This is an approved electrical design plan document for the State of Utah's Division of Facilities Construction and Management (DFCM) for Project #27060150, involving the replacement of an emergency generator system at the Logan First District Court located at 135 North 100 West, Logan, Utah 84321. The project scope includes the replacement of the existing 150 kW emergency generator and automatic transfer switch (ATS) with new NFPA 110 Level 1 compliant equipment, installation of a new generator docking station to comply with NEC 700.3(F), demolition and reconstruction of the concrete generator pad, interception and extension of five existing underground conduits (one 2.5", one 1.5", and three 1" conduits), installation of new feeders and control wiring from the ATS to the docking station, relocation of temperature sensors, installation of remote annunciator equipment, and associated electrical infrastructure modifications. The design was prepared by Sine Source Engineering of Logan, Utah, with DFCM approval dated July 31, 2026, and reviewed for code compliance by Thomas Peterson on September 8, 2026. The electrical design comprises three main sheets: a cover sheet, an abbreviations and legend sheet, an electrical site plan, and an electrical one-line diagram, specifying all work to conform to the 2021 and 2023 International Building Code, National Electrical Code, and local Utah codes.
The construction cost estimate for this Stage II invitation to bid is $165,000.00, with only contractors prequalified under the DFCM Stage I Prequalification process and listed on the current DFCM Prequalified Contractors list as of the solicitation date eligible to submit bids. The project documents contain detailed general notes, sheet-specific notes, and keyed notes addressing submittal requirements limited to two reviews, contractor responsibility for field verification and coordination with the building owner during non-business hours shutdowns, mandatory provision of a temporary portable generator with 10-second maximum startup time to maintain building operations during the switchover, strict adherence to code compliance standards, and comprehensive documentation requirements including as-built AutoCAD drawings with clarity matching original design documents. All electrical installations must comply with current NEC standards and DFCM requirements, with the contractor responsible for conduit routing, proper panel clearances, grounding systems, and coordination with existing electrical systems and other trades.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
SITE LOCATION PLAN
N
PROJECT ENGINEER
DESIGN TEAM
DFCM Project No. - 27060150
135 NORTH 100 WEST
LOGAN, UTAH 84321
95 WEST GOLF COURSE ROAD SUITE 102
PHONE: (435) 787-1445SINE SOURCE ENGINEERING
LOGAN, UTAH 84321
FAX: (877) 207-3199
CONTACT: ERIC RASMUSSEN
Special Use and Occupancy (e.g. High Rise, Covered Mall): __________________ Change in Use: Yes ______ No ______ Mixed Occupancy: Yes ______ No ______
Guildelines ADA Accessibility Building Conservation Uniform Code for National Electrical Code
Conservation Code International Energy International Fire Code International Plumbing Code International Mechanical Code International Building Code
YearYear
APPLICABLE CODES
A. Occupancy and Group: ________ ________ ________ ________ ________
CODE ANALYSIS
N/A
N/A
N/A X
DRAWING INDEX LOGAN FIRST DISTRICT COURT
GENERATOR AND TRANSFER SWITCH REPLACEMENT
X
BUILDING
LOCATIONLOGAN, UT
W 100 N
N
W
N M
AI
N
S
TR
EE
T
US 89
N
WLW'S
TRUCK STOP
LOGAN
H.S.
LOGAN
TABERNACLE
ELECTRICAL
EE001 ABBREVIATIONS, G.P.N., LEGEND &
SHEET INDEX
EP101 ELECTRICAL SITE PLAN
EP102 ELECTRICAL ONE-LINE DIAGRAM
1 2 3 4 5
A
B
C
D
1 2 3 4 5 SHEET OF 3
A
SHEET NUMBER
SHEET TITLE
COPYRIGHT:
C
D
DESCRIPTIONMARK DATE
B
CHK'D BY:
ISSUE TYPE:
ISSUE DATE:
DRAWN BY:
DFCM PROJECT NO:
Phone: (801) 538 - 3018 Salt Lake City, Utah 84114 4110 State Office Building
DFCM
dfcm.utah.gov
LOGAN
FIRST DISTRICT
COURT
GENERATOR
REPLACEMENT
Sine
Source
Engineering
95 West Golf Course Road
Suite 102
Logan, Ut 84321 office: (435) 787-1445 fax: 1-877-207-3199 www.sinesource.net
LA
ST
S
AV
E 7/
/2
T:
\J
O
BS
\2
L O
G
AN
C O
U R
T G
EN
ER
AT
O
R R
EP
LA
C
EM
EN
T\
D
R
AW
IN
G
S\
E
LE
C
TR
IC
AL
\S
IN
E
SO
U R
C E
PR
O
JE
C
T\
SH
EE
TS
\E E0
C
O
VE
R S
H
EE
T.
