631-25-001 Building 1 Lightning Protection Technical Questions and Answers.pdf
PDF 1 MB Posted
- Attached to
- 5920--631-25-001 Building 1 Lightning Protection
- Solicitation number
- 36C24125R0031
About this file
This is a Questions and Answers document for a lightning protection system project at Building 1, accompanied by technical specifications for surge protective devices and electrical plans. The Q&A addresses specific technical requirements including the absence of an existing counterpoise ring, location of surge protection devices, bonding requirements for water services, and specifications for lightning arrestors on telephone, radio and TV antenna services.
Key technical details include the need for approximately 700 feet of 3/0 copper and conduit in the basement for bonding three water services, installation of surge protection devices on two Siemens 208/120 2500A electrical service panels, and telephone service connections in room B108A. The accompanying specification section 26 43 13 details requirements for Type 2 Surge Protective Devices, while electrical plans 01EA-EP101 and 01WA-EP101 show equipment locations and demolition details. The project requires bid bonds per FAR 52.228-1(b), and allows high-compression crimps as an alternative to exothermic welds for underground grounding connections.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C24125R0031 0002.docx | DOCX document | |
| Site Visit Sign In Sheet 631-25-001 Building 1 Lightning Protection.pdf | ||
| SOW building 1 lightning protection R1.pdf | ||
| 36C24125R0031 0001.docx | DOCX document | |
| P07 MA20240003 12.13.2024.pdf | ||
| 631-25-001 Drawings.pdf | ||
| 36C24125R0031.docx | DOCX document | |
| 631-25-001 Specifications.pdf | ||
| SOW Building 1 Lightning Protection.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
631-25-001 Building 1 Lightning Protection
Questions and Answers
1. Does Building 1 have an existing counterpoise ring? If not, will one need to be installed for this project or will ground rods at each downlead suffice?
Answer: There is no existing ground ring for the building and no new one is proposed, downleads should suffice. Final drawings shall be provided after field verification by the lightning system designer.
2. Note 4 on drawing 01-EP112 mentions a one line diagram showing where surge protection devices are to be installed. Can this drawing and specs for the surge protection devices needed be provided?
Answer: Drawing 01EA-EP101 and 01WA-EP101 added for reference. Only SPD is required from these two drawings. Spec section 26 43 13 added.
3. Note 13 on drawing ESS503 calls for bonding to domestic and fire waterlines, can a drawing showing the location and quantity of lines needing bonded be provided?Answer:
PDF added for reference. Water services will need bonded. This needs to be field verified and add. Approximately 700’ of 3/0 copper and conduit will be needed in the basement.
This includes bonding the 3 services together.
4. Note 14 on drawing Ess503 calls for lightning arrestors on the telephone service, radio and TV antennas, can a drawing be provided showing the location of these items?
Answer: Telephone service is in room B108A and the radio antenna is located on the flat roof in the center of the building.
5. Are bid bonds required with quotes.
Answer: Per FAR 52.228-1(b), the bidder shall furnish a bid guarantee in the form of a firm commitment, e.g., bid bond supported by good and sufficient surety or sureties acceptable to the Government, postal money order, certified check, cashier’s check, irrevocable letter of credit, or, under Treasury Department regulations, certain bonds or notes of the United States.
6. Will surge protection devices be required for the communication and low voltage lines entering the building? If yes, please confirm the type of system, maximum operating voltage and amperage, number and size of wires, method of connection, data speed, and length of run.
Answer: Yes, Phone service is in room B108A
7. Please provide the quantity of main electrical service panels requiring surge protection.
Answer: 2
8. Please provide the manufacturer of the electrical service panel, and the voltage configuration.
Answer: Siemens 208/120 2500A
9. Will high-compression crimps, listed for the purpose of underground grounding connections be permitted as an alternative to exothermic welds?
Answer: Yes
10. Will services need to be bonded?
Answer: Yes, building 1 has 3 services and they will need to be bonded together with a 3/0 copper. The 700’ in question 3 includes the water and electric services.
Electrical Distribution System Upgrade Phase 2 12-12-22
631-18-003
01-01-17
26 43 13 - 1
SECTION 26 43 13
SURGE PROTECTIVE DEVICES
PART 1 - GENERAL
1.1 DESCRIPTION
A. This section specifies the furnishing, installation, and connection of
Type 2 Surge Protective Devices, as defined in NFPA 70, and indicated as SPD in this section.
1.2 RELATED WORK
A. Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS:
Requirements that apply to all sections of Division 26.
1.3 QUALITY ASSURANCE
A. Quality Assurance shall be in accordance with Paragraph, QUALIFICATIONS
(PRODUCTS AND SERVICES) in Section 26 05 11, REQUIREMENTS FOR
ELECTRICAL INSTALLATIONS.
1.4 SUBMITTALS
A. Submit in accordance with Paragraph, SUBMITTALS in Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS, and the following requirements:
1. Manufacturer’s Literature and Data for each product:
a. Provide manufacturer’s catalog information, weights, mounting requirements, data and listings.
2. Shop Drawings:
a. Submit sufficient information to demonstrate compliance with drawings and specifications.
b. Include electrical ratings and device nameplate data.
3. Manuals:
a. Submit, simultaneously with the shop drawings, companion copies of complete maintenance and operating manuals including technical data sheets, wiring diagrams, and information for ordering replacement parts.
b. If changes have been made to the maintenance and operating manuals originally submitted, submit updated maintenance and operating manuals two weeks prior to the final inspection.
4. Test Reports:
c. Provide a final report for all acceptance checks for all tests, test results and verifications per paragraphs 3.2 and 3.3.
