMATIC LOCKOUT

WHEN THE OUTDOOR HIGH AMBIENT TEMPERATURE IS TOO HIGH FOR PROPER COOLING.

MINIMUM POSITION CONTROL SHALL BE STANDARD AND ADJUSTABLE THROUGH THE

BUILDING MANAGEMENT SYSTEM. A SPRING RETURN MOTOR SHALL ENSURE CLOSURE

OF OA DAMPERS DURING UNIT SHUTDOWN OR POWER INTERRUPTION. MECHANICAL

COOLING SHALL BE AVAILABLE TO AID THE ECONOMIZER MODE AT ANY AMBIENT.

SMOKE DETECTION & AHU SHUTDOWN:

MONITOR THE SUPPLY AIR DUCT SMOKE DETECTOR, IN COORDINATION WITH THE FIRE

ALARM SYSTEM, AND INDICATE WHEN IN ALARM.

THE BUILDING FIRE ALARM SYSTEM MUST PROVIDE AN AHU SHUT DOWN SIGNAL,

HARDWIRED TO THE AHU.

THE BUILDING FIRE ALARM SYSTEM MUST PROVIDE ONE DIGITAL OUTPUT TO THE BAS TO

INDICATE ALARM CONDITION. WIRING FOR THIS ALARM POINT MUST BE PROVIDED BY

THE BAS SUBCONTRACTOR. UPON RECEIPT OF THIS ALARM, THE BAS MUST SHUT

DOWN ALL AIR MOVING EQUIPMENT IN THE BUILDING.

HUMIDITY CONTROL

UPON A RISE IN HUMIDITY LEVEL ABOVE 55% R.H., AS SENSED BY THE RETURN DUCT

HUMIDITY SENSOR, THE SUPPLY AIR DISCHARGE TEMPERATURE SHALL RESET TO 55°F

UNTIL THE RETURN R.H. FALLS BELOW 50% THE DX COMPRESSORS MUST BE INDEXED

TO 100% BY THE BAS AND ALL VAV BOX HEATING COILS MUST BE MODULATED TO

MAINTAIN SPACE TEMPERATURE 1° F LOWER THAN THE COOLING SETPOINT.

FILTER BANKS: PROVIDE PRESSURE DIFFERENTIAL SWITCHES ACROSS ALL FILTER

BANKS AND INDICATE DIRTY FILTER STATUS BASED ON MANUFACTURERS FILTER

PRESSURE DROP DATA.

UNOCCUPIED MODE:

WHEN THE TEMPERATURE DROPS BELOW THE UNOCCUPIED LOW LIMIT SETPOINT OR

RISES ABOVE THE UNOCCUPIED HIGH LIMIT OR IF TWO OR MORE ZONES HAVE FALLEN

BELOW 50°F, THE UNIT MUST OPERATE IN PREPARATORY MODE.

WHEN THE UNIT IS DISABLED, THE SUPPLY FAN MUST RAMP DOWN AND TURN OFF. THE

DX COMPRESSORS ARE INDEXED OFF. THE OUTDOOR AIR DAMPER IS CLOSED. THE

RETURN AIR DAMPER IS OPEN.

MORNING WARM UP:

DURING MORNING WARMUP,AT A TIME DETERMINED BY OWNER AND PROGRAMMED AT

INSTALLATION, THE SUPPLY FAN SHALL OPERATE AT LOW SPEED TO CIRCULATE AIR AND

GRADUALLY INCREASE SPACE TEMPERATURE. SUPPLY TEMPERATURE SHALL BE

MONITORED, AND FAN SPEED AND COMPRESSOR SETTINGS SHALL ADJUST AS NEEDED

TO CONTINUE TEMPERATURE INCREASE. ONCE THE DESIGN TEMPERATURE LEVEL IS

REACHED, THE FAN SPEED AND COMPRESSOR SETTINGS SHALL MAINTAIN THOSE

LEVELS.

FREEZESTAT:

SHOULD THE FREEZESTAT DETECT THE OUTSIDE AIR TEMPERATURE IS AT A LEVEL THAT

WOULD HARM THE UNIT, THE SUPPLY FAN SHALL SHUT OFF, THE OUTSIDE AIR INTAKE

DAMPER SHALL CLOSE, THE COMPRESSOR SHALL SWITCH TO HEATING MODE, AND AN

ALARM SHALL BE SENT TO THE BAS. ONCE THE OUTDOOR AIR CONDITIONS ARE

VERIFIED ACCEPTABLE, THE SEQUENCE SHALL REVERSE.

ROOFTOP AIR HANDLING UNIT CONTROLS SCHEMATIC (RTU-1, -2)

NOTES:

1) COORDINATE CONTROLS WITH EXISTING INFRASTRUCTURE, INCLUDING BUT NOT LIMITED TO EMERGENCY SHUTDOWN, DUCT STATIC PRESSURE, DUCT SMOKE DETECTORS, ETC.

2) ROOFTOP MANUFACTURER SHALL PROVIDE TURN-KEY SOLUTION PACKAGE CONTROLS.

