26 56 00 BSD-Exterior Lighting-DC15128-ADDM---2018-09-07.pdf
PDF 84 KB Posted
- Attached to
- AMENDMENT 2: Headquarters Parking Lot at the Mike Monroney Aeronautical Center, Oklahoma City, Oklahoma.
- Solicitation number
- 6973GH-18-R-00255
About this file
26 56 00 BSD-Exterior Lighting-DC15128-ADDM---2018-09-07 (pdf)
View the file
Other files
Show all 47
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FAA HQ Parking Lot EXTERIOR LIGHTING 26 5600 - 1
DC15128 09/07/2018 ADDENDUM
SECTION 26 5600
EXTERIOR LIGHTING
PART 1 GENERAL
1.01 SECTION INCLUDES
A. Exterior luminaires.
B. Ballasts.
C. Lamps.
D. Poles and accessories.
E. Luminaire accessories.
1.02 RELATED REQUIREMENTS
A. Section 26 05 26 - Grounding and Bonding for Electrical Systems.
B. Section 26 05 37 - Boxes.
1.03 REFERENCE STANDARDS
A. AASHTO LTS - Standard Specifications for Structural Supports for Highway Signs, Luminaires and Traffic Signals; American Association of State Highway and Transportation Officials; 5th Edition, with 2011 Interim Revisions
B. ANSI C136.10 - American National Standard for Roadway and Area Lighting Equipment - Locking-Type Photocontrol Devices and Mating Receptacles - Physical and Electrical Interchangeability and Testing; 2010.
C. IEEE C2 - National Electrical Safety Code; 2012.
D. IEEE C62.41.2 - Recommended Practice on Characterization of Surges in Low-Voltage (1000 V and less) AC Power Circuits; 2002 (Cor 1, 2012).
E. IESNA LM-5 - Photometric Measurements of Area and Sports Lighting Installations; 2004 (Reaffirmed 2007).
F. IESNA LM-63 - ANSI Approved Standard File Format for Electronic Transfer of Photometric Data and Related Information; 2002 (Reaffirmed 2008).
G. IESNA LM-64 - Photometric Measurements of Parking Areas; 2001 (Reaffirmed 2007).
H. IESNA RP-8 - American National Standard Practice for Roadway Lighting; Illuminating Engineering Society of North America; 2000(R2005) (ANSI/IES RP8).
I. NECA 1 - Standard for Good Workmanship in Electrical Construction; National Electrical Contractors Association; 2010.
J. NECA/IESNA 501 - Recommended Practice for Installing Exterior Lighting Systems; 2006.
K. NEMA 410 - Performance Testing for Lighting Controls and Switching Devices with Electronic Fluorescent Ballasts; National Electrical Manufacturers Association; 2011.
L. NFPA 70 - National Electrical Code; National Fire Protection Association; Most Recent Edition Adopted by Authority Having Jurisdiction, Including All Applicable Amendments and Supplements.
M. UL 1598 - Luminaires; Current Edition, Including All Revisions.
N. UL 8750 - Light Emitting Diode (LED) Equipment for Use in Lighting Products; Current Edition, Including All Revisions.
1.04 ADMINISTRATIVE REQUIREMENTS
A. Coordination:
1. Coordinate placement of poles and associated foundations with utilities, curbs, sidewalks, trees, walls, fences, striping, etc. installed under other sections or by others. Coordinate elevation to obtain specified foundation height.
FAA HQ Parking Lot EXTERIOR LIGHTING 26 5600 - 2
2. Notify ARCHITECT of any conflicts or deviations from the contract documents to obtain direction prior to proceeding with work.
1.05 SUBMITTALS
A. Shop Drawings:
1. Indicate dimensions and components for each luminaire that is not a standard product of the manufacturer.
2. Provide photometric calculations where luminaires are proposed for substitution.
3. Provide structural calculations for each pole proposed for substitution.
B. Product Data: Provide manufacturer's standard catalog pages and data sheets including detailed information on luminaire construction, dimensions, ratings, finishes, mounting requirements, listings, service conditions, photometric performance, weight, effective projected area (EPA), and installed accessories; include model number nomenclature clearly marked with all proposed features.
1. Lamps: Include rated life and initial and mean lumen output.
2. Poles: Include information on maximum supported effective projected area (EPA) and weight for the design wind speed.
C. Samples:
1. Provide one sample(s) of each specified luminaire where indicated.
2. Provide one sample(s) of each custom luminaire.
3. Provide one sample(s) of each luminaire proposed for substitution upon request.
D. Certificates for Poles and Accessories: Manufacturer's documentation that products are suitable for the luminaires to be installed and comply with designated structural design criteria.
