7-3202600039 Attachment 7 Project Drawings.pdf

PDF 4 MB Posted

Attached to
RFP 3202600039 CCRC Backup Generator
Solicitation number
3202600039
Issued by
Travis County, Austin City, Texas

About this file

This is a project drawings attachment for a backup generator installation project at the Texas Workforce Commission's Criss Cole Rehabilitation Center located at 4800 North Lamar Boulevard in Austin, Texas. The drawings package includes plumbing and electrical specifications and details for the installation of a 400 kilowatt natural gas-powered generator with associated infrastructure. The project involves new natural gas piping from an existing meter to the generator equipment, installation of a pressure regulator system located a minimum of 3 feet from all electrical equipment within the mechanical yard, and complete electrical interconnection including underground and overhead conduit routing from the generator pad to the main electrical room. The natural gas piping specifications include Schedule 40 metallic pipe with maximum developed lengths of 59 linear feet for 5 PSI pressure systems and 100 linear feet for low-pressure systems below 2 PSI, with support requirements every 5 feet using hot-dipped galvanized or stainless steel fasteners. Electrical work includes installation of a new automatic transfer switch (ATS) rated at 1400 amperes, proper grounding and bonding systems compliant with NEC standards, conduit systems with compression connections, and comprehensive labeling and identification of all circuits and equipment.

The project documentation specifies that the contractor must coordinate with Austin Energy for a scheduled utility outage prior to demolition and new work, with key contact Elizabeth Kasprowicz at the Austin Energy Key Account Manager office. The electrical design is based on peak demand load analysis showing 344 kilowatt-hours with an additional 25 percent buffer for new loads, totaling 430 kilovolt-amperes and 1,194 amperes at 208 volts three-phase. The generator specifications include Cummins equipment with weather-protective, sound-attenuated Level 2 enclosure rated at 75 decibels at 23 feet, vertical discharge configuration, natural gas fuel type, and full accessory packages including fuel filters, lube oil filters, air intake filters, coolers, transfer pumps, and priming pumps. All materials and installation must comply with applicable plumbing and electrical codes including the 2023 National Electrical Code, NFPA standards, ASME standards, and local authority having jurisdiction requirements. The contractor is responsible for testing and commissioning all systems, providing temporary construction power and lighting, maintaining functionality of existing building systems, and conducting short circuit coordination studies and arc flash hazard analysis with calculated labels per NFPA 70E.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

PLUMBING ABBREVIATIONS

DESCRIPTION AAB DESCRIPTION AAB

ABOVE CEILING A/C LAVATORY LAV

ABOVE FINISHED FLOOR AFF MAN HOLE MH

ABOVE GRADE. GROUND AG MAXIMUM MAX

ACCESS PANEL AP MECHANICAL MECH

ACRYLONITRILE BUTADIENE STYTENE ABS MINIMUM MIN

AIR ADMITTANCE VALVE AAV MIXING VALVE MV

ARCHITECT ARCH MOP SINK MS

AUTHORITY HAVING JURISDICTION AHJ NORMALLY CLOSED NC

BACKFLOW PREVENTER BFP NORMALLY OPEN NO

BELOW FINISHED FLOOR BFF NOT IN CONTRACT NIC

BELOW FLOOR B/F NOT TO SCALE NTS

BELOW GRADE/ GROUND BG EXISTING TO BE PROTECTED IN PLACE (P)

BELOW SLAB B/S POLYETHYLENE PE

BOTTOM OF PIPE BOP POLYETHYLENE CROSS-LINKED PEX

BRAKE HORSEPOWER BHP POLYVINYL CHLORIDE PVC

BRITISH THERMAL UNIT BTUH POLYVYLIDENE FLOURIDE/ DIOFLOURIDE PVDF

BTUH ( THOUSANDS ) MBH POUND LB

CAST IRON CI POUNDS PER SQUARE INCH PSI

CELCIUS C POUNDS PER SQUARE INCH ABSOLUTE PSIA

CHILLED WATER RETURN CHWR POUNDS PER SQUARE INCH GAUGE PSIG

CHILLED WATER SUPPLY CHWS PRESSURE DROP PD

CHLORINATED POLYVINYL CHLORIDE CPVC PRESSURE REDUCING VALVE PRV

CLEANOUT CO PUMP, BOOSTER BP

CLEANOUT, FLOOR FCO PUMP, CHILLED WATER CHWP

CLEANOUT, GRADE GCO PUMP, CIRCULATION CP

CLEANOUT, GRADE TWO-WAY DGCO PUMP, HOT WATER HWP

CLEANOUT, WALL WCO REDUCED PRESSURE ZONE RPZ

CLEANOUT, YARD YCO EXISTING TO BE RELOCATED (R)

CLEANOUT, YARD TWO-WAY DYCO REVOLUTION PER MINUTE RPM

CONDENSER RETURN CWR SCHEDULE SCH

CONDENSER SUPPLY CWS SHOWER SH

COPPER CU SINK SK

CUBIC FEET CF SQUARE FEET SF

CUBIC FEET PER HOUR CFH STRUCTURAL STRUC

CUBIC FEET PER MINUTE CFM TEMPERATURE TEMP

EXISTING TO BE DEMOLISHED/ REMOVED (D) TEMPERATURE, ENTERING WATER EWT

DEGREE D TEMPERATURE, LEAVING WATER LWT

DIAMETER DIA THERMOSTATIC MIXING VALVE TMV

DRAIN, AREA AD TOP OF PIPE TOP

DRAIN, FLOOR FD TRAP PRIMER TP

DRAIN, ROOF PRIMARY RD TYPICAL TYP

DRAIN, ROOF SECONDARY SRD ULTRAVIOLET UV

ELECTRICAL ELEC UNDERGROUND UG

ELEVATION ELEV UNIT, AIR HANDLING AHU

EXISTING EXIST, (E) UNIT, FAN COIL FC

FAHRENHEIT F UNLESS NOTED OTHERWISE UNO

FAT, OIL, AND GAS FOG UP/ DOWN UP/DN

FOOT/ FEET FT VACUUM BREAKER VB

FEET PER MINUTE FPM VALVE FLOW COEFFICIENT CV

FEET PER SECOND FPS VENT THRU ROOF VTR

FIXTURE UNIT FU WATER GAUGE WG

FLEXIBLE FLEX WATER CLOSET WC

FLOOR FLR WATER HAMMER ARRESTOR WHA

FLOOR SINK FS WATER, OIL, AND GAS WOG

FUTURE (F)

GALLON GAL ELECTRICAL

GALLONS PER HOUR GPH VOLTAGE V, VOLT

GALLONS PER MINUTE GPM WATTAGE W, WATT

HEAD IN FEET FTHD KILOWATT KW

HEAD IN INCHES WATER COLUMN INWC PHASE PH

HEATING HOT WATER RETURN HWR AMPERE A, AMP

HEATING HOT WATER SUPPLY HWS

HEATING, VENTILATION, AIR CONDITIONING HVAC

HORSEPOWER HP

HOUR HR

HUB DRAIN HD

INCHES PER HOUR IN/HR

INDIRECT DRAIN/ RECEPTOR ID

INDIRECT WASTE IW

INVERT ELEVATION IE

WATER SYSTEMS

SYSTEM TYPE ABBV LINE TYPE

NATURAL GAS SYSTEMS

LOW PRESSURE GAS (LESS THAN 2 PSI)

MEDIUM PRESSURE GAS ( 2PSI - 5 PSI)

HIGH PRESSURE GAS (GREATER THAN 5 PSI)

LIQUID GAS

SYSTEM TYPE ABBV LINE TYPE

HPG

MPG

G

LG

PLUMBING PIPE TYPES

UNION, SCREWED

VCR FITTING WITH CAP

TEE, OUTLET DOWN

REDUCER, ECCENTRIC

FLANGE JOINT

REDUCER, CONCENTRIC

ELBOW, TURN-UP

ELBOW, TURN-DOWN

INDICATES TIE-IN BETW. EXIST. AND NEW

PIPE CAP

BLIND FLANGE

CAPPED TEE

PIPE FITTINGS

UNION, FLANGED

BALL JOINT

PLUGGED PIPE

COUPLING (JOINT)

CROSSING

TEE

TEE, OUTLET UP

P-TRAP

HIGHER PIPE

LOWER PIPE

BFP

BALL

DIAPHRAGM

GAS COCK

GATE

BALANCING

GLOBE

PLUG

PRESSURE REDUCING

PRESSURE RELIEF

QUICK OPENING

CHECK

SPRING CHECK

SWING CHECK

BALL CHECK

GAUGE COCK

PRESSURE-TEMPERATURE RELIEF

ALARM CHECK

BACK FLOW PREVENTER,

DOUBLE CHECK TYPE

PLUMBING VALVES

S

THERMOMETER WELL ONLY

THRUST BLOCK

TEST PLUG

STRAINER, WYE

STRAINER W/ BLOW DOWN

PITCH OF PIPE, RISE (R) OR DROP (D)

PRESSURE GAUGE AND COCK

PRESSURE SWITCH

METER

FLOW METER, VENTURI

FLOW SWITCH

FLOW METER, INSERTION

FLEX CONNECTION

FLOWMETER, ORIFICE

EXPANSION LOOP

FILTER

EXPANSION JOINT

AIR VENT, AUTOMATIC W/SERVICE VALVE

ANCHOR

AIR VENT, AUTOMATIC W/SERVICE VALVE

ALIGNMENT GUIDE (PIPE SLEEVE)

AIR VENT, MANUAL

PIPING SPECIALITIES

PURGE PORT

F

FM

F

M

P

TB

TOP TO BOTTOM

1"-CW

1"-HW

1"-DI

1"-HWR

PIPING IDENTIFIED FROM

TOP TO BOTTOM

PLUMBING TAGS

PIPING IDENTIFIED FROM

LEFT TO RIGHT

PIPING IDENTIFIED FROM

1"-HWR

1"-HW

1"-DI

1"-CW

1"-HWR

1"-HW

1"-DI

1"-CW

X-1TYPE/MARK (SEE SCHEDULE)

PLUMBING EQUIPMENT/FIXTURE TAGS

CODE AND REGULATORIES ABBREVIATIONS

DESCRIPTION AAB DESCRIPTION AAB

AMERICAN NATIONAL STANDARDS ANSI NATIONAL ELECTRICAL CODE NEC

AMERICAN SOCIETY OF CIVIL ENGINEERS ASCE NATIONAL FIRE PROTECTION ASSOCIATION NFPA

AMERICAN SOCIETY OF HEATING, REFRIGERATING AND

AIR-CONDITIONING ENGINEERS

ASHRAE UNIFORM BUILDING CODE UBC

AMERICAN SOCIETY OF MECHANICAL ENGINEERS ASME UNIFORM FIRE CODE UFC

AMERICAN SOCIETY OF PLUMBING ENIGNEERS ASPE UNIFORM PLUMBING CODE UPC

AMERICAN SOCIETY OF SANITARY ENGINEERING ASSE UNDERWRITERS LABORATORIES UL

AMERICAN SOCIETY OF TESTING AND MATERIALS ASTM

AMERICAN WATER WORKS ASSOCIATION AWWA

CAST IRON SOIL PIPE INSTITUTE CISPI

FACTORY MUTAL FM

INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS IEEE

INTERNATIONAL ASSOCIATION OF PLUMBING AND

MECHANICAL OFFICIALS

IAPMO

INTERNATIONAL BUILDING CODE IBC

INTERNATIONAL ENERGY CONSERVATION CODE IECC

INTERNATIONAL FIRE CODE IFC

INTERNATIONAL FUEL GAS CODE IFGC

INTERNATIONAL MECHANICAL CODE IMC

INTERNATIONAL PLUMBING CODE IPC

INTERNATIONAL RESIDENTIAL CODE IRC

GENERAL PLUMBING SYMBOLS

REVISION NUMBER - SHOWN ON PLANS

POINT WHERE NEW CONNECTS TO EXISTING

NUMBER OF DETAIL ON SHEET

NUMBER OF SHEET WHERE DETAIL APPEARS

KEYNOTE

CONTINUATION SYMBOL

ROOM NAME AND NUMBER

ITEM TO BE DEMOLISHED

AREA NOT IN CONTRACT

PIPE SIZE TAG (DIAMETER)

ABOVE GROUND PIPING

BELOW GROUND PIPING

PIPE INVERT ELEVATION TAG

EXISTING PIPE TAG

PIPING BEING DEMOLISHED

PIPE SLOPE TAG

INVERT: -105'- 0" 127/128"

1/8" / 12" SLOPE

2"

(E)

Room

7300 FM 2222 #2

Austin, Texas 78730-2314 USA

512.744.4400 main - 512.744.4444 fax www.eeace.com

EEA Project No.

