About this file

This document provides details for a federal solicitation seeking bids to upgrade fire protection and emergency notification systems. The solicitation number is 36C25223B0022 and is being issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 12 for project 550-22-102-CON. Interested vendors are invited to submit bids by the response date to provide drawings, installation, maintenance, and related services to improve fire safety equipment and emergency alerts at a VA medical center. The solicitation includes a 19MB PDF file with project drawings and specifications. Bids are due by the date listed to be considered for an award to be made thereafter to upgrade critical life safety systems for veterans receiving care at this VA facility.

View the file

Other files

File Type Posted
36C25223B0022 0003.docx DOCX document
Fire Detection and Alarm 28 31 00 - updated Spec1.pdf PDF
550-22-102 RFIs and Responses1.pdf PDF
General Requirements 01 00 00 - - updated Spec1.pdf PDF
Wage Determination 08-28-2023.pdf PDF
36C25223B0022 0002.docx DOCX document
Wage Determination 08-09-2023.pdf PDF
550-22-102 RFIs and Responses.pdf PDF
Fire Detection and Alarm 28 31 00 - updated Spec.pdf PDF
36C25223B0022 0001.docx DOCX document
Wage Determination 08-01-2023.pdf PDF
General Requirements 01 00 00 - - updated Spec.pdf PDF
550-22-102 SOW - synopsis - Updated POP.pdf PDF
Wage Determination 6-22-23.pdf PDF
550-22-102 Specifications_v9 of 11.pdf PDF
550-22-102 Specifications_v3 of 11.pdf PDF
550-22-102 Specifications_v7 of 11.pdf PDF
550-22-102 Specifications_v10 of 11.pdf PDF
550-22-102 Specifications_v6 of 11.pdf PDF
550-22-102 Specifications_v4 of 11.pdf PDF
36C25223B0022_3.docx DOCX document
550-22-102 Specifications_v5 of 11.pdf PDF
550-22-102 Specifications_v11 of 11.pdf PDF
Pre-Construction Checklist.pdf PDF
550-22-102 Specifications_v8 of 11.pdf PDF
550-22-102 Specifications_v2 of 11.pdf PDF
550-22-102 Specifications_v1 of 11.pdf PDF
550-22-102 SOW - synopsis.pdf PDF
Show all 28

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

AR

CH

T em pla te_

R1 9_ de tac he d.r vt 4/4

/20

3:

:54 P

M

58 & 98

DANVILLE VA MEDICAL CENTER

1900 E MAIN ST, DANVILLE, IL 61832

VAMC PROJECT #: 550-22-102

UPGRADE FIRE PROTECTION AND EMERGENCY NOTIFICATION

SHEET INDEXPROJECT SUMMARYAERIAL IMAGE

MR ZAM

00-GI001

COVER

1"

5' 3/3

2"

1' 1/1

6"

1' 1/3

2"

1' 1"

1"

1"

1"

1"

9" 6"

3"

3"

1' 1'-

6" 1'

6"

1 1 /2"

1'

2' 1'

6"

1"

1' 3'

2' 1'

3/4

1'

4' 2'

1'

1/2

1' 6'

4' 2'

3/8

1'

8' 4'

3/1

6"

1' 8'

4' 2'

1/4

1'

8' 4'

1/8

1'

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:

10987654321

10987654321

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

3/3 0/2

2 2

:41 :45

P M

1900 E MAIN ST, DANVILLE, IL 61832

550-22-102

VEG 22.02

UPGRADE FIRE PROTECTION AND

EMERGENCY NOTIFICATION

100% CONSTRUCTION

DOCUMENTS

12/14/2022

Sheet # Sheet Title

00-GI001 COVER

00-GI002 GENERAL INFORMATION AND ABBREVIATIONS

00-GI110 ICRA DIAGRAMS - BUILDING 58

00-GI111 ICRA DIAGRAMS - BUILDING 58

00-GI112 ICRA DIAGRAMS - BUILDING 98

00-GI113 ICRA DIAGRAMS - BUILDING 98

00-FA001 FIRE ALARM GENERAL NOTES AND LEGEND

00-FA002 FIRE ALARM SEQUENCE OF OPERATIONS

00-FA003 FIRE ALARM RISER DIAGRAMS

58-FD101 B58 - BASEMENT FIRE ALARM DEMOLITION PLAN - AREA A

58-FD102 B58 - BASEMENT FIRE ALARM DEMOLITION PLAN - AREAS B & C

58-FD103 B58 - FIRST FLOOR FIRE ALARM DEMOLITION PLAN - AREA A

58-FD104 B58 - FIRST FLOOR FIRE ALARM DEMOLITION PLAN - AREAS B & C

58-FD105 B58 - SECOND FLOOR FIRE ALARM DEMOLITION PLAN - AREA A

58-FD106 B58 - SECOND FLOOR FIRE ALARM DEMOLITION PLAN - AREAS B & C

58-FD107 B58 - THIRD FLOOR FIRE ALARM DEMOLITION PLAN - AREA A

58-FD108 B58 - THIRD FLOOR FIRE ALARM DEMOLITION PLAN - AREAS B & C

58-FD109 B58 - FOURTH FLOOR FIRE ALARM DEMOLITION PLAN - AREAS A & B

58-FD110 B58 - FIFTH FLOOR FIRE ALARM DEMOLITION PLAN - AREAS A & B

58-FD111 B58 - ATTIC FIRE ALARM DEMOLITION PLAN - AREAS A & B

98-FD101 B98 - BASEMENT FIRE ALARM DEMOLITION PLAN - AREA A

98-FD102 B98 - BASEMENT FIRE ALARM DEMOLITION PLAN - AREA B

98-FD103 B98 - FIRST FLOOR FIRE ALARM DEMOLITION PLAN - AREA A

98-FD104 B98 - FIRST FLOOR FIRE ALARM DEMOLITION PLAN - AREA B

98-FD105 B98 - SECOND FLOOR FIRE ALARM DEMOLITION PLAN - AREA A

98-FD106 B98 - SECOND FLOOR FIRE ALARM DEMOLITION PLAN - AREA B

98-FD107 B98 - THIRD FLOOR FIRE ALARM DEMOLITION PLAN - AREA A

98-FD108 B98 - THIRD FLOOR FIRE ALARM DEMOLITION PLAN - AREA B

98-FD109 B98 - ATTIC FIRE ALARM DEMOLITION PLAN

58-FA101 B58 - BASEMENT FIRE ALARM NEW WORK PLAN - AREA A

58-FA102 B58 - BASEMENT FIRE ALARM NEW WORK PLAN - AREAS B & C

58-FA103 B58 - FIRST FLOOR FIRE ALARM NEW WORK PLAN - AREA A

58-FA104 B58 - FIRST FLOOR FIRE ALARM NEW WORK PLAN - AREAS B & C

58-FA105 B58 - SECOND FLOOR FIRE ALARM NEW WORK PLAN - AREA A

58-FA106 B58 - SECOND FLOOR FIRE ALARM NEW WORK PLAN - AREAS B & C

58-FA107 B58 - THIRD FLOOR FIRE ALARM NEW WORK PLAN - AREA A

58-FA108 B58 - THIRD FLOOR FIRE ALARM NEW WORK PLAN - AREAS B & C

58-FA109 B58 - FOURTH FLOOR FIRE ALARM NEW WORK PLAN - AREAS A & B

58-FA110 B58 - FIFTH FLOOR FIRE ALARM NEW WORK PLAN - AREAS A & B

58-FA111 B58 - ATTIC FIRE ALARM NEW WORK PLAN - AREAS A & B

98-FA101 B98 - BASEMENT FIRE ALARM NEW WORK PLAN - AREA A

98-FA102 B98 - BASEMENT FIRE ALARM NEW WORK PLAN - AREA B

98-FA103 B98 - FIRST FLOOR FIRE ALARM NEW WORK PLAN - AREA A

98-FA104 B98 - FIRST FLOOR FIRE ALARM NEW WORK PLAN - AREA B

98-FA105 B98 - SECOND FLOOR FIRE ALARM NEW WORK PLAN - AREA A

98-FA106 B98 - SECOND FLOOR FIRE ALARM NEW WORK PLAN - AREA B

98-FA107 B98 - THIRD FLOOR FIRE ALARM NEW WORK PLAN - AREA A

98-FA108 B98 - THIRD FLOOR FIRE ALARM NEW WORK PLAN - AREA B

98-FA109 B98 - ATTIC FIRE ALARM NEW WORK PLAN

00-E-001 ELECTRICAL NOTES

00-E-002 ELECTRICAL PLAN - FIRE ALARM RISER CIRCUITING

58-E-101 B58 - BASEMENT ELECTRICAL PLAN - AREA A

58-E-102 B58 - FIRST FLOOR ELECTRICAL PLAN - AREA A

98-E-101 B98 - BASEMENT ELECTRICAL PLAN - AREA B

98-E-102 B98 - FIRST FLOOR ELECTRICAL PLAN - AREA A

MRohall Snapshot

MRohall Snapshot

ZMiller Image

A. CONTRACTORS AND THEIR SUPERVISORY PERSONNEL SHALL REVIEW THE GENERAL AND

SUPPLEMENTARY CONDITIONS TO THE CONTRACT.

B. WORK SHALL CONFORM WITH PROJECT SPECIFICATIONS.

C. CONTRACTOR SHALL BECOME FULLY ACQUAINTED WITH CONDITIONS RELATED TO THE WORK.

QUESTIONS WILL BE DIRECTED TO VHA COR.

D. CONTRACTOR WILL BE SOLELY RESPONSIBLE FOR THE MEANS, METHODS AND SEQUENCES OF

CONSTRUCTION AND THE SAFETY OF CONSTRUCTION PERSONNEL AND VISITORS.

E. DRAWINGS CONTAINED IN THIS SET SHALL NOT BE REPRODUCED FOR SHOP DRAWINGS. COPIES OF

THESE DRAWINGS SUBMITTED AS SHOP DRAWINGS WILL BE REJECTED AND RETURNED TO THE

CONTRACTOR. REFER TO SPECIFICATION SECTION 01 33 23.

F. EACH CONTRACTOR AND SUBCONTRACTOR WILL EXAMINE SUBSTRATE AND/OR CONDITIONS UNDER WHICH THE WORK WILL BE INSTALLED AND REPORT TO THE CONTRACTOR, IN WRITING, CONDITIONS DETRIMENTAL TO THE PROPER AND TIMELY EXECUTION OF THEIR WORK. DO NOT PROCEED UNTIL

UNSATISFACTORY CONDITIONS ARE CORRECTED. COMMENCING WITH INSTALLATION WILL

CONSTITUTE ACCEPTANCE OF THE SUBSTRATE AND/OR CONDITIONS.

G. DO NOT SCALE DRAWINGS: FOLLOW WRITTEN DIMENSIONS AND NOTES. CONTACT VHA COR FOR

CLARIFICATIONS, IF REQUIRED.

H. "TYPICAL", AS USED IN THESE DOCUMENTS, MEANS THAT THE CONDITION OR DIMENSION IS

REPRESENTATIVE OF, OR THE SAME, FOR SIMILAR CONDITIONS THROUGHOUT.

I. IF THERE IS A DISCREPANCY BETWEEN SMALL SCALE AND LARGE SCALE DRAWINGS, (PLAN, SECTION, & DETAIL DRAWINGS, ETC), CONTACT VHA COR FOR CLARIFICATION.

J. IF THERE IS A DISCREPANCY BETWEEN THE DRAWINGS AND THE SPECIFICATIONS, SPECIFICATIONS

GOVERN. CONTACT VHA COR FOR CLARIFICATION.

