6-JF26-018-IFB PLANS 20260323-24187 COTTONWOOD AUD.pdf
PDF 4 MB Posted
- Solicitation number
- JF26-018-IFB
- Issued by
- Salt Lake County, Utah
About this file
This is an Invitation for Bids (IFB) electrical plan document issued by Granite School District (GSD) for an Auditorium Lighting System Upgrade at Cottonwood High School, located at 5717 South 1300 East, Murray, Utah 84121. The project seeks bids from responsive and responsible General Electrical Contractors (E200) to replace the auditorium house lighting system in accordance with the project manual, specifications, and attached electrical drawings. The comprehensive electrical plan package includes symbols and schedules, overall electrical plans, demolition plans for the main level, upper level, and basement level, new electrical plans for each level, one-line diagrams, panelboard schedules, and detailed electrical diagrams. The project encompasses the installation of new lighting fixtures, control systems, emergency lighting, relay panels (SRP1-SRP5), a new distribution panel (DMA), connector strips with outlet boxes, network infrastructure, and associated conduit and wiring throughout the three-level auditorium facility. A pre-bid meeting is required for all bidders. Award recommendation is anticipated at the May 5, 2026 Granite School District Board meeting, with final award to be issued following board approval. The contract will be awarded to the lowest cost responsive and responsible vendor.
The electrical plan documents specify detailed conductor and conduit scheduling for parallel runs, transformer specifications, panelboard configurations, and load calculations to ensure voltage drop compliance. The project involves coordination with mechanical and ceiling contractors, reuse of existing conduit and equipment where possible, removal and replacement of existing fixtures and control systems, and compliance with NEC code requirements. Existing electrical systems including transformers, panels, disconnect switches, and wire ways are identified for retention or removal based on project requirements. The district has established specific mounting heights, device locations, and safety protocols including fire-rated penetration sealing and coordination with door hardware and furniture suppliers. Funding sources and final contract pricing terms are subject to board approval at the May 5, 2026 meeting.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
GRANITE SCHOOL DISTRICT
2500 SOUTH STATE ST.
SALT LAKE CITY, UTAH 84115
AUDITORIUM LIGHTING
SYSTEM UPGRADE
COTTONWOOD HIGH SCHOOL
5717 South 1300 East
MURRAY, UTAH 84121
VICINITY PLAN
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
SYMBOL DESCRIPTION
MOUNTING
HEIGHT NOTES SYMBOL DESCRIPTION
MOUNTING
HEIGHT NOTES
ONE CIRCUIT, HOME RUN TO PANEL
TWO CIRCUIT, HOME RUN TO PANEL
THREE CIRCUIT, HOME RUN TO PANEL
CONDUIT RUN CONCEALED IN WALL OR CEILING
CONDUIT RUN CONCEALED IN FLOOR OR GROUND
CONDUIT UP
CONDUIT DOWN
GENERAL
CONDUIT STUB LOCATION CONDUIT
CAP
CONDUIT/CIRCUIT CONTINUATION
JUNCTION BOX ('F' IN FLOOR) AS NOTED
LIGHT FIXTURE (LETTER DESIGNATES TYPE)X
X X
EQUIPMENT NUMBER
842 ARCHITECTURAL ROOM NUMBER
DEVICE/EQUIPMENT (TEXT DESIGNATES TYPE) SEE SCHEDULEX
DEVICE/EQUIPMENT (TEXT DESIGNATES TYPE) SEE SCHEDULE/LEGENDX
EQUIPMENT PANEL SEE DRAWINGS +72" 6.
CABLE TRAY (BASKET/LADDER) AS NOTED
GROUND BUS BAR +18" 6.
CEILING LIGHT FIXTURE CEILING 1.
WALL LIGHT FIXTURE AS NOTED 1.
RECESSED DOWNLIGHT FIXTURE CEILING 1.
LIGHT FIXTURE AS NOTED 1.
BOLARD BASE
CONCRETE 1.
STEP LIGHT FIXTURE AS NOTED 1.
LIGHTING
EGRESS LIGHT FIXTURE AS NOTED 1.
BASEAREA LIGHT POLE AND FIXTURE CONCRETE 1., SEE DIAGRAM
RECESSED WALL-WASH DOWNLIGHT FIXTURE CEILING 1.
IN-GRADE LIGHT FIXTURE 1.BASE
CONCRETE
FLOOD OR TRACK FIXTURE AS NOTED 1.
CEILING / WALL MOUNTED EXIT LIGHT 1. 3. 8.
CEILING/
AS NOTED
EMERGENCY LIGHT FIXTURE 1.AS NOTED
COMBO EXIT / EMERGENCY LIGHT FIXTURE 1.AS NOTED
POWER PACK SEE DIAGRAM, SPEC.CEILING
ABOVE
POWER PACK SEE DIAGRAM, SPEC.CEILING
ABOVE
CEILING
ABOVE
(SUBSCRIPT INDICATES NUMBER OF RELAYS)
DIGITAL ROOM CONTROLLER
SEE DIAGRAM. SPEC.
EMERGENCY LIGHTING CONTROL UNIT SEE DIAGRAM, SPEC.CEILING
ABOVE
SINGLE POLE SWITCH +46" 2. 4.
THREE-WAY SWITCH 2. 4.+46"
FOUR-WAY SWITCH 2. 4.+46"
KEY OPERATED SWITCH 2. 4.+46"
SWITCH WITH PILOT LIGHT 2. 4.+46"
VARIABLE INTENSITY SWITCH 2. 4.+46"
TIMER SWITCH 2. 4.+46"
MOMENTARY CONTACT SWITCHMOMENTARY CONTACT SWITCH 2. 4.+46"
LOW VOLTAGE WALLSTATION (SUBSCRIPT INDICATES
CONFIGURATION & CONTROL SEQUENCE) DIAGRAM, SPEC.
2., SEE+46"X
DUAL TECH CEILING MOUNTED OCCUPANCY SENSOR
(PROVIDE WITH ALL PP AND ROOM CONTROLLERS) DIAGRAM, SPEC.
SEECEILING
DUAL TECH WALL MOUNTED OCCUPANCY SENSOR
(SUBSCIPT D = DIMMING AND DAY-LIGHT CONTROL) DIAGRAM, SPEC.
2. 4., SEE+46"
PHOTO-ELECTRIC CONTROL
(LOCATE ON ROOF, FACE NORTH) PER MFR.
MOUNT ASAS NOTED
DIGITAL DAYLIGHT SENSOR
SEE DIAGRAM,
SPEC.CEILING
TIME CLOCK 2.+60"
RECEPTACLE SWITCH PACK
ABOVE
CEILING
DUPLEX RECEPTACLE 9.
5mA GFCI CIRCUIT BREAKER PROTECTED RECEPTACLE 13.5mA GFCI CIRCUIT BREAKER PROTECTED RECEPTACLE 13.
TOMBSTONE RECEPTACLE
POWER POLE
POWER
UPPER OUTLET
SWITCH CONTROLLEDDUPLEX RECEPTACLE 2. 9.
+18" OR
AS NOTED
SIMPLEX RECEPTACLE 2. 9.
+18" OR
AS NOTED
TAMPER-PROOF RECEPTACLE 2. 9.
+18" OR
AS NOTED
DUPLEX RECEPTACLE WITH USB OUTLET 2. 9.
+18" OR
AS NOTED
WEATHERPROOF RECEPTACLE 2. 9.AS NOTED
+24" OR
ISOLATED GROUND RECEPTACLE 2. 9.
+18" OR
AS NOTED
GROUND FAULT INTERRUPTER DUPLEX RECEPTACLE 2. 9.
+18" OR
AS NOTED
GROUND FAULT INTERRUPTER FOURPLEX RECEPTACLE 2. 9.
+18" OR
AS NOTED
TVSS PROTECTED RECEPTACLE 2. 9.
+18" OR
AS NOTED
RECEPTACLE SWITCH PACK
ABOVE
CEILING
FLAT PANEL DISPLAY WALL BOX, TVSS RECEPT.,
SPEC. 26 2726
SEE DIAGRAM &
DATA AND OTHER DEVICES, REFER TO DIAGRAMS AS NOTED
CEILING PROJECTION SYSTEM CEILING BOX AND SPEC.
SEE DIAGRAMABOVE
CEILING
CLOCK OUTLET 2.+90"
PLUGMOLD/SURFACE RACEWAY 2. SEE SPEC.
+46" OR
AS NOTED
DUPLEX RECEPTACLE 2. 9. 11.
+18" OR
AS NOTED
DUPLEX RECEPTACLE EMERGENCY POWER (RED) 2. 9. 11.
+18" OR
AS NOTED
FOURPLEX RECEPTACLE 2. 9. 11.
+18" OR
AS NOTED
FOURPLEX RECEPTACLE EMERGENCY POWER (RED) 2. 9. 11.
+18" OR
AS NOTED
CORD DROP SEE DIAGRAM
DOOR BELL CHIME +90" 2.
FLOOR BOX - SEE SCHEDULE SEE DIAGRAM, SPEC. FLOOR
POKE THRU - SEE SCHEDULE SEE DIAGRAM, SPEC. FLOOR
MOTOR OUTLET
TO SUIT
EQUIP.
