631-25-001 Building 1 Lightning Protection Technical Questions and Answers.pdf

PDF 1 MB Posted

Attached to
5920--631-25-001 Building 1 Lightning Protection
Solicitation number
36C24125R0031
Issued by

About this file

This is a Questions and Answers document for a lightning protection system project at Building 1, accompanied by technical specifications for surge protective devices and electrical plans. The Q&A addresses specific technical requirements including the absence of an existing counterpoise ring, location of surge protection devices, bonding requirements for water services, and specifications for lightning arrestors on telephone, radio and TV antenna services.

Key technical details include the need for approximately 700 feet of 3/0 copper and conduit in the basement for bonding three water services, installation of surge protection devices on two Siemens 208/120 2500A electrical service panels, and telephone service connections in room B108A. The accompanying specification section 26 43 13 details requirements for Type 2 Surge Protective Devices, while electrical plans 01EA-EP101 and 01WA-EP101 show equipment locations and demolition details. The project requires bid bonds per FAR 52.228-1(b), and allows high-compression crimps as an alternative to exothermic welds for underground grounding connections.

View the file

Other files

File Type Posted
36C24125R0031 0002.docx DOCX document
Site Visit Sign In Sheet 631-25-001 Building 1 Lightning Protection.pdf PDF
SOW building 1 lightning protection R1.pdf PDF
36C24125R0031 0001.docx DOCX document
P07 MA20240003 12.13.2024.pdf PDF
631-25-001 Drawings.pdf PDF
36C24125R0031.docx DOCX document
631-25-001 Specifications.pdf PDF
SOW Building 1 Lightning Protection.pdf PDF

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

631-25-001 Building 1 Lightning Protection

Questions and Answers

1. Does Building 1 have an existing counterpoise ring? If not, will one need to be installed for this project or will ground rods at each downlead suffice?

Answer: There is no existing ground ring for the building and no new one is proposed, downleads should suffice. Final drawings shall be provided after field verification by the lightning system designer.

2. Note 4 on drawing 01-EP112 mentions a one line diagram showing where surge protection devices are to be installed. Can this drawing and specs for the surge protection devices needed be provided?

Answer: Drawing 01EA-EP101 and 01WA-EP101 added for reference. Only SPD is required from these two drawings. Spec section 26 43 13 added.

3. Note 13 on drawing ESS503 calls for bonding to domestic and fire waterlines, can a drawing showing the location and quantity of lines needing bonded be provided?Answer:

PDF added for reference. Water services will need bonded. This needs to be field verified and add. Approximately 700’ of 3/0 copper and conduit will be needed in the basement.

This includes bonding the 3 services together.

4. Note 14 on drawing Ess503 calls for lightning arrestors on the telephone service, radio and TV antennas, can a drawing be provided showing the location of these items?

Answer: Telephone service is in room B108A and the radio antenna is located on the flat roof in the center of the building.

5. Are bid bonds required with quotes.

Answer: Per FAR 52.228-1(b), the bidder shall furnish a bid guarantee in the form of a firm commitment, e.g., bid bond supported by good and sufficient surety or sureties acceptable to the Government, postal money order, certified check, cashier’s check, irrevocable letter of credit, or, under Treasury Department regulations, certain bonds or notes of the United States.

6. Will surge protection devices be required for the communication and low voltage lines entering the building? If yes, please confirm the type of system, maximum operating voltage and amperage, number and size of wires, method of connection, data speed, and length of run.

Answer: Yes, Phone service is in room B108A

7. Please provide the quantity of main electrical service panels requiring surge protection.

Answer: 2

8. Please provide the manufacturer of the electrical service panel, and the voltage configuration.

Answer: Siemens 208/120 2500A

9. Will high-compression crimps, listed for the purpose of underground grounding connections be permitted as an alternative to exothermic welds?

Answer: Yes

10. Will services need to be bonded?

Answer: Yes, building 1 has 3 services and they will need to be bonded together with a 3/0 copper. The 700’ in question 3 includes the water and electric services.

Electrical Distribution System Upgrade Phase 2 12-12-22

631-18-003

01-01-17

26 43 13 - 1

SECTION 26 43 13

SURGE PROTECTIVE DEVICES

PART 1 - GENERAL

1.1 DESCRIPTION

A. This section specifies the furnishing, installation, and connection of

Type 2 Surge Protective Devices, as defined in NFPA 70, and indicated as SPD in this section.

1.2 RELATED WORK

A. Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS:

Requirements that apply to all sections of Division 26.

1.3 QUALITY ASSURANCE

A. Quality Assurance shall be in accordance with Paragraph, QUALIFICATIONS

(PRODUCTS AND SERVICES) in Section 26 05 11, REQUIREMENTS FOR

ELECTRICAL INSTALLATIONS.

1.4 SUBMITTALS

A. Submit in accordance with Paragraph, SUBMITTALS in Section 26 05 11, REQUIREMENTS FOR ELECTRICAL INSTALLATIONS, and the following requirements:

1. Manufacturer’s Literature and Data for each product:

a. Provide manufacturer’s catalog information, weights, mounting requirements, data and listings.

2. Shop Drawings:

a. Submit sufficient information to demonstrate compliance with drawings and specifications.

b. Include electrical ratings and device nameplate data.

3. Manuals:

a. Submit, simultaneously with the shop drawings, companion copies of complete maintenance and operating manuals including technical data sheets, wiring diagrams, and information for ordering replacement parts.

b. If changes have been made to the maintenance and operating manuals originally submitted, submit updated maintenance and operating manuals two weeks prior to the final inspection.

4. Test Reports:

c. Provide a final report for all acceptance checks for all tests, test results and verifications per paragraphs 3.2 and 3.3.

