6-2-CR27001-27093730 Approved Plans.pdf
PDF 9 MB Posted
- Solicitation number
- CR27001
- Issued by
- Utah
About this file
This is a set of construction documents prepared by Spectrum Engineers for the Southern Utah University (SUU) Multi-Purpose Building Electrical Updates project in Cedar City, Utah, in coordination with the State of Utah Division of Facilities Construction and Management (DFCM). The project involves the replacement of select older electrical equipment serving the multipurpose building, including a medium voltage transformer rated at 300 kVA (12,470V delta to 208/120V wye), distribution boards, and multiple panelboards designated A through M. The construction documents include electrical site plans, demolition and power plans for basement, level 1, and level 2, one-line diagrams, panel schedules, conduit routing details, grounding diagrams, and typical installation details. The project requires coordination with DFCM for all inspections, and a code inspection report recommending certificate of occupancy issuance is mandatory before the building can be occupied. All power outages must be coordinated with SUU and documented in writing at least two weeks prior to occurrence, with the contractor required to submit a signed outage plan and method of procedure identifying risks and mitigation strategies. The transformer lead time shall not exceed four months from order placement.
The construction documents establish that all work must comply with current National Electrical Code (NEC), International Building Code (IBC), National Fire Protection Association (NFPA), and International Fire Code (IFC) standards, with final compliance and approval subject to on-site field inspection by the Authority Having Jurisdiction. The project involves extensive underground raceway and cable work, with the electrical contractor responsible for all trenching, backfill, compaction, and concrete or asphalt cutting and replacement associated with underground installations. Equipment specifications include NEMA 3R enclosures for outdoor equipment, seismic restraint compliance per ASCE 7-05, and arc flash and coordination studies from the medium voltage transformer to all branch panelboards. The contractor must provide detailed submittals in PDF format with bookmarks and highlighting, and deferred submittals for seismic restraint of nonstructural components must be submitted to DFCM a minimum of two weeks prior to planned installation. The construction cost estimate for the project is $413,678.00.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
324 S. State St., Suite 400 Salt Lake City, UT 84111
801-328-5151 www.spectrum-engineers.com
C
A
B
2 3
D
E
1 2 3
C
4 5
2026 Spectrum Engineers, Inc.
SHEET TITLE
SUU PROJECT NO:
DRAWN BY:
CHECKED BY:
SIGNATURE:
RECORD DRAWING DATE:
DESIGNED BY:
A
ISSUE:
DATE:
B
4 5
D
E
SPECTRUM PROJECT NO:
SE PROJECT #: SE PROJECT #:
P2502349
Au to de sk
D oc s:
//2
- S
U U
M ul ti- Pu rp os e Bu ild in g El ec tri ca l U pd at es /2
- S
U U
M ul ti- Pu rp os e Bu ild in g El ec tri ca l U pd at es
El ec
.rv t
7/ 1/
1:
:2
AM
MSM
LSK
JKC
240787 05/29/2026
CONSTRUCTION
DOCUMENTS
COVER SHEET
E1
SOUTHERN
UTAH
UNIVERSITY
MULTI-PURPOSE
BUILDING
ELECTRICAL
UPDATES
654 W 200 S
MULTIPURPOSE
CENTER #212F,
CEDAR CITY, UT
84720
MULTI-PURPOSE BUILDING
ELECTRICAL UPDATES
240787
654 W 200 S MULTIPURPOSE CENTER #212F,
CEDAR CITY, UT 84720
CONSTRUCTION DOCUMENTS - 05/29/2026
Mark: Date: Description
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
07/01/2026
REVIEWED FOR CODE
COMPLIANCE
North: ______ South: ______ East: ______ West: ______
Special Use and Occupancy (e.g. High Rise, Covered Mall): __________________
d) Unlimited Area Building: Yes ______ No ______ Code Section: ______ a a
3) Three Story: A (3)______
2) Two Story: A (2)______
1) One Story: ______
c) Total Allowable Area for:
1_< Allowable Area Actual Area
b) Sum of the Ratio Calculations for Mixed Occupancies:
a) 0.25I = 100f F P 30
WstA I 100100 fIAt taA = A + +
Official for Complex Buildings. Including, but not limited to:
g) Fire Stopping, Including Tested Design Number.
f) Exterior and Interior Accessibility Route.
e) Fire Assembly Locator Sheet.
a) High Rise Requirements.
b) Atriums.
c) Performance Based Criteria.
d) Means or Egress Analysis.
2) Additional Code Information shall be provided at the discretion of the Building
Code Accessibility Chapters, the more restrictive requirement shall govern.
through - ADA Guidelines and specific reference to the International Building
1) In case of conflict with the U.S. Department of Justice Federal Registers Parts
FOOTNOTES:
d) Drinking Fountains: ______ Service Sinks: ______
c) Bath Tubs or Showers: ______
b) Lavatories - Required (m) ______ (f) ______ Provided (m) ______ (f) _____
a) Water Closets - Required (m) ______ (f) ______ Provided (m) ______ (f) ____
M. Minimum Number of Required Plumbing Facilities:
Exit Width Required: ______ Exit Width Provided: ______
Element Hours Assembly ListingListing
Element AssemblyHours
Smoke Partitions Fire Partitions
Exterior Bearing Walls Interior Bearing Walls Exterior Non-Bearing Walls Structural Frame Partitions - Permanent Fire Barriers
Floors - Ceiling Floors Roofs - Ceiling Roofs Exterior Doors and Windows Shaft Enclosures Fire Walls
BAHTBABABA
Design Wind Speed: ______ mphB. Seismic Design Category: ______
L. Design Occupant Load: ______
K. Fire Resistance Rating Requirements for Building Elements (hours).
Area Modifications:J:
____________________________________________Tabular Area:I:
per Floor (square feet): __________________________Actual AreaH:
Number of Stories: ______ Building Height: ______G:
Required: ______ Provided: ______ Type of Sprinkler System: ____________
Sprinklers:F:
Mixed Occupancies: ______ Nonseparated Uses: ______E.
separation distance (in hours):
Requirements for the Exterior Walls based on the fireFire Resistance RatingD.
C. Type of Construction (circle one):
Change in Use: Yes ______ No ______ Mixed Occupancy: Yes ______ No _____
Guidelines ADA Accessibility Building Conservation Uniform Code for National Electrical Code
Conservation Code International Energy International Fire Code International Plumbing Code International Mechanical Code International Building Code
YearYear
APPLICABLE CODES
A. Occupancy and Group: ________ ________ ________ ________ ______
CODE ANALYSIS
SPECIAL NOTE:
THIS PROJECT IS TO BE INSPECTED BY DFCM. THE ELECTRICAL CONTRACTOR
IS TO COORDINATE WITH DFCM FOR INSPECTIONS. A CODE INSPECTION
REPORT IS REQUIRED. MORE THAN SP INSPECTION MAY BE REQUIRED.
N/A N/A N/A
N/A
N/A
BII
N/A N/A N/A N/A
N/A
N/A N/A
N/A N/A N/A N/A
N/A N/A
N/A N/A N/A
1 20
21,250
N/A
N/A N/A
N/A
N/A N/A N/A
N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A N/A N/A
N/A N/A N/A N/A
N/A
N/A N/A
N/A N/A N/A N/A
N/AN/AN/AN/A
N/A N/A N/A
No. 12735266 Mario S.
Martinez
E
ED
P ROF E S S
ENG
I ONA L
IN
E
E R
S N
CI
L
S T A T E O F T A H U
324 S. State St., Suite 400 Salt Lake City, UT 84111
801-328-5151 www.spectrum-engineers.com
C
A
B
2 3
D
E
1 2 3
C
4 5
2026 Spectrum Engineers, Inc.
SHEET TITLE
SUU PROJECT NO:
DRAWN BY:
CHECKED BY:
SIGNATURE:
RECORD DRAWING DATE:
DESIGNED BY:
A
ISSUE:
DATE:
B
4 5
D
E
SPECTRUM PROJECT NO:
P2502349
05/29/2026
Au to de sk
D oc s:
//2
- S
U U
M ul ti- Pu rp os e Bu ild in g El ec tri ca l U pd at es /2
- S
U U
M ul ti- Pu rp os e Bu ild in g El ec tri ca l U pd at es
El ec
.rv t
7/ 1/
1:
:2
AM
MSM
LSK
JKC
240787 05/29/2026
CONSTRUCTION
DOCUMENTS
ELECTRICAL COVER
SHEET
E2
SOUTHERN
UTAH
UNIVERSITY
MULTI-PURPOSE
BUILDING
ELECTRICAL
UPDATES
654 W 200 S
MULTIPURPOSE
CENTER #212F,
CEDAR CITY, UT
84720
ELECTRICAL SHEET INDEX
E1 COVER SHEET
E2 ELECTRICAL COVER SHEET
E3 ELECTRICAL SITE PLAN
E4 ENLARGED ELECTRICAL SITE PLANS
E5 CONDUIT ROUTING DETAILS
E6 BASEMENT OVERALL ELECTRICAL DEMOLITION PLAN
E7 LEVEL 1 OVERALL ELECTRICAL DEMOLITION PLAN
E8 LEVEL 2 OVERALL ELECTRICAL DEMOLITION PLAN
E9 BASEMENT OVERALL POWER PLAN
E10 LEVEL 1 OVERALL POWER PLAN
E11 LEVEL 2 OVERALL POWER PLAN
E12 ONE-LINE DIAGRAMS
E13 PANEL SCHEDULES
E14 PANEL SCHEDULES
E15 TYPICAL DETAILS
E16 LABELING DETAILS
E17 GROUNDING DIAGRAMS AND DETAILS
GENERAL ELECTRICAL NOTES
1. CLARIFICATION METHODS: AT THE TIME OF BIDDING, BIDDERS SHALL FAMILIARIZE
THEMSELVES WITH THE DRAWINGS AND SPECIFICATIONS. ANY QUESTIONS,
MISUNDERSTANDINGS, CONFLICTS, DELETIONS, DISCONTINUED PRODUCTS,
CATALOG NUMBER DISCREPANCIES, DISCREPANCIES BETWEEN THE EQUIPMENT
SUPPLIED AND THE INTENT OR FUNCTION OF THE EQUIPMENT, ETC, SHALL BE
SUBMITTED TO THE ARCHITECT/ENGINEER IN WRITING FOR CLARIFICATION PRIOR
TO ISSUANCE OF THE FINAL ADDENDUM AND BIDDING OF THE PROJECT. WHERE
DISCREPANCIES OR MULTIPLE INTERPRETATIONS OCCUR, THE MOST STRINGENT
(WHICH IS GENERALLY RECOGNIZED AS THE MOST COSTLY) THAT MEETS THE
INTENT OF THE DOCUMENTS SHALL BE ENFORCED.
2. OWNER FURNISHED ITEMS: THE OWNER WILL FURNISH MATERIAL AND
EQUIPMENT AS INDICATED IN THE CONTRACT DOCUMENTS TO BE INCORPORATED
INTO THE WORK. THESE ITEMS ARE ASSIGNED TO THE INSTALLER AND COSTS
FOR RECEIVING, HANDLING, STORAGE, IF REQUIRED, AND INSTALLATION ARE
INCLUDED IN THE CONTRACT SUM.