State of registration Firm Registration No.

20250239

F-2497

TX

REVISIONS:

24-1053.00

DECEMBER 4, 2025

EXCEPT AS MAY BE OTHERWISE PROVIDED BY CONTRACT,

THESE DRAWINGS AND SPECIFICATIONS ARE PROPERTY

OF THE CLIENT LISTED, AND ARE ISSUED IN STRICT

CONFIDENCE AND SHALL NOT BE MADE AVAILABLE,

REPRODUCED, OR COPIED, OR USED FOR ANY OTHER

INTENDED PURPOSE, OR AS BASIS FOR MANUFACTURE OR

SALE OF APARATUS WITHOUT WRITTEN PERMISSION.

CONFIDENTIAL AND PROPRIETARY

SHEET NUMBER:

SHEET NAME:

PROJECT NUMBER:

ISSUE DATE:

SEAL(S) / CONSULTANT:

CLIENT / PROJECT NAME:

Criss Cole

Rehabilitation

Center

Generator

4800 N.Lamar

Blvd. Austin, TX.

78756

24-1053.00

P0.0

PLUMBING GENERAL NOTES &

SYMBOLS

PLUMBING SHEET INDEX

P0.0 PLUMBING GENERAL NOTES & SYMBOLS

P3.0 PLUMBING PLAN

P5.0 PLUMBING DETAILS

1. CONTRACTOR SHALL REVIEW AND ADHERE TO ALL NOTES LOCATED IN THE MEP SHEET

SET.

2. PROVIDE PIPING MATERIALS AND FACTORY-FABRICATED PIPING PRODUCTS OF SIZES,

TYPES, PRESSURE RATINGS, AND CAPACITIES AS INDICATED. WHERE NOT INDICATED,

PROVIDE PROPER SELECTION AS DETERMINED BY INSTALLER TO COMPLY WITH

INSTALLATION REQUIREMENTS. PROVIDE SIZES, AND TYPES MATCHING PIPING AND

EQUIPMENT CONNECTIONS; PROVIDE FITTINGS OF MATERIALS WHICH MATCH PIPE

MATERIALS USED IN SOIL, AND VENT PIPING SYSTEMS.

3. NOT ALL PIPE SIZES ARE SHOWN ON PLANS FOR CLARITY. REFER TO RISER DIAGRAMS

FOR PIPING SIZES.

4. COORDINATE FIRE ALARM CONNECTIONS TO FIRE PROTECTION SYSTEM WITH FIRE

PROTECTION CONTRACTOR.

5. INSTALL PIPING TO ALLOW FOR EXPANSION AND CONTRACTION WITHOUT STRESSING

PIPE, JOINTS, OR CONNECTED EQUIPMENT.

6. SLEEVE FOUNDATION BEAM PENETRATIONS WITH SCH. 40 STEEL PIPE SLEEVE OF 2"

LARGER DIAMETER.

7. GAS PIPING:

a. FURNISH AND INSTALL A GAS COCK, DIRT LEG, AND UNION CONNECTION AT EACH

PIECE OF EQUIPMENT.

b. SUPPORT PIPING EVERY 5 FEET, AS REQUIRED BY OWNER, AS DETAILED ON

DRAWINGS, OR BY STANDARD INDUSTRY PRACTICE, WHICHEVER IS MORE STRINGENT.

c. TESTING AND PURGING OF GAS PIPING SHALL BE DONE PER THE REQUIREMENTS OF

THE LOCAL GAS COMPANY, LOCAL CODES, AND APPLICABLE NFPA 54 CODES.

d. GAS PIPING INSTALLED IN RETURN AIR PLENUMS OR BURIED BELOW BUILDING

INTERIOR CONCRETE SLABS SHALL BE SLEEVED AND VENTED TO ATMOSPHERE IN

ACCORDANCE WITH ALL CODES.

e. GAS PIPING EXPOSED TO EXTERIOR SHALL BE PAINTED WITH 2 COATS OF YELLOW

BITUMINOUS BASED RUST-INHIBITING PAINT.

f. ALL BUILDING INTERIOR MOUNTED PRESSURE REGULATOR SHALL BE OPD TYPE AND

VENTED TO ATMOSPHERE. UTILIZE MAXITROL; 325-L SERIES LINE PRESSURE

REGULATORS WITH OPD.

GENERAL PLUMBING NOTES:

Digitally Signed

Mark Mikulin, PE (TX)

2025.12.04 10:35:11-06'00'

NATURAL

GAS METER

(E) 2" HG

(E) 3" MG

(E

3" M

G

1 1/4" MG 4" G

GENERATOR GEN-1

PLUMBING NOTES

A. FIELD VERIFY SIZES OF ALL MAINS, BRANCHES, AND VALVES PRIOR TO

ORDER AND INSTALLATION.

B. CONTRACTOR TO VERIFY EXISTING GAS SERVICES ARE NOT AFFECTED BY

GENERATOR ADDITION. EXISTING GAS FLOW RATES TO REMAIN AS

EXISTING.

C. NATURAL GAS TO BE INSTALLED 1'-0" MINIMUM ABOVE FINISHED FLOOR OF

MECHANICAL YARD.

D. DO NOT ANCHOR SUPPORTS IN MORTAR. ANCHOR ONLY IN BRICK OR CMU.

E. NATURAL GAS SUPPORTS AND FASTNERS TO BE HOT DIPPED GALVANIZED

(NOT ELECTRO-GALVANIZED, ZINC PLATED, ETC.) OR STAINLESS STEEL.

F. PAINT ALL NEW, MODIFIED, OR REPLACED PIPING TO MATCH EXISTING.

PAINT ALL EXPOSED PIPING WITH A RUST INHIBITOR PAINT TO PREVENT

EXTERIOR PIPE RUSTING DUE TO MOISTURE AND CHEMICALS.

7300 FM 2222 #2

Austin, Texas 78730-2314 USA

512.744.4400 main - 512.744.4444 fax www.eeace.com

EEA Project No.

State of registration Firm Registration No.

20250239

F-2497

TX

REVISIONS:

24-1053.00

DECEMBER 4, 2025

EXCEPT AS MAY BE OTHERWISE PROVIDED BY CONTRACT,

THESE DRAWINGS AND SPECIFICATIONS ARE PROPERTY

OF THE CLIENT LISTED, AND ARE ISSUED IN STRICT

CONFIDENCE AND SHALL NOT BE MADE AVAILABLE,

REPRODUCED, OR COPIED, OR USED FOR ANY OTHER

INTENDED PURPOSE, OR AS BASIS FOR MANUFACTURE OR

SALE OF APARATUS WITHOUT WRITTEN PERMISSION.

CONFIDENTIAL AND PROPRIETARY

SHEET NUMBER:

SHEET NAME:

PROJECT NUMBER:

ISSUE DATE:

SEAL(S) / CONSULTANT:

CLIENT / PROJECT NAME:

Criss Cole

Rehabilitation

Center

Generator

4800 N.Lamar

Blvd. Austin, TX.

78756

24-1053.00

P3.0

PLUMBING PLAN

1/8" = 1'-0"P3.0

1 PLUMBING PLAN

NEW WORK KEYNOTES

1 NEW NATURAL GAS METER TO BE PROVIDED AND INSTALLED BY UTILITY SERVICE

PROVIDER. CONTRACTOR TO PROVIDE NEW GAS REGULATOR AND ACCESSORIES

DOWNSTREAM OF THE GAS METER. REFER TO DETAIL 1 / P5.0 FOR GAS RISER

DIAGRAM.

2 LOCATE PRESSURE REGULATOR(S) A MINIMUM OF 3-FT FROM ALL ELECTRICAL

EQUIPMENT WITHIN THE MECHANICAL YARD.

GAS

NATURAL GAS

(5 PSI OR LESS)

2" AND BELOW

STD WT BLACK CARBON STEEL ASTM

A53 GRADE B

TYPE E OR S

CL. 150 MALLEABLE IRON

ASTM A197, ASME B16.3

THREADED

N/A

BA-2

EXPOSED EXERIOR GAS PIPING SHALL BE PAINTED WITH RUST-

INHIBITING PAINT.

3" AND ABOVE

BUTTWELD: STD WT CS

ASTM A234, ASME B16.9

BUTTWELD PER ASME B31.9 FOR BUILDING

SERVICES PIPING

GA-1

SCHEDULE NOTES

1. ALL PLUMBING MATERIALS TO MEET PLUMBING CODE REQUIREMENTS.

2. PROVIDE PRODUCT LISTED OR ENGINEER PRE-APPROVED EQUAL, APPLIES TO ALL PRODUCTS LISTED IN SCHEDULE.

3. INSTALL ALL PRODUCTS PER THE MANUFACTURERS RECOMMENDATIONS.

4. ALL PIPING IS TO BE SUPPORTED PER ANSI B31.9, ASME B31.1, MSS SP-58 AND MSS SP-69 AND MANUFACTURER'S INSTRUCTIONS.

5. CLEAN AND FLUSH ALL NEWLY INSTALLED PIPING AND STRAINER / FILTERS WITH SYSTEM APPROPRIATE MATERIAL PRIOR TO PUTTING SYSTEM INTO OPERATION.

6. PVC, CPVC AND CAST IRON PIPE AND FITTINGS SHALL BE BY CHARLOTTE PIPE OR EQUAL.

7. PVC SHALL NOT TO BE USED IN THE FOLLOWING LOCATIONS:

A. HVAC PLENUMS OR IN EXTERIOR LOCATIONS WHERE EXPOSED TO SUNLIGHT; COATINGS OR WRAPS ARE NOT ALLOWED IN THESE LOCATIONS.

B. DOMESTIC WATER SUPPLY SYSTEMS INSIDE OF THE BUILDING.

8. PIPING SYSTEMS SHALL BE TESTED IN ACCORDANCE WITH THE APPLICABLE CODES AND LOCAL AHJ.

9. WHEN JOINING DISIMILAR METALS USE DIELECTRIC NIPPLES OR COUPLINGS, OR DIELECTRIC FLANGE KITS ON LARGER PIPING. DIELCTRIC UNIONS ARE NOT ALLOWED.

