Annual Inspection Report- Elgin TRACON 2025 Fire Alarm.pdf
PDF 1 MB Posted
- Solicitation number
- 697DCK-26-C-00139
About this file
This is a Fire Alarm Systems Inspection Certificate for FAA Tracon Elgin facility located at 1100 Bowes Road, Elgin, Illinois. The inspection was performed by Convergint 101, with Lead Fire Alarm Specialist Eric Skowronski conducting the assessment on March 20, 2025, in accordance with NFPA 72 Standards. The facility's fire alarm system utilizes an EST 3est control panel installed on May 24, 2016, with software version dated July 30, 2019, monitored by EM 24 central station (phone: 1-773-777-0707). The inspection encompassed 696 total devices across five categories: Auxiliary (23 items), Control (43 items), Indicating (46 items), Initiating (563 items), and Supervisory (21 items). All tested items passed inspection with a 100% pass rate across all categories, including 479 smoke detectors, 42 pull stations, 18 duct detectors, 14 waterflow switches, 26 batteries, 15 tamper switches, 12 fan shutdown relays, 11 power supplies, 10 heat detectors, 8 elevator controls, and various other auxiliary and indicating devices.
The inspection documented detailed testing results for all fire alarm components, including battery performance tests showing charge levels ranging from 70% to 100%, verification of central station signal transmission with all signals confirmed received at EM 24 (Operator #114), and comprehensive testing of smoke detectors, heat detectors, pull stations, waterflow switches, and duct detectors throughout the facility's three floors and basement areas. All sprinkler system tamper switches and waterflow sensors for 13 zones tested successfully. The inspector's NICET Fire Alarm Systems Level I certification (Number 160484) validates the inspection credentials. No discrepancies or failed items were identified during the inspection period, with all devices properly addressing life safety requirements for the federal facility.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FAA Tracon Elgin 1100 Bowes Road Elgin, il 60123 1-847-608-5788
Building Contact:
Title:
Environmental Coordinator
Company:
Contact:
Title:
Convergint 101 Eric SkowronskiLead Fire Alarm Specialist
Inspection Date: Mar 20, 2025 Tested to NFPA 72 Standards
Fire Alarm Systems
INSPECTION
CERTIFICATE
This Inspection was performed in accordance with applicable NFPA Standards. The subsequent pages of this report provide performance measurements, listed ranges of acceptable results, and complete documentation of the inspection. Whenever discrepancies exist between acceptable performance standards and actual test results, notes and/or recommended solutions have been proposed or provided for immediate review and approval.
Page of 2 78 Executive Summary
Convergint 101 Download Date: 02/19/2026
EXECUTIVE SUMMARY
Generated by: BuildingReports.com
Building Information FAA Tracon Elgin 1100 Bowes Road Elgin, il 60123 United States of America
Contact:
Phone:
Fax:
Mobile:
Email: G
Inspection Performed By Convergint 101 2000 Center Dr. Ste A315 Hoffman Estates, IL 60192 United States of America
Inspector: E
Phone:
Fax:
Mobile:
Email:
System Control Unit Manufacturer: EST Inspection Date: 03/17/2025 IDC Style:
Model Number: 3est Install Date: 05/24/2016 SLC Style:
Software Version: Version Date: 07/30/2019 NAC Style:
Location: 1st environmental office main panel
Disconnect Location: Disconnect Type:
Current Protection:
Monitoring Company: EM 24 Phone: 1-773-777-0707 Account #:
Central Station Signal Verification Type: Digital Communicator Mfg: EST Model #: 3est
Test Time/Date: 3/20/25 1:09:36 AM Restore Time: Note: Confirmed all signals received with OP #114 @ EM24
Page of 3 78 Executive Summary
Convergint 101 Download Date: 02/19/2026
Building: FAA Tracon Elgin Contact:
Company: Convergint 101 Inspector:
Inspection Summary
Category
Total Items Serviced Passed Failed/Other
Qty % Qty % Qty % Qty %
Auxiliary 23 3.30% 23 100.00% 23 100.00% 0 0.00%
Control 43 6.18% 43 100.00% 43 100.00% 0 0.00%
Indicating 46 6.61% 46 100.00% 46 100.00% 0 0.00%
Initiating 563 80.89% 563 100.00% 563 100.00% 0 0.00%
Supervisory 21 3.02% 21 100.00% 21 100.00% 0 0.00%
Totals 696 100% 696 100.00% 696 100.00% 0 0.00%
Certification
Eric Skowronski Certifications Certification Type Number
NICET Fire Alarm Systems Level I 160484
Page of 4 78 Notes & Recommendations
Convergint 101 Download Date: 02/19/2026
Control Panel: 1 - EST 3estBuilding: FAA Tracon Elgin
NOTES & RECOMMENDATIONS
Generated by: BuildingReports.com
The Notes & Recommendations Report details additional inspection notes made by the Inspectors during the course of the building inspection. Notes are grouped by Category.
Note Device Type Location Comment ScanID
CONTROL
1 Communicator 1st environmental office main panel EM24:
7737770707 ACC. 021408 PASS 408. alarm, trouble, supervisory
Passed 52430868
Confirmed all signals received with OP #114 @ EM24
Page of 5 78 Inspection & Testing
Convergint 101 Download Date: 02/19/2026
Control Panel: 1 - EST 3estBuilding: FAA Tracon Elgin
INSPECTION & TESTING
Generated by: BuildingReports.com
The Inspection & Testing section lists all of the items inspected in your building. Items are grouped by Passed or Failed/Other .
Items are listed by Category. Each item includes the services performed, and the time & date at which testing occurred.
Device Type Location Service Time Date
PASSED
Auxiliary
Fan Shutdown 3rd FL Kitchen PH AHU3 Shutdown Relay Tested 7:30:45 AM 03/18/2025
Fan Shutdown AHU 4 & 5 Shutdown Relay Tested 7:30:39 AM 03/18/2025
Fan Shutdown AHU 6 Shutdown Relay Tested 7:30:20 AM 03/18/2025
Programmable Relay Door Relay In DGP Room Power Supply Tested 11:58:15 PM 03/19/2025
Programmable Relay Door Relay In DGP Room Power Supply Tested 11:58:18 PM 03/19/2025
Programmable Relay Kitchen Penthouse Door Relay In FACP #1 Tested 11:58:12 PM 03/19/2025
Control
Communication Line 1st environmental office main panel Tested 1:09:07 AM 03/20/2025
Communicator 1st environmental office main panel EM24:
7737770707 ACC. 021408 PASS 408. alarm, trouble, supervisory
Tested 1:09:36 AM 03/20/2025
Control Panel 1st environmental office main panel Tested 12:44:12 PM 03/17/2025
Indicating
Indicating Device 1st FL - Horn/Strobe V1-1 - From BPS#1 Tested 11:56:53 PM 03/19/2025
Indicating Device 1st FL - Horn/Strobe V1-10 - From BPS#3 Tested 11:57:02 PM 03/19/2025
Indicating Device 1st FL - Horn/Strobe V1-11 - From BPS#3 Tested 11:57:41 PM 03/19/2025
Indicating Device 1st FL - Horn/Strobe V1-13 - From BPS#4 Tested 11:57:44 PM 03/19/2025