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

MAXIMO WORKORDER NO:

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

PROJECT NO:

D E

P

AR

TM

E

N T

O F

TH

E

N A

VY

N

A

VA

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S

YS

TE

M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D

M

ID

-A

TL

AN

TI

C

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CL

AS

SI

FI

ED

SIGNED FINAL

NICHOLAS A. HALL

NICHOLAS A. HALL

PATRICK FAULKNER

EE

__ ___ ___ ___ ___ ____ ___ ___ ___ ___ __A

B C D E F G H JA-430C1

M-702

CO

NT

RO

LS

MCM

RVG RVG

APRIL 30, 2025

199.26

7242175

CH

ER

RY

P

OI

NT

, N

OR

TH

C

AR

OL

IN

A

MA

RI

NE

C

OR

PS

A

IR

S

TA

TI

ON

N

AV

FA

C

S

YS

C O

M M

ID

-A

TL

AN

TI

C

FR

C

-E , M

A R

IN

E

C O

R

PS

A

IR

S

TA

TI

O

N

R E

P

LA

C E

R O

O

FT

O P

H V

A C

E Q

U

IP

M E

N T

B U

IL

D

IN

G

12913253

6) THE HVAC (ATFP) EMERGENCY SHUTOFF SWITCH IS FOUND IN ENTRY 102 AS SHOWN ON NAVFAC DRAWING 12782579 RD AND DETAIL D2 ON NAVFAC DRAWING 12782597. THE NEW HVAC EQUIPMENT NEEDS TO TIE INTO THE EXISTING EMERGENCY SHUTOFF SWITCH.

5) UNIT STATUS: SERVES AS A MONITORED POINT AT THE M&C SOFTWARE (FRONT-END) AND AS A COOLING REQUEST

4) ALARM CONDITIONS MARKED WITH AN ASTERISK (*) SHALL BE ACTIVE ONLY WHEN THE SYSTEM IS IN OCCUPIED MODE AND HAS BEEN IN OCCUPIED MODE FOR MORE THAN: * = 5 MINUTES ** = 30 MINUTES

3) SYS-OCC: AS DESCRIBED IN THE POINTS SCHEDULE INSTRUCTIONS, OVERRIDE OF SYS-OCC IS ACCOMPLISHED THROUGH THE SYSTEM SCHEDULER.

2) UNIT MANUFACTURERS PROOFS AND SAFETIES: THE CONTRACTOR SHALL SHOW EACH PROOF AND SAFETY AS A SEPARATE ROW.

1) THE CONTRACTOR SHALL COMPLETE THE POINTS SCHEDULE AS SPECIFIED AND AS DESCRIBED IN THE POINTS SCHEDULE INSTRUCTIONS DRAWING.

Notes:

OTHER POINTS FLT-P-HL MIXED AIR FILTER PRESSURE HIGH LIMIT SWITCH <___> ALM/NORMAL <___> BI ~ ~ ~ X ~ ~ TRUE crit <___>

RA-D-C RETURN AIR DAMPER COMMAND ~ <0-100%> <___> AO ~ X X X ~ X ~ ~ ~

RA-RH-SP RETURN AIR HUMIDITY SETPOINT SEE SCHED 20%-60% <___> AI ~ ~ X ~ ~ X ~ ~ ~

RA-RH RETURN AIR RELATIVE HUMIDITY ~ <___> <___> AI ~ ~ X X ~ ~ ~ ~ ~

RA-T RETURN AIR TEMPERATURE ~ <___> <___> AI ~ X X X ~ ~ ~ ~ ~

RETURN AIR

RF-C RELIEF FAN COMMAND ~ ON/OFF <___> <___> ~ X X X ~ X ~ ~ ~

CLG-C COOLING COMMAND ~ ON/OFF <___> <___> ~ X X X ~ X ~ ~ ~

SA-T-SP SUPPLY AIR TEMPERATURE SETPOINT 53 DEG F ~ <___> ~ ~ X X ~ ~ X ~ ~ ~

SA-T SUPPLY AIR TEMPERATURE ~ <___> <___> AI ~ X X X ~ ~ *SA-T MORE THAN 10 DEG F ABOVE OR BELOW SETPOINT crit <___>SUPPLY AIR

SF-C SUPPLY FAN COMMAND ~ ON/OFF <___> <___> ~ X X X ~ X ~ ~ ~

RF-D-C RELIEF AIR DAMPER COMMAND ~ <0-100%> <___> AO ~ X X X ~ X ~ ~ ~

FRZ FREEZESTAT ~ <___> <___> AI ~ X X X ~ ~ OUTSIDE AIR TEMPERATURE LOWER THAN MINIMUM crit <___> OA-AFMS OUTSIDE AIR AIR FLOW MEASURING STATION ~ <___> <___> AI ~ X X X ~ ~ INFO INFO ~

OA-D-C OUTSIDE AIR DAMPER COMMAND ~ <0-100%> <___> AO ~ X X X ~ X ~ ~ ~MIXED AIR

TEMPERATURE

CONTROL

OA-T OUTSIDE AIR TEMPERATURE ~ <___> <___> AI ~ X X X ~ ~ ~ ~ ~

SPACE-T SPACE TEMPERATURE (EXISTING) ~ <___> <___> AI ~ X X X ~ ~ ~ ~ ~

RF-SS RETURN FAN START/STOP ~ ON/OFF <___> <___> ~ X X X ~ X ~ ~ ~

SF-SS SUPPLY FAN START/STOP ~ ON/OFF <___> <___> ~ X X X ~ X ~ ~ ~

SYS-OCC OCCUPANCY INPUT (FROM SYSTEM SCHEDULER) (EXISTING) <___> <___> NVI ~ X X ~ ~ X ~ ~ ~ SPACE-T-HL SPACE TEMPERATURE HIGH LIMIT SETPOINT (EXISTING) 82 DEG F ~ <___> ~ ~ ~ X ~ ~ X ~ ~ ~

