This is a limited asbestos, lead, and hazardous materials inspection and survey report prepared for the Southern Utah University America First Events Center (AFEC) Air Handlers 7 & 8 located at 351 West Center Street in Cedar City, Utah 84720. The survey was conducted in August 2026 by R & R Environmental, Inc. of Sandy, Utah on behalf of the Utah Department of Government Operations, Division of Facilities, Construction and Management (DFCM), with Aubrey Stapel serving as the Hazmat Program Manager. The survey involved visual assessment and bulk sampling of suspect asbestos-containing materials (ACM) from the air handler rooms scheduled for replacement. Twenty-five representative samples were collected from various materials and submitted for analysis via Polarized Light Microscopy (PLM) to Reservoirs Environmental, Inc., an NVLAP-accredited laboratory in Denver, Colorado.
The survey identified asbestos-containing materials in the building, specifically 7% Chrysotile in pin adhesive covering over 350 square feet in undamaged condition and 1% asbestos in pipe thread sealant covering approximately 25 square feet. All other tested materials—including silver caulk, black/gray caulk, and thermal system insulation mudding—showed no asbestos detection. The survey was conducted by Trevor Thacker, a Utah Certified Asbestos Building Inspector (Certification Number ASB-8872), and reviewed by David C. Roskelley, MSPH, CIH, CSP (Certification Number ASB-1370), both representing R & R Environmental, Inc. under State of Utah Company Certification ASBC-237. The report concludes that identified asbestos-containing materials must be removed prior to disturbance by a licensed abatement contractor before the air handler replacement project, which carries a construction cost estimate of $1,274,789.00, can proceed.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ASBESTOS (LIMITED), LEAD (LIMITED), AND HAZARDOUS MATERIALS
INSPECTION, SURVEY AND ASSESSMENT
FOR THE
SOUTHERN UTAH UNIVERSITY
AMERICA FIRST EVENTS CENTER (AFEC)
AIR HANDLERS 7 & 8
351 WEST CENTER STREET
CEDAR CITY, UTAH 84720
A LIMITED ASBESTOS SURVEY AND ASSESSMENT
FOR THE
SOUTHERN UTAH UNIVERSITY
AMERICA FIRST EVENTS CENTER (AFEC)
AIR HANDLERS 7 & 8
September 10, 2026
Prepared for:
Mrs. Aubrey Stapel Hazmat Program Manager
Utah Department of Government Operations Division of Facilities, Construction and Management (DFCM)
Taylorsville State Office Building, 3rd Floor 4315 South 2700 West
Taylorsville, Utah 84114
PH: (801) 641-0964
Prepared by:
R & R Environmental, Inc. (R & R) 47 West 9000 South, Suite #2
Sandy, Utah 84070 jamison@rrenviro.com Phone (801) 928-1560
TABLE OF CONTENTS
ASBESTOS
1.0 INTRODUCTION
2.0 EXECUTIVE SUMMARY
3.0 SAMPLING METHODS
4.0 SURVEY RESULTS
5.0 CONCLUSIONS
6.0 LIMITATIONS AND EXCLUSION OF WARRANTY.……………………………………………………6
List of Appendices
Appendix A Sample Log
Appendix B Laboratory Report
Appendix C Photo Log
Appendix D Floor Plans
Appendix E State of Utah Certifications
Asbestos Survey Report Page 1
SUU, AFEC
Air Handlers 7 & 8
1.0 INTRODUCTION
R & R Environmental, Inc. (R & R) was contacted to conduct a limited asbestos survey for the Southern Utah University, America First Event Center, Air Handlers 7 & 8 located at 351 West Center Street in Cedar City, Utah 84720. The air handlers 7 and 8 scheduled to be replaced. The survey consisted of a visual assessment of the building for suspect asbestos containing materials (ACM) and bulk sampling of the materials. The fieldwork component of this survey was conducted by Mr. Trevor Thacker who is a Utah Certified Asbestos Building Inspector.
This report presents the conditions and observations noted on the visit dates.
The following general information is included in this survey report:
• Executive Summary (Section 2.0)
• Sampling Methods (Section 3.0)
• Analytical Results (Section 4.0)
• Conclusions (5.0)
• Limitations & Exclusion of Warranty (6.0)
Asbestos Survey Report Page 2
2.0 EXECUTIVE SUMMARY
The following material(s) containing asbestos or assumed to contain asbestos were identified during this limited survey.
Material/ Homogenous Area
Sample Location
Quantity
Lab Result (%/Type)
Assessment
Friable
Y/N
Pin Adhesive Air Handler
Rm 7, 8 >350 ft2 7% Chrysotile Undamaged No
Pipe Thread Sealant Air Handler
Rm 7, 8 ~25 ft2
<0.25% Trem/Act (By Point Count)
Undamaged No
Asbestos Survey Report Page 3
SOUTHERN UTAH UNIVERSITY, AMERICA FIRST EVENT CENTER
351 WEST CENTER STREET, CEDAR CITY, UTAH 84720
DATE OF SURVEY: AUGUST 2026
NESHAP - REGULATED
ASBESTOS-CONTAINING MATERIALS (R-ACM)
1. Friable asbestos material (>1% asbestos and can be crumbled, pulverized, or reduced to powder by hand pressure) Thermal system insulation (TSI)* Textured ceiling material (TCM)* (Wallpaper) Spray-on insulation or fireproofing* Blown-in insulation* Ceiling tiles/panels* Plaster, gypsum board, gypsum board joint compound* (Plaster & Concrete Surfacing) Cloth materials* (Boiler Flue Gasket) Paper materials* (HVAC Paper Tape and Insulating Board) Electrical wiring insulation* Sink undercoating (loose)* Other* (Boiler & Fire Rated Curtain)
2. Category I ACM which has become friable
Packings Gaskets Resilient floor coverings (floor tile and sheet vinyl) Asphalt roofing products (Dust Debris, Roofing Underlayment Debris, Flashing Material)
3. Category I ACM that will be or has been subjected to sanding, grinding, cutting, or abrading
Packings Gaskets Resilient floor coverings (floor tile and sheet vinyl) Asphalt roofing products
4. Category II ACM that has a high probability of becoming or has become friable during demolition or renovation operations Asbestos cement materials (TransiteT)* Asphalt, tar and rubber-base ACM products other than roofing products* Non-asphalt and non-paper roofing products* Paint* Fire brick and/or mortar* Stainless steel sink undercoating (solid)* Encapsulated TCM* Encapsulated TSI* X Mastic for floor tile, ceiling tile, cove molding, etc.* Other (Fire Rated Door/Frame)
Asbestos Survey Report Page 4
SOUTHERN UTAH UNIVERSITY, AMERICA FIRST EVENT CENTER
351 WEST CENTER STREET, CEDAR CITY, UTAH 84720
DATE OF SURVEY: AUGUST 2026
NESHAP NON-REGULATED
ASBESTOS-CONTAINING MATERIAL (N-R-ACM)
1. > 1% asbestos
2. Category I Non-friable (cannot be crumbled, pulverized, or reduced to powder by hand pressure) ACM with >1% asbestos by new PLM procedure Packings (Caulk and Window Glazing) X Gaskets (Pipe Thread Sealant) Resilient floor coverings (Floor Tile) Asphalt roofing products
3. Category II Non-friable ACM with >1% asbestos by new PLM procedure (Category includes items meeting Category I definition but not specifically listed in that category) Asbestos cement materials (TransiteT)* (Fume hoods, counter tops, and window panels) Asphalt, tar and rubber-base ACM products other than roofing products* Non-asphalt and non-paper roofing products* Paint* (Silver Paint Sealant) Fire brick and/or mortar* Sink undercoating (solid)* Mastic for floor tile, ceiling tile, cove molding, etc.* Other*
Notes:
1. (*) Denotes R&R’s interpretation of materials included in this category.
