7-JF26-027-IFB 5793 Churchill FA System Upgrade ECE - Permit Set.pdf

PDF 3 MB Posted

Attached to
Construction: Fire Alarm Upgrade at Churchill Jr High
Solicitation number
JF26-027-IFB
Issued by
Salt Lake County, Utah

About this file

This is a permit set of electrical construction drawings prepared by Electrical Consulting Engineers for the Granite School District's fire alarm and carbon monoxide detection system upgrade project at Churchill Junior High School located at 3450 East Oakview Drive, Millcreek, Utah 84124. The project scope includes removal of existing fire alarm devices, conduit, and conductors, and installation of a new fire alarm control panel (FACU: E3-BB-BB), transponder (SBB-D4), and associated detection and notification equipment throughout the main and second floors of the facility. New equipment to be installed includes photoelectric smoke detectors (ASD-PL3), heat detectors (ATD-L3R), combination smoke/carbon monoxide detectors (CO1224TR), manual pull stations (MS-7AF), horns with strobes (P2WL/PC2WL), strobes (SWL/SCWL), fire sprinkler flow and tamper switches (AMM-4F), and duct detectors with sampling tubes. The fire alarm system will operate as a Class A loop configuration with in and out cables running in separate conduits and plenum where required. Drawings include a fire alarm riser diagram, demolition plans for both floors, installation plans for both floors, general notes with symbol lists, and connection details for sprinkler risers and firestop assemblies.

The invitation for bids requires response from a licensed General Electrical Contractor (E200) and mandates attendance at a pre-bid meeting as detailed in the project manual. Award recommendation is scheduled for presentation at the Granite School District Board meeting on June 2, 2026, with final award to be issued following board approval. The project will involve coordination with the fire alarm manufacturer's representative and includes provisions for automatic fan shutdown programming tied to the new fire alarm control panel and carbon monoxide detection system. If the fire alarm system operates off after hours, a fire watch will be required. The electrical work includes a dedicated 20-ampere, single-pole, red circuit breaker connection for the new fire alarm control panel and transponder, utilizing existing circuits where possible, with all necessary conduit, conductors, and junction boxes to complete the installation.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

GRANITE SCHOOL DISTRICT

E000

COVER SHEET

CHURCHILL JUNIOR HIGH SCHOOL

3450 EAST OAKVIEW DRIVE

MILLCREEK, UTAH 84124

CHECKED BY:

ECE PROJECT NO.

DRAWN BY:

SHEET NUMBER

DATE DESCRIPTION

REVISIONS:

NO. DATE DESCRIPTION

ISSUED:

NO.

ELECTRICAL CONSULTING ENGINEERS

323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5793

Sheet Index

E000: COVER SHEET

E001:GENERAL NOTES AND SYMBOLS

E002: PHOTOS

E003: FIRE ALARM RISER DIAGRAM

ED101: MAIN FLOOR FIRE ALARM DEMOLITION

ED102: SECOND FLOOR FIRE ALARM DEMOLITION

EY101: MAIN FLOOR FIRE ALARM INSTALL

EY102: SECOND FLOOR FIRE ALARM INSTALL

ELECTRICAL CONSULTING ENGINEERS

323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5793

FIRE ALARM & CARBON MONOXIDE UPGRADE

E001

GENERAL NOTES,

SYMBOLS LIST

AND DETAILS

TYPICAL WIRING FOR EACH SPRINKLER RISER (SEE FIRE SPRINKLER

DRAWINGS FOR QUANTITY AND LOCATIONS.)

MAIN

OS&Y VALVE

DETECTOR SWITCH FURNISHED AND

INSTALLED BY SPRINKLER

4 #14, 1/2''CONDUIT

ALARM VALVE

SEAL TIGHT

4 #14, 1/2''CONDUIT

WALL MOUNTED JUNCTION BOX

FLOW SWITCH FURNISHED AND INSTALLED BY

SPRINKLER CONTRACTOR, WIRED BY ELEC.