START/STOP

SPACE-T-LL SPACE TEMPERATURE LOW LIMIT SETPOINT (EXISTING) 62 DEG F ~ <___> ~ ~ ~ X ~ ~ X ~ ~ ~

RST-BUT SYSTEM RESET BUTTON (EXISTING) ~ ~ <___> <__> ~ ~ ~ ~ ~ ~ ~ ~ ~

ES-BUT EMERGENCY SHUTDOWN (EXISTING) ~ ALM/NORMAL <___> <___> ~ ~ ~ ~ ~ ~ ALM crit <___> MA-T-LL MIXED AIR TEMPERATURE LOW LIMIT (FREEZESTAT) 35 DEG F ALM/NORMAL <___> BI ~ ~ ~ X ~ ~ ALM crit <___> SA-P-HL SUPPLY AIR PRESSURE HIGH LIMIT 3 "WC ALM/NORMAL <___> BI ~ ~ ~ X ~ ~ ALM crit <___> RF-S RELIEF FAN STATUS ~ ON/OFF <___> BI ~ X X X ~ ~ RETURN FAN PROOF FAILED crit <___>

PROOFS

SAFETIES

SF-S SUPPLY FAN STATUS ~ ON/OFF <___> BI ~ X X X ~ ~ SUPPLY FAN PROOF FAILED crit <___>

FUNCTION NAME DESCRIPTION

SETTING

(WITH UNITS)

RANGE

(WITH UNITS)

nci/CPT

NAME

IO

TYPE HOA REQ'D

DISP

REQ'D

TREND

REQ'D

NODE ID: <___> LDP

VIEW

REQ'D

M&C LDP

OVRD

REQ'D

M&C

OVRD

REQ'D

ALARM CONDITION

(SEE NOTES)

ALARM

PRIORITY

M&C

ROUTING

NODE ADDRESS: Domain = <___>, Subnet = <___>, Node = <___> LDP AND M&C DISPLAY OVERRIDES ALARMS

NODE LOCATION: <___>

NODE: <DDC##>

ROOFTOP UNIT CONTROL POINTS (RTU-1, -2)

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

SYMBOL DESCRIPTION

SAFETY SWITCH

NEMA ENCLOSURE RATING

SWITCH RATING 30A-3P,15A, 3R

FUSE AMP RATING

(NF INDICATES NON-FUSED TYPE)

PANELBOARDH2R1PANEL NAME

ELECTRICAL EQUIPMENT / MOTOR

CONNECTIONS

X

X-XXX

X

X-XXX

DETAIL

NOT TO SCALE

DETAIL IDENTIFICATION

NUMBER

NUMBER OF SHEET ON

WHICH DETAIL IS DRAWN

SHEET NOTE1

REVISION NOTE INDICATOR1

CROSS REFERENCING SYMBOL

POINT OF DISCONNECT

POINT OF CONNECTION

MISCELLANEOUS SYMBOLS

SYMBOL DESCRIPTION

NUMBER OF SHEET ON

WHICH DETAIL IS INDICATED

DETAIL IDENTIFICATION

NUMBER

SYMBOL WHERE DETAIL IS TAKEN

LINETYPES

LINETYPE DESCRIPTION

LINETYPE REPRESENTS NEW WORK TO BE INSTALLED

LINETYPE REPRESENTS EXISTING WORK TO REMAIN

LINETYPE REPRESENTS DEMOLITION WORK TO BE REMOVED

NUMBER OF POLES

MISCELLANEOUS EQUIPMENT

CONNECTION

E

ELECTRICAL ABBREVIATIONS

A, AMP

AF

AFF

AFG

AHU

AIC

AT

ATS

C

CB

DISC

DN

EA

EC

EMT

FLA

FU

GFCI

GND

GRS

JB

KCMIL

LTG

MAX

MCB

MCM

MDP

MIN

MLO

MT

MTD

NEC

NEMA

NF

NIC

NTS

P

PB

P/BD

PH

PNL

RCPT

REQD

REV

RGS

RM

RMC

SP

SPD

SPEC

SW

TYP

UGND

U.N.O.

UTIL

V

WP

XFMR

AMPERE

AMPERE FRAME

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AIR HANDLING UNIT

AMPERE INTERRUPTING CURRENT

AMPERE TRIP

AUTOMATIC TRANSFER SWITCH

CONDUIT

CIRCUIT BREAKER

DISCONNECT

DOWN

EACH

EMPTY CONDUIT

ELECTRICAL METALLIC TUBING

FULL LOAD AMPERES

FUSE, FUSED

GROUND FAULT CIRCUIT INTERRUPTER

GROUND

GALVANIZED RIGID STEEL

JUNCTION BOX

1000 CIRCULAR MILS

LIGHTING

MAXIMUM

MAIN CIRCUIT BREAKER

THOUSAND CIRCULAR MILS

MAIN DISTRIBUTION PANEL

MINIMUM, MIN

MAIN LUGS ONLY

MOUNT

MOUNTED

NATIONAL ELECTRICAL CODE

NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION

NON-FUSED

NOT IN CONTRACT

NOT TO SCALE

POLE

PULL BOX, PUSH BUTTON

PANEL BOARD

PHASE

PANEL

RECEPTACLE

REQUIRED

REVISION

RIGID GALVANIZED STEEL

ROOM

RIGID METAL CONDUIT

SINGLE POLE

SURGE PROTECTION DEVICE (TVSS)

SPECIFICATION

SWITCH

TYPICAL

UNDERGROUND

UNLESS NOTED OTHERWISE

UTILITY

VOLT(S)

WEATHER PROOF

TRANSFORMER

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

MAXIMO WORKORDER NO:

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

PROJECT NO:

