This is an Interior Path-of-Construction (POC) Asbestos Survey Report prepared by Terracon Consultants, Inc. for the Smith Clinic located at 2525 A Holly Hall Street in Houston, Texas. The survey was conducted on September 16, 2025, by Texas Department of State Health Services (TDSHS) licensed asbestos inspectors Christian H. Pedraza and Jonathan Hernandez in accordance with Environmental Protection Agency (EPA) regulations 40 CFR 763 (AHERA), Texas Asbestos Health Protection Rules (TAHPR), and OSHA standards. The survey identified and documented asbestos-containing materials (ACM) within the interior path-of-construction of three renovation projects: SCP ACS SC Linear Accelerators Replacement (Rooms 1302/1302A, 1303/1303A, and 1304/1304A), SCP ACS SC CT Scans (1-3) and CT Simulator Replacement (Rooms 1605, 1607, 1609, and 1112), and SCP ASS SC RAD Fluoroscopy Replacement (Rooms 1226, 1227, and 1228). The total path-of-construction area surveyed encompassed approximately 3,550 square feet. Fifty-six (56) bulk samples were collected from sixteen (16) homogeneous areas of suspect ACM throughout the surveyed spaces and submitted to Micro Analytical Services, Inc. (MAS), a TDSHS-licensed and NVLAP-accredited laboratory, for analysis by polarized light microscopy (PLM).
The laboratory analysis, completed on September 17, 2025, determined that asbestos was not identified in any of the samples collected. The survey encompassed interior building components including painted gypsum wallboard systems, white ceramic wall tile systems, white 2' x 2' ceiling tiles, painted gypsum wallboard ceilings, wood pattern strip vinyl flooring, vinyl floor tile systems, and ceramic floor tile systems. All sampled materials, including black cove base with tan mastic, brown wood pattern strip vinyl flooring, tan vinyl floor tile systems, white ceiling tiles, and painted gypsum wallboard systems, were determined to contain no detectable asbestos. The report notes that while reasonable effort was made to survey accessible suspect materials, additional suspect ACM could potentially exist in walls, voids, or concealed areas above ceilings that were not fully accessible. The survey complies with regulatory requirements mandating asbestos identification and classification prior to renovation activities, and the findings support proceeding with the planned renovation projects at Smith Clinic without asbestos remediation concerns for the surveyed areas.
View the file
Other files
Show all 22
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Interior POC Asbestos Survey Report
Smith Clinic – 1st Level | Houston, Texas
September 19, 2025 | Terracon Project No. 92257965
Facilities | Environmental | Geotechnical | Materials i
TABLE OF CONTENTS
1.1 Project Objective
1.2 Limitations………………………………………………………………………………………………………….1
3.1 Visual Assessment
3.2 Physical Assessment
3.3 Sample Collection
3.4 Sample Analysis
APPENDICES
Appendix A Asbestos Inspection Sample Summary Appendix B Asbestos Analytical Laboratory Report Appendix C Sample Location Map Appendix D Site Photographs Appendix E Licenses & Certifications
September 19, 2025 | Terracon Project No. 92257965
Facilities | Environmental | Geotechnical | Materials 1
INTRODUCTION
Terracon Consultants, Inc. (Terracon) conducted an interior path-of-construction (POC) asbestos survey of selected areas of the various areas in the Smith Clinic – 1st Level located at 2525 A Holly Hall Street in Houston, Texas. The survey was conducted on September 16, 2025, by a State of Texas licensed asbestos inspector in general accordance with Terracon Proposal No. P92257965 dated September 17, 2025.
Building components in the POC were surveyed, and homogeneous areas of suspect asbestos-containing materials (ACM) were visually identified and documented. Although reasonable effort was made to survey accessible suspect materials, additional suspect but un-sampled materials could be located in walls, voids or in other concealed areas. Suspect ACM samples were collected in general accordance with the sampling protocols outlined in Environmental Protection Agency (EPA) regulation 40 CFR 763 (Asbestos Hazard Emergency Response Act, AHERA) and the Texas Asbestos Health Protection Rules (TAHPR). Samples were delivered to a State of Texas licensed laboratory for analysis by polarized light microscopy (PLM).
1.1 Project Objective
We understand the purpose of this survey was to identify and quantify ACM present within the interior POC of the SCP ACS SC LINEAR ACCELERATORS REPLACEMENT (LINEAR 1-2), SCP ACS SC CT SCANS (1-3) AND CT SIMULATOR REPLACEMENT, and the SCP ASS SC RAD FLUOROSCOPY REPLACEMENT (RF ROOMS 1,2), prior to renovation. POC areas were depicted on drawings provided to Terracon by the client. TAHPR, Senate Bill 509 and EPA regulation 40 CFR 61, Subpart M, National Emission Standards for Hazardous Air Pollutants (NESHAP) require that an asbestos survey be performed prior to issuance of a city construction permit and prohibit the release of asbestos fibers to the atmosphere during renovation or demolition activities. The asbestos NESHAP requires that potentially regulated ACM be identified, classified and quantified prior to planned disturbances or demolition activities. The Occupational Safety and Health Administration (OSHA) has promulgated a worker protection standard for the disturbance of materials containing asbestos during demolition and renovation projects.
1.2 Limitations
Terracon assessed multiple areas above the drywall and ceiling systems, where possible, but did not observe additional suspect materials. Access to areas above the ceiling was limited, and the potential exists for additional suspect ACM to be present in these inaccessible areas.
Terracon lifted floor coverings in several areas in the building but did not observe additional floor coverings/layers; however, as Terracon could not assess beneath all floor coverings in
September 19, 2025 | Terracon Project No. 92257965
Facilities | Environmental | Geotechnical | Materials 2 all areas, there may be isolated areas of additional suspect material present beneath existing coverings.
Interior building components were included in the survey. Destructive sampling was conducted as indicated in Terracon’s proposal.
Terracon did not have any inaccessible areas and was able to collect samples throughout the POC areas
BUILDING DESCRIPTION
Building Description and Information
Building Multi-Story Building
POC Area Description
Smith Clinic – 1st level areas including:
SCP ACS SC LINEAR ACCELERATORS REPLACEMENT (LINEAR 1-2)
(Rooms 1302/1302A, 1303/1303A and 1304/1304A)
SCP ACS SC CT SCANS (1-3) AND CT SIMULATOR REPLACEMENT
(Rooms 1605, 1607, 1609 and 112)
SCP ASS SC RAD FLUOROSCOPY REPLACEMENT (RF ROOMS 1,2)
(Rooms 1226, 1227 and 1228)
Total POC Area ~3,550 SF
Building Use Medical Facility
Roof N/A
Exterior N/A
Interior POC Walls Painted gypsum wallboard system and white ceramic wall tile system
Interior POC Ceilings White 2’ x 2’ ceiling tile and painted gypsum wallboard system
Interior POC Floors Wood pattern strip vinyl flooring, vinyl floor tile system and ceramic floor tile system
Additional Information N/A
FIELD ACTIVITIES
Mr. Christian H. Pedraza, a Texas Department of State Health Services (TDSHS) licensed asbestos inspector (License No. 60-4222), and Mr. Jonathan Hernandez, a TDSHS licensed asbestos inspector (License No. 60-4222), conducted the asbestos survey in general accordance with the sample collection protocols established in AHERA. Copies of their licenses are is attached in Appendix E. The following sections present a summary of survey activities.
