This document is a combined synopsis and solicitation from the United States Coast Guard for annual backflow prevention system inspection services at the US Coast Guard Air Station in Sitka, Alaska. The solicitation seeks quotes for inspection of backflow prevention assemblies in accordance with the attached statement of work, to be completed no later than February 15, 2024. Quotes are due by 1pm Alaska time on January 17, 2024 and shall be submitted to the contracting officer via email. This acquisition is set aside 100% for small businesses with a size standard of $19 million. The place of performance will be at the US Coast Guard Air Station in Sitka.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Back Flow Form
Anchorage Water & Wastewater Utility Attn: Field Services 3000 Arctic Blvd. Anchorage, AK 99503-3813 Phone: (907) 564-2762
FAX: (907)786-5001
EMAIL: awwufieldservices@awwu.blz
Service Type
Existing New Replacement
Replaces SN# Serial Number MOA # 2bK1702 Assembly ID Contact Name Test Due Date Tom Logan 09/19/2022
Assembly Location Information Facility Name Location ID Coast Guard Air Station Sitka Maintenance shop Service Address Zip Phone Sitka 99835 (907)942-7562
Property Information Mailing Name Coast Guard Air Station Sitka Address 1 611 Airport Drive City ST Zip Telephone Sitka Ak 99835
Assembly Information Type Size Mfr Model DC 4” Ames 2000ss
Equip Location Maintenance shop
Hazard Type Sprinkler
Water Turn Off Authorization: (Print) Time
10:09:00 AM
Is the Assembly installed in accordance with manufacturers recommendations and/or local codes? Yes No
Test Date 09/19/2022 https://mydoforms.appspot.com/
Initial Test
Pass Fail
Reduced Pressure Principal Assembly Check Valve #1 Check Valve #2 Relief Valve
Held at 3.0 PSID Held at 6.0 PSID Opened at PSID
Closed Tight Leaked
Closed Tight Leaked
Did Not Open
Pressure Vacuum Breaker Air Inlet Check Valve
Opened at PSID Held at PSID Did Not Open Leaked
Repairs and Materials Used Na
Final Test
Pass
Reduced Pressure Principal Assembly Check Valve #1 Check Valve #2 Relief Valve
Held at PSID Held at PSID Opened at PSID
Closed Tight Closed Tight
Pressure Vacuum Breaker Air Inlet Check Valve
Opened at PSID Held at PSID
Test Gauge Used:
Manufacturer/Model: SN: Calib/Accur Date:
Midwest 845 Na
Remarks
Photos
Image 1 Image 2
Image 3 Image 4
Image 5 Image 6
Image 7 Image 8
Image 9 Image 10
Service Restored Yes No
The above is certified to be true at the time of testing Tester Name Company Name Gregory Stevenson North Star Fire Protection, LLC Company Address Phone Number 520 W. 58th Ave. Unit G Anchorage, AK 99518 (907)677-1233 Tester Signature Certified Tester #
BAT 010
Customer Email Tomas.m.logan@uscg.mil
Other Email
Powered by www.doForms.com https://mydoforms.appspot.com/imageViewer?blobKey=ag9zfm15ZG9mb3Jtcy1ocmRyFwsSCmJsb2Jfc3RvcmUYgID0k_bg3QgM&blobName=9a856g853r3oft0$$05042020162136$$Published$$426$$P1$$P1.jpg https://mydoforms.appspot.com/imageViewer?blobKey=ag9zfm15ZG9mb3Jtcy1ocmRyFwsSCmJsb2Jfc3RvcmUYgID046_L5QkM&blobName=9a856g853r3oft0$$05042020162136$$Published$$426$$S1$$S1.jpg https://www.doForms.com