This document provides USCG responses to questions asked regarding Request for Quotation (RFQ) 70Z03824QK0000023 for the purchase of a 750kVA Pad Mount Transformer. The RFQ includes a detailed list of the salient characteristics and requirements for the transformer, including kVA, voltages, taps, bushings, fluid, frequency, temperature rise, cooling class, fusing, and a load break switch. The USCG clarifies that the tank enclosure must be stainless steel. This is a 100% small business set-aside solicitation with a closing date of 31 May 2024 and an anticipated award date of 6 June 2024. All responsible small businesses are invited to submit quotations. Delivery is required within 22 weeks after receipt of order. No drawings, specifications, or schematics are available from the USCG.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

70Z03824QK0000023

Responses to Questions

Amendment 1 Answers provided 21 May 2024

This document provides United States Coast Guard (USCG) responses for questions that have been asked regarding request for quotation (RFQ) 70Z03824QK0000023. Question numbers are provided simply as a reference and in no way infer a prioritization of the questions.

Number Question USCG Response 1 This is not enough information to generate a proper quote. I will need the following:

kVA:

High Voltage:

Low Voltage:

Taps:

HV Bushings:

LV Bushings:

Fluid:

Frequency:

Temperature Rise:

Cooling Class:

Fusing:

Switch:

kVA: 750KVA High Voltage: 13200V Low Voltage: 480Y/277 Wye-N Taps: 5 position tap change, with 2.5% changes, with 2 positions above and 2 positions below HV Bushings: Dead Front LV Bushings: Live front Fluid: FR-3 Fluid Frequency: 60 HZ Temperature Rise: 65 deg C Cooling Class: KNAN self-cooled Fusing: Bayonet current limiting Fuses Switch: 4 position load break switch

2 Could you accept mild steel for the tank enclosure, or does it need to be stainless steel?

Stainless Steel.

PLEASE REFER TO THE SOLICITATIONS ATTACHMENT 1 “INSTRUCTIONS TO OFFERORS”

FOR A COMPLETE LIST OF THE SALIENT CHARACTERISTICS AND REQUIREMENTS.