A. THE INSTALLER'S RESPONSIBILITIES ARE THE SAME AS IF THE INSTALLER
FURNISHED THE MATERIALS OR EQUIPMENT.
B. THE OWNER WILL ARRANGE AND PAY FOR DELIVERY OF OWNER
FURNISHED ITEMS FREIGHT ON BOARD JOB SITE AND THE INSTALLER WILL
INSPECT DELIVERIES FOR DAMAGE. IF OWNER FURNISHED ITEMS ARE
DAMAGED, DEFECTIVE OR MISSING, DOCUMENT DAMAGED ITEMS WITH
THE TRANSPORT COMPANY AND THE OWNER WILL ARRANGE
FOR REPLACEMENT. THE OWNER WILL ALSO ARRANGE FOR
MANUFACTURER'S FIELD SERVICES, AND THE DELIVERY OF
MANUFACTURER'S WARRANTIES AND BONDS TO THE INSTALLER.
C. THE INSTALLER IS RESPONSIBLE FOR DESIGNATING THE DELIVERY DATES
OF OWNER FURNISHED ITEMS AND FOR RECEIVING, UNLOADING AND
HANDLING OWNER FURNISHED ITEMS AT THE SITE.THE INSTALLER IS
RESPONSIBLE FOR PROTECTING OWNER FURNISHED ITEMS FROM
DAMAGE, INCLUDING DAMAGE FROM EXPOSURE TO THE ELEMENTS, AND
TO REPAIR OR REPLACE ITEMS DAMAGED AS A RESULT OF HIS
OPERATIONS.
SITE COORDINATION
THE LOCATION, CAPACITY, AND VOLTAGE OF THE LINES ARE ALL IN ACCORDANCE
WITH DATA GIVEN THIS OFFICE BY THE UTILITY COMPANY. COORDINATE WITH
THE LOCAL UTILITY COMPANY FOR THE INSTALLATION OF THE ELECTRICAL
SERVICE. COMPLY WITH UTILITY REGULATIONS. REPORT DISCREPANCIES TO
THE ENGINEER.
SUU
PERSON CONTACTED: MATT VANDENBERG
PHONE NUMBER: (435) 559-1859
EMAIL: VANDENBERGHE@SUU.EDU
ELECTRIC UTILITY
DEFINITIONS
NOTE: ALL DEFINITIONS MAY NOT BE USED.
INDICATED: THE TERM "INDICATED" REFERS TO GRAPHIC REPRESENTATIONS,
NOTES, OR SCHEDULES ON THE DRAWINGS, OTHER PARAGRAPHS OR
SCHEDULES IN THE SPECIFICATIONS, AND SIMILAR REQUIREMENTS IN THE
CONTRACT DOCUMENTS. WHERE TERMS SUCH AS "SHOWN", "NOTED",
"SCHEDULED", AND "SPECIFIED" ARE USED, IT IS TO HELP THE READER LOCATE
THE REFERENCE, NO LIMITATION ON LOCATION IS INTENDED.
DIRECTED: TERMS SUCH AS "DIRECTED", "REQUESTED", AUTHORIZED",
"SELECTED", "APPROVED", "REQUIRED", AND "PERMITTED" MEAN "DIRECTED BY
THE ENGINEER", "REQUESTED BY THE ENGINEER", AND SIMILAR PHRASES.
APPROVED: THE TERM "APPROVED", WHERE USED IN CONJUNCTION WITH THE
ENGINEER'S ACTION ON THE CONTRACTOR'S SUBMITTALS, APPLICATIONS, AND
REQUESTS, IS LIMITED TO THE ENGINEER'S DUTIES AND RESPONSIBILITIES AS
STATED IN GENERAL AND SUPPLEMENTARY CONDITIONS.
FURNISH: THE TERM "FURNISH" IS USED TO MEAN "SUPPLY AND DELIVER TO
THE PROJECT SITE, READY FOR UNLOADING, UNPACKING, ASSEMBLY,
INSTALLATION, AND SIMILAR OPERATIONS."
INSTALL: THE TERM "INSTALL" IS USED TO DESCRIBE OPERATIONS AT PROJECT
SITE INCLUDING THE ACTUAL "UNLOADING, UNPACKING, ASSEMBLY, ERECTION,
PLACING, ANCHORING, APPLYING, WORKING TO DIMENSION, FINISHING,
CURING, PROTECTING, CLEANING, AND SIMILAR OPERATIONS."
PROVIDE: THE TERM "PROVIDE" MEANS "TO FURNISH AND INSTALL, COMPLETE
AND READY FOR THE INTENDED USE."
INSTALLER: AN "INSTALLER" IS THE CONTRACTOR OR AN ENTITY ENGAGED BY
THE CONTRACTOR, EITHER AS AN EMPLOYEE, SUBCONTRACTOR, OR SUB-
SUBCONTRACTOR, FOR PERFORMANCE OF A PARTICULAR CONSTRUCTION
ACTIVITY, INCLUDING INSTALLATION, ERECTION, APPLICATION, AND SIMILAR
OPERATIONS. INSTALLERS ARE REQUIRED TO BE EXPERIENCED IN THE
OPERATIONS THEY ARE ENGAGED TO PERFORM.
TECHNOLOGY SYSTEMS: THE TERM "TECHNOLOGY SYSTEMS" IS USED TO
DESCRIBE ALL LOW VOLTAGE SYSTEMS GENERALLY REFERRED TO AS
"SPECIAL SYSTEMS". THESE SYSTEMS INCLUDE BUT ARE NOT NECESSARILY
LIMITED TO ALL SYSTEMS WHICH UTILIZE VOLTAGES OF LESS THAN 71 VOLTS
SUCH AS SOUND SYSTEMS, VIDEO SYSTEMS, TV SYSTEMS, SECURITY
SYSTEMS, VOICE AND DATA CABLING SYSTEMS, ETC...
ABBREVIATIONS
NOTE: ALL ABBREVIATIONS MAY NOT BE USED.
1P SINGLE POLE
1PH SINGLE-PHASE
1WAY ONE-WAY
2/C TWO-CONDUCTOR
2WAY TWO-WAY
3/C THREE-CONDUCTOR
3WAY THREE-WAY
4OUT QUADRUPLE RECEPTACLE
OUTLET
4PDT FOUR-POLE DOUBLE THROW
4PST FOUR-POLE SINGLE THROW
4W FOUR-WIRE
4WAY FOUR-WAY
A ABOVE COUNTER
AC ARMORED CABLE
ACS ACCESS CONTROL SYSTEM
ADA AMERICANS WITH DISABILITIES
ACT
ADJ ADJACENT
AFF ABOVE FINISHED FLOOR
AFG ABOVE FINISHED GRADE
AIC AMPERE INTERRUPTING
CAPACITY
ALUM ALUMINUM
AMP AMPERE
ANN ANNUNCIATOR
AP ACCESS POINT (WIRELESS
DATA)
AR AS REQUIRED
ASC AMPS SHORT CIRCUIT
ATS AUTOMATIC TRANSFER
SWITCH
AV AUDIO VISUAL
AWG AMERICAN WIRE GAGE
BB
XFMR
BUCK-BOOST TRANSFORMER
BFF BELOW FINISHED FLOOR
BFG BELOW FINISHED GRADE
C CEILING MOUNTED
CAT CATEGORY
CATV COMMUNITY ANTENNA
TELEVISION
CB CIRCUIT BREAKER
CCBA CUSTOM COLOR AS SELECTED
BY ARCHITECT
CCTV CLOSED CIRCUIT TELEVISION
CF/CI CONTRACTOR FURNISHED/
CONTRACTOR INSTALLED
CF/OI CONTRACTOR FURNISHED/
OWNER INSTALLED
CFBA CUSTOM FINISH AS SELECTED
BY ARCHITECT
CI CONTACT INDICATOR
CKT CIRCUIT
CM CONSTRUCTION MANAGER
CND CONDUIT
CO CONVENIENCE OUTLET
COR CONTRACTING OFFICER'S
REPRESENTATIVE
CP CONTROL PANEL
CR CARD READER
CT CURRENT TRANSFORMER
CTV CABLE TELEVISION
CU COPPER
dBA UNIT OF SOUND LEVEL
DPDT DOUBLE POLE, DOUBLE
THROW
DS DISCONNECT SWITCH
E ENHANCED
EA EACH
EM EMERGENCY
EMT ELECTRICAL METALLIC TUBING
ENT ELECTRIC NONMETALLIC
TUBING
EPO EMERGENCY POWER OFF
EQUIP EQUIPMENT
ER EQUIPMENT ROOM
EX EXISTING
F FURNITURE MOUNTED
FA FIRE ALARM
FCP FIRE ALARM CONTROL PANEL
FLA FULL LOAD AMPS
FMC FLEXIBLE METAL CONDUIT
FOB FREIGHT ON BOARD
FPP FIBER PATCH PANEL
FVNR FULL VOLTAGE
NON-REVERSING
FVR FULL VOLTAGE REVERSING
GEN GENERATOR
GFCI GROUND FAULT INTERRUPTER
GFP GROUND FAULT PROTECTION
GIG GIGA HERTZ
GND GROUND
HD HEAVY DUTY
HID HIGH INTENSITY DISCHARGE
HOA HAND-OFF-AUTOMATIC
HP HORSE POWER
HPF HIGH POWER FACTOR
HPS HIGH PRESSURE SODIUM
HV HIGH VOLTAGE
HWM HORIZONTAL WIRE
MANAGEMENT
HZ HERTZ
I/O INPUT/ OUTPUT
IG ISOLATED GROUND
IMC INTERMEDIATE METAL
CONDUIT
IN/IS INSULATED/ ISOLATED
IR INFRARED
J-BOX JUNCTION BOX
kV KILOVOLT kVA KILOVOLT AMPERE kVAR KILOVOLT AMPERE REACTIVE kW KILOWATT kWh KILOWATT HOUR
LED LIGHT EMITTING DIODE
LFMC LIQUID TIGHT FLEXIBLE METAL
CONDUIT
LFNC LIQUID TIGHT FLEXIBLE
NONMETALLIC CONDUIT
LPS LOW PRESSURE SODIUM
LRA LOCKED ROTOR AMPS
LTG LIGHTING
LV LOW VOLTAGE
MATV MASTER ANTENNA TELEVISION
SYSTEM
MAX MAXIMUM
MC METAL CLAD
MCA MINIMUM CIRCUIT AMPS
MCB MAIN CIRCUIT BREAKER
MCC MOTOR CONTROL CENTER
MCP MOTOR CIRCUIT PROTECTION
MDP MAIN DISTRIBUTION PANEL
MG MOTOR GENERATOR
MH MANHOLE
MIN MINIMUM
MLO MAIN LUGS ONLY
MOCP MAXIMUM OVERCURRENT
PROTECTION
MTS MANUAL TRANSFER SWITCH
NA NOT APPLICABLE
NC NORMALLY CLOSED
NEC NATIONAL ELECTRICAL CODE
NEMA NATIONAL ELECTRICAL
MANUFACTURERS
ASSOCIATION
NFC NATIONAL FIRE CODE
NFPA NATIONAL FIRE PROTECTION
ASSOCIATION
NIC NOT IN CONTRACT
NL NIGHT LIGHT
NO NORMALLY OPEN
NTS NOT TO SCALE
OC ON CENTER
OCP OVER CURRENT PROTECTION
OE OWNER ELECTRONICS
OF/CI OWNER FURNISHED/
CONTRACTOR INSTALLED
OF/OI OWNER FURNISHED/ OWNER
INSTALLED
OFP OBTAIN FROM PLANS
OH DR OVERHEAD (COILING) DOOR
OL OVERLOAD
PB PUSHBUTTON
PF POWER FACTOR
PH PHASE
PNL PANEL
PNM PLENUM
PR PAIR
PS POWER SUPPLY
PT POTENTIAL TRANSFORMER
PTZ PAN/TILT/ZOOM
PV PHOTO VOLTAIC
QTY QUANTITY
R REMOVE
RCP REFLECTED CEILING PLAN
RMC RIGID METAL CONDUIT
RNC RIGID NONMETAL CONDUIT
RO REMOTE DOOR OPEN
RPM REVOLUTIONS PER MINUTE
RPP RISER PATCH PANEL
RR REMOVE AND RELOCATE
S/S START/STOP
SCA SHORT CIRCUIT AMPS
SCBA STANDARD COLOR AS
SELECTED BY ARCHITECT
SEC SECURITY
SF SQUARE FOOT (FEET)
SFBA STANDARD FINISH AS
SELECTED BY ARCHITECT
SPD SURGE PROTECTIVE DEVICE
SPDT SINGLE POLE, DOUBLE THROW
SPEC SPECIFICATION
SPP STATION PATCH PANEL
SPST SINGLE POLE, SINGLE THROW
ST SINGLE THROW
SWBD SWITCHBOARD
SWGR SWITCHGEAR
TL TWIST LOCK
TP TELEPHONE POLE
TP TWISTED PAIR
TR TELECOMMMUNICATIONS
ROOM
TTB TELEPHONE TERMINAL BOARD
TV TELEVISION
TVSS TRANSIENT VOLTAGE SURGE
SUPPRESSER
TYP TYPICAL
UF UNDERFLOOR
UGND UNDERGROUND
UPS UNINTERRUPTIBLE POWER
SUPPLY
V VOLTS
VA VOLT AMPERE
VFC/VF
D
VARIABLE FREQUENCY MOTOR
CONTROLLER
VIC VIDEO INTERCOM SYSTEM
VSS VIDEO SURVEILLANCE SYSTEM
VWM VERTICAL WIRE MANAGEMENT
W/ WITH
W/O WITHOUT
WP WEATHERPROOF
WPP WIRELESS PATCH PANEL
XFMR TRANSFORMER
WIRING METHODS
SYMBOL DESCRIPTION
SYMBOLS LEGEND
WIRING.
