RFP_70FB7019R00000017.pdf

PDF 638 KB Posted

Attached to
Generator Indefinite Delivery Indefinite Quantity RFP Federal contract opportunity
Solicitation number
70FB7019R00000017
Issued by
Federal Emergency Management Agency

About this file

This request for proposal solicits bids for an indefinite delivery indefinite quantity contract to provide generators ranging from 15 to over 1,000 kW. The Federal Emergency Management Agency intends to award multiple fixed-price contracts for each of its regions to support emergency response operations. The base period of performance is one year with four optional one-year extensions. Bids are due by November 4, 2019. Awards will be made by January 2, 2020. The solicitation requires generators of various sizes, as well as optional external fuel tanks and training, with deliveries to various domestic and overseas locations. The North American Industry Classification System codes covered are 335312 for motor and generator manufacturing.

Request for Proposal

View the file

Other files for this federal contract opportunity

Other files attached to Generator Indefinite Delivery Indefinite Quantity RFP, newest first.
File Type Posted
Attachment 4 Past Performance Updated.pdf PDF
Statement of Work Generator IDIQ November 2019 UPDATED.pdf PDF
Amendment 00001.pdf PDF
Attachment_2_Generator_Specifications_v1_(1).xlsx XLSX spreadsheet
Attachment_1_Generator_IDIQ_Pricing.xlsx XLSX spreadsheet
Attachment_3_Vendor_Specs_Complete_v1_(1).xlsx XLSX spreadsheet
Attachment_1_Generator_IDIQ_Pricing.xlsx XLSX spreadsheet
Attachment_2_Generator_Specifications_v1_(1).xlsx XLSX spreadsheet
Attachment_3_Vendor_Specs_Complete_v1_(1).xlsx XLSX spreadsheet
Attachment_4_Past_Performance.pdf PDF
Attachment_3_Generator_Specifications_v1_(1)_Draft.xlsx XLSX spreadsheet
Statement_of_Work_Generator_IDIQ.pdf PDF
Show all 12

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SEE ADDENDUMIS CHECKED

CODE 18a. PAYMENT WILL BE MADE BY

CODE

FACILITYCODE

17b. CHECK IF REMITTANCE IS DIFFERENT AND PUT SUCH ADDRESS IN OFFER

OFFEROR

FEMA HQ

WASHINGTON DC 20472

500 C STREET SW

ACQUISITION MANAGEMENT

FEDERAL EMERGENCY MANAGEMENT AGENCY

FEMA HQ

FEMA CODE 16. ADMINISTERED BYCODE

X

X

335312

SIZE STANDARD:

% FOR:SET ASIDE:UNRESTRICTED ORFEMA HQ

RFPIFB

10. THIS ACQUISITION ISCODE

RFQ

14. METHOD OF SOLICITATION

13b. RATING

NAICS:

SMALL BUSINESS

11/29/2019 1000 ES

11/04/2019

202-646-3924Isaac Chapple (No collect calls)

INFORMATION CALL:

FOR SOLICITATION 8. OFFER DUE DATE/LOCAL TIMEb. TELEPHONE NUMBER a. NAME

4. ORDER NUMBER3. AWARD/ 6. SOLICITATION

70FB7019R00000017

5. SOLICITATION NUMBER

SOLICITATION/CONTRACT/ORDER FOR COMMERCIAL ITEMS 1. REQUISITION NUMBER PAGE OF

1 88 OFFEROR TO COMPLETE BLOCKS 12, 17, 23, 24, & 30

3RD FLOOR

TELEPHONE NO.

17a. CONTRACTOR/

WASHINGTON DC 20472

500 C STREET SW

FEDERAL EMERGENCY MANGEMENT AGENCY

FEMA

15. DELIVER TO

WASHINGTON DC 20472

3RD FLOOR

500 C STREET SW

OFFICE OF CHIEF PROCUREMENT OFFICE

FEDERAL EMERGENCY MANAGEMENT AGENCY

9. ISSUED BY

7.

2. CONTRACT NO.

EFFECTIVE DATE

1,000

18b. SUBMIT INVOICES TO ADDRESS SHOWN IN BLOCK 18a UNLESS BLOCK BELOW

ISSUE DATE

DELIVERY FOR FOB DESTINA-

TION UNLESS BLOCK IS

MARKED

11.

SEE SCHEDULEX

12. DISCOUNT TERMS

THIS CONTRACT IS A

RATED ORDER UNDER

DPAS (15 CFR 700)

13a.

SERVICE-DISABLED

VETERAN-OWNED

SMALL BUSINESS

HUBZONE SMALL

BUSINESS

8(A)

FEMA HQ

WOMEN-OWNED SMALL BUSINESS

(WOSB) ELIGIBLE UNDER THE WOMEN-OWNED

SMALL BUSINESS PROGRAM

EDWOSB

24.

AMOUNT

23.

UNIT PRICE

22.

UNIT

21.

QUANTITY

20.

SCHEDULE OF SUPPLIES/SERVICES

19.

ITEM NO.

The purpose of this solicitation is to procure a multiple award IDIQ contracts for Generators.

Delivery: 30 Days After Award Period of Performance: 01/02/2020 to 01/01/2025

0001 Generator: 15-35kW (15-60kW range) EA

Product/Service Code: 6105 Continued ...

(Use Reverse and/or Attach Additional Sheets as Necessary)

HEREIN, IS ACCEPTED AS TO ITEMS:

X

XX

DATED

Isaac Chapple

. YOUR OFFER ON SOLICITATION (BLOCK 5),

INCLUDING ANY ADDITIONS OR CHANGES WHICH ARE SET FORTH

COPIES TO ISSUING OFFICE. CONTRACTOR AGREES TO FURNISH AND DELIVER

ARE

ARE

31c. DATE SIGNED

27b. CONTRACT/PURCHASE ORDER INCORPORATES BY REFERENCE FAR 52.212-4. FAR 52.212-5 IS ATTACHED. ADDENDA

31a. UNITED STATES OF AMERICA (SIGNATURE OF CONTRACTING OFFICER)

30c. DATE SIGNED 31b. NAME OF CONTRACTING OFFICER (Type or print)

ALL ITEMS SET FORTH OR OTHERWISE IDENTIFIED ABOVE AND ON ANY ADDITIONAL

SHEETS SUBJECT TO THE TERMS AND CONDITIONS SPECIFIED.

