7-JF26-026-IFB-REBID 5762 Bennion JHS FA Upgrade ECE - Permit Set 1.pdf
PDF 3 MB Posted
- Solicitation number
- JF26-026-IFB-REBID
- Issued by
- Salt Lake County, Utah
About this file
This is a permit set of technical drawings for a Fire Alarm and Carbon Monoxide Detection System upgrade project at Bennion Junior High School, located at 6055 South 2700 West, West Jordan, Utah 84129, prepared by Electrical Consulting Engineers (ECE) under Project No. 5762. The project scope includes the complete removal of existing fire alarm devices, conduit, and conductors, and the installation of new addressable fire alarm equipment including photoelectric smoke detectors, heat detectors, combination smoke/carbon monoxide detectors, manual pull stations, horns with strobes, and strobe lights throughout both floors of the facility. The drawings specify installation of a new Fire Alarm Control Panel (FACU) in the office/first floor computer lab area, integration with existing magnetic door holders for automatic release during alarm, replacement of existing monitor modules for tamper and flow switches with new addressable modules, and installation of a VESDA Laser Plus 4-port air sampling device in the cafeteria for early warning detection. Additional work includes tying air fans to the new fire alarm control panel for automatic shutdown during alarm conditions, providing duct detectors in return air ducts with sampling tubes, installing fire sprinkler flow and tamper switches, and providing three control modules for elevator recall coordination. The drawings reference a Class "A" loop configuration with plenum-rated cables and specify that devices must be installed without splicing between devices, with all work coordinated through the fire alarm manufacturer representative.
The technical specifications detail equipment part numbers including FACU model E3-BB-BB with NAC SBB-D4 and Remote Annunciator E3-BB-BAA, photoelectric smoke detectors (ASD-PL3), heat detectors (ATD-L3R), combination smoke/carbon monoxide detectors (CO1224TR), manual pull stations (MS-7AF), and notification devices such as horn/strobe combinations and blue strobe lights for carbon monoxide notification. The drawings indicate demolition requirements for existing duct detectors and sampling tubes in return and supply ducts, with new detectors to be installed only in return ducts. Standard installation heights are specified at 48 inches maximum and 16 inches minimum for electrical outlets, 34 inches maximum for manual pull stations, and 96 inches above finished floor for notification appliances. Conduit and wiring specifications include 3/4-inch conduit for fire alarm loops, 1/2-inch flex conduit with maximum 6-foot runs for ceiling installations, and typical addressable circuits with 4 #14 conductors. The drawings also specify firestop requirements for cables and conduits through concrete walls with 2-hour fire rating and 0-hour temperature rating, and require wireguard protection over devices with coordination of all work with the fire alarm system manufacturer.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GRANITE SCHOOL DISTRICT
6055 SOUTH 2700 WEST
WEST JORDAN, UTAH 84129
BENNION JUNIOR HIGH SCHOOL
E000
COVER SHEET
CHECKED BY:
ECE PROJECT NO.
DRAWN BY:
SHEET NUMBER
DATE DESCRIPTION
REVISIONS:
NO. DATE DESCRIPTION
ISSUED:
NO.
LD AM
B E
N N
IO
N
J U
N
IO
R H
IG
H
S C
H O
O L
F
IR
E A
L A
R M
U P
G R
A D
E
S
O U
T H
W E
S T
W E
S T
J O
R D
A N
U
T A
H
ELECTRICAL CONSULTING ENGINEERS
323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5762
E000: COVER SHEET
E001: GENERAL NOTES, SYMBOLS LIST AND
DETAILS
E002: FIRE ALARM RISER DIAGRAM
E003: EXISTING CONDITIONS - PHOTOS
ED101: FIRST FLOOR DEMOLITION PLAN -
FIRE ALARM
ED102: SECOND FLOOR DEMOLITION PLAN -
FIRE ALARM
ED401: ENLARGED DEMOLITION FLOOR
PLANS - FIRE ALARM
ED402: ENLARGED DEMOLITION FLOOR
PLANS - FIRE ALARM
EY101: FIRST FLOOR PLAN - FIRE ALARM
EY102: SECOND FLOOR PLAN - FIRE ALARM
EY103: CAFETERIA - VESDA
EY401: ENLARGED FLOOR PLANS - FIRE
ALARM
EY402: ENLARGED FLOOR PLANS - FIRE
ALARM
ELECTRICAL CONSULTING ENGINEERS
323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5762
FIRE ALARM & CARBON MONOXIDE UPGRADE
E001
GENERAL NOTES,
SYMBOLS LIST
AND DETAILS
GENERAL NOTES:
SPECIAL NOTES:
CHECKED BY:
ECE PROJECT NO.
