5-3-CR27001-27093730 Approved Specifications.pdf
PDF 2 MB Posted
- Solicitation number
- CR27001
- Issued by
- Utah
About this file
This document comprises approved electrical construction specifications for a multipurpose building electrical upgrade project at Southern Utah University, issued by the State of Utah Division of Facilities Construction and Management (DFCM). The specifications cover comprehensive Division 26 electrical work including common work results, medium-voltage cables, low-voltage electrical power conductors and cables, grounding and bonding systems, hangers and supports, raceways and boxes, underground ducts and raceways, vibration and seismic controls, identification systems, overcurrent protective devices, pad-mounted transformers, switchboards, panelboards, and electricity metering. The project is identified as Project #27093730 with a construction cost estimate of $413,678.00. The specifications detail all materials, products, installation methods, quality assurance requirements, and field quality control testing procedures necessary for completion of the electrical installation work.
The specifications establish detailed requirements for materials sourcing, manufacturer qualifications, testing agency certifications, and compliance with applicable codes including NFPA 70, IEEE standards, UL listings, and NETA acceptance testing standards. All cable splicing and termination work must be performed by qualified personnel with minimum ten years of journeyman experience and manufacturer certification. The specifications mandate comprehensive field testing including hi-pot testing for medium-voltage cables with two weeks' written notice to the architect and owner prior to energization. Grounding system resistance testing must be performed using the fall-of-potential method according to IEEE 81, with maximum allowable ground resistance values ranging from 3 to 10 ohms depending on equipment capacity. Documentation requirements include material certificates, source quality-control test reports, field quality-control test reports, and preparation of detailed test and inspection reports for inclusion in the owner's operation and maintenance manuals. All work must comply with industry standards and be performed in a professional manner with proper protection and maintenance of all finishes and coatings throughout the project.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Division Section Title Pages
SPECIFICATIONS GROUP
Facility Services Subgroup
DIVISION 26 – ELECTRICAL
260500 COMMON WORK RESULTS FOR ELECTRICAL 4
260513 MEDIUM-VOLTAGE CABLES 6
260519 LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES 4
260526 GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS 7
260529 HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS 5
260533 RACEWAY AND BOXES FOR ELECTRICAL SYSTEMS 8
260543 UNDERGROUND DUCTS AND RACEWAYS FOR ELECTRICAL SYSTEMS 8
260548 VIBRATION AND SEISMIC CONTROLS FOR ELECTRICAL SYSTEMS 7
260553 IDENTIFICATION FOR ELECTRICAL SYSTEMS 8
260574 OVERCURRENT PROTECTIVE DEVICE AND ARC FLASH STUDY 12
261219 PAD-MOUNTED, LIQUID-FILLED, MEDIUM-VOLTAGE TRANSFORMERS 12
262413 SWITCHBOARDS 10
262416 PANELBOARDS 8
262713 ELECTRICITY METERING 6
END OF TABLE OF CONTENTS
MULTI-PURPOSE BUILDING ELECTRICAL CONSTRUCTION DOCUMENTS
UPDATES MAY 29, 2026
COMMON WORK RESULTS FOR ELECTRICAL 260500 - 1
SECTION 260500
COMMON WORK RESULTS FOR ELECTRICAL
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes:
1. Electrical equipment coordination and installation.
2. Sleeves for raceways and cables.
3. Sleeve seals.
4. Grout.
5. Common electrical installation requirements.
1.3 DEFINITIONS
A. EPDM: Ethylene-propylene-diene terpolymer rubber.
1.4 COORDINATION
A. Coordinate arrangement, mounting, and support of electrical equipment:
1. To allow maximum possible headroom unless specific mounting heights that reduce headroom are indicated.
2. To provide for ease of disconnecting the equipment with minimum interference to other installations.
3. To allow right of way for piping and conduit installed at required slope.
4. So connecting raceways, cables, wireways, cable trays, and busways will be clear of obstructions and of the working and access space of other equipment.
B. Coordinate electrical connections to equipment:
1. Refer to equipment manufacturer's shop drawings and written instructions.
Provide all power and control wiring with associated raceways for complete operation.
2. Verify electrical requirements of equipment on nameplate and installation manual. Ensure that the electrical connections meet the requirements and notify Engineer of any discrepancies.
3. Meet with equipment manufacturers representatives to coordinate equipment installation and electrical connections.
C. Coordinate installation of required supporting devices and set sleeves in cast-in-place concrete, masonry walls, and other structural components as they are constructed.
D. Coordinate sleeve selection and application with selection and application of firestopping specified in Division 07 Section "Penetration Firestopping."."
PART 2 - PRODUCTS
2.1 SLEEVES FOR RACEWAYS AND CABLES
A. Steel Pipe Sleeves: ASTM A 53/A 53M, Type E, Grade B, Schedule 40, galvanized steel, plain ends.
COMMON WORK RESULTS FOR ELECTRICAL 260500 - 2
B. Cast-Iron Pipe Sleeves: Cast or fabricated "wall pipe," equivalent to ductile-iron pressure pipe, with plain ends and integral waterstop, unless otherwise indicated.
C. Sleeves for Rectangular Openings: Galvanized sheet steel.
1. Minimum Metal Thickness:
a. For sleeve cross-section rectangle perimeter less than 50 inches (1270
mm) and no side more than 16 inches (400 mm), thickness shall be
0.052 inch (1.3 mm).
b. For sleeve cross-section rectangle perimeter equal to, or more than, 50 inches (1270 mm) and 1 or more sides equal to, or more than, 16 inches (400 mm), thickness shall be 0.138 inch (3.5 mm).
2.2 SLEEVE SEALS
A. Description: Modular, water tight sealing device, designed for field assembly, to fill annular space between sleeve and raceway or cable.
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Advance Products & Systems, Inc.
b. Calpico, Inc.
c. Metraflex Co.
d. O-Z Gedney
e. Pipeline Seal and Insulator, Inc.
2. Sealing Elements: EPDM interlocking links shaped to fit surface of cable or conduit. Include type and number required for material and size of raceway or cable.
