631-25-001 Drawings.pdf

PDF 2 MB Posted

Attached to
5920--631-25-001 Building 1 Lightning Protection
Solicitation number
36C24125R0031
Issued by

About this file

These are construction drawings for a lightning protection system upgrade project at Building 1 (Liberty Building) of the VA Medical Center in Central Western Massachusetts. The drawings include detailed lightning protection plans, system details, and grounding details dated May 30, 2023.

The drawings show roof-level lightning protection plans with air terminals, down conductors, and grounding systems for the Liberty Building. Specific technical details are provided for various components including crossover cable connectors, pipe clamps, bonding lugs, air terminal bases, and grounding connections. The plans indicate both existing building features (like the greenhouse and slate roof areas) and new lightning protection system elements to be installed. The drawings include standard notes regarding installation requirements, testing procedures, and material specifications for the lightning protection system components.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

CATWALK CATWALK

1E-A 1WA

I

L

N

V

V

V

V

V

V

V

V

V

V V

V

V V V

V V

V

V

V

V

V

V

V

V

V

V

V

V

V

V

V

V

V

V

V

V

V

OPEN

OPEN

EXISTING

GREENHOUSE

V

VV

V

V

V

V

V

V

V

01-EP112

LIGHTNING PROTECTION PLAN -

LIBERTY BLDG 01

W.H.H. E.J.D.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

CONSTRUCTION

DOCUMENTS

MAY 30, 2023

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

ELECTRICAL DISTRIBUTION

SYSTEM UPGRADE - PHASE 2

VA CWM

631-18-003

Project Director

MAY 30, 2023Revisions: Date:

© Copyright 2020 DuBois & King Inc.

85 MAIN STREET

SPRINGFIELD, VT 05156

TEL: (802) 591-4326

FAX: (866) 783-7101

www.dubois-king.com

I:\ 5\

V

AM

C

E le c D is t P ha se

3\ D ra w in gs

\E le ct ric al \0

1-

EP

LI

G

H

TN

IN

G

P R

O

TE

C

TI

O N

P

LA

N

LI

BE

R

TY

B

LD

G .d w g

1/

2/

:1 6:

PM

AutoCAD SHX Text

DORMER (TYPICAL)

AutoCAD SHX Text

RIDGE LINES

AutoCAD SHX Text

SLATE ROOF

AutoCAD SHX Text

LOWER LEVEL FLAT ROOF

AutoCAD SHX Text

UPPER LEVEL FLAT ROOF

AutoCAD SHX Text

VENT (TYPICAL)

AutoCAD SHX Text

BASEMENT

AutoCAD SHX Text

FIRST FLR.

AutoCAD SHX Text

SECOND FLR.

AutoCAD SHX Text

T.O. ATTIC SLAB

AutoCAD SHX Text

BASEMENT FLR.

AutoCAD SHX Text

FIRST FLR.

AutoCAD SHX Text

SECOND FLR.

AutoCAD SHX Text

T.O. ATTIC SLAB

AutoCAD SHX Text

FINISH GRADE

AutoCAD SHX Text

FINISH GRADE VARIES

AutoCAD SHX Text

BUILDING 1WA. SUPPLIES POWER TO WEST SIDE OF BUILDING

AutoCAD SHX Text

BUILDING 1EA. SUPPLIED POWER TO EAST SIDE OF BUILDING

AutoCAD SHX Text

BOND ALL ROOF TOP EQUIPMENT /HATCH

AutoCAD SHX Text

ROOF EQUIPMENT

AutoCAD SHX Text

BOND ALL ROOF VENTS (TYPICAL)

AutoCAD SHX Text

LIGHTNING PROTECTION DOWN LEADS ON 100' MAX PERIMETER SPACING.

AutoCAD SHX Text

LIGHTNING TERMINALS OR RIDGE AT MAX OF 25' SPACING

AutoCAD SHX Text

TYPICAL DORMERS

AutoCAD SHX Text

TYPICAL PLUMBING VENTS

AutoCAD SHX Text

GROUND DROPS LOCATED AT 100' MAX LINEAR SPACING AROUND BUILDING PERIMETER.

AutoCAD SHX Text

ROOF CATWALK

AutoCAD SHX Text

REFER TO DETAILS ON SHEET ESS503 (TYPICAL)

AutoCAD SHX Text

TYPICAL AIR TERMINAL, REFER TO SHEET ESS503

AutoCAD SHX Text

AutoCAD SHX Text 16'

AutoCAD SHX Text 32'

AutoCAD SHX Text 8'

AutoCAD SHX Text

AutoCAD SHX Text

SCALE: 1/16" = 1'-0" (BASE BID)

AutoCAD SHX Text BUILDING No. 1 - LIBERTY BUILDING - SOUTH ELEVATION

AutoCAD SHX Text

AutoCAD SHX Text 16'

AutoCAD SHX Text 32'

AutoCAD SHX Text 8'

AutoCAD SHX Text

AutoCAD SHX Text LIGHTNING PROTECTION SYSTEM NOTES: 1. DRAWINGS ARE PROVIDED AS GUIDES FOR LIGHTNING DRAWINGS ARE PROVIDED AS GUIDES FOR LIGHTNING PROTECT SYSTEM DESIGNER FINAL DRAWINGS BY LIGHTNING PROTECTION SYSTEM DESIGN SHALL BE PROVIDED AFTER FIELD VERIFICATION OF SITE CONDITIONS. LIGHTNING SYSTEM DESIGNER SHALL PROVIDE DRAWING AS PART OF SHOP DRAWING SUBMITTAL, REFER TO SPECIFICATIONS. 2. THE LIGHTNING PROTECTION SYSTEM SHALL BE DESIGNED THE LIGHTNING PROTECTION SYSTEM SHALL BE DESIGNED PER NFPA 780 AND U.L. MASTER LABELED. LIGHTNING PROTECTION SYSTEM SHALL BE UL TESTED & INSPECTED. 3. ALL GROUND RODS/SYSTEMS SHOULD MEET THE MIN ALL GROUND RODS/SYSTEMS SHOULD MEET THE MIN RESISTANCE AND TESTED TO MEET NFPA70/780 FOR A LIGHTNING PROTECTION SYSTEM. THE SYSTEM SHALL BE TESTED PRIOR TO THE UL INSPECTION. 4. REFER TO ONE-LINE DIAGRAMS FOR SURGE PROTECTIVE REFER TO ONE-LINE DIAGRAMS FOR SURGE PROTECTIVE DEVICES (SPD) IS BEING INSTALLED AS PART OF THIS PROJECT. THE SPD MAYBE LOCATED IN THE GENERATOR BUILDING LOCATED NEXT TO THE BUILDING. 5. BUILDING No. 1 HAS NORMAL POWER FROM PANELS BUILDING No. 1 HAS NORMAL POWER FROM PANELS 1EA-MDP, 1WA-MDP & 1S-MDP WITH NEW SPD IN AND LIFE SAFETY, CRITICAL & EQUIPMENT BRANCH POWER FROM BUILDINGS No. 1EA & 1WA.

