7-10-02-2026 0571405975-EE-Combined Final.pdf
PDF 7 MB Posted
- Attached to
- 2026 Pump Station Improvements Project
- Solicitation number
- US.256212
- Issued by
- Lancaster County, Pennsylvania
About this file
This file comprises combined engineering drawings and utility coordination documentation prepared by RETTEW ASSOCIATES, INC. for the Upper Leacock Township Municipal Authority's 2026 Pump Station Improvements project located in Pennsylvania. The project encompasses electrical, mechanical, and site improvements across four pump stations: Bareville, Hertzog, Glenn Brook, and Apricot. Key scope elements include installation of new aeration systems with blower motors and control panels, replacement of emergency generators (50KW capacity), automatic transfer switches, intake louver motorized dampers with controls, new gas piping and fuel systems, flow meter relocation with electrical connections, and associated conduit and power distribution modifications. The utility coordination response deadline was October 1, 2026, with responses received from PPL Electric Utilities Corporation, UGI Utilities Inc., Buckeye Partners, Comcast/Cable Protection Services Inc., Frontier Communication of PA Inc., and Upper Leacock Township Municipal Authority. The project must be substantially completed within 240 calendar days of the Notice to Proceed, with sealed bids due on November 5, 2026 at 10:00 AM online through PennBID. A voluntary pre-bid meeting and site visit is scheduled for October 29, 2026 at 10:00 AM at 161 Newport Road, Leola, PA 17540.
Bidders must submit a certified check or bid bond equivalent to 10% of the total bid amount, with bonds to be issued by a surety licensed in the Commonwealth of Pennsylvania. The successful bidder shall furnish performance and payment bonds in the amount of 100% of the contract price. All bidders must bid on all items listed on the Bid Form, and bids shall remain open for 60 days from the date of opening, or 120 days if award is delayed by required governmental approvals, bond sales, or grant awards. The project is subject to Pennsylvania Prevailing Wage Act conditions, Federal OSHA requirements, Pennsylvania Act 229 of 2002, the Pennsylvania One Call Act (Act 287 of 1974, as amended), and Pennsylvania Human Relations Act provisions. The drawings indicate that coordination of electrical work is required with mechanical contractors, general contractors, and equipment vendors, and the contractor must maintain pump station operations during construction to minimize service outages.
View the file
Other files
Show all 12
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ONE CALL SYSTEM SERIAL NUMBER:
PA ONE CALL UNDERGROUND UTILITY PROTECTION ACT
PURSUANT TO THE PROVISIONS OF ACT NO. 287 OF 1974, AS AMENDED BY ACT
187 OF 1996, ACT 181 OF 2006, ACT 160 OF 2016 AND ACT 50 OF 2017 OF THE
PENNSYLVANIA STATE LEGISLATURE, RETTEW ASSOCIATES, INC. HAS
PERFORMED THE FOLLOWING IN PREPARING THESE DRAWINGS REQUIRING
EXCAVATION OR DEMOLITION WORK AT SITES WITHIN THE POLITICAL
SUBDIVISION(S) SHOWN ON THE DRAWINGS:
1. PURSUANT TO SECTION 4, CLAUSE (2) OF SAID ACT, RETTEW
ASSOCIATES, INC. REQUESTED FROM EACH FACILITY OWNER
DESIGNATED ON SUCH LIST PROVIDED BY THE ONE CALL SYSTEM
NOTIFICATION, THE INFORMATION PRESCRIBED BY SECTION 2, CLAUSE
(4) OF SAID ACT, NOT LESS THAN TEN (10) NOR MORE THAN NINETY (90)
BUSINESS DAYS BEFORE FINAL DESIGN IS TO BE COMPLETED.
2. PURSUANT TO SECTION 4, CLAUSE (5) OF SAID ACT, RETTEW
ASSOCIATES, INC. HAS MET THEIR OBLIGATIONS OF CLAUSE (2) BY
CALLING THE PENNSYLVANIA ONE CALL SYSTEM SERVING THE
LOCATION WHERE THE WORK IS TO BE PERFORMED, AND SHOWING
THE ASSOCIATED SERIAL NUMBER(S) ON THIS/THESE DRAWING(S).
3. PURSUANT TO SECTION 4, CLAUSE (3) OF SAID ACT, RETTEW
ASSOCIATES, INC. HAS SHOWN UPON THIS/THESE DRAWING(S) THE
POSITION AND TYPE OF EACH FACILITY, AS DERIVED PURSUANT TO THE
REQUEST MADE AS REQUIRED BY CLAUSE (2),
4. PURSUANT TO SECTION 4, CLAUSE (5) OF SAID ACT, RETTEW
ASSOCIATES, INC. HAS SHOWN UPON THIS/THESE DRAWING(S) THE
TOLL-FREE NUMBER FOR THE ONE CALL SYSTEM AND THE SERIAL
NUMBER(S) FOR THE ASSOCIATED ONE CALL SYSTEM NOTIFICATION(S),
ADDITIONALLY, RETTEW ASSOCIATES, INC. DOES NOT MAKE ANY
REPRESENTATION, WARRANTY, ASSURANCE OR GUARANTEE THAT THE
INFORMATION RECEIVED PURSUANT TO SAID REQUEST, AND AS REFLECTED ON
THIS/THESE DRAWING(S), IS CORRECT OR ACCURATE. INFORMATION REFLECTED
ON THIS/THESE DRAWING(S) IS SHOWN AS REQUIRED BY SAID ACT NO. 160 OF
2016, AND AS PROVIDED BY THE FACILITY OWNER PURSUANT TO SECTION 2,
CLAUSE (4) OF SAID ACT.
DATE:
CALL BEFORE YOU DIG!