3. Pressure Plates: Carbon steel. Include two for each sealing element.
4. Connecting Bolts and Nuts: Carbon steel with corrosion-resistant coating of length required to secure pressure plates to sealing elements. Include one for each sealing element.
2.3 GROUT
A. Nonmetallic, Shrinkage-Resistant Grout: ASTM C 1107, factory-packaged, nonmetallic aggregate grout, noncorrosive, nonstaining, mixed with water to consistency suitable for application and a 30-minute working time.
PART 3 - EXECUTION
3.1 COMMON REQUIREMENTS FOR ELECTRICAL INSTALLATION
A. Comply with NECA 1.
B. Measure indicated mounting heights to bottom of unit for suspended items and to center of unit for wall-mounting items.
C. Headroom Maintenance: If mounting heights or other location criteria are not indicated, arrange and install components and equipment to provide maximum possible headroom consistent with these requirements.
D. Equipment: Install to facilitate service, maintenance, and repair or replacement of components of both electrical equipment and other nearby installations. Connect in such a way as to facilitate future disconnecting with minimum interference with other items in the vicinity.
E. Right of Way: Give to piping systems installed at a required slope.
COMMON WORK RESULTS FOR ELECTRICAL 260500 - 3
3.2 SLEEVE INSTALLATION FOR ELECTRICAL PENETRATIONS
A. Electrical penetrations occur when raceways, cables, wireways, cable trays, or busways penetrate concrete slabs, concrete or masonry walls, or fire-rated floor and wall assemblies.
B. Concrete Slabs and Walls: Install sleeves for penetrations unless core-drilled holes or formed openings are used. Install sleeves during erection of slabs and walls.
C. Use pipe sleeves unless penetration arrangement requires rectangular sleeved opening.
D. Fire-Rated Assemblies: Install sleeves for penetrations of fire-rated floor and wall assemblies unless openings compatible with firestop system used are fabricated during construction of floor or wall.
E. Cut sleeves to length for mounting flush with both surfaces of walls.
F. Extend sleeves installed in floors 2 inches (50 mm) above finished floor level.
G. Size pipe sleeves to provide 1/4-inch (6.4-mm) annular clear space between sleeve and raceway or cable, unless indicated otherwise.
H. Seal space outside of sleeves with grout for penetrations of concrete and masonry
1. Promptly pack grout solidly between sleeve and wall so no voids remain. Tool exposed surfaces smooth; protect grout while curing.
I. Interior Penetrations of Non-Fire-Rated Walls and Floors: Seal annular space between sleeve and raceway or cable, using joint sealant appropriate for size, depth, and location of joint. Comply with requirements in Division 07 Section "Joint Sealants.".
J. Fire-Rated-Assembly Penetrations: Maintain indicated fire rating of walls, partitions, ceilings, and floors at raceway and cable penetrations. Install sleeves and seal raceway and cable penetration sleeves with firestop materials. Comply with requirements in Division 07 Section "Penetration Firestopping."
K. Aboveground, Exterior-Wall Penetrations: Seal penetrations using steel pipe sleeves and mechanical sleeve seals. Select sleeve size to allow for 1-inch (25-mm) annular clear space between pipe and sleeve for installing mechanical sleeve seals.
L. Underground, Exterior-Wall Penetrations: Install cast-iron pipe sleeves. Size sleeves to allow for 1-inch (25-mm) annular clear space between raceway or cable and sleeve for installing mechanical sleeve seals. Install water-tight assembly.
1. Slope underground conduits away from building to prevent accumulated water from traveling down conduit into building.
3.3 SLEEVE-SEAL INSTALLATION
A. Install to seal exterior wall penetrations.
B. Use type and number of sealing elements recommended by manufacturer for raceway or cable material and size. Position raceway or cable in center of sleeve. Assemble mechanical sleeve seals and install in annular space between raceway or cable and sleeve. Tighten bolts against pressure plates that cause sealing elements to expand and make watertight seal.
COMMON WORK RESULTS FOR ELECTRICAL 260500 - 4
3.4 FIRESTOPPING
A. Apply firestopping to penetrations of fire-rated floor and wall assemblies for electrical installations to restore original fire-resistance rating of assembly. Firestopping materials and installation requirements are specified in Division 07 Section "Penetration Firestopping."
END OF SECTION 260500
SECTION 260513
MEDIUM-VOLTAGE CABLES
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes cables and related splices, terminations, and accessories for medium-voltage electrical distribution systems.
1.3 DEFINITIONS
A. NETA ATS: Acceptance Testing Specification.
1.4 SUBMITTALS
A. Product Data: For each type of cable and fault indicator specified. Include splices and terminations for cables and cable accessories.
B. Calculations: When requested by Engineer, submit cable pull tension and side-wall pressure calculations to show that values are within cable manufacturer's limits and recommendations. Submit statement by the manufacturer that calculated values are within the limits of the cable.
C. Qualification Data: For Installer and testing agency.
D. Material Certificates: For each cable and accessory type, signed by manufacturers.
E. Source quality-control test reports.
F. Field quality-control test reports.
1.5 QUALITY ASSURANCE
A. Installer: Engage a cable splicer, trained and certified by splice material manufacturer, to install, splice, and terminate medium-voltage cable.
1. Cable splices and terminations shall be made only by qualified cable splicers in strict accordance with the recommendations of the cable manufacturer and this specification. The qualifications shall consist of evidence to satisfy the Engineer that each cable splicer has worked as a journeyman in his trade for the past ten years, continuously. A list of jobs, types of cable and voltage levels worked on during this period and manufacturer's training certificates must be supplied as the required evidence.
B. Manufacturer: The manufacturer of medium voltage power cables shall have a performance record demonstrating a minimum of 30 years successful operating experience in utility and industrial power cable applications.
C. Testing Agency Qualifications: An independent agency, with the experience and capability to conduct the testing indicated, that is a member company of the InterNational Electrical Testing Association or is a nationally recognized testing laboratory (NRTL) as defined by OSHA in 29 CFR 1910.7, and that is acceptable to authorities having jurisdiction.
