657A5-21-401 - Drawings R2_Part6 - 10 pages.pdf

PDF 15 MB Posted

Attached to
Z2DA--657A5-21-401, Construct New Campus Chiller Plant, MRN
Solicitation number
36C25526R0129
Issued by

About this file

These are contract documents for a construction project at Marion VA Medical Center consisting of electrical and mechanical systems design drawings and schedules. The project involves construction of a new energy center (Building 49) and includes comprehensive mechanical, electrical, power, fire alarm, and lighting systems for a multi-story facility.

The scope encompasses HVAC systems including three 356.66 kVA chillers, multiple chilled water pumps (primary and secondary), condenser water pumps, cooling towers, and basin heaters on the roof. The electrical infrastructure includes a 1500 kVA transformer with 800A disconnect, automatic transfer switches, distribution panels rated for 480Y/277V three-phase service, and motor control centers. Lighting design features LED fixtures throughout including 2x2 flat panels (B1/B2), 1x4 industrial strips (C1/C2), low bay fixtures (LB1/LB2), exterior wall packs (WP1/WP2), and pole-mounted fixtures (PL1-PL4). The project incorporates emergency lighting, lightning protection systems with air terminals and down conductors, and heating/cooling equipment serving multiple rooms including a control room, electrical rooms, H.A.C. space, and toilet facilities. Distribution panels detailed include E-EQ-1HDP1 (356.66 kVA), E-EQ-1HDP2 (713.33 kVA estimated demand), US-49 (390.27 kVA connected load), and GP-1HDP1. The electrical design provides for variable frequency drives on multiple motors, remote shut-off capabilities, and coordination between Division 22, 23, 26, and 27 work requirements. Construction documents are dated 05/07/2026 with the project marked as "fully sprinklered."

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

UH

UH

UH

UH

UH

F F F

GF

WH

F F

UH

49-1

49-EQ1

49-EQ-2

49-MCC1

CT1/CT2

BREAKER

49-MCC3

ATS-49/US49

ATS-49-1/US49-1

US-49-1

US-49

49-EF1

49-EF1

1500 KVA

TRANSFORMER

SWITCH

800A

DISC

PB

PB

PB

CT-1 CT-2 CT-3

CH-3CH-2CH-1

EF

ON ROOF

EF

ON ROOF

CU

ON ROOF

EF

ON ROOF

40 HP

PUMP

40 HP

PUMP

40 HP

PUMP

30 HP

PUMP

30 HP

PUMP

30 HP

PUMP

P-10

US-49-1

US-49

US-49

VFD

VFD

VFD

CONDENSER SYSTEM DX10

CHILLER SYSTEM DX10

METER ENCLOSURE

TRANSFORMER

PB

BASIN

HEATER

BASIN

HEATER

BASIN

HEATER

TYP.

TYP.

TYP.

P-3

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Date:Revisions:No.

A u to d e s k D o c s /M a ri o n I

L V

A

N e w E n e rg y C e n te r/

-0

-M

E P

-C e n tr a l.

rv t

/5 /2

:2

:0

P M

ED100

BUILDING 49 DEMOLITION PLAN

05/07/2026 MSG DMB

CONSTRUCT NEW

CAMPUS CHILLER PLANT

657A5-21-401

2401 W MAIN ST, MARION IL 62959

CONTRACT

DOCUMENTS 49

MARION VA

MEDICAL

CENTER Approved: Owner

SCALE: 1/4" = 1'-0"

FIRST FLOOR DEMOLITION PLAN

A. REMOVAL PLANS MAY NOT NECESSARILY SHOW ALL ITEMS REQUIRED TO BE REMOVED.

B. REMOVAL OF ELECTRICAL ITEMS SHALL INCLUDE REMOVALS BACK TO THE EXISTING ELECTRICAL

DISTRIBUTION CENTER, PANEL OR LAST ACTIVE OUTLET, FIXTURE OR DEVICE REMAINING.

C. REMOVE ALL ABANDONED EXTRANEOUS CONDUITS, SUPPORTS, CONTROLS, ETC.

D. REMOVALS OF RECEPTACLES, TELEPHONE, DATA OUTLETS, ETC. INCLUDE REMOVAL OF THE DEVICE, BACKBOX, CONDUIT, WIRING, ETC.

E. ALL EXISTING FLUORESCENT LAMPS AND BALLASTS REMOVED ARE TO BE PUT INTO CONTAINERS FURNISHED BY THE OWNER AND DISPOSED OF BY A QUALIFIED CONTRACTOR AT AN APPROVED DISPOSAL

FACILITY.

F. ALL EXISTING CONDUIT, EQUIPMENT, CONTROLS, ETC. SHOWN DASHED SHALL BE REMOVED. THE MAJORITY OF ELECTRICAL WORK TO BE REMOVED IS SHOWN. REMOVE ALL INCIDENTAL ITEMS ASSOCIATED WITH THE

DEMOLITION WORK.

G. ALL EXISTING FIRE ALARM EQUIPMENT AND DEVICES SHALL BE REMOVED AS NOTED. CONTRACTOR SHALL SALVAGE EQUIPMENT AS DIRECTED BY THE OWNER AND STORED IN A LOCATION DESIGNATED BY THE OWNER. ALL OTHER EQUIPMENT AND DEVICES NOT SALVAGED SHALL BE REMOVED AS DIRECTED FROM THE

PREMISE.

H. CONTRACTOR SHALL COORDINATE WITH THE OWNER IN REGARD TO REMOVALS. CONTRACTOR SHALL SALVAGE EQUIPMENT AS DIRECTED BY THE OWNER AND STORED IN A LOCATION DESIGNATED BY THE OWNER. ALL OTHER EQUIPMENT AND MATERIALS NOT SALVAGED SHALL BE REMOVED FROM THE PREMISE.

I. HVAC AND PLUMBING EQUIPMENT, DISCONNECT ELECTRICAL SOURCE TO EQUIPMENT AND REMOVE FEEDER

BACK TO SOURCE.

GENERAL NOTES

1. THE ENTIRE AREA WITHIN THE DASHED LINES SHALL BE REMOVED ELECTRICALLY. DISCONNECT AND REMOVE ALL ELECTRICAL DISTRIBUTION EQUIPMENT, TRANSFORMERS, AUTOMATIC TRANSFER SWITCHES, MOTOR CONTROL CENTERS, DISCONNECTS, MOTOR CONTROLLERS, WIRING DEVICES, LIGHTING FIXTURES, FIRE ALARM DEVICES, AND HVAC/PLUMBING EQUIPMENT. REMOVE ALL

ASSOCIATED WIRING AND CONDUIT.

2. DISCONNECT HEAT TRACE AND REMOVE CIRCUITRY BACK TO SOURCE.

3. DISCONNECT EXISTING LIGHTING CONTACTOR LC-1 AND STORE AND PROTECT FOR REINSTALLATION IN NEW CHILLER PLANT.

INTERMATIC TIMER CONNECTED TO LC-1 SHALL BE DISCONNECTED AND TURNED OVER TO THE VA. REFER TO SITE PHOTO ON THIS

SHEET.

PLAN NOTES

SITE KEY PLAN

NEW CHILLER PLANT - BLDG 49

EXISTING CHILLER PLANT - BLDG 49

37MOD-5

MOD-1

MOD-4

MOD-6

NORTH

SCALE: NONE

LC-1 SITE PHOTO

1 CONTRACT DOCUMENTS 05/07/2026

UP

FACP

GF

GF

F F

F

S

F

F F

F

F

F

F

F

F

F

J

UH

UH

UH

UH

GF

J

J J J

J

UH

J

FS VV

J

J

J

J

J

J

GF GF

GF

J J

GF

J

FS

S S F

J

J J

J

J J J

JJJ

J

J

J

J

J

J

J

J

J

JJ

J

J

GF

L2 1-

R

L2 1-

R

GF

S F

A

D

632 54

B

C

ELECTRICAL ROOM

ELECTRICAL ROOM

CONTROL ROOM

TR

H.A.C.

GP-1HDP1

GP-1HDP2

E-

EQ

-1

HD

P1

E-

EQ

-1

HD

P2

EQ-ATS-4EQ-ATS-3EQ-ATS-1

EQ-ATS-2 EQ-ATS-5 LS-ATS

CH-1

CH-2

CH-3

PCHWP-1PCHWP-2PCHWP-3

SCHWP-1

SCHWP-2

SCHWP-3

CDWP-1CDWP-2CDWP-3

US-49

X-FORMER

US-49

MV

SW

US-49

MV

SW

US-49

LV

SEC

CHILLER PLANT

DWH-1

1LNA - 8,10

VFD

PCHWP-3

EQ-ATS-4 - 1

EQ-ATS-3 - 1

EQ-ATS-1 - 1

E100

T-1LEA

T-1LNA

1LNA

FU

TU

RE

S

EC

Generator Annunciator

Panel

SP-1A SP-1B

1LEA - 2

1LEA - 2

1LEA - 3

1LEA - 3

1LEA - 4

1LEA - 4 1LNA - 1

1LNA - 1

1LEA - 5

1LEA - 5 1LEA - 5

1LEA - 6

1LEA2 - 14 1LEA - 8 1LEA - 7

1LEA - 8

1LNA - 1

1LNA - 1

1LEA - 7

1LEA - 7

1LEA - 6

1LEA - 6

1HNDP1 - 22,24,26

VAV-1

1HNDP1 - 7,9,11

VAV-2

1LNA - 3,5

VAV-3

1LEA - 27

7 7

T-1LLS 1HEA1LEA1LLS1LLS - 1

1LEA - 26

E-EQ-1HDP2 - 2 E-EQ-1HDP1 - 6 E-EQ-1HDP1 - 2

E-EQ-1HDP2 - 3

E-EQ-1HDP1 - 7

E-EQ-1HDP1 - 3

E-EQ-1HDP1 - 4E-EQ-1HDP1 - 8E-EQ-1HDP2 - 4

1HNDP1 - 8,10,12

1HNDP1 - 13,15,17

UH-4

1HNDP1

1L

NA

1L

NA

LCP-1

VFD

PCHWP-22

VFD

PCHWP-12

VFD

SCHWP-12

VFD

SCHWP-22

VFD

SCHWP-32

E-EQ-1HDP2 - 9

CDWF-1

9 9

1LEA2 - 2

1LEA2 - 4

UH-1

UH-2

UH-3

1HNDP1 - 19,21,23

1HNDP1 - 14,16,18

UH-5

1LNA - 4,6

A

D

61 32 54

B

C

A.4

A.6

2 2 2

1LEA21LNA -12

ATS

Annunciator

Panel

1LEA2 - 13

1LEA2 - 13

1LEA2 - 13

1LEA2 - 13

1LEA2 - 16,18,20

1LEA2 - 4

1LEA - 28

1LEA - 28

1LEA - 28

1LEA - 28

1LEA - 28

20 20 20

202020

1LEA2 - 17 1LEA2 - 17

1LEA2 - 17

1LEA2 - 17

1LEA2 - 17

1HNDP1 -30,32,34

1LLS - 6

1LLS - 6

1LNA - 1

1LEA - 33,35,37

EH-2

1HEA - 28,30,32

TYP.