CONDUIT STUB. DIMENSION RECORD DRAWINGS AND MARK.
CONDUCTOR & CONDUIT ("CC") SCHEDULE INDICATOR. REFER
TO ONE-LINE DIAGRAM.1
JUNCTION BOX.J
JUNCTION BOX, SYSTEMS FURNITURE COMMUNICATION
CONNECTION.SCJ
JUNCTION BOX, SYSTEMS FURNITURE POWER CONNECTION.SPJ
PULL BOX.PB
JUNCTION BOX, CEILING.CJ
WIRING DEVICES
RECEPTACLE, DUPLEX: NEMA 5-20R.
RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUIT
INTERRUPTER, WET LABEL, "WEATHERPROOF IN USE":
NEMA 5-20R.W
RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUIT
INTERRUPTER, WEATHERPROOF: NEMA 5-20R.WP
RECEPTACLE, QUADRAPLEX: NEMA 5-20R.
SYMBOL DESCRIPTION
SYMBOLS LEGEND
SYMBOL DESCRIPTION
SYMBOLS LEGEND
GROUND BUSBAR. REFER TO GROUNDING RISER DIAGRAM FOR
ADDITIONAL INFORMATION.
SINGLE BRANCH CIRCUIT HOME RUN TO PANELBOARD WITH
DEDICATED NEUTRAL CONDUCTOR. LETTER AND NUMBER
NOTATION IDENTIFY PANEL AND CIRCUIT NUMBER.A-1
3. EXPOSED STRUCTURE AREAS: INSTALL RACEWAYS BETWEEN DECK AND
STRUCTURE WHEREVER POSSIBLE IN EXPOSED STRUCTURE CEILING AREAS.
ROUTE RACEWAYS IN CONCEALED AREAS WHEREVER POSSIBLE. REFER ALL
CONDITIONS WHERE RACEWAYS MUST BE INSTALLED WHICH CANNOT COMPLY
WITH THESE REQUIREMENTS TO THE ARCHITECT.
4. SUBMITTALS: PROVIDE ORIGINAL ELECTRONIC PDF FORMAT, BOUND,
BOOKMARKED (EACH SECTION AND PRODUCT), AND HIGHLIGHTED. JOB NAME
AND SUBCONTRACTOR SHALL BE ON THE FRONT COVER. PREPARE INDEX OF
EQUIPMENT SUBMITTED IN EACH TAB.
5. ALL WORK SHALL BE DONE ACCORDING TO THE CURRENT NATIONAL ELECTRIC
CODE (NEC), IBC, NFPA, AND IFC. COMPLIANCE AND FINAL APPROVAL IS SUBJECT
TO THE ON SITE FIELD INSPECTION OF THE AHJ.
6. PROJECT DRAWINGS MEET DFCM STANDARDS.
7 THE FOLLOWING DOCUMENTS ARE REQUIRED BEFORE A CERTIFICATE OF
OCCUPANCY IS ISSUED:
• A CODE INSPECTION REPORT RECOMMENDING THAT A CERTIFICATE OF
OCCUPANCY BE ISSUED.
• CERTIFICATE OF FIRE CLEARANCE FROM THE STATE FIRE MARSHALL.
REFERENCE AND LINE SYMBOLS
DETAIL INDICATOR: A5 INDICATES DETAIL NUMBER, E-501
INDICATES DRAWING SHEET WHERE DETAIL IS SHOWN.
A5 E-501
ELEVATION OR SECTION INDICATOR, EXTERIOR: A5 INDICATES
ELEVATION OR SECTION NUMBER, E-201 INDICATES DRAWING
SHEET WHERE ELEVATION OR SECTION IS SHOWN.
A5 E-201
ELEVATION OR SECTION INDICATOR, INTERIOR: A5 INDICATES
ELEVATION OR SECTION NUMBER, E-201 INDICATES DRAWING
SHEET WHERE ELEVATION OR SECTION IS SHOWN.
A5 E-201
ROOM IDENTIFIER WITH ROOM NAME AND NUMBER.
ROOM NAME
KEYNOTE INDICATOR.1
REVISION INDICATOR.1
CU-1 EQUIPMENT INDICATOR.
BREAK, STRAIGHT: TO BREAK PARTS OF DRAWING
BREAK, ROUND
MATCH LINE INDICATOR: CENTER, EXTRA WIDE LINE.MATCH LINE
SEE XX/X-XXX
NEW LINE: MEDIUM LINE.
HIDDEN FEATURES LINE: HIDDEN, THIN LINE
EXISTING TO REMAIN LINE: THIN LINE.
DEMOLITION LINE: DASHED, MEDIUM LINE
PROPERTY LINE: DASHED, WIDE LINE.
CONTRACT LIMIT LINE: DASHDOT, WIDE LINE.
ELECTRICAL EQUIPMENT INDICATOR. "XXX" INDICATES TYPE OF
EQUIPMENT OR EQUIPMENT ID. "EF-X" IDENTIFIES MECHANICAL
EQUIPMENT BEING SERVED. REFER TO EQUIPMENT SCHEDULE
FOR ADDITIONAL INFORMATION.
EF-X
XXX
EQUIPMENT INDICATOR. "X-X" INDICATES EQUIPMENT MARK
SHOWN ON EQUIPMENT SCHEDULE. "1LA-3" IDENTIFIES PANEL
EQUIPMENT IS CIRCUITED TO. REFER TO EQUIPMENT SCHEDULE
FOR ADDITIONAL INFORMATION.
1LA-3
X-X
MECHANICAL EQUIPMENT INDICATOR. "X-X" INDICATES
EQUIPMENT MARK SHOWN ON EQUIPMENT SCHEDULE. "XMDP"
IDENTIFIES PANEL EQUIPMENT IS CIRCUITED TO. REFER TO
EQUIPMENT SCHEDULE FOR ADDITIONAL INFORMATION.
XMDP
X-X
IN-GRADE PULLBOX INDICATOR. "XXXET" INDICATES LABEL
SHOWN ON SCHEDULE. "#" IDENTIFIES SEQUENCE NUMBER
SHOWN ON SITE AND RISER DIAGRAM. REFER TO PLANS AND
EXTERIOR PULLBOX SCHEDULE FOR ADDITIONAL INFORMATION.
XXXET
SITE ELECTRICAL AND COMMUNICATIONS UTILITIES
IN-GRADE PULLBOX, HAND HOLE. OPTIONS WITH SQUARE OR
ROUND CORNERS. REFER TO PLANS AND EXTERIOR PULLBOX
SCHEDULE FOR ADDITIONAL INFORMATION. . .
ELECTRICAL POWER AND DISTRIBUTION
FUSE WITH RATING (ONE-LINE DIAGRAM).
DISCONNECT, FUSED (ONE-LINE DIAGRAM).
DISCONNECT, NONFUSED (ONE-LINE DIAGRAM).
CIRCUIT BREAKER (ONE-LINE DIAGRAM).
CIRCUIT BREAKER WITH SHUNT TRIP (ONE-LINE DIAGRAM).
S.T.
CIRCUIT BREAKER, MOTOR CIRCUIT PROTECTION
(ONE-LINE DIAGRAM).
MCP
MOTOR.
TRANSFORMER (ONE-LINE DIAGRAM).
DELTA CONNECTION (ONE-LINE DIAGRAM).
WYE CONNECTION (ONE-LINE DIAGRAM).
PANELBOARD (ONE-LINE DIAGRAM)."1H"
PANELBOARD WITH MAIN LUGS ONLY. BUS SIZE AND PHASE AS
SHOWN (ONE-LINE DIAGRAM).
225/3
"1H"
PANELBOARD WITH MAIN CIRCUIT BREAKER. SIZE AND PHASE AS
SHOWN (ONE-LINE DIAGRAM).
225/3
"1H"
PANELBOARD WITH MAIN AND SUB FEED CIRCUIT BREAKER
(ONE-LINE DIAGRAM).
60/3
225/3
"1H"
ELECTRICAL POWER AND DISTRIBUTION
PANELBOARD WITH SUB FEED LUGS (ONE-LINE DIAGRAM).
225/3 225/3 "1H" "1H"
PANELBOARD WITH CIRCUIT BREAKER AND SUB FEED LUGS
(ONE-LINE DIAGRAM).
225/3 "1H" "1H"
CT CABINET PER UTILITY'S REQUIREMENTS (ONE-LINE DIAGRAM).
CT CABINET PER UTILITY'S REQUIREMENTS (ONE-LINE DIAGRAM).
TRANSFER SWITCH (ONE-LINE DIAGRAM).
DIGITAL MULTIMETER (ONE-LINE DIAGRAM).DMM
SERVICE ENTRANCE SURGE PROTECTION (ONE-LINE DIAGRAM).