1. Testing Agency's Field Supervisor: Person currently certified by the InterNational
Electrical Testing Association or the National Institute for Certification in Engineering Technologies to supervise on-site testing specified in Part 3.
D. Source Limitations: Obtain all cables from a single manufacturer.
E. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.
F. Comply with IEEE C2 and NFPA 70.
1.6 PROJECT CONDITIONS
A. Interruption of Existing Electric Service: Do not interrupt electric service to facilities occupied by Owner or others unless permitted under the following conditions and then only after arranging to provide temporary electric service according to requirements indicated:
1. Notify Engineer and Owner no fewer than two weks in advance of proposed interruption of electric service.
2. Do not proceed with interruption of electric service without Engineer's and
Owner's written permission.
PART 2 - PRODUCTS
2.1 MANUFACTURERS
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. Cables:
a. Kerite Co. (The).
b. Okonite Company (The).
2. Cable Splicing Products and Accessories:
a. Raychem Corp.; Telephone Energy and Industrial Division; Tyco
International Ltd.
b. 3M; Electrical Products Division; type "QS3" cold-shrink.
3. Cable Terminating Products and Accessories:
a. Thomas & Betts, Elastimold.
b. 3M; Electrical Products Division.
2.2 CABLES
A. Cable Type: MV105.
B. Comply with UL 1072, AEIC CS 8, ICEA S-93-639 and ICEA S-97-682
C. Comply with ASTM B-8, B-496, B400 and B231.
D. Conductor: Copper.
E. Conductor Stranding: Uncoated annealed Class B concentric compact round, stranded copper per ASTM B-496 and as required by UL 1072, Paragraphs 4 through 12 and ICEA S-93-639 /NEMA WC74, Part 2.
F. Conductor Screen: Extruded semi-conducting EPR compound.
G. Conductor Insulation: Ethylene-propylene rubber.
1. Voltage Rating: 15 kV.
2. Insulation Thickness: 133 percent insulation level.
3. The ethylene content of the elastomer used in the insulation compound shall not exceed 72% by weight nor shall the insulation compound contain any polyethylene.
4. Insulation Shield: Extruded semi-conducting compound having peel strength requirements per ICEA S-96-682.
5. Suitable for 105C continuous, 140C for emergency overload protection and
250C for safe short circuit conductor temperature.
6. Emergency overload operation may occur for periods up to 1500 hours cumulative during the life of the cable.
H. Shielding: 5-mil copper tape, helically applied over semiconducting insulation shield, minimum 12.5% overlap wrap for duct applications, and minimum 25% overlap wrap with "CT" rating for cable tray applications. Per ICEA S-93-639 / NEMA WC74 and AEIC CS- 8.
I. Cable Jacket:
1. Flame and sunlight-resistant PVC.
J. Cables Labeled "For CT Use", and IEEE 1202 (FT4).
2.3 SPLICE KITS
A. Connectors and Splice Kits: Comply with IEEE 404; type as recommended by cable or splicing kit manufacturer for the application.
B. Splicing and Termination Products: As recommended, in writing, by splicing kit manufacturer for specific sizes, ratings, and configurations of cable conductors. Include all components required for complete splice and termination, with detailed instructions.
1. EPR to EPR splices: Combination tape and cold-shrink-rubber sleeve kit with rejacketing by cast-epoxy-resin encasement or other waterproof, abrasion-resistant material.
2. Splice materials shall provide long-term permanent set capabilities, such as silicone, to deliver reliable and consistent interfacial pressure for life of cable.
3. Splice products shall be manufactured in the USA.
4. All splices shall be factory tested -partial discharge and 1-minute withstand.
2.4 SOLID TERMINATIONS
A. Shielded-Cable Terminations: Do not use solid terminations unless required for connection to transformer primary bushings. Comply with the following classes of IEEE 48. Insulation class is equivalent to that of cable. Include shield ground strap for shielded cable terminations.
1. Class 1 Terminations: Modular type or heat-shrink type, furnished as a kit, with stress-relief tube; multiple, molded-silicone rubber, insulator modules; shield ground strap; and compression-type connector.
2.5 SEPARABLE INSULATED CONNECTORS
A. Description: Modular system, complying with IEEE 386, with disconnecting, single-pole, cable terminators and with matching, stationary, plug-in, dead-front terminals designed for cable voltage and for sealing against moisture.
B. Terminations at Distribution Points: Modular type, consisting of terminators installed on cables and modular, dead-front, terminal junctions for interconnecting cables.
C. Load-Break Cable Terminators: Elbow-type units with 200-A load make/break and continuous-current rating; coordinated with insulation diameter, conductor size, and material of cable being terminated. Include test point on terminator body that is capacitance coupled.
D. Dead-Break Cable Terminators: Elbow-type unit with 600-A continuous-current rating;
designed for de-energized disconnecting and connecting; coordinated with insulation diameter, conductor size, and material of cable being terminated. Include test point on terminator body that is capacitance coupled.
2.6 ARC-PROOFING MATERIALS
A. Tape for First Course on Metal Objects: 10-mil- (250-micrometer-) thick, corrosion-protective, moisture-resistant, PVC pipe-wrapping tape.
B. Arc-Proofing Tape: Fireproof tape, flexible, conformable, intumescent to 0.3 inch (8 mm) thick, compatible with cable jacket.
C. Glass-Cloth Tape: Pressure-sensitive adhesive type, 1/2 inch (13 mm) wide.
2.7 FAULT INDICATORS
A. Indicators: Manually reset fault indicator with inrush restraint feature, arranged to clamp to cable sheath and provide a display after a fault has occurred in cable. Instrument shall not be affected by heat, moisture, and corrosive conditions and shall be recommended by manufacturer for installation conditions.
B. Fault indicators shall be installed on the end of each new cables (each phase) installed with this project.
C. Resetting Tool: Designed for use with fault indicators, with moisture-resistant storage and carrying case.
2.8 SOURCE QUALITY CONTROL
A. Test and inspect cables according to ICEA S-93-639 and S-97-682 before shipping.
PART 3 - EXECUTION
3.1 INSTALLATION
A. Cables shall be installed for future CT type fault indicators at terminations. Fault indicators to be provided by Owner.