K. DISCREPANCIES BETWEEN THE DRAWINGS AND ACTUAL CONDITIONS SHALL BE REPORTED TO THE

VHA COR, IN WRITING, FOR RESOLUTION PRIOR TO PROCEEDING WITH THE WORK.

L. DISCREPANCIES SHALL BE REPORTED TO THE VHA COR IN WRITING FOR RESOLUTION, PRIOR TO PROCEEDING WITH THE WORK. NO CHANGE ORDERS OR EXTENSIONS OF TIME WILL BE ALLOWED OR

ACCEPTED FOR PROCEEDING WITH THE WORK WITHOUT THE CONTRACTING OFFICER'S WRITTEN

DIRECTION AND APPROVAL. ALSO, CONTRACTOR SHALL REPAIR AND/OR REPLACE UNAUTHORIZED

WORK, AS INDICATED BY THE VHA COR, AT NO ADDITIONAL COST TO THE VHA.

M. DISSIMILAR METAL MATERIALS SHALL BE ISOLATED WITH AN APPROVED NONMETAL ISOLATION

MATERIAL IN ACCORDANCE WITH SPECIFICATIONS.

N. EXTERIOR EXPOSED STEEL SHALL BE PAINTED PER SPECIFICATION SECTION 09 91 00.

O. CONTRACTOR SHALL VERIFY THE LOCATIONS OF EXISTING UNDERGROUND UTILITIES AND THEIR SERVICE CONNECTIONS WITH THE PROPER UTILITY COMPANY, COORDINATE ISSUES WITH VHA COR.

P. CONTRACTOR SHALL COORDINATE SIZE, LOCATIONS AND NUMBER OF ROOF OPENINGS AND ROOF

ACCESSORIES WITH OTHER TRADES. REFER TO THE ARCHITECTURAL, STRUCTURAL, PLUMBING,

MECHANICAL AND ELECTRICAL DRAWINGS FOR REFERENCE AND SPECIFICATIONS FOR

REQUIREMENTS.

Q. LOCATIONS AND SIZES OF CONCRETE MECHANICAL AND ELECTRICAL EQUIPMENT PADS SHALL BE

COORDINATED BY THE MECHANICAL AND ELECTRICAL CONTRACTORS WITH THE SELECTED

EQUIPMENT MANUFACTURER AND/OR SUPPLIER. LOCATIONS ARE TO BE APPROVED BY THE VHA COR

PRIOR TO PROCEEDING WITH THE WORK.

R. PROVIDE INDEPENDENT FRAMING AND ATTACHMENTS TO THE STRUCTURE, ADEQUATE TO SUPPORT THE CEILING SYSTEM, LIGHT FIXTURES, DUCTS, DIFFUSERS, SPRINKLER PIPING AND BUS DUCTS.

S. CONTRACTOR TO INSTALL WOOD BLOCKING AND PLYWOOD AS REQUIRED FOR THE MOUNTING OF

TOILET ACCESSORIES, MILLWORK, CASEWORK, AV EQUIPMENT, MEP ITEMS AND RADIOLOGY

EQUIPMENT, ETC. REFER TO SPECIFICATIONS.

T. PROPRIETARY PRODUCTS IN THE DRAWINGS SHALL MEET SPECIFICATION REQUIREMENTS.

A

ROOM NAME

P2

RB3

C

SECTION, DETAIL, OR ELEVATION TITLE EXAMPLE

ELEVATION CALLOUT EXAMPLE

DETAIL CALLOUT EXAMPLE

SECTION CALLOUT EXAMPLE

SECTION, DETAIL, OR ELEVATION

SYMBOL IDENTIFIERS

DETAIL NAME

LETTER OR NUMBER DESIGNATOR

DRAWING SEQUENCE NUMBER

INDICATES WHERE TITLE IS LOCATED

ONE OR TWO CHARACTER

DISCIPLINE DESIGNATOR (MAY

NOT BE PRESENT IF CALLOUT

AND TITLE ARE ON DRAWINGS

WITHIN THE SAME DISCIPLINE)

AE101

DOOR NUMBER TAG

WALL TYPE TAG

WINDOW TYPE TAG

CENTER LINE

WALL FINISH TAG

COLUMN BUBBLE

ROOM TAG

WALL COLOR

BASE TYPE / COLOR

MATCH LINE

DETAIL NUMBER

ON SHEET

SHEET NUMBER

DETAIL NUMBER ON SHEET

SHEET NUMBER

NEW LINE TYPE

EXISTING LINE TYPE

DEMO LINE TYPE

DEMO HATCH TYPE

1 View Name 1/8" = 1'-0"

AE101

AE101

A A101

FLOOR PLAN SYMBOLS LEGEND

EARTH / COMPACT FILL

GRAVEL / GRANULAR FILL

CONCRETE

SAND/ MORTAR/

PLASTER/ CUT STONE

BRICK

CONCRETE MASONRY UNIT

STONE (ELEVATION)

BATT INSULATION

ROOF INSULATION

RIGID INSULATION

ACOUSTICAL TILE (SECTION)

GYPSUM BOARD

COVER BOARD

STEEL / METAL

FINISH WOOD

CONT WOOD BLOCKING /

ROUGH FRAMING

CAST STONE

DISCONTINUOUS

WOOD BLOCKING /

SHIM

PLYWOOD

MASONRY INSULATION

FIREPROOFING

EIFS (SECTION)

METAL / WALL PANELS

SPANDREL

GLASS

MATERIALS LEGEND

1 HOUR FIRE NEW

2 HOUR FIRE NEW

1 HOUR FIRE EXISTING

2 HOUR FIRE EXISTING

0 HOUR SMOKE PARTITION NEW

0.5 HOUR SMOKE NEW

1 HOUR FIRE/SMOKE NEW

2 HOUR FIRE/SMOKE NEW

SMOKE EXISTING

0.5 HOUR SMOKE EXISTING

1 HOUR FIRE/SMOKE EXISTING

2 HOUR FIRE/SMOKE EXISTING

C:

\U se rs\

VA

A rch ite ct

\D oc um en ts\ Re vit

\19

.25 _A

RC

H_

R2 2_ zm ille r4

NR

TZ

.rv t 4/1

3/2

2 7 :06

:51 A

M

GENERAL NOTESGENERAL ABBREVIATIONS

A

ABA ARCHITECTURAL BARRIERS ACT

AC AIR CONDITIONING

AD AREA DRAIN

ADJ ADJUSTABLE / ADJACENT

AFF ABOVE FINISH FLOOR

AHU AIR HANDLING UNIT

ALT ALTERNATE

ALUM ALUMINUM

ANOD ANODIZED

AP ACCESS PANEL

APPROX APPROXIMATE

ARCH ARCHITECT / ARCHITECTURAL

ATTEN ATTENUATION

AUTO AUTOMATIC

AV AUDIO / VISUAL

AVG AVERAGE

B

BD BOARD

BLDG BUILDING

BM BENCH MARK / BEAM

BO BOTTOM OF

BOC BACK OF CURB

BOT BOTTOM

BRG BEARING

BRK BRICK

BRKT BRACKET

BSMT BASEMENT

BTWN BETWEEN

BVL BEVELED

C

CAP CAPACITY

CB CATCH BASIN

CCTV CLOSED CIRCUIT TV

CF CUBIC FEET

CFM CUBIC FEET PER MINUTE

CI CAST IRON

CIP CAST-IN-PLACE

CL CENTER LINE

CLG CEILING

CLR CLEAR / CLEARANCE

CMP CORRUGATED METAL PIPE

CMU CONCRETE MASONRY UNIT

CO CLEAN OUT

COL COLUMN

COMB COMBINATION

CONC CONCRETE

CONN CONNECTION / CONNECT

CONST CONSTRUCT / CONSTRUCTION

CONT CONTINUOUS

CONTR CONTRACTOR

COORD COORDINATE

COR CONTRACTING OFFICER'S

REPRESENTATIVE

CORR CORRIDOR / CORRUGATED

CP CONCRETE PIPE

CS COUNTERSINK

CU CUBIC

CW COLD WATER

D

DBL DOUBLE

DEMO DEMOLISH / DEMOLITION

DEPT DEPARTMENT

DF DRINKING FOUNTAIN

DIA DIAMETER

DIAG DIAGONAL

DIM DIMENSION

DN DOWN

DR DOOR

DTL DETAIL

DWG DRAWING

E

E EAST

EA EACH

ABBREVIATIONS LISTED BELOW ARE GENERAL ABBREVIATIONS ACROSS ALL DISCIPLINES. DISCIPLINE SPECIFIC ABBREVIATIONS MAY SUPERSEDE GENERAL ABBREVIATIONS. REFER TO DISCIPLINE SPECIFIC ABBREVIATIONS SHEETS.

EF EXHAUST FAN

EL ELEVATION

ELEC ELECTRICAL

ELEV ELEVATOR

EM EMERGENCY

EP ELECTRICAL PANELBOARD

EQ EQUAL

EQUIP EQUIPMENT

EST ESTIMATE

ETR EXISTING TO REMAIN

EW EACH WAY

EWC ELECTRIC WATER COOLER

EXH EXHAUST

EXIST EXISTING

EXT EXTERIOR

F

FA FIRE ALARM

FB FACE BRICK

FBO FURNISHED BY OWNER

FD FLOOR DRAIN

FDC FIRE DEPARTMENT CONNECTION

FDN FOUNDATION

FF FINISH FLOOR

FF&E FIXTURES, FURNITURE & EQUIPMENT

FFE FINISH FLOOR ELEVATION

FH FIRE HYDRANT

FHC FIRE HOSE CABINET

FIXT FIXTURE

FLR FLOOR

FLUOR FLUORESCENT

FOC FACE OF CONCRETE

FOM FACE OF MASONRY

FR FIRE RATED

FRMG FRAMING

FS FLOOR SINK

FT FOOT/ FEET

FTG FOOTING

FUT FUTURE

G

GA GAUGE

GALV GALVANIZED

GC GENERAL CONTRACTOR

GOVT GOVERNMENT

GPM GALLON PER MINUTE

H

H HIGH

HB HOSE BIBB

HC HOLLOW CORE

HORIZ HORIZONTAL

HR HOUR

HS HIGH STRENGTH

HT HEIGHT

HTG HEATING

HTR HEATER

HVAC HEATING / VENTILATING / AIR

CONDITIONING

HW HOT WATER

HYD HYDRANT

I

IBC INTERNATIONAL BUILDING CODE

ID INSIDE DIAMETER

IN INCH

INCL INCLUDE (D), (ING)

INFO INFORMATION

INST INSTALL / INSTALLATION

INSUL INSULATE / INSULATION

INT INTERIOR

INV INVERT

J

JAN JANITOR

JB JUNCTION BOX

JST JOIST

JT JOINT

K

KIT KITCHEN

KO KNOCKOUT

L

L LONG / LENGTH

LAB LABORATORY

LAV LAVATORY

LBS POUNDS

LF LINEAR FOOT (FEET)

