7-JF26-025-IFB 6064 Jim Bridger Fire Alarm Upgrade ECE - Permit Set.pdf
PDF 3 MB Posted
- Solicitation number
- JF26-025-IFB
- Issued by
- Salt Lake County, Utah
About this file
This is a permit set of electrical construction drawings for a fire alarm and carbon monoxide detection system upgrade at Jim Bridger Elementary School, prepared by Electrical Consulting Engineers (ECE) for the Granite School District (GSD) in West Jordan, Utah. The project involves the installation of a new fire alarm control panel with transponder, photoelectric and heat detectors, combination smoke/carbon monoxide detectors, manual pull stations, horns with strobes, ADA strobes, flow switches, tamper switches, and related wiring and conduit throughout the facility. The work includes removal of existing fire alarm equipment and devices, patching and painting of affected areas, replacement of damaged ceiling tiles, and removal of abandoned conduit and components. Specific installation locations are detailed across multiple floor plan sheets covering the main level, mezzanine areas, and boiler room, with devices to be integrated into a Class A loop configuration. The project also requires the installation of a duct detector in return air and programming for automatic fan shutdown during alarm conditions, along with provisions for a new 2'x2' access panel in existing ceilings and sealing of all penetrations on finished surfaces.
The specifications require shop drawings, a one-year warranty on all labor and material from the date of acceptance, and strict adherence to the National Electrical Code and UL-approved materials. Contractors must perform site inspections prior to bidding and include all charges related to existing conditions in their bids. The electrical work must utilize rigid steel conduit (minimum 3/4" diameter) with THHN copper conductors, proper conductor sizing based on run length, and specific installation details for sprinkler riser connections and ceiling-mounted devices. Special considerations include protocols for potential asbestos-containing materials on site, provisions for fire alarm system operation during installation of the new system, and deferred submittals for battery calculations, voltage drop calculations, and alarm control equipment details to be provided by the fire alarm manufacturer. The pre-bid meeting attendance is required, with board approval anticipated at the June 2, 2026 meeting and final award to be issued following that approval.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
CHECKED BY:
ECE PROJECT NO.
DRAWN BY:
SHEET NUMBER
DATE DESCRIPTION
REVISIONS:
NO. DATE DESCRIPTION
ISSUED:
NO.
GCY AM
ELECTRICAL CONSULTING ENGINEERS
323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 6064
J
IM
B R
ID
G
E R
E L E
M E
N T
A R
Y S
C H
O O
L
F
IR
E A
L A
R M
A N
D C
A R
B O
N M
O N
O X
ID
E
U P
G R
A D
E
C
Y C
L A
M E
N W
A Y
W E
S T
J O
R D
A N
U
T