27a. SOLICITATION INCORPORATES BY REFERENCE FAR 52.212-1, 52.212-4. FAR 52.212-3 AND 52.212-5 ARE ATTACHED. ADDENDA

26. TOTAL AWARD AMOUNT (For Govt. Use Only)

OFFER

STANDARD FORM 1449 (REV. 2/2012)

Prescribed by GSA - FAR (48 CFR) 53.212

ARE NOT ATTACHED.

ARE NOT ATTACHED.

AUTHORIZED FOR LOCAL REPRODUCTION

PREVIOUS EDITION IS NOT USABLE

30b. NAME AND TITLE OF SIGNER (Type or print)

30a. SIGNATURE OF OFFEROR/CONTRACTOR

28. CONTRACTOR IS REQUIRED TO SIGN THIS DOCUMENT AND RETURN

25. ACCOUNTING AND APPROPRIATION DATA

29. AWARD OF CONTRACT:

REF.

32e. MAILING ADDRESS OF AUTHORIZED GOVERNMENT REPRESENTATIVE

32c. DATE 32b. SIGNATURE OF AUTHORIZED GOVERNMENT REPRESENTATIVE

ACCEPTED, AND CONFORMS TO THE CONTRACT, EXCEPT AS NOTED:

32a. QUANTITY IN COLUMN 21 HAS BEEN

RECEIVED INSPECTED

40. PAID BY39. S/R VOUCHER NUMBER38. S/R ACCOUNT NUMBER

37. CHECK NUMBER

FINALPARTIAL

36. PAYMENT

FINALPARTIAL

35. AMOUNT VERIFIED

CORRECT FOR

34. VOUCHER NUMBER33. SHIP NUMBER

COMPLETE

32g. E-MAIL OF AUTHORIZED GOVERNMENT REPRESENTATIVE

42d. TOTAL CONTAINERS42c. DATE REC'D (YY/MM/DD)

42b. RECEIVED AT (Location)

42a. RECEIVED BY (Print)

41c. DATE41b. SIGNATURE AND TITLE OF CERTIFYING OFFICER

41a. I CERTIFY THIS ACCOUNT IS CORRECT AND PROPER FOR PAYMENT

STANDARD FORM 1449 (REV. 2/2012) BACK

24.

AMOUNT

23.

UNIT PRICE

22.

UNIT

21.

QUANTITY

20.

SCHEDULE OF SUPPLIES/SERVICES

19.

ITEM NO.

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2019 to 12/02/2020

0002 Generator: 35-60kW (15-60kW range) EA

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2019 to 12/02/2020

0003 Generator: 61-100kW EA

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2019 to 12/02/2020

0004 Generator: 101-200kW EA

Continued ...

32f. TELEPHONE NUMBER OF AUTHORIZED GOVERNMENT REPRESENTATIVE

32d. PRINTED NAME AND TITLE OF AUTHORIZED GOVERNMENT REPRESENTATIVE

88 2 of

ITEM NO. SUPPLIES/SERVICES QUANTITY UNIT UNIT PRICE AMOUNT

NAME OF OFFEROR OR CONTRACTOR

3 88

CONTINUATION SHEET

REFERENCE NO. OF DOCUMENT BEING CONTINUED PAGE OF

(A) (B) (C) (D) (E) (F)

70FB7019R00000017

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2019 to 12/02/2020

0005 Generator: 201-300kW (Low Range) EA

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2019 to 12/02/2020

0006 Generator: 301-400kW (High Range) EA

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2019 to 12/02/2020

0007 Generator: 401-704kW EA

Continued ...

NSN 7540-01-152-8067 OPTIONAL FORM 336 (4-86)

Sponsored by GSA

FAR (48 CFR) 53.110

4 88

CONTINUATION SHEET

REFERENCE NO. OF DOCUMENT BEING CONTINUED PAGE OF

(A) (B) (C) (D) (E) (F)

70FB7019R00000017

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2019 to 12/02/2020

0008 Generator: 705-1mW EA

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2019 to 12/02/2020

0009 External Tank (15-100kW generator range) EA

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2019 to 12/02/2020

0010 External Tank (101-200kW generator range) EA

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2019 to 12/02/2020

0011 External Tank (201-400kW generator range) EA

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2019 to 12/02/2020

Continued ...

NSN 7540-01-152-8067 OPTIONAL FORM 336 (4-86)

5 88

CONTINUATION SHEET

REFERENCE NO. OF DOCUMENT BEING CONTINUED PAGE OF

(A) (B) (C) (D) (E) (F)

70FB7019R00000017

0012 On Site Training EA

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2019 to 12/02/2020

0013 Shipping EA

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2019 to 12/02/2020

0014 Other Direct Cost (ODC) EA

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2019 to 12/02/2020

1001 Generator: 15-35kW (15-60kW range) EA

(Option Line Item)

Date Option to be Exercised12/02/2020

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2020 to 12/02/2021

1002 Generator: 35-60kW (15-60kW range) EA

(Option Line Item)

Date Option to be Exercised12/02/2020

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2020 to 12/02/2021

1003 Generator: 61-100kW EA

(Option Line Item)

Date Option to be Exercised12/02/2020

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2020 to 12/02/2021

Continued ...

NSN 7540-01-152-8067 OPTIONAL FORM 336 (4-86)

6 88

CONTINUATION SHEET

REFERENCE NO. OF DOCUMENT BEING CONTINUED PAGE OF

(A) (B) (C) (D) (E) (F)

70FB7019R00000017

1004 Generator: 101-200kW EA

(Option Line Item)

Date Option to be Exercised12/02/2020

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2020 to 12/02/2021

1005 Generator: 201-300kW (Low Range) EA

(Option Line Item)

Date Option to be Exercised12/02/2020

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2020 to 12/02/2021

1006 Generator: 301-400kW (High Range) EA

(Option Line Item)

Date Option to be Exercised12/02/2020

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2020 to 12/02/2021

1007 Generator: 401-704kW EA

(Option Line Item)

Date Option to be Exercised12/02/2020

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2020 to 12/02/2021

1008 Generator: 705-1mW EA

Continued ...