PENNSYLVANIA LAW REQUIRES THREE (3) WORKING
DAYS NOTICE FOR CONSTRUCTION PHASE AND TEN (10)
WORKING DAYS IN DESIGN STAGE - STOP CALL1-800-242-1776
IT IS THE CLIENT'S RESPONSIBILITY TO NOTIFY RETTEW NO LESS THAN 10 DAYS AND NO
MORE THAN 90 DAYS PRIOR TO THE CONSTRUCTION BEGIN DATE. THIS NOTIFICATION
WILL ALLOW US TO UPDATE THE PA811 ONE CALL TICKETS ASSOCIATED WITH THIS
PROJECT, WHICH IS A REQUIREMENT UNDER ACT 287.
Response Due Date: 10/01/26 Survey Review Completed by: Date:
UTILITY/COMPANY
RESPONSE RCVD
(select one) TICKET #
RETTEW ACTION
Map/No Map
CONTACT
NAME
CONTACT
CONTACT
PHONE
KARL Auto Response
Electric PPL Elecdtric Utilities Corporation 20262603608 Pamela Seitzer pdseitzer@pplweb.com (570) 368-5394
20262603704 20262603749 20262603806
Gas
UGI Utilities Inc 9/24/26 20262603608 Geoffrey Ferguson gferguson@ugi.com (610) 807-3118
9/24/26 20262603704 Luke MacNair macnairl@ugi.com (717) 413-1080
20262603749
20262603806
Buckeye Partners 9/17/26 Clear 20262603704 Brian Barr bbarr@buckeye.com (610) 904-4156
Communication Comcast/Cable Protection Servcies Inc 9/17/26 Clear 20262603608 Debbie King debbie_king@cableps.com (804) 562-3409
9/17/26 20262603704 9/17/26 20262603749 9/17/26 20262603806
Frontier Communication of PA Inc 20262603608 Michael Navich Michael.Navich@FTR.com (570) 208-3375
20262603749 20262603806
Water/Sewer Upper Leacock Twp Municipal Authority/Upper Leacock Twp 20262603608 Robert Fricke rfricke@ultwp.com (717) 656-9755
20262603704 ext. 532 20262603749 20262603806
Upper Leacock TMA/Upper Leacock Twp 20262603608 Derek Martin dmartin@ultwp.com (717) 656-9755
20262603704 ext. 554 20262603749 20262603806
S
12FS
CF
S
FM
SS
E
E
PIPING TRENCH DETAIL
ELECTRICAL SYMBOL LEGEND
2x2 LED LAY-IN FIXTURE WITH
NORMAL/EMERGENCY SINGLE RECEPTACLE
2x4 LED LAY-IN FIXTURE
WITH NORMAL/EMERGENCY SPECIAL PURPOSE RECEPTACLE
INDUSTRIAL LED FIXTURE DUPLEX RECEPTACLE
LINEAR INDUSTRIAL LED WITH
NORMAL/EMERGENCY
DUPLEX RECEPTACLE WITH
WEATHER PROOF COVER, GFCI
EXTERIOR LED WALL PACK DUPLEX RECEPTACLE, ABOVE
COUNTER BACKSPLASH MOUNTED
EXTERIOR LED AREA FIXTURE DUPLEX RECEPTACLE, GFCI
DOWNLIGHT DUPLEX RECEPTACLE WITH
USB PORTS
EMERGENCY BATTERY UNIT DUPLEX RECEPTACLE, GFCI, ABOVE
COUNTER BACKSPLASH MOUNTED
EMERGENCY REMOTE HEADS DUPLEX RECEPTACLE TAMPER
RESISTANT
EXIT SIGN DIRECTIONAL
ARROW AS REQUIRED QUADRUPLEX RECEPTACLE
EXIT SIGN DIRECTIONAL
ARROW AS REQUIRED
DUPLEX RECEPTACLE CEILING
MOUNTED
EXIT SIGN WITH HEADS DUPLEX RECEPTACLE FLOOR
MOUNTED
120/208V PANELBOARD
480/277V PANELBOARD
DUPLEX RECEPTACLE FLOOR
MOUNTED WITH DATA OUTLET
FIRE ALARM CONTROL PANEL DATA OUTLET - (#) DENOTES NUMBER
OF CABLE DROPS/OUTLET JACKS
WIRELESS ACCESS POINT VARIABLE FREQUENCY DRIVE
MOTION DETECTOR - CEILING
MOUNTED/WALL MOUNTED GROUND ROD/TEST WELL
CALL SWITCH MOTOR OPERATED DAMPER
CHECK-IN CALL SWITCH PUSHBUTTON CONTROL FOR
OVERHEAD DOOR
PUBLIC ANNOUNCEMENT HORN SECURITY CAMERA
HEAT TRACE DOOR CONTACT
POWER POLE FIRE ALARM/SECURITY KEYPAD
JUNCTION BOX/CONNECTIONS FIRE ALARM KNOX BOX
OCCUPANCY SENSOR POWER PACK FIRE ALARM PULL STATION
MOTOR FIRE ALARM HORN/STROBE
CEILING/WALL MOUNTED
DISCONNECT SWITCH FIRE ALARM STROBE
CEILING/WALL MOUNTED
MOTOR STARTER WITH
DISCONNECT SWITCH
FIRE ALARM SPEAKER
CEILING/WALL MOUNTED
LIGHTNING PROTECTION FIRE ALARM SMOKE DETECTOR
CEILING/WALL MOUNTED
MOTOR RATED SWITCH
CARD READER FIRE ALARM SMOKE/CO DETECTOR
CEILING/WALL MOUNTED
CEILING CORD DROP HEAT DETECTOR
NOT ALL SYMBOL UTILIZED ON PROJECTS
WP
GFCI
C
GFCI
USB
C
GFCI
TR
FACP #
W VFD
M M
CS M
CCS
PA
HT DC
PP K
J K
P F
FF
F FF
S S
L S S
S M
CR S S
CO CO
CD H
ELECTRICAL GENERAL NOTES
· COORDINATE INSTALLATION OF NEW ITEMS AND EQUIPMENT WITH THE OWNER'S REPRESENTATIVE, MAINTENANCE
STAFF, AND THE WORK OF OTHER CONTRACTORS. THE CONTRACTOR SHALL INCUR ALL COSTS ASSOCIATED WITH THE RELOCATION OF EQUIPMENT CONFLICTING WITH NEW WORK OF OTHER DISCIPLINES THAT HAS NOT BEEN
COORDINATED.