September 19, 2025 | Terracon Project No. 92257965
Facilities | Environmental | Geotechnical | Materials 3
3.1 Visual Assessment
Our survey activities began with visual observation of the POC to identify homogeneous areas of suspect ACM. A homogeneous area (HA) consists of building materials that appear similar throughout in terms of color, texture and date of application; building materials identified as glass, wood, fiberglass, metal or rubber were not considered suspect ACM. The assessment was conducted throughout visually accessible areas of the POC.
3.2 Physical Assessment
Terracon conducted a physical assessment of each HA of suspect ACM to assess the friability and condition of the materials. The EPA defines a friable material as a material, when dry, can be crumbled, pulverized or reduced to powder by hand pressure. Terracon assessed friability by physically touching suspect ACM.
3.3 Sample Collection
Based on results of the visual observation, Terracon collected random bulk samples from each HA of suspect ACM observed in general accordance with AHERA sampling protocols. Sample team members collected bulk samples using wet methods as applicable to reduce the potential for fiber release. Samples were placed in sealable containers and labeled with unique sample numbers using an indelible marker.
Fifty-six (56) bulk samples were collected from sixteen (16) homogeneous areas of suspect ACM. A summary of suspect ACM samples collected during the survey is included in the chain-of-custody (COC) in Appendix B.
3.4 Sample Analysis
Bulk samples were submitted under COC to Micro Analytical Services, Inc (MAS) of Houston, Texas, for analysis by PLM per EPA methodology EPA/600/R-93/116. The percentage of asbestos, where applicable, was determined by microscopic visual estimation. MAS is accredited under the National Voluntary Laboratory Accreditation Program (NVLAP Accreditation No. 200618-0) and licensed by the TDSHS (TDSHS No. 30-0341).
REGULATORY OVERVIEW
Title 25, Part 1, Chapter 296, TAHPR, regulates asbestos fiber emission and asbestos waste disposal practices for public buildings. TAHPR also require the identification and classification of existing asbestos-containing building materials prior to demolition or renovation activity.
Under TAHPR, asbestos-containing building materials are classified as either friable or
September 19, 2025 | Terracon Project No. 92257965
Facilities | Environmental | Geotechnical | Materials 4 nonfriable ACM containing 1% or more asbestos. Friable materials are those that, when dry, may be crumbled, pulverized or reduced to powder by hand pressure.
TAHPR requires that any asbestos-related activity be performed by TDSHS licensed individuals. An asbestos-related activity consists of the disturbance (whether intentional or unintentional), removal, encapsulation, or enclosure of asbestos, including preparations or final clearance activities, the performance of asbestos surveys, the development of management plans and response actions, asbestos project design, the collection or analysis of asbestos samples, monitoring for airborne asbestos, or any other activity required to be licensed under TAHPR.
TAHPR requires that abatement in public buildings be performed by a TDSHS licensed asbestos abatement contractor in accordance with a project design prepared by a TDSHS licensed asbestos consultant. In addition, a TDSHS licensed asbestos consultant agency must perform 3rd party air monitoring during the abatement activities. TAHPR requires that written notification be submitted before beginning renovation projects that include the disturbance of any quantity of ACM in a public or commercial building or facility, and before the demolition of a building or facility, even when no asbestos is present. This written notification must be provided to the TDSHS at least 10 working days prior to the commencement of asbestos abatement or demolition activities.
40 CFR Part 61 Subpart M, the asbestos NESHAP, regulates asbestos fiber emission and asbestos waste disposal practices for commercial buildings and facilities. NESHAP requires the identification and classification of existing asbestos containing building materials prior to demolition or renovation activity. Under NESHAP, building materials containing >1% asbestos are classified as either friable, Category I nonfriable or Category II nonfriable ACM. Friable materials are those that, when dry, may be crumbled, pulverized or reduced to powder by hand pressure. Category I nonfriable ACM includes packing, gaskets, resilient floor coverings and asphalt roofing products. Category II nonfriable ACM includes any nonfriable materials other than those classified as Category I materials.
Regulated asbestos-containing materials (RACM) includes all friable ACM; Category I non-friable ACM that has become friable or will be or has been subjected to sanding, grinding, cutting, or abrading; and Category II non-friable ACM that has a high probability of becoming or has become crumbled, pulverized, or reduced to powder in the course of renovation or demolition activity.
29 CFR 1926.1101, OSHA Asbestos standard for the construction industry, regulates workplace exposure to asbestos. The OSHA standard classifies construction and maintenance activities that could disturb ACM and specifies work practices and precautions employers must follow when engaging in each class of regulated work. The OSHA standard also requires that employee exposure to airborne asbestos fibers be maintained below the Permissible Exposure
September 19, 2025 | Terracon Project No. 92257965
Facilities | Environmental | Geotechnical | Materials 5
Limit (PEL) of 0.1 asbestos fibers per cubic centimeter (f/cc) of air as an 8-hour Time Weighted Average (TWA).
FINDINGS AND RECOMMENDATIONS
Asbestos was not identified in the samples collected on September 16, 2025. The laboratory analytical report is included as Appendix B.
If suspect asbestos-containing materials are discovered during the renovation work that were not sampled as part of this survey, they should not be disturbed until the presence of asbestos is either confirmed or ruled out by laboratory analysis.
GENERAL COMMENTS
Terracon conducted this interior POC asbestos survey in a manner consistent with the level of care and skill ordinarily exercised by members of the profession currently practicing under similar conditions in the same locale. The results, findings, conclusions, and recommendations expressed in this report are based on conditions observed during our survey of the POC areas.
The information contained in this report is relevant to the date on which this survey was performed and should not be relied upon to represent conditions later. This report has been prepared on behalf of and exclusively for use by Client for specific application to their project as discussed. This report is not a bidding document. Contractors, consultants or others reviewing this report must draw their own conclusions regarding further investigation or remediation deemed necessary. Terracon does not warrant the work of regulatory agencies, laboratories or other third parties supplying information that may have been used in the preparation of this report. No warranty, express or implied, is made.
