This document is a Bill of Quantities (BOQ) for a solar photovoltaic (PV) system to be installed at the John F. Kennedy (JFK) Hospital Neonatal Intensive Care Unit (NICU) in Liberia. The BOQ lists the detailed equipment, materials, and labor required for the system, including inverters, charge controllers, PV modules, batteries, wiring, and civil works. The total estimated cost is $0, with a breakdown of material, labor, transportation, overhead, and profit costs.
The related federal contract opportunity is for the "Solarization of John F. Kennedy (JFK) Hospital Neonatal Intensive Care Unit (NICU)," solicitation number 72066924R00002. The objective is to install a solar PV system alongside existing diesel generators to provide reliable power and address challenges with grid outages and generator malfunctions, ensuring continuous power to critical NICU equipment. The system must be able to sustain NICU operations for at least six hours during power disruptions.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
IGCE
| NICU Solar Bill of Quantities (BOQ) | ||||||
| Item No. | Description | Name of Item | Quantity | Unit | Unit Cost | Total Cost |
| 1 | Mobilization and demobilzation | 1 | LS | $0 | $0 | |
| 2 | Provide for insurance/performance bond | 1 | LS | $0 | $0 | |
| Inverters | ||||||
| 3 | Inverters | OutBack Power Systems GS7048E | 7 | number | $0 | $0 |
| 4 | Inverter load center | OutBack Power Systems GSLC 175-230 | 6 | number | $0 | $0 |
| 5 | Inverters support stand | Aluminum support stand, 4.83 x 9.67 x 0.42 (ft) (H x W x D) | 1 | number | $0 | $0 |
| 6 | AC output load center | 3-phase, 12 breaker panel | 1 | number | $0 | $0 |
| 7 | AC input load center | 3-phase, 12 breaker panel | 1 | number | $0 | $0 |
| 8 | Transfer switch | 4 pole transfer switch, 100A | 1 | number | $0 | $0 |
| Controls and Monitorig | ||||||
| 9 | System controls | OutBack Power Systems Mate3S | 5 | number | $0 | $0 |
| 10 | Communications hub | OutBack Power Systems HUB 10 | 2 | number | $0 | $0 |
| 11 | DC shunt monitoring device | OutBack Power Systems FLEXnet DC | 2 | number | $0 | $0 |
| Charge Controllers | ||||||
| 12 | Charge controller | OutBack Power Systems FLEXmax 100 | 8 | number | $0 | $0 |
| PV Array | 0 | |||||
| 13 | PV modules | Maxeon SPR X22-485-COM | 65 | number | $0 | $0 |
| 14 | PV combiner disconnects | Midnite Solar MNPV4 Deluxe | 6 | number | $0 | $0 |
| 15 | PV combiner disconnect security box | Plastic lockable box (3.5'x5'x8") | 1 | number | $0 | $0 |
| 16 | PV wire | PV Wire, MC 4 connectors ( # of Charge controllers x 3 strings each) | 20 | number | $0 | $0 |
| 17 | PV racking | Unirac RM5 | 31,600 | LS | $0 | $0 |
| 18 | Miscelaneous and incidentals | Conduit, junction box (12"x8"x6"), cable ties, etc | 1 | number | $0 | $0 |
| Battery | ||||||
| 19 | Batteries | Simpliphi LFP Lithium 3.8-48 | 78 | number | $0 | $0 |
| 20 | Battery racks | Battery Racking | 6 | number | $0 | $0 |
| 21 | Battery connecting strips | 600A, positive and negative strip, 7 connections (3 per battery rack) with enclosure | 28 | number | $0 | $0 |
| 22 | Battery combiner w/ disconnect breaker | Midnite Solar MNBCB 1000/100 | 3 | number | $0 | $0 |
| 23 | Battery combiner breakers | Midnite Solar inverter breakers - 250 A | 8 | number | $0 | $0 |
| 24 | Battery combiner breakers | Midnite Solar charge controller breakers -125 A | 6 | number | $0 | $0 |
| 25 | Battery combiner breakers | Midnite Solar battery breakers - 125 A | 15 | number | $0 | $0 |
| Wiring and cables | ||||||
| 26 | Minigrid electrical balance of system | Interior cables including bus bars, wiring, conduit wiring troughs, disconnects, grounding, and all necessary fixing accessories, as specified and as shown on drawings E-101 to E-112. | 1 | LS | $0 | $0 |
| 27 | Lightning protection system | Lightning arresters, conductors, conduit, grounding, and all necessary fixing accessories, as specified and as shown on drawings E-113. | 1 | LS | $0 | $0 |
| Civil Works | ||||||
| 28 | Masonry Wall, Painting, Door installation & Lintel | Supply and construct all materials for civil works which should include the construction of concrete pedestal for cabinets, Concrete Masonry wall and wooden door completely install with lock as per drawings. | 1 | number | $0 | $0 |
| 29 | Raised Access Floor | Supply and construct all materials for a Raised Access Flooring System above the existing concrete floor in the battery room for cabling as per drawings. | 1 | number | $0 | $0 |
| Internal Lighting | ||||||
| 30 | Internal Lighting | Supply and install internal wiring in electrical room and switch gear room to include the installation of lighting sockets and switches as per drawing | 1 | number | $0 | $0 |
| Air-Conditioning System | ||||||
| 35 | Electrical Room | Furnish and install one 9,000 BTU/hr air cooling system for the Battery Room; shop drawing approval of the equipment and installation methods required; includes all equipment, materials, labor to complete the work | 1 | number | $0 | $0 |
| 36 | Switch Gear Room | Furnish and install one 18,000 BTU/hr air cooling system for the Switch Gear Room; shop drawing approval of the equipment and installation methods required; includes all equipment, materials, labor to complete the work | 1 | number | $0 | $0 |
| Total Material Cost | $0 |
Labor Cost @ 25% of Total Material Cost $0
Transportation, Overhead & Profit @ 20% of Total Material Cost $0
GRAND TOTAL $0