1LEA2 - 4

1LEA - 34

1LEA - 34

151LEA - 34

1LEA - 39

1LEA - 38

1LEA - 38

1LEA - 38

1LEA - 38

1LEA - 39

1LEA2 - 19

1LEA2 - 19

1LEA2 - 19

1LEA2 - 19

1LEA2 - 19

1LEA2 - 19

1LEA - 42

1LEA - 42

1LEA - 42

1LEA - 42

1LEA - 42

1LEA - 42

1LEA2 - 15

C

TR

AC-1

1L

EA

,12 ,14

1L

EA

,15 ,17

1LEA - 19

1LEA - 16

1LEA - 18 1LEA - 16

C

AC-2

TRANSFORMER

MANUAL SWITCHES

METER

MAIN

BREAKER

EQ-ATS-1

EQ-ATS-3

MOD-1

DISCONNECT

SWITCH

EQ-ATS-2

1HNDP1

MOD-5&6

DISCONNECT

SWITCH

EQ-ATS-5

EQ-ATS-2

EQ-ATS-4

SPARE

FUTURE

SECTION

FUTURE

SECTION

FUTURE

SECTION

FUTURE

SECTION

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Date:Revisions:No.

C :\U se rs

\d m br

\A pp D at a\

Lo ca l\A ut od es k\ R ev it\

Au to de sk

R ev it

\C ol la bo ra tio nC ac he

\L Q

C 3M

U F8

4E

LP

\5 d1 ac

3- 2a e8 -4

5-b5 5f

-c ff8

3c 3d

3a

\e e-fd

-4 d-ab

-2 dc f.r vt

5/ 5/

1:

:5

PM

E100

FIRST FLOOR - POWER & FIRE

ALARM

05/07/2026 MSG DMB

CONSTRUCT NEW

CAMPUS CHILLER PLANT

657A5-21-401

2401 W MAIN ST, MARION IL 62959

CONTRACT

DOCUMENTS 49

MARION VA

MEDICAL

CENTER Approved: Owner

SCALE: 1/4" = 1'-0"

FIRST FLOOR PLAN - POWER & FIRE ALARM1

GENERAL NOTES:

A.

B.

C.

EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A

SEPARATE GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR.

MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND NORMAL BRANCH WIRING DEVICES SHALL HAVE

DIVIDERS BETWEEN DEVICES.

RECEPTACLES IN PRECAST WALLS SHALL BE SURFACE MOUNTED ON WALL.

SITE KEY PLAN

NEW CHILLER PLANT - BLDG 49

EXISTING CHILLER PLANT - BLDG 49

37MOD-5

MOD-1

49 MOD-4

MOD-6

NORTH

PLAN NOTES:

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

14.

15.

16.

17.

18.

19.

20.

21.

22.

23.

24.

25.

26.

CHILLER PLANT HAS HIGH AMBIENT NOISE LEVELS. DIV 26 PROVIDE ADDITIONAL NOTIFICATION APPLIANCES AS REQUIRED TO ACHIEVE

REQUIRED SOUND LEVELS.

PROVIDE REMOTE TURN OFF, AUX CONTACT, AND ALL ASSOCIATED WIRING FROM VFD TO RESPECTIVE PUMP. COORDINATE EXACT

REQUIREMENTS WITH DIVISION 23.

PROVIDE GENERATOR ANNUNCIATOR PANEL AND CONNECT TO EXISTING GENERATOR IN BUILDING 47. PROVIDE ALL REQUIRED POWER, COMMUNICATION, AND CONTROL WIRING. COORDINATE EXACT WIRING REQUIREMENTS, POINT LIST, AND PROTOCOL WITH GENERATOR

MANUFACTURER.

PROVIDE 120V/1PH CONNECTION FOR DCC PANEL. COORDINATE EXACT CONNECTION REQUIREMENTS WITH DIV 23 PRIOR TO ROUGH-IN.

INDOOR UNIT IS FED THROUGH OUTDOOR UNIT . PROVIDE INTERCONNECTING WIRE AS REQUIRED FOR A COMPLETE AND OPERATION

INSTALLATION.

RACK MOUNTED RECEPTACLE. COORDINATE EXACT MOUNTING WITH DIV 27 PRIOR TO ROUGH-IN. PROVIDE 4-#12 CU, 1#12 G IN 0.75"

CONDUIT.

PROVIDE A 120V, 1Ø ELECTRICAL CONNECTION TO DRAINAGE PUMP CONTROL PANEL. PROVIDE (2) #12 CU AND (1) #12 G IN 3/4" CONDUIT.

PROVIDE A 208V, 3Ø ELECTRICAL CONNECTION TO DRAINAGE PUMPS. PROVIDE (3) #12 CU AND (1) #12 G IN 3/4" CONDUIT. COORDINATE EXACT LOCATION AND CONNECTION REQUIREMENTS WITH DIV 22 PRIOR TO ROUGH-IN. PROVIDE ALL COMPONENTS REQUIRED FOR A

COMPLETE AND OPERATIONAL INSTALLATION.

MULTI-UNIT ENCLOSED METER. REFER TO SINGLE LINE.

PROVIDE EMERGENCY POWER-OFF (EPO) PUSHBUTTON WITH WEATHERPROOF COVER FOR EMERGENCY SHUTDOWN OF ALL CHILLERS.

COORDINATE EXACT INTERLOCKING AND CONTROL REQUIREMENTS WITH DIV 23 AND CHILLER MANUFACTURER TO ENSURE PROPER INTEGRATION WITH CHILLER CONTROL SYSTEMS. PROVIDE ALL WIRING, CONDUIT, AND ACCESSORIES REQUIRED FOR A COMPLETE AND

FUNCTIONAL INSTALLATION.

PROVIDE 120V, 1Ø ELECTRICAL CONNECTION TO ELECTRICAL ACTUATOR VALVE. COORDINATE EXACT LOCATION AND CONNECTION REQUIREMENTS WITH DIV 23 PRIOR TO ROUGH-IN. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE AND OPERATIONAL

INSTALLATION.

PROVIDE 20HP VFD FOR PRIMARY CHILLED WATER PUMPS. COORDINATE EXACT CONNECTION REQUIREMENTS WITH MANUFACTURER AND DIV 23. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE AND OPERATIONAL INSTALLATION.

PROVIDE 60HP VFD FOR SECONDARY CHILLED WATER PUMPS. COORDINATE EXACT CONNECTION REQUIREMENTS WITH MANUFACTURER AND DIV 23. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE AND OPERATIONAL INSTALLATION.

PROVIDE 208V/3PH TO OVERHEAD DOOR MOTOR AND DISCONNECT SWITCH. COORDINATE EXACT CONNECTION REQUIREMENTS WITH MANUFACTURER AND DIV 23. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE AND OPERATIONAL INSTALLATION.

PROVIDE AND COORDINATE EXACT LOCATION, MOUNTING, AND ACCESS REQUIREMENTS OF FLOW SWITCH AND TAMPER SWITCH WITH

DIV 21 PRIOR TO ROUGH-IN.

PROVIDE 120V, 1Ø ELECTRICAL CONNECTION TO FLOW METER. COORDINATE EXACT LOCATION AND CONNECTION REQUIREMENTS WITH DIV 22 PRIOR TO ROUGH-IN. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE AND OPERATIONAL INSTALLATION.

TELECOMMUNICATIONS SERVICE GROUNDING BUSBAR. REFER TO DIV 27 DRAWINGS FOR ADDITIONAL INFORMATION.

PROVIDE #6 AWG TO TELECOMMUNICATIONS SERVICE GROUND BAR.

PROVIDE #3/0 GROUNDING ELECTRODE CONDUCTOR FROM UNIT SUBSTATION TO BUILDING STEEL.

PROVIDE #3/0 GROUNDING ELECTRODE CONDUCTOR FROM UNIT SUBSTATION TO WATER SERVICE.

PROVIDE UNISTRUT SUPPORT FRAMING AS REQUIRED TO SECURELY MOUNT DISCONNECTS FED FROM FLOOR. MAINTAIN REQUIRED WORKING CLEARANCES AND PROVIDE RIGID SUPPORT IN ACCORDANCE WITH NEC AND SEISMIC REQUIREMENTS.

PROVIDE GROUND BAR.

REINSTALL EXISTING LIGHTING CONTACTOR LC-1. VERIFY EQUIPMENT CONDITION PRIOR TO INSTALLATION AND PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE AND OPERATIONAL INSTALLATION. PROVIDE AUXILIARY CONTACT WITH CONNECTION TO

PHOTOCELL ON THE ROOF FOR ON/OFF CONTROL OF THE EXISTING POLE LIGHTS.

PROVIDE 120V, 1Ø ELECTRICAL CONNECTION TO CDW SYSTEM WATER TREATMENT CONTROL PANEL. COORDINATE EXACT LOCATION AND CONNECTION REQUIREMENTS WITH DIV 23 PRIOR TO ROUGH-IN. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE AND

OPERATIONAL INSTALLATION.

PROVIDE ATS ANNUNCIATOR PANEL AND CONNECT TO EXISTING ATS MONITORING IN BUILDING 47. PROVIDE ALL REQUIRED POWER, COMMUNICATION, AND CONTROL WIRING. COORDINATE EXACT WIRING REQUIREMENTS, POINT LIST, AND PROTOCOL WITH ATS

MANUFACTURER. PROVIDE 2-#10 CU, 1-#10 G CONDUCTORS.

PROVIDE 480V/3Ø TO ELECTRICAL HOIST AND DISCONNECT SWITCH. COORDINATE EXACT CONNECTION AND MOUNTING REQUIREMENTS WITH MANUFACTURER AND DIV 23. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE AND OPERATIONAL INSTALLATION.

PROVIDE 120V, 1Ø ELECTRICAL HOIST CONTROL POWER . COORDINATE EXACT CONNECTION AND MOUNTING REQUIREMENTS WITH MANUFACTURER AND DIV 23. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE AND OPERATIONAL INSTALLATION.

SCALE: NONE

ENLARGED TR ROOM2

NTS3 UNIT SUBSTATION "US-49" ELEVATION

F

FJ J

J

J

J

S

S

S

S

F

J

J

J

J

J

J

J

J

J

J

J

J

J

J

J

A

D

632 54

B

C

AHU-1-EH

AHU-2-EH

AHU-1-FS

AHU-2-FS

VFD

CT-3

VFD

CT-2

VFD

CT-1

1LEA - 20

1LEA - 20

1LEA - 20

VFD

EF-1

1H E

A

1H E

A

1HEA - 5,7,9 1HEA - 4,6,8

1HEA - 11,13,15 1HEA - 10,12,14

RF-2

1LEA2 - 1,3,5

1LEA - 22

1LEA - 21

1LEA - 31

A

D

1 32

B

C

A.4

A.6

VFD

RF-2

3 3

VFD

EF-3

1LEA - 22

1LEA - 36

1LEA - 36

1LEA - 36

1LEA - 40 10

1LEA - 40

1LEA - 40

1LEA - 41

1LEA - 41

1LEA - 41

1LEA2 - 21

1LEA2 - 21

1LEA2 - 21

1LEA2 - 21

1LEA2 - 21

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Date:Revisions:No.

