CG Academy Sprinkler Reports.pdf

PDF 7 MB Posted

Attached to
CG Academy fire sprinkler system service
Solicitation number
70Z08425RCGA00002
Issued by

About this file

This is a weekly/monthly fire pump inspection report form for the USCG Academy in New London, CT. The form documents inspections performed at multiple locations within the facility, specifically focused on fire pump systems and their components. The form includes sections for recording test results for RPBA (Reduced Pressure Backflow Assembly), DCVA (Double Check Valve Assembly), and PVBA/SVBA (Pressure Vacuum Breaker Assembly/Spill-resistant Vacuum Breaker Assembly) inspections.

The form specifies inspection parameters including line pressure, check valve differentials, and relief valve operations. It requires documentation of test dates, times, PSI readings, and pass/fail results. The inspection location shown is the Alumni Center (1st Floor Next To Men's Room) Key #6, with equipment details including a Wilkins Model 350A 6" assembly with serial number U02289. The form includes space for certified tester information, CT license numbers, and dates, with visual inspections noted for July 11, 2024. The form is designed for tracking fire protection system compliance and maintenance over time, with spots for recording up to 26 separate inspection entries.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

203-440-0550 Office /24 Hour Emergency www.facility-compliance.com

LINE PRESSURE: PSID.

INTIAL TEST RESULTS TEST AFTER REPAIR OR CLEANING

SERVICE ADDRESS:

CROSS-CONNECTION CONTROLLED:

LOCATION:

MODEL: SIZE: SERIAL NO:

Backflow Prevention Form

NAME OF FACILITY:

STATE OF CT APPROVED ASSEMBLY:

Yes No

METER READING

No. 2 Check Valve: Closed Tight Leaked

Closed Tight Leaked

DCVA

No. 1 Check Valve: Differential psid

No. 2 Check Valve: Differential psid

Passed Test: Yes No

Leaked

Leaked

Date: ______________________ Certified Tester's Signature

Repaired By:

Certified Tester's Signature

CT License No: _____________

Initial Test By: _________________________________ Cer. No: __________________

Repair Person's Printed Name

Repair Test By: Cer. No: __________________ Date: ______________________

Date: ______________________

Passed Test: Yes No

RPBA

Relief Valve Opened psid

Yes No

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

PVBA/

SVBA

CERTIFIED TESTER'S TYPED OR PRINTED NAME

AG Approved Air Gap: Yes No

PLEASE RECORD REPAIR INSPECTION CLEANING

INFORMATION IN SECTION BELOW

Is this a proper installation? FIRE SERVICE BY-PASS METER

Pipe Diameter _____ inches Seperation ________ inches

REMARKS:

Test Equipment: Make: _____________ Model: _______________ Serial #: ________ ___________Accuracy Date: ____________ I CERTIFY THIS REPORT IS ACCURATE, AND THAT I HAVE USED MANUFACTURER APPROVED TEST METHODS

CERTIFIED: _____________________________________________________________________________________________

Failed to Open

Air Inlet valve fully opened: Yes No Check Valve: _____________________________ psid

TEST RECORDS MUST BE KEPT FOR AT LEAST THREE YEARS* *USE ONLY MANUFACTURER'S REPLACEMENT PARTS psid

Relief Valve Opened No. 2 Check Valve: Closed Tight

Leaked Closed Tight

Leaked

Passed Test:

Yes Yes psid

No psid psid psid

No. 1 Check Valve: Differential

No. 2 Check Valve: Differential

Passed Test: Yes No

Leaked

Leaked

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

Failed to Open

Air Inlet valve fully opened: Yes No

Check Valve: _______________________ psid

No

INTIAL TEST RESULTS TEST AFTER REPAIR OR CLEANING

SERVICE ADDRESS:

CROSS-CONNECTION CONTROLLED:

LOCATION:

MODEL: SIZE: SERIAL NO:

Backflow Prevention Form

NAME OF FACILITY:

STATE OF CT APPROVED ASSEMBLY:

Yes No

METER READING

No. 2 Check Valve: Closed Tight Leaked

Closed Tight Leaked

DCVA

No. 1 Check Valve: Differential psid

No. 2 Check Valve: Differential psid

Passed Test: Yes No

Leaked

Leaked

Date: ______________________ Certified Tester's Signature

Repaired By:

Certified Tester's Signature

CT License No: _____________

Initial Test By: _________________________________ Cer. No: __________________

Repair Person's Printed Name

Repair Test By: Cer. No: __________________ Date: ______________________

Date: ______________________

Passed Test: Yes No

RPBA

Relief Valve Opened psid

Yes No

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

PVBA/

SVBA

CERTIFIED TESTER'S TYPED OR PRINTED NAME

AG Approved Air Gap: Yes No

PLEASE RECORD REPAIR INSPECTION CLEANING

INFORMATION IN SECTION BELOW

Is this a proper installation? FIRE SERVICE BY-PASS METER

Pipe Diameter _____ inches Seperation ________ inches

REMARKS:

Test Equipment: Make: _____________ Model: _______________ Serial #: ________ ___________Accuracy Date: ____________ I CERTIFY THIS REPORT IS ACCURATE, AND THAT I HAVE USED MANUFACTURER APPROVED TEST METHODS

CERTIFIED: _____________________________________________________________________________________________

Failed to Open

Air Inlet valve fully opened: Yes No Check Valve: _____________________________ psid

TEST RECORDS MUST BE KEPT FOR AT LEAST THREE YEARS* *USE ONLY MANUFACTURER'S REPLACEMENT PARTS psid

Relief Valve Opened No. 2 Check Valve: Closed Tight

Leaked Closed Tight

Leaked

Passed Test:

Yes Yes psid

No psid psid psid

No. 1 Check Valve: Differential

No. 2 Check Valve: Differential

Passed Test: Yes No

Leaked

Leaked

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

Failed to Open

Air Inlet valve fully opened: Yes No

INTIAL TEST RESULTS TEST AFTER REPAIR OR CLEANING

SERVICE ADDRESS:

CROSS-CONNECTION CONTROLLED:

LOCATION:

MODEL: SIZE: SERIAL NO:

Backflow Prevention Form

NAME OF FACILITY:

STATE OF CT APPROVED ASSEMBLY:

Yes No

METER READING

No. 2 Check Valve: Closed Tight Leaked

Closed Tight Leaked

DCVA

No. 1 Check Valve: Differential psid

No. 2 Check Valve: Differential psid

Passed Test: Yes No

Leaked

Leaked

Date: ______________________ Certified Tester's Signature

Repaired By:

Certified Tester's Signature

CT License No: _____________

Initial Test By: _________________________________ Cer. No: __________________

Repair Person's Printed Name

Repair Test By: Cer. No: __________________ Date: ______________________

Date: ______________________

Passed Test: Yes No

RPBA

Relief Valve Opened psid

Yes No

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

PVBA/

SVBA

CERTIFIED TESTER'S TYPED OR PRINTED NAME

AG Approved Air Gap: Yes No

PLEASE RECORD REPAIR INSPECTION CLEANING

INFORMATION IN SECTION BELOW

Is this a proper installation? FIRE SERVICE BY-PASS METER

Pipe Diameter _____ inches Seperation ________ inches

REMARKS:

Test Equipment: Make: _____________ Model: _______________ Serial #: ________ ___________Accuracy Date: ____________ I CERTIFY THIS REPORT IS ACCURATE, AND THAT I HAVE USED MANUFACTURER APPROVED TEST METHODS

CERTIFIED: _____________________________________________________________________________________________

Failed to Open

Air Inlet valve fully opened: Yes No Check Valve: _____________________________ psid

TEST RECORDS MUST BE KEPT FOR AT LEAST THREE YEARS* *USE ONLY MANUFACTURER'S REPLACEMENT PARTS psid

Relief Valve Opened No. 2 Check Valve: Closed Tight

Leaked Closed Tight

Leaked

Passed Test:

Yes Yes psid

No psid psid psid

No. 1 Check Valve: Differential

No. 2 Check Valve: Differential

Passed Test: Yes No

Leaked

Leaked

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

Failed to Open

Air Inlet valve fully opened: Yes No

INTIAL TEST RESULTS TEST AFTER REPAIR OR CLEANING

SERVICE ADDRESS:

CROSS-CONNECTION CONTROLLED:

LOCATION:

MODEL: SIZE: SERIAL NO:

Backflow Prevention Form

NAME OF FACILITY:

STATE OF CT APPROVED ASSEMBLY:

Yes No

METER READING

No. 2 Check Valve: Closed Tight Leaked

Closed Tight Leaked

DCVA

No. 1 Check Valve: Differential psid

No. 2 Check Valve: Differential psid

Passed Test: Yes No

Leaked

Leaked

Date: ______________________ Certified Tester's Signature

Repaired By:

Certified Tester's Signature

CT License No: _____________

Initial Test By: _________________________________ Cer. No: __________________

Repair Person's Printed Name

Repair Test By: Cer. No: __________________ Date: ______________________

Date: ______________________

Passed Test: Yes No

RPBA

Relief Valve Opened psid

Yes No

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

PVBA/

SVBA

CERTIFIED TESTER'S TYPED OR PRINTED NAME

AG Approved Air Gap: Yes No

PLEASE RECORD REPAIR INSPECTION CLEANING

INFORMATION IN SECTION BELOW

Is this a proper installation? FIRE SERVICE BY-PASS METER

Pipe Diameter _____ inches Seperation ________ inches

REMARKS:

Test Equipment: Make: _____________ Model: _______________ Serial #: ________ ___________Accuracy Date: ____________ I CERTIFY THIS REPORT IS ACCURATE, AND THAT I HAVE USED MANUFACTURER APPROVED TEST METHODS

CERTIFIED: _____________________________________________________________________________________________

Failed to Open

Air Inlet valve fully opened: Yes No Check Valve: _____________________________ psid

TEST RECORDS MUST BE KEPT FOR AT LEAST THREE YEARS* *USE ONLY MANUFACTURER'S REPLACEMENT PARTS psid

Relief Valve Opened No. 2 Check Valve: Closed Tight

Leaked Closed Tight

Leaked

Passed Test:

Yes Yes psid

No psid psid psid

No. 1 Check Valve: Differential

No. 2 Check Valve: Differential

Passed Test: Yes No

Leaked

Leaked

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

Failed to Open

Air Inlet valve fully opened: Yes No

INTIAL TEST RESULTS TEST AFTER REPAIR OR CLEANING

SERVICE ADDRESS:

CROSS-CONNECTION CONTROLLED:

LOCATION:

MODEL: SIZE: SERIAL NO:

Backflow Prevention Form

NAME OF FACILITY:

STATE OF CT APPROVED ASSEMBLY:

Yes No

METER READING

No. 2 Check Valve: Closed Tight Leaked

Closed Tight Leaked

DCVA

No. 1 Check Valve: Differential psid

No. 2 Check Valve: Differential psid

Passed Test: Yes No

Leaked

Leaked

Date: ______________________ Certified Tester's Signature

Repaired By:

Certified Tester's Signature

CT License No: _____________

Initial Test By: _________________________________ Cer. No: __________________

Repair Person's Printed Name

Repair Test By: Cer. No: __________________ Date: ______________________

Date: ______________________

Passed Test: Yes No

RPBA

Relief Valve Opened psid

Yes No

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

PVBA/

SVBA

CERTIFIED TESTER'S TYPED OR PRINTED NAME

AG Approved Air Gap: Yes No

PLEASE RECORD REPAIR INSPECTION CLEANING

INFORMATION IN SECTION BELOW

Is this a proper installation? FIRE SERVICE BY-PASS METER

Pipe Diameter _____ inches Seperation ________ inches

REMARKS:

Test Equipment: Make: _____________ Model: _______________ Serial #: ________ ___________Accuracy Date: ____________ I CERTIFY THIS REPORT IS ACCURATE, AND THAT I HAVE USED MANUFACTURER APPROVED TEST METHODS

CERTIFIED: _____________________________________________________________________________________________

Failed to Open

Air Inlet valve fully opened: Yes No Check Valve: _____________________________ psid

TEST RECORDS MUST BE KEPT FOR AT LEAST THREE YEARS* *USE ONLY MANUFACTURER'S REPLACEMENT PARTS psid

Relief Valve Opened No. 2 Check Valve: Closed Tight

Leaked Closed Tight

Leaked

Passed Test:

Yes Yes psid

No psid psid psid

No. 1 Check Valve: Differential

No. 2 Check Valve: Differential

Passed Test: Yes No

Leaked

Leaked

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

Failed to Open

Air Inlet valve fully opened: Yes No

INTIAL TEST RESULTS TEST AFTER REPAIR OR CLEANING

SERVICE ADDRESS:

CROSS-CONNECTION CONTROLLED:

LOCATION:

MODEL: SIZE: SERIAL NO:

Backflow Prevention Form

NAME OF FACILITY:

STATE OF CT APPROVED ASSEMBLY:

Yes No

METER READING

No. 2 Check Valve: Closed Tight Leaked

Closed Tight Leaked

DCVA

No. 1 Check Valve: Differential psid

No. 2 Check Valve: Differential psid

Passed Test: Yes No

Leaked

Leaked

Date: ______________________ Certified Tester's Signature

Repaired By:

Certified Tester's Signature

CT License No: _____________

Initial Test By: _________________________________ Cer. No: __________________

Repair Person's Printed Name

Repair Test By: Cer. No: __________________ Date: ______________________

Date: ______________________

Passed Test: Yes No

RPBA

Relief Valve Opened psid

Yes No

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

PVBA/

SVBA

CERTIFIED TESTER'S TYPED OR PRINTED NAME

AG Approved Air Gap: Yes No

PLEASE RECORD REPAIR INSPECTION CLEANING

INFORMATION IN SECTION BELOW

Is this a proper installation? FIRE SERVICE BY-PASS METER

Pipe Diameter _____ inches Seperation ________ inches

REMARKS:

Test Equipment: Make: _____________ Model: _______________ Serial #: ________ ___________Accuracy Date: ____________ I CERTIFY THIS REPORT IS ACCURATE, AND THAT I HAVE USED MANUFACTURER APPROVED TEST METHODS

CERTIFIED: _____________________________________________________________________________________________

Failed to Open

Air Inlet valve fully opened: Yes No Check Valve: _____________________________ psid

TEST RECORDS MUST BE KEPT FOR AT LEAST THREE YEARS* *USE ONLY MANUFACTURER'S REPLACEMENT PARTS psid

Relief Valve Opened No. 2 Check Valve: Closed Tight

Leaked Closed Tight

Leaked

Passed Test:

Yes Yes psid

No psid psid psid

No. 1 Check Valve: Differential

No. 2 Check Valve: Differential

Passed Test: Yes No

Leaked

Leaked

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

Failed to Open

Air Inlet valve fully opened: Yes No

INTIAL TEST RESULTS TEST AFTER REPAIR OR CLEANING

SERVICE ADDRESS:

CROSS-CONNECTION CONTROLLED:

LOCATION:

MODEL: SIZE: SERIAL NO:

Backflow Prevention Form

NAME OF FACILITY:

STATE OF CT APPROVED ASSEMBLY:

Yes No

METER READING

No. 2 Check Valve: Closed Tight Leaked

Closed Tight Leaked

DCVA

No. 1 Check Valve: Differential psid

No. 2 Check Valve: Differential psid

Passed Test: Yes No

Leaked

Leaked

Date: ______________________ Certified Tester's Signature

Repaired By:

Certified Tester's Signature

CT License No: _____________

Initial Test By: _________________________________ Cer. No: __________________

Repair Person's Printed Name

Repair Test By: Cer. No: __________________ Date: ______________________

Date: ______________________

Passed Test: Yes No

RPBA

Relief Valve Opened psid

Yes No

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

PVBA/

SVBA

CERTIFIED TESTER'S TYPED OR PRINTED NAME

AG Approved Air Gap: Yes No

PLEASE RECORD REPAIR INSPECTION CLEANING

INFORMATION IN SECTION BELOW

Is this a proper installation? FIRE SERVICE BY-PASS METER

Pipe Diameter _____ inches Seperation ________ inches

REMARKS:

Test Equipment: Make: _____________ Model: _______________ Serial #: ________ ___________Accuracy Date: ____________ I CERTIFY THIS REPORT IS ACCURATE, AND THAT I HAVE USED MANUFACTURER APPROVED TEST METHODS

CERTIFIED: _____________________________________________________________________________________________

Failed to Open

Air Inlet valve fully opened: Yes No Check Valve: _____________________________ psid

TEST RECORDS MUST BE KEPT FOR AT LEAST THREE YEARS* *USE ONLY MANUFACTURER'S REPLACEMENT PARTS psid

Relief Valve Opened No. 2 Check Valve: Closed Tight

Leaked Closed Tight

Leaked

Passed Test:

Yes Yes psid

No psid psid psid

No. 1 Check Valve: Differential

No. 2 Check Valve: Differential

Passed Test: Yes No

Leaked

Leaked

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

Failed to Open

Air Inlet valve fully opened: Yes No

INTIAL TEST RESULTS TEST AFTER REPAIR OR CLEANING

SERVICE ADDRESS:

CROSS-CONNECTION CONTROLLED:

LOCATION:

MODEL: SIZE: SERIAL NO:

Backflow Prevention Form

NAME OF FACILITY:

STATE OF CT APPROVED ASSEMBLY:

Yes No

METER READING

No. 2 Check Valve: Closed Tight Leaked

Closed Tight Leaked

DCVA

No. 1 Check Valve: Differential psid

No. 2 Check Valve: Differential psid

Passed Test: Yes No

Leaked

Leaked

Date: ______________________ Certified Tester's Signature

Repaired By:

Certified Tester's Signature

CT License No: _____________

Initial Test By: _________________________________ Cer. No: __________________

Repair Person's Printed Name

Repair Test By: Cer. No: __________________ Date: ______________________

Date: ______________________

Passed Test: Yes No

RPBA

Relief Valve Opened psid

Yes No

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

PVBA/

SVBA

CERTIFIED TESTER'S TYPED OR PRINTED NAME

AG Approved Air Gap: Yes No

PLEASE RECORD REPAIR INSPECTION CLEANING

INFORMATION IN SECTION BELOW

Is this a proper installation? FIRE SERVICE BY-PASS METER

Pipe Diameter _____ inches Seperation ________ inches

REMARKS:

Test Equipment: Make: _____________ Model: _______________ Serial #: ________ ___________Accuracy Date: ____________ I CERTIFY THIS REPORT IS ACCURATE, AND THAT I HAVE USED MANUFACTURER APPROVED TEST METHODS

CERTIFIED: _____________________________________________________________________________________________

Failed to Open

Air Inlet valve fully opened: Yes No Check Valve: _____________________________ psid

TEST RECORDS MUST BE KEPT FOR AT LEAST THREE YEARS* *USE ONLY MANUFACTURER'S REPLACEMENT PARTS psid

Relief Valve Opened No. 2 Check Valve: Closed Tight

Leaked Closed Tight

Leaked

Passed Test:

Yes Yes psid

No psid psid psid

No. 1 Check Valve: Differential

No. 2 Check Valve: Differential

Passed Test: Yes No

Leaked

Leaked

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

Failed to Open

Air Inlet valve fully opened: Yes No

INTIAL TEST RESULTS TEST AFTER REPAIR OR CLEANING

SERVICE ADDRESS:

CROSS-CONNECTION CONTROLLED:

LOCATION:

MODEL: SIZE: SERIAL NO:

Backflow Prevention Form

NAME OF FACILITY:

STATE OF CT APPROVED ASSEMBLY:

Yes No

METER READING

No. 2 Check Valve: Closed Tight Leaked

Closed Tight Leaked

DCVA

No. 1 Check Valve: Differential psid

No. 2 Check Valve: Differential psid

Passed Test: Yes No

Leaked

Leaked

Date: ______________________ Certified Tester's Signature

Repaired By:

Certified Tester's Signature

CT License No: _____________

Initial Test By: _________________________________ Cer. No: __________________

Repair Person's Printed Name

Repair Test By: Cer. No: __________________ Date: ______________________

Date: ______________________

Passed Test: Yes No

RPBA

Relief Valve Opened psid

Yes No

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

PVBA/

SVBA

CERTIFIED TESTER'S TYPED OR PRINTED NAME

AG Approved Air Gap: Yes No

PLEASE RECORD REPAIR INSPECTION CLEANING

INFORMATION IN SECTION BELOW

Is this a proper installation? FIRE SERVICE BY-PASS METER

Pipe Diameter _____ inches Seperation ________ inches

REMARKS:

Test Equipment: Make: _____________ Model: _______________ Serial #: ________ ___________Accuracy Date: ____________ I CERTIFY THIS REPORT IS ACCURATE, AND THAT I HAVE USED MANUFACTURER APPROVED TEST METHODS

CERTIFIED: _____________________________________________________________________________________________

Failed to Open

Air Inlet valve fully opened: Yes No Check Valve: _____________________________ psid

TEST RECORDS MUST BE KEPT FOR AT LEAST THREE YEARS* *USE ONLY MANUFACTURER'S REPLACEMENT PARTS psid

Relief Valve Opened No. 2 Check Valve: Closed Tight

Leaked Closed Tight

Leaked

Passed Test:

Yes Yes psid

No psid psid psid

No. 1 Check Valve: Differential

No. 2 Check Valve: Differential

Passed Test: Yes No

Leaked

Leaked

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

Failed to Open

Air Inlet valve fully opened: Yes No

INTIAL TEST RESULTS TEST AFTER REPAIR OR CLEANING

SERVICE ADDRESS:

CROSS-CONNECTION CONTROLLED:

LOCATION:

MODEL: SIZE: SERIAL NO:

Backflow Prevention Form

NAME OF FACILITY:

STATE OF CT APPROVED ASSEMBLY:

Yes No

METER READING

No. 2 Check Valve: Closed Tight Leaked

Closed Tight Leaked

DCVA

No. 1 Check Valve: Differential psid

No. 2 Check Valve: Differential psid

Passed Test: Yes No

Leaked

Leaked

Date: ______________________ Certified Tester's Signature

Repaired By:

Certified Tester's Signature

CT License No: _____________

Initial Test By: _________________________________ Cer. No: __________________

Repair Person's Printed Name

Repair Test By: Cer. No: __________________ Date: ______________________

Date: ______________________

Passed Test: Yes No

RPBA

Relief Valve Opened psid

Yes No

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

PVBA/

SVBA

CERTIFIED TESTER'S TYPED OR PRINTED NAME

AG Approved Air Gap: Yes No

PLEASE RECORD REPAIR INSPECTION CLEANING

INFORMATION IN SECTION BELOW

Is this a proper installation? FIRE SERVICE BY-PASS METER

Pipe Diameter _____ inches Seperation ________ inches

REMARKS:

Test Equipment: Make: _____________ Model: _______________ Serial #: ________ ___________Accuracy Date: ____________ I CERTIFY THIS REPORT IS ACCURATE, AND THAT I HAVE USED MANUFACTURER APPROVED TEST METHODS

CERTIFIED: _____________________________________________________________________________________________

Failed to Open

Air Inlet valve fully opened: Yes No Check Valve: _____________________________ psid

TEST RECORDS MUST BE KEPT FOR AT LEAST THREE YEARS* *USE ONLY MANUFACTURER'S REPLACEMENT PARTS psid

Relief Valve Opened No. 2 Check Valve: Closed Tight

Leaked Closed Tight

Leaked

Passed Test:

Yes Yes psid

No psid psid psid

No. 1 Check Valve: Differential

No. 2 Check Valve: Differential

Passed Test: Yes No

Leaked

Leaked

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

Failed to Open

Air Inlet valve fully opened: Yes No

INTIAL TEST RESULTS TEST AFTER REPAIR OR CLEANING

SERVICE ADDRESS:

CROSS-CONNECTION CONTROLLED:

LOCATION:

MODEL: SIZE: SERIAL NO:

Backflow Prevention Form

NAME OF FACILITY:

STATE OF CT APPROVED ASSEMBLY:

Yes No

METER READING

No. 2 Check Valve: Closed Tight Leaked

Closed Tight Leaked

DCVA

No. 1 Check Valve: Differential psid

No. 2 Check Valve: Differential psid

Passed Test: Yes No

Leaked

Leaked

Date: ______________________ Certified Tester's Signature

Repaired By:

Certified Tester's Signature

CT License No: _____________

Initial Test By: _________________________________ Cer. No: __________________

Repair Person's Printed Name

Repair Test By: Cer. No: __________________ Date: ______________________

Date: ______________________

Passed Test: Yes No

RPBA

Relief Valve Opened psid

Yes No

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

PVBA/

SVBA

CERTIFIED TESTER'S TYPED OR PRINTED NAME

AG Approved Air Gap: Yes No

PLEASE RECORD REPAIR INSPECTION CLEANING

INFORMATION IN SECTION BELOW

Is this a proper installation? FIRE SERVICE BY-PASS METER

Pipe Diameter _____ inches Seperation ________ inches

REMARKS:

Test Equipment: Make: _____________ Model: _______________ Serial #: ________ ___________Accuracy Date: ____________ I CERTIFY THIS REPORT IS ACCURATE, AND THAT I HAVE USED MANUFACTURER APPROVED TEST METHODS