APPENDIX A – ASBESTOS SURVEY SAMPLE SUMMARY
Smith Clinic – 1st Level
2525 A Holly Hall Street Houston, Texas 77054
Terracon Project No. 92257965
Sample
ID
Material Location (Area) Percent/Type
Asbestos Friability
Assessed Condition
Estimated Quantity
SCP ACS SC LINEAR ACCELERATORS REPLACEMENT (LINEAR 1-2)
1-3 Black cove base with tan mastic Linear Accelerators 1, 2 and 3 ND NA Good ~528 lf
4-6 Brown wood pattern strip vinyl flooring Linear Accelerators 1, 2 and 3 ND NA Good ~3,045 sf
7-9 Tan 12”x12” vinyl floor tile system Linear Accelerator Controls 1, 2 and 3
ND NA Good ~547 sf
10-12 White 2’x2’ ceiling tiles Linear Accelerators Control 1, linacs 2 and 3
ND NA Good ~3,582 sf
13-19 Painted gypsum wallboard system with smooth finish
Linear Accelerator 1, Linear Accelerator Control 1, Linear
Accelerator 2, Linear Accelerator Control 3, and
Linear Accelerator 3
ND NA Good ~5,800 sf
SCP ACS SC CT SCANS (1-3) AND CT SIMULATOR REPLACEMENT
1-3 Black cove base with tan mastic CT Scans 1, 2 and 3 ND NA Good ~250 lf
4-6 Brown wood pattern strip vinyl flooring CT Scans 1, 2 and 3 ND NA Good ~1,250 sf
7-11 Painted gypsum wallboard system with smooth finish CT Scans 1, 2 and 3 ND NA Good ~2,250 sf
12-14 White 2’x2’ ceiling tiles CT Scans 1, 2 and 3 ND NA Good ~1,250 sf
APPENDIX A – ASBESTOS SURVEY SAMPLE SUMMARY
Smith Clinic – 1st Level
2525 A Holly Hall Street Houston, Texas 77054
Terracon Project No. 92257965
Sample
ID
Material Location (Area) Percent/Type
Asbestos Friability
Assessed Condition
Estimated Quantity
15-17 Painted gypsum wallboard with smooth finish (ceilings) Restroom ND NA Good ~50 sf
18-20 White 3”x3” ceramic wall tile system Restroom ND NA Good ~105 sf
21-23 Gray 6”x6” ceramic floor tile system Restroom ND NA Good ~50 sf
SCP ACS SC RAD FLUOROSCOPY REPLACEMENT (RF ROOMS 1,2)
1-3 Brown wood pattern strip vinyl flooring Rooms 1226, 1227 and 1228 ND NA Good ~1,208 sf
4-6 Black cove base with tan mastic Rooms 1226, 1227 and 1228 ND NA Good ~190 lf
7-9 White 2’x2’ ceiling tiles Rooms 1226, 1227 and 1228 ND NA Good ~1,028 sf
10-14 Painted gypsum wallboard system with smooth finish Rooms 1226, 1227 and 1228 ND NA Good ~2,100 sf sf = square feet lf = linear feet ND = None Detected NA = Not Applicable Friable ACM are materials containing 1% or more asbestos that, when dry, may be crumbled, pulverized, or reduced to powder by hand pressure.
Category I ACM include nonfriable gaskets, packings, asphaltic roofing materials, and resilient flooring containing 1% asbestos or more.
Category II ACM include all other nonfriable materials containing 1% asbestos or more.
APPENDIX B
ASBESTOS ANALYTICAL LABORATORY REPORT
Micro Analytical Services, Inc. 11301 Richmond Ave. Ste.K100B♦Houston♦Tx 77082♦Phone(281)497-4500♦Fax(281)497-4517
NVLAP Lab Code: 200618-0 TDSHS License No. 30-0341
PLM BULK ASBESTOS ANALYSIS REPORT
CLIENT: Terracon MAS JOB NO.: 20105-00
PROJECT: SCP ACS SC Linear Accelerators Replacement (linear 1-2) REPORT DATE: September 17, 2025
TERRACON PROJECT: 92257961
IDENTIFICATION: Asbestos, Bulk Sample Analysis, Quantitation by Visual Area Estimation
TEST METHOD: Polarized Light Microscopy with Dispersion Staining EPA - 40 CFR Appendix E to Subpart E of Part 763, Interim Method of the Determination of Asbestos in Bulk Insulation Samples EPA - 600/R-93/116: Method for the Determination of Asbestos in Bulk Building Material
STATEMENT OF LABORATORY ACCREDITATION
These samples were analyzed at Micro Analytical Services, Inc. in the Asbestos Laboratory at 11301 Richmond Ave. Suite K100B, Houston, Texas, 77082. The Laboratory holds accreditation from the National Institute of Standards and Technology under the National Voluntary Laboratory Accreditation Program (NVLAP). This laboratory is also licensed and authorized to perform as an Asbestos Laboratory in the State of Texas within the purview of Texas Civil Statutes, Article 4477-3a, as amended, so long as this license is not suspended or revoked and is renewed according to the rules adopted by the Texas Board of Health.
The samples were analyzed in general accordance with the procedures outlined in the EPA - 40 CFR Appendix E to Subpart E of Part 763, Interim Method of the Determination of Asbestos in Bulk Insulation Samples, EPA - 600/R-93/116: Method for the Determination of Asbestos in Bulk Building Material, under AHERA, for the analysis of asbestos in building materials by polarized light microscopy. The results of each bulk sample relate only to the material tested as submitted to the laboratory and the results shall not be used to claim product endorsement by NVLAP or any agency of the U.S.
Government.
Specific questions concerning bulk sample results shall be directed to the Asbestos Bulk Laboratory at Micro Analytical Services, Inc.