A u to d e s k D o c s /M a ri o n I

L V

A

N e w E n e rg y C e n te r/

-0

-M

E P

-C e n tr a l.

rv t

/5 /2

:2

:0

P M

E101

MEZZANINE - POWER & FIRE

ALARM

05/07/2026 MSG DMB

CONSTRUCT NEW

CAMPUS CHILLER PLANT

657A5-21-401

2401 W MAIN ST, MARION IL 62959

CONTRACT

DOCUMENTS 49

MARION VA

MEDICAL

CENTER Approved: Owner

SCALE: 1/4" = 1'-0"

MEZZANINE - POWER & FIRE ALARM

GENERAL NOTES:

A. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A

SEPARATE GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR.

B. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND NORMAL BRANCH WIRING DEVICES SHALL HAVE

DIVIDERS BETWEEN DEVICES.

SITE KEY PLAN

NEW CHILLER PLANT - BLDG 49

EXISTING CHILLER PLANT - BLDG 49

37MOD-5

MOD-1

MOD-4

MOD-6

NORTH

PLAN NOTES:

1. PROVIDE 30A, 277V/1PH CONNECTION FOR POWER CONNECTION TO HEAT TRACE CONTROLLERS. PROVIDE (2) #10 CU, (1) #10 G IN 0.75" CONDUIT. COORDINATE EXACT REQUIREMENTS WITH DIV 23. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE AND OPERATIONAL

INSTALLATION.

2. PROVIDE 120V-1PH CONNECTION TO AHU LIGHT SWITCH AND RECEPTACLE. COORDINATE EXACT CONNECTION REQUIREMENTS WITH DIV

23. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE AND OPERATIONAL INSTALLATION.

3. PROVIDE 40HP VFD FOR COOLING TOWER. PROVIDE REMOTE TURN OFF, AUX CONTACT, AND ALL ASSOCIATED WIRING FROM VFD TO RESPECTIVE COOLING TOWER. COORDINATE EXACT REQUIREMENTS WITH DIV 23. PROVIDE ALL COMPONENTS REQUIRED FOR A

COMPLETE AND OPERATIONAL INSTALLATION.

4. PROVIDE 5HP VFD FOR EXHAUST FAN. PROVIDE REMOTE TURN OFF, AUX CONTACT, AND ALL ASSOCIATED WIRING FROM VFD TO RESPECTIVE EXHAUST FAN. COORDINATE EXACT REQUIREMENTS WITH DIV 23. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE

AND OPERATIONAL INSTALLATION.

5. PROVIDE 480V, 3Ø ELECTRICAL CONNECTION TO AHU ELECTRIC HEATING COIL. COORDINATE EXACT CONNECTION REQUIREMENTS WITH MANUFACTURER AND DIV 23. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE AND OPERATIONAL INSTALLATION.

6. PROVIDE 120V, 1Ø ELECTRICAL CONNECTION TO FLOW METER. COORDINATE EXACT LOCATION AND CONNECTION REQUIREMENTS WITH DIV 23 PRIOR TO ROUGH-IN. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE AND OPERATIONAL INSTALLATION.

7. PROVIDE 2HP VFD FOR RETURN FAN. COORDINATE EXACT REQUIREMENTS WITH DIV 23. PROVIDE ALL COMPONENTS REQUIRED FOR A

COMPLETE AND OPERATIONAL INSTALLATION.

8. COORDINATE EXACT LOCATION, MOUNTING, REMOTE TEST SWITCHES AND ACCESS REQUIREMENTS OF DUCT-MOUNTED SMOKE

DETECTORS WITH DIV 23 PRIOR TO ROUGH-IN.

9. PROVIDE 1.5 HP VFD FOR EXHAUST FAN. PROVIDE REMOTE TURN OFF, AUX CONTACT, AND ALL ASSOCIATED WIRING FROM VFD TO RESPECTIVE EXHAUST FAN. COORDINATE EXACT REQUIREMENTS WITH DIV 23. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE

AND OPERATIONAL INSTALLATION.

10. PROVIDE 120V, 1Ø ELECTRICAL CONNECTION TO ELECTRICAL ACTUATOR VAVLE. COORDINATE EXACT LOCATION AND CONNECTION REQUIREMENTS WITH DIV 23 PRIOR TO ROUGH-IN. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE AND OPERATIONAL

INSTALLATION.

F

WP/GF

J J J J J J

WP/GF

J

SCALE:SCALE: SCALE: SCALE: NONENONENONENONE

AIR TERMINAL DETAIL "B"AIR TERMINAL DETAIL "E"THRU-ROOF DETAIL "T"AIR TERMINAL DETAIL "C"

NO. 97 1/2" X 36" COPPER, LEAD COATED

CHIMNEY AIR TERMINAL

NO. 251L LEAD COATED COPPER LOOP

FASTENER WITH STAINLESS STEEL

SCREWS

NO. 28 COPPER

LIGHTNING CONDUCTOR

(28 X 17 AWG)

NO. 150 BRONZE

FLAT SURFACE BASE

NO. 71, 1/2" X 12" COPPER AIR TERMINAL

NO. 28 ALUMINUM

LIGHTNING CONDUCTOR

(28 X 14 AWG)

NO. 251 COPPER LOOP CABLE CLIP WITH STAINLESS

STEEL SCREW (3'-0" O.C.)

NO. 230 THRU-ROOF ASSEMBLY MOUNTED ON CONCRETE

ROOF DECK EXTENDING THROUGH INSULATION &

ROOFING MATERIALS TO 6" ABOVE FINISHED ROOF

FLASHING BY ROOFING CONTRACTOR

2" SCHEDULE 40 PVC WITH

CAP LENGTH AS REQUIRED

1/2" STAINLESS STEEL OR

BRASS THREAD ROD

NO. 28 CLASS II ALUMINUM

LIGHTNING CONDUCTOR (28 X 14

AWG)

NO. A81 5/8" X 12" ALUMINUM AIR TERMINAL

NO. A150 ALUMINUM FLAT SURFACE PLATE

NO. A37 ALUMINUM

LIGHTNING CONDUCTOR

NO. A251 ALUMINUM LOOP CABLE CLIP

NO. A217 ALUMINUM BONDING PLATE

NO. 211 BIMETAL CONNECTOR

NO. 28 COPPER

LIGHTNING CONDUCTOR

(28 X 14 AWG) NO. 28 CLASS II COPPER LIGHTNING CONDUCTOR DOWN IN

EXTERIOR WALL CONSTRUCTION TO LOWER ROOF OR GROUND

A

D

632 54

B

C

TYP.

TYP.

TYP.

1LEA - 9,11

CU-1

NEMA

3R

TYP.

EF-1

EF-2

WP

CT-1 CT-2 CT-3

BH-3BH-2BH-1

NEMA

3R

NEMA

3R

NEMA

3R

NEMA

3R

NEMA

3R

NEMA

3R

E-EQ-1HDP1 - 1

1HEA - 16,18,20

1LEA - 29

1LEA - 25

NEMA

3R

E-EQ-1HDP1 - 5 E-EQ-1HDP2 - 1

E-EQ-1HDP1 - 9 E-EQ-1HDP1 - 10 E-EQ-1HDP2 - 7

1L

EA

2 -

1L

EA

7 8

1L

EA

2 -

1L

EA

2 -

7 8 7 8

1L

EA

2 -

1L

EA

2 -

BSP-1

E-EQ-1HDP2 - 8

NEMA

3R

TYP.

CT 1

CT 2

CT 3

A

D

61 32 54

B

C

A.4

A.6

1LEA - 30,32

CU-2

NEMA

3R

10 10 10 101010

NEMA

3R

EH-1

1HEA - 23,25,27

1LEA - 25

EF-3

1HEA - 22,24,26

NEMA

3R 10

1LEA2 - 23

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Date:Revisions:No.

C :\U se rs

\d m br

\A pp D at a\

Lo ca l\A ut od es k\ R ev it\

Au to de sk

R ev it

\C ol la bo ra tio nC ac he

\L Q

C 3M

U F8

4E

LP

\5 d1 ac

3- 2a e8 -4

5-b5 5f

-c ff8

3c 3d

3a

\e e-fd

-4 d-ab

-2 dc f.r vt

5/ 5/

1:

:5

PM

E102

ROOF - POWER & FIRE ALARM

05/07/2026 MSG DMB

CONSTRUCT NEW

CAMPUS CHILLER PLANT

657A5-21-401

2401 W MAIN ST, MARION IL 62959

CONTRACT

DOCUMENTS 49

MARION VA

MEDICAL

CENTER Approved: Owner

SCALE: 1/4" = 1'-0"

ROOF - POWER & FIRE ALARM1

PLAN NOTES:

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

PROVIDE LIGHTNING PROTECTION CONDUCTOR ON ROOF.

PROVIDE LIGHTNING PROTECTION AIR TERMINAL.

PROVIDE LIGHTNING PROTECTION SYSTEM DOWN CONDUCTOR CONCEALED IN BUILDING AND GROUND ROD.

BOND LIGHTNING PROTECTION TO MECHANICAL EQUIPMENT AND DUCT WORK PENETRATING ROOF.

BOND LIGHTNING PROTECTION TO ALL PIPING PENETRATING ROOF.

PROVIDE HEAT TRACE ON ALL HOT AND COLD WATER PIPING EXPOSED TO FREEZING TEMPERATURES. COORDINATE EXACT

REQUIREMENTS WITH DIVISION 23.

PROVIDE 120V-1PH CONNECTION TO LLC WATER CONTROL PANEL ON COOLING TOWER CELL. PROVIDE INTERCONNECTION WIRE BETWEEN CONTROL PANEL AND SOLENOID VALVE AS REQUIRED. COORDINATE EXACT CONNECTION REQUIREMENTS WITH DIV 23.

PROVIDE 120V-1PH CONNECTION TO CONTROL PANEL ON COOLING TOWER CELL. PROVIDE INTERCONNECTION WIRE BETWEEN CONTROL PANEL AND SOLENOID VALVE AS REQUIRED. COORDINATE EXACT REQUIREMENTS WITH DIV 23.

PROVIDE REMOTE TURN OFF, AUX CONTACT, AND ALL ASSOCIATED WIRING FROM VFD TO RESPECTIVE MOTOR. COORDINATE EXACT

REQUIREMENTS WITH DIVISION 23.

PROVIDE UNISTRUT SUPPORT FRAMING AS REQUIRED TO SECURELY MOUNT DISCONNECTS FED FROM FLOOR. MAINTAIN REQUIRED WORKING CLEARANCES AND PROVIDE RIGID SUPPORT IN ACCORDANCE WITH NEC AND SEISMIC REQUIREMENTS.

PROVIDE 480V/3PH TO ELECTRICAL HOIST AND DISCONNECT SWITCH. COORDINATE EXACT CONNECTION REQUIREMENTS WITH MANUFACTURER AND DIV 23. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE AND OPERATIONAL INSTALLATION.

PROVIDE 120V, 1Ø ELECTRICAL HOIST CONTROL POWER . COORDINATE EXACT CONNECTION AND MOUNTING REQUIREMENTS WITH MANUFACTURER AND DIV 23. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE AND OPERATIONAL INSTALLATION.