5. Certifications: Two weeks prior to final inspection, submit the following.

01-01-17

26 43 13 - 2

a. Certification by the manufacturer that the SPD conforms to the requirements of the drawings and specifications.

b. Certification by the Contractor that the SPD has been properly installed.

1.5 APPLICABLE PUBLICATIONS

A. Publications listed below (including amendments, addenda, revisions, supplement and errata) form a part of this specification to the extent referenced. Publications are referenced in the text by the basic designation only.

B. Institute of Engineering and Electronic Engineers (IEEE):

IEEE C62.41.2-02........Characterization of Surges in Low-Voltage (1000

V and Less) AC Power Circuits

IEEE C62.45-08..........Surge Testing for Equipment Connected to Low-

Voltage (1000 V and Less) AC Power Circuits

C. National Fire Protection Association (NFPA):

70-23...................National Electrical Code (NEC)

110-22..................Standard for Emergency and Standby Power

Systems

D. Underwriters Laboratories, Inc. (UL):

UL 1283-17..............Electromagnetic Interference Filters

UL 1449-21..............Surge Protective Devices

1.6 WARRANTY

A. Construction Warranty: FAR clause 52.246-21, "Warranty of

Construction."

PART 2 - PRODUCTS

2.1 SWITCHGEAR/SWITCHBOARD SPD

A. General Requirements:

1. Comply with IEEE and UL.

2. Modular design with field-replaceable modules, or non-modular design.

3. Fuses, rated at 200 kA interrupting capacity.

4. Bolted compression lugs for internal wiring.

5. Integral disconnect switch.

6. Redundant suppression circuits.

7. LED indicator lights for power and protection status.

8. Audible alarm, with silencing switch, to indicate when protection has failed.

01-01-17

26 43 13 - 3

9. Form-C contacts rated at 5 A and 250-V ac, one normally open and one normally closed, for remote monitoring of protection status.

Contacts shall reverse on failure of any surge diversion module or on opening of any current-limiting device.

10. Four-digit transient-event counter.

B. Surge Current per Phase: Minimum 240kA per phase.

2.3 ENCLOSURES

A. Enclosures: NEMA 1.

PART 3 - EXECUTION

3.1 INSTALLATION

A. Installation shall be in accordance with the NEC, as shown on the drawings, and manufacturer’s instructions.

B. Factory-installed SPD: Switchgear, switchboard, or panelboard manufacturer shall install SPD at the factory.

C. Field-installed SPD: Contractor shall install SPD with conductors or buses between SPD and points of attachment as short and straight as possible. Do not exceed manufacturer's recommended lead length. Do not bond neutral and ground.

1. Provide a circuit breaker as a dedicated disconnecting means for

TVSS as shown on drawings.

D. Do not perform insulation resistance tests on switchgear, switchboards, panelboards, or feeders with the SPD connected. Disconnect SPD before conducting insulation resistance tests and reconnect SPD immediately after insulation resistance tests are complete.

3.2 ACCEPTANCE CHECKS AND TESTS

A. Perform in accordance with the manufacturer's recommendations. In addition, include the following:

1. Visual Inspection and Tests:

a. Compare equipment nameplate data with specifications and approved shop drawings.

b. Inspect physical, electrical, and mechanical condition.

c. Verify that disconnecting means and feeder size and maximum length to SPD corresponds to approved shop drawings.

d. Verifying tightness of accessible bolted electrical connections by calibrated torque-wrench method.

e. Vacuum-clean enclosure interior. Clean enclosure exterior.

f. Verify the correct operation of all sensing devices, alarms, and indicating devices.

01-01-17

26 43 13 - 4

3.3 FOLLOW-UP VERIFICATION

A. After completion of acceptance checks and tests, the Contractor shall show by demonstration in service that SPD are in good operating condition and properly performing the intended function.

3.4 INSTRUCTION

A. Refer to Specification 01 00 00 for requirements for training and instructions.

B. Provide the services of a factory-trained technician for one 2-hour training period for instructing personnel in the maintenance and operation of the SPD, on the date requested by the COR.

---END---

01EA-EP101

BUILDING NO. 1EA FIRST LEVEL

ELECTRICAL PLAN 01EA

W.H.H. E.J.D.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

CONSTRUCTION

DOCUMENTS

MAY 30, 2023

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

ELECTRICAL DISTRIBUTION

SYSTEM UPGRADE - PHASE 2

VA CWM

631-18-003

Project Director

MAY 30, 2023Revisions: Date:

© Copyright 2020 DuBois & King Inc.

85 MAIN STREET

SPRINGFIELD, VT 05156

TEL: (802) 591-4326

FAX: (866) 783-7101

www.dubois-king.com

I:\ 5\

V

AM

C

E le c D is t P ha se

3\ D ra w in gs

\E le ct ric al \0

1E A-

EP

BU

IL

D

IN

G

N O

. 1

EA

F

IR

ST

L

EV

EL

E

LE

C

TR

IC

AL

P

LA

N .d w g

1/

2/

4:

:3

PM

631-25-001 Only in scope work

AutoCAD SHX Text

EXISTING PANEL 1EA-A/C TO BE RELOCATED

AutoCAD SHX Text

EXISTING GENERATOR MAIN BRKR

AutoCAD SHX Text

EXISTING SWBD E1EA-MDP

AutoCAD SHX Text

EXISTING ATS#1(LS) TO BE REMOVED

AutoCAD SHX Text

EXISTING ATS#3(EB) TO BE REMOVED

AutoCAD SHX Text

EXISTING ATS#2(CB) TO BE REMOVED

AutoCAD SHX Text

EXISTING E1EA-EB TO BE REMOVED

AutoCAD SHX Text

EXISTING PANEL E1EA-CB

AutoCAD SHX Text

EXISTING PANEL E1EA-LS

AutoCAD SHX Text

EXISTING PANEL E1EA-LESH

AutoCAD SHX Text

EXISTING 300KW GENERATOR

AutoCAD SHX Text

EXISTING WIREWAY TO BE REMOVED

AutoCAD SHX Text

TRENCH WITH EMERGENCY CIRCUITS TO BE UPGRADED

AutoCAD SHX Text NOTES: 1. EXISTING INTERIOR AND EXTERIOR LIGHTS TO BE EXISTING INTERIOR AND EXTERIOR LIGHTS TO BE REMOVED AND REPLACED WITH NEW LIGHTS. FIELD VERIFY LOCATION AND QUANTITY. EXISTING WIRING AND CONTROLS TO REMAIN. EXIT SIGNS TO REMAIN.

