7-JF26-025-IFB 6064 Jim Bridger Fire Alarm Upgrade ECE - Permit Set.pdf

PDF 3 MB Posted

Attached to
Construction: Fire Alarm Upgrade at Bridger Elementary
Solicitation number
JF26-025-IFB
Issued by
Salt Lake County, Utah

About this file

This is a permit set of electrical construction drawings for a fire alarm and carbon monoxide detection system upgrade at Jim Bridger Elementary School, prepared by Electrical Consulting Engineers (ECE) for the Granite School District (GSD) in West Jordan, Utah. The project involves the installation of a new fire alarm control panel with transponder, photoelectric and heat detectors, combination smoke/carbon monoxide detectors, manual pull stations, horns with strobes, ADA strobes, flow switches, tamper switches, and related wiring and conduit throughout the facility. The work includes removal of existing fire alarm equipment and devices, patching and painting of affected areas, replacement of damaged ceiling tiles, and removal of abandoned conduit and components. Specific installation locations are detailed across multiple floor plan sheets covering the main level, mezzanine areas, and boiler room, with devices to be integrated into a Class A loop configuration. The project also requires the installation of a duct detector in return air and programming for automatic fan shutdown during alarm conditions, along with provisions for a new 2'x2' access panel in existing ceilings and sealing of all penetrations on finished surfaces.

The specifications require shop drawings, a one-year warranty on all labor and material from the date of acceptance, and strict adherence to the National Electrical Code and UL-approved materials. Contractors must perform site inspections prior to bidding and include all charges related to existing conditions in their bids. The electrical work must utilize rigid steel conduit (minimum 3/4" diameter) with THHN copper conductors, proper conductor sizing based on run length, and specific installation details for sprinkler riser connections and ceiling-mounted devices. Special considerations include protocols for potential asbestos-containing materials on site, provisions for fire alarm system operation during installation of the new system, and deferred submittals for battery calculations, voltage drop calculations, and alarm control equipment details to be provided by the fire alarm manufacturer. The pre-bid meeting attendance is required, with board approval anticipated at the June 2, 2026 meeting and final award to be issued following that approval.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CHECKED BY:

ECE PROJECT NO.

DRAWN BY:

SHEET NUMBER

DATE DESCRIPTION

REVISIONS:

NO. DATE DESCRIPTION

ISSUED:

NO.

GCY AM

ELECTRICAL CONSULTING ENGINEERS

323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 6064

J

IM

B R

ID

G

E R

E L E

M E

N T

A R

Y S

C H

O O

L

F

IR

E A

L A

R M

A N

D C

A R

B O

N M

O N

O X

ID

E

U P

G R

A D

E

C

Y C

L A

M E

N W

A Y

W E

S T

J O

R D

A N

U

T

E000

COVER SHEET

GRANITE SCHOOL DISTRICT

ELECTRICAL CONSULTING ENGINEERS

323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 6064

JIM BRIDGER ELEMENTARY SCHOOL

FIRE ALARM AND CARBON MONOXIDE UPGRADE

5368 CYCLAMEN WAY

WEST JORDAN, UT 84081

E001

GENERAL NOTES,

SYMBOL LIST AND

DETAILS

FIRE ALARM SYSTEMS SYMBOL LIST

SYMBOL DESCRIPTION

ELECTRICAL PANEL LOCATION, PART #: FACU: E3-BB-BB, NAC: SBB-D4, REMOTE

ANNUNCIATOR: E3-BB-BAA

FIRE ALARM SYSTEM PHOTOELECTRIC SMOKE DETECTOR, PART #: ASD-PL3

FIRE ALARM HEAT DETECTOR, PART #: ATD-L3R

FIRE ALARM COMBINATION SMOKE/CARBON MONOXIDE DETECTOR, PART #:

