528A7-18-726 Renovate 4B for Cardiology - Drawings for Construction.pdf
PDF 25 MB Posted
- Attached to
- Z1DA--528A7-18-726 RENOVATE 4B FOR CARDIOLOGY
- Solicitation number
- 36C24220B0066
About this file
This document outlines a federal contract opportunity to renovate space in a Veterans Affairs medical facility. The solicitation number is 36C24220B0066 and seeks to renovate the 4B ward for cardiology services at the Veterans Integrated Service Network 2 facility under opportunity Z1DA--528A7-18-726. The work includes renovating existing space to upgrade the cardiology department. The Department of Veterans Affairs Veterans Health Administration is the contracting agency. The response due date and other details are not provided in this high-level overview of the opportunity.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
COVER SHEET
AND
DRAWING INDEX
GI001
ARFTMH
DESIGN RENOVATION
FOR 4B CARDIOLOGY
528A7-18-726
B
A
C
D
E
F
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
Revisions Date
Reviewed:
Reviewed:
Drawing Title Project Title
Location
Building Number Checked
Project No.
DRAWING NO.
Drawn
Date
Approved: Project Director
Reviewed: Facility Director
Reviewed: Facility Manager
BID DOCUMENTS
FULLY SPRINKLERED
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE WHATSOEVER
WITHOUT THE SEAL AND SIGNATURE OF THE PROFESSIONAL ENGINEER.
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering
A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0499-0126
Scient is ts | Engineers | Program Managers
Mabbett & Associates, Inc.
105 Central Street, Stoneham, MA 02180
T. 781-275-6050 www.mabbett.com
N A
ROOM NAME DESIGNATION
ROOM NUMBER DESIGNATION (IF PRESENT)
ROOM AREA DESIGNATION (IF PRESENT)
PARTITION TYPE DESIGNATION. SEE
PARTITION LEGEND
DOOR NUMBER DESIGNATION
SPECIAL NOTATION (e.g. DEMO NOTE)
W1 WINDOW TYPE DESIGNATION
1T ACCESSORY ITEM- SEE ACCESSORY
SCHEDULE
DATUM POINT OR WORK POINT
BUILDING SECTION
WALL SECTION
DETAIL NUMBER
SHEET NUMBER WHERE
DETAIL IS LOCATED
DETAIL NUMBER
SHEET NUMBER WHERE
DETAIL IS LOCATED
EXTENT OF SECTION
A-XXX
A1
A2 B1
DETAIL NUMBERS
SHEET NUMBER WHERE
DETAIL IS LOCATED
ELEVATIONS
REVISION NOTE
REVISION NUMBER
EXTENT OF REVISION
A1 A2 A3 A4 A5 A6 A7
B1 B2 B3 B4 B5 B6 B7
C1 C2 C3 C4 C5 C6 C7
D1 D2 D3 D4 D5 D6 D7
E1 E2 E3 E4 E5 E6 E7
F1 F2 F3 F4 F5 F6 F7
DETAIL NUMBER DETAIL SCALE
DETAIL NAME
DETAIL NUMBER
SCALE: 1/8" = 1'-0"
AXX
View Name
ROOM NAME
00000
1500 SF
DETAIL SECTION
DETAIL NUMBER
SHEET NUMBER WHERE
DETAIL IS LOCATED
EXTENT OF SECTION
PLAN DETAIL
DETAIL
NUMBER
SHEET NUMBER
WHERE DETAIL
IS LOCATED
EXTENT
OF DETAIL
R01
NNNL
A-XXX
A-XXX
A-XXX
A-XXX
A-XXX
NEW DOOR IN NEW OR EXISTING
PARTITION, SEE DOOR SCHEDULE
EXISTING DOOR IN NEW OR EXISTING
PARTITION, WITH MODIFICATION. SEE
DOOR SCHEDULE
EXISTING DOOR TO BE REMOVED,
SEE REMOVAL PLAN
EXISTING DOOR TO REMAIN, IN
EXISTING PARTITION
E-###
FINISHED SURFACES-NEW
REMOVAL OF EXISTING
EXISTING SURFACES
GRAVEL / STONE
CONCRETE - CAST
IN PLACE
CONCRETE
MASONRY UNIT
BRICK
CONCRETE -
PRECAST
STONE
GRANITE
MARBLE
SAND / MORTAR
GYPSUM
WALLBOARD
ALUMINUM
STEEL
RIGID INSULATION
TILE
P LAM OVER
COMPOSITE
WOOD
WOOD - FINISHED
PLYWOOD
ACOUSTIC TILE
CARPET
EARTH
BATT INSULATION WOOD
BLOCKING
REINFORCING -
WWF
SOLID SURFACE
QUARTZ
CULTERED MARBLE
SYNTHETIC
1' -4
ELEV SECTION
8" 1'
-4
2' -0
TOP OF MASONRY
UNIT BEYOND
ACTUAL FACE
OF MASONRY
F R
O M
E
LE
V A
T
IO
N
1' A B
FOR DOOR OPENING
INFORMATION SEE
DOOR SCHEDULE
WP
A-101
2"
7'-4" 4'-8"
3' -0
WP
2'-2"
FINISHED
FACE OF
NON-
MASONRY
WALL
NOMINAL
FACE OF
MASONRY
WALL
3 B
6 A
6 A
1 A
B6
A-001
1' -6
B
4" 1"
5/ 8"
1/
2" 5/
8"
S E
E P
LA
N
2"
33 ACTUAL FACE
OF MASONRY
NOMINAL
DIMENSION
FROM PLAN
1/2" JT WIDTH
FACE OF
FINISHED
SURFACE
FROM PLAN
NOMINAL DIM
FROM PLAN
NOMINAL OPENING
TYPE 2
RATING = ---
TEST = ---
STC = ---
4 7/8"
3-5/8" METAL STUDS- 20 GAUGE
AT 16" O.C.
1 LAYER 5/8" GWB- TYPE "X."
TYPE 1
RATING = 1 HR
TEST = U-465
STC = 47
1 LAYER 5/8" TILE BACKER BOARD
AT ALL TOILET/SHOWER ROOMS
2 1/2" MINERAL WOOL INSULATION
1 1/2" RIGID INSUL. ADHESIVE
APPLIED TO EXIST WALL & INSUL
MFR STD TAPE
1 5/8" METAL STUDS - 20 GA AT 16"
OC. BRACE STUDS TO MASONRY
@ 48" OC.
1 LAYER 5/8" GWB.
EXG. EXTERIOR WALL
TYPE 3
RATING = 1 HR
TEST = U-465
STC = 47
2 1/2" METAL STUDS - GA 2
ROWS - AT 16" OC
1 LAYER 5/8" GWB - TYPE 'X'
PATIENT ROOM SIDE. TILE
BACKER BOARD ON TOILET
ROOM SIDE. BRACE EACH PAIR
STUDS AT 48" OC VERTICAL.
PROVIDE 2 LAYERS 2 1/2" MINERAL
WOOL INSULATION.
SEE PLAN.
5 3/8"
TYPE 4
RATING = 1 HR
TEST = UL-U465
STC = 51
3 5/8" METAL STUDS - 20
GA AT 16" OC
2 1/2" MINERAL WOOL INSULATION
1 LAYER 5/8" SOUND
DEADENING TYPE 'X' GWB
1/2" RC-1 CHANNELS 25 GA
AT 24" O.C.
1 LAYER 5/8" GWB - TYPE 'X'
TYPE 8
5/8" GWB ADHESIVE APPLIED TO
EXIST SURFACE
TYPE 7
2 1/2" MTL STUDS - 20 GA
@ 16" OC
1 LAYER 5/8" GWB
5 3/4"
TYPE 5
RATING = 1 HR
TEST = UL-U465
STC = 51
4" METAL STUDS - 20 GA
AT 16" OC
2 1/2" MINERAL WOOL INSULATION
1 LAYER 5/8" SOUND
DEADENING TYPE 'X' GWB
1/2" RC-1 CHANNELS 25 GA
AT 24" O.C.
1 LAYER 5/8" GWB - TYPE 'X'
7 3/4"
TYPE 6
RATING = 1 HR
TEST = UL-U465
STC = 51
6" METAL STUDS - 20 GA
AT 16" OC
2 1/2" MINERAL WOOL INSULATION
1 LAYER 5/8" SOUND
DEADENING TYPE 'X' GWB
1/2" RC-1 CHANNELS 25 GA
AT 24" O.C.
1 LAYER 5/8" GWB - TYPE 'X'
RATING = ---
TEST = ---
STC = ---
RATING = ---
TEST = ---
STC = ---
TYPE 9
RATING = ---
TEST = ---
STC = ---
1 1/2" RIGID INSUL. ADHESIVE
APPLIED TO EXIST WALL & INSUL
MFR STD TAPE
3 1/2" METAL STUDS - 20 GA AT 16"
OC. BRACE STUDS TO MASONRY
@ 48" OC.
1 LAYER 5/8" GWB.
EXG. EXTERIOR WALL
4 7/8"
3-5/8" METAL STUDS- 20 GAUGE
AT 16" O.C.
1 LAYER 5/8" GWB- TYPE "X."
TYPE 1
RATING = 1 HR
TEST = U-465
STC = 47
1.1
1 LAYER 5/8" TILE BACKER BOARD
AT ALL TOILET/SHOWER ROOMS
2 1/2" MINERAL WOOL INSULATION
EXTEND ALL MATERIALS
TO UNDERSIDE OF
DECK/SLAB
_A
EXTEND GB MATERIAL
ABOVE CLG & BRACE
STUDS AT STRUCT ABOVE,
AS REQD.
AT INSULATED WALLS
PROVIDE 2-1/2" BATT
INSULATION MIN 24" TO EA
SIDE OF WALL.
