657A5-21-401 - Drawings R2_Part3 - 18 pages.pdf

PDF 15 MB Posted

Attached to
Z2DA--657A5-21-401, Construct New Campus Chiller Plant, MRN
Solicitation number
36C25526R0129
Issued by

About this file

This is a comprehensive set of design and construction documents for a fire suppression sprinkler system installation at Marion VA Medical Center.

The project requires a complete wet pipe fire suppression sprinkler system for new construction areas, with piping located above ceilings in exposed structural areas unless otherwise indicated. The design basis specifies light hazard areas limited to 225 square feet per sprinkler with 0.10 GPM/square foot density plus 100 GPM hose allowance; ordinary hazard Group 1 areas at 130 square feet per sprinkler with 0.15 GPM/square foot density plus 250 GPM hose allowance; ordinary hazard Group 2 areas at 130 square feet per sprinkler with 0.20 GPM/square foot density plus 250 GPM hose allowance; and generator rooms (extra hazard Group 2) at 100 square feet per sprinkler with 0.4 GPM/square foot density plus 500 GPM hose stream allowance. Sprinklers at roof deck shall have a K factor of 8.0. All piping sizing 2 inches and smaller shall be black steel Schedule 40 with threaded connections; piping 2.5 inches and larger shall be black steel Schedule 10 with grooved connections only. Quick response sprinklers are required in all areas except high temperature areas, telecommunications rooms, and electrical switchgear rooms. All sprinkler heads must be UL-listed and FM-approved. The contractor must perform necessary flow tests, verify adequate installation space, obtain approvals from authorities having jurisdiction, and provide hydraulic calculations and stamped drawings. All penetrations through fire-rated assemblies must be fire-stopped per specifications. The work requires coordination with VAMC, other trades, and the phasing plan, with any work outside the project scope requiring COR approval minimum five working days in advance. Comprehensive plumbing and drainage plans are also included showing water distribution, sanitary drainage, and storm drainage systems throughout the facility.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

A.

B.

C.

D.

E.

F.

G.

1.

2.

3.

4.

5.

H.

I.

J.

K.

1.

2.

L.

1.

M.

N.

O.

P.

Q.

R.

S.

T.

U.

V.

PROVIDE A COMPLETE FIRE SUPPRESSION SPRINKLER SYSTEM IN THE NEW AREA.

COORDINATE WORK WITH VAMC, PHASING PLAN AND OTHER TRADES. OFFSET AND/

OR RELOCATE SERVICES AS NEEDED TO ACCOMMODATE NEW WORK OF OTHER

TRADES.

DESIGN SERVICES SHALL FOLLOW ALL VA STANDARD DESIGN PRACTICES, DETAILS,

SPECIFICATIONS AND SITE SPECIFIC COR REQUIREMENTS AS WELL AS WORK SHOWN

ON THESE DOCUMENTS. REFERENCE VA FIRE PROTECTION DESIGN MANUAL. ALL

DEVIATIONS FROM AFOREMENTIONED REQUIREMENTS SHALL BE APPROVED BY THE

COR.

MAKE NECESSARY FLOW TESTS (SPECIFICATIONS 21 13 13), LAYOUT SYSTEMS, OBTAIN

APPROVALS FROM THE AUTHORITIES HAVING JURISDICTION PRIOR TO BEGINNING ANY

FABRICATION OR INSTALLATION WORK.

VERIFY THAT THERE IS ADEQUATE SPACE TO INSTALL ALL NEW PIPING REQUIRED TO

COMPLETE THIS WORK.

ALL SPRINKLER PIPING IS LOCATED ABOVE THE CEILING (AT THE BOTTOM STRUCTURE

IN EXPOSED STRUCTURAL AREAS), UNLESS OTHERWISE INDICATED.

THE BASIS OF DESIGN OF SPACING AND SIZING FOR THE COMPLETE FIRE

SUPPRESSION SPRINKLER SYSTEM SHALL BE FOR A WET PIPE SYSTEM

HYDRAULICALLY CALCULATED FOR A:

LIGHT HAZARD AREA LIMITED TO A MAXIMUM OF 225 SQ. FT. PER SPRINKLER WITH

THE DENSITY OF 0.10 GPM/SQ. FT. PROVIDE AN ADDITION OF 100 GPM HOSE

ALLOWANCE.

ALL MECHANICAL, ELECTRICAL, DATA, TR, AND SIMILAR SPACE AREAS SHALL BE

ORDINARY HAZARD (GROUP 1) LIMITED TO A MAXIMUM OF 130 SQ. FT. PER

SPRINKLER WITH A DENSITY OF 0.15 GPM/SQ. FT. PROVIDE AN ADDITION OF 250

GPM HOSE ALLOWANCE.

ALL BOILER, STORAGE, TRASH, FILE STORAGE AND SIMILAR SPACE AREAS SHALL

BE ORDINARY HAZARD (GROUP 2) LIMITED TO A MAXIMUM OF 130 SQ. FT. PER

SPRINKLER WITH A DENSITY OF 0.20 GPM/ SQ. FT. PROVIDE AN ADDITION OF 250

GPM HOSE ALLOWANCE.

GENERATOR ROOMS SHALL BE EXTRA HAZARD (GROUP 2) LIMITED TO A MAXIMUM

OF 100 SQ. FT PER SPRINKLER WITH A DENSITY OF 0.4 GPM/ SQ. FT. PROVIDE AN

ADDITION OF 500 GPM HOSE STREAM ALLOWANCE.

SPRINKLERS AT ROOF DECK SHALL HAVE A K FACTOR OF 8.0.

PROVIDE SPRINKLER LOCATIONS, PIPING LAYOUTS AND SIZING. SPRINKLER PIPING

SHALL BE MINIMUM 1" SIZE. PROVIDE HYDRAULIC CALCULATIONS AND STAMPED

DRAWINGS PER SPECIFICATION REQUIREMENTS.

ALL SPRINKLER LOCATIONS MUST BE COORDINATED WITH ALL EQUIPMENT KINDRED

TO OTHER TRADES. SPRINKLER LOCATIONS MUST BE APPROVED BY THE ARCHITECT

BEFORE WORK COMMENCES. ALL PENDENT TYPE SPRINKLERS LOCATED IN

SUSPENDED CEILING TILE AREAS SHALL BE LOCATED IN THE CENTER OF THE CEILING

TILE. REFER TO THE ARCHITECTURAL DRAWINGS REFLECTIVE CEILING PLANS FOR

ADDITIONAL INFORMATION ON ALL CEILING TYPES, HEIGHTS AND OTHER

ARCHITECTURAL FEATURES.

SPRINKLERS SHALL BE "QUICK RESPONSE" TYPE IN ALL AREAS EXCEPT HIGH

TEMPERATURE AREAS, TELECOMMUNICATION ROOMS, AND ELECTRICAL

SWITCHGEAR ROOMS. SPRINKLERS (UNLESS OTHERWISE NOTED):

EXPOSED AREAS - UPRIGHT OR PENDENT TYPE - STANDARD BRASS

CEILING AREAS - RECESSED PENDENT TYPE

CONCEALED SPRINKLERS ARE NOT PERMITTED.

ALL SPRINKLER HEADS SHALL BE UL LISTED AND FM APPROVED.

SPRINKLER SYSTEM PIPING AND FITTINGS SHALL BE IN ACCORDANCE WITH NFPA 13.

PIPING SIZES 2" AND SMALLER SHALL BE BLACK STEEL SCHEDULE 40 WITH

THREADED END CONNECTIONS.

PIPING SIZES 2.5" AND LARGER SHALL BE BLACK STEEL SCHEDULE 10 WITH

GROOVED CONNECTIONS. GROOVES IN SCHEDULE 10 PIPING SHALL BE ROLLED

GROOVED ONLY.

ACOUSTICAL CEILINGS ACCESS IDENTIFICATION MARKERS: COLORED MARKERS WITH

PRESSURE SENSITIVE ADHESIVE ON ONE SIDE, PAPER OR PLASTIC, 6 TO 9 MM (1/4 TO

3/8 INCH) DIAMETER. REFER TO SPECIFICATION 09 51 00 SECTION 2.6.C.

COLOR CODE: PROVIDE THE FOLLOWING COLOR MARKERS FOR SERVICE

IDENTIFICATION:

RED - SPRINKLER SYSTEM: VALVES AND CONTROLS.

ANNULAR SPACE AT PIPE AND OTHER SIMILAR PENETRATION OF FIRE RATED

ASSEMBLIES SHALL BE FIRE STOPPED. IN ADDITION, PENETRATIONS THROUGH 0-

HOUR RATED WALLS & FLOOR SHALL BE SEALED TO RETARD THE PASSAGE OF

SMOKE. REFER TO SPECIFICATIONS FOR FIRESTOPPING.

REFER TO ARCHITECTURAL DRAWINGS FOR SMOKE COMPARTMENTS, SMOKE

PARTITIONS, FIRE BARRIERS, LOCATIONS AND FIRE RATINGS OF NEW AND EXISTING

WALL ASSEMBLIES. ALL PENETRATIONS THROUGH FIRE RATED ASSEMBLIES SHALL BE

PROTECTED AND/ OR FIRE STOPPED AS REQUIRED TO MAINTAIN FIRE RATINGS

INDICATED. COORDINATE WITH ALL TRADES TO ENSURE FIRE RATED PENETRATION

REQUIREMENTS AND DETAILS ARE MET. ALL SPRINKLER ZONES SHALL MATCH SMOKE

COMPARTMENTS.

ALL REMOVED MATERIAL AND EQUIPMENT SO DESIGNATED BY THE COR, SHALL BE

TURNED OVER AND PLACED WHERE DIRECTED. ALL MATERIAL AND EQUIPMENT,

WHICH THE OWNER DOES NOT WISH TO RETAIN, SHALL BECOME THE PROPERTY OF

THE CONTRACTOR RESPONSIBLE FOR THE REMOVAL

ANY RENOVATION WORK REQUIRED "OUTSIDE" OF THE BOUNDARIES/ EXTENTS OF A

SPECIFIC PHASE OF WORK (OR TEMPORARY CONSTRUCTION WALLS SHALL BE BID AS

"NIGHT WORK" AND SHALL BE AS DIRECTED BY THE COR.

ALL CORE DRILLS AND PIPE EXTENSIONS THRU THE EXISTING STRUCTURAL FLOOR

SLAB OR STRUCTURAL WALL SHALL BE X-RAYED TO DETERMINE THE EXACT LOCATION

OF THE "REBAR" IN THE STRUCTURAL SLAB OR WALL. DO NOT CUT THE LOWER

(BOTTOM REBAR) IN THE STRUCTURAL FLOOR SLAB.

WORK IN EXISTING AREAS WITH NO/ LIMITED ARCHITECTURAL SCOPE, THE

CONTRACTOR SHALL PROVIDE ALL REQUIRED FLOOR/ WALL PROTECTION (AS

REQUIRED) AND REPLACE ANY DAMAGED CEILING TILES WITH NEW. RETURN AREA

BACK TO ORIGINAL CONDITION UPON COMPLETION OF WORK.