E000
COVER SHEET
GRANITE SCHOOL DISTRICT
ELECTRICAL CONSULTING ENGINEERS
323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 6064
JIM BRIDGER ELEMENTARY SCHOOL
FIRE ALARM AND CARBON MONOXIDE UPGRADE
5368 CYCLAMEN WAY
WEST JORDAN, UT 84081
E001
GENERAL NOTES,
SYMBOL LIST AND
DETAILS
FIRE ALARM SYSTEMS SYMBOL LIST
SYMBOL DESCRIPTION
ELECTRICAL PANEL LOCATION, PART #: FACU: E3-BB-BB, NAC: SBB-D4, REMOTE
ANNUNCIATOR: E3-BB-BAA
FIRE ALARM SYSTEM PHOTOELECTRIC SMOKE DETECTOR, PART #: ASD-PL3
FIRE ALARM HEAT DETECTOR, PART #: ATD-L3R
FIRE ALARM COMBINATION SMOKE/CARBON MONOXIDE DETECTOR, PART #:
CO1224TR
FIRE ALARM MANUAL PULL STATION, +42" A.F.F., PART #: MS-7AF
FIRE ALARM HORN WITH STROBE, HIGH DECIBEL, +96" A.F.F., PART #: WALL: P2WL,
CEILING: PC2WL, WEATHER PROOF: P2RK
A.D.A. STROBE FOR FIRE ALARM, +96" A.F.F., PART #: WALL: SWL, CEILING: SCWL
BLUE STROBE LIGHT
FIRE SPRINKLER FLOW SWITCH, PART #: AMM-4F
FIRE SPRINKLER TEMPER SWITCH, PART #: AMM-4F
FLOOR FLOOD SENSOR
BEAM DETECTOR TRANSMITTER - LETTER INDICATES PAIRING
BEAM DETECTOR RECEIVER - LETTER INDICATES PAIRING
BEAM CONTROLLER
RELAY MODULE, PART #: PR-3
KITCHEN HOOD MONITOR
CONTROL MODULE
CONTROL MODULE WITH RELAY
B
CM
R
FFS
TS
FS
F
ABBREVIATIONS SYMBOL LIST
SYMBOL DESCRIPTION
W.P. INDICATES WEATHER PROOF EQUIPMENT
A INDICATES DEVICE IS ABOVE COUNTER TOP
AMP. AMPERAGE
A.F.F. ABOVE FINISHED FLOOR
B.CO BLUE CARBON MONOXIDE STROBE
CLG. INDICATES CEILING MOUNTED DEVICE
EM INDICATES DEVICE IS ON EMERGENCY CIRCUIT
EX INDICATES DEVICE IS EXISTING
F.A.C.P. FIRE ALARM CONTROL PANEL
F.A.R.A.P. FIRE ALARM REMOTE ANNUNCIATOR PANEL
K.V.A. KILO VOLT AMPERAGE
K.W. KILOWATT
M.C.B. MAIN CIRCUIT BREAKER
M.L.O. MAIN LUG ONLY
O.T.R. ON THE ROOF
S INDICATES DEVICE IS SURFACE MOUNTED
T.V.S.S. TRANSIENT VOLTAGE SURGE SUPPRESSOR
TYP TYPICAL
U.P.S. UNINTERRUPTIBLE POWER SUPPLY
XFMR TRANSFORMER
CALLOUT SYMBOL LIST
SYMBOL DESCRIPTION
LIGHTING FIXTURE CALLOUT NUMBER INDICATES A SUGGESTED QUANTITY- TO BE
VERIFIED
MECHANICAL EQUIPMENT CALLOUT
DETAIL REFERENCE CALLOUT
REVISION NUMBER CALLOUT
EQUIPMENT CALLOUT
REFERENCE NOTE CALLOUT
GENERAL NOTES:
1. PRIOR TO SUBMITTING A BID THE ELECTRICAL CONTRACTOR SHALL INSPECT THE SITE AND
INCLUDE IN HIS BID PACKAGE ALL CHARGES DUE TO EXISTING CONDITIONS. SHOP
DRAWINGS ARE REQUIRED. ALL LABOR, MATERIAL AND WORKMANSHIP SHALL BE
GUARANTEED FOR A PERIOD OF 1 YEAR FROM THE DATE OF ACCEPTANCE BY THE TENANT.
REPLACE OR REPAIR ALL DEFECTS DURING THE GUARANTEED PERIOD.
2. MINIMUM SIZE OF CONDUIT TO BE 3/4". ALUMINUM CONDUITS SHALL NOT BE USED.
3. USE RIGID STEEL SET SCREW TYPE FITTINGS ONLY FOR INTERIOR WORK. DIE CAST
FITTINGS SHALL NOT BE USED.
4. RUN A NEUTRAL CONDUCTOR FOR EACH PHASE CONDUCTOR (EACH CIRCUIT) IN A
CONDUIT. NOT MORE THAN THREE (3) CIRCUITS IN A CONDUIT. THREE (3) PHASE
CONDUCTORS, THREE (3) NEUTRAL CONDUCTORS (ONE FOR EACH PHASE) AND ONE (1)
GROUND CONDUCTOR FOR A TOTAL OF SEVEN (7) CONDUCTORS.