E. Manufacturer's Installation Instructions: Indicate application conditions and limitations of use stipulated by product testing agency. Include instructions for storage, handling, protection, examination, preparation, installation, and starting of product.
F. Operation and Maintenance Data: Instructions for each product including information on replacement parts.
G. Maintenance Materials: Furnish the following for OWNER's use in maintenance of project.
1. Extra Ballasts: Two percent of total quantity installed for each type, but not less than one of each type.
1.06 QUALITY ASSURANCE
A. Conform to requirements of NFPA 70.
B. Maintain at the project site a copy of each referenced document that prescribes execution requirements.
C. Manufacturer Qualifications: Company specializing in manufacturing the products specified in this section with minimum three years documented experience.
1.07 DELIVERY, STORAGE, AND HANDLING
A. Receive, handle, and store products according to NECA/IESNA 501 and manufacturer's written instructions.
B. Keep products in original manufacturer's packaging and protect from damage until ready for installation.
PART 2 PRODUCTS
2.01 LUMINAIRE TYPES
A. Available Manufacturers: Subject to compliance with requirements, manufacturers offering products that may be incorporated in the Work include but are not limited to, the following:
1) Acuity Brands, Inc.
2) Cooper Lighting, a division of Cooper Industries.
3) Hubbell Lighting, Inc.
4) Lithonia Lighting
5) LSI Industries
FAA HQ Parking Lot EXTERIOR LIGHTING 26 5600 - 3
6) As listed on the Fixture Schedule on the drawings.
2.02 LUMINAIRES
A. Provide products that comply with requirements of NFPA 70.
B. Provide products that are listed and labeled as complying with UL 1598, where applicable.
C. Provide products listed and classified by Underwriters Laboratories Inc. as suitable for the purpose specified and indicated.
D. Unless otherwise indicated, provide complete luminaires including lamp(s) and all sockets, ballasts, reflectors, lenses, housings and other components required to position, energize and protect the lamp and distribute the light.
E. Unless specifically indicated to be excluded, provide all required conduit, boxes, wiring, connectors, hardware, poles, foundations, supports, trims, accessories, etc. as necessary for a complete operating system.
F. Provide products suitable to withstand normal handling, installation, and service without any damage, distortion, corrosion, fading, discoloring, etc.
G. Provide luminaires listed and labeled as suitable for wet locations unless otherwise indicated.
H. LED Luminaire Components: UL 8750 recognized or listed as applicable.
I. Exposed Hardware: Stainless steel.
2.03 BALLASTS
A. Manufacturers:
1. General Electric Company/GE Lighting: www.gelighting.com.
2. Osram Sylvania: www.sylvania.com.
3. Philips Lighting Electronics/Advance: www.advance.philips.com.
4. Manufacturer Limitations: Where possible, for each type of luminaire provide ballasts produced by a single manufacturer.
B. All Ballasts:
1. Provide ballasts containing no polychlorinated biphenyls (PCBs).
2. Minimum Efficiency/Efficacy: Provide ballasts complying with all current applicable federal and state ballast efficiency/efficacy standards.
2.04 LAMPS
A. Manufacturers:
1. General Electric Company/GE Lighting: www.gelighting.com.
2. Osram Sylvania: www.sylvania.com.
3. Philips Lighting Company: www.lighting.philips.com.
4. Manufacturer Limitations: Where possible, provide lamps produced by a single manufacturer.
B. Lamps - General Requirements:
1. Unless explicitly excluded, provide new, compatible, operable lamps in each luminaire.
2. Verify compatibility of specified lamps with luminaires to be installed. Where lamps are not specified, provide lamps per luminaire manufacturer's recommendations.
3. Minimum Efficiency: Provide lamps complying with all current applicable federal and state lamp efficiency standards.
4. Color Temperature Consistency: Unless otherwise indicated, for each type of lamp furnish products which are consistent in perceived color temperature. Replace lamps that are determined by the ARCHITECT to be inconsistent in perceived color temperature.
2.05 POLES
A. All Poles:
1. Provide poles and associated support components suitable for the luminaire(s) and associated supports and accessories to be installed.
2. Structural Design Criteria:
FAA HQ Parking Lot EXTERIOR LIGHTING 26 5600 - 4
a. Comply with AASHTO LTS.
b. Wind Load: Include effective projected area (EPA) of luminaire(s) and associated supports and accessories to be installed.