LH LEFT HAND

LLH LONG LEG HORIZONTAL

LLV LONG LEG VERTICAL

LPT LOW POINT

LRG LARGE

LT LIGHT

LTG LIGHTING

LVR LOUVER

LWC LIGHTWEIGHT CONCRETE

M

MAS MASONRY

MAX MAXIMUM

MBR MEMBER

MECH MECHANICAL

MED MEDIUM

MFG MANUFACTURING

MFR MANUFACTURER

MH MANHOLE

MIN MINIMUM

MISC MISCELLANEOUS

MOD MODULAR

MTD MOUNTED

MTG MOUNTING

MTL METAL

N

N NORTH

NA NOT APPLICABLE

NIC NOT IN CONTRACT

NO NUMBER

NOM NOMINAL

NSF NET SQUARE FEET

NTS NOT TO SCALE

O

OA OVERALL

OC ON CENTER

OD OUTSIDE DIAMETER

OH OVERHEAD / OPPOSITE HAND

OPNG OPENING

OPP OPPOSITE

OPR OPERABLE

ORD OVERFLOW ROOF DRAIN

OZ OUNCE

P

PA PUBLIC ADDRESS

PB PUSH BUTTON

PC PRECAST CONCRETE

PCF POUNDS PER CUBIC FOOT

PERF PERFORATE (D)

PERM PERMANENT

PERP PERPENDICULAR

PL PLATE / PROPERTY LINE

PLUMB PLUMBING

PNL PANEL

PR PAIR

PREFAB PREFABRICATE (D)

PREFIN PREFINISHED

PRELIM PRELIMINARY

PREP PREPARE (D)

PROJ PROJECT

PSF POUNDS PER SQUARE FOOT

PSI POUNDS PER SQUARE INCH

PVC POLYVINYL CHLORIDE

PVG PAVING

Q

QTY QUANTITY

R

R RISER / RADIUS

RA RETURN AIR

RCP REFLECTED CEILING PLAN

RD ROOF DRAIN

REINF REINFORCE (D), (ING)

REQD REQUIRED

REV REVISED/ REVISION

RH RIGHT HAND

RM ROOM

ROW RIGHT OF WAY

RR RESTROOM

RTU ROOF TOP UNIT

S

S SOUTH

SAN SANITARY SEWER

SCH SCHEDULE

SCRN SCREEN

SECT SECTION

SF SQUARE FOOT (SQFT)

SHT SHEET

SIM SIMILAR

SOG SLAB ON GRADE

SPEC SPECIFICATION (S)

SPKLR SPRINKLE

SPKR SPEAKER

SQ SQUARE

SS STAINLESS STEEL

STD STANDARD

STL STEEL

STOR STORAGE

STRUCT STRUCTURE / STRUCTURAL

SUSP SUSPENDED

SY SQUARE YARD (SQ YD)

SYM SYMMETRICAL / SYMBOL

SYS SYSTEM

T

TEL TELEPHONE

TEMP TEMPORARY / TEMPERED

THK THICK (NESS)

THRU THROUGH

TO TOP OF

TOC TOP OF CURB / CONCRETE

TOD TOP OF DECK

TOM TOP OF MASONRY

TOP TOP OF PARAPET

TOR TOP OF ROOF

TOS TOP OF STEEL

TOW TOP OF WALL

TRANSF TRANSFORMER

TV TELEVISION

TYP TYPICAL

U

UH UNIT HEATER

UNO UNLESS NOTED OTHERWISE

V

VERT VERTICAL

VEST VESTIBULE

VHA VETERANS HEALTH ADMINISTRATION

VIF VERIFY IN FIELD

VTR VENT THROUGH ROOF

W

W WEST, WIDTH, WIDE

W/ WITH

W/IN WITHIN

W/O WITHOUT

WC WATER CLOSET

WH WALL HYDRANT / WATER HEATER

WT WEIGHT

X, Y, Z, MISC

& AND

@ AT

YD YARD

MR ZAM

00-GI002

GENERAL INFORMATION AND

ABBREVIATIONS 58 & 98

7'- 6"

5'

1"

5'

5'

3/3

2"

1'

8'

1/1

6"

1'

1/3 2"

1'

1"

1"

1"

0'

1"

1"

9" 6"

3"

3"

1' 1'-

6" 1'

6"

1 1 /2"

1'

2' 1'

6"

1"

1' 3'

2' 1'

3/4

1'

4' 2'

1'

1/2

1' 6'

4' 2'

3/8

1'

8' 4'

3/1

6"

1' 8'

4' 2'

1/4

1'

8' 4'

1/8

1'

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

3/3 0/2

2 2

:41 :45

P M

1900 E MAIN ST, DANVILLE, IL 61832

550-22-102

VEG 22.02

UPGRADE FIRE PROTECTION AND

EMERGENCY NOTIFICATION

100% CONSTRUCTION

DOCUMENTS

12/14/2022

ZMiller Image

PIPE BASEMENT

PIPE BASEMENT

UP UP

DN DN

DOCK

136A

FHCFHC

CHART

EQUIP

ALCOVE

CHART CHART

EQUIP

ALCOVE ALCOVE

CHART

CHART

IP

HOLD

C:

\U se rs\

VA

A rch ite ct

\D oc um en ts\ Re vit

\19

.25 _A

RC

H_

R2 2_ zm ille r4

NR

TZ

.rv t 4/1

3/2

2 7 :06

:51 A

M

MR ZAM

00-GI110

ICRA DIAGRAMS - BUILDING 58

7'- 6"

5'

1"

5'

5'

3/3

2"

1'

8'

1/1

6"

1'

1/3 2"

1'

1"

1"

1"

0'

1"

1"

9" 6"

3"

3"

1' 1'-

6" 1'

6"

1 1 /2"

1'

2' 1'

6"

1"

1' 3'

2' 1'

3/4

1'

4' 2'

1'

1/2

1' 6'

4' 2'

3/8

1'

8' 4'

3/1

6"

1' 8'

4' 2'

1/4

1'

8' 4'

1/8

1'

KEY PLAN

GENERAL NOTES

Pl an

N or thTrue North

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

3/3 0/2

2 2

:41 :45

P M

1900 E MAIN ST, DANVILLE, IL 61832

550-22-102

VEG 22.02

UPGRADE FIRE PROTECTION AND

EMERGENCY NOTIFICATION

100% CONSTRUCTION

DOCUMENTS

12/14/2022

1/8" = 1'-0"

ICRA DIAGRAM - BUILDING 58 - BASEMENTF5

1/8" = 1'-0"

ICRA DIAGRAM - BUILDING 58 - FIRST FLOORC5

1/8" = 1'-0"

ICRA DIAGRAM - BUILDING 58 - SECOND FLOORF1

1/8" = 1'-0"

ICRA DIAGRAM - BUILDING 58 - THIRD FLOORC1

NO ICRA BARRIER

REQUIRED

CLASS II PRECAUTION

CLASS III PRECAUTION

CLASS III/IV PRECAUTION

LEGEND

A. ICRA PRECAUTION CLASSIFICATION IS BASED ON VALHALLA'S

UNDERSTANDING OF THE CURRENT USE OF SPACES AT THE TIME OF DESIGN.

VERIFY ALL CLASSIFICATIONS WITH THE VHA INFECTION CONTROL

SUPERVISOR PRIOR TO CONSTRUCTION.

B. AREAS SHOW WORST CASE CLASSIFICATION, LOWER PRECAUTION

CLASSIFICATION MAY BE USED WITHIN MARKED ARES WHEN APPROVED BY

THE VHA COR AND INFECTION CONTROL SUPERVISOR.

C. AT ANY CONNECTION BETWEEN DIFFERING PRECAUTION CLASSIFICATIONS,

PROVIDE BARRIERS IN COMPLIANCE WITH THE MORE RESTRICTIVE

CLASSIFICATION.

FOR

REFERENCE

ONLY

AutoCAD SHX Text

FHC

AutoCAD SHX Text

FHC

AutoCAD SHX Text

EP

AutoCAD SHX Text

FHC

AutoCAD SHX Text

EQUIP ALCOVE

AutoCAD SHX Text

CHART

AutoCAD SHX Text

EQUIP ALCOVE

F-1

P-1

P-2

MECHANICAL SPACE

C:

\U se rs\

VA

A rch ite ct

\D oc um en ts\ Re vit

\19

.25 _A

RC

H_

R2 2_ zm ille r4

NR

TZ

.rv t 4/1

3/2

2 7 :06

:51 A

M

MR ZAM

00-GI111

ICRA DIAGRAMS - BUILDING 58

7'- 6"

5'

1"

5'

5'

3/3

2"

1'

8'

1/1

6"

1'

1/3 2"

1'

1"

1"

1"

0'

1"

1"

9" 6"

3"

3"

1' 1'-

6" 1'

6"

1 1 /2"

1'

2' 1'

6"

1"

1' 3'

2' 1'

3/4

1'

4' 2'

1'

1/2

1' 6'

4' 2'

3/8

1'

8' 4'

3/1

6"

1' 8'

4' 2'

1/4

1'

8' 4'

1/8

1'

KEY PLAN

GENERAL NOTES

Pl an

N or thTrue North

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

3/3 0/2

2 2

:41 :45

P M

1900 E MAIN ST, DANVILLE, IL 61832

550-22-102

VEG 22.02

UPGRADE FIRE PROTECTION AND

EMERGENCY NOTIFICATION

100% CONSTRUCTION

DOCUMENTS

12/14/2022

1/8" = 1'-0"

ICRA DIAGRAM - BUILDING 58 - FOURTH FLOORF5

1/8" = 1'-0"

ICRA DIAGRAM - BUILDING 58 - FIFTH FLOORC5

1/8" = 1'-0"

ICRA DIAGRAM - BUILDING 58 - ATTICF1

NO ICRA BARRIER

REQUIRED

CLASS II PRECAUTION

CLASS III PRECAUTION

CLASS III/IV PRECAUTION

LEGEND

A. ICRA PRECAUTION CLASSIFICATION IS BASED ON VALHALLA'S

UNDERSTANDING OF THE CURRENT USE OF SPACES AT THE TIME OF DESIGN.

VERIFY ALL CLASSIFICATIONS WITH THE VHA INFECTION CONTROL

SUPERVISOR PRIOR TO CONSTRUCTION.

B. AREAS SHOW WORST CASE CLASSIFICATION, LOWER PRECAUTION

CLASSIFICATION MAY BE USED WITHIN MARKED ARES WHEN APPROVED BY

THE VHA COR AND INFECTION CONTROL SUPERVISOR.

C. AT ANY CONNECTION BETWEEN DIFFERING PRECAUTION CLASSIFICATIONS,

PROVIDE BARRIERS IN COMPLIANCE WITH THE MORE RESTRICTIVE

CLASSIFICATION.

FOR

REFERENCE

ONLY

UP

UPUP

UP

ELEV.

P-1

ELEV.

P-2

CRAWL

SPACE

UP

ANALYST 1

ANALYST 2

CODER 3

CODER 4

CODER 5

CODER 6

BB1

DOCK

STATION 3STATION 5

C:

\U se rs\

VA

A rch ite ct

\D oc um en ts\ Re vit

\19

.25 _A

RC

H_

R2 2_ zm ille r4

NR

TZ

.rv t 4/1

3/2

2 7 :06

:51 A

M

MR ZAM

00-GI112

ICRA DIAGRAMS - BUILDING 98

7'- 6"

5'

1"

5'

5'

3/3

2"

1'

8'

1/1

6"

1'

1/3 2"

1'

1"

1"

1"

0'

1"

1"

9" 6"

3"

3"

1' 1'-

6" 1'

6"

1 1 /2"

1'

2' 1'

6"

1"

1' 3'

2' 1'

3/4

1'

4' 2'

1'

1/2

1' 6'

4' 2'

3/8

1'

8' 4'

3/1

6"

1' 8'

4' 2'

1/4

1'

8' 4'

1/8

1'

KEY PLAN

GENERAL NOTES

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

3/3 0/2

2 2

:41 :45

P M

1900 E MAIN ST, DANVILLE, IL 61832

550-22-102

VEG 22.02

UPGRADE FIRE PROTECTION AND

EMERGENCY NOTIFICATION

Pl an

N or th

True North

100% CONSTRUCTION

DOCUMENTS

12/14/2022

1/8" = 1'-0"

ICRA DIAGRAM - BUILDING 98 - BASEMENTF3

1/8" = 1'-0"

ICRA DIAGRAM - BUILDING 98 - FIRST FLOORD3

NO ICRA BARRIER

REQUIRED

CLASS II PRECAUTION

CLASS III PRECAUTION

CLASS III/IV PRECAUTION

LEGEND

A. ICRA PRECAUTION CLASSIFICATION IS BASED ON VALHALLA'S

UNDERSTANDING OF THE CURRENT USE OF SPACES AT THE TIME OF DESIGN.