5. THE MINIMUM SIZE OF THE CONDUCTORS ARE TO BE #12 AWG THHN COPPER, UNLESS
INDICATED OTHERWISE ON THE DRAWINGS.
6. ALL J-BOXES SHALL HAVE MINIMUM DEPTH OF 2-3/8" UNLESS OTHERWISE SPECIFIED.
SECURE ALL J-BOXES AS SHOWN IN THE DETAILS. FURNISH AND INSTALL PROPER MUD
RINGS.
7. ALL ELECTRICAL WIRING MUST BE IN CONDUIT (MC CABLE IS PERMITTED).
8. USE NO. 10 THHN CONDUCTORS FOR CONDUCTOR LENGTH OVER 100 FEET, NO. 8 THHN
OVER 200 FEET, NO. 6 THHN OVER 300 FEET AND NO. 4 THHN OVER 400 FEET LENGTH.
9. ALL CONDUITS EXPOSED TO THE WEATHER SHALL BE GALVANIZED RIGID STEEL, UNLESS
OTHERWISE NOTED.
10. PROVIDE UPDATED, TYPED WRITTEN, PANEL SCHEDULES FOR NEW AND EXISTING
PANELBOARDS SHOWING CIRCUIT CHANGES MADE DURING THIS PROJECT.
11. ALL NEW WORK MUST MEET THE CURRENT ADOPTED NATIONAL ELECTRICAL CODE.
12. ALL MATERIALS USED IN THIS INSTALLATION SHALL BE U.L. APPROVED AND NEW.
THROUGH CONCRETE WALLS
MAY 09, 2013
F RATING - 2 HR
T RATING - 0 HR
L RATING AT AMBIENT - LESS THAN 1 CFM/SQ. FT.
L RATING AT 400 F - LESS THAN 1 CFM/SQ. FT.
SECTION A-A
WALL ASSEMBLY
A
A
SCALE: TYPICAL FIRESTOP FOR CABLES/CONDUIT
N.T.S.
ANCHOR TO WALL WITH
EPOXY ANCHORS AS
REQUIRED BY WEIGHT
SUPPORTED (TYPICAL)
TYPICAL WIRING FOR EACH SPRINKLER RISER (SEE FIRE SPRINKLER
DRAWINGS FOR QUANTITY AND LOCATIONS.)
MAIN
OS&Y VALVE
DETECTOR SWITCH FURNISHED AND
INSTALLED BY SPRINKLER
4 #14, 1/2''CONDUIT
ALARM VALVE
SEAL TIGHT
4 #14, 1/2''CONDUIT
WALL MOUNTED JUNCTION BOX
FLOW SWITCH FURNISHED AND INSTALLED BY
SPRINKLER CONTRACTOR, WIRED BY ELEC.
RISER
CONDUIT 8 #14 THW, 3/4''CONDUIT
TO FIRE ALARM MASTER TYPICAL
EACH SPRINKLER RISER.
CEILING
SCALE:
FIRE SPRINKLER CONNECTION DETAIL
N.T.S.
CONTRACTOR, WIRED BY ELEC.
1. EXISTING FIRE ALARM SYSTEM IS TO REMAIN IN OPERATION UNTIL THE NEW SYSTEM IS
INSTALLED, TESTED AND PUT IN OPERATION.
2. ALL CONDUIT AND BOXES IN THE BRICK WALLS CAN REMAIN. PROVIDE COVER PLATE
FOR THE BOXES TO MATCH COLOR OF THE BRICKS.
3. PATCH AND PAINT ALL WALLS WHERE DEVICES ARE REMOVED. PAINT COLOR IS TO
MATCH THE REST OF THE EXISTING WALL.
4. REPLACE ALL TILES DAMAGED DURING CONSTRUCTION AND TILES WHERE DEVICES ARE
REMOVED WITH MATCHING NEW ONES.
5. CONTRACTOR MUST REMOVE ALL ABANDONED CONDUIT, CONDUCTORS, J-BOXES, ETC.
IN ACCESSIBLE CEILINGS.