CERTIFIED: _____________________________________________________________________________________________

Failed to Open

Air Inlet valve fully opened: Yes No Check Valve: _____________________________ psid

TEST RECORDS MUST BE KEPT FOR AT LEAST THREE YEARS* *USE ONLY MANUFACTURER'S REPLACEMENT PARTS psid

Relief Valve Opened No. 2 Check Valve: Closed Tight

Leaked Closed Tight

Leaked

Passed Test:

Yes Yes psid

No psid psid psid

No. 1 Check Valve: Differential

No. 2 Check Valve: Differential

Passed Test: Yes No

Leaked

Leaked

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

Failed to Open

Air Inlet valve fully opened: Yes No

INTIAL TEST RESULTS TEST AFTER REPAIR OR CLEANING

SERVICE ADDRESS:

CROSS-CONNECTION CONTROLLED:

LOCATION:

MODEL: SIZE: SERIAL NO:

Backflow Prevention Form

NAME OF FACILITY:

STATE OF CT APPROVED ASSEMBLY:

Yes No

METER READING

No. 2 Check Valve: Closed Tight Leaked

Closed Tight Leaked

DCVA

No. 1 Check Valve: Differential psid

No. 2 Check Valve: Differential psid

Passed Test: Yes No

Leaked

Leaked

Date: ______________________ Certified Tester's Signature

Repaired By:

Certified Tester's Signature

CT License No: _____________

Initial Test By: _________________________________ Cer. No: __________________

Repair Person's Printed Name

Repair Test By: Cer. No: __________________ Date: ______________________

Date: ______________________

Passed Test: Yes No

RPBA

Relief Valve Opened psid

Yes No

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

PVBA/

SVBA

CERTIFIED TESTER'S TYPED OR PRINTED NAME

AG Approved Air Gap: Yes No

PLEASE RECORD REPAIR INSPECTION CLEANING

INFORMATION IN SECTION BELOW

Is this a proper installation? FIRE SERVICE BY-PASS METER

Pipe Diameter _____ inches Seperation ________ inches

REMARKS:

Test Equipment: Make: _____________ Model: _______________ Serial #: ________ ___________Accuracy Date: ____________ I CERTIFY THIS REPORT IS ACCURATE, AND THAT I HAVE USED MANUFACTURER APPROVED TEST METHODS

CERTIFIED: _____________________________________________________________________________________________

Failed to Open

Air Inlet valve fully opened: Yes No Check Valve: _____________________________ psid

TEST RECORDS MUST BE KEPT FOR AT LEAST THREE YEARS* *USE ONLY MANUFACTURER'S REPLACEMENT PARTS psid

Relief Valve Opened No. 2 Check Valve: Closed Tight

Leaked Closed Tight

Leaked

Passed Test:

Yes Yes psid

No psid psid psid

No. 1 Check Valve: Differential

No. 2 Check Valve: Differential

Passed Test: Yes No

Leaked

Leaked

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

Failed to Open

Air Inlet valve fully opened: Yes No

INTIAL TEST RESULTS TEST AFTER REPAIR OR CLEANING

SERVICE ADDRESS:

CROSS-CONNECTION CONTROLLED:

LOCATION:

MODEL: SIZE: SERIAL NO:

Backflow Prevention Form

NAME OF FACILITY:

STATE OF CT APPROVED ASSEMBLY:

Yes No

METER READING

No. 2 Check Valve: Closed Tight Leaked

Closed Tight Leaked

DCVA

No. 1 Check Valve: Differential psid

No. 2 Check Valve: Differential psid

Passed Test: Yes No

Leaked

Leaked

Date: ______________________ Certified Tester's Signature

Repaired By:

Certified Tester's Signature

CT License No: _____________

Initial Test By: _________________________________ Cer. No: __________________

Repair Person's Printed Name

Repair Test By: Cer. No: __________________ Date: ______________________

Date: ______________________

Passed Test: Yes No

RPBA

Relief Valve Opened psid

Yes No

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

PVBA/

SVBA

CERTIFIED TESTER'S TYPED OR PRINTED NAME

AG Approved Air Gap: Yes No

PLEASE RECORD REPAIR INSPECTION CLEANING

INFORMATION IN SECTION BELOW

Is this a proper installation? FIRE SERVICE BY-PASS METER

Pipe Diameter _____ inches Seperation ________ inches

REMARKS:

Test Equipment: Make: _____________ Model: _______________ Serial #: ________ ___________Accuracy Date: ____________ I CERTIFY THIS REPORT IS ACCURATE, AND THAT I HAVE USED MANUFACTURER APPROVED TEST METHODS

CERTIFIED: _____________________________________________________________________________________________

Failed to Open

Air Inlet valve fully opened: Yes No Check Valve: _____________________________ psid

TEST RECORDS MUST BE KEPT FOR AT LEAST THREE YEARS* *USE ONLY MANUFACTURER'S REPLACEMENT PARTS psid

Relief Valve Opened No. 2 Check Valve: Closed Tight

Leaked Closed Tight

Leaked

Passed Test:

Yes Yes psid

No psid psid psid

No. 1 Check Valve: Differential

No. 2 Check Valve: Differential

Passed Test: Yes No

Leaked

Leaked

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

Failed to Open

Air Inlet valve fully opened: Yes No

INTIAL TEST RESULTS TEST AFTER REPAIR OR CLEANING

SERVICE ADDRESS:

CROSS-CONNECTION CONTROLLED:

LOCATION:

MODEL: SIZE: SERIAL NO:

Backflow Prevention Form

NAME OF FACILITY:

STATE OF CT APPROVED ASSEMBLY:

Yes No

METER READING

No. 2 Check Valve: Closed Tight Leaked

Closed Tight Leaked

DCVA

No. 1 Check Valve: Differential psid

No. 2 Check Valve: Differential psid

Passed Test: Yes No

Leaked

Leaked

Date: ______________________ Certified Tester's Signature

Repaired By:

Certified Tester's Signature

CT License No: _____________

Initial Test By: _________________________________ Cer. No: __________________

Repair Person's Printed Name

Repair Test By: Cer. No: __________________ Date: ______________________

Date: ______________________

Passed Test: Yes No

RPBA

Relief Valve Opened psid

Yes No

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

PVBA/

SVBA

CERTIFIED TESTER'S TYPED OR PRINTED NAME

AG Approved Air Gap: Yes No

PLEASE RECORD REPAIR INSPECTION CLEANING

INFORMATION IN SECTION BELOW

Is this a proper installation? FIRE SERVICE BY-PASS METER

Pipe Diameter _____ inches Seperation ________ inches

REMARKS:

Test Equipment: Make: _____________ Model: _______________ Serial #: ________ ___________Accuracy Date: ____________ I CERTIFY THIS REPORT IS ACCURATE, AND THAT I HAVE USED MANUFACTURER APPROVED TEST METHODS

CERTIFIED: _____________________________________________________________________________________________

Failed to Open

Air Inlet valve fully opened: Yes No Check Valve: _____________________________ psid

TEST RECORDS MUST BE KEPT FOR AT LEAST THREE YEARS* *USE ONLY MANUFACTURER'S REPLACEMENT PARTS psid

Relief Valve Opened No. 2 Check Valve: Closed Tight

Leaked Closed Tight

Leaked

Passed Test:

Yes Yes psid

No psid psid psid

No. 1 Check Valve: Differential

No. 2 Check Valve: Differential

Passed Test: Yes No

Leaked

Leaked

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

Failed to Open

Air Inlet valve fully opened: Yes No

INTIAL TEST RESULTS TEST AFTER REPAIR OR CLEANING

SERVICE ADDRESS:

CROSS-CONNECTION CONTROLLED:

LOCATION:

MODEL: SIZE: SERIAL NO:

Backflow Prevention Form

NAME OF FACILITY:

STATE OF CT APPROVED ASSEMBLY:

Yes No

METER READING

No. 2 Check Valve: Closed Tight Leaked

Closed Tight Leaked

DCVA

No. 1 Check Valve: Differential psid

No. 2 Check Valve: Differential psid

Passed Test: Yes No

Leaked

Leaked

Date: ______________________ Certified Tester's Signature

Repaired By:

Certified Tester's Signature

CT License No: _____________

Initial Test By: _________________________________ Cer. No: __________________

Repair Person's Printed Name

Repair Test By: Cer. No: __________________ Date: ______________________

Date: ______________________

Passed Test: Yes No

RPBA

Relief Valve Opened psid

Yes No

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

PVBA/

SVBA

CERTIFIED TESTER'S TYPED OR PRINTED NAME

AG Approved Air Gap: Yes No

PLEASE RECORD REPAIR INSPECTION CLEANING

INFORMATION IN SECTION BELOW

Is this a proper installation? FIRE SERVICE BY-PASS METER

Pipe Diameter _____ inches Seperation ________ inches

REMARKS:

Test Equipment: Make: _____________ Model: _______________ Serial #: ________ ___________Accuracy Date: ____________ I CERTIFY THIS REPORT IS ACCURATE, AND THAT I HAVE USED MANUFACTURER APPROVED TEST METHODS

CERTIFIED: _____________________________________________________________________________________________

Failed to Open

Air Inlet valve fully opened: Yes No Check Valve: _____________________________ psid

TEST RECORDS MUST BE KEPT FOR AT LEAST THREE YEARS* *USE ONLY MANUFACTURER'S REPLACEMENT PARTS psid

Relief Valve Opened No. 2 Check Valve: Closed Tight

Leaked Closed Tight

Leaked

Passed Test:

Yes Yes psid

No psid psid psid

No. 1 Check Valve: Differential

No. 2 Check Valve: Differential

Passed Test: Yes No

Leaked

Leaked

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

Failed to Open

Air Inlet valve fully opened: Yes No

INTIAL TEST RESULTS TEST AFTER REPAIR OR CLEANING

SERVICE ADDRESS:

CROSS-CONNECTION CONTROLLED:

LOCATION:

MODEL: SIZE: SERIAL NO:

Backflow Prevention Form

NAME OF FACILITY:

STATE OF CT APPROVED ASSEMBLY:

Yes No

METER READING

No. 2 Check Valve: Closed Tight Leaked

Closed Tight Leaked

DCVA

No. 1 Check Valve: Differential psid

No. 2 Check Valve: Differential psid

Passed Test: Yes No

Leaked

Leaked

Date: ______________________ Certified Tester's Signature

Repaired By:

Certified Tester's Signature

CT License No: _____________

Initial Test By: _________________________________ Cer. No: __________________

Repair Person's Printed Name

Repair Test By: Cer. No: __________________ Date: ______________________

Date: ______________________

Passed Test: Yes No

RPBA

Relief Valve Opened psid

Yes No

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

PVBA/

SVBA

CERTIFIED TESTER'S TYPED OR PRINTED NAME

AG Approved Air Gap: Yes No

PLEASE RECORD REPAIR INSPECTION CLEANING

INFORMATION IN SECTION BELOW

Is this a proper installation? FIRE SERVICE BY-PASS METER

Pipe Diameter _____ inches Seperation ________ inches

REMARKS:

Test Equipment: Make: _____________ Model: _______________ Serial #: ________ ___________Accuracy Date: ____________ I CERTIFY THIS REPORT IS ACCURATE, AND THAT I HAVE USED MANUFACTURER APPROVED TEST METHODS

CERTIFIED: _____________________________________________________________________________________________

Failed to Open

Air Inlet valve fully opened: Yes No Check Valve: _____________________________ psid

TEST RECORDS MUST BE KEPT FOR AT LEAST THREE YEARS* *USE ONLY MANUFACTURER'S REPLACEMENT PARTS psid

Relief Valve Opened No. 2 Check Valve: Closed Tight

Leaked Closed Tight

Leaked

Passed Test:

Yes Yes psid

No psid psid psid

No. 1 Check Valve: Differential

No. 2 Check Valve: Differential

Passed Test: Yes No

Leaked

Leaked

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

Failed to Open

Air Inlet valve fully opened: Yes No

INTIAL TEST RESULTS TEST AFTER REPAIR OR CLEANING

SERVICE ADDRESS:

CROSS-CONNECTION CONTROLLED:

LOCATION:

MODEL: SIZE: SERIAL NO:

Backflow Prevention Form

NAME OF FACILITY:

STATE OF CT APPROVED ASSEMBLY:

Yes No

METER READING

No. 2 Check Valve: Closed Tight Leaked

Closed Tight Leaked

DCVA

No. 1 Check Valve: Differential psid

No. 2 Check Valve: Differential psid

Passed Test: Yes No

Leaked

Leaked

Date: ______________________ Certified Tester's Signature

Repaired By:

Certified Tester's Signature

CT License No: _____________

Initial Test By: _________________________________ Cer. No: __________________

Repair Person's Printed Name

Repair Test By: Cer. No: __________________ Date: ______________________

Date: ______________________

Passed Test: Yes No

RPBA

Relief Valve Opened psid

Yes No

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

PVBA/

SVBA

CERTIFIED TESTER'S TYPED OR PRINTED NAME

AG Approved Air Gap: Yes No

PLEASE RECORD REPAIR INSPECTION CLEANING

INFORMATION IN SECTION BELOW

Is this a proper installation? FIRE SERVICE BY-PASS METER

Pipe Diameter _____ inches Seperation ________ inches

REMARKS:

Test Equipment: Make: _____________ Model: _______________ Serial #: ________ ___________Accuracy Date: ____________ I CERTIFY THIS REPORT IS ACCURATE, AND THAT I HAVE USED MANUFACTURER APPROVED TEST METHODS

CERTIFIED: _____________________________________________________________________________________________

Failed to Open

Air Inlet valve fully opened: Yes No Check Valve: _____________________________ psid

TEST RECORDS MUST BE KEPT FOR AT LEAST THREE YEARS* *USE ONLY MANUFACTURER'S REPLACEMENT PARTS psid

Relief Valve Opened No. 2 Check Valve: Closed Tight

Leaked Closed Tight

Leaked

Passed Test:

Yes Yes psid

No psid psid psid

No. 1 Check Valve: Differential

No. 2 Check Valve: Differential

Passed Test: Yes No

Leaked

Leaked

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

Failed to Open

Air Inlet valve fully opened: Yes No

INTIAL TEST RESULTS TEST AFTER REPAIR OR CLEANING

SERVICE ADDRESS:

CROSS-CONNECTION CONTROLLED:

LOCATION:

MODEL: SIZE: SERIAL NO:

Backflow Prevention Form

NAME OF FACILITY:

STATE OF CT APPROVED ASSEMBLY:

Yes No

METER READING

No. 2 Check Valve: Closed Tight Leaked

Closed Tight Leaked

DCVA

No. 1 Check Valve: Differential psid

No. 2 Check Valve: Differential psid

Passed Test: Yes No

Leaked

Leaked

Date: ______________________ Certified Tester's Signature

Repaired By:

Certified Tester's Signature

CT License No: _____________

Initial Test By: _________________________________ Cer. No: __________________

Repair Person's Printed Name

Repair Test By: Cer. No: __________________ Date: ______________________

Date: ______________________

Passed Test: Yes No

RPBA

Relief Valve Opened psid

Yes No

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

PVBA/

SVBA

CERTIFIED TESTER'S TYPED OR PRINTED NAME

AG Approved Air Gap: Yes No

PLEASE RECORD REPAIR INSPECTION CLEANING

INFORMATION IN SECTION BELOW

Is this a proper installation? FIRE SERVICE BY-PASS METER

Pipe Diameter _____ inches Seperation ________ inches

REMARKS:

Test Equipment: Make: _____________ Model: _______________ Serial #: ________ ___________Accuracy Date: ____________ I CERTIFY THIS REPORT IS ACCURATE, AND THAT I HAVE USED MANUFACTURER APPROVED TEST METHODS

CERTIFIED: _____________________________________________________________________________________________

Failed to Open

Air Inlet valve fully opened: Yes No Check Valve: _____________________________ psid

TEST RECORDS MUST BE KEPT FOR AT LEAST THREE YEARS* *USE ONLY MANUFACTURER'S REPLACEMENT PARTS psid

Relief Valve Opened No. 2 Check Valve: Closed Tight

Leaked Closed Tight

Leaked

Passed Test:

Yes Yes psid

No psid psid psid

No. 1 Check Valve: Differential

No. 2 Check Valve: Differential

Passed Test: Yes No

Leaked

Leaked

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

Failed to Open

Air Inlet valve fully opened: Yes No

INTIAL TEST RESULTS TEST AFTER REPAIR OR CLEANING

SERVICE ADDRESS:

CROSS-CONNECTION CONTROLLED:

LOCATION:

MODEL: SIZE: SERIAL NO:

Backflow Prevention Form

NAME OF FACILITY:

STATE OF CT APPROVED ASSEMBLY:

Yes No

METER READING

No. 2 Check Valve: Closed Tight Leaked

Closed Tight Leaked

DCVA

No. 1 Check Valve: Differential psid

No. 2 Check Valve: Differential psid

Passed Test: Yes No

Leaked

Leaked

Date: ______________________ Certified Tester's Signature

Repaired By:

Certified Tester's Signature

CT License No: _____________

Initial Test By: _________________________________ Cer. No: __________________

Repair Person's Printed Name

Repair Test By: Cer. No: __________________ Date: ______________________

Date: ______________________

Passed Test: Yes No

RPBA

Relief Valve Opened psid

Yes No

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

PVBA/

SVBA

CERTIFIED TESTER'S TYPED OR PRINTED NAME

AG Approved Air Gap: Yes No

PLEASE RECORD REPAIR INSPECTION CLEANING

INFORMATION IN SECTION BELOW

Is this a proper installation? FIRE SERVICE BY-PASS METER

Pipe Diameter _____ inches Seperation ________ inches

REMARKS:

Test Equipment: Make: _____________ Model: _______________ Serial #: ________ ___________Accuracy Date: ____________ I CERTIFY THIS REPORT IS ACCURATE, AND THAT I HAVE USED MANUFACTURER APPROVED TEST METHODS

CERTIFIED: _____________________________________________________________________________________________

Failed to Open

Air Inlet valve fully opened: Yes No Check Valve: _____________________________ psid

TEST RECORDS MUST BE KEPT FOR AT LEAST THREE YEARS* *USE ONLY MANUFACTURER'S REPLACEMENT PARTS psid

Relief Valve Opened No. 2 Check Valve: Closed Tight

Leaked Closed Tight

Leaked

Passed Test:

Yes Yes psid

No psid psid psid

No. 1 Check Valve: Differential

No. 2 Check Valve: Differential

Passed Test: Yes No

Leaked

Leaked

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

Failed to Open

Air Inlet valve fully opened: Yes No

INTIAL TEST RESULTS TEST AFTER REPAIR OR CLEANING

SERVICE ADDRESS:

CROSS-CONNECTION CONTROLLED:

LOCATION:

MODEL: SIZE: SERIAL NO:

Backflow Prevention Form

NAME OF FACILITY:

STATE OF CT APPROVED ASSEMBLY:

Yes No

METER READING

No. 2 Check Valve: Closed Tight Leaked

Closed Tight Leaked

DCVA

No. 1 Check Valve: Differential psid

No. 2 Check Valve: Differential psid

Passed Test: Yes No

Leaked

Leaked

Date: ______________________ Certified Tester's Signature

Repaired By:

Certified Tester's Signature

CT License No: _____________

Initial Test By: _________________________________ Cer. No: __________________

Repair Person's Printed Name

Repair Test By: Cer. No: __________________ Date: ______________________

Date: ______________________

Passed Test: Yes No

RPBA

Relief Valve Opened psid

Yes No

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

PVBA/

SVBA

CERTIFIED TESTER'S TYPED OR PRINTED NAME

AG Approved Air Gap: Yes No

PLEASE RECORD REPAIR INSPECTION CLEANING

INFORMATION IN SECTION BELOW

Is this a proper installation? FIRE SERVICE BY-PASS METER

Pipe Diameter _____ inches Seperation ________ inches

REMARKS:

Test Equipment: Make: _____________ Model: _______________ Serial #: ________ ___________Accuracy Date: ____________ I CERTIFY THIS REPORT IS ACCURATE, AND THAT I HAVE USED MANUFACTURER APPROVED TEST METHODS

CERTIFIED: _____________________________________________________________________________________________

Failed to Open

Air Inlet valve fully opened: Yes No Check Valve: _____________________________ psid

TEST RECORDS MUST BE KEPT FOR AT LEAST THREE YEARS* *USE ONLY MANUFACTURER'S REPLACEMENT PARTS psid

Relief Valve Opened No. 2 Check Valve: Closed Tight

Leaked Closed Tight

Leaked

Passed Test:

Yes Yes psid

No psid psid psid

No. 1 Check Valve: Differential

No. 2 Check Valve: Differential

Passed Test: Yes No

Leaked

Leaked

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

Failed to Open

Air Inlet valve fully opened: Yes No

INTIAL TEST RESULTS TEST AFTER REPAIR OR CLEANING

SERVICE ADDRESS:

CROSS-CONNECTION CONTROLLED:

LOCATION:

MODEL: SIZE: SERIAL NO:

Backflow Prevention Form

NAME OF FACILITY:

STATE OF CT APPROVED ASSEMBLY:

Yes No

METER READING

No. 2 Check Valve: Closed Tight Leaked

Closed Tight Leaked

DCVA

No. 1 Check Valve: Differential psid

No. 2 Check Valve: Differential psid

Passed Test: Yes No

Leaked

Leaked

Date: ______________________ Certified Tester's Signature

Repaired By:

Certified Tester's Signature

CT License No: _____________

Initial Test By: _________________________________ Cer. No: __________________

Repair Person's Printed Name

Repair Test By: Cer. No: __________________ Date: ______________________

Date: ______________________

Passed Test: Yes No

RPBA

Relief Valve Opened psid

Yes No

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

PVBA/

SVBA

CERTIFIED TESTER'S TYPED OR PRINTED NAME

AG Approved Air Gap: Yes No

PLEASE RECORD REPAIR INSPECTION CLEANING

INFORMATION IN SECTION BELOW

Is this a proper installation? FIRE SERVICE BY-PASS METER

Pipe Diameter _____ inches Seperation ________ inches

REMARKS:

Test Equipment: Make: _____________ Model: _______________ Serial #: ________ ___________Accuracy Date: ____________ I CERTIFY THIS REPORT IS ACCURATE, AND THAT I HAVE USED MANUFACTURER APPROVED TEST METHODS

CERTIFIED: _____________________________________________________________________________________________

Failed to Open

Air Inlet valve fully opened: Yes No Check Valve: _____________________________ psid

TEST RECORDS MUST BE KEPT FOR AT LEAST THREE YEARS* *USE ONLY MANUFACTURER'S REPLACEMENT PARTS psid

Relief Valve Opened No. 2 Check Valve: Closed Tight

Leaked Closed Tight

Leaked

Passed Test:

Yes Yes psid

No psid psid psid

No. 1 Check Valve: Differential

No. 2 Check Valve: Differential

Passed Test: Yes No

Leaked

Leaked

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

Failed to Open

Air Inlet valve fully opened: Yes No

INTIAL TEST RESULTS TEST AFTER REPAIR OR CLEANING

SERVICE ADDRESS:

CROSS-CONNECTION CONTROLLED:

LOCATION:

MODEL: SIZE: SERIAL NO:

Backflow Prevention Form

NAME OF FACILITY:

STATE OF CT APPROVED ASSEMBLY:

Yes No

METER READING

No. 2 Check Valve: Closed Tight Leaked

Closed Tight Leaked

DCVA

No. 1 Check Valve: Differential psid

No. 2 Check Valve: Differential psid

Passed Test: Yes No

Leaked

Leaked

Date: ______________________ Certified Tester's Signature

Repaired By:

Certified Tester's Signature

CT License No: _____________

Initial Test By: _________________________________ Cer. No: __________________

Repair Person's Printed Name

Repair Test By: Cer. No: __________________ Date: ______________________

Date: ______________________

Passed Test: Yes No

RPBA

Relief Valve Opened psid

Yes No

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

PVBA/

SVBA

CERTIFIED TESTER'S TYPED OR PRINTED NAME

AG Approved Air Gap: Yes No

PLEASE RECORD REPAIR INSPECTION CLEANING

INFORMATION IN SECTION BELOW

Is this a proper installation? FIRE SERVICE BY-PASS METER

Pipe Diameter _____ inches Seperation ________ inches

REMARKS:

Test Equipment: Make: _____________ Model: _______________ Serial #: ________ ___________Accuracy Date: ____________ I CERTIFY THIS REPORT IS ACCURATE, AND THAT I HAVE USED MANUFACTURER APPROVED TEST METHODS

CERTIFIED: _____________________________________________________________________________________________

Failed to Open

Air Inlet valve fully opened: Yes No Check Valve: _____________________________ psid

TEST RECORDS MUST BE KEPT FOR AT LEAST THREE YEARS* *USE ONLY MANUFACTURER'S REPLACEMENT PARTS psid

Relief Valve Opened No. 2 Check Valve: Closed Tight

Leaked Closed Tight

Leaked

Passed Test:

Yes Yes psid

No psid psid psid

No. 1 Check Valve: Differential

No. 2 Check Valve: Differential

Passed Test: Yes No

Leaked

Leaked

Passed Test: Yes No

Leaked

Air Inlet: Opened psid

Failed to Open

Air Inlet valve fully opened: Yes No