Indicating Device 1st FL - Horn/Strobe V1-14 - From BPS#10 Tested 11:57:37 PM 03/19/2025
Indicating Device 1st FL - Horn/Strobe V1-15 - From BPS#4 Tested 11:57:47 PM 03/19/2025
Indicating Device 1st FL - Horn/Strobe V1-2 - From BPS#1 Tested 11:56:56 PM 03/19/2025
Page of 6 78
Convergint 101 Download Date: 02/19/2026
Device Type Location Service Time Date
PASSED (continued)
Indicating (continued)
Indicating Device 1st FL - Horn/Strobe V1-3 - From BPS#1 Tested 11:57:53 PM 03/19/2025
Indicating Device 1st FL - Horn/Strobe V1-4 - From BPS#1 Tested 11:56:50 PM 03/19/2025
Indicating Device 1st FL - Horn/Strobe V1-5 - From BPS#2 Tested 11:56:35 PM 03/19/2025
Indicating Device 1st FL - Horn/Strobe V1-6 - From BPS#2 Tested 11:57:14 PM 03/19/2025
Indicating Device 1st FL - Horn/Strobe V1-7 - From BPS#2 Tested 11:56:42 PM 03/19/2025
Indicating Device 1st FL - Horn/Strobe V1-8 - From BPS#2 Tested 11:56:37 PM 03/19/2025
Indicating Device 1st FL - Horn/Strobe V1-9 - From BPS#3 Tested 11:57:56 PM 03/19/2025
Indicating Device 1st FL BPS #1 CCMS Office Enviornmental Tested 11:55:44 PM 03/19/2025
Indicating Device 1st FL BPS #1 Sense 2CCMS Room #75 Tested 11:55:41 PM 03/19/2025
Indicating Device 1st FL BPS #10 CO2/DGPOffice Room #101 Tested 11:56:02 PM 03/19/2025
Indicating Device 1st FL BPS #2 Admin Electric Room #51 Tested 11:56:05 PM 03/19/2025
Indicating Device 1st FL BPS #2 Sense 2Electric Room #51 Tested 11:55:57 PM 03/19/2025
Indicating Device 1st FL BPS #4 CCMS Office Enviornmental Tested 11:55:36 PM 03/19/2025
Indicating Device 1st FL BPS #4 Sense 2CCMS Room #75 Tested 11:55:50 PM 03/19/2025
Indicating Device 1st FL BPS #7 CO2/DGPOffice Room #101 Tested 11:56:09 PM 03/19/2025
Indicating Device 1st FL BPS #8 CO2/DGPOffice Room #101 Tested 11:55:38 PM 03/19/2025
Indicating Device 2nd FL - Horn/Strobe V2-1 - From BPS#5 Tested 11:56:26 PM 03/19/2025
Indicating Device 2nd FL - Horn/Strobe V2-10 - From BPS#7 Tested 11:56:59 PM 03/19/2025
Indicating Device 2nd FL - Horn/Strobe V2-11 - From BPS#7 Tested 11:57:21 PM 03/19/2025
Indicating Device 2nd FL - Horn/Strobe V2-2 - From BPS#5 Tested 11:56:47 PM 03/19/2025
Indicating Device 2nd FL - Horn/Strobe V2-3 - From BPS#5 Tested 11:56:32 PM 03/19/2025
Indicating Device 2nd FL - Horn/Strobe V2-4 - From BPS#5 Tested 11:56:44 PM 03/19/2025
Indicating Device 2nd FL - Horn/Strobe V2-5 - From BPS#6 Tested 11:57:11 PM 03/19/2025
Indicating Device 2nd FL - Horn/Strobe V2-9 - From BPS#7 Tested 11:57:18 PM 03/19/2025
Indicating Device 2nd FL - Horn/Strobe V3-4 - From BPS#7 Tested 11:57:08 PM 03/19/2025
Page of 7 78
Convergint 101 Download Date: 02/19/2026
Device Type Location Service Time Date
PASSED (continued)
Indicating (continued)
Indicating Device 2nd FL - Red Lamp V2-13L - From BPS#8 Tested 11:57:34 PM 03/19/2025
Indicating Device 2nd FL - Red Lamp V2-14L - From BPS#8 Tested 11:56:29 PM 03/19/2025
Indicating Device 2nd FL BPS #3 CO2/DGPOffice Room #101 Tested 11:56:14 PM 03/19/2025
Indicating Device 2nd FL BPS #3 Sense 2CO2 Room #101 Tested 11:56:11 PM 03/19/2025
Indicating Device 2nd FL BPS #5 Admin Electric Room #242 Tested 11:56:20 PM 03/19/2025
Indicating Device 2nd FL BPS #5 Sense 2Electric Room #242 Tested 11:55:47 PM 03/19/2025
Indicating Device 2nd FL BPS #6 Admin Electric Room #242 Tested 11:56:23 PM 03/19/2025
Indicating Device 2nd FL BPS #6 Sense 2Electric Room #242 Tested 11:56:00 PM 03/19/2025
Indicating Device 2nd FL BPS #7 Sense 2CO2 Room #101 Tested 11:56:17 PM 03/19/2025
Indicating Device 2nd FL BPS#10 Sense 2CO2 Room #101 Tested 11:55:53 PM 03/19/2025
Indicating Device 3rd FL - Horn/Strobe V3-1 - From BPS#4 Tested 11:57:50 PM 03/19/2025
Indicating Device 3rd FL - Horn/Strobe V3-2 - From BPS#6 Tested 11:57:25 PM 03/19/2025
Indicating Device 3rd FL - Horn/Strobe V3-3 - From BPS#6 Tested 11:57:29 PM 03/19/2025
Initiating
Duct Detector 1st FL Enviornmental AHU 4&5 Return Duct Tested 7:14:55 AM 03/18/2025
Duct Detector 1st FL Enviornmental AHU 4&5 Supply Duct Tested 7:15:50 AM 03/18/2025
Duct Detector 3rd FL Kitchen PH AHU3 Supply Duct Tested 7:09:43 AM 03/18/2025
Duct Detector 1st Enviorn. AHU 6Supply Duct Detector Tested 7:13:41 AM 03/18/2025
Heat Detector 1st FL Generator Room Heat Detector Tested 6:43:33 AM 03/18/2025
Heat Detector 1st FL Generator Room Heat Detector Tested 6:43:45 AM 03/18/2025
Heat Detector 1st FL Generator Room Heat Detector Tested 6:43:48 AM 03/18/2025
Heat Detector PIT Passenger Elevator Pit Heat Detector Tested 12:53:26 PM 03/19/2025
Heat Detector 1st Generator Room Heat Detector Tested 6:43:29 AM 03/18/2025
Pull Station 1st FL Admin East Lobby Pull Station Tested 7:17:47 AM 03/17/2025
Pull Station 1st FL Admin N. Corr.Pull Station Tested 6:45:52 AM 03/17/2025
Page of 8 78
Convergint 101 Download Date: 02/19/2026
Device Type Location Service Time Date
PASSED (continued)
Initiating (continued)
Pull Station 1st FL Admin SE By Stair 1 Pull Station Tested 7:14:56 AM 03/17/2025
Pull Station 1st FL Battery Room Pull Station Tested 12:28:22 PM 03/17/2025
Pull Station 1st FL Battery Room Pull Station Tested 12:28:43 PM 03/17/2025
Pull Station 1st FL Boiler Room Pull Station Tested 12:24:29 PM 03/17/2025
Pull Station 1st FL Dock Area S. Pull Station Tested 11:42:30 AM 03/17/2025
Pull Station 1st FL Generator Elec. RM Pull Station Tested 12:09:19 PM 03/17/2025
Pull Station 1st FL Generator Elec. RM Pull Station Tested 6:43:56 AM 03/18/2025
Pull Station 1st FL Generator RoomPull Station Tested 6:42:15 AM 03/18/2025
Pull Station 1st FL Generator RoomPull Station Tested 6:43:16 AM 03/18/2025
Pull Station 1st FL Machine Shop Pull Station Tested 11:53:19 AM 03/17/2025
Pull Station 1st FL Mechanical Room Pull Station Tested 11:56:25 AM 03/17/2025
Pull Station 1st FL Mechanical Room Pull Station Tested 11:59:06 AM 03/17/2025
Pull Station 1st FL Mechanical Room Pull Station Tested 12:01:09 PM 03/17/2025
Pull Station 1st FL UPS Room Pull Station Tested 12:17:04 PM 03/17/2025
Pull Station 1st FL UPS Room Pull Station Tested 12:23:08 PM 03/17/2025
Pull Station 1st FL W. Corridor ByStair 2 Pull Station Tested 6:53:31 AM 03/17/2025
Pull Station 1st FL W. Dock Area Pull Station Tested 11:42:52 AM 03/17/2025
Pull Station 1st FL W. Vestibule Pull Station Tested 6:42:06 AM 03/17/2025
Pull Station 1st FL West Lounge Pull Station Tested 6:43:59 AM 03/17/2025
Pull Station 1st FL West Lounge Pull Station Tested 6:44:58 AM 03/17/2025
Pull Station 3rd FL Kitchen PH Pull Station Tested 11:48:25 AM 03/17/2025
Smoke Detector 1st FL Admin E. Corr.By AT Waiting Smoke Tested/Cleaned 7:14:06 AM 03/17/2025
Smoke Detector 1st FL Admin Logist. Spec. Office Smoke Tested/Cleaned 6:54:44 AM 03/17/2025