NSN 7540-01-152-8067 OPTIONAL FORM 336 (4-86)

7 88

CONTINUATION SHEET

REFERENCE NO. OF DOCUMENT BEING CONTINUED PAGE OF

(A) (B) (C) (D) (E) (F)

70FB7019R00000017

(Option Line Item)

Date Option to be Exercised12/02/2020

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2020 to 12/02/2021

1009 External Tank (15-100kW generator range) EA

(Option Line Item)

Date Option to be Exercised12/02/2020

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2020 to 12/02/2021

1010 External Tank (101-200kW generator range) EA

(Option Line Item)

Date Option to be Exercised12/02/2020

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2020 to 12/02/2021

1011 External Tank (201-400kW generator range) EA

(Option Line Item)

Date Option to be Exercised12/02/2020

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2020 to 12/02/2021

1012 On Site Training EA

(Option Line Item)

Date Option to be Exercised12/02/2020

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2020 to 12/02/2021

1013 Shipping EA

(Option Line Item)

Date Option to be Exercised12/02/2021

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Continued ...

NSN 7540-01-152-8067 OPTIONAL FORM 336 (4-86)

8 88

CONTINUATION SHEET

REFERENCE NO. OF DOCUMENT BEING CONTINUED PAGE OF

(A) (B) (C) (D) (E) (F)

70FB7019R00000017

Period of Performance: 12/03/2021 to 12/02/2022

1014 Other Direct Cost (ODC) EA

(Option Line Item)

Date Option to be Exercised12/02/2021

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2021 to 12/02/2022

2001 Generator: 15-35kW (15-60kW range) EA

(Option Line Item)

Date Option to be Exercised12/02/2021

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2021 to 12/02/2022

2002 Generator: 35-60kW (15-60kW range) EA

(Option Line Item)

Date Option to be Exercised12/02/2021

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2021 to 12/02/2022

2003 Generator: 61-100kW EA

(Option Line Item)

Date Option to be Exercised12/02/2021

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2021 to 12/02/2022

2004 Generator: 101-200kW EA

(Option Line Item)

Date Option to be Exercised12/02/2021

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2021 to 12/02/2022

Continued ...

NSN 7540-01-152-8067 OPTIONAL FORM 336 (4-86)

9 88

CONTINUATION SHEET

REFERENCE NO. OF DOCUMENT BEING CONTINUED PAGE OF

(A) (B) (C) (D) (E) (F)

70FB7019R00000017

2005 Generator: 201-300kW (Low Range) EA

(Option Line Item)

Date Option to be Exercised12/02/2021

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2021 to 12/02/2022

2006 Generator: 301-400kW (High Range) EA

(Option Line Item)

Date Option to be Exercised12/02/2021

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2021 to 12/02/2022

2007 Generator: 401-704kW EA

(Option Line Item)

Date Option to be Exercised12/02/2021

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2021 to 12/02/2022

2008 Generator: 705-1mW EA

(Option Line Item)

Date Option to be Exercised12/02/2021

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2021 to 12/02/2022

2009 External Tank (15-100kW generator range) EA

(Option Line Item)

Date Option to be Exercised12/02/2021

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2021 to 12/02/2022

2010 External Tank (101-200kW generator range) EA

(Option Line Item)

Date Option to be Exercised12/02/2021

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Continued ...

NSN 7540-01-152-8067 OPTIONAL FORM 336 (4-86)

10 88

CONTINUATION SHEET

REFERENCE NO. OF DOCUMENT BEING CONTINUED PAGE OF

(A) (B) (C) (D) (E) (F)

70FB7019R00000017

Period of Performance: 12/03/2021 to 12/02/2022

2011 External Tank (201-400kW generator range) EA

(Option Line Item)

Date Option to be Exercised12/02/2021

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2021 to 12/02/2022

2012 On Site Training EA

(Option Line Item)

Date Option to be Exercised12/02/2021

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2021 to 12/02/2022

2013 Shipping EA

(Option Line Item)

Date Option to be Exercised12/02/2021

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2021 to 12/02/2022

2014 Other Direct Cost (ODC) EA

(Option Line Item)

Date Option to be Exercised12/02/2021

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2021 to 12/02/2022

3001 Generator: 15-35kW (15-60kW range) EA

(Option Line Item)

Date Option to be Exercised12/02/2022

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2022 to 12/02/2023

3002 Generator: 35-60kW (15-60kW range) EA

Continued ...

NSN 7540-01-152-8067 OPTIONAL FORM 336 (4-86)

11 88

CONTINUATION SHEET

REFERENCE NO. OF DOCUMENT BEING CONTINUED PAGE OF

(A) (B) (C) (D) (E) (F)

70FB7019R00000017

(Option Line Item)

Date Option to be Exercised12/02/2022

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2022 to 12/02/2023

3003 Generator: 61-100kW EA

(Option Line Item)

Date Option to be Exercised12/02/2022

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2022 to 12/02/2023

3004 Generator: 101-200kW EA

(Option Line Item)

Date Option to be Exercised12/02/2022

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2022 to 12/02/2023

3005 Generator: 201-300kW (Low Range) EA

(Option Line Item)

Date Option to be Exercised12/02/2022

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2022 to 12/02/2023

3006 Generator: 301-400kW (High Range) EA

(Option Line Item)

Date Option to be Exercised12/02/2022

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2022 to 12/02/2023

3007 Generator: 401-704kW EA

(Option Line Item)

Date Option to be Exercised12/02/2022

Product/Service Code: 6105

Continued ...

NSN 7540-01-152-8067 OPTIONAL FORM 336 (4-86)

12 88

CONTINUATION SHEET

REFERENCE NO. OF DOCUMENT BEING CONTINUED PAGE OF

(A) (B) (C) (D) (E) (F)

70FB7019R00000017

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2022 to 12/02/2023

3008 Generator: 705-1mW EA

(Option Line Item)

Date Option to be Exercised12/02/2022

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2022 to 12/02/2023

3009 External Tank (15-100kW generator range) EA

(Option Line Item)

Date Option to be Exercised12/02/2022

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2022 to 12/02/2023

3010 External Tank (101-200kW generator range) EA

(Option Line Item)

Date Option to be Exercised12/02/2022

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2022 to 12/02/2023

3011 External Tank (201-400kW generator range) EA

(Option Line Item)

Date Option to be Exercised12/02/2022

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2022 to 12/02/2023

3012 On Site Training EA

(Option Line Item)

Date Option to be Exercised12/02/2022

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2022 to 12/02/2023

3013 Shipping EA

(Option Line Item)

Date Option to be Exercised12/02/2022

Continued ...