2. New PLM procedure is outlined in Appendix A, Subpart F, 40 CFR, Part 783, Section 1, Polarized
Light Microscopy.
3. The Environmental Protection Agency (EPA) National Emission Standard for Hazardous Air
Pollutants (NESHAP) asbestos revision as outlined in 40 CFR, Part 61, became effective November 20, 1990. The asbestos classification system outlined in the revision and included in this section is dynamic in nature. Asbestos materials classified as “NON-REGULATED” at the time of the survey may become “REGULATED” due to ongoing or planned maintenance, renovation, or demolition actions, which can transform a material containing greater than 1% asbestos from a “non-friable” and NON-REGULATED to a friable and REGULATED condition. Classification of ACM in this section and in the executive summary of this report is, therefore, based on the observations of the surveyor at the time of the survey and may or may not be appropriate at later dates.
4. Maintenance, renovation, demolition, weathering, normal wear, water, or other damage can alter the “NON-REGULATED” status of materials, and necessitate precautions required for handling them as “REGULATED” asbestos-materials.
Asbestos Survey Report Page 5
3.0 SAMPLING METHODS
Survey procedures were based on those outlined in Title 40 Code of Federal Regulation (CFR) Part 763, USEPA Asbestos Hazard Emergency Response Act, and the Asbestos Model Accreditation Plan (effective April 4, 1994). The procedures included visual observation, physical inspection, bulk sample collection, and condition assessment of suspect ACM. The number of samples collected was based on the amount and accessibility of each homogeneous material, with consideration given for the type, age, and condition.
Twenty-five (25) samples were collected from the suspect materials to assess the presence of asbestos (or lack thereof) in building materials/systems. Each sample collected was placed into a sealable plastic bag or tub, marked with a unique sample identification code, and packaged for subsequent shipment to the laboratory for analysis. Individual sample identification consisted of a numeric code denoting the sampling media/location.
After packaging and labeling, samples were submitted under proper chain-of-custody to Reservoirs Environmental, Inc., Denver, Colorado. The National Voluntary Laboratory Accreditation Program (NVLAP), Lab Code 101896 accredits Reservoirs for asbestos analysis.
Samples were analyzed via Polarized Light Microscopy (PLM) utilizing EPA Method 600/M4- 82-020. Please note that USEPA and OSHA regulations define an ACM as a material containing more than one (1) percent asbestos, by volume, as determined by PLM analysis. In the case of multi-layer systems (e.g., floor tile/mastic layers), the laboratory analyzed and reported each layer separately.
4.0 SURVEY RESULTS
Twenty-five (25) representative samples collected were submitted for analytical determination. A summary of analytical results for samples collected and analyzed for this survey are in Appendix B (Laboratory Results) and are discussed below by building material/system type. Photographs of the buildings where samples were taken are included as Appendix C. Floor Plans of the building where samples were taken are included in Appendix D
Asbestos Survey Report Page 6
5.0 CONCLUSIONS
Asbestos-containing materials were identified in the building. See Executive Summary for details.
The identified materials must be removed prior to disturbance by a licensed abatement contractor.
6.0 LIMITATIONS AND EXCLUSION OF WARRANTY
This asbestos survey and assessment was performed using procedures and a level of diligence typically exercised by professional consultants performing similar services. However, asbestos-containing material (ACM) can be present in a structure, but not identified using ordinary investigative procedures.
No asbestos survey can completely, eliminate uncertainty regarding the presence of ACM.
R&R Environmental, Inc.’s level of diligence and investigative procedures are intended to reduce, but not eliminate, potential uncertainty regarding the presence of ACM. The procedures used for this survey attempt to establish a balance between the competing goals of limiting investigative costs, time, and building damage, and reducing the uncertainty about unknown conditions. Therefore, the determinations in this report should not be construed as a guarantee that all ACM present in the subject property has been included in this report.
This report presents R&R Environmental, Inc.’s professional determinations, which are dependent upon information obtained during performance of consulting services. R&R Environmental, Inc. assumes no responsibility for omissions or errors resulting from inaccurate information provided by sources outside of R&R Environmental, Inc.
No warranty or guarantee, expressed or implied, is made regarding the findings, conclusions, or recommendations contained in this report. The limitations presented above supersede the requirements or provisions of all other contracts or scopes of work, implied, or otherwise, except stated or acknowledged herein.
Asbestos Survey Report Page 7
A LIMITED ASBESTOS SURVEY AND ASSESSMENT
OF THE
SOUTHERN UTAH UNIVERSITY
AMERICA FIRST EVENT CENTER (AFEC)
AIR HANDLERS 7 & 8
During the month of August 2026, R & R Environmental, Inc. (R & R) of Sandy, Utah, conducted a limited asbestos survey and assessment of the Southern Utah University, America First Event Center, Air Handlers 7 & 8 located at 351 West Center Street in Cedar City, Utah 84720. Bulk samples of suspect asbestos-containing materials were collected and analyzed. The condition of all friable and non-friable asbestos-containing materials was, assessed. The following accredited inspector conducted the survey and assessment.