Smoke Detector 1st FL Admin Men's Room Smoke Detector Tested/Cleaned 7:13:11 AM 03/17/2025
Smoke Detector 1st FL Admin N. By Main Stair Smoke Tested/Cleaned 6:41:07 AM 03/17/2025
Page of 9 78
Convergint 101 Download Date: 02/19/2026
Device Type Location Service Time Date
PASSED (continued)
Initiating (continued)
Smoke Detector 1st FL Admin NW Corr.By AF Conf. RM Smoke
Tested/Cleaned 6:57:19 AM 03/17/2025
Smoke Detector 1st FL Admin NW PSU Secretary Smoke Tested/Cleaned 6:55:16 AM 03/17/2025
Smoke Detector 1st FL Admin NW PSU/ Admin Officer Smoke Tested/Cleaned 6:56:15 AM 03/17/2025
Smoke Detector 1st FL Admin NW PSU/ DSS Office Smoke Tested/Cleaned 9:29:00 AM 03/18/2025
Smoke Detector 1st FL Admin NW PSU/ MSS Office Smoke Tested/Cleaned 9:28:57 AM 03/18/2025
Smoke Detector 1st FL Admin S. AATM Office Smoke Tested/Cleaned 7:12:13 AM 03/17/2025
Smoke Detector 1st FL Admin S. QA/ AMA Office Smoke Tested/Cleaned 7:07:14 AM 03/17/2025
Smoke Detector 1st FL Admin SE AT Confernece Room Smoke
Tested/Cleaned 7:15:13 AM 03/17/2025
Smoke Detector 1st FL Admin SE AT Manager Office Smoke Tested/Cleaned 7:12:38 AM 03/17/2025
Smoke Detector 1st FL Admin SW AMPP Office Smoke Tested/Cleaned 7:03:14 AM 03/17/2025
Smoke Detector 1st FL Admin SW AMPP Office Smoke Tested/Cleaned 7:03:40 AM 03/17/2025
Smoke Detector 1st FL Admin SW Corr.By QA Office Smoke Tested/Cleaned 7:04:44 AM 03/17/2025
Smoke Detector 1st FL Admin SW PlansConference Room Smoke
Tested/Cleaned 7:03:04 AM 03/17/2025
Smoke Detector 1st FL Admin Storage Room Smoke Tested/Cleaned 7:09:36 AM 03/17/2025
Smoke Detector 1st FL Admin W. Corr.By AF Office Smoke Tested/Cleaned 6:58:38 AM 03/17/2025
Smoke Detector 1st FL Admin W. PASS Office Smoke Tested/Cleaned 6:58:52 AM 03/17/2025
Smoke Detector 1st FL Admin W. PPS/ APS Area Smoke Tested/Cleaned 6:59:40 AM 03/17/2025
Smoke Detector 1st FL Admin W. PSS Storage Room Smoke Tested/Cleaned 7:01:39 AM 03/17/2025
Smoke Detector 1st FL Admin WashroomSmoke Detector Tested/Cleaned 7:15:41 AM 03/17/2025
Smoke Detector 1st FL Admin WashroomSmoke Detector Tested/Cleaned 7:15:53 AM 03/17/2025
Smoke Detector 1st FL Admin Women's Room Smoke Detector
Tested/Cleaned 7:13:50 AM 03/17/2025
Smoke Detector 1st FL Dock Area Janitor Closet Smoke Tested/Cleaned 8:36:46 AM 03/18/2025
Smoke Detector 1st FL Dock Area Womens Washroom Smoke Tested/Cleaned 11:42:02 AM 03/17/2025
Page of 10 78
Convergint 101 Download Date: 02/19/2026
Device Type Location Service Time Date
PASSED (continued)
Initiating (continued)
Smoke Detector 1st FL Generator Electric Room Smoke Tested/Cleaned 12:10:26 PM 03/17/2025
Smoke Detector 1st FL Maintenance Office by FACP Smoke Tested/Cleaned 6:33:47 AM 03/17/2025
Smoke Detector 1st FL Mechanical Room Smoke Detector Tested/Cleaned 12:00:15 PM 03/17/2025
Smoke Detector 1st FL Mechanical Room Smoke Detector Tested/Cleaned 12:02:06 PM 03/17/2025
Smoke Detector 1st FL NW Cafeteria Lounge Smoke Detector Tested/Cleaned 6:44:10 AM 03/17/2025
Smoke Detector 1st FL NW Cafeteria Smoke Detector Tested/Cleaned 6:42:27 AM 03/17/2025
Smoke Detector 1st FL NW Cafeteria Smoke Detector Tested/Cleaned 6:43:37 AM 03/17/2025
Smoke Detector 1st FL NW Dock Area Smoke Detector Tested/Cleaned 12:41:07 PM 03/17/2025
Smoke Detector 1st FL NW Kitchen Smoke Detector Tested/Cleaned 6:39:06 AM 03/17/2025
Smoke Detector 1st FL SW Cafeteria Smoke Detector Tested/Cleaned 6:45:24 AM 03/17/2025
Smoke Detector 1st FL UPS Room Smoke Detector Tested/Cleaned 12:19:22 PM 03/17/2025
Smoke Detector 3rd FL Kitchen Penthouse Smoke Tested/Cleaned 11:50:20 AM 03/17/2025
Smoke Detector PIT Passenger Elevator Pit Smoke Detector Tested/Cleaned 12:53:33 PM 03/19/2025
Smoke Detector 1st 1st FL Admin CorridorBy Conference Smoke
Tested/Cleaned 6:47:12 AM 03/17/2025
Smoke Detector 1st 1st FL Admin NW AF Technician Area Smoke
Tested/Cleaned 6:56:57 AM 03/17/2025
Smoke Detector 1st 1st FL Admin Pass. Elev. Lobby Smoke Tested/Cleaned 7:18:25 AM 03/17/2025
Smoke Detector 1st 1st FL Admin S. AT Clerk Office Smoke Tested/Cleaned 7:11:11 AM 03/17/2025
Smoke Detector 1st 1st FL NW Cafeteria Smoke Detector Tested/Cleaned 6:42:59 AM 03/17/2025
Smoke Detector 1st 1st FL UPS Room Smoke Detector Tested/Cleaned 12:13:13 PM 03/17/2025
Smoke Detector 1st 1st FL UPS Room Smoke Detector Tested/Cleaned 12:18:22 PM 03/17/2025
Smoke Detector 1st Admin AF Asst.Manager Smoke Tested/Cleaned 6:48:31 AM 03/17/2025
Smoke Detector 1st Admin AF Conference Room Smoke Tested/Cleaned 6:57:41 AM 03/17/2025
Smoke Detector 1st Admin AF Copy/Storage Room Smoke Tested/Cleaned 6:53:51 AM 03/17/2025
Smoke Detector 1st Admin AF Manager Smoke Tested/Cleaned 6:50:17 AM 03/17/2025
Page of 11 78
Convergint 101 Download Date: 02/19/2026
Device Type Location Service Time Date
PASSED (continued)
Initiating (continued)
Smoke Detector 1st Admin AF Office Smoke Tested/Cleaned 6:49:19 AM 03/17/2025
Smoke Detector 1st Admin AF Secretary Smoke Tested/Cleaned 6:48:19 AM 03/17/2025
Smoke Detector 1st Admin E. LobbySmoke Detector Tested/Cleaned 7:17:24 AM 03/17/2025
Smoke Detector 1st Admin E. Security Office Smoke Tested/Cleaned 7:17:02 AM 03/17/2025
Smoke Detector 1st Admin Joint Conference Room Smoke Tested/Cleaned 6:46:36 AM 03/17/2025
Smoke Detector 1st Admin Joint Conference Room Smoke 59 Tested/Cleaned 6:46:45 AM 03/17/2025
Smoke Detector 1st Admin NW AF Technician Area Smoke Tested/Cleaned 6:56:42 AM 03/17/2025
Smoke Detector 1st Admin NW Corr.By AF Conf. RM Smoke Tested/Cleaned 6:55:02 AM 03/17/2025
Smoke Detector 1st Admin NW Corr.By AF Manager Smoke Tested/Cleaned 6:47:33 AM 03/17/2025
Smoke Detector 1st Admin NW Corr.By AF Manager Smoke Tested/Cleaned 6:47:43 AM 03/17/2025
Smoke Detector 1st Admin NW Corr.By AF Tech Area Smoke Tested/Cleaned 6:58:24 AM 03/17/2025
Smoke Detector 1st Admin NW Corr.By Stair 2 Smoke Tested/Cleaned 6:53:24 AM 03/17/2025
Smoke Detector 1st Admin NW Electric Room Smoke Tested/Cleaned 6:52:58 AM 03/17/2025
Smoke Detector 1st Admin NW PSU/ Sector Analyst Smoke Tested/Cleaned 6:55:47 AM 03/17/2025
Smoke Detector 1st Admin NW Waiting Area Smoke Tested/Cleaned 7:16:27 AM 03/17/2025
Smoke Detector 1st Admin NW Women's Locker Smoke Tested/Cleaned 6:51:49 AM 03/17/2025
Smoke Detector 1st Admin S. AMA Office Smoke Tested/Cleaned 7:11:42 AM 03/17/2025
Smoke Detector 1st Admin S. AT Office Smoke Tested/Cleaned 7:06:30 AM 03/17/2025
Smoke Detector 1st Admin S. AT Office Smoke Tested/Cleaned 7:10:42 AM 03/17/2025
Smoke Detector 1st Admin S. Corr.By Women Locker Smoke Tested/Cleaned 7:09:59 AM 03/17/2025