_B
CLG
24" MIN 24" MIN
CLG 6"
EXTEND GB MATERIAL
ABOVE CLG & BRACE
STUDS AT STRUCT ABOVE,
AS REQD TO PROVIDE
STABILITY
_C
CLG 6"
STOP GB ABOVE CLG ONE
SIDE; EXTEND ALL OTHER
MATERIALS TO
UNDERSIDE OF
DECK/SLAB
_D
CLG 6"
LOW WALL, SEE
DWGS FOR HT
_E
CLG
V A
R
IE
S
BULKHEAD
CONDITIONS VARY-
SEE DWGS FOR
DETAILS. BRACE
STUDS AT STRUCT
ABOVE, AS REQD TO
PROVIDE STABILITY
_F
CLG 6"
V
A R
IE
S
BULKHEAD
CONDITIONS VARY-
SEE DWGS FOR
DETAILS. BRACE
STUDS AT STRUCT
ABOVE, AS REQD TO
PROVIDE STABILITY
_G
CLG 6"
V
A R
IE
S
CLG
1A
CONSTRUCTION TYPES :
HEIGHT TYPES :
ADDITIONAL RELATED NOTES: SEE "GENERAL NOTES"
SEE SPECIFIC NOTES ON PLANS AND
DETAILS; SEE SPECIFICATIONS
TEST DESIGNATIONS : UL= UNDERWRITERS LABORATORIES
OSU= OHIO STATE UNIVERSITY
UC= UNIVERSITY OF CALIFORNIA
ALPHABET SUFFIX DESIGNATES
PARTITION HEIGHT NOTED BELOW
NUMERAL PREFIX DESIGNATES
PARTITION CONSTRUCTION NOTED
ABOVE
A Se rv ic e D i s a b le d Ve t e r an Owned
Sm a l l
B u s iness
SDVOSB
CVE
Location
Building Number
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0500-0016
o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
B
A
C
D
E
F
Revisions Date
Date
Project No.
Drawing NO.
Project Title
Checked Drawn
Drawing Title
Approved:
DESIGN RENOVATION
FOR 4B CARDIOLOGY
SYRACUSE VAMC, SYRACUSE, NY
Project Director
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE PROFESSIONAL ENGINEER.
Reviewed: Facility Manager
Reviewed: Facility Director
Reviewed:
Reviewed:
2020-10-26
528A7-18-726
BID DOCUMENTS
FULLY SPRINKLERED
SH AE
Scientists | Engineers | Program Managers
Mabbett & Associates, Inc.
105 Central Street, Stoneham, MA 02180
T.
781-275-6050 www.mabbett.com GI-100
GENERAL INFORMATION
ABBREVIATIONS
RM ROOM
RO ROUGH OPENING
S
SC SOLID CORE
SCHED SCHEDULE
SECT SECTION
SF SQUARE FEET
SHT SHEET
SHTHG SHEATHING
SIM SIMILAR
SLNT SEALANT
SND SANITARY NAPKIN
DISPENSER
SNDU SANITARY NAPKIN DISPOSAL
UNIT
SPEC SPECIFICATION
SPKLR SPRINKLER
SQ SQUARE
SSM SOLID SURFACE MATERIAL
SST STAINLESS STEEL
STC SOUND TRANSMISSION
CLASS
STD STANDARD
STL STEEL
STL JST STEEL JOIST
STL LNTL STEEL LINTEL
STL PLATE STEEL PLATE
STN STONE
STRUCT STRUCTURAL
SUSP SUSPENDED
SV SHEET VINYL
SVT SHEET VINYL FLOORING
SYMM SYMMETRICAL
T
T TREAD
T&G TONGUE AND GROOVE
TEL TELEPHONE
TEMP TEMPERATURE
TER TERRAZZO
TERM TERMINAL
THK THICKNESS
THRES THRESHOLD
TK BD TACKBOARD
TMPD TEMPERED
TO TOP OF
TOC TOP OF CONCRETE
TOS TOP OF STEEL
TOW TOP OF WALL
TRANS TRANSOM, TRANSPARENT
TYP TYPICAL
U
UC UNDERCUT
UL UNDERWRITER'S LABATORY
(TEST)
UNO UNLESS NOTED OTHERWISE
UR URINAL
V
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
VIF VERIFY IN FIELD
VNR VENEER
VP VENEER PLASTER
VR VAPOR RETARDER
VT VINYL TILE
VWC VINYL WALLCOVERING
W
W WIDE
W/ WITH
W/O WITHOUT
WC WATER CLOSET
WD WOOD
WDW WINDOW
WDWT WINDOW TREATMENT
WGL WIRED GLASS
WP WATERPROOFING
WPT WORKPOINT
WS WEATHERSTRIP
WWF WELDED WIRE FABRIC
JOB SPECIFIC ABBREVIATIONS
AMP ACOUSTICAL METAL PANEL
BE BAKED ON ENAMEL
CC CONTRACTOR SUPPLIED &
INSTALLED
COR CONTRACTING OFFICER'S
TECHNICAL
REPRESENTATIVE
CTG COATING
DC DOOR CONTROL
DISTR DISTRIBUTION
EFTR EXIST FINISH TO REMAIN
FC FILE CABINET
GBP 3 SIZE GLOVE DISPENSER
ICB INTEGRAL COVE BASE
LGMF LIGHT GA METAL FRAMING
MC METAL CEILING
MTD MOUNTED
MW MICROWAVE
PCP PORTLAND CEMENT PLASTER
PFW POLYPROPYLENE FABRIC
WALL COVERING
RCT RADIANT CEILING TILE
REF REFRIGERATOR
RF RAISED RUBBER FLOORING
RST RESILIENT STAIR TREADS
RTF RESILIENT TILE FLOORING
SD SOAP DISPENSER
SHD SHARPS DISPENSER
TPD TOILET PAPER DISPENSER
VAMC SYRACUSE VA MEDICAL
CENTER
VC VA SUPPLIED &
CONTRACTOR INSTALLED
VV VA SUPPLIED & INSTALLED
WSF VINYL SHEET FLOORING
(HEAT WELDED SEAMS)
ZA ZONE ALARM
ZVB ZONE VALVE BOX
ABBREVIATIONS
FURG FURRING
FURN FURNISHED/FURNITURE
FWC FABRIC WALL COVERING
G
GA GAUGE
GALV GALVANIZED
GB GRAB BAR
GC GENERAL CONTRACTOR
GCT GLAZED CERAMIC TILE
GL GLASS/GLAZING
GWB GYPSUM WALLBOARD
GYP GYPSUM
H
HC HOLLOW CORE
HCP HANDICAPPED
HDBD HARDBOARD
HDW HARDWARE
HDWD HARDWOOD
HM HOLLOW METAL
HNDRL HANDRAIL
HORIZ HORIZONTAL
HR HOUR
HT HEIGHT
HVAC HEATING/VENTILATING/AIR
CONDITIONING
I
ID INSIDE DIAMETER
INCL INCLUDE(D)(-ING)
INSUL INSULATE(D)(-ION)(-ING)
INT INTERIOR
INV INVERT
J
JAN JANITOR
JT JOINT
L
LAM LAMINATE(D)
LAV LAVATORY
LF LINEAR FEET
LL LIVE LOAD
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LT GA LIGHT GAUGE
LTG LIGHTING
LVR LOUVER
M
MACH MACHINE
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MEMB MEMBRANE
MEZZ MEZZANINE
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MKR BD MARKER BOARD
MLDG MOULDING
MO MASONRY OPENING
MR MOISTURE RESISTANT
MTL METAL
MULL MULLION
N
NA NOT APPLICABLE
NAT NATURAL
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
NPS NOMINAL PIPE SIZE
NTS NOT TO SCALE
O
OA OVERALL
OC ON CENTER
OD OUTSIDE DIAMETER
OPH OPPOSITE HAND
OPNG OPENING
OPP OPPOSITE
P
PBD PARTICLE BOARD
PCT PORCELAIN CERAMIC TILE
PERIM PERIMETER
PL PROPERTY LINE
PLAM PLASTIC LAMINATE
PLAS PLASTER
PLBG PLUMBING
PLYWD PLYWOOD
PNL PANEL
PNT PAINT
PNTD PAINTED
PR PAIR
PREFAB PREFABRICAT(D)
PT PRESSURE TREATED
PTD PAPER TOWER DISPENSER
PTN PARTITION
PVC POLYVINYL CHLORIDE
(PLASTIC)
PVG PAVING
Q
QT QUARRY TILE
QTY QUANTITY
R
R RADIUS/RISER
RB RESILIENT BASE
RBR RUBBER
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REF REFRIDGERATOR
REINF REINFORCE(D)
REQ'D REQUIRED
RESIL RESILIENT
RESIL C RESILIENT CHANNEL
RET RETURN
REV REVISION
ABBREVIATIONS
A
A/C AIR CONDITIONING
AB ANCHOR BOLT
ACC ACCESIBLE
ACS PNL ACCESS PANEL
ADDM ADDENDUM
ADJ ADJUSTABLE
AFF ABOVE FINISH FLOOR
AHR ANCHOR(AGE)
ALT ALTERNATE
ALUM ALUMINUM
ANN PNL ANNUNCIATOR PANEL
ANOD ANODIZED
APC ACOUSTICAL PANEL CEILING
APPROX APPROXIMATE
ARCH ARCHITECT(URAL)
ASB ASBESTOS
ASPH ASPHALT
ATC ACOUSTICAL TILE CEILING
B
BD BOARD
BEV BEVELED
BLDG BUILDING
BLKG BLOCKING
BLKT BLANKET
BM BEAM, BENCHMARK
BOT OF BOTTOM OF
BRG BEARING
BSMT BASEMENT
BUR BUILT-UP ROOF
C
CAB CABINET
CEM CEMENT
CH BD CHALKBOARD
CIP CAST-IN-PLACE
CJ CONTROL JOINT
CLG CEILING
CLL CONTRACT LIMIT LINE
CLO CLOSET
CLR CLEAR
CMP CORRUGATED METAL PIPE
CMPST COMPOSITE
CMT CERAMIC MOSAIC TILE
CMU CONCRETE MASONRY UNIT
COL COLUMN
COMB COMBINATION
CONC CONCRETE
CONSTR CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
COORD COORDINATE
CORR CORRIDOR
CPRS FL COMPRESSIBLE FILLER
CPT CARPET
CR CARD READER
CRS COLD ROLLED STEEL
CT CERAMIC TILE
D
D DEPTH
DET DETAIL
DF DRINKING FOUNTAIN
DFLCT DEFLECTION
DH DOUBLE HUNG
DIA DIAMETER
DIAG DIAGONAL
DIM DIMENSION
DL DEAD LOAD
DMPF DAMPPROOFING
DR DOOR
DWG DRAWING
E
EA EACH
EIFS EXTERIOR INSULATION AND
FINISH SYSTEM
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRIC(AL)
ELEV ELEVATOR
EMHO ELECTROMAGNETIC HOLD
OPEN
ENTR ENTRANCE
EP ELECTRIC PANEL
EQ EQUAL
EQUIP EQUIPMENT
EST ESTIMATE
EWC ELECTRIC WATER COOLER
EXH EXHAUST
EXIST EXISTING
EXP EXPOSED, EXPANSION
EXT EXTERIOR
F
FAAP FIRE ALARM ANNUNCIATOR
PANEL
FCU FAN COIL UNIT
FD FLOOR DRAIN
FDTN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FH FIRE HYDRANT
FIN FINISH(ED)
FIXT FIXTURE
FLASH FLASHING
FLG FLOORING
FLR FLOOR
FM FACTORY MUTUAL
FO FACE OF
FOF FACE OF FINISH
FOS FACE OF STUD
FP FIREPROOFING
FR FRAME
FRMG FRAMING
FRP FIBERGLASS REINFORCED
PLASTIC/PANEL
FRTW FIRE RETARDANT TREATED
WOOD
FT FOOT/FEET
FTG FOOTING
DIMENSIONING LEGEND NOTES
Key Name DIM LEGEND NOTE
1 MASONRY PLAN DIMENSIONS AT SCALES NOT SHOWING INDIVIDUAL MODULES ARE TO NOMINAL FACE OF MASONRY
2 NON MASONRY DIMENSIONS ARE TO FINISHED FACE OF MATERIAL UNLESS NOTED OTHERWISE
3 MASONRY ON DRAWINGS SHOWN WITH INDIVIDUAL MODULAR UNITS ARE DIMENSIONED TO ACTUAL SIZE, AND WHERE
SHOWN INCLUDE REFERENCES TO MODULAR DIMENSIONS.
