About this file

GENERAL REPAIR REPORT-TW (pdf)

View the file

Other files

File Type Posted
CONTRACTOR'S RELEASE FORM.doc DOC document
TOWER REPAIR REPORT-WT.pdf PDF
SOW.pdf PDF
EXPERIENCE INFO FORM.pdf PDF
TOWER REPAIR REPORT-BM.pdf PDF
TOWER REPAIR REPORT-BP.pdf PDF
WD-AZ180032.pdf PDF
GENERAL REPAIR REPORT-BP.pdf PDF
6973GH-18-R-00153.pdf PDF
GENERAL REPAIR REPORT-BM.pdf PDF
TOWER REPAIR REPORT-WT.pdf PDF
GENERAL REPAIR REPORT-TW.pdf PDF
WD-AZ180032.pdf PDF
GENERAL REPAIR REPORT-BM.pdf PDF
CONTRACTOR'S RELEASE FORM.doc DOC document
EXPERIENCE INFO FORM.pdf PDF
SOW.pdf PDF
TOWER REPAIR REPORT-BP.pdf PDF
GENERAL REPAIR REPORT-BP.pdf PDF
TOWER REPAIR REPORT-BM.pdf PDF
Show all 20

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Structural Analysis and Condition Assessment for LMR Sites

Whitetank Mountain, Arizona (AZ2143)

STRUCTURAL AND CONDITION ASSESSMENT

REPORT

September 9, 2016

SENSITIVE BUT UNCLASSIFIED (SBU) GSA Order #: GS-P-00-16-LY-7055 PROPERTY OF THE UNITED STATES GOVERNMENT GSA Contract #: GS-07-P-15-UC-D-7000

COPYING, DISSEMINATION, OR DISTRIBUTION OF THIS PDN: EP-GS-P-00-16-LY-7055

DOCUMENT TO UNAUTHORIZED RECIPIENTS HGA Commission Number 2111-064-00

IS PROHIBITED

Do not remove this notice Properly destroy or return documents when no longer needed

420 North 5th Street, Suite 100 Minneapolis, Minnesota 55401

Tower Engineering Professionals

326 Tryon Road Raleigh, North Carolina 27603

STRUCTURAL AND CONDITION ASSESSMENT REPORT

FOR

[WHITETANK MOUNTAIN] AZ2143

80’ SELF SUPPORTING TOWER

BUCKEYE, MARICOPA COUNTY, ARIZONA

TEP # 69922_85717

Revision 0

Respectfully Submitted By:

Prepared For:

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

Graham

Date: September 9, 2016

Stephen Fiskum, FAIA Tower Engineering Professionals

HGA Architects and Engineers 326 Tryon Road

420 5th Street North, Suite 100 Raleigh, NC 27603

Minneapolis, MN 55401 (919) 661-6351

(612) 758-4502 StructuresReview@tepgroup.net

Subject: Executive Summary

Tower Designation: Site Number: AZ2143

Site Name: Whitetank Mountain

Engineering Firm Designation: TEP Project Number: 69922_85717

Site Data: N. Tower Road, Buckeye, Maricopa County, AZ 85326

Lat., Long.: 33.575406, -112.578769

(N 33° 34' 31.46'', W 112° 34' 43.57”)

80 Foot ± – Self Supporting Tower

Tower Engineering Professionals (TEP) is pleased to provide this executive summary for the Phase I Scope of Work, which included a Maintenance and Condition Assessment, Capital Expenditure Table, Steel and Appurtenance

Mapping, and Structural Analysis for the above referenced site.

Maintenance and Condition Assessment

Overall Tower Condition (Excellent/Good/Average/Fair/Poor): Average*

Tower Type: 80-ft self supporting tower

Tower Age: Approximately 20-30 years**

Number of Guy Wires: N/A

Tower Access Road Condition: Poor, extremely rocky terrain, all-wheel drive vehicles with high ground clearance necessary

A periodic inspection for the above referenced site was performed by Kyle C. Edwards, P.E., C.W.I. and Andrew E.

Propst of TEP during the July 13, 2016 site visit. The inspection was in accordance with the ANSI/TIA-222-G-2005, Annex J: Maintenance and Condition Assessment (Normative). TEP observed the following checklist items requiring some measure of possible or required corrective action: 1) Structure Condition, 2) Finish, 3) Grounding, 4) Antennas and Lines, 5) Concrete Foundations, and 6) Non-TIA Related Items. Refer to the Maintenance and Condition

Assessment Report for specific details.

*TEP defines the tower conditions as follows:

Excellent - The tower has sufficient capacity to carry the existing loads. No modifications are required at this time. In addition, the tower has no maintenance issues of note and doesn’t require maintenance repairs at this time.

Good - The tower has sufficient capacity to carry the existing loads. No modifications are required at this time. However, the tower has some maintenance issues of note that require attention.

Average - The tower does not have sufficient capacity to carry the existing loads. Modifications will be required to bring the tower into compliance with the

ANSI/TIA-222-G standard for the existing loading. In addition, the tower may have minor maintenance issues of note that require attention.

Fair - The tower does not have sufficient capacity to carry the existing loads. Modifications will be required to bring the tower into compliance with the

ANSI/TIA-222-G standard for the existing loading. In addition, the tower has maintenance issues of note that require attention. Based on the itemized estimate in our Capital Expenditure Table, modifying the existing tower may be the most cost effective solution.

Poor - The tower does not have sufficient capacity to carry the existing loads. Modifications will be required to bring the tower into compliance with the

ANSI/TIA-222-G standard for the existing loading. In addition, the tower has maintenance issues of note that require attention. Based on the itemized estimate in our Capital Expenditure Table and/or the condition of the tower, a full tower replacement may be the best solution.

**Tower Age was estimated based on tower identification tags, tower manufacturer information, tower research, type and condition of tower components, and/or historical site images

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

TEP Project Number 69922_85717 September 9, 2016

AZ2143 - Whitetank Mountain

326 Tryon Road, Raleigh, NC 27603 (o) 919-661-6351 (f) 919-661-6350 www.tepgroup.net

Condition Assessment of Non-Tower Assets

During the site visit, TEP conducted a visual inspection of all Non-Tower Owned Assets. TEP did not find any non-tower assets that require urgent corrective repairs. However, TEP recommends regular inspection and maintenance by licensed professionals based on manufacturer specifications. Refer to Section L of the Maintenance and Condition

Assessment Report for any applicable additional information.