PUSHBUTTON 2.+46"
NON-FUSED DISCONNECT SWITCH 5. 6.+60"
FUSED DISCONNECT SWITCH 5. 6.+60"
BREAKER DISCONNECT SWITCH 5. 6.+60"
MANUAL STARTER THERMAL OVERLOAD SWITCH WITH PILOT LIGHT 2.+46"
MAGNETIC STARTER 6. 7.+60"
MAGNETIC STARTER / DISCONNECT COMBINATION +60" 6. 7.
VARIABLE FREQUENCY DRIVE +66" 6.
PANEL BOARD +72" 6.
MAIN DISTRIBUTION PANEL
UTILITY METER +72" 6.
CORD REEL SEE DIAGRAM
CONTROLLED DUPLEX RECEPTACLE 2. 9.
+18" OR
AS NOTED
CONTROLLED FOURPLEX RECEPTACLE 2. 9.
+18" OR
AS NOTED
SPECIAL PURPOSE OUTLET 2. 10. W/CAP.+18" OR
AS NOTED
TELECOMMUNICATIONS
WALL PHONE 2.W
+60" OR
AS NOTED
DATA OUTLET , ONE CABLE 2. 9. 11.+18" OR
AS NOTED
DATA OUTLET, TWO CABLES 2. 9. 11.+18" OR
AS NOTED
DATA OUTLET, THREE CABLES 2. 9. 11.+18" OR
AS NOTED
DATA OUTLET , "X" INDICATES QUANTITYX 2. 9. 11.+18" OR
AS NOTED
DATA OUTLET , CEILING AS NOTED
TELEVISION OUTLET
+18" OR
AS NOTED
2. 9. 11.
TELEPHONE TERMINAL BOARD
EQUIPMENT CEILING RACK CEILING
EQUIPMENT 4-POST RACK/CABINET 18. SEE SPEC.AS NOTED
EQUIPMENT 2-POST 18. SEE SPEC.AS NOTED
SPLITTER
ABOVE
CEILING
VIA
ABOVE
CEILING
FIBER BDA
ABOVE
CEILING
ANTENNAXX CEILINGPS = PUBLIC SERVICE
COM = CELLULAR/COMMERCIAL
WIRELESS ACCESS POINT, TWO CABLES 11.
SOLID = WALL, DASHED = CEILING
SYMBOL SCHEDULE
1. SEE FIXTURE SCHEDULE FOR TYPE, MOUNTING AND WATTAGE.
4. SUBSCRIPT INDICATES FIXTURES TO BE CONTROLLED.
8. DOUBLE ARROWS INDICATE A DOUBLE FACE UNIT.
3. REFER TO DRAWINGS FOR DIRECTIONAL ARROWS.
STANDARD MOUNTING HEIGHT UNLESS OTHERWISE NOTED ON PLANS
11. SOLID BOX AROUND DEVICE INDICATES INSTALLED IN FLOOR,
6. HEIGHT MEASURED TO TOP OF THE BOX FROM FINISHED FLOOR.
5. NEMA TYPE 'ND' NON-FUSED UNLESS NOTED 'F' (FUSED). USE 'HD' 480V.
2. HEIGHT MEASURED TO CENTER LINE OF THE BOX FROM THE FINISHED FLOOR.
10. SUBSCRIPT INDICATES NEMA CONFIGURATION.
* TYPICAL SYMBOL SCHEDULE. SOME SYMBOLS MAY NOT BE USED IN THIS SET OF DRAWINGS.
12. COORDINATE WITH DOOR HARDWARE SUPPLIER.
7. PROVIDE H.O.A. AND S.S. PUSHBUTTONS AS REQUIRED.
13. FOR WATER COOLER LOCATION, SEE DIAGRAM R002. FOR ALL OTHER LOCATIONS
MOUNT AT +16" TO BOTTOM OF THE BOX FROM FINISHED FLOOR, OR AS NOTED.
9. DEVICES NOTED WITH AN "A" ADJACENT TO IT INDICATES TO COORDINATE
14. ARROWS SHOWN ON DEVICE INDICATE THE SENSOR AIMING LOCATION.
15. CAMERA NUMBERS ARE SHOWN INSIDE THE CAMERA SYMBOL. CAMERA TYPES ARE
16. MOUNT ON TRACK OF OVERHEAD DOOR 6" FROM TOP OF DOOR UNLESS OVERHEAD
17. INSTALL DEVICES PER MANUFACTURER'S INSTALLATION INSTRUCTIONS.
SHOWN IN CAMERA TAGS.
DOOR IS ROLL UP DOOR, THEN MOUNT PER MANUFACTURER'S INSTRUCTIONS.
DASHED BOX AROUND DEVICE INDICATES INSTALLED IN CEILING.
NOTES:
18. DASHED LINE INDICATES EQUIPMENT CLEARANCES. ARROW DENOTES FRONT OF RANK.
19. SPEAKER TO BE MOUNTED IN HORIZONTAL POSITION.
20. MOUNTING HEIGHTS IS TO BOTTOM OF DISPLAY.
WITH MILLWORK SHOP DRAWINGS AND ELEVATIONS FOR HEIGHT.
GENERAL NOTES
1. CONSULT ARCHITECTURAL REFLECTED CEILING PLANS FOR EXACT LOCATION OF ALL LIGHTING FIXTURES.
2. VERIFY ALL EQUIPMENT DIMENSIONS AND LOCATIONS BEFORE BEGINNING ROUGH IN. CONSULT ALL APPLICABLE CONTRACT DRAWINGS AND SHOP DRAWINGS TO INSURE NEC CODE CLEARANCES REQUIRED AROUND ALL
ELECTRICAL EQUIPMENT.
3. CONTRACTOR SHALL VERIFY ALL ELECTRICAL LOADS (VOLTAGE, PHASE, CONNECTION REQUIREMENTS, ETC.) OF ALL EQUIPMENT FURNISHED UNDER ALL DIVISIONS, INCLUDING ALL EXISTING EQUIPMENT TO BE RE-USED. REVIEW
ALL SHOP DRAWINGS AND EXISTING EQUIPMENT BEFORE BEGINNING ROUGH IN.
4. SEE SECTION 265100 (16510) OF THE SPECIFICATION REQUIRED COORDINATION MEETINGS WITH MECHANICAL AND
CEILING CONTRACTORS.
5. SEE APPLICABLE SHOP DRAWINGS FOR ROUGH IN LOCATION OF ALL EQUIPMENT, WIRING DEVICES, ETC. WHERE APPLICABLE MOUNT ALL WIRING DEVICES ABOVE BACK SPLASH EXCEPT THOSE SERVING UNDER COUNTER
EQUIPMENT.
6. SEE SPECIFICATION FOR ENERGY SAVING LAMP AND BALLAST REQUIREMENTS.
7. FINISHES OF ALL LIGHT FIXTURES SHALL BE AS SELECTED BY ARCHITECT.
8. THE ELECTRICAL CONTRACTOR SHALL NOTIFY AND COOPERATE WITH THE MECHANICAL CONTRACTOR SUCH THAT NO PIPING, DUCTS, OR EQUIPMENT FOREIGN TO THE OPERATION OF THE ELECTRICAL EQUIPMENT SHALL BE PERMITTED TO BE INSTALLED IN, ENTER OR PASS THRU ELECTRICAL ROOMS OR SPACES, OR ABOVE OR BELOW
ELECTRICAL EQUIPMENT IN OTHER AREAS.
9. ELECTRICAL BOXES SHALL NOT BE LOCATED IN MASONRY COLUMNS IN BRICK WALLS OR IN GROUTED CELLS
ADJACENT TO OPENINGS. COORDINATE LOCATION OF BOXES WITH MASONRY CONTRACTOR.
10. ALL PENETRATIONS OF FIRE RATED FLOORS, WALLS, AND CEILINGS SHALL BE SEALED WITH APPROVED MATERIAL
TO MAINTAIN FIRE RATING OF SURFACE PENETRATED.
11. CONTRACTOR SHALL VERIFY FURNITURE LAYOUT PRIOR TO ANY FLOORBOX OR POKE-THRU INSTALLATION.
COORDINATE EXACT LOCATION OF FLOOR BOX OR POKE-THRU WITH OWNER AND FURNITURE PROVIDER PRIOR
TO ROUGH-IN.
12. CIRCUITS EXTENDING OVER 70' FOR 120 VOLT AND 115' FOR 277 VOLT 20 AMP CIRCUITS SHALL BE RUN WITH
CONDUCTORS PER TABLE BELOW.
A. THESE ARE BASED ON MAXIMUM LENGTH OF CIRCUIT.
B. PERFORM VOLTAGE DROP CALCULATIONS AND PROVIDE CONDUCTOR SIZE TO KEEP BRANCH CIRCUIT
VOLTAGE DROP LESS THAN 3% WITH A 15 AMP LOAD.
C. CONTRACTOR SHALL ENSURE THAT THE INSTALLATION OF EACH BRANCH CIRCUIT STAYS WITHIN 3% VOLTAGE DROP FOR A 15 AMP LOAD. IF NECESSARY, CONTRACTOR SHALL INCREASE WIRE AND CONDUIT
SIZE TO MEET THE STANDARD AT NO ADDITIONAL COST TO OWNER.