4 MASONRY COURSING LINES IN ELEVATON REPRESENT NOMINAL DIMENSIONS. VERTICAL JOINTS ARE DIMENSIONED TO CENTERLINE OF JOINT. HORIZONTAL JOINTS ARE DIMENSIONED TO TOP OF MASONRY IN ELEVATION AND IN SECTION.
5 DIMENSIONS ARE FROM STRUCTURAL COLUMN CENTERLINES, UNO.
6 AT INTERSECTION OF DIFFERENT PARTITION TYPES, CONTINUE PARTITION OF GREATER FIRE RATING THROUGH
INTERSECTION UNO.
7 REFER TO PARTITION SCHEDULE FOR PARTITION THICKNESS AND HEIGHT.
8 NON-ARCHITECTURAL DISCIPLINE INFORMATION IF SHOWN IS FOR REFERENCE ONLY. OBJECTS AND INFORMATION SHOWN
MAY NOT BE ALL INCLUSIVE. REFER TO APPROPRIATE DISCIPLINE FOR INFORMATION.
9 REFER TO WORKPOINTS WHERE SHOWN FOR ELEMENTS PLACED ON NON-PARALLEL OR NON-PARALLEL RELATIONSHIPS.
WORKPOINTS MAY ALSO BE SHOWN AS LAYOUT STARTING POINTS IN ORDER TO MAINTAIN CORRECT RELATIONSHIPS
BETWEEN ELEMENTS.
GENERAL NOTES-ARCHITECTURE
Key Name GENERAL NOTES
1 SEE "REGULATORY PLAN" FOR REGULATORY INFORMATION AND UL ASSEMBLY DESIGNATIONS FOR FIRE RATED STEEL
STRUCTURE AND FLOOR ASSEMBLIES.
SCALE: NO SCALE
F1
ABBREVIATIONS
SCALE: NO SCALE
E3
MATERIALS LEGEND
SCALE: NO SCALE
C3
GRAPHIC KEY
SCALE: NO SCALE
D9
DIMENSIONING GUIDE ELEV/SECTION
SCALE: NO SCALE
F8
DIMENSIONING GUIDE PLAN
SCALE: NO SCALE
C9
DIMENSIONING GUIDE DETAIL
SCALE: NO SCALE
F6
PARTITIONS
D .7
PC .1PD .1
P B
P
P5.8
P B
P
R A M P
D N
RAMP
DN
DN
DN
DN
UP
DN
UP
DN
DN
DN
UP DN
U P
U P
U P
D N
UP
UP
UP
UP
N E
W A
D D
IT
IO
N E
X
IS
T
IN
G B
U
IL
D
IN
G
U P
U P
D N
R A M P
D N
D N
BRICK
SIDEWALK
CONCRETE
SIDEWALK
SERVICE ELEVATORS
CONTRACTOR ACCESS
VAN BUREN STREET
UNIVERSITY PLACE
N O P Q
R S T U
M
TEMPORARY
WALKOFF MAT
TEMP. 2 HR
FIRE BARRIER
TEMP. 2 HR FIRE BARRIER
AND 90 MIN. DOOR & 48"
DOOR FRAME.
GENERAL NOTES:
1. DEMOLITION AND CONSTRUCTION THAT IS DISRUPTIVE TO THE OWNER'S
OPERATIONS ARE TO BE PERFORMED ONLY BETWEEN THE HOURS OF 7:00 AM TO
4:00 PM IN 2 HRS ON (MAX) & 2 HRS OFF (MIN) INCREMENTS. EXACT TIMES TO BE
COORDINATED W/ VAMC COR.
2. REFER TO SHEET AD-100 FOR EXISTING FLOOR PLAN CONFIGURATION.
4. CONTRACTOR TO MAINTAIN NEGATIVE AIR IN ALL PHASE IN CONSTRUCTION
AREAS. PROVIDE MANOMETER TO MONITOR PRESSURE AT CONSTRUCTION DOOR.
5. INFECTION CONTROL CLASS IV - VERIFY WITH C.O.R.
6. DOOR AT STAIR 5 MAY NEVER BE USED FOR RE-ENTRY. THIS DOOR WILL ALWAYS
BE LOCKED.
7. SMOKE HEADS SHALL BE COVERED FOR THE DURATION OF WORK DAY & BE
REMOVED PRIOR TO LEAVING WORK AREA AT THE END OF EACH WORK DAY.
8. CONSTRUCTION DOOR SHALL BE EQUIPPED WITH CLOSER & STOREROOM
FUNCTION LOCKSET. COMPATIBLE WITH VA 7 PM SFIC. DOOR SHALL ALWAYS BE
LOCKED.
4A
B426
B425B423B421
B424B422
B427
B418
B420
B419B417B415B413
B416B410B408B406B404
B411
B436
B440
B442
B444
B446
B439
B441
B443
B445
B447
B437
B407 B409
B439A
B413A
B416A
B414
A Se rv ic e D i s a b le d Ve t e r an Owned
Sm a l l
B u s iness
SDVOSB
CVE
Location
Building Number
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0500-0016
o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
B
A
C
D
E
F
Revisions Date
ACTUAL
NORTH
Date
Project No.
Drawing NO.
Project Title
Checked Drawn
Drawing Title
Approved:
DESIGN RENOVATION
FOR 4B CARDIOLOGY
SYRACUSE VAMC, SYRACUSE, NY
Project Director
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE PROFESSIONAL ENGINEER.
Reviewed: Facility Manager
Reviewed: Facility Director
Reviewed:
Reviewed:
2020-10-26
528A7-18-726
BID DOCUMENTS
FULLY SPRINKLERED
KEYPLAN
SH AE
AREA
OF
WORK
UP
DN
Scientists | Engineers | Program Managers
Mabbett & Associates, Inc.
105 Central Street, Stoneham, MA 02180
T.
781-275-6050 www.mabbett.com GC-100
4B FLOOR ICRA AND PHASING
PLAN-CONTRACTOR ACCESS
& SITE PLAN
SCALE: 1/32" = 1'-0"
F1
BASEMENT & PARTIAL SITE PLAN
SCALE: 1/8" = 1'-0"
D5
4TH FLOOR ICRA PLAN
Cradle
Extender
S
Cradle
Extender
C C
C1
C C
C C1 C
CC
C1
CC
B
B
B B B
B B
SD
SD
SD
OC
OC
SD
OC
S
S
GENERAL NOTES:
1. CONTRACTOR MUST FOLLOW ALL INFECTION CONTROL
PROCEDURES AND TEMPORARY CONSTRUCTION DEFINED IN
PROJECT MANUAL.
2. CONTRACTOR IS TO COORDINATE ALL WORK AND SCHEDULES
WITH VAMC COR. ROOMS SHOWN ARE NOT AVAILABLE FOR USE
CONCURRENTLY.
3. NEGATIVE PRESSURE MUST BE MAINTAINED 24/7 IN EACH
ACTIVE WORK AREA.
4. NO CONTRACTOR STORAGE IS ACCEPTABLE IN CORRIDORS.
ALL MATERIALS MUST BE CONTAINED IN THE ACTIVE WORK
AREA, OR ASSIGNED AREAS ACCEPTABLE TO THE COR.