DRAWN BY:
SHEET NUMBER
DATE DESCRIPTION
REVISIONS:
NO. DATE DESCRIPTION
ISSUED:
NO.
LD AM
B E
N N
IO
N
J U
N
IO
R H
IG
H
S C
H O
O L
F
IR
E A
L A
R M
U P
G R
A D
E
S
O U
T H
W E
S T
W E
S T
J O
R D
A N
U
T A
H
ELECTRICAL CONSULTING ENGINEERS
323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5762
TYPICAL WIRING FOR EACH SPRINKLER RISER (SEE FIRE SPRINKLER
DRAWINGS FOR QUANTITY AND LOCATIONS.)
MAIN
OS&Y VALVE
DETECTOR SWITCH FURNISHED AND
INSTALLED BY SPRINKLER
4 #14, 1/2''CONDUIT
ALARM VALVE
SEAL TIGHT
4 #14, 1/2''CONDUIT
WALL MOUNTED JUNCTION BOX
FLOW SWITCH FURNISHED AND INSTALLED BY
SPRINKLER CONTRACTOR, WIRED BY ELEC.
RISER
CONDUIT 8 #14 THW, 3/4''CONDUIT
TO FIRE ALARM MASTER TYPICAL
EACH SPRINKLER RISER.
CEILING
SCALE:
FIRE SPRINKLER CONNECTION DETAIL
N.T.S.
CONTRACTOR, WIRED BY ELEC.
ANCHOR TO WALL WITH
EPOXY ANCHORS AS
REQUIRED BY WEIGHT
SUPPORTED (TYPICAL)
SCALE: STANDARD HEIGHTS FOR
N.T.S.
M
A X
M
IN
IM
U
M
ELECTRICAL
OUTLETS
PULL
FIRE
CEILING
DECK
STROBE LIGHT
OR HORN &
STROBE
SMOKE, HEAT,
& FLAME
DETECTORS
LIGHT SWITCHES
FIRE ALARM PULL STATION
M
A X
PUSH BUTTONS
BEAM
STRUCTURAL
JOIST OR
DROPPED
CEILING
STANDARD HEIGHTS
FOR AREAS WITH
CEILING DECK OR
DROPPED CEILINGS
SURFACE MOUNT CONDUITS ON CEILING.
DO NOT PENDANT MOUNT CONDUITS
EXCEPT AT ROOF DECK MAINTAIN 1-1/2"
SEPARATION BETWEEN DECK &
HANDICAPPED ACCESS
CONDUITS.
THROUGH CONCRETE WALLS
MAY 09, 2013
F RATING - 2 HR
T RATING - 0 HR
L RATING AT AMBIENT - LESS THAN 1 CFM/SQ. FT.
L RATING AT 400 F - LESS THAN 1 CFM/SQ. FT.
SECTION A-A
WALL ASSEMBLY
A
A
SCALE: TYPICAL FIRESTOP FOR CABLES/CONDUIT
N.T.S.
FIRE ALARM SYSTEMS SYMBOL LIST
SYMBOL DESCRIPTION
ELECTRICAL PANEL LOCATION, PART #: FACU: E3-BB-BB, NAC: SBB-D4, REMOTE
ANNUNCIATOR: E3-BB-BAA
FIRE ALARM SYSTEM PHOTOELECTRIC SMOKE DETECTOR, PART #: ASD-PL3
FIRE ALARM HEAT DETECTOR, PART #: ATD-L3R
FIRE ALARM COMBINATION SMOKE/CARBON MONOXIDE DETECTOR, PART #:
CO1224TR
FIRE ALARM MANUAL PULL STATION, +42" A.F.F., PART #: MS-7AF
FIRE ALARM HORN WITH STROBE, HIGH DECIBEL, +96" A.F.F., PART #: WALL: P2WL,
CEILING: PC2WL, WEATHER PROOF: P2RK
A.D.A. STROBE FOR FIRE ALARM, +96" A.F.F., PART #: WALL: SWL, CEILING: SCWL
BLUE STROBE LIGHT
FIRE SPRINKLER FLOW SWITCH, PART #: AMM-4F
FIRE SPRINKLER TEMPER SWITCH, PART #: AMM-4F
BEAM DETECTOR TRANSMITTER - LETTER INDICATES PAIRING
BEAM DETECTOR RECEIVER - LETTER INDICATES PAIRING
BEAM CONTROLLER
RELAY MODULE, PART #: PR-3
KITCHEN HOOD MONITOR
CONTROL MODULE
CONTROL MODULE WITH RELAY