AutoCAD SHX Text

SCALE: 1/16" = 1'-0" (BASE BID)

AutoCAD SHX Text

BUILDING NO. 1 - LIBERTY BUILDING ROOF LEVEL LIGHTNING PROTECTION PLAN

AutoCAD SHX Text

PARTIAL LEGEND: CLASS 1 CABLE AIR TERMINAL DOWNLEAD TO GROUND ROD

AutoCAD SHX Text

AutoCAD SHX Text

ESS503

LIGHTNING PROTECTION SYSTEM

DETAILS --

W.H.H. E.J.D.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

CONSTRUCTION

DOCUMENTS

MAY 30, 2023

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

ELECTRICAL DISTRIBUTION

SYSTEM UPGRADE - PHASE 2

VA CWM

631-18-003

Project Director

MAY 30, 2023Revisions: Date:

© Copyright 2020 DuBois & King Inc.

85 MAIN STREET

SPRINGFIELD, VT 05156

TEL: (802) 591-4326

FAX: (866) 783-7101

www.dubois-king.com

I:\ 5\

V

AM

C

E le c D is t P ha se

3\ D ra w in gs

\E le ct ric al \6

-1

8-

ES

S5

L

IG

H

TN

IN

G

P R

O

TE

C

TI

O N

S

YS

TE

M

D

ET

AI

LS

.d w g

1/ 2/

4:

:3

PM

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

WATERLINE BONDING STRAP

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

BONDING STRAP AT (VENT PIPES)

AutoCAD SHX Text

2" WIDE COPPER STRAP

AutoCAD SHX Text

SYMBOL

AutoCAD SHX Text

COPPER CONDUCTOR

AutoCAD SHX Text

COPPER ADHESIVE

AutoCAD SHX Text

EVERY 3'-0" MAX.

AutoCAD SHX Text

CABLE FASTENER

AutoCAD SHX Text 3/8" x 12" SOLID COPPER

AutoCAD SHX Text

AIR TERMINAL

AutoCAD SHX Text

ADHESIVE BASE

AutoCAD SHX Text

CAST COPPER

AutoCAD SHX Text LIGHTNING PROTECTION STANDARD NOTES: 1. THE LIGHTNING PROTECTION SYSTEM AS SHOWN ON ROOF DRAWINGS HAS THE LIGHTNING PROTECTION SYSTEM AS SHOWN ON ROOF DRAWINGS HAS BEEN DESIGNED IN ACCORDANCE WITH PROJECT LIGHTNING PROTECTION SYSTEM SPECIFICATION. THE INSTALLATION SHALL COMPLY WITH THE SPECIFICATION AND NFPA 780. FINAL LAYOUT SHALL BE BY THE LIGHTNING PROTECTION DRAWINGS. 2. THE LIGHTNING PROTECTION SYSTEM SHALL BE A U.L. LABELED SYSTEM FOR THE LIGHTNING PROTECTION SYSTEM SHALL BE A U.L. LABELED SYSTEM FOR EACH BUILDING 3. CONDUCTORS SHALL MAINTAIN A HORIZONTAL OR DOWNWARD COURSE, FREE CONDUCTORS SHALL MAINTAIN A HORIZONTAL OR DOWNWARD COURSE, FREE FROM ''U'' OR ''V'' (DOWN AND UP) POCKETS. 4. NO BEND OF A CONDUCTOR SHALL FORM AN ANGLE OF LESS THAN 90°NOR NO BEND OF A CONDUCTOR SHALL FORM AN ANGLE OF LESS THAN 90°NOR SHALL HAVE A RADIUS OF BEND LESS THAN 8 INCHES. 5. AIR TERMINALS SHALL BE PLACED 20'-0'' MAXIMUM SPACING AROUND THE AIR TERMINALS SHALL BE PLACED 20'-0'' MAXIMUM SPACING AROUND THE ROOF PERIMETER OR ALONG ROOF RIDGES AND WITHIN 2'-0'' OF OUTSIDE CORNER EDGE. 6. MID ROOF AIR TERMINALS SHALL BE PLACED 50'-0'' MAXIMUM SPACING. MID ROOF AIR TERMINALS SHALL BE PLACED 50'-0'' MAXIMUM SPACING. 7. ACTUAL JOB SITE CONDITIONS MAY REQUIRE SLIGHT ALTERATIONS IN AIR ACTUAL JOB SITE CONDITIONS MAY REQUIRE SLIGHT ALTERATIONS IN AIR TERMINAL, DOWN CONDUCTOR AND GROUND ROD LOCATIONS. 8. BARE COPPER MATERIALS SHALL NOT BE INSTALLED ON ALUMINUM SURFACES BARE COPPER MATERIALS SHALL NOT BE INSTALLED ON ALUMINUM SURFACES AND ALUMINUM MATERIALS SHALL NOT BE INSTALLED ON COPPER SURFACES. 9. ALL LIGHTNING PROTECTION CONDUCTORS SHALL BE FASTENED HORIZONTALLY ALL LIGHTNING PROTECTION CONDUCTORS SHALL BE FASTENED HORIZONTALLY AND VERTICALLY NOT MORE THAN 3'-0'' O.C. MAXIMUM SPACING. 10. METALLIC BODIES OF INDUCTANCE SITUATED WITHIN 6'-0'' OF A LIGHTNING METALLIC BODIES OF INDUCTANCE SITUATED WITHIN 6'-0'' OF A LIGHTNING CONDUCTOR OR ANOTHER BONDED METAL BODY SHALL BE INTERCONNECTED TO THE LIGHTNING CONDUCTOR SYSTEM, UNLESS INHERENTLY GROUNDED. 11. BOND TO ALL METAL BODIES OF CONDUCTANCE WITHIN 6'-0'' OF THE MAIN BOND TO ALL METAL BODIES OF CONDUCTANCE WITHIN 6'-0'' OF THE MAIN LIGHTNING CONDUCTOR SUCH AS EXHAUST FANS, ROOF VENTS, METAL COOLING TOWERS, H.V.A.C. UNITS, LADDERS, RAILINGS, ANTENNAS, SKYLIGHT FRAMES, METAL STACKS AND ANY OTHER LARGE METAL BODY WHOSE HEIGHT EXCEEDS THAT OF THE AIR TERMINALS IN USE, UNLESS PROTECTED BY HIGHER ROOF ELEVATIONS. 12. CONNECTIONS TO GROUND ROD SHALL BE MADE AT A POINT NOT LESS CONNECTIONS TO GROUND ROD SHALL BE MADE AT A POINT NOT LESS THAN 1'-0'' BELOW FINISHED GRADE AND 2'-0'' AWAY FROM FOUNDATION WALL. 13. BOND TO WATERLINES (DOMESTIC & FIRE). BOND TO WATERLINES (DOMESTIC & FIRE). 14. A LIGHTNING ARRESTOR, PROTECTOR OR ANTENNA DISCHARGE UNIT SHALL BE A LIGHTNING ARRESTOR, PROTECTOR OR ANTENNA DISCHARGE UNIT SHALL BE INSTALLED ON EACH ELECTRIC AND TELEPHONE SERVICE AND RADIO AND TELEVISION ANTENNA LEAD-IN BY THE ELECTRICAL CONTRACTOR, OR OTHERS, PER NFPA-70. 15. ROOF PLAN DOES NOT SHOW ALL ROOF GRADE MOUNTED EQUIPMENT (ROOF ROOF PLAN DOES NOT SHOW ALL ROOF GRADE MOUNTED EQUIPMENT (ROOF TOP UNITS, AIR HANDLERS, FANS, ETC.).