5. Certifications: Two weeks prior to final inspection, submit the following.
01-01-17
26 43 13 - 2
a. Certification by the manufacturer that the SPD conforms to the requirements of the drawings and specifications.
b. Certification by the Contractor that the SPD has been properly installed.
1.5 APPLICABLE PUBLICATIONS
A. Publications listed below (including amendments, addenda, revisions, supplement and errata) form a part of this specification to the extent referenced. Publications are referenced in the text by the basic designation only.
B. Institute of Engineering and Electronic Engineers (IEEE):
IEEE C62.41.2-02........Characterization of Surges in Low-Voltage (1000
V and Less) AC Power Circuits
IEEE C62.45-08..........Surge Testing for Equipment Connected to Low-
Voltage (1000 V and Less) AC Power Circuits
C. National Fire Protection Association (NFPA):
70-23...................National Electrical Code (NEC)
110-22..................Standard for Emergency and Standby Power
Systems
D. Underwriters Laboratories, Inc. (UL):
UL 1283-17..............Electromagnetic Interference Filters
UL 1449-21..............Surge Protective Devices
1.6 WARRANTY
A. Construction Warranty: FAR clause 52.246-21, "Warranty of
Construction."
PART 2 - PRODUCTS
2.1 SWITCHGEAR/SWITCHBOARD SPD
A. General Requirements:
1. Comply with IEEE and UL.
2. Modular design with field-replaceable modules, or non-modular design.
3. Fuses, rated at 200 kA interrupting capacity.
4. Bolted compression lugs for internal wiring.
5. Integral disconnect switch.
6. Redundant suppression circuits.
7. LED indicator lights for power and protection status.
8. Audible alarm, with silencing switch, to indicate when protection has failed.
01-01-17
26 43 13 - 3
9. Form-C contacts rated at 5 A and 250-V ac, one normally open and one normally closed, for remote monitoring of protection status.
Contacts shall reverse on failure of any surge diversion module or on opening of any current-limiting device.
10. Four-digit transient-event counter.
B. Surge Current per Phase: Minimum 240kA per phase.
2.3 ENCLOSURES
A. Enclosures: NEMA 1.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Installation shall be in accordance with the NEC, as shown on the drawings, and manufacturer’s instructions.
B. Factory-installed SPD: Switchgear, switchboard, or panelboard manufacturer shall install SPD at the factory.
C. Field-installed SPD: Contractor shall install SPD with conductors or buses between SPD and points of attachment as short and straight as possible. Do not exceed manufacturer's recommended lead length. Do not bond neutral and ground.
1. Provide a circuit breaker as a dedicated disconnecting means for
TVSS as shown on drawings.
D. Do not perform insulation resistance tests on switchgear, switchboards, panelboards, or feeders with the SPD connected. Disconnect SPD before conducting insulation resistance tests and reconnect SPD immediately after insulation resistance tests are complete.
3.2 ACCEPTANCE CHECKS AND TESTS
A. Perform in accordance with the manufacturer's recommendations. In addition, include the following:
1. Visual Inspection and Tests:
a. Compare equipment nameplate data with specifications and approved shop drawings.
b. Inspect physical, electrical, and mechanical condition.
c. Verify that disconnecting means and feeder size and maximum length to SPD corresponds to approved shop drawings.
d. Verifying tightness of accessible bolted electrical connections by calibrated torque-wrench method.
e. Vacuum-clean enclosure interior. Clean enclosure exterior.
f. Verify the correct operation of all sensing devices, alarms, and indicating devices.
01-01-17
26 43 13 - 4
3.3 FOLLOW-UP VERIFICATION
A. After completion of acceptance checks and tests, the Contractor shall show by demonstration in service that SPD are in good operating condition and properly performing the intended function.
3.4 INSTRUCTION
A. Refer to Specification 01 00 00 for requirements for training and instructions.
B. Provide the services of a factory-trained technician for one 2-hour training period for instructing personnel in the maintenance and operation of the SPD, on the date requested by the COR.
---END---
01EA-EP101
BUILDING NO. 1EA FIRST LEVEL
ELECTRICAL PLAN 01EA
W.H.H. E.J.D.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
CONSTRUCTION
DOCUMENTS
MAY 30, 2023
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
ELECTRICAL DISTRIBUTION
SYSTEM UPGRADE - PHASE 2
VA CWM
631-18-003
Project Director
MAY 30, 2023Revisions: Date:
© Copyright 2020 DuBois & King Inc.
85 MAIN STREET
SPRINGFIELD, VT 05156
TEL: (802) 591-4326
FAX: (866) 783-7101
www.dubois-king.com
I:\ 5\
V
AM
C
E le c D is t P ha se
3\ D ra w in gs
\E le ct ric al \0
1E A-
EP
BU
IL
D
IN
G
N O
. 1
EA
F
IR
ST
L
EV
EL
E
LE
C
TR
IC
AL
P
LA
N .d w g
1/
2/
4:
:3
PM
631-25-001 Only in scope work
AutoCAD SHX Text
EXISTING PANEL 1EA-A/C TO BE RELOCATED
AutoCAD SHX Text
EXISTING GENERATOR MAIN BRKR
AutoCAD SHX Text
EXISTING SWBD E1EA-MDP
AutoCAD SHX Text
EXISTING ATS#1(LS) TO BE REMOVED
AutoCAD SHX Text
EXISTING ATS#3(EB) TO BE REMOVED
AutoCAD SHX Text
EXISTING ATS#2(CB) TO BE REMOVED
AutoCAD SHX Text
EXISTING E1EA-EB TO BE REMOVED
AutoCAD SHX Text
EXISTING PANEL E1EA-CB
AutoCAD SHX Text
EXISTING PANEL E1EA-LS
AutoCAD SHX Text
EXISTING PANEL E1EA-LESH
AutoCAD SHX Text
EXISTING 300KW GENERATOR
AutoCAD SHX Text
EXISTING WIREWAY TO BE REMOVED
AutoCAD SHX Text
TRENCH WITH EMERGENCY CIRCUITS TO BE UPGRADED
AutoCAD SHX Text NOTES: 1. EXISTING INTERIOR AND EXTERIOR LIGHTS TO BE EXISTING INTERIOR AND EXTERIOR LIGHTS TO BE REMOVED AND REPLACED WITH NEW LIGHTS. FIELD VERIFY LOCATION AND QUANTITY. EXISTING WIRING AND CONTROLS TO REMAIN. EXIT SIGNS TO REMAIN.
