657A5-21-401 - Drawings R2_Part6 - 10 pages.pdf
PDF 15 MB Posted
- Solicitation number
- 36C25526R0129
About this file
These are contract documents for a construction project at Marion VA Medical Center consisting of electrical and mechanical systems design drawings and schedules. The project involves construction of a new energy center (Building 49) and includes comprehensive mechanical, electrical, power, fire alarm, and lighting systems for a multi-story facility.
The scope encompasses HVAC systems including three 356.66 kVA chillers, multiple chilled water pumps (primary and secondary), condenser water pumps, cooling towers, and basin heaters on the roof. The electrical infrastructure includes a 1500 kVA transformer with 800A disconnect, automatic transfer switches, distribution panels rated for 480Y/277V three-phase service, and motor control centers. Lighting design features LED fixtures throughout including 2x2 flat panels (B1/B2), 1x4 industrial strips (C1/C2), low bay fixtures (LB1/LB2), exterior wall packs (WP1/WP2), and pole-mounted fixtures (PL1-PL4). The project incorporates emergency lighting, lightning protection systems with air terminals and down conductors, and heating/cooling equipment serving multiple rooms including a control room, electrical rooms, H.A.C. space, and toilet facilities. Distribution panels detailed include E-EQ-1HDP1 (356.66 kVA), E-EQ-1HDP2 (713.33 kVA estimated demand), US-49 (390.27 kVA connected load), and GP-1HDP1. The electrical design provides for variable frequency drives on multiple motors, remote shut-off capabilities, and coordination between Division 22, 23, 26, and 27 work requirements. Construction documents are dated 05/07/2026 with the project marked as "fully sprinklered."
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
UH
UH
UH
UH
UH
F F F
GF
WH
F F
UH
49-1
49-EQ1
49-EQ-2
49-MCC1
CT1/CT2
BREAKER
49-MCC3
ATS-49/US49
ATS-49-1/US49-1
US-49-1
US-49
49-EF1
49-EF1
1500 KVA
TRANSFORMER
SWITCH
800A
DISC
PB
PB
PB
CT-1 CT-2 CT-3
CH-3CH-2CH-1
EF
ON ROOF
EF
ON ROOF
CU
ON ROOF
EF
ON ROOF
40 HP
PUMP
40 HP
PUMP
40 HP
PUMP
30 HP
PUMP
30 HP
PUMP
30 HP
PUMP
P-10
US-49-1
US-49
US-49
VFD
VFD
VFD
CONDENSER SYSTEM DX10
CHILLER SYSTEM DX10
METER ENCLOSURE
TRANSFORMER
PB
BASIN
HEATER
BASIN
HEATER
BASIN
HEATER
TYP.
TYP.
TYP.
P-3
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
A u to d e s k D o c s /M a ri o n I
L V
A
N e w E n e rg y C e n te r/
-0
-M
E P
-C e n tr a l.
rv t
/5 /2
:2
:0
P M
ED100
BUILDING 49 DEMOLITION PLAN
05/07/2026 MSG DMB
CONSTRUCT NEW
CAMPUS CHILLER PLANT
657A5-21-401
2401 W MAIN ST, MARION IL 62959
CONTRACT
DOCUMENTS 49
MARION VA
MEDICAL
CENTER Approved: Owner
SCALE: 1/4" = 1'-0"
FIRST FLOOR DEMOLITION PLAN
A. REMOVAL PLANS MAY NOT NECESSARILY SHOW ALL ITEMS REQUIRED TO BE REMOVED.
B. REMOVAL OF ELECTRICAL ITEMS SHALL INCLUDE REMOVALS BACK TO THE EXISTING ELECTRICAL
DISTRIBUTION CENTER, PANEL OR LAST ACTIVE OUTLET, FIXTURE OR DEVICE REMAINING.
C. REMOVE ALL ABANDONED EXTRANEOUS CONDUITS, SUPPORTS, CONTROLS, ETC.
D. REMOVALS OF RECEPTACLES, TELEPHONE, DATA OUTLETS, ETC. INCLUDE REMOVAL OF THE DEVICE, BACKBOX, CONDUIT, WIRING, ETC.
E. ALL EXISTING FLUORESCENT LAMPS AND BALLASTS REMOVED ARE TO BE PUT INTO CONTAINERS FURNISHED BY THE OWNER AND DISPOSED OF BY A QUALIFIED CONTRACTOR AT AN APPROVED DISPOSAL
FACILITY.
F. ALL EXISTING CONDUIT, EQUIPMENT, CONTROLS, ETC. SHOWN DASHED SHALL BE REMOVED. THE MAJORITY OF ELECTRICAL WORK TO BE REMOVED IS SHOWN. REMOVE ALL INCIDENTAL ITEMS ASSOCIATED WITH THE
DEMOLITION WORK.
G. ALL EXISTING FIRE ALARM EQUIPMENT AND DEVICES SHALL BE REMOVED AS NOTED. CONTRACTOR SHALL SALVAGE EQUIPMENT AS DIRECTED BY THE OWNER AND STORED IN A LOCATION DESIGNATED BY THE OWNER. ALL OTHER EQUIPMENT AND DEVICES NOT SALVAGED SHALL BE REMOVED AS DIRECTED FROM THE
PREMISE.
H. CONTRACTOR SHALL COORDINATE WITH THE OWNER IN REGARD TO REMOVALS. CONTRACTOR SHALL SALVAGE EQUIPMENT AS DIRECTED BY THE OWNER AND STORED IN A LOCATION DESIGNATED BY THE OWNER. ALL OTHER EQUIPMENT AND MATERIALS NOT SALVAGED SHALL BE REMOVED FROM THE PREMISE.
I. HVAC AND PLUMBING EQUIPMENT, DISCONNECT ELECTRICAL SOURCE TO EQUIPMENT AND REMOVE FEEDER
BACK TO SOURCE.
GENERAL NOTES
1. THE ENTIRE AREA WITHIN THE DASHED LINES SHALL BE REMOVED ELECTRICALLY. DISCONNECT AND REMOVE ALL ELECTRICAL DISTRIBUTION EQUIPMENT, TRANSFORMERS, AUTOMATIC TRANSFER SWITCHES, MOTOR CONTROL CENTERS, DISCONNECTS, MOTOR CONTROLLERS, WIRING DEVICES, LIGHTING FIXTURES, FIRE ALARM DEVICES, AND HVAC/PLUMBING EQUIPMENT. REMOVE ALL
ASSOCIATED WIRING AND CONDUIT.
2. DISCONNECT HEAT TRACE AND REMOVE CIRCUITRY BACK TO SOURCE.
3. DISCONNECT EXISTING LIGHTING CONTACTOR LC-1 AND STORE AND PROTECT FOR REINSTALLATION IN NEW CHILLER PLANT.
INTERMATIC TIMER CONNECTED TO LC-1 SHALL BE DISCONNECTED AND TURNED OVER TO THE VA. REFER TO SITE PHOTO ON THIS
SHEET.
PLAN NOTES
SITE KEY PLAN
NEW CHILLER PLANT - BLDG 49
EXISTING CHILLER PLANT - BLDG 49
37MOD-5
MOD-1
MOD-4
MOD-6
NORTH
SCALE: NONE
LC-1 SITE PHOTO
1 CONTRACT DOCUMENTS 05/07/2026
UP
FACP
GF
GF
F F
F
S
F
F F
F
F
F
F
F
F
F
J
UH
UH
UH
UH
GF
J
J J J
J
UH
J
FS VV
J
J
J
J
J
J
GF GF
GF
J J
GF
J
FS
S S F
J
J J
J
J J J
JJJ
J
J
J
J
J
J
J
J
J
JJ
J
J
GF
L2 1-
R
L2 1-
R
GF
S F
A
D
632 54
B
C
ELECTRICAL ROOM
ELECTRICAL ROOM
CONTROL ROOM
TR
H.A.C.
GP-1HDP1
GP-1HDP2
E-
EQ
-1
HD
P1
E-
EQ
-1
HD
P2
EQ-ATS-4EQ-ATS-3EQ-ATS-1
EQ-ATS-2 EQ-ATS-5 LS-ATS
CH-1
CH-2
CH-3
PCHWP-1PCHWP-2PCHWP-3
SCHWP-1
SCHWP-2
SCHWP-3
CDWP-1CDWP-2CDWP-3
US-49
X-FORMER
US-49
MV
SW
US-49
MV
SW
US-49
LV
SEC
CHILLER PLANT
DWH-1
1LNA - 8,10
VFD
PCHWP-3
EQ-ATS-4 - 1
EQ-ATS-3 - 1
EQ-ATS-1 - 1
E100
T-1LEA
T-1LNA
1LNA
FU
TU
RE
S
EC
Generator Annunciator
Panel
SP-1A SP-1B
1LEA - 2
1LEA - 2
1LEA - 3
1LEA - 3
1LEA - 4
1LEA - 4 1LNA - 1
1LNA - 1
1LEA - 5
1LEA - 5 1LEA - 5
1LEA - 6
1LEA2 - 14 1LEA - 8 1LEA - 7
1LEA - 8
1LNA - 1
1LNA - 1
1LEA - 7
1LEA - 7
1LEA - 6
1LEA - 6
1HNDP1 - 22,24,26
VAV-1
1HNDP1 - 7,9,11
VAV-2
1LNA - 3,5
VAV-3
1LEA - 27
7 7
T-1LLS 1HEA1LEA1LLS1LLS - 1
1LEA - 26
E-EQ-1HDP2 - 2 E-EQ-1HDP1 - 6 E-EQ-1HDP1 - 2
E-EQ-1HDP2 - 3
E-EQ-1HDP1 - 7
E-EQ-1HDP1 - 3
E-EQ-1HDP1 - 4E-EQ-1HDP1 - 8E-EQ-1HDP2 - 4
1HNDP1 - 8,10,12
1HNDP1 - 13,15,17
UH-4
1HNDP1
1L
NA
1L
NA
LCP-1
VFD
PCHWP-22
VFD
PCHWP-12
VFD
SCHWP-12
VFD
SCHWP-22
VFD
SCHWP-32
E-EQ-1HDP2 - 9
CDWF-1
9 9
1LEA2 - 2
1LEA2 - 4
UH-1
UH-2
UH-3
1HNDP1 - 19,21,23
1HNDP1 - 14,16,18
UH-5
1LNA - 4,6
A
D
61 32 54
B
C
A.4
A.6
2 2 2
1LEA21LNA -12
ATS
Annunciator
Panel
1LEA2 - 13
1LEA2 - 13
1LEA2 - 13
1LEA2 - 13
1LEA2 - 16,18,20
1LEA2 - 4
1LEA - 28
1LEA - 28
1LEA - 28
1LEA - 28
1LEA - 28
20 20 20
202020
1LEA2 - 17 1LEA2 - 17
1LEA2 - 17
1LEA2 - 17
1LEA2 - 17
1HNDP1 -30,32,34
1LLS - 6
1LLS - 6
1LNA - 1
1LEA - 33,35,37
EH-2
1HEA - 28,30,32
TYP.