SITE KEY PLAN

NEW CHILLER PLANT - BLDG 49

EXISTING CHILLER PLANT - BLDG 49

37MOD-5

MOD-1

49 MOD-4

MOD-6

NORTH

GENERAL NOTES:

A.

B.

EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A

SEPARATE GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR.

MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND NORMAL BRANCH WIRING DEVICES SHALL HAVE

DIVIDERS BETWEEN DEVICES.

SCALE: NONE

LIGHTNING PROTECTION DETAILS2

DM

OS

O S

OS

3 3

DM

A

D

632 54

B

C C1

C1

B1B1

B2

B2B1

B1 B1

B1B2

C1 C2C2

C1C1

C2C2

C2 C1

C2

C1

C1

C1

C1

C2

9' - 0" 9' - 0" 9' - 0"

9' - 0"

9' - 0"9' - 0"

9' - 0"

9' - 0" 9' - 0"

9' - 0"9' - 0"9' - 0"

9' - 0" 9' - 0" 9' - 0"

18' - 0"

18' - 0"

18' - 0"

18' - 0"

18' - 0"

19' - 0" 18' - 0"

17' - 0" 17' - 0"

LB2

LB1

LB1

LB2

LB2

C2 C1

C2 C1

18' - 0"

16' - 6"

18' - 0"

18' - 0"

18' - 0"

18' - 0"

18' - 0"18' - 0"

17' - 0"

16' - 0"

18' - 0"

16' - 0"

LB1

LB2

LB1

LB1

LB1

LB1LB1LB1

LB1

LB1

LB1

LB2

CONTROL

ROOM

H.A.C.

TR

ELECTRICAL

ROOM

ELECTRICAL

ROOM

C1

9' - 0"

X1 8' - 0"

WP2

10' - 0"

WP2

10' - 0"

WP2

a b a b abab

D1

EM-1

EM-1

EM-1

EM-1

1LEA 1HEA

1LLS - 5

1LLS - 3

1HEA - 1

1LLS - 4

1HEA - 1

1LLS - 4

1HEA - 1

1HEA - 1

1HEA - 1 1LLS - 4

1HEA - 1

1HEA - 1

1HEA - 1

1LLS - 4

1HEA - 1

1HEA - 1

1HEA - 1

1HEA - 1

1LLS - 5

1LLS - 5

1HEA - 1

1HEA - 1

1HEA - 2

1HEA - 21HEA - 2

1HEA - 2

1HEA - 21HEA - 2

1HEA - 2

1HEA - 2

1LLS - 3

1HEA - 2

1HEA - 21HEA - 2

1HEA - 2

1HEA - 2

1HEA - 2

1LLS - 3

1LLS - 3

1LLS - 3

1LLS - 3

1HEA - 2 1HEA - 2

1HEA - 2 1LLS - 3

1LLS - 3

1LLS - 3

1LLS - 3

1LLS - 3

1LLS - 3

1LLS - 3

1LLS - 3

1LLS - 4

1LLS - 3

WP2

1LLS - 3

1LLS - 3

1LLS - 3

1HNDP1

1LNA

T-1LNA

A

D

1 32

B

C

A.4

A.6 a b a b a b b b b b a b b bb b a a a b b a b bba b b a b a a b a b b a b a

1LLS - 5

a b a b a ba a

8' - 0"

8' - 0"

7' - 6"

B2

1LLS - 3

X1

8' - 0"

1LLS - 4

12' - 0"

LB1

1HEA - 1

b

C1

1HEA - 1

b

WM

9' - 0"

C1

1HEA - 1

b

WM

6' - 0"

1HEA - 1

C11HEA - 1 b

WM

9' - 0"

C11HEA - 1 b

C2

9' - 0"1LLS - 3

a

C1 b

WM

8' - 0"

1HEA - 1 C1 b

WM

8' - 0"

1HEA - 1

C1 b

WM

8' - 0"

1HEA - 1

C1 b

WM

8' - 0"

1HEA - 1

C1b

WM

8' - 0"

1HEA - 1

TOILET

TYP.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Date:Revisions:No.

A u to d e s k D o c s /M a ri o n I

L V

A

N e w E n e rg y C e n te r/

-0

-M

E P

-C e n tr a l.

rv t

/5 /2

:2

:1

P M

E103

FIRST FLOOR - LIGHTING

05/07/2026 MSG DMB

CONSTRUCT NEW

CAMPUS CHILLER PLANT

657A5-21-401

2401 W MAIN ST, MARION IL 62959

CONTRACT

DOCUMENTS 49

MARION VA

MEDICAL

CENTER Approved: Owner

SCALE: 1/4" = 1'-0"

FIRST FLOOR - LIGHTING

PLAN NOTES

SITE KEY PLAN

NEW CHILLER PLANT - BLDG 49

EXISTING CHILLER PLANT - BLDG 49

37MOD-5

MOD-1

MOD-4

MOD-6

NORTH

GENERAL NOTES:

A. ALL FINAL LOCATIONS AND ARRANGEMENTS OF LIGHTING FIXTURES SHALL BE OBTAINED FROM THE ARCHITECTURAL REFLECTED

CEILING PLAN.

B. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A

SEPARATE GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR.

C. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND NORMAL BRANCH WIRING DEVICES SHALL HAVE

DIVIDERS BETWEEN DEVICES.

D. RELOCATE FIXTURES AS REQUIRED TO AVOID CONFLICTS WITH EQUIPMENT, PIPING, AND OTHER TRADES. COORDINATE WITH ALL

TRADES AS REQUIRED.

1. PROVIDE UL 924 LISTED EMERGENCY LIGHTING CONTROL DEVICE FOR LIFE SAFETY LIGHTING. DEVICE SHALL AUTOMATICALLY

OVERRIDE NORMAL CONTROLS TO FULL ILLUMINATION UPON LOSS OF NORMAL POWER.

A

D

632 54

B

C

C2 C2C1

C2 C2C1C1

C2 C2C1C1

C1 C1

MEZZANINE

a b

1LLS - 2 1HEA - 3 1LLS - 2

1LLS - 21HEA - 31HEA - 31LLS - 2

1HEA - 3

1LLS - 2 1HEA - 3 1HEA - 3 1LLS - 2

1HEA - 3

A

D

61 32 54

B

C

A.4

A.6

X1

1LLS - 2

C1

C1C2

1HEA - 3

1LLS - 2 1HEA - 3

C1C1

1HEA - 31HEA - 3

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Date:Revisions:No.

A u to d e s k D o c s /M a ri o n I

L V

A

N e w E n e rg y C e n te r/

-0

-M

E P

-C e n tr a l.

rv t

/5 /2

:2

:1

P M

E104

MEZZANINE - LIGHTING

05/07/2026 MSG DMB

CONSTRUCT NEW

CAMPUS CHILLER PLANT

657A5-21-401

2401 W MAIN ST, MARION IL 62959

CONTRACT

DOCUMENTS 49

MARION VA

MEDICAL

CENTER Approved: Owner

SCALE: 1/4" = 1'-0"

MEZZANINE - LIGHTING

SITE KEY PLAN

NEW CHILLER PLANT - BLDG 49

EXISTING CHILLER PLANT - BLDG 49

37MOD-5

MOD-1

MOD-4

MOD-6

NORTH

GENERAL NOTES:

A. ALL FINAL LOCATIONS AND ARRANGEMENTS OF LIGHTING FIXTURES SHALL BE OBTAINED FROM THE ARCHITECTURAL REFLECTED

CEILING PLAN.

B. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A

SEPARATE GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR.

C. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND NORMAL BRANCH WIRING DEVICES SHALL HAVE

DIVIDERS BETWEEN DEVICES.

D. RELOCATE FIXTURES AS REQUIRED TO AVOID CONFLICTS WITH EQUIPMENT, PIPING, AND OTHER TRADES. COORDINATE WITH ALL

TRADES AS REQUIRED.

PLAN NOTES

1. LIGHT FIXTURES IN THIS AREA SHOWN ON FIRST FLOOR LIGHTING PLAN.

2. MOUNT LIGHT FIXTURES FROM STRUCTURAL BEAM. PROVIDE APPROPRIATE SUPPORTS AND HARDWARE FOR A COMPLETE

INSTALLATION.

PCPC

A

D

632 54

B

C

WP1

WP1

WP1

WP1

9' - 0"

9' - 0"

9' - 0"

9' - 0"

WP1

9' - 0"

WP1

9' - 0"

WP1

9' - 0"

1HEA - 21

1HEA - 21

1HEA - 21

1HEA - 21

1HEA - 211HEA - 21

1HEA - 21

A

D

1 32

B

C

A.4

A.6

X2

1LLS - 2

1HNDP1 - 28 1HNDP1 - 28

WP1

9' - 0"

1HEA - 21

WP1

18' - 0"

1HEA - 21

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Date:Revisions:No.

A u to d e s k D o c s /M a ri o n I

L V

A

N e w E n e rg y C e n te r/

-0

-M

E P

-C e n tr a l.

rv t

/5 /2

:2

:1

P M

E105

ROOF - LIGHTING

05/07/2026 MSG DMB

CONSTRUCT NEW

CAMPUS CHILLER PLANT

657A5-21-401

2401 W MAIN ST, MARION IL 62959

CONTRACT

DOCUMENTS 49

MARION VA

MEDICAL

CENTER Approved: Owner

SCALE: 1/4" = 1'-0"

ROOF - LIGHTING

PLAN NOTES

SITE KEY PLAN

NEW CHILLER PLANT - BLDG 49

EXISTING CHILLER PLANT - BLDG 49

37MOD-5

MOD-1

MOD-4

MOD-6

NORTH

GENERAL NOTES:

A. ALL FINAL LOCATIONS AND ARRANGEMENTS OF LIGHTING FIXTURES SHALL BE OBTAINED FROM THE ARCHITECTURAL REFLECTED

CEILING PLAN.

B. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A

SEPARATE GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR.

C. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND NORMAL BRANCH WIRING DEVICES SHALL HAVE

DIVIDERS BETWEEN DEVICES.

1. PROVIDE SPRING WOUND TIMER TO CONTROL WP1 ROOF FIXTURES.

2. PROVIDE SPECIFICATION GRADE 277V PHOTOCELL ON ROOF FOR SITE LIGHTING CONTROL. CONNECT TO

LIGHTING CONTROL PANEL AND LIGHTING CONTACTOR.

3. SURFACE MOUNTED LIGHTING. COORDINATE CONDUIT ROUTING PRIOR TO ROUGH-IN.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Date:Revisions:No.

A u to d e s k D o c s /M a ri o n I

L V

A

N e w E n e rg y C e n te r/

-0

-M

E P

-C e n tr a l.

rv t

/5 /2

:2

:1

P M

E500

ELECTRICAL SCHEDULES

05/07/2026 MSG DMB

CONSTRUCT NEW

CAMPUS CHILLER PLANT

657A5-21-401

2401 W MAIN ST, MARION IL 62959

CONTRACT

DOCUMENTS 49

MARION VA

MEDICAL

CENTER Approved: Owner

NOTES:

1. REFER TO SINGLE LINE FOR WIRE SIZING.

2. POWER FOR THE INDOOR UNIT IS FED THROUGH THE OUTDOOR UNIT.

PROVIDE INTERCONNECTING WIRE AS REQUIRED FOR A COMPLETE AND

OPERATION INSTALLATION.

