Annual Inspection Report- Elgin TRACON 2025 Sprinkler.pdf
PDF 472 KB Posted
- Solicitation number
- 697DCK-26-C-00139
About this file
This is an Annual Fire Sprinkler Inspection Report prepared by Allegiant Fire Protection for Convergint Technologies at 1100 Bowes, Elgin, Illinois 60123, dated October 9, 2025. The inspection was conducted by technician Jon Rocke (NICET #151246) under Job Number 43232892, with owner representative Greg Stritzel present. The facility features 13 fire suppression systems across two floors with mixed deck heights (approximately 10-20 feet) and a single Fire Department Connection (FDC).
The inspection confirmed that the building is currently occupied, all fire protection systems are in service, and all visible sprinkler equipment is free of damage, corrosion, and properly maintained. All piping, hangers, bracing, and fire department connections were found to be in good condition with no leaks or mechanical damage. Control valves across all systems are in correct positions, locked or supervised, accessible, and operational. Main drain and waterflow tests across all 12 systems yielded consistent results with static pressure of 80 PSI before and residual pressure of 65 PSI, with pressure after waterflow at 75 PSI and waterflow times within 60 seconds. The inspector identified two necessary improvements: (1) completion of 5-year internal pipe and check valve inspection and FDC hydrostatic testing for the 13 risers, and (2) replacement of 26 water gauges rated 0-300 PSI that are due for replacement.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
2760 Beverly Dr.
Suite 9 Aurora, IL 60502 630.506.5535 www.allegiantfire.net
IL FSC#: FSC0392
Report to:
Property:
Address:
City:
State: Zip:
Date:
Job Number:
Technician:
FIRE SPRINKLER INSPECTION REPORT
CONTROL VALVES Continued
Description Type Size Location Note # System #11 - Environmental Supply - West System #12 - Administration - Penthouse
System #13- Kitchen / Penthouse System (Locked)
OS&Y 4”
OS&Y 4”
OS&Y 4”
Post Indicator 8”
Riser Room Riser Room Riser Room Near Dock
Convergint Technologies Convergint - FAA-Central Logistics Svc Area, 1100 Bowes
1100 Bowes Elgin
IL 60123
10/09/2025 07:00am CDT 43232892
Jon Rocke
Suite 9 Aurora, IL 60502 630.506.5535 www.allegiantfire.net
IL FSC#: FSC0392
Report to:
Property:
Address:
City:
State: Zip:
Date:
Job Number:
Technician:
FIRE SPRINKLER INSPECTION REPORT
MAIN DRAIN AND WATERFLOW TEST RESULTS Continued
System # Riser Size Size of Test Pipe
PSI Static Pressure Before
PSI Residual Pressure
PSI Pressure After
Waterflow Time (sec) Note #
System #13 - 2nd. Flr - Kitchen / Penthouse 4” 2” 80 65 75 Within 60
10/09/2025 07:00am CDT 43232892
Jon Rocke
Convergint Technologies Convergint - FAA-Central Logistics Svc Area, 1100 Bowes
1100 Bowes Elgin
IL 60123
Suite 9 Aurora, IL 60502 630.506.5535 www.allegiantfire.net
IL FSC #: FSC0392
Report to:
Property:
Address:
City:
State: Zip:
Date:
Job Number:
Technician:
Annual FIRE SPRINKLER INSPECTION REPORT
Central Station POS/Acct Out IN
GENERAL YES NO N/A Note # Is the building currently occupied?
Has the occupancy classification and hazard of contents remained the same since the last inspection?
Are all fire protection systems in service?
Has the system remained in service without modifications or actuations of devices/alarms since last inspection?
Fire pump onsite?
SPRINKLERS (visible) YES NO N/A Note # Free of damage or leaks?
Free of corrosion, foreign material, or paint, loading?
Installed in proper orientation?
Fluid in glass bulbs?
Spare head box contains proper number and type of heads, including wrench(s)?
Escutcheon plates are present and installed correctly?
Minimum clearance between sprinklers and storage?
Sprinklers tested or replaced per appropriate testing schedule?
Sprinkler heads in use and earliest date on heads:
Standard: Quick Response: ESFR: Dry Pendant:
PIPING YES NO N/A Note # In good condition with no external corrosion?
No leaks or mechanical damage?
Correct alignment/No external loads?
Wet Sprinkler piping not exposed to freezing temperatures?
Hangers/bracing not damaged or loose?
FIRE DEPARTMENT CONNECTIONS YES NO N/A Note # Visible and accessible?
Couplings swivel and operate properly?
Plugs or caps in place?
Identification signs are in place?
Ball drip valve is functional/not leaking?
ANTI-FREEZE SYSTEMS YES NO N/A Note # Have all anti-freeze systems been tested?
Proper signage and placard info in place?