1LEA2 - 4
1LEA - 34
1LEA - 34
151LEA - 34
1LEA - 39
1LEA - 38
1LEA - 38
1LEA - 38
1LEA - 38
1LEA - 39
1LEA2 - 19
1LEA2 - 19
1LEA2 - 19
1LEA2 - 19
1LEA2 - 19
1LEA2 - 19
1LEA - 42
1LEA - 42
1LEA - 42
1LEA - 42
1LEA - 42
1LEA - 42
1LEA2 - 15
C
TR
AC-1
1L
EA
,12 ,14
1L
EA
,15 ,17
1LEA - 19
1LEA - 16
1LEA - 18 1LEA - 16
C
AC-2
TRANSFORMER
MANUAL SWITCHES
METER
MAIN
BREAKER
EQ-ATS-1
EQ-ATS-3
MOD-1
DISCONNECT
SWITCH
EQ-ATS-2
1HNDP1
MOD-5&6
DISCONNECT
SWITCH
EQ-ATS-5
EQ-ATS-2
EQ-ATS-4
SPARE
FUTURE
SECTION
FUTURE
SECTION
FUTURE
SECTION
FUTURE
SECTION
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
C :\U se rs
\d m br
\A pp D at a\
Lo ca l\A ut od es k\ R ev it\
Au to de sk
R ev it
\C ol la bo ra tio nC ac he
\L Q
C 3M
U F8
4E
LP
\5 d1 ac
3- 2a e8 -4
5-b5 5f
-c ff8
3c 3d
3a
\e e-fd
-4 d-ab
-2 dc f.r vt
5/ 5/
1:
:5
PM
E100
FIRST FLOOR - POWER & FIRE
ALARM
05/07/2026 MSG DMB
CONSTRUCT NEW
CAMPUS CHILLER PLANT
657A5-21-401
2401 W MAIN ST, MARION IL 62959
CONTRACT
DOCUMENTS 49
MARION VA
MEDICAL
CENTER Approved: Owner
SCALE: 1/4" = 1'-0"
FIRST FLOOR PLAN - POWER & FIRE ALARM1
GENERAL NOTES:
A.
B.
C.
EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A
SEPARATE GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR.
MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND NORMAL BRANCH WIRING DEVICES SHALL HAVE
DIVIDERS BETWEEN DEVICES.
RECEPTACLES IN PRECAST WALLS SHALL BE SURFACE MOUNTED ON WALL.
SITE KEY PLAN
NEW CHILLER PLANT - BLDG 49
EXISTING CHILLER PLANT - BLDG 49
37MOD-5
MOD-1
49 MOD-4
MOD-6
NORTH
PLAN NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
CHILLER PLANT HAS HIGH AMBIENT NOISE LEVELS. DIV 26 PROVIDE ADDITIONAL NOTIFICATION APPLIANCES AS REQUIRED TO ACHIEVE
REQUIRED SOUND LEVELS.
PROVIDE REMOTE TURN OFF, AUX CONTACT, AND ALL ASSOCIATED WIRING FROM VFD TO RESPECTIVE PUMP. COORDINATE EXACT
REQUIREMENTS WITH DIVISION 23.
PROVIDE GENERATOR ANNUNCIATOR PANEL AND CONNECT TO EXISTING GENERATOR IN BUILDING 47. PROVIDE ALL REQUIRED POWER, COMMUNICATION, AND CONTROL WIRING. COORDINATE EXACT WIRING REQUIREMENTS, POINT LIST, AND PROTOCOL WITH GENERATOR
MANUFACTURER.
PROVIDE 120V/1PH CONNECTION FOR DCC PANEL. COORDINATE EXACT CONNECTION REQUIREMENTS WITH DIV 23 PRIOR TO ROUGH-IN.
INDOOR UNIT IS FED THROUGH OUTDOOR UNIT . PROVIDE INTERCONNECTING WIRE AS REQUIRED FOR A COMPLETE AND OPERATION
INSTALLATION.
RACK MOUNTED RECEPTACLE. COORDINATE EXACT MOUNTING WITH DIV 27 PRIOR TO ROUGH-IN. PROVIDE 4-#12 CU, 1#12 G IN 0.75"
CONDUIT.
PROVIDE A 120V, 1Ø ELECTRICAL CONNECTION TO DRAINAGE PUMP CONTROL PANEL. PROVIDE (2) #12 CU AND (1) #12 G IN 3/4" CONDUIT.
PROVIDE A 208V, 3Ø ELECTRICAL CONNECTION TO DRAINAGE PUMPS. PROVIDE (3) #12 CU AND (1) #12 G IN 3/4" CONDUIT. COORDINATE EXACT LOCATION AND CONNECTION REQUIREMENTS WITH DIV 22 PRIOR TO ROUGH-IN. PROVIDE ALL COMPONENTS REQUIRED FOR A
COMPLETE AND OPERATIONAL INSTALLATION.
MULTI-UNIT ENCLOSED METER. REFER TO SINGLE LINE.
PROVIDE EMERGENCY POWER-OFF (EPO) PUSHBUTTON WITH WEATHERPROOF COVER FOR EMERGENCY SHUTDOWN OF ALL CHILLERS.
COORDINATE EXACT INTERLOCKING AND CONTROL REQUIREMENTS WITH DIV 23 AND CHILLER MANUFACTURER TO ENSURE PROPER INTEGRATION WITH CHILLER CONTROL SYSTEMS. PROVIDE ALL WIRING, CONDUIT, AND ACCESSORIES REQUIRED FOR A COMPLETE AND
FUNCTIONAL INSTALLATION.
PROVIDE 120V, 1Ø ELECTRICAL CONNECTION TO ELECTRICAL ACTUATOR VALVE. COORDINATE EXACT LOCATION AND CONNECTION REQUIREMENTS WITH DIV 23 PRIOR TO ROUGH-IN. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE AND OPERATIONAL
INSTALLATION.
PROVIDE 20HP VFD FOR PRIMARY CHILLED WATER PUMPS. COORDINATE EXACT CONNECTION REQUIREMENTS WITH MANUFACTURER AND DIV 23. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE AND OPERATIONAL INSTALLATION.
PROVIDE 60HP VFD FOR SECONDARY CHILLED WATER PUMPS. COORDINATE EXACT CONNECTION REQUIREMENTS WITH MANUFACTURER AND DIV 23. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE AND OPERATIONAL INSTALLATION.
PROVIDE 208V/3PH TO OVERHEAD DOOR MOTOR AND DISCONNECT SWITCH. COORDINATE EXACT CONNECTION REQUIREMENTS WITH MANUFACTURER AND DIV 23. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE AND OPERATIONAL INSTALLATION.
PROVIDE AND COORDINATE EXACT LOCATION, MOUNTING, AND ACCESS REQUIREMENTS OF FLOW SWITCH AND TAMPER SWITCH WITH
DIV 21 PRIOR TO ROUGH-IN.
PROVIDE 120V, 1Ø ELECTRICAL CONNECTION TO FLOW METER. COORDINATE EXACT LOCATION AND CONNECTION REQUIREMENTS WITH DIV 22 PRIOR TO ROUGH-IN. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE AND OPERATIONAL INSTALLATION.
TELECOMMUNICATIONS SERVICE GROUNDING BUSBAR. REFER TO DIV 27 DRAWINGS FOR ADDITIONAL INFORMATION.
PROVIDE #6 AWG TO TELECOMMUNICATIONS SERVICE GROUND BAR.
PROVIDE #3/0 GROUNDING ELECTRODE CONDUCTOR FROM UNIT SUBSTATION TO BUILDING STEEL.
PROVIDE #3/0 GROUNDING ELECTRODE CONDUCTOR FROM UNIT SUBSTATION TO WATER SERVICE.
PROVIDE UNISTRUT SUPPORT FRAMING AS REQUIRED TO SECURELY MOUNT DISCONNECTS FED FROM FLOOR. MAINTAIN REQUIRED WORKING CLEARANCES AND PROVIDE RIGID SUPPORT IN ACCORDANCE WITH NEC AND SEISMIC REQUIREMENTS.
PROVIDE GROUND BAR.
REINSTALL EXISTING LIGHTING CONTACTOR LC-1. VERIFY EQUIPMENT CONDITION PRIOR TO INSTALLATION AND PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE AND OPERATIONAL INSTALLATION. PROVIDE AUXILIARY CONTACT WITH CONNECTION TO
PHOTOCELL ON THE ROOF FOR ON/OFF CONTROL OF THE EXISTING POLE LIGHTS.
PROVIDE 120V, 1Ø ELECTRICAL CONNECTION TO CDW SYSTEM WATER TREATMENT CONTROL PANEL. COORDINATE EXACT LOCATION AND CONNECTION REQUIREMENTS WITH DIV 23 PRIOR TO ROUGH-IN. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE AND
OPERATIONAL INSTALLATION.
PROVIDE ATS ANNUNCIATOR PANEL AND CONNECT TO EXISTING ATS MONITORING IN BUILDING 47. PROVIDE ALL REQUIRED POWER, COMMUNICATION, AND CONTROL WIRING. COORDINATE EXACT WIRING REQUIREMENTS, POINT LIST, AND PROTOCOL WITH ATS
MANUFACTURER. PROVIDE 2-#10 CU, 1-#10 G CONDUCTORS.
PROVIDE 480V/3Ø TO ELECTRICAL HOIST AND DISCONNECT SWITCH. COORDINATE EXACT CONNECTION AND MOUNTING REQUIREMENTS WITH MANUFACTURER AND DIV 23. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE AND OPERATIONAL INSTALLATION.
PROVIDE 120V, 1Ø ELECTRICAL HOIST CONTROL POWER . COORDINATE EXACT CONNECTION AND MOUNTING REQUIREMENTS WITH MANUFACTURER AND DIV 23. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE AND OPERATIONAL INSTALLATION.
SCALE: NONE
ENLARGED TR ROOM2
NTS3 UNIT SUBSTATION "US-49" ELEVATION
F
FJ J
J
J
J
S
S
S
S
F
J
J
J
J
J
J
J
J
J
J
J
J
J
J
J
A
D
632 54
B
C
AHU-1-EH
AHU-2-EH
AHU-1-FS
AHU-2-FS
VFD
CT-3
VFD
CT-2
VFD
CT-1
1LEA - 20
1LEA - 20
1LEA - 20
VFD
EF-1
1H E
A
1H E
A
1HEA - 5,7,9 1HEA - 4,6,8
1HEA - 11,13,15 1HEA - 10,12,14
RF-2
1LEA2 - 1,3,5
1LEA - 22
1LEA - 21
1LEA - 31
A
D
1 32
B
C
A.4
A.6
VFD
RF-2
3 3
VFD
EF-3
1LEA - 22
1LEA - 36
1LEA - 36
1LEA - 36
1LEA - 40 10
1LEA - 40
1LEA - 40
1LEA - 41
1LEA - 41
1LEA - 41
1LEA2 - 21
1LEA2 - 21
1LEA2 - 21
1LEA2 - 21
1LEA2 - 21
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
A u to d e s k D o c s /M a ri o n I
L V
A
N e w E n e rg y C e n te r/
-0
-M
E P
-C e n tr a l.
rv t
/5 /2
:2
:0
P M
E101
MEZZANINE - POWER & FIRE
ALARM
05/07/2026 MSG DMB
CONSTRUCT NEW
CAMPUS CHILLER PLANT
657A5-21-401
2401 W MAIN ST, MARION IL 62959
CONTRACT
DOCUMENTS 49
MARION VA
MEDICAL
CENTER Approved: Owner
SCALE: 1/4" = 1'-0"
MEZZANINE - POWER & FIRE ALARM
GENERAL NOTES:
A. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A
SEPARATE GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR.
B. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND NORMAL BRANCH WIRING DEVICES SHALL HAVE
DIVIDERS BETWEEN DEVICES.
SITE KEY PLAN
NEW CHILLER PLANT - BLDG 49
EXISTING CHILLER PLANT - BLDG 49
37MOD-5
MOD-1
MOD-4
MOD-6
NORTH
PLAN NOTES:
1. PROVIDE 30A, 277V/1PH CONNECTION FOR POWER CONNECTION TO HEAT TRACE CONTROLLERS. PROVIDE (2) #10 CU, (1) #10 G IN 0.75" CONDUIT. COORDINATE EXACT REQUIREMENTS WITH DIV 23. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE AND OPERATIONAL
INSTALLATION.
2. PROVIDE 120V-1PH CONNECTION TO AHU LIGHT SWITCH AND RECEPTACLE. COORDINATE EXACT CONNECTION REQUIREMENTS WITH DIV
23. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE AND OPERATIONAL INSTALLATION.
3. PROVIDE 40HP VFD FOR COOLING TOWER. PROVIDE REMOTE TURN OFF, AUX CONTACT, AND ALL ASSOCIATED WIRING FROM VFD TO RESPECTIVE COOLING TOWER. COORDINATE EXACT REQUIREMENTS WITH DIV 23. PROVIDE ALL COMPONENTS REQUIRED FOR A
COMPLETE AND OPERATIONAL INSTALLATION.
4. PROVIDE 5HP VFD FOR EXHAUST FAN. PROVIDE REMOTE TURN OFF, AUX CONTACT, AND ALL ASSOCIATED WIRING FROM VFD TO RESPECTIVE EXHAUST FAN. COORDINATE EXACT REQUIREMENTS WITH DIV 23. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE
AND OPERATIONAL INSTALLATION.
5. PROVIDE 480V, 3Ø ELECTRICAL CONNECTION TO AHU ELECTRIC HEATING COIL. COORDINATE EXACT CONNECTION REQUIREMENTS WITH MANUFACTURER AND DIV 23. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE AND OPERATIONAL INSTALLATION.
6. PROVIDE 120V, 1Ø ELECTRICAL CONNECTION TO FLOW METER. COORDINATE EXACT LOCATION AND CONNECTION REQUIREMENTS WITH DIV 23 PRIOR TO ROUGH-IN. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE AND OPERATIONAL INSTALLATION.
7. PROVIDE 2HP VFD FOR RETURN FAN. COORDINATE EXACT REQUIREMENTS WITH DIV 23. PROVIDE ALL COMPONENTS REQUIRED FOR A
COMPLETE AND OPERATIONAL INSTALLATION.
8. COORDINATE EXACT LOCATION, MOUNTING, REMOTE TEST SWITCHES AND ACCESS REQUIREMENTS OF DUCT-MOUNTED SMOKE
DETECTORS WITH DIV 23 PRIOR TO ROUGH-IN.
9. PROVIDE 1.5 HP VFD FOR EXHAUST FAN. PROVIDE REMOTE TURN OFF, AUX CONTACT, AND ALL ASSOCIATED WIRING FROM VFD TO RESPECTIVE EXHAUST FAN. COORDINATE EXACT REQUIREMENTS WITH DIV 23. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE
AND OPERATIONAL INSTALLATION.
10. PROVIDE 120V, 1Ø ELECTRICAL CONNECTION TO ELECTRICAL ACTUATOR VAVLE. COORDINATE EXACT LOCATION AND CONNECTION REQUIREMENTS WITH DIV 23 PRIOR TO ROUGH-IN. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE AND OPERATIONAL
INSTALLATION.
F
WP/GF
J J J J J J
WP/GF
J
SCALE:SCALE: SCALE: SCALE: NONENONENONENONE
AIR TERMINAL DETAIL "B"AIR TERMINAL DETAIL "E"THRU-ROOF DETAIL "T"AIR TERMINAL DETAIL "C"
NO. 97 1/2" X 36" COPPER, LEAD COATED
CHIMNEY AIR TERMINAL
NO. 251L LEAD COATED COPPER LOOP
FASTENER WITH STAINLESS STEEL
SCREWS
NO. 28 COPPER
LIGHTNING CONDUCTOR
(28 X 17 AWG)
NO. 150 BRONZE
FLAT SURFACE BASE
NO. 71, 1/2" X 12" COPPER AIR TERMINAL
NO. 28 ALUMINUM
LIGHTNING CONDUCTOR
(28 X 14 AWG)
NO. 251 COPPER LOOP CABLE CLIP WITH STAINLESS
STEEL SCREW (3'-0" O.C.)
NO. 230 THRU-ROOF ASSEMBLY MOUNTED ON CONCRETE
ROOF DECK EXTENDING THROUGH INSULATION &
ROOFING MATERIALS TO 6" ABOVE FINISHED ROOF
FLASHING BY ROOFING CONTRACTOR
2" SCHEDULE 40 PVC WITH
CAP LENGTH AS REQUIRED
1/2" STAINLESS STEEL OR
BRASS THREAD ROD
NO. 28 CLASS II ALUMINUM
LIGHTNING CONDUCTOR (28 X 14
AWG)
NO. A81 5/8" X 12" ALUMINUM AIR TERMINAL
NO. A150 ALUMINUM FLAT SURFACE PLATE
NO. A37 ALUMINUM
LIGHTNING CONDUCTOR
NO. A251 ALUMINUM LOOP CABLE CLIP
NO. A217 ALUMINUM BONDING PLATE
NO. 211 BIMETAL CONNECTOR
NO. 28 COPPER
LIGHTNING CONDUCTOR
(28 X 14 AWG) NO. 28 CLASS II COPPER LIGHTNING CONDUCTOR DOWN IN
EXTERIOR WALL CONSTRUCTION TO LOWER ROOF OR GROUND
A
D
632 54
B
C
TYP.
TYP.
TYP.
1LEA - 9,11
CU-1
NEMA
3R
TYP.
EF-1
EF-2
WP
CT-1 CT-2 CT-3
BH-3BH-2BH-1
NEMA
3R
NEMA
3R
NEMA
3R
NEMA
3R
NEMA
3R
NEMA
3R
E-EQ-1HDP1 - 1
1HEA - 16,18,20
1LEA - 29
1LEA - 25
NEMA
3R
E-EQ-1HDP1 - 5 E-EQ-1HDP2 - 1
E-EQ-1HDP1 - 9 E-EQ-1HDP1 - 10 E-EQ-1HDP2 - 7
1L
EA
2 -
1L
EA
7 8
1L
EA
2 -
1L
EA
2 -
7 8 7 8
1L
EA
2 -
1L
EA
2 -
BSP-1
E-EQ-1HDP2 - 8
NEMA
3R
TYP.
CT 1
CT 2
CT 3
A
D
61 32 54
B
C
A.4
A.6
1LEA - 30,32
CU-2
NEMA
3R
10 10 10 101010
NEMA
3R
EH-1
1HEA - 23,25,27
1LEA - 25
EF-3
1HEA - 22,24,26
NEMA
3R 10
1LEA2 - 23
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
C :\U se rs
\d m br
\A pp D at a\
Lo ca l\A ut od es k\ R ev it\
Au to de sk
R ev it
\C ol la bo ra tio nC ac he
\L Q
C 3M
U F8
4E
LP
\5 d1 ac
3- 2a e8 -4
5-b5 5f
-c ff8
3c 3d
3a
\e e-fd
-4 d-ab
-2 dc f.r vt
5/ 5/
1:
:5
PM
E102
ROOF - POWER & FIRE ALARM
05/07/2026 MSG DMB
CONSTRUCT NEW
CAMPUS CHILLER PLANT
657A5-21-401
2401 W MAIN ST, MARION IL 62959
CONTRACT
DOCUMENTS 49
MARION VA
MEDICAL
CENTER Approved: Owner
SCALE: 1/4" = 1'-0"
ROOF - POWER & FIRE ALARM1
PLAN NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
PROVIDE LIGHTNING PROTECTION CONDUCTOR ON ROOF.
PROVIDE LIGHTNING PROTECTION AIR TERMINAL.
PROVIDE LIGHTNING PROTECTION SYSTEM DOWN CONDUCTOR CONCEALED IN BUILDING AND GROUND ROD.
BOND LIGHTNING PROTECTION TO MECHANICAL EQUIPMENT AND DUCT WORK PENETRATING ROOF.
BOND LIGHTNING PROTECTION TO ALL PIPING PENETRATING ROOF.
PROVIDE HEAT TRACE ON ALL HOT AND COLD WATER PIPING EXPOSED TO FREEZING TEMPERATURES. COORDINATE EXACT
REQUIREMENTS WITH DIVISION 23.
PROVIDE 120V-1PH CONNECTION TO LLC WATER CONTROL PANEL ON COOLING TOWER CELL. PROVIDE INTERCONNECTION WIRE BETWEEN CONTROL PANEL AND SOLENOID VALVE AS REQUIRED. COORDINATE EXACT CONNECTION REQUIREMENTS WITH DIV 23.
PROVIDE 120V-1PH CONNECTION TO CONTROL PANEL ON COOLING TOWER CELL. PROVIDE INTERCONNECTION WIRE BETWEEN CONTROL PANEL AND SOLENOID VALVE AS REQUIRED. COORDINATE EXACT REQUIREMENTS WITH DIV 23.
PROVIDE REMOTE TURN OFF, AUX CONTACT, AND ALL ASSOCIATED WIRING FROM VFD TO RESPECTIVE MOTOR. COORDINATE EXACT
REQUIREMENTS WITH DIVISION 23.
PROVIDE UNISTRUT SUPPORT FRAMING AS REQUIRED TO SECURELY MOUNT DISCONNECTS FED FROM FLOOR. MAINTAIN REQUIRED WORKING CLEARANCES AND PROVIDE RIGID SUPPORT IN ACCORDANCE WITH NEC AND SEISMIC REQUIREMENTS.
PROVIDE 480V/3PH TO ELECTRICAL HOIST AND DISCONNECT SWITCH. COORDINATE EXACT CONNECTION REQUIREMENTS WITH MANUFACTURER AND DIV 23. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE AND OPERATIONAL INSTALLATION.
PROVIDE 120V, 1Ø ELECTRICAL HOIST CONTROL POWER . COORDINATE EXACT CONNECTION AND MOUNTING REQUIREMENTS WITH MANUFACTURER AND DIV 23. PROVIDE ALL COMPONENTS REQUIRED FOR A COMPLETE AND OPERATIONAL INSTALLATION.
SITE KEY PLAN
NEW CHILLER PLANT - BLDG 49
EXISTING CHILLER PLANT - BLDG 49
37MOD-5
MOD-1
49 MOD-4
MOD-6
NORTH
GENERAL NOTES:
A.