Smoke Detector 1st Admin S. Corr.By Women Locker Smoke Tested/Cleaned 7:10:30 AM 03/17/2025
Smoke Detector 1st Admin S. QA/ AMQA Office Smoke Tested/Cleaned 7:06:11 AM 03/17/2025
Smoke Detector 1st Admin SE Corr.By AT Manager Smoke Tested/Cleaned 7:14:20 AM 03/17/2025
Smoke Detector 1st Admin SW AT Copy/Storage RM Smoke Tested/Cleaned 7:07:47 AM 03/17/2025
Smoke Detector 1st Admin SW Conference Room Smoke 37 Tested/Cleaned 7:02:09 AM 03/17/2025
Page of 12 78
Convergint 101 Download Date: 02/19/2026
Device Type Location Service Time Date
PASSED (continued)
Initiating (continued)
Smoke Detector 1st Admin SW Corr.By AT Office Smoke Tested/Cleaned 7:01:25 AM 03/17/2025
Smoke Detector 1st Admin SW QA Office Smoke Tested/Cleaned 7:05:01 AM 03/17/2025
Smoke Detector 1st Admin SW QA Playback Office Smoke Tested/Cleaned 7:05:30 AM 03/17/2025
Smoke Detector 1st Admin SW QA Storage Room Smoke Tested/Cleaned 7:05:45 AM 03/17/2025
Smoke Detector 1st Admin Vending Area Smoke Detector Tested/Cleaned 6:41:34 AM 03/17/2025
Smoke Detector 1st Admin W OfficeBy Elec Room Smoke Tested/Cleaned 6:58:01 AM 03/17/2025
Smoke Detector 1st Admin W. By Men's Locker Smoke Tested/Cleaned 7:09:03 AM 03/17/2025
Smoke Detector 1st Admin W. Corr.By Men's Locker Smoke Tested/Cleaned 7:08:12 AM 03/17/2025
Smoke Detector 1st Admin W. Corr.By Men's Locker Smoke Tested/Cleaned 7:08:36 AM 03/17/2025
Smoke Detector 1st Admin W. Corr.By PPS/APS Area Smoke Tested/Cleaned 7:00:36 AM 03/17/2025
Smoke Detector 1st Admin W. Electric Room Smoke Tested/Cleaned 7:01:03 AM 03/17/2025
Smoke Detector 1st Admin W. PPS/ APS Area Smoke Tested/Cleaned 6:59:22 AM 03/17/2025
Smoke Detector 1st Admin W. PPS/ APS Area Smoke Tested/Cleaned 7:00:11 AM 03/17/2025
Smoke Detector 1st Battery Room Smoke Detector Tested/Cleaned 12:26:30 PM 03/17/2025
Smoke Detector 1st Battery Room Smoke Detector Tested/Cleaned 12:27:12 PM 03/17/2025
Smoke Detector 1st Battery Room Smoke Detector Tested/Cleaned 12:27:57 PM 03/17/2025
Smoke Detector 1st Caferteria Servery Line Smoke Tested/Cleaned 6:37:42 AM 03/17/2025
Smoke Detector 1st Dock Area MensWashroom Smoke Tested/Cleaned 11:42:12 AM 03/17/2025
Smoke Detector 1st FL Admin NW Badging Office Smoke Tested/Cleaned 6:51:19 AM 03/17/2025
Smoke Detector 1st FL Mechanical Room Smoke Detector Tested/Cleaned 11:57:34 AM 03/17/2025
Smoke Detector 1st Generator Electric Room Smoke Tested/Cleaned 12:08:46 PM 03/17/2025
Smoke Detector 1st Generator Electric Room Smoke Tested/Cleaned 12:09:06 PM 03/17/2025
Smoke Detector 1st Generator Electric Room Smoke Tested/Cleaned 12:10:00 PM 03/17/2025
Smoke Detector 1st Mechanical Room Smoke Detector Tested/Cleaned 11:55:12 AM 03/17/2025
Smoke Detector 1st Mechanical Room Smoke Detector Tested/Cleaned 11:56:04 AM 03/17/2025
Page of 13 78
Convergint 101 Download Date: 02/19/2026
Device Type Location Service Time Date
PASSED (continued)
Initiating (continued)
Smoke Detector 1st Mechanical Room Smoke Detector Tested/Cleaned 11:56:56 AM 03/17/2025
Smoke Detector 1st Mechanical Room Smoke Detector Tested/Cleaned 11:58:07 AM 03/17/2025
Smoke Detector 1st Mechanical Room Smoke Detector Tested/Cleaned 11:58:29 AM 03/17/2025
Smoke Detector 1st Mechanical Room Smoke Detector Tested/Cleaned 11:58:43 AM 03/17/2025
Smoke Detector 1st Mechanical Room Smoke Detector Tested/Cleaned 11:59:48 AM 03/17/2025
Smoke Detector 1st Mechanical Room Smoke Detector Tested/Cleaned 12:00:34 PM 03/17/2025
Smoke Detector 1st Mechanical Room Smoke Detector Tested/Cleaned 12:00:53 PM 03/17/2025
Smoke Detector 1st Mechanical Room Smoke Detector Tested/Cleaned 12:01:41 PM 03/17/2025
Smoke Detector 1st Mechanical Room Smoke Detector Tested/Cleaned 12:04:00 PM 03/17/2025
Smoke Detector 1st Mechanical Room Smoke Detector Tested/Cleaned 12:05:09 PM 03/17/2025
Smoke Detector 1st Mechanical Room Smoke Detector Tested/Cleaned 12:06:04 PM 03/17/2025
Smoke Detector 1st Mechanical Room Smoke Detector Tested/Cleaned 12:07:20 PM 03/17/2025
Smoke Detector 1st Mechanical Room Smoke Detector Tested/Cleaned 12:39:36 PM 03/17/2025
Smoke Detector 1st Mechanical Room Smoke Detector Tested/Cleaned 12:39:44 PM 03/17/2025
Smoke Detector 1st NW Cafeteria Smoke Detector Tested/Cleaned 6:42:47 AM 03/17/2025
Smoke Detector 1st NW Dock Area Smoke Detector Tested/Cleaned 11:43:26 AM 03/17/2025
Smoke Detector 1st NW Dock Area Smoke Detector Tested/Cleaned 11:44:06 AM 03/17/2025
Smoke Detector 1st NW Dock Area Smoke Detector Tested/Cleaned 11:46:05 AM 03/17/2025
Smoke Detector 1st NW Kitchen DryStorage Smoke Tested/Cleaned 6:40:01 AM 03/17/2025
Smoke Detector 1st NW Kitchen Office Smoke Detector Tested/Cleaned 6:39:44 AM 03/17/2025
Smoke Detector 1st NW Kitchen Serving Area Smoke Tested/Cleaned 6:38:03 AM 03/17/2025
Smoke Detector 1st NW Kitchen Smoke Detector Tested/Cleaned 6:39:29 AM 03/17/2025
Smoke Detector 1st NW Lounge AreaSmoke Detector Tested/Cleaned 6:44:43 AM 03/17/2025
Smoke Detector 1st NW Sprinkler Riser Room Smoke Tested/Cleaned 8:35:54 AM 03/18/2025
Smoke Detector 1st NW Storage By Dock Smoke Detector Tested/Cleaned 11:52:56 AM 03/17/2025
Page of 14 78
Convergint 101 Download Date: 02/19/2026
Device Type Location Service Time Date
PASSED (continued)
Initiating (continued)
Smoke Detector 1st NW Storage By Dock Smoke Detector Tested/Cleaned 11:53:07 AM 03/17/2025
Smoke Detector 1st Tool Shop By Dock Smoke Detector Tested/Cleaned 8:43:15 AM 03/18/2025
Smoke Detector 1st Tool Storage Room Smoke Detector Tested/Cleaned 11:54:15 AM 03/17/2025
Smoke Detector 1st UPS Room Smoke Detector Tested/Cleaned 12:14:12 PM 03/17/2025
Smoke Detector 1st UPS Room Smoke Detector Tested/Cleaned 12:15:59 PM 03/17/2025
Smoke Detector 1st UPS Room Smoke Detector Tested/Cleaned 12:16:36 PM 03/17/2025
Smoke Detector 1st UPS Room Smoke Detector Tested/Cleaned 12:21:12 PM 03/17/2025
Smoke Detector 1st UPS Room Smoke Detector Tested/Cleaned 12:21:41 PM 03/17/2025
Smoke Detector 1st UPS Room Smoke Detector Tested/Cleaned 12:22:32 PM 03/17/2025
Smoke Detector 3rd 3rd FL Kitchen Penthouse Smoke Tested/Cleaned 11:49:38 AM 03/17/2025
Smoke Detector 3rd FL Kitchen PH Topof Stair Smoke Tested/Cleaned 11:47:25 AM 03/17/2025
Smoke Detector 3rd Kitchen Penthouse Smoke Tested/Cleaned 11:47:52 AM 03/17/2025
Smoke Detector 3rd Kitchen Penthouse Smoke Tested/Cleaned 11:48:10 AM 03/17/2025
Smoke Detector 3rd Kitchen Penthouse Smoke Tested/Cleaned 11:48:42 AM 03/17/2025
Smoke Detector 3rd Kitchen Penthouse Smoke Tested/Cleaned 11:49:01 AM 03/17/2025
Smoke Detector 3rd Kitchen Penthouse Smoke Tested/Cleaned 11:49:22 AM 03/17/2025
Smoke Detector 3rd Kitchen Penthouse Smoke Tested/Cleaned 11:50:01 AM 03/17/2025