AutoCAD SHX Text

SYMBOL

AutoCAD SHX Text R

AutoCAD SHX Text

90 MINIMUM

AutoCAD SHX Text

SECONDARY BONDING CONDUCTOR (CONNECT TO NEAREST CONDUCTOR)

AutoCAD SHX Text

BONDING STRAP WITH BONDING LUG

AutoCAD SHX Text

COPPER CONDUCTOR (CONNECT TO NEAREST DOWN CONDUCTOR, STEEL OR GROUND ROD)

AutoCAD SHX Text

CAST BRONZE BONDING PLATE (CONNECT TO (FIRE & DOMESTIC WATERLINES)

AutoCAD SHX Text

BS

AutoCAD SHX Text

AutoCAD SHX Text

WL

AutoCAD SHX Text

AutoCAD SHX Text

OP

AutoCAD SHX Text

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

AIR TERMINAL BASE DETAIL

AutoCAD SHX Text %%uOFFSET PARAPET

AutoCAD SHX Text COPPER AIR TERMINAL 3/8" x 12"

AutoCAD SHX Text

COPPER LIGHTNING CONDUCTOR

AutoCAD SHX Text

OFFSET PARAPET BASE

AutoCAD SHX Text

NOTE: SEAL METAL COPING PENETRATIONS W/ SILICONE SEALANT.

AutoCAD SHX Text

METAL SCREWS (2) #HB-80SS

AutoCAD SHX Text

METAL CAP

AutoCAD SHX Text

CABLE FASTENER W/ METAL SCREWS (EVERY 3FT.)

AutoCAD SHX Text NOTE: LIGHTNING PROTECTION COMPONENT LIGHTNING PROTECTION COMPONENT MATERIALS SHALL BE GALVANICALLY COMPATIBLE WITH METAL COPING. COPPER COMPONENTS SHALL NOT BE INSTALLED ON ALUMINUM SURFACES. ELEC. ENGINEER AND INSTALLING CONTRACTOR MUST VERIFY.

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

POINT PROTECTOR

AutoCAD SHX Text

%%UAIR TERMINAL

AutoCAD SHX Text

PP

AutoCAD SHX Text

AutoCAD SHX Text AIR TERMINAL 3/8" x 12" SOLID COPPER

AutoCAD SHX Text

STAINLESS STEEL SET SCREW

AutoCAD SHX Text

POINT PROTECTOR

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

ADHESIVE AIR TERMINAL BASE

AutoCAD SHX Text

AA

AutoCAD SHX Text

AutoCAD SHX Text

SYMBOL

AutoCAD SHX Text

BP

AutoCAD SHX Text

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

BONDING PLATE

AutoCAD SHX Text

MAIN CONDUCTOR

AutoCAD SHX Text

CORROSION RESISTANT COPPER BONDING PLATE

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

BONDING LUG

AutoCAD SHX Text

BL

AutoCAD SHX Text

AutoCAD SHX Text

STAINLESS STEEL SCREW

AutoCAD SHX Text

BONDING LUG

AutoCAD SHX Text

SECONDARY BONDING CONDUCTOR

AutoCAD SHX Text

DL

AutoCAD SHX Text

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

LOWER ROOF DETAIL

AutoCAD SHX Text %%uDOWNLEAD TO

AutoCAD SHX Text

PROPER ROOF FLASHING- (FURNISHED AND INSTALLED BY THE ROOFING CONTRACTOR)

AutoCAD SHX Text COPPER CONDUCTOR IN 1" (25MM) PVC CONDUIT (ALL PVC CONDUIT SHALL BE FURNISHED, INSTALLED, WEATHERPROOFED AND MAINTAINED FREE FROM OBSTRUCTIONS BY THE ELECTRICAL CONTRACTOR)

AutoCAD SHX Text

STUB OUT CONDUIT

AutoCAD SHX Text

TOP OF PARAPET

AutoCAD SHX Text

LOWER ROOF

AutoCAD SHX Text NOTE: NO BEND OF A CONDUCTOR SHALL FORM NO BEND OF A CONDUCTOR SHALL FORM AN INCLUDED ANGLE OF LESS THAN 90 DEGREES OR HAVE A RADIUS OF BEND LESS THAN 8 INCHES.

AutoCAD SHX Text

UPPER ROOF

AutoCAD SHX Text

SEAL WITH SILICONE SEALANT TO PREVENT INGRESS OF WATER

AutoCAD SHX Text

MAIN ROOF CONDUCTOR COPPER

AutoCAD SHX Text

DRIP LOOP

AutoCAD SHX Text

8" MAX.