MAXIMUM LENGTH
<70 MIN. #12 AWG
70 - 115
115 - 170
170 - 270
20 AMP MINIMUM BRANCH CIRCUIT CONDUCTOR SIZING
BRANCH CIRCUIT VOLTAGE
CONDUCTOR LENGTH (FT) 120 VOLT 277 VOLT
271 - 380
>380
MIN. #12 AWG
MIN. #10 AWG MIN. #12 AWG
MIN. #8 AWG MIN. #10 AWG
MIN. #6 AWG MIN. #8 AWG
NOTE B MIN. #8 AWG
NOTE B NOTE B
1. COORDINATE ALL NEW ELECTRICAL EQUIPMENT REQUIREMENTS AND MAKE CONNECTION TO EXISTING SYSTEMS. THIS INCLUDES LIGHTING, POWER, SIGNAL, RACEWAY AND OTHER SYSTEMS INCLUDED
UNDER DIVISION 26 (16).
2. RELOCATE, REWIRE AND/OR RECONNECT EXISTING ELECTRICAL DEVICES AND/OR EQUIPMENT THAT
FOR ANY REASON OBSTRUCTS CONSTRUCTION.
3. CONCEAL ALL RACEWAY AND WIRING IN EXISTING WALLS, CEILINGS, FLOORS, ETC. EXCEPT WHERE THE USE OF SURFACE METAL RACEWAYS (E.G. WIRE MOLD) IS INDICATED ON DRAWINGS OR IN SPEC.
4. LEAVE ALL EXISTING EQUIPMENT, IN PORTIONS OF THE BUILDING NOT BEING REMODELED, IN WORKING CONDITION. RESTORE ALL INTERRUPTED BRANCH CIRCUITS, FEEDERS, ETC. TO WORKING
CONDITION.
5. EXISTING RACEWAYS MAY BE REUSED (IN PLACE) WHERE POSSIBLE, AND WHERE IN COMPLIANCE WITH
THE SPECIFICATIONS AND THE INTENT OF THE CONTRACT DOCUMENTS. INSURE INTEGRITY OF
EXISTING RACEWAY BEFORE REUSE.
6. REMOVE ALL RACEWAYS, CONDUCTORS, BOXES, DEVICES, EQUIPMENT, ETC. THAT ARE NOT TO BE
REUSED.
7. REMOVE EXISTING LIGHT FIXTURES WHICH ARE NOT TO BE REUSED, PLACE IN CARTON, LABEL APPROPRIATELY, AND RETURN TO OWNER, OR PROPERLY DISPOSE OF FIXTURES THAT THE OWNER
CHOOSES NOT TO KEEP.
8. DO NOT PENETRATE STRUCTURAL ELEMENTS OF FLOORS, WALLS, CEILINGS, ROOFS, ETC.
9. DISCONNECT AND RECONNECT ANY/ALL FIXTURES, DEVICES, EQUIPMENT, ETC. REQUIRED FOR
PROPER COMPLETION OF THE WORK.
DEMOLITION NOTES
E100 SYMBOLS, SCHEDULES AND NOTES
E101 ELECTRICAL PLAN - OVERALL
E201 ELECTRICAL DEMOLITION PLAN - AUDITORIUM MAIN LEVEL
E202 ELECTRICAL DEMOLITION PLAN - AUDITORIUM UPPER LEVEL
E203 ELECTRICAL DEMOLITION PLAN - AUDITORIUM BASEMENT LEVEL
E301 ELECTRICAL PLAN - AUDITORIUM MAIN LEVEL
E302 ELECTRICAL PLAN - AUDITORIUM UPPER LEVEL
E303 ELECTRICAL PLAN - AUDITORIUM BASEMENT LEVEL
E401 ONE-LINE DIAGRAM
E402 PANELBOARD SCHEDULES
E501 ELECTRICAL DIAGRAMS
E502 ELECTRICAL DIAGRAMS
INDEX OF ELECTRICAL DRAWINGS
G
SD
C O
TT
O
N W
O O
D H
IG
H
S C
H O
O L
AU
D
IT
O
R
IU
M L
IG
H
TI
N
G U
PG
R
AD
E
S
E, M
U R
R
AY
, U T
181 E 5600 S, Murray, UT 84107 | (801) 530-3148
E100
O
E301
E201
'DP1'
E203
E1
E2
E1E2
E2
E1
G
SD
C O
TT
O
N W
O O
D H
IG
H
S C
H O
O L
AU
D
IT
O
R
IU
M L
IG
H
TI
N
G U
PG
R
AD
E
S
E, M
U R
R
AY
, U T
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
E101
PLAN
NORTH
ELECTRICAL PLAN OVERALL
1/32" = 1'-0" 0 16' 32' 64'
E1 PROVIDE CODE SIZED PULL BOX IN FEEDER TO NEW PANEL 'AEP'. SEE ONE-LINE DIAGRAM SHEET E401 FOR
ADDITIONAL REQUIREMENTS.
E2 FEEDER FOR NEW PANEL 'AEP' ROUTED IN TUNNEL. SEE ONE-LINE DIAGRAM SHEET E401 FOR ADDITIONAL
REQUIREMENTS.
SHEET KEYNOTES
PLAN
NORTH
ELECTRICAL PLAN OVERALL TUNNEL
1" = 60'-0" 0 30' 60' 120'
E203
D17D17D17
D17
D17
D17
D17
D17
D17
D17 D17 D17
D17
D17
D17
D3
D3
D3
D3
D3
D6
D4
D1
(TYP)
D1
(TYP)
D1
(TYP)
D1
(TYP)
D1
(TYP)
D1
(TYP)
D4
D4
D7
D4 D4
D6
D3
D4D5D5D5
D5
D5
D5
D5 D5 D5
D9
D9
G
SD
C O
TT
O
N W
O O
D H
IG
H
S C
H O
O L
AU
D
IT
O
R
IU
M L
IG
H
TI
N
G U
PG
R
AD
E
S
E, M
U R
R
AY
, U T
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
E201
D1 REMOVE EXISTING FIXTURE AND DISCARD. MAINTAIN EXITING CONDUIT AND WIRING TO BE REUSED WITH NEW
FIXTURE.
D2 EXISTING STAGE DISCONNECT TO REMAIN.
D3 EXISTING OUTLET BOXES TO BE REPLACED. EXISTING WIRING BACK TO DIMMING RACK TO BE REMOVED AND
RE-PULLED. EXISTING CONDUIT TO REMAIN.
D4 EXISTING LIGHTING CONTROL TO BE REPLACED. EXISTING CONDUIT RUNNING BACKSTAGE TO REMAIN.
BACKSTAGE THE CONDUIT SHALL BE RE-ROUTED TO THE NEW EQUIPMENT LOCATION. REMOVE EXISTING
WIRING.
D5 REMOVE EXISTING EXIT SIGN AND DISCARD. MAINTAIN EXISTING CONDUIT AND WIRING TO BE REUSED WITH NEW EXIT SIGN. REMOVE EMERGENCY 'BUG-EYE' FIXTURES. REMOVE AND DISCARD ANY SURFACE MOUNTED
RACEWAY TO EMERGENCY 'BUG-EYE' FIXTURES.
D6 EXISTING WALL SCONCES TO BE REPLACED LIKE FOR LIKE. MAINTAIN CONDUIT AND WIRING TO FIXTURES.
D7 EXISTING LIGHTING CONTROL BOX TO BE REMOVED. EXISTING DMX AND HOUSING LIGHTING WIRING BACK TO THE BOOTH SHALL BE REMOVED. EXISTING CONDUIT TO BOOTH SHALL REMAIN AND BE REUSED FOR NEW
LIGHTING NETWORK CONNECTION.
D8 EXISTING DIMMER RACK TO BE REMOVED. ALL BRANCH CIRCUIT WIRING TO BE REMOVED. EXISTING FEEDERS
TO DIMMER RACK TO BE REMOVED. ALL EXISTING CONDUITS SHALL REMAIN AND BE REUSED.
D9 REMOVE EXISTING EMERGENCY 'BUG-EYE' FIXTURE. REMOVE ANY SURFACE MOUNTED RACEWAY.
D17 EXISTING FLOOR BOX HOUSING TO REMAIN. EXISTING FACEPLATE AND INTERIOR MOUNTING PLATE TO BE
REMOVED AND REPLACED.
D18 EXISTING DIMMER RACK FEEDER PULL BOX TO REMAIN. PULL FEEDER BACK TO PULL BOX. SEE ELECTRICAL
PLAN SHEET E301 FOR NEW REQUIREMENTS.
SHEET KEYNOTES
PLAN
NORTH
AUDITORIUM MAIN LEVEL
ELECTRICAL DEMOLITION PLAN
1/8" = 1'-0" 0 4' 8' 16'
'HF'
D1
(TYP)
D1
(TYP)
D1
(TYP)
D1
(TYP)
D1
(TYP)
D1
(TYP)
D1
(TYP)
D1
(TYP)
D1
(TYP)
D1
(TYP)
D1
(TYP)
D1
(TYP)
D1
(TYP)
D1
(TYP)
D1
(TYP)
D1
(TYP)
D1
(TYP) D1
(TYP)
D1
(TYP)
D1
(TYP)
D1
(TYP)
D1
(TYP)
D1
(TYP)
D1
(TYP)
D1
(TYP)D1
(TYP)
D1
(TYP)
D1
D1
D7
DaD8
Db
D1
D14
D14
D14
D14
D15
Db
Dc
Db
Dc
Db
Dc
Db
Dc
Db
Dc
D15D15D15D15
D9
D9
D5 D9
D5 D9
G
SD
C O
TT
O
N W
O O
D H
IG
H
S C
H O
O L
AU
D
IT
O
R
IU
M L
IG
H
TI
N
G U
PG
R
AD
E
S
E, M
U R
R
AY
, U T
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
E202
D1 REMOVE EXISTING FIXTURE AND DISCARD. MAINTAIN EXISTING EXISTING CONDUIT AND WIRING TO BE REUSED
WITH NEW FIXTURE.