Smoke Detector 3rd Kitchen Penthouse Smoke Tested/Cleaned 11:50:49 AM 03/17/2025
Waterflow Switch Sprinkler Riser Room Main Waterflow Tested 12:30:42 PM 03/17/2025
Waterflow Switch Sprinkler Zone 1 Waterflow Tested 12:30:39 PM 03/17/2025
Waterflow Switch Sprinkler Zone 10 Waterflow Tested 12:30:12 PM 03/17/2025
Waterflow Switch Sprinkler Zone 11 Waterflow Tested 12:30:09 PM 03/17/2025
Waterflow Switch Sprinkler Zone 12 Waterflow Tested 12:30:06 PM 03/17/2025
Waterflow Switch Sprinkler Zone 13 Waterflow Tested 12:29:55 PM 03/17/2025
Waterflow Switch Sprinkler Zone 2 Waterflow Tested 12:30:37 PM 03/17/2025
Page of 15 78
Convergint 101 Download Date: 02/19/2026
Device Type Location Service Time Date
PASSED (continued)
Initiating (continued)
Waterflow Switch Sprinkler Zone 3 Waterflow Tested 12:30:34 PM 03/17/2025
Waterflow Switch Sprinkler Zone 4 Waterflow Tested 12:30:31 PM 03/17/2025
Waterflow Switch Sprinkler Zone 5 Waterflow Tested 12:30:28 PM 03/17/2025
Waterflow Switch Sprinkler Zone 6 Waterflow Tested 12:30:25 PM 03/17/2025
Waterflow Switch Sprinkler Zone 7 Waterflow Tested 12:30:21 PM 03/17/2025
Waterflow Switch Sprinkler Zone 8 Waterflow Tested 12:30:18 PM 03/17/2025
Waterflow Switch Sprinkler Zone 9 Waterflow Tested 12:30:14 PM 03/17/2025
Supervisory
Supervisory Device 1st FL Generator Room Heat Trace Tested 6:28:35 AM 03/18/2025
Supervisory Device 1st FL Mechanical Room Heat Trace Tested 6:28:26 AM 03/18/2025
Supervisory Device 2nd Red Lamp Power monitor Tested 11:58:06 PM 03/19/2025
Supervisory Device 2nd Red Lamp Power monitor Tested 11:58:09 PM 03/19/2025
Tamper Switch Incoming Water Valve Tamper #1 Tested 12:29:14 PM 03/17/2025
Tamper Switch Incoming Water Valve Tamper #2 Tested 12:29:11 PM 03/17/2025
Tamper Switch Sprinkler Zone 1 Valve Tamper Tested 12:29:17 PM 03/17/2025
Tamper Switch Sprinkler Zone 10 Valve Tamper Tested 12:29:43 PM 03/17/2025
Tamper Switch Sprinkler Zone 11 Valve Tamper Tested 12:29:47 PM 03/17/2025
Tamper Switch Sprinkler Zone 12 Valve Tamper Tested 12:29:50 PM 03/17/2025
Tamper Switch Sprinkler Zone 13 Valve Tamper Tested 12:29:52 PM 03/17/2025
Tamper Switch Sprinkler Zone 2 Valve Tamper Tested 12:29:20 PM 03/17/2025
Tamper Switch Sprinkler Zone 3 Valve Tamper Tested 12:29:23 PM 03/17/2025
Tamper Switch Sprinkler Zone 4 Valve Tamper Tested 12:29:25 PM 03/17/2025
Tamper Switch Sprinkler Zone 5 Valve Tamper Tested 12:29:28 PM 03/17/2025
Tamper Switch Sprinkler Zone 6 Valve Tamper Tested 12:29:31 PM 03/17/2025
Tamper Switch Sprinkler Zone 7 Valve Tamper Tested 12:29:34 PM 03/17/2025
Page of 16 78
Convergint 101 Download Date: 02/19/2026
Control Panel: 2 - EST Siga278Building: FAA Tracon Elgin
Device Type Location Service Time Date
PASSED (continued)
Supervisory (continued)
Tamper Switch Sprinkler Zone 8 Valve Tamper Tested 12:29:37 PM 03/17/2025
Tamper Switch Sprinkler Zone 9 Valve Tamper Tested 12:29:40 PM 03/17/2025
Device Type Location Service Time Date
PASSED
Auxiliary
Elevator 1st Equipment ElevCar #1 Alt. Relay Tested 12:54:50 PM 03/19/2025
Elevator 1st Equipment ElevCar #1 Hat Relay Tested 12:54:53 PM 03/19/2025
Elevator 1st Equipment ElevCar #1 Primary Relay Tested 12:54:47 PM 03/19/2025
Elevator 1st Equipment ElevCar #1 Shunt Relay Tested 12:54:56 PM 03/19/2025
Elevator 1st Equipment ElevCar #2 Alt. Relay Tested 1:15:45 PM 03/19/2025
Elevator 1st Equipment ElevCar #2 Hat Relay Tested 1:15:48 PM 03/19/2025
Elevator 1st Equipment ElevCar #2 Primary Relay Tested 1:15:42 PM 03/19/2025
Elevator 1st Equipment ElevCar #2 Shunt Relay Tested 1:15:51 PM 03/19/2025
Fan Shutdown 3rd FL Admin Mech. AHU 1 Return Relay Tested 7:30:27 AM 03/18/2025
Fan Shutdown 3rd FL Admin Mech. AHU 1 Supply Relay Tested 7:30:33 AM 03/18/2025
Fan Shutdown 3rd FL Admin Mech. AHU 2 Return Relay Tested 7:30:36 AM 03/18/2025
Fan Shutdown 3rd FL Admin Mech. AHU 2 Supply Relay Tested 7:30:30 AM 03/18/2025
Fan Shutdown AHU 17 Shutdown Relay Tested 7:30:52 AM 03/18/2025
Fan Shutdown AHU 18 Shutdown Relay Tested 7:30:17 AM 03/18/2025
Fan Shutdown AHU 19 Shutdown Relay Tested 7:30:23 AM 03/18/2025
Fan Shutdown AHU 20 Shutdown Relay Tested 7:30:48 AM 03/18/2025
Fan Shutdown AHU 21 Shutdown Relay Tested 7:30:42 AM 03/18/2025
Control
Battery 1st Admin wing electrical closet BPS 2 Tested 8:58:45 AM 03/18/2025
Page of 17 78
Convergint 101 Download Date: 02/19/2026
Device Type Location Service Time Date
PASSED (continued)
Control (continued)
Battery 1st Admin wing electrical closet BPS 2 Tested 8:59:12 AM 03/18/2025
Battery 1st CO2 FACP room BPS 3 Tested 8:49:22 AM 03/18/2025
Battery 1st CO2 FACP room BPS 3 Tested 8:49:48 AM 03/18/2025
Battery 1st CO2 FACP room BPS 7 Tested 8:51:25 AM 03/18/2025
Battery 1st CO2 FACP room BPS 7 Tested 8:52:22 AM 03/18/2025
Battery 1st CO2 FACP room BPS 8 Tested 8:52:26 AM 03/18/2025
Battery 1st CO2 FACP room BPS 8 Tested 8:52:40 AM 03/18/2025
Battery 1st CO2 FACP room BPS10 Tested 8:47:09 AM 03/18/2025
Battery 1st CO2 FACP room BPS10 Tested 8:47:18 AM 03/18/2025
Battery 1st CO2 FACP room Door holders Tested 8:50:25 AM 03/18/2025
Battery 1st CO2 FACP room Door holders Tested 8:50:31 AM 03/18/2025
Battery 1st CO2 FACP room below main panel Tested 8:55:18 AM 03/18/2025
Battery 1st CO2 FACP room below main panel Tested 8:55:57 AM 03/18/2025
Battery 1st CO2 FACP room bottom cabinet apu Tested 8:56:49 AM 03/18/2025
Battery 1st CO2 FACP room bottom cabinet apu Tested 8:56:52 AM 03/18/2025
Battery 1st Environmental FACP BPS1 Tested 9:25:21 AM 03/17/2025
Battery 1st Environmental FACP BPS1 Tested 9:25:28 AM 03/17/2025
Battery 1st Environmental FACP BPS1 Tested 9:39:59 AM 03/17/2025
Battery 1st Environmental FACP BPS1 Tested 9:40:07 AM 03/17/2025
Battery 1st Environmental FACP BPS4 Tested 9:25:44 AM 03/17/2025
Battery 1st Environmental FACP BPS4 Tested 9:25:52 AM 03/17/2025
Battery 2nd Admin wing electrical closet BPS5 Tested 9:02:53 AM 03/18/2025
Battery 2nd Admin wing electrical closet BPS5 Tested 9:03:01 AM 03/18/2025
Battery 2nd Admin wing electrical closet BPS6 Tested 9:01:48 AM 03/18/2025
Battery 2nd Admin wing electrical closet BPS6 Tested 9:01:57 AM 03/18/2025
Page of 18 78
Convergint 101 Download Date: 02/19/2026
Device Type Location Service Time Date
PASSED (continued)
Control (continued)
Control Panel 1st CO2 FACP room main panel 2 Tested 12:44:06 PM 03/17/2025
Power Supply 1st Admin wing electrical closet BPS2 Tested 8:58:43 AM 03/18/2025
Power Supply 1st CO2 FACP room BPS 3 Tested 8:49:29 AM 03/18/2025
Power Supply 1st CO2 FACP room BPS 7 Tested 9:13:03 AM 03/18/2025
Power Supply 1st CO2 FACP room BPS 8 Tested 8:52:48 AM 03/18/2025