LOCATION / AREA PROTECTED TEMP Note # LOCATION / AREA PROTECTED TEMP Note # 1 3 2 4
(*Any additional anti-freeze system results will be listed in Note # Section)
Convergint Technologies 10/09/2025
Convergint - FAA-Central Logistics Svc Area, 1100 Bowes 43232892 1100 Bowes
Elgin Jon Rocke
IL 60123
Handled By Customer -
✔ ✔1994 2016
Suite 9 Aurora, IL 60502 630.506.5535 www.allegiantfire.net
IL FSC #: FSC0392
Report to:
Property:
Address:
City:
State: Zip:
Date:
Job Number:
Technician:
Annual FIRE SPRINKLER INSPECTION REPORT
CONTROL VALVES YES NO N/A Note # All Control Valves in the correct (open or closed) position?
Locked or supervised?
Easily accessible?
Free from damage or leaks?
Proper signage in place?
Tamper Switches operate properly?
All Control Valves operated through full range and return to normal position?
OS&Y Valves properly lubricated?
Description Type Size Location Note #
(*Any additional control valves will be listed on a separate sheet.)
MAIN DRAIN AND WATERFLOW TEST RESULTS YES NO N/A Note #
Do main drain test results differ more than 10% from previous test?
System # Riser Size Size of Test
Pipe
PSI Static Pressure Before
PSI Residual Pressure
PSI Pressure After
Waterflow Time (sec) Note #
(*Any additional main drain/waterflow results will be listed on a separate sheet.)
FIVE YEAR REQUIREMENTS YES NO N/A Note # Have all Check Valves, Pre-action or Deluge Valves been internally inspected within the last 5 years?
Has the piping in all systems been checked for obstructive materials within the last 5 years?
System Gauges tested or replaced within the last 5 years?
Convergint Technologies 10/09/2025
Convergint - FAA-Central Logistics Svc Area, 1100 Bowes 43232892 1100 Bowes
IL
Jon RockeElgin
60123
System before backflow
System #2 - 1st Flr. Admin. / Elev.
System #3 - 1st Flr. Equip. Rm.
System #4 - 1st Flr. Equip. Repair Rm.
System #5 - 1st Flr. Equip. Rm.
System #6 - 2nd. Flr. Operations / Lobby System #7 - 2nd. Flr. Operations
System #8 - Catwalk System #9 - Administration Wing
System #10 - 2nd. Flr. Administration Wing
System after backflow System #1 - 1st Flr. Environmental
OS&Y 8” Riser Room OS&Y 8” Riser Room OS&Y 4” Riser Room OS&Y 2 1/2” Riser Room OS&Y 2 1/2” Riser Room OS&Y 4” Riser Room OS&Y 4” Riser Room OS&Y 4” Riser Room OS&Y 6” Riser Room OS&Y 6” Riser Room OS&Y 4” Riser Room OS&Y 4” Riser Room
80 65 75 Within 60
Within 60
Within 60
Within 60
Within 60
Within 60
Within 60
Within 60
Within 60
Within 60
Within 60
Within 60
System #1 - 1st Flr. - Environmental 4” 2” System #2 - 1st Flr. - Administration - Elev. 2 1/2” 2” System #3 - 1st Flr. - Equipment Room 2 1/2” 2” System #4 - 1st Flr. - Equipment Repair 4” 2” System #5 - 1st Flr. - Equipment Room 4” 2” System #6 - 2nd. Flr - Operations / Lobby 4” 2” System #7 - 2nd. Flr - Operations 6” 2” System #8 - 2nd. Flr - Catwalk 6” 2” System #9 - 2nd. Flr - Administration Wing 4” 2” System #10 - 2nd. Flr - 2nd Flr. Administration Wing 4” 2” System #11 - 2nd. Flr - Environmental Supply West 4” 2” System #12 - 2nd. Flr - Administration / Penthouse 4” 2”
Suite 9 Aurora, IL 60502 630.506.5535 www.allegiantfire.net
IL FSC #: FSC0392
Report to:
Property:
Address:
City:
State: Zip:
Date:
Job Number:
Technician:
Annual FIRE SPRINKLER INSPECTION REPORT
INSPECTION & SUGGESTED IMPROVEMENTS WERE DISCUSSED WITH THE UNDERSIGNED OWNER OR OWNERS REPRESENTATIVE:
By this signature, I certify: I state that the information on this form is correct at the time and place of my inspection, and that all equipment tested now was left in operational condition upon completion of this inspection except as noted in comments above.
OWNER / REPRESENTATIVE SIGNATURE INSPECTOR SIGNATURE
IL License #
PRINT NAME DATE PRINT NAME NICET #
Note #
THE INSPECTOR SUGGESTS THE FOLLOWING NECESSARY IMPROVEMENTS:
(these suggestions are not the result of an engineering survey)
MODIFICATIONS OR CORRECTIONS MADE DURING THIS INSPECTION:
Convergint Technologies 10/09/2025
Convergint - FAA-Central Logistics Svc Area, 1100 Bowes 43232892 1100 Bowes
Elgin Jon Rocke
IL 60123
1 5 Year internal pipe and check valve internal pipe and check valve inspection and FDC Hydro (13 Risers, Mixed deck height (~10''-20'', Single FDC).
2 (26) 0-300 Water Gauges due for replacement.
Greg Stritzel 10/09/2025 Jon Rocke 151246
FSI0238