Attachment J.3 - Drawings - JFK NICU Revised.pdf

PDF 8 MB Posted

Attached to
Solarization of John F. Kennedy (JFK) Hospital Neonatal Intensive Care Unit (NICU)
Solicitation number
72066924R00002-Solarization-JFK-NICU
Issued by

About this file

This document appears to be a set of technical drawings for the solarization of the Neonatal Intensive Care Unit (NICU) at the John F. Kennedy (JFK) Hospital in Liberia.

The drawings provide details on the solar photovoltaic (PV) system to be installed, including the PV array layout, electrical one-line diagram, wiring and cable tray details, equipment room layout, and lightning protection system. The system is designed to provide at least 6 hours of backup power to critical NICU equipment in the event of grid outages or generator failures. Key system components include 54 solar modules totaling 26.2 kW DC, 6 inverters with 42 kW AC capacity, and a 219 kWh battery storage system. The design complies with the Electricity Minigrid Code of Liberia and other relevant standards.

This set of drawings is part of the solicitation for the "Solarization of John F. Kennedy (JFK) Hospital Neonatal Intensive Care Unit (NICU)" contract, issued by the US Agency for International Development (USAID) in Liberia under Solicitation Number 72066924R00002.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

REPUBLIC OF LIBERIA

UNITED STATES AGENCY FOR INTERNATIONAL DEVELOPMENT

SOLARIZATION OF JFK HOSPITAL

NEONATAL INTENSIVE CARE UNIT

Volume I - Drawings

ISSUED FOR CONSTRUCTION

July 2023

USAID: LIBERIA A&E IDIQ TASK ORDER 2

SUBTASK 4: SOLARIZATION OF JFK HOSPITAL

NEONATAL INTENSIVE CARE UNIT

100% DESIGN SUBMITTAL - NOT FOR CONSTRUCTION

1310 N Courthouse Rd, Ste 610 Arlington, VA 22201 Ph: +1 703 829 6133

JFK HOSPITAL NICU

SOLARIZATION

SHEET INDEX

COUNT SHEET TITLE

GENERAL DRAWINGS

1 G-001 COVER PAGE

2 G-002 SHEET INDEX

3 G-003 NOTES

4 PV-001 SOLAR PV ARRAY LAYOUT

5 PV-002 SOLAR PV ARRAY STRINGS

6 PV-003 SOLAR PV RACKING DETAILS

7 C-001 NEW EQUIPMENT ROOM

8 C-002 WIRING TRENCH AND CABLE TRAY LAYOUT

9 C-003 EQUIPMENT ROOM RAISED FLOOR-1

10 C-004 EQUIPMENT ROOM RAISED FLOOR-2

11 E-001 ELECTRICAL ROOM EQUIPMENT LAYOUT

12 E-002 ELECTRICAL ROOM SECTIONS-1

13 E-003 ELECTRICAL ROOM SECTIONS-2

14 E-004 ELECTRICAL ROOM SECTIONS-3

15 E-005 ELECTRICAL ROOM LIGHTING PLAN

16 E-006 ELECTRICAL ONE-LINE

17 E-007 CONDUCTOR AND EQUIPMENT TABLES

18 E-008 AC SUPPLY TO INVERTERS

19 E-009 INVERTER OUTPUT CIRCUIT DIAGRAM

20 E-010 BATTERY STRING CONNECTIONS

21 E-011 CHARGE CONTROLLER RISER DIAGRAM

22 E-012 INVERTER RISER DIAGRAM

23 E-013 MONITORING AND COMMUNICATIONS

24 E-014 LIGHTNING PROTECTION SYSTEM LAYOUT

25 E-015 LIGHTNING PROTECTION AND GROUND ELEVATIONS

26 E-016 SOLAR PV GROUND DETAILS

27 M-001 EQUIPMENT ROOM MECHANICAL

G-002

SHEET INDEX

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

REV.NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRWN

AutoCAD SHX Text

CHKD

AutoCAD SHX Text

DESIGNED BY:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CROSS CHK'D BY:

AutoCAD SHX Text

APPROVED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

SHEET CHK'D BY:

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text G

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

REMARKS

AutoCAD SHX Text

NOVEMBER 28, 2022

AutoCAD SHX Text

LOCAL A/E LOGO

USAID: LIBERIA A&E IDIQ TASK ORDER 2

SUBTASK 4: SOLARIZATION OF JFK HOSPITAL

NEONATAL INTENSIVE CARE UNIT

100% DESIGN SUBMITTAL - NOT FOR CONSTRUCTION

1310 N Courthouse Rd, Ste 610 Arlington, VA 22201 Ph: +1 703 829 6133

JFK HOSPITAL NICU

SOLARIZATION

NOTES

GENERAL NOTES:

1. WORK SHALL COMPLY WITH THE REQUIREMENTS OF THE FOLLOWING:

a. ELECTRICITY MINIGRID CODE OF LIBERIA 2022, SPECIFICALLY SECTIONS 7.2.3, 8.8, 8.11, 8.12, 8.14, AND 11

b. INTERNATIONAL ELECTRIC CODE 61271-1

c. NATIONAL ELECTRIC CODE

d. NFPA 780

e. ISO 9060, 9846, AND 9847

2. THE FOLLOWING ARE GENERAL DESIGN PARAMETERS BASED ON THE APPLICABLE CODES

AND BEST PRACTICES FOR SOLAR PV MINIGRID DESIGN.

a. EQUIPMENT RATED FOR 1,000 V SYSTEM.

b. EQUIPMENT RATED FOR 230/400 V THREE-PHASE GRID AT 50 HZ.

c. SYSTEM WILL BE INSTALLED SUCH THAT IT WILL NEVER BE CONNECTED IN PARALLEL

TO THE POWER GRID.

d. SYSTEM EQUIPMENT WILL BE CONSTRUCTED OF NON-CORROSIVE MATERIALS OR

INCLUDE CORROSION PROTECTION SO THAT IT IS CAPABLE OF OPERATING IN

COASTAL AND MARINE ENVIRONMENTS.

e. ELECTRICAL ROOM HOUSING BATTERIES, INVERTERS, CHARGE CONTROLLERS, AND

OTHER BALANCE OF PLANT EQUIPMENT WILL BE A SECURE ROOM WITH LOCKED

DOORS.

f. EXTREME ANNUAL TEMPERATURE = 23.8°C (EUROPEAN COMMISSION PVGIS DATA).

g. WIND DESIGN SPEED OF 140 KILOMETERS PER HOUR

h. SEE OTHER RELEVANT SHEETS FOR ADDITIONAL ELECTRICAL, CIVIL, AND

STRUCTURAL NOTES.

