6-2-CS27015-27060150-Approved Plans.pdf

PDF 5 MB Posted

Attached to
DFCM Construction - Prequalified Electrical Stage II - Administrative Office of the Courts - Logan Court Generator Replacement - Project #27060150
Solicitation number
CS27015
Issued by
Utah

About this file

This is an approved electrical design plan document for the State of Utah's Division of Facilities Construction and Management (DFCM) for Project #27060150, involving the replacement of an emergency generator system at the Logan First District Court located at 135 North 100 West, Logan, Utah 84321. The project scope includes the replacement of the existing 150 kW emergency generator and automatic transfer switch (ATS) with new NFPA 110 Level 1 compliant equipment, installation of a new generator docking station to comply with NEC 700.3(F), demolition and reconstruction of the concrete generator pad, interception and extension of five existing underground conduits (one 2.5", one 1.5", and three 1" conduits), installation of new feeders and control wiring from the ATS to the docking station, relocation of temperature sensors, installation of remote annunciator equipment, and associated electrical infrastructure modifications. The design was prepared by Sine Source Engineering of Logan, Utah, with DFCM approval dated July 31, 2026, and reviewed for code compliance by Thomas Peterson on September 8, 2026. The electrical design comprises three main sheets: a cover sheet, an abbreviations and legend sheet, an electrical site plan, and an electrical one-line diagram, specifying all work to conform to the 2021 and 2023 International Building Code, National Electrical Code, and local Utah codes.

The construction cost estimate for this Stage II invitation to bid is $165,000.00, with only contractors prequalified under the DFCM Stage I Prequalification process and listed on the current DFCM Prequalified Contractors list as of the solicitation date eligible to submit bids. The project documents contain detailed general notes, sheet-specific notes, and keyed notes addressing submittal requirements limited to two reviews, contractor responsibility for field verification and coordination with the building owner during non-business hours shutdowns, mandatory provision of a temporary portable generator with 10-second maximum startup time to maintain building operations during the switchover, strict adherence to code compliance standards, and comprehensive documentation requirements including as-built AutoCAD drawings with clarity matching original design documents. All electrical installations must comply with current NEC standards and DFCM requirements, with the contractor responsible for conduit routing, proper panel clearances, grounding systems, and coordination with existing electrical systems and other trades.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

SITE LOCATION PLAN

N

PROJECT ENGINEER

DESIGN TEAM

DFCM Project No. - 27060150

135 NORTH 100 WEST

LOGAN, UTAH 84321

95 WEST GOLF COURSE ROAD SUITE 102

PHONE: (435) 787-1445SINE SOURCE ENGINEERING

LOGAN, UTAH 84321

FAX: (877) 207-3199

CONTACT: ERIC RASMUSSEN

Special Use and Occupancy (e.g. High Rise, Covered Mall): __________________ Change in Use: Yes ______ No ______ Mixed Occupancy: Yes ______ No ______

Guildelines ADA Accessibility Building Conservation Uniform Code for National Electrical Code

Conservation Code International Energy International Fire Code International Plumbing Code International Mechanical Code International Building Code

YearYear

APPLICABLE CODES

A. Occupancy and Group: ________ ________ ________ ________ ________

CODE ANALYSIS

N/A

N/A

N/A X

DRAWING INDEX LOGAN FIRST DISTRICT COURT

GENERATOR AND TRANSFER SWITCH REPLACEMENT

X

BUILDING

LOCATIONLOGAN, UT

W 100 N

N

W

N M

AI

N

S

TR

EE

T

US 89

N

WLW'S

TRUCK STOP

LOGAN

H.S.

LOGAN

TABERNACLE

ELECTRICAL

EE001 ABBREVIATIONS, G.P.N., LEGEND &

SHEET INDEX

EP101 ELECTRICAL SITE PLAN

EP102 ELECTRICAL ONE-LINE DIAGRAM

1 2 3 4 5

A

B

C

D

1 2 3 4 5 SHEET OF 3

A

SHEET NUMBER

SHEET TITLE

COPYRIGHT:

C

D

DESCRIPTIONMARK DATE

B

CHK'D BY:

ISSUE TYPE:

ISSUE DATE:

DRAWN BY:

DFCM PROJECT NO:

Phone: (801) 538 - 3018 Salt Lake City, Utah 84114 4110 State Office Building

DFCM

dfcm.utah.gov

LOGAN

FIRST DISTRICT

COURT

GENERATOR

REPLACEMENT

Sine

Source

Engineering

95 West Golf Course Road

Suite 102

Logan, Ut 84321 office: (435) 787-1445 fax: 1-877-207-3199 www.sinesource.net

LA

ST

S

AV

E 7/

/2

T:

\J

O

BS

\2

L O

G

AN

C O

U R

T G

EN

ER

AT

O

R R

EP

LA

C

EM

EN

T\

D

R

AW

IN

G

S\

E

LE

C

TR

IC

AL

\S

IN

E

SO

U R

C E

PR

O

JE

C

T\

SH

EE

TS

\E E0

C

O

VE

R S

H

EE

T.

D

W G

MJR

#27060150

LA

ST

S

AV

ED

: 3

Ju l 2

135 NORTH 100 WEST

LOGAN, UTAH 84321

ECR

DFCM APPROVAL

JULY 31, 2026

CD SET

SSE

7/31/2026

COVER SHEET

EE000

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

REVIEWED FOR

CODE COMPLIANCE

THOMAS PETERSON

09/08/2026

SHEET INDEX

Sheet Number Sheet Title

EE000 COVER SHEET

EE001 ABBREVIATIONS, G.P.N., LEGEND & SHEET INDEX

EP101 ELECTRICAL SITE PLAN

EP102 ELECTRICAL ONE-LINE DIAGRAM

1 2 3 4 5

A

B

C

D

1 2 3 4 5 SHEET OF 3

A

SHEET NUMBER

SHEET TITLE

COPYRIGHT:

C

D

DESCRIPTIONMARK DATE

B

CHK'D BY:

ISSUE TYPE:

ISSUE DATE:

DRAWN BY:

DFCM PROJECT NO:

Phone: (801) 538 - 3018 Salt Lake City, Utah 84114 4110 State Office Building

DFCM

dfcm.utah.gov

LOGAN

FIRST DISTRICT

COURT

GENERATOR

REPLACEMENT

Sine

Source

Engineering

95 West Golf Course Road

Suite 102

Logan, Ut 84321 office: (435) 787-1445 fax: 1-877-207-3199 www.sinesource.net

LA

ST

S

AV

E 4/

/2

T:

\J

O

BS

\2

L O

G

AN

C O

U R

T G

EN

ER

AT

O

R R

EP

LA

C

EM

EN

T\

D

R

AW

IN

G

S\

E

LE

C

TR

IC

AL

\S

IN

E

SO

U R

C E

PR

O

JE

C

T\

SH

EE

TS

\E E0

A

BB

R

EV

IA

TI

O

N S, G .P

.N

LE

G

EN

D

S

H

EE

T

IN

D

EX

.D W

G

MJR

#27060150

LA

ST

S

AV

ED

: 1

Ap r 2

135 NORTH 100 WEST

LOGAN, UTAH 84321

ECR

DFCM APPROVAL

JULY 31, 2026

CD SET

SSE

7/31/2026

ELECTRICAL ABBREVIATIONS

A

AF

AFF

AFG

AFI

AIC

AL

ARCH

AS

AWG

BLDG

BKBD

C

CAB

CAT

C/B

CKT

CLG

CO

COMM

CONN

CU

DEMO

DISC

DN

DWG

EA

ELEC

ELEV

EMER, EM

EMT

EOLR

EQUIP

EX, EXIST

FBO

FCU

FF

FIXT

FLEX

FLUOR

FT

GFI

GND

HP

HVAC

IG

IMC

IN

ISC

JB, J-BOX

KCMIL

KVA

KW

AMPERE

AMP FUSE

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

ARC-FAULT CIRCUIT-INTERRUPTER

AMPERE INTERRUPTING CAPACITY

ALUMINUM

ARCHITECT(URAL)

AMP SWITCH

AMERICAN WIRE GAUGE

BUILDING

BACKBOARD

CONDUIT

CABINET

CATALOG/CATEGORY

CIRCUIT BREAKER

CIRCUIT

CEILING

CONDUIT ONLY

COMMUNICATION

CONNECTION

COPPER

DEMOLITION/DEMOLISH

DISCONNECT

DOWN

DRAWING

EACH

ELECTRICAL

ELEVATOR

EMERGENCY

ELECTRICAL METALLIC TUBING

END OF LINE RESISTOR

EQUIPMENT

EXISTING

FURNISHED BY OTHERS

FAN COIL UNIT

FINISHED FLOOR

FIXTURE

FLEXIBLE METALLIC CONDUIT (STEEL)

FLUORESCENT

FEET OR FOOT

GROUND FAULT INTERRUPTER

GROUND

HORSEPOWER

HEATING, VENTILATING & AIR CONDITIONING

ISOLATED GROUND

INTERMEDIATE METAL CONDUIT

INCH(ES)

SHORT CIRCUIT AMPERES, KA

JUNCTION BOX

THOUSAND CIRCULAR MILS

KILOVOLT AMPERE

KILOWATT

LTG

MAX

MCB

MECH

MFR

MIN

MLO

MTD

NEC

NECA

NEMA

NEUT

NFC

NC

NIC

NL

NO

NTS

OCP

P

PH

PNL

PWR

QTY

RECEP

REQ'D

RGSC

RM

SCHED

SECT

SP

SN

SPEC

SW

SWBD

SWGR

SYS

TEMP

TELE

XFMR

T-STAT

TWP

TWSP

TYP

UBC

UL

UMC

UNO

V

VA

W W/

WG

WP

LIGHTING

MAXIMUM

MAIN CIRCUIT BREAKER

MECHANICAL

MANUFACTURER

MINIMUM

MAIN LUGS ONLY

MOUNTED

NATIONAL ELECTRICAL CODE

NATIONAL ELECTRICAL CONTRACTOR'S ASSOCIATION

NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION

NEUTRAL

NATIONAL FIRE CODE

NORMALLY CLOSED

NOT IN CONTRACT

NIGHT LITE

NORMALLY OPEN

NOT TO SCALE

OVERCURRENT PROTECTION

POLE

PHASE

PANEL

POWER

QUANTITY

RECEPTACLE

REQUIRED

RIGID GALVANIZED STEEL CONDUIT

ROOM

SCHEDULE

SECTION

SINGLE POLE

SOLID NEUTRAL

SPECIFICATION

SWITCH

SWITCHBOARD

SWITCH GEAR

SYSTEM

TEMPORARY

TELEPHONE

TRANSFORMER

THERMOSTAT

TWISTED PAIR

TWISTED SHEILDED PAIR

TYPICAL

UNIFORM BUILDING CODE

UNDERWRITERS LABORATORY

UNIFORM MECHANICAL CODE

UNLESS NOTED OTHERWISE

VOLT OR VOLTAGE

VOLT AMPERE

WATT

WITH

WIRE GUARD

UL LISTED WEATHERPROOF, NEMA 3R or 4

FACP

J

WP

m MOTOR PROTECTIVE THERMAL SWITCH

SIMPLEX OUTLET

DUPLEX OUTLET

DUPLEX OUTLET: GROUND FAULT INTERRUPTER

DUPLEX OUTLET: EMERGENCY SOURCE

DUPLEX OUTLET: WEATHERPROOF

DOUBLE DUPLEX OUTLET

DOUBLE DUPLEX OUTLET: GROUND FAULT INTERRUPTER

DOUBLE DUPLEX OUTLET: EMERGENCY GROUND FAULT

INTERRUPTER

SPECIAL OUTLET: SEE PANEL SCHEDULE

JUNCTION BOX

DISCONNECT, 22KAIC MINIMUM

AUTOMATIC TRANSFER SWITCH

QUANTITY OF CONDUCTORS: SHORT LINES = PHASE /SWITCH LONG

LINES = NEUTRAL

HOME-RUN

DISTRIBUTION PANEL

PANELBOARD

COMMUNICATIONS RACK

PHONE BACKBOARD

FIRE ALARM CONTROL PANEL

DOUBLE DUPLEX OUTLET: EMERGENCY SOURCE

COMMUNICATIONS ENCLOSURE

SSU MOTOR PROTECTIVE FUSED THERMAL SWITCH

DATA RACK; FREE STANDING CABINET

XA

YP

FEEDER SIZE (REFER TO CONDUIT AND CONDUCTOR SCHEDULE

UNLESS OTHERWISE NOTED)