3.PROVIDE MOTOR STARTER SUITABLE FOR 50 HP MOTOR, WITH OVERLOAD

PROTECTION. STARTER SHALL BE ACROSS-THE-LINE UNLESS OTHERWISE

INDICATED. PROVIDE SOFT STARTER WHERE REQUIRED TO LIMIT INRUSH

CURRENT.

MOTORS, STARTERS, DISCONNECTS & CONTROLS

MARK

MOTOR STARTER DISCONNECT MEANS CONTROL FEEDER

S E

E N

O T

E

NAMEPLATE

CHARACTERISTICS LOCATION

N E

M A

S

IZ

E

TYPE LOCATION

F U

R N

IS

H

E D

B Y

TYPE LOCATION

F U

R N

IS

H

E D

B Y

I N

T E

R L O

C K

W

IT

H M

O T

O R

N O

B

Y E

.C

M A

N U

A L A

T S

T A

R T

E R

I N

T E

G R

A L

W

IT

H E

Q U

IP

M

E N

T

F U

R N

IS

H

E D

B Y

S E

E N

O T

E

N U

M B

E R

O F

C O

N D

U C

T O

R S

W

IR

E S

IZ

E

G R

O U

N D

S

IZ

E

C O

N D

U

IT

S

IZ

E

H O

R S

E P

O W

E R

H

P

L O

A D k V

A

V

-1 P

H

V

-1 P

H

V

-3 P

H

V

-1 P

H

V

-3 P

H

V

-1 P

H

V

-1 P

H

V

-3 P

H

R O

O M

N U

M B

E R

ROOM NAME M

A

N U

A L

M A

G N

E T

IC

E C

M

E Q

U

IP

M E

N T

C O

N T

R O

L P

A N

E L

V F

D

S E

E N

O T

E

N E

A R

M O

T O

R

M O

T O

R C

O N

T C

E N

T E

R

E Q

U

IP

C O

N T

P A

N E

L

R O

O M

N U

M B

E R

S E

E N

O T

E

D

IS

C S

W

IT

C H

M A

N U

A L S

T A

R T

E R

R E

C E

P T

A C

L E

F E

E D

E R

S W

O R

B R

E A

K E

R

N E

M A

T Y

P E

D

IS

C S

IZ

E

F U

S E

S

IZ

E

N E

A R

M O

T O

R

M O

T O

R C

O N

T C

E N

T E

R

E Q

U

IP

C O

N T

P A

N E

L

P A

N E

L B

O A

R D

S E

E N

O T

E

AC-1 AIR CONDITIONING UNIT 0.5 0.1 ● ● ● DIV 23 ● 1 30 NF ● DIV 26 ● DIV 23 - - - - 2

AC-2 AIR CONDITIONING UNIT 0.5 0.1 ● ● ● DIV 23 ● 1 30 NF ● DIV 26 ● DIV 23 - - - - 2

CU-1 CONDENSING UNIT 18 FLA 3.83 ● ROOF ● ● DIV 23 ● 3R 30 NF ● DIV 26 ● DIV 23 2 10 10 0.75"

CU-2 CONDENSING UNIT 18 FLA 3.83 ● ROOF ● ● DIV 23 ● 3R 30 NF ● DIV 26 ● DIV 23 2 10 10 0.75"

AHU-1-EH ELECTRIC HEATING COIL 37.56 ● 200 MEZZANINE DIV 23 ● 1 60 60 ● DIV 26 ● DIV 23 3 4 10 1.25"

AHU-1-FS AIR HANDLER FANS (4) 6 14.3 ● 200 MEZZANINE ● ● DIV 23 ● - - - ● DIV 26 ● DIV 23 3 12 12 0.75"

AHU-2-EH ELECTRIC HEATING COIL 10.43 ● 200 MEZZANINE DIV 23 ● 1 30 20 ● DIV 26 ● DIV 23 3 12 12 0.75"

AHU-2-FS AIR HANDLER FANS (2) 6 6.98 ● 200 MEZZANINE ● ● DIV 23 ● - - - ● DIV 26 ● DIV 23 3 12 12 0.75"

BSP-1 BASIN SWEEPER PUMP 3 13.58 ● ROOF ● ● DIV 23 ● 3R 60 NF ● DIV 26 ● DIV 23 - - - - 1

CDWF-1 MEDIA FILTER PUMP 20 37.69 ● 100 CHILLER PLANT ● ● DIV 23 ● 1 100 NF ● DIV 26 ● DIV 23 - - - - 1

CH-1 CHILLER 356.66 ● 100 CHILLER PLANT ● ● MFG ● - - - ● MFG ● DIV 23 - - - - 1

CH-2 CHILLER 356.66 ● 100 CHILLER PLANT ● ● MFG ● - - - ● MFG ● DIV 23 - - - - 1

CH-3 CHILLER 0 ● 100 CHILLER PLANT ● ● MFG ● - - - ● MFG ● DIV 23 - - - - 1

CDWP-1 CONDENSER WATER PUMP 50 54.04 ● 100 CHILLER PLANT 3 ● ● 3 DIV 26 ● 1 100 NF ● 3 DIV 26 ● DIV 23 - - - - 1

CDWP-2 CONDENSER WATER PUMP 50 0 ● 100 CHILLER PLANT 3 ● ● 3 DIV 26 ● 1 100 NF ● 3 DIV 26 ● DIV 23 - - - - 1

CDWP-3 CONDENSER WATER PUMP 50 54.04 ● 100 CHILLER PLANT 3 ● ● 3 DIV 26 ● 1 100 NF ● 3 DIV 26 ● DIV 23 - - - - 1

BH-1 BASIN HEATER 28.9 FLA 24.03 ● ROOF ● ● DIV 23 ● 3R 60 NF ● DIV 26 ● DIV 23 - - - - 1

BH-2 BASIN HEATER 28.9 FLA 0 ● ROOF ● ● DIV 23 ● 3R 60 NF ● DIV 26 ● DIV 23 - - - - 1

BH-3 BASIN HEATER 28.9 FLA 24.03 ● ROOF ● ● DIV 23 ● 3R 60 NF ● DIV 26 ● DIV 23 - - - - 1

CT-1 COOLING TOWER 40 43.23 ● ROOF ● DIV 26 ● 3R 100 NF ● DIV 26 ● DIV 23 - - - - 1

CT-2 COOLING TOWER 40 0 ● ROOF ● DIV 26 ● 3R 100 NF ● DIV 26 ● DIV 23 - - - - 1

CT-3 COOLING TOWER 40 43.23 ● ROOF ● DIV 26 ● 3R 100 NF ● DIV 26 ● DIV 23 - - - - 1

EF-1 EXHAUST FAN 5 6.32 ● ROOF ● ● DIV 26 ● 3R 30 NF ● DIV 23 ● DIV 23 3 12 12 0.75"

EF-2 EXHAUST FAN .5 1.18 ● ROOF ● ● DIV 23 ● - - - ● MFG ● DIV 23 2 12 12 0.75"

EF-3 EXHAUST FAN 1.5 2.49 ● ROOF ● ● DIV 26 ● 3R 30 NF ● DIV 23 ● DIV 23 3 12 12 0.75"

EH-1 ELECTRICAL HOIST 5 6.32 ● ROOF DIV 23 ● 3R 30 NF ● DIV 26 ● DIV 23 3 10 10 0.75"

EH-2 ELECTRICAL HOIST 5 6.32 ● ROOF DIV 23 ● 1 30 NF ● DIV 26 ● DIV 23 3 10 10 0.75"

PCHWP-1 PRI CHILLED WATER PUMP 20 17.46 ● 100 CHILLER PLANT ● ● DIV 26 ● 1 60 NF ● DIV 26 ● DIV 23 - - - - 1

PCHWP-2 PRI CHILLED WATER PUMP 20 0 ● 100 CHILLER PLANT ● ● DIV 26 ● 1 60 NF ● DIV 26 ● DIV 23 - - - - 1

PCHWP-3 PRI CHILLED WATER PUMP 20 17.46 ● 100 CHILLER PLANT ● ● DIV 26 ● 1 60 NF ● DIV 26 ● DIV 23 - - - - 1

RF-2 RETURN FAN 2 2.49 ● 200 MEZZANINE ● ● DIV 23 ● - - - ● DIV 26 ● DIV 23 3 12 12 0.75"

SCHWP-1 SEC CHILLED WATER PUMP 60 64.02 ● 100 CHILLER PLANT ● ● DIV 26 ● 1 200 NF ● DIV 26 ● DIV 23 - - - - 1

SCHWP-2 SEC CHILLED WATER PUMP 60 0 ● 100 CHILLER PLANT ● ● DIV 26 ● 1 200 NF ● DIV 26 ● DIV 23 - - - - 1

SCHWP-3 SEC CHILLED WATER PUMP 60 64.02 ● 100 CHILLER PLANT ● ● DIV 26 ● 1 200 NF ● DIV 26 ● DIV 23 - - - - 1

SP-1A SUMP PUMP 0.5 2.16 ● 100 CHILLER PLANT ● ● MFG ● - - - ● MFG ● DIV 22 3 12 12 0.75"

SP-1B SUMP PUMP 0.5 2.16 ● 100 CHILLER PLANT ● ● MFG ● - - - ● MFG ● DIV 22 3 12 12 0.75"

UH-1 UNIT HEATER 7.5 ● 100 CHILLER PLANT ● ● MFG ● - - - ● DIV 26 ● DIV 23 3 12 12 0.75"

UH-2 UNIT HEATER 7.5 ● 100 CHILLER PLANT ● ● MFG ● - - - ● DIV 26 ● DIV 23 3 12 12 0.75"

UH-3 UNIT HEATER 7.5 ● ● ● MFG ● - - - ● DIV 26 ● DIV 23 3 12 12 0.75"

UH-4 UNIT HEATER 7.5 ● 100 CHILLER PLANT ● ● MFG ● - - - ● DIV 26 ● DIV 23 3 12 12 0.75"

UH-5 UNIT HEATER 2 ● 104 TOILET ● ● MFG ● ● MFG ● DIV 23 2 12 12 0.75"

VAV-1 VAV BOX 6 ● 106 ELECTRICAL ROOM ● ● DIV 23 ● 1 30 NF ● DIV 26 ● DIV 23 3 12 12 0.75"

VAV-2 VAV BOX 7.48 ● 105 ELECTRICAL ROOM ● ● DIV 23 ● 1 30 NF ● DIV 26 ● DIV 23 3 12 12 0.75"

VAV-3 VAV BOX 1 ● 101 CONTROL ROOM ● ● DIV 23 ● 1 30 NF ● DIV 26 ● DIV 23 2 12 12 0.75"

DWH-1 WATER HEATER 4.49 ● 103 H.A.C. DIV 22 ● 1 30 NF ● DIV 26 ● DIV 22 2 10 10 0.75"

356.66

54.04

24.03

43.23

17.46

64.02

CCT.