PLUMBING PIPE SCHEDULE

PIPING ID SERVICE SIZE MATERIAL TYPE FITTING TYPE JOINT TYPE INSULATION TYPE VALVES REMARKS

Digitally Signed

2025.12.04 10:35:22-06'00'

7300 FM 2222 #2

Austin, Texas 78730-2314 USA

512.744.4400 main - 512.744.4444 fax www.eeace.com

EEA Project No.

State of registration Firm Registration No.

20250239

F-2497

TX

REVISIONS:

24-1053.00

DECEMBER 4, 2025

EXCEPT AS MAY BE OTHERWISE PROVIDED BY CONTRACT,

THESE DRAWINGS AND SPECIFICATIONS ARE PROPERTY

OF THE CLIENT LISTED, AND ARE ISSUED IN STRICT

CONFIDENCE AND SHALL NOT BE MADE AVAILABLE,

REPRODUCED, OR COPIED, OR USED FOR ANY OTHER

INTENDED PURPOSE, OR AS BASIS FOR MANUFACTURE OR

SALE OF APARATUS WITHOUT WRITTEN PERMISSION.

CONFIDENTIAL AND PROPRIETARY

SHEET NUMBER:

SHEET NAME:

PROJECT NUMBER:

ISSUE DATE:

SEAL(S) / CONSULTANT:

CLIENT / PROJECT NAME:

Criss Cole

Rehabilitation

Center

Generator

4800 N.Lamar

Blvd. Austin, TX.

78756

24-1053.00

P5.0

PLUMBING DETAILS

TABLE 1215.2(6) [UPC 2021]

SCEDULE 40 METALLIC PIPE [NFPA 54: TABLE 6.2.1(g)]

GAS: NATURAL

INLET PRESSURE: 5.0 PSI

PRESSURE DROP: 3.5 PSI

TOTAL DEVELOPED LENGTH: 59 LF

PIPE SIZE

(INCHES)

MAXIMUM FLOW

(CFH)

1/2 1,300

3/4 2,630

1 4,800

1-1/4 9,960

1-1/2 14,800

2 28,500

2-1/2 45,400

3 80,200

4 164,000

TOTAL HORIZONTAL PIPING = 45 FT

TOTAL VERTICAL PIPING = FT

SUBTOTAL PIPING LENGTH = FT

ADD FOR FITTINGS= 25% FT

TOTAL DEVELOPED LENGTH = FT

12" = 1'-0"P5.0

2 NATURAL GAS RISER DIAGRAM - DEMO

12" = 1'-0"P5.0

1 NATURAL GAS RISER DIAGRAM - NEW WORK

TABLE 1215.2(1) [UPC 2021]

SCEDULE 40 METALLIC PIPE [NFPA 54: TABLE 6.2.1(b)]

GAS: NATURAL

INLET PRESSURE: LESS THAN 2 PSI

PRESSURE DROP: 0.5 IN.WC.

TOTAL DEVELOPED LENGTH: 100 LF

PIPE SIZE

(INCHES)

MAXIMUM FLOW

(CFH)

1/2 50

3/4 104

1 195

1-1/4 400

1-1/2 600

2 1,160

2-1/2 1,840

3 3,260

4 6,640

Digitally Signed

2025.12.04 10:35:37-06'00'

A AMPERE

AC ABOVE COUNTER

AFF ABOVE FINISHED FLOOR

AIC AMP INTERRUPTING CAPACITY

A/V AUDIO VISUAL

ATS AUTOMATIC TRANSFER SWITCH

BLDG BUILDING

C CONDUIT

CKT CIRCUIT

CM CONTROL MODULE

CONN CONNECT OR CONNECTION

CT CURRENT TRANSFORMER

DIM DIMENSION

EA EACH

EC ELECTRICAL CONTRACTOR

EF EXHAUST FAN

ELEC ELECTRIC, ELECTRICAL

EMER EMERGENCY

EPO EMERGENCY POWER OFF

EWC ELECTRIC WATER COOLER

FACP FIRE ALARM CONTROL PANEL

FLA FULL LOAD AMPS

FS FLOW SWITCH

FSD FIRE SMOKE DAMPER

GC GENERAL CONTRACTOR

GFI GROUND FAULT INTERRUPTER

GND GROUND

HOA HAND-OFF-AUTO

HP HORSEPOWER

HPS HIGH PRESSURE SODIUM

HTR HEATER

J-BOX JUNCTION BOX

KCM THOUSAND CIRCULAR MILLS

ELECTRICAL ABBREVIATIONS LIST

LOTO LOCK OUT TAG OUT

LTG LIGHT OR LIGHTING

MCB MAIN CIRCUIT BREAKER

MC MOTOR CONTROL CENTER

MCP MOTOR CIRCUIT PROTECTOR

MIN MINIMUM

MH METAL HALIDE

MLO MAIN LUGS ONLY

MNS MASS NOTIFICATION SYSTEM

MRS MOTOR RATED SWITCH

MSB MAIN SWITCH BOARD

MTD MOUNTED

MTS MANUAL TRANSFER SWITCH

MV MEDIUM VOLTAGE

N.I.C. NOT IN CONTRACT

NL NIGHT LIGHT (UNSWITCHED)

NTS NOT TO SCALE

∅ PHASE

OL OVERLOAD

OE OVER HEAD ELECTRIC

PS PULL STRING

RECPT RECEPTACLE

RGS RIGID GALVANIZED STEEL

SPD SURGE PROTECTION DEVICE

TS TAMPER SWITCH

TYP. TYPICAL

UG UNDERGROUND

UNO UNLESS NOTED OTHERWISE

V VOLTAGE

WH WATER HEATER

WP WEATHER PROOF

WR WEATHER RATED

XFMR TRANSFORMER

ELECTRICAL EQUIPMENT CLEARANCE REQUIREMENTS

KEYED NOTES:

3' (0-150V TO GND),

3.5' (151V-600V TO GND), 4'

(OVER 150V WITH EXPOSED

LIVE PARTS ON OTHER

SIDE).

DEDICATED EQUIPMENT

SPACE SHALL BE KEPT

CLEAR TO 6FT ABOVE

EQUIPMENT OR TO

STRUCTURE OF ALL BUT

CONDUIT SERVING

EQUIPMENT.

MIN OFFSET SHALL BE

DEPTH OF EQUIPMENT ON

PERPENDICULAR WALL

ELECTRICAL

EQUIPMENT

ELECTRICAL

EQUIPMENT

WORKING

SPACE XFMR

30"

MIN

DOOR

WIDTH

MINUS 3"

ES

DH

3/ 4"

3/ 4"

3/ 4"

3/ 4"

1"

S

TO LTG/PANEL

TO DOOR OPERATOR

TO PLENUM, EXCEPT TO IT CLOSET

WHERE CEILING IS EXPOSED TO

DECK OR INACCESSIBLE

TO FACP

TO CONTACTOR

48" 1.

2.

REFER TO RCP FOR CEILING TYPES IN

ALL AREAS.

PRIORITY FOR PROXIMITY TO DOOR

SHALL BE AS SHOWN.

3"

18"

3/ 4"

1/

4"

1- 2"

, 1 -1

AV1

2"

TO FLOORBOX

TO PANEL

TO PLENUM. TO IT CLOSET

WHERE CEILING IS EXPOSED

TO DECK OR INACCESSIBLE.

TO PLENUM, EXCEPT TO AV

EQUIP. WHERE CEILING IS

EXPOSED TO DECK OR

INACCESSIBLE.

EXIT

6"

TV TV

3/ 4" 2"

60"

BACKSPLASH

AC AC

4"

FIRE

FIRE ALARM

PULL DOWN

SIMPLEX

WALL MNT TV

VERIFY TV HT

BEFORE

INSTALL AND

CENTER

OUTLETS

BEHIND TV

4"

80"

MINIMUM

CLEARANCE

TO CEILING

6"

CLEARANCE

TO CEILING

SHALL HAVE

PRIORITY

OVER 80"

ABOVE

FINISHED

FLOOR

MIN HT TO

BOTTOM

OF

NOTIFICATION

APPLIANCES

OS

8"

MAX12'-0"

MINIMUM

CLEARANCE

TO CEILING

NAMEPLATE REQUIREMENTS

ELECTRICAL PANELS EQUIPMENT CONTROLS

1.

2.

3.

4.

5.

SPECIFICATIONS

NAMEPLATE: 1/16" PHENOLIC PLASTIC LAMINATE, TWO FLAT HEAD

SCREWS

FINISHED AREA WIRING DEVICES: ADHESIVE LABELS, CLEAR W/ BLACK

TEXT

J-BOXES: USE PERMANENT INK MARKER AND PAINT AS NOTED

OUTDOOR AND HARSH ENVIRO WIRING DEVICES: MARKER ON INSIDE OF

COVER

IN PUBLIC AREAS SUCH AS LOBBIES, CONF. ROOMS, ETC, LABEL INSIDE

OF RECEPTACLE COVERS AND EXPOSED JBOX COVERS USING MARKER.

PLACE A DOT OF PAINT ON OUTSIDE OF SPECIAL SYSTEMS BOXES.

RECEPTACLES J-BOXES

PNL # CKT

PWR IT FIRE

NO

PAINT

ORANGE

COVER

RED

COVER

L1#1 120V

COM FA

NAC

PANEL L1

208/120V, 3PH, 4W

225A, FED FROM H1

VIA XFMR T-L1

CWP-VFD

208/120V, 3PH, 4W

5HP, FED FROM L1

CLNG

J

J

SINGLE RECEPTACLE

DUPLEX RECEPTACLE

SPLIT CONTROLLED DUPLEX RECEPTACLE

CONTROLLED DUPLEX RECEPTACLE

WALL MOUNTED JUNCTION BOX

CEILING MOUNTED JUNCTION BOX

MULTIOUTLET ASSEMBLY

SAFETY DISCONNECT SWITCH (NON-FUSED)

SAFETY DISCONNECT SWITCH (FUSED)

M MOTOR RATED TOGGLE SWITCH

P POWER POLE (OPEN OFFICE STYLE)

UTILITY SERVICE POWER POLE

T30

TRANSFORMER. THE TRANSFORMER TYPE IS

INDICATED BY A NUMBER INDICATING KVA RATING

FOLLOWING THE UPPER CASE LETTER "T"

POWER DEVICE LEGEND

SPECIAL RECEPTACLE

FB1 FLOORBOX (SEE FLOORBOX SCHEDULE)

ELECTRICAL PANELBOARD

FLOOR CLEARANCE AREA

USB RECEPTACLE

QUADPLEX RECEPTACLE

FLOOR MOUNTED DUPLEX RECEPTACLE

FLOOR MOUNTED QUADPLEX RECEPTACLE

CEILING DUPLEX RECEPTACLE

COMBINATION MOTOR STARTER (FUSED)

EMERGENCY POWER OFF BUTTON

TCS

OS

LIGHTING CONTROLS LEGEND

LIGHT SWITCH

LIGHT SWITCH WITH INTEGRAL OCCUPANCY SENSOR

CELING MOUNTED OCCUPANCY SENSOR

CELING MOUNTED DAYLIGHT SENSOR

A LIGHTING CONTROL TAG

(SEE LIGHTING CONTROL MATRIX)

CELING MOUNTED PHOTOCELL

TOUCHSCREEN CONTROL STATION

OS

DS

PC

PC

DS

OS WALL MOUNTED OCCUPANCY SENSOR

WALL MOUNTED DAYLIGHT SENSOR

WALL MOUNTED PHOTOCELL

AV1

SPECIAL SYSTEMS DEVICES

VOICE/DATA OUTLET

TELEPHONE OUTLET

CEILING VOICE/DATA OUTLET

DATA OUTLET

CEILING OUTLET

AUTO PUSH DOOR BUTTON

ELECTRIC STRIKE

MAGNETIC LOCK

CARD READER

SECURITY KEYPAD

CLNG

CLNG

ML

ES

CR

TV DATA OUTLET

1V2D

# OF VOICE AND # OF DATA OUTLETS.

EXAMPLE: 1V2D = 1 VOICE, 2 DATA

# OF DATA OUTLETS

TV

WIRELESS ACCESS POINT

AUDIO VIDEO INPUT JACK BOX

ELECTRICAL SYMBOL NOTES

LOWERCASE LETTER INDICATED LIGHTING

ZONE (WHERE APPLICABLE)

A d P1#1

EXIT LIGHTS. STEM INDICATES WALL MOUNTING. NO STEM INDICATES

CEILING MOUNTING. SHADED AREA INDICATES ILLUMINATED FACE(S).