B.
EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A
SEPARATE GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR.
MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND NORMAL BRANCH WIRING DEVICES SHALL HAVE
DIVIDERS BETWEEN DEVICES.
SCALE: NONE
LIGHTNING PROTECTION DETAILS2
DM
OS
O S
OS
3 3
DM
A
D
632 54
B
C C1
C1
B1B1
B2
B2B1
B1 B1
B1B2
C1 C2C2
C1C1
C2C2
C2 C1
C2
C1
C1
C1
C1
C2
9' - 0" 9' - 0" 9' - 0"
9' - 0"
9' - 0"9' - 0"
9' - 0"
9' - 0" 9' - 0"
9' - 0"9' - 0"9' - 0"
9' - 0" 9' - 0" 9' - 0"
18' - 0"
18' - 0"
18' - 0"
18' - 0"
18' - 0"
19' - 0" 18' - 0"
17' - 0" 17' - 0"
LB2
LB1
LB1
LB2
LB2
C2 C1
C2 C1
18' - 0"
16' - 6"
18' - 0"
18' - 0"
18' - 0"
18' - 0"
18' - 0"18' - 0"
17' - 0"
16' - 0"
18' - 0"
16' - 0"
LB1
LB2
LB1
LB1
LB1
LB1LB1LB1
LB1
LB1
LB1
LB2
CONTROL
ROOM
H.A.C.
TR
ELECTRICAL
ROOM
ELECTRICAL
ROOM
C1
9' - 0"
X1 8' - 0"
WP2
10' - 0"
WP2
10' - 0"
WP2
a b a b abab
D1
EM-1
EM-1
EM-1
EM-1
1LEA 1HEA
1LLS - 5
1LLS - 3
1HEA - 1
1LLS - 4
1HEA - 1
1LLS - 4
1HEA - 1
1HEA - 1
1HEA - 1 1LLS - 4
1HEA - 1
1HEA - 1
1HEA - 1
1LLS - 4
1HEA - 1
1HEA - 1
1HEA - 1
1HEA - 1
1LLS - 5
1LLS - 5
1HEA - 1
1HEA - 1
1HEA - 2
1HEA - 21HEA - 2
1HEA - 2
1HEA - 21HEA - 2
1HEA - 2
1HEA - 2
1LLS - 3
1HEA - 2
1HEA - 21HEA - 2
1HEA - 2
1HEA - 2
1HEA - 2
1LLS - 3
1LLS - 3
1LLS - 3
1LLS - 3
1HEA - 2 1HEA - 2
1HEA - 2 1LLS - 3
1LLS - 3
1LLS - 3
1LLS - 3
1LLS - 3
1LLS - 3
1LLS - 3
1LLS - 3
1LLS - 4
1LLS - 3
WP2
1LLS - 3
1LLS - 3
1LLS - 3
1HNDP1
1LNA
T-1LNA
A
D
1 32
B
C
A.4
A.6 a b a b a b b b b b a b b bb b a a a b b a b bba b b a b a a b a b b a b a
1LLS - 5
a b a b a ba a
8' - 0"
8' - 0"
7' - 6"
B2
1LLS - 3
X1
8' - 0"
1LLS - 4
12' - 0"
LB1
1HEA - 1
b
C1
1HEA - 1
b
WM
9' - 0"
C1
1HEA - 1
b
WM
6' - 0"
1HEA - 1
C11HEA - 1 b
WM
9' - 0"
C11HEA - 1 b
C2
9' - 0"1LLS - 3
a
C1 b
WM
8' - 0"
1HEA - 1 C1 b
WM
8' - 0"
1HEA - 1
C1 b
WM
8' - 0"
1HEA - 1
C1 b
WM
8' - 0"
1HEA - 1
C1b
WM
8' - 0"
1HEA - 1
TOILET
TYP.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
A u to d e s k D o c s /M a ri o n I
L V
A
N e w E n e rg y C e n te r/
-0
-M
E P
-C e n tr a l.
rv t
/5 /2
:2
:1
P M
E103
FIRST FLOOR - LIGHTING
05/07/2026 MSG DMB
CONSTRUCT NEW
CAMPUS CHILLER PLANT
657A5-21-401
2401 W MAIN ST, MARION IL 62959
CONTRACT
DOCUMENTS 49
MARION VA
MEDICAL
CENTER Approved: Owner
SCALE: 1/4" = 1'-0"
FIRST FLOOR - LIGHTING
PLAN NOTES
SITE KEY PLAN
NEW CHILLER PLANT - BLDG 49
EXISTING CHILLER PLANT - BLDG 49
37MOD-5
MOD-1
MOD-4
MOD-6
NORTH
GENERAL NOTES:
A. ALL FINAL LOCATIONS AND ARRANGEMENTS OF LIGHTING FIXTURES SHALL BE OBTAINED FROM THE ARCHITECTURAL REFLECTED
CEILING PLAN.
B. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A
SEPARATE GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR.
C. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND NORMAL BRANCH WIRING DEVICES SHALL HAVE
DIVIDERS BETWEEN DEVICES.
D. RELOCATE FIXTURES AS REQUIRED TO AVOID CONFLICTS WITH EQUIPMENT, PIPING, AND OTHER TRADES. COORDINATE WITH ALL
TRADES AS REQUIRED.
1. PROVIDE UL 924 LISTED EMERGENCY LIGHTING CONTROL DEVICE FOR LIFE SAFETY LIGHTING. DEVICE SHALL AUTOMATICALLY
OVERRIDE NORMAL CONTROLS TO FULL ILLUMINATION UPON LOSS OF NORMAL POWER.
A
D
632 54
B
C
C2 C2C1
C2 C2C1C1
C2 C2C1C1
C1 C1
MEZZANINE
a b
1LLS - 2 1HEA - 3 1LLS - 2
1LLS - 21HEA - 31HEA - 31LLS - 2
1HEA - 3
1LLS - 2 1HEA - 3 1HEA - 3 1LLS - 2
1HEA - 3
A
D
61 32 54
B
C
A.4
A.6
X1
1LLS - 2
C1
C1C2
1HEA - 3
1LLS - 2 1HEA - 3
C1C1
1HEA - 31HEA - 3
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
A u to d e s k D o c s /M a ri o n I
L V
A
N e w E n e rg y C e n te r/
-0
-M
E P
-C e n tr a l.
rv t
/5 /2
:2
:1
P M
E104
MEZZANINE - LIGHTING
05/07/2026 MSG DMB
CONSTRUCT NEW
CAMPUS CHILLER PLANT
657A5-21-401
2401 W MAIN ST, MARION IL 62959
CONTRACT
DOCUMENTS 49
MARION VA
MEDICAL
CENTER Approved: Owner
SCALE: 1/4" = 1'-0"
MEZZANINE - LIGHTING
SITE KEY PLAN
NEW CHILLER PLANT - BLDG 49
EXISTING CHILLER PLANT - BLDG 49
37MOD-5
MOD-1
MOD-4
MOD-6
NORTH
GENERAL NOTES:
A. ALL FINAL LOCATIONS AND ARRANGEMENTS OF LIGHTING FIXTURES SHALL BE OBTAINED FROM THE ARCHITECTURAL REFLECTED
CEILING PLAN.
B. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A
SEPARATE GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR.
C. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND NORMAL BRANCH WIRING DEVICES SHALL HAVE
DIVIDERS BETWEEN DEVICES.
D. RELOCATE FIXTURES AS REQUIRED TO AVOID CONFLICTS WITH EQUIPMENT, PIPING, AND OTHER TRADES. COORDINATE WITH ALL
TRADES AS REQUIRED.
PLAN NOTES
1. LIGHT FIXTURES IN THIS AREA SHOWN ON FIRST FLOOR LIGHTING PLAN.
2. MOUNT LIGHT FIXTURES FROM STRUCTURAL BEAM. PROVIDE APPROPRIATE SUPPORTS AND HARDWARE FOR A COMPLETE
INSTALLATION.
PCPC
A
D
632 54
B
C
WP1
WP1
WP1
WP1
9' - 0"
9' - 0"
9' - 0"
9' - 0"
WP1
9' - 0"
WP1
9' - 0"
WP1
9' - 0"
1HEA - 21
1HEA - 21
1HEA - 21
1HEA - 21
1HEA - 211HEA - 21
1HEA - 21
A
D
1 32
B
C
A.4
A.6
X2
1LLS - 2
1HNDP1 - 28 1HNDP1 - 28
WP1
9' - 0"
1HEA - 21
WP1
18' - 0"
1HEA - 21
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
A u to d e s k D o c s /M a ri o n I
L V
A
N e w E n e rg y C e n te r/
-0
-M
E P
-C e n tr a l.
rv t
/5 /2
:2
:1
P M
E105
ROOF - LIGHTING
05/07/2026 MSG DMB
CONSTRUCT NEW
CAMPUS CHILLER PLANT
657A5-21-401
2401 W MAIN ST, MARION IL 62959
CONTRACT
DOCUMENTS 49
MARION VA
MEDICAL
CENTER Approved: Owner
SCALE: 1/4" = 1'-0"
ROOF - LIGHTING
PLAN NOTES
SITE KEY PLAN
NEW CHILLER PLANT - BLDG 49
EXISTING CHILLER PLANT - BLDG 49
37MOD-5
MOD-1
MOD-4
MOD-6
NORTH
GENERAL NOTES:
A. ALL FINAL LOCATIONS AND ARRANGEMENTS OF LIGHTING FIXTURES SHALL BE OBTAINED FROM THE ARCHITECTURAL REFLECTED
CEILING PLAN.
B. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE NO MORE THAN THREE CIRCUITS. EACH BRANCH CIRCUIT HOMERUN SHALL HAVE A
SEPARATE GREEN INSULATED EQUIPMENT GROUNDING CONDUCTOR.
C. MULTI-GANG BACKBOXES FOR DIFFERENT VOLTAGES AND TYPES OF EMERGENCY AND NORMAL BRANCH WIRING DEVICES SHALL HAVE
DIVIDERS BETWEEN DEVICES.
1. PROVIDE SPRING WOUND TIMER TO CONTROL WP1 ROOF FIXTURES.
2. PROVIDE SPECIFICATION GRADE 277V PHOTOCELL ON ROOF FOR SITE LIGHTING CONTROL. CONNECT TO
LIGHTING CONTROL PANEL AND LIGHTING CONTACTOR.
3. SURFACE MOUNTED LIGHTING. COORDINATE CONDUIT ROUTING PRIOR TO ROUGH-IN.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
A u to d e s k D o c s /M a ri o n I
L V
A
N e w E n e rg y C e n te r/
-0
-M
E P
-C e n tr a l.
rv t
/5 /2
:2
:1
P M
E500
ELECTRICAL SCHEDULES
05/07/2026 MSG DMB
CONSTRUCT NEW
CAMPUS CHILLER PLANT
657A5-21-401
2401 W MAIN ST, MARION IL 62959
CONTRACT
DOCUMENTS 49
MARION VA
MEDICAL
CENTER Approved: Owner
NOTES:
1. REFER TO SINGLE LINE FOR WIRE SIZING.
2. POWER FOR THE INDOOR UNIT IS FED THROUGH THE OUTDOOR UNIT.
PROVIDE INTERCONNECTING WIRE AS REQUIRED FOR A COMPLETE AND
OPERATION INSTALLATION.