D5 REMOVE EXISTING EXIT SIGN AND DISCARD. MAIN EXISTING CONDUIT AND WIRING TO BE REUSED WITH NEW EXIT SIGN. REMOVE AND DISCARD ANY SURFACE MOUNTED RACEWAY TO EMERGENCY 'BUG-EYE' FIXTURES.
REMOVE EMERGENCY 'BUG-EYE' FIXTURES.
D9 REMOVE EXISTING EMERGENCY 'BUG-EYE' FIXTURE. PROVIDE A BLANK COVER PLATE OVER JUNCTION BOX, PAINT COVER PLATE TO MATCH THE ADJACENT WALL COVER.
D14 EXISTING FRONT OF HOUSE CONNECTOR STRIPS TO BE REMOVED AND REPLACE. EXISTING CONDUITS TO
REMAIN, ALL EXISTING WIRING TO BE REMOVED BACK TO DIMMER RACK.
D15 EXISTING CONNECTOR STRIP CONNECTED TO ELECTRIC TO BE REMOVED AND REPLACED. ALL EXISTING SCHEDULE 40 PIPING SHALL BE MAINTAINED AND REUSED ON THE NEW CONNECTOR STRIPS. REPLACE ANY
DAMAGED PIPING HAS REQUIRED.
D20 EXISTING GRID IRON JUNCTION BOXED TO REMAIN. PROVIDE MULTI CABLES FROM JUNCTION BOXES TO BE
REMOVED AND REPLACED.
Da EXISTING DISCONNECT FEEDING DIMMING PANEL TO BE REMOVED. EXISTING FEEDERS TO REMAIN.
Db EXISTING GRID IRON JUNCTION BOXES TO REMAIN. REMOVE ALL EXISTING WIRING BACK TO DIMMER RACK.
Dc REMOVE EXISTING MULTI-CABLE.
SHEET KEYNOTES
PLAN
NORTH
AUDITORIUM UPPER LEVEL
ELECTRICAL DEMOLITION PLAN
E203
D1
(TYP)
D1
(TYP)
D1
(TYP)
D1
(TYP)
D1
(TYP)
D1
(TYP)
D1
(TYP)
D1
(TYP)
D11
D12
D13 D14D15
D6 D5
D4
D2
D3D10
D9
D8
D7
D9
D1
D1
G
SD
C O
TT
O
N W
O O
D H
IG
H
S C
H O
O L
AU
D
IT
O
R
IU
M L
IG
H
TI
N
G U
PG
R
AD
E
S
E, M
U R
R
AY
, U T
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
E203
D1 EXISTING MECHANICAL DUCTWORK TO REMAIN.
D2 EXISTING TRANSFORMER TO REMAIN.
D3 EXISTING FUSED DISCONNECT SERVING SOUND BOOTH DIMMING PANEL TO BE REMOVED.
D4 EXISTING FUSED DISCONNECT SERVING COMPANY SWITCH TO BE REMOVED.
D5 EXISTING FUSED DISCONNECT SERVING DIMMING PANEL TO BE REMOVED.
D6 EXISTING FUSED DISCONNECT SERVING BLACK BOX THEATER DIMMING PANEL TO BE REMOVED.
D7 EXISTING DIMMING PANEL TO BE REMOVED.
D8 EXISTING BRANCH PANEL TO BE REMOVED. TRANSFER CIRCUITS TO NEW PANEL 'DMA. SEE ELECTRICAL
ENLARGED PLAN - AUDITORIUM BASEMENT LEVEL SHEET E303.
D9 EXISTING WIRE WAYS TO REMAIN.
D10 EXISTING GUTTER TO REMAIN.
D11 EXISTING STRAND LIGHTING CONTROL PANEL TO BE REMOVED.
D12 EXISTING WIRE WAYS TO REMAIN.
D13 EXISTING COMPANY SWITCH TO REMAIN.
D14 EXISTING FUSED SWITCH SERVING PANEL 'HG' TO BE REMOVED.
D15 EXISTING PANEL 'HG' TO REMAIN.
D16 REMOVE EXISTING FIXTURE AND DISCARD. MAINTAIN EXITING CONDUIT AND WIRING TO BE REUSED WITH NEW
FIXTURE.
SHEET KEYNOTES
PLAN
NORTH
1 AUDITORIUM BASEMENT LEVEL
ELECTRICAL DEMOLITION PLAN
1/8" = 1'-0" 0 4' 8' 16'
PLAN
NORTH
3 AUDITORIUM MAIN LEVEL
ELECTRICAL DEMOLITION ENLARGED PLAN
1/4" = 1'-0" 0 2' 4' 8'
PLAN
NORTH
2 AUDITORIUM BASEMENT LEVEL
ELECTRICAL DEMOLITION ENLARGED PLAN
1/4" = 1'-0" 0 2' 4' 8'
E303
OB15OB17OB19
OB21
OB22
OB23
OB24
OB25
OB26
OB20 OB18 OB16
OB35
OB34
OB33
OB32
OB31
OB28
OB29
OB27
CS1
S1
S1
OB30
X1 X1
HS1 HS1
EM
EM
EM
EM
EM
EM
D6
SRP5-2
D6
SRP5-2
D6
SRP5-1
D6
SRP5-1
D6
SRP5-2
D6
SRP5-1
D6
SRP5-1
D6
SRP5-1
D6
SRP5-2
D6
SRP5-1
D6
SRP5-1
D6
SRP5-2
D6
SRP5-1
D6
SRP5-1
D6
SRP5-2
D6
SRP5-1
D6
SRP5-1
D6
SRP5-1D6
SRP5-1
D6
SRP5-2
D6
SRP5-1
D6
SRP5-1
D6
SRP5-1
D6
SRP5-1
D6
SRP5-2
D6
SRP5-1
D6
SRP5-2
D6
SRP5-1
D6
SRP5-2
D6
SRP5-2D6
SRP5-2
D6
SRP5-2
D6
SRP5-1
D6
SRP5-1
D6
SRP5-1
D6
SRP5-1
D6
SRP5-2
D6
SRP5-2
D6
SRP5-1
D6
SRP5-1
D6
SRP5-1
D6
SRP5-2
D6
SRP5-2
D6
SRP5-1
D6
SRP5-1
D6
SRP5-1
D6
SRP5-1
D6
SRP5-2
D6
SRP5-1
D6
SRP5-1
D6
SRP5-2
D6
SRP5-1
D6
SRP5-1
D6
SRP5-1
D6
SRP5-2
D6
SRP5-1
D6
SRP5-1
D6
SRP5-2
D6
SRP5-1
D6
SRP5-1
D6
SRP5-2
D6
SRP5-1
D6
SRP5-1
D6
SRP5-2
D6
SRP5-1
D6
SRP5-1D6
SRP5-2
D6
SRP5-2
D6
SRP5-1
D6
SRP5-1
D6
SRP5-1
X1
X1
X1
X1
HS1
HS1
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
D6
SRP5-2
EM
HS1
HS1
LIGHTING
G
SD
C O
TT
O
N W
O O
D H
IG
H
S C
H O
O L
AU
D
IT
O
R
IU
M L
IG
H
TI
N
G U
PG
R
AD
E
S
E, M
U R
R
AY
, U T
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
E301
E1
SHEET KEYNOTES
PLAN
NORTH
AUDITORIUM MAIN LEVEL
ELECTRICAL PLAN
'HF'
Ea
Eb
Ea
Eb
Ea
Eb
Ea
Eb
Ea
Eb
Ec
OB14
Ec
OB13
Ec
OB12
Ec
OB11
Ec
OB10
D7
D7A
SL1
SL4
SL4
SL4
SL4
SRP5
X1
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
SRP5-7
D7
SRP5-6
D7
SRP5-7
D7
SRP5-7
D7
SRP5-7
D7
SRP5-7
D7
SRP5-7
D7
SRP5-7
D7
SRP5-7
D7
SRP5-7
D7
SRP5-6
D7
SRP5-6
D7
SRP5-6
D7
SRP5-6
D7
SRP5-6
D7
SRP5-6
D7
SRP5-6
D7
SRP5-6
D7
SRP5-6
D7
SRP5-6
D7
SRP5-6
D7
SRP5-6
D7
SRP5-6
D7
SRP5-6
D7
SRP5-6
D7
SRP5-6
D7
SRP5-6
D7
SRP5-6
D7
SRP5-6
D7
SRP5-6
D7
SRP5-6
D7
SRP5-6
D7
SRP5-6
SRP5-3
D7A
SRP5-4
D7A
SRP5-4
D7A
SRP5-4
D7A
SRP5-4
D7A
SRP5-4
D7A
SRP5-4
D7A
SRP5-4
D7A
SRP5-4
D7A
SRP5-4
D7A
SRP5-4
D7A
SRP5-4
D7B
SRP5-4
D7A
SRP5-4
D7B
SRP5-4
D7B
SRP5-4
D7B
SRP5-4
D7A
SRP5-4
D7B
SRP5-4
D7B
SRP5-4
D7A
SRP5-4
D7B
SRP5-4D7A
SRP5-4
D7A
SRP5-4
D7A
SRP5-4
D7B
SRP5-4
SRP5-8SL1
SRP5-8
SL1
SRP5-8
SL1
SRP5-8
SL1
SRP5-8
SL1
SRP5-8
SL1
SRP5-8
SL1
SRP5-8
SL1
SRP5-8
SL1
SRP5-8
SL1
SRP5-8
SRP5-10
SRP5-10
SRP5-10
SRP5-10
D7A
SRP5-3
D7A
SRP5-3
D7A
SRP5-3
D7A
SRP5-3
D7A
SRP5-3
D7A
SRP5-3
D7A
SRP5-3
D7A
SRP5-3
D7A
SRP5-3
D7A
SRP5-3
D7A
SRP5-3
D7A
SRP5-3
D7A
SRP5-3
D7A
SRP5-3
D7A
SRP5-3
D7A
SRP5-3
D7A
SRP5-3
D7A
SRP5-3
D7A
SRP5-3
D7A
SRP5-3
D7B
SRP5-3
EM
D7B
SRP5-4
D7B
SRP5-3
D7B
SRP5-3
D7B
SRP5-3
D7B
SRP5-3
D7B
SRP5-3
D7B
SRP5-3
D7B
SRP5-3
D7B
SRP5-3
D7B
SRP5-3
D7B
SRP5-3
D7B
SRP5-3
OB7
OB6
OB5
OB4
X1
LIGHTING
LIGHTING
G
SD
C O
TT
O
N W
O O
D H
IG
H
S C
H O
O L
AU
D
IT
O
R
IU
M L
IG
H
TI
N
G U
PG
R
AD
E
S
E, M
U R
R
AY
, U T
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
E302
Ea PROVIDE NEW 14"X14" GRID IRON JUNCTION BOXES WITH TERMINALS FOR A MINIMUM OF (10) 20A CIRCUITS.