AutoCAD SHX Text

ROOF

AutoCAD SHX Text

COPPER CONDUCTOR

AutoCAD SHX Text

PIPE CLAMP

AutoCAD SHX Text NOTE: -LP CONDUCTOR SHALL REMAIN IN A HORIZONTAL OR DOWN- WARD PATH AVOIDING "U" & "V" POCKETS (DOWN & UP). -NO BEND OF A CONDUCTOR SHALL FORM AN INCLUDED ANGLE OF LESS THAN 90 DEGREES OR HAVE A RADIUS OF BEND LESS THAN 8 INCHES.

AutoCAD SHX Text R=RADIUS OF BEND, 8" (203mm) MINIMUM

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

SADDLE AIR TERMINAL BASE DETAIL

AutoCAD SHX Text

SA

AutoCAD SHX Text

AutoCAD SHX Text

SYMBOL

AutoCAD SHX Text 1/2" x 18" SOLID COPPER AIR TERMINAL

AutoCAD SHX Text

SADDLE AIR TERMINAL BASE

AutoCAD SHX Text

CAST PRESSURE CABLE CONN.

AutoCAD SHX Text

COPPER CONDUCTOR

AutoCAD SHX Text

FC

AutoCAD SHX Text

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

FLASHING CONNECTOR

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

CABLE CONNECTOR

AutoCAD SHX Text

FC

AutoCAD SHX Text

AutoCAD SHX Text

ROOF FLASHING

AutoCAD SHX Text NOTE: PROVIDE BONDING PROVIDE BONDING CONNECTION TO METAL FLASHING AT EACH DOWNLEAD LOCATION.

AutoCAD SHX Text

SECONDARY BONDING CONDUCTOR (CONNECT TO NEAREST DOWN CONDUCTOR)

AutoCAD SHX Text

COPPER CONDUCTOR

AutoCAD SHX Text

CABLE CONNECTOR

AutoCAD SHX Text

FLASHING CONNECTOR

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

CABLE CONNECTOR

AutoCAD SHX Text

CROSSOVER

AutoCAD SHX Text

CC

AutoCAD SHX Text

AutoCAD SHX Text

CROSSOVER CABLE CONNECTOR

AutoCAD SHX Text

COPPER CONDUCTOR

AutoCAD SHX Text

FC

AutoCAD SHX Text

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

TYPICAL PIPE CLAMP

AutoCAD SHX Text

PP

AutoCAD SHX Text

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

BEND DETAILS

AutoCAD SHX Text

%%UTYPICAL RADIUS

AutoCAD SHX Text

SYMBOL

AutoCAD SHX Text

SP

AutoCAD SHX Text

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

PVC SLEEVE THROUGH PARAPET

AutoCAD SHX Text

3/4" PVC SLEEVE THROUGH PARAPET WALL

AutoCAD SHX Text (PARAPET WALL SHALL BE DRILLED AND PROPERLY WATERPROOFED & SEALED BY THE ROOFING CONTR.)

AutoCAD SHX Text

(3/4" PVC SLEEVES SHALL BE FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR)

AutoCAD SHX Text

COPPER DOWN CONDUCTOR

AutoCAD SHX Text COPPER LIGHTNING CONDUCTOR (SHALL REMAIN IN HORIZONTAL OR DOWNWARD PATH TO GROUND GRID. CONDUCTOR MAY RISE 8" MAXIMUM.)

AutoCAD SHX Text

24" MIN.

AutoCAD SHX Text

12" MIN.

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

DOWNLEAD TO GROUND DETAIL

AutoCAD SHX Text

SYMBOL

AutoCAD SHX Text

AutoCAD SHX Text

COPPER DOWN CONDUCTOR (WITH DRIP LOOP)

AutoCAD SHX Text

SEAL PVC CONDUIT WITH SILICONE SELANT TO PREVENT INGRESS OF WATER

AutoCAD SHX Text

PROPER ROOF FLASHING (FURNISHED AND INSTALLED BY THE ROOFING CONTRACTOR)

AutoCAD SHX Text DOWN CONDUCTOR IN 1" PVC CONDUIT (ALL PVC CONDUIT SHALL BE FURNISHED, INSTALLED, WEATHERPROOFED AND MAINTAINED FREE FROM OBSTRUCTIONS BY THE ELECTRICAL CONTRACTOR)

AutoCAD SHX Text

FINISHED GRADE

AutoCAD SHX Text 5/8" x 10'-0" COPPERWELD GROUND ROD

AutoCAD SHX Text

GROUND ROD CONNECTOR

AutoCAD SHX Text

RECOMMENDED

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

DOWNLEAD TO GROUND DETAIL

AutoCAD SHX Text

AutoCAD SHX Text

ALTERNATE

AutoCAD SHX Text UTILIZE APPROVED HARDWARE, TIN PLATED ONE-HOLE CONDUCTOR, LOOP FASTENER WITH SS SCREW SIZED FOR LP CONDUCTOR

AutoCAD SHX Text

FINISHED GRADE

UNDERGROUND LP CONDUCTOR AND GROUND ROD COPPER & COPPERCLAD (TYPICAL).

ESS507

GROUNDING DETAILS

W.H.H. E.J.D.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

CONSTRUCTION

DOCUMENTS

MAY 30, 2023

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

ELECTRICAL DISTRIBUTION

SYSTEM UPGRADE - PHASE 2

VA CWM

631-18-003

Project Director

MAY 30, 2023Revisions: Date:

© Copyright 2020 DuBois & King Inc.