B. Install cables according to IEEE 576 and manufacturer's recommendation.
C. Pull Conductors: Do not exceed manufacturer's recommended maximum pulling tensions and sidewall pressure values.
1. Prior to pulling conductors through raceway mandrel at 80% and swab at 100% until clean.
2. Where necessary, use manufacturer-approved pulling compound or lubricant that will not deteriorate jacket or insulation.
COMMON WORK RESULTS FOR ELECTRICAL 260500 - 5
3. Use pulling means, including fish tape, cable, rope, and basket-weave cable grips that will not damage cables and raceways. Do not use rope hitches for pulling attachment to cable.
D. All HV underground feeders will include a ground conductor. The ground shall be minimum 4/0 copper and have 600 V insulation. The ground conductor shall be grounded at all manholes and transformer vaults.
E. Bend Radius: Maintain minimum bend radius as recommended by manufacturer. Where not indicated by manufacturer, use 12 times the outside diameter of the cable as the minimum bend radius.
F. Install exposed cables in vaults and manholes parallel and perpendicular to surfaces of exposed structural members and follow surface contours where possible.
G. Support cables according to Division 26 Section “Hangers and supports for Electrical Systems.
H. Install "buried-cable" warning tape 12 inches (305 mm) above duct bank..
I. In manholes, handholes, pull boxes, junction boxes, and cable vaults, train cables around walls by the longest route from entry to exit and support cables at intervals adequate to prevent sag.
1. All feeders entering a manhole shall ring the manhole a minimum of 360 degrees prior to terminating onto a switch or exiting the manhole.
2. Individually mount cables and support with hardware equivalent to:
a. ZSI, Inc. "Porce-A-Clamp" (or approved equal) cable clamps.
b. B-Line B409-XX (or approved equal) Shelf Bracket.
c. B-Line B822 or 823 End Cap (or approved equal).
J. Install cable splices at pull points and elsewhere as indicated; use standard kits. "T-body" splices are not allowed. All splices shall be made with the specified splice kits.
K. Install terminations at ends of conductors and seal multiconductor cable ends with standard kits.
L. Install separable insulated-connector components as follows:
1. Protective Cap: At each terminal junction, with one on each terminal to which no feeder is indicated to be connected.
2. Portable Feed-Through Accessory: Three.
3. Standoff Insulator: Three.
M. Arc Proofing: Unless otherwise indicated, arc proof medium-voltage cable in all manholes, vaults, and at locations not protected by conduit or termination materials. In addition to arc-proofing tape manufacturer's written instructions, apply arc proofing as follows:
1. Clean cable sheath.
2. Wrap metallic cable components with 10-mil (250-micrometer) pipe-wrapping tape.
3. Smooth surface contours with electrical insulation putty.
4. Individually wrap each conductor.
5. Apply arc-proofing tape in one half-lapped layer with coated side toward cable.
6. Band arc-proofing tape with 1-inch- (25-mm-) wide bands of half-lapped, adhesive, glass-cloth tape 2 inches (50 mm) o.c.
N. Install fault indicators on each phase where indicated.
COMMON WORK RESULTS FOR ELECTRICAL 260500 - 6
O. Ground shields of shielded cable at terminations, splices, and separable insulated connectors. Ground metal bodies of terminators, splices, cable and separable insulated-connector fittings, and hardware.
P. Identify cables according to Division 26 Section "Identification for Electrical Systems."
1. Conductors shall be color-coded by phase with 8” of half lapped colored tape:
a. Phase A: Black
b. Phase B: Red
c. Phase C: Blue
2. Color-coded taping shall occur at all terminations, manholes, pullboxes, and similar.
3. Feeder identification tags shall be provided for each cable, attached to phase B using a black weather resistant zip tie, in each manhole, transformer vault, and terminations.
4. Provide feeder tags per details and "Identification" section.
3.2 FIELD QUALITY CONTROL
A. Testing: Engage a qualified testing and inspecting agency to perform the following field tests and inspections and prepare test reports:
B. Perform the following field tests and inspections and prepare test reports:
1. Perform each visual and mechanical inspection and electrical test stated in
NETA ATS. Certify compliance with test parameters.
2. After installing medium-voltage cables and before electrical circuitry has been energized, test for compliance with requirements.
3. Testing will include hi-pot testing. Provide 2 week notice of hi-pot testing in writing to A/E and Owner to allow Owner to attend testing.
4. Hi-pot testing results shall be submitted to A/E and Owner for review prior to energizing cable.
C. Copies of all test reports shall be included in Owner O&M manuals.
D. Remove and replace malfunctioning units and retest as specified above.
END OF SECTION 260513
SECTION 260519
LOW-VOLTAGE ELECTRICAL POWER CONDUCTORS AND CABLES
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes the following:
1. Building wires and cables rated 600 V and less.
2. Connectors, splices, and terminations rated 600 V and less.
1.3 Related Sections include the following:
A. Division 26 Section "Medium-Voltage Cables" for single-conductor cables, cable splices, and terminations for electrical distribution systems with 2001 to 35,000 V.
1.4 SUBMITTALS
A. Not required.
1.5 QUALITY ASSURANCE
A. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use.
B. Comply with NFPA 70.
1.6 COORDINATION
A. MC Cable shall not be used unless specifically approved by Facilities Management electrical engineer(s) through the University Project Manager.
PART 2 - PRODUCTS
2.1 CONDUCTORS AND CABLES
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. American Insulated Wire Corp.; a Leviton Company.
2. General Cable Corporation.
3. Senator Wire & Cable Company.
4. Southwire Company.
B. Copper Conductors: Comply with NEMA WC 70.
C. Conductor Insulation: Comply with NEMA WC 70 for Types THHN-THWN-2, XHHW-2 CT rated, and SO.
D. Aluminum Conductors: Not permitted.
E. Cables installed in cable tray shall be rated for “Cable Tray” use, CT listed.
F. Multiconductor Cable: Type SO with ground wire.
2.2 CONNECTORS AND SPLICES
A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
1. AFC Cable Systems, Inc.
2. Hubbell Power Systems, Inc.
3. O-Z/Gedney; EGS Electrical Group LLC.
4. 3M; Electrical Products Division.