Power Supply 1st CO2 FACP room BPS10 Tested 8:47:26 AM 03/18/2025
Power Supply 1st CO2 FACP room Door Holder Tested 8:50:24 AM 03/18/2025
Power Supply 1st CO2 FACP room bottom cabinet Tested 8:56:46 AM 03/18/2025
Power Supply 1st environment BPS 1 FACP room Tested 9:25:15 AM 03/17/2025
Power Supply 1st environment BPS 4 FACP room Tested 9:25:40 AM 03/17/2025
Power Supply 2nd Admin wing electrical closet BPS5 Tested 9:01:42 AM 03/18/2025
Power Supply 2nd Admin wing electrical closet BPS5 Tested 9:02:51 AM 03/18/2025
Printer 1st CO2 FACP room main panel 2 Tested 9:13:06 AM 03/18/2025
Indicating
Strobe 2nd In Situation room 249. Tested 11:57:59 PM 03/19/2025
Initiating
Duct Detector 2nd FL Ops. AHU 17 Supply Duct Detector Tested 7:24:26 AM 03/18/2025
Duct Detector 2nd FL Ops. AHU 18 Return Duct Detector Tested 7:24:37 AM 03/18/2025
Duct Detector 2nd FL Ops. AHU 18 Supply Duct Detector Tested 7:24:33 AM 03/18/2025
Duct Detector 2nd FL Ops. AHU 19 Return Duct Detector Tested 7:20:49 AM 03/18/2025
Duct Detector 2nd FL Ops. AHU 20 Return Duct Detector Tested 7:20:43 AM 03/18/2025
Duct Detector 2nd FL Ops. AHU 20 Supply Duct Detector Tested 7:20:46 AM 03/18/2025
Duct Detector 2nd FL Ops. AHU 21 Return Duct Detector Tested 7:20:36 AM 03/18/2025
Duct Detector 2nd FL Ops. AHU 21 Supply Duct Detector Tested 7:20:40 AM 03/18/2025
Duct Detector 3rd FL Admin Mech. AHU 1 Return Duct Det Tested 7:00:01 AM 03/18/2025
Page of 19 78
Convergint 101 Download Date: 02/19/2026
Device Type Location Service Time Date
PASSED (continued)
Initiating (continued)
Duct Detector 3rd FL Admin Mech. AHU 1 Supply Duct Det Tested 6:59:27 AM 03/18/2025
Duct Detector 3rd FL Admin Mech. AHU 2 Return Duct Det Tested 7:05:18 AM 03/18/2025
Duct Detector 3rd FL Admin Mech. AHU 2 Supply Duct Det Tested 7:04:15 AM 03/18/2025
Duct Detector 2nd Ops. AHU 17 Return Duct Detector Tested 7:24:30 AM 03/18/2025
Duct Detector 2nd Ops. AHU 19 Supply Duct Detector Tested 7:20:53 AM 03/18/2025
Heat Detector 2nd FL Admin NE Smoking Room Heat Tested 6:54:20 AM 03/18/2025
Heat Detector PIT Freight Elevator Pit Heat Detector Tested 1:15:54 PM 03/19/2025
Heat Detector TOS Freight Elevator Top of Shaft Heat Tested 1:15:57 PM 03/19/2025
Heat Detector TOS Passenger Elevator Top of Shaft Heat Tested 12:53:52 PM 03/19/2025
Heat Detector 1st Elevator Machine Room Heat Tested 6:54:15 AM 03/18/2025
Pull Station 1st FL Equipment RoomEast Pull Station Tested 9:41:46 AM 03/17/2025
Pull Station 1st FL Equipment RoomN.E. Pull Station Tested 9:37:04 AM 03/17/2025
Pull Station 1st FL Equipment RoomN.W. Pull Station Tested 10:06:52 AM 03/17/2025
Pull Station 1st FL Equipment RoomN.W. Pull Station Tested 12:41:47 PM 03/17/2025
Pull Station 1st FL Equipment RoomNorth Pull Station Tested 10:05:25 AM 03/17/2025
Pull Station 1st FL Equipment RoomStair #4 Pull Station Tested 8:30:53 AM 03/18/2025
Pull Station 1st FL Equipment RoomWest Pull Station Tested 9:23:35 AM 03/17/2025
Pull Station 2nd FL Admin N. Pull Station By Stair 2 Tested 7:30:51 AM 03/17/2025
Pull Station 2nd FL Admin SE Pull Station By Stair 1 Tested 7:53:25 AM 03/17/2025
Pull Station 2nd FL Ops N. Maint. Area Pull Station Tested 9:04:18 AM 03/17/2025
Pull Station 2nd FL Ops TRACON North Pull Station Tested 9:00:51 AM 03/17/2025
Pull Station 2nd FL Ops TRACON West Pull Station Tested 8:48:49 AM 03/17/2025
Pull Station 3rd FL Admin Mech. RMPull Station Tested 8:05:22 AM 03/17/2025
Pull Station 3rd FL Ops Center Stair #3 Pull Station Tested 7:22:57 AM 03/17/2025
Pull Station 3rd FL Ops In CatwalkCenter Pull Station Tested 9:06:00 AM 03/17/2025
Page of 20 78
Convergint 101 Download Date: 02/19/2026
Device Type Location Service Time Date
PASSED (continued)
Initiating (continued)
Pull Station 3rd FL Ops In CatwalkWest Pull Station Tested 7:23:13 AM 03/17/2025
Pull Station Guard Building Visitor Area Pull Tested 12:54:11 PM 03/18/2025
Pull Station Guard Building Waiting Area Pull Tested 12:54:08 PM 03/18/2025
Pull Station Guard Building Work Area Pull Station Tested 12:54:06 PM 03/18/2025
Smoke Detector 1st FL Equipment RoomCent. Sub-Floor Smoke
Tested/Cleaned 7:39:42 AM 03/18/2025
Smoke Detector 1st FL Equipment RoomCent. Sub-Floor Smoke
Tested/Cleaned 7:40:43 AM 03/18/2025
Smoke Detector 1st FL Equipment RoomCent. Sub-Floor Smoke
Tested/Cleaned 7:58:35 AM 03/18/2025
Smoke Detector 1st FL Equipment RoomCent. Sub-Floor Smoke
Tested/Cleaned 7:59:30 AM 03/18/2025
Smoke Detector 1st FL Equipment RoomCenter Smoke Detector
Tested/Cleaned 9:50:53 AM 03/17/2025
Smoke Detector 1st FL Equipment RoomEast Sub-Floor Smoke
Tested/Cleaned 7:49:01 AM 03/18/2025
Smoke Detector 1st FL Equipment RoomEast Sub-Floor Smoke
Tested/Cleaned 8:25:05 AM 03/18/2025
Smoke Detector 1st FL Equipment RoomEast Sub-Floor Smoke
Tested/Cleaned 8:26:25 AM 03/18/2025
Smoke Detector 1st FL Equipment RoomN.E. Sub-Floor Smoke
Tested/Cleaned 7:42:26 AM 03/18/2025
Smoke Detector 1st FL Equipment RoomN.E. Sub-Floor Smoke
Tested/Cleaned 7:46:36 AM 03/18/2025
Smoke Detector 1st FL Equipment RoomN.W. Sub-Floor Smoke
Tested/Cleaned 8:06:41 AM 03/18/2025
Smoke Detector 1st FL Equipment RoomNorth Sub-Floor Smoke
Tested/Cleaned 7:41:19 AM 03/18/2025
Smoke Detector 1st FL Equipment RoomNorth Sub-Floor Smoke
Tested/Cleaned 7:41:44 AM 03/18/2025
Page of 21 78
Convergint 101 Download Date: 02/19/2026
Device Type Location Service Time Date
PASSED (continued)
Initiating (continued)
Smoke Detector 1st FL Equipment RoomNorth Sub-Floor Smoke
Tested/Cleaned 7:43:01 AM 03/18/2025
Smoke Detector 1st FL Equipment RoomNorth Sub-Floor Smoke
Tested/Cleaned 7:43:46 AM 03/18/2025
Smoke Detector 1st FL Equipment RoomS.E. Smoke Detector Tested/Cleaned 9:58:44 AM 03/17/2025
Smoke Detector 1st FL Equipment RoomS.E. Sub-Floor Smoke
Tested/Cleaned 7:50:00 AM 03/18/2025
Smoke Detector 1st FL Equipment RoomS.E. Sub-Floor Smoke
Tested/Cleaned 8:00:36 AM 03/18/2025
Smoke Detector 1st FL Equipment RoomS.W. Sub-Floor Smoke
Tested/Cleaned 7:54:30 AM 03/18/2025
Smoke Detector 1st FL Equipment RoomS.W. Sub-Floor Smoke
Tested/Cleaned 7:56:53 AM 03/18/2025
Smoke Detector 1st FL Equipment RoomS.W. Sub-Floor Smoke
Tested/Cleaned 8:22:43 AM 03/18/2025
Smoke Detector 1st FL Equipment RoomSouth Smoke Detector
Tested/Cleaned 9:53:59 AM 03/17/2025
Smoke Detector 1st FL Equipment RoomSouth Smoke Detector
Tested/Cleaned 9:54:39 AM 03/17/2025
Smoke Detector 1st FL Equipment RoomSouth Sub-Floor Smoke
Tested/Cleaned 7:52:26 AM 03/18/2025
Smoke Detector 1st FL Equipment RoomWest Sub-Floor Smoke
Tested/Cleaned 7:38:02 AM 03/18/2025
Smoke Detector 1st FL Equipment RoomWest Sub-Floor Smoke
Tested/Cleaned 7:39:15 AM 03/18/2025