B
CM
R
CALLOUT SYMBOL LIST
SYMBOL DESCRIPTION
LIGHTING FIXTURE CALLOUT NUMBER INDICATES A SUGGESTED QUANTITY- TO BE
VERIFIED
MECHANICAL EQUIPMENT CALLOUT
DETAIL REFERENCE CALLOUT
REVISION NUMBER CALLOUT
EQUIPMENT CALLOUT
REFERENCE NOTE CALLOUT
ABBREVIATIONS SYMBOL LIST
SYMBOL DESCRIPTION
W.P. INDICATES WEATHER PROOF EQUIPMENT
A INDICATES DEVICE IS ABOVE COUNTER TOP
AMP. AMPERAGE
A.F.F. ABOVE FINISHED FLOOR
B.CO BLUE CARBON MONOXIDE STROBE
CLG. INDICATES CEILING MOUNTED DEVICE
EM INDICATES DEVICE IS ON EMERGENCY CIRCUIT
EX INDICATES DEVICE IS EXISTING
F.A.C.P. FIRE ALARM CONTROL PANEL
F.A.R.A.P. FIRE ALARM REMOTE ANNUNCIATOR PANEL
K.V.A. KILO VOLT AMPERAGE
K.W. KILOWATT
M.C.B. MAIN CIRCUIT BREAKER
M.L.O. MAIN LUG ONLY
O.T.R. ON THE ROOF
S INDICATES DEVICE IS SURFACE MOUNTED
T.V.S.S. TRANSIENT VOLTAGE SURGE SUPPRESSOR
TYP TYPICAL
U.P.S. UNINTERRUPTIBLE POWER SUPPLY
XFMR TRANSFORMER
SCALE:
N.T.S.
1/2" FLEX x 6' (MAX)
MAINTAIN CLASS A WIRING
LAY-IN TILE CEILING
3/4" CONDUIT FOR FIRE
ALARM LOOP
4" SQUARE x 2-1/8" J-BOX
AT CEILING DECK
3/4" CONDUIT FOR
FIRE ALARM LOOP
CONNECTIONS FOR FIRE ALARM
DEVICES IN LAY-IN CEILINGS
EXISTING EST PANEL
CONDUITS
& ONE 3/4"
TWO 1"
TRANSPONDER
DEDICATED CIRCUIT
120 VAC W/GROUND
1 CAT-6E TO PHONE BOARD
2 CAT-6E TO NETWORK PORTS
FACU
MINI
BATTERY
CABINET
2 #14'S
TYPICAL 24 AUX POWER
1 PAIR #14'S TWISTED
TYPICAL ADDRESSABLE CIRCUIT
4 #14'S4 #14'S
TO FAN
SHUTDOWN
2 #14'S
TYPICAL NOTIFICATION CIRCUIT
2 #14'S
TYPICAL CO NOTIFICATION CIRCUIT
B WP
E002
CHECKED BY:
ECE PROJECT NO.
DRAWN BY:
SHEET NUMBER
DATE DESCRIPTION
REVISIONS:
NO. DATE DESCRIPTION
ISSUED:
NO.
LD AM
B E
N N
IO
N
J U
N
IO
R H
IG
H
S C
H O
O L
F
IR
E A
L A
R M
U P
G R
A D
E
S
O U
T H
W E
S T
W E
S T
J O
R D
A N
U
T A
H
ELECTRICAL CONSULTING ENGINEERS
323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5762
TYPICAL FIRE
ALARM RISER
DIAGRAM
SPECIAL NOTES:
E003
EXISTING
CONDITIONS -
PHOTOS
CHECKED BY:
ECE PROJECT NO.
DRAWN BY:
SHEET NUMBER
DATE DESCRIPTION
REVISIONS:
NO. DATE DESCRIPTION
ISSUED:
NO.
LD AM
B E
N N
IO
N
J U
N
IO
R H
IG
H
S C
H O
O L
F
IR
E A
L A
R M
U P
G R
A D
E
S
O U
T H
W E
S T
W E
S T
J O
R D
A N
U
T A
H
ELECTRICAL CONSULTING ENGINEERS
323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5762
E0033
E003
DUCT DETECTOR IN FAN
ROOM OFF OF SCIENCE 202
(1 OF 2)
E003
DUCT DETECTOR IN FAN ROOM
ABOVE BOY'S RESTROOM
(1 OF 3)
E003
DUCT DETECTOR IN FAN ROOM
ABOVE THEATER (1 OF 8)
E003
E003 6
E003
DUCT DETECTORS IN MECH.