Eb PROVIDE NEW SO MULTI-CABLE WITH WIRING FOR A MINIMUM OF (10) 20A CIRCUITS. CONTRACTOR TO COORDINATE WIRE SIZING TO ENSURE VOLTAGE DROP ARE WITHIN THE SPECIFICATION REQUIREMENTS.
PROVIDE ALL STRAIN RELIEF'S, CORD GRIPS AND CABLE CRADLES REQUIRED FOR A FULLY SUPPORTED
SYSTEM.
Ec PROVIDE NEW HANGER BRACKETS FOR MOUNTING OF NEW CONNECTOR STRIPS. CONTRACTOR TO VERIFY HANGER BRACKET REQUIREMENTS TO MATCH THE EXISTING HANGING OF THE CONNECTOR STRIPS. HANGING OF THE NEW CONNECTOR STRIPS SHALL BE INSTALLED OR REVIEWED BY A CERTIFIED AND EXPERIENCED RIGGING INSTALLER PRIOR TO HANGING LIGHT FIXTURES. ALL EXISTING SCHEDULE 40 PIPING SHALL BE
REUSED FOR THE NEW CONNECTOR STRIPS.
SHEET KEYNOTES
PLAN
NORTH
AUDITORIUM UPPER LEVEL
ELECTRICAL PLAN
E303
S1 S1
S1 S1
S1 S1
S1 S1
S1 S1
S1 S1
S1 S1
S1 S1
S1 S1
E8
E6 E5 E3
DMA-20
'SMP'
E2
E4
E3E3
XFMR
'ET1'
'EDM' 'DMA' 'DMDP' 'S
RP
4'
'S
RP
3'
'S
RP
2'
'S
RP
1'
E3
E7
E1
E1
DMA-22
'EDBK''EDMK'
'BCLTS''BCLTS'
G
SD
C O
TT
O
N W
O O
D H
IG
H
S C
H O
O L
AU
D
IT
O
R
IU
M L
IG
H
TI
N
G U
PG
R
AD
E
S
E, M
U R
R
AY
, U T
181 E 5600 S, Murray, UT 84107 | (801) 530-3148 info@resolutgroup.com | resolutgroup.com
E303
E1 EXISTING DUCTWORK.
E2 EXISTING TRANSFORMER. SEE ONE-LINE DIAGRAM SHEET E401 FOR ADDITIONAL REQUIREMENTS.
E3 EXISTING WIRE WAYS SERVING DIMMING CIRCUITS TO REMAIN.
E4 EXISTING WIRE WAY SERVING SOUND BOOTH TO REMAIN.
E5 EXISTING COMPANY SWITCH. SEE ONE-LINE DIAGRAM SHEEE401 FOR ADDITIONAL REQUIREMENTS.
E6 EXISTING PANEL 'HG'. SEE ONE-LINE DIAGRAM SHEET E401 FOR ADDITIONAL REQUIREMENTS.
E7 NEW PANEL 'DMA'. RELOCATE EXISTING CIRCUITS TO THIS PANEL.
E8 UTILIZE EXISTING CONDUIT, WIRING AND CONTROL FRO NEW FIXTURES.
SHEET KEYNOTES
PLAN
NORTH
1 AUDITORIUM BASEMENT LEVEL
ELECTRICAL PLAN
1/8" = 1'-0" 0 4' 8' 16'
PLAN
NORTH
3 AUDITORIUM MAIN LEVEL
ELECTRICAL ENLARGED PLAN
1/4" = 1'-0" 0 2' 4' 8'
PLAN
NORTH
2 AUDITORIUM BASEMENT LEVEL
ELECTRICAL ENLARGED PLAN
1/4" = 1'-0" 0 2' 4' 8'
3" 250204 5525
3"
3" 350
XHHW
XHHW
5004"
5004"
550 5
535 5
XHHW
4"
3"
44/0
2/0
3/0
1/0
3/0
1/0
1"
1"
1"
1"
1"
3/4"
3/4"
1-1/2"
1-1/2"
1-1/2"
1-1/4"
2"
2"
2"
2-1/2"
250255
4/054X 5
53X 5
2"
2"
551X
2"51 5
2"
COPPER
4/0
3/0
2/0
1/0
3"
3"
2-1/2"
2"
2"
1-1/2"
1-1/4"
1-1/4"
1-1/4"
1"
1"
444X
334X
443X
333X
442X
332X
441X
331X
220 30 3/4" 10 10
INSULATION
SIZEQUAN.
CONDUCTOR
AMP.TYPE
CONDUCTOR & CONDUIT SCHEDULE
62/0140 2" 552X *
2-1/2"
2-1/2"
3"35054 3/012161200550-4
550-4 1000 1216 2/04 5 500 4"
4"35053 1/0744800535-3
2 3"500 1550-2 600 608 5
FOR PARALLEL RUNS
CONDUCTOR & CONDUIT SCHEDULE
COPPER
4"500411 50041804000450-11
4"50048 40030403000450-8
450-7 2500 2665 3507 4 500 4"
435-4 1200 1240 3/04 4 350 3"
450-3 1000 1140 2/03 4 500 4"
450-2 800 760 1/02 4 500 4"
SETS
3"
TYPE
CONDUCTOR
QUAN. SIZE
350 1435-2 600 620 4
350-2 800 760 1/02 3 500 4"
3620600335-2 1350 3"2
350-3 1000 1140 2/03 3 500 4"
335-4 1200 1240 3/04 3 350 3"
3"40035 4/016751600340-5
4"40056 4/016751600540-6
3"40045 4/016751600440-5
440-6 2000 2010 2506 4 400 4"
446040044X-2 34/0 2-1/2"2
536840054X-2 34/0 3"2 *
COND.
SIZE
EQ. GND.
COND.
THHN
THWN
THHN
THWN
THHN
THWN
THHN
THWN
THHN
THWN
THHN
THWN
THHN
THWN
THHN
THWN
THHN
THWN
THHN
THWN
THHN
THWN
THHN
THWN
THHN
THWN
THHN
THWN
THHN
THWN
THHN
THWN
THHN
THWN
THHN
THWN
THHN
THWN
THHN
THWN
THHN
THWN
THHN
THWN
THHN
THWN
THHN
THWN
THHN
THWN
THHN
THWN
THHN
THWN
THHN
THWN
THHN
THWN
THHN
THWN
THHN
THWN
THHN
THWN
THHN
THWN
THHN
THWN
THHN
THWN
THHN
THWN
THHN
THWN
THHN
THWN
MAX. O.C.
PROT.
COND.
AMPS
CONDUIT
SIZE
EQ. GND.
COND.
NOTES:
IN PARALLEL RUNS SIZE GND. COND. IN
ACCORDANCE WITH NEC PARA. 250-122.
GND. CONDUCTOR MAY BE DELETED
ON SERVICE ENTRANCE CONDUCTORS
* 200% NEUTRAL, DERATED TO 80% BASED ON
NEC 310.15.B(5)(C)
T51X-1
T54X-1
T535-1
T525-2
T550-2
T540-3
T550-4
T540-6
T550-10 1030403000
616081600
412161200
608600
2408400
1248225
1184175
1120100
5 2"
5 3"
5 3"
5 4"
4"500
3"250
4/0
1/0
4"400
4"
4"
CONDUCTOR & O.C. PROT.