Smoke Detector 1st FL Equipment RoomWest Sub-Floor Smoke
Tested/Cleaned 8:04:12 AM 03/18/2025
Smoke Detector 1st FL Equipment S.W.Hall Smoke Det Tested/Cleaned 9:20:46 AM 03/17/2025
Smoke Detector 1st FL Maint. Shop ByElev Sub-Floor Smoke Tested/Cleaned 8:07:54 AM 03/18/2025
Smoke Detector 1st FL Maint. Shop Sub-Floor Smoke Tested/Cleaned 7:44:27 AM 03/18/2025
Page of 22 78
Convergint 101 Download Date: 02/19/2026
Device Type Location Service Time Date
PASSED (continued)
Initiating (continued)
Smoke Detector 1st FL Telco Room North Sub-Floor Smoke Tested/Cleaned 8:29:12 AM 03/18/2025
Smoke Detector 1st FL Telco Room South Sub-Floor Smoke Tested/Cleaned 8:29:50 AM 03/18/2025
Smoke Detector 1st FL Welness CenterSmoke Detector Tested/Cleaned 9:24:36 AM 03/17/2025
Smoke Detector 1st FL Welness CenterSmoke Detector Tested/Cleaned 9:24:40 AM 03/17/2025
Smoke Detector 2nd FL Admin Center Janitors Closet Smoke Tested/Cleaned 7:50:34 AM 03/17/2025
Smoke Detector 2nd FL Admin North Corridor Smoke Tested/Cleaned 7:30:26 AM 03/17/2025
Smoke Detector 2nd FL Admin North Corridor Smoke Tested/Cleaned 7:36:11 AM 03/17/2025
Smoke Detector 2nd FL Admin S. CBI Dev. Office Smoke Tested/Cleaned 7:49:47 AM 03/17/2025
Smoke Detector 2nd FL Admin S. ETG Dev. Office Smoke Tested/Cleaned 7:48:33 AM 03/17/2025
Smoke Detector 2nd FL Admin S.E. AT Managers Office Smoke
Tested/Cleaned 7:51:57 AM 03/17/2025
Smoke Detector 2nd FL Admin S.E. Smoke Detector Tested/Cleaned 7:52:55 AM 03/17/2025
Smoke Detector 2nd FL Admin South Contract Support SD Tested/Cleaned 7:46:41 AM 03/17/2025
Smoke Detector 2nd FL Admin South Contract Support SD Tested/Cleaned 7:47:07 AM 03/17/2025
Smoke Detector 2nd FL Admin W. A.T. South Classroom Smoke
Tested/Cleaned 7:42:40 AM 03/17/2025
Smoke Detector 2nd FL Admin W. A.T. South Classroom Smoke
Tested/Cleaned 7:42:55 AM 03/17/2025
Smoke Detector 2nd FL Admin Women's Locker RM Lounge
SD
Tested/Cleaned 7:55:58 AM 03/17/2025
Smoke Detector 2nd FL Admin Women's Locker Room Smoke Tested/Cleaned 7:56:08 AM 03/17/2025
Smoke Detector 2nd FL Admin Women's Locker Room Smoke Tested/Cleaned 12:39:15 PM 03/17/2025
Smoke Detector 2nd FL Atrium Smoke Detector Tested/Cleaned 7:53:39 AM 03/17/2025
Smoke Detector 2nd FL Atrium Smoke Detector Tested/Cleaned 7:53:53 AM 03/17/2025
Smoke Detector 2nd FL Atrium Smoke Detector Tested/Cleaned 7:54:13 AM 03/17/2025
Smoke Detector 2nd FL Ops ETG Area Sub-Floor Smoke Tested/Cleaned 1:03:15 AM 03/20/2025
Smoke Detector 2nd FL Ops Freight Elevator Lobby Smoke Tested/Cleaned 9:07:16 AM 03/17/2025
Page of 23 78
Convergint 101 Download Date: 02/19/2026
Device Type Location Service Time Date
PASSED (continued)
Initiating (continued)
Smoke Detector 2nd FL Ops N. Maint. Area Smoke Tested/Cleaned 9:08:41 AM 03/17/2025
Smoke Detector 2nd FL Ops N. Maint. Area Sub-Floor Smoke Tested/Cleaned 1:03:06 AM 03/20/2025
Smoke Detector 2nd FL Ops N. Maint. Area Sub-Floor Smoke Tested/Cleaned 1:03:09 AM 03/20/2025
Smoke Detector 2nd FL Ops N. Maint. Area Sub-Floor Smoke Tested/Cleaned 1:03:12 AM 03/20/2025
Smoke Detector 2nd FL Ops N. Maint. Area Sub-Floor Smoke Tested/Cleaned 1:03:18 AM 03/20/2025
Smoke Detector 2nd FL Ops N. Maint. Area Sub-Floor Smoke Tested/Cleaned 1:04:37 AM 03/20/2025
Smoke Detector 2nd FL Ops N. Maint. Area Sub-Floor Smoke Tested/Cleaned 1:04:41 AM 03/20/2025
Smoke Detector 2nd FL Ops NE Entry to Washroom Smoke Tested/Cleaned 9:02:32 AM 03/17/2025
Smoke Detector 2nd FL Ops NE Men's Room Smoke Detector Tested/Cleaned 9:01:46 AM 03/17/2025
Smoke Detector 2nd FL Ops NE Women'sRoom Smoke Detector
Tested/Cleaned 9:01:34 AM 03/17/2025
Smoke Detector 2nd FL Ops NW Maint. Area Smoke Detector Tested/Cleaned 9:09:17 AM 03/17/2025
Smoke Detector 2nd FL Ops North Electric Room Smoke Tested/Cleaned 9:07:29 AM 03/17/2025
Smoke Detector 2nd FL Ops North Maint. Area Smoke Tested/Cleaned 9:02:58 AM 03/17/2025
Smoke Detector 2nd FL Ops North Maint. Area Smoke Tested/Cleaned 9:03:19 AM 03/17/2025
Smoke Detector 2nd FL Ops North Maint. Area Smoke Tested/Cleaned 9:03:43 AM 03/17/2025
Smoke Detector 2nd FL Ops North Maint. Area Smoke Tested/Cleaned 9:08:57 AM 03/17/2025
Smoke Detector 2nd FL Ops North Sys.Engineer Office Smoke Tested/Cleaned 8:55:25 AM 03/17/2025
Smoke Detector 2nd FL Ops South Interview Room Smoke Tested/Cleaned 8:45:11 AM 03/17/2025
Smoke Detector 2nd FL Ops South Supervisor Area Smoke Tested/Cleaned 8:45:41 AM 03/17/2025
Smoke Detector 2nd FL Ops TRACON Cent. E. Sub-FL Smoke Tested/Cleaned 1:03:26 AM 03/20/2025
Smoke Detector 2nd FL Ops TRACON Cent. E. Sub-FL Smoke Tested/Cleaned 1:04:10 AM 03/20/2025
Smoke Detector 2nd FL Ops TRACON Cent. E. Sub-FL Smoke Tested/Cleaned 1:04:25 AM 03/20/2025
Smoke Detector 2nd FL Ops TRACON Cent. E. Sub-FL Smoke Tested/Cleaned 1:04:29 AM 03/20/2025
Smoke Detector 2nd FL Ops TRACON Center East Smoke Tested/Cleaned 8:54:25 AM 03/17/2025
Page of 24 78
Convergint 101 Download Date: 02/19/2026
Device Type Location Service Time Date
PASSED (continued)
Initiating (continued)
Smoke Detector 2nd FL Ops TRACON Center East Smoke Tested/Cleaned 8:58:06 AM 03/17/2025
Smoke Detector 2nd FL Ops TRACON Center East Smoke Tested/Cleaned 8:59:53 AM 03/17/2025
Smoke Detector 2nd FL Ops TRACON Center East Smoke Tested/Cleaned 9:00:15 AM 03/17/2025
Smoke Detector 2nd FL Ops TRACON Center Smoke Detector Tested/Cleaned 8:53:03 AM 03/17/2025
Smoke Detector 2nd FL Ops TRACON Center Smoke Detector Tested/Cleaned 8:53:15 AM 03/17/2025
Smoke Detector 2nd FL Ops TRACON Center Smoke Detector Tested/Cleaned 8:53:31 AM 03/17/2025
Smoke Detector 2nd FL Ops TRACON Center Smoke Detector Tested/Cleaned 8:54:02 AM 03/17/2025
Smoke Detector 2nd FL Ops TRACON Center SubFloor Smoke Tested/Cleaned 1:03:23 AM 03/20/2025
Smoke Detector 2nd FL Ops TRACON Center SubFloor Smoke Tested/Cleaned 1:04:00 AM 03/20/2025
Smoke Detector 2nd FL Ops TRACON Center SubFloor Smoke Tested/Cleaned 1:04:02 AM 03/20/2025
Smoke Detector 2nd FL Ops TRACON Center SubFloor Smoke Tested/Cleaned 1:04:06 AM 03/20/2025
Smoke Detector 2nd FL Ops TRACON Center West Smoke Tested/Cleaned 8:49:48 AM 03/17/2025
Smoke Detector 2nd FL Ops TRACON Center West Smoke Tested/Cleaned 8:51:02 AM 03/17/2025
Smoke Detector 2nd FL Ops TRACON Center West Smoke Tested/Cleaned 8:51:06 AM 03/17/2025
Smoke Detector 2nd FL Ops TRACON Center West Smoke Tested/Cleaned 8:52:15 AM 03/17/2025
Smoke Detector 2nd FL Ops TRACON Cnt/West Sub-Floor Smoke
Tested/Cleaned 1:03:35 AM 03/20/2025
Smoke Detector 2nd FL Ops TRACON Cnt/West Sub-Floor Smoke
Tested/Cleaned 1:03:50 AM 03/20/2025
Smoke Detector 2nd FL Ops TRACON Cnt/West Sub-Floor Smoke