3.PROVIDE MOTOR STARTER SUITABLE FOR 50 HP MOTOR, WITH OVERLOAD
PROTECTION. STARTER SHALL BE ACROSS-THE-LINE UNLESS OTHERWISE
INDICATED. PROVIDE SOFT STARTER WHERE REQUIRED TO LIMIT INRUSH
CURRENT.
MOTORS, STARTERS, DISCONNECTS & CONTROLS
MARK
MOTOR STARTER DISCONNECT MEANS CONTROL FEEDER
S E
E N
O T
E
NAMEPLATE
CHARACTERISTICS LOCATION
N E
M A
S
IZ
E
TYPE LOCATION
F U
R N
IS
H
E D
B Y
TYPE LOCATION
F U
R N
IS
H
E D
B Y
I N
T E
R L O
C K
W
IT
H M
O T
O R
N O
B
Y E
.C
M A
N U
A L A
T S
T A
R T
E R
I N
T E
G R
A L
W
IT
H E
Q U
IP
M
E N
T
F U
R N
IS
H
E D
B Y
S E
E N
O T
E
N U
M B
E R
O F
C O
N D
U C
T O
R S
W
IR
E S
IZ
E
G R
O U
N D
S
IZ
E
C O
N D
U
IT
S
IZ
E
H O
R S
E P
O W
E R
H
P
L O
A D k V
A
V
-1 P
H
V
-1 P
H
V
-3 P
H
V
-1 P
H
V
-3 P
H
V
-1 P
H
V
-1 P
H
V
-3 P
H
R O
O M
N U
M B
E R
ROOM NAME M
A
N U
A L
M A
G N
E T
IC
E C
M
E Q
U
IP
M E
N T
C O
N T
R O
L P
A N
E L
V F
D
S E
E N
O T
E
N E
A R
M O
T O
R
M O
T O
R C
O N
T C
E N
T E
R
E Q
U
IP
C O
N T
P A
N E
L
R O
O M
N U
M B
E R
S E
E N
O T
E
D
IS
C S
W
IT
C H
M A
N U
A L S
T A
R T
E R
R E
C E
P T
A C
L E
F E
E D
E R
S W
O R
B R
E A
K E
R
N E
M A
T Y
P E
D
IS
C S
IZ
E
F U
S E
S
IZ
E
N E
A R
M O
T O
R
M O
T O
R C
O N
T C
E N
T E
R
E Q
U
IP
C O
N T
P A
N E
L
P A
N E
L B
O A
R D
S E
E N
O T
E
AC-1 AIR CONDITIONING UNIT 0.5 0.1 ● ● ● DIV 23 ● 1 30 NF ● DIV 26 ● DIV 23 - - - - 2
AC-2 AIR CONDITIONING UNIT 0.5 0.1 ● ● ● DIV 23 ● 1 30 NF ● DIV 26 ● DIV 23 - - - - 2
CU-1 CONDENSING UNIT 18 FLA 3.83 ● ROOF ● ● DIV 23 ● 3R 30 NF ● DIV 26 ● DIV 23 2 10 10 0.75"
CU-2 CONDENSING UNIT 18 FLA 3.83 ● ROOF ● ● DIV 23 ● 3R 30 NF ● DIV 26 ● DIV 23 2 10 10 0.75"
AHU-1-EH ELECTRIC HEATING COIL 37.56 ● 200 MEZZANINE DIV 23 ● 1 60 60 ● DIV 26 ● DIV 23 3 4 10 1.25"
AHU-1-FS AIR HANDLER FANS (4) 6 14.3 ● 200 MEZZANINE ● ● DIV 23 ● - - - ● DIV 26 ● DIV 23 3 12 12 0.75"
AHU-2-EH ELECTRIC HEATING COIL 10.43 ● 200 MEZZANINE DIV 23 ● 1 30 20 ● DIV 26 ● DIV 23 3 12 12 0.75"
AHU-2-FS AIR HANDLER FANS (2) 6 6.98 ● 200 MEZZANINE ● ● DIV 23 ● - - - ● DIV 26 ● DIV 23 3 12 12 0.75"
BSP-1 BASIN SWEEPER PUMP 3 13.58 ● ROOF ● ● DIV 23 ● 3R 60 NF ● DIV 26 ● DIV 23 - - - - 1
CDWF-1 MEDIA FILTER PUMP 20 37.69 ● 100 CHILLER PLANT ● ● DIV 23 ● 1 100 NF ● DIV 26 ● DIV 23 - - - - 1
CH-1 CHILLER 356.66 ● 100 CHILLER PLANT ● ● MFG ● - - - ● MFG ● DIV 23 - - - - 1
CH-2 CHILLER 356.66 ● 100 CHILLER PLANT ● ● MFG ● - - - ● MFG ● DIV 23 - - - - 1
CH-3 CHILLER 0 ● 100 CHILLER PLANT ● ● MFG ● - - - ● MFG ● DIV 23 - - - - 1
CDWP-1 CONDENSER WATER PUMP 50 54.04 ● 100 CHILLER PLANT 3 ● ● 3 DIV 26 ● 1 100 NF ● 3 DIV 26 ● DIV 23 - - - - 1
CDWP-2 CONDENSER WATER PUMP 50 0 ● 100 CHILLER PLANT 3 ● ● 3 DIV 26 ● 1 100 NF ● 3 DIV 26 ● DIV 23 - - - - 1
CDWP-3 CONDENSER WATER PUMP 50 54.04 ● 100 CHILLER PLANT 3 ● ● 3 DIV 26 ● 1 100 NF ● 3 DIV 26 ● DIV 23 - - - - 1
BH-1 BASIN HEATER 28.9 FLA 24.03 ● ROOF ● ● DIV 23 ● 3R 60 NF ● DIV 26 ● DIV 23 - - - - 1
BH-2 BASIN HEATER 28.9 FLA 0 ● ROOF ● ● DIV 23 ● 3R 60 NF ● DIV 26 ● DIV 23 - - - - 1
BH-3 BASIN HEATER 28.9 FLA 24.03 ● ROOF ● ● DIV 23 ● 3R 60 NF ● DIV 26 ● DIV 23 - - - - 1
CT-1 COOLING TOWER 40 43.23 ● ROOF ● DIV 26 ● 3R 100 NF ● DIV 26 ● DIV 23 - - - - 1
CT-2 COOLING TOWER 40 0 ● ROOF ● DIV 26 ● 3R 100 NF ● DIV 26 ● DIV 23 - - - - 1
CT-3 COOLING TOWER 40 43.23 ● ROOF ● DIV 26 ● 3R 100 NF ● DIV 26 ● DIV 23 - - - - 1
EF-1 EXHAUST FAN 5 6.32 ● ROOF ● ● DIV 26 ● 3R 30 NF ● DIV 23 ● DIV 23 3 12 12 0.75"
EF-2 EXHAUST FAN .5 1.18 ● ROOF ● ● DIV 23 ● - - - ● MFG ● DIV 23 2 12 12 0.75"
EF-3 EXHAUST FAN 1.5 2.49 ● ROOF ● ● DIV 26 ● 3R 30 NF ● DIV 23 ● DIV 23 3 12 12 0.75"
EH-1 ELECTRICAL HOIST 5 6.32 ● ROOF DIV 23 ● 3R 30 NF ● DIV 26 ● DIV 23 3 10 10 0.75"
EH-2 ELECTRICAL HOIST 5 6.32 ● ROOF DIV 23 ● 1 30 NF ● DIV 26 ● DIV 23 3 10 10 0.75"
PCHWP-1 PRI CHILLED WATER PUMP 20 17.46 ● 100 CHILLER PLANT ● ● DIV 26 ● 1 60 NF ● DIV 26 ● DIV 23 - - - - 1
PCHWP-2 PRI CHILLED WATER PUMP 20 0 ● 100 CHILLER PLANT ● ● DIV 26 ● 1 60 NF ● DIV 26 ● DIV 23 - - - - 1
PCHWP-3 PRI CHILLED WATER PUMP 20 17.46 ● 100 CHILLER PLANT ● ● DIV 26 ● 1 60 NF ● DIV 26 ● DIV 23 - - - - 1
RF-2 RETURN FAN 2 2.49 ● 200 MEZZANINE ● ● DIV 23 ● - - - ● DIV 26 ● DIV 23 3 12 12 0.75"
SCHWP-1 SEC CHILLED WATER PUMP 60 64.02 ● 100 CHILLER PLANT ● ● DIV 26 ● 1 200 NF ● DIV 26 ● DIV 23 - - - - 1
SCHWP-2 SEC CHILLED WATER PUMP 60 0 ● 100 CHILLER PLANT ● ● DIV 26 ● 1 200 NF ● DIV 26 ● DIV 23 - - - - 1
SCHWP-3 SEC CHILLED WATER PUMP 60 64.02 ● 100 CHILLER PLANT ● ● DIV 26 ● 1 200 NF ● DIV 26 ● DIV 23 - - - - 1
SP-1A SUMP PUMP 0.5 2.16 ● 100 CHILLER PLANT ● ● MFG ● - - - ● MFG ● DIV 22 3 12 12 0.75"
SP-1B SUMP PUMP 0.5 2.16 ● 100 CHILLER PLANT ● ● MFG ● - - - ● MFG ● DIV 22 3 12 12 0.75"
UH-1 UNIT HEATER 7.5 ● 100 CHILLER PLANT ● ● MFG ● - - - ● DIV 26 ● DIV 23 3 12 12 0.75"
UH-2 UNIT HEATER 7.5 ● 100 CHILLER PLANT ● ● MFG ● - - - ● DIV 26 ● DIV 23 3 12 12 0.75"
UH-3 UNIT HEATER 7.5 ● ● ● MFG ● - - - ● DIV 26 ● DIV 23 3 12 12 0.75"
UH-4 UNIT HEATER 7.5 ● 100 CHILLER PLANT ● ● MFG ● - - - ● DIV 26 ● DIV 23 3 12 12 0.75"
UH-5 UNIT HEATER 2 ● 104 TOILET ● ● MFG ● ● MFG ● DIV 23 2 12 12 0.75"
VAV-1 VAV BOX 6 ● 106 ELECTRICAL ROOM ● ● DIV 23 ● 1 30 NF ● DIV 26 ● DIV 23 3 12 12 0.75"
VAV-2 VAV BOX 7.48 ● 105 ELECTRICAL ROOM ● ● DIV 23 ● 1 30 NF ● DIV 26 ● DIV 23 3 12 12 0.75"
VAV-3 VAV BOX 1 ● 101 CONTROL ROOM ● ● DIV 23 ● 1 30 NF ● DIV 26 ● DIV 23 2 12 12 0.75"
DWH-1 WATER HEATER 4.49 ● 103 H.A.C. DIV 22 ● 1 30 NF ● DIV 26 ● DIV 22 2 10 10 0.75"
356.66
54.04
24.03
43.23
17.46
64.02
CCT.
NO.