CO1224TR

FIRE ALARM MANUAL PULL STATION, +42" A.F.F., PART #: MS-7AF

FIRE ALARM HORN WITH STROBE, HIGH DECIBEL, +96" A.F.F., PART #: WALL: P2WL,

CEILING: PC2WL, WEATHER PROOF: P2RK

A.D.A. STROBE FOR FIRE ALARM, +96" A.F.F., PART #: WALL: SWL, CEILING: SCWL

BLUE STROBE LIGHT

FIRE SPRINKLER FLOW SWITCH, PART #: AMM-4F

FIRE SPRINKLER TEMPER SWITCH, PART #: AMM-4F

FLOOR FLOOD SENSOR

BEAM DETECTOR TRANSMITTER - LETTER INDICATES PAIRING

BEAM DETECTOR RECEIVER - LETTER INDICATES PAIRING

BEAM CONTROLLER

RELAY MODULE, PART #: PR-3

KITCHEN HOOD MONITOR

CONTROL MODULE

CONTROL MODULE WITH RELAY

B

CM

R

FFS

TS

FS

F

ABBREVIATIONS SYMBOL LIST

SYMBOL DESCRIPTION

W.P. INDICATES WEATHER PROOF EQUIPMENT

A INDICATES DEVICE IS ABOVE COUNTER TOP

AMP. AMPERAGE

A.F.F. ABOVE FINISHED FLOOR

B.CO BLUE CARBON MONOXIDE STROBE

CLG. INDICATES CEILING MOUNTED DEVICE

EM INDICATES DEVICE IS ON EMERGENCY CIRCUIT

EX INDICATES DEVICE IS EXISTING

F.A.C.P. FIRE ALARM CONTROL PANEL

F.A.R.A.P. FIRE ALARM REMOTE ANNUNCIATOR PANEL

K.V.A. KILO VOLT AMPERAGE

K.W. KILOWATT

M.C.B. MAIN CIRCUIT BREAKER

M.L.O. MAIN LUG ONLY

O.T.R. ON THE ROOF

S INDICATES DEVICE IS SURFACE MOUNTED

T.V.S.S. TRANSIENT VOLTAGE SURGE SUPPRESSOR

TYP TYPICAL

U.P.S. UNINTERRUPTIBLE POWER SUPPLY

XFMR TRANSFORMER

CALLOUT SYMBOL LIST

SYMBOL DESCRIPTION

LIGHTING FIXTURE CALLOUT NUMBER INDICATES A SUGGESTED QUANTITY- TO BE

VERIFIED

MECHANICAL EQUIPMENT CALLOUT

DETAIL REFERENCE CALLOUT

REVISION NUMBER CALLOUT

EQUIPMENT CALLOUT

REFERENCE NOTE CALLOUT

GENERAL NOTES:

1. PRIOR TO SUBMITTING A BID THE ELECTRICAL CONTRACTOR SHALL INSPECT THE SITE AND

INCLUDE IN HIS BID PACKAGE ALL CHARGES DUE TO EXISTING CONDITIONS. SHOP

DRAWINGS ARE REQUIRED. ALL LABOR, MATERIAL AND WORKMANSHIP SHALL BE

GUARANTEED FOR A PERIOD OF 1 YEAR FROM THE DATE OF ACCEPTANCE BY THE TENANT.

REPLACE OR REPAIR ALL DEFECTS DURING THE GUARANTEED PERIOD.

2. MINIMUM SIZE OF CONDUIT TO BE 3/4". ALUMINUM CONDUITS SHALL NOT BE USED.

3. USE RIGID STEEL SET SCREW TYPE FITTINGS ONLY FOR INTERIOR WORK. DIE CAST

FITTINGS SHALL NOT BE USED.

4. RUN A NEUTRAL CONDUCTOR FOR EACH PHASE CONDUCTOR (EACH CIRCUIT) IN A

CONDUIT. NOT MORE THAN THREE (3) CIRCUITS IN A CONDUIT. THREE (3) PHASE

CONDUCTORS, THREE (3) NEUTRAL CONDUCTORS (ONE FOR EACH PHASE) AND ONE (1)

GROUND CONDUCTOR FOR A TOTAL OF SEVEN (7) CONDUCTORS.

