This document provides the United States Coast Guard (USCG) responses to questions regarding Request for Quotation (RFQ) 70Z03824QK0000023 for the purchase of a 750kVA pad mount transformer. The RFQ specifies the required transformer characteristics, including kVA, voltages, taps, bushings, fluid, frequency, temperature rise, cooling class, fusing, and switch. It also indicates that stainless steel is required for the tank enclosure and provides details on the availability of a forklift and loading dock, as well as the delivery hours. The solicitation is a 100% small business set-aside, with the applicable NAICS code being 335311 and a size standard of 800 employees. Offers are due by 31 May 2024, and the anticipated award date is on or about 6 June 2024. The document also outlines the USCG Ombudsman Program for Agency Protests, which provides an alternative dispute resolution forum for interested parties.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

70Z03824QK0000023

Responses to Questions

Amendment 2 Answers provided 23 May 2024

This document provides United States Coast Guard (USCG) responses for questions that have been asked regarding request for quotation (RFQ) 70Z03824QK0000023. Question numbers are provided simply as a reference and in no way infer a prioritization of the questions.

Number Question USCG Response 1 This is not enough information to generate a proper quote. I will need the following:

kVA:

High Voltage:

Low Voltage:

Taps:

HV Bushings:

LV Bushings:

Fluid:

Frequency:

Temperature Rise:

Cooling Class:

Fusing:

Switch:

kVA: 750KVA High Voltage: 13200V Low Voltage: 480Y/277 Wye-N Taps: 5 position tap change, with 2.5% changes, with 2 positions above and 2 positions below HV Bushings: Dead Front LV Bushings: Live front Fluid: FR-3 Fluid Frequency: 60 HZ Temperature Rise: 65 deg C Cooling Class: KNAN self-cooled Fusing: Bayonet current limiting Fuses Switch: 4 position load break switch

2 Could you accept mild steel for the tank enclosure, or does it need to be stainless steel?

Stainless Steel.

3 Is there a forklift or loading dock at the location and what are the hours of operation?

Yes, there are both a forklift and loading dock.

Deliveries shall be made between the hours of 6:45 AM – 3:15 PM EST, Monday through Friday.

PLEASE REFER TO THE SOLICITATIONS ATTACHMENT 1 “INSTRUCTIONS TO OFFERORS”

FOR A COMPLETE LIST OF THE SALIENT CHARACTERISTICS AND REQUIREMENTS.