Asset Type Coordinates Condition Notes

Estimated

Remaining

Life

Shelter CMU Brick 33.575422, -112.578833 Good No major issues observed 10+ years

Roof Metal 33.575422, -112.578833 Good No major issues observed 10+ years

Shelter

Access

Single

Door

33.575422, -112.578833 Good

Located on northwest side of shelter, no major issues visible 10+ years

Power

Supply

Power

Meter

33.575422, -112.578833 Good Appears to be working properly 10+ years

Power

Supply Generator

33.575442, -112.578933 Good

Reli-On fuel cell generator, no major issues observed 10+ years

A/C Unit

(2)

Through

Wall

33.575422, -112.578833 Good

Mitsubishi and LG manufacturer tags, both appear to be working properly 10+ years

Cellular

Receivers

33.575422, -112.578833 Good

Shelter houses various units associated with communication equipment, no major issues of note

10+ years

Capital Expenditure Table

A cost estimate of $24,950 was provided to cover repairs and additional inspections as recommended in the

Maintenance and Condition Assessment Report and the Structural Analysis Report. The recommended repair schedule ranges from 6 months to 5 years. Also note that this estimate does not include any foundation reinforcements that may be required. TEP cannot say with certainty that modifying the existing tower would be more cost effective than a replacement without completing a Structural Modification Design Analysis. Refer to the

Capital Expenditure Table for details. For itemized repairs, refer to the Capital Expenditure Table for details. TEP estimated a ROM cost for full tower replacement would range from approximately $160,000 for a 100-ft self supporting tower to $250,000 for a 200-ft self supporting tower. These estimates do not include pricing for site specific costs related to zoning, permitting, environmental studies, etc.

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

Steel and Appurtenance Mapping

The original design criteria were unavailable for review. A Steel and Appurtenance Mapping was performed in order to obtain the necessary tower and appurtenance loading information needed to conduct the Structural Analysis for this site. The antennas recorded during our Steel and Appurtenance Mapping are depicted in the table below. TEP denoted the owner of the equipment under the “Owner/Tenant” column based on information available on site.

Refer to the Steel and Appurtenance Mapping Report for additional detail.

Elevation

(ft) Qty Antenna Model

Mount

Type

Owner/

Tenant

88.0 1 Andrew DB224-A Sidearm CBP

82.8 1 RFI BA40-41-DIN Sidearm CBP

81.0 1 1”Ø x 8’ Omni Sidearm PHX Fire

78.5 1 2.5”Ø x 10’ Omni Sidearm PHX Fire & Water

62.0 1 Empty Standoff Mount CBP

60.3 1 8’ Ø Grid Dish Pipe CBP

54.8 1 RFI BA40-41-DIN Sidearm CBP

50.0 1 Andrew DB224 Sidearm PHX Fire

37.0 1 Andrew DB224 Sidearm PHX Fire

35.0 1 8’ Ø Grid Dish Pipe CBP

32.3 1 3”Ø x 7’ Omni Sidearm PHX Fire & Water

31.0 1 Scala 94150-003 Pipe CBP

20.3 1 Radiation Systems P-22A72GF Pipe CBP

20.0 1 Radiation Systems P-22A96GF Pipe CBP

10.5 1 Andrew UHX10-59-P6A Pipe City of Phoenix

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

Structural Analysis

The Structural Analysis report outlines overstresses in the tower diagonal bracing from 0’ to 39’ elevations. TEP believes that the majority of the overstresses can be attributed to the more stringent loading and analysis criteria as required by the latest ANSI/TIA-222-G-2-2009 Standard, as compared to previous versions of the TIA Standard for which the tower was originally designed. Based on our analysis we have determined the tower stress level for each controlling component, under the following load case, to be:

LC1: Existing Equipment Insufficient Capacity Note: See Table 1 for the existing loading

Thank you for the opportunity to provide this service for you. If you have any questions or comments, please contact our office.

Component % Capacity

Leg (T3) 71.2

Diagonal (T4) 160.4

Horizontal (T4) 38.9

Top Girt (T5) 40.8

Bolt Checks 38.7

Anchor Rods 18.5

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

MASTER TABLE OF CONTENTS

���� MAINTENANCE AND CONDITION ASSESSMENT

���� CAPITAL EXPENDITURE TABLE

���� ANNEX A: STEEL AND APPURTENANCE MAPPING

���� ANNEX B: STRUCTURAL ANALYSIS

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

MAINTENANCE AND CONDITION ASSESSMENT

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

Date: September 9, 2016

HGA Architects and Engineers 326 Tryon Road

420 5th Street North, Suite 100 Raleigh, NC 27603

Minneapolis, MN 55401 (919) 661-6351

(612) 758-4502 StructuresReview@tepgroup.net

Subject: Maintenance and Condition Assessment Report

Tower Designation: Site Number: AZ2143

Site Name: Whitetank Mountain

Engineering Firm Designation: TEP Project Number: 69922_85717

Site Data: N. Tower Road, Buckeye, Maricopa County, AZ 85326

Lat., Long.: 33.575406, -112.578769

(N 33° 34' 31.46”, W 112° 34' 43.57”)

80 Foot ± – Self Supporting Tower

Dear Mr. Fiskum, Tower Engineering Professionals (TEP) completed a periodic inspection for the above referenced site. The onsite investigation was performed by Kyle C. Edwards, P.E., C.W.I. and Andrew E. Propst of TEP during the July 13, 2016 site visit. The inspection was in accordance with the ANSI/TIA-222-G-2005, Annex J: Maintenance and Condition Assessment

(Normative), including all addendums (addendums TIA-222-G-1 2007 and TIA 222-G-2 2009); the checklist can be found on pages 3 thru 8 of this report.

Observations and recommendations are listed herein. The inspection included observation of the tower components and CBP owned assets. For the purpose of this inspection, the tower legs were named by letter according to the magnetic azimuth defined by a line from the center of tower to the leg. “A” leg is the leg closest to magnetic north, followed clockwise by “B” and “C.”

Thank you for the opportunity to provide this service for you. If you have any questions or comments, please contact our office.