ARROW INDICATES DIRECTIONAL ARROW ON ILLUMINATED FACE(S).

AE DIAGONAL HATCH INDICATES EMERGENCY/EGRESS LIGHTING AND/OR

TAGGED WITH "E" (AS IN "AE")d

P1#1

CONDUIT IN CEILING, FLOOR OR WALL AS REQUIRED BY FIELD CONDITIONS

CONDUIT IN FLOOR

1 REVISION NUMBER - SHOWN ON PLANS

NUMBER OF DETAIL ON SHEET

NUMBER OF SHEET WHERE DETAIL APPEARS

1 KEYED NOTE (SEE SCHEDULE)

Room

6 ROOM NAME AND NUMBER

NEW

EXISTING TO BE REMOVED/RELOCATED

EXISTING TO REMAIN

ITEM TO BE

REMOVED

GRAPHICAL REPRESENTATION OF PHASING, TYPICAL FOR ALL SYMBOLS.

a

SWITCHING INSTRUCTIONS

LOWER CASE LETER DESIGNATES A

SWITCHLEG, LETTER WILL BE SHOWN NEXT TO

EACH FIXTURE CONTROLLED BY SWITCH

SPECIFICATION NOTES:

2 = DOUBLE POLE

3 = THREE WAY

4 = FOUR WAY

D = DIMMER

EP = EXPLOSION PROOF

K = KEY OPERATED

T = TIMER

AC

MOUNTING REQUIREMENTS

48" = MOUNT AT 48 INCHES ABOVE FINISHED FLOOR

AC = MOUNT ABOVE COUNTER 4" ABOVE BACK-SPLASH

(MOUNT AT 18 INCHES ABOVE FINISH FLOOR U.N.O.)

SPECIFICATION NOTES:

GFI = INTEGRAL GROUND FAULT TRIP MODULE

IG = ISOLATED GROUND

MG = MARINE GRADE

TL = TWIST-LOCK

TR = TAMPER-RESISTANT

WP = WEATHER RESISTANT RECEPTACLE WITH

METAL WEATHERPROOF WHILE IN USE COVER

GFI

FIXTURE TYPE ID (SEE LIGHT FIXTURE SCHEDULE)

PANEL NAME & CIRCUIT NUMBER

M

ELECTRICAL ONE LINE SYMBOLS

MOLDED CASE/ THERMAL MAGENTIC CIRCUIT BREAKER

FUSED DISCONNECT SWITCH

FUSE, HOLDER & PULLER

GROUND

POTENTIAL TRANSFORMER

CURRENT TRANSFORMER

UTILITY METER

SURGE PROTECTION DEVICE

X MOTOR, "X" INDICATING HORSE POWER

AUTOMATIC TRANSFER SWITCH

ST SHUNT TRIP (K=KIRK KEY INTERLOCK, RT=REMOTE TRIP)

K KIRK-KEY

DRAWOUT CIRCUIT BREAKER, AIR TYPE

DRAWOUT CIRCUIT BREAKER, VAC TYPE

THERMAL OVERLOAD

NON-FUSED DISCONNECT SWITCH

SPD

6"

OS

CR F FAA

ELECTRICAL SHEET INDEX

E0.0 ELECTRICAL SYMBOLS AND LEGENDS

E0.1 ELECTRICAL GENERAL NOTES

E0.2 ELECTRICAL GENERAL NOTES

E1.0 EQUIPMENT SCHEDULES

E3.0 ELECTRICAL PLANS

E5.0 ELECTRICAL ONE-LINE

7300 FM 2222, Bldg. 2, Ste. 2 Austin, Texas 78730-2314 USA

512.744.4400 main - 512.744.4444 fax www.eeace.com

EEA Project No.

State of registration Firm Registration No.

20250239

F-2497

TX

REVISIONS:

24-1053.00

DECEMBER 4, 2025

EXCEPT AS MAY BE OTHERWISE PROVIDED BY CONTRACT,

THESE DRAWINGS AND SPECIFICATIONS ARE PROPERTY

OF THE CLIENT LISTED, AND ARE ISSUED IN STRICT

CONFIDENCE AND SHALL NOT BE MADE AVAILABLE,

REPRODUCED, OR COPIED, OR USED FOR ANY OTHER

INTENDED PURPOSE, OR AS BASIS FOR MANUFACTURE OR

SALE OF APARATUS WITHOUT WRITTEN PERMISSION.

CONFIDENTIAL AND PROPRIETARY

SHEET NUMBER:

SHEET NAME:

PROJECT NUMBER:

ISSUE DATE:

SEAL(S) / CONSULTANT:

CLIENT / PROJECT NAME:

Criss Cole Rehabilitation

Center Generator

4800 N.Lamar Blvd. Austin, TX.

78756

24-1053.00

E0.0

ELECTRICAL SYMBOLS AND

LEGENDS

1.1. SPECIAL SYSTEMS INCLUDE, BUT ARE NOT LIMITED TO, TELECOMMUNICATIONS, FIRE

ALARM, AUDIO/VIDEO, ACCESS CONTROL SYSTEMS.

1.2. FOR SPECIAL SYSTEMS EQUIPMENT AND DEVICES SHOWN ON THE CONSTRUCTION

DOCUMENTS, OR EQUIPMENT AND DEVICES THAT CAN BE REASONABLY IMPLIED AS

REQUIRED TO OPERATE ITEMS SHOWN, ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE

FOR POWER, RACEWAY/BOX/ENCLOSURES ROUGH-IN, AND INFRASTRUCTURE PROVISION

EVEN IF SAID SPECIAL SYSTEMS ARE PROVIDED BY A SPECIALIST CONTRACTOR, OWNER'S

AGENT, OR UNDER SEPARATE CONTRACT.

1.3. TELECOMMUNICATIONS: IT CABLING, JACKS, EQUIPMENT RACKS, NETWORKING

EQUIPMENT, AND PATCH PANELS WILL BE PROVIDED AND INSTALLED BY TELECOM

CONTRACTOR. ALL OTHER WORK BY ELEC. CONTRACTOR.

1.4. FIRE ALARM: CONTROL PANELS, MODULES, NOTIFICATION APPLIANCES, INITIATING

DEVICES, WIRING, BATTERIES, AND MISC. MATERIALS SHALL BE PROVIDED BY

SPECIALIST FIRE ALARM CONTRACTOR UNDER THIS CONTRACT.

1.5. AUDIO/VIDEO: COORDINATE SCOPE WITH OWNER PRIOR TO BID.

1.6. ACCESS CONTROL (SECURITY): COORDINATE SCOPE WITH OWNER PRIOR TO BID.

1.7. COORDINATE REQUIREMENTS FOR DATA ROOMS WITH OWNER'S INFORMATION

TECHNOLOGIES REPRESENTATIVE (IT REP).

1.8. AT MINIMUM, THE FOLLOWING GENERAL PROVISIONS SHALL BE PROVIDED BY THE

CONTRACTOR. ADDITIONAL ITEMS SPECIFIED ELSEWHERE ON THE CONSTRUCTION

DOCUMENTS:

1.8.1. DOUBLE GANG DEVICE BOX WITH SINGLE GANG REDUCER (AS NEEDED) AT

EACH LOCATION SHOWN ON PLANS. NOTE THAT SOME SPECIAL SYSTEMS EQUIPMENT

MAY REQUIRE A DIFFERENT SIZE BOX. COORDINATE LOCATIONS AND SIZES FOR

BOXES WITH RESPECTIVE SPECIALIST CONTRACTORS PRIOR TO ROUGH-IN.

1.8.2. CONDUIT WITH PULL STRINGS FROM SOURCE (TELEPHONE BACKBOARD,

SECURITY PANEL, FACP, ETC) OR ACCESSIBLE CEILING SPACE TO ALL DEVICE

LOCATIONS SHOWN ON THESE PLANS. HOMERUN CONDUITS MAY BE COMBINED

WHERE APPROVED BY SPECIALIST CONTRACTOR. COORDINATE CONDUIT SIZES WITH

RESPECTIVE SPECIALIST CONTRACTORS PRIOR TO INSTALLATION.

1.9. POWER LIMITED AND NON POWER LIMITED CABLE SHALL NOT SHARE COMMON

RACEWAYS OR ENTER JUNCTION BOXES THROUGH THE SAME OPENING.

SPECIAL SYSTEMS NOTES:

2025.12.04 10:35:55-06'00'

7300 FM 2222, Bldg. 2, Ste. 2

512.744.4400 main - 512.744.4444 fax www.eeace.com

EEA Project No.

State of registration Firm Registration No.

20250239

F-2497

TX

REVISIONS:

24-1053.00

DECEMBER 4, 2025

EXCEPT AS MAY BE OTHERWISE PROVIDED BY CONTRACT,

THESE DRAWINGS AND SPECIFICATIONS ARE PROPERTY

OF THE CLIENT LISTED, AND ARE ISSUED IN STRICT

CONFIDENCE AND SHALL NOT BE MADE AVAILABLE,

REPRODUCED, OR COPIED, OR USED FOR ANY OTHER

INTENDED PURPOSE, OR AS BASIS FOR MANUFACTURE OR

SALE OF APARATUS WITHOUT WRITTEN PERMISSION.

CONFIDENTIAL AND PROPRIETARY

SHEET NUMBER:

SHEET NAME:

PROJECT NUMBER:

ISSUE DATE:

SEAL(S) / CONSULTANT:

CLIENT / PROJECT NAME:

Criss Cole Rehabilitation

Center Generator

4800 N.Lamar Blvd. Austin, TX.

78756

24-1053.00

E0.1

ELECTRICAL GENERAL NOTES

CODE REQUIREMENTS

THE CONTRACTOR SHALL COMPLY WITH ALL APPLICABLE REQUIREMENTS OF LAWS, RULES, REGULATIONS, CODES STANDARDS, AND ORDINANCES OF FEDERAL, STATE, AND LOCAL AUTHORITIES HAVING JURISDICTION, AND ALL EQUIPMENT AND MATERIALS SHALL COMPLY WITH SAID AUTHORITIES WHETHER INDICATED ON THE CONTRACT

DOCUMENTS OR NOT.