VERIFY ALL CLASSIFICATIONS WITH THE VHA INFECTION CONTROL

SUPERVISOR PRIOR TO CONSTRUCTION.

B. AREAS SHOW WORST CASE CLASSIFICATION, LOWER PRECAUTION

CLASSIFICATION MAY BE USED WITHIN MARKED ARES WHEN APPROVED BY

THE VHA COR AND INFECTION CONTROL SUPERVISOR.

C. AT ANY CONNECTION BETWEEN DIFFERING PRECAUTION CLASSIFICATIONS,

PROVIDE BARRIERS IN COMPLIANCE WITH THE MORE RESTRICTIVE

CLASSIFICATION.

FOR

C:

\U se rs\

VA

A rch ite ct

\D oc um en ts\ Re vit

\19

.25 _A

RC

H_

R2 2_ zm ille r4

NR

TZ

.rv t 4/1

3/2

2 7 :06

:51 A

M

MR ZAM

00-GI113

ICRA DIAGRAMS - BUILDING 98

7'- 6"

5'

1"

5'

5'

3/3

2"

1'

8'

1/1

6"

1'

1/3 2"

1'

1"

1"

1"

0'

1"

1"

9" 6"

3"

3"

1' 1'-

6" 1'

6"

1 1 /2"

1'

2' 1'

6"

1"

1' 3'

2' 1'

3/4

1'

4' 2'

1'

1/2

1' 6'

4' 2'

3/8

1'

8' 4'

3/1

6"

1' 8'

4' 2'

1/4

1'

8' 4'

1/8

1'

KEY PLAN

GENERAL NOTES

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

3/3 0/2

2 2

:41 :45

P M

1900 E MAIN ST, DANVILLE, IL 61832

550-22-102

VEG 22.02

UPGRADE FIRE PROTECTION AND

EMERGENCY NOTIFICATION

Pl an

N or th

True North

100% CONSTRUCTION

DOCUMENTS

12/14/2022

1/8" = 1'-0"

ICRA DIAGRAM - BUILDING 98 - SECOND FLOORF3

1/8" = 1'-0"

ICRA DIAGRAM - BUILDING 98 - THIRD FLOORD3

1/8" = 1'-0"

ICRA DIAGRAM - BUILDING 98 - ATTICF1

NO ICRA BARRIER

REQUIRED

CLASS II PRECAUTION

CLASS III PRECAUTION

CLASS III/IV PRECAUTION

LEGEND

A. ICRA PRECAUTION CLASSIFICATION IS BASED ON VALHALLA'S

UNDERSTANDING OF THE CURRENT USE OF SPACES AT THE TIME OF DESIGN.

VERIFY ALL CLASSIFICATIONS WITH THE VHA INFECTION CONTROL

SUPERVISOR PRIOR TO CONSTRUCTION.

B. AREAS SHOW WORST CASE CLASSIFICATION, LOWER PRECAUTION

CLASSIFICATION MAY BE USED WITHIN MARKED ARES WHEN APPROVED BY

THE VHA COR AND INFECTION CONTROL SUPERVISOR.

C. AT ANY CONNECTION BETWEEN DIFFERING PRECAUTION CLASSIFICATIONS,

PROVIDE BARRIERS IN COMPLIANCE WITH THE MORE RESTRICTIVE

CLASSIFICATION.

FOR

F

S

P

S

S

C

ANN

FACP

S

FIRE ALARM CONTROL PANEL, NEW

ANNUNCIATOR PANEL, NEW

NOTIFICATION APPLIANCE CIRCUIT POWER EXTENDER, NEW

AMPLIFIER, NEW

SMOKE DETECTOR, NEW

SUBSCRIPT E - DESIGNATED FOR ELEVATOR RECALL

HEAT DETECTOR, NEW

DUCT DETECTOR, NEW

MANUAL PULL STATION, NEW

STROBE ONLY (CEILING MOUNT), NEW

SPEAKER/STROBE (CEILING MOUNT), NEW

SPEAKER ONLY (WALL MOUNT), NEW

SPEAKER ONLY (CEILING MOUNT), NEW

HORN/STROBE (CEILING MOUNT), NEW

HORN ONLY (WALL MOUNT), NEW

ADDRESSABLE INPUT MODULE, NEW

ADDRESSABLE OUTPUT MODULE, NEW

GAS DETECTOR, CARBON MONOXIDE, NEW

DOOR HOLDER CONNECTION TO FIRE ALARM SYSTEM, NEW

C

C

AIM

AOM

CO

DH

NAC

AMP

F

P

VS

WF

ANN

FACP

FIRE ALARM CONTROL PANEL, TO BE DEMOLISHED

ANNUNCIATOR PANEL, TO BE DEMOLISHED

SMOKE DETECTOR, TO BE DEMOLISHED

HEAT DETECTOR, TO BE DEMOLISHED

DUCT DETECTOR, TO BE DEMOLISHED

MANUAL PULL STATION, TO BE DEMOLISHED

STROBE ONLY (WALL MOUNT), TO BE DEMOLISHED

HORN/STROBE (CEILING MOUNT), TO BE DEMOLISHED

HORN/STROBE (WALL MOUNT), TO BE DEMOLISHED

TAMPER SWITCH, EXISTING TO REMAIN

WATERFLOW SWITCH, EXISTING TO REMAIN

REMOTE INDICATOR LAMP, TO BE DEMOLISHED

ADDRESSABLE INPUT MODULE, TO BE DEMOLISHED

ADDRESSABLE OUTPUT MODULE, TO BE DEMOLISHED

DOOR HOLDER CONNECTION TO FIRE ALARM SYSTEM, EXISTING TO BE REMAIN

ELEVATOR CONTROLLER - EXISTING TO REMAIN

ELEVATOR SHUNT TRIP BREAKER - EXISTING TO REMAIN

C

AIM

AOM

DH

ELEV

SHNT

7'- 6"

5'

1"

5'

5'

3/3

2"

1'

8'

1/1

6"

1'

1/3 2"

1'

1"

1"

1"

0'

1"

1"

9" 6"

3"

3"

1' 1'-

6" 1'

6"

1 1 /2"

1'

2' 1'

6"

1"

1' 3'

2' 1'

3/4

1'

4' 2'

1'

1/2

1' 6'

4' 2'

3/8

1'

8' 4'

3/1

6"

1' 8'

4' 2'

1/4

1'

8' 4'

1/8

1'

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

3/3 0/2

2 2

:41 :45

P M

1900 E MAIN ST, DANVILLE, IL 61832

550-22-102100% CONSTRUCTION

VEG 22.02

UPGRADE FIRE PROTECTION AND

EMERGENCY NOTIFICATION

8171 MAPLE LAWN BLVD.

SUITE 320

FULTON, MD 20759

(301) 323-3599

WWW.COFFMAN.COM

DOCUMENTS

12/14/2022 ML MCP

00-FA001

FIRE ALARM GENERAL NOTES

SCOPE OF WORK

THE SCOPE OF WORK INCLUDES THE DESIGN AND INSTALLATION OF

NEW FIRE ALARM SYSTEM FOR BUILDINGS 58 AND 98 AT VETERANS

AFFAIRS (VA) MEDICAL CENTER IN DANVILLE, ILLINOIS. THE SCOPE OF

WORK INCLUDES THE INSTALLATION OF A COMPLETE FIRE ALARM

SYSTEM WITH VOICE EVACUATION FOR BUILDING 58 FEATURING STAFF

RESPONSE NOTIFICATION AND A HORN/STROBE TEMPORAL 3 GENERAL

EVACUATION ALARM SYSTEM FOR BUILDING 98. THE SYSTEM SHALL

CONSIST OF THE FOLLOWING: NEW FIRE ALARM CONTROL PANELS

(FACP), HEAT DETECTORS, HORN/STROBES (B98), SPEAKER/STROBES

(B58), STROBES, HORNS (B98), SPEAKERS (B58), AND ASSOCIATED

WIRING. THE SYSTEM SHALL BE DESIGNED, INSTALLED AND TESTED IN

ACCORDANCE WITH ALL APPLICABLE CODES, THE VA FIRE PROTECTION

DESIGN MANUAL AND ALL SPECIFICATIONS. THE NEW FIRE ALARM

CONTROL UNITS FOR BUILDING 58 AND 98 MUST BE INTEGRATED INTO

THE CAMPUS MASTER PANEL NETWORK TO ENABLE TO DISTRIBUTION OF

SIGNALS TO THE CENTRAL STATION. THIS CONNECTION INCLUDES THE

DEMOLITION OF EXISTING NETWORK WIRING AND ADDITION OF NEW

NETWORK WIRING.

THE NEW SYSTEM DOES NOT ANTICIPATE THE REUSE OF ANY

COMPONENTS OF THE EXISTING FIRE ALARM SYSTEM SUCH THAT A

BRAND NEW SYSTEM WILL BE INSTALLED. EXISTING CONDUIT AND

BOXES WILL NOT BE REUSED.

THE SYSTEM WILL BE DESIGNED AND INSTALLED TO BE PARALLEL TO

THE EXISTING FIRE ALARM SYSTEMS FOR EACH BUILDING SUCH THAT NO

IMPAIRMENT TO THE EXISTING SYSTEM IS ANTICIPATED. UPON

SUCCESSFUL INSTALLATION, TESTING AND APPROVAL OF THE NEW

SYSTEM, THE CONTRACTOR SHALL COMPLETELY DEMOLISH THE

EXISTING SYSTEM, IN ACCORDANCE WITH THE SPECIFICATIONS.

INCLUDED IN THE SCOPE OF WORK IS THE RECONNECTION OF THE

EXISTING BUILDING 212 FIRE ALARM EQUIPMENT BACK TO THE BUILDING

98 SYSTEM. ALL EXISTING EQUIPMENT AND WIRING IN BUILDING 212

SHALL BE REUSED AND SHALL BE RECONNECTED TO THE NEW BUILDING

98 PANEL. PER DISCUSSIONS WITH ONSITE STAFF, THE SIGNALING LINE

CIRCUIT RUNS FROM BUILDING 212 TO THE BUILDING 98 MAIN FIRE

ALARM CONTROL PANEL. THE CONTRACTOR IS RESPONSIBLE FOR

PROGRAMMING THE NEW BUILDING 98 FIRE ALARM SYSTEM TO MEET

THE CURRENT BUILDING 212 SEQUENCE OF OPERATIONS (IN ADDITION

TO ANY PROGRAMMING UNRELATED TO BUILDING 212). CONTRACTOR

SHALL UTILIZE THE EXISTING FIRE ALARM PROGRAM FOR BUILDING 212

AND INCLUDE IT IN THE NEW FIRE ALARM SYSTEM FOR BUILDING 98.