5. THE MINIMUM SIZE OF THE CONDUCTORS ARE TO BE #12 AWG THHN COPPER, UNLESS

INDICATED OTHERWISE ON THE DRAWINGS.

6. ALL J-BOXES SHALL HAVE MINIMUM DEPTH OF 2-3/8" UNLESS OTHERWISE SPECIFIED.

SECURE ALL J-BOXES AS SHOWN IN THE DETAILS. FURNISH AND INSTALL PROPER MUD

RINGS.

7. ALL ELECTRICAL WIRING MUST BE IN CONDUIT (MC CABLE IS PERMITTED).

8. USE NO. 10 THHN CONDUCTORS FOR CONDUCTOR LENGTH OVER 100 FEET, NO. 8 THHN

OVER 200 FEET, NO. 6 THHN OVER 300 FEET AND NO. 4 THHN OVER 400 FEET LENGTH.

9. ALL CONDUITS EXPOSED TO THE WEATHER SHALL BE GALVANIZED RIGID STEEL, UNLESS

OTHERWISE NOTED.

10. PROVIDE UPDATED, TYPED WRITTEN, PANEL SCHEDULES FOR NEW AND EXISTING

PANELBOARDS SHOWING CIRCUIT CHANGES MADE DURING THIS PROJECT.

11. ALL NEW WORK MUST MEET THE CURRENT ADOPTED NATIONAL ELECTRICAL CODE.

12. ALL MATERIALS USED IN THIS INSTALLATION SHALL BE U.L. APPROVED AND NEW.

THROUGH CONCRETE WALLS

MAY 09, 2013

F RATING - 2 HR

T RATING - 0 HR

L RATING AT AMBIENT - LESS THAN 1 CFM/SQ. FT.

L RATING AT 400 F - LESS THAN 1 CFM/SQ. FT.

SECTION A-A

WALL ASSEMBLY

A

A

SCALE: TYPICAL FIRESTOP FOR CABLES/CONDUIT

N.T.S.

ANCHOR TO WALL WITH

EPOXY ANCHORS AS

REQUIRED BY WEIGHT

SUPPORTED (TYPICAL)

TYPICAL WIRING FOR EACH SPRINKLER RISER (SEE FIRE SPRINKLER

DRAWINGS FOR QUANTITY AND LOCATIONS.)

MAIN

OS&Y VALVE

DETECTOR SWITCH FURNISHED AND

INSTALLED BY SPRINKLER

4 #14, 1/2''CONDUIT

ALARM VALVE

SEAL TIGHT

4 #14, 1/2''CONDUIT

WALL MOUNTED JUNCTION BOX

FLOW SWITCH FURNISHED AND INSTALLED BY

SPRINKLER CONTRACTOR, WIRED BY ELEC.

RISER

CONDUIT 8 #14 THW, 3/4''CONDUIT

TO FIRE ALARM MASTER TYPICAL

EACH SPRINKLER RISER.

CEILING

SCALE:

FIRE SPRINKLER CONNECTION DETAIL

N.T.S.

CONTRACTOR, WIRED BY ELEC.

1. EXISTING FIRE ALARM SYSTEM IS TO REMAIN IN OPERATION UNTIL THE NEW SYSTEM IS

INSTALLED, TESTED AND PUT IN OPERATION.

2. ALL CONDUIT AND BOXES IN THE BRICK WALLS CAN REMAIN. PROVIDE COVER PLATE

FOR THE BOXES TO MATCH COLOR OF THE BRICKS.

3. PATCH AND PAINT ALL WALLS WHERE DEVICES ARE REMOVED. PAINT COLOR IS TO

MATCH THE REST OF THE EXISTING WALL.

4. REPLACE ALL TILES DAMAGED DURING CONSTRUCTION AND TILES WHERE DEVICES ARE

REMOVED WITH MATCHING NEW ONES.