5. ENTRY TO EACH ROOM IS TO BE SEALED W/ OVERLAPPING
REINF. FIRE RESISTANT PLASTIC PARTITION SUCH THAT
NEGATIVE AIR PRESSURE IS MAINTAINED BETWEEN CORRIDOR
& ROOM BY EXHAUSTING AIR OUT OF ROOM.
6. PROVIDE WALK OFF MATS AND PLASTIC ISOLATION INSIDE
EACH ROOM BY EACH DOOR. ALL VA EQUIPMENT & PROPERTY
MUST BE COVERED PRIOR TO WORK STARTING.
7. ALL CONTRACTOR EQUIPMENT/CARTS ETC... MUST BE WIPED
DOWN PRIOR TO ENTRY. ONCE IN, CARTS SHOULD BE WIPED
DOWN PRIOR TO RELOCATION TO NEW WORK AREA AND MUST
BE COVERED.
8. CONSTRUCTION ACTIVITIES CAN NOT HAPPEN
CONCURRENTLY IN CT SCAN 1 AND CT SCAN 2.
9. ALL THIRD FLOOR WORK WILL BE COMPLETED AFTER HOURS,
4PM-9PM.
B344
CT SCANNER2
B343
CONTROL ROOM 2
B342
MECH ROOM
B325
CORRIDOR
B341
CT SCANNER 1
B317
ANGIO
B318
OBSERVATION
B316
VESTIBULE
B316A
ELEC.
B316
SIEMENS EQUIPMENT
B314
PORTABLE C-ARM
B314A
ELEC.
B312
OFFICE
B320
CORRIDOR
B315
STORAGE
B313
STEP DOWN
B311
WAITINGB309
STORAGE
B311A
W/C
B307
IV ROOM
B340
STAFF
B338
OFFICE
B339
MECH ROOM
B336
OFFICE
B341A
CONTROL ROOM 1
A MINIMUM OF ONE CT SCAN
AND ITS ASSOCIATED CONTROL
ROOM MUST BE OPERATIONAL
AT ALL TIMES 24/7.
PROVIDE TEMPORARY PROTECTION OF ALL
MEDICAL EQUIPMENT DURING CONSTRUCTION
PROVIDE TEMPORARY
PARTITION BETWEEN CT ROOMS
DURING CONSTRUCTION
ACTIVITIES IN EITHER ROOM.
GENERAL NOTES:
1. DEMOLITION AND CONSTRUCTION THAT IS DISRUPTIVE TO THE
OWNER'S OPERATIONS ARE TO BE PERFORMED ONLY BETWEEN THE
HOURS OF 4:00 PM TO 9:00 PM. EXACT TIME TO BE COORDINATED W/
VAMC COR.
2. REFER TO SHEET AD-100 FOR EXISTING FLOOR PLAN CONFIGURATION.
3. CONTRACTOR TO MAINTAIN NEGATIVE AIR IN ALL CONSTRUCTION
AREAS. PROVIDE MANOMETER AT TEMPORARY WALL.
4. CONTRACTOR TO MAINTAIN AND PERFORM ALL INFECTION CONTROL
PROCEDURES REQUIRED BY VA AT ALL TIMES.
5. CONSTRUCTION ACTIVITIES CAN NOT HAPPEN CONCURRENTLY IN CT
SCAN 1 AND CT SCAN 2 OR THEIR RESPECTIVE CONTROL ROOMS.
6. REPLACE ALL GRID OR TILE THAT IS DAMAGED.
7. EXISTING CEILING MAY NOT REFLECT THE CONDITIONS & RCP SHOWN.
B344
CT SCANNER2
B343
CONTROL ROOM
B342
ELEC.
B325
CORRIDOR
B341
CT SCANNER 1
B317
ANGIO
B318
OBSERVATION
B316
VESTIBULE
B316A
ELEC.
B316
SIEMENS EQUIPMENT
B314
PORTABLE C-ARM
B314A
ELEC.
B312
OFFICE
B320
CORRIDOR
B315
STORAGE
B313
STEP DOWN
B311
WAITING
B309
STORAGE
B311A
W/C
B307
IV ROOM
B340
STAFF
B338
OFFICE
B339
MECH ROOM
B336
OFFICE
ALL WORK WITHIN THIS AREA MUST BE
PERFORMED IN ONE WEEKEND BETWEEN
5:00 PM FRIDAY AND 5:00 PM SUNDAY.
A Se rv ic e D i s a b le d Ve t e r an Owned
Sm a l l
B u s iness
SDVOSB
CVE
Location
Building Number
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0500-0016
o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
B
A
C
D
E
F
Revisions Date
ACTUAL
NORTH
Date
Project No.
Drawing NO.
Project Title
Checked Drawn
Drawing Title
Approved:
DESIGN RENOVATION
FOR 4B CARDIOLOGY
SYRACUSE VAMC, SYRACUSE, NY
Project Director
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE PROFESSIONAL ENGINEER.
Reviewed: Facility Manager
Reviewed: Facility Director
Reviewed:
Reviewed:
2020-10-26
528A7-18-726
BID DOCUMENTS
FULLY SPRINKLERED
KEYPLAN
SH AE
AREA
OF
WORK
UP
DN
Scientists | Engineers | Program Managers
Mabbett & Associates, Inc.
105 Central Street, Stoneham, MA 02180
T.
781-275-6050 www.mabbett.com GC-101
3B FLOOR ICRA AND PHASING
PLAN
SCALE: 1/8" = 1'-0"
D1
3RD FLOOR ICRA PLAN
SCALE: 1/8" = 1'-0"
D5
3RD FLOOR REFLECTED CEILING PLAN
UP
NON-RATED
1 HR FIRE BARRIER
2 HR FIRE BARRIER
SMOKE PARTITION
N O P Q
R S T U
EXISTING 4TH
FLOOR CENTER
SMOKE
COMPARTMENT
-ZONE 42
EXISTING 4TH
FLOOR B WING
SMOKE
COMPARTMENT
-ZONE 43
EXISTING
ZONE 40
EXAM/OFFICE
B444
EXAM/OFFICE
B442
EXAM/OFFICE
B440
EXAM/OFFICE
B438
EXAM/CHF
B436
SCREENING
B434
EXAM/OFFICE
B445
EXAM/OFFICE
B443
EXAM/OFFICE
B441
EXAM/OFFICE
B439
PACER
B437
SCREENING
B435
HAC
B407
CLEAN STORAGE
B433
CLEAN LINEN
B431
EXAM/OFFICE
B427
EXAM/OFFICE
B425
READING RM
B423
TLT
B426A
EXAM/OFFICE
B424
EXAM/OFFICE
B422
ECHO RM
B421
ECHO RM
B419
ECHO RM
B417
CHF INFUSION
B413
PUBLIC TLT
B432
SOILED HOLDING
B411
STRESS/ECHO TEST
B414
STRESS/ECHO TEST
B416
SCHEDULE
B408A
CASE MGR
B410
RECEPTION
B408
WAITING AREA
B406
ELEC
B418
OXYGEN
B415
STAFF WORK AREA
B426
ELEC
B409
CORRIDOR
B400C
CORRIDOR
B400A CORRIDOR
B400B
STAIR 5
4S5
E1.A
E2
E X
IS
T
IN
G
D E
A D
E N
D
3' -8
0'
-0
EXISTING DEAD END 82'-0" > 20'-0"
ZONE 75
E2.A
E3
E1
E3.A
4A
DOOR TO REMAIN. TO BE
REPAIRED & PREPARED
FOR PAINT.
1 - 1
TRAVEL DISTANCE
LINE TO EXIT
TRAVEL DISTANCE
PATH-SEE SCHEDULE
FOR DISTANCE
CODE SYNOPSIS
PROJECT OVERVIEW:
RENOVATE 4B FOR CARDIOLOGY, SYRACUSE VA MEDICAL CENTER
APPLICABLE CODES:
· NFPA 13-2019 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS
· NFPA 72-2019 NATIONAL FIRE ALARM CODE
· NFPA 90A-2018 STANDARD FOR THE INSTALLATION OF AIR CONDITIONING AND VENTILATING SYSTEMS
· NFPA 99-2018 STANDARD FOR HEALTH CARE FACILITIES
· NFPA 101-2018 LIFE SAFETY CODE
· NFPA 220-2018 STANDARD ON TYPES OF BUILDING CONSTRUCTION
· NFPA 291-2019 RECOMMENDED PRACTICE FOR FIRE FLOW TESTING AND MARKING OF HYDRANTS
· VA DESIGN GUIDE AND TECHNICAL GUIDE
· VA FIRE PROTECTION DESIGN MANUAL- DEC. 2015
· UNIFORM FEDERAL ACCESSIBILITY STANDARDS WITH VA BARRIER FREE DESIGN GUIDE (PG 18-13)
BUILDING USE CLASSIFICATION:
HEALTH CARE
HEALTH CARE OCCUPANCY (NFPA 101 - CHAPTER 18)
BUILDING CONSTRUCTION:
BUILDING STRUCTURE: STEEL COLUMNS/BEAMS, ENCASED IN CONCRETE, CONCRETE SLABS
NUMBER OF STORIES: ELEVEN (B, G, 1-9) PLUS PENTHOUSE
CONSTRUCTION TYPE: TYPE II (222) NFPA-101
SPRINKLER: FULLY SPRINKLERED IN ACCORDANCE WITH "NFPA 13-INSTALLATION OF SPRINKLER SYSTEMS"
FIRE EXTINGUISHERS: PROVIDE IN ACCORDANCE WITH "NFPA-10-PORTABLE FIRE EXTINGUISHERS" WITH TRAVEL DISTANCE - OF 75 FT.