AutoCAD SHX Text
EXISTING TELEPHONE, JACK AND UNDERGROUND CONDUITS TO BE RELOCATED
AutoCAD SHX Text
EXISTING TRANSFORMER TO BE RELOCATED TO AVOID NEW DOOR
AutoCAD SHX Text
EXISTING PULLBOX AND FEEDERS TO TRANSFORMER
AutoCAD SHX Text RELOCATE EXISTING THERMOSTATS, TELEPHONE AND CONDUITS IN THIS AREA FOR DOOR AND NEW EQUIPMENT
AutoCAD SHX Text
EXISTING SWBD 1EA-MDP
AutoCAD SHX Text
CONDUITS TO TRANSFORMER
AutoCAD SHX Text
NEW ISOLATION BYPASS AUTOMATIC TRANSFER SWITCH E1EA-CB-ATS
AutoCAD SHX Text
NEW PANEL E1EA-EB
AutoCAD SHX Text
RELOCATED PANEL 1EA-A/C
AutoCAD SHX Text
EXISTING GENERATOR MAIN BRKR
AutoCAD SHX Text
EXISTING SWBD 1EA-MDP
AutoCAD SHX Text
EXISTING SWBD E1EA-MDP
AutoCAD SHX Text
EXISTING PANEL E1EA-CB
AutoCAD SHX Text
EXISTING PANEL E1EA-LS
AutoCAD SHX Text
EXISTING PANEL E1EA-LESH
AutoCAD SHX Text
EXISTING 300KW GENERATOR
AutoCAD SHX Text
NEW ISOLATION BYPASS AUTOMATIC TRANSFER SWITCH E1EA-LS-ATS
AutoCAD SHX Text
NEW ISOLATION BYPASS AUTOMATIC TRANSFER SWITCH E1EA-EB-ATS
AutoCAD SHX Text
NEW METERING PANEL
AutoCAD SHX Text
NEW SURGE PROTECTIVE DEVICE
AutoCAD SHX Text
NEW SURGE PROTECTIVE DEVICE
AutoCAD SHX Text NEW LIGHTS TO REPLACE EXISTING INTERIOR LIGHTS IN EXISTING LOCATIONS (TYP.) UTILIZE EXISTING WIRING
AutoCAD SHX Text
E1EA-LESH-8
AutoCAD SHX Text
E1EA- LESH-16
AutoCAD SHX Text
PROVIDE NEW GENERATOR WIRING MONITORING SYSTEM
AutoCAD SHX Text
EXISTING METASYS EQUIPMENT
AutoCAD SHX Text DUCT BANKS TO BUILDING No. 1 EAST ELECTRIC VAULTS
AutoCAD SHX Text NEW LIGHTS TO REPLACE EXISTING EXTERIOR LIGHTS IN EXISTING LOCATIONS (TYP.) UTILIZE EXISTING WIRING
AutoCAD SHX Text
RELOCATED TRANSFORMER, FIELD COORDINATE WITH COR ON EXACT REQUIREMENTS
AutoCAD SHX Text
GENERATOR INTAKE HOOD
AutoCAD SHX Text
NEW CONCRETE PAD
AutoCAD SHX Text
NEW WIRE AND CONDUIT MATCH EXISTING SIZES
AutoCAD SHX Text
E1EA- LESH-5
AutoCAD SHX Text DRY SUPPRESSION SYSTEM AND CONTROLS, AREA INDICATED BY SHADING. IT DENOTES AREA TO BE PROTECTED BY DRY AGENT SUPPRESSION SYSTEM (REFER TO SPEC 21 2200)
AutoCAD SHX Text
NEW GENERATOR DOCKING STATION PER REQUIREMENTS ON NEC ARTICLE 700.3 (F)
AutoCAD SHX Text
SCALE: 1/4" = 1'-0"
AutoCAD SHX Text
BUILDING NO. 1EA - DEMOLITION PLAN
AutoCAD SHX Text
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
BUILDING 01EA ONE-LINE
AutoCAD SHX Text
FROM TRANSFORMER TR12
AutoCAD SHX Text
TO BUILDING 01 PANEL 1E-109
AutoCAD SHX Text
EXISTING BUILDING 1EA 300KW GENERATOR
AutoCAD SHX Text
EXISTING E1EA-GEN. MB 120/208 3 /4W1200A/3P
AutoCAD SHX Text
BUILDING 01EA
AutoCAD SHX Text
EXISTING SWBD E1EA-MDP 120/208 3 /4W1000A/3P
AutoCAD SHX Text
NEW ATS E1EA-LS-ATS (LS) 400A
AutoCAD SHX Text
NEW ATS E1EA-EB-ATS 400A
AutoCAD SHX Text
NEW ATS E1EA-CB-ATS (CB) 400A
AutoCAD SHX Text
E1EA-LS
AutoCAD SHX Text 120/208
AutoCAD SHX Text 3%%c, 4W
AutoCAD SHX Text 400A 3P
AutoCAD SHX Text
E1EA-EB
AutoCAD SHX Text 120/208
AutoCAD SHX Text 3%%c, 4W
AutoCAD SHX Text 400A 3P
AutoCAD SHX Text
E1EA-CB
AutoCAD SHX Text 120/208
AutoCAD SHX Text 3%%c, 4W
AutoCAD SHX Text 400A 3P
AutoCAD SHX Text
E1EA-LESH
AutoCAD SHX Text 120/208