BUILDING 212 IS NOT DEPICTED IN THIS DRAWING PACKAGE.

APPLICABLE CODES

VA FIRE PROTECTION DESIGN MANUAL, EIGHTH EDITION, JUNE 2021

NFPA 1 FIRE CODE, 2021

NFPA 70 NATIONAL ELECTRICAL CODE, 2020

NFPA 72 NATIONAL FIRE ALARM CODE, 2019

NFPA 90A AIR-CONDITIONING AND VENTILATING SYSTEMS, 2018

NFPA 101 LIFE SAFETY CODE, 2021

GENERAL NOTES

THE AWARDED CONTRACTOR SHALL BE RESPONSIBLE FOR

PRODUCTION OF ALL DESIGN AND SUBMITTAL DOCUMENTS AND

OBTAINING ALL REQUIRED INFORMATION FOR APPROVALS.

ALL DRAWINGS ARE CONCEPTUAL ONLY AND ARE NOT INTENDED TO

BE USED FOR EXACT MEASURE OR FABRICATION. THE QUANTITY

AND LOCATION OF DEVICES/APPLIANCES SHALL INCLUDE, AT A

MINIMUM, THE LAYOUT SHOWN ON THESE DRAWINGS. THE

CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ADDITIONAL

DEVICES/APPLIANCES AS NECESSARY TO COMPLY WITH APPLICABLE

CODES, STATEMENT OF WORK, SPECIFICATIONS, AUDIBILITY, AND

INTELLIGIBILITY. THE CONTRACTOR SHALL COORDINATE THE

INSTALLATION OF SYSTEM COMPONENTS, WIRING AND CONDUIT

WITH ALL OTHER TRADES.

ALL COMPONENTS REQUIRED FOR A WORKING FIRE ALARM SYSTEM

ARE NOT SHOWN ON THESE CONCEPT DRAWINGS. THE

CONTRACTOR SHALL PROVIDE EQUIPMENT AS NECESSARY FOR A

FULLY OPERATIONAL SYSTEM THAT COMPLIES WITH ALL

APPLICABLE CODES, STATEMENT OF WORK, SPECIFICATIONS AND

MANUFACTURER'S REQUIREMENTS. WHERE SURVIVABILITY IS

REQUIRED FOR SYSTEMS EMPLOYING RELOCATION OR PARTIAL

EVACUATION, WIRING INSTALLED IN METAL RACEWAY WITHIN

BUILDINGS THAT ARE PROTECTED THROUGHOUT BY SPRINKLERS

ARE CONSIDERED TO MEET THE NFPA 72 REQUIREMENTS FOR

PATHWAY SURVIVABILITY AS A 2-HOUR PERFORMANCE

ALTERNATIVE THAT HAS BEEN APPROVED BY THE AUTHORITY

HAVING JURISDICTION (VA) AND IS PERMITTED FOR VOICE

COMMUNICATION SYSTEMS IN VA FACILITIES. WHERE SURVIVABILITY

IS REQUIRED AND WHERE FIRE EMERGENCY VOICE/ALARM

CONTROL EQUIPMENT, METAL JUNCTION BOXES, TERMINAL

CABINETS, AND POWER SUPPLIES ARE LOCATED IN A BUILDING

SPRINKLER PROTECTED THROUGHOUT IN ACCORDANCE WITH NFPA

13, AND WHERE THE CONTROL EQUIPMENT IS ALSO PROTECTED IN

ACCORDANCE WITH NFPA 72, 10.4.5, THEY ARE CONSIDERED

PROTECTED BY OTHER EQUIVALENT MEANS TO PROVIDE A 2-HOUR

FIRE RESISTANCE RATING APPROVED BY THE AUTHORITY HAVING

JURISDICTION (VA) MEETING THE REQUIREMENT OF NFPA 72 (2019),

24.4.8.6.6 (3).

THE FIRE ALARM SYSTEM DESIGN AND INSTALLATION SHALL BE IN

ACCORDANCE WITH NFPA 72, VA FIRE PROTECTION DESIGN MANUAL

AND ALL OTHER CODES LISTED ON THIS SHEET.

ALL FIRE ALARM EQUIPMENT SHALL BE INSTALLED PER PROJECT

SPECIFICATION AND THE MANUFACTURER'S INSTRUCTIONS.

THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL MEANS AND

METHODS OF JOB SAFETY. WORK SHALL BE PERFORMED IN

ACCORDANCE WITH ALL APPLICABLE CODES AND REGULATIONS.

VISIBLE AND AUDIBLE NOTIFICATION APPLIANCES SHALL BE

PROVIDED THROUGHOUT THE AREA INCLUDED IN THE SCOPE OF

WORK WHERE REQUIRED BY NFPA 72, AND VA FIRE PROTECTION

DESIGN MANUAL. CONTRACTOR TO CONFIRM CEILING TYPES AND

HEIGHTS IN THE LOCATIONS OF EQUIPMENT FROM THOSE SHOWN

ON APPROVED SHOP DRAWINGS. THE CONTRACTOR SHALL BE

RESPONSIBLE FOR RECTIFYING UNAUTHORIZED NONCOMPLIANT

CHANGES AT NO ADDITIONAL CHARGE TO THE OWNER.

CONTRACTOR TO DEMOLISH EXISTING FIRE ALARM EQUIPMENT,

CIRCUITS AND CONDUIT. DEVICE/APPLIANCE LOCATIONS SHOWN ON

THE DEMOLITION DRAWINGS ARE FOR CONVENIENCE ONLY AND

MAY NOT BE COMPLETE. CONTRACTOR SHOULD PERFORM AN

EXISTING CONDITIONS SURVEY TO ENSURE THAT ALL EXISTING

COMPONENTS ARE REMOVED UPON DEMOLITION OF THE SYSTEM.

IT SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR TO RETURN

ALL WIRES TO THE PANEL FREE OF OPENS, GROUNDS, SHORTS

AND/OR ANY OTHER CONDITION THAT MAY PREVENT THE PROPER

OPERATION OF THE FIRE ALARM SYSTEM.

NEW FIRE ALARM DEVICES MUST BE MARKED 'NOT IN SERVICE' UNTIL

THE NEW SYSTEM HAS BEEN TESTED AND ACCEPTED. AFTER THE

NEW SYSTEM IS ACCEPTED, EXISTING APPLIANCES MUST BE

MARKED 'NOT IN SERVICE' UNTIL REMOVED.

PENETRATIONS OF FLOORS AND RATED WALLS MUST BE

FIRESTOPPED BY THE END OF THE WORK SHIFT. IF THERE IS SOME

REASON NOT TO APPLY THE FINAL FIRESTOPPING MATERIAL,

TEMPORARY MATERIALS SUCH AS MINERAL WOOL SHOULD BE

UTILIZED IN THE INTERIM.

INSTALLATION NOTES

CIRCUITS SHALL MEET THE FOLLOWING REQUIREMENTS:

CLASS B SIGNALING LINE CIRCUITS

CLASS B NOTIFICATION APPLIANCE CIRCUITS (NAC)

CLASS B INITIATING DEVICE CIRCUITS (IDC)

CLASS X CIRCUIT BETWEEN PANELS

VISIBLE AND COMBINATION AUDIBLE/VISIBLE ALARM NOTIFICATION APPLIANCES

MOUNTED ON A WALL SHALL BE MOUNTED AT A MINIMUM OF 80 INCHES AND

MAXIMUM OF 96 INCHES ABOVE THE FINISHED FLOOR MEASURED TO THE

BOTTOM OF THE LENS, OR 6 INCHES BELOW THE CEILING MEASURED TO THE

TOP OF THE LENS (WHICH EVER IS LOWER). CEILING-MOUNTED APPLIANCES

MOUNTED IN FINISHED CEILINGS SHALL BE FLUSH TO THE CEILING. CEILING

APPLIANCES IN EXPOSED APPLICATIONS SHALL BE LOCATED ON THE CEILING

OR SUSPENDED BELOW ANY OBSTRUCTIONS.

AUDIBLE-ONLY APPLIANCES MOUNTED ON THE WALL SHALL BE MOUNTED AT A

IN THE GENERAL EVACUATION APPLICATION, AUDIBLE-ONLY APPLIANCES SHALL

BE TAPPED TO PROVIDE AT LEAST 15 DB ABOVE THE AVERAGE AMBIENT SOUND

LEVEL OR 5 DB ABOVE THE MAXIMUM SOUND LEVEL HAVING A DURATION OF AT

LEAST 60 SECONDS.

ALL FIRE ALARM DEVICES/APPLIANCES SHALL BE INSTALLED CENTER OF TILE IN

AREAS WITH 2' X 2' SUSPENDED CEILING TILES. DEVICES SHALL BE INSTALLED IN

QUARTER OR CENTER OF TILE IN AREAS WITH 2' X 4' SUSPENDED CEILING TILES.

ALL FIRE PROTECTION VALVES SHALL BE ELECTRICALLY SUPERVISED BY THE

FIRE ALARM SYSTEM. EACH VALVE SHALL BE INDIVIDUALLY MONITORED. ALL

CONTROL VALVES, WATERFLOW SWITCHES AND TAMPER SWITCH DEVICES

SHOULD BE EXISTING TO REMAIN. FIRE ALARM CONTRACTOR SHALL MAKE ALL

ELECTRICAL CONNECTIONS TO THE ABOVE DEVICES.

DUCT DETECTORS SHALL BE INSTALLED ON THE SUPPLY AND RETURN SIDES OF

THE AIR HANDLING EQUIPMENT WHERE REQUIRED BY NFPA 90A.

ALL INITIATING DEVICES SHALL BE FIELD LOCATED BASED UPON THE LOCATION

OF DIFFUSERS, LIGHTS, AND OTHER POTENTIAL OBSTRUCTIONS.

PROVIDE A PERMANENT LABEL FOR EACH WIRE/CIRCUIT (WITHIN ALL PANELS,

CABINETS AND JUNCTION BOXES) INDICATING IT'S APPLICATION/USE/SERVICE.

ALL WIRING, CABLES, BOXES, TROUGHS AND OTHER RELATED EQUIPMENT

SHALL COMPLY WITH THE NEC.

ALL PENETRATIONS OF FIRE RESISTANCE RATED BARRIERS, WALLS, AND

SHAFT/ASSEMBLIES SHALL BE DRILLED AND SEALED WITH AN APPROVED UL

FIRE-RATED THROUGH-PENETRATION ASSEMBLY. SEE ARCHITECTURAL AND

LIFE SAFETY PLANS FOR LOCATIONS OF SMOKE PARTITION AND FIRE BARRIER

WALLS. ALL PENETRATIONS IN FIRE RESISTANCE-RATED WALLS SHALL BE

FIRESTOPPED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS.

FIRE ALARM DEVICE LEGEND

58 AND 98

7'- 6"

5'

1"

5'

5'

3/3

2"

1'

8'

1/1

6"

1'

1/3 2"

1'

1"

1"

1"

0'

1"

1"

9" 6"

3"

3"

1' 1'-

6" 1'

6"

1 1 /2"

1'

2' 1'

6"

1"

1' 3'

2' 1'

3/4

1'

4' 2'

1'

1/2

1' 6'

4' 2'

3/8

1'

8' 4'

3/1

6"

1' 8'

4' 2'

1/4

1'

8' 4'

1/8

1'

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

3/3 0/2

2 2

:41 :45

P M

1900 E MAIN ST, DANVILLE, IL 61832

550-22-102100% CONSTRUCTION

VEG 22.02

UPGRADE FIRE PROTECTION AND

EMERGENCY NOTIFICATION

8171 MAPLE LAWN BLVD.

SUITE 320

FULTON, MD 20759

(301) 323-3599

WWW.COFFMAN.COM

DOCUMENTS

12/14/2022 ML MCP

00-FA002

FIRE ALARM SEQUENCE OF

OPERATIONS

1) THE SEQUENCE OF OPERATIONS OF THE FIRE ALARM SYSTEM

SHALL BE PROGRAMMED IN ACCORDANCE WITH THE SEQUENCE OF

OPERATIONS ON THIS SHEET AND THE REQUIREMENTS OF THE

SPECIFICATION AND THE VA DESIGN MANUAL.