· FIELD VERIFY ALL DIMENSIONS. DRAWINGS ARE ILLUSTRATIVE AND MAY NOT REFLECT EXACT CONDITIONS OR
DIMENSIONS.
· DO NOT SCALE THE DRAWINGS. DRAWINGS ARE DIAGRAMMATIC AND SHOW THE GENERAL ARRANGEMENT OF EQUIPMENT AND SYSTEMS. THEY ARE NOT INTENDED TO SHOW EVERY OFFSET, FITTING, AND COMPONENT. DO NOT USE THE PLANS FOR EXACT LOCATIONS OF EQUIPMENT, FIXTURES, OR ARCHITECTURAL ITEMS SUCH AS WALLS, WINDOWS, SOFFITS, AND PILASTERS. SPECIFIC LOCATIONS,MOUNTING HEIGHTS AND OVERALL DIMENSIONS OF DEVICES AND FIXTURES ARE TO BE OBTAINED FROM THE ARCHITECTURAL DRAWINGS AND DETAIL WHEN AVAILABLE.
· DRAWINGS SPECIFIC TO THIS TRADE DO NOT LIMIT THE RESPONSIBILITY OR WORK REQUIRED BY THE CONTRACT DOCUMENTS. REFER TO DRAWINGS AND SPECIFICATIONS OF OTHER TRADES FOR COMPLETE INFORMATION PRIOR TO BID. COORDINATE FINAL ELECTRICAL AND CONTROL CONNECTIONS WITH APPROVED VENDOR EQUIPMENT
SUBMITTALS BEFORE COMPLETING WORK.
· WHERE CONFLICTS EXIST AMONG DRAWINGS, SPECIFICATIONS, AND EQUIPMENT SCHEDULES, THE MOST STRINGENT SHALL APPLY. NOTIFY THE ENGINEER/ARCHITECT OF ALL CONFLICTS FOR RESOLUTION OR INTERPRETATION.
· NOTIFY THE OWNER IN WRITING AND FIELD VERIFY CONDITIONS BEFORE PERFORMING ANY SAWCUTTING, TRENCHING, CORING, OR ANY OTHER STRUCTURAL MODIFICATIONS. ENSURE THAT NO ADVERSE EFFECT TO THE BUILDING'S
STRUCTURAL INTEGRITY WILL OCCUR.
· ALL FLOOR MOUNTED ELECTRICAL EQUIPMENT SHALL BE MOUNTED ON A CONCRETE PAD BY THE EC. THE PAD SHALL
BE 3" HIGH WITH CHAMFERED EDGES AND SHALL EXTEND 2" BEYOND EDGES OF EQUIPMENT.
· BRANCH CIRCUIT SIZING FROM DISCONNECT, STARTER OR VFD, OR CONTROL PANEL TO MOTOR/EQUIPMENT SHALL MATCH WHAT IS SHOWN FROM MCC/PANELBOARD TO DISCONNECT, STARTER OR VFD, OR CONTROL PANEL UNO.
MOTOR BRANCH CIRCUITS FED FROM VFD SHALL BE VFD CABLE IN APPROPRIATELY SIZED CONDUIT.
· ALL EQUIPMENT INSTALLED WITHIN AREAS THAT ARE LISTED AS CLASSIFIED AREAS SHALL BE UL LISTED AND LABELED FOR INSTALLATION IN THAT AREA. ALL CONDUIT TRANSITIONING FROM CLASSIFIED AREAS TO UNCLASSIFIED AREAS
SHALL HAVE PROPER SEAL-OFF FITTINGS.
· ALL WORK SHOWN IN BOLD IS NEW WORK OR MODIFICATION OF EXISTING INSTALLATIONS TO BE COMPLETED BY THE CONTRACTOR UNDER THIS PROJECT. SEE PROJECT SPECIFICATIONS AND SEQUENCE/PHASING OF WORK FOR THIS PROJECT. CONTRACTORS SHALL READ AND UNDERSTAND THE REQUIREMENTS BEFORE SUBMITTING BID OR
COMPLETING CONTRACTOR WORK.
EXHAUST OR RELIEF AIR DUCT RISER
SUPPLY AIR DUCT RISER
RETURN AIR DUCT RISER
ROOFTOP EXHAUSTER
ROOFTOP INTAKE HOOD
ROOFTOP RELIEF HOOD
EXHAUST GRILLE OR REGISTER
RETURN GRILLE OR REGISTER
4-WAY CEILING DIFFUSER OR REGISTER
2-WAY CEILING DIFFUSER
2-WAY CORNER CEILING DIFFUSER
3-WAY CEILING DIFFUSER
MITERED ELBOW W/ TURNING VANES
FLEXIBLE CONNECTION
FIRE DAMPER (FD)
MANUAL VOLUME DAMPER
THERMOSTAT
EMERGENCY BURNER SHUT-OFF SWITCH
HUMIDISTAT
MOTOR OPERATED DAMPER
CONTROL SWITCH
DUCT SMOKE DETECTOR
CARBON MONOXIDE SENSOR
NITROGEN DIOXIDE SENSOR
DOOR LOUVER, SEE ARCH. DWGS.
DOOR UNDERCUT, SEE ARCH. DWGS.