GENERATOR, ANNUNCIATOR (ONE-LINE DIAGRAM).ANN
GENERATOR, POWER (ONE-LINE DIAGRAM).G
METER.M
EARTH GROUND (ONE-LINE DIAGRAM).
PUSH BUTTON, REMOTE EMERGENCY STOP.EPO
KIRK-KEY MECHANICAL INTERLOCK (ONE-LINE DIAGRAM)K
DISTRIBUTION PANELBOARD, MOTOR CONTROL CENTER,
PLUG-IN BUSWAY, MEDIUM VOLTAGE SWITCHBOARD
(ONE-LINE DIAGRAM).
"1DPHA"
CIRCUIT BREAKER, ADJUSTABLE TRIP. “#AF” REPRESENTS FRAME
RATING. “#AT” REPRESENTS TRIP UNIT. (ONE-LINE DIAGRAM).
#AF
#AT
PANELBOARD WITH MAIN LUGS ONLY AND SURGE PROTECTION
WITH CIRCUIT BREAKER (ONE-LINE DIAGRAM).
25/3
225/3
"1H"
CIRCUIT BREAKER, SOLID STATE WITH ARC ENERGY REDUCTION
SYSTEM INCLUDING ENERGY REDUCING MAINTENANCE
SWITCHING WITH LOCAL STATUS INDICATOR FULLY COMPLIANT
WITH NEC 240.87 (ONE-LINE DIAGRAM)
CIRCUIT BREAKER, ADJUSTABLE TRIP CURVE. L=LONG TIME
CURVE ADJUSTMENT, S=SHORT TIME CURVE ADJUSTMENT,
I=INSTANTANEOUS CURVE ADJUSTMENT, G=GROUND FAULT
ADJUSTMENT FULLY COMPLIANT WITH NEC 210.13, 215.10 AND
230.95. (ONE-LINE DIAGRAM).
LSIG
CURRENT TRANSFORMER (CT) (ONE-LINE DIAGRAM).
CONDUIT TYPES
CONDUIT, POWER 208V
(ONELINE) TRANSFORMER TERMINATION
PROJECT SCOPE
THIS PROJECT CONSISTS OF BUT NOT LIMITED TO THE REPLACEMENT OF
SELECT OLDER ELECTRICAL EQUIPMENT SERVING THE MULTIPURPOSE
BUILDING: INCLUDING THE MEDIUM VOLTAGE TRANSFORMER, DISTRIBUTION
BOARDS, AND PANELBOARDS.
PROJECT POWER OUTAGES
ALL POWER OUTAGES SHALL BE COORDINATED AND ADJUSTED TO OWNERS
SCHEDULE AND BE NOTIFIED IN WRITING 2 WEEKS PRIOR TO OUTAGE.
CONTRACTOR SHALL BE REQUIRED TO HAVE SIGNED AND REVIEWED OUTAGE
PLAN ALONG WITH METHOD OF PROCEDURE (MOP). CONTRACTOR SHALL
INDICATE ALL RISKS AND PROPOSE HOW TO MITIGATE THE RISKS. THE
FOLLOWING ARE SPECIFIC REQUIREMENTS PER LOCATION:
ALL PANELS REPLACEMENTS AND FEEDERS SHALL OCCUR AFTER HOURS OR AS
APPROVED BY SUU. REPLACEMENT OF TRANSFORMERS AND INSTALLATION OF
NEW SWITCHBOARD SHALL BE PHASED TO REDUCE OR ELIMINATE A BUILDING
OUTAGE. SUBJECT TO CONTRACTOR MEANS AND METHODS, DESIGN INTENT IS
AS FOLLOWS:
1. INSTALLATION OF TRANSFORMER PAD, TRANSFORMER, AND ASSOCIATED
CONDUITS.
2. PROVIDE TEMPORARY CABLING OF EXISTING MDP AND SECONDARY SERVICE
DISCONNECT SWITCH.
3. INSTALL NEW SWITCHBOARD, CONDUITS AND WIRING.
4. REMOVE TEMPORARY CABLING AND TERMINATE PERMANENT CABLING.
PANELBOARD CABINET, FLUSH MOUNTED.
PANELBOARD CABINET, SURFACE MOUNTED, 1 SECTION.
PANELBOARD CABINET, SURFACE MOUNTED, 2 SECTION.
DP#__
DISTRIBUTION PANEL OR SWITCHBOARD.
LP
LIGHTING RELAY, CONTACTOR PANEL, OR DIMMING ENCLOSURE.
SWITCH, TOGGLE MOTOR STARTER WITH OVERLOAD
PROTECTION.ST
TRANSFORMER (SEE ONE-LINE FOR SIZE)
1.
2.
3.
4.
Deferred submittals for seismic restraint of nonstructural components must be submitted to the DFCM Building Official a minimum of two weeks prior to the planned installation in order to allow for plan review and forwarding to inspectors. In the event that the submittal is deficient additional time may become necessary.
When seismic restraint of non-structural components is installed prior to receiving DFCM approval it shall not be covered or concealed until receiving both plan review and inspection approval. Further, installers are proceeding at their own risk until plan review and inspection approval occurs.
The requirements for seismic restraint of nonstructural components cannot be satisfied by a general reference to Design Manuals.
The design professional may utilize these manuals as a basis of their design, but must provide all supporting documentation to ensure that the design conforms to the requirements of ASCE 7-05, Chapter 13.
Submittals must include details of the proposed seismic restraint of nonstructural components. These details must show specific information relating to the materials, type, size, and locations of anchorages; materials used for bracing; attachment requirements of bracing to structure and component; and locations of transverse and longitudinal sway bracing and rod stiffeners. Submittals may also require structural calculations, engineering reports, test data, and/or specifications to ensure code compliance.
MEP Components:
Fire Sprinklers
Mechanical Equipment (i.e. HVAC, fans, air handlers, boilers, furnaces, tanks, chillers, water heaters, heat exchangers, evaporators, engines, turbines, pumps, compressors, MFR equipment, etc.)
Electrical Equipment (i.e. generators, batteries, inverters, transformers, MCC, panel boards, switch gear, cabinets, etc.)
Elevator & Escalator Components
Communication Equipment, Computers, Instrumentation, and Controls
Roof-mounted Chimneys, Stacks, Cooling & Electrical Towers
Lighting Fixtures
Vibration Isolated Components
Piping & Conduit Systems
Ductwork (including in-line components)
Conveyors
Cable Trays
Other:
NOT
REQUIRED
ON CONST.
DOCUMENTS
DEFERRED
SUBMITTAL COMMENTS
X
X
X
X
X
X
X
X
X
X
X
X
X
NONSTRUCTURAL COMPONENT CHECKLIST
Equipment Pads
Mark: Date: Description
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
07/01/2026
E4 A1
D1
E3
MULTIPURPOSE BUILDING
(EX)
"S10"
(EX)
"TX-MP"
E4 A3
E4 E3
E4 E1
EXISTING MV
TRANSFORMER
EXISTING LADDER
TO LOWER VAULT
No. 12735266 Mario S.
Martinez
E
ED
P ROF E S S
ENG
I ONA L
IN
E
E R
S N
CI
L
S T A T E O F T A H U
324 S. State St., Suite 400 Salt Lake City, UT 84111
801-328-5151 www.spectrum-engineers.com
C
A
B
2 3
D
E
1 2 3
C
4 5
2026 Spectrum Engineers, Inc.
SHEET TITLE
SUU PROJECT NO:
DRAWN BY:
CHECKED BY:
SIGNATURE:
RECORD DRAWING DATE:
DESIGNED BY:
A
ISSUE:
DATE:
B
4 5
D
E
SPECTRUM PROJECT NO:
P2502349
05/29/2026
Au to de sk
D oc s:
//2
- S
U U
M ul ti- Pu rp os e Bu ild in g El ec tri ca l U pd at es /2
- S
U U
M ul ti- Pu rp os e Bu ild in g El ec tri ca l U pd at es
El ec
.rv t
7/ 1/
1:
:3
AM
MSM
LSK
JKC
240787 05/29/2026
CONSTRUCTION
DOCUMENTS
ELECTRICAL SITE
PLAN
E3
SOUTHERN
UTAH
UNIVERSITY
MULTI-PURPOSE
BUILDING
ELECTRICAL
UPDATES
654 W 200 S
MULTIPURPOSE
CENTER #212F,
CEDAR CITY, UT
84720
1 CONTRACTOR IS RESPONSIBLE FOR ALL TRENCHING, BACKFILL, AND COMPACTION
ASSOCIATED TO ALL ELECTRICAL UNDERGROUND RACEWAYS AND CABLES. SEE
UNDERGROUND RACEWAY DETAILS FOR REQUIREMENTS FOR EACH TRENCH.
2 THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL CONCRETE/ASPHALT
CUTTING AND REPLACEMENT OF CONCRETE/ASPHALT TO MATCH EXISTING
ASSOCIATED WITH UNDERGROUND RACEWAYS PROVIDED AS PART OF THIS
PROJECT.
3 REFER TO PLANS FOR CONSTRAINTS ON PHYSICAL DIMENSIONS AND CLEARANCE
REQUIREMENTS OF EQUIPMENT. PROVIDE EQUIPMENT DIMENSIONS THAT FALL
WITHIN THE CONSTRAINTS OF EACH SPECIFIC LOCATION.
4 PROVIDE SERVICE RATED EQUIPMENT AT EACH SERVICE ENTRANCE.
5 SERVICE EQUIPMENT SHALL BE LEGIBLY MARKED IN THE FIELD WITH THE MAXIMUM
AVAILABLE FAULT CURRENT. VERIFY OR RE-CALCULATE THE AVAILABLE FAULT
CURRENT AT THE SERVICE WHERE MODIFICATIONS TO THE ELECTRICAL
INSTALLATION OCCUR. PLEASE INCLUDE NOTES IN THE ELECTRICAL DRAWINGS OR
SUPPLY CALCULATIONS WHERE APPLICABLE. SEE NEC 110.24. (B)
GENERAL SHEET NOTES
SCALE: 1/16" = 1'-0"A1 ELECTRICAL SITE PLAN - (FOR REFERENCE)
SCALE: NTSD1 SITE TRANSFORMER LOCATION (FOR REFERENCE)
NORTH
SHEET KEYNOTES
1 PROTECT AND MAINTAIN EXISTING SWITCH.
2 EXISTING COMMUNICATIONS CONDUIT.
3 EXISTING WATER LINE.
4 EXISTING IRRIGATION MAIN.
5 EXISTING WATER MANHOLE.
6 DEMOLISH EXISTING CABLING IN EXISTING RACEWAYS.
Mark: Date: Description
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
07/01/2026
(EX)
"TX-MP"
C1
E5
"TX-MP"
C1
E5
A3
E5
"MDP" 5
A1 E15
(EX)
"TX-MP"
(EX)
"TX-MP"
(EX)
"MDP"
C1
E5
UTILITY
103A
C1
E5
UTILITY
103A
No. 12735266 Mario S.