FIXTURES TYPE(S)
CONTROLLED
*INDICATES SPARE FOR
FUTURE USE
* A.
B.
C.
LEAVE SLACK IN ALL CONDUCTORS SUCH THAT THEY MAY
BE MOVED FROM ONE RELAY TO ANOTHER AS REQUIRED.
EXTERIOR LIGHTING TO BE AUTOMATICALLY CONTROLLED
BY TIME-OF-DAY SCHEDULE AND PHOTOCELL. OPERATION
INTENT IS FOR LIGHT POLES COME ON AT DUSK AND TURN
OFF AT DAWN. ALSO FOR TIME-OF-DAY CONTROL TO DIM TO
50% AT MIDNIGHT UNTIL 6AM. INTEGRAL LIGHT POLE MOTION
SENSORS TO DIM THE POLE LIGHTS WHEN NO MOTION IS
DETECTED IN THE PARKING LOT AREA. REFER TO LIGHTING
CONTROL DETAILS AND SEQUENCE OF OPERATION
SCHEDULE FOR ADDITIONAL OPERATION INFORMATION.
DEVICES SHALL BE CONNECTED AND WIRED PER
MANUFACTURERS RECOMMENDATIONS AND WIRING
INSTRUCTIONS. PROVIDE ALL RELAYS, POWER PACKS,
SENSORS, AND MISCELLANEOUS DEVICES FOR A COMPLETE
AND OPERABLE SYSTEM.
GENERAL NOTES
NEW SITE LTG (PL1,PL2)
LCP-1
LCP-1 - 1
PHOTOCELL
(EXTERIOR)
LV
1.
2.
LIGHTING CONTROL RELAY(S) IN A NEMA 1 ENCLOSURE BY
E.C. ELECTRONIC LIGHTING CONTROLLER FOR CONTROL OF
LIGHTING CIRCUITS AS INDICATED. PROVIDE QUANTITY OF
RELAYS AS INDICATED.
EQUAL BY HUBBELL, LEVITON, SQUARE-D, NLIGHT,
CRESTRON OR LC&D.
DETAIL NOTES
1 2
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
SEE FIXTURE SCHEDULE FOR POLE AND FIXTURE ASSEMBLY.
ANCHOR BOLTS BY POLE SUPPLIER, CONNECT TO REBAR VIA
WIRE TIES.
CHAMFERED EDGE.
FINISH GRADE, COMPACT TO 95%.
SIX #4 REINFORCING BARS VERTICALLY ON #3 STIRRUPS AT
18" O.C.
PVC CONDUIT, SCHEDULE 40.
RIGID GALVANIZED STEEL CONDUIT.
GROUND ROD.
1/2" PVC GROUND CONDUCTOR SLEEVE WITH #8 GROUND
CONDUCTOR.
BASE PLATE, LEVELING NUTS, BASE GROUT.
EXOTHERMICALLY WELDED GROUND CONNECTION.
LIGHTNING ARRESTOR.
HANDHOLE.
DETAIL NOTES
2'- 6" 1'-
6" 2" .
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
C :\U se rs
\d m br
\A pp D at a\
Lo ca l\A ut od es k\ R ev it\
Au to de sk
R ev it
\C ol la bo ra tio nC ac he
\L Q
C 3M
U F8
4E
LP
\5 d1 ac
3- 2a e8 -4
5-b5 5f
-c ff8
3c 3d
3a
\e e-fd
-4 d-ab
-2 dc f.r vt
5/
/2
4:
:4
PM
E600
ELECTRICAL SCHEDULES
05/07/2026 MSG DMB
CONSTRUCT NEW
CAMPUS CHILLER PLANT
657A5-21-401
2401 W MAIN ST, MARION IL 62959
CONTRACT
DOCUMENTS 49
MARION VA
MEDICAL
CENTER Approved: Owner
NOTES:
1.
LUMINAIRES
MARK IMAGE
LAMPS
L O
AD
(V
A)
F
IX
TU
R
E
VO
LT
AG
E
Manufacturer CATALOG NO. DESCRIPTION
TRIM COLOR MOUNTING SIZE
S
EE
N O
TE
D
EL
IV
ER
ED
L
U M
EN
S
COLOR W
H
IT
E
B
LA
C K
A
LU
M
IN
U M
B R
O N
ZE
S
TA
N D
AR
D
S
EE
N O
TE
S-SURFACE
R-RECESSED
SM-STEM MTD
WM-WALL MTD
C-CHAIN MTD
UC-UNDER CAB
CS-CEIL SURFACE D
IA
M
ET
ER
W
ID
TH
L
EN
G
TH
D
EP
TH
B1 2000 4000K 15 277 LITHONIA OR EQUAL CPX-2X2-2000LM-80CRI-40K-SWL-MIN1-ZT-MVOLT 2X2 LED FLAT PANEL R 24" 24" 6"
B2 2000 4000K 15 120 LITHONIA OR EQUAL CPX-2X2-2000LM-80CRI-40K-SWL-MIN1-ZT-MVOLT 2X2 LED FLAT PANEL R 24" 24" 6"
C1 4000 4000K 25 277 LITHONIA OR EQUAL CLX-L48-4000LM-SEF-FDL-WD-MVOLT-GZ1-40K-80CRI-WH 1X4 LED INDUSTRIAL STRIP <V
AR
IE
S>
<V
AR
IE
S>
<V
AR
IE
S>
<V
AR
IE
S>
<V
AR
IE
S>
C/WM <VARI
ES>
<VARIE
S>
4"
C2 4000 4000K 25 120 LITHONIA OR EQUAL CLX-L48-4000LM-SEF-FDL-WD-MVOLT-GZ1-40K-80CRI-WH 1X4 LED INDUSTRIAL STRIP ● C/WM 4" 48" 4"
D1 1400 4000K 28 120 FINELITE OR EQUAL S17 LED-WM-VCF-PF-4'-B-840-96-277-FC-10%-SW VANITY OVER SINK S 6" 24" 3"
EM-1 1 120 LITHONIA OR EQUAL EU2C M6 EMERGENCY LIGHT S 5.375" 13" 5.75"
LB1 15000 4000K 100 277 LITHONIA OR EQUAL MLX-L8-15000LM-80CRI-40K-WGDL-MD-MIN10-ZT-MVOLT-WH LED LOW BAY FIXTURE ● C 12" 96" 5.5"
LB2 15000 4000K 100 120 LITHONIA OR EQUAL MLX-L8-15000LM-80CRI-40K-WGDL-MD-MIN10-ZT-MVOLT-WH LED LOW BAY FIXTURE ● C 12" 96" 5.5"
PL1 11296 4000K 93 277 LITHONIA OR EQUAL DSXO LED P4 40K 70CRIT4M XVOLT RPA PIR DMG EGSR DDBXD 20' LED POLE FIXTURE WITH TYPE 4 DISTRIBUTION POLE 12" 17.125" 6" 1
PL2 11296 4000K 93 277 LITHONIA OR EQUAL DSXO LED P4 40K 70CRIT4M XVOLT RPA PIR DMG EGSR DDBXD 20' LED TWO-HEAD POLE FIXTURE WITH TYPE 4 DISTRIBUTION POLE 12" 17.125" 6" 1
PL3 11296 4000K 93 480 LITHONIA OR EQUAL DSXO LED P4 40K 70CRIT4M XVOLT RPA PIR DMG EGSR DDBXD 20' LED TWO-HEAD POLE FIXTURE WITH TYPE 4 DISTRIBUTION POLE 12" 17.125" 6" 1
PL4 11296 4000K 93 480 LITHONIA OR EQUAL DSXO LED P4 40K 70CRIT4M XVOLT RPA PIR DMG EGSR DDBXD 20' LED POLE FIXTURE WITH TYPE 4 DISTRIBUTION POLE 12" 17.125" 6" 1
WP1 4500 4000K 35 277 LITHONIA OR EQUAL WDGE2 LED-P2-40K -70CRI-R4-MVOLT-SRM-PE-DMG-PIR1FC3V-DDBXD LED EXTERIOR WALL PACK ● WM 9" 13.5"
WP2 14000 4000K 106 120 LITHONIA OR EQUAL WDGE4 LED-P2-40K -70CRI-R4-MVOLT-SRM-PE-DMG-PIR1FC3V-DDBXD LED EXTERIOR WALL PACK ● WM 9" 13.5"
X1 5 120 LITHONIA OR EQUAL LED DIE CAST EXIT SIGN ● WM/CS 9" 13" 2.375"
X2 5 120 LITHONIA OR EQUAL LED EXTERIOR EXIT SIGN ● WM 9" 13" 2.375"
NOTES:
1.
LIGHTING CONTROL SEQUENCE OF OPERATIONS
CONTROL
NUMBER TYPICAL CONTROL TYPE OR SPACE NAME
OCCUPANCY SENSOR TIME CLOCK WALL SWITCH DAYLIGHT SENSOR INTEGRATION POINTS
S
EE
N O
TE
DETAIL
NUMBER V
AC
AN
C Y
M O
D E
(M
AN
U
AL
O N
O C
C U
PA
N
C Y
M O
D E
(A U
TO
O
N
S
EN
SO
R
T
IM
E O
U T
PE
R
IO
D
(I N
M
IN
U
TE
S)
H
IG
H
LO
W
O
PE
R
AT
IO
N
: O C
C U
PI
ED
: 1
VA
C
AN
T:
0%
S C
H
ED
U
LE
D O
N A
T
S C
H
ED
U
LE
D O
FF
A
T
O C
C U
PI
ED
T
IM
E
ST
AR
T
U N
O C
C U
PI
ED
T
IM
E
ST
AR
T
A
FT
ER
H
O U
R S
O
VE
R R
ID
E
SW
IT
C H
(2 H
O U
R S)
O N
O
FF
O
N
LY
D
IM
M
ER
S W
IT
C
H
K
EY
S W
IT
C
H
S C
EN
E
SW
IT
C H
G R
AP
H
IC
AL
W
AL
L
ST
AT
IO
N
IN
D
O O
R
O N
O
FF
O
N
LY
IN
D
O O
R
D
IM
M
IN
G
L
IG
H T
LE
VE
L M
AI
N
TA
IN
ED
A
T
(IN
F O
O
TC
AN
D
LE
S
'-6 " A
.F .F
E
XT
ER
IO
R P
H O
TO
C
EL
L
- O N
O
FF
O C
C U
PA
N
C Y
ST
AT
U S
(B
IN
AR
Y
IN
PU
T
- R
EA
D
O N
LY
O C
C U
PI
ED
U
N O
C C
U
PI
ED
D
IM
M
IN
G O
U
TP
U T
LE
VE
L (A
N
AL
O G
V
AL
U E
- R
EA
D
W R
IT
E
- 0 -1
R
EL
AY
S
TA
TU
S (B
IN
AR
Y
VA
LU
E
- R
EA
D
W R
IT
E
- O N
O
FF
M
EA
SU
R
ED
L
IG
H
T
LE
VE
L
(A N
AL
O
G
IN
PU
T
- 0 -2
FC
1 ON/OFF ● N/A
2 DIMMER ●
3 VACANCY SENSING - SINGLE ZONE ● 15 ●
4 OCCCANCY SENSING - SINGLE ZONE ● 15 ● YES 25% YES
6 SITE LIGHTING ● 30 DUSK DAWN 50% YES 1
SCALE: NONE
EXTERIOR AUTOMATIC LIGHTING CONTROLS1
SCALE: NONE
PL1, PL2, & PL3 POLE BASE DETIAL2
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
VA FORM 08 - 6231
A
FULLY SPRINKLERED
U.S. Department of Veterans Affairs
B
C
D
E
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
Date:Revisions:No.