EXISTING WORK
DEMOLITION WORK
NEW WORK
CONNECT TO EXISTING
DISCONNECT FROM EXISTING
HVAC SYMBOL LEGEND
12x20
UP
T
S B
H
M
S
D
DL
DU
S R
CO
NO
DUCT (1ST FIGURE, SIDE SHOWN;
2ND FIGURE, SIDE NOT SHOWN)
INCLINED RISE (UP) OR DROP (DN) ARROW
IN DIRECTION OF AIR FLOW
STANDARD BRANCH FOR SUPPLY &
RETURN (NO SPLITTER)
MITERED ELBOW W/O TURNING VANES
(USE ONLY WHERE SHOWN)
FIRE SMOKE DAMPER (FSD)
SMOKE DAMPER (SD)
E UNDERGROUND ELECTRICAL CONDUIT
ELECTRICAL ABBREVIATIONS
A AMPERES
AC ALTERNATING CURRENT
AB ABOVE
AFF ABOVE FINISH FLOOR
AFG ABOVE FINISH GRADE
AHJ AUTHORITY HAVING JURISDICTION
AL ALUMINUM
ARCH ARCHITECTURAL
BEL BELOW
BFF BELOW FINISH FLOOR
BFG BELOW FINISH GRADE
BLDG BUILDING
C CONDUIT
CLG CEILING
DC DIRECT CURRENT
DEG,° DEGREE
DIA., ∅ DIAMETER
DISC DISCONNECT
DN DOWN
DWG DRAWING
EC ELECTRICAL CONTRACTOR
EF EXHAUST FAN
ETR EXISTING TO REMAIN
EX, (E) EXISTING
F FUSE
FLA FULL LOAD AMPERES
GC GENERAL CONTRACTOR
GFCI GROUND FAULT CIRCUIT INTERRUPTER
GRD GROUND
H HIGH
HP HORSEPOWER
IN, " INCHES
INS INSULATION
KW KILOWATTS
LB, # POUNDS
MAX MAXIMUM
MC MECHANICAL CONTRACTOR
MCA MINIMUM CIRCUIT AMPACITY
MCC MOTOR CONTROL CENTER
MH MANHOLE
MOD MOTOR OPERATED DAMPER
MFR MANUFACTURER
MIN MINIMUM
MTD, MTG MOUNTED, MOUNTING
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NUMBER
OC ON CENTER
P POLE
PC PLUMBING CONTRACTOR
PH PHASE
PWR POWER
SCH SCHEDULE
SEC SECONDARY
SHLD SHIELDED
S&C STUB AND CAP
SF SQUARE FEET
SPEC SPECIFICATIONS
SN SOLID NEUTRAL
SS STAINLESS STEEL
SW SWITCH
T TOE SPACE MOUNTED
TEMP TEMPERATURE
THRU THROUGH
TYP TYPICAL
UNO UNLESS NOTED OTHERWISE
V VOLTS
VFD VARIABLE FREQUENCY DRIVE
W WATTS, WIRE
WL WET LOCATION
WP WEATHERPROOF
XFMR TRANSFORMER
-0
5-
SS
(E) MOTOR OPERATED INTAKE LOUVER
(E) A
(E) A
(E) GENERATOR LINE BREAKER
(E) TELEMETERING ALARM EQUIPMENT
(E) WP
GFCI
(E)(E)
(E) GRAVITY OPERATED
EXHAUST LOUVER
(E) ODOR CONTROL MOTOR
(E) EXHAUST DUCT
(E) A
(E) A
(E) 55KW EMERGENCY
GENERATOR
(E) PUMP CONTROL PANEL
(E) PANEL "L"
(E) UNIT HEATER 5KW,
240V - 1Ø
(E) TRANSFER SWITCH
(E) MAIN BREAKER
(E) BATTERY CHARGER
(E) TL
(E) B
GENERATOR BUILDING PLAN - BAREVILLE
SCALE: NONE
E
1. CONTRACTOR SHALL EXTEND 1"C AND CONDUCTORS FROM NEW AERATION SYSTEM CONTROL PANEL TO EXISTING JUNCTION BOX AND EXISTING 2" CONDUIT FOR PATHWAY BACK TO GENERATOR BUILDING AND PANEL. PROVIDE SEAL OFF FITTINGS AT EACH VERTICAL CONDUIT RUN FROM UNDERGROUND PATHWAY. CONTRACTOR SHALL ROUTE POWER AND CONTROL CIRCUITS IN SEPARATE SHIELDED CABLE CONSTRUCTION AS SHOWN IN NEW AND EXISTING 2" C.
2. CONTRACTORS SHALL EXTEND 3/4"C AND CONDUCTORS FROM EACH AERATION SYSTEM CP TO AERATION SYSTEM BLOWER MOTOR. PROVIDE RATED FLEXIBLE WHIP CONDUIT AT BLOWER AND SEAL OFF FITTING AT CONDUIT VERTICAL RUN BELOW CP. COORDINATE CONDUIT ROUTE TO AERATOR EQUIPMENT AND MAINTENANCE POINTS ON UNIT.
3. CONTRACTOR SHALL ROUTE (4) #14 CU CONDUCTORS FROM AERATION BLOWER CP TO EXISTING DUPLEX PUMP CONTROL PANEL FOR "PUMP RUN" INTERLOCK TO CONTROL PANEL. CONTRACTOR SHALL PROVIDE 1" C FROM CONTROL PANEL TO
EXISTING J-BOX AS PATHWAY.
PLAN NOTES
SCALE: 1/8" = 1'-0"
LP-15,17
ELECTRICAL SITE PLAN - BAREVILLE PUMP STATION
NOTE 3
NOTE 1
NOTE 2
-0
5-
FRONT VIEW
FINISHED GRADE
NO SCALE
A
E-03
(E) PUMP STATION CONTROL PANEL
NOTES:
1. ADD 2P 15 240V ENCLOSED CIRCUIT BREAKER TO INTERIOR OF EXISTING
CABINET FOR AERATION BLOWER CONTROL PANEL. CONNECT ECB LINE
SIDE TO POWER TERMINAL BLOCK WITH (2) #12 AND #12 GROUND. EXTEND (2)
#12 AND #12G IN 3/4"C FROM EWB TO AERATION CONTROL PANEL.
NO SCALE
B
E-03
INTERIOR PHOTO - (E) PUMP STATION CONTROL PANEL
1. CONTRACTOR SHALL EXTEND 1"C AND CONDUCTORS FROM NEW AERATION SYSTEM CONTROL PANEL TO NEW ENCLOSED CIRCUIT BREAKER AT PUMP STATION CONTROL PANEL. PROVIDE SEAL OFF FITTINGS AT EACH VERTICAL
RUN FROM UNDERGROUND PATHWAY.