5. Tyco Electronics Corp.
B. Description: Factory-fabricated connectors and splices of size, ampacity rating, material, type, and class for application and service indicated.
PART 3 - EXECUTION
3.1 CONDUCTOR MATERIAL APPLICATIONS
A. Service and Feeders: Copper. All conductors No. 12 AWG and larger shall be stranded.
B. Branch Circuits: Copper. All conductors No. 12 AWG and larger shall be stranded.
3.2 CONDUCTOR INSULATION AND MULTICONDUCTOR CABLE APPLICATIONS AND WIRING
METHODS
A. Service Entrance: Type XHHW-2, single conductors in raceway.
B. Feeders: Type THHN-THWN-2, single conductors in raceway.
C. Branch Circuits: Type THHN-THWN-2, single conductors in raceway.
D. Multi-Wire Branch Circuits: Install no more than three circuits in a raceway, unless specifically shown otherwise.
E. Neutral Conductors: Provide one neutral conductor for each phase conductor. Shared neutral conductors are not allowed.
F. Minimum Branch Circuit Conductor Size: Provide the following minimum sizes for distances listed on 20A branch circuits to prevent excessive voltage drop. The circuit length shall be measured along the length of the conductor form the circuit breaker in the panelboard to the last device on the circuit. Increase raceway size to comply with conductor fill requirements of NFPA 70.
G. Upsizing of Conductors
1. Branch Circuit Voltage of 120V:
a. Circuit lengths less than 70 feet: Provide minimum #12 AWG conductor size.
b. Circuit lengths between 70 feet and 110 feet and/or where more than 3 current carrying conductors are installed in a single raceway: Provide minimum #10 AWG conductor size.
c. Circuit lengths between 110 feet and 170 feet: Provide minimum #8 AWG conductor size.
d. Circuit lengths greater than 170 feet: Perform voltage drop calculations and provide conductor size to keep branch circuit voltage drop less than 3% with a 15 amp load.
e.
2. Branch Circuit Voltage of 277V:
a. Circuit lengths less than 150 feet: Provide minimum #12 AWG conductor size.
b. Circuit lengths between 150 feet and 240 feet: Provide minimum #10 AWG conductor size.
c. All lighting circuits feeding site lighting: Provide minimum #8 AWG conductor size for all conductors including equipment ground.
d. Circuit lengths between 240 feet and 380 feet: Provide minimum #8 AWG conductor size.
e. Circuit lengths greater than 380 feet: Perform voltage drop calculations and provide conductor size to keep branch circuit voltage drop less than 3% with a 15 amp load
H. Cord Drops and Portable Appliance Connections: Type SO, hard service cord with stainless-steel, wire-mesh, strain relief device at terminations to suit application.
I. Class 1 Control Circuits: Type THHN-THWN-2, in raceway.
J. Class 2 Control Circuits: Type THHN-THWN-2, in raceway.
3.3 INSTALLATION OF CONDUCTORS AND CABLES
A. Install all conductors and cables in raceways per Division 26 Section, "Raceway and Boxes for Electrical Systems."
B. Conceal cables in finished walls, ceilings, and floors, unless otherwise indicated.
C. Use manufacturer-approved pulling compound or lubricant where necessary; compound used must not deteriorate conductor or insulation. Do not exceed manufacturer's recommended maximum pulling tensions and sidewall pressure values.
D. Use pulling means, including fish tape, cable, rope, and basket-weave wire/cable grips, that will not damage cables or raceway.
E. Install exposed cables parallel and perpendicular to surfaces of exposed structural members, and follow surface contours where possible. Paint to match conduits to surface in finished spaces.
F. Support cables according to Division 26 Section "Hangers and Supports for Electrical Systems."
G. Identify and color-code conductors and cables according to Division 26 Section "Identification for Electrical Systems."
3.4 CONNECTIONS
A. Tighten electrical connectors and terminals according to manufacturer's published torque-tightening values. If manufacturer's torque values are not indicated, use those specified in UL 486A.
B. Make splices and taps that are compatible with conductor material and that possess equivalent or better mechanical strength and insulation ratings than unspliced conductors.
1. Splices for No. 10 AWG and smaller shall be screw on type similar to Scotch or
Ideal wing nut connectors.
2. Crimp on splices designed to be used without wire stripping shall not be acceptable.
3. Use oxide inhibitor in each splice, termination, and tap for aluminum conductors.
C. Wiring at Outlets: Install conductor at each outlet, with at least 12 inches (300 mm) of slack.
3.5 FIELD QUALITY CONTROL
A. Perform tests and inspections and prepare test reports.
B. Tests and Inspections:
1. After installing conductors and cables and before electrical circuitry has been energized, test service entrance and feeder conductors.
2. Perform each visual and mechanical inspection and electrical test stated in NETA
Acceptance Testing Specification. Certify compliance with test parameters.
a.
C. Test Reports: Prepare a written report to record the following:
1. Test procedures used.
2. Test results that comply with requirements.
3. Test results that do not comply with requirements and corrective action taken to achieve compliance with requirements.
D. Remove and replace malfunctioning units and retest as specified above.
END OF SECTION 260519
SECTION 260526
GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. Section Includes: Grounding systems and equipment.
B. Section includes grounding systems and equipment, plus the following special applications:
1. Overhead-line grounding.
2. Underground distribution grounding.
3. Ground bonding common with lightning protection system.
1.3 SUBMITTALS
A. Field quality-control reports.
1.4 QUALITY ASSURANCE
A. Comply with NFPA 70 for grounding and bonding of electrical systems.
B. Comply with UL 467 for grounding and bonding materials and equipment.
C. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, by a qualified testing agency, and marked for intended location and application.