2) CONTRACTOR SHALL CONFIRM SEQUENCE OF OPERATIONS AND

ALL REQUIRED PRE-RECORDED MESSAGES WITH THE

CONTRACTING OFFICER/RESIDENT ENGINEER OR DESIGNATED

ALTERNATE PRIOR TO PRODUCING SHOP DRAWINGS AND PRIOR TO

PROGRAMMING THE SYSTEM.

58 AND 98

GENERAL NOTES

NO SCALE

BUILDING 58 FIRE ALARM SEQUENCE OF OPERATIONSF1 NO SCALE

BUILDING 98 FIRE ALARM SEQUENCE OF OPERATIONSF6

LEVEL 5

ATTIC

LEVEL 4

LEVEL 3

LEVEL 2

LEVEL 1

BASEMENT LEVEL

FACP

S

P

S

F

S

P

S

F

S

P

F

S

P

VSWF

S

F

S

P

F

S

P

F

S

P

F

NAC

LLA SMOKE ZONE

1A SMOKE ZONE 1B SMOKE ZONE

2A SMOKE ZONE 2B SMOKE ZONE

3A SMOKE ZONE 3B SMOKE ZONE

4A SMOKE ZONE 4B SMOKE ZONE

5A SMOKE ZONE 5B SMOKE ZONE

6A SMOKE ZONE

NAC

NAC NAC

NAC NAC

NAC NAC

NAC NAC

NAC

S

S

1C SMOKE ZONE

S

S

S

S

S

S

S

S

S

S

AMP

S

NAC

EOLR

EOLR

EOLR EOLR

EOLR EOLR

EOLR

EOLR

EOLR

EOLR

EOLR

EOLR

EOLR

EOLR

EOLR

EOLR

EOLR

EOLR

EOLR

EOLR

EOLR

EOLR

EOLR

EOLR

EOLR

EOLR

AIMAIM

VSWF

AIMAIM

VSWF

AIMAIM

VSWF

AIMAIM

VSWF

AIMAIM

VSWF

AIMAIM

VSWF

AIMAIM

NEW CONNECTION TO CAMPUS

MASTER PANEL NETWORK

ELEV

AOMAIMAOM

SHNT

ELEV

AOMAIMAOM

SHNT

ATTIC

LEVEL 3

LEVEL 2

LEVEL 1

BASEMENT LEVEL

FACP

S

P

S

F

S

P

F

S

P

F

NAC

NAC

NAC

NAC EOLR

EOLR

EOLR

EOLR

EOLR

EOLR

EOLR

EOLR

NEW CONNECTION TO

CAMPUS MASTER

PANEL NETWORK

VSWF

AIMAIM

VSWF

AIMAIM

VSWF

AIMAIM

S

P

S

F

NAC

EOLR

EOLR

VSWF

AIMAIM

S

P

F

VSWF

AIMAIM

ELEV

AOMAIMAOM

SHNT

FIRE ALARM CONTROL PANEL

BATTERY CABINET (IF REQUIRED)

BLOCKING AND

ATTACHMENT PER

MANUFACTURER'S

RECOMMENDATIONS

FIRE ALARM CONTROL PANEL

BATTERY CABINET (IF REQUIRED)

BLOCKING AND

ATTACHMENT PER

MANUFACTURER'S

RECOMMENDATIONS

7'- 6"

5'

1"

5'

5'

3/3

2"

1'

8'

1/1

6"

1'

1/3 2"

1'

1"

1"

1"

0'

1"

1"

9" 6"

3"

3"

1' 1'-

6" 1'

6"

1 1 /2"

1'

2' 1'

6"

1"

1' 3'

2' 1'

3/4

1'

4' 2'

1'

1/2

1' 6'

4' 2'

3/8

1'

8' 4'

3/1

6"

1' 8'

4' 2'

1/4

1'

8' 4'

1/8

1'

00KEYNOTES

GENERAL NOTES

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

3/3 0/2

2 2

:41 :45

P M

1900 E MAIN ST, DANVILLE, IL 61832

550-22-102100% CONSTRUCTION

VEG 22.02

UPGRADE FIRE PROTECTION AND

EMERGENCY NOTIFICATION

8171 MAPLE LAWN BLVD.

SUITE 320

FULTON, MD 20759

(301) 323-3599

WWW.COFFMAN.COM

DOCUMENTS

12/14/2022 ML MCP

00-FA003

FIRE ALARM RISER DIAGRAM AND

DETAILS

1) RISER DIAGRAMS ARE CONCEPTUAL IN NATURE AND ARE NOT

INTENDED TO SHOW A COMPLETE SYSTEM. THE CONTRACTOR

SHALL EXPAND ON THE CONCEPTUAL RISER DIAGRAM FOR A

COMPLETE SYSTEM.

2) THE BIDDING CONTRACTOR SHALL FAMILIARIZE THEMSELVES WITH

THE COMPLEXITIES OF THIS BUILDING. THESE DRAWINGS ARE

DIAGRAMMATIC ONLY. THE AWARDED CONTRACTOR SHALL BE

RESPONSIBLE FOR PRODUCTION OF ALL DESIGN AND SUBMITTAL

DOCUMENTS AND OBTAINING ALL REQUIRED INFORMATION FOR

APPROVALS.

3) WIRING LAYOUT AND ROUTING IS CONCEPTUAL. THE CONTRACTOR

IS RESPONSIBLE FOR DESIGNING AND PROVIDING ALL WIRING,

CONDUIT AND ROUTING REQUIRED BY THE SPECIFICATIONS AND

THE VA FIRE PROTECTION DESIGN MANUAL. PATHWAY

SURVIVABILITY, WHERE REQUIRED, IS NOT DEPICTED. THE

CONTRACTOR SHALL BE REQUIRED TO MEET NFPA 72

REQUIREMENTS FOR PATHWAY SURVIVABILITY, IF REQUIRED.

4) WHERE SURVIVABILITY IS REQUIRED FOR SYSTEMS EMPLOYING

RELOCATION OR PARTIAL EVACUATION, WIRING INSTALLED IN

METAL RACEWAY WITHIN BUILDINGS THAT ARE PROTECTED

THROUGHOUT BY SPRINKLERS ARE CONSIDERED TO MEET THE

NFPA 72 REQUIREMENTS FOR PATHWAY SURVIVABILITY AS A

2-HOUR PERFORMANCE ALTERNATIVE THAT HAS BEEN APPROVED

BY THE AUTHORITY HAVING JURISDICTION (VA) AND IS PERMITTED

FOR VOICE COMMUNICATION SYSTEMS IN VA FACILITIES.

5) REFER TO SHEET 00-E-002 FOR ELECTRICAL CONNECTIONS.

NO SCALE

BUILDING 58 FIRE ALARM RISER DIAGRAMD1 NO SCALE

BUILDING 98 FIRE ALARM RISER DIAGRAMD5

58 AND 98

NO SCALE

BUILDING 58 FIRE ALARM CONTROL PANEL ELEVATION VIEW AMBASSADOR AREA C1-4AF1

1) THE FIRE ALARM CONTROL PANEL MUST BE MOUNTED SO THAT CONTROL

UNIT DISPLAYS, VISIBLE INDICATORS, OR CONTROLS SHALL BE MOUNTED

SUCH THAT THE DISTANCE TO THE HIGHEST SWITCH, LAMP, OR TEXTUAL

DISPLAY DOES NOT EXCEED 6 FT ABOVE THE FINISHED FLOOR, AND THE

LOWEST SWITCH, LAMP, OR TEXTUAL DISPLAY SHALL NOT BE LESS THAN 15 IN.

ABOVE THE FINISHED FLOOR, UNLESS OTHERWISE PERMITTED BY THE

AUTHORITY HAVING JURISTICTION.

NO SCALE

BUILDING 98 FIRE ALARM CONTROL PANEL ELEVATION VIEWF4

ELECTRICAL

CLOSET

ALARM

EQUIP

ROOM7

ENTRY

CB-1

ELEVATOR

LOBBY

7A

LAB

STORAGE

7B

MECH

ROOM

7C

STORAGE

PIPE BASEMENT

ST1

STAIR

1A-1

HSK

1A

SPD

MECHANICAL

1B

HSK

1B-2

ELEV

SHAFT

1B-1

ELEV

MECH

ROOM

ELEV

ELEV

ELEV

ELEV

VS

WF

WF

VS

WF

VS

WF

VS

WF

VS

FACP

F

P

P

P

VS

WF

VS

P

AIMAIMAIM

AIMAIMAIM

AIM

AIM

AIM

AIM

AIM

AIM

AIM

PIPE BASEMENT

PIPE BASEMENT

7'- 6"

5'

1"

5'

5'

3/3

2"

1'

8'

1/1

6"

1'

1/3 2"

1'

1"

1"

1"

0'

1"

1"

9" 6"

3"

3"

1' 1'-

6" 1'

6"

1 1 /2"

1'

2' 1'

6"

1"

1' 3'

2' 1'

3/4

1'

4' 2'

1'

1/2

1' 6'

4' 2'

3/8

1'

8' 4'

3/1

6"

1' 8'

4' 2'

1/4

1'

8' 4'

1/8

1'

00KEYNOTES

KEY PLAN

GENERAL NOTES

Pl an

N or thTrue North

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

3/3 0/2

2 2

:41 :45

P M

1900 E MAIN ST, DANVILLE, IL 61832

550-22-102100% CONSTRUCTION

VEG 22.02

UPGRADE FIRE PROTECTION AND

EMERGENCY NOTIFICATION

8171 MAPLE LAWN BLVD.

SUITE 320

FULTON, MD 20759

(301) 323-3599

WWW.COFFMAN.COM

DOCUMENTS

12/14/2022 ML MCP

58 - FD101

B58 - BASEMENT FIRE ALARM

DEMOLITION PLAN - AREA A

1/8" = 1'-0"

BUILDING 58 - BASEMENT FIRE ALARM DEMOLITION PLAN - AREA AE6

1) CONTRACTOR TO DEMOLISH EXISTING FIRE ALARM EQUIPMENT,

CIRCUITS AND CONDUIT. DEVICE/APPLIANCE LOCATIONS SHOWN ON THE

DEMOLITION DRAWINGS ARE FOR CONVENIENCE ONLY AND MAY NOT BE

COMPLETE. CONTRACTOR SHOULD PERFORM AN EXISTING CONDITIONS

SURVEY TO ENSURE THAT ALL EXISTING COMPONENTS ARE REMOVED

UPON DEMOLITION OF THE SYSTEM.

MA

TC

HL

IN

E

F7 /58

-F D1

MA

TC

HL

IN

E

F7 /58

-F D1

MATCHLINE

F2/58-FD102

MATCHLINE

F2/58-FD102

1) LOCATION OF EXISTING FIRE ALARM CONTOL UNIT FROM

PREVIOUS RENOVATION OF THE BUILDING.