2. CONTRACTORS SHALL EXTEND 3/4"C AND CONDUCTORS FROM EACH AERATION SYSTEM CP TO AERATION SYSTEM BLOWER MOTOR. PROVIDE RATED FLEXIBLE WHIP CONDUIT AT BLOWER AND SEAL OFF FITTING AT CONDUIT VERTICAL RUN BELOW CP. COORDINATE CONDUIT ROUTE TO AERATOR EQUIPMENT AND MAINTENANCE POINTS ON UNIT.
3. CONTRACTOR SHALL EXTEND 1"C AND FLOW METER CABLE FROM NEW VALVE/METER VAULT FOR RELOCATED FLOW.
FLOW METER TO PUMP STATION CONTROL PANEL REMOTE FLOW METER INDICATING TRANSMITTER. PROVIDE SEAL OFF FITTINGS AT EACH VERTICAL RUN FROM UNDER GROUND PATHWAY. THE CONTRACTOR SHALL ELECTRICALLY DISCONNECT EXISTING FLOW FLOW METER AT EXISTING VAULT FOR RELOCATION BY GC. RECONNECT ELECTRICALLY AT
NEW VALVE/METER VAULT.
4. CONTRACTOR SHALL ROUTE (4) #14 CU CONDUCTORS IN 3/4" C FROM AERATION BLOWER CP TO EXISTING DUPLEX PUMP
CONTROL PANEL FOR "PUMP RUN: INTERLOCK TO CP.
PLAN NOTES
SCALE: 1/8" = 1'-0"
UE
UE
UE
NOTE 2
NOTE 3
NOTE 1
ELECTRICAL SITE PLAN - HERTZOG PUMP STATION
NOTE 4
-0
5-
(E) A
S (E) FOR TYPE 'A' LIGHTS
(E) FOR TYPE 'B' LIGHTS
(E) WP
GFCI
(E) TIME SWITCH AND STARTER
(E) B
(E)
(E) PANEL 'L'
(E) TELEMETERING
ALARM EQUIPMENT
(E) DUPLEX PUMP CONTROL PANEL
M
(E) PUMP CONTROL PANEL CIRCUIT BREAKER
(E) 200 AMP, SELF-CONTAINED RATE METER
(E)
(E) TL
(E)
(E) MOTOR OPERATED INTAKE LOUVER
AND CONTROLS. SEE SCHEMATIC
(E) BATTERY CHARGER
(E) GRAVITY OPERATED
EXHAUST LOUVER
ELECTRICAL FLOOR PLAN - GLENN BROOK
SCALE: 1/4" = 1'-0"
(E) 5 KW UNIT HEATER
240V, 1Ø WITH CORD
AND CORD ASSEMBLY
S
AUTOMATIC TRANSFER SWITCH
50KW GENERATOR
L-21,23
WET WELL AERATION
BLOWER CP
(E) MAGMETER INDICATING
TRANSMITTER
ENVIREP PRO-AIR WET WELL
AERATION SYSTEM (2 H.P.)
MOUNTED ON CONCRETE PAD
(E) MAIN CIRCUIT BREAKER
(E) ODOR CONTROL
(E) GRAVITY OPERATED
EXHAUST LOUVER
EMERGENCY GENERATOR
MECHANICAL FLOOR PLAN - GLENN BROOK
SCALE: 1/4" = 1'-0"
(E) 5 KW UNIT HEATER 240V, 1Ø
WITH CORD AND CORD ASSEMBLY
(E) WATER CLOSET TO REMAIN
(E) MOP SINK TO REMAIN
(E) EYEWASH AND SHOWER TO REMAIN
1 1/2" FROM METER TO
APPLIANCE REGULATOR
REPLACE (E) METER FOR NEW
CONNECTED LOAD. COORDINATE
INSTALLATION WITH UGI. (6'-8" W.C.,
919 MBH CONNECTED LOAD, 25'-0"
DEVELOPED LENGTH)
(E) GAS UP TO UNIT HEATER
PROVIDE NEW MAXITROL
325-9 APPLIANCE REGULATOR
ANCHOR BOLTS
(TYPICAL)
FLEXIBLE FUEL LINES
GAS CONTROL VALVE
PRIMARY REGULATOR
MANUAL SHUT-OFF
VALVE
2'-0"
FINISHED GRADE
VENT LINE WITH INSECT
SCREEN ON OPEN END
FLEXIBLE EXHAUST CONNECTOR
ALUMINUM EXHAUST DUCT
GRAVITY EXHAUST LOUVER
16" MAX.
BLACK IRON EXHAUST PIPE
NATURAL GAS EMERGENCY
GENERATOR
CONDENSATION TRAP
WITH PETCOCK DRAIN
PIPE ENLARGER
(IF REQIURED)
GAS CARBURETOR
SEAMLESS FLEXIBLE
EXHAUST TUBING
1/2" PETCOCK
DRAIN
" M
IN
SLOPE 1/4" PER FEET
30°
PIPE SLEEVE AND GUARD
METAL PIPE HANGER (TYPICAL)
2"x2"x1/4" ANGLE (TYPICAL)
2x6 (TYPICAL)
1200° INSULATION WRAPPED
AROUND MUFFLER AND PIPING
EXHAUST MUFFLER
NO SCALE
A
E-04
FUEL AND EXHAUST SYSTEM DETAIL GAS GENERATOR
HINGED ACCESS PANEL
FROM GAS METER
FU
6A
FU
6A
INTAKE DAMPER
LIMIT SWITCH
120V FROM A.T.S.
EMERG. SOURCEL-9
TD
TIME DELAY RELAY ADJ.
0-45 SEC. ON DELAY
CONTROL RELAY
D.P.D.T., 10 AMP
CONTACTS
INTAKE LOUVER
DAMPER MOTOR
(POWER OPEN,
SPRING CLOSE)
CR
CR
OPEN CLOSE
XO
THERMOSTAT
CLOSES ON
RISE IN TEMP.