1. ALL WORK SHALL BE PERFORMED PER:

1.1. 2023 NATIONAL ELECTRICAL CODE - NEC

1.2. NATIONAL FIRE PROTECTION ASSOCIATION - NFPA

2. THE PUBLICATIONS AND STANDARDS OF THE FOLLOWING AUTHORITIES, IN ADDITION TO THOSE SPECIFIED IN RELATED SUPPLEMENTARY CONDITIONS, SHALL BE OBSERVED DURING CONSTRUCTION AND ARE REFERENCED IN THE DOCUMENTATION BY THE ABBREVIATIONS NOTED:

2.1. UNITED STATES OF AMERICA STANDARDS INSTITUTE - USASI

2.2. INSTITUTE OF ELECTRICAL AND ELECTRONIC ENGINEERS - IEEE

2.3. NATIONAL ELECTRICAL CODE - NEC

2.4. NATIONAL FIRE PROTECTION ASSOCIATION - NFPA

2.5. UNDERWRITER'S LABORATORY - UL

2.6. NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION - NEMA

2.7. CERTIFIED BALLAST MANUFACTURERS - CBM

2.8. AMERICAN SOCIETY FOR TESTING AND MATERIALS - ASTM

2.9. OCCUPATIONAL SAFETY AND HEALTH ACT - OSHA

3. U.N.O., EQUIPMENT AND DEVICES SHALL BE MOUNTED PER ADA AND TAS REQUIREMENTS.

3.1. OPERABLE DEVICES (SWITCHES, CARD READERS, ETC) AT OR BELOW 48" AFF

3.2. RECEPTACLES, TELEPHONE AND DATA OUTLETS AT 18" AFF (15" MIN TO BOTTOM OF DEVICE), UNO

SCOPE OF WORK

1. THE SCOPE OF WORK SHALL INCLUDE COMPLETE PROVISIONS FOR ELECTRICAL POWER DISTRIBUTION TO ALL LIGHTING, DEVICES, APPLIANCES, AND EQUIPMENT SHOWN

ON THE CONSTRUCTION DOCUMENTS.

1.1. PROVISIONS INCLUDE, BUT ARE NOT LIMITED TO, ALL SUPPLIES, MATERIALS, EQUIPMENT, TOOLS AND LABOR.

1.2. PROVISIONS ALSO INCLUDE ALL MISCELLANEOUS MATERIALS REQUIRED TO COMPLETE THE WORK SHOWN INCLUDING, BUT NOT LIMITED TO, SUPPORTS, HANGERS, RACEWAYS, BOXES, SLEEVES, SEALS, EQUIPMENT PADS, WIRING CONNECTORS, TERMINALS, LABELS, SIGNS, AND MARKERS.

1.3. THE CONSTRUCTION DOCUMENTS INCLUDE ALL PLANS, ELEVATIONS, DETAILS, DIAGRAMS, SCHEDULES, AND NOTES ON THE DRAWINGS AND THE WRITTEN

SPECIFICATIONS INCLUDING ANY ITEMS MENTIONED IN EITHER THE SPECIFICATIONS OR ON THE DRAWINGS BUT NOT IN THE OTHER.

1.4. WHERE USED ON THE PLANS AND IN THE SPECIFICATIONS AND WHERE NOT SPECIFICALLY NOTED OTHERWISE, THE TERM "PROVIDE" AND THE TERM "INSTALL"

SHALL MEAN FURNISH, INSTALL, CONNECT AND TEST.

1.5. UNLESS EXPLICITLY NOTED "BY OTHERS" OR "EXISTING", ALL ITEMS SHOWN GRAPHICALLY OR SPECIFIED BY NOTES AND DETAILS ON THE PLANS SHALL BE

FURNISHED, INSTALLED, CONNECTED, AND TESTED AS NEEDED.

2. ADDITIONALLY, THE SCOPE OF WORK SHALL INCLUDE:

2.1. APPLICATION FOR TEMPORARY AND PERMANENT ELECTRICAL SERVICE, PERMITTING, INSPECTION, AND PAYMENT OF ALL ASSOCIATED FEES.

2.2. TESTING AND COMMISSIONING OF ELECTRICAL SYSTEMS.

2.3. EQUIPMENT RENTAL.

2.4. TEMPORARY CONSTRUCTION POWER AND LIGHTING.

2.5. PROVISIONS FOR MAINTAINING THE FUNCTIONALITY OF EXISTING TO REMAIN BUILDING COMMUNICATIONS, FIRE ALARM, SECURITY/ACCESS CONTROL, PUBLIC

ADDRESS, AND BELL SYSTEMS THAT WILL BE AFFECTED BY THE WORK.

2.6. SHORT CIRCUIT COORDINATION STUDY AND ARC FLASH HAZARD ANALYSIS WITH CALCULATED LABELS PER NFPA 70E.

SUBMITTALS

1. PRODUCT DATA: SUBMIT CATALOG DATA SHOWING MANUFACTURER'S NAME AND CONTACT INFORMATION, ALL STANDARD FEATURES, AMPERAGE, VOLTAGE, AIC RATINGS, DIMENSIONS, WEIGHTS, LISTINGS & PRODUCT LABELS, MATERIAL TYPES, FINISHES AND CLEARLY INDICATING WHICH OPTIONAL FEATURES WILL BE PROVIDED.

1.1. WHERE MULTIPLE SIZES ARE LISTED, INDICATE SIZES TO BE USED.

1.2. WHERE MULTIPLE PRODUCTS ARE SHOWN ON THE SAME PAGE, INDICATE WHICH PRODUCTS TO BE USED.

2. SHOP DRAWINGS (WHERE APPLICABLE): MANUFACTURER OR CONTRACTOR PREPARED DRAWINGS SHOWING ALL RELEVANT DIMENSIONS, WEIGHTS, ELECTRICAL & MECHANICAL CONNECTION REQUIREMENTS, CONDUIT ENTRY POINTS, ASSEMBLY REQUIREMENTS, LIFTING REQUIREMENTS, LIFTING POINTS, REQUIRED CLEARANCES.

INCLUDE PLAN VIEWS & ELEVATIONS.

2.1. INCLUDE ALL RELEVANT ELECTRICAL DIAGRAMS INCLUDING SCHEMATIC AND INTERCONNECTION DIAGRAMS FOR POWER, SIGNAL, AND CONTROL WIRING.

COORDINATION

1. ALL POWER OUTAGES SHALL BE COORDINATED IN WRITING WITH OWNER SEVEN (7) BUSINESS DAYS (MIN) PRIOR TO THE OUTAGE. COORDINATE SHUT-DOWN OF

UTILITIES WITH UT PM AND FACILITY SERVICES.

2. COOPERATE FULLY WITH THE OWNER OR THEIR REPRESENTATIVE DURING CONSTRUCTION OPERATIONS TO MINIMIZE CONFLICTS AND TO FACILITATE OWNER USAGE SO

AS NOT TO INTERFERE WITH THE OWNER'S OPERATIONS.

3. THE DRAWINGS ARE DIAGRAMMATIC. THEY DO NOT SHOW SWITCHES, POWER AND DATA OUTLETS, SPECIAL SYSTEMS COMPONENTS (FA, ACCESS CONTROL, A/V, ETC), ELECTRICAL EQUIPMENT, EQUIPMENT CONNECTIONS, REQUIRED RACEWAY, ETC. IN THEIR EXACT DIMENSIONED LOCATIONS. THE CONTRACTOR MUST CAREFULLY REVIEW THE ARCHITECTURAL, STRUCTURAL MECHANICAL, PLUMBING, FIRE PROTECTION, AND SPECIAL SYSTEMS PLANS TO IDENTIFY CONFLICTS AND AREAS THAT

REQUIRE COORDINATION.

4. COORDINATE ELECTRICAL AND SPECIAL SYSTEMS EQUIPMENT ROUGH-IN WITH FURNITURE, MILLWORK, SIGNS, MECHANICAL AND PLUMBING SYSTEMS, SPRINKLER SYSTEMS, ARCHITECTURAL AND STRUCTURAL ELEMENTS, AND THE OWNER'S REPRESENTATIVE. MINOR CHANGES IN ELECTRICAL EQUIPMENT LOCATIONS AND LAYOUT THAT ARE REQUIRED BY SITE CONDITIONS OR ORDERED BY THE DESIGN TEAM PRIOR TO PERFORMANCE OF WORK SHALL BE MADE BY THE CONTRACTOR WITHOUT

ADDITIONAL CHARGES TO THE OWNER .

5. MAINTAIN REQUIRED NEC WORKING SPACE AND DEDICATED EQUIPMENT SPACE AROUND ALL ELECTRICAL EQUIPMENT, CONTROLS PANELS, ETC THAT ARE SUBJECT TO MAINTENANCE, TESTING, OR USER INTERFACE. COORDINATE WITH OTHER TRADES. IF CLEARANCE CANNOT BE PROVIDED, THE CONTRACTOR SHALL NOTIFY THE

ENGINEER PRIOR TO ROUGH-IN.

6. COORDINATE COLOR SELECTIONS FOR LUMINAIRES AND ALL DEVICE PLATES WITH ARCHITECT.

7. COORDINATE POWER REQUIREMENTS FOR HVAC CONTROLS, FIRE ALARM, SECURITY, AND OTHER SPECIAL SYSTEMS TO MAKE SURE THAT ALL WORK IS COVERED IN THE

BID.

8. CONTACT UT EHS TO DISPOSE OF THE FOLLOWING WASTE FROM RENOVATION; SILVER TIPPED FLORESCENT LIGHT BULBS (REMOVED INTACT), ALL BALLASTS NOT LABELED “NO PCBS”, MERCURY CONTAINING THERMOSTATS, SMOKE DETECTORS AND EXIT SIGNS THAT CONTAIN RADIOACTIVE MATERIAL. CONTRACTOR TO BUY DOT APPROVED CONTAINERS, PLACE WASTE IN CONTAINERS AND USE UT WASTE TAGS FOR EACH CONTAINER. COMPLETE REQUEST FOR DISPOSAL (UT EID REQUIRED) AND

SUBMIT TO EHS.

QUALIFICATIONS

1. MANUFACTURER: COMPANY SPECIALIZING IN MANUFACTURING PRODUCTS SHOWN ON THE CONSTRUCTION DOCUMENTS WITH MINIMUM THREE YEARS DOCUMENTED

EXPERIENCE.

2. INSTALLER: A STATE LICENSED ELECTRICIAN WITH DOCUMENTED EXPERIENCE INSTALLING ALL EQUIPMENT SPECIFIED HERE IN SHALL DIRECTLY SUPERVISE ALL WORK.

WHERE NOTED IN THE SPECIFICATIONS, REQUIRED BY CODE, OR REQUIRED BY THE MANUFACTURER, INSTALLER SHALL BE A MANUFACTURER TRAINED AND/OR

CERTIFIED INSTALLER OF THE SPECIFIC PRODUCT TO BE INSTALLED.

3. WHERE TESTING IS REQUIRED BY THE CONSTRUCTION DOCUMENTS, EQUIPMENT MANUFACTURER, OR CODE; TESTING SHALL BE PERFORMED BY AN AGENCY WITH DOCUMENTED EXPERIENCE AND PROPERLY CALIBRATED, FULLY FUNCTIONING EQUIPMENT, THAT IS A MEMBER OF THE INTERNATIONAL ELECTRICAL TESTING ASSOCIATION, MANUFACTURER CERTIFIED, OR IS A NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL), AND IS ACCEPTABLE TO THE AUTHORITY HAVING

JURISDICTION.

QUALITY ASSURANCE

1. UNLESS OTHERWISE APPROVED, ALL EQUIPMENT SHALL BE NEW, PROPERLY DESIGNED, FROM A REPUTABLE MANUFACTURER MEETING THE SPECIFICATION QUALIFICATIONS, IN COMPLIANCE WITH THE SPECIFICATION REQUIREMENTS, AND IN FULL WORKING ORDER.