D E

P

AR

TM

E

N T

O F

TH

E

N A

VY

N

A

VA

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S

YS

TE

M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D

M

ID

-A

TL

AN

TI

C

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CL

AS

SI

FI

ED

SIGNED FINAL

NICHOLAS A. HALL

NICHOLAS A. HALL

PATRICK FAULKNER

EE

__ ___ ___ ___ ___ ____ ___ ___ ___ ___ __A

B C D E F G H JA-430C1

E-001

LE

G

EN

D

AN

D

AB

BR

EV

IA

TI

O

NS

JMW

KEA KEA

APRIL 30, 2025

199.26

7242175

CH

ER

RY

P

OI

NT

, N

OR

TH

C

AR

OL

IN

A

MA

RI

NE

C

OR

PS

A

IR

S

TA

TI

ON

N

AV

FA

C

S

YS

C O

M M

ID

-A

TL

AN

TI

C

FR

C

-E , M

A R

IN

E

C O

R

PS

A

IR

S

TA

TI

O

N

R E

P

LA

C E

R O

O

FT

O P

H V

A C

E Q

U

IP

M E

N T

B U

IL

D

IN

G

12913254

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

BUILDING GENERAL NOTES

1. CONTRACTOR SHALL VERIFY DEVICE LOCATIONS IN THE FIELD PRIOR TO ROUGH–IN.

2. ALL CONDUITS SHALL BE DE-BURRED AND PROVIDED WITH BUSHINGS TO PREVENT CABLE

DAMAGE. CONDUIT FITTINGS SHALL HAVE INSULATED THROATS.

3. ALL SPARE CONDUITS SHALL BE PROVIDED WITH PULL WIRE.

4. CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING AND SCHEDULING THE DEMOLITION

AND RELOCATION OF EXISTING ELECTRICAL SYSTEMS WITH USERS AND THE CONTRACTING

OFFICER. DOWN TIMES SHALL BE SCHEDULED IN ADVANCE TO AVOID INTERRUPTION OF

SYSTEMS. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ANY TEMPORARY SERVICES

REQUIRED FOR ALL SYSTEMS DURING DEMOLITION AND RELOCATION.

1. DEMOLITION DRAWINGS ARE BASED ON EXISTING PLANS AND FIELD INVESTIGATION. PRIOR TO DEMOLITION. VISIT THE EXISTING BUILDING PRIOR TO BID IN ORDER TO BECOME FAMILIAR WITH

THE EXISTING CONDITIONS AND IN ORDER TO AVOID CONFLICTS.

2. DASHED ITEMS: ITEMS SHOWN DASHED ON DEMOLITION PLANS ARE EXISTING AND MUST BE

REMOVED COMPLETE, INCLUDING BOXES, CONDUIT, WIRE, FASTENERS, AND ASSOCIATED

APPURTENANCES, U.N.O.

3. SOLID ITEMS: ITEMS SHOWN SOLID ON DEMOLITION PLANS ARE EXISTING TO REMAIN.

4. CIRCUITING TO REMAIN: EXISTING CIRCUITING TO REMAIN MUST BE REROUTED OR

RECONNECTED, AS REQUIRED, WHERE AFFECTED BY NEW WORK IN ORDER TO MAINTAIN

CONTINUITY OF CIRCUIT. ENSURE THAT THE CIRCUITRY THAT REMAINS IS SAFE AND CODE

COMPLIANT.

5. EXISTING CONDUIT: EXISTING CONDUITS AND WIRING THAT WILL NOT BE REUSED MUST BE

REMOVED WHERE THEY WILL BE EXPOSED UPON COMPLETION OF NEW WORK. EXISTING

CONDUIT TO REMAIN CONCEALED IN WALLS MUST BE ABANDONED.

6. REPAIR DAMAGE: EXERCISE CARE IN REMOVAL OF DEMOLITION ITEMS. REPAIR, AT NO

ADDITIONAL COST TO OWNER, ANY DAMAGE CAUSED TO EXISTING CONSTRUCTION AND/OR

EQUIPMENT TO REMAIN.

7. ASSOCIATED APPURTENANCES: REMOVE ELECTRICAL APPURTENANCES (DISCONNECTS,

STARTERS, WIRING, CONDUIT, ETC.) ASSOCIATED WITH EQUIPMENT TO BE REMOVED BY

OTHERS.

8. KNOCKOUT PLUGS AND COVERS: CONDUIT REMOVED MUST BE REMOVED IN ITS ENTIRETY,

INCLUDING FITTINGS, MOUNTING DEVICES, MOUNTING HARDWARE, ETC. PROVIDE CONDUIT

PLUGS AND BLANKS FOR OPENINGS CREATED BY THE REMOVAL OF CONDUIT. PROVIDE BLANK

COVER PLATES FOR OPENED OUTLET BOXES CREATED BY THE REMOVAL OF THE EQUIPMENT

AND/OR DEVICES.

9. DEMOLISHED MATERIALS: MATERIALS REMOVED UNDER DEMOLITION, NOT TO BE RELOCATED OR

DESIGNATED TO BE TURNED OVER TO THE OWNER, WILL BECOME PROPERTY OF THE

CONTRACTOR AND MUST BE REMOVED COMPLETELY FROM THE SITE.

10. SCHEDULE OUTAGES: WORK AND POWER OUTAGES IN THE EXISTING BUILDING MUST BE

SCHEDULED AT TIMES CONVENIENT TO THE OWNER.

11. NOTIFICATION: NOTIFY THE OWNER PRIOR TO TURNING OFF ANY CIRCUITS.

12. EXISTING CIRCUITS: IF DURING THE COURSE OF CONSTRUCTION, IT IS DETERMINED BY THE

CONTRACTOR THAT AN EXISTING CIRCUIT BECOMES SPARE, THE CONTRACTOR MUST UPDATE

THE PANELBOARD DIRECTORY TO INDICATE SUCH, EVEN IF IT IS NOT EXPLICITLY MARKED ON

THE ELECTRICAL PLANS.