70°-140° RANGE
- TERMINAL POINTS
CR
N
TD
TO ALARM PANEL
"GENERATOR LOUVER FAILURE"
SCALE: 3/4" = 1'-0"
B
E-04
EXISTING INTAKE LOUVER CONTROL SCHEMATIC
(E) DUPLEX
PUMP PANEL
PROVIDE
4#1/0, #6 GND
IN 1 1/2" C
4#14 IN 3/4" C FROM
AUXILLIARY CONTACTS ON
ATS TO ALARM PANEL FOR
POWER FAILURE ALARM
PROVIDE NEW 260A AUTOMATIC
TRANSFER SWITCH
(E) PANEL L
G2
NEW 50KW, 63KVA, 120/240V,
3PH, 4W GENERATOR AND
200A CIRCUIT BREAKERM
(E) 120/240V, 3PH,
4W SERVICE BY PPL
(E) 225AF/200AT 3P MAIN
CIRCUIT BREAKER TO REMAIN
EXTEND
EXISTING
WIRE/CONDUIT
3#4 + #8 GND IN
1 1/2" C
NEW PULL BOX
SIZED FOR TAP
(E) PPL METER
NO SCALE
C
E-04
ONE-LINE DIAGRAM
(E) CONDUCTOR CONDUIT
PROVIDE 4, #3/0,
#6 GND IN 2" C
SPD
(E)20HP
CP
AERATION
3#10, #10 GRD IN 3/4"C
2#10, #10 GRD
IN 3/4"C
NEW 30A
ECB
4#3/0, #6 GRD IN 2"C
(E) LOUVER
CONTROL PANEL
15A ECB
CP
2#14 IN 3/4"C FROM CP CTRL RELAY
TO INTAKE LOUVER CTRL "OPEN"
2#14 IN 3/4"C FROM CP CTRL RELAY
TO ALARM PANEL FOR GENERATOR
COMMON ALARM
(E)20HP
KEYED NOTES
1 CONTRACTOR SHALL DISCONNECT AND REMOVE EXISTING GENERATOR AND REPLACE WITH NEW GENERATOR AS SHOWN.
CONTRACTOR SHALL REVIEW EXISTING CONDITIONS WITH CONCRETE PAD, ELECTRICAL CONNECTIONS, AND CONDUIT ROUTES FOR COORDINATION WITH NEW GENERATOR AND ATS SWITCH REPLACEMENT IN SAME LOCATIONS. REUSE/REWORK EXISTING CONCRETE PAD FOR NEW GENERATOR OR REPLACE. COORDINATE ALL WORK WITH OWNER DURING CONSTRUCTION TO MINIMIZE OUTAGES AS PUMP STATION MUST REMAIN ONLINE DURING CONSTRUCTION.
2 CONTRACTOR SHALL DISCONNECT EXISTING EXHAUST DUCT SHEET METAL AND NATURAL GAS CONNECTIONS TO FACILITATE THE INSTALLATION OF THE NEW GENERATOR. PROVIDE NEW EXHAUST DUCT SHEET METAL AND FLEXIBLE CONNECTOR FROM NEW GENERATOR AS REQUIRED. PROVIDE NEW GAS PIPING AND CONNECTIONS AS SHOWN. PROVIDE
GENERATOR ENGINE EXHAUST PIPING AND INSULATION.
3 CONTRACTOR SHALL DISCONNECT AND REWORK EXISTING BATTERY CHARGING LEADS FROM FROM EXISTING GENERATOR
BATTERY CONNECTIONS AND RECONNECT TO NEW BATTERY ON NEW GENERATOR
4 CONTRACTORS SHALL EXTEND 3/4"C AND CONDUCTORS FROM EACH AERATION SYSTEM CP TO AERATION SYSTEM BLOWER MOTOR. PROVIDE RATED FLEXIBLE WHIP CONDUIT AT BLOWER AND SEAL OFF FITTING AT CONDUIT VERTICAL RUN BELOW CP. COORDINATE CONDUIT ROUTE TO AERATOR EQUIPMENT AND MAINTENANCE POINTS ON UNIT.
5 CONTRACTOR SHALL ROUTE (4) #14 CU CONDUCTORS IN 3/4" C FROM AERATION BLOWER CP TO EXISTING DUPLEX PUMP
CONTROL PANEL FOR "PUMP RUN: INTERLOCK TO CP.
6 CONTRACTOR SHALL DISCONNECT ELECTRICAL OPERATOR AT EXISTING MOTOR OPERATED LOUVER ACTIVATOR FROM MOTORIZED LOUVER/DAMPER REPLACEMENT BY GC. CONTRACTOR SHALL RECONNECT NEW MOTOR OPERATED LOUVER
ACTIVATOR TO EXISTING CONTROL CIRCUIT. TEST ACTIVATION WITH EXISTING CONTROLS.
7 GC TO REPLACE EXISTING MOTOR OPERATED INTAKE LOUVER, RUSKIN ELF375DX 47x57 OR EQUAL, WITH 120V MOTOR OPERATED DAMPER. VERIFY EXACT SIZE IN FIELD. EC TO PROVIDE CONTROLS TO INTERLOCK INTAKE LOUVER OPEN WHEN
GENERATOR IS ENERGIZED.
8 CONTRACTOR SHALL DISCONNECT EXISTING SPD AND REMOVE CONDUIT/WIRE BACK TO SOURCE. PROVIDE AND CONNECT
NEW SPD AS SHOWN.
-0
5-
1. CONTRACTOR SHALL EXTEND 1"C AND CONDUCTORS FROM NEW AERATION SYSTEM CONTROL PANEL TO PANEL L AND NEW CIRCUIT BREAKER AT PANEL. PROVIDE SEAL OFF FITTINGS AT EACH AT EACH VERTICAL RUN FROM UNDERGROUND PATHWAY.