FOR TRANSFORMER SECONDARY
COPPER THHN/THWN
(200% NEUTRAL) 480-208/120
750 335-4
500 350-2
300 335-2
225 350
112.5 32X
75 31X
45 34
30 36
3"350
3"4/0
2"3/0
2"1
3"3504
4/0 2-1/2"
4"400
4 4"
3"
CONDUCTOR
QUAN. SIZE
830403000
516751600
412401200
620600
2460400
1230225
1200175
1110100
SETS
31X75
32X112.5
350225
335-2300
350-2500
335-4750 T450-8
T440-5
T435-4
T435-3
T44X-2
T435-2
T44X-1
T43X-1
T41-1
480-208/120
COPPER THHN/THWN
FOR TRANSFORMER SECONDARY
CONDUCTOR & O.C. PROT.
* SEE SCHEDULE FOR CONDUIT AND WIRE SIZE
5 500
NOTES:
TRANS
KVA
MIN.
Z%
COND.
AMPS
CONDUIT
SIZE
GROUNDING ELECTRODE CONDUCTOR. (NEC 250.66)
SUPPLY SIDE BONDING JUMPER. (NEC 250.102 (C)(1))
XHHW INSULATION.
CONDUCTOR
QUAN. SIZE
SETS
TRANS
KVA
MIN.
Z%
COND.
AMPS
CONDUIT
SIZE
O.C.
PROT.
TYPE
COND.*
O.C.
PROT.
TYPE
COND.*
O.C.
PROT.
TYPE
COND.*
O.C.
PROT.
TYPE
COND.*
3/0
3/0
3/0
3/0
2/0
1/0
1/0
2/0
2/0
3/0
3/0
3/0
GEC 1
GEC 1
3/0
2/0
1/0
4/0
2/0
2/0
1/0
BONDING
JUMPER
BONDING
JUMPER
COPPER CONDUCTOR
& O.C. PROT. FOR
TRANSFORMER PRIMARY
COPPER CONDUCTOR
& O.C. PROT. FOR
TRANSFORMER PRIMARY
100A 3P
PANEL
'TA'
EXIST.
100A 3P
PANEL
'TC'
EXIST.
200A 3P
PANEL
'TE1'
EXIST.
150A 3P
PANEL
'TF'
EXIST.
100A 3P
PANEL
'TP'
EXIST.
400A 3P
50A 3P
PANEL
'BR'
EXIST.
175A 3P
PANEL
'K'
EXIST.
225A 3P
200A 3P
150A 3P
200A 3P
PANEL
'DW'
EXIST.
225A 3P
PANEL
'C'
EXIST.
225A 3P
PANEL
'B'
EXIST.
300A 3P
50A 3P
300A 3P
PANEL
'MC'
EXIST.
PANEL
'TE2'
EXIST.
MAIN SWITCHBOARD
480/277 VOLT, 3 PHASE, 4 WIRE
2000 AMP
2000A BUS DUCT FEED
FROM GENERATOR BUILDING
PANEL
'KB'
EXIST.
PANEL
'KA'
EXIST.
EXISTING TRANSFORMER
480 VOLT - 208/120 VOLT,
3 PHASE, 4 WIRE
112.5 KVA
PANEL
'TB'
EXIST.
EXISTING TRANSFORMER
480 VOLT - 208/120 VOLT,
3 PHASE, 4 WIRE
300 KVA
EXISTING TRANSFORMER
480 VOLT - 208/120 VOLT,
3 PHASE, 4 WIRE
30 KVA
PANEL
'H'
EXIST.
EXISTING TRANSFORMER
480 VOLT - 208/120 VOLT,
3 PHASE, 4 WIRE
112.5 KVA
50A 3P
PANEL
'HC'
EXIST.
200A 3P
PANEL
'HF'
EXIST.
100A 3P
PANEL
'HB'
EXIST.
EXISTING DISTRIBUTION PANEL 'HA'
208/120 VOLT, 3 PHASE, 4 WIRE
400 AMP
225A 3P
PANEL
'D'
EXIST.
EXISTING TRANSFORMER
480 VOLT - 208/120 VOLT,
3 PHASE, 4 WIRE
112.5 KVA
100A 3P
PANEL
'DD'
EXIST.
50A 3P
PANEL
'DF'
EXIST.
150A 3P
PANEL
'DA'
EXIST.
EXISTING DISTRIBUTION PANEL 'LDA'
208/120 VOLT, 3 PHASE, 4 WIRE
400 AMP
125A 3P
PANEL
'DC'
EXIST.
125A 3P
PANEL
'DB'
EXIST.
PANEL
'CA'
EXIST.
EXISTING TRANSFORMER
480 VOLT - 208/120 VOLT,
3 PHASE, 4 WIRE
45 KVA
PANEL
'CB'
EXIST.
PANEL
'CC'
EXIST.
(3) EXISTING TRANSFORMERS
480 VOLT - 120 VOLT,
1 PHASE, 3 WIRE
15 KVA
PANEL
EXIST.
PANEL
EXIST.
PANEL
'BA'
EXIST.
EXISTING TRANSFORMER
480 VOLT - 208/120 VOLT,
3 PHASE, 4 WIRE
45 KVA
PANEL
'BB'
EXIST.
PANEL
'A'
EXIST.
EXISTING TRANSFORMER
480 VOLT - 208/120 VOLT,
3 PHASE, 4 WIRE
112.5 KVA
150A 3P
PANEL
'DT'
EXIST.
150A 3P
PANEL
'AL'
EXIST.
125A 3P
PANEL
'AB'
EXIST.
EXISTING DISTRIBUTION PANEL 'AA'
208/120 VOLT, 3 PHASE, 4 WIRE
400 AMP
100A 3P
PANEL
'AC'
EXIST.
100A 3P
PANEL
'AG'
EXIST.
400A 3P
PANEL
'AH'
EXIST.
PANEL
'AJ'
EXIST.
PANEL
'AD'
EXIST.
PANEL
'AE'
EXIST.
PANEL
'AF'
EXIST.
NO SCALE
ONE-LINE DIAGRAM
800A 3P
400A 3P
400A 3P
EXISTING
DIMMER RACK
EXISTING
DIMMER RACK
SOUND BOOTH
EXISTING
COMPANY
SWITCH
400A 3P
EXISTING
DIMMING
PANEL
BLACKBOX
300A 3P400A
3P
225KW EXISTING
EMERGENCY GENERATOR
480/277V, 3 PHASE, 4 WIRE,
400A EXISTING
AUTOMATIC
TRANSFER
SWITCH
E1 INTERCEPT EXISTING 3-1/2" CONDUIT AND EXTEND TO DISTRIBUTION PANEL. PROVIDE (4) #500 MCM AND
(1) #500 MCM FOR ENTIRE LENGTH.
E2 INTERCEPT EXISTING 2" CONDUIT AND EXTEND TO DISTRIBUTION PANEL. PROVIDE (4) #3/0 THWN CU AND
(1) #6 THWN CU GND FOR ENTIRE LENGTH.
E3 INTERCEPT EXISTING 3" CONDUIT AND EXTEND TO DISTRIBUTION PANEL AND NEW RELAY PANEL 'SRP5'.
PROVIDE JUNCTION BOX AND SPLICE TO EXISTING (4) #350 MCM CU AND (1) #3/0 THWN CU GND.
SHEET KEYNOTES
50A 3P
PANEL
'E'
EXIST.
100A 3P
PANEL
'EP'
EXIST.
200A 3P
PANEL
'G'
EXIST.
EXISTING DISTRIBUTION PANEL 'DP1'
480/277 VOLT, 3 PHASE, 4 WIRE
400 AMP
150A 3P
PANEL
'F'
EXIST.
PANEL
'EDM'
EXIST.
400A 3P
500A 3P
1 2 3 4 5 6
SPACE
ONLY
TRANSFORMER 'ET1'
480 VOLT - 208/120 VOLT,
3 PHASE, 4 WIRE
30 KVA
T41-1
PANEL
'FA'
EXIST.
EXISTING
TRANSFORMER
480 VOLT -
208/120 VOLT,
3 PHASE, 4 WIRE
30 KVA
PANEL
'FB'
EXIST.
PANEL
'EA'
EXIST.
EXISTING
TRANSFORMER
480 VOLT -
208/120 VOLT,
3 PHASE, 4 WIRE
9 KVA
PANEL
'GA'
EXIST.
EXISTING
TRANSFORMER
480 VOLT - 208/120 VOLT,
3 PHASE, 4 WIRE
75 KVA
PANEL
'GB'
EXIST.
225A 3P
PANEL
'HG'
EXIST.
200A 3P
200A 3P
NEW DISTRIBUTION PANEL 'DMP1'
208/120 VOLT, 3 PHASE, 4 WIRE
1200 AMP
200A 3P
1200A 3P
400A 3P
4 5 6 7 8 9
200A 3P
200A 3P
100A 3P
200A 3P
COMPANYPANEL
'SRP2'
RELAY
PANEL
'DMA'
PANEL
'SRP1'
RELAY
SWITCH
EXIST.
PANEL
'SRP3'
RELAY
BLACK
SWITCH
EXIST.