A

XA

YP

x-y

BREAKER: "x" = BREAKER AMPERAGE "y" = QUANTITY OF POLES

BRANCH PANEL

GROUND

CT AND METER

DIRECT METER

TRANSFORMER

GENERATOR

ATS ANNUNCIATOR

TRANSFER SWITCH (AUTOMATIC UNLESS OTHERWISE NOTED)

SURGE PROTECTIVE DEVICE

DISCONNECT SWITCH: "x" = SWITCH AMPERAGE "y" = QUANTITY OF

POLES

FUSE; "x" = FUSE TYPE; "y" = FUSE AMPERAGE

MOTOR; hp = MOTOR HORSEPOWERhp

BRANCH PANEL WITH MAIN BREAKER

BRANCH PANEL WITH SUBFEED BREAKER

x

POWER AND DISTRIBUTION

COMMUNICATIONS

FIRE ALARM

BRANCH CIRCUITING

ELECTRICAL LEGEND

ONE-LINE

M

M

SIMPLEX OUTLET: GROUND FAULT INTERRUPTER

G

METER/METER SOCKET

DETAIL CALL-OUT; TOP "X" REFERS TO DETAIL NUMBER & BOTTOM

"XXX" REFERS TO SHEET NUMBER

ANNOTATIONS

XXX

X

GENERAL WALL-MOUNTED BOX HEIGHT DETAIL

BAR STRAPS

+60 = TOP OF BOX

60 = MIDDLE OF BOX

-60 = BOTTOM OF BOX

NAC NOTIFICATION APPLIANCE CIRCUIT PANEL

# ELECTRICAL KEYED NOTE CALLOUT

STRUCTURAL KEYED NOTE CALLOUT#

ATS

DOCKING STATION FOR PORTABLE GENERATORDS

1. ALL ELECTRICAL INSTALLATIONS TO CONFORM TO THE LATEST NEC AND LOCAL CODES.

2. REVIEW THE STATE DESIGN REQUIREMENTS MANUAL PRIOR TO BID. NOTIFY ENGINEER OF CONFLICTS BETWEEN

STATE REQUIREMENTS AND THESE DOCUMENTS PRIOR TO BID.

3. SUBMITTALS FOR EACH SYSTEM WILL BE REVIEWED BY ENGINEER UP TO TWO TIMES--ONE FULL SUBMITTAL FOR OVERALL COMPLIANCE AND ONE RESUBMITTAL. ADDITIONAL REVIEWS WILL BE CHARGED TO CONTRACTOR AT

ENGINEER'S STANDARD BILLING RATE.

4. SUBMITTALS TO ENGINEER SHALL INCLUDE ALL SPECIFIED SYSTEMS IN FIRST SUBMITTAL. PARTIAL SUBMITTALS WILL BE RETURNED TO CONTRACTOR AS INCOMPLETE AND WILL BE CONSIDERED ONE OF TWO INCLUDED

SUBMITTAL REVIEWS.

5. THE CLARITY OF RECORD DRAWING CHANGES MADE BY THE CONTRACTOR SHALL BE EQUAL TO THE ORIGINAL DRAWINGS AS JUDGED BY THE ARCHITECT OR THE RECORD SET WILL BE RETURNED TO THE CONTRACTOR FOR

CLARIFICATION.

6. “RECORD” OR “AS-BUILT” DRAWINGS SHALL BE FURNISHED BY THE CONTRACTOR AT JOB COMPLETION, THE CONTRACTOR SHALL BE REQUIRED TO FURNISH A COMPLETE SET OF “BLUE-PRINT READY” AUTOCAD ELECTRICAL DRAWINGS FOR ALL CONTRACTOR GENERATED CHANGES FROM THE DRAWINGS OF A CLARITY EQUAL TO THE ORIGINAL DRAWINGS AS JUDGED BY THE ENGINEER. CONTACT ENGINEER FOR REPRODUCIBLE ORIGINAL MEDIA.

PROVIDE DRAWINGS IN AUTOCAD FORMAT.

7. EMT IS NOT ALLOWED IN EXTERIOR APPLICATIONS

8. ALL UNDERGROUND CONDUITS SHALL USE WRAPPED RIGID CONDUIT FOR ALL BENDS OVER 30 DEGREES PER DFCM

STANDARD.

9. MOUNTING HEIGHT OF GENERAL PURPOSE OUTLETS AND SWITCHES SHALL BE 16” TO BOTTOM AND 48” TO TOP

RESPECTIVELY UNLESS OTHERWISE NOTED.

10. ALL PARALLEL CONDUCTORS TO BE INSTALLED IN ACCORDANCE WITH NEC ARTICLE 310.4. WIRE IS TO BE LAID ON A

FLAT SURFACE FOR MEASUREMENT. USE TORQUE WRENCH ON TERMINATIONS.

11. A GFI OUTLET SHALL BE INSTALLED AT EACH LOCATION DESIGNATED BY “GFI” ON THE DRAWINGS. DOWNSTREAM

PROTECTION BY A GFI OUTLET UPSTREAM IS NOT ALLOWED.

12. FIELD VERIFY CONDITIONS FOR NEW WIRING. SURFACE RACEWAYS MUST RECEIVE PRIOR APPROVAL FROM THE ARCHITECT BEFORE BID AND MUST BE PAINTED TO MATCH THE SURFACE ON WHICH THEY ARE MOUNTED.

13. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE TO FIELD VERIFY ALL PANEL CLEARANCES PER NEC 110.26

AND NOTIFY ELECTRICAL ENGINEER OF CONFLICTS.

14. CIRCUIT WIRE SIZES MUST, AT MINIMUM, MATCH BRANCH CIRCUIT BREAKERS PER NEC. VERIFY WITH PANEL

SCHEDULES BEFORE PULLING WIRE.

15. ALL ELECTRICAL EQUIPMENT SHALL BE LOCATED SO AS NOT TO INTERFERE WITH WOOD TRIM AND MOLDINGS.

16. THE ELECTRICAL CONTRACTOR SHALL RUN RACEWAYS IN A NEAT AND WORKMANLIKE MANNER.

17. ALL PATCH, REPAIR, REPAINT AND COVER UP REQUIRED AS A RESULT OF EMERGENCY GENERATOR SYSTEM UPGRADE IS TO BE THE RESPONSIBILITY OF THE TRADE CONTRACTOR, BUT ACTUAL WORK IS TO BE PERFORMED BY

QUALIFIED PERSONNEL.