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

Self Supporting Tower Maintenance and Condition Assessment Report September 9, 2016

TEP Project Number 69922_85717 AZ2143 - Whitetank Mountain

TABLE OF CONTENTS

1) ANSI/TIA-222-G-MAINTENANCE AND CONDITION ASSESSMENT

2) SUMMARY

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

ANSI/TIA-222-G MAINTENANCE AND CONDITION ASSESSMENT

A. STRUCTURE CONDITION

A.1. Damaged members (legs and bracing)

Okay Possible Improvement Needs Repair Not Applicable

Notes:

A.2. Loose members

Okay Possible Improvement Needs Repair Not Applicable

Notes:

A.3. Missing members

Okay Possible Improvement Needs Repair Not Applicable

Notes:

A.4. Climbing facilities, platforms, catwalks – all secure

Okay Possible Improvement Needs Repair Not Applicable

Notes: Missing nut locking device on ladder hardware. Safety climb cable cap is missing. See summary for details.

A.5. Loose and/or missing bolts and/or nut locking devices

Okay Possible Improvement Needs Repair Not Applicable

Notes: Missing leg bolt, loose secondary horizontal bolts, and skewed knife plates observed. See summary for details.

A.6. Visible cracks in welded connections

Notes:

B. FINISH

B.1. Paint and/or galvanizing condition

Notes:

B.2. Rust and/or corrosion condition including mounts and accessories

Okay Possible Improvement Needs Repair Not Applicable

Notes: Corroded mount hardware and surface corrosion observed on antenna mounts. See summary for details.

B.3. FAA or ICAO color marking conditions

Okay Possible Improvement Needs Repair Not Applicable

Notes:

B.4. Water collection in members (to be remedied, e.g., unplug drain holes, etc.)

Okay Possible Improvement Needs Repair Not Applicable

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

C. LIGHTING

C.1. Conduit, junction boxes, and fasteners (weather tight and secure)

Notes:

C.2. Drains and vents openings (unobstructed)

Okay Possible Improvement Needs Repair Not Applicable

Notes:

C.3. Wiring Condition

Okay Possible Improvement Needs Repair Not Applicable

Notes:

C.4. Light lenses

Okay Possible Improvement Needs Repair Not Applicable

Notes:

C.5. Bulb condition

Okay Possible Improvement Needs Repair Not Applicable

Notes:

C.6.a. Controllers functioning (Flasher)

Okay Possible Improvement Needs Repair Not Applicable

Notes:

C.6.b. Controllers functioning (Photo control)

Okay Possible Improvement Needs Repair Not Applicable

Notes:

C.6.c. Controllers functioning (Alarms)

D. GROUNDING

D.1. Connections

Notes: Insufficient weatherproofing on ground wire. See summary for details.

D.2. Corrosion

Okay Possible Improvement Needs Repair Not Applicable

Notes:

D.3. Lightning protection (secured to structure)

Okay Possible Improvement Needs Repair Not Applicable

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

E. ANTENNAS AND LINES

E.1. Antenna condition

Notes: Antenna located on C-leg at 32.3-ft is missing rain cap. See summary for details.

E.2. Mount and/or ice shield condition (bent, loose, and/or missing members)

Okay Possible Improvement Needs Repair Not Applicable

Notes: Loose antenna mounts and unused mounts were observed on the tower. See summary for details.

E.3. Feed line condition (flanges, seals, dents, jacket damage, grounding, etc.)

Okay Possible Improvement Needs Repair Not Applicable

Notes: Coax is damaged and has insufficient weatherproofing. See summary for details.

E.4. Hanger condition (snap-ins, bolt on, kellum grips, etc.)

Okay Possible Improvement Needs Repair Not Applicable

Notes:

E.5. Secured to structure

F. OTHER APPURTENANCES (WALKWAYS, PLATFORMS, SENSORS, FLOODLIGHTS, ETC.)

F.1. Condition

Notes:

F.2. Secured to structure

G. INSULATOR CONDITION

G.1. Cracking and chipping

Notes:

G.2. Cleanliness of insulators

Okay Possible Improvement Needs Repair Not Applicable

Notes:

G.3. Spark gaps set properly

Okay Possible Improvement Needs Repair Not Applicable

Notes:

G.4. Isolation transformer condition

Okay Possible Improvement Needs Repair Not Applicable

Notes:

G.5. Bolts and connection secure

Okay Possible Improvement Needs Repair Not Applicable

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

H. GUYS

H.1. Strand condition (corrosion, breaks, nicks, kinks, etc.)

Notes:

H.2.a. Guy Hardware Conditions (Turnbuckles or equivalent (secure and safety properly applied)

Okay Possible Improvement Needs Repair Not Applicable

Notes:

H.2.b. Guy Hardware Conditions (Cable thimbles properly in place (if required))

Okay Possible Improvement Needs Repair Not Applicable

Notes:

H.2.c. Guy Hardware Conditions (Service sleeves properly in place (if required))

Okay Possible Improvement Needs Repair Not Applicable

Notes:

H.2.d.i. Guy Hardware Conditions (Cable connectors (end fittings) (Cable clamps applied properly and bolts tight))

Okay Possible Improvement Needs Repair Not Applicable

Notes:

H.2.d.ii. Guy Hardware Conditions (Cable connectors (end fittings) (Wire serving properly applied))

Okay Possible Improvement Needs Repair Not Applicable

Notes:

H.2.d.iii. Guy Hardware Conditions (Cable connectors (end fittings) (No signs of slippage or damaged strands))

Okay Possible Improvement Needs Repair Not Applicable

Notes:

H.2.d.iv. Guy Hardware Conditions (Cable connectors (Preformed wraps – properly applied, fully wrapped, & sleeve in place))

Okay Possible Improvement Needs Repair Not Applicable

Notes:

H.2.d.v. Guy Hardware Conditions (Cable connectors (end fittings) (Poured sockets secure and showing no separation))

Okay Possible Improvement Needs Repair Not Applicable

Notes:

H.2.d.vi. Guy Hardware Conditions (Cable connectors (Shackles, bolts, pins, and cotter pins secure and in good condition))

Okay Possible Improvement Needs Repair Not Applicable

Notes:

H.3. Guy tensions

Okay Possible Improvement Needs Repair Not Applicable

Notes:

H.4. Measure guy tensions

Okay Possible Improvement Needs Repair Not Applicable

Notes:

H.5. Record temperature, wind speed and wind direction

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

I. CONCRETE FOUNDATIONS

I.1.a. Ground condition (Settlement, movement or earth cracks)

Notes:

I.1.b. Ground condition (Erosion)

Okay Possible Improvement Needs Repair Not Applicable

Notes:

I.1.c. Ground condition (Site condition (standing water, drainage, trees, etc.))