MAX. ALLOWABLE NUMBER OF STORIES (ABOVE GRADE):
EXISTING
MAX ALLOWABLE AREAS:
LIFE SAFETY CODE: UNLIMITED
BUILDING COMPONENTS NFPA 220 2018
NFPA 101 2018
RATED CONSTRUCTION FIRE RATING
(IN HOURS)
EXTERIOR WALLS -
LOAD BEARING 2
NON-LOADBEARING 0
INTERIOR BEARING WALLS 2
EXIT, EXIT HALLWAY STAIRWAY 2
ENCLOSURE (4 OR MORE STORIES)
MECHANICAL SHAFTS, ELEVATOR HOIST WAYS (4 OR MORE) 2
EXIT ACCESS CORRIDORS 1 (SMOKE TIGHT)
HORIZONTAL EXITS NA
MIN. # OF EXITS/FLOOR (<500 OCCUP. LOAD) 2
(>501-1,000) 3
SMOKE BARRIERS 1
COLUMNS 2
COLUMNS (ROOF ONLY) 1
BEAMS 2
BEAMS (ROOF ONLY) 1
FLOOR CONSTRUCTION (INCLUDING BEAMS) 2
ROOF CONSTRUCTION
SOILED LINEN ROOMS 1 HR
STORAGE ROOMS MORE THAN 100 SF 1 HR
TRAVEL DISTANCE (FT)
· FROM ANY POINT TO EXIT (WITH AUTO FIRE SUPP. SYS) 200 FT (18.2.6.2.1) (E1)(E1.A)
· MAXIMUM DEAD END LENGTH REQUIRED 30 FT (18.2.5.2)
(SPRINKLERED BUILDING)
. FROM ANY POINT TO DOOR IN BUILDING SUBDIVISION 200 FT (18.3.7.1(5)) (E2) (E2.A)
SMOKE BARRIER. 100 FT (18.2.5.3) (E3)
. COMMON PATH OF TRAVEL
REQUIRED EGRESS WIDTH:
DOORWAYS 34" MIN.
STAIR DOORS 36" WIDE
STAIRS 44"
CORRIDOR WIDTH 96"
OPENING PROTECTIVES IN RATED CONSTRUCTION
DOORS IN 1 HR. RATED CONSTRUCTION (SELF-CLOSING, SELF LATCHING) 3/4 HR., LABEL "C"
DOORS IN 1 HOUR SMOKE BARRIER RATED BUILDING SUBDIVISION (SELF CLOSING) 20 MIN
SMOKECOMPARTMENT
. MINIMUM OF 2 PER FLOOR 18.3.7.1
. MAXIMUM OF 40,000 SF 18.3.7.1 (3)(C)
. IF LESS THAN 150 FT IN LENGTH OR WIDTH, TRAVEL DISTANCE TO SMOKE BARRIER
IS NOT LIMITED.
A Se rv ic e D i s a b le d Ve t e r an Owned
Sm a l l
B u s iness
SDVOSB
CVE
Location
Building Number
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0500-0016
o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
B
A
C
D
E
F
Revisions Date
ACTUAL
NORTH
Date
Project No.
Drawing NO.
Project Title
Checked Drawn
Drawing Title
Approved:
DESIGN RENOVATION
FOR 4B CARDIOLOGY
SYRACUSE VAMC, SYRACUSE, NY
Project Director
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE PROFESSIONAL ENGINEER.
Reviewed: Facility Manager
Reviewed: Facility Director
Reviewed:
Reviewed:
2020-10-26
528A7-18-726
BID DOCUMENTS
FULLY SPRINKLERED
KEYPLAN
SH AE
AREA
OF
WORK
UP
DN
Scientists | Engineers | Program Managers
Mabbett & Associates, Inc.
105 Central Street, Stoneham, MA 02180
T.
781-275-6050 www.mabbett.com AE-100
4B LIFE SAFETY PLAN
SCALE: NO SCALE
E9
GRAPHIC KEY
SCALE: 1/8" = 1'-0"
D5
REGULATORY PLAN
SCALE: NO SCALE
F1
CODE SUMMARY
SCHEDULE-TRAVEL DISTANCE PATHS
PATH LENGTH ALLOWED PATH TYPE
E1 89'-1" 200' EGRESS
E1.A 122'-4" 200' EGRESS
E2 110'-4" 200' BUILDING SUBDIVISION
E2.A 131'-9" 200' BUILDING SUBDIVISION
E3 85'-1" 100' COMMON PATH
E3.A 82'-11" 100' COMMON PATH
SCALE: NO SCALE
E7
TRAVEL DISTANCE
REMOVE EXISTING WD BLOCKING
REMOVE EXISTING SSM WINDOW SILL & STOOL
EXISTING PRECAST CONCRETE
WINDOW SILL TO REMAIN
EXISTING ALUMINUM WINDOW SYSTEM TO REMAIN
WINDOW JAMB BEYOND
EXISTING BRICK VENEER, CMU AND
PLASTER FINISH TO REMAIN
N O P Q R S T U
B426
B425B423B421
B424B422
B427
B418
B420
B419B417B415B413
B416B410B408B406B404
B411
B436
B440
B442
B444
B446
B439
B441
B443
B445
B447
B437
B407 B409
B439A
B413A
B416A
B414
R01
R01
R01
R01
R01
R01
R01
R01
R01
R01
R01
R01
R01 R01
R01
R01
R01 R01
R01
R01
R01
R01
R01
R01
R01
R01
R01
R01
R01
R01
R01
R01
R01
R01
R01
R01
R01
R01 R01 R01
R01
R01
R01
R01
R01 R01
R01
R01
R01
R01R01R01
R01
R01
R01
R01
R01
R01
R01
R01
R01R01R01
R01 R01
R02
R02
R02R02R02
R02R02R02
R02
R02
R02
R02
R02
R02R02R02R02R02
R02
R02
R02
R02 R02
R02 R02
R02 R02
R02
R02
R02
R02
R02
R02
R02 R02 R02 R02 R02
R02
R01
R16 R14
R16
R14
R16
R14
R16
R14
R16
R14
R16
R14
R16
R14
R16
R14
R16
R14
R16
R14
R16
R14
R16
R14
R16
R14
R16 R14 R16 R14 R16 R14 R16 R14
R16 R14 R16 R14 R16 R14 R16 R14
R16 R14 R16 R14 R16 R14 R16 R14
R16 R14 R16 R14
R16 R14 R16 R14 R16 R14 R16 R14R06R06R06
R06R06
R06R06R06R06
R06R13
R06
R13
R06
R06
R06
R06
R06
R06
R06
R06
R06
R06
R06
R06 R06 R06 R06
R06 R06 R06
R06
R06
R06
R06
R01
R01
R01
R01 R01 R01
R01 R01
R01
R01
R01
R01 R01
R01
R06
R06
R01
R06
R01
R01
R01R01
R01
R01
R01
R01
R06
R04R03R04R03R04R03
R04R03
R04R03R04R03R04R03R04R03R04R03R04R03R04R03
R04R03
R04R03
R04R03
R04R03
R04R03
R04R03
R04R03
R04R03
R04R03
R04R03
R04R03 R04R03
R04R03 R04R03 R04R03 R04R03
R04R03 R04R03
R04 R07
R04 R07 R04 R07
R04 R07
R04 R07
R01
R01 R01
R13
R13
R13
R13
R09
R05
R13
R08
4A
R06
R06
R08
R08
R02
R04R03 R04R03
R04R03
R01
R01
R01
R01
R01
R01
R01
R15
R06
R06
R10R10R10
R10R10
R10R10R10R10
R10
R10
R10
R10
R10
R10
R10
R10
R10
R10
R10
R10 R10 R10 R10
R10 R10 R10
R10
R10
R10
R12
R12
EXISTING FLOOR
EXISTING WALL
PORTION OF TERRAZZO
COVE TO BE REMOVED
REMOVE COMPLETELY AND
FILL FOR FLUSH FINISH AT
WALLS TO BE REMOVED
1. THE CONTRACTOR SHALL NOT CONSIDER DEMOLITION AND ALTERATION NOTES TO BE ALL-INCLUSIVE. IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO INSPECT AND ASSESS EACH AREA AND TO FULFILL THE DESIGN INTENT OF THE WORK INDICATED BY THE CONTRACT DOCUMENTS. ANY WORK NOT SPECIFICALLY SHOWN OR NOTED, BUT IS REASONABLY IMPLIED BY THE REMAINING DOCUMENTS WILL BE INCLUDED IN
THE CONTRACT.
2. THE CONTRACTOR SHALL VERIFY ALL CONDITIONS AND DIMENSIONS WITHIN THE CONTRACT LIMITS AND NOTIFY THE COR IMMEDIATELY IN WRITING OF ANY DEVIATION FROM CONTRACT DOCUMENTS NECESSITATED BY FIELD CONDITIONS OR ITEMS NOT COVERED.
3. DASHED LINES ON DEMOLITION PLANS REPRESENT WALLS, DOORS, SOFFITS, CEILINGS, CASEWORK, ETC. TO BE REMOVED.
4. FOR ALL SURFACES SCHEDULED TO REMAIN, PATCH, MATCH SURFACES DISTURBED BY DEMOLITION OR REMOVAL OF EQUIPMENT OR UTILITIES.
PROVIDE PATCHING TO MATCH ADJACENT WORK IN FINISH, STRUCTURAL QUALITIES, COURSING OF MASONRY AND OTHER CHARACTERISTICS.
PATCH SURFACES TO COMPLY WITH FIRE RATINGS, SMOKE-TIGHT RATINGS, ACOUSTICAL CRITERIA AND OTHER PERFORMANCE CRITERIA INDICATED. PREPARE SURFACES AS NECESSARY TO PROVIDE A PROPER SUBSTRATE FOR SPECIFIED FINISH. REFINISH ENTIRE SURFACE CORNER TO CORNER AS NECESSARY TO PROVIDE AN EVEN FINISH TO MATCH ADJACENT FINISH. ALL WORK SHALL REFLECT HIGHEST LEVEL OF INDUSTRY
STANDARDS FOR EACH TRADE.
