Drawings.pdf

PDF 7 MB Posted

Attached to
Condenser Water Box and Tubesheet Protective Coating – Building 450
Solicitation number
6-B175-Q-00172-00
Issued by

About this file

This document is a performance report from Carrier Corporation for chiller replacement units at Argonne Building 450, dated July 19, 2024. The report provides detailed specifications and performance data for two identical Carrier 19XR-A67B67648ERGS chillers (models CH-802_803 and CH-801).

The chillers are 2,100-ton capacity water-cooled units manufactured in Charlotte, NC, utilizing R-513A refrigerant with freestanding starters and 4160V-3-60Hz motor controllers rated at 1,324.7 kW. Key specifications include A67 evaporators and B67 condensers with marine waterboxes rated at 150 psi, both using 3/4-inch copper rifled tubes with fresh water circulation. Operating dimensions are 290 inches length by 130 inches width by 137 inches height, with total operating weight of 98,929 pounds and refrigerant charge of 3,878 pounds. At full load, the units deliver 2,100 tons of cooling capacity with power consumption of 1,326 kW and efficiency of 0.6316 kW/TonR, achieving COP ratings of 5.568 kW/kW. The evaporator operates with 60°F inlet and 40°F outlet temperatures at 2,518 gpm flow rate with 11.7 feet of water pressure drop, while the condenser operates at 99.40°F leaving and 85°F entering temperatures at 4,151 gpm with 12.5 feet of water pressure drop. The units comply with ASHRAE 90.1 efficiency standards across multiple years (2007, 2010, 2013, 2016) and are AHRI-certified. The report includes comprehensive performance curves, acoustic data (82 dBA at full load), and detailed technical drawings showing plan views, front views, rear views, and compressor end views with all connection points and service clearances clearly identified.

View the file

Other files

File Type Posted
Addendum 0001.doc DOC document
Appendix D8C-12-DEC-2023.pdf PDF
Appendix A-71COM-22-OCT-2025.PDF PDF
ANL-70B Reps and Certs Long-13-JAN-2025.PDF PDF
ANL-366H (on-site high risk)-01-OCT-2024.PDF PDF
SOW.pdf.pdf PDF
ANL-70 Request for Quotation.doc DOC document

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Compressor

Size 648

Weights

Total Rigging Weight 76742 lb

Total Operating Weight 98929 lb

Refrigerant Weight 3878 lb

Motor & Motor Controller

Size R

Line Voltage-Phase-Hertz 4160(V)-3-60(Hz)