AutoCAD SHX Text

EXISTING TELEPHONE, JACK AND UNDERGROUND CONDUITS TO BE RELOCATED

AutoCAD SHX Text

EXISTING TRANSFORMER TO BE RELOCATED TO AVOID NEW DOOR

AutoCAD SHX Text

EXISTING PULLBOX AND FEEDERS TO TRANSFORMER

AutoCAD SHX Text RELOCATE EXISTING THERMOSTATS, TELEPHONE AND CONDUITS IN THIS AREA FOR DOOR AND NEW EQUIPMENT

AutoCAD SHX Text

EXISTING SWBD 1EA-MDP

AutoCAD SHX Text

CONDUITS TO TRANSFORMER

AutoCAD SHX Text

NEW ISOLATION BYPASS AUTOMATIC TRANSFER SWITCH E1EA-CB-ATS

AutoCAD SHX Text

NEW PANEL E1EA-EB

AutoCAD SHX Text

RELOCATED PANEL 1EA-A/C

AutoCAD SHX Text

EXISTING GENERATOR MAIN BRKR

AutoCAD SHX Text

EXISTING SWBD 1EA-MDP

AutoCAD SHX Text

EXISTING SWBD E1EA-MDP

AutoCAD SHX Text

EXISTING PANEL E1EA-CB

AutoCAD SHX Text

EXISTING PANEL E1EA-LS

AutoCAD SHX Text

EXISTING PANEL E1EA-LESH

AutoCAD SHX Text

EXISTING 300KW GENERATOR

AutoCAD SHX Text

NEW ISOLATION BYPASS AUTOMATIC TRANSFER SWITCH E1EA-LS-ATS

AutoCAD SHX Text

NEW ISOLATION BYPASS AUTOMATIC TRANSFER SWITCH E1EA-EB-ATS

AutoCAD SHX Text

NEW METERING PANEL

AutoCAD SHX Text

NEW SURGE PROTECTIVE DEVICE

AutoCAD SHX Text

NEW SURGE PROTECTIVE DEVICE

AutoCAD SHX Text NEW LIGHTS TO REPLACE EXISTING INTERIOR LIGHTS IN EXISTING LOCATIONS (TYP.) UTILIZE EXISTING WIRING

AutoCAD SHX Text

E1EA-LESH-8

AutoCAD SHX Text

E1EA- LESH-16

AutoCAD SHX Text

PROVIDE NEW GENERATOR WIRING MONITORING SYSTEM

AutoCAD SHX Text

EXISTING METASYS EQUIPMENT

AutoCAD SHX Text DUCT BANKS TO BUILDING No. 1 EAST ELECTRIC VAULTS

AutoCAD SHX Text NEW LIGHTS TO REPLACE EXISTING EXTERIOR LIGHTS IN EXISTING LOCATIONS (TYP.) UTILIZE EXISTING WIRING

AutoCAD SHX Text

RELOCATED TRANSFORMER, FIELD COORDINATE WITH COR ON EXACT REQUIREMENTS

AutoCAD SHX Text

GENERATOR INTAKE HOOD

AutoCAD SHX Text

NEW CONCRETE PAD

AutoCAD SHX Text

NEW WIRE AND CONDUIT MATCH EXISTING SIZES

AutoCAD SHX Text

E1EA- LESH-5

AutoCAD SHX Text DRY SUPPRESSION SYSTEM AND CONTROLS, AREA INDICATED BY SHADING. IT DENOTES AREA TO BE PROTECTED BY DRY AGENT SUPPRESSION SYSTEM (REFER TO SPEC 21 2200)

AutoCAD SHX Text

NEW GENERATOR DOCKING STATION PER REQUIREMENTS ON NEC ARTICLE 700.3 (F)

AutoCAD SHX Text

SCALE: 1/4" = 1'-0"