Martinez
E
ED
P ROF E S S
ENG
I ONA L
IN
E
E R
S N
CI
L
S T A T E O F T A H U
324 S. State St., Suite 400 Salt Lake City, UT 84111
801-328-5151 www.spectrum-engineers.com
C
A
B
2 3
D
E
1 2 3
C
4 5
2026 Spectrum Engineers, Inc.
SHEET TITLE
SUU PROJECT NO:
DRAWN BY:
CHECKED BY:
SIGNATURE:
RECORD DRAWING DATE:
DESIGNED BY:
A
ISSUE:
DATE:
B
4 5
D
E
SPECTRUM PROJECT NO:
P2502349
05/29/2026
Au to de sk
D oc s:
//2
- S
U U
M ul ti- Pu rp os e Bu ild in g El ec tri ca l U pd at es /2
- S
U U
M ul ti- Pu rp os e Bu ild in g El ec tri ca l U pd at es
El ec
.rv t
7/ 1/
1:
:5
AM
MSM
LSK
JKC
240787 05/29/2026
CONSTRUCTION
DOCUMENTS
ENLARGED
ELECTRICAL SITE
PLANS
E4
SOUTHERN
UTAH
UNIVERSITY
MULTI-PURPOSE
BUILDING
ELECTRICAL
UPDATES
654 W 200 S
MULTIPURPOSE
CENTER #212F,
CEDAR CITY, UT
84720
1 CONTRACTOR IS RESPONSIBLE FOR ALL TRENCHING, BACKFILL, AND COMPACTION
ASSOCIATED TO ALL ELECTRICAL UNDERGROUND RACEWAYS AND CABLES. SEE
UNDERGROUND RACEWAY DETAILS FOR REQUIREMENTS FOR EACH TRENCH.
2 THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL CONCRETE/ASPHALT
CUTTING AND REPLACEMENT OF CONCRETE/ASPHALT TO MATCH EXISTING
ASSOCIATED WITH UNDERGROUND RACEWAYS PROVIDED AS PART OF THIS
PROJECT.
3 REFER TO PLANS FOR CONSTRAINTS ON PHYSICAL DIMENSIONS AND CLEARANCE
REQUIREMENTS OF EQUIPMENT. PROVIDE EQUIPMENT DIMENSIONS THAT FALL
WITHIN THE CONSTRAINTS OF EACH SPECIFIC LOCATION.
4 PROVIDE SERVICE RATED EQUIPMENT AT EACH SERVICE ENTRANCE.
5 SERVICE EQUIPMENT SHALL BE LEGIBLY MARKED IN THE FIELD WITH THE MAXIMUM
AVAILABLE FAULT CURRENT. VERIFY OR RE-CALCULATE THE AVAILABLE FAULT
CURRENT AT THE SERVICE WHERE MODIFICATIONS TO THE ELECTRICAL
INSTALLATION OCCUR. PLEASE INCLUDE NOTES IN THE ELECTRICAL DRAWINGS OR
SUPPLY CALCULATIONS WHERE APPLICABLE. SEE NEC 110.24. (B)
GENERAL SHEET NOTES
SHEET KEYNOTES
1 PROTECT AND MAINTAIN EXISTING CONDUITS. DEMOLISH EXISTING CABLING.
2 DEMOLISH TREES AND SHRUBS.
3 PROVIDE NEW CABLING IN EXISTING RACEWAYS.
4 EXISTING LADDER ENTRY INTO AREA BELOW.
5 INTERCEPT EXISTING SPARE CONDUIT IN DUCTBANK AND EXTEND TO NEW
TRANSFORMER LOCATION. PROVIDE NEW WIRING AND TERMINATIONS FROM SWITCH
TO TRANSFORMER.
6 PROJECT SHALL BE PHASED SUCH THAT THE NEW TRANSFORMER IS INSTALLED
WITH WIRING AND TERMINATION AND NEW CONDUITS ARE INSTALLED FROM TO NEW
TRANSFORMER TO THE LOCATION OF THE NEW SWITCHBOARD, PRIOR TO THE
DEMOLITION OF THE EXISTING TRANSFORMER. TEMPORARY CABLES SHALL BE
PROVIDED FROM TRANSFORMER TO EXISTING MDP DURING THE INSTALLATION OF
THE NEW SWITCHBOARD.
7 DEMOLISH EXISTING CABLING IN EXISTING RACEWAYS.
8 EXISTING COMMUNICATIONS CONDUIT.
9 EXISTING WATER LINE.
10 EXISTING WATER MANHOLE.
11 EXISTING IRRIGATION MAIN.
12 DEMOLISH EXISTING TRANSFORMER. RETAIN CONDUITS AND PAD FOR REUSE.
13 PROVIDE (4) 3" CONDUIT STUBBED INTO BUILDING.
14 PROVIDE NEW GROUND ROD IN MDP.
15 EXTEND EXISTING TRANSFORMER PAD FOR NEW SWITCHBOARD.
16 VACUUM EXCAVATE AROUND EXISTING CONDUITS, MANHOLE, AND UTILITIES. UPON
FINDINGS, SUBMIT A LAYOUT PLAN SHOWING PROPOSED CONDUIT ROUTING IN
RELATION TO EXISTING SITE UTILITIES.
17 PROVIDE TEMPORARY FENCING DURING CONSTRUCTION OF THE SWITCHBOARD AND
TRANSFORMER. PROPOSED PLACEMENT SHOWN. FIRE DEPARTMENT CONNECTION
MUST MAINTAIN ACCESS.
18 PROVIDE NEW PULLBOX CONNECTING EXISTING CONDUITS AND EXTENDED
CONDUITS. PROVIDE SUPPORTS AS REQUIRED.
19 PROVIDE GROUND.
20 EXTEND EXISTING (4) 4" CONDUITS TO NEW PULLBOX.
21 PROVIDE GATE FOR FIRE DEPARTMENT ACCESS AT FIRE DEPARTMENT CONNECTION
(FDC). COORDINATE FINAL GATE LOCATION AND SITE ACCESS REQUIREMENTS WITH
SUU AND THE LOCAL FIRE MARSHAL FOR FINAL APPROVAL.
22 COORDINATE WITH THE SUU GROUNDS DEPARTMENT FOR WATER SHUTOFF UPON
TRENCHING.
23 PROVIDE (4) 2" CONDUIT STUBBED INTO BUILDING.
24 EXISTING FIRE DEPARTMENT CONNECTION. SHOWN FOR REFERENCE ONLY.
SCALE: 1/4" = 1'-0"A1 DEMOLITION ELECTRICAL SITE PLAN
SCALE: 1/4" = 1'-0"A3 NEW CONSTRUCTION ELECTRICAL SITE PLAN
SCALE:C1 DEMOLITION TRANSFORMER ISO VIEW
SCALE: NTSC3 NEW TRANSFORMER ISO VIEW
NORTH NORTH
SCALE: 1/4" = 1'-0"
UTILITY 103A ENLARGED
ELECTRICAL DEMOLITION PLANE1 SCALE: 1/4" = 1'-0"
NEW UTILITY 103A ENLARGED
ELECTRICAL PLANE3
NORTH NORTH
Mark: Date: Description
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
07/01/2026
LADDER FOR ENTRY
EXISTING CABLE TRAY FOR CABLING
EXISTING CONDUITS TO MDP
EXISTING CABLE TRAY FOR CABLING
EXISTING CONDUITS TO
EXISTING TRANSFORMER
No. 12735266 Mario S.
Martinez
E
ED
P ROF E S S
ENG
I ONA L
IN
E
E R
S N
CI
L
S T A T E O F T A H U
324 S. State St., Suite 400 Salt Lake City, UT 84111
801-328-5151 www.spectrum-engineers.com
C
A
B
2 3
D
E
1 2 3
C
4 5
2026 Spectrum Engineers, Inc.
SHEET TITLE
SUU PROJECT NO:
DRAWN BY:
CHECKED BY:
SIGNATURE:
RECORD DRAWING DATE:
DESIGNED BY:
A
ISSUE:
DATE:
B
4 5
D
E
SPECTRUM PROJECT NO:
P2502349
05/29/2026
Au to de sk
D oc s:
//2
- S
U U
M ul ti- Pu rp os e Bu ild in g El ec tri ca l U pd at es /2
- S
U U
M ul ti- Pu rp os e Bu ild in g El ec tri ca l U pd at es
El ec
.rv t
7/ 1/
1:
:5
AM
MSM
LSK
JKC
240787 05/29/2026
CONSTRUCTION
DOCUMENTS
CONDUIT ROUTING
DETAILS
E5
SOUTHERN
UTAH
UNIVERSITY
MULTI-PURPOSE
BUILDING
ELECTRICAL
UPDATES
654 W 200 S
MULTIPURPOSE
CENTER #212F,
CEDAR CITY, UT
84720
1 CONTRACTOR IS RESPONSIBLE FOR ALL TRENCHING, BACKFILL, AND COMPACTION
ASSOCIATED TO ALL ELECTRICAL UNDERGROUND RACEWAYS AND CABLES. SEE
UNDERGROUND RACEWAY DETAILS FOR REQUIREMENTS FOR EACH TRENCH.
2 THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR ALL CONCRETE/ASPHALT
CUTTING AND REPLACEMENT OF CONCRETE/ASPHALT TO MATCH EXISTING
ASSOCIATED WITH UNDERGROUND RACEWAYS PROVIDED AS PART OF THIS
PROJECT.
3 REFER TO PLANS FOR CONSTRAINTS ON PHYSICAL DIMENSIONS AND CLEARANCE
REQUIREMENTS OF EQUIPMENT. PROVIDE EQUIPMENT DIMENSIONS THAT FALL
WITHIN THE CONSTRAINTS OF EACH SPECIFIC LOCATION.
4 PROVIDE SERVICE RATED EQUIPMENT AT EACH SERVICE ENTRANCE.
5 SERVICE EQUIPMENT SHALL BE LEGIBLY MARKED IN THE FIELD WITH THE MAXIMUM
AVAILABLE FAULT CURRENT. VERIFY OR RE-CALCULATE THE AVAILABLE FAULT
CURRENT AT THE SERVICE WHERE MODIFICATIONS TO THE ELECTRICAL
INSTALLATION OCCUR. PLEASE INCLUDE NOTES IN THE ELECTRICAL DRAWINGS OR
SUPPLY CALCULATIONS WHERE APPLICABLE. SEE NEC 110.24. (B)
GENERAL SHEET NOTES
SHEET KEYNOTES
SCALE: NTSC1 CONDUIT ROUTING PHOTO (FOR REFERENCE)
SCALE: NTSA3 CONDUIT VAULT ROUTING PHOTO (FOR REFERENCE)
SCALE: NTSC3 CONDUIT ROUTING PHOTO (FOR REFERENCE)
Mark: Date: Description
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
07/01/2026
A
(EX)
"C"
No. 12735266 Mario S.