Flow Controls

Condenser Float Valve 6F

Economizer Float Valve 6S

Flasc Orifice 79

Isolation Valve Installed

Economizer Size 6

Dimensions

Length 290 in

Width 130 in

Height 137 in

Configuration Evaporator

Size A67

Waterbox Type Marine Waterbox, 150 psi

Passes 2

Nozzle Arrangement C - 2 Passes, Nozzles on Drive End

Tubing 3/4" 0.028" Copper Rifled Evaporator Tubes

Fluid Type Fresh Water

Fouling Factor 0.000100 (hr-sqft-F)/BTU

Condenser

B67

Marine Waterbox, 150 psi

S - 2 Passes, Nozzles on Compressor End

3/4" 0.035" Copper Rifled Condenser Tubes

Fresh Water

0.000250 (hr-sqft-F)/BTU

Chiller Starter / VFD Freestanding Starter

Refrigerant Type R-513A

Operation Type Cooling

Manufacturing Source Charlotte, NC USA

19XR-A67B67648ERGS

Page 1 of 5NG eCat Applied Chillers North America v3.5.0.0

Performance Report

Argonne Bldg 450 Chiller Repl - CH-802_803

Carrier NAC Sales Office

Date: 07/19/2024 2:02 PM Prepared By: Anthony Maciaga

Cooler water volume = 650 gallons Condenser water volume = 915 gallons

Oil quantity = 28.5 gallons

Full Load Performance Percent Load Chiller

Percent Load 100.00

Chiller Capacity 2100 Tons

Chiller Power 1326 kW

Chiller Efficiency 0.6316 kW/TonR

Chiller COPʀ 5.568 kW/kW

IPLV.IP *0.5137 kW/TonR

IPLV, COPʀ 6.845

NPLV.IP *0.5470 kW/TonR

NPLV, COPʀ 6.430

Evaporator

Entering Temperature 60.00 °F

Leaving Temperature 40.00 °F

Flow Rate 2518 gpm

Pressure Drop 11.7 ft H₂O

Condenser

Leaving Temperature 99.40 °F

Entering Temperature 85.00 °F

Flow Rate 4151 gpm

Pressure Drop 12.5 ft H₂O

Heat Rejection 29727 MBH

Motor & Motor Controller

Motor Rated Load KW 1324.7 kW

Motor Rated Load Amps 210.4

Motor OLTA 227

Motor locked rotor A 1291

Max Fuse/ CB Amps 450

Min Circuit Ampacity 263

Heat Exchangers

Suction Temp 39.6 °F

Full Load

(1) Certified in accordance with the AHRI Water-Cooled Water-Chilling and Heat Pump Water-Heating Packages Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI).

Certified units may be found in the AHRI Directory at www.ahridirectory.org.

(2) Unable to meet all input requirements.This selection is the best available Note: The (*) sign(s) in table above denote that the data in this selection does not meet the required criteria entered in the Selection Inputs section of the E-Cat Selection Software.

http://www.ahrinet.org/WCCL.aspx

This unit complies with the efficiency requirements of :

ASHRAE 90.1 Criteria 2007.

ASHRAE 90.1 2010 Path A.

ASHRAE 90.1 2010 Path B.

ASHRAE 90.1 2013 Path A.

ASHRAE 90.1 2013 Path B.

ASHRAE 90.1 2016 Path A.

ASHRAE 90.1 2016 Path B.

1 Point LEED EAC4 can be earned when selecting the 19XR AquaEdge

Page 2 of 5NG eCat Applied Chillers North America v3.5.0.0

Performance Report

Argonne Bldg 450 Chiller Repl - CH-802_803

Carrier NAC Sales Office

Date: 07/19/2024 2:02 PM Prepared By: Anthony Maciaga

Minimum entering condenser water temperature = 60F

Percent Load 100.00 75.00 50.00 25.00

Chiller Capacity *2100 Tons 1575 Tons 1050 Tons 525.0 Tons

Chiller Power 1196 kW 800.0 kW 509.1 kW 362.0 kW

Chiller Efficiency 0.5695 kW/TonR 0.5080 kW/TonR 0.4849 kW/TonR 0.6896 kW/TonR

Chiller COPʀ 6.176 kW/kW 6.924 kW/kW 7.253 kW/kW 5.100 kW/kW

IPLV.IP *0.5137 kW/TonR NA NA NA

IPLV, COPʀ 6.845 NA NA NA

NPLV.IP *0.5470 kW/TonR NA NA NA

NPLV, COPʀ 6.430 NA NA NA

Evaporator

Entering Temperature 54.00 °F 51.50 °F 49.00 °F 46.50 °F

Leaving Temperature 44.00 °F 44.00 °F 44.00 °F 44.00 °F

Flow Rate 5034 gpm 5034 gpm 5034 gpm 5034 gpm

Pressure Drop 40.3 ft H₂O 40.5 ft H₂O 40.7 ft H₂O 40.9 ft H₂O

Condenser

Leaving Temperature 94.30 °F 81.89 °F 69.57 °F 67.42 °F

Entering Temperature 85.00 °F 75.00 °F 65.00 °F 65.00 °F

Flow Rate 6329 gpm 6329 gpm 6329 gpm 6329 gpm

Pressure Drop 26.9 ft H₂O 27.6 ft H₂O 28.4 ft H₂O 28.5 ft H₂O

Motor & Motor Controller

Motor Rated Load Amps 192.4 139.3 106.2 87.7

Motor OLTA 208 NA NA NA

Motor locked rotor A 1291 NA NA NA

Max Fuse/ CB Amps 400 NA NA NA

Min Circuit Ampacity 241 NA NA NA

AHRI Tolerances

AHRI Test Tolerance% 5.00 7.25 10.00 14.75

Max Efficiency 0.5979 0.5448 0.5334 0.7913

Min Capacity 1995.0 NA NA NA

Max IPLV.IP 0.5651 NA NA NA

Percent Load

IPLV.IP

(1) Certified in accordance with the AHRI Water-Cooled Water-Chilling and Heat Pump Water-Heating Packages Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI).