PROVIDE AUTOMATIC OR MANUAL AIR VENT AT OR NEAR THE HIGH POINT(S) IN THE

SPRINKLER SYSTEM PIPING, IN AN ACCESSIBLE LOCATION. PROVIDE DRAINS AT LOW

POINTS AS REQUIRED BY NFPA. PIPE DRAIN TO EXTERIOR, MOP BASIN OR APPROVED

FLOOR DRAIN.

PHASING: REFER TO ARCHITECTURAL DRAWINGS FOR AN OUTLINE OF PROJECT

PHASING. ADDITIONAL NOTES DESCRIBING PHASING DETAILS MAY BE INCLUDED

THROUGHOUT THIS DRAWING SET. INCLUDE ALL LABOR AND MATERIAL TO

ACCOMMODATE PHASING.

BID ITEMS: REFER TO ARCHITECTURAL DRAWING AND SPECIFICATION SECTION 01 00

00 FOR AN OUTLINE OF BID ITEMS. ADDITIONAL NOTES DESCRIBING BID ITEM DETAILS

MAY BE INCLUDED THROUGHOUT THIS DRAWING SET.

SEISMIC REQUIREMENTS FOR SPRINKLER SYSTEM:

SITE CLASS: C (PER GEOTECHNICAL REPORT)

RISK CATEGORY: IV (SERVES ESSENTIAL HOSPITAL OPERATIONS

MAPPED SHORT SPECTRAL ACCELERATION (S s): 1.05

MAPPED 1 SECOND SPECTRAL ACCELERATION (S1): 0.28

DESIGN SHORT SPECTRAL RESPONSE (SDS): 0.66

DESIGN 1 SECOND SPECTRAL RESPONSE (SD1): 0.39

SEISMIC DESIGN CATEGORY: D

FIRE SUPPRESSION DESIGN NOTESABBREVIATIONS

AC - AIR COMPRESSOR

ACC - ACCESS

AD - ACCESS DOOR

ADB - ACID DILUTION BASIN

ADJ - ADJUSTABLE

AFF - ABOVE FINISHED FLOOR

AFG - ABOVE FINISHED GRADE

ALT - ALTERNATE

AP - ACCESS PANEL

APPROX - APPROXIMATE

ARCH - ARCHITECT OR ARCHITECTURAL

ASSY - ASSEMBLY

BFP - BACKFLOW PREVENTER

BLDG - BUILDING

BOB - BOTTOM OF BEAM

BOD - BOTTOM OF DUCT

BOE - BOTTOM OF EQUIPMENT

BOF - BOTTOM OF FOOTING

BOG - BOTTOM OF GRILLE

BOP - BOTTOM OF PIPE

BOT - BOTTOM

BTWN - BETWEEN

CA - COMPRESSED AIR

CFCI - CONTRACTOR FURNISHED CONTRACTOR

INSTALLED

CLG - CEILING

CONN - CONNECT OR CONNECTION

CONTR - CONTRACTOR

COR - CONTRACTING OFFICER'S REPRESENTATIVE

CORR - CORRIDOR

CTR - CENTER

CWS - COMBINATION WATER SERVICE

D - DEPTH

DET - DETAIL

DIA - DIAMETER

DIM - DIMENSION

DN - DOWN

DS - SPRINKLER (DRY)

DWG - DRAWING

EA - EACH

EC - ELECTRICAL (DIVISION 26)

EJ - EXPANSION JOINT

ELEC - ELECTRICAL

ELEV - ELEVATOR

EQ - EQUAL

EQUIP - EQUIPMENT

ETR - EXISTING TO REMAIN

EQS - EQUIPMENT SUPPLIER

EXP - EXPANSION

EXT - EXTERIOR

EX - EXISTING

F - FIRE SUPPRESSION (STANDPIPE/SPRINKLER MAIN)

FCE - FIRE CONTROL EQUIPMENT

FCO - FLOOR CLEANOUT

FD - FLOOR DRAIN

FDC - FIRE DEPARTMENT CONNECTION

FDV - FIRE DEPARTMENT VALVE

FF - FINISHED FLOOR ELEVATION

FHC - FIRE HOSE CABINET

FLR - FLOOR

FPM - FEET PER MINUTE

FR - FIRE RISER

FS - FIRE SERVICE

FSC - FIRE SUPPRESSION (DIVISION 21)

FT - FEET

FTG - FOOTING

GA - GAUGE

GAL - GALLON

GALV - GALVANIZED

GC - GENERAL TRADES (DIVISION 01)

GPM - GALLONS PER MINUTE

HC - HVAC (DIVISION 23)

HD - HUB DRAIN

HP - HORSEPOWER OR HIGH POINT

HR - HOSE REEL

HT - HEAT TRACE

HVAC - HEATING, VENTILATING, AND AIR CONDITIONING

ID - INSIDE DIAMETER

INV - INVERT ELEVATION

IN - INCHES

JS - JANITOR SINK

L - LENGTH

LBS - POUNDS

MAX - MAXIMUM

MB - MOP BASIN

MC - MECHANICAL (DIVISION 23)

MEZZ - MEZZANINE

MFR - MANUFACTURER

MIN - MINIMUM

MISC - MISCELLANEOUS

MTD - MOUNTED

MTG - MOUNTING

N/C - NORMALLY CLOSED

NIC - NOT IN CONTRACT

N/O - NORMALLY OPEN

NOM - NOMINAL

NPT - NATIONAL PIPE THREAD

NTS - NOT TO SCALE

OA - OUTDOOR AIR

OD - OUTSIDE DIAMETER

OFCI - OWNER FURNISHED CONTRACTOR

INSTALLED

OFOI - OWNER FURNISHED OWNER INSTALLED

PC - PLUMBING (DIVISION 22)

OR PUMPED CONDENSATE RETURN

PIV - POST INDICATOR VALVE

PLBG - PLUMBING

PS - PRE-ACTION/DELUGE SPRINKLER

PRESS - PRESSURE

PRV - PRESSURE REGULATING VALVE

PSF - POUNDS PER SQUARE FOOT

PSI - POUNDS PER SQUARE INCH

PSV - PRESSURE SUSTAINING VALVE

PSIG - POUNDS PER SQUARE INCH GAUGE

RAD - RADIUS

REC - RECESSED

REQD - REQUIRED

RI - ROUGH IN

RPM - REVOLUTIONS PER MINUTE

S - SPRINKLER (WET)

SCH - SCHEDULE

SD - SPRINKLER DRAIN

SHT - SHEET

SK - SINK

SPEC - SPECIFICATIONS

SQ - SQUARE

STD - STANDARD

STRUC - STRUCTURAL OR STRUCTURE

SUC - SITE UTILITY CONTRACTOR

TEMP - TEMPERATURE

TOB - TOP OF BEAM

TOD - TOP OF DUCT

TOE - TOP OF EQUIPMENT

TOF - TOP OF FOOTING

TOJ - TOP OF JOIST

TOP - TOP OF PIPE

TOS - TOP OF SLAB OR TOP OF STEEL

TYP - TYPICAL

UNO - UNLESS NOTED OTHERWISE

VEL - VELOCITY

VIB - VALVE IN BOX

VOL - VOLUME

W/ - WITH

W/O - WITHOUT

WIV - WALL INDICATOR VALVE

WS - WATER SERVICE

VALVES AND FITTINGS

T

P

FOB

FOT

CONCENTRIC PIPE REDUCER

ECCENTRIC PIPE REDUCER

GAUGE - PRESSURE

GAUGE - TEMPERATURE OR THERMOMETER

UNION

CLEANOUT

STRAINER

STRAINER - WITH A BLOW DOWN VALVE AND HOSE

CONNECTION

VALVE - DRAIN WITH HOSE END CONNECTION

VALVE - PRESSURE REGULATING

VALVE - SAFETY RELIEF. PIPE DISCHARGE AIR

GAPPED TO FLOOR DRAIN UNLESS NOTED

OTHERWISE.

PLUG - PRESSURE AND TEMPERATURE TEST

TRAP PRIMER

GAUGE - VACUUM WITH STOP

CLEANOUT - TO GRADE OR FINISHED FLOOR

END CAP

MIXING FAUCET

PLUG

HOSE BIB

WALL HYDRANT

VALVE - PLUG

VALVE - SHUTOFF AND BOX

VALVE - SHUTOFF ON RISER

V

VB

TP

CO

VALVE - SOLENOID S

P/T VALVE - PRESSURE AND TEMPERATURE SAFETY

RELIEF. PIPE DISCHARGE AIR GAPPED TO

FLOOR DRAIN UNLESS NOTED OTHERWISE.

VALVE - CHECK

VALVE - SHUTOFF: BALL, GATE, BUTTERFLY VALVE

(REFER TO SPECIFICATIONS FOR REQUIRED TYPE

BASED ON APPLICATIONS)

AUTOMATIC FLOW CONTROLLER WITH P/T PLUG IN

AND OUT

VALVE - COMBINATION SHUTOFF AND

BALANCING (REFER TO SPECIFICATIONS FOR

REQUIRED TYPE BASED ON APPLICATIONS)

A1

P1 P1OR

A1

OH

P2

B P2

GENERAL FLOOR PLAN NOTES

RISER OR STACK NUMBER

DETAIL: B = DETAIL DESIGNATION

P2 = SHEET WHERE DETAIL IS LOCATED

FIRE SUPPRESSION HAZARD CLASSIFICATION AND

HAZARD CLASSIFICATION GROUP

SECTION: 1 = SECTION DESIGNATION

P2 = SHEET WHERE DETAIL IS LOCATED

EQUIPMENT REFERENCE. LETTER DESIGNATION

VARIES. REFER TO SCHEDULES.

EQUIPMENT, DEVICE, OR PLUMBING FIXTURE MARK.

LETTER DESIGNATIONS REFER TO SCHEDULES.

CONNECT TO EXISTING

PLAN NOTE. APPLIES ONLY TO THE SHEET WHICH

IT IS SHOWN UNLESS NOTED OTHERWISE.

DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.