Martinez
E
ED
P ROF E S S
ENG
I ONA L
IN
E
E R
S N
CI
L
S T A T E O F T A H U
324 S. State St., Suite 400 Salt Lake City, UT 84111
801-328-5151 www.spectrum-engineers.com
C
A
B
2 3
D
E
1 2 3
C
4 5
2026 Spectrum Engineers, Inc.
SHEET TITLE
SUU PROJECT NO:
DRAWN BY:
CHECKED BY:
SIGNATURE:
RECORD DRAWING DATE:
DESIGNED BY:
A
ISSUE:
DATE:
B
4 5
D
E
SPECTRUM PROJECT NO:
P2502349
05/29/2026
Au to de sk
D oc s:
//2
- S
U U
M ul ti- Pu rp os e Bu ild in g El ec tri ca l U pd at es /2
- S
U U
M ul ti- Pu rp os e Bu ild in g El ec tri ca l U pd at es
El ec
.rv t
7/ 1/
1:
:5
AM
MSM
LSK
JKC
240787 05/29/2026
CONSTRUCTION
DOCUMENTS
BASEMENT OVERALL
ELECTRICAL
DEMOLITION PLAN
E6
SOUTHERN
UTAH
UNIVERSITY
MULTI-PURPOSE
BUILDING
ELECTRICAL
UPDATES
654 W 200 S
MULTIPURPOSE
CENTER #212F,
CEDAR CITY, UT
84720
GENERAL SHEET NOTES
SHEET KEYNOTES
1 PROTECT AND MAINTAIN ALL RACEWAYS AND WIRING ASSOCIATED WITH ALL
PANELBOARDS UNLESS SPECIFICALLY DIRECTED.
2 PROVIDE ARC FLASH AND COORDINATION STUDY FOR ELECTRICAL
INFRASTRUCTURE FROM THE MEDIUM TRANSFORMER TO ALL BRANCH
PANELBOARDS.
3 PROVIDE ALL NEW PRINTED LABELS FOR ALL EQUIPMENT, INCLUDING NEW PANEL
SCHEDULES.
4 CONTRACTOR SHALL FIELD VERIFY ALL PANELBOARDS FOR RETROFITTING WITH
THE EXISTING PANELBOARD BUCKET IN THE EXISTING CMU WALL CAVITY.
CONTRACTOR SHALL REDUE SPARE CIRCUIT BREAKERS AS NEEDED TO MEET SIZE
REQUIREMENTS.
SCALE: 1/8" = 1'-0"A1 BASEMENT ELECTRICAL DEMOLITION PLAN
NORTH
Mark: Date: Description
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
07/01/2026
(E X) "e
UTILITY
GYM
RESTROOM
102A
UTILITY
103A
CUSTODIAL
104A
OFFICE
OFFICE
WOMENS
LOCKER
STEAM RM
104B
TOWEL CAGE
104C
OUTDOOR PATIO
SHOWER
TOWEL CAGE
114A
SHOWER
LAUNDRY
106A
CUSTODIAL
DANCE LAB
DANCE LAB
116 A
CORRIDOR
100B
STORAGE
STORAGE
112A
CUSTODIAL
SHOWER
OFFICE
106B
OFFICE
106B
CORRIDOR
100A
ELEVATOR
111C
ELEVATOR
100D
ELEC
111D
CUSTODIAL
111E
HALLWAY
DRESSING
107E
OFFICE
107D
OFFICE
107C
CORRIDOR
MENS DRESSING
OFFICE
108B
RM
CUSTODIAL
107B
SHOWERS
CUSTODIAL
COMPUTER LAB
108A
CORRIDOR
100C
TOWEL CAGE
107A
CUSTODIAL
CLASSROOM
CLASSROOM
STORAGE
111B
STORAGE
111A
COMPUTER LAB
STORAGE
106D
VESTIBULE
116B
CUSTODIAL
110A
LADDER
(EX)
"DS"
(EX)
"FDS"
A B
(EX)
"D"
(EX)
"J"
(EX)
"E"
(EX)
"MDP"
(EX)
"G"
(EX)
"K"
No. 12735266 Mario S.
Martinez
E
ED
P ROF E S S
ENG
I ONA L
IN
E
E R
S N
CI
L
S T A T E O F T A H U
324 S. State St., Suite 400 Salt Lake City, UT 84111
801-328-5151 www.spectrum-engineers.com
C
A
B
2 3
D
E
1 2 3
C
4 5
2026 Spectrum Engineers, Inc.
SHEET TITLE
SUU PROJECT NO:
DRAWN BY:
CHECKED BY:
SIGNATURE:
RECORD DRAWING DATE:
DESIGNED BY:
A
ISSUE:
DATE:
B
4 5
D
E
SPECTRUM PROJECT NO:
P2502349
05/29/2026
Au to de sk
D oc s:
//2
- S
U U
M ul ti- Pu rp os e Bu ild in g El ec tri ca l U pd at es /2
- S
U U
M ul ti- Pu rp os e Bu ild in g El ec tri ca l U pd at es
El ec
.rv t
7/ 1/
1:
:5
AM
MSM
LSK
JKC
240787 05/29/2026
CONSTRUCTION
DOCUMENTS
LEVEL 1 OVERALL
ELECTRICAL
DEMOLITION PLAN
E7
SOUTHERN
UTAH
UNIVERSITY
MULTI-PURPOSE
BUILDING
ELECTRICAL
UPDATES
654 W 200 S
MULTIPURPOSE
CENTER #212F,
CEDAR CITY, UT
84720
GENERAL SHEET NOTES
SHEET KEYNOTES
1 PROTECT AND MAINTAIN ALL RACEWAYS AND WIRING ASSOCIATED WITH ALL
PANELBOARDS UNLESS SPECIFICALLY DIRECTED.
2 PROVIDE ARC FLASH AND COORDINATION STUDY FOR ELECTRICAL
INFRASTRUCTURE FROM THE MEDIUM TRANSFORMER TO ALL BRANCH
PANELBOARDS.
3 PROVIDE ALL NEW PRINTED LABELS FOR ALL EQUIPMENT, INCLUDING NEW PANEL
SCHEDULES.
4 CONTRACTOR SHALL FIELD VERIFY ALL PANELBOARDS FOR RETROFITTING WITH
THE EXISTING PANELBOARD BUCKET IN THE EXISTING CMU WALL CAVITY.
CONTRACTOR SHALL REDUE SPARE CIRCUIT BREAKERS AS NEEDED TO MEET SIZE
REQUIREMENTS.
SCALE: 1" = 10'-0"A1 LEVEL 1 OVERALL DEMOLITION POWER PLAN
NORTH
Mark: Date: Description
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
07/01/2026
(EX)
"LA"
(EX)
"F"
(EX)
"LB"
N.C.A.T.E RM
CLASSROOM
CLASSROOM
CORRIDOR
CONFERENCE
205-K
CUSTODIAL
WORKROOM
205-A
RECEPTION
CORRIDOR
CLASSROOM
STORAGE
211-A
STORAGE
210-A
CUSTODIAL
MENS RR
OFFICE
205-I
OFFICE
205-J
WOMENS RR
CORRIDOR
OFFICE
205-H
OFFICE
205-G
OFFICE
205-F
OFFICE
205-E
OFFICE
205-D
OFFICE
205-C
OFFICE
205-B
STORAGE
202-A
CUSTODIAL
ELEVATOR
200B
DEPT STORAGE
221-A
RECEPTION
OFFICE
209-A
MECHANICAL
209-J
OFFICE
209-B
OFFICE
209-C
OFFICE
209-D
OFFICE
209-E
OFFICE
209-F
OFFICE
209-G
OFFICE
209-H
STORAGE
209-A
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
N.C.A.T.E.
CUSTODIAL
RECEPTION
OFFICE
212-A
CONFERENCE
212-B
OFFICE
212-C
OFFICE
212-D
OFFICE
212-E
OPEN TO
BELOW
OPEN TO
BELOW
DEPT STORAGE
A B
(EX)
"A"
(EX)
"B"
No. 12735266 Mario S.
Martinez
E
ED
P ROF E S S
ENG
I ONA L
IN
E
E R
S N
CI
L
S T A T E O F T A H U
324 S. State St., Suite 400 Salt Lake City, UT 84111
801-328-5151 www.spectrum-engineers.com
C
A
B
2 3
D
E
1 2 3
C
4 5
2026 Spectrum Engineers, Inc.
SHEET TITLE
SUU PROJECT NO:
DRAWN BY:
CHECKED BY:
SIGNATURE:
RECORD DRAWING DATE:
DESIGNED BY:
A
ISSUE:
DATE:
B
4 5
D
E
SPECTRUM PROJECT NO:
P2502349
05/29/2026
Au to de sk
D oc s:
//2
- S
U U
M ul ti- Pu rp os e Bu ild in g El ec tri ca l U pd at es /2
- S
U U
M ul ti- Pu rp os e Bu ild in g El ec tri ca l U pd at es
El ec
.rv t
7/ 1/
1:
:5
AM
MSM
LSK
JKC
240787 05/29/2026
CONSTRUCTION
DOCUMENTS
LEVEL 2 OVERALL
ELECTRICAL
DEMOLITION PLAN
E8
SOUTHERN
UTAH
UNIVERSITY
MULTI-PURPOSE
BUILDING
ELECTRICAL
UPDATES
654 W 200 S
MULTIPURPOSE
CENTER #212F,
CEDAR CITY, UT
84720
GENERAL SHEET NOTES
SHEET KEYNOTES
1 PROTECT AND MAINTAIN EXISTING PANELBOARD AND ALL ASSOCIATED LOADS.
SCALE: 1" = 10'-0"A1 LEVEL 2 OVERALL DEMOLITION POWER PLAN
NORTH
1 PROTECT AND MAINTAIN ALL RACEWAYS AND WIRING ASSOCIATED WITH ALL
PANELBOARDS UNLESS SPECIFICALLY DIRECTED.
2 PROVIDE ARC FLASH AND COORDINATION STUDY FOR ELECTRICAL
INFRASTRUCTURE FROM THE MEDIUM TRANSFORMER TO ALL BRANCH
PANELBOARDS.
3 PROVIDE ALL NEW PRINTED LABELS FOR ALL EQUIPMENT, INCLUDING NEW PANEL
SCHEDULES.
4 CONTRACTOR SHALL FIELD VERIFY ALL PANELBOARDS FOR RETROFITTING WITH
THE EXISTING PANELBOARD BUCKET IN THE EXISTING CMU WALL CAVITY.
CONTRACTOR SHALL REDUE SPARE CIRCUIT BREAKERS AS NEEDED TO MEET SIZE
REQUIREMENTS.
Mark: Date: Description
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
07/01/2026
"C"
A
No. 12735266 Mario S.
Martinez
E
ED
P ROF E S S
ENG
I ONA L
IN
E
E R
S N
CI
L
S T A T E O F T A H U
324 S. State St., Suite 400 Salt Lake City, UT 84111
801-328-5151 www.spectrum-engineers.com
C
A
B
2 3
D
E
1 2 3
C
4 5
2026 Spectrum Engineers, Inc.
SHEET TITLE
SUU PROJECT NO:
DRAWN BY:
CHECKED BY:
SIGNATURE:
RECORD DRAWING DATE:
DESIGNED BY:
A
ISSUE:
DATE:
B
4 5
D
E
SPECTRUM PROJECT NO:
P2502349
05/29/2026
Au to de sk
D oc s:
//2
- S
U U
M ul ti- Pu rp os e Bu ild in g El ec tri ca l U pd at es /2
- S
U U
M ul ti- Pu rp os e Bu ild in g El ec tri ca l U pd at es
El ec
.rv t
7/ 1/
1:
:5
AM
MSM
LSK
JKC
240787 05/29/2026
CONSTRUCTION
DOCUMENTS
BASEMENT OVERALL
POWER PLAN
E9
SOUTHERN
UTAH
UNIVERSITY
MULTI-PURPOSE
BUILDING
ELECTRICAL
UPDATES
654 W 200 S
MULTIPURPOSE
CENTER #212F,
CEDAR CITY, UT
84720
GENERAL SHEET NOTES
SHEET KEYNOTES
1 PROTECT AND MAINTAIN ALL RACEWAYS AND WIRING ASSOCIATED WITH ALL
PANELBOARDS UNLESS SPECIFICALLY DIRECTED.