PART 2 - PRODUCTS
2.1 CONDUCTORS
A. Insulated Conductors: Copper wire or cable insulated for 600 V unless otherwise required by applicable Code or authorities having jurisdiction.
B. Bare Copper Conductors:
1. Solid Conductors: ASTM B 3.
2. Stranded Conductors: ASTM B 8.
3. Tinned Conductors: ASTM B 33.
4. Bonding Cable: 28 kcmil, 14 strands of No. 17 AWG conductor, 1/4 inch (6 mm) in diameter.
5. Bonding Conductor: No. 4 or No. 6 AWG, stranded conductor.
6. Bonding Jumper: Copper tape, braided conductors terminated with copper ferrules; 1-5/8 inches (41 mm) wide and 1/16 inch (1.6 mm) thick.
7. Tinned Bonding Jumper: Tinned-copper tape, braided conductors terminated with copper ferrules; 1-5/8 inches (41 mm) wide and 1/16 inch (1.6 mm) thick.
C. Grounding Bus: Predrilled rectangular bars of annealed copper, 1/4 by 4 inches (6.3 by 100 mm) in cross section, with 9/32-inch (7.14-mm) holes spaced 1-1/8 inches (28 mm) apart. Stand-off insulators for mounting shall comply with UL 891 for use in switchboards, 600 V. Lexan or PVC, impulse tested at 5000 V.
2.2 CONNECTORS
A. Listed and labeled by an NRTL acceptable to authorities having jurisdiction for applications in which used and for specific types, sizes, and combinations of conductors and other items connected.
B. Bolted Connectors for Conductors and Pipes: Copper or copper alloy, pressure type with at least two bolts.
1. Pipe Connectors: Clamp type, sized for pipe.
C. All lugs used in the building system shall be rated for copper only.
D. Welded Connectors: Exothermic-welding kits of types recommended by kit manufacturer for materials being joined and installation conditions.
E. Bus-bar Connectors: Mechanical type, cast silicon bronze, solderless compression-type wire terminals, and long-barrel, two-bolt connection to ground bus bar.
2.3 GROUNDING ELECTRODES
A. Ground Rods: Copper-clad steel; 3/4 inch by 10 feet (19 mm by 3 m) in diameter.
PART 3 - EXECUTION
3.1 APPLICATIONS
A. Conductors: Install solid conductor for No. 8 AWG and smaller, and stranded conductors for No. 6 AWG and larger unless otherwise indicated.
B. Underground Grounding Conductors: Install two bare tinned-copper conductors, No. 4/0 AWG minimum.
1. Bury at least 36 inches (900 mm) below grade.
2. Duct-Bank Grounding Conductor: Bury 12 inches (300 mm) above duct bank when indicated as part of duct-bank installation.
3. Terminate Grounds at manholes and building.
C. Isolated Grounding Conductors:
1. Green-colored insulation with continuous yellow stripe. On feeders with isolated ground, identify grounding conductor where visible to normal inspection, with alternating bands of green and yellow tape, with at least three bands of green and two bands of yellow.
D. Grounding Bus: Install in electrical and telephone equipment rooms, in rooms housing service equipment, and elsewhere as indicated.
1. Install bus on insulated spacers 2 inches (50 mm) minimum from wall, 6 inches
(150 mm) above finished floor unless otherwise indicated.
2. Where indicated on both sides of doorways, route bus up to top of door frame, across top of doorway, and down to specified height above floor; connect to horizontal bus.
E. Conductor Terminations and Connections:
1. Pipe and Equipment Grounding Conductor Terminations: Bolted connectors.
2. Underground Connections: Welded connectors except at test wells and as otherwise indicated.
3. Connections to Ground Rods at Test Wells: Bolted connectors.
4. Connections to Structural Steel: Welded connectors.
F. Conduits:
1. All metallic conduits shall be properly grounded and bonded.
2. For the following applications a separate code sized insulated ground conductor
(in addition to the equipment grounding conductor), shall be terminated to an insulated/isolated ground buss:
a. Conduits serving a 120/208V panels or other feeders.
3.2 GROUNDING AT THE SERVICE
A. Equipment grounding conductors and grounding electrode conductors shall be connected to the ground bus. Install a main bonding jumper between the neutral and ground buses.
3.3 GROUNDING SEPARATELY DERIVED SYSTEMS
A. Generator: Install grounding electrode(s) at the generator location. The electrode shall be connected to the equipment grounding conductor and to the frame of the generator.
3.4 GROUNDING UNDERGROUND DISTRIBUTION SYSTEM COMPONENTS
A. Comply with IEEE C2 grounding requirements.
B. Grounding Manholes and Handholes: Install two driven ground rods through manhole or handhole floor at opposite corners, close to wall, and set rod depth so 4 inches (100 mm) will extend above finished floor. If necessary, install ground rod before manhole is placed and provide No. 4/0 AWG bare, tinned-copper conductor from ground rod into manhole through a waterproof sleeve in manhole wall. Protect ground rods passing through concrete floor with a double wrapping of pressure-sensitive insulating tape or heat-shrunk insulating sleeve from 2 inches (50 mm) above to 6 inches (150 mm) below concrete.
Seal floor opening with waterproof, nonshrink grout. Install 4/0 bare copper conductor around entire manhole, ground all connections and ground rods to this conductor.
Ground the duct bank ground conductors to this ground ring as well.
C. Grounding Connections to Manhole Components: Bond exposed-metal parts such as inserts, cable racks, pulling irons, ladders, and cable shields within each manhole or handhole, to ground rod or grounding conductor. Make connections with No. 4 AWG minimum, stranded, hard-drawn copper bonding conductor. Train conductors level or plumb around corners and fasten to manhole walls. Connect to cable armor and cable shields according to written instructions by manufacturer of splicing and termination kits.
D. Pad-Mounted Transformers and Switches: Install two ground rods at each pad. Ground pad-mounted equipment and noncurrent-carrying metal items associated with substations by connecting them to underground duct bank grounding conductors, encased electrode conductors, re-enforcing rebar of equipment pad and other available grounding electrodes.