D
W G
MJR
#27060150
LA
ST
S
AV
ED
: 3
Ju l 2
135 NORTH 100 WEST
LOGAN, UTAH 84321
ECR
DFCM APPROVAL
JULY 31, 2026
CD SET
SSE
7/31/2026
COVER SHEET
EE000
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
THOMAS PETERSON
09/08/2026
SHEET INDEX
Sheet Number Sheet Title
EE000 COVER SHEET
EE001 ABBREVIATIONS, G.P.N., LEGEND & SHEET INDEX
EP101 ELECTRICAL SITE PLAN
EP102 ELECTRICAL ONE-LINE DIAGRAM
1 2 3 4 5
A
B
C
D
1 2 3 4 5 SHEET OF 3
A
SHEET NUMBER
SHEET TITLE
COPYRIGHT:
C
D
DESCRIPTIONMARK DATE
B
CHK'D BY:
ISSUE TYPE:
ISSUE DATE:
DRAWN BY:
DFCM PROJECT NO:
Phone: (801) 538 - 3018 Salt Lake City, Utah 84114 4110 State Office Building
DFCM
dfcm.utah.gov
LOGAN
FIRST DISTRICT
COURT
GENERATOR
REPLACEMENT
Sine
Source
Engineering
95 West Golf Course Road
Suite 102
Logan, Ut 84321 office: (435) 787-1445 fax: 1-877-207-3199 www.sinesource.net
LA
ST
S
AV
E 4/
/2
T:
\J
O
BS
\2
L O
G
AN
C O
U R
T G
EN
ER
AT
O
R R
EP
LA
C
EM
EN
T\
D
R
AW
IN
G
S\
E
LE
C
TR
IC
AL
\S
IN
E
SO
U R
C E
PR
O
JE
C
T\
SH
EE
TS
\E E0
A
BB
R
EV
IA
TI
O
N S, G .P
.N
LE
G
EN
D
S
H
EE
T
IN
D
EX
.D W
G
MJR
#27060150
LA
ST
S
AV
ED
: 1
Ap r 2
135 NORTH 100 WEST
LOGAN, UTAH 84321
ECR
DFCM APPROVAL
JULY 31, 2026
CD SET
SSE
7/31/2026
ELECTRICAL ABBREVIATIONS
A
AF
AFF
AFG
AFI
AIC
AL
ARCH
AS
AWG
BLDG
BKBD
C
CAB
CAT
C/B
CKT
CLG
CO
COMM
CONN
CU
DEMO
DISC
DN
DWG
EA
ELEC
ELEV
EMER, EM
EMT
EOLR
EQUIP
EX, EXIST
FBO
FCU
FF
FIXT
FLEX
FLUOR
FT
GFI
GND
HP
HVAC
IG
IMC
IN
ISC
JB, J-BOX
KCMIL
KVA
KW
AMPERE
AMP FUSE
ABOVE FINISHED FLOOR
ABOVE FINISHED GRADE
ARC-FAULT CIRCUIT-INTERRUPTER
AMPERE INTERRUPTING CAPACITY
ALUMINUM
ARCHITECT(URAL)
AMP SWITCH
AMERICAN WIRE GAUGE
BUILDING
BACKBOARD
CONDUIT
CABINET
CATALOG/CATEGORY
CIRCUIT BREAKER
CIRCUIT
CEILING
CONDUIT ONLY
COMMUNICATION
CONNECTION
COPPER
DEMOLITION/DEMOLISH
DISCONNECT
DOWN
DRAWING
EACH
ELECTRICAL
ELEVATOR
EMERGENCY
ELECTRICAL METALLIC TUBING
END OF LINE RESISTOR
EQUIPMENT
EXISTING
FURNISHED BY OTHERS
FAN COIL UNIT
FINISHED FLOOR
FIXTURE
FLEXIBLE METALLIC CONDUIT (STEEL)
FLUORESCENT
FEET OR FOOT
GROUND FAULT INTERRUPTER
GROUND
HORSEPOWER
HEATING, VENTILATING & AIR CONDITIONING
ISOLATED GROUND
INTERMEDIATE METAL CONDUIT
INCH(ES)
SHORT CIRCUIT AMPERES, KA
JUNCTION BOX
THOUSAND CIRCULAR MILS
KILOVOLT AMPERE
KILOWATT
LTG
MAX
MCB
MECH
MFR
MIN
MLO
MTD
NEC
NECA
NEMA
NEUT
NFC
NC
NIC
NL
NO
NTS
OCP
P
PH
PNL
PWR
QTY
RECEP
REQ'D
RGSC
RM
SCHED
SECT
SP
SN
SPEC
SW
SWBD
SWGR
SYS
TEMP
TELE
XFMR
T-STAT
TWP
TWSP
TYP
UBC
UL
UMC
UNO
V
VA
W W/
WG
WP
LIGHTING
MAXIMUM
MAIN CIRCUIT BREAKER
MECHANICAL
MANUFACTURER
MINIMUM
MAIN LUGS ONLY
MOUNTED
NATIONAL ELECTRICAL CODE
NATIONAL ELECTRICAL CONTRACTOR'S ASSOCIATION
NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION
NEUTRAL
NATIONAL FIRE CODE
NORMALLY CLOSED
NOT IN CONTRACT
NIGHT LITE
NORMALLY OPEN
NOT TO SCALE
OVERCURRENT PROTECTION
POLE
PHASE
PANEL
POWER
QUANTITY
RECEPTACLE
REQUIRED
RIGID GALVANIZED STEEL CONDUIT
ROOM
SCHEDULE
SECTION
SINGLE POLE
SOLID NEUTRAL
SPECIFICATION
SWITCH
SWITCHBOARD
SWITCH GEAR
SYSTEM
TEMPORARY
TELEPHONE
TRANSFORMER
THERMOSTAT
TWISTED PAIR
TWISTED SHEILDED PAIR
TYPICAL
UNIFORM BUILDING CODE
UNDERWRITERS LABORATORY
UNIFORM MECHANICAL CODE
UNLESS NOTED OTHERWISE
VOLT OR VOLTAGE
VOLT AMPERE
WATT
WITH
WIRE GUARD
UL LISTED WEATHERPROOF, NEMA 3R or 4
FACP
J
WP
m MOTOR PROTECTIVE THERMAL SWITCH
SIMPLEX OUTLET
DUPLEX OUTLET
DUPLEX OUTLET: GROUND FAULT INTERRUPTER
DUPLEX OUTLET: EMERGENCY SOURCE
DUPLEX OUTLET: WEATHERPROOF
DOUBLE DUPLEX OUTLET
DOUBLE DUPLEX OUTLET: GROUND FAULT INTERRUPTER
DOUBLE DUPLEX OUTLET: EMERGENCY GROUND FAULT
INTERRUPTER
SPECIAL OUTLET: SEE PANEL SCHEDULE
JUNCTION BOX
DISCONNECT, 22KAIC MINIMUM
AUTOMATIC TRANSFER SWITCH
QUANTITY OF CONDUCTORS: SHORT LINES = PHASE /SWITCH LONG
LINES = NEUTRAL
HOME-RUN
DISTRIBUTION PANEL
PANELBOARD
COMMUNICATIONS RACK
PHONE BACKBOARD
FIRE ALARM CONTROL PANEL
DOUBLE DUPLEX OUTLET: EMERGENCY SOURCE
COMMUNICATIONS ENCLOSURE
SSU MOTOR PROTECTIVE FUSED THERMAL SWITCH
DATA RACK; FREE STANDING CABINET
XA
YP
FEEDER SIZE (REFER TO CONDUIT AND CONDUCTOR SCHEDULE
UNLESS OTHERWISE NOTED)
A
XA
YP
x-y
BREAKER: "x" = BREAKER AMPERAGE "y" = QUANTITY OF POLES
BRANCH PANEL
GROUND
CT AND METER
DIRECT METER
TRANSFORMER
GENERATOR
ATS ANNUNCIATOR
TRANSFER SWITCH (AUTOMATIC UNLESS OTHERWISE NOTED)