"UP TO" SYMBOL (ITEM ON FLOOR ABOVE)

EXISTING PIPE TO REMAIN

EXISTING PIPE TO BE REMOVED

EXPANSION JOINT

WATER METERM

PIPING SYMBOLS

BOTTOM CONNECTION (45°)

BRANCH TEE CONNECTION (NOTE:

BULLHEAD TEE'S ARE NOT PERMITTED)

DIRECTION OF PITCH

DROP

ELBOW DOWN

ELBOW UP

FLOW DIRECTION DESIGNATION

PUMP

RISE

TOP CONNECTION (45°)

TOP CONNECTION (90°)

BOTTOM CONNECTION (90°)

D

R

PIPE RISER

BC

TC

FLEX PIPING

FIRE SUPPRESSION SYMBOLS

PIPING DESIGNATIONS

FS

PIV

S

CONCEALED PENDENT SPRINKLER

FIRE HYDRANT

FLOW SWITCH

GATE VALVE OS&Y

INSTITUTIONAL PENDENT SPRINKLER

PENDENT SPRINKLER

POST INDICATOR VALVE

RECESSED PENDENT SPRINKLER

SIDE WALL SPRINKLER

SUPERVISED VALVE

UPRIGHT SPRINKLER

FIRE DEPARTMENT VALVE

SPRINKLER PIPE (DRY)

FIRE SUPPRESSION (STANDPIPE/

SPRINKLER MAIN)

FIRE SERVICE

PRE-ACTION / DELUGE SPRINKLER PIPE

SPRINKLER PIPE (WET)

SPRINKLER DRAIN PIPE

DS

F

FS

PS

S

SD

COMMMMBINATION FIRE SUPPRESSION &

DOMESTIC WATER SERVICE CWS

DEMOLISH TO POINT INDICATED

LOCATION: NORTH OF BUILDING 7

STATIC PRESSURE: 61.3 PSI

RESIDUAL PRESSURE: 39.3 PSI

FLOW: 754 GPM

DATE: 3/27/2026

NOTE: PERFORM HYDRAULIC CALCULATIONS UTILIZING THE BASIS OF DESIGN FLOW

TEST DATA PROVIDED TO BID THE FIRE SUPPRESSION SPRINKLER SYSTEM. UPON

AWARD OF THE PROJECT, A FLOW TEST ALONG WITH CORRESPONDING HYDRAULIC

CALCULATIONS SHALL BE PERFORMED TO VERIFY ADEQUATE PRESSURE AND FLOW.

BASIS OF DESIGN FLOW TEST DATA

0-HR Smoke Partition - [IBC 710] / NFPA 101-8.4

1-HR Smoke Barrier - [IBC 709] / NFPA 101-8.5

1-HR Fire Barrier - [IBC 706] / NFPA 101-8.3

2-HR Fire Barrier - [IBC 706] / NFPA 101-8.3

Existing Wall to Remain

New Wall

CODE LEGEND

BRANCH

FLEXIBLE HOSE

CEILING PANELCEILING GRID

SPRINKLER

6' - 0" MAXIMUM

REFER TO SPECIFICATION 21 13 13 SECTION 2.1. SUPPORT FLEXIBLE HOSE AS REQUIRED.

MOUNTING PLATE

REFER TO MANUFACTURER'S

MINIMUM EXPOSURE

DIMENSION TO OBTAIN FM

APPROVED QUICK RESPONSE

LISTING.

1" [2

5.4 mm

1 1 /4"

[3 1.8 mm

1/8

3 m m]

MOUNTING

SURFACE

ADJUSTABLE OUTER

CUP/ ESCUTCHEON

[15

0m m]

[25 mm

[15

0m m]

INSULATE

PIPE

PIPE SLEEVE

WHERE SPECIFIED

FLOOR

WELD

1/4" [6.4mm]

ANCHOR ROD FOR

NEW CONSTRUCTION

FIRESTOP MATERIAL

3/4" [19mm]

APPROVED FIRESTOP

INSULATION WITH

VAPOR BARRIER

3/4" [19mm] APPROVED

FIRESTOP INSULATION WITH

VAPOR BARRIER 6"

[150mm]

MASONRY

PARTITION INSULATED

PIPE OR

DUCT

6" [150mm]

FIRESTOP

MATERIAL

DRYWALL PARTITION

PARTITION SUPPORT

FLOOR OR DECK PENETRATION

6" [150mm]

6" [150mm]

PARTITION OR CHASE PENETRATION

NOTE:

1. APPLICABLE TO PENETRATIONS OF ALL FIRE RATED MEMBRANES,

IN ACCORDANCE WITH NFPA 101.

REFER TO SPECIFICATIONS SECTION 07 84 00, FIRE STOPPING SYSTEMS.

F

WS

FIRE MAIN

SIGNAL WIRING IN CONDUIT

TO ALARM BELL ON WALL

OF BLDG

WATER FLOW SWITCH.

FURNISHED & WIRED

EXTERIOR WALL

SPLASH BLOCK

GRADE

PRESSURE GAUGE

TEE CONNECTION

MAIN DRAIN VALVE

MAIN DRAIN & TEST LINE

FLOOR

FLANGE - TYPICAL

SLEEVE THRU FOUNDATION WALL

FOOTING

FIRE SUPPRESSION

SERVICE

4"

-0 M

IN

P

S

W S

6"

4"

2.5" TEST HOSE CONNECTIONS ON RISER

TO FACILITATE FORWARD FLOW TEST

DCDA

DOUBLE CHECK ASSEMBLY

M

TO DOMESTIC WATER MAIN

S

FDC

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Date:Revisions:No.

C :\U se rs

\b sg ay do s\ Ap pD at a\ Lo ca l\A ut od es k\

R ev it\ Au to de sk R ev it

\C ol la bo ra tio nC ac he \F

G L2

C N

YF

N

2R

VU

3\

5d 1a c9

-2 ae

8-

-b f-c ff8 3c

3d

3a \e e-fd

-4 d-ab

-2 dc f.r vt 5/

5/

:4 7:

P

M

F001

ABBREVIATIONS, SYMBOLS &

INDEX OF DRAWINGS

05/07/2026 BDF BSG

CONSTRUCT NEW

CAMPUS CHILLER PLANT

657A5-21-401

2401 W MAIN ST, MARION IL 62959

CONTRACT

DOCUMENTS 49

MARION VA

MEDICAL

CENTER Approved: Owner

INDEX OF DRAWINGS

SHEET NUMBER SHEET NAME

F001 ABBREVIATIONS, SYMBOLS & INDEX OF DRAWINGS

FD101 FIRST FLOOR PLAN - DEMOLITION

FX101 FIRST FLOOR PLAN - NEW WORK

FX102 MEZZANINE PLAN - NEW WORK

FX201 ROOF PLAN - NEW WORK

NTS1 SPRINKLER FLEXIBLE HOSE

NTS3 SEMI-RECESSED PENDENT SPRINKLER

NTS2 PIPE PENETRATION OF SMOKE/ FIRE BARRIERS

NTS4 FIRE RISER

1 CONTRACT DOCUMENTS 05/07/2026

BFP

3" - F

3"

F

3" - F

3"

F

3" - F

FDC

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Date:Revisions:No.

C :\U se rs

\b sg ay do s\ Ap pD at a\ Lo ca l\A ut od es k\

R ev it\ Au to de sk R ev it

\C ol la bo ra tio nC ac he \F

G L2

C N

YF

N

2R

VU

3\

5d 1a c9

-2 ae

8-

-b f-c ff8 3c

3d

3a \e e-fd

-4 d-ab

-2 dc f.r vt 5/

5/

:4 7:

P

M

FD101

FIRST FLOOR PLAN - DEMOLITION

05/07/2026 BDF BSG

CONSTRUCT NEW

CAMPUS CHILLER PLANT

657A5-21-401

2401 W MAIN ST, MARION IL 62959

CONTRACT

DOCUMENTS 49

MARION VA

MEDICAL

CENTER Approved: Owner

1/4" = 1'-0"

FIRST FLOOR PLAN

NOTES

1 PIPING EXTENDING TO WATER SERVICE. SEE PLUMBING DRAWING FOR

ADDITIONAL INFORMATION.

2 REMOVE EXISTING PIPING OR ITEM OF EQUIPMENT (TYPE AS INDICATED)

COMPLETE.

3 MECHANICAL EQUIPMENT SHOWN FOR REFERENCE ONLY.

4 PLUMBING FIXTURE AND EQUIPMENT SHOWN FOR REFERENCE ONLY.

SITE KEY PLAN

NEW CHILLER PLANT - BLDG 49

EXISTING CHILLER PLANT - BLDG 49

37MOD-5

MOD-1

49 MOD-4

MOD-6

NORTH

SHEET NOTES

A.

B.

C.

REFER TO SHEET P001 FOR ABBREVIATIONS, SYMBOLS & GENERAL NOTES.

COORDINATE ALL WORK WITH CONSTRUCTION MANAGER'S PHASING REQUIREMENTS.

ANY WORK REQUIRED OUTSIDE OF PROJECT SCOPE AREA FOR REMOVALS, SERVICE INTERRUPTIONS, OR TEMPORARY SERVICES TO BE

CLOSELY COORDINATED WITH COR A MINIMUM OF FIVE (5) WORKING DAYS AHEAD OF TIME.

A

D

632 54

B

C

DNF

STAIRS 2

TYP.

TYP.

TYP.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Date:Revisions:No.

C :\U se rs

\b sg ay do s\ Ap pD at a\ Lo ca l\A ut od es k\

R ev it\ Au to de sk R ev it

\C ol la bo ra tio nC ac he \F

G L2

C N

YF

N

2R

VU

3\

5d 1a c9

-2 ae

8-

-b f-c ff8 3c

3d

3a \e e-fd

-4 d-ab

-2 dc f.r vt 5/

5/

:4 7:

P

M

FX201

ROOF PLAN - NEW WORK

05/07/2026 BDF BSG

CONSTRUCT NEW

CAMPUS CHILLER PLANT

657A5-21-401

2401 W MAIN ST, MARION IL 62959

CONTRACT

DOCUMENTS 49

MARION VA

MEDICAL

CENTER Approved: Owner

1/4" = 1'-0"

ROOF FIRE SUPPRESSION PLAN - NEW WORK

PLAN NOTES

1 SCOPE OF NEW WORK AREA REQUIRING SPRINKLER PROTECTION.

COORDINATE INSTALLATION OF NEW PIPING WITH NEW MECHANICAL,

ELECTRICAL, AND PLUMBING SYSTEMS.

2 CEILING OPEN TO STRUCTURE IN THIS AREA.

3 MECHANICAL EQUIPMENT SHOWN FOR REFERENCE ONLY.

SITE KEY PLAN

NEW CHILLER PLANT - BLDG 49

EXISTING CHILLER PLANT - BLDG 49

37MOD-5

MOD-1

49 MOD-4

MOD-6

NORTH

SHEET NOTES

A.

B.

C.

D.

REFER TO SHEET P001 FOR ABBREVIATIONS, SYMBOLS & GENERAL NOTES.

COORDINATE ALL WORK WITH CONSTRUCTION MANAGER'S PHASING REQUIREMENTS.

ANY WORK REQUIRED OUTSIDE OF PROJECT SCOPE AREA FOR REMOVALS, SERVICE INTERRUPTIONS, OR TEMPORARY SERVICES TO BE

CLOSELY COORDINATED WITH COR A MINIMUM OF FIVE (5) WORKING DAYS AHEAD OF TIME.

SPRINKLER PIPES SHALL BE SIZED ACCORDING TO HYDRAULIC CALCULATIONS.

D

632 54

B

C

MEZZANINE OH

3OH

TYP.

F FF

4DNF

UPF

DNF 5

6DNF

DNF

F

DNF 8

9 9

F

F

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Date:Revisions:No.

