550-22-102 Specifications_v11 of 11.pdf
PDF 511 KB Posted
- Attached to
- Z1DA--Invitation for Bid 550-22-102-CON Upgrade Fire Protection and Emergency Notification
- Solicitation number
- 36C25223B0022
About this file
This document outlines specifications for upgrading the fire protection and emergency notification system at the Danville VA Medical Center in Danville, Illinois. The specifications call for upgrading the existing fire alarm system to an addressable fire alarm control panel that will divide the building into twenty smoke zones. The system must include a voice evacuation component with pre-recorded messages for each zone describing the floor, level and area. Programming requirements are specified to allow for future system expansion through adding or removing devices, zones, and text messages. Related federal contract opportunity number 36C25223B0022 through the Department of Veterans Affairs invites bids for the upgrade, identified as solicitation number 550-22-102-CON, with the Veterans Health Administration as the contracting agency.
View the file
Other files
Show all 28
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
10-11
28 31 00 - 27 system. The INPUT/OUTPUT matrix format shall be as shown in Appendix A to NFPA 72.
C. Furnish the services of a competent instructor for instructing personnel in the programming requirements necessary for system expansion. Such programming shall include addition or deletion of devices, zones, indicating circuits and printer/display text.
PART 4 - SCHEDULES
4.1 SMOKE ZONE DESCRIPTIONS:
A. Building 58 Zone LLA – Basement Business – “Basement”
B. Building 58 Zone 1A – First Floor Health Care – “First Floor West”
C. Building 58 Zone 1B – First Floor Health Care – “First Floor North”
D. Building 58 Zone 1C – First Floor Health Care – “First Floor East”
E. Building 58 Zone 2A – Second Floor Health Care – “Second Floor West”
F. Building 58 Zone 2B – Second Floor Health Care – “Second Floor East”
G. Building 58 Zone 3A – Third Floor Health Care – “Third Floor West”
H. Building 58 Zone 3B – Third Floor Health Care – “Third Floor East”
I. Building 58 Zone 4A – Fourth Floor Health Care – “Fourth Floor West”
J. Building 58 Zone 4B – Fourth Floor Health Care – “Fourth Floor East”
K. Building 58 Zone 5A – Fifth Floor Health Care – “Fifth Floor West”
L. Building 58 Zone 5B – Fifth Floor Health Care – “Fifth Floor East”
M. Building 58 Zone 6A – Attic Business – “Attic”
4.2 DIGITIZED VOICE MESSAGES:
A. Digitized voice messages shall be provided for each smoke zone of
Building 58. The messages shall be arranged with a 3 second alert tone, a message and a description of the fire alarm area (floor, level and smoke zone). A sample of such a message is as follows:
Alert Tone
Code Red
Second Floor, East Wing
Code Red
Second Floor, East Wing
Code Red
Second Floor, East Wing
4.3 LOCATION OF VOICE MESSAGES:
Upon receipt of an alarm signal from the building fire alarm system, the voice communication system shall automatically transmit a 3 second
Danville VA Medical Center 1900 E Main St, Danville, IL 61832
Upgrade Fire Protection T.O.
100% Construction Documents
12/14/2022
10-11
28 31 00 - 28 tone alert and a pre-recorded fire alarm message throughout the building.
- - END - -
Danville VA Medical Center 1900 E Main St, Danville, IL 61832
Upgrade Fire Protection T.O.
100% Construction Documents
12/14/2022