C :\U se rs
\d m br
\A pp D at a\
Lo ca l\A ut od es k\ R ev it\
Au to de sk
R ev it
\C ol la bo ra tio nC ac he
\L Q
C 3M
U F8
4E
LP
\5 d1 ac
3- 2a e8 -4
5-b5 5f
-c ff8
3c 3d
3a
\e e-fd
-4 d-ab
-2 dc f.r vt
5/ 5/
1:
:5
PM
E601
PANEL SCHEDULES
05/07/2026 MSG DMB
CONSTRUCT NEW
CAMPUS CHILLER PLANT
657A5-21-401
2401 W MAIN ST, MARION IL 62959
CONTRACT
DOCUMENTS 49
MARION VA
MEDICAL
CENTER Approved: Owner
98.26 kVA 107.65 kVA (129 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes:
Special Circuit Breaker (SCB) Types: GF=GFCI Breaker, ST=Shunt Trip Breaker, AF=AFCI Breaker, GP=GFPE Breaker
Total Est. Demand: 129 A Total Conn.: 118 A
Resistive Heat 5,000 VA 100.00% 5,000 VA Total Est. Demand: 107.65 kVA Motor 90,729 VA 110.35% 100,119 VA Total Conn. Load: 98.26 kVA Lighting 2,530 VA 100.00% 2,530 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Load: 34.68 kVA 30.83 kVA 32.74 kVA 41 Spare 20 A 1 0 0 1 20 A Spare 42 39 Spare 20 A 1 0 0 1 20 A Spare 40 37 Spare 20 A 1 0 0 1 20 A Spare 38 35 Spare 20 A 1 0 0 1 20 A Spare 36 33 Spare 20 A 1 0 0 1 20 A Spare 34 31 Spare 20 A 1 0 2.106 -- -- -- -- 32 29 Spare 20 A 1 0 2.106 -- -- -- -- 30
27 -- -- -- -- 2.106 2.106 3 20 A EH-2 28
25 -- -- -- -- 2.106 0.831 -- -- -- -- 26
23 EH-1 20 A 3 2.106 0.831 -- -- -- -- 24
21 Lighting 20 A 1 0.315 0.831 3 15 A EF-3 22
19 HEAT TRACE GP 30 A 1 2.5 2.106 -- -- -- -- 20
17 HEAT TRACE GP 30 A 1 2.5 2.106 -- -- -- -- 18
15 -- -- -- -- 3.478 2.106 3 20 A EF-1 16
13 -- -- -- -- 3.478 2.328 -- -- -- -- 14
11 AHU-2-EH 20 A 3 3.478 2.328 -- -- -- -- 12
9 -- -- -- -- 12.521 2.328 3 15 A AHU-2-FS 10
7 -- -- -- -- 12.521 4.767 -- -- -- -- 8
5 AHU-1-EH 60 A 3 12.521 4.767 -- -- -- -- 6
3 LGT ELECTRICAL... 20 A 1 0.275 4.767 3 20 A AHU-1-FS 4
1 LGT CHILLER PLANT... 20 A 1 1.575 0.365 1 20 A LGT CONTROL ROOM... 2
CKT Circuit Description
SCB
Type Trip Poles
A B C Poles Trip
SCB
Type Circuit Description CKT
Voltage: 480Y/277V-3PH-4W Mains Rating: 250 A Supply From: E-EQ-1HDP2 Enclosure: Type 1 Mains Type: MLO
Location: ELECTRICAL ROOM 105 Mounting: Surface A.I.C. Rating: 42KAIC Panel: 1HEA Construction Phase:
202.77 kVA 218.78 kVA (263 A)
TOTAL CONNECTED ESTIMATED DEMAND
NOTES: 1. REFER TO SINGLE LINE FOR OVER CURRENT PROTECTION AND WIRE SIZE INFROMATION.
2. NON-TYPICAL N+1 LOAD SHALL ONLY BE ENERGIZED WHEN THE CORRESPONDING PRIMARY EQUIPMENT IS NOT
ENERGIZED.
Total Est. Demand: 263 A Total Conn.: 244 A
Total Est. Demand: 218.78 kVA Total Conn. Load: 202.77 kVA
Motor 202,775 VA 107.89% 218,779 VA Load Classification Connected... Demand Factor Estimated... Panel Totals 13 Spare 0.00 kVA 200 A 3 200 A LSI 12 Spare 0.00 kVA 200 A 3 200 A LSI 11 SPD 0.00 kVA 60 A 3 60 A TM - - - - 1 10 BH-2 0.00 kVA 40 A 3 40 A TM - - - - 1 9 BH-1 24.03 kVA 40 A 3 40 A TM - - - - 1 8 CDWP-2 0.00 kVA 150 A 3 100 A LSI - - - - 1,2 7 SCHWP-2 0.00 kVA 150 A 3 125 A LSI - - - - 1,2 6 PCHWP-2 0.00 kVA 100 A 3 60 A LSI - - - - 1,2 5 CT-2 0.00 kVA 100 A 3 90 A LSI - - - - 1,2 4 CDWP-1 54.04 kVA 150 A 3 100 A LSI - - - - 1 3 SCHWP-1 64.02 kVA 150 A 3 125 A LSI - - - - - 2 PCHWP-1 17.46 kVA 100 A 3 60 A LSI - - - - 1 1 CT-1 43.23 kVA 100 A 3 90 A LSI - - - - 1
CKT
CIRCUIT
DESCRIPTION
APPROX.
CONNECTED
LOAD
FRAME
SIZE POLES
TRIP
SETTING
BREAKER
TYPE
NUMBER OF
CONDUCTORS
WIRE
SIZE
GROUND
SIZE
CONDUIT
SIZE
SEE
NOTE
Feeder Size: REFER TO SINGLE LINE Spec. Ref. #: 26 24 16 Voltage: 480Y/277V-3PH-4W Mains Rating: 600 A
Supply From: EQ-ATS-2 Enclosure: Type 1 Mains Type: MLO Location: ELECTRICAL ROOM 105 Mounting: Surface A.I.C. Rating: REFER TO SINGLE LINE
DISTRIBUTION PANEL:E-EQ-1HDP1
390.27 kVA 406.27 kVA (489 A)
TOTAL CONNECTED ESTIMATED DEMAND
NOTES: 1. REFER TO SINGLE LINE FOR WIRE SIZING.
Resistive Heat 5,000 VA 100.00% 5,000 VA Receptacle 8,460 VA 100.00% 8,460 VA Total Est. Demand: 489 A Power 18,088 VA 100.00% 18,088 VA Total Conn.: 469 A Motor 356,187 VA 104.49% 372,191 VA Total Est. Demand: 406.27 kVA Lighting 2,530 VA 100.00% 2,530 VA Total Conn. Load: 390.27 kVA Equipment 0 VA 0.00% 0 VA Load Classification Connected... Demand Factor Estimated... Panel Totals 12 Spare 0.00 kVA 400 A 1 20 A 11 Spare 0.00 kVA 400 A 1 20 A 10 SPD 0.00 kVA 400 A 1 60 A 9 CDWF-1 37.69 kVA 100 A 3 80 A LSI - - - - 1 8 BSP-1 13.58 kVA 40 A 3 40 A TM - - - - 1 7 BH-3 24.03 kVA 40 A 3 40 A TM - - - - 1 6 T-1LEA 37.97 kVA 125 A 3 125 A TM - - - - 1 5 1HEA 98.26 kVA 250 A 3 250 A 100% - - - - 1 4 CDWP-3 54.04 kVA 150 A 3 100 A LSI - - - - 1 3 SCHWP-3 64.02 kVA 150 A 3 125 A LSI - - - - 1 2 PCHWP-3 17.46 kVA 100 A 3 60 A LSI - - - - 1 1 CT-3 43.23 kVA 100 A 3 90 A LSI - - - - 1
CKT
CIRCUIT
DESCRIPTION
APPROX.
CONNECTED
LOAD
FRAME
SIZE POLES
TRIP
SETTING
BREAKER
TYPE
NUMBER OF
CONDUCTORS
WIRE
SIZE
GROUND
SIZE
CONDUIT
SIZE
SEE
NOTE
Feeder Size: REFER TO SINGLE LINE Spec. Ref. #: 26 24 16 Voltage: 480Y/277V-3PH-4W Mains Rating: 600 A
Supply From: EQ-ATS-5 Enclosure: Type 1 Mains Type: MLO Location: ELECTRICAL ROOM 105 Mounting: Surface A.I.C. Rating: REFER TO SINGLE LINE
DISTRIBUTION PANEL:E-EQ-1HDP2
713.33 kVA 713.33 kVA (858 A)
TOTAL CONNECTED ESTIMATED DEMAND
NOTES: 1. REFER TO SINGLE LINE FOR WIRE INFORMATION.
2. NON-TYPICAL N+1 LOAD SHALL ONLY BE ENERGIZED WHEN THE CORRESPONDING PRIMARY EQUIPMENT IS NOT
ENERGIZED.
Total Est. Demand: 858 A Total Conn.: 858 A
Total Est. Demand: 713.33 kVA Total Conn. Load: 713.33 kVA
HVAC 713,328 VA 100.00% 713,328 VA
Load Classification Connected... Demand Factor Estimated... Panel Totals 4 SPD 0.00 kVA 400 A 1 60 A TM 3 EQ-ATS-4 0.00 kVA 800 A 3 800 A LSIA 1,2 2 EQ-ATS-3 356.66 kVA 800 A 3 800 A LSIA 1 1 EQ-ATS-1 356.66 kVA 800 A 3 800 A LSIA 1
CKT
CIRCUIT
DESCRIPTION
APPROX.
CONNECTED
LOAD
FRAME
SIZE POLES
TRIP
SETTING
BREAKER
TYPE
NUMBER OF
CONDUCTORS
WIRE
SIZE
GROUND
SIZE
CONDUIT
SIZE
SEE
NOTE
Feeder Size: REFER TO SINGLE LINE Spec. Ref. #: 26 24 16 Voltage: 480Y/277V-3PH-4W Mains Rating: 1200 A
Supply From: Enclosure: Type 1 Mains Type: MLO Location: ELECTRICAL ROOM 105 Mounting: Surface A.I.C. Rating: REFER TO SINGLE LINE
DISTRIBUTION PANEL:GP-1HDP1
593.04 kVA 609.04 kVA (733 A)
TOTAL CONNECTED ESTIMATED DEMAND
NOTES: 1. REFER TO SINGLE LINE FOR WIRE INFORMATION.
2. NON-TYPICAL N+1 LOAD SHALL ONLY BE ENERGIZED WHEN THE CORRESPONDING PRIMARY EQUIPMENT IS NOT
ENERGIZED.