DESIGN CONSIDERATIONS

1. INVERTER SIZING ACCOUNTS FOR INSTANTANEOUS OPERATING LOADS IN KW

2. INVERTER SIZING ACCOUNTS FOR IN RUSH, STARTUP AMPS

3. BATTERY ENERGY STORAGE SYSTEM DESIGNED TO PROVIDE 6 HOURS OF EMERGENCY

BACKUP FOR NICU'S PROJECTED LOADS

4. ROOF MOUNTED BALLASTED RACKING SYSTEM WITH MINIMAL ROOF PENETRATIONS

5. PANELS MOUNTED TO RACKING IN A BOLT THROUGH SYSTEM FOR RESILIENCY IN HIGH

WINDS

6. PV ARRAY LAYOUT DESIGNED WITH ROW SPACING AND ACCESS WALKWAYS ALLOWING

ACCESS FOR SERVICING

7. HIGH EFFICIENCY MODULES USED TO MAXIMIZE POTENTIAL PV CAPACITY ON LIMITED

ROOF SPACE

8. SPARES - BILL OF QUANTITIES INCLUDES 11 SPARE MODULES AND 6 SPARE BATTERIES

SYSTEM SUMMARY

GENERAL

· TILT 5 DEGREES

· AZIMUTH 0 DEGREES

RACKING

· MANUFACTURER UNIRAC RM5

· TYPE FLAT ROOF, BALLASTED

MODULES

· MODULE MODEL MAXEON SPR-X22-485-COM

· MODULE POWER 485 W

· TOTAL # OF MODULES 54

· TOTAL MODULE CAPACITY 26.2 kWDC

COMBINER DISCONNECTS

· PV DISCONNECT MODEL MIDNITE SOLAR MNPV4 DELUX

· TOTAL # OF PV DISCONNECTS 6

· BATTERY DISCONNECT #1 MODEL MIDNITE SOLAR MNBCB 1000/50

· TOTAL # OF DISCONNECT #1 3

ENERGY STORAGE SYSTEM

· BATTERY MODEL SIMPLIPHI LITHIUM 3.8-48-M

· BATTERY CAPACITY 3.04 kWh (80% DEPTH OF DISCHARGE)

· # OF BATTERIES 72

· TOTAL BATTERY CAPACITY 219 kWH

· CHARGE CONTROLLERS OUTBACK FM100

· # OF CHARGE CONTROLLERS 6

INVERTERS

· INVERTER MODEL OUTBACK GS7048E

· INVERTER POWER 7 kWAC

· TOTAL # OF INVERTERS 6

· TOTAL INVERTER CAPACITY 42 kWAC

MONITORING AND CONTROLS

· SYSTEM CONTROLS OUTBACK MATE 3S

· COMMUNICATIONS HUB OUTBACK HUB10

· DC SHUNT MONITORING OUTBACK FLEXNET DC

· TOTAL # OF UNITS 2 (OF EACH)

NOTES

G-003

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

REV.NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRWN

AutoCAD SHX Text

CHKD

AutoCAD SHX Text

DESIGNED BY:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CROSS CHK'D BY:

AutoCAD SHX Text

APPROVED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

SHEET CHK'D BY:

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text G

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

REMARKS

AutoCAD SHX Text

NOVEMBER 28, 2022

WATER

TOWER

ROOF LINE OF

UTILITY BUILDING

73'-6"

39'-6"

PV003

1'-6"

4'

4'

4'

31'-6"

27'-5"

E015

E015

27'-5"

WATER

PIPES

1'-11"

1'-11"

5' 0' 5' 10' 15' 20'

N

JFK HOSPITAL NICU SOLAR PV LAYOUT

SCALE: 1/4" = 1'

NOTES:

1. PV ARRAY LOCATED ON UTILITY BUILDING ROOF

2. AZIMUTH - 180 DEGREES (SOUTH)

3. TILT - 5 DEGREES

4. 1,836 ft2 AVAILABLE FOR PV ARRAY

5. PV ARRAY CAPACITY - 26 kWDC

6. INVERTER CAPACITY - 42 kWAC

7. BATTERY CAPACITY - 219 KWh

USAID: LIBERIA A&E IDIQ TASK ORDER 2

SUBTASK 4: SOLARIZATION OF JFK HOSPITAL

NEONATAL INTENSIVE CARE UNIT

100% DESIGN SUBMITTAL - NOT FOR CONSTRUCTION

1310 N Courthouse Rd, Ste 610 Arlington, VA 22201 Ph: +1 703 829 6133

JFK HOSPITAL NICU

SOLARIZATION

SOLAR PV ARRAY LAYOUT PV-001

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

REV.NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRWN

AutoCAD SHX Text

CHKD

AutoCAD SHX Text

DESIGNED BY:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CROSS CHK'D BY:

AutoCAD SHX Text

APPROVED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

SHEET CHK'D BY:

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text G

AutoCAD SHX Text

REMARKS

AutoCAD SHX Text

NOVEMBER 28, 2022

1A 1A 1A

1B

1C

2A 2A

3B2C 3B

3C 3C

5A4C 4C 4C 5A

6A 6A 6A 6C 6C

6B 6B 6B 6C 5C 5C

5B 5B

5C

PV ARRAY

GROUNDING

COPPER BUS BAR

PV ARRAY

GROUNDING

COPPER BUS BAR

TO PV SYSTEM

GROUND PIT

1B1B

1C 1C

2A

2B 2B 2B

2C 2C

3A 3A

3A 3B

3C

4B4A 4A 4A 4B4B

5A 5B

MODULE STRING AND WIRING DIAGRAM

SCALE: NTS

USAID: LIBERIA A&E IDIQ TASK ORDER 2

SUBTASK 4: SOLARIZATION OF JFK HOSPITAL

NEONATAL INTENSIVE CARE UNIT

100% DESIGN SUBMITTAL - NOT FOR CONSTRUCTION

1310 N Courthouse Rd, Ste 610 Arlington, VA 22201 Ph: +1 703 829 6133

JFK HOSPITAL NICU

SOLARIZATION

SOLAR PV ARRAY STRINGS PV-002

NOTES:

1. MODULES CONNECTED IN STRINGS OF 3

2. 3 STRINGS CONNECTED IN PV COMBINER BOXES

3. ALL POSITIVE AND NEGATIVE PV CONDUCTORS FROM EACH STRING SHALL

BE INSTALLED IN CONDUIT

4. JUNCTION BOX FOR PV CONDUCTORS AND LEADING TO PV COMBINER

BOXES

5. EACH PV ROW MUST BE CONNECTED TO THE GROUND BUS BAR

6. USE YELLOW-GREEN CONDUCTOR TO BOND ANY NON-CONTINUOUS PV

ROW

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

REV.NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRWN

AutoCAD SHX Text

CHKD

AutoCAD SHX Text

DESIGNED BY:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CROSS CHK'D BY:

AutoCAD SHX Text

APPROVED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

SHEET CHK'D BY:

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text G

AutoCAD SHX Text

REMARKS

AutoCAD SHX Text

NOVEMBER 28, 2022

PV003

CONCRETE

BALLAST

11.0"

4.25" 8.00"

CONCRETE

BALLAST

USAID: LIBERIA A&E IDIQ TASK ORDER 2

SUBTASK 4: SOLARIZATION OF JFK HOSPITAL

NEONATAL INTENSIVE CARE UNIT

100% DESIGN SUBMITTAL - NOT FOR CONSTRUCTION

1310 N Courthouse Rd, Ste 610 Arlington, VA 22201 Ph: +1 703 829 6133

JFK HOSPITAL NICU

SOLARIZATION

SOLAR PV RACKING DETAILS PV-003

PV RACK DETAIL PLAN VIEW

SCALE: NTS

PV RACK ELEVATION

SCALE: NTS

NOTES:

1. UNIRAC RM5 SELECTED AS A REPRESENTATIVE

RACKING SOLUTION

2. 11" ROW SPACING OPTION

3. FINAL PV RACK DESIGNS TO BE COMPLETED BY

RACKING VENDOR

4. PV RACK DIMENSIONS ARE NOMINAL AND TO BE

VERIFIED BY RACKING VENDOR

5. CONCRETE BALLAST SIZES AND LOCATIONS TO

BE DETERMINED BY RACKING VENDOR

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

REV.NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRWN

AutoCAD SHX Text

CHKD

AutoCAD SHX Text

DESIGNED BY:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CROSS CHK'D BY:

AutoCAD SHX Text

APPROVED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

SHEET CHK'D BY:

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text G

AutoCAD SHX Text

REMARKS

AutoCAD SHX Text

NOVEMBER 28, 2022

6"

15'-7"

6" 7'-10"

11'

ELECTRICAL ROOM

(NEW)

SW

IT

C H

G

EA

R

SWITCH GEAR ROOM (EXISTING)

OFFICE (EXISTING)

NEW WALLS

2' 0' 8' 12'4'

USAID: LIBERIA A&E IDIQ TASK ORDER 2

SUBTASK 4: SOLARIZATION OF JFK HOSPITAL

NEONATAL INTENSIVE CARE UNIT

100% DESIGN SUBMITTAL - NOT FOR CONSTRUCTION

1310 N Courthouse Rd, Ste 610 Arlington, VA 22201 Ph: +1 703 829 6133

JFK HOSPITAL NICU

SOLARIZATION

NEW EQUIPMENT ROOM C-001

JFK HOSPITAL NICU SOLARIZATION EQUIPMENT ROOM POWER PLAN

SCALE: 3/8" = 1'

N

NOTES:

1. NEW ELECTRICAL ROOM TO HOUSE SYSTEM ELECTRICAL COMPONENTS

INCLUDING BATTERIES, BATTERY CABINETS, CHARGE CONTROLLERS,

INVERTERS, COMBINER BOXES, CONTROLS, AIR CONDITIONER

CONDUCTORS, CONDUIT, AND CABLE TRAY.

2. TWO NEW 6" THICK WALLS TO BE INSTALLED IN SOUTHWEST CORNER OF

UTILITY BUILDING.

3. NEW ELECTRICAL ROOM TO INCLUDE A SECURE LOCKABLE DOOR.

4. NEW RAISED FLOOR TO BE CONSTRUCTED WHERE NEW CONDUCTORS

AND CONDUIT WILL BE INSTALLED (SEE DRAWINGS C-002 TO C-004).

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

REV.NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRWN

AutoCAD SHX Text

CHKD

AutoCAD SHX Text

DESIGNED BY:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CROSS CHK'D BY:

AutoCAD SHX Text

APPROVED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

SHEET CHK'D BY:

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text G

AutoCAD SHX Text

REMARKS

AutoCAD SHX Text

NOVEMBER 28, 2022

EXISTING CABLE

ROUTE (IN TRENCH

UNDER EXISTING

FLOOR)

EXISTING UNDERGROUND

CONDUITS UNDER

EXISTING FLOOR TO

SWITCHGEAR

3'-1" 1'-6" 3'-3"

7'-4"

1'-6"

4'-8"

PROPOSED

CABLE

TRAY

EXISTING UNDERGROUND

CONDUITS UNDER

EXISTING FLOOR TO

SWITCHGEAR

C004

USAID: LIBERIA A&E IDIQ TASK ORDER 2

SUBTASK 4: SOLARIZATION OF JFK HOSPITAL

NEONATAL INTENSIVE CARE UNIT

100% DESIGN SUBMITTAL - NOT FOR CONSTRUCTION

1310 N Courthouse Rd, Ste 610 Arlington, VA 22201 Ph: +1 703 829 6133

JFK HOSPITAL NICU

SOLARIZATION

WIRING TRENCH AND CABLE TRAY LAYOUT C-002

N

EXISTING WIRING TRENCH LAYOUT

SCALE: 3/4" = 1'

PRPOSED CABLE TRAY LAYOUT

SCALE: 3/4" = 1'

NOTES:

1. NEW CONDUCTORS AND

CONDUIT TO RUN UNDER THE

ELECTRICAL ROOM FLOOR

2. NEW CONDUIT TO BE INSTALLED

IN EITHER THE EXISTING WIRING

TRENCH OR IN A NEW CABLE

TRAY. FINAL DETERMINATION OF

CONDUIT LOCATIONS TO BE

DETERMINED BY INSTALLER.

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

REV.NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRWN

AutoCAD SHX Text

CHKD

AutoCAD SHX Text

DESIGNED BY:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CROSS CHK'D BY:

AutoCAD SHX Text

APPROVED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

SHEET CHK'D BY:

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text G

AutoCAD SHX Text

REMARKS

AutoCAD SHX Text

NOVEMBER 28, 2022

7'-10"

BATTERY

CABINET

CONCRETE

PEDESTAL

C004

15'-7"

7'-10"

C004

USAID: LIBERIA A&E IDIQ TASK ORDER 2

SUBTASK 4: SOLARIZATION OF JFK HOSPITAL

NEONATAL INTENSIVE CARE UNIT

100% DESIGN SUBMITTAL - NOT FOR CONSTRUCTION

1310 N Courthouse Rd, Ste 610 Arlington, VA 22201 Ph: +1 703 829 6133

JFK HOSPITAL NICU

SOLARIZATION

EQUIPMENT ROOM RAISED FLOOR-1 C-003

CONCRETE PEDESTAL PLAN

SCALE: 3/4" = 1'

RAISED FLOOR WOOD FRAMING PLAN

SCALE: 3/4" = 1'

N

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

REV.NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRWN

AutoCAD SHX Text

CHKD

AutoCAD SHX Text

DESIGNED BY:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CROSS CHK'D BY:

AutoCAD SHX Text

APPROVED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

SHEET CHK'D BY:

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text G

AutoCAD SHX Text

REMARKS

AutoCAD SHX Text

NOVEMBER 28, 2022

C004

PROPOSED WOODEN

RAISED FLOOR

EXISTING 5" CONCRETE

FLOOR

CABLE TRAY

BENEATH

RAISED FLOOR

HARDWOOD

TIMBER FRAMING

CONCRETE

PADS

8"

BATTERY CABINET

USAID: LIBERIA A&E IDIQ TASK ORDER 2

SUBTASK 4: SOLARIZATION OF JFK HOSPITAL

NEONATAL INTENSIVE CARE UNIT

100% DESIGN SUBMITTAL - NOT FOR CONSTRUCTION

1310 N Courthouse Rd, Ste 610 Arlington, VA 22201 Ph: +1 703 829 6133

JFK HOSPITAL NICU

SOLARIZATION

ELECTRICAL ROOM RAISED FLOOR-2 C-004

RAISED FLOOR WOOD PANEL PLAN

SCALE: 3/4" = 1'

RAISED FLOOR WOOD SECTION

SCALE: 3/4" = 1'

N

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

REV.NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRWN

AutoCAD SHX Text

CHKD

AutoCAD SHX Text

DESIGNED BY:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CROSS CHK'D BY:

AutoCAD SHX Text

APPROVED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

SHEET CHK'D BY:

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text G

AutoCAD SHX Text

REMARKS

AutoCAD SHX Text

NOVEMBER 28, 2022

E002

E102

E003

AC OUTPUT LOAD

CENTER

INVERTER INVERTER INVERTER INVERTER INVERTER INVERTER

BATTERY RACK

BATTERY

COMBINER

MNBCB 1000/100

BATTERY

COMBINER

MNBCB 1000/100

BATTERY

COMBINER

MNBCB 1000/100

CHARGE

CONT

CHARGE

CONT

CHARGE

CONT

COMMUNICATIONS

PORT AND CONTROLS

15'-7"