NSN 7540-01-152-8067 OPTIONAL FORM 336 (4-86)

13 88

CONTINUATION SHEET

REFERENCE NO. OF DOCUMENT BEING CONTINUED PAGE OF

(A) (B) (C) (D) (E) (F)

70FB7019R00000017

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2022 to 12/02/2023

3014 Other Direct Cost (ODC) EA

(Option Line Item)

Date Option to be Exercised12/02/2022

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2022 to 12/02/2023

4001 Generator: 15-35kW (15-60kW range) EA

(Option Line Item)

Date Option to be Exercised12/02/2023

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2023 to 12/02/2024

4002 Generator: 35-60kW (15-60kW range) EA

(Option Line Item)

Date Option to be Exercised12/02/2023

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2023 to 12/02/2024

4003 Generator: 61-100kW EA

(Option Line Item)

Date Option to be Exercised12/02/2023

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2023 to 12/02/2024

4004 Generator: 101-200kW EA

(Option Line Item)

Date Option to be Exercised12/02/2023

Product/Service Code: 6105

Continued ...

NSN 7540-01-152-8067 OPTIONAL FORM 336 (4-86)

14 88

CONTINUATION SHEET

REFERENCE NO. OF DOCUMENT BEING CONTINUED PAGE OF

(A) (B) (C) (D) (E) (F)

70FB7019R00000017

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2023 to 12/02/2024

4005 Generator: 201-300kW (Low Range) EA

(Option Line Item)

Date Option to be Exercised12/02/2023

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2023 to 12/02/2024

4006 Generator: 301-400kW (High Range) EA

(Option Line Item)

Date Option to be Exercised12/02/2023

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2023 to 12/02/2024

4007 Generator: 401-704kW EA

(Option Line Item)

Date Option to be Exercised12/02/2023

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2023 to 12/02/2024

4008 Generator: 705-1mW EA

(Option Line Item)

Date Option to be Exercised12/02/2023

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2023 to 12/02/2024

4009 External Tank (15-100kW generator range) EA

(Option Line Item)

Date Option to be Exercised12/02/2023

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2023 to 12/02/2024

4010 External Tank (101-200kW generator range) EA

(Option Line Item)

Continued ...

NSN 7540-01-152-8067 OPTIONAL FORM 336 (4-86)

15 88

CONTINUATION SHEET

REFERENCE NO. OF DOCUMENT BEING CONTINUED PAGE OF

(A) (B) (C) (D) (E) (F)

70FB7019R00000017

Date Option to be Exercised12/02/2023

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2023 to 12/02/2024

4011 External Tank (201-400kW generator range) EA

(Option Line Item)

Date Option to be Exercised12/02/2023

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2023 to 12/02/2024

4012 On Site Training EA

(Option Line Item)

Date Option to be Exercised12/02/2023

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2023 to 12/02/2024

4013 Shipping EA

(Option Line Item)

Date Option to be Exercised12/02/2023

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2023 to 12/02/2024

4014 Other Direct Cost (ODC) EA

(Option Line Item)

Date Option to be Exercised12/02/2023

Product/Service Code: 6105

Product/Service Description: MOTORS, ELECTRICAL

Period of Performance: 12/03/2023 to 12/02/2024

NSN 7540-01-152-8067 OPTIONAL FORM 336 (4-86)

SECTION B – SUPPLIES, SERVICES, AND PRICES

B.1 ITEMS TO BE ACQUIRED

B.2 PRICE SCHEDULE

B.3 MINIMUM AND MAXIMUM QUANTITIES FOR MULTIPLE AWARD CONTRACTS

SECTION C - STATEMENT OF WORK

PART 1: GENERAL

1.1 BACKGROUND

1.2 SCOPE

1.3 GENERAL

PART 2: CONTRACTOR DELIVERABLES

2.1 PRODUCTS

2.2 QUALITY

2.3 INSPECTION/ACCEPTANCE

2.4 DELIVERY LOCATION AND SCHEDULE

2.4.1 Delivery Location

2.4.2 Delivery Schedule

SECTION D - PACKAGING AND MARKING

SECTION E - INSPECTION AND ACCEPTANCE

SECTION F - DELIVERIES AND PERFORMANCE

SECTION G - CONTRACT ADMINISTRATION DATA

G.2 CONTRACTING OFFICER

G.3 CONTRACTING OFFICER REPRESENTATIVE

G.4 DELIVERY/DELIVERY MONITORS

G.5 DELIVERY ORDERS

G.6 DELIVERY ORDER PROCEDURES

G.7 DELIVERY ORDER ISSUANCE

G.8 MODIFICATIONS

G.9 BILLING INSTRUCTIONS (JUN 2014)

G.10 DEFECTIVE OR IMPROPER INVOICES (JUN 2014)

G.11 INVOICE APPROVAL (JUN 2014)

G.12 INVOICE INSTRUCTIONS (JUN 2014)

SECTION H - SPECIAL CONTRACT REQUIREMENT

SECTION I - CONTRACT CLAUSES

I.2 - Addendum to FAR 52.212-4 I 2.10 - 52.217-9 -- Option to Extend the Term of the Contract

Section J - LIST OF DOCUMENTS, EXHIBITS, AND OTHER ATTACHMENTS Section K - REPRESENTATIONS, CERTIFICATION, AND OTHER STATEMENTS OF BIDDERS ...49

NOTICE LISTING SOLICITATION PROVISIONS INCORPORATED BY REFERENCE

Section L - INSTRUCTIONS, CONDITIONS AND NOTICES TO BIDDERS

L.3 SERVICE OF PROTEST (FAR 52.233-2) (SEP 2006)

L.6 COMMITMENT OF GOVERNMENT TO AWARD CONTRACT(S) AND EXPENDITURE

OF FUNDS

L.7 ALTERNATE PROPOSAL INFORMATION (FEMA 52.215-205)

L.8 RESTRICTION ON USE AND DISCLOSURE OF PROPOSAL/QUOTATION

INFORMATION (DATA)

L.9 OFFEROR ACCEPTANCE PERIOD

L.10 PROPOSAL PREPARATION INSTRUCTIONS

VOLUME I

M.2 ACQUISITION APPROACH:

M.3 SOURCE SELECTION TRADE-OFF PROCESS:

70FB7019R00000017

SECTION B – SUPPLIES, SERVICES, AND PRICES

B.1 ITEMS TO BE ACQUIRED

The contractor shall provide generators with necessary fuel tanks and fuel lines (with proper connections and appurtenances as identified in the generator specifications, minimum and maximum kW range for each size, listed in Attachment 2 – Generator Criteria as specified in the award. Generators can generally be classified into the 401kW Above and 400kW and Below.