85 MAIN STREET

SPRINGFIELD, VT 05156

TEL: (802) 591-4326

FAX: (866) 783-7101

www.dubois-king.com

I:\ 5\

V

AM

C

E le c D is t P ha se

3\ D ra w in gs

\E le ct ric al \6

-1

8-

ES

S5

G R

O U

N D

IN

G

D

ET

AI

LS

.d w g

1/ 2/

:1

6:

P M

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

TYPICAL GROUNDING DETAILS @ GROUND ROD

AutoCAD SHX Text

AutoCAD SHX Text G2

AutoCAD SHX Text

%%USPLICE CONNECTOR

AutoCAD SHX Text

%%UTAP CONNECTOR

AutoCAD SHX Text

%%UCROSS CONNECTOR

AutoCAD SHX Text

# 2/0 AWG RUN & TAPS (STRANDED)

AutoCAD SHX Text

GROUNDING CABLE MINIMUM # 2/0 AWG

AutoCAD SHX Text NOTES: : 1. GROUND CLAMPS SHALL BE SIZED ACCORDING TO MANUFACTURER'S SPECIFICATIONS FOR SIZE GROUND CLAMPS SHALL BE SIZED ACCORDING TO MANUFACTURER'S SPECIFICATIONS FOR SIZE CABLE USED, AS SHOWN ON PLANS, UNLESS OTHERWISE NOTED. 2. ALL GROUNDING OF STRUCTURES AND EQUIPMENT SHALL BE IN ACCORDANCE WITH SPECIFICATIONS ALL GROUNDING OF STRUCTURES AND EQUIPMENT SHALL BE IN ACCORDANCE WITH SPECIFICATIONS AND PER MANUFACTURER'S GROUNDING INSTRUCTIONS.

AutoCAD SHX Text DETAIL 'G1' NOTES: : 1. GROUND CONNECTION SHALL BE SIZED AND INSTALLED ACCORDING TO THE GROUND CONNECTION SHALL BE SIZED AND INSTALLED ACCORDING TO THE MANUFACTURER'S SPECIFICATIONS FOR SIZE CABLE USED, AS SHOWN ON PLANS, UNLESS OTHERWISE NOTED. CADWELD GROUNDING SYSTEM OR APPROVED EQUAL EXOTHERMIC CONNECTOR SHALL BE USED FOR ALL BELOW GRADE GROUNDING CONNECTIONS.

AutoCAD SHX Text DETAIL 'G2' NOTES: : 1. GROUND CONNECTIONS SHALL BE SIZED AND INSTALLED ACCORDING TO GROUND CONNECTIONS SHALL BE SIZED AND INSTALLED ACCORDING TO THE MANUFACTURER'S SPECIFICATIONS FOR SIZE CABLE AND ROD USED, AS SHOWN ON PLANS, UNLESS OTHERWISE NOTED.

AutoCAD SHX Text

SILICON BRONZE BOLT (CLASS 2 FIT)

AutoCAD SHX Text

SILICON BRONZE LOCKWASHER

AutoCAD SHX Text

SILICON BRONZE NUT (CLASS 2 FIT)

AutoCAD SHX Text

ALUMINUM BOLT (2024-T4 WITH ANODIC

AutoCAD SHX Text

FINISH AND CLASS 2A FIT)

AutoCAD SHX Text

ALUMINUM LOCKWASHER (7075-T6

AutoCAD SHX Text

ETCH FINISH REG. DESIGN)

AutoCAD SHX Text

ALUMINUM NUT (PLAIN)(6061-T6

AutoCAD SHX Text

WAX FINISH CLASS 2R FIT)

AutoCAD SHX Text

STAINLESS STEEL BOLT

AutoCAD SHX Text

(MATERIAL SERIES 18-8

AutoCAD SHX Text

CLASS 2A TOLERANCE)

AutoCAD SHX Text

STAINLESS STEEL FLAT WASHER

AutoCAD SHX Text

(MATERIAL SERIES 18-8,

AutoCAD SHX Text

MEDIUM DESIGN)

AutoCAD SHX Text

STAINLESS STEEL LOCKWASHER

AutoCAD SHX Text

(MATERIAL SERIES 18-8,

AutoCAD SHX Text

REGULAR DESIGN)

AutoCAD SHX Text

ALUMINUM

AutoCAD SHX Text

COPPER

AutoCAD SHX Text

STAINLESS STEEL NUT

AutoCAD SHX Text

(MATERIAL SERIES 18-8,

AutoCAD SHX Text

CLASS 2B FIT)

AutoCAD SHX Text

(ALUMINUM TO COPPER)

AutoCAD SHX Text

ALUMINUM BOLT (2024-T4 WITH

AutoCAD SHX Text

ANODIC FINISH & CLASS 2A FIT)

AutoCAD SHX Text

ALUMINUM FLAT WASHER (7075-T6

AutoCAD SHX Text

OR 2024-T4 MEDIUM DESIGN)

AutoCAD SHX Text

ALUMINUM LOCKWASHER (7075-T6

AutoCAD SHX Text

ETCH FINISH REGULAR DESIGN)

AutoCAD SHX Text

ALUMINUM NUT (PLAIN)(6061-T6

AutoCAD SHX Text

WAX FINISH & CLASS 2B FIT)

AutoCAD SHX Text

(ALUMINUM TO ALUMINUM)