7'-10"

AIR CONDITIONER

E004

PV

COMBINER

BOXES

BATTERY RACKBATTERY RACK BATTERY RACK

AC INPUT LOAD

CENTER

COMMUNICATIONS

PORT AND CONTROLS

0' 1' 2' 3' 4' 5'1'

USAID: LIBERIA A&E IDIQ TASK ORDER 2

SUBTASK 4: SOLARIZATION OF JFK HOSPITAL

NEONATAL INTENSIVE CARE UNIT

100% DESIGN SUBMITTAL - NOT FOR CONSTRUCTION

1310 N Courthouse Rd, Ste 610 Arlington, VA 22201 Ph: +1 703 829 6133

JFK HOSPITAL NICU

SOLARIZATION

ELECTRICAL ROOM EQUIPMENT LAYOUT E-001

ELECTRICAL ROOM LAYOUT

SCALE: 1-1/4" = 1'

N

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

REV.NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRWN

AutoCAD SHX Text

CHKD

AutoCAD SHX Text

DESIGNED BY:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CROSS CHK'D BY:

AutoCAD SHX Text

APPROVED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

SHEET CHK'D BY:

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text G

AutoCAD SHX Text

REMARKS

AutoCAD SHX Text

NOVEMBER 28, 2022

MIDNITE SOLAR

MNBCB 1000/100

MIDNITE SOLAR

MNBCB 1000/100

MIDNITE SOLAR

MNBCB 1000/100

RAISED FLOOR

15'-7"15'-7"

CABLE TRAY

RAISED FLOOR CABLE

TRAY

13'

OUTBACK

MATE 3S

OUTBACK

HUB10

PORT

MIN 36"

ABOVE

FLOOR

MIN 6"

C H

AR

G

E C

O N

TR

O

LL

ER

C H

AR

G

E C

O N

TR

O

LL

ER

C H

AR

G

E C

O N

TR

O

LL

ER

C H

AR

G

E C

O N

TR

O

LL

ER

C H

AR

G

E C

O N

TR

O

LL

ER

RAISED FLOOR

7'-10"

RAISED FLOOR CABLE

TRAY

13'

C H

AR

G

E C

O N

TR

O

LL

ER

CABLE TRAY

1" (25 mm) DIA

EMT CONDUIT

(TYP.)

USAID: LIBERIA A&E IDIQ TASK ORDER 2

SUBTASK 4: SOLARIZATION OF JFK HOSPITAL

NEONATAL INTENSIVE CARE UNIT

100% DESIGN SUBMITTAL - NOT FOR CONSTRUCTION

1310 N Courthouse Rd, Ste 610 Arlington, VA 22201 Ph: +1 703 829 6133

JFK HOSPITAL NICU

SOLARIZATION

ELECTRICAL ROOM SECTIONS - 1 E-002

BATTERY COMBINER BOX LAYOUT

SCALE: NTS6 CHARGE CONTROLLER LAYOUT

SCALE: NTS7

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

REV.NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRWN

AutoCAD SHX Text

CHKD

AutoCAD SHX Text

DESIGNED BY:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CROSS CHK'D BY:

AutoCAD SHX Text

APPROVED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

SHEET CHK'D BY:

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text G

AutoCAD SHX Text

REMARKS

AutoCAD SHX Text

NOVEMBER 28, 2022

2" MIN

OUTBACK

MATE 3S

OUTBACK

HUB10

PORT

INVERTER

#1

INV

LOAD

CENTER

INV

LOAD

CENTER

INV

LOAD

CENTER

INV

LOAD

CENTER

INV

LOAD

CENTER

INV

LOAD

CENTER

CABLE TRAY

3 PHASE

AC

OUTPUT

LOAD

CENTER

15'-7"15'-7"

AIR CONDITIONER

RAISED FLOORRAISED FLOOR CABLE

TRAY

13'

INVERTER

#2

INVERTER

#3

INVERTER

#4

INVERTER

#5

INVERTER

#6

USAID: LIBERIA A&E IDIQ TASK ORDER 2

SUBTASK 4: SOLARIZATION OF JFK HOSPITAL

NEONATAL INTENSIVE CARE UNIT

100% DESIGN SUBMITTAL - NOT FOR CONSTRUCTION

1310 N Courthouse Rd, Ste 610 Arlington, VA 22201 Ph: +1 703 829 6133

JFK HOSPITAL NICU

SOLARIZATION

ELECTRICAL ROOM SECTIONS - 2 E-003

INVERTER LAYOUT

SCALE: NTS8

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

REV.NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRWN

AutoCAD SHX Text

CHKD

AutoCAD SHX Text

DESIGNED BY:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CROSS CHK'D BY:

AutoCAD SHX Text

APPROVED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

SHEET CHK'D BY:

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text G

AutoCAD SHX Text

REMARKS

AutoCAD SHX Text

NOVEMBER 28, 2022

13'

RAISED FLOORRAISED FLOOR CABLE

TRAY

2'-5"1'-10"

1'-7"

5'-3"

3'-7"

1'-7"

1'-8"

E104

3'-7"1'-10" 2'-5"

2'-11"

1'-7"

1'-6"

1'-7"

1'-6"

1'-7"

1'-6"

1'-7"

1'-10"

USAID: LIBERIA A&E IDIQ TASK ORDER 2

SUBTASK 4: SOLARIZATION OF JFK HOSPITAL

NEONATAL INTENSIVE CARE UNIT

100% DESIGN SUBMITTAL - NOT FOR CONSTRUCTION

1310 N Courthouse Rd, Ste 610 Arlington, VA 22201 Ph: +1 703 829 6133

JFK HOSPITAL NICU

SOLARIZATION

ELECTRICAL ROOM SECTIONS - 3 E-004

BATTERY LAYOUT

SCALE: NTS9 BATTERY PLAN VIEW

SCALE: NTS10

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

REV.NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRWN

AutoCAD SHX Text

CHKD

AutoCAD SHX Text

DESIGNED BY:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CROSS CHK'D BY:

AutoCAD SHX Text

APPROVED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

SHEET CHK'D BY:

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text G

AutoCAD SHX Text

REMARKS

AutoCAD SHX Text

NOVEMBER 28, 2022

S

S

18,000 BTU A/C 9,000 BTU A/C

LEGEND

LIGHT FIXTURE

RECEPTICAL

S SINGLE SWITCH

A/C AIR CONDITIONER

SWITCH LINE

CIRCUIT LINE

PANEL BOARD

S

2' 0' 8' 12'4'

USAID: LIBERIA A&E IDIQ TASK ORDER 2

SUBTASK 4: SOLARIZATION OF JFK HOSPITAL

NEONATAL INTENSIVE CARE UNIT

100% DESIGN SUBMITTAL - NOT FOR CONSTRUCTION

1310 N Courthouse Rd, Ste 610 Arlington, VA 22201 Ph: +1 703 829 6133

JFK HOSPITAL NICU

SOLARIZATION

EQUIPMENT ROOM LIGHTING PLAN E-005

JFK HOSPITAL NICU SOLARIZATION EQUIPMENT ROOM LIGHTING PLAN

SCALE: 3/8" = 1'N

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

REV.NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRWN

AutoCAD SHX Text

CHKD

AutoCAD SHX Text

DESIGNED BY:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CROSS CHK'D BY:

AutoCAD SHX Text

APPROVED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

SHEET CHK'D BY:

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text G

AutoCAD SHX Text

REMARKS

AutoCAD SHX Text

NOVEMBER 28, 2022

TO FACILITY

LOADS

K M

AC

OUTPUT

LOAD

CENTER

AC INPUT

LOAD

CENTER

7 8

H

INVERTER

INVERTER

LOAD

CENTER

C

A

B D

COMBINER/

DISCONNECT

CHARGE

CONTROLLER

INVERTER LOAD

CENTER

C

1 2 3

1 2 3

1 2 3

A

B D

COMBINER/

DISCONNECT

CHARGE

CONTROLLER

INVERTER LOAD

CENTER

C

1 2 3

1 2 3

1 2 3

A

B D

COMBINER/

DISCONNECT

CHARGE

CONTROLLER

INVERTER LOAD

CENTER

C

1 2 3

1 2 3

1 2 3

A

B D

COMBINER/

DISCONNECT

CHARGE

CONTROLLER

INVERTER LOAD

CENTER

C

1 2 3

1 2 3

1 2 3

A

B D

COMBINER/

DISCONNECT

CHARGE

CONTROLLER

INVERTER LOAD

CENTER

C

1 2 3

1 2 3

1 2 3

A

B D

COMBINER/

DISCONNECT

CHARGE

CONTROLLER

INVERTER LOAD

CENTER

C

1 2 3

1 2 3

1 2 3

7 8

H

INVERTER

INVERTER

LOAD

CENTER

C

H

INVERTER

INVERTER

LOAD

CENTER

C

H

INVERTER

INVERTER

LOAD

CENTER

C

H

INVERTER

INVERTER

LOAD

CENTER

C

H

INVERTER

INVERTER

LOAD

CENTER

C

MNBCB

1000/100

COMBINER

BOX

BATT BATT BATT

BATT BATT BATT

BATT BATT BATT

BATT BATT BATT

BATTBATTBATT

BATTBATTBATT

BATTBATTBATT

BATTBATTBATT

5 5

7MNBCB

1000/100

COMBINER

BOX

BATT BATT BATT

BATT BATT BATT

BATT BATT BATT

BATT BATT BATT

BATTBATTBATT

BATTBATTBATT

BATTBATTBATT

BATTBATTBATT

5 5

7MNBCB

1000/100

COMBINER

BOX

BATT BATT BATT

BATT BATT BATT

BATT BATT BATT

BATT BATT BATT

BATTBATTBATT

BATTBATTBATT

BATTBATTBATT

BATTBATTBATT

5 5

USAID: LIBERIA A&E IDIQ TASK ORDER 2

SUBTASK 4: SOLARIZATION OF JFK HOSPITAL

NEONATAL INTENSIVE CARE UNIT

100% DESIGN SUBMITTAL - NOT FOR CONSTRUCTION

1310 N Courthouse Rd, Ste 610 Arlington, VA 22201 Ph: +1 703 829 6133

JFK HOSPITAL NICU

SOLARIZATION

ELECTRICAL ONE LINE E-006

JFK HOSPITAL NICU SOLARIZATION ELECTRICAL ONE LINE DIAGRAM

SCALE: NTS

NOTES:

1. SEE DRAWING E-007 FOR

CONDUCTOR AND

EQUIPMENT TABLES

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

REV.NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRWN

AutoCAD SHX Text

CHKD

AutoCAD SHX Text

DESIGNED BY:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CROSS CHK'D BY:

AutoCAD SHX Text

APPROVED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

SHEET CHK'D BY:

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text G

AutoCAD SHX Text

REMARKS

AutoCAD SHX Text

NOVEMBER 28, 2022

EQUIPMENT

TAG QUANTITY NAME EQUIPMENT MODEL DESCRIPTION

A 6 COMBINER BOX GROUP MAXEON 485 W MODULES

3 MODULE STRINGS, 4

STRINGS PER COMBINER

DISCONNECT (X3) AND3

MODULE STRINGS, 3

STRINGS PER COMBINER

BOX (X2)