C :\U se rs

\b sg ay do s\ Ap pD at a\ Lo ca l\A ut od es k\

R ev it\ Au to de sk R ev it

\C ol la bo ra tio nC ac he \F

G L2

C N

YF

N

2R

VU

3\

5d 1a c9

-2 ae

8-

-b f-c ff8 3c

3d

3a \e e-fd

-4 d-ab

-2 dc f.r vt 5/

5/

:4 7:

P

M

FX102

MEZZANINE PLAN - NEW WORK

05/07/2026 BDF BSG

CONSTRUCT NEW

CAMPUS CHILLER PLANT

657A5-21-401

2401 W MAIN ST, MARION IL 62959

CONTRACT

DOCUMENTS 49

MARION VA

MEDICAL

CENTER Approved: Owner

1/4" = 1'-0"

MEZZANINE PLAN - NEW WORK

PLAN NOTES

1 SCOPE OF NEW WORK AREA REQUIRING SPRINKLER PROTECTION.

COORDINATE INSTALLATION OF NEW PIPING WITH NEW MECHANICAL,

ELECTRICAL, AND PLUMBING SYSTEMS.

2 MECHANICAL EQUIPMENT SHOWN FOR REFERENCE ONLY.

3 HIGH CEILINGS OPEN TO FLOOR BELOW IN THIS AREA. SEE FIRST FLOOR

PLAN FOR ADDITIONAL DETAIL REGARDING EQUIPMENT LOCATIONS.

4 SPRINKLER BRANCH MAIN DOWN TO SERVE ELECTRIC ROOM 106. REFER TO

FIRST FLOOR PLAN.

5 SPRINKLER BRANCH MAIN DOWN TO SERVE ELECTRIC ROOM 105. FIRE

STOP FLOOR PENETRATION.

6 SPRINKLER BRANCH MAIN DOWN TO SERVE OFFICE AND SUPPORT ROOMS.

7 SPRINKLER BRANCH MAIN UP TO SERVE ROOF ACCESS AREA. SEE ROOF

PLAN FOR ADDITIONAL DETAIL.

8 4" SPRINKLER MAIN DOWN TO WATER SERVICE. SEE FIRST FLOOR PLAN

FOR ADDITIONAL DETAIL.

9 EXTENTS OF MEZZANINE.

10 CEILINGS OPEN TO STRUCTURE IN THIS AREA.

SITE KEY PLAN

NEW CHILLER PLANT - BLDG 49

EXISTING CHILLER PLANT - BLDG 49

37MOD-5

MOD-1

49 MOD-4

MOD-6

NORTH

SHEET NOTES

A.

B.

C.

D.

REFER TO SHEET P001 FOR ABBREVIATIONS, SYMBOLS & GENERAL NOTES.

COORDINATE ALL WORK WITH CONSTRUCTION MANAGER'S PHASING REQUIREMENTS.

ANY WORK REQUIRED OUTSIDE OF PROJECT SCOPE AREA FOR REMOVALS, SERVICE INTERRUPTIONS, OR TEMPORARY SERVICES TO BE

CLOSELY COORDINATED WITH COR A MINIMUM OF FIVE (5) WORKING DAYS AHEAD OF TIME.

M BFP

S

A

D

632 54

B

C

OH

OH

OH

H.A.C.

ELECTRICAL

ROOM

ELECTRICAL

ROOM

CHILLER

PLANT

OH

CONTROL

ROOM

TR

TOILET

FDC

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

OH

LH

LH

UPF6

UPF

UPF

UPF

UPF 8

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Date:Revisions:No.

C :\U se rs

\b sg ay do s\ Ap pD at a\ Lo ca l\A ut od es k\

R ev it\ Au to de sk R ev it

\C ol la bo ra tio nC ac he \F

G L2

C N

YF

N

2R

VU

3\

5d 1a c9

-2 ae

8-

-b f-c ff8 3c

3d

3a \e e-fd

-4 d-ab

-2 dc f.r vt 5/

5/

:4 7:

P

M

FX101

FIRST FLOOR PLAN - NEW WORK

05/07/2026 BDF BSG

CONSTRUCT NEW

CAMPUS CHILLER PLANT

657A5-21-401

2401 W MAIN ST, MARION IL 62959

CONTRACT

DOCUMENTS 49

MARION VA

MEDICAL

CENTER Approved: Owner

PLAN NOTES

1 ONLY PIPING SERVING THIS ROOM SHALL EXTEND INTO THE ROOM. DO NOT

LOCATE PIPING/SPRINKLERS OVER ELECTRICAL EQUIPMENT.

2 PIPING EXTENDS TO WATER SERVICE. SEE PLUMBING SHEETS FOR

FURTHER DETAIL.

3 MECHANICAL AND ELECTRICAL EQUIPMENT SHOWN FOR REFERENCE ONLY.

4 HIGH CEILING OPEN TO STRUCTURE IN THIS AREA. SEE MEZZANINE PLANS

FOR ADDITIONAL DETAIL.

5 SCOPE OF NEW WORK AREA REQUIRING SPRINKLER PROTECTION.

COORDINATE INSTALLATION OF NEW PIPING WITH NEW MECHANICAL,

ELECTRICAL, AND PLUMBING SYSTEMS.

6 SPRINKLER PIPING TO EXTEND TO THE HIGH BAY ROOF DECK.

7 SPRINKLER BRANCH MAIN FROM ABOVE TO SERVE ELECTRIC ROOM 106.

FIRE STOP WALL PENETRATION.

8 SPRINKLER BRANCH MAIN FROM ABOVE TO SERVE ELECTRIC ROOM 105.

FIRE STOP CEILING PENETRATION.

9 SPRINKLER BRANCH MAIN FROM ABOVE TO SERVE OFFICE/SUPPORT AREA.

10 CONNECT WATER METER TO THE VA METERING SYSTEM. INSTALL WATER

METER PER MARION WATER DEPARTMENT REQUIREMENTS.

1/4" = 1'-0"

FIRST FLOOR FIRE SUPPRESSION PLAN - NEW WORK

SITE KEY PLAN

NEW CHILLER PLANT - BLDG 49

EXISTING CHILLER PLANT - BLDG 49

37MOD-5

MOD-1

49 MOD-4

MOD-6

NORTH

SHEET NOTES

A.

B.

C.

D.

REFER TO SHEET P001 FOR ABBREVIATIONS, SYMBOLS & GENERAL NOTES.

COORDINATE ALL WORK WITH CONSTRUCTION MANAGER'S PHASING REQUIREMENTS.

ANY WORK REQUIRED OUTSIDE OF PROJECT SCOPE AREA FOR REMOVALS, SERVICE INTERRUPTIONS, OR TEMPORARY SERVICES TO BE

CLOSELY COORDINATED WITH COR A MINIMUM OF FIVE (5) WORKING DAYS AHEAD OF TIME.

A1

P1 P1OR

A1

OH

P2

B P2

GENERAL FLOOR PLAN NOTES

RISER OR STACK NUMBER

DETAIL: B = DETAIL DESIGNATION

P2 = SHEET WHERE DETAIL IS LOCATED

FIRE SUPPRESSION HAZARD CLASSIFICATION AND

HAZARD CLASSIFICATION GROUP

SECTION: 1 = SECTION DESIGNATION

P2 = SHEET WHERE DETAIL IS LOCATED

EQUIPMENT REFERENCE. LETTER DESIGNATION

VARIES. REFER TO SCHEDULES.

EQUIPMENT, DEVICE, OR PLUMBING FIXTURE MARK.

LETTER DESIGNATIONS REFER TO SCHEDULES.

CONNECT TO EXISTING

PLAN NOTE. APPLIES ONLY TO THE SHEET WHICH

IT IS SHOWN UNLESS NOTED OTHERWISE.

DETAIL NOTE. APPLIES ONLY TO THE ASSOCIATED DETAIL.

"UP TO" SYMBOL (ITEM ON FLOOR ABOVE)

PIPING DESIGNATIONS

DOMESTIC COLD WATER

DOMESTIC HOT WATER

DOMESTIC HOT WATER RETURN

EXISTING PIPE TO REMAIN

EXISTING PIPE TO BE REMOVED

HOT WATER PIPE (140 DEGS. F.)

HOT WATER RETURN PIPE (140 DEGS. F.)

HOT WATER RETURN PIPE (180 DEGS. F.)

140R

180R

EXPANSION JOINT

WATER METERM

PIPING SYMBOLS

BOTTOM CONNECTION (45°)

BRANCH TEE CONNECTION (NOTE:

BULLHEAD TEE'S ARE NOT PERMITTED)

DIRECTION OF PITCH

DROP

ELBOW DOWN

ELBOW UP

FLOW DIRECTION DESIGNATION

PUMP

RISE

TOP CONNECTION (45°)

TOP CONNECTION (90°)

BOTTOM CONNECTION (90°)

D

R

PIPE RISER

HOT WATER PIPE (180 DEGS. F.)

ARGON PIPE

COMPRESSED AIR PIPE

DIESEL FUEL PIPE

FUEL OIL FLOW LINE

FUEL OIL GAUGE LINE

FUEL OIL RETURN LINE

FUEL OIL SUPPLY LINE

NATURAL GAS PIPE

GARAGE DRAINAGE PIPE

GAS SERVICE

HYDROGEN PIPE

HELIUM PIPE

KITCHEN WASTE PIPE

LABORATORY COMPRESSED AIR PIPE

LABORATORY VENT PIPE

LABORATORY VACUUM PIPE

LABORATORY WASTE PIPE

GASOLINE PIPE (NON-LEAD)

NON-POTABLE

(OVERFLOW) SECONDARY STORM DRAINAGE PIPE

PROPANE GAS PIPE

PUMP DISCHARGE PIPE

PURE WATER PIPE

SANITARY DRAINAGE PIPE

SOFT COLD WATER

STORM DRAINAGE PIPE

FUEL TANK VENT PIPE

TRAP PRIMER DISCHARGE PIPE

TEMPERED WATER PIPE

SANITARY SEWER VENT

WATER SERVICE

LV

AR

CA

DF

FOF

FOG

FOR

FOS

G

GD

GS

H2

HE

IV

IW

LA

LV

LW

NG

NPW

OD

P

PD

PW

SAN

SCW

STM

T

TP

TW

V

WS

INDIRECT VENT PIPE

INDIRECT WASTE PIPE

K

ACID VENT PIPEAV

ACID WASTE PIPEAW

BC

TC

COMBINATION FIRE SUPPRESSION &

DOMESTIC WATER SERVICECWS

FLEX PIPINGMEDICAL INSTRUMENT AIR PIPE

MEDICAL NITROGEN PIPE

MEDICAL COMPRESSED AIR PIPE

MEDICAL SURGICAL VACUUM-EXHAUST PIPE

MEDICAL NITROUS OXIDE PIPE

MEDICAL OXYGEN PIPE

WASTE ANESTHESIA GAS DISPOSAL PIPE

IA

N2

MA

MV

NO

O2

WAGD

MEDICAL CARBON DIOXIDE PIPECO2

MEDICAL SURGICAL VACUUM PIPE

MEDICAL COMPRESSED AIR-INTAKE PIPEMA-IN

MV-EX

VALVES AND FITTINGS

T

P

FOB

FOT

CONCENTRIC PIPE REDUCER

ECCENTRIC PIPE REDUCER

GAUGE - PRESSURE

GAUGE - TEMPERATURE OR THERMOMETER

UNION

CLEANOUT

STRAINER

STRAINER - WITH A BLOW DOWN VALVE AND HOSE

CONNECTION

VALVE - DRAIN WITH HOSE END CONNECTION

VALVE - PRESSURE REGULATING

VALVE - SAFETY RELIEF. PIPE DISCHARGE AIR

GAPPED TO FLOOR DRAIN UNLESS NOTED

OTHERWISE.