Analyst: Tony T. Dang
Approved Signatory:
Micro Analytical Services, Inc. 11301 Richmond Ave. Ste. K100B♦Houston♦Texas 77082♦Phone(281) 497-4500♦Fax(281) 497-4517
Samples have been analyzed by the EPA - 40 CFR Appendix E to Subpart E of Part 763, Interim Method of the Determination of Asbestos in Bulk Insulation Samples, EPA - 600/R-93/116: Method for the Determination of Asbestos in Bulk Building Material. The test results herein relate only to the sample submitted and analyzed. This report may only be reproduced in full with the approval of the Bulk Asbestos Laboratory of Micro Analytical Services (MAS). The above percentages are visual estimates of area percent. MAS is not responsible for any errors resulting from improper or incorrect sampling or shipping procedures. These samples will be retained for a period of 30 days. Accreditation by NVLAP in no way constitutes or implies product certification, approval, or endorsement by NIST. Some materials, especially floor tiles, contain asbestos fibers too thin to be detected by this method. NVLAP Lab Code: 200618 TDSHS License: 30-0341
Analyzed by: Tony Dang Approved NVLAP Signatory: Tony Dang
Polarized Light Microscopy Analysis
Terracon . MAS Project #: 20105-00 11555 Clay Road Suite 100 Date Received: 09/16/2025 Houston, Texas 77043-1239 Date Analyzed: 09/17/2025
Project Name: SCP ACS SC Linear Accelerators Replacement (linear 1-2) Field ID/ Layer # Sample Description Asbestos Asbestos Non-Asbestos Lab ID Detected? Constituents Constituents (Yes/No) (%) (%) 1-FC3-1 1 Black non-fibrous cove base No 100% Vinyl
MAS615147
1-FC3-1 2 Beige non-fibrous mastic No 100% Mastic
MAS615147
1-FC3-2 1 Black non-fibrous cove base No 100% Vinyl
MAS615148
1-FC3-2 2 Beige non-fibrous mastic No 100% Mastic
MAS615148
1-FC3-3 1 Black non-fibrous cove base No 100% Vinyl
MAS615149
1-FC3-3 2 Beige non-fibrous mastic No 100% Mastic
MAS615149
2-FT5-4 1 Brown non-fibrous vinyl No 5% fibrous Glass MAS615150 floor tile 15% Synthetic 80% Other 2-FT5-4 2 Beige non-fibrous mastic No 100% Mastic
MAS615150
2-FT5-5 1 Brown non-fibrous vinyl No 5% fibrous Glass MAS615151 floor tile 15% Synthetic 80% Other 2-FT5-5 2 Beige non-fibrous mastic No 100% Mastic
MAS615151
2-FT5-6 1 Brown non-fibrous vinyl No 5% fibrous Glass MAS615152 floor tile 15% Synthetic 80% Other 2-FT5-6 2 Beige non-fibrous mastic No 100% Mastic
MAS615152
Micro Analytical Services, Inc. 11301 Richmond Ave. Ste. K100B♦Houston♦Texas 77082♦Phone(281) 497-4500♦Fax(281) 497-4517
Samples have been analyzed by the EPA - 40 CFR Appendix E to Subpart E of Part 763, Interim Method of the Determination of Asbestos in Bulk Insulation Samples, EPA - 600/R-93/116: Method for the Determination of Asbestos in Bulk Building Material. The test results herein relate only to the sample submitted and analyzed. This report may only be reproduced in full with the approval of the Bulk Asbestos Laboratory of Micro Analytical Services (MAS). The above percentages are visual estimates of area percent. MAS is not responsible for any errors resulting from improper or incorrect sampling or shipping procedures. These samples will be retained for a period of 30 days. Accreditation by NVLAP in no way constitutes or implies product certification, approval, or endorsement by NIST. Some materials, especially floor tiles, contain asbestos fibers too thin to be detected by this method. NVLAP Lab Code: 200618 TDSHS License: 30-0341
Lab ID Detected? Constituents Constituents (Yes/No) (%) (%) 3-FT2-7 1 Beige non-fibrous floor tile No 100% Other
MAS615153
3-FT2-7 2 Yellow non-fibrous mastic No 100% Mastic
MAS615153
3-FT2-8 1 Beige non-fibrous floor tile No 100% Other
MAS615154
3-FT2-8 2 Yellow non-fibrous mastic No 100% Mastic
MAS615154
3-FT2-9 1 Beige non-fibrous floor tile No 100% Other
MAS615155
3-FT2-9 2 Yellow non-fibrous mastic No 100% Mastic
MAS615155
4-CT-10 1 Beige fibrous ceiling tile No 10% Mineral Wool MAS615156 with white paint 40% Cellulose 30% Perlite 20% Other 4-CT-11 1 Beige fibrous ceiling tile No 10% Mineral Wool MAS615157 with white paint 40% Cellulose 30% Perlite 20% Other 4-CT-12 1 Beige fibrous ceiling tile No 10% Mineral Wool MAS615158 with white paint 40% Cellulose 30% Perlite 20% Other 5-WB4-13 1 White non-fibrous texture No 100% Other MAS615159 with white paint 5-WB4-13 2 White non-fibrous joint No 70% Cellulose MAS615159 compound with paper backing 30% Other
Micro Analytical Services, Inc. 11301 Richmond Ave. Ste. K100B♦Houston♦Texas 77082♦Phone(281) 497-4500♦Fax(281) 497-4517
Samples have been analyzed by the EPA - 40 CFR Appendix E to Subpart E of Part 763, Interim Method of the Determination of Asbestos in Bulk Insulation Samples, EPA - 600/R-93/116: Method for the Determination of Asbestos in Bulk Building Material. The test results herein relate only to the sample submitted and analyzed. This report may only be reproduced in full with the approval of the Bulk Asbestos Laboratory of Micro Analytical Services (MAS). The above percentages are visual estimates of area percent. MAS is not responsible for any errors resulting from improper or incorrect sampling or shipping procedures. These samples will be retained for a period of 30 days. Accreditation by NVLAP in no way constitutes or implies product certification, approval, or endorsement by NIST. Some materials, especially floor tiles, contain asbestos fibers too thin to be detected by this method. NVLAP Lab Code: 200618 TDSHS License: 30-0341
Lab ID Detected? Constituents Constituents (Yes/No) (%) (%) 5-WB4-13 3 White fibrous gypsum with No 40% Cellulose MAS615159 brown paper 60% Gypsum 5-WB4-14 1 White non-fibrous texture No 100% Other MAS615160 with white paint 5-WB4-14 2 White non-fibrous joint No 70% Cellulose MAS615160 compound with paper backing 30% Other 5-WB4-14 3 White fibrous gypsum with No 40% Cellulose MAS615160 brown paper 60% Gypsum 5-WB4-15 1 White non-fibrous texture No 100% Other MAS615161 with white paint 5-WB4-15 2 White non-fibrous joint No 70% Cellulose MAS615161 compound with paper backing 30% Other 5-WB4-15 3 White fibrous gypsum with No 40% Cellulose MAS615161 brown paper 60% Gypsum 5-WB4-16 1 White non-fibrous texture No 100% Other MAS615162 with white paint 5-WB4-16 2 White non-fibrous joint No 70% Cellulose MAS615162 compound with paper backing 30% Other 5-WB4-16 3 White fibrous gypsum with No 40% Cellulose MAS615162 brown paper 60% Gypsum 5-WB4-17 1 White non-fibrous texture No 100% Other MAS615163 with white paint 5-WB4-17 2 White non-fibrous joint No 70% Cellulose MAS615163 compound with paper backing 30% Other 5-WB4-17 3 White fibrous gypsum with No 40% Cellulose MAS615163 brown paper 60% Gypsum 5-WB4-18 1 White non-fibrous texture No 100% Other MAS615164 with white paint
Micro Analytical Services, Inc. 11301 Richmond Ave. Ste. K100B♦Houston♦Texas 77082♦Phone(281) 497-4500♦Fax(281) 497-4517
Samples have been analyzed by the EPA - 40 CFR Appendix E to Subpart E of Part 763, Interim Method of the Determination of Asbestos in Bulk Insulation Samples, EPA - 600/R-93/116: Method for the Determination of Asbestos in Bulk Building Material. The test results herein relate only to the sample submitted and analyzed. This report may only be reproduced in full with the approval of the Bulk Asbestos Laboratory of Micro Analytical Services (MAS). The above percentages are visual estimates of area percent. MAS is not responsible for any errors resulting from improper or incorrect sampling or shipping procedures. These samples will be retained for a period of 30 days. Accreditation by NVLAP in no way constitutes or implies product certification, approval, or endorsement by NIST. Some materials, especially floor tiles, contain asbestos fibers too thin to be detected by this method. NVLAP Lab Code: 200618 TDSHS License: 30-0341
Lab ID Detected? Constituents Constituents (Yes/No) (%) (%) 5-WB4-18 2 White non-fibrous joint No 70% Cellulose MAS615164 compound with paper backing 30% Other 5-WB4-18 3 White fibrous gypsum with No 40% Cellulose MAS615164 brown paper 60% Gypsum 5-WB4-19 1 White non-fibrous texture No 100% Other MAS615165 with white paint 5-WB4-19 2 White non-fibrous joint No 70% Cellulose MAS615165 compound with paper backing 30% Other 5-WB4-19 3 White fibrous gypsum with No 40% Cellulose MAS615165 brown paper 60% Gypsum
Micro Analytical Services, Inc. 11301 Richmond Ave. Ste.K100B♦Houston♦Tx 77082♦Phone(281)497-4500♦Fax(281)497-4517
CLIENT: Terracon MAS JOB NO.: 20107-00
PROJECT: SCP ACS SC RAD Fluoroscopy Replacement REPORT DATE: September 17, 2025
TEST METHOD: Polarized Light Microscopy with Dispersion Staining EPA - 40 CFR Appendix E to Subpart E of Part 763, Interim Method of the
These samples were analyzed at Micro Analytical Services, Inc. in the Asbestos Laboratory at 11301 Richmond Ave. Suite K100B, Houston, Texas, 77082. The Laboratory holds accreditation from the National Institute of Standards and Technology under the National Voluntary Laboratory Accreditation Program (NVLAP). This laboratory is also licensed and authorized to perform as an Asbestos Laboratory in the State of Texas within the purview of Texas Civil Statutes, Article 4477-3a, as amended, so long as this license is not suspended or revoked and is renewed according to the rules adopted by the Texas Board of Health.