NO.

FIXTURES TYPE(S)

CONTROLLED

*INDICATES SPARE FOR

FUTURE USE

* A.

B.

C.

LEAVE SLACK IN ALL CONDUCTORS SUCH THAT THEY MAY

BE MOVED FROM ONE RELAY TO ANOTHER AS REQUIRED.

EXTERIOR LIGHTING TO BE AUTOMATICALLY CONTROLLED

BY TIME-OF-DAY SCHEDULE AND PHOTOCELL. OPERATION

INTENT IS FOR LIGHT POLES COME ON AT DUSK AND TURN

OFF AT DAWN. ALSO FOR TIME-OF-DAY CONTROL TO DIM TO

50% AT MIDNIGHT UNTIL 6AM. INTEGRAL LIGHT POLE MOTION

SENSORS TO DIM THE POLE LIGHTS WHEN NO MOTION IS

DETECTED IN THE PARKING LOT AREA. REFER TO LIGHTING

CONTROL DETAILS AND SEQUENCE OF OPERATION

SCHEDULE FOR ADDITIONAL OPERATION INFORMATION.

DEVICES SHALL BE CONNECTED AND WIRED PER

MANUFACTURERS RECOMMENDATIONS AND WIRING

INSTRUCTIONS. PROVIDE ALL RELAYS, POWER PACKS,

SENSORS, AND MISCELLANEOUS DEVICES FOR A COMPLETE

AND OPERABLE SYSTEM.

GENERAL NOTES

NEW SITE LTG (PL1,PL2)

LCP-1

LCP-1 - 1

PHOTOCELL

(EXTERIOR)

LV

1.

2.

LIGHTING CONTROL RELAY(S) IN A NEMA 1 ENCLOSURE BY

E.C. ELECTRONIC LIGHTING CONTROLLER FOR CONTROL OF

LIGHTING CIRCUITS AS INDICATED. PROVIDE QUANTITY OF

RELAYS AS INDICATED.

EQUAL BY HUBBELL, LEVITON, SQUARE-D, NLIGHT,

CRESTRON OR LC&D.

DETAIL NOTES

1 2

1.

2.

3.

4.

5.

6.

7.

8.

9.

10.

11.

12.

13.

SEE FIXTURE SCHEDULE FOR POLE AND FIXTURE ASSEMBLY.

ANCHOR BOLTS BY POLE SUPPLIER, CONNECT TO REBAR VIA

WIRE TIES.

CHAMFERED EDGE.

FINISH GRADE, COMPACT TO 95%.

SIX #4 REINFORCING BARS VERTICALLY ON #3 STIRRUPS AT

18" O.C.

PVC CONDUIT, SCHEDULE 40.

RIGID GALVANIZED STEEL CONDUIT.

GROUND ROD.

1/2" PVC GROUND CONDUCTOR SLEEVE WITH #8 GROUND

CONDUCTOR.

BASE PLATE, LEVELING NUTS, BASE GROUT.

EXOTHERMICALLY WELDED GROUND CONNECTION.

LIGHTNING ARRESTOR.

HANDHOLE.

DETAIL NOTES

2'- 6" 1'-

6" 2" .

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Date:Revisions:No.

C :\U se rs

\d m br

\A pp D at a\

Lo ca l\A ut od es k\ R ev it\

Au to de sk

R ev it

\C ol la bo ra tio nC ac he

\L Q

C 3M

U F8

4E

LP

\5 d1 ac

3- 2a e8 -4

5-b5 5f

-c ff8

3c 3d

3a

\e e-fd

-4 d-ab

-2 dc f.r vt

5/

/2

4:

:4

PM

E600

ELECTRICAL SCHEDULES

05/07/2026 MSG DMB

CONSTRUCT NEW

CAMPUS CHILLER PLANT

657A5-21-401

2401 W MAIN ST, MARION IL 62959

CONTRACT

DOCUMENTS 49

MARION VA

MEDICAL

CENTER Approved: Owner

NOTES:

1.

LUMINAIRES

MARK IMAGE

LAMPS

L O

AD

(V

A)

F

IX

TU

R

E

VO

LT

AG

E

Manufacturer CATALOG NO. DESCRIPTION

TRIM COLOR MOUNTING SIZE

S

EE

N O

TE

D

EL

IV

ER

ED

L

U M

EN

S

COLOR W

H

IT

E

B

LA

C K

A

LU

M

IN

U M

B R

O N

ZE

S

TA

N D

AR

D

S

EE

N O

TE

S-SURFACE

R-RECESSED

SM-STEM MTD

WM-WALL MTD

C-CHAIN MTD

UC-UNDER CAB

CS-CEIL SURFACE D

IA

M

ET

ER

W

ID

TH

L

EN

G

TH

D

EP

TH

B1 2000 4000K 15 277 LITHONIA OR EQUAL CPX-2X2-2000LM-80CRI-40K-SWL-MIN1-ZT-MVOLT 2X2 LED FLAT PANEL R 24" 24" 6"

B2 2000 4000K 15 120 LITHONIA OR EQUAL CPX-2X2-2000LM-80CRI-40K-SWL-MIN1-ZT-MVOLT 2X2 LED FLAT PANEL R 24" 24" 6"

C1 4000 4000K 25 277 LITHONIA OR EQUAL CLX-L48-4000LM-SEF-FDL-WD-MVOLT-GZ1-40K-80CRI-WH 1X4 LED INDUSTRIAL STRIP <V

AR

IE

S>

<V

AR

IE

S>

<V

AR

IE

S>

<V

AR

IE

S>

<V

AR

IE

S>

C/WM <VARI

ES>

<VARIE

S>

4"

C2 4000 4000K 25 120 LITHONIA OR EQUAL CLX-L48-4000LM-SEF-FDL-WD-MVOLT-GZ1-40K-80CRI-WH 1X4 LED INDUSTRIAL STRIP ● C/WM 4" 48" 4"

D1 1400 4000K 28 120 FINELITE OR EQUAL S17 LED-WM-VCF-PF-4'-B-840-96-277-FC-10%-SW VANITY OVER SINK S 6" 24" 3"

EM-1 1 120 LITHONIA OR EQUAL EU2C M6 EMERGENCY LIGHT S 5.375" 13" 5.75"

LB1 15000 4000K 100 277 LITHONIA OR EQUAL MLX-L8-15000LM-80CRI-40K-WGDL-MD-MIN10-ZT-MVOLT-WH LED LOW BAY FIXTURE ● C 12" 96" 5.5"

LB2 15000 4000K 100 120 LITHONIA OR EQUAL MLX-L8-15000LM-80CRI-40K-WGDL-MD-MIN10-ZT-MVOLT-WH LED LOW BAY FIXTURE ● C 12" 96" 5.5"

PL1 11296 4000K 93 277 LITHONIA OR EQUAL DSXO LED P4 40K 70CRIT4M XVOLT RPA PIR DMG EGSR DDBXD 20' LED POLE FIXTURE WITH TYPE 4 DISTRIBUTION POLE 12" 17.125" 6" 1

PL2 11296 4000K 93 277 LITHONIA OR EQUAL DSXO LED P4 40K 70CRIT4M XVOLT RPA PIR DMG EGSR DDBXD 20' LED TWO-HEAD POLE FIXTURE WITH TYPE 4 DISTRIBUTION POLE 12" 17.125" 6" 1

PL3 11296 4000K 93 480 LITHONIA OR EQUAL DSXO LED P4 40K 70CRIT4M XVOLT RPA PIR DMG EGSR DDBXD 20' LED TWO-HEAD POLE FIXTURE WITH TYPE 4 DISTRIBUTION POLE 12" 17.125" 6" 1

PL4 11296 4000K 93 480 LITHONIA OR EQUAL DSXO LED P4 40K 70CRIT4M XVOLT RPA PIR DMG EGSR DDBXD 20' LED POLE FIXTURE WITH TYPE 4 DISTRIBUTION POLE 12" 17.125" 6" 1

WP1 4500 4000K 35 277 LITHONIA OR EQUAL WDGE2 LED-P2-40K -70CRI-R4-MVOLT-SRM-PE-DMG-PIR1FC3V-DDBXD LED EXTERIOR WALL PACK ● WM 9" 13.5"

WP2 14000 4000K 106 120 LITHONIA OR EQUAL WDGE4 LED-P2-40K -70CRI-R4-MVOLT-SRM-PE-DMG-PIR1FC3V-DDBXD LED EXTERIOR WALL PACK ● WM 9" 13.5"

X1 5 120 LITHONIA OR EQUAL LED DIE CAST EXIT SIGN ● WM/CS 9" 13" 2.375"

X2 5 120 LITHONIA OR EQUAL LED EXTERIOR EXIT SIGN ● WM 9" 13" 2.375"

NOTES:

1.

LIGHTING CONTROL SEQUENCE OF OPERATIONS

CONTROL

NUMBER TYPICAL CONTROL TYPE OR SPACE NAME

OCCUPANCY SENSOR TIME CLOCK WALL SWITCH DAYLIGHT SENSOR INTEGRATION POINTS

S

EE

N O

TE

DETAIL

NUMBER V

AC

AN

C Y

M O

D E

(M

AN

U

AL

O N

O C

C U

PA

N

C Y

M O

D E

(A U

TO

O

N

S

EN

SO

R

T

IM

E O

U T

PE

R

IO

D

(I N

M

IN

U

TE

S)

H

IG

H

LO

W

O

PE

R

AT

IO

N

: O C

C U

PI

ED

: 1

VA

C

AN

T:

0%

S C

H

ED

U

LE

D O

N A

T

S C

H

ED

U

LE

D O

FF

A

T

O C

C U

PI

ED

T

IM

E

ST

AR

T

U N

O C

C U

PI

ED

T

IM

E

ST

AR

T

A

FT

ER

H

O U

R S

O

VE

R R

ID

E

SW

IT

C H

(2 H

O U

R S)

O N

O

FF

O

N

LY

D

IM

M

ER

S W

IT

C

H

K

EY

S W

IT

C

H

S C

EN

E

SW

IT

C H

G R

AP

H

IC

AL

W

AL

L

ST

AT

IO

N

IN

D

O O

R

O N

O

FF

O

N

LY

IN

D

O O

R

D

IM

M

IN

G

L

IG

H T

LE

VE

L M

AI

N

TA

IN

ED

A

T

(IN

F O

O

TC

AN

D

LE

S

'-6 " A

.F .F

E

XT

ER

IO

R P

H O

TO

C

EL

L

- O N

O

FF

O C

C U

PA

N

C Y

ST

AT

U S

(B

IN

AR

Y

IN

PU

T

- R

EA

D

O N

LY

O C

C U

PI

ED

U

N O

C C

U

PI

ED

D

IM

M

IN

G O

U

TP

U T

LE

VE

L (A

N

AL

O G

V

AL

U E

- R

EA

D

W R

IT

E

- 0 -1

R

EL

AY

S

TA

TU

S (B

IN

AR

Y

VA

LU

E

- R

EA

D

W R

IT

E

- O N

O

FF

M

EA

SU

R

ED

L

IG

H

T

LE

VE

L

(A N

AL

O

G

IN

PU

T

- 0 -2

FC

1 ON/OFF ● N/A

2 DIMMER ●

3 VACANCY SENSING - SINGLE ZONE ● 15 ●

4 OCCCANCY SENSING - SINGLE ZONE ● 15 ● YES 25% YES

6 SITE LIGHTING ● 30 DUSK DAWN 50% YES 1

SCALE: NONE

EXTERIOR AUTOMATIC LIGHTING CONTROLS1

SCALE: NONE

PL1, PL2, & PL3 POLE BASE DETIAL2

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Date:Revisions:No.