AutoCAD SHX Text 3%%c, 4W
AutoCAD SHX Text 125A 3P
AutoCAD SHX Text
EXISTING SWBD 1EA-MDP 120/208 3 /4W2500A/3P
AutoCAD SHX Text
TO BUILDING 01 E1E-LS
AutoCAD SHX Text
TO BUILDING 01 PANEL E1E-EB
AutoCAD SHX Text
TO BUILDING 01 PANEL E1E-B2
AutoCAD SHX Text
TO BUILDING 01 1E-ATS#4
AutoCAD SHX Text
TO BUILDING 01 1E-ATS#4
AutoCAD SHX Text 4#1/0, 1#6G, 1-1/2"C
AutoCAD SHX Text
(6) 4#600KCMIL, 1#2G, 3-1/2"C
AutoCAD SHX Text 4#1, 1#6G, 1-1/2"C
AutoCAD SHX Text
4#250KCMIL, 1#4G, 2-1/2"C
AutoCAD SHX Text 4#4/0, 1#4G, 2-1/2"C
AutoCAD SHX Text
TO BUILDING 01 PANEL E1E-CB
AutoCAD SHX Text 4#1/0, 1#6G, 1-1/2"C
AutoCAD SHX Text
TO BUILDING 01 PANEL E1E-202
AutoCAD SHX Text 4#1/0, 1#6G, 1-1/2"C
AutoCAD SHX Text
TO BUILDING 01 PANEL E1E-206
AutoCAD SHX Text 4#1/0, 1#6G, 1-1/2"C
AutoCAD SHX Text
(2) 4#300KCMIL, 1#3G, 3"C
AutoCAD SHX Text
(2) 4#300KCMIL, 1#3G, 3"C
AutoCAD SHX Text
1EA-A/C
AutoCAD SHX Text 120/208
AutoCAD SHX Text 3%%c, 4W
AutoCAD SHX Text 220A 3P
AutoCAD SHX Text
TO BUILDING 01 PANEL 1EB-4
AutoCAD SHX Text
TO BUILDING 01 PANEL 1E-104
AutoCAD SHX Text
TO BUILDING 01 PANEL 1E-105
AutoCAD SHX Text
4#600KCMIL, 1#2G, 3-1/2"C
AutoCAD SHX Text
4#250KCMIL, 1#4G, 2-1/2"C
AutoCAD SHX Text
4#250KCMIL, 1#4G, 2-1/2"C
AutoCAD SHX Text
NEW
AutoCAD SHX Text
SCALE: 1/4" = 1'-0"
AutoCAD SHX Text
BUILDING NO. 1EA - ELECTRICAL PLAN
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
NEW METERING SYSTEM CONTROL PANEL
AutoCAD SHX Text
NEW SURGE PROTECTIVE DEVICE
AutoCAD SHX Text NEW GENERATOR DOCKING STATION 1200A, 3P, 4W WITH 1200A CIRCUIT BREAKER AND SOLID STATE TRIP, START/STOP GENERATOR CONTACTS AND KIRK KEY INTERLOCK WITH EXISTING GENERATO CIRCUIT BREAKER
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
NEW SURGE PROTECTIVE DEVICE
AutoCAD SHX Text KEY NOTES: EXISTING FEEDERS TO BE REPLACED WITH NEW. EXISTING UNDERGROUND CONDUITS TO REMAIN EXISTING EQUIPMENT BRANCH (EB) TO BE SEPARATED FROM LIFE SAFETY (LS) AND CRITICAL BRANCH (CB) WIRING EXISTING 4" CONDUIT WITH CONTROL WIRES. REMOVE CONTROL WIRES AND REROUTE IN NEW 1" CONDUIT FROM GENERATOR CONTROL PANEL TO BREAKER PANEL. 3/4" C WITH GENERATOR CONTROL WIRES (10#14) FROM GENERATOR CONTROL PANEL TO GENERATOR BREAKER PANEL. RUN CONDUIT EXPOSED ON CEILING AND WALL. FIELD VERIFY EXACT WIRING EXISTING 4" CONDUITS, REMOVE EXISTING 4#500KCMIL TYPE W WIRES. PROVIDE NEW 3 SETS OF 4#444 KCMIL, 1#2G RHH/RWH-2 FLEXIBLE POWER CABLE (925 STRAND) IN EXISTING CONDUITS FROM GENERATOR ALTERNATOR TO GENERATOR CIRCUIT BREAKER. PROVIDE ADDITIONAL WIRE LUGS AT GENERATOR ALTERNATOR. PROVIDE WITH 90°C COMPRESSION LUGS AT EACH END. PROVIDEDWITH SHOO-PIN CONNECTORS. PROVIDE 3/4"C WITH NETWORK CABLING TO BMS METASYS NETWORK EQUIPMENT EXISTING DAYTANK AND PIPING TO BE REPLACED (SEE SPECIFICATIONS FOR REQUIREMENTS)
AutoCAD SHX Text
EXISTING EQUIPMENT TO BE REMOVED REFER TO NOTES FOR ADDITIONAL INFORMATION.
AutoCAD SHX Text
LEGEND
AutoCAD SHX Text
EXISTING TO REMAIN REFER TO SUMMARY OF WORK NOTES FOR ADDITIONAL INFORMATION.
AutoCAD SHX Text
NEW WORK REFER TO NOTES FOR ADDITIONAL INFORMATION.