SURGE PROTECTIVE DEVICE
DISCONNECT SWITCH: "x" = SWITCH AMPERAGE "y" = QUANTITY OF
POLES
FUSE; "x" = FUSE TYPE; "y" = FUSE AMPERAGE
MOTOR; hp = MOTOR HORSEPOWERhp
BRANCH PANEL WITH MAIN BREAKER
BRANCH PANEL WITH SUBFEED BREAKER
x
POWER AND DISTRIBUTION
COMMUNICATIONS
FIRE ALARM
BRANCH CIRCUITING
ELECTRICAL LEGEND
ONE-LINE
M
M
SIMPLEX OUTLET: GROUND FAULT INTERRUPTER
G
METER/METER SOCKET
DETAIL CALL-OUT; TOP "X" REFERS TO DETAIL NUMBER & BOTTOM
"XXX" REFERS TO SHEET NUMBER
ANNOTATIONS
XXX
X
GENERAL WALL-MOUNTED BOX HEIGHT DETAIL
BAR STRAPS
+60 = TOP OF BOX
60 = MIDDLE OF BOX
-60 = BOTTOM OF BOX
NAC NOTIFICATION APPLIANCE CIRCUIT PANEL
# ELECTRICAL KEYED NOTE CALLOUT
STRUCTURAL KEYED NOTE CALLOUT#
ATS
DOCKING STATION FOR PORTABLE GENERATORDS
1. ALL ELECTRICAL INSTALLATIONS TO CONFORM TO THE LATEST NEC AND LOCAL CODES.
2. REVIEW THE STATE DESIGN REQUIREMENTS MANUAL PRIOR TO BID. NOTIFY ENGINEER OF CONFLICTS BETWEEN
STATE REQUIREMENTS AND THESE DOCUMENTS PRIOR TO BID.
3. SUBMITTALS FOR EACH SYSTEM WILL BE REVIEWED BY ENGINEER UP TO TWO TIMES--ONE FULL SUBMITTAL FOR OVERALL COMPLIANCE AND ONE RESUBMITTAL. ADDITIONAL REVIEWS WILL BE CHARGED TO CONTRACTOR AT
ENGINEER'S STANDARD BILLING RATE.
4. SUBMITTALS TO ENGINEER SHALL INCLUDE ALL SPECIFIED SYSTEMS IN FIRST SUBMITTAL. PARTIAL SUBMITTALS WILL BE RETURNED TO CONTRACTOR AS INCOMPLETE AND WILL BE CONSIDERED ONE OF TWO INCLUDED
SUBMITTAL REVIEWS.
5. THE CLARITY OF RECORD DRAWING CHANGES MADE BY THE CONTRACTOR SHALL BE EQUAL TO THE ORIGINAL DRAWINGS AS JUDGED BY THE ARCHITECT OR THE RECORD SET WILL BE RETURNED TO THE CONTRACTOR FOR
CLARIFICATION.
6. “RECORD” OR “AS-BUILT” DRAWINGS SHALL BE FURNISHED BY THE CONTRACTOR AT JOB COMPLETION, THE CONTRACTOR SHALL BE REQUIRED TO FURNISH A COMPLETE SET OF “BLUE-PRINT READY” AUTOCAD ELECTRICAL DRAWINGS FOR ALL CONTRACTOR GENERATED CHANGES FROM THE DRAWINGS OF A CLARITY EQUAL TO THE ORIGINAL DRAWINGS AS JUDGED BY THE ENGINEER. CONTACT ENGINEER FOR REPRODUCIBLE ORIGINAL MEDIA.
PROVIDE DRAWINGS IN AUTOCAD FORMAT.
7. EMT IS NOT ALLOWED IN EXTERIOR APPLICATIONS
8. ALL UNDERGROUND CONDUITS SHALL USE WRAPPED RIGID CONDUIT FOR ALL BENDS OVER 30 DEGREES PER DFCM
STANDARD.
9. MOUNTING HEIGHT OF GENERAL PURPOSE OUTLETS AND SWITCHES SHALL BE 16” TO BOTTOM AND 48” TO TOP
RESPECTIVELY UNLESS OTHERWISE NOTED.
10. ALL PARALLEL CONDUCTORS TO BE INSTALLED IN ACCORDANCE WITH NEC ARTICLE 310.4. WIRE IS TO BE LAID ON A
FLAT SURFACE FOR MEASUREMENT. USE TORQUE WRENCH ON TERMINATIONS.
11. A GFI OUTLET SHALL BE INSTALLED AT EACH LOCATION DESIGNATED BY “GFI” ON THE DRAWINGS. DOWNSTREAM
PROTECTION BY A GFI OUTLET UPSTREAM IS NOT ALLOWED.
12. FIELD VERIFY CONDITIONS FOR NEW WIRING. SURFACE RACEWAYS MUST RECEIVE PRIOR APPROVAL FROM THE ARCHITECT BEFORE BID AND MUST BE PAINTED TO MATCH THE SURFACE ON WHICH THEY ARE MOUNTED.
13. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE TO FIELD VERIFY ALL PANEL CLEARANCES PER NEC 110.26
AND NOTIFY ELECTRICAL ENGINEER OF CONFLICTS.
14. CIRCUIT WIRE SIZES MUST, AT MINIMUM, MATCH BRANCH CIRCUIT BREAKERS PER NEC. VERIFY WITH PANEL
SCHEDULES BEFORE PULLING WIRE.
15. ALL ELECTRICAL EQUIPMENT SHALL BE LOCATED SO AS NOT TO INTERFERE WITH WOOD TRIM AND MOLDINGS.
16. THE ELECTRICAL CONTRACTOR SHALL RUN RACEWAYS IN A NEAT AND WORKMANLIKE MANNER.
17. ALL PATCH, REPAIR, REPAINT AND COVER UP REQUIRED AS A RESULT OF EMERGENCY GENERATOR SYSTEM UPGRADE IS TO BE THE RESPONSIBILITY OF THE TRADE CONTRACTOR, BUT ACTUAL WORK IS TO BE PERFORMED BY
QUALIFIED PERSONNEL.