B.2 PRICE SCHEDULE

Offerors shall provide a detail breakdown for each contract line item numbers (CLINs) listed above. Contractor must use format in Attachment 1. If Attachment 1 format is not utilized, the proposal is deemed UNACCEPTABLE.

B.3 MINIMUM AND MAXIMUM QUANTITIES FOR MULTIPLE AWARD

CONTRACTS

As referred to in paragraph (b) of FAR Clause 52.216-22, “Indefinite Quantity” of this contract, the guaranteed contract minimum is the amount of the smallest generator to be purchase under this IDIQ per contract to include the base and option periods. The contract ceiling amount shall not exceed the maximum quantity of supplies, the total amount of supplies ordered under this shall not exceed the total productive capacity of all vendors under this contract.

B.4 CONTRACT TYPE

The Department Homeland Security (DHS) - Federal Emergency Management Agency (FEMA) intends to award up to three (3) generators 400kw below and three (3) 400kw above Indefinite Delivery-Indefinite Quantity (IDIQ) contracts with Firm-Fixed-Price (FFP) CLINs.

SECTION C - STATEMENT OF WORK

Generator Purchase - IDIQ Department of Homeland Security (DHS)

Federal Emergency Management Agency (FEMA)

Contents

PART 1: GENERAL

1.1 BACKGROUND

1.2 SCOPE

1.3 GENERAL

PART 2: CONTRACTOR DELIVERABLES

2.1 PRODUCTS

2.2 QUALITY

2.3 INSPECTION/ACCEPTANCE

2.4 DELIVERY LOCATION AND SCHEDULE

2.4.1 Delivery Location

2.4.2 Delivery Schedule

PART 1: GENERAL

1.1 BACKGROUND

The Department of Homeland Security (DHS) – Federal Emergency Management Agency (FEMA) maintains a fleet of generators at Distribution Centers (DC) located at both within the Continental United States (CONUS) and outside Other than Continental United States (OCONUS) locations, in order to support emergency response operations.

The agency is currently updating the fleet to meet Tier 4Final EPA compliance.

1.2 SCOPE

The contractor shall provide generators and Generator Sets (external tanks if applicable) to support Disaster Relief Operations.

1.3 GENERAL

The generator (and external tank, if applicable) requirement is to support FEMA’s generator fleet which is maintained to support emergency response operations; and the procurement is to fill shortfalls at identified locations (in IDIQ Delivery Order) within the fleet due to the lifecycle of generators. The generator requirement is set up as an IDIQ which gives FEMA the ability to place future orders for generators of various type(s) and sizes as described in the specifications below.

The Contractor shall provide primary and an alternate (if applicable) Point-of Contact person(s) who will have the authority to commit the company, as required to execute the award. The contractor(s) shall furnish all professional, technical and clerical services as well as materials, equipment and facilities to meet the stated specifications and project requirements defined in this Statement of Work (SOW).

PART 2: CONTRACTOR DELIVERABLES

2.1 PRODUCTS

The contractor shall provide generators with necessary fuel tanks and fuel lines (with proper connections and appurtenances as identified in the generator specifications, minimum and maximum kW range for each size, listed in Attachment 2 – Generator Criteria as specified in the individual delivery order. Generators are classified into two categories 400kW below (to include external tanks which are indicated within specifications) and 401kW and above. Within each classification, there are sub-classifications which indicate the required ranges as specified in Attachment 2 – Generator Specifications.

The specific quantities, kW size requirement (minimum-maximum FEMA acceptable range) and delivery locations will be specified within the solicitation for the delivery orders themselves.

A detailed listing of all the required specifications is in Attachment 2 – Generator Criteria. Therefore, the specifications shall include, but not be limited to:

2.1 (a) - Generators 400kW and BELOW (CONUS & OCONUS):

Units are to be Skid Mounted to include 2ea FORK POCKETS (6”x10” x .250 and rub spacers) Rated for prime power Units must be a power module in a container Units must be 3-phase switchable 120/208v, 139/240v, and 277/280v. As per the required specifications, vendors SHALL provide hardware and/or software, manuals or other documentation (in digital (CD-disk) or hard copy) that provide DETAILED directions with allow FEMA mechanics to switch/set output voltages and phase configurations on generator and voltage regulator

Excitation SHALL be either: brushless with IVR OR brushless with AVR Load terminals SHALL be: bus bar with lugs Integrally mounted automated load bank system (56kW Units and above):

Units (56kW and above) shall contain an integrally – mounted automated load bank system shall have the ability to apply no more than 40% resistive load during periods of low temperature/load conditions.

SHALL have the capability to constantly monitor, sense and manage exhaust temperature with automatic shut-off for periods of high load conditions

SHALL have indicator light incorporated into the unit to indicate when load bank system is turned ON (“dummy light”)

Be fully automated, zero operator input required

Emissions:

MUST BE Tier 4Final emission compliant and meet all Environmental

Protection Agency (EPA) regulations; require Ultra Low Sulfur Diesel Fluid (ULSDF) – meeting California Emissions requirements

SHALL be capable to perform “Active or Passive Regen” on its own with no operator at full-rated speed

SHALL have the capability to “NOT REGEN” at 80-90% load As per the required specifications, vendors need to explain how generators would be manufactured with Tier 4Final engines (no aftermarket modification is authorized); and they also are required to provide documentation/proof that engines will meet the Tier 4Final engine capability requirements.

Engine accessories: shall at a minimum meet the requirements in Attachment

Battery: SHALL be either: Sealed Gel Cell OR Absorbed Glass Matt (AGM); and must include a master shut-off switch

Control panel components: shall at a minimum meet the requirements in Attachment 2.