POWER GENERAL NOTES

1. BRANCH CIRCUIT CONDUCTOR SIZES SHOWN ON PLANS AND PANEL SCHEDULES ARE BASED ON

VOLTAGE DROP CALCULATIONS USING APPROXIMATE CIRCUIT ROUTING PATHS. WHEN FIELD

INSTALLED BRANCH CIRCUIT CONDUCTORS FOR 120 VOLT BRANCH CIRCUITS EXCEED 100 FEET, CONDUCTORS SHALL BE NO SMALLER THAN #10 AWG. WHEN PLANS OR PANEL SCHEDULES

SHOW BRANCH CIRCUIT CONDUCTORS LARGER THAN #10 AWG, USE THE LARGER CONDUCTOR.

2. DISCONNECTING DEVICES, STARTERS, AND/OR CONTROLLERS FOR ALL MECHANICAL

EQUIPMENT SHALL BE PROVIDED BY THE MECHANICAL CONTRACTOR/VENDOR. THE ELECTRICAL

CONTRACTOR SHALL PROVIDE AND INSTALL BREAKERS, CONDUIT AND WIRE TO THE

MECHANICAL EQUIPMENT DISCONNECTING MEANS. SIZES SHOWN ON THE ELECTRICAL PLANS

ARE BASED ON DESIGN EQUIPMENT. CONTRACTOR SHALL VERIFY ACTUAL SIZES PROVIDED AND

MAKE ALL NECESSARY ADJUSTMENTS AT NO COST TO THE GOVERNMENT.

3. ALL 120 VOLT SINGLE PHASE CIRCUITS SHALL HAVE A DEDICATED NEUTRAL. MULTI-WIRE

BRANCH CIRCUITS ARE NOT ALLOWED UNLESS SPECIFICALLY NOTED OTHERWISE.

4. PLANS SHOW A SEPARATE CONDUIT FOR EACH CIRCUIT. FOR 120 VOLT SINGLE PHASE BRANCH CIRCUITS, UP TO THREE HOME RUN CIRCUITS CAN BE COMBINED IN A SINGLE CONDUIT BACK TO THE PANEL. THE AMPACITY OF EACH CONDUCTOR SHALL BE REDUCED, AND THE CONDUIT SHALL

BE SIZED PER NEC REQUIREMENTS. SIZE CONDUIT TO PROVIDE SPARE CAPACITY FOR ONE

ADDITIONAL 20 AMP CIRCUIT IN EACH CONDUIT.

5. AN EQUIPMENT GROUNDING CONDUCTOR SHALL BE INSTALLED IN EACH CONDUIT. IT SHALL BE

SIZED PER THE NEC FOR THE LARGEST OVERCURRENT DEVICE PROTECTING CONDUCTORS IN

THE CONDUIT.

POWER DEMOLITION NOTES

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

MAXIMO WORKORDER NO:

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

PROJECT NO:

D E

P

AR

TM

E

N T

O F

TH

E

N A

VY

N

A

VA

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S

YS

TE

M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D

M

ID

-A

TL

AN

TI

C

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CL

AS

SI

FI

ED

SIGNED FINAL

NICHOLAS A. HALL

NICHOLAS A. HALL

PATRICK FAULKNER

EE

__ ___ ___ ___ ___ ____ ___ ___ ___ ___ __A

B C D E F G H JA-430C1

E-002

G

EN

ER

AL

N O

TE

S

JMW

KEA KEA

APRIL 30, 2025

199.26

7242175

CH

ER

RY

P

OI

NT

, N

OR

TH

C

AR

OL

IN

A

MA

RI

NE

C

OR

PS

A

IR

S

TA

TI

ON

N

AV

FA

C

S

YS

C O

M M

ID

-A

TL

AN

TI

C

FR

C

-E , M

A R

IN

E

C O

R

PS

A

IR

S

TA

TI

O

N

R E

P

LA

C E

R O

O

FT

O P

H V

A C

E Q

U

IP

M E

N T

B U

IL

D

IN

G

12913255

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

EX RTU-1

EX RTU-2

D E F G

04'8' 16' 24'8'

GRAPHIC SCALE: 1/8"GRAPHIC SCALE: = 1'-0"

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

MAXIMO WORKORDER NO:

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

PROJECT NO:

D E

P

AR

TM

E

N T

O F

TH

E

N A

VY

N

A

VA

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S

YS

TE

M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D

M

ID

-A

TL

AN

TI

C

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CL

AS

SI

FI

ED

SIGNED FINAL

NICHOLAS A. HALL

NICHOLAS A. HALL

PATRICK FAULKNER

EE

__ ___ ___ ___ ___ ____ ___ ___ ___ ___ __A

B C D E F G H JA-430C1

ED130

EL

EC

TR

IC

AL

R

O O

F

PL

AN

DE

M

O

LI

TI

O

N

JMW

KEA KEA

APRIL 30, 2025

199.26

7242175

CH

ER

RY

P

OI

NT

, N

OR

TH

C

AR

OL

IN

A

MA

RI

NE

C

OR

PS

A

IR

S

TA

TI

ON

N

AV

FA

C

S

YS

C O

M M

ID

-A

TL

AN

TI

C

FR

C

-E , M

A R

IN

E

C O

R

PS

A

IR

S

TA

TI

O

N

R E

P

LA

C E

R O

O

FT

O P

H V

A C

E Q

U

IP

M E

N T

B U

IL

D

IN

G

12913256SCALE: 1/8" = 1'-0"ED130

ELECTRICAL ROOF PLAN - DEMOLITION1

SHEET KEYNOTES

1 REMOVE EXISTING CONDUITS AND EXISTING HOMERUN

CIRCUIT BACK TO PANEL ‘MDP’. REFER TO EP601 FOR

ADDITIONAL INFORMATION.

GENERAL SHEET NOTES

1 REFER TO SHEETS E-001 AND E-002 FOR ELECTRICAL

LEGEND, ELECTRICAL GENERAL NOTES, AND ELECTRICAL

ABBREVIATIONS.