18. REMOVE ALL UNUSED CONDUITS AND CIRCUITS AS THEY ARE IDENTIFIED AS UNUSED OR ABANDONED.
19. DO NOT SCALE FLOOR PLANS. FIELD VERIFY CONDITIONS FOR ACCURATE DIMENSIONS AND FLOOR PLANS.
20. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE TO FIELD VERIFY ALL PANEL CLEARANCES PER NEC 110.26
21. PANEL INDEXES SHALL INCLUDE ALL PERTINENT INFORMATION ON THE PANEL SCHEDULES INCLUDING INFORMATION ON LIGHTS AND OUTLETS. DO NOT SIMPLY COPY THE CIRCUIT DESCRIPTION COLUMN. INDEXES TO BE
TYPEWRITTEN.
22. PROVIDE A GENERATOR SYSTEM GROUND PER NEC 250.30.
23. BEFORE RUNNING CONDUITS, PLACING OUTLETS OR ORDERING EQUIPMENT, THE CONTRACTOR SHALL REVIEW THE SPECIFICATIONS AND SHOP DRAWINGS OF THE EQUIPMENT SERVED BY THE CONDUIT, OUTLETS, AND/OR
EQUIPMENT.
24. ELECTRICAL CONTRACTOR SHALL INSTALL A PULL STRING IN ALL UNUSED POWER AND LIGHTING CONDUITS.
25. DISCONNECT SWITCHES ARE SHOWN IN APPROXIMATE LOCATIONS ONLY. CONTRACTOR SHALL FIELD VERIFY LOCATION OF ALL ELECTRICAL SWITCHES AND MOTOR CONTROL FOR PROPER CODE CLEARANCES. NOTIFY ARCHITECT IMMEDIATELY OF ANY CONFLICTS WITH OTHER TRADES REGARDING PROPER EQUIPMENT CLEARANCES.
26. ALL OUTLETS MUST BE MOUNTED FLUSH WITH THE COVER PLATE AND SECURED FIRMLY TO THE OUTLET BOX.
27. IDENTIFY ALL EMERGENCY OUTLET COVER PLATES WITH THE PANEL AND CIRCUIT NUMBER.
28. PROVIDE AN EQUIPMENT GROUNDING CONDUCTOR, PULLED INTO THE CONDUIT WITH THE PHASE CONDUCTOR, IN
ALL SERVICE, FEEDER, AND BRANCH CIRCUITS.
29. PROVIDE A NEUTRAL CONDUCTOR FOR EACH BREAKER TRIP HANDLE. NEUTRALS SHALL NOT BE SHARED BETWEEN
BRANCH CIRCUITS.
30. ALL CIRCUITS TO BE MINIMUM #12 CU IN MINIMUM 3/4” CONDUIT UNLESS OTHERWISE NOTED.
31. MC CABLE IS NOT AN APPROVED ALTERNATE TO CONDUCTORS IN CONDUIT.
32. WHERE THERE ARE CONFLICTS IN THE DRAWINGS AND/OR SPECIFICATIONS THE CONTRACTOR SHALL NOTIFY THE ENGINEER PRIOR TO BID. WHERE NO NOTIFICATION IS GIVEN THE MORE STRINGENT INTERPRETATION (GENERALLY
INTERPRETED TO BE THE MORE COSTLY) WILL BE ENFORCED.
33. ALL PANEL AND SWITCHBOARD SHUTDOWNS SHALL BE COORDINATED IN ADVANCE WITH OWNER.
34. SHUTDOWNS SHALL BE DONE DURING OWNER'S NON-BUSINESS HOURS, GENERALLY CONSIDERED TO BE NIGHTS AND HOLIDAYS. POWER SHALL BE RESTORED TO AFFECTED AREAS PRIOR TO OWNER'S NEXT SCHEDULED USE OF
AREA.
35. CONTRACTOR SHALL IMPLEMENT METHODS TO MINIMIZE ALL SHUTDOWNS (SERVICE, FEEDERS & CIRCUITS)
DURATIONS.
GENERAL PROJECT NOTES
ABBREVIATIONS, G.P.N.,
LEGEND & SHEET INDEX
EE001
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
CHILLER
1. EXISTING ITEMS TO BE REMOVED ARE INDICATED AS BOLD/DASHED. ITEMS TO REMAIN
ARE SHOWN AS LIGHT/SOLID.
2. CIRCUIT ROUTING IS SCHEMATIC UNLESS OTHERWISE NOTED.
3. PANEL LOCATIONS INDICATED ARE APPROXIMATE. FIELD VERIFY EXACT LOCATIONS.
4. ALL NEW HORIZONTAL CONDUITS SHALL BE RUN UNDERGROUND UNLESS INDICATED IN
DRAWINGS OR WRITTEN PERMISSION FROM DFCM PRIOR TO BIDDING.
GENERAL SHEET NOTES
1. EXISTING UTILITY TRANSFORMER, METERING SWITCH BOARD, SERVICE, PANELS, AND
EQUIPMENT INDICATED TO REMAIN.
2. REPLACE EXISTING EMERGENCY GENERATOR AND ATS WITH NEW EMERGENCY
GENERATOR AND ATS. UPGRADE SITE AS INDICATED TO ACCOUNT FOR GENERATOR
SWITCHOVER
3. INTERCEPT (5)EXISTING UNDERGROUND CONDUITS SERVING GENERATOR ( (1)2.5", (1)1.5" &
(3)1") AND EXTEND CONDUITS TO DOCKING STATION. REPLACE EXISTING GENERATOR
FEEDERS, CONTROL WIRING, AND BRANCH CIRCUITS WITH NEW COMPLETE FROM ATS OR
SUPPLY PANEL TO GENERATOR DOCKING STATION.
4. PROVIDE NEW DOCKING STATION FOR GENERATOR TO COMPLY WITH NEC 700.3 (F). REFER
TO SHEET EP102 FOR ADDITIONAL INFORMATION.
5. DEMO EXISTING CONCRETE AS INDICATED AND REPLACE TO ACCOMMODATE FOR NEW
GENERATOR PAD.
6. PROVIDE LEVEL 12" REINFORCED GENERATOR CONCRETE PAD. REINFORCED PAD SHALL
FINISH 2" ABOVE SURROUNDING CONCRETE AND SHALL BE A MINIMUM OF 6" LARGER IN
ALL DIRECTIONS THAN THE GENERATOR FOOTPRINT. EXTEND PAD TO CMU WALLS ON
GENERATOR'S SOUTH AND WEST SIDES. SEE B/EP101.