5. CONTRACTOR MUST REMOVE ALL ABANDONED CONDUIT, CONDUCTORS, J-BOXES, ETC.

IN ACCESSIBLE CEILINGS.

6. CLASS "A" LOOP MUST BE MAINTAINED TO ALL NEW FIRE ALARM DEVICES.

7. PLENUM CABLES ARE ALLOWED TO BE USED FOR NEW CABLES AS LONG AS THE

FOLLOWING ARE MET: THE RUN IS CONCEALED, USED IN CONJUNCTION WITH

NON-METALLIC BOXES, AND RACEWAYS ONLY. PROVIDE J-HOOKS EVERY 5 FEET TO

SUPPORT THE CABLES. DO NOT LAY THE CABLES ON TOP OF EXISTING CEILING OR

ANYWHERE THAT CAN BE DAMAGED. IF METALLIC BOXES AND CONDUIT ARE TO BE USED

UTILIZE MC CABLE FOR ALL THE WIRING.

8. THE CONTRACTOR IS ALLOWED TO USE 1/2" EMT CONDUIT ON SURFACES IN LIEU OF

WIREMOLD. PAINT CONDUIT ON EXPOSED SURFACES. COLOR TO MATCH COLOR OF

GROUT OF EXISTING BRICKS.

9. ALL EXISTING ABANDONED FIRE ALARM CONDUIT, CABLES, J-BOXES, ETC. MUST BE

REMOVED AT THE END OF THE PROJECT.

10. THE CONTRACTOR IS TO PROVIDE A UNIT COST FOR NEW 2'X2' ACCESS PANEL IN

EXISTING CEILING.

11. THE CONTRACTOR IS TO SEAL AND PAINT ALL PENETRATIONS ON FINISHED WALLS AND

CEILINGS. PAINT COLOR IS TO MATCH THE WALL OR CEILING ACCORDINGLY.

12. ASBESTOS CONTAINING MATERIALS (ACM) MAY BE PRESENT AT THE PROJECT SITE. GSD

WILL ABATE ACM OR PROVIDE CONTRACTOR WITH A PROTOCOL FOR USE WHEN

DRILLING, CUTTING, OR FASTENING TO ACM.

13. REFER TO SPECS FOR APPROVED MANUFACTURES. MANUFACTURER'S MODEL

NUMBERS AND LISTING INFORMATION FOR EQUIPMENT WILL BE PROVIDED BY THE

ELECTRICAL CONTRACTOR AND ALSO ON DEFERRED SUBMITTALS.

14. BATTERY CALCULATIONS WILL BE PROVIDED BY THE FIRE ALARM MANUFACTURE ON

DEFERRED SUBMITTALS.

15. VOLTAGE DROP CALCULATIONS WILL BE PROVIDED BY FIRE ALARM MANUFACTURER ON

DEFERRED SUBMITTALS.

16. ALARM CONTROL AND TROUBLE SIGNALING EQUIPMENT WILL BE IN THE FIRE ALARM

CONTROL PANEL. REFER TO DEFERRED SUBMITTALS.

17. INTERFACE OF FIRE SAFETY CONTROL FUNCTIONS WILL BE IN THE FIRE ALARM

CONTROL PANEL. REFER TO DEFERRED SUBMITTALS.

SPECIAL NOTES:

SCALE:

N.T.S.

1/2" FLEX x 6' (MAX)

MAINTAIN CLASS A WIRING

LAY-IN TILE CEILING

3/4" CONDUIT FOR FIRE

ALARM LOOP

4" SQUARE x 2-1/8" J-BOX

AT CEILING DECK

3/4" CONDUIT FOR

FIRE ALARM LOOP

CONNECTIONS FOR FIRE ALARM

DEVICES IN LAY-IN CEILINGS

SCALE: STANDARD HEIGHTS FOR

N.T.S.