PLUG - PRESSURE AND TEMPERATURE TEST

TRAP PRIMER

GAUGE - VACUUM WITH STOP

CLEANOUT - TO GRADE OR FINISHED FLOOR

END CAP

MIXING FAUCET

PLUG

HOSE BIB

WALL HYDRANT

VALVE - PLUG

VALVE - SHUTOFF AND BOX

VALVE - SHUTOFF ON RISER

V

VB

TP

CO

VALVE - SOLENOID S

P/T VALVE - PRESSURE AND TEMPERATURE SAFETY

RELIEF. PIPE DISCHARGE AIR GAPPED TO

FLOOR DRAIN UNLESS NOTED OTHERWISE.

VALVE - CHECK

VALVE - SHUTOFF: BALL, GATE, BUTTERFLY VALVE

(REFER TO SPECIFICATIONS FOR REQUIRED TYPE

BASED ON APPLICATIONS)

AUTOMATIC FLOW CONTROLLER WITH P/T PLUG IN

AND OUT

VALVE - COMBINATION SHUTOFF AND

BALANCING (REFER TO SPECIFICATIONS FOR

REQUIRED TYPE BASED ON APPLICATIONS)

ABBREVIATIONS

AAP - AREA ALARM PANEL (MEDICAL GAS)

AC - AIR COMPRESSOR OR AIR CONDITIONER

ACC - ACCESS

ACCU - AIR COOLED CONDENSING UNIT

AD - ACCESS DOOR OR AREA DRAIN

ADB - ACID DILUTION BASIN

ADJ - ADJUSTABLE

AFF - ABOVE FINISHED FLOOR

AFG - ABOVE FINISHED GRADE

ALT - ALTERNATE

AP - ACCESS PANEL

APPROX - APPROXIMATE

AR - AIR RECEIVER OR ARGON

ARCH - ARCHITECT OR ARCHITECTURAL

ASSY - ASSEMBLY

AV - ACID VENT

AW - ACID WASTE

BDD - BACK DRAFT DAMPER

BFP - BACKFLOW PREVENTER

BLDG - BUILDING

BOB - BOTTOM OF BEAM

BOD - BOTTOM OF DUCT

BOE - BOTTOM OF EQUIPMENT

BOF - BOTTOM OF FOOTING

BOG - BOTTOM OF GRILLE

BOP - BOTTOM OF PIPE

BOT - BOTTOM

BT - BATHTUB

BTU - BRITISH THERMAL UNIT

BTUH - BRITISH THERMAL UNIT PER HOUR

BTWN - BETWEEN

CA - COMPRESSED AIR

CB - CATCH BASIN

CBD - COUNTER BALANCED BACKDRAFT DAMPER

CFCI - CONTRACTOR FURNISHED CONTRACTOR

INSTALLED

CFM - CUBIC FEET PER MINUTE

CHS - CHILLED WATER SUPPLY

CHR - CHILLED WATER RETURN

CI - CAST IRON

CK - CLINICAL SINK

CLG - CEILING

CMU - CONCRETE MASONRY UNIT

CO - CLEAN OUT

CO2 - MEDICAL CARBON DIOXIDE

CONN - CONNECT OR CONNECTION

CONTR - CONTRACTOR

COR - CONTRACTING OFFICER'S REPRESENTATIVE

CORR - CORRIDOR

CRP - CORROSION RESISTANT PIPE

CRV - CORROSION RESISTENT VENT PIPE

CS - CLINICAL SINK OR COLD SOFT WATER

CTR - CENTER

CU - COPPER

CW - COLD WATER

CWS - COMBINATION WATER SERVICE

OR CONDENSER WATER SUPPLY

CWR - CONDENSER WATER RETURN

D - DEPTH OR DRAIN LINE

DB - DIALYSIS BOX

DD - DECK DRAIN

DET - DETAIL

DF - DRINKING FOUNTAIN OR WATER COOLER

OR DIESEL FUEL

DFU - DRAINAGE FIXTURE UNIT

DI - DEIONIZED WATER

DIA - DIAMETER

DIM - DIMENSION

DN - DOWN

DS - DOWN SPOUT OR SPRINKLER (DRY)

DT - PERFORATED DRAIN TILE

DWG - DRAWING

EA - EACH

EC - ELECTRICAL (DIVISION 26)

EEW - EMERGENCY EYE WASH

EJ - EXPANSION JOINT

ELEC - ELECTRICAL

ELEV - ELEVATOR

EQ - EQUAL

EQUIP - EQUIPMENT

ET - EXPANSION TANK

ETR - EXISTING TO REMAIN

ES - EMERGENCY SHOWER

EQS - EQUIPMENT SUPPLIER

EWC - ELECTRICAL WATER COOLER

EXH - EXHAUST AIR

EXP - EXPANSION

EXT - EXTERIOR

EX - EXISTING

F - FIRE SUPPRESSION (STANDPIPE/SPRINKLER

MAIN)

FCE - FIRE CONTROL EQUIPMENT

FCO - FLOOR CLEANOUT

FD - FLOOR DRAIN

FDC - FIRE DEPARTMENT CONNECTION

FDV - FIRE DEPARTMENT VALVE

FF - FINISHED FLOOR ELEVATION

FHC - FIRE HOSE CABINET

FLR - FLOOR

FM - FORCE MAIN

FOB - FLAT ON BOTTOM

FOF - FUEL OIL FLOW

FOG - FUEL OIL GAUGE

FOR - FUEL OIL RETURN

FOS - FUEL OIL SUPPLY

FOT - FLAT ON TOP

FPM - FEET PER MINUTE

FR - FIRE RISER

FS - FLOOR SINK OR FIRE SERVICE

FSC - FIRE SUPPRESSION (DIVISION 21)

FT - FEET

FTG - FOOTING

G - GAS OR NATURAL GAS

GA - GAUGE

GAL - GALLON

GALV - GALVANIZED

GC - GENERAL TRADES (DIVISION 01)

GD - GARAGE DRAINAGE

GPM - GALLONS PER MINUTE

GS - GAS SERVICE

GW - GREASE WASTE

H2 - HYDROGEN

HB - HOSE BIBB

HC - HVAC (DIVISION 23)

HD - HUB DRAIN

HE - HELIUM

HG - REFRIGERANT HOT GAS

HP - HORSEPOWER OR HIGH POINT

HPC - HIGH PRESSURE CONDENSATE RETURN

HPS - HIGH PRESSURE STEAM SUPPLY

HPW - HIGH PURITY WATER

HPWR - HIGH PURITY WATER RETURN

HR - HOSE REEL

HT - HEAT TRACE

HTR - HEATER

HVAC - HEATING, VENTILATING, AND AIR

CONDITIONING

HW - HOT WATER

HWR - HEATING HOT WATER RETURN

HWS - HEATING HOT WATER SUPPLY

IA - MEDICAL INSTRUMENT AIR

ID - INSIDE DIAMETER

INV - INVERT ELEVATION

IN - INCHES

IV - INDIRECT VENT

IW - INDIRECT WASTE

JS - JANITOR SINK

K - KITCHEN WASTE

KEC - KITCHEN EQUIPMENT

L - LENGTH

LA - LABORATORY COMPRESSED AIR

LAV - LAVATORY

LBS - POUNDS

LCW - LABORATORY COLD WATER

LEC - LABORATORY EQUIPMENT

LHW - LABORATORY HOT WATER

LHWR - LABORATORY HOT WATER RETURN

LPC - LOW PRESSURE CONDENSATE RETURN

LPS - LOW PRESSURE STEAM SUPPLY

LV - LABORATORY VACUUM OR LABORATORY

VENT

LW - LABORATORY WASTE

MA - MEDICAL COMPRESSED AIR

MAP - MASTER ALARM PANEL (MEDICAL GAS)

MAX - MAXIMUM

MB - MOP BASIN

MC - MECHANICAL (DIVISION 23)

MEZZ - MEZZANINE

MFR - MANUFACTURER

MH - MANHOLE

MIN - MINIMUM OR MINUTE

MISC - MISCELLANEOUS

MTD - MOUNTED

MTG - MOUNTING

MPC - MEDIUM PRESSURE CONDENSATE RETURN

MPS - MEDIUM PRESSURE STEAM SUPPLY

MU - WATER MAKE-UP

MV - MEDICAL SURGICAL VACUUM

N2 - MEDICAL NITROGEN

N/C - NORMALLY CLOSED

NG - GASOLINE (NON-LEAD)

NIC - NOT IN CONTRACT

N/O - NORMALLY OPEN

NO - MEDICAL NITROUS OXIDE

NOM - NOMINAL

NPW - NON-POTABLE WATER

NPT - NATIONAL PIPE THREAD

NTS - NOT TO SCALE

O2 - MEDICAL OXYGEN

OA - OUTDOOR AIR

OD - OUTSIDE DIAMETER OR OVERFLOW

DRAIN

OFCI - OWNER FURNISHED CONTRACTOR

INSTALLED

OFOI - OWNER FURNISHED OWNER INSTALLED

P - PROPANE GAS

PC - PLUMBING (DIVISION 22) OR PUMPED

CONDENSATE RETURN

PD - PUMP DISCHARGE OR PARAPET DRAIN

PIV - POST INDICATOR VALVE

PLBG - PLUMBING

PS - PRE-ACTION/DELUGE SPRINKLER

PRESS - PRESSURE

PRV - PRESSURE REGULATING VALVE

PSF - POUNDS PER SQUARE FOOT

PSI - POUNDS PER SQUARE INCH

PSV - PRESSURE SUSTAINING VALVE

PSIG - POUNDS PER SQUARE INCH GAUGE

PW - PURE WATER

RA - RETURN AIR

RAD - RADIUS

RCP - REINFORCED CONCRETE PIPE

RD - ROOF DRAIN

REC - RECESSED

REQD - REQUIRED

RI - ROUGH IN

RL - REFRIGERANT LIQUID

ROS - REVERSE OSMOSIS WATER SUPPLY

ROR - REVERSE OSMOSIS WATER RETURN

RPM - REVOLUTIONS PER MINUTE

RS - REFRIGERANT SUCTION

RV - RELIEF VALVE

S - SPRINKLER (WET)

SA - SHOCK ARRESTOR OR SUPPLY AIR

SAN - SANITARY OR SANITARY DRAIN

SCH - SCHEDULE

SCW - SOFT COLD WATER

SD - SPRINKLER DRAIN OR SUBSOIL DRAIN

SH - SHOWER

SHT - SHEET

SK - SINK

SPEC - SPECIFICATIONS

SQ - SQUARE

SR - SUPPLY RISER

SS - SANITARY STACK (SOIL OR WASTE) OR

STAINLESS STEEL

STD - STANDARD

STM - STORM OR STORM DRAINAGE

STRUC - STRUCTURAL OR STRUCTURE

SUC - SITE UTILITY CONTRACTOR

T - FUEL TANK VENT

TD - TRENCH DRAIN

TEMP - TEMPERATURE

TOB - TOP OF BEAM

TOD - TOP OF DUCT

TOE - TOP OF EQUIPMENT

TOF - TOP OF FOOTING

TOJ - TOP OF JOIST

TOP - TOP OF PIPE

TOS - TOP OF SLAB OR TOP OF STEEL

TF - TRAP FILLER

TP - TRAP PRIMER OR TRAP PRIMER

DISCHARGE

TW - TEMPERED WATER

TYP - TYPICAL

UR - URINAL

UNO - UNLESS NOTED OTHERWISE

V - VENT OR SANITARY SEWER VENT

VAC - VACUUM

VC - VACUUM CLEANING

VCV - VACUUM CLEANING VALVE

VE - VACUUM EXHAUST

VEL - VELOCITY

VIB - VALVE IN BOX

VOL - VOLUME

VP - VACUUM PUMP

VS - VENT STACK

VTR - VENT THROUGH ROOF

VR - VENT RISER

W/ - WITH

W/O - WITHOUT

W - WASTE

WAGD - WASTE ANESTHESIA GAS DISPOSAL

WC - WATER CLOSET

WCO - WALL CLEANOUT

WH - WALL HYDRANT OR WATER HEATER

WIV - WALL INDICATOR VALVE

WS - WATER SERVICE

YCO - YARD CLEANOUT

ZVC - ZONE VALVE CABINET

DEMOLISH TO POINT INDICATED

GENERAL NOTES

A.