3.5 EQUIPMENT GROUNDING
A. Install insulated equipment grounding conductors with all feeders and branch circuits.
B. Air-Duct Equipment Circuits: Install insulated equipment grounding conductor to duct-mounted electrical devices operating at 120 V and more, including air cleaners, heaters, dampers, humidifiers, and other duct electrical equipment. Bond conductor to each unit and to air duct and connected metallic piping.
C. HVAC Metallic Duct and Pipe Bonding within secure areas: Bond all metallic ductwork and metallic piping within each secure area with #10CU ground and connect to the nearest available ground bus within the secure room.
D. Water Heater, Heat-Tracing, and Antifrost Heating Cables: Install a separate insulated equipment grounding conductor to each electric water heater and heat-tracing cable.
Bond conductor to heater units, piping, connected equipment, and components.
E. Isolated Grounding Receptacle Circuits: Install an insulated equipment grounding conductor connected to the receptacle grounding terminal. Isolate conductor from raceway and from panelboard grounding terminals. Terminate at equipment grounding conductor terminal of the applicable derived system or service unless otherwise indicated.
F. Poles Supporting Outdoor Lighting Fixtures: Install grounding electrode and a separate insulated equipment grounding conductor in addition to grounding conductor installed with branch-circuit conductors.
G. Isolated Equipment Enclosure Circuits: For designated equipment supplied by a branch circuit or feeder, isolate equipment enclosure from supply circuit raceway with a nonmetallic raceway fitting listed for the purpose. Install fitting where raceway enters enclosure, and install a separate insulated equipment grounding conductor. Isolate conductor from raceway and from panelboard grounding terminals. Terminate at equipment grounding conductor terminal of the applicable derived system or service unless otherwise indicated.
H. Signal and Communication Equipment: In addition to grounding and bonding required by NFPA 70, provide a separate grounding system complying with requirements in TIA/ATIS
J-STD-607-A.
1. For telephone, alarm, voice and data, and other communication equipment, provide No. 4 AWG minimum insulated grounding conductor in raceway from grounding electrode system to each service location, terminal cabinet, wiring closet, and central equipment location.
2. Service and Central Equipment Locations and Wiring Closets: Terminate grounding conductor on a 1/4-by-4-by-12-inch (6.3-by-100-by-300-mm) grounding bus.
3. Terminal Cabinets: Terminate grounding conductor on cabinet grounding terminal.
3.6 INSTALLATION
A. Branch Circuits:
1. Raceways used for single or multiple branch circuits shall include a code sized green insulated ground conductor.
2. Circuits used for isolated ground outlets shall be run in separate raceways; or, shall have a separate green insulated ground conductor installed and tagged with identification at all outlet and junction boxes.
B. Grounding Conductors: Route along shortest and straightest paths possible unless otherwise indicated or required by Code. Avoid obstructing access or placing conductors where they may be subjected to strain, impact, or damage.
C. Ground Bonding Common with Existing Lightning Protection System: Comply with NFPA 780 and UL 96 when interconnecting with lightning protection system. Bond electrical power system ground directly to lightning protection system grounding conductor at closest point to electrical service grounding electrode. Use bonding conductor sized same as system grounding electrode conductor, and install in conduit.
D. Ground Rods: Drive rods until tops are 2 inches (50 mm) below finished floor or final grade unless otherwise indicated.
1. Interconnect ground rods with grounding electrode conductor below grade and as otherwise indicated. Make connections without exposing steel or damaging coating if any.
2. For grounding electrode system, install at least three rods spaced at least one-rod length from each other and located at least the same distance from other grounding electrodes, and connect to the service grounding electrode conductor.
E. Bonding Straps and Jumpers: Install in locations accessible for inspection and maintenance except where routed through short lengths of conduit.
1. Bonding to Structure: Bond straps directly to basic structure, taking care not to penetrate any adjacent parts.
2. Bonding to Equipment Mounted on Vibration Isolation Hangers and Supports:
Install bonding so vibration is not transmitted to rigidly mounted equipment.
3. Use exothermic-welded connectors for outdoor locations; if a disconnect-type connection is required, use a bolted clamp.
F. Grounding and Bonding for Piping:
1. Metal Water Service Pipe: Install insulated copper grounding conductors, in conduit, from building's main service equipment, or grounding bus, to main metal water service entrances to building. Connect grounding conductors to main metal water service pipes; use a bolted clamp connector or bolt a lug-type connector to a pipe flange by using one of the lug bolts of the flange. Where a dielectric main water fitting is installed, connect grounding conductor on street side of fitting. Bond metal grounding conductor conduit or sleeve to conductor at each end.
2. Water Meter Piping: Use braided-type bonding jumpers to electrically bypass water meters. Connect to pipe with a bolted connector.
3. Bond each aboveground portion of gas piping system downstream from equipment shutoff valve.
G. Grounding for Steel Building Structure: Install a driven ground rod at base of each corner column and at intermediate exterior columns at distances not more than 60 feet (18 m) apart.
H. Bonding of Exposed Structural Metal: Bond all exposed structural metal that is not grounded to the service equipment enclosure. The points of attachment of the bonding jumpers shall be accessible.
I. Ufer Ground (Concrete-Encased Grounding Electrode): Fabricate according to NFPA 70;
use a minimum of 20 feet (6 m) of bare copper conductor not smaller than No. 2 AWG.
1. If concrete foundation is less than 20 feet (6 m) long, coil excess conductor within base of foundation.
2. Bond grounding conductor to reinforcing steel in at least four locations and to anchor bolts. Extend grounding conductor below grade and connect to building's grounding grid or to grounding electrode external to concrete.
3.7 LABELING
A. Comply with requirements in Division 26 Section "Identification for Electrical Systems" Article for instruction signs. The label or its text shall be green.
B. Install labels at the telecommunications bonding conductor and grounding equalizer and at the grounding electrode conductor where exposed.
1. Label Text: "If this connector or cable is loose or if it must be removed for any reason, notify the facility manager."
3.8 FIELD QUALITY CONTROL
A. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect, test, and adjust components, assemblies, and equipment installations, including connections.