AutoCAD SHX Text A

AutoCAD SHX Text B

AutoCAD SHX Text

%%UTABLE 2

AutoCAD SHX Text

BRONZE CONNECTIONS CLAMPING HARDWARE

AutoCAD SHX Text

ALUMINUM CONNECTIONS CLAMPING HARDWARE

AutoCAD SHX Text

ALUMINUM CONNECTION TONGUE MOUNTED HARDWARE

AutoCAD SHX Text

ALUMINUM CONNECTION TONGUE MOUNTED HARDWARE

AutoCAD SHX Text GENERAL NOTES APPLYING TO ELECTRICAL CONNECTIONS: 1. FOR ALUMINUM TO ALUMINUM CONNECTIONS AND ALUMINUM TO FOR ALUMINUM TO ALUMINUM CONNECTIONS AND ALUMINUM TO COPPER CONNECTIONS WITHOUT A COPPER LINED CONTACT (BOLTED). a. VIGOROUSLY CLEAN ALL CONTACT SURFACES OF THE VIGOROUSLY CLEAN ALL CONTACT SURFACES OF THE CONNECTOR AND CONDUCTOR WITH A STIFF STAINLESS STEEL WIRE BRUSH TO REMOVE OXIDES. A TYPICALLY BRIGHT ALUMINUM SURFACE SHOULD BE OBTAINED. DO NOT WIRE BRUSH PLATED CONTACT SURFACES. b. IMMEDIATELY COAT THESE CONTACT AREAS WITH A LIBERAL IMMEDIATELY COAT THESE CONTACT AREAS WITH A LIBERAL AMOUNT OF CONTACT SEALANT. c. INSTALL FITTING WITH BOLTS FINGER TIGHT. IF A INSTALL FITTING WITH BOLTS FINGER TIGHT. IF A GENEROUS BEAD OF COMPOUND DOES NOT APPEAR, REMOVE THE CONDUCTOR AND ADD MORE SEALANT. d. ALTERNATELY (CRISSCROSS) AND EVENLY TIGHTEN BOLTS ALTERNATELY (CRISSCROSS) AND EVENLY TIGHTEN BOLTS WITH A TORQUE WRENCH TO THE VALUES SHOWN IN TABLE 1. e. EXCESS SEALANT SQUEEZED OUT OF JOINT CAN BE LEFT AS EXCESS SEALANT SQUEEZED OUT OF JOINT CAN BE LEFT AS IS OR CAN BE LIGHTLY SMOOTHED ALONG CONTACT LINE. f. ALL EXCESS SEALANT MUST BE REMOVED ENTIRELY FROM ALL EXCESS SEALANT MUST BE REMOVED ENTIRELY FROM CABLE INSULATION. 2. FOR ALUMINUM CONNECTORS WITH A COPPER LINER TO COPPER FOR ALUMINUM CONNECTORS WITH A COPPER LINER TO COPPER CONNECTION (BOLTED). a. THE USE OF A CONTACT SEALANT IN THIS TYPE OF JOINT IS THE USE OF A CONTACT SEALANT IN THIS TYPE OF JOINT IS NOT ABSOLUTELY NECESSARY. CORROSION PROTECTION OF THE JOINT, IN STEPS GIVEN IN A-1 TO A-5 SHALL BE FOLLOWED. 3. FOR ALUMINUM COMPRESSION CONNECTORS. FOR ALUMINUM COMPRESSION CONNECTORS. a. VIGOROUSLY CLEAN THE CONDUCTOR CONTACT AREA WITH A VIGOROUSLY CLEAN THE CONDUCTOR CONTACT AREA WITH A STAINLESS STEEL BRUSH. DO NOT ATTEMPT TO CLEAN CONNECTOR BARREL. IT IS NOT NECESSARY TO APPLY SEALANT TO THE CONDUCTOR. ALL CONNECTORS WILL HAVE SEALANT APPLIED AT THE FACTORY, EXCEPT FULL TENSION CONNECTORS WITH STEEL INNER SLEEVES. b. FULLY INSERT THE CONDUCTOR INTO THE BARREL AND FULLY INSERT THE CONDUCTOR INTO THE BARREL AND CRIMP. CRIMPING SHOULD BEGIN NEAREST THE CENTER OF SLEEVE TYPE CONNECTORS. FOR CLOSED BARREL TYPE CONNECTORS CRIMPING SHOULD BEGIN AT THE CLOSED END AND WORK TOWARD THE OPEN END. EXCESS SEALANT SQUEEZED OUT OF THE JOINT MAY BE SMOOTHED OUT AROUND THE MOUTH OF THE BARREL, ALL EXCESS SEALANT MUST BE REMOVED FROM ANY CABLE INSULATION. c. PROPER DIES AND COMPRESSION TOOLS TO BE USED AS PROPER DIES AND COMPRESSION TOOLS TO BE USED AS DETERMINED BY MANUFACTURER. 4. FOR BRONZE TO COPPER AND COPPER TO COPPER CONNECTIONS FOR BRONZE TO COPPER AND COPPER TO COPPER CONNECTIONS (BOLTED) a. CONTACT SEALANTS DESIGNED FOR COPPER TO COPPER AND CONTACT SEALANTS DESIGNED FOR COPPER TO COPPER AND BRONZE ARE REQUIRED. b. VIGOROUSLY CLEAN CONDUCTOR AND CONNECTOR CONTACT VIGOROUSLY CLEAN CONDUCTOR AND CONNECTOR CONTACT SURFACES WITH A STAINLESS STEEL WIRE BRUSH. c. COAT SURFACES WITH CONTACT SEALANT. COAT SURFACES WITH CONTACT SEALANT. d. ALTERNATELY AND EVENLY TIGHTEN BOLTS WITH A TORQUE ALTERNATELY AND EVENLY TIGHTEN BOLTS WITH A TORQUE WRENCH TO VALUES AS INDICATED IN TABLE 1. 5. FOR COPPER TO ALUMINUM CONNECTIONS USING CONNECTIONS FOR COPPER TO ALUMINUM CONNECTIONS USING CONNECTIONS USING COPPER CONNECTORS (BOLTED). a. TIN PLATE THE COPPER BASE CONNECTIONS USE SEALANT TIN PLATE THE COPPER BASE CONNECTIONS USE SEALANT BETWEEN THE ALUMINUM AND COPPER PADS. b. ALUMINUM CONDUCTOR IN A STANDARD COPPER BASE ALUMINUM CONDUCTOR IN A STANDARD COPPER BASE CONNECTION IS NOT RECOMMENDED. 6. FOR COPPER TO ALUMINUM CONNECTIONS USING ALUMINUM FOR COPPER TO ALUMINUM CONNECTIONS USING ALUMINUM CONNECTORS (BOLTED) a. PROPER CARE MUST BE OBSERVED WHEN MAKING THIS PROPER CARE MUST BE OBSERVED WHEN MAKING THIS CONNECTION. UTILIZE ALL STEPS AS OUTLINE IN PROCEDURE "A". ALL CONTACT SURFACES MUST BE COMPLETELY COATED WITH SEALANT. WHERE ALUMINUM CONNECTORS ARE TIN PLATED, PROCEDURE "A" SHALL ALSO BE FOLLOWED. 7. FOR GALVANIZED STEEL TO COPPER AND GALVANIZED STEEL TO FOR GALVANIZED STEEL TO COPPER AND GALVANIZED STEEL TO ALUMINUM CONNECTIONS UTILIZING ALUMINUM OR COPPER (BRONZE) CONNECTORS (BOLTED). a. UTILIZE PROCEDURES AS OUTLINED IN "A" FOR ALUMINUM UTILIZE PROCEDURES AS OUTLINED IN "A" FOR ALUMINUM CONNECTORS. b. UTILIZE PROCEDURES AS OUTLINED IN "D" FOR COPPER UTILIZE PROCEDURES AS OUTLINED IN "D" FOR COPPER CONNECTORS. 8. RECOMMENDED TORQUE VALUES FOR CONNECTORS. NOTE: CARE RECOMMENDED TORQUE VALUES FOR CONNECTORS. NOTE: CARE SHALL BE TAKEN TO AVOID SEALANT FROM BEING APPLIED TO ANY HARDWARE SINCE TORQUE VALUES WILL BE AFFECTED.