Resistive Heat 5,000 VA 100.00% 5,000 VA Receptacle 8,460 VA 100.00% 8,460 VA Total Est. Demand: 733 A Power 18,088 VA 100.00% 18,088 VA Total Conn.: 713 A Motor 558,962 VA 102.86% 574,966 VA Total Est. Demand: 609.04 kVA Lighting 2,530 VA 100.00% 2,530 VA Total Conn. Load: 593.04 kVA Equipment 0 VA 0.00% 0 VA Load Classification Connected... Demand Factor Estimated... Panel Totals 3 SPD 0.00 kVA 60 A 1 60 A TM - - - - - 2 EQ-ATS-5 390.27 kVA 600 A 3 600 A LSIA - - - - - 1 EQ-ATS-2 202.77 kVA 600 A 3 600 A LSIA - - - - -
CKT
CIRCUIT
DESCRIPTION
APPROX.
CONNECTED
LOAD
FRAME
SIZE POLES
TRIP
SETTING
BREAKER
TYPE
NUMBER OF
CONDUCTORS
WIRE
SIZE
GROUND
SIZE
CONDUIT
SIZE
SEE
NOTE
Feeder Size: REFER TO SINGLE LINE Spec. Ref. #: 26 24 16 Voltage: 480Y/277V-3PH-4W Mains Rating: 1000 A
Supply From: Enclosure: Type 1 Mains Type: MLO Location: ELECTRICAL ROOM 105 Mounting: Surface A.I.C. Rating: REFER TO SINGLE LINE
DISTRIBUTION PANEL:GP-1HDP2
37.97 kVA 38.93 kVA (108 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes: 1. THIS PANEL SHALL BE PROVIDED WITH A DOUBLE SET OF LUGS.
Special Circuit Breaker (SCB) Types: GF=GFCI Breaker, ST=Shunt Trip Breaker, AF=AFCI Breaker, GP=GFPE Breaker
Total Est. Demand: 108 A Receptacle 8,460 VA 100.00% 8,460 VA Total Conn.: 105 A Power 18,088 VA 100.00% 18,088 VA Total Est. Demand: 38.93 kVA Motor 11,420 VA 108.38% 12,377 VA Total Conn. Load: 37.97 kVA Equipment 0 VA 0.00% 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Panel Loads: 11.00 kVA 13.11 kVA 13.86 kVA Feed Thru Lugs Loads: 4.07 kVA 4.23 kVA 3.77 kVA
This Panel Loads: 6.93 kVA 8.88 kVA 10.09 kVA
41 ACTUATOR VAVLE 20 A 1 1.2 1.2 1 20 A ACTUATOR VAVLE 42
39 ACTUATOR VAVLE 20 A 1 0.8 1.2 1 20 A ACTUATOR VAVLE 40
37 -- -- -- -- 0.416 1.6 1 20 A ACTUATOR VAVLE 38
35 -- -- -- -- 0.416 0.3 1 20 A ACTUATOR VAVLE 36
33 SP-1A & SP-1B 20 A 3 0.416 0.54 1 20 A FLOW METER 34
31 AHU-2 LGT 20 A 1 0.18 1.914 -- -- -- -- 32
29 EF-2 15 A 1 1.176 1.914 2 25 A AC-2/CU-2 30
27 DP CNTR PNL 30 A 1 0.2 0.9 1 20 A FLOW METER 28
25 R. ROOF 20 A 1 0.36 0.18 1 20 A BAS CNTR 26
23 GATE CONTROL 20 A 1 0.18 0.18 1 20 A CT CELL 24
21 AHU-1 LGT 20 A 1 0.18 0.4 1 20 A FLOW METER 22
19 R TR 102 20 A 1 0.36 0.54 1 20 A R. MEZZANINE 200 20
17 -- -- -- -- 0.06 0.36 1 20 A R TR 102 18
15 -- -- -- -- 0.06 0.72 1 20 A R TR 102 16
13 R. TR 102 20 A 3 0.06 0.06 -- -- -- -- 14
11 -- -- -- -- 1.966 0.06 -- -- -- -- 12
9 AC-1/CU-1 25 A 2 1.966 0.06 3 20 A R. TR 102 10
7 R. CHILLER PLANT 100 20 A 1 0.54 0.36 1 20 A R. CHILLER PLANT 100 8
5 R. CHILLER PLANT 100 20 A 1 0.54 0.54 1 20 A R. CHILLER PLANT 100 6
3 R. CONTROL ROOM... 20 A 1 0.72 0.72 1 20 A R. CONTROL ROOM... 4
1 0.36 1 20 A R. CONTROL ROOM... 2
CKT Circuit Description
SCB
Type Trip Poles
A B C Poles Trip
SCB
Type Circuit Description CKT
Voltage: 208Y/120V-3PH-4W Mains Rating: 250 A Supply From: T-1LEA Enclosure: Type 1 Mains Type: MCB
Location: ELECTRICAL ROOM 105 Mounting: Surface A.I.C. Rating: 22KAIC Panel: 1LEA Construction Phase: NEW
1,662.78 kVA 1,678.79 kVA (2019 A)
TOTAL CONNECTED ESTIMATED DEMAND
NOTES: 1. REFER TO SINGLE LINE FOR WIRE INFORMATION.
2. NON-TYPICAL N+1 LOAD SHALL ONLY BE ENERGIZED WHEN THE CORRESPONDING PRIMARY EQUIPMENT IS NOT
ENERGIZED.
Resistive Heat 24,493 VA 100.00% 24,493 VA Spare 300,000 VA 100.00% 300,000 VA Receptacle 9,900 VA 100.00% 9,900 VA Power 18,848 VA 100.00% 18,848 VA Other 500 VA 100.00% 500 VA Total Est. Demand: 2019 A Motor 584,443 VA 102.74% 600,447 VA Total Conn.: 2000 A Lighting 5,270 VA 100.00% 5,270 VA Total Est. Demand: 1,678.79 kVA HVAC 719,330 VA 100.00% 719,330 VA Total Conn. Load: 1,662.78 kVA Equipment 0 VA 0.00% 0 VA Load Classification Connected... Demand Factor Estimated... Panel Totals 10 SPARE 0.00 kVA 800 A 3 800 A LSIG - - - - - 9 SPD 0.00 kVA 60 A 3 60 A GF - - - - 1 8 EX MOD1 120.00 kVA 250 A 3 250 A GF - - - - 1 7 EX MOD 5&6 180.00 kVA 400 A 3 400 A GF - - - - 1 6 1HNDP1 56.42 kVA 200 A 3 200 A GF - - - - 1 5 EQ-ATS-5 390.27 kVA 600 A 3 600 A LSIG - - - - 1 4 EQ-ATS-4 0.00 kVA 800 A 3 800 A LSIG - - - - 1,2 3 EQ-ATS-3 356.66 kVA 800 A 3 800 A LSIG - - - - 1 2 EQ-ATS-2 202.77 kVA 600 A 3 600 A LSIG - - - - 1 1 EQ-ATS-1 356.66 kVA 800 A 3 800 A LSIG - - - - 1
CKT
CIRCUIT
DESCRIPTION
APPROX.
CONNECTED
LOAD
FRAME
SIZE POLES
TRIP
SETTING
BREAKER
TYPE
NUMBER OF
CONDUCTORS
WIRE
SIZE
GROUND
SIZE
CONDUIT
SIZE
SEE
NOTE
Feeder Size: REFER TO SINGLE LINE Spec. Ref. #: 26 11 16 Voltage: 480Y/277V-3PH-4W Mains Rating: 2500 A
Supply From: Enclosure: Type 1 Mains Type: MCB Location: ELECTRICAL ROOM 106 Mounting: Surface A.I.C. Rating: REFER TO SINGLE LINE
DISTRIBUTION PANEL:US-49
US-49 XFRM GDP
GDP
(NEW) (NEW) (NEW) (NEW)
(NEW)(NEW)(NEW)
356.66 kVA
EXISTING
33.26 kVA
17.46 kVA
64.02 kVA
54.04 kVA
24.03 kVA
356.66 kVA
12.07 kVA 12.69 kVA (35 A)
TOTAL CONNECTED ESTIMATED DEMAND
Notes:
Special Circuit Breaker (SCB) Types: GF=GFCI Breaker, ST=Shunt Trip Breaker, AF=AFCI Breaker, GP=GFPE Breaker
Total Est. Demand: 35 A Receptacle 1,440 VA 100.00% 1,440 VA Total Conn.: 33 A Power 8,140 VA 100.00% 8,140 VA Total Est. Demand: 12.69 kVA Motor 2,486 VA 125.00% 3,107 VA Total Conn. Load: 12.07 kVA Equipment 0 VA 0.00% 0 VA
Load Classification Connected Load Demand Factor Estimated Demand Panel Totals
Total Load: 4.07 kVA 4.23 kVA 3.77 kVA 41 Spare 20 A 1 0 -- 1 -- Space 42 39 Spare 20 A 1 0 -- 1 -- Space 40 37 Spare 20 A 1 0 -- 1 -- Space 38 35 Spare 20 A 1 0 -- 1 -- Space 36 33 Spare 20 A 1 0 -- 1 -- Space 34 31 Spare 20 A 1 0 -- 1 -- Space 32 29 Spare 20 A 1 0 -- 1 -- Space 30 27 Spare 20 A 1 0 -- 1 -- Space 28 25 Spare 20 A 1 0 -- 1 -- Space 26 23 HOIST CONT 20 A 1 0.18 -- 1 -- Space 24 21 ACTUATOR VAVLE 20 A 1 1 -- 1 -- Space 22
19 ACTUATOR VAVLE 20 A 1 1.2 1.32 -- -- -- -- 20
17 R. ELECTRICAL ROO... 20 A 1 0.9 1.32 -- -- -- -- 18
15 HOIST CONT 20 A 1 0.18 1.32 3 20 A OVERHEAD DOOR 16
13 EM SHUT OFF 20 A 1 0 0.18 1 20 A R. CHILLER PLANT 100 14
11 MEDIA CONVTER 20 A 1 0.18 0.18 1 20 A GATE CONTROL 12
9 CT CONTROL PANEL 20 A 1 0.18 0.18 1 20 A CT CELL 10
7 CT CONTROL PANEL 20 A 1 0.18 0.18 1 20 A CT CELL 8
5 -- -- -- -- 0.829 0.18 1 20 A CT CONTROL PANEL 6
3 -- -- -- -- 0.829 0.54 1 20 A FLOW METER 4
1 RF-2 20 A 3 0.829 0.18 1 20 A VALVE CONTROL... 2
CKT Circuit Description
SCB
Type Trip Poles
A B C Poles Trip
SCB
Type Circuit Description CKT
Voltage: 208Y/120V-3PH-4W Mains Rating: 250 A Supply From: 1LEA Enclosure: Type 1 Mains Type: MCB
Location: ELECTRICAL ROOM 105 Mounting: Surface A.I.C. Rating: 22KAIC Panel: 1LEA2 Construction Phase: NEW(NEW)
| 14.04_ED100 - BUILDING 49 DEMOLITION PLAN |
| 14.05_E100-FIRST FLOOR - POWER & FIRE ALARM |