The samples were analyzed in general accordance with the procedures outlined in the EPA - 40 CFR Appendix E to Subpart E of Part 763, Interim Method of the Determination of Asbestos in Bulk Insulation Samples, EPA - 600/R-93/116: Method for the Determination of Asbestos in Bulk Building Material, under AHERA, for the analysis of asbestos in building materials by polarized light microscopy. The results of each bulk sample relate only to the material tested as submitted to the laboratory and the results shall not be used to claim product endorsement by NVLAP or any agency of the U.S.
Government.
Specific questions concerning bulk sample results shall be directed to the Asbestos Bulk Laboratory at Micro Analytical
Micro Analytical Services, Inc. 11301 Richmond Ave. Ste. K100B♦Houston♦Texas 77082♦Phone(281) 497-4500♦Fax(281) 497-4517
Samples have been analyzed by the EPA - 40 CFR Appendix E to Subpart E of Part 763, Interim Method of the Determination of Asbestos in Bulk Insulation Samples, EPA - 600/R-93/116: Method for the Determination of Asbestos in Bulk Building Material. The test results herein relate only to the sample submitted and analyzed. This report may only be reproduced in full with the approval of the Bulk Asbestos Laboratory of Micro Analytical Services (MAS). The above percentages are visual estimates of area percent. MAS is not responsible for any errors resulting from improper or incorrect sampling or shipping procedures. These samples will be retained for a period of 30 days. Accreditation by NVLAP in no way constitutes or implies product certification, approval, or endorsement by NIST. Some materials, especially floor tiles, contain asbestos fibers too thin to be detected by this method. NVLAP Lab Code: 200618 TDSHS License: 30-0341
Terracon . MAS Project #: 20107-00
Project Name: SCP ACS SC RAD Fluoroscopy Replacement
Lab ID Detected? Constituents Constituents (Yes/No) (%) (%) 1-FT5-1 1 Brown fibrous vinyl floor tile No 5% fibrous Glass MAS615189 15% Synthetic 80% Vinyl 1-FT5-1 2 Beige non-fibrous mastic No 100% Mastic
MAS615189
1-FT5-1 3 Grey fibrous floor substrate No 3% Cellulose MAS615189 97% Other 1-FT5-2 1 Brown fibrous vinyl floor tile No 5% fibrous Glass MAS615190 15% Synthetic 80% Vinyl 1-FT5-2 2 Beige non-fibrous mastic No 100% Mastic
MAS615190
1-FT5-2 3 Grey fibrous floor substrate No 3% Cellulose MAS615190 97% Other 1-FT5-3 1 Brown fibrous vinyl floor tile No 5% fibrous Glass MAS615191 15% Synthetic 80% Vinyl 1-FT5-3 2 Beige non-fibrous mastic No 100% Mastic
MAS615191
1-FT5-3 3 Grey fibrous floor substrate No 3% Cellulose MAS615191 97% Other 2-FC3-4 1 Black non-fibrous cove base No 100% Vinyl
MAS615192
2-FC3-4 2 Beige non-fibrous mastic No 100% Mastic
MAS615192
2-FC3-5 1 Black non-fibrous cove base No 100% Vinyl
MAS615193
Micro Analytical Services, Inc. 11301 Richmond Ave. Ste. K100B♦Houston♦Texas 77082♦Phone(281) 497-4500♦Fax(281) 497-4517
Samples have been analyzed by the EPA - 40 CFR Appendix E to Subpart E of Part 763, Interim Method of the Determination of Asbestos in Bulk Insulation Samples, EPA - 600/R-93/116: Method for the Determination of Asbestos in Bulk Building Material. The test results herein relate only to the sample submitted and analyzed. This report may only be reproduced in full with the approval of the Bulk Asbestos Laboratory of Micro Analytical Services (MAS). The above percentages are visual estimates of area percent. MAS is not responsible for any errors resulting from improper or incorrect sampling or shipping procedures. These samples will be retained for a period of 30 days. Accreditation by NVLAP in no way constitutes or implies product certification, approval, or endorsement by NIST. Some materials, especially floor tiles, contain asbestos fibers too thin to be detected by this method. NVLAP Lab Code: 200618 TDSHS License: 30-0341
Lab ID Detected? Constituents Constituents (Yes/No) (%) (%) 2-FC3-4 2 Beige non-fibrous mastic No 100% Mastic
MAS615192
2-FC3-5 1 Black non-fibrous cove base No 100% Vinyl
MAS615193
2-FC3-5 2 Beige non-fibrous mastic No 100% Mastic
MAS615193
2-FC3-6 1 Black non-fibrous cove base No 100% Vinyl
MAS615194
2-FC3-6 2 Beige non-fibrous mastic No 100% Mastic
MAS615194
3-CT3-7 1 Beige fibrous ceiling tile No 10% fibrous Glass MAS615195 with white paint 40% Cellulose 30% Perlite 20% Other 3-CT3-8 1 Beige fibrous ceiling tile No 10% fibrous Glass MAS615196 with white paint 40% Cellulose 30% Perlite 20% Other 3-CT3-9 1 Beige fibrous ceiling tile No 10% fibrous Glass MAS615197 with white paint 40% Cellulose 30% Perlite 20% Other 4-WB4-10 1 White non-fibrous texture No 100% Other MAS615198 with white paint 4-WB4-10 2 White non-fibrous joint No 70% Cellulose MAS615198 compound with beige paper 30% Other 4-WB4-10 3 White fibrous gypsum with No 60% Cellulose MAS615198 brown paper 40% Gypsum
Micro Analytical Services, Inc. 11301 Richmond Ave. Ste. K100B♦Houston♦Texas 77082♦Phone(281) 497-4500♦Fax(281) 497-4517
Samples have been analyzed by the EPA - 40 CFR Appendix E to Subpart E of Part 763, Interim Method of the Determination of Asbestos in Bulk Insulation Samples, EPA - 600/R-93/116: Method for the Determination of Asbestos in Bulk Building Material. The test results herein relate only to the sample submitted and analyzed. This report may only be reproduced in full with the approval of the Bulk Asbestos Laboratory of Micro Analytical Services (MAS). The above percentages are visual estimates of area percent. MAS is not responsible for any errors resulting from improper or incorrect sampling or shipping procedures. These samples will be retained for a period of 30 days. Accreditation by NVLAP in no way constitutes or implies product certification, approval, or endorsement by NIST. Some materials, especially floor tiles, contain asbestos fibers too thin to be detected by this method. NVLAP Lab Code: 200618 TDSHS License: 30-0341