Certified units may be found in the AHRI Directory at www.ahridirectory.org.

(2) Full load compressor map point outside full load selection area. Verify compressor model selected is valid.

Note: The (*) sign(s) in table above denote that the data in this selection does not meet the required criteria entered in the Selection Inputs section of the E-Cat Selection Software.

Note: The (*) sign(s) in table above denote that the full load point of this selection is not in the Full Load Selection area of the Compressor Map. Please review the Compressor Map report for more detail.

http://www.ahrinet.org/WCCL.aspx

This unit complies with the efficiency requirements of :

ASHRAE 90.1 Criteria 2007.

ASHRAE 90.1 2010 Path A.

ASHRAE 90.1 2010 Path B.

ASHRAE 90.1 2013 Path A.

ASHRAE 90.1 2013 Path B.

ASHRAE 90.1 2016 Path A.

ASHRAE 90.1 2016 Path B.

1 Point LEED EAC4 can be earned when selecting the 19XR AquaEdge

Page 3 of 5NG eCat Applied Chillers North America v3.5.0.0

Performance Report

Argonne Bldg 450 Chiller Repl - CH-802_803

Carrier NAC Sales Office

Date: 07/19/2024 2:02 PM Prepared By: Anthony Maciaga

Chiller Capacity 2100 Tons 1575 Tons 1050 Tons 525.0 Tons

Chiller Power 1326 kW 859.9 kW 537.8 kW 382.7 kW

Chiller Efficiency 0.6316 kW/TonR 0.5460 kW/TonR 0.5122 kW/TonR 0.7289 kW/TonR

Chiller COPʀ 5.568 kW/kW 6.441 kW/kW 6.866 kW/kW 4.825 kW/kW

IPLV.IP *0.5137 kW/TonR NA NA NA

IPLV, COPʀ 6.845 NA NA NA

NPLV.IP *0.5470 kW/TonR NA NA NA

NPLV, COPʀ 6.430 NA NA NA

Evaporator

Entering Temperature 60.00 °F 54.99 °F 49.98 °F 44.99 °F

Leaving Temperature 40.00 °F 40.00 °F 40.00 °F 40.00 °F

Flow Rate 2518 gpm 2518 gpm 2518 gpm 2518 gpm

Pressure Drop 11.7 ft H₂O 11.8 ft H₂O 11.9 ft H₂O 12.1 ft H₂O

Condenser

Leaving Temperature 99.40 °F 85.59 °F 72.01 °F 68.71 °F

Entering Temperature 85.00 °F 75.00 °F 65.00 °F 65.00 °F

Flow Rate 4149 gpm 4149 gpm 4149 gpm 4149 gpm

Pressure Drop 12.5 ft H₂O 12.8 ft H₂O 13.2 ft H₂O 13.3 ft H₂O

Motor & Motor Controller

Motor Rated Load Amps 210.4 147.0 109.0 90.0

Motor OLTA 227 NA NA NA

Motor locked rotor A 1291 NA NA NA

Max Fuse/ CB Amps 450 NA NA NA

Min Circuit Ampacity 263 NA NA NA

AHRI Tolerances

AHRI Test Tolerance% 4.25 6.25 8.50 11.75

Max Efficiency 0.6584 0.5801 0.5558 0.8145

Min Capacity 2010.8 NA NA NA

Max IPLV.IP 0.0000 NA NA NA

Percent Load

NPLV.IP

(1) Certified in accordance with the AHRI Water-Cooled Water-Chilling and Heat Pump Water-Heating Packages Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI).

Certified units may be found in the AHRI Directory at www.ahridirectory.org.

(2) Note: The (*) sign(s) in table above denote that the data in this selection does not meet the required criteria entered in the Selection Inputs section of the E-Cat Selection Software.

http://www.ahrinet.org/WCCL.aspx

This unit complies with the efficiency requirements of :

ASHRAE 90.1 Criteria 2007.

ASHRAE 90.1 2010 Path A.

ASHRAE 90.1 2010 Path B.

ASHRAE 90.1 2013 Path A.

ASHRAE 90.1 2013 Path B.

ASHRAE 90.1 2016 Path A.