AutoCAD SHX Text

BUILDING NO. 1EA - DEMOLITION PLAN

AutoCAD SHX Text

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

BUILDING 01EA ONE-LINE

AutoCAD SHX Text

FROM TRANSFORMER TR12

AutoCAD SHX Text

TO BUILDING 01 PANEL 1E-109

AutoCAD SHX Text

EXISTING BUILDING 1EA 300KW GENERATOR

AutoCAD SHX Text

EXISTING E1EA-GEN. MB 120/208 3 /4W1200A/3P

AutoCAD SHX Text

BUILDING 01EA

AutoCAD SHX Text

EXISTING SWBD E1EA-MDP 120/208 3 /4W1000A/3P

AutoCAD SHX Text

NEW ATS E1EA-LS-ATS (LS) 400A

AutoCAD SHX Text

NEW ATS E1EA-EB-ATS 400A

AutoCAD SHX Text

NEW ATS E1EA-CB-ATS (CB) 400A

AutoCAD SHX Text

E1EA-LS

AutoCAD SHX Text 120/208

AutoCAD SHX Text 3%%c, 4W

AutoCAD SHX Text 400A 3P

AutoCAD SHX Text

E1EA-EB

AutoCAD SHX Text 120/208

AutoCAD SHX Text 3%%c, 4W

AutoCAD SHX Text 400A 3P

AutoCAD SHX Text

E1EA-CB

AutoCAD SHX Text 120/208

AutoCAD SHX Text 3%%c, 4W

AutoCAD SHX Text 400A 3P

AutoCAD SHX Text

E1EA-LESH

AutoCAD SHX Text 120/208

AutoCAD SHX Text 3%%c, 4W

AutoCAD SHX Text 125A 3P

AutoCAD SHX Text

EXISTING SWBD 1EA-MDP 120/208 3 /4W2500A/3P

AutoCAD SHX Text

TO BUILDING 01 E1E-LS

AutoCAD SHX Text

TO BUILDING 01 PANEL E1E-EB

AutoCAD SHX Text

TO BUILDING 01 PANEL E1E-B2

AutoCAD SHX Text

TO BUILDING 01 1E-ATS#4

AutoCAD SHX Text

TO BUILDING 01 1E-ATS#4

AutoCAD SHX Text 4#1/0, 1#6G, 1-1/2"C

AutoCAD SHX Text

(6) 4#600KCMIL, 1#2G, 3-1/2"C

AutoCAD SHX Text 4#1, 1#6G, 1-1/2"C

AutoCAD SHX Text

4#250KCMIL, 1#4G, 2-1/2"C

AutoCAD SHX Text 4#4/0, 1#4G, 2-1/2"C

AutoCAD SHX Text

TO BUILDING 01 PANEL E1E-CB

AutoCAD SHX Text 4#1/0, 1#6G, 1-1/2"C

AutoCAD SHX Text

TO BUILDING 01 PANEL E1E-202

AutoCAD SHX Text 4#1/0, 1#6G, 1-1/2"C

AutoCAD SHX Text

TO BUILDING 01 PANEL E1E-206

AutoCAD SHX Text 4#1/0, 1#6G, 1-1/2"C

AutoCAD SHX Text

(2) 4#300KCMIL, 1#3G, 3"C

AutoCAD SHX Text

(2) 4#300KCMIL, 1#3G, 3"C

AutoCAD SHX Text

1EA-A/C

AutoCAD SHX Text 120/208

AutoCAD SHX Text 3%%c, 4W

AutoCAD SHX Text 220A 3P

AutoCAD SHX Text

TO BUILDING 01 PANEL 1EB-4

AutoCAD SHX Text

TO BUILDING 01 PANEL 1E-104

AutoCAD SHX Text

TO BUILDING 01 PANEL 1E-105

AutoCAD SHX Text

4#600KCMIL, 1#2G, 3-1/2"C

AutoCAD SHX Text

4#250KCMIL, 1#4G, 2-1/2"C

AutoCAD SHX Text

4#250KCMIL, 1#4G, 2-1/2"C

AutoCAD SHX Text

NEW

AutoCAD SHX Text

SCALE: 1/4" = 1'-0"

AutoCAD SHX Text

BUILDING NO. 1EA - ELECTRICAL PLAN

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

NEW METERING SYSTEM CONTROL PANEL

AutoCAD SHX Text

NEW SURGE PROTECTIVE DEVICE

AutoCAD SHX Text NEW GENERATOR DOCKING STATION 1200A, 3P, 4W WITH 1200A CIRCUIT BREAKER AND SOLID STATE TRIP, START/STOP GENERATOR CONTACTS AND KIRK KEY INTERLOCK WITH EXISTING GENERATO CIRCUIT BREAKER

AutoCAD SHX Text

EXISTING

AutoCAD SHX Text

EXISTING

AutoCAD SHX Text

EXISTING

AutoCAD SHX Text

EXISTING

AutoCAD SHX Text

NEW SURGE PROTECTIVE DEVICE

AutoCAD SHX Text KEY NOTES: EXISTING FEEDERS TO BE REPLACED WITH NEW. EXISTING UNDERGROUND CONDUITS TO REMAIN EXISTING EQUIPMENT BRANCH (EB) TO BE SEPARATED FROM LIFE SAFETY (LS) AND CRITICAL BRANCH (CB) WIRING EXISTING 4" CONDUIT WITH CONTROL WIRES. REMOVE CONTROL WIRES AND REROUTE IN NEW 1" CONDUIT FROM GENERATOR CONTROL PANEL TO BREAKER PANEL. 3/4" C WITH GENERATOR CONTROL WIRES (10#14) FROM GENERATOR CONTROL PANEL TO GENERATOR BREAKER PANEL. RUN CONDUIT EXPOSED ON CEILING AND WALL. FIELD VERIFY EXACT WIRING EXISTING 4" CONDUITS, REMOVE EXISTING 4#500KCMIL TYPE W WIRES. PROVIDE NEW 3 SETS OF 4#444 KCMIL, 1#2G RHH/RWH-2 FLEXIBLE POWER CABLE (925 STRAND) IN EXISTING CONDUITS FROM GENERATOR ALTERNATOR TO GENERATOR CIRCUIT BREAKER. PROVIDE ADDITIONAL WIRE LUGS AT GENERATOR ALTERNATOR. PROVIDE WITH 90°C COMPRESSION LUGS AT EACH END. PROVIDEDWITH SHOO-PIN CONNECTORS. PROVIDE 3/4"C WITH NETWORK CABLING TO BMS METASYS NETWORK EQUIPMENT EXISTING DAYTANK AND PIPING TO BE REPLACED (SEE SPECIFICATIONS FOR REQUIREMENTS)

AutoCAD SHX Text

EXISTING EQUIPMENT TO BE REMOVED REFER TO NOTES FOR ADDITIONAL INFORMATION.

AutoCAD SHX Text

LEGEND

AutoCAD SHX Text

EXISTING TO REMAIN REFER TO SUMMARY OF WORK NOTES FOR ADDITIONAL INFORMATION.