2. WHERE TWO OR MORE ITEMS OF THE SAME CLASS OF EQUIPMENT ARE REQUIRED, THESE ITEMS SHALL BE PRODUCTS OF A SINGLE MANUFACTURER; HOWEVER, THE COMPONENT PARTS OF THE ITEM NEED NOT BE THE PRODUCTS OF THE SAME MANUFACTURER UNLESS STATED IN THE TECHNICAL SECTION.

3. LISTING AND LABELING: WHERE REQUIRED, ALL ELECTRICAL COMPONENTS, DEVICES, AND ACCESSORIES SHALL BE LISTED AND LABELED AS DEFINED IN NFPA 70, ARTICLE 100, BY A TESTING AGENCY ACCEPTABLE TO AUTHORITIES HAVING JURISDICTION AND MARKED FOR THE INTENDED USE. TESTING AGENCY SHALL BE UL UNLESS

NOTED OTHERWISE OR PRE-APPROVED BY OWNER AND AHJ.

4. ALL EQUIPMENT USED FOR TESTING SHALL BE IN FULL WORKING ORDER AND CALIBRATED PER THE MANUFACTURER'S RECOMMENDATIONS.

GENERAL ELECTRICAL REQUIREMENTS:

IDENTIFICATION

1. PROVIDE APPROPRIATE LABELS AND WARNING SIGNS FOR ALL EQUIPMENT, WIRING DEVICES, CONDUCTORS, CABLES, BOX, AND ENCLOSURES. PROVIDE BURIED

DETECTABLE WARNING TAPE FOR UNDERGROUND CONDUITS.

2. CONDUCTOR TAGGING: TAG ALL CONDUCTORS AT MOTOR CONTROLS, PANELS, TERMINAL CABINETS AND JUNCTION BOXES. TAG CIRCUITS WHICH PASS THROUGH

OTHER DEVICES SUCH AS LIGHTING CONTACTORS.

3. PROVIDE A TYPED PANEL DIRECTORY FOR EACH PANEL PROVIDED OR MODIFIED FOR THIS PROJECT. DIRECTORY SHALL IDENTIFY THE CIRCUIT NUMBER, LOADS SERVED, AND LOCATION OF LOADS BY ROOM NUMBER. MOUNT ON INSIDE OF EACH PANEL AND FILE THEM WITH THE OWNER WHEN THE WORK IS COMPLETED.

4. PROVIDE EACH PANEL WITH A MANUFACTURER PREPARED ARC FLASH HAZARD WARNING LABEL.

5. ALL ELECTRICAL EQUIPMENT SHALL BE IDENTIFIED BY MEANS OF 3"X1" (MIN)NAMEPLATES PERMANENTLY ATTACHED TO THE EQUIPMENT, PLATES SHALL BE METAL, PLASTIC, OR SIMILAR, BLACK WITH 1/4"h (MIN) ENGRAVED WHITE LETTERS.

6. JUNCTION AND PULL BOXES SHALL BE LABELED WITH PANEL NAME, CIRCUIT #, AND VOLTAGE.

7. RECEPTACLES SHALL BE LABELED WITH THE PANEL NAME AND CIRCUIT #. USE WHITE LABELS WITH BLACK TEXT. RECEPTACLES IN LOBBIES AND OTHER "HIGH END"

AREAS SHALL BE LABELED BEHIND THE FACEPLATE.

8. FIRE ALARM, EMERGENCY/CRITICAL PWR, LIFE SAFETY LABELS, INCLUDING RECEPTACLES, SHALL BE COLOR CODED & ENGRAVED.

GENERAL REQUIREMENTS

1. THE CONTRACTOR SHALL PROVIDE CONCRETE HOUSEKEEPING PADS FOR ALL FLOOR MOUNTED ELECTRICAL EQUIPMENT. THE CONCRETE SHALL PROTRUDE 3" PAST THE EDGE OF THE ELECTRICAL EQUIPMENT ON ALL SIDES. THE CONCRETE PAD SHALL BE 6" TALL AND CONTAIN A 1/2" CHAMFER ON ALL SIDES. PROVIDE A MINIMUM OF 3000

PSI CONCRETE AND #4 REBAR.

2. ALL TERMINALS, LUGS AND BUS JOINTS SHALL BE TIGHTENED PER THE MANUFACTURER'S TORQUE RECOMMENDATIONS.

3. NO FOREIGN SYSTEMS SUCH AS PIPING, DUCT WORK, ETC SHALL BE INSTALLED ABOVE ELECTRICAL EQUIPMENT.

4. PROVIDE SLEEVES FOR PENETRATIONS THROUGH WALLS/FLOORS. SEAL ALL OPENINGS. USE FIRE-RATED SEALANT FOR OPENINGS IN RATED WALLS.

5. PERFORM GROUND PENETRATING RADAR SCAN BEFORE CUTTING EXISTING STRUCTURES. COORDINATE LOCATIONS WITH STRUCTURAL ENGINEER/ARCHITECT.

CONDUCTORS AND CABLES

1. ALL BUILDING WIRING SHALL BE INSULATED COPPER CONDUCTORS RUN FROM LOAD TO SOURCE INSIDE RACEWAY, CONTINUOUS (WITHOUT SPLICES) BETWEEN JUNCTION

AND PULL BOXES, AND EXPOSED INSIDE PANELS ONLY.

2. ALL SINGLE POLE CIRCUITS SHALL HAVE A DEDICATED NEUTRAL CONDUCTOR ROUTED TO THE SOURCE PANEL.

3. FIELD VERIFY WHETHER A NEUTRAL IS REQUIRED FOR ALL TWO AND THREE POLE CIRCUITS. FOR ALL LOADS EXCEPT MOTORS, A NEUTRAL IS ASSUMED TO BE REQUIRED

UNLESS FIELD DETERMINED TO BE UNNECESSARY.

4. ALL POWER & CONTROL WIRING ROUTED THROUGH RETURN AIR PLENUMS SHALL BE PLENUM RATED.

5. UP TO 3-20A CIRCUITS MAY SHARE A RACEWAY FOR HOMERUNS WHERE SUITABLE & PER NEC CONDUIT FILL RULES.

6. 120V, 20A. HOME RUNS LONGER THAN 100' AND 277V, 20A. HOME RUNS LONGER THAN 150' SHALL BE #10 MIN.

GROUNDING AND BONDING

1. ALL RACEWAYS AND CIRCUITS SHALL BE PROVIDED WITH A NEC 250 COMPLIANT GREEN GROUND CONDUCTOR.

2. ALL EQUIPMENT SHALL BE PROPERLY BONDED.

3. UPON COMPLETION OF THE WORK, ALL PARTS OF THE ELECTRICAL INSTALLATION SHALL BE MEGGER TESTED AND PROVED TO BE FREE OF UNWANTED GROUNDS AND

OTHER DEFECTS.

4. ROUTING OF GROUNDING ELECTRODE CONDUCTORS SHALL BE IN METAL CONDUIT IN ALL LOCATIONS THAT ARE SUBJECT TO PHYSICAL ABUSE OR ENVIRONMENTAL

DETERIORATION SUCH AS EXTERIOR MOUNTED, EXPOSED BELOW LAY IN CEILING, ETC.

HANGERS AND SUPPORTS

1. SUPPORT RACEWAYS USING GALVANIZED STEEL OR MALLEABLE IRON STRAPS; CHANNEL OR PIPE CLAMPS AS APPROPRIATE.

2. PROVIDE SUPPORTS AT ALL BOXES, ELEC. EQUIP., LOADS, & AT CODE REQUIRED INTERVALS ALONG RACEWAYS.

3. GROUP RELATED RACEWAYS AND SUPPORT USING STEEL CHANNEL CONDUIT RACKS WITH 25% SPARE CAPACITY.

4. SUPPORT LTG, ELEC. EQUIP., RACEWAYS/BOXES, ETC. INDEPENDENTLY. DO NOT USE CEILING SUPPORT WIRES, PIPING SYSTEMS, ETC.

RACEWAY AND BOXES

1. PROVIDE COMPLETE RACEWAY SYSTEMS FROM SOURCE TO ALL LOADS WITH DEDICATED SUPPORTS FOR EACH RACEWAY ELEMENT.

2. PROVIDE ALL REQUIRED BOXES & SUPPORTS FOR WIRING DEVICES, TELECOMMUNICATIONS, FIRE ALARM, ACCESS CONTROL, CONTROLS EQUIPMENT, ALARMS, SENSORS, ETC.

3. PROVIDE PULL BOXES AT APPROPRIATE LOCATIONS FOR ALL POWER AND SPECIAL SYSTEMS RACEWAYS WHETHER SHOWN ON PLANS OR NOT. INSTALL IN CONCEALED, ACCESSIBLE LOCATIONS.

4. DO NOT INSTALL RACEWAY WITH MORE THAN THE EQUIVALENT OF THREE NINETY DEGREE BENDS BETWEEN PULL POINTS.

5. THE CONDUIT ROUTING SHOWN ON THESE PLANS IS DIAGRAMMATIC.

6. COORDINATE INTERIOR ROUTING WITH OTHER TRADES; STRUCTURE; NEW AND EXISTING UTILITIES, DUCTWORK, PIPING; AND OTHER EXISTING CONDITIONS AS REQUIRED

FOR A COMPLETE, CONFLICT FREE INSTALLATION.

7. COORDINATE SITE ROUTING WITH OTHER TRADES; STRUCTURE; NEW AND EXISTING BURIED UTILITIES, PAVED AREAS, CONDUIT SLEEVES, AND LANDSCAPING BEFORE

DIGGING TO AVOID CONFLICTS, DAMAGE, AND TO ALLOW FOR FUTURE INSTALLATIONS.

8. ROUTE RACEWAYS PARALLEL AND PERPENDICULAR TO WALLS, FLOORS, AND CEILINGS.

9. ROUTE EXPOSED CONDUIT PARALLEL AND TIGHT TO STRUCTURAL ELEMENTS. FOLLOW ALL SURFACE CONTOURS; DO NOT ROUTE IN FREE AIR FROM POINT TO POINT.

10. INSTALL RACEWAYS SO THAT IT DRAINS TO JUNCTION AND PULL BOXES TO AVOID MOISTURE TRAPS AT LOW POINTS; INSTALL JUNCTION BOX WITH DRAIN FITTING AT LOW

POINTS IN CONDUIT SYSTEM.

11. INSTALL FITTINGS TO ACCOMMODATE EXPANSION AND DEFLECTION WHERE RACEWAY CROSSES SEISMIC, CONTROL, AND EXPANSION JOINTS.

12. INSTALL SUITABLE PULL STRING OR CORD IN EACH EMPTY RACEWAY, LABEL, AND CAP.

13. CLOSE ENDS AND UNUSED OPENINGS IN SURFACE RACEWAYS, WIREWAY, BOXES, AND ENCLOSURES.

14. WHERE POSSIBLE, ALL CONDUIT ROUTED THROUGH ROOF STRUCTURE SHALL SHARE COMMON PENETRATIONS AS MECHANICAL DUCTWORK OR PIPING. COORDINATE

WITH MECHANICAL CONTRACTOR.

15. ALL ROOF AND WALL PENETRATIONS SHALL BE FLASHED AND SEALED TO MAINTAIN THE FIRE RATING AND WATERPROOFING OF THE STRUCTURE PER THE

MANUFACTURER OF THE MATERIAL'S RECOMMENDED PRACTICES.