Page 5 of 5NG eCat Applied Chillers North America v3.5.0.0

Argonne Bldg 450 Chiller Repl - CH-802_803

Carrier NAC Sales Office

Note: 1) Minimum Flow Rate is 3 ft/sec for standard calculation results and 1.5 ft/sec when the user selects Variable Primary Flow.

2) This does not imply that the chiller can be properly applied over the entire range of evaporator water flow rates represented. The chart is to represent pressure drops only.

Evaporator

Size A67

Waterbox Type Marine Waterbox, 150 psi

Passes 2

Tubing 3/4" 0.028" Copper Rifled Evaporator Tubes

Flow Rate 2518 gpm

Pressure Drop 11.7 ft H₂O

Fluid Type Fresh Water

Minimum Flow Rate 1930 gpm

Maximum Flow Rate (12.0 ft/sec) 7721 gpm

19XR-A67B67648ERGS

1 Point LEED EAC4 can be earned when selecting the 19XR AquaEdge

Page 1 of 1NG eCat Applied Chillers North America v3.5.0.0

Chiller Evaporator Pressure Drop

Argonne Bldg 450 Chiller Repl - CH-802_803

Carrier NAC Sales Office

Note: This does not imply that the chiller can be properly applied over the entire range of condenser water flow rates represented. The chart is to represent pressure drops only.

Condenser

Size B67

Waterbox Type Marine Waterbox, 150 psi

Passes 2

Tubing 3/4" 0.035" Copper Rifled Condenser Tubes

Flow Rate 4151 gpm

Pressure Drop 12.5 ft H₂O

Fluid Type Fresh Water

Minimum Flow Rate (3.0 ft/sec) 2721 gpm

Maximum Flow Rate (12.0 ft/sec) 10880 gpm

19XR-A67B67648ERGS

1 Point LEED EAC4 can be earned when selecting the 19XR AquaEdge

Page 1 of 1NG eCat Applied Chillers North America v3.5.0.0

Chiller Condenser Pressure Drop

Argonne Bldg 450 Chiller Repl - CH-802_803

Carrier NAC Sales Office

19XR-A67B67648ERGS

Estimated Sound Pressure Levels - dB re: 20 micropascal.

Sound pressure levels used to develop this program were measured per AHRI Standard 575.

The sound pressure levels were measured in an acoustical free-field, i.e. a non-reflective environment. Field sound measurements can vary significantly as a function of the reflectivity and proximity of nearby surfaces and the presence of other sound sources.

Notes:

Airborne Sound Pressure, dB Sound Treatment: No Treatment

Full Load

Octave Band Center Frequency, Hz

Percent Load

DBA 31.5 63 125 250 500 1 k 2 k 4 k 8 k

100.00 82 35 44 61 63 68 78 78 71 65

IPLV

Octave Band Center Frequency, Hz

Percent Load

DBA 31.5 63 125 250 500 1 k 2 k 4 k 8 k

100.00 81 31 42 60 62 68 77 78 70 66

75.00 81 32 44 58 62 69 78 77 69 64

50.00 82 37 48 61 64 71 80 76 69 63

25.00 87 37 59 69 66 73 85 79 71 64

NPLV

Octave Band Center Frequency, Hz

Percent Load

DBA 31.5 63 125 250 500 1 k 2 k 4 k 8 k

100.00 82 35 44 61 63 68 78 78 71 65

75.00 83 31 42 59 62 68 81 77 69 65

50.00 83 36 48 61 64 71 81 77 70 63

25.00 88 37 60 69 67 74 86 80 72 64

The sound pressure level depicted above is based on constant speed. For a VFD driven chiller, it is estimated that, on average, there will be a 2-3 dbA reduction in the overall sound pressure level based on a typical reduction in compressor head at part-load operating conditions.