AutoCAD SHX Text

NEW WORK REFER TO NOTES FOR ADDITIONAL INFORMATION.

AutoCAD SHX Text WIRING NOTES: 1. LIFE SAFETY AND CRITICAL BRANCH WIRING TO BE PHYSICALLY LIFE SAFETY AND CRITICAL BRANCH WIRING TO BE PHYSICALLY SEPARATED FROM THE NORMAL AND EQUIPMENT BRANCH WIRING.

AutoCAD SHX Text PARTIAL LEGEND (N) DENOTES PANEL ON NORMAL POWER SYSTEM DENOTES PANEL ON NORMAL POWER SYSTEM (LS) DENOTES PANEL IS ON LIFE SAFETY SYSTEM DENOTES PANEL IS ON LIFE SAFETY SYSTEM (CB) DENOTES PANEL IS ON CRITICAL BRANCH SYSTEM DENOTES PANEL IS ON CRITICAL BRANCH SYSTEM (EB) DENOTES PANEL IS ON EQUIPMENT BRANCH SYSTEM DENOTES PANEL IS ON EQUIPMENT BRANCH SYSTEM (EM) DENOTES EQUIPMENT ON EMERGENCY SYSTEMDENOTES EQUIPMENT ON EMERGENCY SYSTEM

AutoCAD SHX Text LIGHTNING PROTECTION SYSTEM NOTES: 1. DRAWINGS ARE PROVIDED AS GUIDES FOR LIGHTNING DRAWINGS ARE PROVIDED AS GUIDES FOR LIGHTNING PROTECT SYSTEM DESIGNER FINAL DRAWINGS BY LIGHTNING PROTECTION SYSTEM DESIGN SHALL BE PROVIDED AFTER FIELD VERIFICATION OF SITE CONDITIONS. LIGHTNING SYSTEM DESIGNER SHALL PROVIDE DRAWING AS PART OF SHOP DRAWING SUBMITTAL, REFER TO SPECIFICATIONS. 2. THE LIGHTNING PROTECTION SYSTEM SHALL BE THE LIGHTNING PROTECTION SYSTEM SHALL BE DESIGNED PER NFPA 780 AND U.L. MASTER LABELED. LIGHTNING PROTECTION SYSTEM SHALL BE UL TESTED & INSPECTED. 3. ALL GROUND RODS/SYSTEMS SHOULD MEET THE MIN ALL GROUND RODS/SYSTEMS SHOULD MEET THE MIN RESISTANCE AND TESTED TO MEET NFPA70/780 FOR A LIGHTNING PROTECTION SYSTEM. THE SYSTEM SHALL BE TESTED PRIOR TO THE UL INSPECTION. 4. REFER TO ONE-LINE DIAGRAMS FOR SURGE PROTECTIVE REFER TO ONE-LINE DIAGRAMS FOR SURGE PROTECTIVE DEVICES (SPD) IS BEING INSTALLED AS PART OF THIS PROJECT. THE SPD MAYBE LOCATED IN THE GENERATOR BUILDING LOCATED NEXT TO THE BUILDING.

AutoCAD SHX Text

WP/(NFMA 3R)

AutoCAD SHX Text

SHADING DENOTES AREA OF BUILDING PROTECTED BY DRY SUSPENSION SYSTEM

AutoCAD SHX Text

TAP EXISTING SWITCHBOARD IN APPROVED MANOR

AutoCAD SHX Text NOTE: FURNISH AND INSTALL NEW EX FIXTURES FOR ALL 3 ROOMS. REPLACE EXISTING FIXTURES IN SAME LOCATION. EXTENDED WIRING 2#12, 1#12G, 3/4"C AHEAD OF LOCAL SWITCHING. EXACT LOCATION BY COR

AutoCAD SHX Text

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 2'

AutoCAD SHX Text

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 2'

AutoCAD SHX Text 3#2/0, 1#4G, 2"C

AutoCAD SHX Text

TO BUILDING 01 ELEVATOR CIRCUIT BREAKER

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

ADDENDUM ITEMS

AutoCAD SHX Text 10/24/23

VHANHMZajacN Polygon

01WA-EP101

BUILDING NO. 1WA - ELECTRICAL

PLAN 01WA

W.H.H. E.J.D.

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h

CONSTRUCTION

DOCUMENTS

MAY 30, 2023

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

ELECTRICAL DISTRIBUTION

SYSTEM UPGRADE - PHASE 2

VA CWM

631-18-003

Project Director

MAY 30, 2023Revisions: Date:

© Copyright 2020 DuBois & King Inc.

85 MAIN STREET

SPRINGFIELD, VT 05156

TEL: (802) 591-4326

FAX: (866) 783-7101

www.dubois-king.com

I:\ 5\

V

AM

C

E le c D is t P ha se

3\ D ra w in gs

\E le ct ric al \0

1W A-

EP

BU

IL

D

IN

G

N O

. 1 W

A

- E

LE

C

TR

IC

AL

P

LA

N

.d w g

1/ 2/

:1

6:

P M

631-25-001 Only in scope work

AutoCAD SHX Text

EXISTING 300KW GENERATOR

AutoCAD SHX Text

EXISTING SWBD 1WA-MDP

AutoCAD SHX Text

EXISTING SWBD E1WA-MDP

AutoCAD SHX Text

EXISTING ATS#1(LS) TO BE REMOVED

AutoCAD SHX Text

EXISTING ATS#3(EB) TO BE REMOVED

AutoCAD SHX Text

EXISTING ATS#2(CB) TO BE REMOVED

AutoCAD SHX Text

EXISTING PANEL E1WA-EB TO BE REMOVED

AutoCAD SHX Text

EXISTING PANEL E1WA-CB

AutoCAD SHX Text

EXISTING PANEL E1WA-LS

AutoCAD SHX Text

EXISTING PANEL E1WA-LESH

AutoCAD SHX Text

EXISTING TRANSFORMER MTD HIGH ON WALL

AutoCAD SHX Text

EXISTING WIREWAY TO BE REMOVED

AutoCAD SHX Text

EXISTING WIRE TRENCH WITH STEEL COVERS

AutoCAD SHX Text

EXISTING GENERATOR MAIN BREAKER

AutoCAD SHX Text NOTES: 1. EXISTING INTERIOR AND EXTERIOR LIGHTS TO BE EXISTING INTERIOR AND EXTERIOR LIGHTS TO BE REMOVED AND REPLACED WITH NEW LIGHTS. FIELD VERIFY LOCATION AND QUANTITY. EXISTING WIRING AND CONTROLS TO REMAIN. EXIT SIGNS TO REMAIN.

AutoCAD SHX Text

3"C WITH WIRES TO BUILDING NO. 1

AutoCAD SHX Text

3/4"C TO HVAC UNIT

AutoCAD SHX Text

CONDUITS TO BE RELOCATED FOR EGRESS PATH

AutoCAD SHX Text

BUILDING NO. 1 WALL

AutoCAD SHX Text

EXISTING MECHANICAL PIPING TO BE RELOCATED REFER TO MECHANICAL DRAWINGS

AutoCAD SHX Text RELOCATE EXISTING THERMOSTATS, TELEPHONE AND CONDUITS IN THIS AREA FOR DOOR AND NEW EQUIPMENT

AutoCAD SHX Text

EXISTING GENERATOR MAIN BREAKER

AutoCAD SHX Text

EXISTING 300KW GENERATOR

AutoCAD SHX Text

EXISTING SWBD 1WA-MDP

AutoCAD SHX Text

EXISTING SWBD E1WA-MDP

AutoCAD SHX Text

EXISTING PANEL E1WA-CB

AutoCAD SHX Text

EXISTING PANEL E1WA-LS

AutoCAD SHX Text

EXISTING PANEL E1WA-LESH

AutoCAD SHX Text

EXISTING TRANSFORMER MTD HIGH ON WALL

AutoCAD SHX Text

NEW ISOLATION BYPASS AUTOMATIC TRANSFER SWITCH E1WA-CB-ATS

AutoCAD SHX Text

NEW PANEL E1WA-EB

AutoCAD SHX Text

NEW ISOLATION BYPASS AUTOMATIC TRANSFER SWITCH E1WA-LS-ATS

AutoCAD SHX Text

NEW ISOLATION BYPASS AUTOMATIC TRANSFER SWITCH E1WA-EB-ATS

AutoCAD SHX Text

NEW METERING PANEL

AutoCAD SHX Text

NEW SURGE PROTECTIVE DEVICE

AutoCAD SHX Text

NEW SURGE PROTECTIVE DEVICE

AutoCAD SHX Text DUCT BANKS TO BUILDING No. 1 WEST ELECTRIC VAULTS

AutoCAD SHX Text

E1WA-LESH-16

AutoCAD SHX Text

EXISTING BMS METASYS NETWORK EQUIPMENT

AutoCAD SHX Text

E1WA- LESH-30

AutoCAD SHX Text

PROVIDE NEW GENERATOR WIRING MONITORING SYSTEM

AutoCAD SHX Text NEW LIGHTS TO REPLACE EXISTING INTERIOR LIGHTS IN INDICATED AND EXTENDED LOCATIONS (TYP.) UTILIZE EXISTING WIRING 3/4"C WITH 2#12, 1#12G

AutoCAD SHX Text NEW LIGHTS TO REPLACE EXISTING EXTERIOR LIGHTS IN EXISTING LOCATIONS (TYP.) UTILIZE EXISTING WIRING

AutoCAD SHX Text

RELOCATED 3" RGS CONDUIT. EXTEND WIRE AND CONDUIT TO SOURCE

AutoCAD SHX Text

RELOCATED 3/4"C RGS CONDUIT. EXTEND WIRE AND CONDUIT

AutoCAD SHX Text

E1WA- LESH-5

AutoCAD SHX Text DRY SUPPRESSION SYSTEM AND CONTROLS, AREA INDICATED BY SHADING DENOTES AREA TO BE PROTECTED BY DRY AGENT SUPPRESSION SYSTEM (REFER TO SPEC 21 2200)

AutoCAD SHX Text

NEW GENERATOR DOCKING STATION PER REQUIREMENTS ON NEC ARTICLE 700.3 (F)