ROOM ON 2ND FLOOR (2 OF 4)
DUCT DETECTOR IN FAN
ROOM ABOVE STE 121 (1 OF 4)
DUCT DETECTOR IN
MECHANICAL ROOM ABOVE
BOILER ROOM (1 OF 2)
FIRE ALARM CONTROL PANEL
IN OFFICE
FIRST FLOOR
COMP LAB
COMP LAB
UT. STUDY
READ
ISS
CONF
ROOM
S T
O R
A G
E
PRINCIPAL CONF
ROOM
OFFICE
FAC ROOM
COUN
COUN
COUN
SEC
ASST
PRIN
OFFICE
GIRLS
LOCKER
RM
GYMNASIUM
BOYS
LOCKER
RM
OFFICE
PE
STORAGE
RM
GIRLS PE
STORAGE
RM
SEWING
HEALTH
FOOD
STORAGE
STORAGE
SHOP
STE
DRAMA
CAFETERIA
CHORUS
GEOGRAPHY
HISTORY
RESOURCE
STORAGE
RESOURCE
RESOURCE
9 ENG 109
8 ENG 110
9TH ENG
8TH ENG
MATH
AUDITORIUM
STAGE
BAND/ORCHESTRA
ART
ART
WEIGHT TRAINING
RESOURCE
STE COM
LAB 127
STORAGE
F.A.C.P.
E003
ED401
MEN
WOMEN
BOILER
ROOM
LIBRARY
WOMEN
MEN
WP
E003
1. REMOVE EXISTING FIRE ALARM DEVICES, ASSOCIATED
CONDUIT AND CONDUCTORS. PROVIDE A BLANK
COVER PLATE FOR J-BOXES IN THE BRICK WALLS.
COVER PLATE TO MATCH COLOR OF THE BRICK.
2. TIE EXISTING MAGNETIC DOOR HOLDER TO NEW FIRE
ALARM CONTROL PANEL FOR AUTOMATIC RELEASE
DURING FIRE ALARM. PROVIDE CONDUIT AND
CONDUCTORS FOR A COMPLETE INSTALLATION.
3. REMOVE EXISTING FIRE ALARM ANNUNCIATOR PANEL
ASSOCIATED CONDUCTORS AND CONDUIT. PROVIDE A
BLANK COVER PLATE FOR THE BOX AND PAINT TO
MATCH COLOR OF WALL.
4. REMOVE EXISTING MONITOR MODULES FOR THE
TEMPER AND FLOW SWITCHES AND REPLACE WITH
NEW ADDRESSABLE MONITOR MODULE.
5. EXISTING EST FIRE ALARM CONTROL PANEL IS TO
REMAIN WITH ASSOCIATED POWER SUPPLY, CONDUIT,
CONDUCTORS, BOXES, ETC.
SCALE: 1/16" = 1'-0"
ED101
FIRST FLOOR
DEMOLITION
PLAN - FIRE
ALARM
CHECKED BY:
ECE PROJECT NO.
DRAWN BY:
SHEET NUMBER
DATE DESCRIPTION
REVISIONS:
NO. DATE DESCRIPTION
ISSUED:
NO.
LD AM
B E
N N
IO
N
J U
N
IO
R H
IG
H
S C
H O
O L
F
IR
E A
L A
R M
U P
G R
A D
E
S
O U
T H
W E
S T
W E
S T
J O
R D
A N
U
T A
H
ELECTRICAL CONSULTING ENGINEERS
323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com
OPEN TO BELOW
OPEN TO BELOW
SCIENCE
SCIENCE
SCIENCE
SKILL 4 SUC
MATH
MATH
MATH/HISTORY
MATH
MATH 7
CHINESE
7 READ
WOMEN
MEN
COM LAB
SCIENCE
SCIENCE
TP
COMPUTER LAB -
LIBRARY LOFT
BUSINESS
WOMEN
MEN
COM LAB
COM LAB
GEOGRAPHY
MECH.
MECHANICAL
ZONE 6
ED401
ED401
ED401
ED402
E003
E003
E003
E003
ED401
E003
1. REMOVE EXISTING FIRE ALARM DEVICES, ASSOCIATED
CONDUIT AND CONDUCTORS. PROVIDE A BLANK
COVER PLATE FOR J-BOXES IN THE BRICK WALLS.
COVER PLATE TO MATCH COLOR OF THE BRICK.
SCALE: 1/16" = 1'-0"
ED102
SECOND
FLOOR
DEMOLITION
PLAN - FIRE
ALARM
CHECKED BY:
ECE PROJECT NO.
DRAWN BY:
SHEET NUMBER
DATE DESCRIPTION
REVISIONS:
NO. DATE DESCRIPTION
ISSUED:
NO.