AutoCAD SHX Text WIRING NOTES: 1. LIFE SAFETY AND CRITICAL BRANCH WIRING TO BE PHYSICALLY LIFE SAFETY AND CRITICAL BRANCH WIRING TO BE PHYSICALLY SEPARATED FROM THE NORMAL AND EQUIPMENT BRANCH WIRING.
AutoCAD SHX Text PARTIAL LEGEND (N) DENOTES PANEL ON NORMAL POWER SYSTEM DENOTES PANEL ON NORMAL POWER SYSTEM (LS) DENOTES PANEL IS ON LIFE SAFETY SYSTEM DENOTES PANEL IS ON LIFE SAFETY SYSTEM (CB) DENOTES PANEL IS ON CRITICAL BRANCH SYSTEM DENOTES PANEL IS ON CRITICAL BRANCH SYSTEM (EB) DENOTES PANEL IS ON EQUIPMENT BRANCH SYSTEM DENOTES PANEL IS ON EQUIPMENT BRANCH SYSTEM (EM) DENOTES EQUIPMENT ON EMERGENCY SYSTEMDENOTES EQUIPMENT ON EMERGENCY SYSTEM
AutoCAD SHX Text LIGHTNING PROTECTION SYSTEM NOTES: 1. DRAWINGS ARE PROVIDED AS GUIDES FOR LIGHTNING DRAWINGS ARE PROVIDED AS GUIDES FOR LIGHTNING PROTECT SYSTEM DESIGNER FINAL DRAWINGS BY LIGHTNING PROTECTION SYSTEM DESIGN SHALL BE PROVIDED AFTER FIELD VERIFICATION OF SITE CONDITIONS. LIGHTNING SYSTEM DESIGNER SHALL PROVIDE DRAWING AS PART OF SHOP DRAWING SUBMITTAL, REFER TO SPECIFICATIONS. 2. THE LIGHTNING PROTECTION SYSTEM SHALL BE THE LIGHTNING PROTECTION SYSTEM SHALL BE DESIGNED PER NFPA 780 AND U.L. MASTER LABELED. LIGHTNING PROTECTION SYSTEM SHALL BE UL TESTED & INSPECTED. 3. ALL GROUND RODS/SYSTEMS SHOULD MEET THE MIN ALL GROUND RODS/SYSTEMS SHOULD MEET THE MIN RESISTANCE AND TESTED TO MEET NFPA70/780 FOR A LIGHTNING PROTECTION SYSTEM. THE SYSTEM SHALL BE TESTED PRIOR TO THE UL INSPECTION. 4. REFER TO ONE-LINE DIAGRAMS FOR SURGE PROTECTIVE REFER TO ONE-LINE DIAGRAMS FOR SURGE PROTECTIVE DEVICES (SPD) IS BEING INSTALLED AS PART OF THIS PROJECT. THE SPD MAYBE LOCATED IN THE GENERATOR BUILDING LOCATED NEXT TO THE BUILDING.
AutoCAD SHX Text
WP/(NFMA 3R)
AutoCAD SHX Text
SHADING DENOTES AREA OF BUILDING PROTECTED BY DRY SUSPENSION SYSTEM
AutoCAD SHX Text
TAP EXISTING SWITCHBOARD IN APPROVED MANOR
AutoCAD SHX Text NOTE: FURNISH AND INSTALL NEW EX FIXTURES FOR ALL 3 ROOMS. REPLACE EXISTING FIXTURES IN SAME LOCATION. EXTENDED WIRING 2#12, 1#12G, 3/4"C AHEAD OF LOCAL SWITCHING. EXACT LOCATION BY COR
AutoCAD SHX Text
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 2'
AutoCAD SHX Text
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 2'
AutoCAD SHX Text 3#2/0, 1#4G, 2"C
AutoCAD SHX Text
TO BUILDING 01 ELEVATOR CIRCUIT BREAKER
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ADDENDUM ITEMS
AutoCAD SHX Text 10/24/23
VHANHMZajacN Polygon
01WA-EP101
BUILDING NO. 1WA - ELECTRICAL
PLAN 01WA
W.H.H. E.J.D.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Fi le
P at h
CONSTRUCTION
DOCUMENTS
MAY 30, 2023
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
ELECTRICAL DISTRIBUTION
SYSTEM UPGRADE - PHASE 2
VA CWM
631-18-003
Project Director
MAY 30, 2023Revisions: Date:
© Copyright 2020 DuBois & King Inc.
85 MAIN STREET
SPRINGFIELD, VT 05156
TEL: (802) 591-4326
FAX: (866) 783-7101
www.dubois-king.com
I:\ 5\
V
AM
C
E le c D is t P ha se
3\ D ra w in gs
\E le ct ric al \0
1W A-
EP
BU
IL
D
IN
G
N O
. 1 W
A
- E
LE
C
TR
IC
AL
P
LA
N
.d w g
1/ 2/
:1
6:
P M
631-25-001 Only in scope work
AutoCAD SHX Text
EXISTING 300KW GENERATOR
AutoCAD SHX Text
EXISTING SWBD 1WA-MDP
AutoCAD SHX Text
EXISTING SWBD E1WA-MDP
AutoCAD SHX Text
EXISTING ATS#1(LS) TO BE REMOVED
AutoCAD SHX Text
EXISTING ATS#3(EB) TO BE REMOVED
AutoCAD SHX Text
EXISTING ATS#2(CB) TO BE REMOVED
AutoCAD SHX Text
EXISTING PANEL E1WA-EB TO BE REMOVED
AutoCAD SHX Text
EXISTING PANEL E1WA-CB
AutoCAD SHX Text
EXISTING PANEL E1WA-LS
AutoCAD SHX Text
EXISTING PANEL E1WA-LESH
AutoCAD SHX Text
EXISTING TRANSFORMER MTD HIGH ON WALL
AutoCAD SHX Text
EXISTING WIREWAY TO BE REMOVED
AutoCAD SHX Text
EXISTING WIRE TRENCH WITH STEEL COVERS
AutoCAD SHX Text
EXISTING GENERATOR MAIN BREAKER
AutoCAD SHX Text NOTES: 1. EXISTING INTERIOR AND EXTERIOR LIGHTS TO BE EXISTING INTERIOR AND EXTERIOR LIGHTS TO BE REMOVED AND REPLACED WITH NEW LIGHTS. FIELD VERIFY LOCATION AND QUANTITY. EXISTING WIRING AND CONTROLS TO REMAIN. EXIT SIGNS TO REMAIN.