7. REPLACE EXISTING CONCRETE PAD WITH NEW 6" SLOPED CONCRETE PAD. MATCH
PREVIOUS PAD SLOPE. SEE PAD DETAIL B/EP101.
8. PROVIDE (3) NEW CIRCUITS TO DOCKING STATION ROUTED THROUGH (3)1" CONDUITS
INDICATED IN KEYED NOTE #3. EXTEND CIRCUITS TO GENERATOR ACCESSORIES IN (3)1"
NEW CONDUITS.
9. PROVIDE NEW UNDERGROUND FEEDERS FROM DOCKING STATION TO GENERATOR. SEE
ONE-LINE.
10. PROVIDE 1.25" CONDUIT FROM DOCKING STATION TO GENERATOR WITH NEW CONTROL
WIRING COMPLETE FROM ATS TO EQUIPMENT PER NEW GENERATOR SHOP DRAWING
REQUIREMENTS.
11. REPLACE EXISTING ANNUNCIATOR WITH NEW RECESSED ANNUNCIATOR AS NEEDED BY
NEW GENERATOR SYSTEM. CUT, PATCH, REPAIR AND PAINT SHEET ROCK AS NEEDED.
PROVIDE NEW CONTROL WIRING FROM ATS TO ANNUNCIATOR. REFER TO GENERATOR
SHOP DRAWINGS FOR CONTROL WIRING REQUIREMENTS.
12. PROVIDE 1" CONDUIT FROM GENERATOR TO E-STOP BUTTON.
13. INTERCEPT EXISTING SURFACE MOUNTED GALVANIZED CONDUIT AND RE-ROUTE TO
DRAIN AS NEEDED TO INSTALL NEW CEMENT PAD.
14. RELOCATE EXISTING TEMPERATURE SENSOR AWAY FROM NEW DOCKING STATION.
UTILIZE EXISTING BACK BOX WITH NEW NEMA 3R COVER AS JUNCTION AND SPLICE POINT.
RELOCATE SENSOR 2' TO THE EAST AND 2' HIGHER THAN EXISTING LOCATION WITH
SURFACE MOUNT CONDUIT ON CMU WALL.
SHEET KEYED NOTES
EP101
2,3
ANN 11
GEN.
UT
XFMR
"H1A" "L1A"
"L1B" "L1C"
"EML"
"ATS"
"TE"
"EMH"
"T1"
"MDP"
T1
TE
1 1
EXISTING
UTILITY
TRANSFORMER
EXISTING
MAIN
SWITCHBOARD
EXISTING
CHILLER
UT
EXISTING
DISC
CHILLER
TO
ATS
TO
EML
TO
ATS
NEW
DOCKING
STATION
ESTOP
(E)UBC (E)UBC (E)UBC
(E )U
C
(E)UC (E)UC (E)UC
(E )3
ØU
F
(E)3ØUF (E)3ØUF
(E )U
BC
NEW150KWGENERATOR PAD
3ØUF
UBCUC
UB
CUC
3Ø
UF
3Ø
UF
L1B -13L1B
-15L1B -32
EXISTING
UTILITY
TRANSFORMER
EXISTING
MAIN
SWITCHBOARD
EXISTING
CHILLER
UT
WPUIEXISTING
DISC
CHILLER
EXISTING
DISC
TO
ATS
EXISTING
GENERATOR
TO BE
REPLACED
TO
ATS
TO
EML
(E )3
ØU
F
(E)3ØUF (E)3ØUF (E)3ØUF
(E )U
C
(E)UC (E)UC (E)UC
(E)UBC
(E)UBC
(E )U
BC
(D)3ØUF
(D)UC
(D)UBC
1 2 3 4 5
A
B
C
D
1 2 3 4 5 SHEET OF 3
A
SHEET NUMBER
SHEET TITLE
COPYRIGHT:
C
D
DESCRIPTIONMARK DATE
B
CHK'D BY:
ISSUE TYPE:
ISSUE DATE:
DRAWN BY:
DFCM PROJECT NO:
Phone: (801) 538 - 3018 Salt Lake City, Utah 84114 4110 State Office Building
DFCM
dfcm.utah.gov
LOGAN
FIRST DISTRICT
COURT
GENERATOR
REPLACEMENT
Sine
Source
Engineering
95 West Golf Course Road
Suite 102
Logan, Ut 84321 office: (435) 787-1445 fax: 1-877-207-3199 www.sinesource.net
LA
ST
S
AV
E 7/
/2
T:
\J
O
BS
\2
L O
G
AN
C O
U R
T G
EN
ER
AT
O
R R
EP
LA
C
EM
EN
T\
D
R
AW
IN
G
S\
E
LE
C
TR
IC
AL
\S
IN
E
SO
U R
C E
PR
O
JE
C
T\
SH
EE
TS
\E P1
E
LE
C
TR
IC
AL
S
IT
E
PL
AN
.D W
G
MJR
#27060150
LA
ST
S
AV
ED
: 3
Ju l 2
135 NORTH 100 WEST
LOGAN, UTAH 84321
ECR
DFCM APPROVAL
JULY 31, 2026
CD SET
SSE
7/31/2026
ELECTRICAL SITE PLAN
EP101
Scale: 1"=20'-0"1
N
W EELECTRICAL SITE PLAN
Scale: 1/8"=1'-0"2
ENLARGED GENERATOR
PAD: DEMO
Scale: 1/8"=1'-0"3
ENLARGED GENERATOR
PAD: NEW
LOCATION MOUNTING
PANEL PANEL "L1B" TYPE EXISTING 3 Ø 4 WIRE 120/208 VOLTS
DOWNSTAIRS FLUSH
NEW REMARKS *PROVIDE NEW BREAKER IN EXISTING PANEL ELECTRICAL X SURFACE
X EXISTING ROOM
1 NEMA RATING 400 AMP MAIN
BOLT ON BREAKERS 400 LUGS
ISOLATED GROUND BUS BREAKER
SURGE PROTECT (SPD)
No. BRKR CIRCUIT DESCRIPTION L O M
WIRE/CND CIRC.
LOAD
CIRC.
LOAD
WIRE/CND
L O M CIRCUIT DESCRIPTION BRKR No.