18. REMOVE ALL UNUSED CONDUITS AND CIRCUITS AS THEY ARE IDENTIFIED AS UNUSED OR ABANDONED.

19. DO NOT SCALE FLOOR PLANS. FIELD VERIFY CONDITIONS FOR ACCURATE DIMENSIONS AND FLOOR PLANS.

20. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE TO FIELD VERIFY ALL PANEL CLEARANCES PER NEC 110.26

21. PANEL INDEXES SHALL INCLUDE ALL PERTINENT INFORMATION ON THE PANEL SCHEDULES INCLUDING INFORMATION ON LIGHTS AND OUTLETS. DO NOT SIMPLY COPY THE CIRCUIT DESCRIPTION COLUMN. INDEXES TO BE

TYPEWRITTEN.

22. PROVIDE A GENERATOR SYSTEM GROUND PER NEC 250.30.

23. BEFORE RUNNING CONDUITS, PLACING OUTLETS OR ORDERING EQUIPMENT, THE CONTRACTOR SHALL REVIEW THE SPECIFICATIONS AND SHOP DRAWINGS OF THE EQUIPMENT SERVED BY THE CONDUIT, OUTLETS, AND/OR

EQUIPMENT.

24. ELECTRICAL CONTRACTOR SHALL INSTALL A PULL STRING IN ALL UNUSED POWER AND LIGHTING CONDUITS.

25. DISCONNECT SWITCHES ARE SHOWN IN APPROXIMATE LOCATIONS ONLY. CONTRACTOR SHALL FIELD VERIFY LOCATION OF ALL ELECTRICAL SWITCHES AND MOTOR CONTROL FOR PROPER CODE CLEARANCES. NOTIFY ARCHITECT IMMEDIATELY OF ANY CONFLICTS WITH OTHER TRADES REGARDING PROPER EQUIPMENT CLEARANCES.

26. ALL OUTLETS MUST BE MOUNTED FLUSH WITH THE COVER PLATE AND SECURED FIRMLY TO THE OUTLET BOX.

27. IDENTIFY ALL EMERGENCY OUTLET COVER PLATES WITH THE PANEL AND CIRCUIT NUMBER.

28. PROVIDE AN EQUIPMENT GROUNDING CONDUCTOR, PULLED INTO THE CONDUIT WITH THE PHASE CONDUCTOR, IN

ALL SERVICE, FEEDER, AND BRANCH CIRCUITS.

29. PROVIDE A NEUTRAL CONDUCTOR FOR EACH BREAKER TRIP HANDLE. NEUTRALS SHALL NOT BE SHARED BETWEEN

BRANCH CIRCUITS.

30. ALL CIRCUITS TO BE MINIMUM #12 CU IN MINIMUM 3/4” CONDUIT UNLESS OTHERWISE NOTED.

31. MC CABLE IS NOT AN APPROVED ALTERNATE TO CONDUCTORS IN CONDUIT.

32. WHERE THERE ARE CONFLICTS IN THE DRAWINGS AND/OR SPECIFICATIONS THE CONTRACTOR SHALL NOTIFY THE ENGINEER PRIOR TO BID. WHERE NO NOTIFICATION IS GIVEN THE MORE STRINGENT INTERPRETATION (GENERALLY

INTERPRETED TO BE THE MORE COSTLY) WILL BE ENFORCED.

33. ALL PANEL AND SWITCHBOARD SHUTDOWNS SHALL BE COORDINATED IN ADVANCE WITH OWNER.

34. SHUTDOWNS SHALL BE DONE DURING OWNER'S NON-BUSINESS HOURS, GENERALLY CONSIDERED TO BE NIGHTS AND HOLIDAYS. POWER SHALL BE RESTORED TO AFFECTED AREAS PRIOR TO OWNER'S NEXT SCHEDULED USE OF

AREA.

35. CONTRACTOR SHALL IMPLEMENT METHODS TO MINIMIZE ALL SHUTDOWNS (SERVICE, FEEDERS & CIRCUITS)

DURATIONS.

GENERAL PROJECT NOTES

ABBREVIATIONS, G.P.N.,

LEGEND & SHEET INDEX

EE001

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

REVIEWED FOR

CODE COMPLIANCE

CHILLER

1. EXISTING ITEMS TO BE REMOVED ARE INDICATED AS BOLD/DASHED. ITEMS TO REMAIN

ARE SHOWN AS LIGHT/SOLID.

2. CIRCUIT ROUTING IS SCHEMATIC UNLESS OTHERWISE NOTED.

3. PANEL LOCATIONS INDICATED ARE APPROXIMATE. FIELD VERIFY EXACT LOCATIONS.

4. ALL NEW HORIZONTAL CONDUITS SHALL BE RUN UNDERGROUND UNLESS INDICATED IN

DRAWINGS OR WRITTEN PERMISSION FROM DFCM PRIOR TO BIDDING.

GENERAL SHEET NOTES

1. EXISTING UTILITY TRANSFORMER, METERING SWITCH BOARD, SERVICE, PANELS, AND

EQUIPMENT INDICATED TO REMAIN.

2. REPLACE EXISTING EMERGENCY GENERATOR AND ATS WITH NEW EMERGENCY

GENERATOR AND ATS. UPGRADE SITE AS INDICATED TO ACCOUNT FOR GENERATOR

SWITCHOVER

3. INTERCEPT (5)EXISTING UNDERGROUND CONDUITS SERVING GENERATOR ( (1)2.5", (1)1.5" &

(3)1") AND EXTEND CONDUITS TO DOCKING STATION. REPLACE EXISTING GENERATOR

FEEDERS, CONTROL WIRING, AND BRANCH CIRCUITS WITH NEW COMPLETE FROM ATS OR

SUPPLY PANEL TO GENERATOR DOCKING STATION.

4. PROVIDE NEW DOCKING STATION FOR GENERATOR TO COMPLY WITH NEC 700.3 (F). REFER

TO SHEET EP102 FOR ADDITIONAL INFORMATION.

5. DEMO EXISTING CONCRETE AS INDICATED AND REPLACE TO ACCOMMODATE FOR NEW

GENERATOR PAD.

6. PROVIDE LEVEL 12" REINFORCED GENERATOR CONCRETE PAD. REINFORCED PAD SHALL

FINISH 2" ABOVE SURROUNDING CONCRETE AND SHALL BE A MINIMUM OF 6" LARGER IN

ALL DIRECTIONS THAN THE GENERATOR FOOTPRINT. EXTEND PAD TO CMU WALLS ON

GENERATOR'S SOUTH AND WEST SIDES. SEE B/EP101.