2) LOCATION OF EXISTING FIBER ENCLOSURE WITH CONNECTION

TO THE CAMPUS NETWORK AND CAMPUS MASTER PANELS.

FIBER ENCLOSURE TO REMAIN AND FIELD WIRING TO THE

EXISTING FIRE ALARM CONTROL UNIT SHALL BE DEMOLISHED

TO ENABLE CONNECTING THE NEW PANEL LOCATED ON THE

FIRST FLOOR INTO THE CAMPUS NETWORK.

1A-1

HSK

1A

SPD

MECHANICAL

1B

HSK

1B-2

ELEV

SHAFT

1B-1

ELEV

MECH

ROOM

MECHANICAL

SPD

10 (1B)

MECHANICAL

TOILET

STORAGE

4A

OFFICE

1C

OFFICE

4B

CLEAN

ROOM

DIRTY

ROOM

PIPE BASEMENT

P

P

P

P

P

P

F

WF

AIM

PIPE BASEMENT

AOM

AOM AIM

7A

LAB

STORAGE

7B

MECH

ROOM

7C

STORAGE

1B-2

ELEV

SHAFT

1B-1

ELEV

MECH

ROOM

WF

VS

VS

P

AIMAIM

AIM

HEAT10

7'- 6"

5'

1"

5'

5'

3/3

2"

1'

8'

1/1

6"

1'

1/3 2"

1'

1"

1"

1"

0'

1"

1"

9" 6"

3"

3"

1' 1'-

6" 1'

6"

1 1 /2"

1'

2' 1'

6"

1"

1' 3'

2' 1'

3/4

1'

4' 2'

1'

1/2

1' 6'

4' 2'

3/8

1'

8' 4'

3/1

6"

1' 8'

4' 2'

1/4

1'

8' 4'

1/8

1'

00KEYNOTES

KEY PLAN

GENERAL NOTES

Pl an

N or thTrue North

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

3/3 0/2

2 2

:41 :45

P M

1900 E MAIN ST, DANVILLE, IL 61832

550-22-102100% CONSTRUCTION

VEG 22.02

UPGRADE FIRE PROTECTION AND

EMERGENCY NOTIFICATION

8171 MAPLE LAWN BLVD.

SUITE 320

FULTON, MD 20759

(301) 323-3599

WWW.COFFMAN.COM

DOCUMENTS

12/14/2022

1/8" = 1'-0"

BUILDING 58 - BASEMENT FIRE ALARM DEMOLITION PLAN - AREA BF71/8" = 1'-0"

BUILDING 58 - BASEMENT FIRE ALARM DEMOLITION PLAN - AREAS CF2

ML MCP

58 - FD102

B58 - BASEMENT FIRE ALARM

DEMOLITION PLAN - AREAS B & C

1) CONTRACTOR TO DEMOLISH EXISTING FIRE ALARM EQUIPMENT,

CIRCUITS AND CONDUIT. DEVICE/APPLIANCE LOCATIONS SHOWN ON THE

DEMOLITION DRAWINGS ARE FOR CONVENIENCE ONLY AND MAY NOT BE

COMPLETE. CONTRACTOR SHOULD PERFORM AN EXISTING CONDITIONS

SURVEY TO ENSURE THAT ALL EXISTING COMPONENTS ARE REMOVED

UPON DEMOLITION OF THE SYSTEM.

MATCHLINE

E6/58-FD101

MATCHLINE

E6/58-FD101 MA

TC

HL

IN

E

E6 /58

-F D1

MA

TC

HL

IN

E

E6 /58

-F D1

DN

DOCK

100B

TIP

100A

LOADING

DOCK

SOILED

LINEN

103B

VAULT

104A

REFRIG

104B

TOILET

MORGUE

ST1

STAIR

C1-1

CORRIDOR

E1

ELEVATOR

E1

ELEVATOR

FREIGHT

ELEV

107A

STORAGE

HKPG

OFFICE

OFFICE

NUCLEAR

MEDICINE

ST2

STAIR

CHEMICALS

113A

TOILET

CHANGING

CHANGING

CONTROL

114A

STORAGE113

X-RAY

X-RAY

115A

TOILET

ELEC

117A

TOILET

117B

IMAGING

117C

EMPLOYEE

LOUNGE

102G

RADIOLOGIST

117D

STORAGE

117F

CHIEF

RADIOLOGY

RECEPTION

117G

CONTROL

117H

EQUIPMENT

117I

CT

SCAN

117J

TOILET

117K

PREP

C1-3A

WAITING

CONTROL

X-RAY

119A

TOILET

120C

TOILET

120A

ULTRASOUND

EXAM

C1-3

CORRIDOR

120B

VASCULAR

EXAM

121A

HOT

LAB

NUCLEAR

MEDICINE

121B

NUCLEAR

MEDICINE

121C

OFFICE

ELEC

C1-2

CORRIDOR

121E

OFFICE

IMAGING

RECEPTION

123A

ADMIN

123B

OFFICE

TOILET

TOILET

BLOOD

DRAW

LAB

C1-4

CORRIDOR

C1-4A

AMBASSADOR

AREA

127A

BLOOD

DRAW

SPECIMEN

PROCESSING

C1-0

MAIN

HALLWAY

128B

CONFERENCE

ROOM

128A

OFFICE

OFFICE

PIPATING

LAB

129A

PIPATING

LAB

131A

OFFICE

BLOOD

BANK

HISTOLOGY/

CYTOLOGY

LAB

C1-5

CORRIDOR

OFFICE

F

P

F

P

P

P

P

P

P

P

F

F

A N

N

P

P

F

WF

P

P

F

VS

PIV

AIM

AIM

UP

DN

DOCK

DH

DH

DH

7'- 6"

5'

1"

5'

5'

3/3

2"

1'

8'

1/1

6"

1'

1/3 2"

1'

1"

1"

1"

0'

1"

1"

9" 6"

3"

3"

1' 1'-

6" 1'

6"

1 1 /2"

1'

2' 1'

6"

1"

1' 3'

2' 1'

3/4

1'

4' 2'

1'

1/2

1' 6'

4' 2'

3/8

1'

8' 4'

3/1

6"

1' 8'

4' 2'

1/4

1'

8' 4'

1/8

1'

00KEYNOTES

KEY PLAN

GENERAL NOTES

Pl an

N or thTrue North

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

3/3 0/2

2 2

:41 :45

P M

1900 E MAIN ST, DANVILLE, IL 61832

550-22-102100% CONSTRUCTION

VEG 22.02

UPGRADE FIRE PROTECTION AND

EMERGENCY NOTIFICATION

8171 MAPLE LAWN BLVD.

SUITE 320

FULTON, MD 20759

(301) 323-3599

WWW.COFFMAN.COM

DOCUMENTS

12/14/2022

1/8" = 1'-0"

BUILDING 58 - FIRST FLOOR FIRE ALARM DEMOLITION PLAN - AREA AE6

ML MCP

58 - FD103

B58 - FIRST FLOOR FIRE ALARM

DEMOLITION PLAN - AREA A

1) CONTRACTOR TO DEMOLISH EXISTING FIRE ALARM EQUIPMENT,

CIRCUITS AND CONDUIT. DEVICE/APPLIANCE LOCATIONS SHOWN ON THE

DEMOLITION DRAWINGS ARE FOR CONVENIENCE ONLY AND MAY NOT BE

COMPLETE. CONTRACTOR SHOULD PERFORM AN EXISTING CONDITIONS

SURVEY TO ENSURE THAT ALL EXISTING COMPONENTS ARE REMOVED

UPON DEMOLITION OF THE SYSTEM.

MATCHLINE

F2/58-FD104

MATCHLINE

F2/58-FD104

MA

TC

HL

IN

E

F7 /58

-F D1

MA

TC

HL

IN

E

F7 /58

-F D1

1) ALL SPACES ON THIS SIDE OF THE SMOKE BARRIER IS DESIGNATED AS

SMOKE ZONE 1A.

2) ALL SPACES ON THIS SIDE OF THE SMOKE BARRIER IS DESIGNATED AS

SMOKE ZONE 1B.

3) ALL SPACES ON THIS SIDE OF THE SMOKE BARRIER IS DESIGNATED AS

SMOKE ZONE 1C.

1 2 2 3

DOCK

102G

STORAGE 102H

STORAGE

102O

STORAGE

102F

STORAGE

ST4

STAIR

102F

LOUNGE

102I

HVAC

102K

STORAGE

102J

STORAGE

C1-9

CORRIDOR

102M

STORAGE

102N

TOILET

102L

STORAGE

102D

LAB

102G-1

INPATIENT

PHARMACY

102B

INPATIENT

PHARMACY 102C

INPATIENT

PHARMACY

102A

INPATIENT

PHARMACY

103A

CHIEF

OFFICE

C1-8

CORRIDOR

100C

GAS

STORAGE

STAFF

LOUNGE

100B

TIP

100A

LOADING

DOCK

SOILED

LINEN

OFFICE

103B

VAULT

104A

REFRIG

MECH

104B

TOILET

MORGUE

P

F

P P

P

P

P

P

P

P

P

F

WF

VS

AIM

AIM

DOCK

UP

DN

136A

100A

LOADING

DOCK

CONFERENCE

ROOM

128A

OFFICE

OFFICE

PIPATING

LAB

129A

PIPATING

LAB

131A

OFFICE

BLOOD

BANK

AUTOMATED

CHEMISTRY

ELEC

CHEMISTRY134

LAB

134A

LAB

136B

LAB

136A

CHIEF

MICROBIOLOGY

OFFICE

MICROBIOLOGY

136C

LAB

STORAGE

C1-6

CORRIDOR

139A

ELEC

138A

OFFICE

PATHOLOGY

OFFICE

ST3

STAIR

C1-7

CORRIDOR

138E

STORAGE

138D

CHIEF

OFFICE

138C

OFFICE

138B

OFFICE

TOILET

TOILET

HISTOLOGY/

CYTOLOGY

LAB

C1-5

CORRIDOR

MECHANICAL

ROOM

ELECTRICAL

EQUIP

ROOM

EMERGENCY

GENERATOR

P

P

P

F

FF

UP

DN

136A

7'- 6"

5'

1"

5'

5'

3/3

2"

1'

8'

1/1

6"

1'

1/3 2"

1'

1"

1"

1"

0'

1"

1"

9" 6"

3"

3"

1' 1'-

6" 1'

6"

1 1 /2"

1'

2' 1'

6"

1"

1' 3'

2' 1'

3/4

1'

4' 2'

1'

1/2

1' 6'

4' 2'

3/8

1'

8' 4'

3/1

6"

1' 8'

4' 2'

1/4

1'

8' 4'

1/8

1'

00KEYNOTES

KEY PLAN

GENERAL NOTES

Pl an

N or thTrue North

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

3/3 0/2

2 2

:41 :45

P M

1900 E MAIN ST, DANVILLE, IL 61832

550-22-102100% CONSTRUCTION

VEG 22.02

UPGRADE FIRE PROTECTION AND

EMERGENCY NOTIFICATION

8171 MAPLE LAWN BLVD.

SUITE 320

FULTON, MD 20759

(301) 323-3599

WWW.COFFMAN.COM

DOCUMENTS

12/14/2022

1/8" = 1'-0"

BUILDING 58 - FIRST FLOOR FIRE ALARM DEMOLITION PLAN - AREA BF71/8" = 1'-0"

BUILDING 58 - FIRST FLOOR FIRE ALARM DEMOLITION PLAN - AREA CF2

ML MCP

58 - FD104

B58 - FIRST FLOOR FIRE ALARM

DEMOLITION PLAN - AREAS B & C

1) CONTRACTOR TO DEMOLISH EXISTING FIRE ALARM EQUIPMENT,

CIRCUITS AND CONDUIT. DEVICE/APPLIANCE LOCATIONS SHOWN ON THE

DEMOLITION DRAWINGS ARE FOR CONVENIENCE ONLY AND MAY NOT BE

COMPLETE. CONTRACTOR SHOULD PERFORM AN EXISTING CONDITIONS

SURVEY TO ENSURE THAT ALL EXISTING COMPONENTS ARE REMOVED

UPON DEMOLITION OF THE SYSTEM.