Okay Possible Improvement Needs Repair Not Applicable

Notes:

I.2.a. Anchorage condition (Nuts and/or nut locking device (tightened))

Okay Possible Improvement Needs Repair Not Applicable

Notes: Half sized jam nut installed on top of anchor bolts. See summary for details.

I.2.b. Anchorage condition (Grout condition)

Okay Possible Improvement Needs Repair Not Applicable

Notes:

I.2.c. Anchorage condition (Anchorages and/or anchor rod condition)

Okay Possible Improvement Needs Repair Not Applicable

Notes:

I.3.a. Concrete condition (Cracking, spalling, or splitting)

Okay Possible Improvement Needs Repair Not Applicable

Notes:

I.3.b. Concrete condition (Chipped or broken concrete)

Okay Possible Improvement Needs Repair Not Applicable

Notes:

I.3.c. Concrete condition (Honeycombing)

Okay Possible Improvement Needs Repair Not Applicable

Notes:

I.3.d. Concrete condition (Low spots to collect moisture)

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

J. GUYED MAST ANCHORS

J.1. Settlement, movement or earth cracks

Notes:

J.2. Backfill heaped over concrete for water shedding

Okay Possible Improvement Needs Repair Not Applicable

Notes:

J.3. Anchor rod condition below earth (Maintain required structural capacity of anchor during exploration.)

Okay Possible Improvement Needs Repair Not Applicable

Notes:

J.4. Corrosion control measures (galvanizing, coating, concrete encasement, cathodic protection systems, etc.)

Okay Possible Improvement Needs Repair Not Applicable

Notes:

J.5. Anchor heads clear of earth

K. TOWER ALIGNMENT

K.1. Tower Plumb and Twist

Notes: Tower twist and plumb was not measured as a part of this scope of work.

L. NON-TIA RELATED ITEMS

L.1. Equipment Shelter

Notes:

L.2. Security

Okay Possible Improvement Needs Repair Not Applicable

Notes: Perimeter fencing was not installed around the compound or guy anchor foundations. See summary for details.

L.3. Other Equipment

Okay Possible Improvement Needs Repair Not Applicable

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

SUMMARY

Photograph Observations and Recommendations

A.4. Climbing facilities, platforms, catwalks (all secure)

Observation:

Missing nut locking device on ladder hardware at 59-ft.

Safety climb cable cap is missing.

Recommendation:

Install a nut locking device. If necessary, re-install a longer bolt to accommodate the use of a nut locking device. Tighten all nuts per the AISC "turn of the nut" method.

Replace safety climb cable cap.

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

A.5. Loose and/or missing bolts and/or nut locking devices

Missing 5/8” dia. leg bolt observed to be replaced with a smaller bolt at 20-ft on the B-leg.

Loose A325 secondary horizontal bolt(s) observed on all faces from 20-ft to 60-ft.

Replace with a new A325N 5/8"dia. leg bolt. Tighten all nuts per the AISC "turn of the nut" method.

Tighten both U-bolt nuts per the AISC "turn of the nut" method.

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

A.5. Loose and/or missing bolts and/or nut locking devices

Skewed knife plate gap observed on secondary horizontals typical throughout the tower height.

No action required. Based on a structural analysis, it has been determined that skewed knife plate gaps are not influential to structural capacity.

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

B.2. Rust and/or corrosion condition including mounts and accessories

Corroded mount hardware observed on the antenna mount at 20-ft on the C-leg.

Surface corrosion observed on antenna mount at 73.5-ft on the A-leg.

Replace all corroded hardware per the mount manufacturer specifications. Install nut locking devices on all bolts. Tighten all nuts per the AISC "turn of the nut" method.

Clean areas of corrosion down to sound metal and coat with two brush coats of ZRC cold galvanizing compound or approved equivalent.

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

D.1. Connections

Ground wiring has insufficient weatherproofing.

Repair ground wire weatherproofing to prevent water intrusion.

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

E.1. Antenna condition

Antenna located on C-leg at 32.3-ft is missing rain cap.

Repair or replace antenna.

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

E.2. Mount and/or ice shield condition (bent, loose, and/or missing members)

Antenna mounts located on B-leg at 20-ft and on C-leg at

32.3-ft are loose.

Unused antenna mount on B-leg at 62-ft

Install nut locking devices. Tighten all nuts per AISC “turn of the nut” method

Removing the unused antenna mount will improve the overall structural capacity of the tower.

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

E.3. Feed line condition (flanges, seals, dents, jacket damage, grounding, etc.)

FH 7/8 coax from 7-ft to 60.3-ft is damaged at 20-ft.

FH 1/2 coax from has insufficient weatherproofing at 77-ft.

Repair coax.

Repair coax weatherproofing to prevent water intrusion.

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

I.2.a. Anchorage condition (Nuts and/or nut locking device

(tightened))

Half sized jam nut installed on top of (1) anchor bolt at each leg.

Place the half sized nut on the bolt first. Tighten the nut to

50% of the overall tightening torque. Place the structural nut on the bolt. Hold the half sized nut to prevent rotation while the structural nut is tightened to the full torque value.

Torque all structural nuts per the requirements of the AISC

Steel Construction Manual.

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

L.2. Security

Perimeter fencing was not installed around the compound or guy anchor foundations.

Install fencing around the compound and guy anchor foundations to ensure security of assets and provide protection to anchor foundations.

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

CAPITAL EXPENDITURE TABLE

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

ANSI/TIA-222-G: CAPITAL EXPENDITURE TABLE

Job Name: AZ2143 - Whitetank Mountain

TEP Number: 69922_85717

A. STRUCTURAL CONDITION

Issue: Repair/Modification: Repair Schedule:

A.1. Damaged members (legs and bracing)

a. The following members were overstressed in the structural analysis:

i. Order Structural Design Drawings for modifications to failing/damaged members.

0-6 months $9,500

● Tower Diagonals from 0'-39'

Sub Total: $9,500

A.4. Climbing facilities, platforms, catwalks – all secure

a. Missing nut locking device on the ladder hardware at 59-ft.

b. Safety climb cable cap is missing.

i. Install a nut locking device. If necessary, re-install a longer bolt to accommodate the use of a nut locking device. Tighten all nuts per the AISC "turn of the nut" method.

ii. Replace safety climb cable cap.

0-6 months $50

Sub Total: $50

A.5. Loose and/or missing bolts and/or nut locking devices

a. Missing 5/8” dia. leg bolt observed to be replaced with a smaller bolt at 20-ft on the B-leg.

b. Loose A325 secondary horizontal bolt(s) observed on all faces from 20-ft to 60-ft.

c. Skewed knife plate gap observed on secondary horizontals typical throughout the tower height.

i. Replace with a new A325N 5/8"dia. leg bolt.