1) Design Wind Speed: 110 miles per hour, with gust factor of 1.3.
c. Dead Load: Include weight of proposed luminaire(s) and associated supports and accessories.
3. Material: Steel, unless otherwise indicated.
4. Shape: Round, tapered, match FAA Standards.
5. Finish: Galvanized. Match existing poles and match FAA Standards.
6. Mounting: Install on concrete foundation, height as indicated on the drawings, unless otherwise indicated.
7. Unless otherwise indicated, provide with the following features/accessories:
a. Top cap.
b. Handhole, standard size.
c. Anchor bolts with leveling nuts or leveling shims.
d. Anchor base cover.
e. Provision for pole-mounted weatherproof GFI receptacle where indicated.
f. Pole to be 27-foot length, mounted on 3-foot concrete pole base, resulting in 30-foot mounting height of luminaire.
B. Metal Poles: Provide ground lug, accessible from handhole or transformer base.
PART 3 EXECUTION
3.01 EXAMINATION
A. Verify that field measurements are as shown on the drawings.
B. Verify that branch circuit wiring installation is completed, tested, and ready for connection to luminaires.
C. Verify that conditions are satisfactory for installation prior to starting work.
3.02 PREPARATION
A. Provide extension rings to bring outlet boxes flush with finished surface.
B. Clean dirt, debris, plaster, and other foreign materials from outlet boxes.
3.03 INSTALLATION
A. Install products according to manufacturer's instructions.
B. Install luminaires securely, in a neat and workmanlike manner, as specified in NECA 1 (general workmanship) and NECA/IESNA 501 (exterior lighting).
C. Install luminaires plumb and square and aligned with building lines and with adjacent luminaires.
D. Pole-Mounted Luminaires:
1. Maintain the following minimum clearances:
a. Comply with IEEE C2.
b. Comply with utility company requirements.
2. Foundation-Mounted Poles:
a. Install foundations plumb.
b. Install poles plumb, using leveling nuts or shims as required to adjust to plumb.
c. Tighten anchor bolt nuts to manufacturer's recommended torque.
d. Install non-shrink grout between pole anchor base and concrete foundation, leaving small channel for condensation drainage.
e. Install anchor base covers or anchor bolt covers as indicated.
3. Grounding:
a. Bond luminaires, metal accessories, metal poles, and foundation reinforcement to branch circuit equipment grounding conductor.
FAA HQ Parking Lot EXTERIOR LIGHTING 26 5600 - 5
b. Provide supplementary ground rod electrode as specified in Section 26 05 26 at each pole bonded to grounding system as indicated.
4. Install separate service conductors, 12 AWG copper, from each luminaire down to handhole for connection to branch circuit conductors.
5. Install non-breakaway in-line fuse holders and fuses complying with Section 26 28 13 in pole handhole or transformer base for each ungrounded conductor.
I. Install accessories furnished with each luminaire.
J. Bond products and metal accessories to branch circuit equipment grounding conductor.
K. Install lamps in each luminaire.
3.04 FIELD QUALITY CONTROL
A. Inspect each product for damage and defects.
B. Operate each luminaire after installation and connection to verify proper operation.
C. Correct wiring deficiencies and repair or replace damaged or defective products. Repair or replace excessively noisy ballasts as determined by ARCHITECT.
D. Measure illumination levels at night with calibrated meters. Record results and submit to Owner.
1. Test according to IESNA LM-64 (parking areas).
3.05 ADJUSTING
A. Aim and position adjustable luminaires to achieve desired illumination as indicated or as directed by ARCHITECT. Secure locking fittings in place.
B. Luminaires with Field-Rotatable Optics: Position optics according to manufacturer's instructions to achieve lighting distribution as indicated or as directed by ARCHITECT.
3.06 CLEANING
A. Clean surfaces according to NECA/IESNA 501 and manufacturer's instructions to remove dirt, fingerprints, paint, or other foreign material and restore finishes to match original factory finish.
3.07 CLOSEOUT ACTIVITIES
A. Demonstration: Demonstrate proper operation of luminaires to ARCHITECT, and correct deficiencies or make adjustments as directed.
B. Just prior to Substantial Completion, replace all lamps that have failed.
3.08 PROTECTION
A. Protect installed luminaires from subsequent construction operations.
END OF SECTION
File details come from the government source that posted it.