6. CLASS "A" LOOP MUST BE MAINTAINED TO ALL NEW FIRE ALARM DEVICES.
7. PLENUM CABLES ARE ALLOWED TO BE USED FOR NEW CABLES AS LONG AS THE
FOLLOWING ARE MET: THE RUN IS CONCEALED, USED IN CONJUNCTION WITH
NON-METALLIC BOXES, AND RACEWAYS ONLY. PROVIDE J-HOOKS EVERY 5 FEET TO
SUPPORT THE CABLES. DO NOT LAY THE CABLES ON TOP OF EXISTING CEILING OR
ANYWHERE THAT CAN BE DAMAGED. IF METALLIC BOXES AND CONDUIT ARE TO BE USED
UTILIZE MC CABLE FOR ALL THE WIRING.
8. THE CONTRACTOR IS ALLOWED TO USE 1/2" EMT CONDUIT ON SURFACES IN LIEU OF
WIREMOLD. PAINT CONDUIT ON EXPOSED SURFACES. COLOR TO MATCH COLOR OF
GROUT OF EXISTING BRICKS.
9. ALL EXISTING ABANDONED FIRE ALARM CONDUIT, CABLES, J-BOXES, ETC. MUST BE
REMOVED AT THE END OF THE PROJECT.
10. THE CONTRACTOR IS TO PROVIDE A UNIT COST FOR NEW 2'X2' ACCESS PANEL IN
EXISTING CEILING.
11. THE CONTRACTOR IS TO SEAL AND PAINT ALL PENETRATIONS ON FINISHED WALLS AND
CEILINGS. PAINT COLOR IS TO MATCH THE WALL OR CEILING ACCORDINGLY.
12. ASBESTOS CONTAINING MATERIALS (ACM) MAY BE PRESENT AT THE PROJECT SITE. GSD
WILL ABATE ACM OR PROVIDE CONTRACTOR WITH A PROTOCOL FOR USE WHEN
DRILLING, CUTTING, OR FASTENING TO ACM.
13. REFER TO SPECS FOR APPROVED MANUFACTURES. MANUFACTURER'S MODEL
NUMBERS AND LISTING INFORMATION FOR EQUIPMENT WILL BE PROVIDED BY THE
ELECTRICAL CONTRACTOR AND ALSO ON DEFERRED SUBMITTALS.
14. BATTERY CALCULATIONS WILL BE PROVIDED BY THE FIRE ALARM MANUFACTURE ON
DEFERRED SUBMITTALS.
15. VOLTAGE DROP CALCULATIONS WILL BE PROVIDED BY FIRE ALARM MANUFACTURER ON
DEFERRED SUBMITTALS.
16. ALARM CONTROL AND TROUBLE SIGNALING EQUIPMENT WILL BE IN THE FIRE ALARM
CONTROL PANEL. REFER TO DEFERRED SUBMITTALS.
17. INTERFACE OF FIRE SAFETY CONTROL FUNCTIONS WILL BE IN THE FIRE ALARM
CONTROL PANEL. REFER TO DEFERRED SUBMITTALS.
SPECIAL NOTES:
SCALE:
N.T.S.
1/2" FLEX x 6' (MAX)
MAINTAIN CLASS A WIRING
LAY-IN TILE CEILING
3/4" CONDUIT FOR FIRE
ALARM LOOP
4" SQUARE x 2-1/8" J-BOX
AT CEILING DECK
3/4" CONDUIT FOR
FIRE ALARM LOOP
CONNECTIONS FOR FIRE ALARM
DEVICES IN LAY-IN CEILINGS
SCALE: STANDARD HEIGHTS FOR
N.T.S.