16. USE MULTI-GANG BOXES IN ALL POSSIBLE LOCATIONS.

17. PAINT EXPOSED RACEWAYS AND BOXES TO MATCH THE SURFACE TO WHICH THEY ARE ATTACHED.

18. ALL CONDUIT SHALL HAVE AN NEC COMPLIANT GROUND AND AN INSULATED THROAT BUSHING IN PLACE FOR PULLING CONDUCTORS.

19. ALL CONNECTIONS TO MOTORS, INSTRUMENTS, MACHINES, AND EQUIPMENT SUBJECT TO MOVEMENT OR VIBRATION SHALL BE MADE USING LIQUID-TIGHT, FLEXIBLE

METAL CONDUIT (LFMC), (3FT MAX).

INSTALLATION:

DELIVERY AND STORAGE

1. STORE ALL ELECTIRCAL/SPECIAL SYSTEMS EQUIPMENT/MATERIALS IN CLEAN, DRY SPACE LOCATED ABOVE GRADE. PROTECT FROM DIRT, WATER, CONSTRUCTION

DEBRIS, TRAFFIC, FREEZE, AND DETERIORATION FROM SUN LIGHT.

2. MAINTAIN FACTORY WRAPPING OR PROVIDE APPROPRIATE COVER FOR ALL LARGE ELECTRICAL EQUIPMENT. FOLLOW ALL MANUFACTURER RECOMMENDATIONS FOR

HUMIDITY AND MAX/MIN TEMPERATURES FOR STORING ELECTRICAL EQUIPMENT.

GENERAL ELECTRICAL REQUIREMENTS:

512.744.4400 main - 512.744.4444 fax www.eeace.com

EEA Project No.

State of registration Firm Registration No.

20250239

F-2497

TX

REVISIONS:

24-1053.00

DECEMBER 4, 2025

EXCEPT AS MAY BE OTHERWISE PROVIDED BY CONTRACT,

THESE DRAWINGS AND SPECIFICATIONS ARE PROPERTY

OF THE CLIENT LISTED, AND ARE ISSUED IN STRICT

CONFIDENCE AND SHALL NOT BE MADE AVAILABLE,

REPRODUCED, OR COPIED, OR USED FOR ANY OTHER

INTENDED PURPOSE, OR AS BASIS FOR MANUFACTURE OR

SALE OF APARATUS WITHOUT WRITTEN PERMISSION.

CONFIDENTIAL AND PROPRIETARY

SHEET NUMBER:

SHEET NAME:

PROJECT NUMBER:

ISSUE DATE:

SEAL(S) / CONSULTANT:

CLIENT / PROJECT NAME:

Criss Cole Rehabilitation

Center Generator

4800 N.Lamar Blvd. Austin, TX.

78756

24-1053.00

E0.2

ELECTRICAL GENERAL NOTES

WIRING DEVICES

1. DUPLEX RECEPTACLES MOUNTED ON OPPOSITE SIDES OF A COMMON WALLS SHALL BE A MINIMUM OF 12" APART. (NO BACK TO BACK OUTLETS) TO REDUCE NOISE TRANSFER, JUNCTION BOXES IN ADJACENT ROOMS SHALL NOT BE INSTALLED IN THE SAME WALL CAVITY. SEPARATE ALL JUNCTION BOXES BY AT LEAST ONE FRAMING

MEMBER.

2. PROVIDE GFI RECEPTACLES & DIMMERS WITH DEDICATED NEUTRALS INDEPENDENT OF OTHER LOADS ON THE CIRCUIT.

ENCLOSED SWITCHES AND CONTACTORS

1. TO FACILITATE SAFE REPAIR AND REPLACEMENT OF EQUIPMENT, PROVIDE ALL STARTERS AND DISCONNECTS WITH LOTO PROVISIONS.

2. MOUNT STARTERS AND DISCONNECTS SERVING HVAC EQUIPMENT TO STRUCTURE ADJACENT TO EQUIPMENT SERVED RATHER THAN MOUNTING DIRECTLY TO THE EQUIPMENT. THIS INCLUDES U-CHANNEL SUPPORT AND 120V MAINTENANCE RECEPTACLE FOR ROOF MOUNTED EQUIPMENT. PROVIDE WORKING SPACE PER NEC

REQUIREMENTS.

LIGHTING

1. REFER TO ARCHITECTURAL REFLECTED CEILING PLAN FOR EXACT LIGHT FIXTURE LOCATIONS AND QUANTITIES.

2. EXAMINE THE AREA OF INSTALLATION TO VERIFY ADEQUATE SPACE AND MOUNTING PROVISIONS ARE PROVIDED FOR THE SPECIFIED LUMINAIRE PRIOR TO ORDERING

LUMINAIRES.

3. VERIFY THAT LUMINAIRES WILL NOT INTERFERE WITH REQUIRED CLEARANCES FOR EQUIPMENT INCLUDING FILTER PULL SPACE, NEC WORKING SPACE IN FRONT OF

DISCONNECTS, CONTROL PANELS, ETC.

4. COORDINATE EXIT LIGHT LOCATIONS WITH STRUCTURE AND BUILDING SYSTEMS TO INSURE EXIT SIGNS ARE VISIBLE.

5. PROVIDE GROUND WIRE AND ONE NEUTRAL CONDUCTOR PER CIRCUIT IN ALL LIGHTING CONDUIT.

6. LABEL ALL CIRCUIT BREAKERS SERVING EMERGENCY LIGHTING.

7. UNO, ALL EXIT SIGNS, EMERGENCY EGRESS PATHWAY LIGHT FIXTURES, LIGHTS NOTED "xE", AND LIGHTS SHOWN CROSS HATCHED SHALL BE CONNECTED TO THE SWITCHED AREA LIGHTING CIRCUIT FOR NORMAL OPERATION AND AN UNSWITCHED CIRCUIT FROM THE SAME OCPD TO AUTOMATICALLY CONTROL POWER TRANSFER TO AN INTEGRAL BATTERY PACK FOR 90 MINUTES OF EMERGENCY OPERATION WHEN LOSS OF NORMAL POWER IS SENSED ON THE UNSWITCHED CIRCUIT. PROVIDE A BATTERY

STATUS INDICATOR MOUNTED IN A VISIBLE LOCATION.

8. INSTALL FIXTURES PLUMB, SQUARE AND LEVEL WITH CEILINGS AND WALLS AND SECURE FIXTURES PER MANUFACTURER'S PRINTED INSTRUCTIONS.

9. ADJUST AIMABLE FIXTURES, CLEAN, AND PROVIDED ALL FIXTURES WITH LAMPS PRIOR TO OWNER OCCUPANCY.

10. U.N.O., LIGHTING SWITCHES IN ROOMS SHALL CONTROL ONLY FIXTURES IN THAT ROOM.

11. WHEN MORE THAN ONE(1) LIGHTING SWITCH IS SHOWN AT A LOCATION THEY SHALL BE GANGED TOGETHER.

12. LUMINAIRE WHIPS MAY BE FMC, 6FT MAX. SECURE TO STRUCTURE USING LISTED SUPPORTS.

13. EXIT SIGNS WITH BACKWARD LETTERING SHALL NOT BE PERMITTED ANYWHERE. SINGLE-SIDED EXIT SIGNS SHALL HAVE A BLANK BACK SIDE.

DOUBLE-SIDED EXIT SIGNS SHALL HAVE ENGLISH LETTERS "E X I T" THAT READ FROM LEFT-TO-RIGHT ON EACH SIDE.

LIGHTING CONTROL REQUIREMENTS

1. OCCUPANCY SENSOR OFF DELAY SHALL BE SET BY EC AT END OF PROJECT TO 20 MINUTES. AMBIENT LIGHT OVERRIDE SHALL BE SET SUCH THAT THE LUMINAIRES ARE SWITCHED OFF WHEN APPROPRIATE FC LEVEL IS MEASURED ON THE FLOOR (REGARDLESS OF THE FOOTCANDLES MEASURED AT THE OCCUPANCY SENSOR).

2. INSTALL DIMMER SWITCHES ON THE LOAD SIDE OF OCCUPANCY SENSORS AND OTHER CONTROLS.

GENERAL REQUIREMENTS

1. COMPLIANCE WITH THE REQUIREMENTS OF THE CONTRACT DOCUMENTS SHALL NOT RELIEVE THE CONTRACTOR OF THE RESPONSIBILITY OF PROVIDING EQUIPMENT THAT IS NEW, PROPERLY DESIGNED, FROM A REPUTABLE MANUFACTURER, AND IN FULL WORKING ORDER.

2. IF CONFLICTS BETWEEN THE SPECIFICATIONS AND DRAWINGS OCCUR, THE HIGHER QUALITY OR QUANTITY SHALL BE PROVIDED AND INSTALLED. WHEN CONFLICTS EXIST, CONTRACTOR SHALL PROVIDE A WRITTEN REQUEST FOR CLARIFICATION FROM THE ENGINEER. CONTRACTOR SHALL BE RESPONSIBLE FOR ANY ADDITIONAL EXPENSES

INCURRED AS A RESULT OF THE CONTRACTOR'S FAILURE TO OBTAIN CLARIFICATION.

3. ALL ELECTRICAL EQUIPMENT ENCLOSURES SHALL BE 16 GAUGE SHEET METAL (MIN). PROVIDED WITH MANUFACTURER'S CORROSION RESISTANT PAINT SYSTEM, PROVIDED WITH CONTINUOUSLY HINGED, LATCHING DOORS (UNO).

4. EQUIPMENT TO BE INSTALLED OUTDOORS SHALL HAVE NEMA 3R ENCLOSURES MIN. EQUIPMENT IN CORROSIVE OR HAZARDOUS ENVIRONMENTS SHALL BE RATED FOR THE

INTENDED USE.

5. CONDUCTORS AND CABLES SHALL BE THHN/THWN SOFT DRAWN, STRANDED COPPER, XHHW FOR UG, USE SOLID COPPER FOR #10 & SMALLER, MIN SIZE #12.

6. FULLY ENCLOSED RACEWAYS AND BOXES REQUIRED FOR ALL WIRING. TYPE REQUIRED IS BY LOCATION.

WIRING DEVICES

1. WIRING DEVICES SHALL BE COMMERCIAL GRADE (MIN), GROUNDING, AND RATED FOR LOAD (20A MIN). NOTE THAT SOME LOCATIONS REQUIRE WEATHER RATED, INDUSTRIAL

OR HEAVY DUTY, AND HOSPITAL GRADE DEVICES.

2. SURFACE MOUNTED RACEWAY FOR RECEPTACLES AND DATA OUTLETS SHALL BE DUAL CHANNEL, METAL RACEWAYS, TWO PIECE DESIGN WITH METAL BASE AND SNAP- ON METAL COVER. ASSEMBLED BASE AND COVER SHALL BE A MINIMUM OF 4" WIDE BY 1.5" DEEP. DEVICE BRACKETS AND COVER PLATES THAT WILL ACCEPT DUPLEX RECEPTACLES AND STANDARD DATA JACK MOUNTING PLATES WITHOUT FIELD CUTTING MUST BE AVAILABLE FROM THE RACEWAY MANUFACTURER.

ENCLOSED SWITCHES AND CONTACTORS

1. DISCONNECTS SHALL BE QUICK MAKE/BREAK LOAD INTERRUPTING KNIFE SWITCHES WITH EXTERNAL HANDLE LOCKABLE IN ON AND OFF POSITIONS, FULLY HINGED DOOR THAT IS LOCKED WHEN ENERGIZED AND PROVIDED WITH A DEFEATER MECHANISM TO OPEN ENCLOSURE WHEN ENERGIZED.