Engine shutdown safety specifications: shall at a minimum meet the requirements in Attachment 2

Fuel Tank (24hr Requirement):

Generators (25kW and above) shall have 24-hour EXTERNAL fuel tank UL 142 double wall required External tank must meet the gallon requirement as stated in the specifications Equipped with an external tank gauge that connects to the generator control panel External basin equipped with liquid level sensor for leakage into basin – link to generator SHALL be double stackable with fuel / triple stackable when empty for storage/transportation capability SHALL include lockable integral cabinet which secures fuel and equipment;

MUST have the ability to fuel the generator while locked SHALL include 25ft of fuel line (w/ H3 or H4 connectors) between external tank and generator Diesel Exhaust Fluid: integrated into generator and approved to provide fuel to operate at full rated speed Manufacture Warranties: Engine and Generator Generators are Not to Exceed (NTE) 104” in height for air transportation mobility Must meet other requirements as outlined in Attachment 2 – generator specifications Acknowledge that a delivery plan is included within the proposal submission

(as stated in in the RFP) Capacity plates and a unique 6-digit identification number Provide to the government at time of proposal submission, detailed specification sheets for each kW size (15 pages/each kW size)

2.1 (b)(i) - Generators 401kW and Above (CONUS Locations):

Units are to be Chassis Mounted with an air ride suspension trailer Rated for prime power Units must be a power module in a container Units must be 3-phase switchable 120/208v, 139/240v, and 277/280v. As per the required specifications, vendors SHALL provide hardware and/or software, manuals or other documentation (in digital (CD-Disk) or hard copy) that provide DETAILED directions with allow FEMA mechanics to switch/set output voltages and phase configurations on generator and voltage regulator

Excitation SHALL be either: brushless with IVR OR brushless with AVR Load terminals SHALL be: bus bar with lugs Emissions: Generators 704kW and below (401-704kW requirement):

MUST BE Tier 4Final emission compliant and meet all EPA regulations;

require Ultra Low Sulfur Diesel Fluid (ULSDF) – meeting California Emissions requirements SHALL be capable to perform “Active or Passive Regen” on its own with no operator at full-rated speed SHALL have the capability to “NOT REGEN” at 80-90% load As per the required specifications, for the 704kW below units, vendors need to explain how generators would be manufactured with Tier 4Final engines (no aftermarket modification is authorized); and they also are required to provide documentation/proof that engines will meet the Tier 4Final engine capability requirements.

Emissions: Generators 705kW and above (705kw – 1mw requirement):

MUST BE Tier 2 (at a minimum) or higher emission compliant (Tier 2, Tier

3, Tier 4i / Tier; Tier 4Final is preferred) IF unit is Tier 4Final / Tier 4i emission compliant and meets all EPA regulations; require Ultra Low Sulfur Diesel Fluid (ULSDF) – meeting California Emissions requirements

SHALL be capable to perform “Active or Passive Regen” on its own with no operator at full-rated speed

As per the required specifications state, vendors need to explain how generators would be manufactured with Tier 4Final engines (no aftermarket modification); and they also are required to provide documentation/proof that engines will meet the Tier 4Final engine capability requirements.

Engine accessories: shall at a minimum meet the requirements in Attachment

Battery: SHALL be either: Sealed Gel Cell OR Absorbed Glass Matt (AGM); and must include a master shut-off switch

Control panel components: shall at a minimum meet the requirements in Attachment 2

Engine shutdown safety specifications: shall at a minimum meet the requirements in Attachment 2

Fuel Tank (24hr requirement):

Units for this requirement SHALL have 24-hour INTERNAL fuel tank at a minimum meeting the following requirements:

Integrated into generator UL 142 double wall required Be equipped with Parker H4 male and female quick disconnects & dust cap – sufficient enough to meet efficient fuel flow Shall contain internal Diesel Engine Fluid (DEF) Tanks (Tier 4i/4Final

ONLY)

Manufacture Warranties for Generator; engine and trailer

Units MUST be parallel capable – multi mode (island, and utility parallel);

load sharing; manual and automatic paralleling capability; and include ALL BOM and REQUIRED cables needed to run generator(s) in parallel

Units shall have 2ea. Fork pockets integrated into the container Generators when removed from chassis trailer, are Not to Exceed (NTE) 104” in height for air transportation mobility Must meet other requirements as outlined in Attachment 2 – generator specifications Acknowledge that a delivery plan is included within the proposal submission

(as stated in in the RFP) Capacity plates and a unique 6-digit identification number Provide to the government at time of proposal submission, detailed specification sheets for each kW size (15 pages per size)

2.1(b)(ii) - Generators 401kW and Above (OCONUS Locations):

Unit Mounting (depending on SIZE)

401-750kW: Skid Mounted to include 2ea FORK POCKETS (6”x10” x .250 and rub spacers)

751->1mW: Chassis Mounted with an air ride suspension trailer Rated for prime power Units must be a power module in a container Units must be 3-phase switchable 120/208v, 139/240v, and 277/280v. As per the required specifications, vendors SHALL provide hardware and/or software, manuals or other documentation (in digital (CD-disk) or hard copy) that provide DETAILED directions with allow FEMA mechanics to switch/set output voltages and phase configurations on generator and voltage regulator

Excitation SHALL be either: brushless with IVR OR brushless with AVR Load terminals SHALL be: bus bar with lugs Emissions: Generators 704kW and below (401-704kW requirement):

MUST BE Tier 4Final emission compliant and meet all EPA regulations;

require Ultra Low Sulfur Diesel Fluid (ULSDF) – meeting California Emissions requirements SHALL be capable to perform “Active or Passive Regen” on its own with no operator at full-rated speed SHALL have the capability to “NOT REGEN” at 80-90% load As per the required specifications, for the 704kW below units, vendors need to explain how generators would be manufactured with Tier 4Final engines (no aftermarket modification is authorized); and they also are required to provide documentation/proof that engines will meet the Tier 4Final engine capability requirements

Emissions: Generators 705kW and above (705kw – >1mw requirement):

MUST BE Tier 2 (at a minimum) or higher emission compliant (Tier 2, Tier 3, Tier 4i / Tier; Tier 4Final is preferred) o IF unit is Tier 4Final / Tier 4i emission compliant and meets all EPA regulations; require Ultra Low Sulfur Diesel Fluid (ULSDF) – meeting California Emissions requirements o SHALL be capable to perform “Active or Passive Regen” on its own with no operator at full-rated speed o SHALL have the capability to “NOT REGEN” at 80-90% load o As per the required specifications state, vendors need to explain how generators would be manufactured with Tier 4Final engines (no aftermarket modification); and they also are required to provide documentation/proof that engines will meet the Tier 4Final engine capability requirements.