5. ALL DEMOLITION SHALL BE PERFORMED IN A SAFE AND ACCEPTABLE MANNER TO ALL AUTHORITIES HAVING JURISDICTION AND THE OWNER. A FIRE
WATCH SHALL BE PROVIDED AS REQUIRED BY VAMC AND APPLICABLE CODES.
6. PROVIDE TEMPORARY PARTITIONS/DUST PROTECTION (RATED AND/OR NON-RATED) AS REQUIRED BY ICRA. REVIEW LOCATIONS OF TEMPORARY PARTITIONS/DUST PROTECTION WITH COR PRIOR TO START OF WORK. REFER TO ICRA & LIFE SAFETY PLANS.
7. HAZARDOUS MATERIAL NOTE: CONTRACTOR SHALL STOP WORK AND INFORM OWNER IMMEDIATELY IN WRITING OF ANY HAZARDOUS MATERIAL ENCOUNTERED OR THOUGHT TO BE HAZARDOUS. COR, AFTER RECEIVING WRITTEN NOTICE, SHALL INSTRUCT CONTRACTOR HOW TO PROCEED.
8. ALL WORK SHALL BE DONE IN PROTECTED SPACE. NO DUST, DIRT OR LIQUID SHALL TRAVEL FROM CONSTRUCTION AREA TO ADJACENT AREAS.
TEMPORARY ICRA PARTITIONS SHALL BE ERECTED PRIOR TO COMMENCING WORK. REFER TO ICRA & LIFE SAFETY PLANS.
9. PRIOR TO ANY DEMOLITION THE CONTRACTOR SHALL COORDINATE BRACING AND MAINTAIN THE STRUCTURAL INTEGRITY OF THE REMAINING
ELEMENTS OF THE BUILDING AND ITS SYSTEMS AS REQUIRED.
10. COMPLY WITH GOVERNING REGULATIONS PERTAINING TO ENVIRONMENTAL PROTECTION FOR POLLUTION CONTROL. THOROUGHLY CLEAN ADJACENT AREAS OF DUST, DIRT AND DEBRIS CAUSED BY DEMOLITION WORK. BEFORE NEW WORK BEGINS, RETURN ADJACENT AREAS TO
CONDITION FOUND PRIOR TO START OF DEMOLITION WORK.
11. CONTRACTOR SHALL COORDINATE ARCHITECTURAL DEMOLITION DRAWINGS AND NOTES WITH MEP/FP DRAWINGS AND NOTES. PATCH OR REBUILD
ANY AREAS TO REMAIN THAT HAVE BEEN DISTURBED BY MEP/FP DEMOLITION.
12. CONTRACTOR SHALL REVIEW ALL ITEMS TO BE DEMOLISHED WITH COR TO IDENTIFY ANY ITEMS TO BE SALVAGED PRIOR TO START OF DEMOLITION.
13. ALL MATERIALS AND ITEMS REMOVED BY CONTRACTOR, UNLESS OTHERWISE NOTED, BECOME HIS PROPERTY AND ARE TO BE REMOVED FROM THE
SITE IN CLOSED CONTAINERS ON A DAILY BASIS OR IN MANNER ACCEPTABLE TO COR.
14. CONTRACTOR SHALL PREPARE FLOOR SLABS PER THE SPECIFICATION SO FINISH FLOORS ARE FLUSH WITH EACH OTHER AND PREPARED TO
ACCEPT NEW FINISH.
15. MAINTAIN ACCESS TO EXITS AND EXIT STAIRS AT ALL TIMES. FIRE ALARM AND SMOKE DETECTION SYSTEM SHALL REMAIN OPERATIONAL AT ALL TIMES. PROTECT SMOKE DETECTORS AS REQUIRED AND IN CONFORMANCE WITH CODES AND LOCAL AUTHORITIES HAVING JURISDICTION.
16. PRIOR TO DEMOLITION, CONTRACTOR SHALL PERFORM A THOROUGH ABOVE-CEILING INSPECTION FOR EXISTING SERVICES THAT ARE TO REMAIN
AND NOTIFY COR IMMEDIATELY OF ANY CONFLICTS WITH INSTALLATION OF NEW WORK.
17. ALL DEMOLITION WORK SHALL BE DONE IN ACCORDANCE WITH PHASING PLANS. MAINTAIN 44" MINIMUM CLEARANCE AT ALL CORRIDORS AT ANY
GIVEN TIME.
18. AFTER DEMOLITION IS COMPLETED AND PRIOR TO THE START OF CONSTRUCTION WORK, CONTRACTOR TO INSTALL CEMENTITIOUS UNDERLAYMENT OVER THE ENTIRE SLAB IN THE PROJECT AREA APPROXIMATELY 6,415 SQ. FT. FILL/PLUG ALL HOLES WATER TIGHT PRIOR TO INSTALLING
UNDERLAYMENT.
REMOVE PIPE, SEE PLUMBING DWGS
16 GA POUR STOP
FLR TOPPING
FLR FINISH
A Se rv ic e D i s a b le d Ve t e r an Owned
Sm a l l
B u s iness
SDVOSB
CVE
Location
Building Number
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0500-0016
o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
B
A
C
D
E
F
Revisions Date
ACTUAL
NORTH
Date
Project No.
Drawing NO.
Project Title
Checked Drawn
Drawing Title
Approved:
DESIGN RENOVATION
FOR 4B CARDIOLOGY
SYRACUSE VAMC, SYRACUSE, NY
Project Director
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE PROFESSIONAL ENGINEER.
Reviewed: Facility Manager
Reviewed: Facility Director
Reviewed:
Reviewed:
2020-10-26
528A7-18-726
BID DOCUMENTS
FULLY SPRINKLERED
KEYPLAN
SH AE
AREA
OF
WORK
UP
DN
Scientists | Engineers | Program Managers
Mabbett & Associates, Inc.
105 Central Street, Stoneham, MA 02180
T.
781-275-6050 www.mabbett.com AD-101
4B DEMOLITION FLOOR PLAN
AND DETAILS
SCALE: 3/16" = 1'-0"
F1
FLOOR PLAN 4B-DEMO
KEYED NOTES-DEMOLITION
NUMBER COMMENT
R01 REMOVE MASONRY & PLASTER WALL SYSTEM, PATCH/REPAIR ANY FLOOR AND/OR CEILING SUBSTRATE DAMAGED BY REMOVAL. PREPARE EXISTING SUBSTRATE TO REMAIN AS REQUIRED TO RECEIVE NEW FINISH WORK. INFILL SLAB W/ CONC TO FLUSH W/ EXIST AT WALL REMOVALS. ALL WALL MOUNTED ACCESSORIES SHALL BE REMOVED AND DISPOSED OF. CONSULT WITH COR PRIOR TO REMOVAL TO DETERMINE WHAT ACCESSORIES ARE TO BE SALVAGED. REFER TO AB SERIES FOR AREAS WHERE THESE MATERIALS REQUIRE SPECIAL HANDLING.
R02 REMOVE DOOR, HM DOOR FRAME, HARDWARE AND ALL ASSOCIATED FASTENERS IN THEIR ENTIRETY.
R03 REMOVE VCT AND MASTIC FROM FLOOR SUBSTRATE, PATCH/REPARE ANY DAMAGE ASSOCIATED WITH REMOVAL AND PREPARE EXISTING SUBSTRATE TO RECEIVE NEW FINISH WORK. REFER TO AB SERIES DRAWINGS FOR AREAS WHERE THESE MATERIALS REQUIRE SPECIAL HANDLING.
R04 REMOVE ACOUSTICAL CEILING TILE, ASSOCIATED GRID, GWB SOFFITS, AND SUPPORT HANGERS. PATCH AND REPAIR ANY DAMAGE ASSOCIATED WITH REMOVAL AT EXISTING WALLS TO REMAIN. PREPARE WALLS TO RECEIVE NEW FINISH WORK AT EXISTING WALLS TO REMAIN.
R05 EXISTING CMU WALL & ELECTRICAL PANELS TO REMAIN.
R06 WALL TO REMAIN, ALL WALL MOUNTED ACCESSORIES SHALL BE REMOVED AND DISPOSED OF. VERIFY WITH COR PRIOR TO REMOVAL TO DETERMINE
WHAT ACCESSORIES THE OWNER WOULD LIKE TO SALVAGE.
R07 REMOVE FLOOR TILE AND SETTING BED, INFILL CONCRETE SLAB TO BE LEVEL WITH SURROUNDING SLAB.
R08 REMOVE WALL TILE AND SETTING MATERIAL ON WALLS TO REMAIN. PREPARE WALL FOR NEW FINISH.
R09 REMOVE CASEWORK AND ASSOCIATED HARDWARE & FASTENERS.
R10 REMOVE WALL BASES AND ANY ADHESIVES AND RESIDUES.
R12 DOOR TO REMAIN. PREP DOOR TO RECEIVE NEW PAINT.
R13 CUT/GRIND EXISTING COVED TERRAZZO BASE TO BE SQUARE AND FLUSH W/ EXIST FLOOR & WALL TO REMAIN. SEE DRAWING B8/AD-101 FOR PORTION
OF TERRAZZO COVE TO BE REMOVED.
R14 REMOVE WINDOW TREATMENTS AND ALL ASSOCIATED SUPPORTS AND HARDWARE.
R15 REMOVE DOOR & HARDWARE COMPLETELY. DOOR FRAME TO REMAIN. DOOR FRAME TO BE REPAIRED AND PREPARED TO BE PAINTED.
R16 REMOVE SSM WINDOW SILL AND PREP SURFACES TO RECEIVE NEW SILL.