AutoCAD SHX Text

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

BUILDING 01WA ONE-LINE

AutoCAD SHX Text

FROM TRANSFORMER TR14

AutoCAD SHX Text

TO BUILDING 01 PANEL 1WB-7

AutoCAD SHX Text

EXISTING BUILDING 1WA 300KW (1050A) GENERATOR

AutoCAD SHX Text

EXISTING E1WA-GEN. MB 120/208 3 /4W1200A/3P

AutoCAD SHX Text

BUILDING 01WA

AutoCAD SHX Text

EXISTING SWBD E1WA-MDP 120/208 3 /4W1000A/3P

AutoCAD SHX Text

E1WA-LS

AutoCAD SHX Text 120/208

AutoCAD SHX Text 3%%c, 4W

AutoCAD SHX Text 400A 3P

AutoCAD SHX Text

E1WA-CB

AutoCAD SHX Text 120/208

AutoCAD SHX Text 3%%c, 4W

AutoCAD SHX Text 400A 3P

AutoCAD SHX Text

E1WA-LESH

AutoCAD SHX Text 120/208

AutoCAD SHX Text 3%%c, 4W

AutoCAD SHX Text 125A 3P

AutoCAD SHX Text

EXISTING SWBD 1WA-MDP 120/208 3 /4W2500A/3P

AutoCAD SHX Text

TO BUILDING 01 E1W-LS

AutoCAD SHX Text

TO BUILDING 01 PANEL E1W-EB

AutoCAD SHX Text

TO BUILDING 01 PANEL E1W-102

AutoCAD SHX Text

TO BUILDING 01 1W-ATS#4

AutoCAD SHX Text

TO BUILDING 01 1W-ATS#4

AutoCAD SHX Text 4#1/0, 1#6G, 1-1/2"C

AutoCAD SHX Text

(6) 4#600KCMIL, 1#2G, 3-1/2"C

AutoCAD SHX Text 4#3/0, 1#6G, 2"C

AutoCAD SHX Text 4#2, 1#6G, 1-1/4"C

AutoCAD SHX Text

TO BUILDING 01 PANEL E1W-CB

AutoCAD SHX Text 4#1/0, 1#6G, 1-1/2"C

AutoCAD SHX Text

TO BUILDING 01 CT SCAN DISC.

AutoCAD SHX Text

4#350KCMIL, 1#3G, 3"C

AutoCAD SHX Text

TO BUILDING 01 PANEL E1W-B2

AutoCAD SHX Text 4#4/0, 1#4G, 2"C

AutoCAD SHX Text

(2) 4#600KCMIL, 1#2G, 3-1/2"C

AutoCAD SHX Text

(2) 4#300KCMIL, 1#3G, 3"C

AutoCAD SHX Text

TO BUILDING 01 PANEL 1WB-105

AutoCAD SHX Text

TO BUILDING 01 E1W-103

AutoCAD SHX Text 4#1/0, 1#6G, 1-1/2"C

AutoCAD SHX Text

TO BUILDING 01 PANEL E1WB-12

AutoCAD SHX Text 4#4/0, 1#4G, 2"C

AutoCAD SHX Text 4#4/0, 1#4G, 2-1/2"C

AutoCAD SHX Text

TO BUILDING 01 PANEL 1W-105

AutoCAD SHX Text

4#500KCMIL, 1#3G, 3"C

AutoCAD SHX Text 4#4/0, 1#4G, 2-1/2"C

AutoCAD SHX Text

TO BUILDING 01 PANEL 1WB-6

AutoCAD SHX Text 4#4/0, 1#4G, 2-1/2"C

AutoCAD SHX Text

SCALE: 1/4" = 1'-0"

AutoCAD SHX Text

BUILDING 1WA - DEMOLITION PLAN PLAN

AutoCAD SHX Text

AutoCAD SHX Text

SCALE: 1/4" = 1'-0"

AutoCAD SHX Text

BUILDING 1WA - ELECTRICAL PLAN

AutoCAD SHX Text

AutoCAD SHX Text KEY NOTES: EXISTING FEEDERS TO BE REPLACED WITH NEW EXISTING UNDERGROUND CONDUITS TO REMAIN EXISTING EQUIPMENT BRANCH (EB) TO BE SEPARATED FROM LIFE SAFETY (LS) AND CRITICAL BRANCH (CB) WIRING EXISTING 4" CONDUIT WITH CONTROL WIRES. REMOVE CONTROL WIRES AND REROUTE IN NEW 3/4" CONDUIT FROM GENERATOR CONTROL PANEL TO BREAKER PANEL. 3/4" C WITH GENERATOR CONTROL WIRES (10#14) FROM GENERATOR CONTROL PANEL TO GENERATOR BREAKER PANEL. RUN CONDUIT EXPOSED ON CEILING AND WALL. EXISTING 4" CONDUITS, REMOVE EXISTING 4#500KCMIL TYPE W WIRES. PROVIDE NEW 3 SETS OF 4#444 KCMIL, 1#2G RHH/RWH-2 FLEXIBLE POWER CABLE (925 STRAND) IN EXISTING CONDUITS FROM GENERATOR ALTERNATOR TO GENERATOR CIRCUIT BREAKER. PROVIDE ADDITIONAL WIRE LUGS AT GENERATOR ALTERNATOR. PROVIDE WITH 90°C COMPRESSION LUGS AT EACH END. PROVIDED WITH SHOO-PINCONNECTORS. PROVIDE 3/4"C WITH NETWORK CABLING TO BMS METASYS NETWORK EQUIPMENT EXISTING DAYTANK AND PIPING TO BE REPLACED (SEE SPECIFICATIONS FOR REQUIREMENTS)

AutoCAD SHX Text

ATS E1WA-LS-ATS (LS) 400A (NEW)

AutoCAD SHX Text

ATS E1WA-CB-ATS 400A (NEW)

AutoCAD SHX Text

ATS E1WA-EB-ATS 400A (NEW)

AutoCAD SHX Text

E1WA-EB

AutoCAD SHX Text 120/208

AutoCAD SHX Text 3%%c, 4W

AutoCAD SHX Text 400A 3P

AutoCAD SHX Text

(NEW)

AutoCAD SHX Text

NEW METERING SYSTEM CONTROL PANEL

AutoCAD SHX Text

NEW SURGE PROTECTIVE DEVICE

AutoCAD SHX Text

EXISTING

AutoCAD SHX Text

EXISTING

AutoCAD SHX Text

EXISTING

AutoCAD SHX Text

NEW SURGE PROTECTIVE DEVICE

AutoCAD SHX Text

TO BUILDING 01 FIRE PUMP CONTROLLER

AutoCAD SHX Text 3#4/0, 1#6G, 2"C

AutoCAD SHX Text WIRING NOTES: 1. LIFE SAFETY AND CRITICAL BRANCH WIRING TO BE PHYSICALLY LIFE SAFETY AND CRITICAL BRANCH WIRING TO BE PHYSICALLY SEPARATED FROM THE NORMAL AND EQUIPMENT BRANCH WIRING.