2 REFER TO MECHANICAL DRAWINGS FOR MECHANICAL

EQUIPMENT TO BE DEMOLISHED.

3 CONTRACTOR SHALL FIELD VERIFY AND UPDATE PANEL

MDP SCHEDULE BEFORE THE COMMENCEMENT OF

DEMOLITION.

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

WOMAN

109.5

SHOWER

MEN

Room

PWD

TOILET

TOILET

113A

PWD CO

CORRIDOR

OFFICE

MECHANICAL

CONFERENCE

SHOWER

WOMEN

VEST

SHOWER

MEN

VENDING

ELECT

MESS

JAN

CORRIDOR

PWD OFFICE

KITCHENETTE

FEAD DIRECTOR

CONFERENCE

FEED DEPUTY

ENERGY MGR155

CONSTR.

CORRIDOR

OFFICE AREA A

CONST. HEAD

AQ HEAD

KITCHENETTE

ASSET MGT HEAD

VESTIBULE 146

ASSET MGT

ASSET MGT

156A

KITCHENETTE

PWD

OFFICE AREA C

FSC HEAD

160A

ROLLING FILES

SCM

OFFICE AERA B

CONFERENCE

OFFICE

VESTIBULE

SUPPLY

MEETING

VESTIBULE

ENTRY

CONFERENCE

PWD

PWD

133A Room

IT/COMM

EP410

D E F G

04'8' 16' 24'8'

GRAPHIC SCALE: 1/8"GRAPHIC SCALE: = 1'-0"

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

MAXIMO WORKORDER NO:

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

PROJECT NO:

D E

P

AR

TM

E

N T

O F

TH

E

N A

VY

N

A

VA

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S

YS

TE

M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D

M

ID

-A

TL

AN

TI

C

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CL

AS

SI

FI

ED

SIGNED FINAL

NICHOLAS A. HALL

NICHOLAS A. HALL

PATRICK FAULKNER

EE

__ ___ ___ ___ ___ ____ ___ ___ ___ ___ __A

B C D E F G H JA-430C1

EP110

LE

VE

L

-P O

W

ER

P

LA

N

JMW

KEA KEA

APRIL 30, 2025

199.26

7242175

CH

ER

RY

P

OI

NT

, N

OR

TH

C

AR

OL

IN

A

MA

RI

NE

C

OR

PS

A

IR

S

TA

TI

ON

N

AV

FA

C

S

YS

C O

M M

ID

-A

TL

AN

TI

C

FR

C

-E , M

A R

IN

E

C O

R

PS

A

IR

S

TA

TI

O

N

R E

P

LA

C E

R O

O

FT

O P

H V

A C

E Q

U

IP

M E

N T

B U

IL

D

IN

G

12913257

SCALE: 1/8" = 1'-0"EP110

LEVEL 1 - POWER PLAN1

GENERAL SHEET NOTES

1 REFER TO SHEETS E-001 AND E-002 FOR ELECTRICAL

LEGEND, ELECTRICAL GENERAL NOTES, AND ELECTRICAL

ABBREVIATIONS.

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

E

E

A

RTU-1

RTU-2

D E F G

MDP-50,52,54

MDP-34,36,38

04'8' 16' 24'8'

GRAPHIC SCALE: 1/8"GRAPHIC SCALE: = 1'-0"

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

MAXIMO WORKORDER NO:

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

PROJECT NO:

D E

P

AR

TM

E

N T

O F

TH

E

N A

VY

N

A

VA

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S

YS

TE

M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D

M

ID

-A

TL

AN

TI

C

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CL

AS

SI

FI

ED

SIGNED FINAL

NICHOLAS A. HALL

NICHOLAS A. HALL

PATRICK FAULKNER

EE

__ ___ ___ ___ ___ ____ ___ ___ ___ ___ __A

B C D E F G H JA-430C1

EP130

EL

EC

TR

IC

AL

R

O O

F

PL

AN

JMW

KEA KEA

APRIL 30, 2025

199.26

7242175

CH

ER

RY

P

OI

NT

, N

OR

TH

C

AR

OL

IN

A

MA

RI

NE

C

OR

PS

A

IR

S

TA

TI

ON

N

AV

FA

C

S

YS

C O

M M

ID

-A

TL

AN

TI

C

FR

C

-E , M

A R

IN

E

C O

R

PS

A

IR

S

TA

TI

O

N

R E

P

LA

C E

R O

O

FT

O P

H V

A C

E Q

U

IP

M E

N T

B U

IL

D

IN

G

12913258

SCALE: 1/8" = 1'-0"EP130

ELECTRICAL ROOF PLAN1

SHEET KEYNOTES

1 DISCONNECTING MEANS PROVIDED WITH MECHANICAL

UNIT.

2 REFER TO ELECTRICAL RISER DIAGRAM ON SHEET EP601

FOR MECHANICAL EQUIPMENT FEEDER SIZE.

GENERAL SHEET NOTES

1 REFER TO SHEETS E-001 AND E-002 FOR ELECTRICAL

LEGEND, ELECTRICAL GENERAL NOTES, AND ELECTRICAL

ABBREVIATIONS.

2 CONVENIENCE OUTLET PROVIDED WITH MECHANICAL

UNIT. REFER TO MECHANICAL DRAWINGS FOR ADDITIONAL

INFORMATION.