AutoCAD SHX Text
3"C WITH WIRES TO BUILDING NO. 1
AutoCAD SHX Text
3/4"C TO HVAC UNIT
AutoCAD SHX Text
CONDUITS TO BE RELOCATED FOR EGRESS PATH
AutoCAD SHX Text
BUILDING NO. 1 WALL
AutoCAD SHX Text
EXISTING MECHANICAL PIPING TO BE RELOCATED REFER TO MECHANICAL DRAWINGS
AutoCAD SHX Text RELOCATE EXISTING THERMOSTATS, TELEPHONE AND CONDUITS IN THIS AREA FOR DOOR AND NEW EQUIPMENT
AutoCAD SHX Text
EXISTING GENERATOR MAIN BREAKER
AutoCAD SHX Text
EXISTING 300KW GENERATOR
AutoCAD SHX Text
EXISTING SWBD 1WA-MDP
AutoCAD SHX Text
EXISTING SWBD E1WA-MDP
AutoCAD SHX Text
EXISTING PANEL E1WA-CB
AutoCAD SHX Text
EXISTING PANEL E1WA-LS
AutoCAD SHX Text
EXISTING PANEL E1WA-LESH
AutoCAD SHX Text
EXISTING TRANSFORMER MTD HIGH ON WALL
AutoCAD SHX Text
NEW ISOLATION BYPASS AUTOMATIC TRANSFER SWITCH E1WA-CB-ATS
AutoCAD SHX Text
NEW PANEL E1WA-EB
AutoCAD SHX Text
NEW ISOLATION BYPASS AUTOMATIC TRANSFER SWITCH E1WA-LS-ATS
AutoCAD SHX Text
NEW ISOLATION BYPASS AUTOMATIC TRANSFER SWITCH E1WA-EB-ATS
AutoCAD SHX Text
NEW METERING PANEL
AutoCAD SHX Text
NEW SURGE PROTECTIVE DEVICE
AutoCAD SHX Text
NEW SURGE PROTECTIVE DEVICE
AutoCAD SHX Text DUCT BANKS TO BUILDING No. 1 WEST ELECTRIC VAULTS
AutoCAD SHX Text
E1WA-LESH-16
AutoCAD SHX Text
EXISTING BMS METASYS NETWORK EQUIPMENT
AutoCAD SHX Text
E1WA- LESH-30
AutoCAD SHX Text
PROVIDE NEW GENERATOR WIRING MONITORING SYSTEM
AutoCAD SHX Text NEW LIGHTS TO REPLACE EXISTING INTERIOR LIGHTS IN INDICATED AND EXTENDED LOCATIONS (TYP.) UTILIZE EXISTING WIRING 3/4"C WITH 2#12, 1#12G
AutoCAD SHX Text NEW LIGHTS TO REPLACE EXISTING EXTERIOR LIGHTS IN EXISTING LOCATIONS (TYP.) UTILIZE EXISTING WIRING
AutoCAD SHX Text
RELOCATED 3" RGS CONDUIT. EXTEND WIRE AND CONDUIT TO SOURCE
AutoCAD SHX Text
RELOCATED 3/4"C RGS CONDUIT. EXTEND WIRE AND CONDUIT
AutoCAD SHX Text
E1WA- LESH-5
AutoCAD SHX Text DRY SUPPRESSION SYSTEM AND CONTROLS, AREA INDICATED BY SHADING DENOTES AREA TO BE PROTECTED BY DRY AGENT SUPPRESSION SYSTEM (REFER TO SPEC 21 2200)
AutoCAD SHX Text
NEW GENERATOR DOCKING STATION PER REQUIREMENTS ON NEC ARTICLE 700.3 (F)
AutoCAD SHX Text
AutoCAD SHX Text
NOT TO SCALE
AutoCAD SHX Text
BUILDING 01WA ONE-LINE
AutoCAD SHX Text
FROM TRANSFORMER TR14
AutoCAD SHX Text
TO BUILDING 01 PANEL 1WB-7
AutoCAD SHX Text
EXISTING BUILDING 1WA 300KW (1050A) GENERATOR
AutoCAD SHX Text
EXISTING E1WA-GEN. MB 120/208 3 /4W1200A/3P
AutoCAD SHX Text
BUILDING 01WA
AutoCAD SHX Text
EXISTING SWBD E1WA-MDP 120/208 3 /4W1000A/3P
AutoCAD SHX Text
E1WA-LS
AutoCAD SHX Text 120/208
AutoCAD SHX Text 3%%c, 4W
AutoCAD SHX Text 400A 3P
AutoCAD SHX Text
E1WA-CB
AutoCAD SHX Text 120/208
AutoCAD SHX Text 3%%c, 4W
AutoCAD SHX Text 400A 3P
AutoCAD SHX Text
E1WA-LESH
AutoCAD SHX Text 120/208
AutoCAD SHX Text 3%%c, 4W
AutoCAD SHX Text 125A 3P
AutoCAD SHX Text
EXISTING SWBD 1WA-MDP 120/208 3 /4W2500A/3P
AutoCAD SHX Text
TO BUILDING 01 E1W-LS
AutoCAD SHX Text
TO BUILDING 01 PANEL E1W-EB
AutoCAD SHX Text
TO BUILDING 01 PANEL E1W-102
AutoCAD SHX Text
TO BUILDING 01 1W-ATS#4
AutoCAD SHX Text
TO BUILDING 01 1W-ATS#4
AutoCAD SHX Text 4#1/0, 1#6G, 1-1/2"C
AutoCAD SHX Text
(6) 4#600KCMIL, 1#2G, 3-1/2"C
AutoCAD SHX Text 4#3/0, 1#6G, 2"C
AutoCAD SHX Text 4#2, 1#6G, 1-1/4"C
AutoCAD SHX Text
TO BUILDING 01 PANEL E1W-CB
AutoCAD SHX Text 4#1/0, 1#6G, 1-1/2"C
AutoCAD SHX Text
TO BUILDING 01 CT SCAN DISC.