Lab ID Detected? Constituents Constituents (Yes/No) (%) (%) 4-WB4-11 1 White non-fibrous texture No 100% Other MAS615199 with white paint 4-WB4-11 2 White non-fibrous joint No 70% Cellulose MAS615199 compound with beige paper 30% Other 4-WB4-11 3 White fibrous gypsum with No 60% Cellulose MAS615199 brown paper 40% Gypsum 4-WB4-12 1 White non-fibrous texture No 100% Other MAS615200 with white paint 4-WB4-12 2 White non-fibrous joint No 70% Cellulose MAS615200 compound with beige paper 30% Other 4-WB4-12 3 White fibrous gypsum with No 60% Cellulose MAS615200 brown paper 40% Gypsum 4-WB4-13 1 White non-fibrous texture No 100% Other MAS615201 with white paint 4-WB4-13 2 White non-fibrous joint No 70% Cellulose MAS615201 compound with beige paper 30% Other 4-WB4-13 3 White fibrous gypsum with No 60% Cellulose MAS615201 brown paper 40% Gypsum 4-WB4-14 1 White non-fibrous texture No 100% Other MAS615202 with white paint 4-WB4-14 2 White non-fibrous joint No 70% Cellulose MAS615202 compound with beige paper 30% Other 4-WB4-14 3 White fibrous gypsum with No 60% Cellulose MAS615202 brown paper 40% Gypsum
Micro Analytical Services, Inc. 11301 Richmond Ave. Ste.K100B♦Houston♦Tx 77082♦Phone(281)497-4500♦Fax(281)497-4517
CLIENT: Terracon MAS JOB NO.: 20106-00
PROJECT: SCP ACS SC CT Scans (1-3) And CT Simulator Replacement REPORT DATE: September 17, 2025
TEST METHOD: Polarized Light Microscopy with Dispersion Staining EPA - 40 CFR Appendix E to Subpart E of Part 763, Interim Method of the
These samples were analyzed at Micro Analytical Services, Inc. in the Asbestos Laboratory at 11301 Richmond Ave. Suite K100B, Houston, Texas, 77082. The Laboratory holds accreditation from the National Institute of Standards and Technology under the National Voluntary Laboratory Accreditation Program (NVLAP). This laboratory is also licensed and authorized to perform as an Asbestos Laboratory in the State of Texas within the purview of Texas Civil Statutes, Article 4477-3a, as amended, so long as this license is not suspended or revoked and is renewed according to the rules adopted by the Texas Board of Health.
The samples were analyzed in general accordance with the procedures outlined in the EPA - 40 CFR Appendix E to Subpart E of Part 763, Interim Method of the Determination of Asbestos in Bulk Insulation Samples, EPA - 600/R-93/116: Method for the Determination of Asbestos in Bulk Building Material, under AHERA, for the analysis of asbestos in building materials by polarized light microscopy. The results of each bulk sample relate only to the material tested as submitted to the laboratory and the results shall not be used to claim product endorsement by NVLAP or any agency of the U.S.
Government.
Specific questions concerning bulk sample results shall be directed to the Asbestos Bulk Laboratory at Micro Analytical
Micro Analytical Services, Inc. 11301 Richmond Ave. Ste. K100B♦Houston♦Texas 77082♦Phone(281) 497-4500♦Fax(281) 497-4517
Samples have been analyzed by the EPA - 40 CFR Appendix E to Subpart E of Part 763, Interim Method of the Determination of Asbestos in Bulk Insulation Samples, EPA - 600/R-93/116: Method for the Determination of Asbestos in Bulk Building Material. The test results herein relate only to the sample submitted and analyzed. This report may only be reproduced in full with the approval of the Bulk Asbestos Laboratory of Micro Analytical Services (MAS). The above percentages are visual estimates of area percent. MAS is not responsible for any errors resulting from improper or incorrect sampling or shipping procedures. These samples will be retained for a period of 30 days. Accreditation by NVLAP in no way constitutes or implies product certification, approval, or endorsement by NIST. Some materials, especially floor tiles, contain asbestos fibers too thin to be detected by this method. NVLAP Lab Code: 200618 TDSHS License: 30-0341
Terracon . MAS Project #: 20106-00
Project Name: SCP ACS SC CT Scans (1-3) And CT Simulator Replacement
Lab ID Detected? Constituents Constituents (Yes/No) (%) (%) 1-FC3-1 1 Black non-fibrous cove base No 100% Vinyl
MAS615166
1-FC3-1 2 Beige non-fibrous mastic No 100% Mastic
MAS615166
1-FC3-2 1 Black non-fibrous cove base No 100% Vinyl
MAS615167
1-FC3-2 2 Beige non-fibrous mastic No 100% Mastic
MAS615167
1-FC3-3 1 Black non-fibrous cove base No 100% Vinyl
MAS615168
1-FC3-3 2 Beige non-fibrous mastic No 100% Mastic
MAS615168
2-FT5-4 1 Brown fibrous vinyl floor tile No 5% fibrous Glass MAS615169 15% Synthetic 80% Vinyl 2-FT5-4 2 Beige non-fibrous mastic No 100% Mastic
MAS615169
2-FT5-4 3 Grey fibrous floor substrate No 2% Cellulose MAS615169 98% Other 2-FT5-5 1 Brown fibrous vinyl floor tile No 5% fibrous Glass MAS615170 15% Synthetic 80% Vinyl
2-FT5-5 2 Beige non-fibrous mastic No 100% Mastic
MAS615170
2-FT5-5 3 Grey fibrous floor substrate No 2% Cellulose MAS615170 98% Other
Micro Analytical Services, Inc. 11301 Richmond Ave. Ste. K100B♦Houston♦Texas 77082♦Phone(281) 497-4500♦Fax(281) 497-4517