Tighten all nuts per the AISC "turn of the nut" method.

ii. Tighten both U-bolt nuts per the AISC "turn of the nut" method.

iii. No action required. Based on a structural analysis, it has been determined that skewed knife plate gaps are not influential to structural capacity.

0-6 months $150

Sub Total: $150

Total: $9,700

B. FINISH

Issue: Repair/Modification: Repair Schedule:

B.2. Rust and/or corrosion condition including mounts and accessories

a. Corroded mount hardware observed on the antenna mount at

20-ft on the C-leg.

b. Surface corrosion observed on antenna mount at

73.5-ft on the A-leg.

i. Replace all corroded hardware per the mount manufacturer specifications. Install nut locking devices on all bolts. Tighten all nuts per the AISC

"turn of the nut" method.

ii. Clean areas of corrosion down to sound metal and coat with two brush coats of ZRC cold galvanizing compound or approved equivalent.

0-1 year $400

Sub Total: $400

Total: $400

C. LIGHTING

NO DEFICIENCIES WERE IDENTIFIED

D. GROUNDING

Issue: Repair/Modification: Repair Schedule:

D.1. Connections

a. Ground wiring has insufficient weatherproofing. i. Repair ground wire weatherproofing to prevent water intrusion.

0-1 year $150

Sub Total: $150

Total: $150

*Items that don't require attention were omitted from this list of itemized modification costs. For a full itemized list of everything that was assessed during our site visit please reference the Maintenance and Condition Assessment.

Fee:

Modification Fee:

Fee:

ii. Complete repairs as specified in Structural Design

Drawings.

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

E. ANTENNAS AND LINES

Issue: Repair/Modification: Repair Schedule:

E.1. Antenna condition

a. Antenna located on C-leg at 32.3-ft is missing rain cap. i. Repair or replace antenna. 0-5 years $350

Sub Total: $350

E.2. Mount and/or ice shield condition (bent, loose, and/or missing members)

a. Antenna mounts located on B-leg at 20-ft and on C-leg at 32.3-ft are loose.

b. Unused antenna mount on B-leg at 62-ft

i. Install nut locking devices. Tighten all nuts per AISC

“turn of the nut” method

ii. Removing the unused antenna mount will improve the overall structural capacity of the tower.

0-1 year $350

Sub Total: $350

E.3. Feed line condition (flanges, seals, dents, jacket damage, grounding, etc.)

a. FH 7/8 coax from 7-ft to 60.3-ft is damaged at 20-ft.

b. FH 1/2 coax from has insufficient weatherproofing at 77-ft.

i. Repair coax.

Ii. Repair coax weatherproofing to prevent water intrusion.

0-1 year $250

Sub Total: $250

Total: $950

F. OTHER APPURTENANCES (WALKWAYS, PLATFORMS, SENSORS, FLOODLIGHTS, ETC.)

NO DEFICIENCIES WERE IDENTIFIED

G. INSULATOR CONDITION

NO DEFICIENCIES WERE IDENTIFIED

H. GUYS

NO DEFICIENCIES WERE IDENTIFIED

I. CONCRETE FOUNDATIONS

Issue: Repair/Modification: Repair Schedule:

I.2.a. Anchorage condition (Nuts and/or nut locking device

(tightened))

a. Half sized jam nut installed on top of (1) anchor bolt at each leg.

i. Place the half sized nut on the bolt first. Tighten the nut to 50% of the overall tightening torque. Place the structural nut on the bolt. Hold the half sized nut to prevent rotation while the structural nut is tightened to the full torque value. Torque all structural nuts per the requirements of the AISC Steel

Construction Manual.

0-1 year $250

Sub Total: $250

Total: $250

J. GUYED MAST ANCHORS

NO DEFICIENCIES WERE IDENTIFIED

K. TOWER ALIGNMENT

NO DEFICIENCIES WERE IDENTIFIED

Fee:

Fee:

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

L. NON-TIA ISSUES

Issue: Repair/Modification: Repair Schedule:

L.2. Security

a. Perimeter fencing was not installed around the compound or guy anchor foundations.

i. Install fencing around the compound and guy anchor foundations to ensure security of assets and provide protection to anchor foundations.

0-1 year $9,000

Sub Total: $9,000

Total: $9,000

OTHER CONSTRUCTION COSTS

Item:

a. Permits / Application Fees $1,000

b. Post Modification Inspection Report $2,000

c. Mobilization Costs $1,500

Sub Total: $4,500

Total: $4,500

GRAND TOTAL: $24,950

Fee:

Fee:

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

ANNEX A:

STEEL AND APPURTENANCE MAPPING

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

TOWER MAPPING

Site Name

TEP #

Client # Date Page of

WHITETANK MOUNTAIN

69922_85717

AZ2143

SEPTEMBER 9, 2016

326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net

Page Title Initials Page # (s) Notes Checklist & Notes

Tower Elevation Tower Section Elevation Transmission Cables

Waveguide

Antenna and Mount Sketch Photos

AEP

6-9 10-11 12-26 27-30

CHECKLIST

Latitude: Longitude:

Ground Elevation:

Site Address:

Tower ID Plate:

Existing Carriers/Site #:

Gate Combo:

Telephone Company:

Pedestal # and Location:

Power Company:

Meter # and Owner:

33.575406° (N 33° 34' 31.46")

4086-FT (VIA GOOGLE EARTH)

N. TOWER ROAD, BUCKEYE, AZ 85326 (MARICOPA COUNTY)

NONE OBSERVED

NONE OBSERVED

N/A

NONE OBSERVED

10 455 878 / CBP

CBP / AZ2143

N/A

-112.578769° (W 112° 34' 43.57")

Crew Leader:

Crew Member: ANDREW E. PROPST

Abbreviations: AGL: Above Ground Level B.C.: Bolt Circle BP: Bent Plate C-C: Center to Center C: Channel CNR: Could Not Record EW: Elliptical Waveguide FH: Foam Heliax

HCL: Hard Copper Line HSS: Hollow Structural Section L: Angle 2L: Double Angle MC: Metal Conduit M.E.: Minimum Edge MOD: Modification PL: Plate

RC: Rigid Conduit S.B.: Stitch Bolts Schl: Schifflerized Angle SM: Smooth Heliax SP: Spacing SR: Solid Rod TH: Thickness Tri: Triangular

KYLE C. EDWARDS, P.E., C.W.I.