AutoCAD SHX Text

'A' BAR

AutoCAD SHX Text

'B' BAR

AutoCAD SHX Text

RECOMMENDED

AutoCAD SHX Text

COPPER

AutoCAD SHX Text

COPPER

AutoCAD SHX Text

(1) SIBR

AutoCAD SHX Text

(2) SS

AutoCAD SHX Text

(3) GS

AutoCAD SHX Text

HARDWARE

AutoCAD SHX Text

TYPE

AutoCAD SHX Text SIBR DENOTES - SILICON BRONZE DENOTES - SILICON BRONZE SS DENOTES - STAINLESS STEEL DENOTES - STAINLESS STEEL GS DENOTES - GALVANIZED STEEL DENOTES - GALVANIZED STEEL AL DENOTES - ALUMINUM DENOTES - ALUMINUM (1),(2),(3) DENOTES - PREFERRED TYPE IN DENOTES - PREFERRED TYPE IN NUMERICAL ORDER

AutoCAD SHX Text

ALUMINUM

AutoCAD SHX Text

COPPER

AutoCAD SHX Text

(1) SS

AutoCAD SHX Text

(2) GS

AutoCAD SHX Text

ALUMINUM

AutoCAD SHX Text

ALUMINUM

AutoCAD SHX Text

(1) AL

AutoCAD SHX Text

(2) SS

AutoCAD SHX Text

(3) GS

AutoCAD SHX Text

GALV. STEEL

AutoCAD SHX Text

(1) SIBR

AutoCAD SHX Text

(2) SS

AutoCAD SHX Text

(3) GS

AutoCAD SHX Text

COPPER

AutoCAD SHX Text

GALV. STEEL

AutoCAD SHX Text

(1) AL

AutoCAD SHX Text

(2) SS

AutoCAD SHX Text

(3) GS

AutoCAD SHX Text

ALUMINUM

AutoCAD SHX Text

BRONZE

AutoCAD SHX Text

(2) SIBR

AutoCAD SHX Text

(2) SS

AutoCAD SHX Text

COPPER

AutoCAD SHX Text 5/16 INCH (8.0mm) 180 POUND INCHES (2.07 KILOGRAM FORCE METER) 180 POUND INCHES (2.07 KILOGRAM FORCE METER) 3/8 INCH (3.5mm) 240 POUND INCHES (2.77 KILOGRAM FORCE METER) 240 POUND INCHES (2.77 KILOGRAM FORCE METER) 1/2 INCH (13mm) 480 POUND INCHES (5.53 KILOGRAM FORCE METER) 480 POUND INCHES (5.53 KILOGRAM FORCE METER) 5/8 INCH (15mm) 660 POUND INCHES (7.60 KILOGRAM FORCE METER) 660 POUND INCHES (7.60 KILOGRAM FORCE METER) 3/4 INCH (19mm) 840 POUND INCHES (9.68 KILOGRAM FORCE METER)840 POUND INCHES (9.68 KILOGRAM FORCE METER)

AutoCAD SHX Text

BOLT DIAMETER

AutoCAD SHX Text

NON-LUBRICATED STEEL AND SILICON BRONZE

AutoCAD SHX Text

TABLE 1

AutoCAD SHX Text 5/16 INCH (8.0mm) 120 POUND INCHES (1.38 KILOGRAM FORCE METER) 120 POUND INCHES (1.38 KILOGRAM FORCE METER) 3/8 INCH (3.5mm) 168 POUND INCHES (1.94 KILOGRAM FORCE METER) 168 POUND INCHES (1.94 KILOGRAM FORCE METER) 1/2 INCH (13mm) 300 POUND INCHES (4.46 KILOGRAM FORCE METER) 300 POUND INCHES (4.46 KILOGRAM FORCE METER) 5/8 INCH (15mm) 480 POUND INCHES (5.53 KILOGRAM FORCE METER) 480 POUND INCHES (5.53 KILOGRAM FORCE METER) 3/4 INCH (19mm) 720 POUND INCHES (8.30 KILOGRAM FORCE METER)720 POUND INCHES (8.30 KILOGRAM FORCE METER)

AutoCAD SHX Text

BOLT DIAMETER

AutoCAD SHX Text

NON-LUBRICATED STEEL AND SILICON BRONZE

AutoCAD SHX Text

1. OXIDE INHIBITING AND SEALING COMPOUNDS SHALL BE APPLIED AS PER OXIDE INHIBITING AND SEALING COMPOUNDS SHALL BE APPLIED AS PER MANUFACTURER'S INSTRUCTIONS AND PER SPECIFICATIONS.

AutoCAD SHX Text

CADWELD TYPE TYPE 'TA'

AutoCAD SHX Text

CADWELD TYPE TYPE 'XA'

AutoCAD SHX Text

# 2/0 AWG RUN (STRANDED)

AutoCAD SHX Text

# 2/0 AWG RUN (STRANDED)

AutoCAD SHX Text

CADWELD TYPE TYPE 'PT'

AutoCAD SHX Text

CADWELD TYPE TYPE 'SS'

AutoCAD SHX Text

# 2/0 AWG RUN (STRANDED)

AutoCAD SHX Text

# 2/0 AWG TAP (STRANDED)

AutoCAD SHX Text

# 2/0 AWG TAP (STRANDED)

AutoCAD SHX Text

CADWELD TYPE TYPE 'GT'

AutoCAD SHX Text

# 2/0 AWG RUN (STRANDED)

AutoCAD SHX Text GROUND ROD 3/4"x10'-0" LG. COPPERWELD

AutoCAD SHX Text

%%UTAP CONNECTOR

AutoCAD SHX Text

CADWELD TYPE TYPE 'TA'