B 6 PV COMBINER DISCONNECT MIDNITE SOLAR MNPV4

COMBINER DISCONNECT

3 STRINGS FUSED ON

POSITIVE WIRES IN EACH

COMBINER DISCONNECT

C 6 INVERTER LOAD CENTER OUTBACK GSLC 175-230

D 6 CHARGE CONTROLLER OUTBACK FM100

E 3 BATTERY COMBINER BOX MIDNITE SOLAR MNBCB

1000/100

F 72 BATTERY BANK SIMPLIPHI LITHIUM 3.8-48-M

3 BATTERIES PER STRING

CONNECTED IN PARALLEL

TO BATTERY BUS BAR

G 3 BATTERY COMBINER BOX MIDNITE SOLAR MNBCB

1000/100

INCLUDES 6x250 A

INVERTER BREAKERS,

6x125 A CHARGE

CONTROLLER BREAKERS,

AND 12x125 A BATTERY

BREAKERS

H 6 INVERTER OUTBACK GS7048E 7 kWac INVERTERS

K 1 AC OUT LOAD CENTER 3-PHASE, 9 400A, MAIN LUG, MINIMUM

16 CIRCUIT, 8 DP BREAKER

M 1 AC INPUT LOAD CENTER

FEEDER SCHEDULE

TAG WIRE TYPE WIRE SIZE (mm2) DESCRITPION

1 COPPER PV WIRE,

1000V 6 PV ARRAY TO PV COMBINER/DISCONNECT

2 COPPER THHN, 600V 16

PV INPUT FROM PV COMBINER/DISCONNECT

TO PV INPUT BREAKER IN INVERTER LOAD

CENTER

3 COPPER THHN, 600V 16

PV INPUT FROM INVERTER LOAD CENTER PV

INPUT BREAKER TO CHARGE CONTROLLER

PV (+) TERMINAL AND PV (-) FROM PV ARRAY

COMBINER/DISCONNECT TO CHARGE

CONTROLLER PV (-) TERMINAL

4 SGT BATTERY CABLE

60VDC

35 CHARGE CONTROLLER MNBCB 1000/100

COMBINER BOX BUS BARS

5 SGT BATTERY CABLE

60VDC

10 BATTERY TO POSITIVE AND NEGATIVE BUS

BAR

6 SGT BATTERY CABLE

60VDC

BATTERY BUS BARS (POSITIVE AND

NEGATIVE) TO MNBCB 1000/100 COMBINER

BOX BUS BARS

7 SGT BATTERY CABLE

60VDC

70 BATTERY COMBINER MNBCB 1000/10 TO

INVERTER LOAD CENTER

8 COPPER THHN, 600V 16

50A AC OUTPUT BREAKER IN OUTBACK

RADIAN GSLC TO 45A DP BREAKER IN AC

LOAD CENTER

9 COPPER THHN 600 25 INVERTER OUTPUT LOAD CENTER TO NICU

DISTRIBUTION BOARD

GROUNDING CONDUCTORS

WIRE TYPE WIRE SIZE (MM2) DESCRITPION

GROUNDING WEEB WEEB PV MODULES TO RAILS

BARE COPPER STRAND,

600V 25 PV ARRAY RACK RAILS TO GROUNDING RODS

BARE COPPER STRAND,

600V 25 PV COMBINER/DISCONNECT TO GROUND

RODS

YELLOW/GREEN

CONDUCTOR 10 OUTBACK RADIAN GSLC TO GROUNDING BUS

BAR IN WIRING TROUGH

YELLOW/GREEN

CONDUCTOR 10 INVERTER TO OUTBCK RADIAN GSLC

YELLOW/GREEN

CONDUCTOR 10 GROUNDING BUS BAR IN CABLE TRAY TO

EARTH GROUND

YELLOW/GREEN

CONDUCTOR 10 CHARGE CONTROLLERS TO GROUNDING BUS

BAR IN WIRING TROUGH

YELLOW/GREEN

CONDUCTOR 10 MNBCB 1000/100 BATTERY COMBINERS TO

GROUNDING BUS BAR IN WIRING TROUGH

YELLOW/GREEN

CONDUCTOR 10 AC OUTPUT LOAD CENTER TO GROUNDING

BUS BAR IN WIRING TROUGH

BARE COPPER STRAND,

600V 50 LIGHTNING ARRESTOR TO GROUNDING ROD

USAID: LIBERIA A&E IDIQ TASK ORDER 2

SUBTASK 4: SOLARIZATION OF JFK HOSPITAL

NEONATAL INTENSIVE CARE UNIT

100% DESIGN SUBMITTAL - NOT FOR CONSTRUCTION

1310 N Courthouse Rd, Ste 610 Arlington, VA 22201 Ph: +1 703 829 6133

JFK HOSPITAL NICU

SOLARIZATION

CONDUCTOR AND EQUIPMENT TABLES E-007

JFK HOSPITAL NICU SOLARIZATION ELECTRICAL ONE LINE DIAGRAM - TABLES

SCALE: NTS

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

REV.NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRWN

AutoCAD SHX Text

CHKD

AutoCAD SHX Text

DESIGNED BY:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CROSS CHK'D BY:

AutoCAD SHX Text

APPROVED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

SHEET CHK'D BY:

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text G

AutoCAD SHX Text

REMARKS

AutoCAD SHX Text

NOVEMBER 28, 2022

L1

L2

L3

N

L1 L3L2

INV 1

INV 2

INV 3

INV 4

A/C

Light/spare

Light/spare

4 x 25 mm2

10 x 10 mm2

1 x 10 mm2

INVERTER AC INPUT LOAD CENTER

EXISTING 3P

BREAKER MDB

45A

INV 5

INV 6

45A

45A

45A

45A

45A45A

36A

10A

10A

100A

100A

100A MAINTENANCE

BYPASS MANUAL

TRANSFER SWITCH

1P (18k BTU A/C)

1P (LIGHTS)

1 x 10 mm2

INVERTER AC INPUT LOAD CENTER

EXISTING 3P

BREAKER MDB 36A

10A

10A

45A

100A 3P

1P (SPARE)

6 x 1P (INVERTERS 1-6)

NICU

100A TRANSFER

SWITCH 3P

FROM INVERTER

POWER

100A 3P100A 3P

USAID: LIBERIA A&E IDIQ TASK ORDER 2

SUBTASK 4: SOLARIZATION OF JFK HOSPITAL

NEONATAL INTENSIVE CARE UNIT

100% DESIGN SUBMITTAL - NOT FOR CONSTRUCTION

1310 N Courthouse Rd, Ste 610 Arlington, VA 22201 Ph: +1 703 829 6133

JFK HOSPITAL NICU

SOLARIZATION

AC SUPPLY TO INVERTERS E-008

AC SUPPLY TO INVERTERS

SCALE: NTS

MAINTENANCE BYPASS SWITCH ONE-LINE DIAGRAM

SCALE: NTS

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

REV.NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRWN

AutoCAD SHX Text

CHKD

AutoCAD SHX Text

DESIGNED BY:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CROSS CHK'D BY:

AutoCAD SHX Text

APPROVED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

SHEET CHK'D BY:

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text G

AutoCAD SHX Text

REMARKS

AutoCAD SHX Text

NOVEMBER 28, 2022

N

L1

L2

L3

45A 3X100A

NICU

4 x 25 mm2

INV- 1 INV- 2 INV- 3

INV- 4 INV- 5 INV- 6

45A 45A 45A 45A 45A

6 x 16 mm2

INVERTER OUTPUT LOAD CENTER

AC LIGHTS

6 x 16 mm2

USAID: LIBERIA A&E IDIQ TASK ORDER 2

SUBTASK 4: SOLARIZATION OF JFK HOSPITAL

NEONATAL INTENSIVE CARE UNIT

100% DESIGN SUBMITTAL - NOT FOR CONSTRUCTION

1310 N Courthouse Rd, Ste 610 Arlington, VA 22201 Ph: +1 703 829 6133

JFK HOSPITAL NICU

SOLARIZATION

INVERTER OUTPUT CIRCUIT DIAGRAM E-009

INVERTER OUTPUT CIRCUIT DIAGRAM

SCALE: NTS

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

REV.NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRWN

AutoCAD SHX Text

CHKD

AutoCAD SHX Text

DESIGNED BY:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CROSS CHK'D BY:

AutoCAD SHX Text

APPROVED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

SHEET CHK'D BY:

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text G

AutoCAD SHX Text

REMARKS

AutoCAD SHX Text

NOVEMBER 28, 2022

INVERTER #1

INVERTER #2

CHARGE CONTROLLER #1

CHARGE CONTROLLER #2

BATTERY RACKS #1

SHELF #1

BATTERY RACK #1

SHELF #2

BATTERY RACK #1

SHELF #3

BATTERY RACK #2

SHELF #1

COMBINER BOX

(MNBCB 1000/100)

8 x 25 mm2

4 x 70 mm2

4 x 35 mm2

8 x 10 mm2 (TYP. OF ALL

BATTERIES)

USAID: LIBERIA A&E IDIQ TASK ORDER 2

SUBTASK 4: SOLARIZATION OF JFK HOSPITAL

NEONATAL INTENSIVE CARE UNIT

100% DESIGN SUBMITTAL - NOT FOR CONSTRUCTION

1310 N Courthouse Rd, Ste 610 Arlington, VA 22201 Ph: +1 703 829 6133

JFK HOSPITAL NICU

SOLARIZATION

BATTERY STRING CONNECTIONS E-010

BATTERY STRING CONNECTIONS

SCALE: NTS

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

REV.NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRWN

AutoCAD SHX Text

CHKD

AutoCAD SHX Text

DESIGNED BY:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CROSS CHK'D BY:

AutoCAD SHX Text

APPROVED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

SHEET CHK'D BY:

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text G

AutoCAD SHX Text

REMARKS

AutoCAD SHX Text

NOVEMBER 28, 2022

MIDNITE SOLAR

MNBCB-1000/100 BATTERY

COMBINER BOX #3

OUTBACK

MATE 3S

ETHERNET CABLES FROM HUB 10 TO

EACH CHARGE CONTROLLER, MATE

3S, AND FLEXNET DC (OUTSIDE OF

CONDUIT)

OUTBACK

FM 100

CHARGE

CONT. #5

OUTBACK

FM 100

CHARGE

CONT. #3

OUTBACK

FM 100

CHARGE

CONT. #6

OUTBACK

FM 100

CHARGE

CONT. #4

INPUT FROM PV ARRAY

THROUGH GSLC LOAD

CENTR (TYP. FOR ALL 6

CHARGE CONTROLLERS)