M
A X
M
IN
IM
U
M
ELECTRICAL
OUTLETS
PULL
FIRE
CEILING
DECK
STROBE LIGHT
OR HORN &
STROBE
SMOKE, HEAT,
& FLAME
DETECTORS
LIGHT SWITCHES
FIRE ALARM PULL STATION
M
A X
PUSH BUTTONS
BEAM
STRUCTURAL
JOIST OR
DROPPED
CEILING
STANDARD HEIGHTS
FOR AREAS WITH
CEILING DECK OR
DROPPED CEILINGS
SURFACE MOUNT CONDUITS ON CEILING.
DO NOT PENDANT MOUNT CONDUITS
EXCEPT AT ROOF DECK MAINTAIN 1-1/2"
SEPARATION BETWEEN DECK &
HANDICAPPED ACCESS
CONDUITS.
(3) HP-FF8
CONDUITS
& ONE 3/4"
TWO 1"
5.2" DEEP
24" WIDE
45.9" HIGH
TRANSPONDER
SBB-D4
w/FCI-DR-D4B
DEDICATED CIRCUIT
120 VAC W/GROUND
1 CAT-6E TO PHONE BOARD
2 CAT-6E TO NETWORK PORTS
FACU
S3-BB-RB
4.5" DEEP
19.375" WIDE
19.375" HIGH
MINI
BATTERY
CABINET
4" DEEP
17" WIDE
8" HIGH
FLPS-7
SLC-PM
SLP-RB
DACT-E3
LCD-SLP
2 #14'S
TYPICAL 24 AUX POWER
1 PAIR #14'S TWISTED
TYPICAL ADDRESSABLE CIRCUIT
4 #14'S4 #14'S
TO FAN
SHUTDOWN
2 #14'S
TYPICAL NOTIFICATION CIRCUIT
2 #14'S
TYPICAL CO NOTIFICATION CIRCUIT
B B
WPB
E002
FIRE ALARM RISER
DIAGRAM
CHECKED BY:
ECE PROJECT NO.
DRAWN BY:
SHEET NUMBER
DATE DESCRIPTION
REVISIONS:
NO. DATE DESCRIPTION
ISSUED:
NO.
GCY AM
ELECTRICAL CONSULTING ENGINEERS
323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 6064
J
IM
B R
ID
G
E R
E L E
M E
N T
A R
Y S
C H
O O
L
F
IR
E A
L A
R M
A N
D C
A R
B O
N M
O N
O X
ID
E
U P
G R
A D
E
C
Y C
L A
M E
N W
A Y
W E
S T
J O
R D
A N
U
T
X
REMOVE EXISTING FIRE ALARM CONTROL
PANEL AND TRANSPONDER ASSOCIATED
POWER SUPPLY, CONDUIT , CONDUCTORS,
BOXES, ETC. AFTER NEW FIRE ALARM SYSTEM
IS INSTALLED AND PUT INTO OPERATION.
PROVIDE A BLANK COVER PLATE FOR BOX AND
PAINT TO MATCH COLOR OF THE WALL.
REMOVE EXISTING FIRE ALARM DEVICES,
ASSOCIATED CONDUIT AND CONDUCTORS.
PROVIDE A BLANK COVER PLATE FOR J-BOXES
IN THE BRICK WALLS. COVER PLATES TO
MATCH COLOR OF THE BRICK.
REMOVE EXISTING DUCT DETECTOR AND
SAMPLING TUBE IN RETURN AND SUPPLY
DUCTS. REMOVE ASSOCIATED CONDUIT,
J-BOXES, ETC.
D1
D2
D3
AHM001
AHM002AHM004AHM009
LADDER
LADDER
AHM006
ANTIFREEZE
FIRE
RISER
UTILIZE EXISTING HEAT AND SMOKE
DETECTORS DEVICES BOXES FOR NEW
DETECTION DEVICES WHERE POSSIBLE. FIELD
VERIFY WORK INVOLVED PRIOR TO BID.
REMOVE THE EXISTING HORN/STROBE FROM
THE WALLS WITH ASSOCIATED CONDUIT,
CONDUCTORS, ETC. ALL THE WAY BACK TO
THEIR ORIGINATION POINTS. PROVIDE BLANK
COVER PLATE FOR BOXES ON THE BLOCK
WALLS. COVER PLATES TO MATCH COLOR OF
THE WALL.