RISER

CONDUIT 8 #14 THW, 3/4''CONDUIT

TO FIRE ALARM MASTER TYPICAL

EACH SPRINKLER RISER.

CEILING

SCALE:

FIRE SPRINKLER CONNECTION DETAIL

N.T.S.

CONTRACTOR, WIRED BY ELEC.

ANCHOR TO WALL WITH

EPOXY ANCHORS AS

REQUIRED BY WEIGHT

SUPPORTED (TYPICAL)

SCALE: STANDARD HEIGHTS FOR

N.T.S.

M

A X

M

IN

IM

U

M

ELECTRICAL

OUTLETS

PULL

FIRE

CEILING

DECK

STROBE LIGHT

OR HORN &

STROBE

SMOKE, HEAT,

& FLAME

DETECTORS

LIGHT SWITCHES

FIRE ALARM PULL STATION

M

A X

PUSH BUTTONS

BEAM

STRUCTURAL

JOIST OR

DROPPED

CEILING

STANDARD HEIGHTS

FOR AREAS WITH

CEILING DECK OR

DROPPED CEILINGS

SURFACE MOUNT CONDUITS ON CEILING.

DO NOT PENDANT MOUNT CONDUITS

EXCEPT AT ROOF DECK MAINTAIN 1-1/2"

SEPARATION BETWEEN DECK &

HANDICAPPED ACCESS

CONDUITS.

THROUGH CONCRETE WALLS

MAY 09, 2013

F RATING - 2 HR

T RATING - 0 HR

L RATING AT AMBIENT - LESS THAN 1 CFM/SQ. FT.

L RATING AT 400 F - LESS THAN 1 CFM/SQ. FT.

SECTION A-A

WALL ASSEMBLY

A

A

SCALE: TYPICAL FIRESTOP FOR CABLES/CONDUIT

N.T.S.

FIRE ALARM SYSTEMS SYMBOL LIST

SYMBOL DESCRIPTION

ELECTRICAL PANEL LOCATION, PART #: FACU: E3-BB-BB, NAC: SBB-D4, REMOTE

ANNUNCIATOR: E3-BB-BAA

FIRE ALARM SYSTEM PHOTOELECTRIC SMOKE DETECTOR, PART #: ASD-PL3

FIRE ALARM HEAT DETECTOR, PART #: ATD-L3R

FIRE ALARM COMBINATION SMOKE/CARBON MONOXIDE DETECTOR, PART #:

CO1224TR

FIRE ALARM MANUAL PULL STATION, +42" A.F.F., PART #: MS-7AF

FIRE ALARM HORN WITH STROBE, HIGH DECIBEL, +96" A.F.F., PART #: WALL: P2WL,

CEILING: PC2WL, WEATHER PROOF: P2RK

A.D.A. STROBE FOR FIRE ALARM, +96" A.F.F., PART #: WALL: SWL, CEILING: SCWL

BLUE STROBE LIGHT

FIRE SPRINKLER FLOW SWITCH, PART #: AMM-4F

FIRE SPRINKLER TEMPER SWITCH, PART #: AMM-4F

BEAM DETECTOR TRANSMITTER - LETTER INDICATES PAIRING

BEAM DETECTOR RECEIVER - LETTER INDICATES PAIRING

BEAM CONTROLLER

RELAY MODULE, PART #: PR-3

KITCHEN HOOD MONITOR

CONTROL MODULE

CONTROL MODULE WITH RELAY

B

CM

R

CALLOUT SYMBOL LIST

SYMBOL DESCRIPTION

LIGHTING FIXTURE CALLOUT NUMBER INDICATES A SUGGESTED QUANTITY- TO BE

VERIFIED

MECHANICAL EQUIPMENT CALLOUT

DETAIL REFERENCE CALLOUT

REVISION NUMBER CALLOUT

EQUIPMENT CALLOUT

REFERENCE NOTE CALLOUT

ABBREVIATIONS SYMBOL LIST

SYMBOL DESCRIPTION

W.P. INDICATES WEATHER PROOF EQUIPMENT

A INDICATES DEVICE IS ABOVE COUNTER TOP

AMP. AMPERAGE

A.F.F. ABOVE FINISHED FLOOR

B.CO BLUE CARBON MONOXIDE STROBE

CLG. INDICATES CEILING MOUNTED DEVICE

EM INDICATES DEVICE IS ON EMERGENCY CIRCUIT

EX INDICATES DEVICE IS EXISTING

F.A.C.P. FIRE ALARM CONTROL PANEL

F.A.R.A.P. FIRE ALARM REMOTE ANNUNCIATOR PANEL

K.V.A. KILO VOLT AMPERAGE

K.W. KILOWATT

M.C.B. MAIN CIRCUIT BREAKER

M.L.O. MAIN LUG ONLY

O.T.R. ON THE ROOF

S INDICATES DEVICE IS SURFACE MOUNTED

T.V.S.S. TRANSIENT VOLTAGE SURGE SUPPRESSOR

TYP TYPICAL

U.P.S. UNINTERRUPTIBLE POWER SUPPLY

XFMR TRANSFORMER

CHECKED BY:

ECE PROJECT NO.

DRAWN BY:

SHEET NUMBER

DATE DESCRIPTION

REVISIONS:

NO. DATE DESCRIPTION

ISSUED:

NO.

C H

U R

C H

IL

L

J U

N

IO

R H

IG

H

S C

H O

O L

F

IR

E A

L A

R M

S Y

S T

E M

U P

G R

A D

E

E

A S

T O

A K

V

IE

W D

R

IV

E

M

IL

L C

R E

E K

U

T A

H

ELECTRICAL CONSULTING ENGINEERS

323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5793

SCALE:

N.T.S.

1/2" FLEX x 6' (MAX)

MAINTAIN CLASS A WIRING

LAY-IN TILE CEILING

3/4" CONDUIT FOR FIRE

ALARM LOOP

4" SQUARE x 2-1/8" J-BOX

AT CEILING DECK

3/4" CONDUIT FOR

FIRE ALARM LOOP

CONNECTIONS FOR FIRE ALARM

DEVICES IN LAY-IN CEILINGS

GENERAL NOTES:

SPECIAL NOTES:

E002

PHOTOS

CHECKED BY:

ECE PROJECT NO.

DRAWN BY:

SHEET NUMBER

DATE DESCRIPTION

REVISIONS:

NO. DATE DESCRIPTION

ISSUED:

NO.

C H

U R

C H

IL

L

J U

N

IO

R H

IG

H

S C

H O

O L

F

IR

E A

L A

R M

S Y

S T

E M

U P

G R

A D

E

E

A S

T O

A K

V

IE

W D

R

IV

E

M

IL

L C

R E

E K

U

T A

H

ELECTRICAL CONSULTING ENGINEERS

323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5793

REMOVE EXISTING

F.A.C.P.

REMOVE THE

EXISTING DEVICE

AND CAGE

(3) HP-FF8

CONDUITS

& ONE 3/4"

TWO 1"

5.2" DEEP

24" WIDE

45.9" HIGH

TRANSPONDER

SBB-D4

w/FCI-DR-D4B

DEDICATED CIRCUIT

120 VAC W/GROUND

1 CAT-6E TO PHONE BOARD

2 CAT-6E TO NETWORK PORTS

FACU

S3-BB-RB

4.5" DEEP

19.375" WIDE

19.375" HIGH

MINI

BATTERY

CABINET

4" DEEP

17" WIDE

8" HIGH

FLPS-7

SLC-PM

SLP-RB

DACT-E3

LCD-SLP

2 #14'S

TYPICAL 24 AUX POWER

1 PAIR #14'S TWISTED

TYPICAL ADDRESSABLE CIRCUIT

4 #14'S4 #14'S

TO FAN

SHUTDOWN

2 #14'S

TYPICAL NOTIFICATION CIRCUIT

2 #14'S

TYPICAL CO NOTIFICATION CIRCUIT

B B

WPB

E003

FIRE ALARM RISER

DIAGRAM

CHECKED BY:

ECE PROJECT NO.