M

A X

M

IN

IM

U

M

ELECTRICAL

OUTLETS

PULL

FIRE

CEILING

DECK

STROBE LIGHT

OR HORN &

STROBE

SMOKE, HEAT,

& FLAME

DETECTORS

LIGHT SWITCHES

FIRE ALARM PULL STATION

M

A X

PUSH BUTTONS

BEAM

STRUCTURAL

JOIST OR

DROPPED

CEILING

STANDARD HEIGHTS

FOR AREAS WITH

CEILING DECK OR

DROPPED CEILINGS

SURFACE MOUNT CONDUITS ON CEILING.

DO NOT PENDANT MOUNT CONDUITS

EXCEPT AT ROOF DECK MAINTAIN 1-1/2"

SEPARATION BETWEEN DECK &

HANDICAPPED ACCESS

CONDUITS.

(3) HP-FF8

CONDUITS

& ONE 3/4"

TWO 1"

5.2" DEEP

24" WIDE

45.9" HIGH

TRANSPONDER

SBB-D4

w/FCI-DR-D4B

DEDICATED CIRCUIT

120 VAC W/GROUND

1 CAT-6E TO PHONE BOARD

2 CAT-6E TO NETWORK PORTS

FACU

S3-BB-RB

4.5" DEEP

19.375" WIDE

19.375" HIGH

MINI

BATTERY

CABINET

4" DEEP

17" WIDE

8" HIGH

FLPS-7

SLC-PM

SLP-RB

DACT-E3

LCD-SLP

2 #14'S

TYPICAL 24 AUX POWER

1 PAIR #14'S TWISTED

TYPICAL ADDRESSABLE CIRCUIT

4 #14'S4 #14'S

TO FAN

SHUTDOWN

2 #14'S

TYPICAL NOTIFICATION CIRCUIT

2 #14'S

TYPICAL CO NOTIFICATION CIRCUIT

B B

WPB

E002

FIRE ALARM RISER

DIAGRAM

CHECKED BY:

ECE PROJECT NO.

DRAWN BY:

SHEET NUMBER

DATE DESCRIPTION

REVISIONS:

NO. DATE DESCRIPTION

ISSUED:

NO.

GCY AM

ELECTRICAL CONSULTING ENGINEERS

323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 6064

J

IM

B R

ID

G

E R

E L E

M E

N T

A R

Y S

C H

O O

L

F

IR

E A

L A

R M

A N

D C

A R

B O

N M

O N

O X

ID

E

U P

G R

A D

E

C

Y C

L A

M E

N W

A Y

W E

S T

J O

R D

A N

U

T

X

REMOVE EXISTING FIRE ALARM CONTROL

PANEL AND TRANSPONDER ASSOCIATED

POWER SUPPLY, CONDUIT , CONDUCTORS,

BOXES, ETC. AFTER NEW FIRE ALARM SYSTEM

IS INSTALLED AND PUT INTO OPERATION.

PROVIDE A BLANK COVER PLATE FOR BOX AND

PAINT TO MATCH COLOR OF THE WALL.

REMOVE EXISTING FIRE ALARM DEVICES,

ASSOCIATED CONDUIT AND CONDUCTORS.

PROVIDE A BLANK COVER PLATE FOR J-BOXES

IN THE BRICK WALLS. COVER PLATES TO

MATCH COLOR OF THE BRICK.

REMOVE EXISTING DUCT DETECTOR AND

SAMPLING TUBE IN RETURN AND SUPPLY

DUCTS. REMOVE ASSOCIATED CONDUIT,

J-BOXES, ETC.

D1

D2

D3

AHM001

AHM002AHM004AHM009

LADDER

LADDER

AHM006

ANTIFREEZE

FIRE

RISER

UTILIZE EXISTING HEAT AND SMOKE

DETECTORS DEVICES BOXES FOR NEW

DETECTION DEVICES WHERE POSSIBLE. FIELD

VERIFY WORK INVOLVED PRIOR TO BID.

REMOVE THE EXISTING HORN/STROBE FROM

THE WALLS WITH ASSOCIATED CONDUIT,

CONDUCTORS, ETC. ALL THE WAY BACK TO

THEIR ORIGINATION POINTS. PROVIDE BLANK

COVER PLATE FOR BOXES ON THE BLOCK

WALLS. COVER PLATES TO MATCH COLOR OF

THE WALL.