SCALE: 1 1/2" = 1'-0"
B8
TERRAZZO COVE REMOVAL AT CORRIDOR WALLS
SCALE: NO SCALE
A8
REMOVAL KEYED NOTES
SCALE: NO SCALE
E8
GENERAL REMOVAL NOTES
SCALE: 1 1/2" = 1'-0"
F4
WINDOW SILL REMOVAL
SCALE: 1 1/2" = 1'-0"
E4
FLOOR PIPE PENETRATION INFILL
N O P Q R S T U
SCREENING
B434
SCREENING
B435
HAC
B407
CLEAN STORAGE
B433
CLEAN LINEN
B431
EXAM/OFFICE
B427
EXAM/OFFICE
B425
READING RM
B423
TLT
B426A
EXAM/OFFICE
B424
EXAM/OFFICE
B422
ECHO RM
B421
ECHO RM
B419
ECHO RM
B417
CHF INFUSION
B413
PUBLIC TLT
B432
SOILED HOLDING
B411
STRESS/ECHO TEST
B414
STRESS/ECHO TEST
B416
SCHEDULE
B408A
CASE MGR
B410
RECEPTION
B408
WAITING AREA
B406
ELEC
B418
/SEEE1 AS-101
OXYGEN
B415
STAFF WORK AREA
B426
ELEC
B409
CORRIDOR
B400C
CORRIDOR
B400A CORRIDOR
B400B
B435
B433 B432
B431
B407
EXG2
B409 B411 B413
B415
B417 B419 B421 B423
B426
B426A
B424B420B418B416B414
STAIR 5
4S5
F/E CLOS
B412
B412 B410B408
B408A
EXG3
EXG1
SCOPES
CR
CR CR
CR
AS-202
B1
A1
AS-200 A5
A3
A1
AS-200 C3C1
A8
AS-200D4
AS-200
D1
AS-200D2
AS-200C6
AS-201
E3
AS-201
E1
SHAFT 2
B424
1 A
1 A1 A1 A
1 A
1 A
1 A 1 A
1 A
1 A
6 A
1 A 1 A
1 A
4 A
4 A4 A
1 A
5 A 5 A 5 A
1 C
1 A
1 C
2 A 2 A
2 A
2 A 2 A
2 A
1.1 A
5 A 5 A
4 A 4 A
4 A
2 A
2 A
2 A
4 A
2 A
4 A
1 A
1 A 1 A 1 A
5 A
1 A
2 A
2 A
2 A
2 A 2 A2 A
2 A
4 A
AS-200 D6
1' -1
3/
4"
'-1 0"
1/
8" 8'
-4
/8
5/
7/
7' -0
6'
-6
1' -3
/4
10'-2 1/4"2'-8 1/2"6'-2"3'-6"
5' -8
/4
9'
-0
/8
8' -1
7/
8" 8'
-7
3 1/8"9'-4 1/8" ±9'-9"9'-9"9'-9"2'-11 1/2"4'-7"4'-10 3/8"2'-0 3/4"4'-8"1'-11 5/8"7'-10"
3'-5 1/2" 3'-9" 2'-1 5/8"
1/
4"
'-7
3/
3'
-3
/4
3' -4
/8
1'
-9
8' -0
9'-9 1/8"9'-9 1/8"9'-9 1/8"9'-11 1/4"9'-11 1/4"9'-11 1/4"9'-8 1/4"8'-5"13'-3 1/4"8'-9"5'-6 1/4"
'-8
/8
8'
-4
/8
'-1
/4
ALIGN
'-7
/4
'-0
/4
3' -8
/8
19'-6"19'-6"19'-6"19'-1"13'-4"9'-8"13'-0"9'-2 1/4" ±
10'-5 1/4"
'-1
0" 9'
-7
/1 6"
'-1
7/
'-3
/4
122'-9 1/4"
8' -0
8 C
8 C 8 C8 C 8 C 8 C8 C 8 C
2 A2 A2 A2 A2 A
9 A
2 A2 A
7 A7 A
7 A
2' -0
3'
-0
3' -0
3'
-0
3' -6
1.1 A1.1 A
1.1 A
1.1 A1.1 A
B422
B425 B427
5 A
TYP
AS-400
B9
TYP
AS-400
B9
TYP
AS-400
B9
1 C
7 C
1 C
1 C
AS-100
F1
1' -5
/4
4 A
5 A
6 A
6 A
AS-100
F2
EXISTING LAUNDRY
CHUTE TO REMAIN
AS-100
F4
AS-101
F5
AS-200 D8
AS-200D6
AS-200D6
AS-200 D6
EXISTING 14"x18" DUCT
TO REMAIN SEE HVAC
EXISTING 10"x10" DUCT
TO REMAIN SEE HVAC
2'-6"
6 A 1 A
EXG4S5
1.1 A
1.1 A1.1 A
1.1 A1.1 A
1.1 A1.1 A
1.1 A
1 A
1 A
1 A
4 A
7 A
7 A1 A1 A 1 A1 A1 A
1 A
8 C8 C 1 A
8 C8 C
8 C
2 A
2 A
2 A
4 A
1.1 A1.1 A
1.1 A1.1 A
9'-2 1/4" ± 13'-0"
4A
SIM
SIM
SIMSIM
SIM
EXISTING 10"x10" DUCT
TO REMAIN SEE HVAC
1.1 A
1.1 A
1.1 A
1.1 A
1.1 A
1.1 A
1.1 A
7 A
2' -6
/8
EXAM/OFFICE
B420
1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING ALL EXISTING CONDITIONS AND ESTABLISHING THE
COMPATIBILITY OF ALL NEW WORK WITH THE EXISTING CONDITIONS.
2. ALL WORK IS BEING DONE ADJACENT TO, ABOVE, & BELOW OCCUPIED SPACE. GENERAL CONTRACTOR TO TAKE EVERY PRECAUTION TO ELIMINATE THE TRAVEL OF LIQUID, DUST AND DIRT FROM THE CONSTRUCTION AREA TO
THOSE SPACES.
3. GENERAL CONTRACTOR SHALL TAKE EVERY PRECAUTION TO MINIMIZE DISRUPTION WITH ADJACENT OCCUPIED SPACE. SCHEDULE AND SEQUENCING OF WORK TO BE COORDINATED WITH COR PRIOR TO BEGINNING WORK (SEE
DWG GC-101)
4. GENERAL CONTRACTOR SHALL PATCH ALL SURFACES TO REMAIN EFFECTED BY DEMOLITION OR REMOVAL OF EXISTING EQUIPMENT & CONSTRUCTION. NEW SURFACES TO BE FILLED, SANDED SMOOTH & FINISHED TO MATCH
ADJACENT SURFACE.
5. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROVISION AND CONTINUOUS MAINTENANCE OF ALL WORK FROM DAMAGE AND SHALL PROTECT THE OWNERS' PROPERTY FROM DAMAGE OR LOSS BY DUST, DIRT, WATER, THEFT, FIRE OR ANY OTHER PHYSICAL DAMAGE IN CONNECTION WITH THE CONTRACT.
6. MAINTAIN EXISTING UTILITIES INDICATED TO REMAIN. KEEP IN SERVICE, AND PROTECT AGAINST DAMAGE DURING ALL RENOVATION WORK. GENERAL CONTRACTOR TO COORDINATE CONSTRUCTION AROUND EXISTING EQUIPMENT, CONDUIT CABLING, ETC. WITH COR AS REQUIRED TO MAINTAIN CONTINUOUS OPERATION.
7. GENERAL CONTRACTOR SHALL COORDINATE EXACT LOCATION OF ALL NEW EQUIPMENT TO BE INSTALLED IN
CEILING WITH EXISTING MECHANICAL AND ELECTRICAL WORK TO REMAIN IN PLACE.
8. COMPLY WITH GOVERNING REGULATIONS PERTAINING TO ENVIRONMENTAL PROTECTION FOR POLLUTION
CONTROL & HAZARDOUS MATERIALS.
9. ALL PENETRATIONS IN RATED ASSEMBLIES SHALL BE SEALED WITH UL/FM APPROVED MATERIAL ASSEMBLIES AND
PROCEDURES ALL PENETRATIONS SHALL BE SEALED ON BOTH SIDES OF PENETRATION.
10. ALL DIMENSIONS ARE FROM FINISH FACE OF WALL TO FINISH FACE OF WALL.
11. LOCATE ALL NEW DOORS 4" FROM INSIDE CORNER UNLESS NOTED OTHERWISE.
12. CONTRACTOR TO PROVIDE NON COMBUSTIBLE BLOCKING AS REQUIRED BEHIND ALL WALLS FOR PROPER
INSTALLATION OF BUMPER GUARDS, WALL MOUNTED EQUIPMENT, WALL CABINETRY, ETC.
13. DRAWINGS SHALL NOT BE SCALED AS A BASIS FOR ESTABLISHING DIMENSIONS OR OTHER INFORMATION.
CONTRACTOR TO VERIFY ALL DIMENSIONS.
14. TEMPORARY PARTITIONS SHALL BE TO UNDERSIDE OF DECK, BE RATED 2HR, BE PROPERLY SEALED, AND THE SPACES UNDER CONSTRUCTION MUST HAVE CONTINUOUS NEGATIVE PRESSURE WITHIN WORK SITE.
