The file's text, extracted by GovTribe without its formatting.
Vision® Air Handling Unit
| Job Information |
| Technical Data Sheet |
Unit Overview
Air Volume cfm
| Static Pressure |
| External Dimensions |
External inWc Total inWc Height in Width in Length in
| CAH007GDAM |
| 2800 |
| 2.00 |
| 3.49 |
| 42* |
| 40* |
| 88** |
*Not including base rails, coil connectors, drain connectors and control boxes.
**Total lower deck length.
Unit
| Approval: |
| ETL Listed / ETL Listed to Canadian Safety Standards (ETL Label / ETLc Label) |
| Outer Panel: |
| 24 gauge G90 Galvanized Steel (unpainted) |
| Liner: |
| 24 gauge Galvanized Steel (unless noted per section) |
| Insulation: |
| R-13 Injected Foam |
| Unit Configuration: |
| Stacked / vertical |
| Drive (Handling) Location: |
| Right |
| Base: |
| None |
| Wall Thickness: |
| 2 in |
| Altitude: |
| 0 ft |
| Parts Warranty: |
| Standard One Year |
| Mixing Box |
| Component: 1 |
| Length: 28 in |
| Shipping Section: 1 |
| Portion |
| Damper |
| Rated CFM |
| Air Pressure Drop |
| Quantity |
| Size (length x width) |
| Location |
| Type |
| Outside Air |
| 20 in x 36 in |
| 16 in x 26 in |
| End |
| UltraSeal Low Leak |
| 2800 cfm |
| 0.07 insWg |
| 1 |
| Return Air |
| 20 in x 36 in |
| 16 in x 26 in |
| Top |
| UltraSeal Low Leak |
| 2800 cfm |
Filter Data
| Type |
| Efficiency |
| Face Velocity |
| Face Area |
| Air Volume |
| Filter Loading |
| Pleated |
| MERV 8 |
| 374 ft/min |
| 7.5 ft² |
| 2800 cfm |
| Side |
| Air Pressure Drop |
| Number of Filters |
| Height |
| Width |
| Depth |
| Clean Air |
| Mean Air |
| Dirty Air |
| 0.16 inWc |
| 0.58 inWc |
| 1.00 inWc |
| 1 |
| 24 in |
| 24 in |
| 2 in |
| 0.16 inWc |
| 0.58 inWc |
| 1.00 inWc |
| 1 |
| 24 in |
| 12 in |
| 2 in |
| 0.16 inWc |
| 0.58 inWc |
| 1.00 inWc |
| 1 |
| 12 in |
| 24 in |
| 2 in |
Door
| Steam Coil |
| Component: 2 |
| Length: 12 in |
| Shipping Section: 1 |
| Coil Model |
| Total Capacity |
| Number of Coils |
| Number of Rows |
| Fins per Inch |
| Tube Diameter |
| Tube Spacing |
(Face x Row)
| 5JA1101C |
| 238273 Btu/hr |
| 1 |
| 1 |
| 11 |
| 0.625 in |
| 1.50 in x 1.299 in |
| Air Volume |
| Air Temperature |
| Coil Air Pressure Drop |
| Finned Height |
| Finned Length |
| Face Area |
| Face Velocity |
| 2800 cfm |
| 10.0 °F |
| 87.8 °F |
| 0.18 inWc |
| 33 in |
| 24 in |
| 5.50 ft² |
| 509 ft/min |
| Fluid |
| Max. Superheat Temp. in Steam Coil Inlet |
| Steam Pressure |
| Condensate Load |
| 5.00 psig |
| 248.00 lb/hr |
| 30.0 °F |
| Connection [Data Per Coil] |
| Min. Fin Surface Temp. |
| Min. Tube Wall Surface Temp. |
| Type |
| Size |
| Location |
| Material |
| Threaded |
| 2.000 in |
| Drive side |
| Carbon steel |
| 32.0 °F |
| 32.0 °F |
Material
| Aluminum .0075 in |
| Copper .020 in |
| Copper |
| Galvanized track |
AHRI 410 Certification
Certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the Range of Standard Rating Conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory at www.ahridirectory.org
| Combination Coil |
| Component: 3 |
| Length: 24 in |
| Shipping Section: 1 |
Chilled Water Coil
| Coil Model |
| Total Capacity |
| Sensible Capacity |
| Number of Coils |
| Number of Rows |
| Fins per Inch |
| Tube Diameter |
| Tube Spacing |
(Face x Row)
| 5WH1204B |
| 80912 Btu/hr |
| 63652 Btu/hr |
| 1 |
| 4 |
| 12 |
| 0.625 in |
| 1.50 in x 1.299 in |
| Air Volume |
| Air Temperature |
| Coil Air Pressure Drop |
| Finned Height |
| Finned Length |
| Face Area |
| Face Velocity |
| Dry Bulb |
| Wet Bulb |
| Dry Bulb |
| Wet Bulb |
| 2800 cfm |
| 80.0 °F |
| 67.0 °F |
| 59.2 °F |
| 57.9 °F |
| 0.46 inWc |
| 33 in |
| 27 in |
| 6.19 ft² |
| 453 ft/min |
| Water |
| Flow Rate |
| Pressure Drop |
| Velocity |
| Volume |
| Weight |
| 44.0 °F |
| 54.1 °F |
| 16.00 gpm |
| 1.40 ftHd |
| 1.60 ft/s |
| 4.0 gal |
| 39.00 lb |
| Connection [Data Per Coil] |
| Min. Fin Surface Temp. |
| Min. Tube Wall Surface Temp. |
| Fouling Factor |
| Type |
| Size |
| Location |
| Material |
| Threaded |
| 1.50 in |
| Drive side |
| Carbon steel |
| 44.0 °F |
| 44.0 °F |
| 0.000 |
| Material |
| Drain Pan |
| Drain Side |
| Aluminum .0075 in |
| Copper .020 in |
| Copper |
| Galv. steel |
| Stainless steel |
| Drive side |
Component performance shown is based on the component air volume shown.