A P P N G C A B C P N G C A P
1 20 3 EX: ROLL UP DOOR EX: ELEV 2 PIT LTG 20 1 2
3 - - - 0 EX: 20 1 4
5 - - - 0 EX: PLUG RM 153 20 1 6
7 20 3 EX: ROLL UP DOOR 0 EX: PLUG RM 152 20 1 8
9 - - - 0 EX: PLUG RM 151 20 1 10
11 - - - 0 EX: PLUG RM 149 20 1 12
13 20 1 GENERATOR BATTERY CHARGER 1 12S 12S 12S 1 1440 1440 EX: FRIDGE RM 150 20 1 14
15 30* 2 GENERATOR HTR 1 10 10 10 1 2000 2000 EX: PLUG RM 150 20 1 16
17 - - - 1 10 2000 2000 EX: PLUG RM 150 20 1 18
19 20 1 EX: PLUG RM 122 0 EX: VENDING RM 150 20 1 20
21 20 1 EX: LTG ELEV 1 PIT 0 EX: PLUG RM 140 & EXTERIOR 20 1 22
23 20 1 EX: PLUG RM 118 0 EX: PLUG RMS 141, 148, 142 20 1 24
25 20 1 EX: PLUG RM 118 0 EX: PLUG RM 138 20 1 26
27 20 1 EX: PLUG RM 118 0 EX: PLUG RMS 139, 130 20 1 28
29 20 1 EX: PLUG RM 118 0 EX: PLUG RM 138 20 1 30
31 20 1 EX: PLUG RM 150 2000 2000 10 10 10 1 1 DOCKING PLUG 30* 2 32
33 20 1 EX: PLUG RM 150 2000 2000 10 1 - - - 34
35 20 1 EX: DISPOSAL 0 EX: LTG CARPORT 20 1 36
37 20 1 EX: LTG ELEV 3 PIT 0 EX: CARPORT PANEL 100 3 38
39 20 1 EX: LTG ELEV 4 PIT 0 - - - 40
41 20 1 EX: LTG ELEV 5 PIT 0 - - - 42
TOTALS 3440 4000 2000
AIC EXISTING
SCCR EXISTING
FEEDER SEE ONE-LINE AMPS/PHASE 29 33 17 PARALLEL RUNS SEE ONE-LINE
BREAKER CODES
A=ARC-FAULT; G=GROUND FAULT; H=HACR; L=LOCKING HANDLE; S=SHUNT TRIP; R=RED PAINTED HANDLE; SF=SUB FEED BREAKER
WIRE CODES
I=ADD'L ISO GROUND TO MATCH SAFETY GROUND; S=UNLESS OTHERWISE SPECIFIED
GENERAL CODES
1LIN=SEE ONE-LINE DIAGRAM
DETAIL KEYED NOTES
1. ALL PENETRATIONS THROUGH CONCRETE AND/OR BUILDING SHALL BE WITH RIGID CONDUITS PER DFCM STANDARD.
2. PROVIDE STEEL PLATE WITH SAME DIMENSIONS AS PANEL BOTTOM PLATE. PUNCH PLATE PER CONDUITS ENTERING PANEL TO
STRAIGHTEN/ORGANIZE CONDUITS PRIOR TO FINAL RISE INTO PANEL.
3. TRANSITION TO WRAPPED RIGID CONDUIT FOR ALL BENDS GREATER THAN 30 DEGREES PER DFCM STANDARD
PVC PVC
TYPICAL PANEL
STEEL PLATE
CONCRETE/BUILDING
PENETRATIONS
RIGID ELBOW, WRAPPED
CONCRETE FLOOR LEVEL
TYPICAL WRAPPED
RIGID RISER
STEEL CHANNEL SUPPORT(S)
RIGID RIGID
Scale: N.T.S.A CONDUIT RISER DETAIL
N
W
E
N
W
E
1. REMOVE EXISTING FLOOR SLAB AS REQ'D. REPLACE WITH NEW 6" FLOOR SLAB, REINFORCED WITH #4 BARS AT 12"
ON CENTER EACH WAY, CENTERED AT 3" DEPTH.
2. AT NEW GENERATOR FOOTPRINT, THICKEN SLAB TO 12" MINIMUM, EXTENDING 6" MINIMUM BEYOND THE EDGES OF GENERATOR FOOTPRINT. EXTEND PAD TO CMU WALL FOUNDATION ON SOUTH AND WEST SIDES. ADD AN ADDITIONAL MAT OF #4 REINFORCED BARS AT 12" ON CENTERED EACH WAY, 3" FROM BOTTOM OF 12" SLAB
PORTION.
3. SEE SITE FOR OVERALL PAD LAYOUT.
4. PROVIDE REBAR DOWELS INTO EXIST CMU WALL 12" ON CENTER AND WIRE TIE TO GENERATOR PAD REBAR.
DETAIL KEYED NOTES
PAD DETAIL
SCALE: NTSB
SEE SITE
SEE SITE
6"
1'
12"
SEE SITE
GENERATOR
2"
CMU WALL
FLATMATCH EXISTING
SLOPE 4
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
NEW AUTOMATIC
TRANSFER SWITCH 3-POLE
250 AMP, 277/480V, 3 PHASE
'ATS'
Scale: NO SCALE1
ELECTRICAL
ONE-LINE DIAGRAM: DEMO
GENERATOR DUAL DOCKING STATION
& LOAD BANK CONNECTION 'DS'
250 AMP, 277/480V, 3Ø, NEMA 3R
TEMPORARY 150KW
277/480V, 3ɸ, 4W
GENERATORG
225A 3P
GENERATOR CAM-LOCK CABLES
G
NEW 150KW
277/480V, 3ɸ, 4W
DIESEL GENERATOR,
24 HR TANK FILLED TO MAX LINE,
ALUMINUM, W.P. ENCLOSURE
225A 3P
EPO
#2 CU
ROD ROD STEEL
UFER
(PAD)
GROUND BAR
#4 CU
#2 CU
1. EXISTING SERVICE AND ELECTRICAL DISTRIBUTION TO REMAIN.
2. REPLACE EXISTING EMERGENCY GENERATOR AND TRANSFER SWITCH WITH
NEW NFPA 110 LEVEL 1 COMPLIANT GENERATOR AND TRANSFER SWITCH.
3. INTERCEPT EXISTING UNDERGROUND EMERGENCY GENERATOR FEEDER
CONDUIT AND EXTEND CONDUIT TO DOCKING STATION. ACTUAL FEEDER ROUTE
UNKNOWN. VERIFY ROUTE PRIOR TO CONSTRUCTION AND NOTIFY ENGINEER OF
DISCREPANCY. PROVIDE NEW FEEDERS COMPLETE FROM ATS TO DOCKING
STATION.