Page 1 of 1NG eCat Applied Chillers North America v3.5.0.0

AquaEdge Chiller Estimated Acoustic Data

Argonne Bldg 450 Chiller Repl - CH-802_803

Date: 07/19/2024 2:02 PM

Carrier NAC Sales Office

Prepared By: Anthony Maciaga

Hinge - Door swing is 180°, 67.75"

Hinge - Door swing is 180°, 67.75"

Hinge - Door swing is 180°, 67.75"

Hinge - Door swing is

Hinged door swing is 180°, 67.75"

Hinge

Condenser

Evaporator

Full Load Performance Percent Load

Percent Load 100.00

Chiller Capacity 2100 Tons

Chiller Power 1326 kW

Chiller Efficiency 0.6316 kW/TonR

Chiller COPʀ 5.568 kW/kW

IPLV.IP *0.5137 kW/TonR

IPLV, COPʀ 6.845

NPLV.IP *0.5470 kW/TonR

NPLV, COPʀ 6.430

Evaporator

Entering Temperature 60.00 °F

Leaving Temperature 40.00 °F

Flow Rate 2518 gpm

Pressure Drop 11.7 ft H₂O

Condenser

Leaving Temperature 99.40 °F

Entering Temperature 85.00 °F

Flow Rate 4151 gpm

Pressure Drop 12.5 ft H₂O

Heat Rejection 29727 MBH

Motor & Motor Controller

Motor Rated Load KW 1324.7 kW

Motor Rated Load Amps 210.4

Motor OLTA 227

Motor locked rotor A 1291

Max Fuse/ CB Amps 450

Min Circuit Ampacity 263

Heat Exchangers

Suction Temp 39.6 °F

Full Load

(1) Certified in accordance with the AHRI Water-Cooled Water-Chilling and Heat Pump Water-Heating Packages Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI).

Certified units may be found in the AHRI Directory at www.ahridirectory.org.

(2) Unable to meet all input requirements.This selection is the best available Note: The (*) sign(s) in table above denote that the data in this selection does not meet the required criteria entered in the Selection Inputs section of the E-Cat Selection Software.

http://www.ahrinet.org/WCCL.aspx

This unit complies with the efficiency requirements of :

ASHRAE 90.1 Criteria 2007.

ASHRAE 90.1 2010 Path A.

ASHRAE 90.1 2010 Path B.

ASHRAE 90.1 2013 Path A.

ASHRAE 90.1 2013 Path B.

ASHRAE 90.1 2016 Path A.

Page 2 of 5NG eCat Applied Chillers North America v3.5.0.0

Argonne Bldg 450 Chiller Repl - CH-801

Carrier NAC Sales Office

Date: 07/19/2024 2:02 PM Prepared By: Anthony Maciaga

Minimum entering condenser water temperature = 60F

Chiller Capacity *2100 Tons 1575 Tons 1050 Tons 525.0 Tons

Chiller Power 1196 kW 800.0 kW 509.1 kW 362.0 kW

Chiller Efficiency 0.5695 kW/TonR 0.5080 kW/TonR 0.4849 kW/TonR 0.6896 kW/TonR

Chiller COPʀ 6.176 kW/kW 6.924 kW/kW 7.253 kW/kW 5.100 kW/kW

IPLV.IP *0.5137 kW/TonR NA NA NA

IPLV, COPʀ 6.845 NA NA NA

NPLV.IP *0.5470 kW/TonR NA NA NA

NPLV, COPʀ 6.430 NA NA NA

Evaporator

Entering Temperature 54.00 °F 51.50 °F 49.00 °F 46.50 °F

Leaving Temperature 44.00 °F 44.00 °F 44.00 °F 44.00 °F

Flow Rate 5034 gpm 5034 gpm 5034 gpm 5034 gpm

Pressure Drop 40.3 ft H₂O 40.5 ft H₂O 40.7 ft H₂O 40.9 ft H₂O

Condenser

Leaving Temperature 94.30 °F 81.89 °F 69.57 °F 67.42 °F

Entering Temperature 85.00 °F 75.00 °F 65.00 °F 65.00 °F

Flow Rate 6329 gpm 6329 gpm 6329 gpm 6329 gpm

Pressure Drop 26.9 ft H₂O 27.6 ft H₂O 28.4 ft H₂O 28.5 ft H₂O

Motor & Motor Controller

Motor Rated Load Amps 192.4 139.3 106.2 87.7

Motor OLTA 208 NA NA NA

Motor locked rotor A 1291 NA NA NA

Max Fuse/ CB Amps 400 NA NA NA

Min Circuit Ampacity 241 NA NA NA

AHRI Tolerances

AHRI Test Tolerance% 5.00 7.25 10.00 14.75

Max Efficiency 0.5979 0.5448 0.5334 0.7913

Min Capacity 1995.0 NA NA NA

Max IPLV.IP 0.5651 NA NA NA

Percent Load

IPLV.IP

(1) Certified in accordance with the AHRI Water-Cooled Water-Chilling and Heat Pump Water-Heating Packages Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI).