1.

2.

CHECKED BY:

ECE PROJECT NO.

DRAWN BY:

SHEET NUMBER

DATE DESCRIPTION

REVISIONS:

NO. DATE DESCRIPTION

ISSUED:

NO.

GCY AM

ELECTRICAL CONSULTING ENGINEERS

323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 6064

J

IM

B R

ID

G

E R

E L E

M E

N T

A R

Y S

C H

O O

L

F

IR

E A

L A

R M

A N

D C

A R

B O

N M

O N

O X

ID

E

U P

G R

A D

E

C

Y C

L A

M E

N W

A Y

W E

S T

J O

R D

A N

U

T

ED101

MAIN LEVEL

DEMO FLOOR

PLAN - FIRE

ALARM

SCALE: 1/16" = 1'-0"

MEZZANINE DEMO FLOOR PLAN - FIRE ALARM

SCALE: 1/8" = 1'-0"

MEZZANINE DEMO FLOOR PLAN - FIRE ALARM

SCALE: 1/8" = 1'-0"

MEZZANINE DEMO FLOOR PLAN - FIRE ALARM

SCALE: 1/8" = 1'-0"

BOILER ROOM DEMO FLOOR PLAN - FIRE ALARM

SCALE: 1/16" = 1'-0"

X

FURNISH AND INSTALL A NEW FIRE ALARM

CONTROL PANEL AND TRANSPONDER WHERE

THE EXISTING ONE IS LOCATED. TIE TO A 20

AMP., 1 POLE, RED CIRCUIT BREAKER IN THE

NEAREST PANEL. PROVIDE CONDUIT,

CONDUCTORS, ETC. FOR A COMPLETE

INSTALLATION.

FURNISH AND INSTALL NEW FIRE ALARM

DEVICE IN THE APPROXIMATE LOCATION

SHOWN. TIE THE NEW DEVICE TO THE FIRE

ALARM CONTROL PANEL IN CLASS "A" LOOP. IN

AND OUT CABLES MUST BE PLENUM RATED. DO

NOT SPLICE CABLES BETWEEN DEVICES.

COORDINATE THIS WORK WITH FIRE ALARM

MANUFACTURER REPRESENTATIVE.

FURNISH AND INSTALL NEW HORN/STROBE ON

THE EXISTING CEILING. TIE TO FIRE ALARM

CONTROL PANEL IN CLASS "A" LOOP. REPLACE

ANY TILE THAT IS DAMAGED IN CONSTRUCTION

WITH NEW AND IS TO MATCH THE EXISTING

CEILING.

FURNISH AND INSTALL NEW HORN/STROBE ON

THE EXISTING WALL. TIE TO FIRE ALARM

CONTROL PANEL IN CLASS "A" LOOP.

FURNISH AND INSTALL NEW STROBE ON THE

EXISTING CEILING TILE. TIE TO FIRE ALARM

CONTROL PANEL IN CLASS "A" LOOP. REPLACE

ANY TILE THAT IS DAMAGED IN CONSTRUCTION

WITH NEW AND IS TO MATCH THE EXISTING

CEILING.

FURNISH AND INSTALL FLOW AND TAMER

SWITCHES. TIE THEM TO THE NEW FIRE ALARM

CONTROL PANEL IN A CLASS "A" LOOP.

PROVIDE MONITOR AND RELAY MODULES FOR

COMPLETE INSTALLATION. VERIFY EXACT

LOCATION AND QUANTITY.

Y1

Y2

Y3

Y6

Y4

Y5

X

FURNISH AND INSTALL A NEW CARBON

MONOXIDE DETECTOR IN THE APPROXIMATE

LOCATION SHOWN. TIE THE NEW DEVICE TO

THE FIRE ALARM CONTROL PANEL IN CLASS "A"

LOOP. IN AND OUT CABLES MUST RUN IN

PLENUM. DO NOT SPLICE CABLES BETWEEN

DEVICES.