43X 41 43X 43X
E1 E2
PANEL
DIMMING
PANEL
'SRP4'
RELAY
43X
PANEL
'SRP5'
RELAY
44X E3
10 11
SPACE
ONLY
SPACE
ONLY
SPACE
ONLY
SPACE
ONLY
T435-4
100A 3P
SPARE
G
SD
C O
TT
O
N W
O O
D H
IG
H
S C
H O
O L
AU
D
IT
O
R
IU
M L
IG
H
TI
N
G U
PG
R
AD
E
S
E, M
U R
R
AY
, U T
181 E 5600 S, Murray, UT 84107 | (801) 530-3148
E401
G
SD
C O
TT
O
N W
O O
D H
IG
H
S C
H O
O L
AU
D
IT
O
R
IU
M L
IG
H
TI
N
G U
PG
R
AD
E
S
E, M
U R
R
AY
, U T
181 E 5600 S, Murray, UT 84107 | (801) 530-3148
E402
SRP1 SRP2 SRP3 BOOTH 1 BOOTH 2 BOOTH 1 BOOTH 2 1
CATWALK
CATWALK
CATWALK
BALCONY
BALCONY
BALCONY
1ST ELEC
1ST ELEC
1ST ELECHR TORM HL TORM
WAP 1 WAP 2
WIRELESS
ACCESS POINT
GATEWAYGATEWAY
HOUSE HOUSE
EDMX
HOUSE
STAGE
SRP4 SRP5
ON
OFF
OFF
CATWALK
AISLE
RUN
1ST ELEC
2ND ELEC
STAGE
3RD ELEC
EQUIPMENT RACK - 44U
120V / 60 Hz.
20A MAX.
(BY OTHERS)
ER1
BASEMENT
1Ø, 2 WIRE + GND
CISCO 28-PORT SWITCH WITH PoE
BRUSH PANEL 2U
UNINTERRUPTIBLE POWER SUPPLY
FURMAN LIGHT/POWER PANEL
24-PORT PATCH PANEL
CISCO 28-PORT SWITCH WITH PoE
BRUSH PANEL 2U
24-PORT PATCH PANEL
UNISON PTS7-RM
PARADIGM 7" TOUCHSCREEN
UNISON ERn2-RM
ARCHITECTURAL CONTROL UNIT
1 - P-ACP
1 - P-SPM-E
1 - URTO
1 - ERn-RPS
RESPONSE 4-PORT GATEWAY (DUAL)
TWO NETWORK INPUTS
(BY ETC)
DRAWER WITH
WRITING SURFACE
(BY ETC)
DRAWER
(BY ETC)
BLANK PANEL
BLANK PANEL
FURMAN LIGHT/POWER PANEL
UNISON P-TS18-V2
RACK-MOUNT
18" TOUCHSCREEN
TWO NETWORK INPUTS
(BY ETC)
DRAWER WITH
WRITING SURFACE
(BY ETC)
DRAWER
(BY ETC)
P-CCS CENTRAL CONTROL SERVER
EQUIPMENT RACK - 18U
120V / 60 Hz.
20A MAX.
(BY OTHERS)
SMP
DOWNSTAGE LEFT
1Ø, 2 WIRE + GND
UNINTERRUPTIBLE POWER SUPPLY
BLANK PANEL
TO LOAD CKTS
3Ø, 4 WIRE + GND
120 / 208 VAC
60Hz.
(BY OTHERS)
ECHO RELAY PANEL
SRP1
24 x 20A 1P RELAYS
1 - DOOR - SURFACE
BASEMENT
200A. MAX.
TO LOAD CKTS
3Ø, 4 WIRE + GND
120 / 208 VAC
60Hz.
(BY OTHERS)
ECHO RELAY PANEL
SRP2
24 x 20A 1P RELAYS
1 - DOOR - SURFACE
BASEMENT
200A. MAX.
TO LOAD CKTS
3Ø, 4 WIRE + GND
120 / 208 VAC
60Hz.
(BY OTHERS)
ECHO RELAY PANEL
SRP3
24 x 20A 1P RELAYS
1 - DOOR - SURFACE
BASEMENT
200A. MAX.
TO LOAD CKTS
3Ø, 4 WIRE + GND
120 / 208 VAC
60Hz.
(BY OTHERS)
ECHO RELAY PANEL
SRP4
24 x 20A 1P RELAYS
1 - DOOR - SURFACE
BASEMENT
200A. MAX.
TO LOAD CKTS
3Ø, 4 WIRE + GND
120 / 208 VAC
60Hz.
(BY OTHERS)
ECHO RELAY PANEL
SRP5
24 x 20A 1P RELAYS
1 - DOOR - SURFACE
LEVEL 2 BOOTH
40A. MAX.
(N)
(N)
(N)
(N)
(N)
4-WIRE 20A MAX. SENSE FEED
TO ENGINEER SPECIFIED
NORMAL POWER SOURCE
(BY OTHERS)
EBDK
BOOTH
1Ø, 2 WIRE + GND
EMERGENCY FEED
100-277VAC 50/60Hz.
20A. MAX.
(BY OTHERS)
DEBC-1
BOOTH
1Ø, 2 WIRE + GND
120-277V / 60Hz.
20A MAX.
EMERGENCY POWER FEED
(BY OTHERS)
SC1008 BCELTS
SC1008R
(1) 20A. 2-WIRE
SENSE CKT.
(1) 20A. 2-WIRE
NORMAL CKT.
(1) 20A. 2-WIRE
NORMAL/
EMERGENCY CKT.
UL ULC
TO NORMAL/
EMERGENCY
FIXTURE
(BY OTHERS)
FROM FIRE ALARM PANEL
1Ø, 2 WIRE + GND
120-277V / 60Hz.
20A MAX.
EMERGENCY POWER FEED
(BY OTHERS)
SC1008 BCELTS
SC1008R
(1) 20A. 2-WIRE
SENSE CKT.
(1) 20A. 2-WIRE
NORMAL CKT.
(1) 20A. 2-WIRE
NORMAL/
EMERGENCY CKT.
UL ULC
TO NORMAL/
EMERGENCY
FIXTURE
(BY OTHERS)
FROM FIRE ALARM PANEL
1Ø, 2 WIRE + GND
120-277V / 60Hz.
20A MAX.
EMERGENCY POWER FEED
(BY OTHERS)
SC1008 BCELTS
SC1008R
(1) 20A. 2-WIRE
SENSE CKT.
(1) 20A. 2-WIRE
NORMAL CKT.
(1) 20A. 2-WIRE
NORMAL/
EMERGENCY CKT.
UL ULC
TO NORMAL/
EMERGENCY
FIXTURE
(BY OTHERS)
FROM FIRE ALARM PANEL
(N)
ION Xe 20 XXXX CONTROL CONSOLE
18" WIDESCREEN LCD MONITOR 18" WIDESCREEN LCD MONITOR
25' NET CABLE
(UL924)
(N)
TO EMERGENCY DMX FIXTURES(D)
RSN-DMX4-DIN GATEWAY
TO DMX FIXTURES(D)
(N)
RSN-DMX4-DIN GATEWAY
TO DMX FIXTURES(D)
(N)
RSN-DMX4-DIN GATEWAY
TO DMX FIXTURES(D)
(N,N,N)
IPAD PROVIDED BY DISTRICT
INSTALLER TO PROVIDE APP FOR IPAD AND ANY PROGRAMING
AND/OR SETUP REQUIRED TO INSURE IT IS FUNCTIONING.
UNISON UH10001
HS1
B
HR FRONT
UNISON UH10001
HS1
B
HR FRONT
(U)
UNISON UH10001
HS1
B
HR REAR
(U)
UNISON UH10001
HS1
B
HL REAR
(U)
UNISON UH10001
HS1
B
HL FRONT
(U)
UNISON UH10001
HS1
B
HL FRONT
(U) (U)
1Ø, 2 WIRE + GND
120V, 50/60 Hz.
20A MAX.
(BY OTHERS)
ETCNet ETCNet
CONSOLE STATION (CS-1)
CONTROL BOOTH
(2) NETWORK INPUTS
AND (2) OUTLET RECEPTECLES
1Ø, 2 WIRE + GND
120V, 50/60 Hz.
20A MAX.
(BY OTHERS)
ETCNet ETCNet
CONSOLE STATION (CS-1)
CONTROL BOOTH
(2) NETWORK INPUTS
AND (2) OUTLET RECEPTECLES
OB1OB2OB3OB4OB5OB6OB7OB8OB9OB10OB11OB12OB13OB14OB15OB16OB17
(N)
(N) (N)
(N) (N)
(N) (N)
(N) (N)
(N,N,N)
(N) (N)
(N)
OB34OB33OB32OB31OB30OB29OB28OB27OB26OB25OB24OB23OB22OB21OB20OB19
OB18
OB35
(N,N,N) (N,N,N)
(N,N,N) (N,N,N)
(N) (N)
(N) (N)
(N) (N)
(N) (N)
(N) (N)
(N) (N)
(N) (N)
(N) (N)
(N) (N)
OUT
RSN-DMX1-O-P
C-CLAMP
SAFETY CABLE
PARADIGM P-TS7-H
HS2
1' DMX CABLE
UPPER UPPER FOH FOH
BALCONY
2ND ELEC
2ND ELEC
2ND ELEC
3RD ELEC
3RD ELEC
3RD ELEC
4TH ELEC
4TH ELEC
4TH ELEC
5TH ELEC
5TH ELEC
5TH ELEC
SL
FP 1
SR
FP 1
SL
FP 2
SR
FP 2
SL
FP 3
SR
FP 3
US FP
US FP
US FP
US FP
US FP
US FP DS FP
SL
APRON FP
SR
APRON FP
NET PLUG-INNET PLUG-INNET PLUG-IN
WIRELESS
ACCESS POINT
BALCONY FRONT
1' DMX CABLE
WIRELESS
ACCESS POINT
HOUSE
1' DMX CABLE
FRONT #1
APRON
FRONT #2
APRON
FRONT #3
APRON
FRONT #4
APRON
FRONT #5
APRON
FRONT #6
APRON
GATEWAY
HOUSEWAP 3
AUDITORIUM PATCH PANEL LABELING1
G
SD
C O
TT
O
N W
O O
D H
IG
H
S C
H O
O L
AU
D
IT
O
R
IU
M L
IG
H
TI
N
G U
PG
R
AD
E
S
E, M
U R
R
AY
, U T
181 E 5600 S, Murray, UT 84107 | (801) 530-3148
E501
ETCNet
PUSH
OUTLET DESIGNATION
CIRCUIT DESIGNATION
CONNECTOR
STRIP #
(OB7)
(B)
LOCATION
(A)
OUTLET DESIGNATION
CIRCUIT DESIGNATION
CONNECTOR
STRIP #
(OB12)
(B)
LOCATION
TORM HR
(A) (D)(C)
NET
(E)
494847
(OB13) TORM HL NET
(F) (G) 47 48 49
A
B
C
D
E
F
G
A B
ETCNet ETCNet
PUSH PUSH
120V 20A
MOUNTING
FLUSHORCHESTRA PIT
1.) CONNECTOR STRIP TROUGH AND COVER
BLACK FINE-TEXTURED POWDER COAT.