Engine accessories: shall at a minimum meet the requirements in Attachment 2 Battery: SHALL be either: Sealed Gel Cell OR Absorbed Glass Matt (AGM);

and must include a master shut-off switch Control panel components: shall at a minimum meet the requirements in

Attachment 2 Engine shutdown safety specifications: shall at a minimum meet the requirements in Attachment 2 Fuel Tank (24hr requirement):

Units for this requirement SHALL have 24-hour INTERNAL fuel tank at a minimum meeting the following requirements:

Integrated into generator UL 142 double wall required Be equipped with Parker H4 male and female quick disconnects & dust cap – sufficient enough to meet efficient fuel flow Shall contain internal Diesel Engine Fluid (DEF) Tanks (Tier 4i/4Final

ONLY)

Provide Manufacture Warranties for Generator; engine and trailer (if applicable depending on SIZE) Units MUST be parallel capable – multi mode (island, and utility parallel);

load sharing; manual and automatic paralleling capability; and include ALL BOM and REQUIRED cables needed to run generator(s) in parallel

Units shall have 2ea. Fork pockets integrated into the container if unit is Chassis mounted

Generators are Not to Exceed (NTE) 104” in height for air transportation mobility. IF unit is trailer mounted, the unit must meet the NTE when it is REMOVED from chassis trailer.

Must meet other requirements as outlined in Attachment 2 – generator specifications

Acknowledge that a delivery plan is included within the proposal submission (as stated in in the RFP)

Capacity plates and a unique 6-digit identification number Provide to the government at time of proposal submission, detailed specification sheets for each kW size (15 pages per size)

As part of this requirement, for diagnostic and troubleshooting purposes, the vendor SHALL provide any hardware and/or software, manuals or other documentation (digital (CD-Disk) or hard copy), to include all diagnostic codes, that will enable FEMA mechanics to perform all diagnostic’s available for the generator(s).

Additionally, as part of this requirement, the vendor SHALL provide one on-site training session at each Distribution Center for FEMA Mechanics on operational guidance with regards to the equipment. Training shall occur AFTER the delivery of all units to given location; no more than 30 days after receipt of generators. Training date(s) and time(s) are TBD dependent on generator delivery timeline – to be agreed upon by the contractor and the Government. Training SHALL include how to switch/set the output voltages and phase configuration on the generator and voltage regulators.

2.2 QUALITY

Equipment furnished under this award shall be NEW, of good quality, in safe operating condition and shall comply with all applicable standards and safety regulations including but not limited to EPA regulations. All safety devices shall be fully functional; to include all manual and automatic emergency shut-off mechanisms. All safety guards, warning labels, and safety related instruction labels shall always be properly affixed.

2.3 INSPECTION/ACCEPTANCE

Prior to delivery of the generator(s), local vendor is to conduct an initial inspection to ensure that the units is in Fully Mission Capable (FMC) condition. Due to up-tempo at time of delivery, the Government will conduct an inspection within 2 weeks of delivery.

Inspection will be completed by FEMA Technical Monitors who will be pre-identified at each destination (task order level). For all orders, the contractor shall obtain Proof of Delivery (P.O.D.) including the time of delivery, full delivery address; and the name and signature of the person who accepted the shipment. The contractor shall provide a customer representative/technician at the delivery location to ensure generators are operational before final acceptance at destination by the Government. FEMA mechanics will be onsite at time of delivery and will verify the mission readiness of each of the units upon acceptance at their respective locations. If the generator fails inspection the contractor will complete repair or replace within 30 days.

2.4 DELIVERY LOCATION AND SCHEDULE

2.4.1 Delivery Location

The Government will require delivery to the Distribution Centers identified in the delivery order solicitation itself, to include quantities and locations.

Distribution Center Address City / State Zip Code

DC Frederick

(CONUS)

4420 Buckeystown Pike

Frederick, MD 21704

DC Atlanta (CONUS) 3780 Southside Industrial Parkway

Atlanta, GA 30354

DC Fort Worth

(CONUS)

501 W. Felix Street Fort Worth, TX 76115

DC Tracy (CONUS) 1547 E. Grant Line Tracy, CA 94035 DC Hawaii

(OCONUS)

99-1269 Iwena Street

Aeia, HI 96701

DC Guam

(OCONUS)

Bldg. 100 Barrigada GU 96913

DC Caribbean

(OOCNUS)

Rd. 1, Km. 25.1, Quebrada Arenas Ward

Caguas, PR 00725

Hours of Performance: Work hours depend on local business practices and time zones.

The vendor shall schedule all delivery activities with the appropriate delivery point of contact after award (to be provided after award by the Project Officer).

Delivery is to include door to door transportation as well as any additional requirements for the labor and downloading of the generators/shipping containers (if applicable). Due to the shipping of generators to an OCONUS locations (when applicable), vendor needs to be prepared to successfully go thru customs inspection at Pod of Entry (POE), and continue delivery transportation to the distribution center. Vendors are to acknowledge that a delivery plan is included within the proposal submission (as stated in the RFP) as part of the requirement on Attachment 2 – Generator Criteria.

2.4.2 Delivery Schedule

Generators:

Delivery Schedule will be determined at the delivery order level.

Training:

Training Schedule will be determined at the delivery order level.

SECTION D - PACKAGING AND MARKING

All generators unit must be package and mark as stated below. Please understand that the government may change the packaging requirement as needed to meet the needs of the Agency mission.

Generators 400kW and BELOW (CONUS & OCONUS):

Units are to be Skid Mounted to include 2ea FORK POCKETS (6”x10” x .250 and rub spacers) Generators 401kW and Above (CONUS Locations):

o Unit Mounting (depending on SIZE) 401-750kW: Skid Mounted to include 2ea FORK POCKETS (6”x10” x .250 and rub spacers) 751->1mW: Chassis Mounted with an air ride suspension trailer

As per the required specifications, for the 704kW below units, vendors need to explain how generators would be manufactured with Tier 4Final engines (no aftermarket modification is authorized); and they also are required to provide documentation/proof that engines will meet the Tier 4Final engine capability requirements. Please see the SOW for additional details.

SECTION E - INSPECTION AND ACCEPTANCE

E.1 NOTICE LISTING CONTRACT CLAUSES INCORPORATED BY

REFERENCE

The following contract clauses pertinent to this section are hereby incorporated by reference (by Citation Number, Title, and Date) in accordance with the clause at FAR "52.252-2 CLAUSES INCORPORATED BY REFERENCE" contained in this document.

See FAR 52.252-2 for an internet address www.farsite.gov for electronic access to the full text of a clause.