LD AM
B E
N N
IO
N
J U
N
IO
R H
IG
H
S C
H O
O L
F
IR
E A
L A
R M
U P
G R
A D
E
S
O U
T H
W E
S T
W E
S T
J O
R D
A N
U
T A
H
ELECTRICAL CONSULTING ENGINEERS
323 East 500 South SLC, UT 84111 Phone : 801.521.8007
1. REMOVE EXISTING DUCT DETECTOR AND SAMPLING
TUBE IN RETURN AND SUPPLY DUCTS. REMOVE
ASSOCIATED CONDUIT, J-BOXES, ETC. NEW DUCT
DETECTOR WILL ONLY BE INSTALLED IN RETURN DUCT.
2. REMOVE EXISTING MONITOR MODULES FOR THE
TAMPER AND FLOW SWITCHES AND REPLACE WITH
NEW MONITOR MODULE. FIELD VERIFY EXACT
NUMBERS.
ZONE 5
ZONE 5
ZONE 5
SCALE: 1/2" = 1'-0"
ED401
ENLARGED
DEMOLITION
FLOOR PLANS
- FIRE ALARM
CHECKED BY:
ECE PROJECT NO.
DRAWN BY:
SHEET NUMBER
DATE DESCRIPTION
REVISIONS:
NO. DATE DESCRIPTION
ISSUED:
NO.
LD AM
B E
N N
IO
N
J U
N
IO
R H
IG
H
S C
H O
O L
F
IR
E A
L A
R M
U P
G R
A D
E
S
O U
T H
W E
S T
W E
S T
J O
R D
A N
U
T A
H
ELECTRICAL CONSULTING ENGINEERS
323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5762
SCALE: 1/2" = 1'-0"
SCALE: 1/2" = 1'-0"
SCALE: 1/2" = 1'-0"
SCALE: 1/2" = 1'-0"
ED401
ED401
ED401
ED401
ED401
ASSOCIATED CONDUIT, J-BOXES, ETC. NEW DUCT
DETECTOR WILL ONLY BE INSTALLED IN RETURN DUCT.
ED402
ENLARGED
DEMOLITION
FLOOR PLANS
- FIRE ALARM
CHECKED BY:
ECE PROJECT NO.
DRAWN BY:
SHEET NUMBER
DATE DESCRIPTION
REVISIONS:
NO. DATE DESCRIPTION
ISSUED:
NO.
LD AM
B E
N N
IO
N
J U
N
IO
R H
IG
H
S C
H O
O L
F
IR
E A
L A
R M
U P
G R
A D
E
S
O U
T H
W E
S T
W E
S T
J O
R D
A N
U
T A
H
ELECTRICAL CONSULTING ENGINEERS
323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5762
SCALE: 1/2" = 1'-0"
ED402
B.CO
FIRST FLOOR
COMP LAB
COMP LAB
UT. STUDY
READ
ISS
CONF
ROOM
S T
O R
A G
E
PRINCIPAL
CONF
ROOM
OFFICE
FAC ROOM
COUN
COUN
COUN
SEC
ASST
PRIN
OFFICEGIRLS
LOCKER
RM
GYMNASIUM
BOYS
LOCKER
RM
OFFICE
PE
STORAGE
RM
GIRLS PE
STORAGE
RM
SEWING
HEALTH
FOOD
STORAGE
STORAGE
SHOP
STE
DRAMA
CAFETERIA
CHORUS
GEOGRAPHY
HISTORY
RESOURCE
STORAGE
RESOURCE
RESOURCE
9 ENG 109
8 ENG 110
9TH ENG
8TH ENG
MATH
AUDITORIUM
STAGE
BAND/ORCHESTRA
ART
ART
WEIGHT TRAINING
RESOURCE
STE COM
LAB 127
STORAGE
ZONE 1
ZONE 1
ZONE 2
ZONE 3
ZONE 2
ZONE 2
ZONE 4
F.A.C.P.
MEN
WOMEN
BOILER
ROOM
LIBRARY
WOMEN
MEN
EY401
WP
WP
WP
WP
WP
WP
B
H
NEW
TRANSPONDER
B
1. FURNISH AND INSTALL NEW FIRE ALARM DEVICES IN THE
APPROXIMATE LOCATION SHOWN. TIE THE NEW DEVICES TO
FIRE ALARM CONTROL PANEL IN CLASS "A" LOOP. IN AND
OUT CABLES MUST BE PLENUM. DO NOT SPLICE CABLES
BETWEEN DEVICES. COORDINATE THIS WORK WITH FIRE
ALARM MANUFACTURER REPRESENTATIVE.
2. TIE EXISTING MAGNETIC DOOR HOLDERS TO NEW FIRE
ALARM CONTROL PANEL. PROVIDE CONTROL MODULE,
CONDUCTORS, ETC. FOR A COMPLETE INSTALLATION.