2. ENCLOSED MOTOR STARTERS SHALL HAVE REMOTE START SIGNAL INPUT, FULL SIZED OVERLOADS, CONTROL XFMR WITH PRIMARY & SECONDARY FUSING, HAND-OFF- AUTO SELECTOR SWITCH, (2) NORMALLY OPEN AND (2) NORMALLY CLOSED AUX. DRY CONTACTS. COORDINATE CPT VOLTAGE WITH CONTRACTOR PROVIDING EQUIPMENT

TO BE CONTROLLED.

LIGHTING

1. ALL LIGHT FIXTURES/LAMPS SHALL BE UL LISTED AND CONFORM TO ALL APPLICABLE UL, ANSI AND NFPA STANDARDS.

2. REFER TO LUMINAIRE SCHEDULE FOR FIXTURE, BALLAST, AND LAMP SPECIFICATIONS. SUBSTITUTIONS SHOULD BE APPROVED PRIOR TO BID.

PRODUCT SPECIFICATIONS:

GENERAL REQUIREMENTS

1. PROVIDE RACEWAY AND BOXES AS SPECIFIED BELOW FOR POWER, LIGHTING, COMMUNICATIONS, FIRE ALARM, ACCESS CONTROL/SECURITY, CONTROLS, AND OTHER

SPECIAL SYSTEMS.

2. PROVIDE RACEWAY AND BOXES FOR ALL EQUIPMENT; LIGHTING; WIRING DEVICES; COMMUNICATIONS EQUIPMENT AND OUTLETS; FIRE ALARM EQUIPMENT, APPLIANCES, AND DEVICES; ACCESS CONTROL/SECURITY POINTS; CONTROLS POINTS; AND OTHER SPECIAL SYSTEMS SHOWN ON PLANS.

3. PROVIDE RACEWAY BOXES AT OTHER LOCATIONS AS REQUIRED FOR SPLICES, TAPS, WIRE PULLING, EQUIPMENT CONNECTIONS, AND COMPLIANCE WITH REGULATORY REQUIREMENTS. RACEWAY AND BOXES ARE SHOWN IN APPROXIMATE LOCATIONS UNLESS DIMENSIONED. PROVIDE RACEWAY TO COMPLETE WIRING SYSTEM.

4. PROVIDE COMPRESSION CONNECTIONS FOR ALL METAL RACEWAYS.

IN CONCRETE

1. PROVIDE WRAPPED RIGID STEEL CONDUIT WHERE ENTERING OR EXITING CONCRETE; FOR ELBOWS 1" AND LARGER.

2. PROVIDE RIGID STEEL CONDUIT FOR STRAIGHT RUNS IN CONCRETE.

3. PROVIDE CAST METAL BOXES. NONMETALLIC MAY BE USED ONLY WITH ENGINEER APPROVAL.

4. USE CONCRETE TIGHT, MASONRY RATED BOXES AND FITTINGS WHERE INSTALLED IN CONCRETE, STONE, BRICK, CMU.

CONCEALED DRY INTERIOR LOCATIONS:

1. PROVIDE RIGID STEEL CONDUIT, INTERMEDIATE METAL CONDUIT, OR ELECTRICAL METALLIC TUBING.

2. PROVIDE SHEET-METAL BOXES.

EXPOSED DRY INTERIOR LOCATIONS:

1. PROVIDE RIGID STEEL CONDUIT BELOW 10 FT, AND RIGID STEEL, INTERMEDIATE METAL, OR ELECTRICAL METALLIC TUBING ABOVE 10 FT.

RACEWAY AND BOX SPECIFICATIONS BY LOCATION:

512.744.4400 main - 512.744.4444 fax www.eeace.com

EEA Project No.

State of registration Firm Registration No.

20250239

F-2497

TX

REVISIONS:

24-1053.00

DECEMBER 4, 2025

EXCEPT AS MAY BE OTHERWISE PROVIDED BY CONTRACT,

THESE DRAWINGS AND SPECIFICATIONS ARE PROPERTY

OF THE CLIENT LISTED, AND ARE ISSUED IN STRICT

CONFIDENCE AND SHALL NOT BE MADE AVAILABLE,

REPRODUCED, OR COPIED, OR USED FOR ANY OTHER

INTENDED PURPOSE, OR AS BASIS FOR MANUFACTURE OR

SALE OF APARATUS WITHOUT WRITTEN PERMISSION.

CONFIDENTIAL AND PROPRIETARY

SHEET NUMBER:

SHEET NAME:

PROJECT NUMBER:

ISSUE DATE:

SEAL(S) / CONSULTANT:

CLIENT / PROJECT NAME:

Criss Cole Rehabilitation

Center Generator

4800 N.Lamar Blvd. Austin, TX.

78756

24-1053.00

E1.0

EQUIPMENT SCHEDULES

1.

ATS SCHEDULE KEYNOTES:

SB - OPTIONAL STANDBY (NEC ART. 702)

LR - LEGALLY REQUIRED STANDBY (NEC ART. 701)

B. LOAD CLASS: EM - EMERGENCY/LIFE SAFETY (NEC ART. 700)

A. ENGINE EXERCISER: START ENGINE EVERY 7 DAYS; RUN FOR 30 MINUTES BEFORE SHUTTING DOWN. BYPASS EXERCISER CONTROL WHEN NORMAL SOURCE FAILS DURING EXERCISING PERIOD.

ATS SCHEDULE GENERAL...

ATS-SB CUMMINS 1400 3 208 3 4 65 SB 1 Y N O 1 15 60 15 5 30 N 1 N -

EN

G

IN

E

ST

A

R T

D

EL

A Y

(S

TR

A

N

SF

ER

D

EL

A

Y (S

M A

X.

T

O

TA

L

TI

M E

TO

TR

A N

SF

ER

(S

TR

A

N

SF

ER

T

O U

TI

LI

TY

(M

TE

ST

M O

D E

TR

A

N

SF

ER

T

O U

TI

LI

TY

(M

EN

G

IN

E

C O

O

LD

O W

N (M

EQ

U

IP

M

EN

T

M A

R K

B A

SI

S

O F

D

ES

IG

N

M A

N U

FA

C

TU

ER

SI

ZE

(A

PO

LE

S

VO

LT

A G

E

PH W

IR

E

W C

R (k

A

LO

A

D C

LA

SS

EN

C

LO

SU

R E

R A

TI

N

G (N

EM

A

B

YP

A

SS

/IS

O

LA

TI

O N

SE

R

VI

C

E

IN

TR

A

N C

E R

A

TE

D

O

PE

N (O

C

LO

SE

D (C

) T R

A N

SI

TI

O

N TIME SETTINGS FROM LOSS

OF UTILITY

TIME SETTINGS FROM

RESTORATION OF UTILITY

R

EM

O

TE

A N

N U

N C

IA

TO

R

SW

IT

C H

P R

IO

R

IT

Y

LE

VE

L

LO

A

D S

H

ED

K

EY

N O

TE

S

ATS SCHEDULE

1. VERTICAL DISCHARGE

GENERATOR SCHEDULE KEYNOTES:

WPS2 - WEATHER PROTECTIVE / SOUND ATTENUATED LEVEL 2 (75 dBA @ 23') WPS1 - WEATHER PROTECTIVE / SOUND ATTENUATED LEVEL 1 (88 dBA @ 23')

WP - WEATHER PROTECTIVE

G. ENCLOSURE TYPES: N - NONE

P - PROPANE

NG - NATURAL GAS

F. FUEL TYPES: D - DIESEL

E. SUB-BASE, DOUBLE WALL DAY TANK TO COMPLY WITH UL 142 OR UL 2085 FOR TANKS EXCEEDING 660 GALLONS

D. PROVIDE WITH THE FOLLOWING ACCESSORIES -FUEL FILTER, LUBE OIL FILTER, INTAKE AIR FILTER, LUBE OIL COOLER, FUEL TRANSFER PUMP, FUEL PRIMING PUMP, GEAR-DRIVEN WATER PUMP. FURNISH FUEL PRESSURE GAGE, WATER TEMPERATURE GAGE, AND LUBE OIL PRESSURE GAGE ON ENGINE/GENERATOR CONTROL PANEL.

C. GENERATOR SHALL COMPLY WITH ASME B15.1, UL 2200, NFPA 37, AND NFPA 110

B. ALL COMPONENTS, DEVICES, AND ACCESSORIES SHALL BE LISTED AND LABELED AS DEFINED BY NFPA 70.

A. SITE CONDITIONS: ALTITUTE 650', AMBIENT TEMP 110°F

GENERATOR SCHEDULE GENERAL...

GEN-1 CUMMINS 400 NG 208 3 4 Standby WPS2 96 10 2 3 H 125 Y Y Y Y Y N N Y 1400A N 1

C

LA

SS

TY

PE

LE

VE

L

EQ

U

IP

M

EN

T

M A

R K

B A

SI

S

O F

D

ES

IG

N

M A

N U

FA

C

TU

ER

C A

PA

C

IT

Y

(K W

FU

EL

T

YP

E

VO

LT

A G

E

PH W

IR

E

R A

TI

N

G

EN

C

LO

SU

R E

TY

PE

NFPA 110

REQUIREMENTS

EM

IS

SI

O

N S

TI

ER

IN

SU

LA

TI

O N

C

LA

SS

TE

M

PE

R

A

TU

R E

R

IS

E

F)

JA

C

K

ET

H

EA

TE

R

O

IL

/F U

EL

H

EA

TE

R

A N

TI

-C

O N

D

EN

SA

TI

O N

H

EA

TE

R

B A

TT

ER

Y H

EA

TE

R

B A

TT

ER

Y C

H A

R G

ER

R

EM

O

TE

A N

N U

N C

IA

TO

R

SE

PR

A

TE

LY

D

ER

IV

ED

S

YS

TE

M

G R

O U

N D

F A

U

LT

M O

N

IT

O R

IN

G

O U

TP

U

T C

IR

C

U

IT

B R

EA

K

ER

(S

LO

A

D B

A N

K

K

EY

N O

TE

S

GENERATOR SCHEDULE

101660.05

Iron Rod Set

Storage

ETR

MSB

ATS-SB

1 GENERATOR GEN-1 2

4 5

SUNSHINE DRIVE

ETR

UTILITY

XFMR

ETR

METER

7300 FM 2222, Bldg. 2, Ste. 2 Austin, Texas 78730-2314 USA

512.744.4400 main - 512.744.4444 fax www.eeace.com

EEA Project No.

State of registration Firm Registration No.

20250239

F-2497

TX

REVISIONS:

24-1053.00

DECEMBER 4, 2025

EXCEPT AS MAY BE OTHERWISE PROVIDED BY CONTRACT,

THESE DRAWINGS AND SPECIFICATIONS ARE PROPERTY

OF THE CLIENT LISTED, AND ARE ISSUED IN STRICT

CONFIDENCE AND SHALL NOT BE MADE AVAILABLE,

REPRODUCED, OR COPIED, OR USED FOR ANY OTHER

INTENDED PURPOSE, OR AS BASIS FOR MANUFACTURE OR

SALE OF APARATUS WITHOUT WRITTEN PERMISSION.

CONFIDENTIAL AND PROPRIETARY

SHEET NUMBER:

SHEET NAME:

PROJECT NUMBER:

ISSUE DATE:

SEAL(S) / CONSULTANT:

CLIENT / PROJECT NAME:

Criss Cole Rehabilitation

Center Generator

4800 N.Lamar Blvd. Austin, TX.

78756

24-1053.00

E3.0

ELECTRICAL PLANS

8' 16'4'0 1/8" = 1'-0"E3.0

1 ELECTRICAL PLAN

NEW WORK…