Number Title Date

52.246-1 Contractor Inspection Requirements APR 1984 52.246-2 Inspection of Supplies - Fixed-Price. AUG 1996 52.246-15 Certificate of Conformance. APR 1984 52.246-16 Responsibility for Supplies APR 1984

E.2 Quality Equipment furnished under this award shall be NEW, of good quality, in safe operating condition and shall comply with all applicable standards and safety regulations including but not limited to Environmental Protection Agency (EPA) regulations. All safety devices shall be fully functional; to include all manual and automatic emergency shut-off mechanisms. All safety guards, warning labels, and safety related instruction labels shall always be properly affixed.

E.3 INSPECTION AND ACCEPTANCE

The Government reserves the right, at all reasonable times, and upon reasonable notice to the Contractor, to inspect or otherwise evaluate the work performed or being performed at the location(s). Prior to delivery of the generator(s), local vendor is to conduct an initial inspection to ensure that the units is in Fully Mission Capable (FMC) condition.

Due to up-tempo at time of delivery, the Government will conduct an inspection within 2 weeks of delivery. Inspection will be completed by FEMA Technical Monitors who will be pre-identified at each destination.

For all orders, the contractor shall obtain Proof of Delivery (P.O.D.) including the time of delivery, full delivery address; and the name and signature of the person who accepted the shipment. The contractor shall provide a customer representative/technician at the delivery location to ensure generators are operational before final acceptance at destination by the Government. FEMA mechanics will be onsite at time of delivery and will verify the mission readiness of each of the units upon acceptance at their respective locations. If the generator fails inspection the contractor will complete repair or replace within 30 days.

http://www.farsite.gov/

SECTION F - DELIVERIES AND PERFORMANCE

F.1 NOTICE LISTING CONTRACT CLAUSES INCORPORATED BY

REFERENCE

The following contract clauses pertinent to this section are hereby incorporated by reference (by Citation Number, Title, and Date) in accordance with the clause at FAR "52.252-2 CLAUSES INCORPORATED BY REFERENCE" contained in this document.

See FAR 52.252-2 for an internet address www.farsite.gov for electronic access to the full text of a clause.

NUMBER TITLE DATE

52.211-13 TIME EXTENSIONS SEP 2000

52.242-15 STOP-WORK ORDER AUG 1989

52.242-17 GOVERNMENT DELAY OF WORK APR 1984

52.247-34 F.O.B. DESTINATION NOV 1991

52.247-48 F.o.b. Destination - Evidence of Shipment FEB 1999

F.2 TERMS OF THE CONTRACT

The contract shall be effective as of the execution date and shall continue through five years one base plus four (4) option periods, except that delivery orders placed prior to the expiration date shall remain in full force and effect until deliveries have been completed and payments, therefore, have been made.

1. The Period of Performance shall be from the date of contract award through 12 months.

2. If Option 1 is exercised, the Period of Performance shall be from the effective date of the option through 12 months.

3. If Option 2 is exercised, the Period of Performance shall be from the effective date of the option through 12 months.

4. If Option 3 is exercised, the Period of Performance shall be from the effective date of the option through 12 months.

5. If Option 4 is exercised, the Period of Performance shall be from the effective date of the option through 12 months.

F.3 PLACE OF PERFORMANCE

The Government will require delivery to the Distribution Centers identified in the delivery order itself, to include quantities and locations.

Distribution Center Address City / State Zip Code

DC Frederick

(CONUS)

4420 Buckeystown Pike

Frederick, MD 21704

DC Atlanta (CONUS) 3780 Southside Industrial Parkway

Atlanta, GA 30354

DC Fort Worth

(CONUS)

501 W. Felix Street Fort Worth, TX 76115 http://www.farsite.gov/

DC Tracy (CONUS) 1547 E. Grant Line Tracy, CA 94035 DC Hawaii

(OCONUS)

99-1269 Iwena Street

Aeia, HI 96701

DC Guam

(OCONUS)

Bldg. 100 Barrigada GU 96913

DC Caribbean

(OOCNUS)

Rd. 1, Km. 25.1, Quebrada Arenas Ward

Caguas, PR 00725

Hours of Performance: Work hours depend on local business practices and time zones.

The vendor shall schedule all delivery activities with the appropriate delivery point of contact after award (to be provided after award by the Project Officer).

Delivery is to include door to door transportation as well as any additional requirements for the labor and downloading of the generators/shipping containers (if applicable). Due to the shipping of generators to an OCONUS locations (when applicable), vendor needs to be prepared to successfully go thru customs inspection at Pod of Entry (POE), and continue delivery transportation to the distribution center. Vendors are to acknowledge that a delivery plan is included within the proposal submission (as stated in the RFP) as part of the requirement on Attachment 2 – Generator Criteria.

F.4 52.247-57 Transportation Transit Privilege Credits. (APR 1984)

(a) If the offeror has established with regulated common carriers transit privileges that can be applied to the supplies when shipped from the original source, the offeror is invited to propose to use these credits for shipping the supplies to the designated Government destinations. The offeror will ship these supplies under commercial bills of lading, paying all remaining transportation charges connected with the shipment, subject to reimbursement by the Government in an amount equal to the remaining charges but not exceeding the amount quoted by the offeror.

(b) After loading on the carrier's equipment and acceptance by the carrier, these shipments under paid commercial bills of lading will move for the account of and at the risk of the Government (unless, pursuant to the Changes clause, the office administering the contract directs use of Government bills of lading).

(c) The amount quoted below by the offeror represents the transportation costs in cents per 100 pounds (freight rate) for full carload/truckload shipments of the supplies from offeror's original source, via offeror's transit plant or point, to the Government destination(s) including the carrier's transit privilege charge, less the applicable transit credit (i.e., the amount (rate) initially paid to the carrier for shipment from original source to offeror's transit plant or point).

(d) The rate per CWT quoted will be used by the Government to evaluate the offered f.o.b. origin price unless a lower rate is applicable on the date of bid opening (or closing date specified for receipt of offers). To have the offer evaluated on this basis, the offeror must insert below the remaining transportation charges that the offeror agrees to pay, including any transit charges, subject to reimbursement by the Government, as explained in this clause, to destinations listed in the Schedule as follows:

RATE PER CWT IN CENTS: [ ]

TO DESTINATION: [ ]

F.5 DELIVERY ORDER LEVEL PERFORMANCE PERIOD

Each Delivery/Delivery Order Proposal request will specify a period of performance.

F.6 DELIVERY SCHEDULE

Delivery of items will be determined…

This is the start of the file's text. The full file is on GovTribe.