B.

C.

D.

E.

F.

G.

H.

I.

J.

K.

L.

M.

N.

O.

1.

P.

Q.

1.

2.

ALL NEW PIPING IS ABOVE THE CEILING (AT THE UNDERSIDE OF STRUCTURE IN

EXPOSED STRUCTURE AREAS), UNLESS OTHERWISE NOTED. ABOVE CEILING UTILITY

SPACE IS LIMITED. COORDINATION WITH ALL TRADES IS CRITICAL, PRIOR TO

INSTALLATION OF ANY WORK.

REFER TO SCHEDULES, DETAILS AND DIAGRAMS FOR PIPING, PIPE SIZES AND

PIPELINE DEVICES NOT INDICATED ON THE FLOOR PLAN.

LOCATIONS AND SIZES OF EXISTING PIPING HAVE BEEN DETERMINED FROM A

REVIEW OF EXISTING DRAWINGS AND/ OR SITE INSPECTION, WHERE POSSIBLE. FIELD

VERIFICATION OF EXACT LOCATIONS, ELEVATIONS, INVERTS, SIZES, DIRECTION OF

FLOW, ETC. SHALL BE REQUIRED PRIOR TO BEGINNING NEW WORK.

ALL DOMESTIC WATER PIPING SHOWN TO BE DEMOLISHED SHALL BE REMOVED BACK

TO WITHIN TWO PIPE DIAMETERS OF ACTIVE MAINS AND CAPPED, OR REMOVED

BACK TO POINTS OF CONNECTION OF NEW WORK. INACCESSIBLE PIPING, WHERE SO

NOTED, TO BE ABANDONED SHALL BE DISCONNECTED FROM ACTIVE MAINS AND

CAPPED IN CONCEALED LOCATIONS.

ABANDONED PIPING DISCOVERED DURING DEMOLITION/ RENOVATION SHALL BE

REMOVED. DOMESTIC WATER DISTRIBUTION PIPING DISCOVERED DURING

DEMOLITION/ RENOVATION SHALL BE REMOVED BACK TO WITH-IN 2 PIPE DIAMETERS

OF THE ACTIVE MAIN AND CAPPED.

NEW CONNECTIONS TO EXISTING PIPING SHALL BE WITH THE SAME SIZE AS THE

EXISTING PIPING UNLESS OTHERWISE NOTED.

ALL REMOVED MATERIAL AND EQUIPMENT SO DESIGNATED BY THE COR, SHALL BE

TURNED OVER AND PLACED WHERE DIRECTED. ALL MATERIAL AND EQUIPMENT,

WHICH THE OWNER DOES NOT WISH TO RETAIN, SHALL BECOME THE PROPERTY OF

THE CONTRACTOR RESPONSIBLE FOR THE REMOVAL.

ANY RENOVATION WORK REQUIRED "OUTSIDE" OF THE BOUNDARIES/ EXTENTS OF A

SPECIFIC PHASE OF WORK (OR TEMPORARY CONSTRUCTION WALLS SHALL BE BID

AS "NIGHT WORK" AND SHALL BE AS DIRECTED BY THE COR.

ALL CORE DRILLS AND PIPE EXTENSIONS THRU THE EXISTING STRUCTURAL FLOOR

SLAB OR STRUCTURAL WALL SHALL BE X-RAYED TO DETERMINE THE EXACT

LOCATION OF THE "REBARS" IN THE STRUCTURAL SLAB. DO NOT CUT THE LOWER

(BOTTOM REBARS) IN THE FLOOR SLAB.

RESTORATION WORK, EXISTING WORK (WALLS, CEILINGS, PARTITIONS, FLOORS)

DISTURBED OR REMOVED AS A RESULT OF PERFORMING REQUIRED NEW WORK,

SHALL BE PATCHED, REPAIRED, REINSTALLED, OR REPLACED WITH NEW WORK, AND

REFINISHED AND LEFT IN AS GOOD CONDITION AS EXISTED BEFORE COMMENCING

WORK.

WORK IN EXISTING AREAS WITH NO/ LIMITED ARCHITECTURAL SCOPE, THE

CONTRACTOR SHALL PROVIDE FLOOR/ WALL PROTECTION (AS REQUIRED) AND

REPLACE ANY DAMAGED CEILING TILES WITH NEW. RETURN AREA BACK TO

ORIGINAL CONDITION UPON COMPLETION OF WORK.

REFER TO ARCHITECTURAL FIRE RATED PARTITION PLAN(S) FOR LOCATIONS AND

FIRE RATINGS OF NEW AND EXISTING WALL ASSEMBLIES. ALL PENETRATIONS

THROUGH FIRE RATED ASSEMBLIES SHALL BE PROTECTED AND/ OR FIRE STOPPED

AS REQUIRED TO MAINTAIN FIRE RATINGS INDICATED. COORDINATE WITH ALL

TRADES TO ENSURE FIRE RATED PENETRATION REQUIREMENTS AND DETAILS ARE

MET.

ANNULAR SPACE OF ALL PIPE & OTHER SIMILAR PENETRATIONS OF FIRE RATED

ASSEMBLIES SHALL BE FIRE STOPPED. IN ADDITION, PENETRATIONS THROUGH 0-

HOUR RATED WALLS & FLOOR SHALL BE SEALED TO RETARD THE PASSAGE OF

SMOKE.

DOMESTIC WATER PIPING MODIFIED BY THIS PROJECT SHALL BE DISINFECTED AND

TESTED IN ITS ENTIRETY. DISINFECTION AND TESTING PROCEDURES SHALL FOLLOW

CAMPUS VA WATER SAFETY PLAN, VA DESIGN MANUALS, VA SPECIFICATIONS,

AND LOCAL REQUIREMENTS.

ACOUSTICAL CEILINGS ACCESS IDENTIFICATION MARKERS: COLORED MARKERS

WITH PRESSURE SENSITIVE ADHESIVE ON ONE SIDE, PAPER OR PLASTIC, 6 TO 9 MM

(1/4 TO 3/8 INCH) DIAMETER. REFER TO SPECIFICATION 09 51 00 SECTION 2.6.C.

COLOR CODE: PROVIDE THE FOLLOWING COLOR MARKERS FOR SERVICE

IDENTIFICATION:

RED - SPRINKLER SYSTEM: VALVES AND CONTROLS.

GREEN - DOMESTIC WATER: VALVES AND CONTROLS.

YELLOW - CHILLED WATER AND HEATING WATER.

ORANGE - DUCTWORK: FIRE DAMPERS.

BLUE - DUCTWORK: DAMPERS AND CONTROLS.

BLACK - GAS: LABORATORY, MEDICAL, AIR AND VACUUM.

COMPLETE LAYOUT DRAWINGS WILL BE REQUIRED BY PARAGRAPH, SUBMITTALS.

CONSTRUCTION WORK WILL NOT START ON ANY SYSTEM UNTIL THE LAYOUT

DRAWINGS HAVE BEEN APPROVED BY VA.

PHASING/ BID NOTES

PHASING: REFER TO ARCHITECTURAL DRAWINGS FOR AN OUTLINE OF PROJECT

PHASING. ADDITIONAL NOTES DESCRIBING PHASING DETAILS MAY BE INCLUDED

THROUGHOUT THIS DRAWING SET.

BID ITEMS: REFER TO ARCHITECTURAL DRAWING AND SPECIFICATION SECTION

01 00 00 FOR AN OUTLINE OF BID ITEMS. ADDITIONAL NOTES DESCRIBING BID ITEM

DETAILS MAY BE INCLUDED THROUGHOUT THIS DRAWING SET.

0-HR Smoke Partition - [IBC 710] / NFPA 101-8.4

1-HR Smoke Barrier - [IBC 709] / NFPA 101-8.5

1-HR Fire Barrier - [IBC 706] / NFPA 101-8.3

2-HR Fire Barrier - [IBC 706] / NFPA 101-8.3

Existing Wall to Remain

New Wall

CODE LEGEND

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Date:Revisions:No.

C :\U se rs

\b sg ay do s\ Ap pD at a\ Lo ca l\A ut od es k\

R ev it\ Au to de sk R ev it

\C ol la bo ra tio nC ac he \F

G L2

C N

YF

N

2R

VU

3\

5d 1a c9

-2 ae

8-

-b f-c ff8 3c

3d

3a \e e-fd

-4 d-ab

-2 dc f.r vt 5/

5/

:4 3:

P

M

P001

ABBREVIATIONS, SYMBOLS &

INDEX OF DRAWINGS

05/07/2026 EWL BSG

CONSTRUCT NEW

CAMPUS CHILLER PLANT

657A5-21-401

2401 W MAIN ST, MARION IL 62959

CONTRACT

DOCUMENTS 49

MARION VA

MEDICAL

CENTER Approved: Owner

INDEX OF DRAWINGS

SHEET NUMBER SHEET NAME

P001 ABBREVIATIONS, SYMBOLS & INDEX OF DRAWINGS

PS001 SITE PLAN

PD001 UNDERSLAB PLAN - DEMOLITION

PD101 FIRST FLOOR PLAN - DEMOLITION

PP001 UNDERSLAB PLAN

PP101 FIRST FLOOR PLAN - DRAINAGE

PP102 MEZZANINE PLAN - DRAINAGE

PP201 ROOF PLAN - DRAINAGE

PL101 FIRST FLOOR PLAN - DISTRIBUTION

PL102 MEZZANINE PLAN - DISTRIBUTION

P601 SCHEDULES AND DETAILS

P901 SANITARY ISOMETRIC

P902 STORM ISOMETRIC

P903 DOMESTIC ISOMETRIC

D

632 54

B

C

PROPOSED BUILDING

APPROX. 7,280 Square Feet

FFE = 470'-6"

DS

DS

P-801

P-801

P-801 4"

W

S 8" - STM

P601

P601

CO

P-801

6" - SAN

CO

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Date:Revisions:No.