4. PROVIDE NEW DOCKING STATION (TRYSTAR TMTS-5 OR EQUIVALENT) FOR
GENERATOR TO COMPLY WITH NEC 700.3 (F). DOCKING STATION SHALL BE
OPERABLE PRIOR TO DEMOLITION OF EXISTING GENERATOR. REFER TO KEYED
NOTE #5.
5. CONTRACTOR SHALL PROVIDE A PORTABLE EMERGENCY GENERATOR WITH
MAXIMUM 10 SEC STARTUP TIME TO KEEP BUILDING OPERATIONAL DURING
GENERATOR CHANGEOVER. CONNECT PORTABLE GENERATOR TO DOCKING
STATION. GENERATOR SHALL AUTOMATICALLY START WITH SIGNAL FROM
BUILDING ATS. PERFORM AND DOCUMENT TEST OF POSITIVE BUILDING
SWITCHOVER PRIOR TO REMOVING EXISTING GENERATOR. TEMPORARY
GENERATOR SHALL BE MAINTAINED ONSITE AND OPERATIONAL UNTIL NEW
GENERATOR IS HAS PASSED ALL INSPECTIONS.
6. PROVIDE GENERATOR GROUNDING ELECTRODE PER NEC.
7. PROVIDE REMOTE GENERATOR ANNUNCIATOR NEAR CONTROL ROOM CLOSET
ADJACENT TO ENTRY DOOR. ROUTE CONDUIT OVERHEAD FROM ATS TO
ANNUNCIATOR.
8. INTERCEPT EXISTING 1.5" CONTROL CONDUIT AND EXTEND CONDUIT TO
DOCKING STATION. PROVIDE ADDITIONAL 1.5" CONDUIT FROM DOCKING STATION
TO GENERATOR. INSTALL NEW CONTROL WIRING COMPLETE FROM ATS TO
EQUIPMENT PER NEW GENERATOR SHOP DRAWINGS REQUIREMENTS.
9. INTERCEPT (3)1" BRANCH CIRCUIT CONDUITS FROM PANEL "L1B" AND EXTEND TO
DOCKING STATION. PROVIDE (2) ADDITIONAL CONDUITS FROM DOCKING STATION
TO GENERATOR. CIRCUIT WITH NEW CONDUCTORS FROM PANEL "L1B" TO
EQUIPMENT. SEE PANEL SCHEDULE FOR CONDUCTOR SIZING.
10. PROVIDE SIGN TO INDICATE TYPE AND LOCATION OF EMERGENCY STANDBY
POWER SOURCE PER NEC 700.7.
11. LOCATE EMERGENCY GENERATOR STOP BUTTON AT ENTRY TO GENERATOR
ENCLOSURE.
12. PROVIDE BREAKER COORDINATION WITH EXISTING DOWNSTREAM BREAKERS.
TO COMPLY WITH NEC 700.32 FOR EMERGENCY DISTRIBUTION.
SHEET KEYED NOTES
1. ALL CONDUCTORS ARE CONSIDERED TO BE COPPER UNLESS SPECIFICALLY
NOTED OTHERWISE.
2. COORDINATE SHUTDOWNS WITH OWNER IN ADVANCE. DO NOT PROCEED WITH
SHUTDOWNS WITHOUT OWNER'S WRITTEN APPROVAL.
3. ALL SHUTDOWNS SHALL BE DONE DURING OWNER'S NON-WORKING HOURS,
GENERALLY CONSIDERED TO BE NIGHTS AND HOLIDAYS. POWER SHALL BE
RESTORED TO AFFECTED AREAS PRIOR TO NEXT REGULARLY SCHEDULED
WORKING HOURS. SEE KEYED NOTE #5 FOR TEMPORARY GENERATOR
REQUIREMENTS TO KEEP BUILDING OPERATIONAL DURING CONSTRUCTION.
4. AIC RATINGS SHOWN INDICATE MINIMUM REQUIRED VALUES. SCCR RATINGS
ARE TO MATCH OR EXCEED AIC RATINGS.
5. A FULL SIZE EQUIPMENT GROUNDING CONDUCTOR SIZED FOR THE
OVERCURRENT PROTECTIVE DEVICE PROTECTING THE CIRCUIT IS REQUIRED IN
EACH RACEWAY OR CABLE FOR PARALLELED CIRCUITS.
6. CONTRACTOR SHALL DOCUMENT FEEDER CONDUCTOR LENGTH ON FIELD
REDLINE SET.
7. RUN PORTIONS OF GROUNDING ELECTRODE CONDUCTORS NOT CONCEALED IN
BUILDING FINISHES IN CONDUIT.
8. ALL NEW HORIZONTALLY RAN CONDUIT SHALL BE RAN UNDERGROUND.
GENERAL SHEET NOTES
CONDUIT AND CONDUCTOR SCHEDULE NOTES
1. CONDUCTORS SHOWN ARE SHOWN FOR EACH CONDUIT WITH MODIFICATIONS
AS NOTED IN NOTE #5. ALL CONDUCTORS SHOWN ARE THWN FOR CU OR
THWN OR XHHW FOR AL UNLESS OTHERWISE NOTED.
2. PROVIDE EQUIPMENT GROUNDING CONDUCTORS PER NEC TABLE 250-122
WHEN CIRCUIT BREAKERS ARE SIZED GREATER THAN AMPERE RATING SHOWN
IN TABLE.
3. PROVIDE #10 NEUTRALS FOR MULTIWIRE BRANCH CIRCUITS SERVING
COMPUTERS.
4. GROUND (G) CONDUCTOR MAY BE DELETED ON SERVICE ENTRANCE
CONDUCTORS.
5. SYMBOL SUBSCRIPTS:
· "IG": INCLUDE IG (INSULATED/ISOLATED GROUND CONDUCTOR)
SCHEDULED ALONG WITH THE GROUND OF EQUIPMENT GROUND
CONDUCTOR.
· "SE": SUBSTITUTE "SE" CONDUCTOR FOR "G" CONDUCTOR SHOWN,
WHICH IS SIZED FOR THE GROUNDING OF THE SECONDARY OF THE
SEPARATELY DERIVED SYSTEM.