NOTES

FCC#: N/A

Special Access Issues (Key Entry, Hidden/Unmarked Access, FM/TV on tower): ANDREA CULP

Compound Detail 2

(520) 300-3035

Ladder 3

MARICOPA COUNTY / UNKNOWN

AEP

AEP

AEP

AEP

AEP

AEP

AEP

AEP

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

TEP #

Client # Date Page of

WHITETANK MOUNTAIN

69922_85717

AZ2143

SEPTEMBER 9, 2016

COMPOUND DETAIL

326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net

Access Road Compound View CBP Equipment Shelter

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

TEP #

Client # Date Page of

WHITETANK MOUNTAIN

69922_85717

AZ2143

SEPTEMBER 9, 2016

326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net

LADDER

Climbing Ladder #1 Sketch

Description Ladder

# Height Width Step Rail (type & size) Rung (type & size) Safety (type & size)

13" 12" SR5

8"Ø SR7

8"Ø 3 8"Ø0'-80'1

Climbing Ladder #1 Photo

Climbing Ladder #1 Photo

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

TEP #

Client # Date Page of

WHITETANK MOUNTAIN

69922_85717

AZ2143

SEPTEMBER 9, 2016

326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net

Description # Height Width Step Rail (type & size) Rung (type & size) Holes (size & spacing)

Waveguide Waveguide

WAVEGUIDE

7'-80'± 19" 48" N/A PL4"X19"X18" (6) 34"Ø, (2) 38"X1"1

2 7'-80'± 14" 36" C-LEG PL2"X14"X3

8"

Waveguide Ladder #1 Sketch

Waveguide Ladder #2 Sketch

Waveguide Ladder #1 Photo

Waveguide Ladder #2 Photo

(5) 14"Ø

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

T/ BASE PLATE

0'-0"± (REF.)

T/ TOWER

80'-0"±

℄ANT. 1

10'-6"

℄ANT. 2

20'-0"

℄ANT. 3

20'-3"

℄ANT. 5

32'-4"

℄ANT. 4

31'-0"

℄ANT. 6

35'-0"

℄ANT. 7

37'-0"

℄ANT. 9

54'-8"

℄ANT. 8

50'-0"

℄ANT. 10

60'-3"

℄ANT. 12

81'-0"

℄ANT. 14

88'-0"

℄ANT. 11

78'-6"

℄ANT. 13

82'-8"

T/ ANT.

98'-0"±

T/ L-ROD

82'-0"

TOWER MAPPING

Site Name

TEP #

Client # Date Page of

WHITETANK MOUNTAIN

69922_85717

AZ2143

SEPTEMBER 9, 2016

TOWER ELEVATION

326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350

TOWER MAPPING

Site Name

TEP #

Client # Date Page of

WHITETANK MOUNTAIN

69922_85717

AZ2143

SEPTEMBER 9, 2016

TOWER SECTION ELEVATION

BASE PLATE PHOTOSECTION _______________1 (0' - 20') PHOTO

MEMBER SIZES

Member

LEG

DIAG.

Size Bolts Gussets/Flange

SR 21

2"Ø

SR 1"Ø

12"Ø X 1"

PL12"X3"X3

8"

Face Width at Top ___________ Face Width at Bottom_________58"

58"

Min. Edge

1"(2) 58"Ø

HORIZ. SR 78"Ø

SUB-HORIZ. SR 78"Ø

(6) 11 4"Ø

PL12"X3"X3

8"

PL3"X4"X14"

1"(2) 58"Ø

2"(1) 58"Ø

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

TOWER MAPPING

Site Name

TEP #

Client # Date Page of

WHITETANK MOUNTAIN

69922_85717

AZ2143

SEPTEMBER 9, 2016

TOWER SECTION ELEVATION

SECTION __________________2 (20' - 40')

MEMBER SIZES

Face Width at Top ___________ Face Width at Bottom_________58"

58"

Member Size Bolts Gussets/FlangeMin. Edge

PHOTO PHOTO

LEG

DIAG.

SR 2"Ø

SR 78"Ø

8"Ø X 1"

PL12"X3"X3

8"1"(2) 58"Ø

HORIZ. SR 78"Ø

SUB-HORIZ. SR 34"Ø

(6) 58"Ø

PL12"X3"X3

8"

PL3"X4"X14"

1"(2) 58"Ø

2"(1) 58"Ø

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

TOWER MAPPING

Site Name

TEP #

Client # Date Page of

WHITETANK MOUNTAIN

69922_85717

AZ2143

SEPTEMBER 9, 2016

TOWER SECTION ELEVATION

SECTION __________________3 (40' - 60')

MEMBER SIZES

Face Width at Top ___________ Face Width at Bottom_________58"

58"

Member Size Bolts Gussets/FlangeMin. Edge

PHOTO PHOTO

LEG

DIAG.

SR 13

4"Ø

SR 78"Ø

8"Ø X 1"

PL12"X3"X3

8"1"(2) 58"Ø

HORIZ. SR 78"Ø

MOD. SR 34"Ø

(6) 58"Ø

PL12"X3"X3

8"

PL3"X4"X14"

1"(2) 58"Ø

2"(1) 58"Ø

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

TOWER MAPPING

Site Name

TEP #

Client # Date Page of

WHITETANK MOUNTAIN

69922_85717

AZ2143

SEPTEMBER 9, 2016

TOWER SECTION ELEVATION

SECTION __________________4 (60' - 80')

MEMBER SIZES

Face Width at Top ___________ Face Width at Bottom_________58"

58"

Member Size Bolts Gussets/FlangeMin. Edge

PHOTO PHOTO

LEG

DIAG.