Inspected by:
Trevor Thacker Date State of Utah, Division of Air Quality Inspector Certification Number: ASB-8872 State of Utah Company Certification: ASBC-237
This report was reviewed by:
David C. Roskelley, MSPH, CIH, CSP Date State of Utah, Division of Air Quality Inspector Certification Number: ASB-1370 AHERA Inspector #5 PSI 65451 I Certified Safety Professional #15774 Certified Industrial Hygienist #8529 State of Utah Company Certification: ASBC-237
Appendix A
Sample Log
SAMPLE LOG
Sample
Material/ Homogenous Area
Sample Location Quantity Lab Result
(%/Type) Assessment
B-01 Pin Adhesive West Wall >350 ft2 7% Chrysotile Undamaged B-02 Pin Adhesive West Wall >350 ft2 7% Chrysotile Undamaged B-03 Silver Caulk Air Handler 8 2 ft2 None Detected Undamaged B-04 Silver Caulk Air Handler 8 2 ft2 None Detected Undamaged B-05 Black/Gray Caulk Air Handler 8 6 ft2 None Detected Undamaged B-06 Black/Gray Caulk Air Handler 8 6 ft2 None Detected Undamaged B-07 Black/Gray Caulk Air Handler 7 6 ft2 None Detected Undamaged B-08 Black/Gray Caulk Air Handler 7 6 ft2 None Detected Undamaged B-09 TSI Mudding Air Handler 7 3 ft2 None Detected Undamaged B-10 TSI Mudding Air Handler 8 3 ft2 None Detected Undamaged
B-11 Pipe Thread Sealant Air Handler 7 ~25 ft2 <0.25% Trem/Act (By Point Count) Undamaged
B-12 Pipe Thread Sealant Air Handler 8 ~25 ft2 <0.25% Trem/Act (By Point Count) Undamaged
B-13 Lagging Tape Air Handler 7 3 ft2 None Detected Undamaged B-14 Lagging Tape Air Handler 8 3 ft2 None Detected Undamaged B-15 Duct Liner Air Handler 8 50 ft2 None Detected Undamaged B-16 Duct Liner Air Handler 7 50 ft2 None Detected Undamaged B-17 Wall Insulation West Wall 950 ft2 None Detected Undamaged B-18 Wall Insulation West Wall 950 ft2 None Detected Undamaged B-19 Drywall System North Wall 1000 ft2 None Detected Undamaged B-20 Drywall System North Wall 1000 ft2 None Detected Undamaged
Material/ Homogenous Area
Sample Location Quantity Lab Result
(%/Type) Assessment
B-21 Drywall System North Wall 1000 ft2 None Detected Undamaged B-22 Wall Penetration (Red) North Wall 1 ft2 None Detected Undamaged B-23 Wall Penetration (Red) North Wall 1 ft2 None Detected Undamaged B-24 White Caulk Air Handler 7 2 ft2 None Detected Undamaged B-25 White Caulk Air Handler 7 2 ft2 None Detected Undamaged
Appendix B
Laboratory Report
September 08, 2026
Sincerely, Jeanne Spencer President
Subcontractor Number:
Laboratory Report: RES 773752-2
Project #/P.O. #: Suu America First Center
Project Description: Air Handlers 7&8
Dave Roskelley R & R Environmental 47 West 9000 South #2 Sandy, UT 84070
Dear Dave, Eurofins Reservoirs is an analytical laboratory accredited for the analysis of Industrial Hygiene and Environmental matrices by the National Voluntary Laboratory Accreditation Program (NVLAP), Lab Code 101896-0 for Transmission Electron Microscopy (TEM) and Polarized Light Microscopy (PLM) analysis and the American Industrial Hygiene Association (AIHA LAP), Lab ID 101533 for Phase Contrast Microscopy (PCM) analysis. This laboratory is currently proficient in both Proficiency Testing and PAT programs respectively.
Eurofins Reservoirs has analyzed the following samples for asbestos content as per your request. The analysis has been completed in general accordance with the appropriate methodology as stated in the attached analysis table. The results have been submitted to your office.
RES 773752-2 is the job number assigned to this study. This report is considered highly confidential and the sole property of the customer. Eurofins Reservoirs will not discuss any part of this study with personnel other than those of the client. The results described in this report only apply to the samples analyzed, as received and with the information provided by the customer (i.e. sample volumes and areas). This report must not be used to claim endorsement of products or analytical results by NVLAP or any agency of the U.S. Government. This report shall not be reproduced except in full, without written approval from Eurofins Reservoirs. Samples will be disposed of after sixty days unless longer storage is requested. If you have any questions about this report, please feel free to call 303-964-1986.
by Camryn Baumgartner
09/08/202609/08/202609/08/202609/08/2026
Eurofins Reservoirs Environmental, Inc Eurofins Reservoirs QA Manual
Effective July 28, 2026 Q:\QAQC\Eurofins Reservoirs QA Manual.pdf
(303) 964-1986 https://www.eurofinsus.com/builtenv https://clients.rei.et.eurofinsus.com
4955 Yarrow St, Suite 100, Arvada, CO 80002
Laboratory Sample IDLaboratory Sample IDLaboratory Sample IDLaboratory Sample ID LLLL Asbestos ContentAsbestos ContentAsbestos ContentAsbestos Content Non-Non-Non-Non- Non-Non-Non-Non- AAAA SubSubSubSub AsbestosAsbestosAsbestosAsbestos FibrousFibrousFibrousFibrous YYYY PhysicalPhysicalPhysicalPhysical PartPartPartPart MineralMineralMineralMineral VisualVisualVisualVisual FibrousFibrousFibrousFibrous ComponentsComponentsComponentsComponents EEEE DescriptionDescriptionDescriptionDescription EstimateEstimateEstimateEstimate ComponentsComponentsComponentsComponents
Client Sample NumberClient Sample NumberClient Sample NumberClient Sample Number RRRR (%) (%) (%) (%) 773752 -773752 -773752 -773752 - B1B1B1B1 A Brown resinous material 45 NDNDNDND 0 100.0 B Black resinous tar 55 ChrysotileChrysotileChrysotileChrysotile 7777 0 93.0 773752 -773752 -773752 -773752 - B2B2B2B2 A Tan insulation 5 NDNDNDND 85 15.0 B Gray granular material 20 NDNDNDND 0 100.0 C Black resinous tar 75 ChrysotileChrysotileChrysotileChrysotile 7777 0 93.0 773752 -773752 -773752 -773752 - B3B3B3B3 A Gray/colorless resinous material w/ silver paint 100 NDNDNDND 0 100.0 773752 -773752 -773752 -773752 - B4B4B4B4 A Gray/colorless resinous material w/ silver paint 100 NDNDNDND 0 100.0 773752 -773752 -773752 -773752 - B5B5B5B5 A Tan resinous material 100 NDNDNDND 0 100.0 773752 -773752 -773752 -773752 - B6B6B6B6 A Tan resinous material 100 NDNDNDND 0 100.0 773752 -773752 -773752 -773752 - B7B7B7B7 A Tan resinous material 100 NDNDNDND 0 100.0 773752 -773752 -773752 -773752 - B8B8B8B8 A Tan resinous material 100 NDNDNDND 0 100.0 773752 -773752 -773752 -773752 - B9B9B9B9 A Orange insulation 20 NDNDNDND 90 10.0 B White sealant 80 NDNDNDND 8 92.0 773752 -773752 -773752 -773752 - B10B10B10B10 A Orange insulation 25 NDNDNDND 90 10.0 B White sealant 75 NDNDNDND 8 92.0 TEM Analysis recommended for organically bound material (i.e. floor tile) if PLM results are <1%.
