This combined synopsis and solicitation requests quotes for annual backflow prevention system inspection services at the US Coast Guard Air Station in Sitka, Alaska. The solicitation seeks inspection of backflow prevention systems in accordance with the statement of work by February 15, 2024. Quotes are due by January 17, 2024 and shall be submitted to the contracting specialist via email. This requirement is set aside 100% for small businesses defined as specialty trade contractors with average annual revenue less than $19 million. The place of performance is the US Coast Guard Air Station located at 611 Airport Road in Sitka.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Back Flow Form

Anchorage Water & Wastewater Utility Attn: Field Services 3000 Arctic Blvd. Anchorage, AK 99503-3813 Phone: (907) 564-2762

FAX: (907)786-5001

EMAIL: awwufieldservices@awwu.blz

Service Type

Existing New Replacement

Replaces SN# Serial Number MOA # 1000520201 Assembly ID Contact Name Test Due Date 10/25/2022

Assembly Location Information Facility Name Location ID

USCG SITKA

Service Address Zip Phone 611 Airport Road 99835 (907)942-7562

Property Information Mailing Name Same Address 1

City ST Zip Telephone

Assembly Information Type Size Mfr Model DC 8” Ames 2000SE

Equip Location Pump room

Hazard Type Sprinkler

Water Turn Off Authorization: (Print) Time

02:36:05 PM

Is the Assembly installed in accordance with manufacturers recommendations and/or local codes? Yes No

Test Date 10/25/2022 https://mydoforms.appspot.com/

Initial Test

Pass Fail

Reduced Pressure Principal Assembly Check Valve #1 Check Valve #2 Relief Valve

Held at 0 PSID Held at 0 PSID Opened at PSID

Closed Tight Leaked

Closed Tight Leaked

Did Not Open

Pressure Vacuum Breaker Air Inlet Check Valve

Opened at PSID Held at PSID Did Not Open Leaked

Repairs and Materials Used Replaced check valve 1 and 2

Final Test

Pass

Reduced Pressure Principal Assembly Check Valve #1 Check Valve #2 Relief Valve

Held at 4.8 PSID Held at 4.6 PSID Opened at PSID

Closed Tight Closed Tight

Pressure Vacuum Breaker Air Inlet Check Valve

Opened at PSID Held at PSID

Test Gauge Used:

Manufacturer/Model: SN: Calib/Accur Date:

Midwest 07143561

Remarks Passed

Photos

Image 1 Image 2

Image 3 Image 4

Image 5 Image 6

Image 7 Image 8

Image 9 Image 10

Service Restored Yes No

The above is certified to be true at the time of testing Tester Name Company Name Steve Sizemore IV North Star Fire Protection, LLC Company Address Phone Number 520 W. 58th Ave. Unit G Anchorage, AK 99518 (907)677-1233 Tester Signature Certified Tester #

BAT 723

Customer Email

Other Email

Powered by www.doForms.com https://mydoforms.appspot.com/imageViewer?blobKey=ag9zfm15ZG9mb3Jtcy1ocmRyFwsSCmJsb2Jfc3RvcmUYgICM8Oqo_woM&blobName=9a856g853r3oft0$$05042020162136$$Published$$457$$P1$$P1.jpg https://mydoforms.appspot.com/imageViewer?blobKey=ag9zfm15ZG9mb3Jtcy1ocmRyFwsSCmJsb2Jfc3RvcmUYgICMoMLxlAsM&blobName=9a856g853r3oft0$$05042020162136$$Published$$457$$S1$$S1.jpg https://www.doForms.com