SR 13

4"Ø

SR 34"Ø

8"Ø X 1"

PL12"X3"X3

8"1"(2) 58"Ø

HORIZ. SR 78"Ø

(6) 58"Ø

PL12"X3"X3

8"1"(2) 58"Ø

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

20°

260° 140°

TOWER MAPPING

Site Name

TEP #

Client # Date Page of

WHITETANK MOUNTAIN

69922_85717

AZ2143

SEPTEMBER 9, 2016

TRANSMISSION CABLES

326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net

Coax # Type/Style Start Height End Height Antenna Carrier Notes

PHX FIRE2 37'-0"

CITY OF PHOENIX

20'-3"

EW52 5'-0" 10'-6" 1

FH 78

FH 12

7'-0"

7'-0"

CBPFH 78

FH 12

FH 12

FH 12

FH 78

FH 78

FH 78

FH 78

7'-0" 7'-0" 7'-0"

7'-0"

7'-0" 7'-0"

7'-0"

7'-0"

20'-0" CBP

CBP

31'-0" CBP

35'-0"

49'-0" CBP

60'-3" CBP

PHX FIRE78'-0"

CBP

CBP

77'-0"

88'-0"

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

TEP #

Client # Date Page of

WHITETANK MOUNTAIN

69922_85717

AZ2143

SEPTEMBER 9, 2016

326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net

TRANSMISSION CABLES (CONTINUED)

PHX FIRE & WATER

32'-4"

FH 78

FH 78

7'-0" 7'-0"

FH 12

FH 78

7'-0" 7'-0"

Coax # Type/Style Start Height End Height Antenna Carrier Notes

CUT

PHX FIRE59'-0"

PHX FIRE & WATER73'-6"

60'-0" -

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

TEP #

Client # Date Page of

WHITETANK MOUNTAIN

69922_85717

AZ2143

SEPTEMBER 9, 2016

ANTENNA AND MOUNT SKETCH

326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net

Side Elevation Plan View

Photo

Mount Elevation LegAntenna # 1 10'-6" B

Mount Type Azimuth

PIPE 75°

Antenna Manufacturer Antenna Model #

ANDREW UHX10-59-P6A

TMA (#) / Model # (Coax Quantity) Size

N/A (1) EW52

Antenna Elevation 10'-6"

Carrier______________CITY OF PHOENIX

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

TEP #

Client # Date Page of

WHITETANK MOUNTAIN

69922_85717

AZ2143

SEPTEMBER 9, 2016

ANTENNA AND MOUNT SKETCH

326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net

Side Elevation Plan View

Photo

Mount Elevation LegAntenna # 2 20'-0" B

Mount Type Azimuth

PIPE 110°

Antenna Manufacturer Antenna Model #

RADIATION SYSTEMS P-22A96GF

TMA (#) / Model # (Coax Quantity) Size

N/A (1) FH 7/8

Antenna Elevation 20'-0"

Carrier______________CBP

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

TEP #

Client # Date Page of

WHITETANK MOUNTAIN

69922_85717

AZ2143

SEPTEMBER 9, 2016

ANTENNA AND MOUNT SKETCH

326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net

Side Elevation Plan View

Photo

Mount Elevation LegAntenna # 3 20'-3" C

Mount Type Azimuth

PIPE 210°

Antenna Manufacturer Antenna Model #

RADIATION SYSTEMS P-22A72GF

TMA (#) / Model # (Coax Quantity) Size

N/A (1) FH 7/8

Antenna Elevation 20'-3"

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

TEP #

Client # Date Page of

WHITETANK MOUNTAIN

69922_85717

AZ2143

SEPTEMBER 9, 2016

ANTENNA AND MOUNT SKETCH

326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net

Side Elevation Plan View

Photo

Mount Elevation LegAntenna # 4 31'-0" A

Mount Type Azimuth

PIPE 90°

Antenna Manufacturer Antenna Model #

SCALA 94150-003

TMA (#) / Model # (Coax Quantity) Size

N/A (1) FH 7/8

Antenna Elevation 31'-0"

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

TEP #

Client # Date Page of

WHITETANK MOUNTAIN

69922_85717

AZ2143

SEPTEMBER 9, 2016

ANTENNA AND MOUNT SKETCH

326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net

Side Elevation Plan View

Photo

Mount Elevation LegAntenna # 5 28'-10" C

Mount Type Azimuth

SIDEARM N/A

Antenna Manufacturer Antenna Model #

UNKNOWN 3"Ø X 7' OMNI

TMA (#) / Model # (Coax Quantity) Size

N/A (1) FH 7/8

Antenna Elevation 32'-4"

Carrier_______________PHX FIRE & WATER

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

TEP #

Client # Date Page of

WHITETANK MOUNTAIN

69922_85717

AZ2143

SEPTEMBER 9, 2016

ANTENNA AND MOUNT SKETCH

326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net

Side Elevation Plan View

Photo

Mount Elevation LegAntenna # 6 35'-0" B

Mount Type Azimuth

PIPE 210°

Antenna Manufacturer Antenna Model #

UNKNOWN GRID 8' Ø

TMA (#) / Model # (Coax Quantity) Size

N/A (1) FH 7/8

Antenna Elevation 35'-0"

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

TEP #

Client # Date Page of

WHITETANK MOUNTAIN

69922_85717

AZ2143

SEPTEMBER 9, 2016

ANTENNA AND MOUNT SKETCH

326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net

Side Elevation Plan View

Photo

Mount Elevation LegAntenna # 7 47'-0" A

Mount Type Azimuth

SIDEARM N/A

Antenna Manufacturer Antenna Model #

ANDREW DB224

TMA (#) / Model # (Coax Quantity) Size

N/A (1) FH 7/8

Antenna Elevation 37'-0"

Carrier______________PHX FIRE

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

TEP #

Client # Date Page of

WHITETANK MOUNTAIN

69922_85717

AZ2143

SEPTEMBER 9, 2016

ANTENNA AND MOUNT SKETCH

326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net

Side Elevation Plan View

Photo

Mount Elevation LegAntenna # 8 59'-0" B

Mount Type Azimuth

SIDEARM N/A

Antenna Manufacturer Antenna Model #

ANDREW DB224

TMA (#) / Model # (Coax Quantity) Size

N/A (1) FH 7/8

Antenna Elevation 50'-0"

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

TEP #

Client # Date Page of

WHITETANK MOUNTAIN

69922_85717

AZ2143

SEPTEMBER 9, 2016

ANTENNA AND MOUNT SKETCH

326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net

Side Elevation Plan View

Photo

Mount Elevation LegAntenna #

- 62'-0" B

Mount Type Azimuth

SIDEARM N/A

Antenna Manufacturer Antenna Model #

TMA (#) / Model # (Coax Quantity) Size

Antenna Elevation

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

TEP #

Client # Date Page of

WHITETANK MOUNTAIN

69922_85717

AZ2143

SEPTEMBER 9, 2016

ANTENNA AND MOUNT SKETCH

326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net

Side Elevation Plan View

Photo

Mount Elevation LegAntenna # 9 49'-0" A

Mount Type Azimuth

SIDEARM N/A

Antenna Manufacturer Antenna Model #

RFI BA40-41-DIN

TMA (#) / Model # (Coax Quantity) Size

N/A (1) FH 7/8

Antenna Elevation 54'-9"