2. CONTRACTORS SHALL EXTEND 3/4"C AND CONDUCTORS FROM EACH AERATION SYSTEM CP TO AERATION SYSTEM BLOWER MOTOR. PROVIDE RATED FLEXIBLE WHIP CONDUIT AT BLOWER AND SEAL OFF FITTING AT CONDUIT VERTICAL RUN BELOW CP.
COORDINATE CONDUIT ROUTE TO AERATOR EQUIPMENT AND MAINTENANCE POINTS ON UNIT.
PLAN NOTES
SCALE: 1/8" = 1'-0"
NOTE 1
NOTE 2
ELECTRICAL SITE PLAN - GLENN BROOK PUMP STATION
-0
5-
(E) B
ELECTRICAL FLOOR PLAN - APRICOT
SCALE: 1/4" = 1'-0"
S (E) FOR TYPE 'A' LIGHTS
(E) FOR TYPE 'B' LIGHTS
(E) WP
GFCI
(E)
(E) PANEL 'L'
(E) TELEMETERING
ALARM EQUIPMENT
(E) DUPLEX PUMP CONTROL PANEL
M
(E) PUMP CONTROL PANEL CIRCUIT BREAKER
AUTOMATIC TRANSFER
SWITCH TO REPLACE EXISTING
(E) 200 AMP, SELF-CONTAINED RATE METER
(E)
(E) TL
(E)
(E) MOTOR OPERATED INTAKE LOUVER
AND CONTROLS. SEE SCHEMATIC
(E) BATTERY CHARGER
(E) GRAVITY OPERATED
EXHAUST LOUVER
(E) 7.5 KW UNIT HEATER
240V, 1Ø WITH CORD
AND CORD ASSEMBLY S
(E) ODOR CONTROL UNIT (BY GEN. CONT.)
(E) TIME SWITCH AND STARTER
50KW GENERATOR
L-17,19WET WELL AERATION
BLOWER CP
(E) MAGMETER INDICATING
TRANSMITTER3
(E) MAIN CIRCUIT BREAKER
MECHANICAL FLOOR PLAN - APRICOT
SCALE: 1/4" = 1'-0"
(E) GRAVITY OPERATED EXHAUST LOUVER
(E) 5 KW UNIT HEATER 240V, 1Ø WITH CORD
AND CORD ASSEMBLY
(E) TIME SWITCH AND STARTER
(E) MOP SINK TO REMAIN
(E) EMERGENCY EYEWASH
AND SHOWER TO REMAIN
(E) 30MBH UNIT HEATER TO REMAIN
(E) GAS UP TO UNIT HEATER
REPLACE (E) METER FOR NEW CONNECTED
LOAD. COORDINATE INSTALLATION WITH
UGI. (6"-8" W.C., 830 MBH CONNECTED LOAD,
25'-0" DEVELOPED LENGTH)
1 1/4" FROM METER TO
APPLIANCE REGULATOR
PROVIDE NEW MAXITROL 325-9
APPLIANCE REGULATOR
2 EMERGENCY GENERATOR
ANCHOR BOLTS
(TYPICAL)
FLEXIBLE FUEL LINES
GAS CONTROL VALVE
PRIMARY REGULATOR
MANUAL SHUT-OFF
VALVE
2'-0"
FINISHED GRADE
VENT LINE WITH INSECT
SCREEN ON OPEN END
FLEXIBLE EXHAUST CONNECTOR
ALUMINUM EXHAUST DUCT
GRAVITY EXHAUST LOUVER
16" MAX.
BLACK IRON EXHAUST PIPE
NATURAL GAS EMERGENCY
GENERATOR
CONDENSATION TRAP
WITH PETCOCK DRAIN
PIPE ENLARGER
(IF REQIURED)
GAS CARBURETOR
SEAMLESS FLEXIBLE
EXHAUST TUBING
1/2" PETCOCK
DRAIN
" M
IN
SLOPE 1/4" PER FEET
30°
PIPE SLEEVE AND GUARD
METAL PIPE HANGER (TYPICAL)
2"x2"x1/4" ANGLE (TYPICAL)
2x6 (TYPICAL)
1200° INSULATION WRAPPED
AROUND MUFFLER AND PIPING
EXHAUST MUFFLER
NO SCALE
A
E-04
FUEL AND EXHAUST SYSTEM DETAIL GAS GENERATOR
HINGED ACCESS PANEL
FROM GAS METER
FU
6A
FU
6A
INTAKE DAMPER
LIMIT SWITCH
120V FROM A.T.S.
EMERG. SOURCEL-9
TD
TIME DELAY RELAY ADJ.
0-45 SEC. ON DELAY
CONTROL RELAY
D.P.D.T., 10 AMP
CONTACTS
INTAKE LOUVER
DAMPER MOTOR
(POWER OPEN,
SPRING CLOSE)
CR
CR
OPEN CLOSE
XO
THERMOSTAT
CLOSES ON
RISE IN TEMP.
70°-140° RANGE
- TERMINAL POINTS
CR
N
TD
TO ALARM PANEL
"GENERATOR LOUVER FAILURE"
SCALE: 3/4" = 1'-0"
B
E101
EXISTING INTAKE LOUVER CONTROL SCHEMATIC
(E) DUPLEX
PUMP PANEL
PROVIDE 4#1/0,
#6 GND IN 1 1/2"C
4#14 IN 3/4" C FROM
AUXILLIARY CONTACTS ON
ATS TO ALARM PANEL FOR
POWER FAILURE ALARM
PROVIDE NEW 260A
AUTOMATIC TRANSFER
SWITCH
(E) PANEL L
G1
NEW 50KW, 63KVA, 120/240V, 3PH, 4W
GENERATOR WITH CONTROLLER
PANEL AND 200A CIRCUIT BREAKERM
(E) 120/240V, 3PH,
4W SERVICE BY PPL
(E) 225AF/200AT 3P MAIN
CIRCUIT BREAKER TO REMAIN
EXTEND EXISTING
WIRE/CONDUIT 3#4 +
#8 GND IN 1 1/2" C
(E) PPL METER
(E) WIREWAY AND SURGE
PROTECTION DEVICE
NO SCALE
C
E101
ONE-LINE DIAGRAM
15HP15HP
(E) LOUVER
CONTROL
PANEL
15A ECB
SPD
30A ECB
CP
2#14 IN 3/4"C FROM CP CONTROL RELAY
TO INTAKE LOUVER CONTROL "OPEN"