3. PROVIDE NEW MONITOR MODULE FOR EXISTING TAMPER
AND FLOW SWITCHES. TIE TO FIRE ALARM CONTROL PANEL
IN CLASS "A" LOOP.
4. FURNISH AND INSTALL NEW FIRE ALARM TRANSPONDER IN
THE APPROXIMATE LOCATION SHOWN. TIE THE
TRANSPONDER TO A NEW RED 20A., 1-POLE CIRCUIT
BREAKER IN EMERGENCY ELECTRICAL PANEL. PROVIDE
CONDUIT, CONDUCTORS, ETC. FOR A COMPLETE
INSTALLATION. REFER TO FA RISER DIAGRAM FOR MORE
INFORMATION.
5. EXISTING EST FIRE ALARM CONTROL PANEL. TIE THE FIRE
ALARM CONTROL PANEL TO THE TRANSPONDER. PROVIDE
CONDUIT, CONDUCTORS, CIRCUIT BREAKER, ETC. FOR A
COMPLETE INSTALLATION. REFER TO FIRE ALARM RISER
DIAGRAM FOR MORE INFORMATION.
6. TIE FIRE ALARM CONTROL PANEL / TRANSPONDER TO A NEW
20 AMP., 1 POLE RED CIRCUIT BREAKER IN EXISTING
EMERGENCY PANEL IN THE BOILER ROOM. PROVIDE
CONDUIT AND CONDUCTORS FOR A COMPLETE
INSTALLATION.
7. FURNISH AND INSTALL A BLUE STROBE LIGHT FOR CO
NOTIFICATION ON THE CEILING IN THE APPROXIMATE
LOCATION SHOWN. TIE TO FIRE ALARM CONTROL PANEL IN
CLASS "A" LOOP FOR A COMPLETE INSTALLATION.
8. PROVIDE WIREGUARD PROTECTION OVER DEVICES.
9. PROVIDE THREE CONTROL MODULES FOR ELEVATOR
RECALL. COORDINATE WITH ELEVATOR MANUFACTURER FOR
TERMINATION POINTS. TIE TO F.A.C.P. FOR A COMPLETE
INSTALLATION.
10. FURNISH AND INSTALL A BLUE STROBE LIGHT FOR NEW "CO"
DETECTORS IN THE APPROXIMATE LOCATION SHOWN. BLUE
LIGHT TO COME ON WHEN ONE OF THE CO DETECTORS IS ON
ALARM. TIE TO THE NEW FIRE ALARM CONTROL PANEL IN
CLASS "A" LOOP FOR A COMPLETE INSTALLATION.
11. FURNISH AND INSTALL NEW CONTROL MODULE IN THE
APPROXIMATE LOCATION SHOWN FOR THE CO BLUE LIGHT
STROBE. TIE TO FIRE ALARM CONTROL PANEL IN A CLASS "A"
LOOP.
FURNISH AND INSTALL NEW FIRE ALARM DEVICES IN
THE APPROXIMATE LOCATION SHOWN. TIE THE NEW
DEVICES TO FIRE ALARM CONTROL PANEL IN CLASS
"A" LOOP. IN AND OUT CABLES MUST BE PLENUM. DO
NOT SPLICE CABLES BETWEEN DEVICES.
COORDINATE THIS WORK WITH FIRE ALARM
MANUFACTURER REPRESENTATIVE.
TIE AIR FANS TO NEW F.A.C.P. FOR AUTOMATIC SHUT
DOWN. PROVIDE ALL REQUIRED PROGRAMMING FOR
PROPER FAN SHUT DOWN DURING ALARM.
CO DETECTORS ARE TO SHUT DOWN PROPER AIR
FANS DURING ALARM. PROVIDE ALL REQUIRED
PROGRAMING FOR PROPER FAN SHUT DOWN DURING
ALARM.
IF THE FIRE ALARM SYSTEM IS TO BE OFF AFTER
HOURS A FIRE WATCH WILL BE REQUIRED.
1.
2.
3.
4.
SCALE: 1/16" = 1'-0"
EY101
FIRST FLOOR
PLAN - FIRE
ALARM
CHECKED BY:
ECE PROJECT NO.
DRAWN BY:
SHEET NUMBER
DATE DESCRIPTION
REVISIONS:
NO. DATE DESCRIPTION
ISSUED:
NO.