C :\U se rs

\b sg ay do s\ Ap pD at a\ Lo ca l\A ut od es k\

R ev it\ Au to de sk R ev it

\C ol la bo ra tio nC ac he \F

G L2

C N

YF

N

2R

VU

3\

5d 1a c9

-2 ae

8-

-b f-c ff8 3c

3d

3a \e e-fd

-4 d-ab

-2 dc f.r vt 5/

5/

:4 4:

P

M

PS001

SITE PLAN

05/07/2026 EWL BSG

CONSTRUCT NEW

CAMPUS CHILLER PLANT

657A5-21-401

2401 W MAIN ST, MARION IL 62959

CONTRACT

DOCUMENTS 49

MARION VA

MEDICAL

CENTER Approved: Owner

1/8" = 1'-0"

PLUMBING SITE PLAN

SITE KEY PLAN

NEW CHILLER PLANT - BLDG 49

EXISTING CHILLER PLANT - BLDG 49

37MOD-5

MOD-1

49 MOD-4

MOD-6

NORTH

SHEET NOTES

A.

B.

REFER TO SHEET P001 FOR ABBREVIATIONS, SYMBOLS & GENERAL NOTES.

ANY WORK REQUIRED OUTSIDE OF PROJECT SCOPE AREA FOR REMOVALS, SERVICE INTERRUPTIONS, OR TEMPORARY SERVICES TO BE

CLOSELY COORDINATED WITH COR A MINIMUM OF FIVE (5) WORKING DAYS AHEAD OF TIME.

NOTES

1 PIPING INDICATED IS BELOW GROUND.

2"

V

2"

V3"

SA

N

3" - SAN

3" - SAN

2" -

SAN

4"

SA

N

3" - SAN3" - SAN

UP2" V UP2" VUP2" VSK

FD

FD

CO

FD

FD

LAV

WC

UP2" V

UP3" WS

W S

3"

TYP.

TYP.

TYP.

TYP.

TYP.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Date:Revisions:No.

C :\U se rs

\b sg ay do s\ Ap pD at a\ Lo ca l\A ut od es k\

R ev it\ Au to de sk R ev it

\C ol la bo ra tio nC ac he \F

G L2

C N

YF

N

2R

VU

3\

5d 1a c9

-2 ae

8-

-b f-c ff8 3c

3d

3a \e e-fd

-4 d-ab

-2 dc f.r vt 5/

5/

:4 4:

P

M

PD001

UNDERSLAB PLAN - DEMOLITION

05/07/2026 EWL BSG

CONSTRUCT NEW

CAMPUS CHILLER PLANT

657A5-21-401

2401 W MAIN ST, MARION IL 62959

CONTRACT

DOCUMENTS 49

MARION VA

MEDICAL

CENTER Approved: Owner

1/4" = 1'-0"

UNDERSLAB PLUMBING PLAN - DEMOLITION

PLAN NOTES

1 DEMOLISH WATER SERVICE BACK TO NEAREST MAIN AND CAP. REVIEW SITE CIVIL DRAWINGS FOR ADDITIONAL

DETAIL. COORDINATE WORK WITH CONTRACTOR PERFORMING SITE WORK.

2 DEMOLISH SANITARY SEWER CONNECTION BACK TO NEAREST MANHOLE AND CAP. REVIEW SITE CIVIL DRAWINGS FOR ADDITIONAL DETAIL. COORDINATE WORK WITH CONTRACTOR PERFORMING SITE WORK.

3 DEMOLISH PIPING IN ITS ENTIRETY.

SITE KEY PLAN

NEW CHILLER PLANT - BLDG 49

EXISTING CHILLER PLANT - BLDG 49

37MOD-5

MOD-1

49 MOD-4

MOD-6

NORTH

SHEET NOTES

A.

B.

C.

REFER TO SHEET P001 FOR ABBREVIATIONS, SYMBOLS & GENERAL NOTES.

COORDINATE ALL WORK WITH CONSTRUCTION MANAGER'S PHASING REQUIREMENTS.

ANY WORK REQUIRED OUTSIDE OF PROJECT SCOPE AREA FOR REMOVALS, SERVICE INTERRUPTIONS, OR TEMPORARY SERVICES TO BE

BF

P

FD

FD FD

FCO

FD

EW SK

WH

LAV

WC

FCO

1.25"

2.5"

0.75" 0.5"

2"

V

2" - V

3" VTR

WATER

TREATMENT

0.5"

3" VTR

1.5

V

2.5"

TYP.

TYP.

TYP.

TYP.

2" - V

DN3" WS

HB

HB

DN2" V DN2" V DN2" V

DN2" V

DCW

DC

W

DCW

DC

W

DH

W

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

2.5"

NP

W

TYP.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Date:Revisions:No.

C :\U se rs

\b sg ay do s\ Ap pD at a\ Lo ca l\A ut od es k\

R ev it\ Au to de sk R ev it

\C ol la bo ra tio nC ac he \F

G L2

C N

YF

N

2R

VU

3\

5d 1a c9

-2 ae

8-

-b f-c ff8 3c

3d

3a \e e-fd

-4 d-ab

-2 dc f.r vt 5/

5/

:4 4:

P

M

PD101

FIRST FLOOR PLAN - DEMOLITION

05/07/2026 EWL BSG

CONSTRUCT NEW

CAMPUS CHILLER PLANT

657A5-21-401

2401 W MAIN ST, MARION IL 62959

CONTRACT

DOCUMENTS 49

MARION VA

MEDICAL

CENTER Approved: Owner

1/4" = 1'-0"

PLUMBING FIRST FLOOR - DEMOLITION

PLAN NOTES

1 WATER PIPING EXTENDING TO FIRE SERVICE. SEE FIRE SUPPRESSION DRAWINGS FOR ADDITIONAL DETAIL.

2 REMOVE EXISTING FIXTURE, PIPING, OR ITEM OF EQUIPMENT (TYPE AS INDICATED) COMPLETE.

3 MECHANICAL EQUIPMENT SHOWN FOR REFERENCE ONLY.

4 PIPING EXTENDS TO MECHANICAL EQUIPMENT. REFER TO MECHANICAL DRAWINGS FOR ADDITIONAL DETAIL.

COORDINATE DEMOLITION WITH MECHANICAL CONTRACTOR.

SITE KEY PLAN

NEW CHILLER PLANT - BLDG 49

EXISTING CHILLER PLANT - BLDG 49

37MOD-5

MOD-1

49 MOD-4

MOD-6

NORTH

SHEET NOTES

A.

B.

C.

REFER TO SHEET P001 FOR ABBREVIATIONS, SYMBOLS & GENERAL NOTES.

COORDINATE ALL WORK WITH CONSTRUCTION MANAGER'S PHASING REQUIREMENTS.

ANY WORK REQUIRED OUTSIDE OF PROJECT SCOPE AREA FOR REMOVALS, SERVICE INTERRUPTIONS, OR TEMPORARY SERVICES TO BE

D

632 54

B

C

P-502

FD-D

FD-D

FD-D

FD-D

FD-S

FD-C

6" - SAN 6" - SAN

4"

SA

N

4"

SA

N

4" - SAN

3" - SAN

3" - SAN

4" -

SAN

ST

M

8" (340 GPM)

INV: 467'-0"

INV: 467'-0"

CO

CO

FD-C

FD-C

CO

4"

W S

HD

CO

6"

SA

N

6"

SA

N SP-1B

P601

SP-1A

P-103

6" - SAN

FD-S

4"

SA

N

UP2" V

UP4" WS UP2" V

6" - SAN 6" - SAN

FD-D

UP2" V

UP2" V3" -

SAN

CO

CO

UP2" V

4" - SAN

3"

SA

N

FD-D

FD-D

UP2" V

UP2" V

FD-D

3"

SA

N

UP2" V

8" UP

(340 GPM)

UP2" V UP2" V

UP2" V

P-414

4" - SAN

3"

SA

N

UP2" V

FD-D

CO

4" - SAN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Date:Revisions:No.

C :\U se rs

\b sg ay do s\ Ap pD at a\ Lo ca l\A ut od es k\

R ev it\ Au to de sk R ev it

\C ol la bo ra tio nC ac he \F

G L2

C N

YF

N

2R

VU

3\

5d 1a c9

-2 ae

8-

-b f-c ff8 3c

3d

3a \e e-fd

-4 d-ab

-2 dc f.r vt 5/

5/

:4 4:

P

M

PP001

UNDERSLAB PLAN

05/07/2026 EWL BSG

CONSTRUCT NEW

CAMPUS CHILLER PLANT

657A5-21-401

2401 W MAIN ST, MARION IL 62959

CONTRACT

DOCUMENTS 49

MARION VA

MEDICAL

CENTER Approved: Owner

1/4" = 1'-0"

UNDERSLAB PLUMBING PLAN

PLAN NOTES

1 NO PIPING TO BE INSTALLED IN THIS AREA.

SITE KEY PLAN

NEW CHILLER PLANT - BLDG 49

EXISTING CHILLER PLANT - BLDG 49

37MOD-5

MOD-1

49 MOD-4

MOD-6

NORTH

SHEET NOTES

A.

B.

REFER TO SHEET P001 FOR ABBREVIATIONS, SYMBOLS & GENERAL NOTES.

ANY WORK REQUIRED OUTSIDE OF PROJECT SCOPE AREA FOR REMOVALS, SERVICE INTERRUPTIONS, OR TEMPORARY SERVICES TO BE

D

632 54

B

C

CONTROL

ROOM

H.A.C.

TR

ELECTRICAL

ROOM

ELECTRICAL

ROOM

P-103

P-414

P-502

FD-D

FD-S

FD-D

FD-D

FD-D

FD-D

UP2" V

8" UP & DN

(340 GPM)

8" OD UP

(225 GPM)

FD-C

DS

DS

6" OD UP

(115 GPM)

FCO

FCO

TOILET

FCO

FD-C

FD-C

TYP.

TYP.

TYP.

TYP.

TYP.

TYP.

DN2" V

FCO

3"

V

CO

2" - V

DN2" V

DN2" V

FD-D

PUMP

CONTROL

PANEL

FD-S 6" HD3

DN2" V

UP3" V

DN2" V

2" - V

DN2" VDN2" V

DN2" V 2" - V

CO

CO

DN2" V

FD-D

FD-D

UP & DN2" V

P601

3" - V

DN2" V 2" - PD

DN1.5" PD

2"

V

P601

P601

UP2" V

FD-D

3" - V2" - V2" - V

UP2" V

DN3" SAN

3" - SAN

FD-D

FCO

DN2" V

2" - V

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Date:Revisions:No.