2 PROVIDE ARC FLASH AND COORDINATION STUDY FOR ELECTRICAL
INFRASTRUCTURE FROM THE MEDIUM TRANSFORMER TO ALL BRANCH
PANELBOARDS.
3 PROVIDE ALL NEW PRINTED LABELS FOR ALL EQUIPMENT, INCLUDING NEW PANEL
SCHEDULES.
4 CONTRACTOR SHALL FIELD VERIFY ALL PANELBOARDS FOR RETROFITTING WITH
THE EXISTING PANELBOARD BUCKET IN THE EXISTING CMU WALL CAVITY.
CONTRACTOR SHALL REDUE SPARE CIRCUIT BREAKERS AS NEEDED TO MEET SIZE
REQUIREMENTS.
NORTH
SCALE: 1/8" = 1'-0"A1 BASEMENT ELECTRICAL POWER PLAN
Mark: Date: Description
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
07/01/2026
"D"
"M"
UTILITY
GYM
RESTROOM
102A
UTILITY
103A
CUSTODIAL
104A
OFFICE
OFFICE
WOMENS
LOCKER
STEAM RM
104B
TOWEL CAGE
104C
OUTDOOR PATIO
SHOWER
TOWEL CAGE
114A
SHOWER
LAUNDRY
106A
CUSTODIAL
DANCE LAB
DANCE LAB
116 A
CORRIDOR
100B
STORAGE
STORAGE
112A
CUSTODIAL
SHOWER
OFFICE
106B
OFFICE
106B
CORRIDOR
100A
ELEVATOR
111C
ELEVATOR
100D
ELEC
111D
CUSTODIAL
111E
HALLWAY
DRESSING
107E
OFFICE
107D
OFFICE
107C
CORRIDOR
MENS DRESSING
OFFICE
108B
RM
CUSTODIAL
107B
SHOWERS
CUSTODIAL
COMPUTER LAB
108A
CORRIDOR
100C
TOWEL CAGE
107A
CUSTODIAL
CLASSROOM
CLASSROOM
STORAGE
111B
STORAGE
111A
COMPUTER LAB
STORAGE
106D
VESTIBULE
116B
CUSTODIAL
110A
A B
"MDP"
"E"
"J"
"G"
"K"
"FUT GP"
No. 12735266 Mario S.
Martinez
E
ED
P ROF E S S
ENG
I ONA L
IN
E
E R
S N
CI
L
S T A T E O F T A H U
324 S. State St., Suite 400 Salt Lake City, UT 84111
801-328-5151 www.spectrum-engineers.com
C
A
B
2 3
D
E
1 2 3
C
4 5
2026 Spectrum Engineers, Inc.
SHEET TITLE
SUU PROJECT NO:
DRAWN BY:
CHECKED BY:
SIGNATURE:
RECORD DRAWING DATE:
DESIGNED BY:
A
ISSUE:
DATE:
B
4 5
D
E
SPECTRUM PROJECT NO:
P2502349
05/29/2026
Au to de sk
D oc s:
//2
- S
U U
M ul ti- Pu rp os e Bu ild in g El ec tri ca l U pd at es /2
- S
U U
M ul ti- Pu rp os e Bu ild in g El ec tri ca l U pd at es
El ec
.rv t
7/ 1/
1:
:0
AM
MSM
LSK
JKC
240787 05/29/2026
CONSTRUCTION
DOCUMENTS
LEVEL 1 OVERALL
POWER PLAN
E10
SOUTHERN
UTAH
UNIVERSITY
MULTI-PURPOSE
BUILDING
ELECTRICAL
UPDATES
654 W 200 S
MULTIPURPOSE
CENTER #212F,
CEDAR CITY, UT
84720
GENERAL SHEET NOTES
SHEET KEYNOTES
1 FORMERLY LABELED AS PANEL "E"
1 PROTECT AND MAINTAIN ALL RACEWAYS AND WIRING ASSOCIATED WITH ALL
PANELBOARDS UNLESS SPECIFICALLY DIRECTED.
2 PROVIDE ARC FLASH AND COORDINATION STUDY FOR ELECTRICAL
INFRASTRUCTURE FROM THE MEDIUM TRANSFORMER TO ALL BRANCH
PANELBOARDS.
3 PROVIDE ALL NEW PRINTED LABELS FOR ALL EQUIPMENT, INCLUDING NEW PANEL
SCHEDULES.
4 CONTRACTOR SHALL FIELD VERIFY ALL PANELBOARDS FOR RETROFITTING WITH
THE EXISTING PANELBOARD BUCKET IN THE EXISTING CMU WALL CAVITY.
CONTRACTOR SHALL REDUE SPARE CIRCUIT BREAKERS AS NEEDED TO MEET SIZE
REQUIREMENTS.
SCALE: 1" = 10'-0"A1 LEVEL 1 OVERALL POWER PLAN
NORTH
Mark: Date: Description
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
07/01/2026
(EX)
"LA"
(EX)
"F"
(EX)
"LB"
N.C.A.T.E RM
CLASSROOM
CLASSROOM
CORRIDOR
CONFERENCE
205-K
CUSTODIAL
WORKROOM
205-A
RECEPTION
CORRIDOR
CLASSROOM
STORAGE
211-A
STORAGE
210-A
CUSTODIAL
MENS RR
OFFICE
205-I
OFFICE
205-J
WOMENS RR
HALLWAY
OFFICE
205-H
OFFICE
205-G
OFFICE
205-F
OFFICE
205-E
OFFICE
205-D
OFFICE
205-C
OFFICE
205-B
STORAGE
202-A
CUSTODIAL
ELEVATOR
200B
DEPT STORAGE
221-A
RECEPTION
OFFICE
209-A
MECHANICAL
209-J
OFFICE
209-B
OFFICE
209-C
OFFICE
209-D
OFFICE
209-E
OFFICE
209-F
OFFICE
209-G
OFFICE
209-H
STORAGE
209-A
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
OFFICE
N.C.A.T.E.
CUSTODIAL
RECEPTION
OFFICE
212-A
CONFERENCE
212-B
OFFICE
212-C
OFFICE
212-D
OFFICE
212-E
OPEN TO
BELOW
OPEN TO
BELOW
DEPT STORAGE
A B
"A"
"B"
No. 12735266 Mario S.
Martinez
E
ED
P ROF E S S
ENG
I ONA L
IN
E
E R
S N
CI
L
S T A T E O F T A H U
324 S. State St., Suite 400 Salt Lake City, UT 84111
801-328-5151 www.spectrum-engineers.com
C
A
B
2 3
D
E
1 2 3
C
4 5
2026 Spectrum Engineers, Inc.
SHEET TITLE
SUU PROJECT NO:
DRAWN BY:
CHECKED BY:
SIGNATURE:
RECORD DRAWING DATE:
DESIGNED BY:
A
ISSUE:
DATE:
B
4 5
D
E
SPECTRUM PROJECT NO:
P2502349
05/29/2026
Au to de sk
D oc s:
//2
- S
U U
M ul ti- Pu rp os e Bu ild in g El ec tri ca l U pd at es /2
- S
U U
M ul ti- Pu rp os e Bu ild in g El ec tri ca l U pd at es
El ec
.rv t
7/ 1/
1:
:0
AM
MSM
LSK
JKC
240787 05/29/2026
CONSTRUCTION
DOCUMENTS
LEVEL 2 OVERALL
POWER PLAN
E11
SOUTHERN
UTAH
UNIVERSITY
MULTI-PURPOSE
BUILDING
ELECTRICAL
UPDATES
654 W 200 S
MULTIPURPOSE
CENTER #212F,
CEDAR CITY, UT
84720
GENERAL SHEET NOTES
SHEET KEYNOTES
1 PROTECT AND MAINTAIN ALL RACEWAYS AND WIRING ASSOCIATED WITH ALL
PANELBOARDS UNLESS SPECIFICALLY DIRECTED.
2 PROVIDE ARC FLASH AND COORDINATION STUDY FOR ELECTRICAL
INFRASTRUCTURE FROM THE MEDIUM TRANSFORMER TO ALL BRANCH
PANELBOARDS.
3 PROVIDE ALL NEW PRINTED LABELS FOR ALL EQUIPMENT, INCLUDING NEW PANEL
SCHEDULES.
4 CONTRACTOR SHALL FIELD VERIFY ALL PANELBOARDS FOR RETROFITTING WITH
THE EXISTING PANELBOARD BUCKET IN THE EXISTING CMU WALL CAVITY.
CONTRACTOR SHALL REDUE SPARE CIRCUIT BREAKERS AS NEEDED TO MEET SIZE
REQUIREMENTS.
SCALE: 1" = 10'-0"A1 LEVEL 2 OVERALL POWER PLAN
NORTH
Mark: Date: Description
DIVISION OF FACILITIES
CONSTRUCTION AND
MANAGEMENT
Jason Van Ausdal
07/01/2026
600/3
GROUND BUS
NEUTRAL BUS
100/3
100/3
"D"
(EX)
225/3
100/3
100/3
"J"
(EX)
100/3
100/3
"K"
(EX)
150/3
"F"
(EX)
225/3
225/3
"G"
(EX)
50/3
50/3
"E"
(EX)
40/3
100/3
"LB"
(EX)
AC-1AC-1
(EX)
AC-2AC-2
(EX)
30/3
100/3
GROUND
PER NEC
#3/0 CU
EXEXEXEX EX
EXEXEX
EX
50/3
50/3
"e"
(EX)
100/3
100/3
"C"
(EX)
100/3
100/3
"B"
(EX)
EXEX
100/3
100/3
"A"
(EX)
EX
100/3
"LA"
EX
EX
100/3
150/3
EX
100/3
100A
EX
100/3
EX
100/3
100A
(EX) ELEV(EX) ELEV
EX
M
70/370/3
EXEX
(EX) GYM(EX) GYM
(EX) POOL(EX) POOL
EX
150/3
"F"
(EX)
40/3
100/3
"LB"
(EX)
AC-1AC-1
(EX)
AC-2AC-2
(EX)
30/3
100/3
GROUND BUS
NEUTRAL BUS
100/3
100/3
"D"
100/3
100/3
"J"
100/3
100/3
"K"
225/3
225/3
"G"
50/3
50/3
"E"
GROUND
PER NEC
EX
EXEXEX
70/3 70/3 50/3
SPARE
50/3
SPARE
50/3
SPARE
DMMTP
LSIG
1000/3 AF
1000/3 AT
LSIGLSIG
1000/3 AF
1000/3 AT
LSIG
LSI
600/3 AF
600/3 AT
LSI
SPARE
400/3 AF
400/3 AT
LSI
SPARE
200/3 AF
200/3 AT
LSI
SPARE
42C
52C
GROUND BUS
NEUTRAL BUS
12C
50/3
50/3
"M"
100/3
100/3
"C"
100/3
100/3
"B"
22C22C
100/3
100/3
"A"
22C
100/3
"LA"
EX
EX
100/3
12C 22C 22C 30C
150/3
70CEX
100/3
100A
(EX) ELEV(EX) ELEV
EX
100/3
EXEX
(EX) GYM(EX) GYM
(EX) POOL(EX) POOL
M
100/3 AF
100/3 AT
LSI
SPARE
100/3 AF
100/3 AT
LSI
SPARE
SPD
60/3
LSI
SPARE
400/3 AF
400/3 AT
LSI
SPARE
EXEX
(EX) DISTRIBUTION PANELBOARD "MDP"
208/120V, 3Ø, 4W
600 A, 65000AIC
GROUND BUS
100% NEUTRAL
SPACE
(EX) "TX-MP" PAD MOUNTED XFMR
300KVA
12,470V DELTA-480/277V WYE
3P, 4W, 1.73%Z
MV05
600 600 600 600 600
SPARE
(EX) "S10"
PAD-MOUNTED SWITCH
(EX)
"S11"
(EX)
"S16"
(EX)
"S9"
5 5 5 5 5 5 5 5 56
6 6
(EX)
"FDS"
(EX)
"DS"100 A
6 6 6
1 DISTRIBUTION PANELBOARD "MDP"
208/120V, 3Ø, 4W
600 A, 65000AIC
GROUND BUS
100% NEUTRAL
MV05
600 600 600 600 600
SPARE
(EX) "S10"
PAD-MOUNTED SWITCH
(EX)
"S11"
(EX)
"S16"
(EX)
"S9"
"TX-MP" PAD MOUNTED XFMR
300KVA, NEMA 3R
12,470V DELTA-208/120V WYE
3P, 4W
DISTRIBUTION PANEL BOARD "M"
208/120V, 3Ø, 4W
1000 A, 65000AIC
GROUND BUS
100% NEUTRAL
NEMA 3R
7 7 7 7 7 7 77 7
22222222
No. 12735266 Mario S.