Samples have been analyzed by the EPA - 40 CFR Appendix E to Subpart E of Part 763, Interim Method of the Determination of Asbestos in Bulk Insulation Samples, EPA - 600/R-93/116: Method for the Determination of Asbestos in Bulk Building Material. The test results herein relate only to the sample submitted and analyzed. This report may only be reproduced in full with the approval of the Bulk Asbestos Laboratory of Micro Analytical Services (MAS). The above percentages are visual estimates of area percent. MAS is not responsible for any errors resulting from improper or incorrect sampling or shipping procedures. These samples will be retained for a period of 30 days. Accreditation by NVLAP in no way constitutes or implies product certification, approval, or endorsement by NIST. Some materials, especially floor tiles, contain asbestos fibers too thin to be detected by this method. NVLAP Lab Code: 200618 TDSHS License: 30-0341
Lab ID Detected? Constituents Constituents (Yes/No) (%) (%) 2-FT5-6 1 Brown fibrous vinyl floor tile No 5% fibrous Glass MAS615171 15% Synthetic 80% Vinyl 2-FT5-6 2 Beige non-fibrous mastic No 100% Mastic
MAS615171
2-FT5-6 3 Grey fibrous floor substrate No 2% Cellulose MAS615171 98% Other 3-WB4-7 1 White non-fibrous texture No 70% Cellulose MAS615172 with tan paint 30% Other 3-WB4-7 2 White non-fibrous joint No 70% Cellulose MAS615172 compound with beige paper 30% Other 3-WB4-7 3 White fibrous gypsum with No 40% Cellulose MAS615172 brown paper 60% Gypsum 3-WB4-8 1 White non-fibrous texture No 70% Cellulose MAS615173 with tan paint 30% Other 3-WB4-8 2 White non-fibrous joint No 70% Cellulose MAS615173 compound with beige paper 30% Other 3-WB4-8 3 White fibrous gypsum with No 40% Cellulose MAS615173 brown paper 60% Gypsum 3-WB4-9 1 White non-fibrous texture No 70% Cellulose MAS615174 with tan paint 30% Other 3-WB4-9 2 White non-fibrous joint No 70% Cellulose MAS615174 compound with beige paper 30% Other 3-WB4-9 3 White fibrous gypsum with No 40% Cellulose MAS615174 brown paper 60% Gypsum 3-WB4-10 1 White non-fibrous texture No 70% Cellulose MAS615175 with tan paint 30% Other
Micro Analytical Services, Inc. 11301 Richmond Ave. Ste. K100B♦Houston♦Texas 77082♦Phone(281) 497-4500♦Fax(281) 497-4517
Samples have been analyzed by the EPA - 40 CFR Appendix E to Subpart E of Part 763, Interim Method of the Determination of Asbestos in Bulk Insulation Samples, EPA - 600/R-93/116: Method for the Determination of Asbestos in Bulk Building Material. The test results herein relate only to the sample submitted and analyzed. This report may only be reproduced in full with the approval of the Bulk Asbestos Laboratory of Micro Analytical Services (MAS). The above percentages are visual estimates of area percent. MAS is not responsible for any errors resulting from improper or incorrect sampling or shipping procedures. These samples will be retained for a period of 30 days. Accreditation by NVLAP in no way constitutes or implies product certification, approval, or endorsement by NIST. Some materials, especially floor tiles, contain asbestos fibers too thin to be detected by this method. NVLAP Lab Code: 200618 TDSHS License: 30-0341
Lab ID Detected? Constituents Constituents (Yes/No) (%) (%) 3-WB4-10 2 White non-fibrous joint No 70% Cellulose MAS615175 compound with beige paper 30% Other 3-WB4-10 3 White fibrous gypsum with No 40% Cellulose MAS615175 brown paper 60% Gypsum 3-WB4-11 1 White non-fibrous texture No 70% Cellulose MAS615176 with tan paint 30% Other 3-WB4-11 2 White non-fibrous joint No 70% Cellulose MAS615176 compound with beige paper 30% Other 3-WB4-11 3 White fibrous gypsum with No 40% Cellulose MAS615176 brown paper 60% Gypsum 4-CT3-12 1 Beige fibrous ceiling tile with No 10% Mineral Wool MAS615177 white paint 40% Cellulose 30% Perlite 20% Other 4-CT3-13 1 Beige fibrous ceiling tile with No 10% Mineral Wool MAS615178 white paint 40% Cellulose 30% Perlite 20% Other 4-CT3-14 1 Beige fibrous ceiling tile with No 10% Mineral Wool MAS615179 white paint 40% Cellulose 30% Perlite 20% Other 5-WB4-15 1 White non-fibrous texture No 100% Other MAS615180 with beige paint 5-WB4-15 2 White non-fibrous joint No 70% Cellulose MAS615180 compound with beige paper 30% Other 5-WB4-15 3 White fibrous gypsum with No 70% Cellulose MAS615180 brown paper 30% Gypsum
Micro Analytical Services, Inc. 11301 Richmond Ave. Ste. K100B♦Houston♦Texas 77082♦Phone(281) 497-4500♦Fax(281) 497-4517
Samples have been analyzed by the EPA - 40 CFR Appendix E to Subpart E of Part 763, Interim Method of the Determination of Asbestos in Bulk Insulation Samples, EPA - 600/R-93/116: Method for the Determination of Asbestos in Bulk Building Material. The test results herein relate only to the sample submitted and analyzed. This report may only be reproduced in full with the approval of the Bulk Asbestos Laboratory of Micro Analytical Services (MAS). The above percentages are visual estimates of area percent. MAS is not responsible for any errors resulting from improper or incorrect sampling or shipping procedures. These samples will be retained for a period of 30 days. Accreditation by NVLAP in no way constitutes or implies product certification, approval, or endorsement by NIST. Some materials, especially floor tiles, contain asbestos fibers too thin to be detected by this method. NVLAP Lab Code: 200618 TDSHS License: 30-0341