DRAWN BY:

SHEET NUMBER

DATE DESCRIPTION

REVISIONS:

NO. DATE DESCRIPTION

ISSUED:

NO.

C H

U R

C H

IL

L

J U

N

IO

R H

IG

H

S C

H O

O L

F

IR

E A

L A

R M

S Y

S T

E M

U P

G R

A D

E

E

A S

T O

A K

V

IE

W D

R

IV

E

M

IL

L C

R E

E K

U

T A

H

ELECTRICAL CONSULTING ENGINEERS

323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com

B

TRANSPONDER

F.A.C.P.

1 1

1 1

1 1

1 1

1 1

11 1

1 1 1

1 1

1 1

11 1

1 1

1 1

1 1

1 1

1 1

1 1

1 1

1 1 1 1

11 1

1. REMOVE EXISTING FIRE ALARM DEVICES, ASSOCCIATED

CONDUIT AND CONDUCTORS. PROVIDE A BLANK COVER

PLATE FOR J-BOXES IN THE BRICK WALLS. COVER PLATE TO

MATCH COLOR OF THE BRICK.

2. REMOVE EXISTING DUCT DETECTOR AND SAMPLING TUBE IN

RETURN AND SUPPLY DUCTS. REMOVE ASSOCIATED

CONDUIT, J-BOXES, ETC.

3. REMOVE EXISTING FIRE ALARM CONTROL PANEL AND

TRANSPONDER ASSOCIATED POWER SUPPLY, CONDUIT,

CONDUCTORS, BOXES, ETC. AFTER NEW FIRE ALARM

SYSTEM IS INSTALLED AND PUT INTO OPERATION. PROVIDE A

BLANK COVER PLATE FOR BOX AND PAINT TO MATCH COLOR

OF THE WALL.

1. UTILIZE EXISTING HEAT AND SMOKE DETECTOR DEVICES

BOXES FOR NEW DETECTION DEVICES. FIELD VERIFY WORK

INVOLVED PRIOR TO BID.

2. REMOVE THE EXISTING HORN/STROBE FROM THE WALLS

WITH ASSOCIATED CONDUIT, CONDUCTORS, ETC. ALL THE

WAY BACK TO THEIR ORIGINATION POINTS. PROVIDE BLANK

COVER PLATE FOR BOXES ON THE BLOCK WALLS.

ED101

MAIN LEVEL

PLAN - FIRE

ALARM

CHECKED BY:

ECE PROJECT NO.

DRAWN BY:

SHEET NUMBER

DATE DESCRIPTION

REVISIONS:

NO. DATE DESCRIPTION

ISSUED:

NO.

C H

U R

C H

IL

L

J U

N

IO

R H

IG

H

S C

H O

O L

F

IR

E A

L A

R M

S Y

S T

E M

U P

G R

A D

E

E

A S

T O

A K

V

IE

W D

R

IV

E

M

IL

L C

R E

E K

U

T A

H

ELECTRICAL CONSULTING ENGINEERS

323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5793

MAIN LEVEL PLAN - FIRE ALARM

SCALE: 1/16" = 1'-0"

1 1 1

1 1 1 1

1 1

1 1

1 1

1 1

1 1

1 1

1. REMOVE EXISTING FIRE ALARM DEVICES, ASSOCCIATED

CONDUIT AND CONDUCTORS. PROVIDE A BLANK COVER

PLATE FOR J-BOXES IN THE BRICK WALLS. COVER PLATE TO

MATCH COLOR OF THE BRICK.

2. REMOVE EXISTING DUCT DETECTOR AND SAMPLING TUBE IN

RETURN AND SUPPLY DUCTS. REMOVE ASSOCIATED

CONDUIT, J-BOXES, ETC.