OF THE CONNECTOR STRIP.
THAN 5'-0" APART ALONG THE LENGTH
BRACKETS SHALL BE PLACED NO GREATER
2.) HANGER BRACKETS ARE GA. STEEL
14 GA. STEEL. ALL ARE FINISHED IN A
ARE 18 GA. STEEL. END CAPS ARE
FINISHED IN A BLACK FINE-TEXTURED
POWDER COAT. INDICATED QUANTITY OF
NOTES:
COVER VIEW
(V)
OUTLET DESIGNATION
CIRCUIT DESIGNATION
(F)
CONNECTOR
STRIP #
OB1
(B)
LOCATION
FOH1
(A) (D)(C) (E) (N)(J)(H)(G) (I) (L)(K) (M) (R)(P)(O) (Q) (T)(S) (U) (Z)(X)(W) (Y) (B1)(A1) (D1)
3.) CIRCUITS ARE DESIGNATED WITH 2.00"
BLACK LEXAN LABELS WITH WHITE TEXT.
4.) CONNECTOR STRIP IS LISTED.
CM
NET NET
OUTLET BOX SHALL BE MOUNTED SO THAT
THE LABELS ARE FACING THE BACK OF HOUSE.
NET NETOB2 FOH2
23456 134 2 6712 7467 5 23 1356 4 91011121314 91112 10 14881214 13 1011 9111314 12
1.) USE LABELING AS INDICATED ON DIAGRAM
NOTES:
494847 47 48 49
MOUNTING
SURFACE
SURFACE
ON/OFF
GROUNDED PIN CONNECTOR (GPC)
(SCALE 32:1)
LEFT SIDE VIEW
(SCALE 8:1)
65'-0"
1.) CONNECTOR STRIP TROUGH AND COVER
BLACK FINE-TEXTURED POWDER COAT.
OF THE CONNECTOR STRIP.
THAN 5'-0" APART ALONG THE LENGTH
BRACKETS SHALL BE PLACED NO GREATER
14 GA. STEEL. ALL ARE FINISHED IN A
ARE 18 GA. STEEL. END CAPS ARE
FINISHED IN A BLACK FINE-TEXTURED
POWDER COAT. INDICATED QUANTITY OF
NOTES:
A C
COVER VIEW
(V)
OUTLET DESIGNATION
CIRCUIT DESIGNATION
(F)
CONNECTOR
STRIP #
OB3
(B)
LOCATION
ELECTRIC 1
(A) (D)(C) (E) (N)(J)(H)(G) (I) (L)(K) (M) (R)(P)(O) (Q) (T)(S) (U) (L1)(D1)(Z)(X)(W) (Y) (B1)(A1) (C1) (H1)(F1)(E1) (G1) (J1)(I1) (K1) (N1)(M1) (O1)
D E F G H I J K L M O P Q R S T U V W X Y Z A1 E1 F1 G1 H1 I1 J1 K1 L1 M1 N1 P1 R1 S1 T1 U1 V1 W1 X1 Y1
3.) CIRCUITS ARE DESIGNATED WITH 2.00"
BLACK LEXAN LABELS WITH WHITE TEXT.
12.50
4.00
REMOVABLE COVER
4.) CONNECTOR STRIP IS LISTED.
CM
4'-0"6'-0"6'-0"6'-0"6'-0"6'-0"6'-0"6'-0"6'-0"6'-0"6'-0"6'-0"3'-0"
(SCALE 8:1)
HANGER BRACKET
6.68
16.00
2.40
4.00
1.50
2.92
(BY OTHERS)
1½" SCHEDULE 40 PIPE
2'-0"
B
NET
D1 Z1
ETCNet
NET
OUTLET BOX SHALL BE MOUNTED SO THAT
THE LABELS ARE FACING UPSTAGE.
2122 21171920 18 1516 22 15
N C1
WL1
OB4 ELECTRIC 2
OB5 ELECTRIC 3
OB6 ELECTRIC 4
NET 2930 29252728 26 2324 30
NET
NET
WL2
WL3
WL4
NET
NET
NET
1920 18
2728 26
191517 16 2122 20
272325 24 2930 28
1718 16
2526 24
2115 22
2923 30
171920 18
252728 26
1516 22
2324 30
1921 20
2729 28
WL118
WL226
WL3
WL3
O1
ETCNet
B1
CONTROL STATION 'HS1'6
NTS
CONTROL STATION 'CS1'2
NTS
OUTLET BOX 'C'3
NTS
OUTLET BOX 'A'5
NTS
CONNECTOR STRIP 'A'7
CONNECTOR STRIP 'B'8
VOLTAGE BARRIER
ETCNet
PUSH
OUTLET DESIGNATION
CIRCUIT DESIGNATION
CONNECTOR
STRIP #
(OB7)
(B)
LOCATION
(A) (D)(C)
NET
(E)
44434443
(OB8) NET
(OB9) NET
(OD10) NET
A B C D E
44434443 46454645 46454645
MOUNTING
FLUSHUPSTAGE RIGHT
UPSTAGE LEFT
DOWNSTAGE RIGHT
DOWNSTAGE LEFT
FLUSH
FLUSH
FLUSH
OUTLET BOX 'B'4
NTS
CONTROL STATION 'CS2'1
NTS
RECEPTACLE MOUNTING PLATE
(TO BE MOUNTED ON RECEPTACLE INSERT PLATE)
(SCALE 1¼=1)
SIDE VIEW
(HINGED DOOR SHOWN OPEN)
DETAIL A
NOTE THAT FLOOR PLATE IS FLOATING...
ie. NOT MECHANICALLY ATTACHED TO HOUSING.
RECEPTACLE MOUNTING PLATE
RECEPTACLE INSERT PLATE
FLOOR PLATE
SKID-PROOF
ETCNet
PUSH
9.00
11.25
(C1)
810 9
GROUNDED PIN CONNECTOR (GPC) LEFT SIDE VIEW
42'-0"
4½" 4½"
36"
18.00
6.25
3.25
18"18"18"18"18"18" 18" 18"18"18"18" 18" 18"18"18"18" 18" 18"18"18"18" 18"18"18"
A B C D E F G H I J K L M N O P Q R S T U V W X Y Z A1 B1
36" 36" 36" 36" 36" 36" 36" 36" 36" 36" 36"33" 33"
REMOVABLE COVER
3" 3"
6.25
REMOVABLE COVER
6'-0" 6'-0" 6'-0" 6'-0" 6'-0" 6'-0" 6'-0"
HANGER BRACKET
6.68
16.00
2.40
4.00
1.50
2.92
(BY OTHERS)
1½" SCHEDULE 40 PIPE
ETCNet
18"18" 18"
C1
ETCNet
D1
(P1)
(Q1)
(R1)
(S1)
(T1)
(U1)
(V1)
(W1)
(X1)
(Y1)
(Z1)
Q1 A2
NET
NET
NET
NET
(Z1)
3133 3238 37 36 35 343138 37 36 35 34 33 323138 37 36 35 34 33 323138 37 36 35 34 33 323138 37 36 35 34 33 32 3941 4046 45 44 43 423941 4046 45 44 43 423941 4045 44 43 42463941 4045 44 43 4246 3941 4042 45 44 4346
G
SD
C O
TT
O
N W
O O
D H
IG
H
S C
H O
O L
AU
D
IT
O
R
IU
M L
IG
H
TI
N
G U
PG
R
AD
E
S
E, M
U R
R
AY
, U T
181 E 5600 S, Murray, UT 84107 | (801) 530-3148
E502
| Sheets and Views |
| 24187-000-Layout1 |
| 24187-100-Layout1 |
| 24187-101-Layout1 |
| 24187-201-Layout1 |
| 24187-202-Layout1 |
| 24187-203-Layout1 |
| 24187-301-Layout1 |
| 24187-302-Layout1 |
| 24187-303-Layout1 |
| 24187-401-Layout1 |
| 24187-402-Layout1 |
| 24187-501-Layout1 |
| 24187-502-Layout1 |
File details come from the government source that posted it. Updated .