PV

INPUT

PV

INPUT

PV

INPUT

FROM 4 BATTERY

BUS BARS

OUTBACK

FM 100

CHARGE

CONT. #2

PV

INPUT

OUTBACK

FM 100

CHARGE

CONT. #1

TO INVERTERS

#5 AND #6

OUTBACK HUB 10 PORT #1

(SEE SHEET E-113)

FLEXNET DC

MIDNITE SOLAR

MNBCB-1000/100 BATTERY

COMBINER BOX #2

FROM 4

BATTERY

BUS BARS

TO INVERTERS

#3 AND #4

FLEXNET DC

MIDNITE SOLAR

MNBCB-1000/100 BATTERY

COMBINER BOX #1

FROM 4

BATTERY

BUS BARS

TO INVERTERS

#1 AND #2

FLEXNET DC

PV

INPUT

USAID: LIBERIA A&E IDIQ TASK ORDER 2

SUBTASK 4: SOLARIZATION OF JFK HOSPITAL

NEONATAL INTENSIVE CARE UNIT

100% DESIGN SUBMITTAL - NOT FOR CONSTRUCTION

1310 N Courthouse Rd, Ste 610 Arlington, VA 22201 Ph: +1 703 829 6133

JFK HOSPITAL NICU

SOLARIZATION

CHARGE CONTROLLER RISER DIAGRAM E-011

CHARGE CONTROLLER RISER DIAGRAM

SCALE: NTS

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

REV.NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRWN

AutoCAD SHX Text

CHKD

AutoCAD SHX Text

DESIGNED BY:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CROSS CHK'D BY:

AutoCAD SHX Text

APPROVED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

SHEET CHK'D BY:

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text G

AutoCAD SHX Text

REMARKS

AutoCAD SHX Text

NOVEMBER 28, 2022

GS7048E

INVERTER

MASTER

OUTBACK GSLC

LOAD CENTER GSLC

175-230

OUTBACK

GS7048E

INVERTER SUB

#1

OUTBACK GSLC

LOAD CENTER GSLC

175-230

OUTBACK

GS7048E

INVERTER SUB

#2

OUTBACK GSLC

LOAD CENTER GSLC

175-230

ETHERNET CABLE TO EACH INVERTER, MATE

3S, AND FLEXNET DC FOR SYSTEM

COMMUNICATIONS

1 2 4

INVERTER LOAD CENTER CONNECTION LEGEND

1. PV COMBINER DISCONNECT

2. CHARGE CONTROLLER

3. MNBCB-2000/200 BATTERY COMBINER BOX

4. AC OUT LOAD CENTER

OUTBACK

GS7048E

INVERTER SUB

#3

OUTBACK GSLC

LOAD CENTER GSLC

175-230

OUTBACK

GS7048E

INVERTER SUB

#4

OUTBACK GSLC

LOAD CENTER GSLC

175-230

OUTBACK

GS7048E

INVERTER SUB

#5

OUTBACK GSLC

LOAD CENTER GSLC

175-230

INVERTER FLEXNET DC

(IN MASTER ONLY)

OUTBACK HUB 10

PORT #2 (SEE

SHEET E-113)

3 1 2 43 1 2 43 1 2 43 2 3 4

OUTBACK

MATE 3S

1 2 43

USAID: LIBERIA A&E IDIQ TASK ORDER 2

SUBTASK 4: SOLARIZATION OF JFK HOSPITAL

NEONATAL INTENSIVE CARE UNIT

100% DESIGN SUBMITTAL - NOT FOR CONSTRUCTION

1310 N Courthouse Rd, Ste 610 Arlington, VA 22201 Ph: +1 703 829 6133

JFK HOSPITAL NICU

SOLARIZATION

INVERTER RISER DIAGRAM E-012

INVERTER RISER DIAGRAM

SCALE: NTS

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

REV.NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRWN

AutoCAD SHX Text

CHKD

AutoCAD SHX Text

DESIGNED BY:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CROSS CHK'D BY:

AutoCAD SHX Text

APPROVED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

SHEET CHK'D BY:

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text G

AutoCAD SHX Text

REMARKS

AutoCAD SHX Text

NOVEMBER 28, 2022

FLEXNET DC

OUTBACK

MATE 3S

6 INVERTERS

OUTBACK HUB

10 PORT #2

OUTBACK

FLEXNET DC

OUTBACK

MATE 3S

6 CHARGE

CONTROLLERS

OUTBACK HUB

10 PORT #1

USAID: LIBERIA A&E IDIQ TASK ORDER 2

SUBTASK 4: SOLARIZATION OF JFK HOSPITAL

NEONATAL INTENSIVE CARE UNIT

100% DESIGN SUBMITTAL - NOT FOR CONSTRUCTION

1310 N Courthouse Rd, Ste 610 Arlington, VA 22201 Ph: +1 703 829 6133

JFK HOSPITAL NICU

SOLARIZATION

MONITORING AND COMMUNICATIONS E-013

MONITORING AND COMMUNICATIONS CONNECTIONS

SCALE: NTS

NOTES

1. ETHERNET CABLE CONNECTING DEVICES TO OUTBACK HUB 10 PORTS

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

REV.NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRWN

AutoCAD SHX Text

CHKD

AutoCAD SHX Text

DESIGNED BY:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CROSS CHK'D BY:

AutoCAD SHX Text

APPROVED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

SHEET CHK'D BY:

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text G

AutoCAD SHX Text

REMARKS

AutoCAD SHX Text

NOVEMBER 28, 2022

20' 20' 20' 12'-8"

19'-4"

19'-9"

18'-8"

ZONE OF PROTECTION

FROM WATER TOWER

LIGHTING ARRESTER

18'-8"

LEGEND

GROUND ROD

LIGHTNING ARRESTER

LIGHTNING PROTECTION

SYSTEM CONDUCTOR

E015

E015

NOTE 4 (DRAWING E-015)

5' 0' 5' 10' 15' 20'

N

JFK HOSPITAL NICU LIGHTNING PROTECTION SYSTEM LAYOUT

SCALE: 1/4" = 1'

NOTES:

1. LIGHTNING PROTECTION SYSTEM DESIGNED IN

ACCORDANCE WITH NFPA 780 2023

2. EACH LIGHTNING ARRESTER SHALL HAVE 2 PATHS TO

GROUND.

3. LIGHTNING ARRESTERS INSTALLED ON TOP OF OR

ON INSIDE VERTICAL SURFACE OF PARAPET

4. CONDUCTORS ON TOP OF OR ON INSIDE VERTICAL

SURFACE OF PARAPET

USAID: LIBERIA A&E IDIQ TASK ORDER 2

SUBTASK 4: SOLARIZATION OF JFK HOSPITAL

NEONATAL INTENSIVE CARE UNIT

100% DESIGN SUBMITTAL - NOT FOR CONSTRUCTION

1310 N Courthouse Rd, Ste 610 Arlington, VA 22201 Ph: +1 703 829 6133

JFK HOSPITAL NICU

SOLARIZATION

LIGHTNING PROTECTION SYSTEM LAYOUT E-014

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

REV.NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRWN

AutoCAD SHX Text

CHKD

AutoCAD SHX Text

DESIGNED BY:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CROSS CHK'D BY:

AutoCAD SHX Text

APPROVED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

SHEET CHK'D BY:

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text G

AutoCAD SHX Text

REMARKS

AutoCAD SHX Text

NOVEMBER 28, 2022

NOTE 1

AND 2 AIR CONDITIONER

NOTE 6

NOTE 5

EXISTING

WIRING TRENCH

NOTE 7

0°

130 ° BEND WITH AT

LEAST A 8" RADIUS

NOTE 8

WATER

TOWER

E015

NOTE 4

NOTE 5

LIGHTING

ARRESTOR

0°

130 ° BEND WITH AT

LEAST A 8" RADIUS

NOTE 4

NOTE 8

130°

NOTE 8

USAID: LIBERIA A&E IDIQ TASK ORDER 2

SUBTASK 4: SOLARIZATION OF JFK HOSPITAL

NEONATAL INTENSIVE CARE UNIT

100% DESIGN SUBMITTAL - NOT FOR CONSTRUCTION

1310 N Courthouse Rd, Ste 610 Arlington, VA 22201 Ph: +1 703 829 6133

JFK HOSPITAL NICU

SOLARIZATION

LIGHTNING PROTECTION AND GROUND ELEVATIONS E-015

SOUTH SIDE ELEVATION - UTILITY BUILDING

SCALE: NTS

WEST SIDE ELEVATION - UTILITY BUILDING

SCALE: NTS1 2

NOTES:

1. 6 MIDNITE SOLAR MNPV4 COMBINER BOXES WITH

50 AMP FUSES AND 300 V BREAKERS

2. PV COMBINER BOXES ENCLOSED IN A 2' x 5' x 0.5'

WATERPROOF AND LOCKABLE PLASTIC BOX

3. 6 WALL PENETRATIONS FROM PV COMBINER

BOXES INTO ELECTRICAL ROOM TO BE

SPECIFIED BY CONTRACTOR IN FIELD

4. 50 mm2 BARE COPPER, 1" (25 mm) DIA PVC

CONDUIT

5. 25 mm2 BARE COPPER 1" (25 mm) DIA PVC

CONDUIT FROM PV ARRAY GROUND BUS BARS

6. 6 mm2 COPPER PV WIRE, 1/2" (13 mm) DIA PVC

CONDUIT

7. 16 mm2 COPPER PV WIRE, 1" (25mm) DIA PVC

CONDUIT FROM PV COMBINER BOXES TO

UNDERGROUND WIRING TRENCH

8. GROUND ROD AT LEAST 8' LONG AND EXTEND

VERTICALLY UNDERGROUND AT LEAST 10'

9. LIGHTNING PROTECTION SYSTEM DESIGN

(LIGHTNING ARRESTERS, GROUND RODS,

CONDUCTORS, AND CONNECTING HARDWARE)

TO COMPLY WITH NFPA 780

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

REV.NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRWN

AutoCAD SHX Text

CHKD

AutoCAD SHX Text

DESIGNED BY:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CROSS CHK'D BY:

AutoCAD SHX Text

APPROVED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

SHEET CHK'D BY:

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text G

AutoCAD SHX Text

REMARKS

AutoCAD SHX Text

NOVEMBER 28, 2022

Grounding Pit section @ G

5'

ELECTRODE IS

6" DIA, 5' DEEP

6 INVERTERS 6 CHARGE CONTROLLERS 3 BATTERY COMBINER BOXES

INVERTER AC INPUT LOAD CENTER

INVERTER LOAD CENTER

PV ARRAY

GROUNDING

PIT

PV ARRAY

ROWS 1-3

PV ARRAY

GROUNDING

PIT

PV ARRAY

ROWS 4-7

PV ARRAY

GROUNDING

PIT

6 PV

COMBINER

BOXES

PV ARRAY

GROUNDING PIT

6'-7"

13'-2"

TO EQUIPMENT

ROOM BUS BAR

E015

TO PV PANEL BUS

BAR 1

TO PV PANEL BUS

BAR 2

TO PV COMBINER

BOXES

USAID: LIBERIA A&E IDIQ TASK ORDER 2

SUBTASK 4: SOLARIZATION OF JFK HOSPITAL

NEONATAL INTENSIVE CARE UNIT

100% DESIGN SUBMITTAL - NOT FOR CONSTRUCTION

1310 N Courthouse Rd, Ste 610 Arlington, VA 22201 Ph: +1 703 829 6133

JFK HOSPITAL NICU

SOLARIZATION

SOLAR PV GROUND DETAILS E-016

COPPER BUS BARS

SCALE: NTS

GROUNDING PIT SECTION

SCALE: NTS

PV ARRAY GROUNDING PIT MESH PLAN VIEW

SCALE: NTS4

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

REV.NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRWN

AutoCAD SHX Text

CHKD

AutoCAD SHX Text

DESIGNED BY:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CROSS CHK'D BY:

AutoCAD SHX Text

APPROVED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

SHEET CHK'D BY:

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text G

AutoCAD SHX Text

REMARKS

AutoCAD SHX Text

NOVEMBER 28, 2022

18,000 BTU A/C 9,000 BTU A/C

2' 0' 8' 12'4'

USAID: LIBERIA A&E IDIQ TASK ORDER 2

SUBTASK 4: SOLARIZATION OF JFK HOSPITAL

NEONATAL INTENSIVE CARE UNIT

100% DESIGN SUBMITTAL - NOT FOR CONSTRUCTION

1310 N Courthouse Rd, Ste 610 Arlington, VA 22201 Ph: +1 703 829 6133

JFK HOSPITAL NICU

SOLARIZATION

EQUIPMENT ROOM MECHANICAL M-001

JFK HOSPITAL NICU SOLARIZATION EQUIPMENT AIR CONDITIONERS

SCALE: 3/8" = 1'N

AutoCAD SHX Text

DRAWING NO.

AutoCAD SHX Text

REV.NO.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

DRWN

AutoCAD SHX Text

CHKD

AutoCAD SHX Text

DESIGNED BY:

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CROSS CHK'D BY:

AutoCAD SHX Text

APPROVED BY:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

SHEET CHK'D BY:

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text C

AutoCAD SHX Text D

AutoCAD SHX Text E

AutoCAD SHX Text F

AutoCAD SHX Text G

AutoCAD SHX Text

REMARKS

AutoCAD SHX Text

NOVEMBER 28, 2022

Sheets and Views
JFK NICU Solar PV_Final-G-001
JFK NICU Solar PV_Final-G-002
JFK NICU Solar PV_Final-G-003
JFK NICU Solar PV_Final-PV-001
JFK NICU Solar PV_Final-PV-002
JFK NICU Solar PV_Final-PV-003
JFK NICU Solar PV_Final-C-001
JFK NICU Solar PV_Final-C-002
JFK NICU Solar PV_Final-C-003
JFK NICU Solar PV_Final-C-004
JFK NICU Solar PV_Final-E-001
JFK NICU Solar PV_Final-E-002
JFK NICU Solar PV_Final-E-003
JFK NICU Solar PV_Final-E-004
JFK NICU Solar PV_Final-E-005
JFK NICU Solar PV_Final-E-006
JFK NICU Solar PV_Final-E-007
JFK NICU Solar PV_Final-E-008
JFK NICU Solar PV_Final-E-009
JFK NICU Solar PV_Final-E-010
JFK NICU Solar PV_Final-E-011
JFK NICU Solar PV_Final-E-012
JFK NICU Solar PV_Final-E-013
JFK NICU Solar PV_Final-E-014
JFK NICU Solar PV_Final-E-015
JFK NICU Solar PV_Final-E-016
JFK NICU Solar PV_Final-M-001

File details come from the government source that posted it. Updated .