Eurofins Reservoirs Environmental, Inc Eurofins Reservoirs QA Manual
Effective July 28, 2026 Q:\QAQC\Eurofins Reservoirs QA Manual.pdf
Job Number:
Client:
Client Project/P.O.:
Client Project Description:
Date Samples Received:
Analysis Type:
Turnaround:
Date Samples Analyzed:
773752-2 R & R Environmental Suu America First Center Air Handlers 7&8 August 03, 2026 EPA 600/R-93/116 - Point Count, Bulk (400) Rush August 04, 2026
EUROFINS RESERVOIRS ENVIRONMENTAL, INC
NVLAP Lab Code 101896-0
AIHA LAP, LLC. LAB ID 101533
TABLE: I ANALYSIS: PLM BULK ANALYSIS, PERCENTAGE COMPOSITION BY VOLUME
NA = Not Analyzed NR = Not Received ND = None Detected TR = Trace; <1 % Visual Estimate Trem-Act = Tremolite-Actinolite
(303) 964-1986 https://www.eurofinsus.com/builtenv https://clients.rei.et.eurofinsus.com
Laboratory Sample IDLaboratory Sample IDLaboratory Sample IDLaboratory Sample ID LLLL Asbestos ContentAsbestos ContentAsbestos ContentAsbestos Content Non-Non-Non-Non- Non-Non-Non-Non-
YYYY PhysicalPhysicalPhysicalPhysical PartPartPartPart MineralMineralMineralMineral VisualVisualVisualVisual FibrousFibrousFibrousFibrous ComponentsComponentsComponentsComponents EEEE DescriptionDescriptionDescriptionDescription EstimateEstimateEstimateEstimate ComponentsComponentsComponentsComponents
Client Sample NumberClient Sample NumberClient Sample NumberClient Sample Number RRRR (%) (%) (%) (%)
773752 -773752 -773752 -773752 - B11B11B11B11 A Brown/multi-colored resinous material 100 Trem/ActTrem/ActTrem/ActTrem/Act TRTRTRTR 2 98.0 Point Count Point Count Point Count Point Count <0.25<0.25<0.25<0.25 773752 -773752 -773752 -773752 - B12B12B12B12 A Brown/multi-colored resinous material 100 Trem/ActTrem/ActTrem/ActTrem/Act TRTRTRTR 2 98.0 Point Count Point Count Point Count Point Count <0.25<0.25<0.25<0.25 773752 -773752 -773752 -773752 - B13B13B13B13 A Orange insulation w/ silver/white wrap 100 NDNDNDND 85 15.0 773752 -773752 -773752 -773752 - B14B14B14B14 A White sealant w/ blue paint 40 NDNDNDND 7 93.0 B White/multi-colored wrap w/ orange insulation 60 NDNDNDND 75 25.0 773752 -773752 -773752 -773752 - B15B15B15B15 A Green/gray insulation 100 NDNDNDND 85 15.0 773752 -773752 -773752 -773752 - B16B16B16B16 A Green/gray insulation 100 NDNDNDND 85 15.0 773752 -773752 -773752 -773752 - B17B17B17B17 A Green/gray insulation w/ silver wrap 100 NDNDNDND 80 20.0 773752 -773752 -773752 -773752 - B18B18B18B18 A Green/gray insulation w/ silver/multi-colored wrap 100 NDNDNDND 80 20.0 773752 -773752 -773752 -773752 - B19B19B19B19 A White compound 5 NDNDNDND 0 100.0 B Tan/white drywall 95 NDNDNDND 10 90.0 773752 -773752 -773752 -773752 - B20B20B20B20 A White compound 7 NDNDNDND 0 100.0 B Tan/white drywall 93 NDNDNDND 12 88.0 TEM Analysis recommended for organically bound material (i.e. floor tile) if PLM results are <1%.
Eurofins Reservoirs Environmental, Inc Eurofins Reservoirs QA Manual
Effective July 28, 2026 Q:\QAQC\Eurofins Reservoirs QA Manual.pdf
Job Number:
Client:
Client Project/P.O.:
Client Project Description:
Date Samples Received:
Analysis Type:
Turnaround:
Date Samples Analyzed:
773752-2 R & R Environmental Suu America First Center Air Handlers 7&8 August 03, 2026 EPA 600/R-93/116 - Point Count, Bulk (400) Rush August 04, 2026
EUROFINS RESERVOIRS ENVIRONMENTAL, INC
NVLAP Lab Code 101896-0
AIHA LAP, LLC. LAB ID 101533
TABLE: I ANALYSIS: PLM BULK ANALYSIS, PERCENTAGE COMPOSITION BY VOLUME
NA = Not Analyzed NR = Not Received ND = None Detected TR = Trace; <1 % Visual Estimate Trem-Act = Tremolite-Actinolite
(303) 964-1986 https://www.eurofinsus.com/builtenv https://clients.rei.et.eurofinsus.com
Laboratory Sample IDLaboratory Sample IDLaboratory Sample IDLaboratory Sample ID LLLL Asbestos ContentAsbestos ContentAsbestos ContentAsbestos Content Non-Non-Non-Non- Non-Non-Non-Non-
YYYY PhysicalPhysicalPhysicalPhysical PartPartPartPart MineralMineralMineralMineral VisualVisualVisualVisual FibrousFibrousFibrousFibrous ComponentsComponentsComponentsComponents EEEE DescriptionDescriptionDescriptionDescription EstimateEstimateEstimateEstimate ComponentsComponentsComponentsComponents
Client Sample NumberClient Sample NumberClient Sample NumberClient Sample Number RRRR (%) (%) (%) (%) 773752 -773752 -773752 -773752 - B21B21B21B21 A Cream tape 10 NDNDNDND 95 5.0 B White joint compound 90 NDNDNDND 0 100.0 773752 -773752 -773752 -773752 - B22B22B22B22 A Red fibrous resinous material 100 NDNDNDND 10 90.0 773752 -773752 -773752 -773752 - B23B23B23B23 A Red fibrous resinous material 100 NDNDNDND 10 90.0 773752 -773752 -773752 -773752 - B24B24B24B24 A Tan resinous material 100 NDNDNDND 0 100.0 773752 -773752 -773752 -773752 - B25B25B25B25 A Tan resinous material 100 NDNDNDND 0 100.0 TEM Analysis recommended for organically bound material (i.e. floor tile) if PLM results are <1%.