2#14 IN 3/4"C FROM CP CONTROL RELAY TO
ALARM PANEL FOR GENERATOR COMMON ALARM
CP
AERATION
2#10, #10 GRD
IN 3/4"C
4#3/0, #6 GRD
IN 2"C
3 #10, #10 GRD
IN 3/4"C
4#3/0, #6 GRD IN 2"C
KEYED NOTES
1 CONTRACTOR SHALL DISCONNECT AND REMOVE EXISTING GENERATOR AND REPLACE WITH NEW GENERATOR AS SHOWN.
CONTRACTOR SHALL REVIEW EXISTING CONDITIONS WITH CONCRETE PAD, ELECTRICAL CONNECTIONS, AND CONDUIT ROUTES FOR COORDINATION WITH NEW GENERATOR AND ATS SWITCH REPLACEMENT IN SAME LOCATIONS. REUSE/REWORK EXISTING CONCRETE PAD FOR NEW GENERATOR OR REPLACE. COORDINATE ALL WORK WITH OWNER DURING CONSTRUCTION TO MINIMIZE OUTAGES AS PUMP STATION MUST REMAIN ONLINE DURING CONSTRUCTION.
2 CONTRACTOR SHALL DISCONNECT EXISTING EXHAUST DUCT SHEET METAL AND NATURAL GAS CONNECTIONS TO FACILITATE THE INSTALLATION OF THE NEW GENERATOR. PROVIDE NEW EXHAUST DUCT SHEET METAL AND FLEXIBLE CONNECTOR FROM NEW GENERATOR AS REQUIRED. PROVIDE NEW GAS PIPING AND CONNECTIONS AS SHOWN. PROVIDE
GENERATOR ENGINE EXHAUST PIPING AND INSULATION.
3 CONTRACTOR SHALL DISCONNECT AND REMOVE EXISTING MAG METER INDICATING TRANSMITTER AND INSTALL NEW
TRANSMITTER AND CONNECT AS PER MANUFACTURER'S DIRECTIONS
4 CONTRACTOR SHALL DISCONNECT AND REWORK EXISTING BATTERY CHARGER LEADS FROM EXISTING GENERATOR
BATTERY CONNECTIONS AND RECONNECT TO NEW BATTERY ON NEW GENERATOR
5 CONTRACTORS SHALL EXTEND 3/4"C AND CONDUCTORS FROM EACH AERATION SYSTEM CP TO AERATION SYSTEM BLOWER MOTOR. PROVIDE RATED FLEXIBLE WHIP CONDUIT BLOWER AND SEAL OFF FITTING AT CONDUIT VERTICAL RUN BELOW CP.
COORDINATE CONDUIT ROUTE TO AERATOR EQUIPMENT AND MAINTENANCE POINTS ON UNIT.
6 CONTRACTOR SHALL ROUTE (4) #14 CU CONDUCTORS IN 3/4" C FROM AERATION BLOWER CP TO EXISTING DUPLEX PUMP
CONTROL PANEL FOR "PUMP RUN: INTERLOCK TO CP.
7 CONTRACTOR SHALL DISCONNECT ELECTRICAL OPERATOR AT EXISTING MOTOR OPERATED LOUVER ACTIVATOR FROM MOTORIZED LOUVER/DAMPER REPLACEMENT BY GC. CONTRACTOR SHALL RECONNECT NEW MOTOR OPERATED LOUVER
ACTIVATOR TO EXISTING CONTROL CIRCUIT. TEST ACTIVATION WITH EXISTING CONTROLS.
8 GC TO REPLACE EXISTING MOTOR OPERATED INTAKE LOUVER, RUSKIN ELF375DX 47x51 OR EQUAL, WITH 120V MOTOR OPERATED DAMPER. VERIFY EXACT SIZE IN FIELD. EC TO PROVIDE CONTROLS TO INTERLOCK INTAKE LOUVER OPEN WHEN
GENERATOR IS ENERGIZED.
9 CONTRACTOR SHALL DISCONNECT EXISTING SPD AND REMOVE CONDUIT/WIRE BACK TO SOURCE. PROVIDE AND CONNECT
NEW SPD AS SHOWN.
-0
5-
RELINE INFLUENT
MANHOLE ACCORDING
TO SECTION 099000
(BID ALT. #3)
1. CONTRACTOR SHALL EXTEND 1"C AND CONDUCTORS FROM NEW AERATION SYSTEM CONTROL PANEL TO PANEL L AND NEW CIRCUIT BREAKER AT PANEL. PROVIDE SEAL OFF FITTINGS AT EACH AT EACH VERTICAL RUN FROM UNDERGROUND PATHWAY.
2. CONTRACTORS SHALL EXTEND 3/4"C AND CONDUCTORS FROM EACH AERATION SYSTEM CP TO AERATION SYSTEM BLOWER MOTOR. PROVIDE RATED FLEXIBLE WHIP CONDUIT BLOWER AND SEAL OFF FITTING AT CONDUIT VERTICAL RUN BELOW CP.
COORDINATE CONDUIT ROUTE TO AERATOR EQUIPMENT AND MAINTENANCE POINTS ON UNIT.
PLAN NOTES
SCALE: 1/8" = 1'-0"
NOTE 2
NOTE 1
ELECTRICAL SITE PLAN - APRICOT PUMP STATION
-0
5-
| Sheets and Views |
| 00G-01 |
| 00G-02 |
| 00G-03-IndexPLAN |
| 01C-01 |
| 01C-02 |
| 01C-03 |
| 01C-04 |
| 01C-05 |
| 01C-06 |
| 99D-01 |
| E-01 |
| E-02 |
| E-03 |
| E-04 |
| E-05 |
| E-06 |
| E-07 |
File details come from the government source that posted it. Updated .