LD AM
B E
N N
IO
N
J U
N
IO
R H
IG
H
S C
H O
O L
F
IR
E A
L A
R M
U P
G R
A D
E
S
O U
T H
W E
S T
W E
S T
J O
R D
A N
U
T A
H
ELECTRICAL CONSULTING ENGINEERS
323 East 500 South SLC, UT 84111 Phone : 801.521.8007
SCIENCE
SCIENCE
SCIENCE
205SKILL 4 SUC
MATH
MATH
MATH/HISTORY
MATH
MATH 7
CHINESE
7 READ
WOMEN
MEN
COM LAB
SCIENCE
SCIENCE
202TP
COMPUTER LAB -
LIBRARY LOFT
BUSINESS
WOMEN
MEN
COM LAB
COM LAB
GEOGRAPHY
MECH.
MECHANICAL
OPEN TO BELOW
OPEN TO BELOW
OPEN TO BELOW
EY401
EY401
EY401
EY402
EY401
H
1. FURNISH AND INSTALL NEW FIRE ALARM DEVICES IN THE
APPROXIMATE LOCATION SHOWN. TIE THE NEW DEVICES TO
FIRE ALARM CONTROL PANEL IN CLASS "A" LOOP. IN AND
OUT CABLES MUST BE PLENUM. DO NOT SPLICE CABLES
BETWEEN DEVICES. COORDINATE THIS WORD WITH FIRE
ALARM MANUFACTURE REPRESENTATIVE.
SCALE: 1/16" = 1'-0"
EY102
SECOND
FLOOR PLAN -
FIRE ALARM
CHECKED BY:
ECE PROJECT NO.
DRAWN BY:
SHEET NUMBER
DATE DESCRIPTION
REVISIONS:
NO. DATE DESCRIPTION
ISSUED:
NO.
LD AM
B E
N N
IO
N
J U
N
IO
R H
IG
H
S C
H O
O L
F
IR
E A
L A
R M
U P
G R
A D
E
S
O U
T H
W E
S T
W E
S T
J O
R D
A N
U
T A
H
ELECTRICAL CONSULTING ENGINEERS
323 East 500 South SLC, UT 84111 Phone : 801.521.8007
CAFETERIA
SCIENCE
COMPUTER LAB -
LIBRARY LOFT
COM LAB
SCIENCE
TP
AUDITORIUM
1. FURNISH AND INSTALL NEW V.E.S.D.A. LASER PLUS 4 PORT AIR
SAMPLING DEVICE IN THE APPROXIMATE LOCATION SHOWN.
TIE THE ALARM OUTPUTS (PRE-ALERT, ALERT, ALARM AND
TROUBLE) TO THE FIRE ALARM PANEL. TIE THE VESDA UNIT TO
A NEW RED 20A, 120V. CIRCUIT BREAKER IN THE NEAREST
PANEL WITH AVAILABLE SPACE. PROVIDE CONDUIT,
CONDUCTORS, CIRCUIT BREAKER, BATTERIES, ETC. FOR A
COMPLETE INSTALLATION.
2. FURNISH AND INSTALL NEW VESDA LASER PLUS AIR
SAMPLING TUBES IN THE APPROXIMATE LOCATIONS SHOWN.
REFER TO THE VESDA SAMPLING PORT DETAIL FOR MORE
INFORMATION. AIR SAMPLING ZONES SHALL COVER LESS
THAN 33 PORTS PER DETECTION UNIT. AIR SAMPLING SYSTEM
MUST BE ENGINEERED, INSTALLED AND CERTIFIED BY VESDA
SYSTEM PROVIDER. PROVIDE TEST PORT AT 4FT A.F.F. AT THE
END OF EACH PIPE RUN TO TEST TRANSPORT TIME . TEST
PORT SHALL BE A VENTED END-CAP. PROVIDE SIGN
INDICATING "TEST PORT". TRANSPORT TIME SHALL BE LESS
THAN 60 SECONDS FOR EQUIPMENT SPACE.
SCALE: 1/8" = 1'-0"
1. DETECTOR LOCATIONS ARE SHOWN TO INDICATE
APPROXIMATE DEVICES COVERAGE LIMITS. FIELD VERIFY
EXACT LOCATIONS TO INSURE THAT DETECTORS ARE
ACCESSIBLE FROM THE FLOOR AND THAT THEY ARE NOT
INSTALLED WITH 4'-0" OF AN AIR DISCHARGE LOUVER.
EY103
CAFETERIA -
VESDA
CHECKED BY:
ECE PROJECT NO.
DRAWN BY:
SHEET NUMBER
DATE DESCRIPTION
REVISIONS:
NO. DATE DESCRIPTION
ISSUED:
NO.