7. REPLACE EXISTING CONCRETE PAD WITH NEW 6" SLOPED CONCRETE PAD. MATCH

PREVIOUS PAD SLOPE. SEE PAD DETAIL B/EP101.

8. PROVIDE (3) NEW CIRCUITS TO DOCKING STATION ROUTED THROUGH (3)1" CONDUITS

INDICATED IN KEYED NOTE #3. EXTEND CIRCUITS TO GENERATOR ACCESSORIES IN (3)1"

NEW CONDUITS.

9. PROVIDE NEW UNDERGROUND FEEDERS FROM DOCKING STATION TO GENERATOR. SEE

ONE-LINE.

10. PROVIDE 1.25" CONDUIT FROM DOCKING STATION TO GENERATOR WITH NEW CONTROL

WIRING COMPLETE FROM ATS TO EQUIPMENT PER NEW GENERATOR SHOP DRAWING

REQUIREMENTS.

11. REPLACE EXISTING ANNUNCIATOR WITH NEW RECESSED ANNUNCIATOR AS NEEDED BY

NEW GENERATOR SYSTEM. CUT, PATCH, REPAIR AND PAINT SHEET ROCK AS NEEDED.

PROVIDE NEW CONTROL WIRING FROM ATS TO ANNUNCIATOR. REFER TO GENERATOR

SHOP DRAWINGS FOR CONTROL WIRING REQUIREMENTS.

12. PROVIDE 1" CONDUIT FROM GENERATOR TO E-STOP BUTTON.

13. INTERCEPT EXISTING SURFACE MOUNTED GALVANIZED CONDUIT AND RE-ROUTE TO

DRAIN AS NEEDED TO INSTALL NEW CEMENT PAD.

14. RELOCATE EXISTING TEMPERATURE SENSOR AWAY FROM NEW DOCKING STATION.

UTILIZE EXISTING BACK BOX WITH NEW NEMA 3R COVER AS JUNCTION AND SPLICE POINT.

RELOCATE SENSOR 2' TO THE EAST AND 2' HIGHER THAN EXISTING LOCATION WITH

SURFACE MOUNT CONDUIT ON CMU WALL.

SHEET KEYED NOTES

EP101

2,3

ANN 11

GEN.

UT

XFMR

"H1A" "L1A"

"L1B" "L1C"

"EML"

"ATS"

"TE"

"EMH"

"T1"

"MDP"

T1

TE

1 1

EXISTING

UTILITY

TRANSFORMER

EXISTING

MAIN

SWITCHBOARD

EXISTING

CHILLER

UT

EXISTING

DISC

CHILLER

TO

ATS

TO

EML

TO

ATS

NEW

DOCKING

STATION

ESTOP

(E)UBC (E)UBC (E)UBC

(E )U

C

(E)UC (E)UC (E)UC

(E )3

ØU

F

(E)3ØUF (E)3ØUF

(E )U

BC

NEW150KWGENERATOR PAD

3ØUF

UBCUC

UB

CUC

3Ø

UF

3Ø

UF

L1B -13L1B

-15L1B -32

EXISTING

UTILITY

TRANSFORMER

EXISTING

MAIN

SWITCHBOARD

EXISTING

CHILLER

UT

WPUIEXISTING

DISC

CHILLER

EXISTING

DISC

TO

ATS

EXISTING

GENERATOR

TO BE

REPLACED

TO

ATS

TO

EML

(E )3

ØU

F

(E)3ØUF (E)3ØUF (E)3ØUF

(E )U

C

(E)UC (E)UC (E)UC

(E)UBC

(E)UBC

(E )U

BC

(D)3ØUF

(D)UC

(D)UBC

1 2 3 4 5

A

B

C

D

1 2 3 4 5 SHEET OF 3

A

SHEET NUMBER

SHEET TITLE

COPYRIGHT:

C

D

DESCRIPTIONMARK DATE

B

CHK'D BY:

ISSUE TYPE:

ISSUE DATE:

DRAWN BY:

DFCM PROJECT NO:

Phone: (801) 538 - 3018 Salt Lake City, Utah 84114 4110 State Office Building

DFCM

dfcm.utah.gov

LOGAN

FIRST DISTRICT

COURT

GENERATOR

REPLACEMENT

Sine

Source

Engineering

95 West Golf Course Road

Suite 102

Logan, Ut 84321 office: (435) 787-1445 fax: 1-877-207-3199 www.sinesource.net

LA

ST

S

AV

E 7/

/2

T:

\J

O

BS

\2

L O

G

AN

C O

U R

T G

EN

ER

AT

O

R R

EP

LA

C

EM

EN

T\

D

R

AW

IN

G

S\

E

LE

C

TR

IC

AL

\S

IN

E

SO

U R

C E

PR

O

JE

C

T\

SH

EE

TS

\E P1

E

LE

C

TR

IC

AL

S

IT

E

PL

AN

.D W

G

MJR

#27060150

LA

ST

S

AV

ED

: 3

Ju l 2

135 NORTH 100 WEST

LOGAN, UTAH 84321

ECR

DFCM APPROVAL

JULY 31, 2026

CD SET

SSE

7/31/2026

ELECTRICAL SITE PLAN

EP101

Scale: 1"=20'-0"1

N

W EELECTRICAL SITE PLAN

Scale: 1/8"=1'-0"2

ENLARGED GENERATOR

PAD: DEMO

Scale: 1/8"=1'-0"3

ENLARGED GENERATOR

PAD: NEW

LOCATION MOUNTING

PANEL PANEL "L1B" TYPE EXISTING 3 Ø 4 WIRE 120/208 VOLTS

DOWNSTAIRS FLUSH

NEW REMARKS *PROVIDE NEW BREAKER IN EXISTING PANEL ELECTRICAL X SURFACE

X EXISTING ROOM

1 NEMA RATING 400 AMP MAIN

BOLT ON BREAKERS 400 LUGS

ISOLATED GROUND BUS BREAKER

SURGE PROTECT (SPD)

No. BRKR CIRCUIT DESCRIPTION L O M

WIRE/CND CIRC.

LOAD

CIRC.

LOAD

WIRE/CND

L O M CIRCUIT DESCRIPTION BRKR No.