MATCHLINE

E6/58-FD103

MATCHLINE

E6/58-FD103 MA

TC

HL

IN

E

E6 /58

-F D1

MA

TC

HL

IN

E

E6 /58

-F D1

1) ALL SPACES IN THIS AREA ARE DESIGNATED AS PART OF SMOKE ZONE 1A.

2) ALL SPACES IN THIS AREA ARE DESIGNATED AS PART OF SMOKE ZONE 1B.

FHC

CHART CHART

EQUIP

ALCOVE ALCOVE

CHART

C2-1

CORRIDOR

ANTEROOM

COMM 200

CHUTE

SPD

206A

CHIEF

205A

TOILET

NOURISHMENT

243A

TOILET

1-PATIENT

ROOM 233

1-PATIENT

ROOM

233A

TOILET

JAN

CLOSET

231A

TOILET

1-PATIENT

ROOM

229D

VACANT

TOILET

229C

HEAD

NURSE

HALL 229A

WARD

CLERK

229B

STAFF

LOUNGE

2-PATIENT

ROOM

228A

TOILET

2-PATIENT

ROOM

227A

TOILET

226A

TOILET

2-PATIENT

ROOM

EQUIP

STOR

224A

TOILET

1-PATIENT

ROOM 222

2-PATIENT

ROOM

ELEC

222A

TOILET

2-PATIENT

ROOM

221A

TOILET

CONFERENCE

TOILET

HALL

218B

RESD

LNG/LKR

218A

PROGRAM

SUPPORT

ASSISTANT

C2-5

CORRIDOR

RESIDENT

STAFF

WORK

MEDICAL

DIRECTOR

INTERNAL

MEDICINE

PHYSICIAN

PHYSICIAN

PROGRAM

MANAGEMENT

OFFICER

MID

LEVEL

WORKROOM

ST2

STAIR

#2

CLEAN

SUPPLY/UTILITY

STORAGE

C2-4

CORRIDOR

SUB

N

STAT

COMFORT

SOIL

HOLD

C2-3

CORRIDOR

ST1

STAIR

#1

MED

NURSE

STATION

218C

PHYSICIAN

C2-6

HALL

P

P

P

F

P

P

P

F

P

P

WF

VS

AIM

AIM

FHC

CHART CHART

EQUIP

ALCOVE ALCOVE

CHART

C2-1

CORRIDOR

ANTEROOM

COMM 200

CHUTE

SPD

206A

CHIEF

205A

TOILET

NOURISHMENT

243A

TOILET

1-PATIENT

ROOM 233

1-PATIENT

ROOM

233A

TOILET

JAN

CLOSET

231A

TOILET

1-PATIENT

ROOM

229D

VACANT

TOILET

229C

HEAD

NURSE

HALL 229A

WARD

CLERK

229B

STAFF

LOUNGE

2-PATIENT

ROOM

228A

TOILET

2-PATIENT

ROOM

227A

TOILET

226A

TOILET

2-PATIENT

ROOM

EQUIP

STOR

224A

TOILET

1-PATIENT

ROOM 222

2-PATIENT

ROOM

ELEC

222A

TOILET

2-PATIENT

ROOM

221A

TOILET

CONFERENCE

TOILET

HALL

218B

RESD

LNG/LKR

218A

PROGRAM

SUPPORT

ASSISTANT

C2-5

CORRIDOR

RESIDENT

STAFF

WORK

MEDICAL

DIRECTOR

INTERNAL

MEDICINE

PHYSICIAN

PHYSICIAN

PROGRAM

MANAGEMENT

OFFICER

MID

LEVEL

WORKROOM

ST2

STAIR

#2

CLEAN

SUPPLY/UTILITY

STORAGE

C2-4

CORRIDOR

SUB

N

STAT

COMFORT

SOIL

HOLD

C2-3

CORRIDOR

ST1

STAIR

#1

MED

NURSE

STATION

218C

PHYSICIAN

C2-6

HALL

DH

DH

7'- 6"

5'

1"

5'

5'

3/3

2"

1'

8'

1/1

6"

1'

1/3 2"

1'

1"

1"

1"

0'

1"

1"

9" 6"

3"

3"

1' 1'-

6" 1'

6"

1 1 /2"

1'

2' 1'

6"

1"

1' 3'

2' 1'

3/4

1'

4' 2'

1'

1/2

1' 6'

4' 2'

3/8

1'

8' 4'

3/1

6"

1' 8'

4' 2'

1/4

1'

8' 4'

1/8

1'

00KEYNOTES

KEY PLAN

GENERAL NOTES

Pl an

N or thTrue North

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase Project Title

Location

Issue Date Checked Drawn

Project Number

Drawing Number

Building Number

Number:

3/3 0/2

2 2

:41 :45

P M

1900 E MAIN ST, DANVILLE, IL 61832

550-22-102100% CONSTRUCTION

VEG 22.02

UPGRADE FIRE PROTECTION AND

EMERGENCY NOTIFICATION

8171 MAPLE LAWN BLVD.

SUITE 320

FULTON, MD 20759

(301) 323-3599

WWW.COFFMAN.COM

DOCUMENTS

12/14/2022

1/8" = 1'-0"

BUILDING 58 - SECOND FLOOR FIRE ALARM DEMOLITION PLAN - AREA AE6

ML MCP

58 - FD105

B58 - SECOND FLOOR FIRE ALARM

DEMOLITION PLAN - AREA A

1) CONTRACTOR TO DEMOLISH EXISTING FIRE ALARM EQUIPMENT,

CIRCUITS AND CONDUIT. DEVICE/APPLIANCE LOCATIONS SHOWN ON THE

DEMOLITION DRAWINGS ARE FOR CONVENIENCE ONLY AND MAY NOT BE

COMPLETE. CONTRACTOR SHOULD PERFORM AN EXISTING CONDITIONS

SURVEY TO ENSURE THAT ALL EXISTING COMPONENTS ARE REMOVED

UPON DEMOLITION OF THE SYSTEM.

MATCHLINE

F2/58-FD106

MATCHLINE

F2/58-FD106

MA

TC

HL

IN

E

F7 /58

-F D1

MA

TC

HL

IN

E

F7 /58

-F D1

1) ALL SPACES ON THIS SIDE OF THE SMOKE BARRIER IS DESIGNATED AS

SMOKE ZONE 2A.

2) ALL SPACES ON THIS SIDE OF THE SMOKE BARRIER IS DESIGNATED AS

SMOKE ZONE 2B.

1 2

205C

PACK/

DISPATCH

205C2

STERILIZERS205C3

AUTO

CART

WASH

205C5

CART

DRY

205C4

ELECTRICAL

205C1

STORAGE 205G

STORAGE

205E

STORAGE/BREAK

ST 4

STAIR

#4

205D

STORAGE

202B

PREP/

ASSEMBLY

205A1

HAC

202C

DECONTAMINATION/

SCOPE

PROCESSING

202A

HAC 205

STORAGE

TOILET

TOILET

C2-1

CORRIDOR

ANTEROOM

COMM 200

CHUTE

SPD

205A

TOILET

P

OFFICE

F

205C

PACK/

DISPATCH

205C2

STERILIZERS205C3

AUTO

CART

WASH

205C5

CART

DRY

205C4

ELECTRICAL

205C1

STORAGE 205G

STORAGE

205E

STORAGE/BREAK

ST 4

STAIR

#4

205D

STORAGE

202B

PREP/

ASSEMBLY

205A1

HAC

202C

DECONTAMINATION/

SCOPE

PROCESSING

202A

HAC 205

STORAGE

TOILET

TOILET

C2-1

CORRIDOR

ANTEROOM

COMM 200

CHUTE

SPD

205A

TOILET

FHC

CHART

EQUIP

ALCOVE

CHART

ANTEROOM

1-PATIENT

ROOM

245A

ANTE

1-PATIENT

ROOM

WORK

244A

TOILET

246A

TOILET

C2-11

CORRIDOR

243A

TOILET

OXYGEN

STORAGE

C2-9

CORRIDOR

1-PATIENT

ROOM

PCC

C2-10

CORRIDOR

2-PATIENT

ROOM

241A

TOILET

240A

TOILET 240

2-PATIENT

ROOM

IV

THERAPY

2-PATIENT

ROOM

238A

TOILET

237A

TOILET

1-PATIENT

ROOM

EQUIP

STORAGE

ELEC

C2-8

CORRIDOR

ST3

STAIR

#3

CLEAN

UTILITY

ELEC

BED

STORAGE

NOURISHMENT

243A

TOILET

1-PATIENT

ROOM 233

1-PATIENT

ROOM

233A

TOILET

JAN

CLOSET

231A

TOILET

1-PATIENT

ROOM

MED

NURSE

STATION

P

F

P

FHC

CHART

EQUIP

ALCOVE

CHART

ANTEROOM

1-PATIENT

ROOM

245A

ANTE

1-PATIENT

ROOM

WORK

244A

TOILET

246A

TOILET

C2-11

CORRIDOR

243A

TOILET

OXYGEN

STORAGE

C2-9

CORRIDOR

1-PATIENT

ROOM

PCC

C2-10

CORRIDOR

2-PATIENT

ROOM

241A

TOILET

240A

TOILET 240

2-PATIENT

ROOM

IV

THERAPY

2-PATIENT

ROOM

238A

TOILET

237A

TOILET

1-PATIENT

ROOM

EQUIP

STORAGE

ELEC

C2-8

CORRIDOR

ST3

STAIR

#3

CLEAN

UTILITY

ELEC

BED

STORAGE

NOURISHMENT

243A

TOILET

1-PATIENT

ROOM 233

1-PATIENT

ROOM

233A

TOILET

JAN

CLOSET

231A

TOILET

1-PATIENT

ROOM

MED

NURSE

STATION

NAC

7'- 6"

5'

1"

5'

5'

3/3

2"

1'

8'

1/1

6"

1'

1/3 2"

1'

1"

1"

1"

0'

1"

1"

9" 6"

3"

3"

1' 1'-

6" 1'

6"

1 1 /2"

1'

2' 1'

6"

1"

1' 3'

2' 1'

3/4

1'

4' 2'

1'

1/2

1' 6'

4' 2'

3/8

1'

8' 4'

3/1

6"

1' 8'

4' 2'

1/4

1'

8' 4'

1/8

1'

00KEYNOTES

KEY PLAN

GENERAL NOTES

Pl an

N or thTrue North

Drawing Title

VA FORM 08 - 6231

F

CONSULTANTS:

750 W HAMPDEN AVE

SUITE 300

ENGLEWOOD, CO 80110

(720) 550-6307 WWW.VALHALLAENGINEERING.COMDate:Revisions:

10987654321

10987654321

E

D

C

B

A

F

E

D

C

B

A

ARCHITECT/ENGINEERS: STAMP:

Approved: Project Director

Phase…

This is the start of the file's text. The full file is on GovTribe.