Martinez
E
ED
P ROF E S S
ENG
I ONA L
IN
E
E R
S N
CI
L
S T A T E O F T A H U
324 S. State St., Suite 400 Salt Lake City, UT 84111
801-328-5151 www.spectrum-engineers.com
C
A
B
2 3
D
E
1 2 3
C
4 5
2026 Spectrum Engineers, Inc.
SHEET TITLE
SUU PROJECT NO:
DRAWN BY:
CHECKED BY:
SIGNATURE:
RECORD DRAWING DATE:
DESIGNED BY:
A
ISSUE:
DATE:
B
4 5
D
E
SPECTRUM PROJECT NO:
P2502349
05/29/2026
Au to de sk
D oc s:
//2
- S
U U
M ul ti- Pu rp os e Bu ild in g El ec tri ca l U pd at es /2
- S
U U
M ul ti- Pu rp os e Bu ild in g El ec tri ca l U pd at es
El ec
.rv t
7/ 1/
1:
:0
AM
MSM
LSK
JKC
240787 05/29/2026
CONSTRUCTION
DOCUMENTS
ONE-LINE DIAGRAMS
E12
SOUTHERN
UTAH
UNIVERSITY
MULTI-PURPOSE
BUILDING
ELECTRICAL
UPDATES
654 W 200 S
MULTIPURPOSE
CENTER #212F,
CEDAR CITY, UT
84720
1. CONDUCTORS SHOWN ARE SHOWN FOR EACH CONDUIT WITH MODIFICATIONS
AS NOTED IN NOTE 5. ALL CONDUCTORS SHOWN ARE THWN UNLESS
OTHERWISE NOTED.
2. PROVIDE EQUIPMENT GROUND CONDUCTORS PER TABLE 250-122 WHEN
CIRCUIT BREAKERS ARE SIZED GREATER THAN AMPERE RATING SHOWN IN
TABLE.
3. PROVIDE #10 NEUTRALS FOR MULTIWIRE BRANCH CIRCUITS SERVING
COMPUTERS.
4. GROUND (G) CONDUCTOR MAY BE DELETED ON SERVICE ENTRANCE
CONDUCTORS.
5. SYMBOL SUBSCRIPTS:
6. RACEWAY ONLY. CONDUCTORS PROVIDED BY UTILITY.
IG
(E.G.)
COPPER CONDUCTOR AND
CONDUIT SCHEDULE
SUBSCRIPT (NOTE 5)
SCHEDULE NUMBER
5C
"2N": INCLUDE TWO NEUTRAL CONDUCTORS SIZED AS SCHEDULED FOR
PHASE AND NEUTRAL CONDUCTORS WHERE THE CONDUCTOR IS #1/0
OR LARGER. INCLUDE A SINGLE 200% RATED CONDUCTOR THAT IS
TWICE THE AMPACITY OF THE SCHEDULED PHASE AND NEUTRAL
CONDUCTOR WHERE THE CONDUCTOR IS BELOW #1/0 IN SIZE.
"CI": PROVIDE CIRCUIT INTEGRITY CABLE; TYPE TWO-HOUR FIRE
RESISTIVE CABLES IN CONDUIT OR PROVIDE FEEDER ENCASED IN
CONCRETE.
"FG" FULL SIZE GROUND, SIZE EQUIPMENT GROUNDING CONDUCTOR TO
BE SAME SIZE AS THE PHASE CONDUCTORS.
"HH": NEUTRAL CURRENTS EXIST DUE TO HIGH HARMONIC "NONLINEAR"
LOADS. CURRENT CARRYING CONDUCTORS DERATED
ACCORDINGLY. PROVIDE THE IG/HH SIZE FOR THE EQUIPMENT
GROUNDING CONDUCTOR.
"IG": INCLUDE IG (INSULATED/ISOLATED GROUND CONDUCTOR)
SCHEDULED ALONG WITH THE GROUND OF EQUIPMENT GROUND
CONDUCTOR.
"MC": PROVIDE FEEDER IN METAL-CLAD CABLE; TYPE MC IN PLACE OF
SINGLE CONDUCTORS IN CONDUIT.
"SE": SUBSTITUTE "SE" CONDUCTOR FOR "G" CONDUCTOR SHOWN, WHICH
IS SIZED FOR THE GROUNDING OF THE SECONDARY OF THE
SEPARATELY DERIVED SYSTEM.
"SER": PROVIDE SERVICE-ENTRANCE CABLE; TYPE SE OR SER IN PLACE OF
SINGLE CONDUCTORS IN CONDUIT.
CONDUCTOR AND CONDUIT SCHEDULE NOTES
SYM AMP
HH
AMPS
CONDUIT
SIZE
CONDCUTOR (NOTE 1)
IG/HH SE NOTESQTY SIZE G
1C 20 - 0.75 2 12 12 12 8 2 2C 20 - 0.75 3 12 12 12 8 2 3C 20 24 0.75 4 12 12 12 8 2 4C 30 - 0.75 2 10 10 10 8 2 5C 30 - 0.75 3 10 10 10 8 2 6C 30 32 0.75 4 10 10 10 8 2 7C 40 - 1 2 8 10 8 6 2 8C 40 - 1 3 8 10 8 6 2 9C 40 44 1 4 8 10 8 6 2 10C 55 - 1 2 6 10 8 4 2 11C 55 - 1 3 6 10 8 4 2 12C 55 60 1.25 4 6 10 8 4 2 13C 70 - 1 2 4 8 4 2 2 14C 70 - 1.25 3 4 8 4 2 2 15C 70 76 1.25 4 4 8 4 2 2 16C 85 - 1.25 2 3 8 3 2 2 17C 85 - 1.25 3 3 8 3 2 2 18C 85 92 1.25 4 3 8 3 2 2 19C 95 - 1.25 3 2 8 2 2 2 20C 95 104 1.5 4 2 8 2 2 2 21C 130 - 1.5 3 1 6 2 2 2 22C 130 116 1.5 4 1 6 2 2 2 23C 150 - 2 3 1/0 6 2 1/0 2 24C 150 136 2 4 1/0 6 2 1/0 2 27C 200 - 2 3 3/0 6 2 2/0 2 28C 200 180 2.5 4 3/0 6 2 2/0 2 29C 230 - 2.5 3 4/0 4 2 2/0 2 30C 230 208 2.5 4 4/0 4 2 2/0 2 34C 310 280 3 4 350 3 1/0 3/0 2 35C 380 - 3.5 3 500 3 3/0 3/0 2
37C 400 - 2 EA 2 3 3/0 3 3/0 3/0 2
38C 400 360 2 EA 2.5 4 3/0 3 3/0 3/0 2
41C 620 - 2 EA 3 3 350 1/0 4/0 3/0 2
42C 620 560 2 EA 3 4 350 1/0 4/0 3/0 2
52C 1240 1120 4 EA 3 4 350 3/0 4/0 3/0 4
70C 150 - 2 4 2/0 4 - - -
SCALE: NTSA1 ONE-LINE DIAGRAM - DEMOLITION
SCALE: NTSA3 ONE-LINE DIAGRAM - NEW
SHEET KEYNOTES
1 DEMOLISH PANELBOARD. RETAIN EXISTING PANELBOARD BUCKET, ALL WIRING AND
CONDUITS ENTERING THE ENCLOSURE TO BE REUSED FOR NEW WORK.
2 PROVIDE NEW PANELBOARD. NEW PANEL SHALL HAVE THE ABILITY TO FIT WITHIN
THE EXISTING PANELBOARD BUCKET IN THE WALL CAVITY FOR ALL RECESSED
PANELS. RECONNECT ALL WIRING AND CONDUITS ENTERING THE ENCLOSURE.
MATCH WIRE SIZE AND EXTEND ALL BRANCH CIRCUIT WIRING AS REQUIRED.
PROVIDE TERMINATION BLOCKS FOR ALL EXTENSIONS FOR PRICING. COORDINATE
WITH SUU FOR APPROVAL OF METHODS OF SPLICING.
3 PROVIDE NEW CONDUIT AND WIRE WHERE SHOWN ON PLANS. REUSE EXISTING
CONDUIT WHERE SHOWN ON PLANS.
4 PROTECT AND MAINTAIN EXISTING PANELBOARD.
5 CONTRACTOR TO DEMOLISH EXISTING CABLING AND TO PROTECT AND MAINTAIN
EXISTING CONDUIT FOR RE-USE.
6 CONTRACTOR TO PROTECT AND MAINTAIN EXISTING FEEDER.
7 CONTRACTOR TO PROVIDE NEW WIRING IN EXISTING CONDUIT.
8 DEMOLISH EXISTING CABLING, PROTECT AND MAINTAIN EXISTING CONDUITS.
9 PROVIDE (4) 3" CND TO INSIDE OF BUILDING. REFER TO PLANS.
10 DISCONNECT EXISTING VITALITY METER FOR REUSE.
11 RECONNECT EXISTING VITALITY METER AND INTEGRATE INTO THE BUILDING
MANAGEMENT. COORDINATE WITH SUU FOR INSTALLATION.
12 EXTEND SPARE CONDUIT FROM EXISTING DUCT BANK. PROVIDE NEW DUCT BANK
EXTENSION AND INSTALL NEW CONTINUOUS CABLING FOR THE ENTIRE RUN.
13 REFER TO TYPICAL PAD MOUNT TRANSFORMER GROUNDING RISER DIAGRAM.
14 PROVIDE 100% RATED CIRCUIT BREAKER.
15 DEMOLISH EXISTING CONDUIT AND WIRING.
16 PROVIDE (4)…