A P P N G C A B C P N G C A P

1 20 3 EX: ROLL UP DOOR EX: ELEV 2 PIT LTG 20 1 2

3 - - - 0 EX: 20 1 4

5 - - - 0 EX: PLUG RM 153 20 1 6

7 20 3 EX: ROLL UP DOOR 0 EX: PLUG RM 152 20 1 8

9 - - - 0 EX: PLUG RM 151 20 1 10

11 - - - 0 EX: PLUG RM 149 20 1 12

13 20 1 GENERATOR BATTERY CHARGER 1 12S 12S 12S 1 1440 1440 EX: FRIDGE RM 150 20 1 14

15 30* 2 GENERATOR HTR 1 10 10 10 1 2000 2000 EX: PLUG RM 150 20 1 16

17 - - - 1 10 2000 2000 EX: PLUG RM 150 20 1 18

19 20 1 EX: PLUG RM 122 0 EX: VENDING RM 150 20 1 20

21 20 1 EX: LTG ELEV 1 PIT 0 EX: PLUG RM 140 & EXTERIOR 20 1 22

23 20 1 EX: PLUG RM 118 0 EX: PLUG RMS 141, 148, 142 20 1 24

25 20 1 EX: PLUG RM 118 0 EX: PLUG RM 138 20 1 26

27 20 1 EX: PLUG RM 118 0 EX: PLUG RMS 139, 130 20 1 28

29 20 1 EX: PLUG RM 118 0 EX: PLUG RM 138 20 1 30

31 20 1 EX: PLUG RM 150 2000 2000 10 10 10 1 1 DOCKING PLUG 30* 2 32

33 20 1 EX: PLUG RM 150 2000 2000 10 1 - - - 34

35 20 1 EX: DISPOSAL 0 EX: LTG CARPORT 20 1 36

37 20 1 EX: LTG ELEV 3 PIT 0 EX: CARPORT PANEL 100 3 38

39 20 1 EX: LTG ELEV 4 PIT 0 - - - 40

41 20 1 EX: LTG ELEV 5 PIT 0 - - - 42

TOTALS 3440 4000 2000

AIC EXISTING

SCCR EXISTING

FEEDER SEE ONE-LINE AMPS/PHASE 29 33 17 PARALLEL RUNS SEE ONE-LINE

BREAKER CODES

A=ARC-FAULT; G=GROUND FAULT; H=HACR; L=LOCKING HANDLE; S=SHUNT TRIP; R=RED PAINTED HANDLE; SF=SUB FEED BREAKER

WIRE CODES

I=ADD'L ISO GROUND TO MATCH SAFETY GROUND; S=UNLESS OTHERWISE SPECIFIED

GENERAL CODES

1LIN=SEE ONE-LINE DIAGRAM

DETAIL KEYED NOTES

1. ALL PENETRATIONS THROUGH CONCRETE AND/OR BUILDING SHALL BE WITH RIGID CONDUITS PER DFCM STANDARD.

2. PROVIDE STEEL PLATE WITH SAME DIMENSIONS AS PANEL BOTTOM PLATE. PUNCH PLATE PER CONDUITS ENTERING PANEL TO

STRAIGHTEN/ORGANIZE CONDUITS PRIOR TO FINAL RISE INTO PANEL.

3. TRANSITION TO WRAPPED RIGID CONDUIT FOR ALL BENDS GREATER THAN 30 DEGREES PER DFCM STANDARD

PVC PVC

TYPICAL PANEL

STEEL PLATE

CONCRETE/BUILDING

PENETRATIONS

RIGID ELBOW, WRAPPED

CONCRETE FLOOR LEVEL

TYPICAL WRAPPED

RIGID RISER

STEEL CHANNEL SUPPORT(S)

RIGID RIGID

Scale: N.T.S.A CONDUIT RISER DETAIL

N

W

E

N

W

E

1. REMOVE EXISTING FLOOR SLAB AS REQ'D. REPLACE WITH NEW 6" FLOOR SLAB, REINFORCED WITH #4 BARS AT 12"

ON CENTER EACH WAY, CENTERED AT 3" DEPTH.

2. AT NEW GENERATOR FOOTPRINT, THICKEN SLAB TO 12" MINIMUM, EXTENDING 6" MINIMUM BEYOND THE EDGES OF GENERATOR FOOTPRINT. EXTEND PAD TO CMU WALL FOUNDATION ON SOUTH AND WEST SIDES. ADD AN ADDITIONAL MAT OF #4 REINFORCED BARS AT 12" ON CENTERED EACH WAY, 3" FROM BOTTOM OF 12" SLAB

PORTION.

3. SEE SITE FOR OVERALL PAD LAYOUT.

4. PROVIDE REBAR DOWELS INTO EXIST CMU WALL 12" ON CENTER AND WIRE TIE TO GENERATOR PAD REBAR.

DETAIL KEYED NOTES

PAD DETAIL

SCALE: NTSB

SEE SITE

SEE SITE

6"

1'

12"

SEE SITE

GENERATOR

2"

CMU WALL

FLATMATCH EXISTING

SLOPE 4

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

REVIEWED FOR

CODE COMPLIANCE

NEW AUTOMATIC

TRANSFER SWITCH 3-POLE

250 AMP, 277/480V, 3 PHASE

'ATS'

Scale: NO SCALE1

ELECTRICAL

ONE-LINE DIAGRAM: DEMO

GENERATOR DUAL DOCKING STATION

& LOAD BANK CONNECTION 'DS'

250 AMP, 277/480V, 3Ø, NEMA 3R

TEMPORARY 150KW

277/480V, 3ɸ, 4W

GENERATORG

225A 3P

GENERATOR CAM-LOCK CABLES

G

NEW 150KW

277/480V, 3ɸ, 4W

DIESEL GENERATOR,

24 HR TANK FILLED TO MAX LINE,

ALUMINUM, W.P. ENCLOSURE

225A 3P

EPO

#2 CU

ROD ROD STEEL

UFER

(PAD)

GROUND BAR

#4 CU

#2 CU

1. EXISTING SERVICE AND ELECTRICAL DISTRIBUTION TO REMAIN.

2. REPLACE EXISTING EMERGENCY GENERATOR AND TRANSFER SWITCH WITH

NEW NFPA 110 LEVEL 1 COMPLIANT GENERATOR AND TRANSFER SWITCH.

3. INTERCEPT EXISTING UNDERGROUND EMERGENCY GENERATOR FEEDER

CONDUIT AND EXTEND CONDUIT TO DOCKING STATION. ACTUAL FEEDER ROUTE

UNKNOWN. VERIFY ROUTE PRIOR TO CONSTRUCTION AND NOTIFY ENGINEER OF

DISCREPANCY. PROVIDE NEW FEEDERS COMPLETE FROM ATS TO DOCKING

STATION.