1. UTILIZE EXISTING HEAT AND SMOKE DETECTOR DEVICES

BOXES FOR NEW DETECTION DEVICES. FIELD VERIFY WORK

INVOLVED PRIOR TO BID.

2. REMOVE THE EXISTING HORN/STROBE FROM THE WALLS

WITH ASSOCIATED CONDUIT, CONDUCTORS, ETC. ALL THE

WAY BACK TO THEIR ORIGINATION POINTS. PROVIDE BLANK

COVER PLATE FOR BOXES ON THE BLOCK WALLS.

ED102

SECOND

LEVEL PLAN -

FIRE ALARM

CHECKED BY:

ECE PROJECT NO.

DRAWN BY:

SHEET NUMBER

DATE DESCRIPTION

REVISIONS:

NO. DATE DESCRIPTION

ISSUED:

NO.

C H

U R

C H

IL

L

J U

N

IO

R H

IG

H

S C

H O

O L

F

IR

E A

L A

R M

S Y

S T

E M

U P

G R

A D

E

E

A S

T O

A K

V

IE

W D

R

IV

E

M

IL

L C

R E

E K

U

T A

H

ELECTRICAL CONSULTING ENGINEERS

323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5793

SECOND LEVEL PLAN - FIRE ALARM

SCALE: 1/16" = 1'-0"

NEW TRANSPONDER

NEW F.A.C.P.

5 5

5 5

WP

WP

5WP

33 3

3 3

3 3

5 3

3 3

3 3

3 3

3 3

3 3

3 3

B

3 3

3 3

1. FURNISH AND INSTALL NEW FIRE ALARM DEVICES IN THE

APPROXIMATE LOCATIONS SHOWN. TIE THE NEW DEVICES

TO NEW FIRE ALARM CONTROL PANEL IN CLASS "A" LOOP.

RUN CABLES IN AND OUT, CABLES IN SEPARATE CONDUITS.

COORDINATE THIS WORK WITH FIRE ALARM MANUFACTURE

REPRESENTATIVE.

2. FURNISH AND INSTALL A NEW CARBON MONOXIDE

DETECTOR IN THE APPROXIMATE LOCATION SHOWN. TIE

THE NEW DEVICE TO FIRE ALARM CONTROL PANEL IN CLASS

"A" LOOP. IN AND OUT CABLES MUST RUN IN PLENUM. DO

NOT SPLICE CABLES BETWEEN DEVICES.

3. INSTALL NEW HEAT DETECTOR AS CLOSE TO THE SAME

LOCATION AS POSSIBLE. PROVIDE NEW CABLES BETWEEN

DEVICES. DON'T SPLICE CABLE BETWEEN DEVICES.

4. FURNISH AND INSTALL NEW DUCT DETECTOR IN THE

RETURN AIR WITH SAMPLING TUBE. TIE THE NEW DETECTOR

TO NEW FIRE ALARM CONTROL PANEL IN CLASS "A" LOOP.

5. FURNISH AND INSTALL NEW HORN/STROBE ON THE

EXISTING CEILING. TIE TO FIRE ALARM CONTROL PANEL IN

CLASS "A" LOOP.

6. FURNISH AND INSTALL A BLUE STROBE LIGHT FOR A NEW

"CO" DETECTOR IN THE APPROXIMATE LOCATION SHOWN.

TIE TO A FIRE ALARM CONTROL PANEL IN CLASS "A" LOOP

FOR A COMPLETE INSTALLATION.

7. FURNISH AND INSTALL NEW FIRE ALARM CONTROL PANEL

AND TRANSPONDER WHERE EXISTING ONE IS LOCATED. TIE

TO A 20 AMP., 1POLE,RED CIRCUIT BREAKER IN THE

NEAREST PANEL. PROVIDE CONDUIT CONDUCTORS, ETC.

FOR A COMPLETE INSTALLATION. UTILIZE EXISTING CIRCUIT

AS POSSIBLE.