C :\U se rs

\b sg ay do s\ Ap pD at a\ Lo ca l\A ut od es k\

R ev it\ Au to de sk R ev it

\C ol la bo ra tio nC ac he \F

G L2

C N

YF

N

2R

VU

3\

5d 1a c9

-2 ae

8-

-b f-c ff8 3c

3d

3a \e e-fd

-4 d-ab

-2 dc f.r vt 5/

5/

:4 4:

P

M

PP101

FIRST FLOOR PLAN - DRAINAGE

05/07/2026 EWL BSG

CONSTRUCT NEW

CAMPUS CHILLER PLANT

657A5-21-401

2401 W MAIN ST, MARION IL 62959

CONTRACT

DOCUMENTS 49

MARION VA

MEDICAL

CENTER Approved: Owner

1/4" = 1'-0"

FIRST FLOOR PLUMBING PLAN - DRAINAGE

PLAN NOTES

1 NO PIPING TO BE INSTALLED IN THIS AREA.

2 MECHANICAL AND ELECTRICAL EQUIPMENT SHOWN FOR REFERENCE ONLY.

3 ROUTE DRAIN PIPING FROM EFFLUENT PUMPS TO STANDPIPE WITH AIRGAP.

SITE KEY PLAN

NEW CHILLER PLANT - BLDG 49

EXISTING CHILLER PLANT - BLDG 49

37MOD-5

MOD-1

49 MOD-4

MOD-6

NORTH

SHEET NOTES

A.

B.

REFER TO SHEET P001 FOR ABBREVIATIONS, SYMBOLS & GENERAL NOTES.

ANY WORK REQUIRED OUTSIDE OF PROJECT SCOPE AREA FOR REMOVALS, SERVICE INTERRUPTIONS, OR TEMPORARY SERVICES TO BE

D

632 54

B

C

TYP.

CO

6" (115 GPM)

6" (215 GPM)

8" DN

(340 GPM) 8" DN

(225 GPM)

RD1

OD1

RD1

OD1

RD1

OD1

8" (225 GPM)

8" (340 GPM)

OD

ST

M

STMSTM

OD

6" (125 GPM)

6" (100 GPM)

OD

CO

6" DN

(115 GPM)

MEZZANINE

CHILLER

PLANT

2"

V

6" (100 GPM)

VTR

DN2" V

OD

6" (115 GPM)

VTR

DN2" V

FD-D

DN2" V

DN2" V

6" (125 GPM)

STM

VTR

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Date:Revisions:No.

C :\U se rs

\b sg ay do s\ Ap pD at a\ Lo ca l\A ut od es k\

R ev it\ Au to de sk R ev it

\C ol la bo ra tio nC ac he \F

G L2

C N

YF

N

2R

VU

3\

5d 1a c9

-2 ae

8-

-b f-c ff8 3c

3d

3a \e e-fd

-4 d-ab

-2 dc f.r vt 5/

5/

:4 4:

P

M

PP102

MEZZANINE PLAN - DRAINAGE

05/07/2026 EWL BSG

CONSTRUCT NEW

CAMPUS CHILLER PLANT

657A5-21-401

2401 W MAIN ST, MARION IL 62959

CONTRACT

DOCUMENTS 49

MARION VA

MEDICAL

CENTER Approved: Owner

1/4" = 1'-0"

MEZZANINE PLUMBING PLAN - DRAINAGE

NOTES

1 MECHANICAL EQUIPMENT SHOWN FOR REFERENCE ONLY.

2 OPEN TO FLOOR BELOW.

SITE KEY PLAN

NEW CHILLER PLANT - BLDG 49

EXISTING CHILLER PLANT - BLDG 49

37MOD-5

MOD-1

49 MOD-4

MOD-6

NORTH

SHEET NOTES

A.

B.

REFER TO SHEET P001 FOR ABBREVIATIONS, SYMBOLS & GENERAL NOTES.

ANY WORK REQUIRED OUTSIDE OF PROJECT SCOPE AREA FOR REMOVALS, SERVICE INTERRUPTIONS, OR TEMPORARY SERVICES TO BE

D

632 54

B

C

RD1

125 GPM

OD1

125 GPM

OD1

100 GPM

RD1

100 GPM

RD1

115 GPM

OD1

115 GPM

VTR

3"

P-806

TYP.

TYP.

VTR

4"

TYP.

VTR

3"

A

D

1 32

B

C

A.4

A.6

'-0

25'-0"

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Date:Revisions:No.

C :\U se rs

\b sg ay do s\ Ap pD at a\ Lo ca l\A ut od es k\

R ev it\ Au to de sk R ev it

\C ol la bo ra tio nC ac he \F

G L2

C N

YF

N

2R

VU

3\

5d 1a c9

-2 ae

8-

-b f-c ff8 3c

3d

3a \e e-fd

-4 d-ab

-2 dc f.r vt 5/

5/

:4 4:

P

M

PP201

ROOF PLAN - DRAINAGE

05/07/2026 EWL BSG

CONSTRUCT NEW

CAMPUS CHILLER PLANT

657A5-21-401

2401 W MAIN ST, MARION IL 62959

CONTRACT

DOCUMENTS 49

MARION VA

MEDICAL

CENTER Approved: Owner

1/4" = 1'-0"

PLUMBING ROOF PLAN - DRAINAGE

PLAN NOTES

1 MECHANICAL EQUIPMENT SHOWN FOR REFERENCE ONLY.

2 SANITARY VENTS MUST BE AT LEAST 25'-0" FROM NEAREST HVAC AIR INTAKE.

SITE KEY PLAN

NEW CHILLER PLANT - BLDG 49

EXISTING CHILLER PLANT - BLDG 49

37MOD-5

MOD-1

49 MOD-4

MOD-6

NORTH

SHEET NOTES

A.

B.

REFER TO SHEET P001 FOR ABBREVIATIONS, SYMBOLS & GENERAL NOTES.

ANY WORK REQUIRED OUTSIDE OF PROJECT SCOPE AREA FOR REMOVALS, SERVICE INTERRUPTIONS, OR TEMPORARY SERVICES TO BE

BFP

M BFP

M

A

D

632 54

B

C

CONTROL

ROOM

H.A.C.

TR

ELECTRICAL

ROOM

ELECTRICAL

ROOM

TYP.

TYP.

TYP.

TYP.

P-103

P-414

P-502

DN4" WS

3"

1.5" 1"

1.5"

DWH-1

TMV-E

P-709

P-801

0.75"

0.5"

ET-1

P-801

P-801

0.5"

0.5"

P601

P-801

UP3" DCW

UP0.75" DCW

UP0.75" DCW

TYP.

P-802

P-802

2.5"7

UP3" DCW

0.75"

0.75"0.5"

1.25" TYP.

TYP.

TYP.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Date:Revisions:No.

C :\U se rs

\b sg ay do s\ Ap pD at a\ Lo ca l\A ut od es k\

R ev it\ Au to de sk R ev it

\C ol la bo ra tio nC ac he \F

G L2

C N

YF

N

2R

VU

3\

5d 1a c9

-2 ae

8-

-b f-c ff8 3c

3d

3a \e e-fd

-4 d-ab

-2 dc f.r vt 5/

5/

:4 4:

P

M

PL101

FIRST FLOOR PLAN -

DISTRIBUTION

05/07/2026 EWL BSG

CONSTRUCT NEW

CAMPUS CHILLER PLANT

657A5-21-401

2401 W MAIN ST, MARION IL 62959

CONTRACT

DOCUMENTS 49

MARION VA

MEDICAL

CENTER Approved: Owner

1/4" = 1'-0"

FIRST FLOOR PLUMBING PLAN - DISTRIBUTION

PLAN NOTES

1 NO PIPING TO BE INSTALLED IN THIS AREA.

2 PIPING EXTENDS TO SERVE FIRE SUPPRESSION SYSTEM. SEE FIRE PROTECTION SHEETS FOR FURTHER

DETAIL.

3 MECHANICAL AND ELECTRICAL EQUIPMENT SHOWN FOR REFERENCE ONLY

4 PIPING EXTENDS TO MECHANICAL EQUIPMENT. REFER TO MECHANICAL DRAWINGS FOR ADDITIONAL DETAIL.

5 MAKE-UP WATER METER FROM MARION WATER DEPARTMENT. INSTALL PER MARION WATER DEPARTMENT

REQUIREMENTS. CONNECT WATER METER TO VA WATER METERING SYSTEM.

6 CONNECT WATER METER TO THE VA METERING SYSTEM. INSTALL WATER METER PER MARION WATER

DEPARTMENT REQUIREMENTS.

7 ROUTE DRAINAGE OF BACKFLOW PREVENTER TO NEARBY MOP BASIN.

SITE KEY PLAN

NEW CHILLER PLANT - BLDG 49

EXISTING CHILLER PLANT - BLDG 49

37MOD-5

MOD-1

49 MOD-4

MOD-6

NORTH

SHEET NOTES

A.

B.

REFER TO SHEET P001 FOR ABBREVIATIONS, SYMBOLS & GENERAL NOTES.

ANY WORK REQUIRED OUTSIDE OF PROJECT SCOPE AREA FOR REMOVALS, SERVICE INTERRUPTIONS, OR TEMPORARY SERVICES TO BE

D

632 54

B

C

P-806

DN0.75" DCW

DN3" DCW

DN0.75" DCW

DN3" DCW

1TYP.

TYP.

P-802

0.75"

3"

0.75" 3"

3"

0.75"

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

VA FORM 08 - 6231

A

FULLY SPRINKLERED

U.S. Department of Veterans Affairs

B

C

D

E

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Date:Revisions:No.

C :\U se rs

\b sg ay do s\ Ap pD at a\ Lo ca l\A ut od es k\

R ev it\ Au to de sk R ev it

\C ol la bo ra tio nC ac he \F

G L2

C N

YF

N

2R

VU

3\

5d 1a c9

-2 ae

8-

-b f-c ff8 3c

3d

3a \e e-fd

-4 d-ab

-2 dc f.r vt 5/

5/

:4 4:

P

M

PL102

MEZZANINE PLAN - DISTRIBUTION

05/07/2026 EWL BSG

CONSTRUCT NEW

CAMPUS CHILLER PLANT

657A5-21-401

2401 W MAIN ST, MARION IL 62959

CONTRACT

DOCUMENTS 49

MARION VA

MEDICAL

CENTER Approved: Owner

1/4" = 1'-0"

PLUMBING 02-MEZZANINE

SITE KEY PLAN

NEW CHILLER PLANT - BLDG 49

EXISTING CHILLER PLANT - BLDG 49

37MOD-5

MOD-1

49 MOD-4

MOD-6

NORTH

SHEET NOTES

A.

B.

REFER TO SHEET P001 FOR ABBREVIATIONS, SYMBOLS & GENERAL NOTES.

ANY WORK REQUIRED OUTSIDE OF PROJECT SCOPE AREA FOR REMOVALS, SERVICE INTERRUPTIONS, OR TEMPORARY SERVICES TO BE

CLOSELY COORDINATED WITH COR A MINIMUM OF FIVE (5) WORKING DAYS AHEAD OF TIME.

PLAN NOTES

1 OPEN TO…