1.
2.
CHECKED BY:
ECE PROJECT NO.
DRAWN BY:
SHEET NUMBER
DATE DESCRIPTION
REVISIONS:
NO. DATE DESCRIPTION
ISSUED:
NO.
GCY AM
ELECTRICAL CONSULTING ENGINEERS
323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 6064
J
IM
B R
ID
G
E R
E L E
M E
N T
A R
Y S
C H
O O
L
F
IR
E A
L A
R M
A N
D C
A R
B O
N M
O N
O X
ID
E
U P
G R
A D
E
C
Y C
L A
M E
N W
A Y
W E
S T
J O
R D
A N
U
T
ED101
MAIN LEVEL
DEMO FLOOR
PLAN - FIRE
ALARM
SCALE: 1/16" = 1'-0"
MEZZANINE DEMO FLOOR PLAN - FIRE ALARM
SCALE: 1/8" = 1'-0"
MEZZANINE DEMO FLOOR PLAN - FIRE ALARM
SCALE: 1/8" = 1'-0"
MEZZANINE DEMO FLOOR PLAN - FIRE ALARM
SCALE: 1/8" = 1'-0"
BOILER ROOM DEMO FLOOR PLAN - FIRE ALARM
SCALE: 1/16" = 1'-0"
X
FURNISH AND INSTALL A NEW FIRE ALARM
CONTROL PANEL AND TRANSPONDER WHERE
THE EXISTING ONE IS LOCATED. TIE TO A 20
AMP., 1 POLE, RED CIRCUIT BREAKER IN THE
NEAREST PANEL. PROVIDE CONDUIT,
CONDUCTORS, ETC. FOR A COMPLETE
INSTALLATION.
FURNISH AND INSTALL NEW FIRE ALARM
DEVICE IN THE APPROXIMATE LOCATION
SHOWN. TIE THE NEW DEVICE TO THE FIRE
ALARM CONTROL PANEL IN CLASS "A" LOOP. IN
AND OUT CABLES MUST BE PLENUM RATED. DO
NOT SPLICE CABLES BETWEEN DEVICES.
COORDINATE THIS WORK WITH FIRE ALARM
MANUFACTURER REPRESENTATIVE.
FURNISH AND INSTALL NEW HORN/STROBE ON
THE EXISTING CEILING. TIE TO FIRE ALARM
CONTROL PANEL IN CLASS "A" LOOP. REPLACE
ANY TILE THAT IS DAMAGED IN CONSTRUCTION
WITH NEW AND IS TO MATCH THE EXISTING
CEILING.
FURNISH AND INSTALL NEW HORN/STROBE ON
THE EXISTING WALL. TIE TO FIRE ALARM
CONTROL PANEL IN CLASS "A" LOOP.
FURNISH AND INSTALL NEW STROBE ON THE
EXISTING CEILING TILE. TIE TO FIRE ALARM
CONTROL PANEL IN CLASS "A" LOOP. REPLACE
ANY TILE THAT IS DAMAGED IN CONSTRUCTION
WITH NEW AND IS TO MATCH THE EXISTING
CEILING.
FURNISH AND INSTALL FLOW AND TAMER
SWITCHES. TIE THEM TO THE NEW FIRE ALARM
CONTROL PANEL IN A CLASS "A" LOOP.
PROVIDE MONITOR AND RELAY MODULES FOR
COMPLETE INSTALLATION. VERIFY EXACT
LOCATION AND QUANTITY.
Y1
Y2
Y3
Y6
Y4
Y5
X
FURNISH AND INSTALL A NEW CARBON
MONOXIDE DETECTOR IN THE APPROXIMATE
LOCATION SHOWN. TIE THE NEW DEVICE TO
THE FIRE ALARM CONTROL PANEL IN CLASS "A"
LOOP. IN AND OUT CABLES MUST RUN IN
PLENUM. DO NOT SPLICE CABLES BETWEEN
DEVICES.