SCALE: 1/16" = 1'-0"

1. MONITOR MODULE IS TO BE GAMEWELL-FCI

MODULE/AMM-4F, AND THE SIGNAL CONTROL

MODULE IS TO BE A MODEL AOM-2SF.

2. TIE AIR FANS TO NEW F.A.C.P. FOR

AUTOMATIC SHUT DOWN. PROVIDE ALL

REQUIRED PROGRAMMING FOR PROPER FAN

SHUT DOWN DURING ALARM.

3. CO DETECTORS ARE TO SHUT DOWN

PROPER AIR FANS DURING ALARM. PROVIDE

ALL REQUIRED PROGRAMING FOR PROPER

FAN SHUT DOWN DURING ALARM.

4. IF THE FIRE ALARM SYSTEM IS TO BE OFF

AFTER HOURS A FIRE WATCH WILL BE

REQUIRED.

EY101

MAIN LEVEL

PLAN - FIRE

ALARM

CHECKED BY:

ECE PROJECT NO.

DRAWN BY:

SHEET NUMBER

DATE DESCRIPTION

REVISIONS:

NO. DATE DESCRIPTION

ISSUED:

NO.

C H

U R

C H

IL

L

J U

N

IO

R H

IG

H

S C

H O

O L

F

IR

E A

L A

R M

S Y

S T

E M

U P

G R

A D

E

E

A S

T O

A K

V

IE

W D

R

IV

E

M

IL

L C

R E

E K

U

T A

H

ELECTRICAL CONSULTING ENGINEERS

323 East 500 South SLC, UT 84111 Phone : 801.521.8007

2 2

4 1

33333

3 3 3 3

1. FURNISH AND INSTALL NEW FIRE ALARM DEVICES IN THE

APPROXIMATE LOCATIONS SHOWN. TIE THE NEW DEVICES

TO FIRE ALARM CONTROL PANEL IN CLASS "A" LOOP. IN AND

BETWEEN DEVICES. COORDINATE THE WORK WITH FIRE

ALARM MANUFACTURE REPRESENTATIVE.

2. FURNISH AND INSTALL A NEW CARBON MONOXIDE

DETECTOR IN THE APPROXIMATE LOCATION SHOWN. TIE

THE NEW DEVICE TO FIRE ALARM CONTROL PANEL IN CLASS

"A" LOOP. IN AND OUT CABLES MUST RUN IN PLENUM. DO

NOT SPLICE CABLES BETWEEN DEVICES.

3. INSTALL NEW HEAT DETECTOR AS CLOSE TO THE SAME

LOCATION AS POSSIBLE. PROVIDE NEW CABLES BETWEEN

DEVICES. DON'T SPLICE CABLE BETWEEN DEVICES.

4. FURNISH AND INSTALL NEW HORN/STROBE ON THE EXISTING

CEILING. TIE TO FIRE ALARM CONTROL PANEL IN CLASS "A"

LOOP.

5. FURNISH AND INSTALL NEW TRANSPONDER IN THE

APPROXIMATE LOCATION SHOWN. TIE TO A 20 AMP., 1POLE,

RED CIRCUIT BREAKER IN NEAREST PANEL. PROVIDE

CONDUIT AND CONDUCTORS FOR A COMPLETE

INSTALLATION.

SCALE: 1/8" = 1'-0"

EY102

SECOND

LEVEL PLAN -

FIRE ALARM

CHECKED BY:

ECE PROJECT NO.

DRAWN BY:

SHEET NUMBER

DATE DESCRIPTION

REVISIONS:

NO. DATE DESCRIPTION

ISSUED:

NO.

C H

U R

C H

IL

L

J U

N

IO

R H

IG

H

S C

H O

O L

F

IR

E A

L A

R M

S Y

S T

E M

U P

G R

A D

E

E

A S

T O

A K

V

IE

W D

R

IV

E

M

IL

L C

R E

E K

U

T A

H

ELECTRICAL CONSULTING ENGINEERS

323 East 500 South SLC, UT 84111 Phone : 801.521.8007

File details come from the government source that posted it. Updated .