4. PROVIDE NEW DOCKING STATION (TRYSTAR TMTS-5 OR EQUIVALENT) FOR

GENERATOR TO COMPLY WITH NEC 700.3 (F). DOCKING STATION SHALL BE

OPERABLE PRIOR TO DEMOLITION OF EXISTING GENERATOR. REFER TO KEYED

NOTE #5.

5. CONTRACTOR SHALL PROVIDE A PORTABLE EMERGENCY GENERATOR WITH

MAXIMUM 10 SEC STARTUP TIME TO KEEP BUILDING OPERATIONAL DURING

GENERATOR CHANGEOVER. CONNECT PORTABLE GENERATOR TO DOCKING

STATION. GENERATOR SHALL AUTOMATICALLY START WITH SIGNAL FROM

BUILDING ATS. PERFORM AND DOCUMENT TEST OF POSITIVE BUILDING

SWITCHOVER PRIOR TO REMOVING EXISTING GENERATOR. TEMPORARY

GENERATOR SHALL BE MAINTAINED ONSITE AND OPERATIONAL UNTIL NEW

GENERATOR IS HAS PASSED ALL INSPECTIONS.

6. PROVIDE GENERATOR GROUNDING ELECTRODE PER NEC.

7. PROVIDE REMOTE GENERATOR ANNUNCIATOR NEAR CONTROL ROOM CLOSET

ADJACENT TO ENTRY DOOR. ROUTE CONDUIT OVERHEAD FROM ATS TO

ANNUNCIATOR.

8. INTERCEPT EXISTING 1.5" CONTROL CONDUIT AND EXTEND CONDUIT TO

DOCKING STATION. PROVIDE ADDITIONAL 1.5" CONDUIT FROM DOCKING STATION

TO GENERATOR. INSTALL NEW CONTROL WIRING COMPLETE FROM ATS TO

EQUIPMENT PER NEW GENERATOR SHOP DRAWINGS REQUIREMENTS.

9. INTERCEPT (3)1" BRANCH CIRCUIT CONDUITS FROM PANEL "L1B" AND EXTEND TO

DOCKING STATION. PROVIDE (2) ADDITIONAL CONDUITS FROM DOCKING STATION

TO GENERATOR. CIRCUIT WITH NEW CONDUCTORS FROM PANEL "L1B" TO

EQUIPMENT. SEE PANEL SCHEDULE FOR CONDUCTOR SIZING.

10. PROVIDE SIGN TO INDICATE TYPE AND LOCATION OF EMERGENCY STANDBY

POWER SOURCE PER NEC 700.7.

11. LOCATE EMERGENCY GENERATOR STOP BUTTON AT ENTRY TO GENERATOR

ENCLOSURE.

12. PROVIDE BREAKER COORDINATION WITH EXISTING DOWNSTREAM BREAKERS.

TO COMPLY WITH NEC 700.32 FOR EMERGENCY DISTRIBUTION.

SHEET KEYED NOTES

1. ALL CONDUCTORS ARE CONSIDERED TO BE COPPER UNLESS SPECIFICALLY

NOTED OTHERWISE.

2. COORDINATE SHUTDOWNS WITH OWNER IN ADVANCE. DO NOT PROCEED WITH

SHUTDOWNS WITHOUT OWNER'S WRITTEN APPROVAL.

3. ALL SHUTDOWNS SHALL BE DONE DURING OWNER'S NON-WORKING HOURS,

GENERALLY CONSIDERED TO BE NIGHTS AND HOLIDAYS. POWER SHALL BE

RESTORED TO AFFECTED AREAS PRIOR TO NEXT REGULARLY SCHEDULED

WORKING HOURS. SEE KEYED NOTE #5 FOR TEMPORARY GENERATOR

REQUIREMENTS TO KEEP BUILDING OPERATIONAL DURING CONSTRUCTION.

4. AIC RATINGS SHOWN INDICATE MINIMUM REQUIRED VALUES. SCCR RATINGS

ARE TO MATCH OR EXCEED AIC RATINGS.

5. A FULL SIZE EQUIPMENT GROUNDING CONDUCTOR SIZED FOR THE

OVERCURRENT PROTECTIVE DEVICE PROTECTING THE CIRCUIT IS REQUIRED IN

EACH RACEWAY OR CABLE FOR PARALLELED CIRCUITS.

6. CONTRACTOR SHALL DOCUMENT FEEDER CONDUCTOR LENGTH ON FIELD

REDLINE SET.

7. RUN PORTIONS OF GROUNDING ELECTRODE CONDUCTORS NOT CONCEALED IN

BUILDING FINISHES IN CONDUIT.

8. ALL NEW HORIZONTALLY RAN CONDUIT SHALL BE RAN UNDERGROUND.

GENERAL SHEET NOTES

CONDUIT AND CONDUCTOR SCHEDULE NOTES

1. CONDUCTORS SHOWN ARE SHOWN FOR EACH CONDUIT WITH MODIFICATIONS

AS NOTED IN NOTE #5. ALL CONDUCTORS SHOWN ARE THWN FOR CU OR

THWN OR XHHW FOR AL UNLESS OTHERWISE NOTED.

2. PROVIDE EQUIPMENT GROUNDING CONDUCTORS PER NEC TABLE 250-122

WHEN CIRCUIT BREAKERS ARE SIZED GREATER THAN AMPERE RATING SHOWN

IN TABLE.

3. PROVIDE #10 NEUTRALS FOR MULTIWIRE BRANCH CIRCUITS SERVING

COMPUTERS.

4. GROUND (G) CONDUCTOR MAY BE DELETED ON SERVICE ENTRANCE

CONDUCTORS.

5. SYMBOL SUBSCRIPTS:

· "IG": INCLUDE IG (INSULATED/ISOLATED GROUND CONDUCTOR)

SCHEDULED ALONG WITH THE GROUND OF EQUIPMENT GROUND

CONDUCTOR.

· "SE": SUBSTITUTE "SE" CONDUCTOR FOR "G" CONDUCTOR SHOWN,

WHICH IS SIZED FOR THE GROUNDING OF THE SECONDARY OF THE

SEPARATELY DERIVED SYSTEM.