FURNISH AND INSTALL A BLUE STROBE LIGHT
FOR NEW "CO" DETECTORS IN THE
APPROXIMATE LOCATION SHOWN. BLUE LIGHT
TO COME WHEN ONE OF THE CO DETECTORS
IS ON ALARM. TIE TO THE NEW FIRE ALARM
CONTROL PANEL IN CLASS "A" LOOP FOR A
COMPLETE INSTALLATION.
PROVIDE WIREGUARD PROTECTION OVER
DEVICE.
FURNISH AND INSTALL NEW CONTROL MODULE
WITH RELAY AT THE APPROXIMATE LOCATION
SHOWN. TIE TO FIRE ALARM CONTROL PANEL
IN CLASS "A" LOOP.
FURNISH AND INSTALL A NEW CONTROL
MODULE IN THE APPROXIMATE LOCATION
SHOWN FOR THE CO BLUE LIGHT STROBE. TIE
TO FIRE ALARM CONTROL PANEL IN A CLASS
"A" LOOP.
FURNISH AND INSTALL NEW DUCT DETECTOR
IN THE RETURN AIR WITH SAMPLING TUBE. TIE
THE NEW DETECTOR TO NEW FIRE ALARM
CONTROL PANEL IN CLASS "A" LOOP.
FURNISH AND INSTALL TAMPER SWITCH FOR
ANTIFREEZE LOOP. TIE INTO THE FIRE ALARM
CONTROL PANEL IN A CLASS "A" LOOP.
Y7
Y8
Y9
Y10
Y11
Y12
Y13
B
B
TRANSPONDER
F.A.C.P
WP
WP
WP
WPWP
WP
AHM001
AHM002AHM004AHM009
LADDER
LADDER
AHM006
ANTIFREEZE
FIRE
RISER
MONITOR MODULE IS TO BE GAMEWELL-FCI
MODULE/PID-95, AND THE SIGNAL CONTROL
MODULE IS TO BE A MODEL SCE-95
TIE AIR FANS TO NEW F.A.C.P. FOR AUTOMATIC
SHUT DOWN. PROVIDE ALL REQUIRED
PROGRAMMING FOR PROPER FAN SHUT DOWN
DURING ALARM.
CO DETECTORS ARE TO SHUT DOWN PROPER
AIR FANS DURING ALARM. PROVIDE ALL
REQUIRED PROGRAMING FOR PROPER FAN
SHUT DOWN DURING ALARM.
IF THE FIRE ALARM SYSTEM IS TO BE OFF
AFTER HOURS A FIRE WATCH WILL BE
REQUIRED.
1.
2.
3.
4.
CHECKED BY:
ECE PROJECT NO.
DRAWN BY:
SHEET NUMBER
DATE DESCRIPTION
REVISIONS:
NO. DATE DESCRIPTION
ISSUED:
NO.
GCY AM
ELECTRICAL CONSULTING ENGINEERS
323 East 500 South SLC, UT 84111 Phone : 801.521.8007 Email : akbar@eceonline.com ECE Project # 6064
J
IM
B R
ID
G
E R
E L E
M E
N T
A R
Y S
C H
O O
L
F
IR
E A
L A
R M
A N
D C
A R
B O
N M
O N
O X
ID
E
U P
G R
A D
E
C
Y C
L A
M E
N W
A Y
W E
S T
J O
R D
A N
U
T
EY101
MAIN LEVEL
FLOOR PLAN -
FIRE ALARM
SCALE: 1/16" = 1'-0"
MEZZANINE FLOOR PLAN - FIRE ALARM
SCALE: 1/8" = 1'-0"
MEZZANINE FLOOR PLAN - FIRE ALARM
SCALE: 1/8" = 1'-0"
MEZZANINE FLOOR PLAN - FIRE ALARM
SCALE: 1/8" = 1'-0"
BOILER ROOM FLOOR PLAN - FIRE ALARM
SCALE: 1/16" = 1'-0"