Lab ID Detected? Constituents Constituents (Yes/No) (%) (%) 5-WB4-16 1 White non-fibrous texture No 100% Other MAS615181 with beige paint 5-WB4-16 2 White non-fibrous joint No 70% Cellulose MAS615181 compound with beige paper 30% Other 5-WB4-16 3 White fibrous gypsum with No 70% Cellulose MAS615181 brown paper 30% Gypsum 5-WB4-17 1 White non-fibrous texture No 100% Other MAS615182 with beige paint 5-WB4-17 2 White non-fibrous joint No 70% Cellulose MAS615182 compound with beige paper 30% Other 5-WB4-17 3 White fibrous gypsum with No 70% Cellulose MAS615182 brown paper 30% Gypsum 6-MA5-18 1 Beige non-fibrous ceramic No 100% Other MAS615183 tile 6-MA5-18 2 Beige non-fibrous mortar No 80% Aggregate MAS615183 20% Other 6-MA5-19 1 Beige non-fibrous ceramic No 100% Other MAS615184 tile 6-MA5-19 2 Beige non-fibrous mortar No 80% Aggregate MAS615184 20% Other 6-MA5-20 1 Beige non-fibrous ceramic No 100% Other MAS615185 tile 6-MA5-20 2 Beige non-fibrous mortar No 80% Aggregate MAS615185 20% Other 7-FT5-21 1 Beige non-fibrous ceramic No 100% Other MAS615186 tile 7-FT5-21 2 Grey non-fibrous mortar No 70% Aggregate MAS615186 30% Other
Micro Analytical Services, Inc. 11301 Richmond Ave. Ste. K100B♦Houston♦Texas 77082♦Phone(281) 497-4500♦Fax(281) 497-4517
Samples have been analyzed by the EPA - 40 CFR Appendix E to Subpart E of Part 763, Interim Method of the Determination of Asbestos in Bulk Insulation Samples, EPA - 600/R-93/116: Method for the Determination of Asbestos in Bulk Building Material. The test results herein relate only to the sample submitted and analyzed. This report may only be reproduced in full with the approval of the Bulk Asbestos Laboratory of Micro Analytical Services (MAS). The above percentages are visual estimates of area percent. MAS is not responsible for any errors resulting from improper or incorrect sampling or shipping procedures. These samples will be retained for a period of 30 days. Accreditation by NVLAP in no way constitutes or implies product certification, approval, or endorsement by NIST. Some materials, especially floor tiles, contain asbestos fibers too thin to be detected by this method. NVLAP Lab Code: 200618 TDSHS License: 30-0341
Lab ID Detected? Constituents Constituents (Yes/No) (%) (%) 7-FT5-22 1 Beige non-fibrous ceramic No 100% Other MAS615187 tile 7-FT5-22 2 Grey non-fibrous mortar No 70% Aggregate MAS615187 30% Other 7-FT5-23 1 Beige non-fibrous ceramic No 100% Other MAS615188 tile 7-FT5-23 2 Grey non-fibrous mortar No 70% Aggregate MAS615188 30% Other
APPENDIX C
SAMPLE LOCATION MAP
STEWAM7
Polygon
STEWAM7
Polygon
STEWAM7
Polygon
STEWAM7
Rectangle
STEWAM7
Text Box 1st Phase
STEWAM7
Rectangle
STEWAM7
Rectangle
STEWAM7
Rectangle
STEWAM7
Rectangle
STEWAM7
Rectangle
STEWAM7
Text Box 2nd Phase
STEWAM7
Polygon
STEWAM7
Polygon
STEWAM7
Rectangle
STEWAM7
Rectangle
STEWAM7
Text Box 3rd Phase
STEWAM7
Rectangle
STEWAM7
Rectangle
STEWAM7
Rectangle
STEWAM7
Polygon
STEWAM7
Rectangle
STEWAM7
Text Box 4th Phase
STEWAM7
Line
STEWAM7
Line
STEWAM7
Rectangle
STEWAM7
Rectangle
STEWAM7
Rectangle
STEWAM7
Rectangle
STEWAM7
Rectangle
STEWAM7
Text Box Mobile PET CT
STEWAM7
Line
STEWAM7
Ellipse
STEWAM7
Ellipse
STEWAM7
Arc
STEWAM7
Arc
STEWAM7
Arc
STEWAM7
Arc
STEWAM7
Line
STEWAM7
Arc
STEWAM7
Arc
STEWAM7
Arc
STEWAM7
Line
STEWAM7
Text Box Exist.
Staff Patio
STEWAM7
Arc
STEWAM7
Line
STEWAM7
Line
STEWAM7
Rectangle
STEWAM7
Arc
STEWAM7
Arc
STEWAM7
Line
STEWAM7
Cloud
STEWAM7
Cloud
STEWAM7
Text Box COMBINE ALL 4 CT's TOGETHER
[24-3SCP01995]
STEWAM7
Text Box LINEAR ACCELERATORS - COMBINE ALL 3 LIN.ACCs [24-3SCP01994]
STEWAM7
Text Box COMBINE GEN RAD and R/F 1 & 2. [24-3SCP01998]
STEWAM7
Cloud
STEWAM7
Rectangle
STEWAM7
Rectangle
STEWAM7
Area Measurement
451.24 sf
STEWAM7
Area Measurement
384.93 sf
STEWAM7
Area Measurement
387.1 sf
STEWAM7
Area Measurement
295.69 sf
STEWAM7
Area Measurement
366.91 sf
STEWAM7
Area Measurement
366.94 sf
STEWAM7
Area Measurement
386.11 sf
STEWAM7
Area Measurement
158.45 sf
STEWAM7
Area Measurement
160.85 sf
STEWAM7
Area Measurement
206.75 sf
STEWAM7
Area Measurement 1,043.85 sf
STEWAM7
Area Measurement
994.52 sf
STEWAM7
Area Measurement
988.83 sf
Hernandez, Jonathan2 Callout 1, 4, 13, 14
Hernandez, Jonathan2 Callout 7, 15
Hernandez, Jonathan2 Callout 2, 10
Hernandez, Jonathan2 Callout 2, 10
Hernandez, Jonathan2 Callout
Hernandez, Jonathan2 Callout 5, 16, 17
Hernandez, Jonathan2 Callout
Hernandez, Jonathan2 Callout 3, 6, 19
Hernandez, Jonathan2 Callout 9, 18
Hernandez, Jonathan2 Callout
Hernandez, Jonathan2 Callout 2, 5, 12, 13
Hernandez, Jonathan2 Callout
Hernandez, Jonathan2 Callout
Hernandez, Jonathan2 Callout 3, 6, 14
Hernandez, Jonathan2 Callout 1, 4, 10, 11
Hernandez, Jonathan2 Callout 1, 4, 10, 11
Hernandez, Jonathan2 Callout
Hernandez, Jonathan2 Callout 1, 12
Hernandez, Jonathan2 Callout 4, 7, 8
Hernandez, Jonathan2 Callout 2, 11, 13
Hernandez, Jonathan2 Callout 15-23
Hernandez, Jonathan2 Callout 3, 6, 9, 10
Hernandez, Jonathan2 Callout
Interior POC Asbestos Inspection Report
September 19, 2025 | Terracon Project No. 92257965
APPENDIX D
SITE PHOTOGRAPHS
September 19, 2025 | Terracon Project No. 92257965
Photo #1 Exterior view of the Linear Accelerator room
Photo #2 Interior view of the Linear Accelerator room
Photo #3 Additional interior view of the Linear Accelerator room
Photo #4 View of the Linear Accelerator Control Room
Photo #5 Exterior view of the RF Rooms Photo #6 Interior view of the RF Rooms
September 19, 2025 | Terracon Project No. 92257965
Photo #7 Additional interior view of the RF Rooms
Photo #8 View of the corridor inside/between the RF Rooms
Photo #9 Exterior view of the CT scan rooms Photo #10 General interior view of the CT scan rooms
Photo #11 View of the CT Scan rooms controls Photo #12 View of the restroom inside CT scan 1
September 19, 2025 | Terracon Project No. 92257965
APPENDIX E
LICENSES & CERTIFICATIONS
September 19, 2025 | Terracon Project No. 92257965