Liu Wenlong Analyst
Eurofins Reservoirs Environmental, Inc Eurofins Reservoirs QA Manual
Effective July 28, 2026 Q:\QAQC\Eurofins Reservoirs QA Manual.pdf
Job Number:
Client:
Client Project/P.O.:
Client Project Description:
Date Samples Received:
Analysis Type:
Turnaround:
Date Samples Analyzed:
773752-2 R & R Environmental Suu America First Center Air Handlers 7&8 August 03, 2026 EPA 600/R-93/116 - Point Count, Bulk (400) Rush August 04, 2026
EUROFINS RESERVOIRS ENVIRONMENTAL, INC
NVLAP Lab Code 101896-0
AIHA LAP, LLC. LAB ID 101533
TABLE: I ANALYSIS: PLM BULK ANALYSIS, PERCENTAGE COMPOSITION BY VOLUME
NA = Not Analyzed NR = Not Received ND = None Detected TR = Trace; <1 % Visual Estimate Trem-Act = Tremolite-Actinolite
(303) 964-1986 https://www.eurofinsus.com/builtenv https://clients.rei.et.eurofinsus.com
SUBMITTED BY INVOICE TO
Client Sample ID Number
RES Job #: 773752
CONTACT INFORMATION SERIES
ASBESTOS LABORATORY REQUESTED ANALYSIS VALID MATRIX CODES LAB NOTES
CHEMISTRY LABORATORY
MICROBIOLOGY LABORATORY
**Turnaround times establish a laboratory priority, subject to laboratory volume and are not guaranteed. Additional fees apply for afterhours, weekends and holidays.**
Laboratory Analysis Instructions
(Sample ID's must be unique)
Company: R & R Environmental Company: R & R Environmental
Address: 47 West 9000 South #2 Address: 47 West 9000 South #2
Sandy, UT 84070 Sandy, UT 84070
Project Number and/or P.O. #: Suu America First Center Project Zip Code:
Project Description/Location: Air Handlers 7&8
Contact: Dave Roskelley -1 PLM Priority Phone: (801) 541-1035
Fax:
Cell: (801) 541-1035
Final Data Deliverable Email Address:
dave@rrenviro.com (+ 8 ADDNL. CONTACTS)
PLM / PCM / TEM / NYS DTL RUSH PRIORITY STANDARD Air = A Bulk = B
Dust = D Food = F
Paint = P Soil = S
Dust RUSH PRIORITY STANDARD
*PRIOR NOTICE REQUIRED FOR SAME DAY TAT
Surface = SU Swab = SW
Tape = T Wipe = W
Metals RUSH PRIORITY STANDARD Drinking Water = DW
Waste Water = WW
Organics* SAME DAY RUSH PRIORITY STANDARD **ASTM E1792 approved wipe media only**
Viable Analysis** PRIORITY STANDARD
**TAT DEPENDENT ON SPEED OF MICROBIAL GROWTH
Medical Device Analysis RUSH STANDARD
Mold Analysis RUSH PRIORITY STANDARD
Special Instructions:
ASBESTOS CHEMISTRY MICROBIOLOGY ICO
1 B1 X B
2 B2 X B
3 B3 X B
4 B4 X B
5 B5 X B
6 B6 X B
7 B7 X B
8 B8 X B
9 B9 X B
10 B10 X B
11 B11 X B
12 B12 X B
13 B13 X B
P L
M
P L
M S h o rt R ep o rt (E
PA
/6
/R
-9 3/
6)
T E
M
P C
M
N Y
S
D U
S T
M E
TA
L
S
O R
G A
N
IC
S
V
IA
B L
E S
M E
D
IC
A L
M O
L D
S am pl e
V ol um e
(L
A re a
S am pl e
Te m pe ra tu re
C
Le ng th (o r A liq uo ts
) x W id th
(o r A re a/
A liq uo t)
M at rix C od e of
C on ta in er s
D at e C ol le ct ed m m
/d d/ yy
T im e C ol le ct ed hh :m m
Eurofins Reservoirs Environmental, Inc establishes a unique Lab Sample ID, for each sample, by preceding each unique Client Sample ID with the laboratory RES Job Number.
Eurofins Reservoirs Environmental, Inc will analyze incoming samples based on information received and will not be responsible for errors or omissions in calculations resulting from the inaccuracy of original data. By signing, client/company representative agrees that submission of the following samples for requested analysis as indicated on this Chain of Custody shall consitute an analytical services agreement with payment terms of NET30. Failure to comply with payment terms may result in a 18% APR finance charge.
Relinquished By:
Trevor Thacker Date/Time: 07/30/2026 15:56:11 Sample Condition: Acceptable
Received By:
Aubree Klausner Date/Time: 08/03/2026 11:28:48 Carrier: Fed-Ex
Eurofins Reservoirs Environmental, Inc Eurofins Reservoirs QA Manual
Effective July 31, 2025 Q:\QAQC\Eurofins Reservoirs QA Manual.pdf
(303) 964-1986 https://www.eurofinsus.com/builtenv https://clients.rei.et.eurofinsus.com
Client Sample ID Number
REQUESTED ANALYSIS VALID MATRIX CODES LAB NOTES
Laboratory Analysis Instructions
(Sample ID's must be unique)
Air = A Bulk = B
Dust = D Food = F
Paint = P Soil = S
Surface = SU Swab = SW
Tape = T Wipe = W
Drinking Water = DW
Waste Water = WW
**ASTM E1792 approved wipe media only**
RES Job #: 773752
Submitted By: R & R Environmental
ASBESTOS CHEMISTRY MICROBIOLOGY ICO
14 B14 X B
15 B15 X B
16 B16 X B
17 B17 X B
18 B18 X B
19 B19 X B
20 B20 X B
21 B21 X B
22 B22 X B
23 B23 X B
24 B24 X B
25 B25 X B
P L
M
P L
M S h o rt R ep o rt (E
PA
/6
/R
-9 3/
6)
T E
M
P C
M
N Y
S
D U
S T
M E
TA
L
S
O R
G A
N
IC
S
V
IA
B L
E S
M E
D
IC
A L
M O
L D
S am pl e
V ol um e
(L
A re a
S am pl e
Te m pe ra tu re
C
Le ng th (o r A liq uo ts
) x W id th
(o r A re a/
A liq uo t)
M at rix C od e of
C on ta in er s
D at e C ol le ct ed m m
/d d/ yy
T im e C ol le ct ed hh :m m
Eurofins Reservoirs Environmental, Inc Eurofins Reservoirs QA Manual
Effective July 31, 2025 Q:\QAQC\Eurofins Reservoirs QA Manual.pdf
(303) 964-1986 https://www.eurofinsus.com/builtenv https://clients.rei.et.eurofinsus.com
Appendix C
Photo Log
PHOTO 1: Southern Utah University, America First Event Center
PHOTO 2: Pin Adhesive contains asbestos
PHOTO 3: Pipe Thread contains asbestos
R & R Environmental, Inc.
47 West 9000 South, Suite #2, Sandy, Utah 84070
(801) 352-2380 • Fax: (801) 352-2381
SITE PHOTOGRAPHS
LIMITED ASBESTOS SURVEY AND ASSESSMENT
SOUTHERN UTAH UNIVERSITY
AMERICA FIRST EVENT CENTER
PROJECT NO:
DESIGNED BY:
SCALE: REVIEWED BY:
DRAWN BY:
DATE:
FILE:
Appendix D
Floor Plan
N
SOUTHERN UTAH UNIV.