B. Perform tests and inspections.
1. Manufacturer's Field Service: Engage a factory-authorized service representative to inspect components, assemblies, and equipment installations, including connections, and to assist in testing.
C. Tests and Inspections:
1. After installing grounding system but before permanent electrical circuits have been energized, test for compliance with requirements.
2. Inspect physical and mechanical condition. Verify tightness of accessible, bolted, electrical connections with a calibrated torque wrench according to manufacturer's written instructions.
3. Test completed grounding system at each location where a maximum ground-resistance level is specified, at service disconnect enclosure grounding terminal , and at individual ground rods. Make tests at ground rods before any conductors are connected.
a. Measure ground resistance no fewer than two full days after last trace of precipitation and without soil being moistened by any means other than natural drainage or seepage and without chemical treatment or other artificial means of reducing natural ground resistance.
b. Perform tests by fall-of-potential method according to IEEE 81.
4. Prepare dimensioned Drawings locating each test well, ground rod and ground-rod assembly, and other grounding electrodes. Identify each by letter in alphabetical order, and key to the record of tests and observations. Include the number of rods driven and their depth at each location, and include observations of weather and other phenomena that may affect test results. Describe measures taken to improve test results.
D. Grounding system will be considered defective if it does not pass tests and inspections.
E. Prepare test and inspection reports.
F. Report measured ground resistances that exceed the following values:
1. Power and Lighting Equipment or System with Capacity of 500 kVA and Less:
10 ohms.
2. Power and Lighting Equipment or System with Capacity of 500 to 1000 kVA: 5 ohms.
3. Power and Lighting Equipment or System with Capacity More Than 1000 kVA: 3 ohms.
4. Power Distribution Units or Panelboards Serving 120V or 208V equipment: 3 ohm(s).
5. Substations and Pad-Mounted Equipment: 5 ohms.
6. Manhole Grounds: 10 ohms.
G. Excessive Ground Resistance: If resistance to ground exceeds specified values, notify Architect promptly and include recommendations to reduce ground resistance.
COMMON WORK RESULTS FOR ELECTRICAL 260500 - 7
END OF SECTION 260526
SECTION 260529
HANGERS AND SUPPORTS FOR ELECTRICAL SYSTEMS
PART 1 - GENERAL
1.1 RELATED DOCUMENTS
A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
1.2 SUMMARY
A. This Section includes the following:
1. Hangers and supports for electrical equipment and systems.
2. Construction requirements for concrete bases.
B. Related Sections include the following:
1. Division 26 Section "Vibration And Seismic Controls For Electrical Systems" for products and installation requirements necessary for compliance with seismic criteria.
1.3 DEFINITIONS
A. EMT: Electrical metallic tubing.
B. IMC: Intermediate metal conduit.
C. RMC: Rigid metal conduit.
1.4 PERFORMANCE REQUIREMENTS
A. Delegated Design: Design supports for multiple raceways, including comprehensive engineering analysis by a qualified professional engineer, using performance requirements and design criteria indicated.
B. Design supports for multiple raceways capable of supporting combined weight of supported systems and its contents.
C. Design equipment supports capable of supporting combined operating weight of supported equipment and connected systems and components.
D. Rated Strength: Adequate in tension, shear, and pullout force to resist maximum loads calculated or imposed for this Project, with a minimum structural safety factor of five times the applied force.
1.5 SUBMITTALS
A. Product Data: For the following:
1. Steel slotted support systems.
B. Shop Drawings: Signed and sealed by a qualified professional engineer. Show fabrication and installation details and include calculations for the following:
1. Trapeze hangers. Include Product Data for components.
2. Steel slotted channel systems. Include Product Data for components.
3. Nonmetallic slotted channel systems. Include Product Data for components.
4. Equipment supports.
C. Welding certificates.
1.6 QUALITY ASSURANCE
A. Welding: Qualify procedures and personnel according to AWS D1.1/D1.1M, "Structural Welding Code - Steel."
B. Comply with NFPA 70.
1.7 COORDINATION
A. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases.
Concrete, reinforcement, and formwork requirements are specified in Division 03.
B. Coordinate installation of roof curbs, equipment supports, and roof penetrations. These items are specified in Division 07 Section "Roof Accessories."
PART 2 - PRODUCTS
2.1 SUPPORT, ANCHORAGE, AND ATTACHMENT COMPONENTS
A. Steel Slotted Support Systems: Comply with MFMA-4, factory-fabricated components for field assembly.
1. Manufacturers: Subject to compliance with requirements, provide products by one of the following:
a. Allied Tube & Conduit.
b. Cooper B-Line, Inc.; a division of Cooper Industries.
c. ERICO International Corporation.
d. GS Metals Corp.
e. Thomas & Betts Corporation.
f. Unistrut; Tyco International, Ltd.
g. Wesanco, Inc.
2. Metallic Coatings: Hot-dip galvanized after fabrication and applied according to
MFMA-4.
3. Nonmetallic Coatings: Manufacturer's standard PVC, polyurethane, or polyester coating applied according to MFMA-4.
4. Painted Coatings: Manufacturer's standard painted coating applied according to
MFMA-4.
5. Channel Dimensions: Selected for applicable load criteria.
B. Raceway and Cable Supports: As described in NECA 1 and NECA 101.
C. Conduit and Cable Support Devices: Steel hangers, clamps, and associated fittings, designed for types and sizes of raceway or cable to be supported.
D. Support for Conductors in Vertical Conduit: Factory-fabricated assembly consisting of threaded body and insulating wedging plug or plugs for non-armored electrical conductors or cables in riser conduits. Plugs shall have number, size, and shape of conductor gripping pieces as required to suit individual conductors or cables supported.
Body shall be malleable iron.
E. Structural Steel for Fabricated Supports and Restraints: ASTM A 36/A 36M, steel plates, shapes, and bars; black and galvanized.
F. Mounting, Anchoring, and Attachment Components: Items for fastening electrical items or their…
This is the start of the file's text. The full file is on GovTribe.