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

MECHANICAL

MDP1

F

4' 02' 8' 12'4'

GRAPHIC SCALE: 1/4"GRAPHIC SCALE: = 1'-0"

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

MAXIMO WORKORDER NO:

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

PROJECT NO:

D E

P

AR

TM

E

N T

O F

TH

E

N A

VY

N

A

VA

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S

YS

TE

M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D

M

ID

-A

TL

AN

TI

C

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CL

AS

SI

FI

ED

SIGNED FINAL

NICHOLAS A. HALL

NICHOLAS A. HALL

PATRICK FAULKNER

EE

__ ___ ___ ___ ___ ____ ___ ___ ___ ___ __A

B C D E F G H JA-430C1

EP410

EN

LA

RG

ED

P

LA

NS

JMW

KEA KEA

APRIL 30, 2025

199.26

7242175

CH

ER

RY

P

OI

NT

, N

OR

TH

C

AR

OL

IN

A

MA

RI

NE

C

OR

PS

A

IR

S

TA

TI

ON

N

AV

FA

C

S

YS

C O

M M

ID

-A

TL

AN

TI

C

FR

C

-E , M

A R

IN

E

C O

R

PS

A

IR

S

TA

TI

O

N

R E

P

LA

C E

R O

O

FT

O P

H V

A C

E Q

U

IP

M E

N T

B U

IL

D

IN

G

12913259

SHEET KEYNOTES

1 EXISTING PANEL TO REMAIN. CONTRACTOR SHALL

MAINTAIN CONTINUITY OF ALL EXISTING CIRCUITS TO

REMAIN.

GENERAL SHEET NOTES

1 REFER TO SHEETS E-001 AND E-002 FOR ELECTRICAL

LEGEND, ELECTRICAL GENERAL NOTES, AND ELECTRICAL

ABBREVIATIONS.

SCALE: 1/4" = 1'-0"EP410

ENLARGED PLAN - MECHANICAL ROOM1

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

500 KVA

PAD-MTD.

TRANSFORMER

MDP

1200A MLO

208V,3PH,4W

(E)

ATS

1200/3

(E)

EXISTING 350 KW

GENERATOR

(OPTIONAL STANDBY)

1200/3 300A MLO 150A MLO 150A MLO 150A MLO 150A MLO 150A MLO 150A MLO 150A MLO 100A MB 100A MB

(E) M

(E) A

(E) B

(E) C

(E) D

(E) F

(E) G

(E) H

(E) T1

(E) T2M

(E)

SPD

(E)

SPD

(E)

SPD

(E) (E)

EXT RTU-2EXT RTU-1

500 KVA

PAD-MTD.

TRANSFORMER

(E) MDP

1200A MLO

208V,3PH,4W

(E)

ATS

1200/3

(E)

EXISTING 350 KW

GENERATOR

(OPTIONAL STANDBY)

1200/3 300A MLO 150A MLO 150A MLO 150A MLO 150A MLO 150A MLO 150A MLO 150A MLO 100A MB 100A MB

(E) M

(E) A

(E) B

(E) C

(E) D

(E) F

(E) G

(E) H

(E) T1

(E) T2M

(E)

SPD

(E)

SPD

(E)

SPD

(E) (E)

RTU-2RTU-1

3 F4-350

F4-300

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

MAXIMO WORKORDER NO:

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

PROJECT NO:

D E

P

AR

TM

E

N T

O F

TH

E

N A

VY

N

A

VA

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S

YS

TE

M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D

M

ID

-A

TL

AN

TI

C

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CL

AS

SI

FI

ED

SIGNED FINAL

NICHOLAS A. HALL

NICHOLAS A. HALL

PATRICK FAULKNER

EE

__ ___ ___ ___ ___ ____ ___ ___ ___ ___ __A

B C D E F G H JA-430C1

EP601

EL

EC

TR

IC

AL

R

IS

ER

D

IA

G

RA

M S

JMW

KEA KEA

APRIL 30, 2025

199.26

7242175

CH

ER

RY

P

OI

NT

, N

OR

TH

C

AR

OL

IN

A

MA

RI

NE

C

OR

PS

A

IR

S

TA

TI

ON

N

AV

FA

C

S

YS

C O

M M

ID

-A

TL

AN

TI

C

FR

C

-E , M

A R

IN

E

C O

R

PS

A

IR

S

TA

TI

O

N

R E

P

LA

C E

R O

O

FT

O P

H V

A C

E Q

U

IP

M E

N T

B U

IL

D

IN

G

12913260

SCALE: NTSEP601

DEMOLITION ELECTRICAL RISER DIAGRAM1

SCALE: NTSEP601

NEW ELECTRICAL RISER DIAGRAM2

SHEET KEYNOTES

1 CONTRACTOR SHALL FIELD VERIFY AND UPDATE PANEL

SCHEDULE BEFORE THE COMMENCEMENT OF

DEMOLITION.

2 REMOVE EXISTING CONDUITS AND EXISTING FEEDER BACK

TO PANEL ‘MDP’.

3 DISCONNECTING MEANS PROVIDED WITH MECHANICAL

UNIT. REFER TO MECHANICAL DRAWINGS AND

SPECIFICATIONS FOR ADDITIONAL INFORMATION.

BRANCH CIRCUIT AND FEEDER SCHEDULE

MARK FEEDER SIZE_I RATINGS

F4-300 4#350kcmil & 1#4G - 3"C 300A (3 PHASE - 4 WIRE + GROUND) F4-350 4#500kcmil & 1#3G -3-1/2"C 350A (3 PHASE - 4 WIRE + GROUND)

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

EXISTING LOAD NEW LOAD

470.6A

EQUIPMENT LOAD SUMMARY

195A

LOAD

RTU - 1

RTU - 2

TOTAL LOAD

264A

275.6A 317A

581A

EXISTING

DEMAND LOAD

PROVIDED BY

CLIENT

120KVA * 1.25 = 150KVA

SERVICE SIZE 1200A * 1.732 * 208V * 0.8 = 345.845 KVA

NET LOAD

+69A

+41.4A

+110.4A

70.25KVA

99.29KVA

169.54KVA

95.11KVA

114.2KVA

209.31KVA

+24.86KVA

+14.77KVA

+39.63KVA

SATISFACTORY TO DATE

APPROVED

ACTIVITY

FOR COMMANDER NAVFAC

SEAL

A/E INFO

A

B

C

D

1 2 3 4 5

1 2 3 4 5

A

B

C

D

SCALE:

MAXIMO WORKORDER NO:

SHEET

NAVFAC DRAWING NO.