AutoCAD SHX Text PARTIAL LEGEND (N) DENOTES PANEL ON NORMAL POWER SYSTEM DENOTES PANEL ON NORMAL POWER SYSTEM (LS) DENOTES PANEL IS ON LIFE SAFETY SYSTEM DENOTES PANEL IS ON LIFE SAFETY SYSTEM (CB) DENOTES PANEL IS ON CRITICAL BRANCH SYSTEM DENOTES PANEL IS ON CRITICAL BRANCH SYSTEM (EB) DENOTES PANEL IS ON EQUIPMENT BRANCH SYSTEM DENOTES PANEL IS ON EQUIPMENT BRANCH SYSTEM (EM) DENOTES EQUIPMENT ON EMERGENCY SYSTEMDENOTES EQUIPMENT ON EMERGENCY SYSTEM

AutoCAD SHX Text LIGHTNING PROTECTION SYSTEM NOTES: 1. DRAWINGS ARE PROVIDED AS GUIDES FOR LIGHTNING DRAWINGS ARE PROVIDED AS GUIDES FOR LIGHTNING PROTECT SYSTEM DESIGNER FINAL DRAWINGS BY LIGHTNING PROTECTION SYSTEM DESIGN SHALL BE PROVIDED AFTER FIELD VERIFICATION OF SITE CONDITIONS. LIGHTNING SYSTEM DESIGNER SHALL PROVIDE DRAWING AS PART OF SHOP DRAWING SUBMITTAL, REFER TO SPECIFICATIONS. 2. THE LIGHTNING PROTECTION SYSTEM SHALL BE DESIGNED THE LIGHTNING PROTECTION SYSTEM SHALL BE DESIGNED PER NFPA 780 AND U.L. MASTER LABELED. LIGHTNING PROTECTION SYSTEM SHALL BE UL TESTED & INSPECTED. 3. ALL GROUND RODS/SYSTEMS SHOULD MEET THE MIN ALL GROUND RODS/SYSTEMS SHOULD MEET THE MIN RESISTANCE AND TESTED TO MEET NFPA70/780 FOR A LIGHTNING PROTECTION SYSTEM. THE SYSTEM SHALL BE TESTED PRIOR TO THE UL INSPECTION. 4. REFER TO ONE-LINE DIAGRAMS FOR SURGE PROTECTIVE REFER TO ONE-LINE DIAGRAMS FOR SURGE PROTECTIVE DEVICES (SPD) IS BEING INSTALLED AS PART OF THIS PROJECT. THE SPD MAYBE LOCATED IN THE GENERATOR BUILDING LOCATED NEXT TO THE BUILDING.

AutoCAD SHX Text NOTE: FURNISH AND INSTALL NEW EX FIXTURES FOR ALL 3 ROOMS. REPLACE EXISTING FIXTURES IN SAME LOCATION. EXTENDED WIRING 2#12, 1#12G, 3/4"C AHEAD OF LOCAL SWITCHING. EXACT LOCATION BY COR

AutoCAD SHX Text

EXISTING EQUIPMENT TO BE REMOVED REFER TO NOTES FOR ADDITIONAL INFORMATION.

AutoCAD SHX Text

LEGEND

AutoCAD SHX Text

EXISTING TO REMAIN REFER TO SUMMARY OF WORK NOTES FOR ADDITIONAL INFORMATION.

AutoCAD SHX Text

NEW WORK REFER TO NOTES FOR ADDITIONAL INFORMATION.

AutoCAD SHX Text

SHADING DENOTES AREA OF BUILDING PROTECTED BY DRY SUSPENSION SYSTEM

AutoCAD SHX Text NEW GENERATOR DOCKING STATION 1200A, 3P, 4W WITH 1200A CIRCUIT BREAKER AND SOLID STATE TRIP, START/STOP GENERATOR CONTACTS AND KIRK KEY INTERLOCK WITH EXISTING GENERATO CIRCUIT BREAKER

AutoCAD SHX Text

WP/(NFMA 3R)

AutoCAD SHX Text

TAP EXISTING SWITCHBOARD IN APPROVED MANOR

AutoCAD SHX Text

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 2'

AutoCAD SHX Text

AutoCAD SHX Text 4'

AutoCAD SHX Text 8'

AutoCAD SHX Text 2'

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

FROM BUILDING 01 PANEL E1S-DP

AutoCAD SHX Text

(2) 4#500KCMIL, 1#3G, 3"C

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

ADDENDUM ITEMS

AutoCAD SHX Text 10/24/23

VHANHMZajacN Polygon

E

LE

V A T O R P

IT P

IT

E

LE

V A T O R

D N

D N

UP

U P

U P

U P

U P

U P

D N

D N

U P

U P

E

LE

V A T O R P

IT P

IT

E

LE

V A T O R

D N

D N

UP

U P

U P

U P

U P

U P

D N

D N

U P

U P

ELECTRIC

ROOM

B244

ELECTRIC

ROOM

B015

Phone

ROOM

B108A

WATER

SERVICE

B152

WATER

SERVICE

B018

WATER

SERVICE

B245

ELECTRIC

ROOM

B129A

WATER

SERVICE

B106A

WATER

SERVICE

B112

BUILDING 1 basement for reference and location of water service and electrical service to be bonded

3/32" = 1'0"

631-25-001 Building 1 Lightning Protection Technical Questions
01EA-EP101
01WA-EP101
631-25-001 Building 1 Lightning Protection Technical Questions
264313 - SURGE PROTECTIVE DEVICES
water service B1
Sheets and Views
water service B1-Layout2
water service B1
Sheets and Views
water service B1-Layout2

File details come from the government source that posted it. Updated .