C :\U se rs

\d m br

\A pp D at a\

Lo ca l\A ut od es k\ R ev it\

Au to de sk

R ev it

\C ol la bo ra tio nC ac he

\L Q

C 3M

U F8

4E

LP

\5 d1 ac

3- 2a e8 -4

5-b5 5f

-c ff8

3c 3d

3a

\e e-fd

-4 d-ab

-2 dc f.r vt

5/ 5/

1:

:5

PM

E601

PANEL SCHEDULES

05/07/2026 MSG DMB

CONSTRUCT NEW

CAMPUS CHILLER PLANT

657A5-21-401

2401 W MAIN ST, MARION IL 62959

CONTRACT

DOCUMENTS 49

MARION VA

MEDICAL

CENTER Approved: Owner

98.26 kVA 107.65 kVA (129 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes:

Special Circuit Breaker (SCB) Types: GF=GFCI Breaker, ST=Shunt Trip Breaker, AF=AFCI Breaker, GP=GFPE Breaker

Total Est. Demand: 129 A Total Conn.: 118 A

Resistive Heat 5,000 VA 100.00% 5,000 VA Total Est. Demand: 107.65 kVA Motor 90,729 VA 110.35% 100,119 VA Total Conn. Load: 98.26 kVA Lighting 2,530 VA 100.00% 2,530 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Load: 34.68 kVA 30.83 kVA 32.74 kVA 41 Spare 20 A 1 0 0 1 20 A Spare 42 39 Spare 20 A 1 0 0 1 20 A Spare 40 37 Spare 20 A 1 0 0 1 20 A Spare 38 35 Spare 20 A 1 0 0 1 20 A Spare 36 33 Spare 20 A 1 0 0 1 20 A Spare 34 31 Spare 20 A 1 0 2.106 -- -- -- -- 32 29 Spare 20 A 1 0 2.106 -- -- -- -- 30

27 -- -- -- -- 2.106 2.106 3 20 A EH-2 28

25 -- -- -- -- 2.106 0.831 -- -- -- -- 26

23 EH-1 20 A 3 2.106 0.831 -- -- -- -- 24

21 Lighting 20 A 1 0.315 0.831 3 15 A EF-3 22

19 HEAT TRACE GP 30 A 1 2.5 2.106 -- -- -- -- 20

17 HEAT TRACE GP 30 A 1 2.5 2.106 -- -- -- -- 18

15 -- -- -- -- 3.478 2.106 3 20 A EF-1 16

13 -- -- -- -- 3.478 2.328 -- -- -- -- 14

11 AHU-2-EH 20 A 3 3.478 2.328 -- -- -- -- 12

9 -- -- -- -- 12.521 2.328 3 15 A AHU-2-FS 10

7 -- -- -- -- 12.521 4.767 -- -- -- -- 8

5 AHU-1-EH 60 A 3 12.521 4.767 -- -- -- -- 6

3 LGT ELECTRICAL... 20 A 1 0.275 4.767 3 20 A AHU-1-FS 4

1 LGT CHILLER PLANT... 20 A 1 1.575 0.365 1 20 A LGT CONTROL ROOM... 2

CKT Circuit Description

SCB

Type Trip Poles

A B C Poles Trip

SCB

Type Circuit Description CKT

Voltage: 480Y/277V-3PH-4W Mains Rating: 250 A Supply From: E-EQ-1HDP2 Enclosure: Type 1 Mains Type: MLO

Location: ELECTRICAL ROOM 105 Mounting: Surface A.I.C. Rating: 42KAIC Panel: 1HEA Construction Phase:

202.77 kVA 218.78 kVA (263 A)

TOTAL CONNECTED ESTIMATED DEMAND

NOTES: 1. REFER TO SINGLE LINE FOR OVER CURRENT PROTECTION AND WIRE SIZE INFROMATION.

2. NON-TYPICAL N+1 LOAD SHALL ONLY BE ENERGIZED WHEN THE CORRESPONDING PRIMARY EQUIPMENT IS NOT

ENERGIZED.

Total Est. Demand: 263 A Total Conn.: 244 A

Total Est. Demand: 218.78 kVA Total Conn. Load: 202.77 kVA

Motor 202,775 VA 107.89% 218,779 VA Load Classification Connected... Demand Factor Estimated... Panel Totals 13 Spare 0.00 kVA 200 A 3 200 A LSI 12 Spare 0.00 kVA 200 A 3 200 A LSI 11 SPD 0.00 kVA 60 A 3 60 A TM - - - - 1 10 BH-2 0.00 kVA 40 A 3 40 A TM - - - - 1 9 BH-1 24.03 kVA 40 A 3 40 A TM - - - - 1 8 CDWP-2 0.00 kVA 150 A 3 100 A LSI - - - - 1,2 7 SCHWP-2 0.00 kVA 150 A 3 125 A LSI - - - - 1,2 6 PCHWP-2 0.00 kVA 100 A 3 60 A LSI - - - - 1,2 5 CT-2 0.00 kVA 100 A 3 90 A LSI - - - - 1,2 4 CDWP-1 54.04 kVA 150 A 3 100 A LSI - - - - 1 3 SCHWP-1 64.02 kVA 150 A 3 125 A LSI - - - - - 2 PCHWP-1 17.46 kVA 100 A 3 60 A LSI - - - - 1 1 CT-1 43.23 kVA 100 A 3 90 A LSI - - - - 1

CKT

CIRCUIT

DESCRIPTION

APPROX.

CONNECTED

LOAD

FRAME

SIZE POLES

TRIP

SETTING

BREAKER

TYPE

NUMBER OF

CONDUCTORS

WIRE

SIZE

GROUND

SIZE

CONDUIT

SIZE

SEE

NOTE

Feeder Size: REFER TO SINGLE LINE Spec. Ref. #: 26 24 16 Voltage: 480Y/277V-3PH-4W Mains Rating: 600 A

Supply From: EQ-ATS-2 Enclosure: Type 1 Mains Type: MLO Location: ELECTRICAL ROOM 105 Mounting: Surface A.I.C. Rating: REFER TO SINGLE LINE

DISTRIBUTION PANEL:E-EQ-1HDP1

390.27 kVA 406.27 kVA (489 A)

TOTAL CONNECTED ESTIMATED DEMAND

NOTES: 1. REFER TO SINGLE LINE FOR WIRE SIZING.

Resistive Heat 5,000 VA 100.00% 5,000 VA Receptacle 8,460 VA 100.00% 8,460 VA Total Est. Demand: 489 A Power 18,088 VA 100.00% 18,088 VA Total Conn.: 469 A Motor 356,187 VA 104.49% 372,191 VA Total Est. Demand: 406.27 kVA Lighting 2,530 VA 100.00% 2,530 VA Total Conn. Load: 390.27 kVA Equipment 0 VA 0.00% 0 VA Load Classification Connected... Demand Factor Estimated... Panel Totals 12 Spare 0.00 kVA 400 A 1 20 A 11 Spare 0.00 kVA 400 A 1 20 A 10 SPD 0.00 kVA 400 A 1 60 A 9 CDWF-1 37.69 kVA 100 A 3 80 A LSI - - - - 1 8 BSP-1 13.58 kVA 40 A 3 40 A TM - - - - 1 7 BH-3 24.03 kVA 40 A 3 40 A TM - - - - 1 6 T-1LEA 37.97 kVA 125 A 3 125 A TM - - - - 1 5 1HEA 98.26 kVA 250 A 3 250 A 100% - - - - 1 4 CDWP-3 54.04 kVA 150 A 3 100 A LSI - - - - 1 3 SCHWP-3 64.02 kVA 150 A 3 125 A LSI - - - - 1 2 PCHWP-3 17.46 kVA 100 A 3 60 A LSI - - - - 1 1 CT-3 43.23 kVA 100 A 3 90 A LSI - - - - 1

CKT

CIRCUIT

DESCRIPTION

APPROX.

CONNECTED

LOAD

FRAME

SIZE POLES

TRIP

SETTING

BREAKER

TYPE

NUMBER OF

CONDUCTORS

WIRE

SIZE

GROUND

SIZE

CONDUIT

SIZE

SEE

NOTE

Feeder Size: REFER TO SINGLE LINE Spec. Ref. #: 26 24 16 Voltage: 480Y/277V-3PH-4W Mains Rating: 600 A

Supply From: EQ-ATS-5 Enclosure: Type 1 Mains Type: MLO Location: ELECTRICAL ROOM 105 Mounting: Surface A.I.C. Rating: REFER TO SINGLE LINE

DISTRIBUTION PANEL:E-EQ-1HDP2

713.33 kVA 713.33 kVA (858 A)

TOTAL CONNECTED ESTIMATED DEMAND

NOTES: 1. REFER TO SINGLE LINE FOR WIRE INFORMATION.

2. NON-TYPICAL N+1 LOAD SHALL ONLY BE ENERGIZED WHEN THE CORRESPONDING PRIMARY EQUIPMENT IS NOT

ENERGIZED.

Total Est. Demand: 858 A Total Conn.: 858 A

Total Est. Demand: 713.33 kVA Total Conn. Load: 713.33 kVA

HVAC 713,328 VA 100.00% 713,328 VA

Load Classification Connected... Demand Factor Estimated... Panel Totals 4 SPD 0.00 kVA 400 A 1 60 A TM 3 EQ-ATS-4 0.00 kVA 800 A 3 800 A LSIA 1,2 2 EQ-ATS-3 356.66 kVA 800 A 3 800 A LSIA 1 1 EQ-ATS-1 356.66 kVA 800 A 3 800 A LSIA 1

CKT

CIRCUIT

DESCRIPTION

APPROX.

CONNECTED

LOAD

FRAME

SIZE POLES

TRIP

SETTING

BREAKER

TYPE

NUMBER OF

CONDUCTORS

WIRE

SIZE

GROUND

SIZE

CONDUIT

SIZE

SEE

NOTE

Feeder Size: REFER TO SINGLE LINE Spec. Ref. #: 26 24 16 Voltage: 480Y/277V-3PH-4W Mains Rating: 1200 A

Supply From: Enclosure: Type 1 Mains Type: MLO Location: ELECTRICAL ROOM 105 Mounting: Surface A.I.C. Rating: REFER TO SINGLE LINE

DISTRIBUTION PANEL:GP-1HDP1

593.04 kVA 609.04 kVA (733 A)

TOTAL CONNECTED ESTIMATED DEMAND

NOTES: 1. REFER TO SINGLE LINE FOR WIRE INFORMATION.

2. NON-TYPICAL N+1 LOAD SHALL ONLY BE ENERGIZED WHEN THE CORRESPONDING PRIMARY EQUIPMENT IS NOT

ENERGIZED.