DES DRW CHK

OF

PROJECT NO:

D E

P

AR

TM

E

N T

O F

TH

E

N A

VY

N

A

VA

L

FA

C

IL

IT

IE

S E

N G

IN

E

E R

IN

G

S

YS

TE

M

S C

O M

M A

N D

DRAWFORM REVISION: 25 AUGUST 2020

PM/DM

BRANCH MANAGER

CHIEF ENG/ARCH

FIRE PROTECTION

NA

VA

L

FA

CI

LI

TI

ES

E

NG

IN

EE

RI

NG

S

YS

TE

M

S

CO

M M

AN

D

M

ID

-A

TL

AN

TI

C

AS NOTED

UNCLASSIFIED

UNCLASSIFIED

UN

CL

AS

SI

FI

ED

SIGNED FINAL

NICHOLAS A. HALL

NICHOLAS A. HALL

PATRICK FAULKNER

EE

__ ___ ___ ___ ___ ____ ___ ___ ___ ___ __A

B C D E F G H JA-430C1

EP701

PA

NE

L

SC

HE

DU

LE

S

JMW

KEA KEA

APRIL 30, 2025

199.26

7242175

CH

ER

RY

P

OI

NT

, N

OR

TH

C

AR

OL

IN

A

MA

RI

NE

C

OR

PS

A

IR

S

TA

TI

ON

N

AV

FA

C

S

YS

C O

M M

ID

-A

TL

AN

TI

C

FR

C

-E , M

A R

IN

E

C O

R

PS

A

IR

S

TA

TI

O

N

R E

P

LA

C E

R O

O

FT

O P

H V

A C

E Q

U

IP

M E

N T

B U

IL

D

IN

G

12913261

1. PROVIDE A NEW 350A BREAKER.

2. CONNECT RTU-1 TO EXISTING 300A BREAKER MADE AVAILABLE DURING DEMOLITION PHASE.

3. CLEARLY MARK THE EXISTING 250A BREAKER MADE AVAILABLE DURING DEMOLITION PHASE AS “SPARE”.

Notes:

Total Est. Demand Current: 1081 A Total Conn. Current: 1081 A

Total Est. Demand: 389364 VA Total Conn. Load: 389364 VA

Power 389364 VA 100.00% 389364 VA Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Legend:

Total Amps: 1089 A 1089 A 1070 A Total Load: 130455 VA 130455 VA 128455 VA

59 1667... 2343... 60 57 1667... 2343... 58

PANEL H 150 A 3

1667... 2343...

3 250 A SPARE

53 1667... 3733... 54 51 1667... 3733... 52

PANEL F 150 A 3

1667... 3733...

3 300 A RTU-1

47 2833... 2833... 48 45 2833... 2833... 46

PANEL D 150 A 3

2833... 2833...

3 250 A PANEL M

41 2000... -- 1 -- SPACE 42

39 2000... -- 1 -- SPACE 40

PANEL C 150 A 3

2000... 4533... 38

35 2117... 4533... 36 33 2117... 4533...

3 350 A RTU-2

PANEL B 150 A 3

2117... -- 1 -- SPACE 32

29 2100... -- 1 -- SPACE 30

27 2100... 2000... 28

PANEL A 150 A 3

2100... 2000...

2 80 A D-WH-4

23 1100... 1261... 24 21 1100... 1261... 22

PANEL T2 100 A 3

1100... 1261...

3 15 A HWP-2

17 1100... -- 1 -- SPACE 18

15 1100... -- 1 -- SPACE 16

PANEL T1 100 A 3

1100... -- 1 -- SPACE 14

11 2000... -- 1 -- SPACE 12

9 2000... -- 1 -- SPACE 10

HWP-1 15 A 3

2000... -- 1 -- SPACE 8

5 0 VA 1677... 6

3 0 VA 1677... 4

SPD 60 A 3

0 VA 1677...

3 60 A EX. PANEL DP

CKT Circuit Description Trip Poles A B C Poles Trip Circuit Description CKT

Notes:

Enclosure: NEMA 1 MCB Rating: 1200 A Mounting: SURFACE Wires: 4 Mains Rating: 1200 A

Supply From: Phases: 3 Mains Type: MLO Location: MECHANICAL 120 Volts: 208/120 A.I.C. Rating: 22000

Branch Panel: MDP

(E) ATS

(E) ATS

SY

M

DE

SC

RI

PT

IO

N

DA

TE

AP

100_G-001 COVER SHEET AND DRAWING INDEX
551_M-001 ABBREVIATIONS, LEGEND AND GENERAL NOTES
552_MD111 MECHANICAL ROOF PLAN -DEMOLITION
553_M-111 MECHANICAL ROOF PLAN - NEW WORK
557_M-501 DETAILS
557_M-601 SCHEDULES
557_M-701 CONTROLS
557_M-702 CONTROLS
601_E-001 LEGEND AND ABBREVIATIONS
601_E-002 GENERAL NOTES
602_ED130 ELECTRICAL ROOF PLAN - DEMOLITION
604_EP110 LEVEL 1 - POWER PLAN
604_EP130 ELECTRICAL ROOF PLAN
604_EP410 ENLARGED PLANS
604_EP601 ELECTRICAL RISER DIAGRAMS