AMERICA FIRST EVENT
CENTER (AFEC)
699 W. CENTER STREET
CEDAR CITY, UT 84720
AUGUST 2026
AIR HANDLERS 7 & 8
ASBESTOS FLOORPLAN
= ASBESTOS SAMPLE NUMBER & LOCATION##
= ASBESTOS CONTAINING PIN ADHESIVE
**** = ASBESTOS CONTAINING PIPE THREAD SEALANT (LOCATION NOT SHOWN)
13 09
Appendix E
State of Utah Certifications
Utah Asbestos Certification
State of Utah
SPENCER J. COX
Governor
DEIDRE HENDERSON
l)e,1ten<mt Governor
February 27, 2026
Trevor Thacker R&R Environmental
Depat1ment of Environmental Quality
Tim Dovis Executive Director
DIVISION OF AIR QUALITY
Bryce C. Bird
Director
47 West 9000 South, Suite 2 Sandy, UT 84070
Dear Mr. Thacker:
Re: Utah Asbestos Program Individual Certification Card
Trevor Thacker
ASB-8872
Inspector (8' 01/20/2027)
~r
DAQA-001-26
The Utah Division of Air Quality (DAQ) has reviewed your Utah Asbestos Program Certification
Application for Individuals and we are pleased to inform you that your application has been approved. Your new asbestos program individual certification card is enclosed with this letter and this card is the sole method of individual certification documentation that you will receive from the DAQ.
Please check the information on your asbestos program certification card carefully. Please confirm that the photograph, name, and certification discipline(s) are correct. Also, please remember to keep your current asbestos program certification card with you at all times when you are performing regulated asbestos work activities.
Please contact Barbara Perkins at (80 I) 536-0221 or at bperkins@utah.gov if you have any questions regarding this letter or the enclosed asbestos program certification card.
Sincerely, Leonard Wright (Feb'25.2026 13·10:01 MST)
Leonard Wright, Manager Air Toxics, Lead-Based Paint, and Asbestos Section
LW;BP:rh
195 No11h 1950 West• Suh Lnko City, UT Mailing Address; P.O. Oox 144820 • Sul1 Luko City, UT 84114-4820
'1'1:lcphonc {801) 536f4000 • Pnx (801) 536~4099 • T,D.D. 800 346-3128 1111vi11.tleq.11tqh,1:ov l'rintcd on IOO¾ recycled pai1cr
Utah Asbestos Certification
SPENCER J. COX
Governor
DETORE HENDERSON
Lieutenant Governor
February 27, 2026
Jamison Moss R&R Environmental
Depa1tment of Environmental Quality
Tim Davis fa:ec11tive Direc/01·
DIVISION OF AIR QUALITY
Bryce C. Bird
Director
47 West 9000 South, Suite 2 Sandy, UT 84070
Dear Mr. Moss:
Re: Utah Asbestos Program Individual Certification Card
Jamison Moss
ASB-6674
"'" Inspector (Eitp:" 02/20/2027)
Project oeMner'(Exp. 01/12/2027) it V .
4U~hD-~~fA.'Q 1· Director, ta IvIs1on o ir ua 1ty
DAQA-001-26
The Utah Division of Air Quality (DAQ) has reviewed your Utah Asbestos Program Certification Application for Individuals and we are pleased to inform you that your application has been approved. Your new asbestos program individual certification card is enclosed with this letter and this card is the sole method of individual certification documentation that you will receive from the DAQ.
Please check the information on your asbestos program certification card carefully. Please confirm that the photograph, name, and certification discipline(s) are correct. Also, please remember to keep your current asbestos program certification card with you at all times when you are performing regulated asbestos work activities.
Please contact Barbara Perkins at (801) 536-0221 or at bperkins@utah.gov if you have any questions regarding this letter or the enclosed asbestos program certification card.
Sincerely, Leonard Wrlgll (Feht2026 09:17:31 Msn
Leonard Wright, Manager Air Toxics, Lead-Based Paint, and Asbestos Section
LW:BP:rh
195 North 1950 Wes1 • Sah Lakll Chy, UT Mailing Address: P.O. Box 144820 • Sall Lake City, UT 84114-4820
Telephone (80 I) 536-4000 • flax (80 I) 536-4099 • T.D.D. 800 346-3128 www.1l1111,111ul,,Mo11 l'rinlcd on 100¼ recycled p11pcr
Utah Lead-Based Paint Certification
SPENCER J. COX
Go,·tmor
DEIDRE HENDERSON
litutenant Gol'limor
February 11, 2025
Steve Smith
Department of Environmental Quality
Kimberly D. Shelley Exec11tfre Director
DIVISION OF AIR QUALITY
Bryce C Bird
Director
R&R Environmental, Inc.
4 7 West 9000 South, #2 Sandy, UT 84070
Dear Mr. Smith:
Re: Utah Lead-Based Paint Program Individual Certification Card
Inspector l Risk Aue
-4~;_·~
Director, Utah D1v1sion of Air Quality
DAQA-002-25
The Utah Division of Air Quality (DAQ) has reviewed your Utah Lead-Based Paint (LBP)
Program Certification Application for Individuals and we are pleased to inform you that your application has been approved. Your new LBP program individual certification card is enclosed with this letter and this card is the sole method of individual certification documentation that you will receive from the DAQ.
Please check the information on your LBP program certification card carefully. Please confirm that the photograph, name, and certification discipline(s) are correct. Also, please remember to keep your current LBP program certification card with you at all times when you are performing regulated LBP work activities.
Please contact Barbara Perkins at (80 l) 536-0221 or at bperkins@utah.gov if you have any questions regarding this letter or the enclosed LBP program certification card.
Sincerely, ~ Sl1J~ Leonard Wright (Feb 7, 2025 12:09 MST)
Leonard Wright, Manager Air Toxics, Lead-Based Paint, and Asbestos Section
LW:BP:lr
195 Nonh 1950 Wes,, 4~' Hoor • Sall Lake City, Ur Mailing Addrm l' 0 llo"< 144820 • Suh Lnl.c Cny. UT 84114-1820
'I elephone (80 I) 536-4000 • l·a"< (801) 536-4099 ·TDD (80 I) 536-1-11-1 ~• u ,, di:tJ mnh gm•
P11111cd on I00~. 1ccycled papc, LIMITED LEAD-BASED PAINT INSPECTION
SOUTHERN UTAH UNIVERSITY
AMERICA FIRST EVENT CENTER (AFEC)
AIR HANDLERS 7 & 8
Utah Department of Government Operations Division of Facilities, Construction and Management (DFCM)
Taylorsville State Office Building, 3rd Floor 4315 South 2700 West
47 West 9000 South, Suite #2
Sandy, Utah 84070
LIMITED LEAD-BASED PAINT INSPECTION
AIR HANDLERS 7 & 8
TABLE OF CONTENTS
TITLE PAGE
1.0 Introduction
2.0 Building Description
3.0 Lead-based Paint Definition
4.0 Procedures
4.1 Paint Sampling Methods
4.2 XRF Calibration
4.3 Field Documentation
5.0 Findings
6.0 Results and Recommendation
8.0 Limitations and Exclusion of Warranty
Appendices
A. Data Tables Table 1 – Building Component with Lead Levels at 0.1 mg/cm2 and above Table 2 – Building Component with Lead Levels at below 0.1 mg/cm2 B. Photograph Log
SUU, AFEC Limited Lead-Based Paint Inspection Air Handlers 7 & 8 Page 1
Limited Lead-Based Paint Inspection
SOUTHERN UTAH UNIVERSITY
AMERICA FIRST EVENT CENTER
AIR HANDLERS 7 & 8
1.0 INTRODUCTION
On August 1, 2026, a lead-based paint (LBP) survey was conducted for the Southern Utah University, America First Event Center, Air Handlers 7 & 8. The purpose of the survey was to identify lead surrounding two air handlers 7 and 8 in the building that are going to be replaced. Measurements for lead in paint were made using a SciApps X550 X-ray Fluorescence (XRF) Spectrum Analyzer. No chip sampling or laboratory analysis was performed for confirmation of XRF measurements.