AutoCAD SHX Text
4#350KCMIL, 1#3G, 3"C
AutoCAD SHX Text
TO BUILDING 01 PANEL E1W-B2
AutoCAD SHX Text 4#4/0, 1#4G, 2"C
AutoCAD SHX Text
(2) 4#600KCMIL, 1#2G, 3-1/2"C
AutoCAD SHX Text
(2) 4#300KCMIL, 1#3G, 3"C
AutoCAD SHX Text
TO BUILDING 01 PANEL 1WB-105
AutoCAD SHX Text
TO BUILDING 01 E1W-103
AutoCAD SHX Text 4#1/0, 1#6G, 1-1/2"C
AutoCAD SHX Text
TO BUILDING 01 PANEL E1WB-12
AutoCAD SHX Text 4#4/0, 1#4G, 2"C
AutoCAD SHX Text 4#4/0, 1#4G, 2-1/2"C
AutoCAD SHX Text
TO BUILDING 01 PANEL 1W-105
AutoCAD SHX Text
4#500KCMIL, 1#3G, 3"C
AutoCAD SHX Text 4#4/0, 1#4G, 2-1/2"C
AutoCAD SHX Text
TO BUILDING 01 PANEL 1WB-6
AutoCAD SHX Text 4#4/0, 1#4G, 2-1/2"C
AutoCAD SHX Text
SCALE: 1/4" = 1'-0"
AutoCAD SHX Text
BUILDING 1WA - DEMOLITION PLAN PLAN
AutoCAD SHX Text
AutoCAD SHX Text
SCALE: 1/4" = 1'-0"
AutoCAD SHX Text
BUILDING 1WA - ELECTRICAL PLAN
AutoCAD SHX Text
AutoCAD SHX Text KEY NOTES: EXISTING FEEDERS TO BE REPLACED WITH NEW EXISTING UNDERGROUND CONDUITS TO REMAIN EXISTING EQUIPMENT BRANCH (EB) TO BE SEPARATED FROM LIFE SAFETY (LS) AND CRITICAL BRANCH (CB) WIRING EXISTING 4" CONDUIT WITH CONTROL WIRES. REMOVE CONTROL WIRES AND REROUTE IN NEW 3/4" CONDUIT FROM GENERATOR CONTROL PANEL TO BREAKER PANEL. 3/4" C WITH GENERATOR CONTROL WIRES (10#14) FROM GENERATOR CONTROL PANEL TO GENERATOR BREAKER PANEL. RUN CONDUIT EXPOSED ON CEILING AND WALL. EXISTING 4" CONDUITS, REMOVE EXISTING 4#500KCMIL TYPE W WIRES. PROVIDE NEW 3 SETS OF 4#444 KCMIL, 1#2G RHH/RWH-2 FLEXIBLE POWER CABLE (925 STRAND) IN EXISTING CONDUITS FROM GENERATOR ALTERNATOR TO GENERATOR CIRCUIT BREAKER. PROVIDE ADDITIONAL WIRE LUGS AT GENERATOR ALTERNATOR. PROVIDE WITH 90°C COMPRESSION LUGS AT EACH END. PROVIDED WITH SHOO-PINCONNECTORS. PROVIDE 3/4"C WITH NETWORK CABLING TO BMS METASYS NETWORK EQUIPMENT EXISTING DAYTANK AND PIPING TO BE REPLACED (SEE SPECIFICATIONS FOR REQUIREMENTS)
AutoCAD SHX Text
ATS E1WA-LS-ATS (LS) 400A (NEW)
AutoCAD SHX Text
ATS E1WA-CB-ATS 400A (NEW)
AutoCAD SHX Text
ATS E1WA-EB-ATS 400A (NEW)
AutoCAD SHX Text
E1WA-EB
AutoCAD SHX Text 120/208
AutoCAD SHX Text 3%%c, 4W
AutoCAD SHX Text 400A 3P
AutoCAD SHX Text
(NEW)
AutoCAD SHX Text
NEW METERING SYSTEM CONTROL PANEL
AutoCAD SHX Text
NEW SURGE PROTECTIVE DEVICE
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
EXISTING
AutoCAD SHX Text
NEW SURGE PROTECTIVE DEVICE
AutoCAD SHX Text
TO BUILDING 01 FIRE PUMP CONTROLLER
AutoCAD SHX Text 3#4/0, 1#6G, 2"C
AutoCAD SHX Text WIRING NOTES: 1. LIFE SAFETY AND CRITICAL BRANCH WIRING TO BE PHYSICALLY LIFE SAFETY AND CRITICAL BRANCH WIRING TO BE PHYSICALLY SEPARATED FROM THE NORMAL AND EQUIPMENT BRANCH WIRING.