FURNISH AND INSTALL A BLUE STROBE LIGHT

FOR NEW "CO" DETECTORS IN THE

APPROXIMATE LOCATION SHOWN. BLUE LIGHT

TO COME WHEN ONE OF THE CO DETECTORS

IS ON ALARM. TIE TO THE NEW FIRE ALARM

CONTROL PANEL IN CLASS "A" LOOP FOR A

COMPLETE INSTALLATION.

PROVIDE WIREGUARD PROTECTION OVER

DEVICE.

FURNISH AND INSTALL NEW CONTROL MODULE

WITH RELAY AT THE APPROXIMATE LOCATION

SHOWN. TIE TO FIRE ALARM CONTROL PANEL

IN CLASS "A" LOOP.

FURNISH AND INSTALL A NEW CONTROL

MODULE IN THE APPROXIMATE LOCATION

SHOWN FOR THE CO BLUE LIGHT STROBE. TIE

TO FIRE ALARM CONTROL PANEL IN A CLASS

"A" LOOP.

FURNISH AND INSTALL NEW DUCT DETECTOR

IN THE RETURN AIR WITH SAMPLING TUBE. TIE

THE NEW DETECTOR TO NEW FIRE ALARM

CONTROL PANEL IN CLASS "A" LOOP.

FURNISH AND INSTALL TAMPER SWITCH FOR

ANTIFREEZE LOOP. TIE INTO THE FIRE ALARM

CONTROL PANEL IN A CLASS "A" LOOP.

Y7

Y8

Y9

Y10

Y11

Y12

Y13

B

B

TRANSPONDER

F.A.C.P

WP

WP

WP

WPWP

WP

AHM001

AHM002AHM004AHM009

LADDER

LADDER

AHM006

ANTIFREEZE

FIRE

RISER

MONITOR MODULE IS TO BE GAMEWELL-FCI

MODULE/PID-95, AND THE SIGNAL CONTROL

MODULE IS TO BE A MODEL SCE-95

TIE AIR FANS TO NEW F.A.C.P. FOR AUTOMATIC

SHUT DOWN. PROVIDE ALL REQUIRED

PROGRAMMING FOR PROPER FAN SHUT DOWN

DURING ALARM.

CO DETECTORS ARE TO SHUT DOWN PROPER

AIR FANS DURING ALARM. PROVIDE ALL

REQUIRED PROGRAMING FOR PROPER FAN

SHUT DOWN DURING ALARM.

IF THE FIRE ALARM SYSTEM IS TO BE OFF

AFTER HOURS A FIRE WATCH WILL BE

REQUIRED.

1.

2.

3.

4.

CHECKED BY:

ECE PROJECT NO.

DRAWN BY:

SHEET NUMBER

DATE DESCRIPTION

REVISIONS:

NO. DATE DESCRIPTION

ISSUED:

NO.

GCY AM

ELECTRICAL CONSULTING ENGINEERS

323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 6064

J

IM

B R

ID

G

E R

E L E

M E

N T

A R

Y S

C H

O O

L

F

IR

E A

L A

R M

A N

D C

A R

B O

N M

O N

O X

ID

E

U P

G R

A D

E

C

Y C

L A

M E

N W

A Y

W E

S T

J O

R D

A N

U

T

EY101

MAIN LEVEL

FLOOR PLAN -

FIRE ALARM

SCALE: 1/16" = 1'-0"

MEZZANINE FLOOR PLAN - FIRE ALARM

SCALE: 1/8" = 1'-0"

MEZZANINE FLOOR PLAN - FIRE ALARM

SCALE: 1/8" = 1'-0"

MEZZANINE FLOOR PLAN - FIRE ALARM

SCALE: 1/8" = 1'-0"

BOILER ROOM FLOOR PLAN - FIRE ALARM

SCALE: 1/16" = 1'-0"

File details come from the government source that posted it. Updated .