The survey work was overseen by David C. Roskelley with R & R Environmental, Inc. in Sandy, Utah. Mr. Roskelley has completed Lead Inspector Training through the University of Utah, Rocky Mountain Center for Occupational and Environmental Health (RMCOEH), an EPA-sponsored Regional Lead Training Center, and is certified by the State of Utah, Division of Environmental Quality, as a Lead Inspector.
The U.S. Department of housing and Urban Development (HUD) Guidelines for the Evaluation and Control of Lead-Based Paint Hazards in housing (HUD Guidelines), Chapter7: Lead-Based Paint Inspection, 1997 Revision, was generally followed for this survey, with modifications appropriate for a non-residential building.
The following accredited and certified inspector oversaw the collection of the samples:
September 10, 2026 David C. Roskelley, MSPH, CIH, CSP Date Lead-Based Paint Inspector Certification Number: PB-1041
The following accredited and certified inspector oversaw the inspection, made assessment, and reviewed the report:
September 10, 2026 David C. Roskelley, MSPH, CIH, CSP Date Lead-Based Paint Inspector Certification Number: PB-1041
Air Handlers 7 & 8 Page 2
2.0 BUILDING DESCRIPTION
Building Identification
Building Name ....... Southern Utah University, America First Event Center Building Address ............. 351 West Center Street, Cedar City, Utah 84720
Building Construction
Building Construction Date Building Type .................................................................. Mechanical Space Building Total Sq. Ft .......................................... (Affected Area) ~2,000 ft2 Structural System ....................................................... Structural Steel, Stone Exterior Wall Construction .................................................................. Brick Floor Deck Construction .............................................. Reinforced Concrete Roof Construction .................................................................................... NA Floors Above Grade ................................................................................. NA Floors Below Grade ................................................................................. NA
Interior Finishes
Floors .............................................................................................. Concrete Walls ........................................ Wallboard System, Brick, Corrugated Steel Attic .......................................................................................................... NA Crawl space .............................................................................................. NA
Building Mechanical
Heating Plant ............................................................................... Central Air Main Heating Distribution .......................................................... Central Air Cooling Plant .............................................................................. Central Air Main A / C Distribution .............................................................. Central Air
Air Handlers 7 & 8 Page 3
3.0 LEAD-BASED PAINT DEFINITIONS
HUD defines “lead-based paint” as any coating that has a lead concentration of 1.0 milligram of lead per square centimeter (1.0 mg/cm2) or greater, or if the lead concentration is greater than 0.5% by weight. The Consumer Product Safety Commission (CPSC) currently considers paint to be lead-containing if the concentration of lead exceeds 600 ppm (0.06% by weight). In 1978, the CPSC banned the sale of lead-based paint to consumers, and banned its application in areas where consumers have direct access to painted surfaces. Both the CPSC and HUD definitions of lead-containing paint are aimed at protecting the general population from exposure to lead in the residential setting.
By contrast, the mission of the Occupational Safety and Health Administration (OSHA) with respect to lead-containing paint, is to protect workers during construction activities that may generate elevated airborne lead concentrations. OSHA states that construction work (including renovation, maintenance, and demolition) carried-out on structures coated with paint have lead concentrations lower than the HUD or CPSC can still result in airborne lead concentrations in excess of regulatory limits. For this reason, OSHA has not defined lead-containing paint, but states that paint having any measurable level of lead may pose a substantial exposure hazard during construction work, depending upon the work performed.
4.0 PROCEDURES
4.1 Paint Sampling Methodologies
Direct measurements of lead in paint were made using a SciApps X550 X-ray Fluorescence (XRF) Spectrum Analyzer. The SciApps X550 X-ray Fluorescence (XRF) Spectrum Analyzer non-destructively measures lead concentrations of painted surfaces, regardless of the number of layers present. These instruments were developed specifically for addressing lead-based paint issues in housing and their use in identifying potential exposure hazards for renovation or construction work must be augmented by selective collection and analysis of physical paint chip samples.
The newer XRF instruments are capable of identifying lead in paint at concentrations of about 0.01 milligram per square centimeter (mg/cm2) or greater. When lead concentrations are lower than this, the instruments are not capable of making accurate, reliable measurements, and the reported lead concentration may underestimate or overestimate the actual lead concentration in the paint. Therefore, an XRF readings of 0.01 mg/cm2 or greater may be considered lead-containing from an OSHA perspective, and any readings of 0.0mg/cm2 or less should be confirmed by the collection and laboratory analysis of paint chip samples, or assumed to be positive for lead.
Where paint chip samples are necessary, samples are collected according to the protocol specified in the HUD Guidelines. The samples are then submitted to a laboratory recognized under the EPA’s National Lead Laboratory Accreditation Program (NLLAP) for analysis by flame atomic absorption spectrophotometry according to American Society of Testing and Materials (ASTM) method ASTM E 1645.
Air Handlers 7 & 8 Page 4
4.2 XRF Calibration
Before beginning the testing and after the testing was completed, the internal calibration of the LPA-1 was checked by taking two consecutive measurements on a National Institute for Standards and Technology (NIST) standard with a known concentration of lead. Three more readings were taken on a lead-free wood block. These calibration checks are reported within the XRF data tables found in Appendix A of this report and are maintained in a file at R & R Environmental, Inc. to detect changes in instrument performance over time.
4.3 Lead Paint Inspection Data Tables
The XRF instrument generates a unique set of data tables for each inspection and can be exported into Microsoft Excel Spreadsheet format .xls. The Sequential Report lists the measurements made throughout the property in sequential order, from the first measurement to the last. The Data table is maintained in a file at R & R Environmental, Inc.
5.0 FINDINGS
The XRF instrument indicated that lead is present of some of the interior building surfaces.
This surface is listed in Table 1 “positive” building components (Measurements of 0.01 mg/cm2 and above) in Appendix A of this report.
Interior:
-Metal Drainpipes (Blue)
Since lead was detected in some of the building’s painted surfaces, the OSHA Lead in Construction Standard (29 CFR 1926.62) will apply to any construction work (including renovation and demolition) that may disturb those surfaces. The standard requires, among other things, the following:
• Initial training on the hazards of lead exposure, proper work practices, respiratory protection, and other topics;
• An initial exposure assessment, by air monitoring, to determine the lead exposure assessment, until sample analysis indicates exposures below the Permissible Exposure Limit;
• Hand washing facilities, designated clean change areas, and designated eating areas.