AutoCAD SHX Text PARTIAL LEGEND (N) DENOTES PANEL ON NORMAL POWER SYSTEM DENOTES PANEL ON NORMAL POWER SYSTEM (LS) DENOTES PANEL IS ON LIFE SAFETY SYSTEM DENOTES PANEL IS ON LIFE SAFETY SYSTEM (CB) DENOTES PANEL IS ON CRITICAL BRANCH SYSTEM DENOTES PANEL IS ON CRITICAL BRANCH SYSTEM (EB) DENOTES PANEL IS ON EQUIPMENT BRANCH SYSTEM DENOTES PANEL IS ON EQUIPMENT BRANCH SYSTEM (EM) DENOTES EQUIPMENT ON EMERGENCY SYSTEMDENOTES EQUIPMENT ON EMERGENCY SYSTEM
AutoCAD SHX Text LIGHTNING PROTECTION SYSTEM NOTES: 1. DRAWINGS ARE PROVIDED AS GUIDES FOR LIGHTNING DRAWINGS ARE PROVIDED AS GUIDES FOR LIGHTNING PROTECT SYSTEM DESIGNER FINAL DRAWINGS BY LIGHTNING PROTECTION SYSTEM DESIGN SHALL BE PROVIDED AFTER FIELD VERIFICATION OF SITE CONDITIONS. LIGHTNING SYSTEM DESIGNER SHALL PROVIDE DRAWING AS PART OF SHOP DRAWING SUBMITTAL, REFER TO SPECIFICATIONS. 2. THE LIGHTNING PROTECTION SYSTEM SHALL BE DESIGNED THE LIGHTNING PROTECTION SYSTEM SHALL BE DESIGNED PER NFPA 780 AND U.L. MASTER LABELED. LIGHTNING PROTECTION SYSTEM SHALL BE UL TESTED & INSPECTED. 3. ALL GROUND RODS/SYSTEMS SHOULD MEET THE MIN ALL GROUND RODS/SYSTEMS SHOULD MEET THE MIN RESISTANCE AND TESTED TO MEET NFPA70/780 FOR A LIGHTNING PROTECTION SYSTEM. THE SYSTEM SHALL BE TESTED PRIOR TO THE UL INSPECTION. 4. REFER TO ONE-LINE DIAGRAMS FOR SURGE PROTECTIVE REFER TO ONE-LINE DIAGRAMS FOR SURGE PROTECTIVE DEVICES (SPD) IS BEING INSTALLED AS PART OF THIS PROJECT. THE SPD MAYBE LOCATED IN THE GENERATOR BUILDING LOCATED NEXT TO THE BUILDING.
AutoCAD SHX Text NOTE: FURNISH AND INSTALL NEW EX FIXTURES FOR ALL 3 ROOMS. REPLACE EXISTING FIXTURES IN SAME LOCATION. EXTENDED WIRING 2#12, 1#12G, 3/4"C AHEAD OF LOCAL SWITCHING. EXACT LOCATION BY COR
AutoCAD SHX Text
EXISTING EQUIPMENT TO BE REMOVED REFER TO NOTES FOR ADDITIONAL INFORMATION.
AutoCAD SHX Text
LEGEND
AutoCAD SHX Text
EXISTING TO REMAIN REFER TO SUMMARY OF WORK NOTES FOR ADDITIONAL INFORMATION.
AutoCAD SHX Text
NEW WORK REFER TO NOTES FOR ADDITIONAL INFORMATION.
AutoCAD SHX Text
SHADING DENOTES AREA OF BUILDING PROTECTED BY DRY SUSPENSION SYSTEM
AutoCAD SHX Text NEW GENERATOR DOCKING STATION 1200A, 3P, 4W WITH 1200A CIRCUIT BREAKER AND SOLID STATE TRIP, START/STOP GENERATOR CONTACTS AND KIRK KEY INTERLOCK WITH EXISTING GENERATO CIRCUIT BREAKER
AutoCAD SHX Text
WP/(NFMA 3R)
AutoCAD SHX Text
TAP EXISTING SWITCHBOARD IN APPROVED MANOR
AutoCAD SHX Text
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 2'
AutoCAD SHX Text
AutoCAD SHX Text 4'
AutoCAD SHX Text 8'
AutoCAD SHX Text 2'
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
FROM BUILDING 01 PANEL E1S-DP
AutoCAD SHX Text
(2) 4#500KCMIL, 1#3G, 3"C
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
AutoCAD SHX Text
ADDENDUM ITEMS
AutoCAD SHX Text 10/24/23
VHANHMZajacN Polygon
E
LE
V A T O R P
IT P
IT
E
LE
V A T O R
D N
D N
UP
U P
U P
U P
U P
U P
D N
D N
U P
U P
E
LE
V A T O R P
IT P
IT
E
LE
V A T O R
D N
D N
UP
U P
U P
U P
U P
U P
D N
D N
U P
U P
ELECTRIC
ROOM
B244
ELECTRIC
ROOM
B015
Phone
ROOM
B108A
WATER
SERVICE
B152
WATER
SERVICE
B018
WATER
SERVICE
B245
ELECTRIC
ROOM
B129A
WATER
SERVICE
B106A
WATER
SERVICE
B112
BUILDING 1 basement for reference and location of water service and electrical service to be bonded
3/32" = 1'0"
| 631-25-001 Building 1 Lightning Protection Technical Questions |
| 01EA-EP101 |
| 01WA-EP101 |
| 631-25-001 Building 1 Lightning Protection Technical Questions |
| 264313 - SURGE PROTECTIVE DEVICES |
| water service B1 |
| Sheets and Views |
| water service B1-Layout2 |
| water service B1 |
| Sheets and Views |
| water service B1-Layout2 |
File details come from the government source that posted it. Updated .