Certified units may be found in the AHRI Directory at www.ahridirectory.org.

(2) Full load compressor map point outside full load selection area. Verify compressor model selected is valid.

Note: The (*) sign(s) in table above denote that the data in this selection does not meet the required criteria entered in the Selection Inputs section of the E-Cat Selection Software.

Note: The (*) sign(s) in table above denote that the full load point of this selection is not in the Full Load Selection area of the Compressor Map. Please review the Compressor Map report for more detail.

http://www.ahrinet.org/WCCL.aspx

This unit complies with the efficiency requirements of :

ASHRAE 90.1 Criteria 2007.

ASHRAE 90.1 2010 Path A.

ASHRAE 90.1 2010 Path B.

ASHRAE 90.1 2013 Path A.

ASHRAE 90.1 2013 Path B.

ASHRAE 90.1 2016 Path A.

ASHRAE 90.1 2016 Path B.

1 Point LEED EAC4 can be earned when selecting the 19XR AquaEdge

Page 3 of 5NG eCat Applied Chillers North America v3.5.0.0

Performance Report

Argonne Bldg 450 Chiller Repl - CH-801

Carrier NAC Sales Office

Chiller Capacity 2100 Tons 1575 Tons 1050 Tons 525.0 Tons

Chiller Power 1326 kW 859.9 kW 537.8 kW 382.7 kW

Chiller Efficiency 0.6316 kW/TonR 0.5460 kW/TonR 0.5122 kW/TonR 0.7289 kW/TonR

Chiller COPʀ 5.568 kW/kW 6.441 kW/kW 6.866 kW/kW 4.825 kW/kW

IPLV.IP *0.5137 kW/TonR NA NA NA

IPLV, COPʀ 6.845 NA NA NA

NPLV.IP *0.5470 kW/TonR NA NA NA

NPLV, COPʀ 6.430 NA NA NA

Evaporator

Entering Temperature 60.00 °F 54.99 °F 49.98 °F 44.99 °F

Leaving Temperature 40.00 °F 40.00 °F 40.00 °F 40.00 °F

Flow Rate 2518 gpm 2518 gpm 2518 gpm 2518 gpm

Pressure Drop 11.7 ft H₂O 11.8 ft H₂O 11.9 ft H₂O 12.1 ft H₂O

Condenser

Leaving Temperature 99.40 °F 85.59 °F 72.01 °F 68.71 °F

Entering Temperature 85.00 °F 75.00 °F 65.00 °F 65.00 °F

Flow Rate 4149 gpm 4149 gpm 4149 gpm 4149 gpm

Pressure Drop 12.5 ft H₂O 12.8 ft H₂O 13.2 ft H₂O 13.3 ft H₂O

Motor & Motor Controller

Motor Rated Load Amps 210.4 147.0 109.0 90.0

Motor OLTA 227 NA NA NA

Motor locked rotor A 1291 NA NA NA

Max Fuse/ CB Amps 450 NA NA NA

Min Circuit Ampacity 263 NA NA NA

AHRI Tolerances

AHRI Test Tolerance% 4.25 6.25 8.50 11.75

Max Efficiency 0.6584 0.5801 0.5558 0.8145

Min Capacity 2010.8 NA NA NA

Max IPLV.IP 0.0000 NA NA NA

Percent Load

NPLV.IP

(1) Certified in accordance with the AHRI Water-Cooled Water-Chilling and Heat Pump Water-Heating Packages Certification Program, which is based on AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI).

Certified units may be found in the AHRI Directory at www.ahridirectory.org.

(2) Note: The (*) sign(s) in table above denote that the data in this selection does not meet the required criteria entered in the Selection Inputs section of the E-Cat Selection Software.

http://www.ahrinet.org/WCCL.aspx

This unit complies with the efficiency requirements of :

ASHRAE 90.1 Criteria 2007.

ASHRAE 90.1 2010 Path A.

ASHRAE 90.1 2010 Path B.

ASHRAE 90.1 2013 Path A.

ASHRAE 90.1 2013 Path B.

ASHRAE 90.1 2016 Path A.