Resistive Heat 5,000 VA 100.00% 5,000 VA Receptacle 8,460 VA 100.00% 8,460 VA Total Est. Demand: 733 A Power 18,088 VA 100.00% 18,088 VA Total Conn.: 713 A Motor 558,962 VA 102.86% 574,966 VA Total Est. Demand: 609.04 kVA Lighting 2,530 VA 100.00% 2,530 VA Total Conn. Load: 593.04 kVA Equipment 0 VA 0.00% 0 VA Load Classification Connected... Demand Factor Estimated... Panel Totals 3 SPD 0.00 kVA 60 A 1 60 A TM - - - - - 2 EQ-ATS-5 390.27 kVA 600 A 3 600 A LSIA - - - - - 1 EQ-ATS-2 202.77 kVA 600 A 3 600 A LSIA - - - - -

CKT

CIRCUIT

DESCRIPTION

APPROX.

CONNECTED

LOAD

FRAME

SIZE POLES

TRIP

SETTING

BREAKER

TYPE

NUMBER OF

CONDUCTORS

WIRE

SIZE

GROUND

SIZE

CONDUIT

SIZE

SEE

NOTE

Feeder Size: REFER TO SINGLE LINE Spec. Ref. #: 26 24 16 Voltage: 480Y/277V-3PH-4W Mains Rating: 1000 A

Supply From: Enclosure: Type 1 Mains Type: MLO Location: ELECTRICAL ROOM 105 Mounting: Surface A.I.C. Rating: REFER TO SINGLE LINE

DISTRIBUTION PANEL:GP-1HDP2

37.97 kVA 38.93 kVA (108 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes: 1. THIS PANEL SHALL BE PROVIDED WITH A DOUBLE SET OF LUGS.

Special Circuit Breaker (SCB) Types: GF=GFCI Breaker, ST=Shunt Trip Breaker, AF=AFCI Breaker, GP=GFPE Breaker

Total Est. Demand: 108 A Receptacle 8,460 VA 100.00% 8,460 VA Total Conn.: 105 A Power 18,088 VA 100.00% 18,088 VA Total Est. Demand: 38.93 kVA Motor 11,420 VA 108.38% 12,377 VA Total Conn. Load: 37.97 kVA Equipment 0 VA 0.00% 0 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Panel Loads: 11.00 kVA 13.11 kVA 13.86 kVA Feed Thru Lugs Loads: 4.07 kVA 4.23 kVA 3.77 kVA

This Panel Loads: 6.93 kVA 8.88 kVA 10.09 kVA

41 ACTUATOR VAVLE 20 A 1 1.2 1.2 1 20 A ACTUATOR VAVLE 42

39 ACTUATOR VAVLE 20 A 1 0.8 1.2 1 20 A ACTUATOR VAVLE 40

37 -- -- -- -- 0.416 1.6 1 20 A ACTUATOR VAVLE 38

35 -- -- -- -- 0.416 0.3 1 20 A ACTUATOR VAVLE 36

33 SP-1A & SP-1B 20 A 3 0.416 0.54 1 20 A FLOW METER 34

31 AHU-2 LGT 20 A 1 0.18 1.914 -- -- -- -- 32

29 EF-2 15 A 1 1.176 1.914 2 25 A AC-2/CU-2 30

27 DP CNTR PNL 30 A 1 0.2 0.9 1 20 A FLOW METER 28

25 R. ROOF 20 A 1 0.36 0.18 1 20 A BAS CNTR 26

23 GATE CONTROL 20 A 1 0.18 0.18 1 20 A CT CELL 24

21 AHU-1 LGT 20 A 1 0.18 0.4 1 20 A FLOW METER 22

19 R TR 102 20 A 1 0.36 0.54 1 20 A R. MEZZANINE 200 20

17 -- -- -- -- 0.06 0.36 1 20 A R TR 102 18

15 -- -- -- -- 0.06 0.72 1 20 A R TR 102 16

13 R. TR 102 20 A 3 0.06 0.06 -- -- -- -- 14

11 -- -- -- -- 1.966 0.06 -- -- -- -- 12

9 AC-1/CU-1 25 A 2 1.966 0.06 3 20 A R. TR 102 10

7 R. CHILLER PLANT 100 20 A 1 0.54 0.36 1 20 A R. CHILLER PLANT 100 8

5 R. CHILLER PLANT 100 20 A 1 0.54 0.54 1 20 A R. CHILLER PLANT 100 6

3 R. CONTROL ROOM... 20 A 1 0.72 0.72 1 20 A R. CONTROL ROOM... 4

1 0.36 1 20 A R. CONTROL ROOM... 2

CKT Circuit Description

SCB

Type Trip Poles

A B C Poles Trip

SCB

Type Circuit Description CKT

Voltage: 208Y/120V-3PH-4W Mains Rating: 250 A Supply From: T-1LEA Enclosure: Type 1 Mains Type: MCB

Location: ELECTRICAL ROOM 105 Mounting: Surface A.I.C. Rating: 22KAIC Panel: 1LEA Construction Phase: NEW

1,662.78 kVA 1,678.79 kVA (2019 A)

TOTAL CONNECTED ESTIMATED DEMAND

NOTES: 1. REFER TO SINGLE LINE FOR WIRE INFORMATION.

2. NON-TYPICAL N+1 LOAD SHALL ONLY BE ENERGIZED WHEN THE CORRESPONDING PRIMARY EQUIPMENT IS NOT

ENERGIZED.

Resistive Heat 24,493 VA 100.00% 24,493 VA Spare 300,000 VA 100.00% 300,000 VA Receptacle 9,900 VA 100.00% 9,900 VA Power 18,848 VA 100.00% 18,848 VA Other 500 VA 100.00% 500 VA Total Est. Demand: 2019 A Motor 584,443 VA 102.74% 600,447 VA Total Conn.: 2000 A Lighting 5,270 VA 100.00% 5,270 VA Total Est. Demand: 1,678.79 kVA HVAC 719,330 VA 100.00% 719,330 VA Total Conn. Load: 1,662.78 kVA Equipment 0 VA 0.00% 0 VA Load Classification Connected... Demand Factor Estimated... Panel Totals 10 SPARE 0.00 kVA 800 A 3 800 A LSIG - - - - - 9 SPD 0.00 kVA 60 A 3 60 A GF - - - - 1 8 EX MOD1 120.00 kVA 250 A 3 250 A GF - - - - 1 7 EX MOD 5&6 180.00 kVA 400 A 3 400 A GF - - - - 1 6 1HNDP1 56.42 kVA 200 A 3 200 A GF - - - - 1 5 EQ-ATS-5 390.27 kVA 600 A 3 600 A LSIG - - - - 1 4 EQ-ATS-4 0.00 kVA 800 A 3 800 A LSIG - - - - 1,2 3 EQ-ATS-3 356.66 kVA 800 A 3 800 A LSIG - - - - 1 2 EQ-ATS-2 202.77 kVA 600 A 3 600 A LSIG - - - - 1 1 EQ-ATS-1 356.66 kVA 800 A 3 800 A LSIG - - - - 1

CKT

CIRCUIT

DESCRIPTION

APPROX.

CONNECTED

LOAD

FRAME

SIZE POLES

TRIP

SETTING

BREAKER

TYPE

NUMBER OF

CONDUCTORS

WIRE

SIZE

GROUND

SIZE

CONDUIT

SIZE

SEE

NOTE

Feeder Size: REFER TO SINGLE LINE Spec. Ref. #: 26 11 16 Voltage: 480Y/277V-3PH-4W Mains Rating: 2500 A

Supply From: Enclosure: Type 1 Mains Type: MCB Location: ELECTRICAL ROOM 106 Mounting: Surface A.I.C. Rating: REFER TO SINGLE LINE

DISTRIBUTION PANEL:US-49

US-49 XFRM GDP

GDP

(NEW) (NEW) (NEW) (NEW)

(NEW)(NEW)(NEW)

356.66 kVA

EXISTING

33.26 kVA

17.46 kVA

64.02 kVA

54.04 kVA

24.03 kVA

356.66 kVA

12.07 kVA 12.69 kVA (35 A)

TOTAL CONNECTED ESTIMATED DEMAND

Notes:

Special Circuit Breaker (SCB) Types: GF=GFCI Breaker, ST=Shunt Trip Breaker, AF=AFCI Breaker, GP=GFPE Breaker

Total Est. Demand: 35 A Receptacle 1,440 VA 100.00% 1,440 VA Total Conn.: 33 A Power 8,140 VA 100.00% 8,140 VA Total Est. Demand: 12.69 kVA Motor 2,486 VA 125.00% 3,107 VA Total Conn. Load: 12.07 kVA Equipment 0 VA 0.00% 0 VA

Load Classification Connected Load Demand Factor Estimated Demand Panel Totals

Total Load: 4.07 kVA 4.23 kVA 3.77 kVA 41 Spare 20 A 1 0 -- 1 -- Space 42 39 Spare 20 A 1 0 -- 1 -- Space 40 37 Spare 20 A 1 0 -- 1 -- Space 38 35 Spare 20 A 1 0 -- 1 -- Space 36 33 Spare 20 A 1 0 -- 1 -- Space 34 31 Spare 20 A 1 0 -- 1 -- Space 32 29 Spare 20 A 1 0 -- 1 -- Space 30 27 Spare 20 A 1 0 -- 1 -- Space 28 25 Spare 20 A 1 0 -- 1 -- Space 26 23 HOIST CONT 20 A 1 0.18 -- 1 -- Space 24 21 ACTUATOR VAVLE 20 A 1 1 -- 1 -- Space 22

19 ACTUATOR VAVLE 20 A 1 1.2 1.32 -- -- -- -- 20

17 R. ELECTRICAL ROO... 20 A 1 0.9 1.32 -- -- -- -- 18

15 HOIST CONT 20 A 1 0.18 1.32 3 20 A OVERHEAD DOOR 16

13 EM SHUT OFF 20 A 1 0 0.18 1 20 A R. CHILLER PLANT 100 14

11 MEDIA CONVTER 20 A 1 0.18 0.18 1 20 A GATE CONTROL 12

9 CT CONTROL PANEL 20 A 1 0.18 0.18 1 20 A CT CELL 10

7 CT CONTROL PANEL 20 A 1 0.18 0.18 1 20 A CT CELL 8

5 -- -- -- -- 0.829 0.18 1 20 A CT CONTROL PANEL 6

3 -- -- -- -- 0.829 0.54 1 20 A FLOW METER 4

1 RF-2 20 A 3 0.829 0.18 1 20 A VALVE CONTROL... 2

CKT Circuit Description

SCB

Type Trip Poles

A B C Poles Trip

SCB

Type Circuit Description CKT

Voltage: 208Y/120V-3PH-4W Mains Rating: 250 A Supply From: 1LEA Enclosure: Type 1 Mains Type: MCB

Location: ELECTRICAL ROOM 105 Mounting: Surface A.I.C. Rating: 22KAIC Panel: 1LEA2 Construction Phase: NEW(NEW)

14.04_ED100 - BUILDING 49 DEMOLITION PLAN
14.05_E100-FIRST FLOOR - POWER & FIRE ALARM