LD AM
B E
N N
IO
N
J U
N
IO
R H
IG
H
S C
H O
O L
F
IR
E A
L A
R M
U P
G R
A D
E
S
O U
T H
W E
S T
W E
S T
J O
R D
A N
U
T A
H
ELECTRICAL CONSULTING ENGINEERS
323 East 500 South SLC, UT 84111 Phone : 801.521.8007
1. TIE EXISTING FAN UNIT TO FIRE ALARM CONTROL PANEL FOR
AUTOMATIC SHUTDOWN. PROVIDE CONDUIT, CONDUCTORS,
RELAYS, ETC. FOR A COMPLETE INSTALLATION.
2. FURNISH AND INSTALL A DUCT DETECTOR IN RETURN AIR
DUCT WITH SAMPLING TUBE FOR EXISTING FAN UNIT. TIE
THE DUCT DETECTOR IN CLASS "A" LOOP TO FIRE ALARM
CONTROL PANEL. PROVIDE CONDUIT AND CONDUCTORS
FOR A COMPLETE INSTALLATION.
3. PROVIDE NEW MONITOR MODULE FOR EXISTING TAMPER
AND FLOW SWITCHES. TIE TO FIRE ALARM CONTROL PANEL
IN CLASS "A" LOOP.
4. FURNISH AND INSTALL NEW FIRE ALARM DEVICES IN THE
APPROXIMATE LOCATION SHOWN. TIE THE NEW DEVICES TO
FIRE ALARM CONTROL PANEL IN CLASS "A" LOOP. IN AND
OUT CABLES MUST BE PLENUM. DO NOT SPLICE CABLES
BETWEEN DEVICES. COORDINATE THIS WORD WITH FIRE
ALARM MANUFACTURE REPRESENTATIVE.
5. TIE VESDA CONTROL PANEL TO A NEW 20 AMP, 1 POLE RED
CIRCUIT BREAKER IN NEAREST ELECTRICAL PANEL. PROVIDE
CONDUIT AND CONDUCTORS FOR A COMPLETE
INSTALLATION. TIE VESA CONTROL PANEL TO EXISTING FIRE
ALARM CONTROL PANEL.
6. FURNISH AND INSTALL NEW TRANSPONDERS IN THE
APPROXIMATE LOCATION SHOWN. FIELD VERIFY EXACT
LOCATION WITH GSD. TIE THE TRANSPONDER TO FIRE ALARM
CONTROL PANEL FOR A COMPLETE INSTALLATION.
7. TIE THE TRANSPONDER TO A 20 AMP, 1 POLE RED CIRCUIT
BREAKER IN NEAREST PANEL. PROVIDE CONDUIT AND
CONDUCTORS FOR A COMPLETE INSTALLATION.
NEW
TRANSPONDER
NEW
TRANSPONDER
VESDA
CONTROL
PANEL
NEW
TRANSPONDER
SCALE: 1/2" = 1'-0"
EY401
ENLARGED
FLOOR PLANS
- FIRE ALARM
CHECKED BY:
ECE PROJECT NO.
DRAWN BY:
SHEET NUMBER
DATE DESCRIPTION
REVISIONS:
NO. DATE DESCRIPTION
ISSUED:
NO.
LD AM
B E
N N
IO
N
J U
N
IO
R H
IG
H
S C
H O
O L
F
IR
E A
L A
R M
U P
G R
A D
E
S
O U
T H
W E
S T
W E
S T
J O
R D
A N
U
T A
H
ELECTRICAL CONSULTING ENGINEERS
323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 5762
SCALE: 1/2" = 1'-0"
SCALE: 1/2" = 1'-0"
SCALE: 1/2" = 1'-0"
ASSOCIATED CONDUIT, J-BOXES, ETC. NEW DUCT
DETECTOR WILL ONLY BE INSTALLED IN RETURN DUCT
2. FURNISH AND INSTALL NEW FIRE ALARM DEVICES IN
THE APPROXIMATE LOCATION SHOWN. TIE THE NEW
DEVICES TO FIRE ALARM CONTROL PANEL IN CLASS "A"
LOOP. IN AND OUT CABLES MUST BE PLENUM. DO NOT
SPLICE CABLES BETWEEN DEVICES. COORDINATE THIS
WORD WITH FIRE ALARM MANUFACTURE
REPRESENTATIVE.
EY402
ENLARGED
FLOOR PLANS
- FIRE ALARM
CHECKED BY:
ECE PROJECT NO.
DRAWN BY:
SHEET NUMBER
DATE DESCRIPTION
REVISIONS:
NO. DATE DESCRIPTION
ISSUED:
NO.
LD AM
B E
N N
IO
N
J U
N
IO
R H
IG
H
S C
H O
O L
F
IR
E A
L A
R M
U P
G R
A D
E
S
O U
T H
W E
S T
W E
S T
J O
R D
A N
U
T A
H
ELECTRICAL CONSULTING ENGINEERS
323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com
File details come from the government source that posted it. Updated .