Static pressure shown is based on the component air volume shown.
AHRI 410 Certification
Certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the Range of Standard Rating Conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory at www.ahridirectory.org
Reheat Hot Water Coil
| Coil Model |
| Total Capacity |
| Number of Coils |
| Number of Rows |
| Fins per Inch |
| Tube Diameter |
| Tube Spacing |
(Face x Row)
| 5JA0601B |
| 111558 Btu/hr |
| 1 |
| 1 |
| 6 |
| 0.625 in |
| 1.50 in x 1.299 in |
| Air Volume |
| Air Temperature |
| Coil Air Pressure Drop |
| Finned Height |
| Finned Length |
| Face Area |
| Face Velocity |
| 2800 cfm |
| 55.0 °F |
| 91.4 °F |
| 0.07 inWc |
| 33 in |
| 24 in |
| 5.50 ft² |
| 509 ft/min |
| Fluid |
| Max. Superheat Temp. in Steam Coil Inlet |
| Steam Pressure |
| Condensate Load |
| 5.00 psig |
| 116.00 lb/hr |
| 30.0 °F |
| Connection [Data Per Coil] |
| Min. Fin Surface Temp. |
| Min. Tube Wall Surface Temp. |
| Type |
| Size |
| Location |
| Material |
| Threaded |
| 2.000 in |
| Drive side |
| Carbon steel |
| 32.0 °F |
| 32.0 °F |
Material
| Aluminum .0075 in |
| Copper .020 in |
| Copper |
| Galvanized track |
Component performance shown is based on the component air volume shown.
Static pressure shown is based on the component air volume shown.
AHRI 410 Certification
Certified in accordance with the AHRI Forced-Circulation Air-Cooling and Air-Heating Coils Certification Program which is based on AHRI Standard 410 within the Range of Standard Rating Conditions listed in Table 1 of the Standard. Certified units may be found in the AHRI Directory at www.ahridirectory.org
| Manual Component |
| Component: 4 |
| Length: 24 in |
| Shipping Section: 1 |
Pressure Drop
0.00 inWc
Door
| Supply Fan |
| Component: 5 |
| Length: 32 in |
| Shipping Section: 2 |
Fan Performance
| Air Volume |
| Static Pressure |
| Brake Horsepower |
| Speed |
| Outlet Velocity |
| 2800 cfm |
| 2.00 inWc |
| 3.49 inWc |
| 0.13 inWc |
| 3.64 BHP |
| 2204 rpm |
| 2854 rpm |
| 3636 ft/min |
Fan Data
| Fan Type |
| Blade Type / Class |
| Quantity of Fans |
| Wheel Diameter |
| Number of Blades |
| Discharge |
| Motor Location |
| Centrifugal DWDI |
| Forward Curved / 2 |
| 1 |
| 9.50 in |
| N/A |
| Top horizontal |
| To Side of Fan |
Motor Data
| Power |
| Electrical Supply |
| Speed |
| Efficiency |
| Enclosure |
| Frame Size |
| Supplier |
| Number of Poles |
| Lock Rotor Current |
| Full Load Current |
| 5.0 HP |
| 200/60/3 V/Hz/Phase |
| 1750 rpm |
| Premium |
| ODP |
| 184 T frame |
| Generic |
| 4 |
| 122.70 A |
| 15.30 A |
Fan Options
| Isolator Type: |
| Rubber in shear |
Drive Package Data*
| Fan Sheave |
| Motor Sheave |
| Belt |
| Number of Belts |
| Actual Drive S.F. |
| Bearing Type |
| AK54H |
| AK66H |
| A31 |
| 1 |
| 1.14 |
| Extended - L50 (500K) |
*Daikin Applied reserves the right to provide a different but equivalent drive package
Door
Unit Sound Power (dB)
| Type |
| 63 Hz |
| 125 Hz |
| 250 Hz |
| 500 Hz |
| 1000 Hz |
| 2000 Hz |
| 4000 Hz |
| 8000 Hz |
| Radiated: |
| 80 |
| 80 |
| 69 |
| 65 |
| 64 |
| 59 |
| 46 |
| 51 |
| Unit Discharge: |
| 90 |
| 90 |
| 87 |
| 86 |
| 86 |
| 87 |
| 84 |
| 81 |
| Unit Return: |
| 80 |
| 80 |
| 71 |
| 71 |
| 71 |
| 72 |
| 66 |
| 60 |
Shipping Section Details
in Weight lb
| Corner Weights (lb) |
| Center of Gravity (in) |
| 1 |
| 88 |
| 825 |
| 218 |
| 202 |
| 195 |
| 211 |
| 43 |
| 19 |
| 20 |
| 2 |
| 32 |
| 340 |
| 101 |
| 76 |
| 70 |
| 94 |
| 15 |
| 17 |
| 19 |
Entire Unit
Lower level only n/a n/a n/a n/a n/a n/a n/a
NOTE: Special components aren't included in the corner weights and center of gravity data.
AHRI Certification
Supply fan performance is certified in accordance with the Central Station Air-Handling Unit Certification Program, which is based on AHRI Standard 430.
Notes
Standard
1. As a standalone component, unit meets or exceeds requirements of ASHRAE 90.1 - 2007. The approving authority is responsible for compliance of multi - component building systems.
| Page 1 of 1 |
| www.DaikinApplied.com |