AutoCAD SHX Text

%%USPLICE CONNECTOR

AutoCAD SHX Text

%%UROD CONNECTOR

AutoCAD SHX Text CADWELD TYPE 'GL' LUG TYPICAL AT ALL GENERATOR HOUSING CORNERS. BOLT TO GROUND GRID CONNECTION POINTS

AutoCAD SHX Text

CONDUCTOR TO GROUND GRID

AutoCAD SHX Text

# 2/0 AWG TAP (STRANDED)

AutoCAD SHX Text

# 2/0 AWG TAP (STRANDED)

AutoCAD SHX Text

# 2/0 AWG RUN (STRANDED)

AutoCAD SHX Text

# 2/0 AWG RUN (STRANDED)

AutoCAD SHX Text

# 2/0 AWG RUN (STRANDED)

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

TYPICAL GROUNDING DETAILS @ GROUND GRID

AutoCAD SHX Text

AutoCAD SHX Text G1

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

RECOMMENDED CONNECTIONS

AutoCAD SHX Text

AutoCAD SHX Text A

AutoCAD SHX Text

BASE MOUNTED FUEL TANK

AutoCAD SHX Text

GENERATOR HOUSING

AutoCAD SHX Text

CONCRETE PAD

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

GENERATOR GROUNDING DETAIL

AutoCAD SHX Text

AutoCAD SHX Text G3

AutoCAD SHX Text

FINISHED GRADE

NOTE: APPROVED OPTION FOR COMPRESSION FITINGS MAYBE USED FOR GROUNDING CONNECTIONS IF APPROVED BY COR

1-AS - 301

1-AS -

NEW ROOF ASSEMBLY

- SINGLE-PLY MEMBRANE

ROOFING

- 1/2" COVER BOARD

- TAPERED RIGID

INSULATION

(6" MINIMUM)

- VAPOR RETARDER

(CONCRETE DECK)

(SEE 2ND FLOOR PLAN FOR

ADDITIONAL INFORMATION)

(E) SLOPED SLATE

SHINGLE ROOF

(E) SLOPED

SHINGLE

ROOF

(E) SLOPED

SHINGLE

ROOF

(E) LOW FLAT BUR

ROOF (EL 439.8)

(E) HIGH FLAT

BUR ROOF

(E) SLOPED SLATE

SHINGLE ROOF

(E) LOW FLAT BUR

ROOF (EL 439.8)

1-AS - 212

1-AS - 212

NEW ROOF ASSEMBLY

- SINGLE-PLY MEMBRANE

ROOFING

- 1/2" COVER BOARD

- TAPERED RIGID

INSULATION

(6" MINIMUM)

- VAPOR RETARDER

(CONCRETE DECK)

(SEE 2ND FLOOR PLAN FOR

ADDITIONAL INFORMATION)

STANDING

SEAM METAL

ROOFING

STANDING SEAM

METAL ROOFING

1-AS - 513

1-AS - 513

1-AS - 514

1-AS - 512

1-AS - 311

1-AS - 510

CLAMP ON SNOW GUARD,

CAST ALUMINUM, MILL

FINISH - (BASIS OF DESIGN:

BERGER RT-200) - TYPICAL

1-AS - 513

1-AS - 513

1-AS - 513

1-AS - 513

SIM

7C

GUTTER AND DOWNSPOUT,

TYPICAL BOTH SIDES

GUTTER AND DOWNSPOUT,

TYPICAL BOTH SIDES

CLAMP ON SNOW GUARD,

CAST ALUMINUM, MILL

FINISH - (BASIS OF DESIGN:

BERGER RT-200) - TYPICAL

1-AS - 312

1-AS - 514

SL DN

1/4"/FT

1" EXPANSION JOINT

BACKER ROD &

SEALANT (TYP.)

OVRFL RD

RD, 2"

INSULATION

MIN.

OVRFL RD

RD

OVRFL RD

RD

OVRFL RD

RD

1-AS - 312

A B

C D

E

D A T E

T

IM

E P

R

IN

T E D th re e i n c h e s o n e f o o t

A o n e a n d o n e h a lf i n c h e s o n e f o o t

B o n e i n c h o n e f o o t

C th re e q u a rt e rs i n c h o n e f o o t

D o n e h a lf i n c h o n e f o o t

E th re e e ig h th s i n c h o n e f o o t

F o n e q u a rt e r in c h o n e f o o t o n e e ig h th i n c h o n e f o o t

1 2 3 4 5 6 7 8 9

1 2 3 4 5 6 7 8 9

A

B

C

D

E

F

VA FORM 08-6231

Number Date Revision

D e p a r t m e n t o f

V e t e r a n s

A ff a ir s

O ff ic e of

F ac il it ie s

Date

VA Project No.

Drawing No.ScaleBuilding #

Location

Project Title

Approved By:

Approved By:

Approved By:

Drawing Title

N

KEY PLAN

CONSULTANTS

MEP / FP

DUBOIS & KING, INC.

28 North Main Street, Randolph, VT 05060

T: 802.728.3376 www.info@dubois-king.com/

FULLY SPRINKLERED

631-451

ARCHITECT OF RECORD

As indicated

C

U se rs \a k a n u sk y \D o cu m e n ts

\V A P ri m a ry

C a re

A rc h a k a n u sk y V B N

S Y .r v t

/2

/2

:4

:1

A

M

Approver

PROPOSED ROOF PLAN

1-AS - 113

UPGRADE PRIMARY CARE 4/25/2022

Approver

Approver

7C 4-25-2022 BULLETIN 7C

7C

7C

7C

7C https://app.procore.com/1497865/project/drawing_areas/1575221/drawing_log/199028057 https://app.procore.com/1497865/project/drawing_areas/1575221/drawing_log/199028057 https://app.procore.com/1497865/project/drawing_areas/1575221/drawing_log/199028051 https://app.procore.com/1497865/project/drawing_areas/1575221/drawing_log/199028098 https://app.procore.com/1497865/project/drawing_areas/1575221/drawing_log/199028060 https://app.procore.com/1497865/project/drawing_areas/1575221/drawing_log/199028053 https://app.procore.com/1497865/project/drawing_areas/1575221/drawing_log/199028053 https://app.procore.com/1497865/project/drawing_areas/1575221/drawing_log/199028047 https://app.procore.com/1497865/project/drawing_areas/1575221/drawing_log/199028047 https://app.procore.com/1497865/project/drawing_areas/1575221/drawing_log/199028047 https://app.procore.com/1497865/project/drawing_areas/1575221/drawing_log/199028047 https://app.procore.com/1497865/project/drawing_areas/1575221/drawing_log/199028047 https://app.procore.com/1497865/project/drawing_areas/1575221/drawing_log/199028083

01-EP112
ESS 503
ESS 507
1-AS - 113_ PROPOSED ROOF PLAN

File details come from the government source that posted it. Updated .