· "2N": INCLUDE TWO NEUTRAL CONDUCTORS, SIZED AS SCHEDULED FOR
PHASED AND NEUTRAL CONDUCTORS.
· "R": RACEWAY ONLY. CONDUCTORS PROVIDED BY UTILITY.
· "V": PHASE AND NEUTRAL CONDUCTORS UPSIZED FOR VOLTAGE DROP.
UPSIZE GROUNDING CONDUCTOR(G) PER NEC 250.122(B).
· "A": ALUMINUM CONDUCTORS ALLOWED FOR FEEDER INDICATED.
ALUMINUM CONDUCTORS ARE NOT TO BE USED FOR CONNECTIONS
TO MOTORS OR MOTOR DRIVEN EQUIPMENT.
6. A FULL SIZE GROUNDING CONDUCTOR (SE OR G AND/OR IG) SHALL BE
INSTALLED IN EACH RACEWAY OR CABLE FOR PARALLELED CIRCUITS.
7. GROUNDING CONDUCTORS (G, IG, AND SE) SHALL BE OF THE SAME
CONDUCTOR MATERIAL AS THE CORRESPONDING PHASE CONDUCTORS TO
KEEP TABLE CALCULATIONS IN 7 . ACCORDANCE WITH NEC REQUIREMENTS.
8. INCREASE CONDUIT TO NEXT LARGEST STANDARD CONDUIT SIZE WHEN IG IS
USED.
* -CONDUIT SIZED FOR COMPACT ALUMINUM CONDUCTORS. USE COPPER CONDUIT
SIZE FOR STANDARD SIZE CONDUCTORS
SUBSCRIPTS (SEE NOTE 5)
XX
#### SCHEDULE NUMBER
CONDUCTOR MATERIALS1
S2QUANTITY OF PARALLEL RUNS
SIZE OF CONDUCTORS
QUANTITY OF
PHASE/NEUTRAL CONDUCTORS
1" CONDUIT
7A
1600A 3P
225A 3P
EXISTNG "MDP"
277/480V, 3Ø, 4W, 65KAIC
PANEL
"EMH"
FROM
METERING
SWITCHBOARD
112.5KVA
XFMR
Scale: NO SCALE2
ELECTRICAL
ONE-LINE DIAGRAM: TEMP
Scale: NO SCALE3
ELECTRICAL
ONE-LINE DIAGRAM: NEW
PANEL
"EMH"
112.5KVA
XFMR
PANEL
"EMH"
112.5KVA
XFMR
225A 3P
EXISTING MDP
277/480V, 3Ø, 4W, 65 KAIC
225A 3P
EXISTING MDP
277/480V, 3Ø, 4W, 65KAIC
REPLACE EXISTING
150KW, 277/480V
EMERGENCY
GENERATOR
G
225A 3P
1" CONDUIT
DEMO
EXISTING
ATS
175A 3P
400A 3P
XXA
3P
100A 3P
XXA
3P
100A 3P
PANEL
"E2"
PANEL
"E3"
PANEL
"E2A"
PANEL
"E3A"
PANEL
"EML" 1
400A 3P
XXA
3P
100A 3P
XXA
3P
100A 3P
PANEL
"E2"
PANEL
"E3"
PANEL
"E2A"
PANEL
"E3A"
PANEL
"EML" 1
400A 3P
XXA
3P
100A 3P
XXA
3P
100A 3P
UPS
DISC
PANEL
"E2"
PANEL
"E3"
PANEL
"E2A"
PANEL
"E3A"
PANEL
"EML" 1
1 1
1 1
175A 3P
175A 3P
1 1
1 1
1 1
1 1
DEMO
EXISTING
ATS2 A 3
GENERATOR DUAL DOCKING STATION
& LOAD BANK CONNECTION 'DS'
300 AMP, 277/480V, 3Ø, NEMA 3R
UPS
DISC
UPS
DISC
A
9 10
1 2 3 4 5
A
B
C
D
1 2 3 4 5 SHEET OF 3
A
SHEET NUMBER
SHEET TITLE
COPYRIGHT:
C
D
DESCRIPTIONMARK DATE
B
CHK'D BY:
ISSUE TYPE:
ISSUE DATE:
DRAWN BY:
DFCM PROJECT NO:
Phone: (801) 538 - 3018 Salt Lake City, Utah 84114 4110 State Office Building
DFCM
dfcm.utah.gov
LOGAN
FIRST DISTRICT
COURT
GENERATOR
REPLACEMENT
Sine
Source
Engineering
95 West Golf Course Road
Suite 102
Logan, Ut 84321 office: (435) 787-1445 fax: 1-877-207-3199 www.sinesource.net
LA
ST
S
AV
E 7/
/2
T:
\J
O
BS
\2
L O
G
AN
C O
U R
T G
EN
ER
AT
O
R R
EP
LA
C
EM
EN
T\
D
R
AW
IN
G
S\
E
LE
C
TR
IC
AL
\S
IN
E
SO
U R
C E
PR
O
JE
C
T\
SH
EE
TS
\E P1
E
LE
C
TR
IC
AL
O
N E-
LI
N
E D
IA
G
R
AM
.D W
G
MJR
#27060150
LA
ST
S
AV
ED
: 2
Ju l 2
135 NORTH 100 WEST
LOGAN, UTAH 84321
ECR
DFCM APPROVAL
JULY 31, 2026
CD SET
SSE
7/31/2026
ELECTRICAL ONE-LINE
DIAGRAM
EP102
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
REVIEWED FOR
CODE COMPLIANCE
THOMAS PETERSON
09/08/2026
./Service 1/Pictures/TX-1 NamePlate.JPG ./Service 1/Pictures/TX-1 NamePlate.JPG ./Service 1/Pictures/TX-1 NamePlate.JPG ./Service 1/Pictures/TX-1 NamePlate.JPG ./Service 1/Pictures/TX-1 NamePlate.JPG ./Service 1/Pictures/TX-1 NamePlate.JPG
| Sheets and Views |
| EE000 COVER SHEET |
| EE001 ABBREVIATIONS, G.P.N., LEGEND & SHEET INDEX |
| EP101 ELECTRICAL SITE PLAN |
| 0.1 - SITE |
| 0.1 - SITE ENLARGED |
| 0.1 - SITE DEMO |
| EP102 ELECTRICAL ONE-LINE DIAGRAM |
| 6 - ONE-LINE DIAGRAMS |