Tested/Cleaned 1:03:53 AM 03/20/2025
Smoke Detector 2nd FL Ops TRACON Cnt/West Sub-Floor Smoke
Tested/Cleaned 1:03:56 AM 03/20/2025
Smoke Detector 2nd FL Ops TRACON East Smoke Detector Tested/Cleaned 8:54:44 AM 03/17/2025
Smoke Detector 2nd FL Ops TRACON East Smoke Detector Tested/Cleaned 8:55:49 AM 03/17/2025
Smoke Detector 2nd FL Ops TRACON East Smoke Detector Tested/Cleaned 8:56:05 AM 03/17/2025
Smoke Detector 2nd FL Ops TRACON East Smoke Detector Tested/Cleaned 8:56:29 AM 03/17/2025
Page of 25 78
Convergint 101 Download Date: 02/19/2026
Device Type Location Service Time Date
PASSED (continued)
Initiating (continued)
Smoke Detector 2nd FL Ops TRACON East Smoke Detector Tested/Cleaned 8:56:48 AM 03/17/2025
Smoke Detector 2nd FL Ops TRACON East Smoke Detector Tested/Cleaned 8:57:07 AM 03/17/2025
Smoke Detector 2nd FL Ops TRACON East Smoke Detector Tested/Cleaned 8:58:51 AM 03/17/2025
Smoke Detector 2nd FL Ops TRACON East Smoke Detector Tested/Cleaned 8:59:11 AM 03/17/2025
Smoke Detector 2nd FL Ops TRACON East Sub-Floor Smoke Tested/Cleaned 1:03:29 AM 03/20/2025
Smoke Detector 2nd FL Ops TRACON East Sub-Floor Smoke Tested/Cleaned 1:03:32 AM 03/20/2025
Smoke Detector 2nd FL Ops TRACON East Sub-Floor Smoke Tested/Cleaned 1:04:12 AM 03/20/2025
Smoke Detector 2nd FL Ops TRACON East Sub-Floor Smoke Tested/Cleaned 1:04:16 AM 03/20/2025
Smoke Detector 2nd FL Ops TRACON East Sub-Floor Smoke Tested/Cleaned 1:04:19 AM 03/20/2025
Smoke Detector 2nd FL Ops TRACON East Sub-Floor Smoke Tested/Cleaned 1:04:22 AM 03/20/2025
Smoke Detector 2nd FL Ops TRACON East Sub-Floor Smoke Tested/Cleaned 1:04:32 AM 03/20/2025
Smoke Detector 2nd FL Ops TRACON East Sub-Floor Smoke Tested/Cleaned 1:04:34 AM 03/20/2025
Smoke Detector 2nd FL Ops TRACON West Smoke Detector Tested/Cleaned 8:46:15 AM 03/17/2025
Smoke Detector 2nd FL Ops TRACON West Smoke Detector Tested/Cleaned 8:48:11 AM 03/17/2025
Smoke Detector 2nd FL Ops TRACON West Smoke Detector Tested/Cleaned 8:48:23 AM 03/17/2025
Smoke Detector 2nd FL Ops TRACON West Sub-Floor Smoke Tested/Cleaned 1:03:44 AM 03/20/2025
Smoke Detector 2nd FL Ops TRACON West Sub-Floor Smoke Tested/Cleaned 1:03:47 AM 03/20/2025
Smoke Detector 2nd FL Ops W. Office Sub-Floor Smoke Tested/Cleaned 1:03:42 AM 03/20/2025
Smoke Detector 2nd FL Ops West Briefing Room Smoke Tested/Cleaned 8:45:03 AM 03/17/2025
Smoke Detector 2nd FL Ops West Center Corridor Smoke Tested/Cleaned 8:43:11 AM 03/17/2025
Smoke Detector 2nd FL Ops West ETG Classroom Area Smoke Tested/Cleaned 9:10:16 AM 03/17/2025
Smoke Detector 2nd FL Ops West ETG Classroom Area Smoke Tested/Cleaned 9:10:38 AM 03/17/2025
Smoke Detector 2nd FL Ops West Office Smoke Detector Tested/Cleaned 8:49:05 AM 03/17/2025
Smoke Detector 2nd FL Ops West Room Smoke Detector Tested/Cleaned 8:49:25 AM 03/17/2025
Smoke Detector 2nd FL Ops West Room Sub-Floor Smoke Tested/Cleaned 1:03:38 AM 03/20/2025
Page of 26 78
Convergint 101 Download Date: 02/19/2026
Device Type Location Service Time Date
PASSED (continued)
Initiating (continued)
Smoke Detector 2nd FL Ops West T.M. Area Office Smoke Tested/Cleaned 8:43:21 AM 03/17/2025
Smoke Detector 2nd FL Ops West T.M. Assist. Manager Smoke
Tested/Cleaned 8:44:08 AM 03/17/2025
Smoke Detector 2nd FL Ops West T.M. Supervisor Area Smoke
Tested/Cleaned 8:43:30 AM 03/17/2025
Smoke Detector 2nd FL Passenger Elevator Lobby Smoke Tested/Cleaned 7:25:04 AM 03/17/2025
Smoke Detector 2nd FL W. ETG ClassRMArea Sub-Floor Smoke
Tested/Cleaned 1:03:21 AM 03/20/2025
Smoke Detector 3rd FL Admin East Smoke Detector Tested/Cleaned 8:27:25 AM 03/17/2025
Smoke Detector 3rd FL Admin East Smoke Detector Tested/Cleaned 8:35:53 AM 03/17/2025
Smoke Detector 3rd FL Admin Mech. Penthouse Smoke Tested/Cleaned 7:59:46 AM 03/17/2025
Smoke Detector 3rd FL Admin Mech. Penthouse Smoke Tested/Cleaned 7:59:50 AM 03/17/2025
Smoke Detector 3rd FL Admin Mech. Penthouse Smoke Tested/Cleaned 8:04:52 AM 03/17/2025
Smoke Detector 3rd FL Admin Mech. Penthouse Smoke Tested/Cleaned 8:04:55 AM 03/17/2025
Smoke Detector 3rd FL Admin SE Smoke Detector Tested/Cleaned 8:23:55 AM 03/17/2025
Smoke Detector 3rd FL Admin SE Smoke Detector Tested/Cleaned 8:26:30 AM 03/17/2025
Smoke Detector 3rd FL Admin SE Smoke Detector Tested/Cleaned 8:26:33 AM 03/17/2025
Smoke Detector 3rd FL Admin SE Smoke Detector Tested/Cleaned 8:26:35 AM 03/17/2025
Smoke Detector 3rd FL Admin SW Smoke Detector Tested/Cleaned 8:17:34 AM 03/17/2025
Smoke Detector 3rd FL Admin SW Smoke Detector Tested/Cleaned 8:17:40 AM 03/17/2025
Smoke Detector 3rd FL Admin SW Smoke Detector Tested/Cleaned 8:19:57 AM 03/17/2025
Smoke Detector 3rd FL Admin South Smoke Detector Tested/Cleaned 8:21:46 AM 03/17/2025
Smoke Detector 3rd FL Admin South Smoke Detector Tested/Cleaned 8:22:36 AM 03/17/2025
Smoke Detector 3rd FL Admin South Smoke Detector Tested/Cleaned 8:23:08 AM 03/17/2025
Smoke Detector 3rd FL Admin Top of Center Stair Smoke Tested/Cleaned 7:22:42 AM 03/17/2025
Smoke Detector 3rd FL Admin West Smoke Detector Tested/Cleaned 8:12:40 AM 03/17/2025
Page of 27 78
Convergint 101 Download Date: 02/19/2026
Device Type Location Service Time Date
PASSED (continued)
Initiating (continued)
Smoke Detector 3rd FL Admin West Smoke Detector Tested/Cleaned 8:13:00 AM 03/17/2025
Smoke Detector 3rd FL Admin West Smoke Detector Tested/Cleaned 8:13:42 AM 03/17/2025
Smoke Detector 3rd FL Admin West Smoke Detector Tested/Cleaned 8:14:33 AM 03/17/2025
Smoke Detector 3rd FL Admin West Smoke Detector Tested/Cleaned 8:15:09 AM 03/17/2025
Smoke Detector 3rd FL Admin West Smoke Detector Tested/Cleaned 8:16:05 AM 03/17/2025
Smoke Detector 3rd FL Admin West Smoke Detector Tested/Cleaned 8:16:13 AM 03/17/2025
Smoke Detector 3rd FL Atrium Smoke Detector Tested/Cleaned 12:39:01 PM 03/17/2025
Smoke Detector 3rd FL Ops. Top of Stair #4 Smoke Tested/Cleaned 9:05:07 AM 03/17/2025
Smoke Detector 2nd-3 2nd to 3rd FL Admin Center Stair Smoke
Tested/Cleaned 7:22:22 AM 03/17/2025
Smoke Detector PIT Freight Elevator Pit Smoke Detector Tested/Cleaned 12:38:05 PM 03/19/2025
Smoke Detector TOS Freight Elevator Top of Shaft Smoke Tested/Cleaned 1:16:08 PM 03/19/2025
Smoke Detector TOS Passenger Elevator Top of Shaft Smoke Tested/Cleaned 12:53:59 PM 03/19/2025
Smoke Detector 1st 1st FL Equipment RoomCenter Smoke Detector
Tested/Cleaned 9:52:19 AM 03/17/2025
Smoke Detector 1st 1st FL Equipment RoomCenter Smoke Detector
Tested/Cleaned 9:52:33 AM 03/17/2025
Smoke Detector 1st 1st FL Equipment RoomEast Smoke Detector
Tested/Cleaned 10:03:38 AM 03/17/2025
Smoke Detector 1st 1st FL Equipment RoomN.E. Smoke Detector
Tested/…