· "2N": INCLUDE TWO NEUTRAL CONDUCTORS, SIZED AS SCHEDULED FOR

PHASED AND NEUTRAL CONDUCTORS.

· "R": RACEWAY ONLY. CONDUCTORS PROVIDED BY UTILITY.

· "V": PHASE AND NEUTRAL CONDUCTORS UPSIZED FOR VOLTAGE DROP.

UPSIZE GROUNDING CONDUCTOR(G) PER NEC 250.122(B).

· "A": ALUMINUM CONDUCTORS ALLOWED FOR FEEDER INDICATED.

ALUMINUM CONDUCTORS ARE NOT TO BE USED FOR CONNECTIONS

TO MOTORS OR MOTOR DRIVEN EQUIPMENT.

6. A FULL SIZE GROUNDING CONDUCTOR (SE OR G AND/OR IG) SHALL BE

INSTALLED IN EACH RACEWAY OR CABLE FOR PARALLELED CIRCUITS.

7. GROUNDING CONDUCTORS (G, IG, AND SE) SHALL BE OF THE SAME

CONDUCTOR MATERIAL AS THE CORRESPONDING PHASE CONDUCTORS TO

KEEP TABLE CALCULATIONS IN 7 . ACCORDANCE WITH NEC REQUIREMENTS.

8. INCREASE CONDUIT TO NEXT LARGEST STANDARD CONDUIT SIZE WHEN IG IS

USED.

* -CONDUIT SIZED FOR COMPACT ALUMINUM CONDUCTORS. USE COPPER CONDUIT

SIZE FOR STANDARD SIZE CONDUCTORS

SUBSCRIPTS (SEE NOTE 5)

XX

#### SCHEDULE NUMBER

CONDUCTOR MATERIALS1

S2QUANTITY OF PARALLEL RUNS

SIZE OF CONDUCTORS

QUANTITY OF

PHASE/NEUTRAL CONDUCTORS

1" CONDUIT

7A

1600A 3P

225A 3P

EXISTNG "MDP"

277/480V, 3Ø, 4W, 65KAIC

PANEL

"EMH"

FROM

METERING

SWITCHBOARD

112.5KVA

XFMR

Scale: NO SCALE2

ELECTRICAL

ONE-LINE DIAGRAM: TEMP

Scale: NO SCALE3

ELECTRICAL

ONE-LINE DIAGRAM: NEW

PANEL

"EMH"

112.5KVA

XFMR

PANEL

"EMH"

112.5KVA

XFMR

225A 3P

EXISTING MDP

277/480V, 3Ø, 4W, 65 KAIC

225A 3P

EXISTING MDP

277/480V, 3Ø, 4W, 65KAIC

REPLACE EXISTING

150KW, 277/480V

EMERGENCY

GENERATOR

G

225A 3P

1" CONDUIT

DEMO

EXISTING

ATS

175A 3P

400A 3P

XXA

3P

100A 3P

XXA

3P

100A 3P

PANEL

"E2"

PANEL

"E3"

PANEL

"E2A"

PANEL

"E3A"

PANEL

"EML" 1

400A 3P

XXA

3P

100A 3P

XXA

3P

100A 3P

PANEL

"E2"

PANEL

"E3"

PANEL

"E2A"

PANEL

"E3A"

PANEL

"EML" 1

400A 3P

XXA

3P

100A 3P

XXA

3P

100A 3P

UPS

DISC

PANEL

"E2"

PANEL

"E3"

PANEL

"E2A"

PANEL

"E3A"

PANEL

"EML" 1

1 1

1 1

175A 3P

175A 3P

1 1

1 1

1 1

1 1

DEMO

EXISTING

ATS2 A 3

GENERATOR DUAL DOCKING STATION

& LOAD BANK CONNECTION 'DS'

300 AMP, 277/480V, 3Ø, NEMA 3R

UPS

DISC

UPS

DISC

A

9 10

1 2 3 4 5

A

B

C

D

1 2 3 4 5 SHEET OF 3

A

SHEET NUMBER

SHEET TITLE

COPYRIGHT:

C

D

DESCRIPTIONMARK DATE

B

CHK'D BY:

ISSUE TYPE:

ISSUE DATE:

DRAWN BY:

DFCM PROJECT NO:

Phone: (801) 538 - 3018 Salt Lake City, Utah 84114 4110 State Office Building

DFCM

dfcm.utah.gov

LOGAN

FIRST DISTRICT

COURT

GENERATOR

REPLACEMENT

Sine

Source

Engineering

95 West Golf Course Road

Suite 102

Logan, Ut 84321 office: (435) 787-1445 fax: 1-877-207-3199 www.sinesource.net

LA

ST

S

AV

E 7/

/2

T:

\J

O

BS

\2

L O

G

AN

C O

U R

T G

EN

ER

AT

O

R R

EP

LA

C

EM

EN

T\

D

R

AW

IN

G

S\

E

LE

C

TR

IC

AL

\S

IN

E

SO

U R

C E

PR

O

JE

C

T\

SH

EE

TS

\E P1

E

LE

C

TR

IC

AL

O

N E-

LI

N

E D

IA

G

R

AM

.D W

G

MJR

#27060150

LA

ST

S

AV

ED

: 2

Ju l 2

135 NORTH 100 WEST

LOGAN, UTAH 84321

ECR

DFCM APPROVAL

JULY 31, 2026

CD SET

SSE

7/31/2026

ELECTRICAL ONE-LINE

DIAGRAM

EP102

DIVISION OF FACILITIES

CONSTRUCTION AND

MANAGEMENT

REVIEWED FOR

CODE COMPLIANCE

THOMAS PETERSON

09/08/2026

./Service 1/Pictures/TX-1 NamePlate.JPG ./Service 1/Pictures/TX-1 NamePlate.JPG ./Service 1/Pictures/TX-1 NamePlate.JPG ./Service 1/Pictures/TX-1 NamePlate.JPG ./Service 1/Pictures/TX-1 NamePlate.JPG ./Service 1/Pictures/TX-1 NamePlate.JPG

Sheets and Views
EE000 COVER SHEET
EE001 ABBREVIATIONS, G.P.N., LEGEND & SHEET INDEX
EP101 ELECTRICAL SITE PLAN
0.1 - SITE
0.1 - SITE ENLARGED
0.1 - SITE DEMO
EP102 ELECTRICAL ONE-LINE DIAGRAM
6 - ONE-LINE DIAGRAMS

File details come from the government source that posted it. Updated .