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

TEP #

Client # Date Page of

WHITETANK MOUNTAIN

69922_85717

AZ2143

SEPTEMBER 9, 2016

ANTENNA AND MOUNT SKETCH

326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net

Side Elevation Plan View

Photo

Mount Elevation LegAntenna # 10 60'-3" C

Mount Type Azimuth

PIPE 210°

Antenna Manufacturer Antenna Model #

UNKNOWN 8'Ø GRID DISH

TMA (#) / Model # (Coax Quantity) Size

N/A (1) FH 7/8

Antenna Elevation 60'-3"

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

TEP #

Client # Date Page of

WHITETANK MOUNTAIN

69922_85717

AZ2143

SEPTEMBER 9, 2016

ANTENNA AND MOUNT SKETCH

326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net

Side Elevation Plan View

Photo

Mount Elevation LegAntenna # 11 73'-6" A

Mount Type Azimuth

SIDEARM N/A

Antenna Manufacturer Antenna Model #

UNKNOWN 2.5"Ø X 10' OMNI

TMA (#) / Model # (Coax Quantity) Size

N/A (1) FH 7/8

Antenna Elevation 78'-6"

Carrier_______________PHX FIRE & WATER

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

TEP #

Client # Date Page of

WHITETANK MOUNTAIN

69922_85717

AZ2143

SEPTEMBER 9, 2016

ANTENNA AND MOUNT SKETCH

326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net

Side Elevation Plan View

Photo

Mount Elevation LegAntenna # 12 76'-0" C

Mount Type Azimuth

SIDEARM N/A

Antenna Manufacturer Antenna Model #

UNKNOWN 1"Ø X 8' OMNI

TMA (#) / Model # (Coax Quantity) Size

N/A (1) FH 7/8

Antenna Elevation 81'-0"

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

TEP #

Client # Date Page of

WHITETANK MOUNTAIN

69922_85717

AZ2143

SEPTEMBER 9, 2016

ANTENNA AND MOUNT SKETCH

326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net

Side Elevation Plan View

Photo

Mount Elevation LegAntenna # 13 77'-0" A

Mount Type Azimuth

SIDEARM N/A

Antenna Manufacturer Antenna Model #

RFI BA40-41-DIN

TMA (#) / Model # (Coax Quantity) Size

N/A (1) FH 7/8

Antenna Elevation 82'-9"

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

TEP #

Client # Date Page of

WHITETANK MOUNTAIN

69922_85717

AZ2143

SEPTEMBER 9, 2016

ANTENNA AND MOUNT SKETCH

326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net

Side Elevation Plan View

Photo

Mount Elevation LegAntenna # 14 78'-0" B

Mount Type Azimuth

SIDEARM N/A

Antenna Manufacturer Antenna Model #

ANDREW DB224-A

TMA (#) / Model # (Coax Quantity) Size

N/A (1) FH 7/8

Antenna Elevation 88'-0"

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

TEP #

Client # Date Page of

WHITETANK MOUNTAIN

69922_85717

AZ2143

SEPTEMBER 9, 2016

326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net

PHOTOS

Partial Tower Elevation

Partial Tower Elevation

Partial Tower Elevation

Base of Tower

Tower Elevation

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

TEP #

Client # Date Page of

WHITETANK MOUNTAIN

69922_85717

AZ2143

SEPTEMBER 9, 2016

326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net

PHOTOS

CA Face

BC Face

AB Face

C Leg

B Leg

A Leg

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

TEP #

Client # Date Page of

WHITETANK MOUNTAIN

69922_85717

AZ2143

SEPTEMBER 9, 2016

326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net

PHOTOS

Typical Mod. Connection

Equipment Shelter by Others

Power Meter

Typical Mod. Connection

CBP Equipment Shelter

Top of Tower

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

TEP #

Client # Date Page of

WHITETANK MOUNTAIN

69922_85717

AZ2143

SEPTEMBER 9, 2016

326 Tryon Road, Raleigh, NC 27603 o) 919.661.6351 f) 919.661.6350 www.tepgroup.net

PHOTOS

Cellular Receivers

Cellular Receivers

Inside CBP Shelter

CBP Fuel Cell Generator

HVAC Units

CBP Shelter Access

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

ANNEX B:

STRUCTURAL ANALYSIS

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

HGA Architects and Engineers 326 Tryon Road 420 5th Street North, Suite 100 Raleigh, NC 27603 Minneapolis, MN 55401 (919) 661-6351

(612) 758-4502 StructuresReview@tepgroup.net

Subject: Structural Analysis Report

Carrier Designation: U.S. Department of Homeland Security Site Number: AZ2143 Site Name: Whitetank Mountain

Engineering Firm Designation: TEP Project Number: 69922_85717

Site Data: N. Tower Road, Buckeye, Maricopa County, AZ 85326 Lat., Long.: 33.575406, -112.578769 (N 33° 34' 31.46'', W 112° 34' 43.57'') 80 Foot ± - Self Supporting Tower Dear Mr. Fiskum, Tower Engineering Professionals is pleased to submit this “Structural Analysis Report” to determine the structural integrity of the above mentioned tower.

The purpose of the analysis is to determine acceptability of the tower stress level. Based on our analysis we have determined the tower stress level for the structure and foundation, under the following load case, to be:

LC1: Existing + Proposed + Reserved Loading Insufficient Capacity Note: See Table 1 for the existing, proposed, and reserved loading

The analysis has been performed in accordance with the ANSI/TIA-222-G-2-2009 Structural Standard for Antenna Supporting Structures and Antennas – Addendum 2 and the 2012 International Building Code.

All modifications and equipment proposed in this report shall be installed in accordance with the appurtenances listed in Table 1 for the determined available structural capacity to be effective.

We at Tower Engineering Professionals appreciate the opportunity of providing our continuing professional services to you and HGA Architects and Engineers. If you have any questions or need further assistance on this or any other projects please give us a call.

Structural analysis prepared by: Nick Smith, E.I.

Structure Capacity Foundation Capacity

160.4% -

PROPERTY OF THE UNITED STATES GOVERNMENT- FOR OFFICIAL USE ONLY- DO NOT REMOVE THIS NOTICE- PROPERLY DESTROY DOCUMENTS WHEN NO LONGER NEEDED

80-ft± Self Supporting Tower Structural…