In addition to the above considerations, the presence of lead in demolition debris has the potential to impose limitations on where and how the debris may be disposed. The Resource Conservation and Recovery Act (RCRA), Subtitles C and D, require that the waste must be analyzed to determine the amount of leachable lead present. The type of test to be performed on the waste is the Toxicity Characteristic Leaching Procedure (TCLP) for lead, and the results of this test will determine whether the material must be handled
Air Handlers 7 & 8 Page 5 and disposed of as hazardous waste. For structures containing large amounts of lead-containing paint, significant potential for failing the TCLP exists.
6.0 RESULTS AND RECOMMENDATIONS
Lead-based paint was detected on some interior surfaces during this limited survey. Any disturbance of materials containing lead-based paint should be done by trained and certified persons.
7.0 LIMITATIONS AND EXCLUSIONS OF WARRANTY
This lead inspection was performed using procedures and a level of diligence typically exercised by professional consultants performing similar services. However, lead-based paint (LBP) can be present in a surface, but not identified using ordinary investigative procedures.
No lead inspection can completely eliminate uncertainty regarding the presence of LBP. R & R Environmental, Inc. level of diligence and investigative procedures are intended to reduce, but not eliminate, potential uncertainty regarding the presence of LBP. The procedures used for this survey attempt to establish a balance between the competing goals of limiting investigative costs, time, and building damage, and reducing the uncertainty about unknown conditions. Therefore, the determinations in this report should not be construed as a guarantee that all LBP present in the subject property has been included in this report.
This report presents R & R Environmental, Inc.’s professional determinations, which are dependent upon information obtained during performance of consulting services. R &R Environmental, Inc. assumes no responsibility for omissions or errors resulting from inaccurate information provided by sources outside of R & R Environmental, Inc.
No warranty or guarantee, expressed or implied, is made regarding the findings, conclusions, or recommendations contained in this report. The limitations presented above supersede the requirements or provisions of all other contracts or scopes of work, implied or otherwise, except those stated or acknowledged herein.
Appendix A
Lead Paint Inspection Data Tables
Table 1
Building Components with Lead Levels at 0.01 mg/cm2 and Above Southern Utah University
America First Event Center
Room Floor
(1) Sample Number
Lead Level (Mg/Cm2) Component Side (1)
Substrate
Color
Condition
1 1.1 CALIBRATE
2 1.0 CALIBRATE
3 1.0 CALIBRATE
Air Handler 7/8 Rm 1 11 0.2 DRAINPIPE CENTER METAL BLUE INTACT
Air Handler 7/8 Rm 1 12 0.2 DRAINPIPE CENTER METAL BLUE INTACT
13 1.0 CALIBRATE
14 1.1 CALIBRATE
15 1.0 CALIBRATE
*Side: A=North, B=East, C=South, D=West
Table 2
Building Components with Lead Levels Below 0.01 mg/cm2
Room
Floor (2)
Number
Lead Level
(mg/cm2)
Component
Side (1)
Substrate
Color
Condition Air Handler
7/8 Rm 1 4 0 FLOOR CENTER CONCRETE GRAY INTACT
Air Handler 7/8 Rm
1 5 0 HANDLER 8 CENTER METAL GRAY INTACT
Air Handler 7/8 Rm
1 6 0 HANDLER 7 CENTER METAL GRAY INTACT
Air Handler 7/8 Rm
2 7 0 TSI CENTER PAPER BLUE INTACT
Air Handler 7/8 Rm
2 8 0 TSI CENTER PAPER RED INTACT
Air Handler 7/8 Rm
2 9 0 TSI CENTER PAPER WHITE INTACT
Air Handler 7/8 Rm
1 10 0 MOTOR CENTER METAL RED INTACT
*Side: A=North, B=East, C=South, D=West
Appendix B
Photograph Log
PHOTO 1: Southern Utah University, America First Event Center
PHOTO 2: Blue metal drain pipes on Air Handlers 7 & 8 contain lead
R & R Environmental, Inc.
47 West 9000 South, Suite #2, Sandy, Utah 84070
(801) 352-2380 • Fax: (801) 352-2381
SITE PHOTOGRAPHS
LIMITED LEAD BASED PAINT INSPECTION
PROJECT NO:
DESIGNED BY:
SCALE:
REVIEWED BY:
DRAWN BY:
DATE:
FILE:
HAZARDOUS MATERIALS INSPECTION
SOUTHERN UTAH UNIVERSITY
AMERICA FIRST EVENT CENTER
AIR HANDLERS 7 & 8
Utah Department of Government Operations Division of Facilities, Construction and Management (DFCM)
Taylorsville State Office Building, 3rd Floor 4315 South 2700 West
47 West 9000 South, Suite #2 Sandy, Utah 84070
SUU, AFEC Hazardous Material Inspection
Hazardous Materials Inspection
Air Handlers 7 & 8 351 West Center Street Cedar City, Utah 84720
On August 1, 2026, Trevor Thacker of R & R Environmental, Inc., conducted a hazardous materials inspection of the Southern Utah University, America First Event Center, Air Handlers 7 & 8 located at 351 West Center Street in Cedar City, Utah 84720. The purpose of this survey was to identify the existence, extent, and condition of hazardous materials.
The inspection was conducted based on an agreement with Southern Utah University.
Hazardous materials requiring proper removal and disposal were identified at the Southern Utah University, America First Event Center, Air Handlers 7 & 8 , in Cedar City, Utah as follows:
Material Location Quantity Unit Cost Fluorescent Bulb Air Handler 7&8 14 bulbs $2.00 / bulb Air Handler Control Module
Air Handler 7&8 2 units $NA / unit
PCB Ballast Air Handler 7&8 7 units $8.00 / unit Thermostats Air Handler 7&8 4 units $75.00 / unit
The State of Utah’s DFCM policy requires the items above to be removed and disposed of at a facility approved to accept such waste prior to demolition. This may or may not be applied to the city of Cedar City in Iron County, but R & R Environmental, Inc.
recommends removal and proper disposal of these components prior to any demolition activities.
The cost estimate to remove and dispose of these hazardous materials is estimated at approximately >$384.00. This cost estimate does not include transportation, removal, design, or management fees associated with dismantling and packaging the materials.
| 2027 SBS : DCR ACM LBP.pdf |
| SBS UT Asbestos Cert 7 13 2027.pdf |
| 2026 SBS : DCR ACM LBP.pdf |
| 2025 SBS : DCR ACM LBP.pdf |
| SBS LBP Cert Exp Jan 2028.pdf |
| DCR ACM Utah Daq July 2027.pdf |
| 2026 SBS : DCR ACM LBP |
| 2026 SBS : DCR ACM LBP |
| 2026 SBS : DCR ACM LBP |
| 2025 SBS : DCR ACM LBP.pdf |
| 2025 DCR ACM LBP.pdf |
2025 SBS : DCR ACM LBP
2026 SBS : DCR ACM LBP
{"type":"Document","isBackSide":false,"languages":["en-us"],"usedOnDeviceOCR":false}
{"type":"Form","isBackSide":false,"languages":["en-us"],"usedOnDeviceOCR":false}
File details come from the government source that posted it. Updated .