Page 5 of 5NG eCat Applied Chillers North America v3.5.0.0

Argonne Bldg 450 Chiller Repl - CH-801

Carrier NAC Sales Office

Note: 1) Minimum Flow Rate is 3 ft/sec for standard calculation results and 1.5 ft/sec when the user selects Variable Primary Flow.

2) This does not imply that the chiller can be properly applied over the entire range of evaporator water flow rates represented. The chart is to represent pressure drops only.

Evaporator

Size A67

Waterbox Type Marine Waterbox, 150 psi

Passes 2

Tubing 3/4" 0.028" Copper Rifled Evaporator Tubes

Flow Rate 2518 gpm

Pressure Drop 11.7 ft H₂O

Fluid Type Fresh Water

Minimum Flow Rate 1930 gpm

Maximum Flow Rate (12.0 ft/sec) 7721 gpm

19XR-A67B67648ERGS

1 Point LEED EAC4 can be earned when selecting the 19XR AquaEdge

Page 1 of 1NG eCat Applied Chillers North America v3.5.0.0

Chiller Evaporator Pressure Drop

Argonne Bldg 450 Chiller Repl - CH-801

Carrier NAC Sales Office

Note: This does not imply that the chiller can be properly applied over the entire range of condenser water flow rates represented. The chart is to represent pressure drops only.

Condenser

Size B67

Waterbox Type Marine Waterbox, 150 psi

Passes 2

Tubing 3/4" 0.035" Copper Rifled Condenser Tubes

Flow Rate 4151 gpm

Pressure Drop 12.5 ft H₂O

Fluid Type Fresh Water

Minimum Flow Rate (3.0 ft/sec) 2721 gpm

Maximum Flow Rate (12.0 ft/sec) 10880 gpm

19XR-A67B67648ERGS

1 Point LEED EAC4 can be earned when selecting the 19XR AquaEdge

Page 1 of 1NG eCat Applied Chillers North America v3.5.0.0

Chiller Condenser Pressure Drop

Argonne Bldg 450 Chiller Repl - CH-801

Carrier NAC Sales Office

19XR-A67B67648ERGS

Estimated Sound Pressure Levels - dB re: 20 micropascal.

Sound pressure levels used to develop this program were measured per AHRI Standard 575.

The sound pressure levels were measured in an acoustical free-field, i.e. a non-reflective environment. Field sound measurements can vary significantly as a function of the reflectivity and proximity of nearby surfaces and the presence of other sound sources.

Notes:

Airborne Sound Pressure, dB Sound Treatment: No Treatment

Full Load

Octave Band Center Frequency, Hz

Percent Load

DBA 31.5 63 125 250 500 1 k 2 k 4 k 8 k

100.00 82 35 44 61 63 68 78 78 71 65

IPLV

Octave Band Center Frequency, Hz

Percent Load

DBA 31.5 63 125 250 500 1 k 2 k 4 k 8 k

100.00 81 31 42 60 62 68 77 78 70 66

75.00 81 32 44 58 62 69 78 77 69 64

50.00 82 37 48 61 64 71 80 76 69 63

25.00 87 37 59 69 66 73 85 79 71 64

NPLV

Octave Band Center Frequency, Hz

Percent Load

DBA 31.5 63 125 250 500 1 k 2 k 4 k 8 k

100.00 82 35 44 61 63 68 78 78 71 65

75.00 83 31 42 59 62 68 81 77 69 65

50.00 83 36 48 61 64 71 81 77 70 63

25.00 88 37 60 69 67 74 86 80 72 64

The sound pressure level depicted above is based on constant speed. For a VFD driven chiller, it is estimated that, on average, there will be a 2-3 dbA reduction in the overall sound pressure level based on a typical reduction in compressor head at part-load operating conditions.

Page 1 of 1NG eCat Applied Chillers North America v3.5.0.0

AquaEdge Chiller Estimated Acoustic Data

Argonne Bldg 450 Chiller Repl - CH-801

Date: 07/19/2024 2:02 PM

Carrier NAC Sales Office

Prepared By: Anthony Maciaga

Hinge - Door swing is

Hinge - Door swing is 180°, 67.75"

Hinge - Door swing is 180°, 67.75"

Hinge - Door swing is

Condenser

Evaporator

Insert from: "001-Plan View.pdf"
Sheets and Views
Model
Insert from: "003-Rear View.pdf"