15. ALL PARTITIONS TO BE TYPE 1A UNLESS NOTED OTHERWISE.
T
CONTROL JOINT EACH SIDE
METAL TRIM EACH SIDE
VINYL WALL COVERING
1 A1 A
5 A
EXISTING STEEL &
CONCRETE COLUMN
CORNER GUARDS AT ECHO
& STRESS ECHO ROOMS
8 C
8 C 8 C
8 C
7/
5/
8"1' -1
/1
6"
FURRING AS REQUIRED
CORNER GUARDS AT ECHO
& STRESS ECHO ROOMS
4 A
6 A
1 A
1' -3
1'
-3
2' -6
RUN RC-1 CHANNEL
CONTINUOUS ON THIS SIDE
30" WALL CABINET ABOVE 30" WALL CABINET ABOVE
O
EXISTING CONCRETE &
STEEL COLUMN
ø 2'-1 1/8"
5/
" PRE-ROLLED & FINISHED .090"
ALUMINUM
ANCHOR SIDE
(FASTENED TO STUD)
VERTICAL BUTT JOINT
MTL STUD ANCHORED TO
EXISTING COLUMN
RECESSED BASE AND CAPITAL
DROP SIDE (KEY SLOT
ATTACHMENT TO ANCHOR)
A Se rv ic e D i s a b le d Ve t e r an Owned
Sm a l l
B u s iness
SDVOSB
CVE
Location
Building Number
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0500-0016
o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
B
A
C
D
E
F
Revisions Date
ACTUAL
NORTH
Date
Project No.
Drawing NO.
Project Title
Checked Drawn
Drawing Title
Approved:
DESIGN RENOVATION
FOR 4B CARDIOLOGY
SYRACUSE VAMC, SYRACUSE, NY
Project Director
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE PROFESSIONAL ENGINEER.
Reviewed: Facility Manager
Reviewed: Facility Director
Reviewed:
Reviewed:
2020-10-26
528A7-18-726
BID DOCUMENTS
FULLY SPRINKLERED
KEYPLAN
SH AE
AREA
OF
WORK
UP
DN
Scientists | Engineers | Program Managers
Mabbett & Associates, Inc.
105 Central Street, Stoneham, MA 02180
T.
781-275-6050 www.mabbett.com AS-100
PARTIAL 4B FLOOR PLAN &
DETAILS
SCALE: 1/4" = 1'-0"
D1
PARTIAL 4B FLOOR PLAN - SOUTH
SCALE: NO SCALE
F7
GENERAL PLAN NOTES
SCALE: 1 1/2" = 1'-0"
F1
PLAN DETAIL @ TYP CORRIDOR COLUMN
KEYED NOTES-PLAN
NUMBER COMMENT
01 ALIGN NEW WALL WITH WINDOW JAMB UNLESS CHASE
CAN BE SMALLER.
02 COAT RACK, PROVIDE BLOCKING, SEE ELEVATIONS.
03 (3) 12" x 18" LOCKERS PER EQUIPMENT PLAN.
04 (8) 12" x 18" LOCKERS PER EQUIPMENT PLAN.
05 ALIGN 1/2" RC-1 CHANNELS. SEE DTL F2/AS-100
06 EXISTING WALL TO REMAIN.
07 COORDINATE FINAL WALL LOCATION WITH EXISTING
CONDITIONS IN FIELD. NEW WALL TO BE LOCATED AS
TIGHT TO EXISTING PIPES/DUCTWORK AS POSSIBLE.
COORD W/ C.O.R.
08 PAINT EXISTING DOOR.
SCALE: NO SCALE
F6
GENERAL PLAN NOTES
SCALE: 1 1/2" = 1'-0"
F2
PLAN DETAIL @ BACK TO BACK SINKS
SCALE: 1 1/2" = 1'-0"
F4
PLAN DETAIL @ ROUND COLUMN
N O P Q
EXAM/OFFICE
B444
EXAM/OFFICE
B442
EXAM/OFFICE
B440
EXAM/OFFICE
B438
EXAM/CHF
B436
SCREENING
B434
EXAM/OFFICE
B445
EXAM/OFFICE
B443
EXAM/OFFICE
B441
EXAM/OFFICE
B439
PACER
B437
SCREENING
B435
CLEAN STORAGE
B433
/SEED1 AS-100
PUBLIC TLT
B432
CORRIDOR
B400C
B445
B443
B441
B439
B437
B435
AS-202 D1C1
AS-201
A6
A8 C6
2 A
2 A2 A
5 A 1 A
2 A2 A
5 A
2 A
5 A 2 A
5 A 2 A
5 A 2 A
1 A
4 A
2 A
4 A 4 A
2 A
5 A
5 A
2 A
2 A 5 A
5 A
2 A
1 A
1' -3
/4
9'
-8
/8
9' -8
/8
9'
-8
/8
9' -8
/8
9'
-8
/8
9' -8
/8
3/
4"
6 1/4"13'-3 7/8" ±8'-4 7/8"13'-6 3/4" ±2 1/4"
1' -4
/8
9'
-8
/8
9' -8
9'
-8
/8
9' -8
/8
9'
-8
/8
9' -8
/8
3/
4"
'-0
/4
'-6
'-6
'-0
/4
13'-0" 9'-8" 13'-4"
36'-0"
8'-0"
2 A 2 A2 A22 A
2 A2 A
2 A 8 C8 C8 C 8 C8 C
8 C
8 C8 C8 C
8 C8 C8 C
2 A
2 A2 A 2 A2 A
2 A
2 A2 A
2 A
2 A2 A
1 A
2 A2 A
1.1 A1.1 A
1 A
8 A
1 A 2 A2 A
2 A
B444
TYP
AS-400
B9
TYP
AS-400
B9
B434
B436
B438
B440
B442
D6
AS-202
AS-200
F8
AS-200
F8
F6
AS-600
5 A
4A
1 A
1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFYING ALL EXISTING CONDITIONS AND ESTABLISHING THE
COMPATIBILITY OF ALL NEW WORK WITH THE EXISTING CONDITIONS.
2. ALL WORK IS BEING DONE ADJACENT TO, ABOVE, & BELOW OCCUPIED SPACE. GENERAL CONTRACTOR TO TAKE EVERY PRECAUTION TO ELIMINATE THE TRAVEL OF LIQUID, DUST AND DIRT FROM THE CONSTRUCTION AREA TO
THOSE SPACES.
3. GENERAL CONTRACTOR SHALL TAKE EVERY PRECAUTION TO MINIMIZE DISRUPTION WITH ADJACENT OCCUPIED SPACE. SCHEDULE AND SEQUENCING OF WORK TO BE COORDINATED WITH COR PRIOR TO BEGINNING WORK (SEE
DWG GC-101)
4. GENERAL CONTRACTOR SHALL PATCH ALL SURFACES TO REMAIN EFFECTED BY DEMOLITION OR REMOVAL OF EXISTING EQUIPMENT & CONSTRUCTION. NEW SURFACES TO BE FILLED, SANDED SMOOTH & FINISHED TO MATCH
ADJACENT SURFACE.
5. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE PROVISION AND CONTINUOUS MAINTENANCE OF ALL WORK FROM DAMAGE AND SHALL PROTECT THE OWNERS' PROPERTY FROM DAMAGE OR LOSS BY DUST, DIRT, WATER, THEFT, FIRE OR ANY OTHER PHYSICAL DAMAGE IN CONNECTION WITH THE CONTRACT.
6. MAINTAIN EXISTING UTILITIES INDICATED TO REMAIN. KEEP IN SERVICE, AND PROTECT AGAINST DAMAGE DURING ALL RENOVATION WORK. GENERAL CONTRACTOR TO COORDINATE CONSTRUCTION AROUND EXISTING EQUIPMENT, CONDUIT CABLING, ETC. WITH COR AS REQUIRED TO MAINTAIN CONTINUOUS OPERATION.
7. GENERAL CONTRACTOR SHALL COORDINATE EXACT LOCATION OF ALL NEW EQUIPMENT TO BE INSTALLED IN
CEILING WITH EXISTING MECHANICAL AND ELECTRICAL WORK TO REMAIN IN PLACE.
8. COMPLY WITH GOVERNING REGULATIONS PERTAINING TO ENVIRONMENTAL PROTECTION FOR POLLUTION
CONTROL & HAZARDOUS MATERIALS.
9. ALL PENETRATIONS IN RATED ASSEMBLIES SHALL BE SEALED WITH UL/FM APPROVED MATERIAL ASSEMBLIES AND
PROCEDURES ALL PENETRATIONS SHALL BE SEALED ON BOTH SIDES OF PENETRATION.
10. ALL DIMENSIONS ARE FROM FINISH FACE OF WALL TO FINISH FACE OF WALL.
11. LOCATE ALL NEW DOORS 4" FROM INSIDE CORNER UNLESS NOTED OTHERWISE.
12. CONTRACTOR TO PROVIDE NON COMBUSTIBLE BLOCKING AS REQUIRED BEHIND ALL WALLS FOR PROPER
INSTALLATION OF BUMPER GUARDS, WALL MOUNTED EQUIPMENT, WALL CABINETRY, ETC.
13. DRAWINGS SHALL NOT BE SCALED AS A BASIS FOR ESTABLISHING DIMENSIONS OR OTHER INFORMATION.
CONTRACTOR TO VERIFY ALL DIMENSIONS.
14. TEMPORARY PARTITIONS SHALL BE TO UNDERSIDE OF DECK, BE RATED 2HR, BE PROPERLY SEALED, AND THE SPACES UNDER CONSTRUCTION MUST HAVE CONTINUOUS NEGATIVE PRESSURE WITHIN WORK SITE.
15. ALL PARTITIONS TO BE TYPE 1A UNLESS NOTED OTHERWISE.
6" 3'
-0
1' -6
1'
-6
3' -0
6"
2'-0" 9"
6 A
1X3 WOOD PAINTED TRIM. (EXTEND
FROM SILL TO UNDERSIDE OF
TRACK)
PROVIDE GWB "J" TRIM @ EDGE (TYP.)
CENTERLINE OF GLASS
SSM COUNTERTOP EXTENDS
THROUGH WINDOW OPENING.
SSM BACKSPLASH AND COUNTERTOP,
AS SCHEDULED.
6 A
1' -6
3'
-0
3' -0
3'
-0
1' -6
S S
M T
R A
N S
A C
T
IO
N C
O U
N T
E R
'-0
1.1 A
2 A
CONCEALED
COUNTER SUPPORT
BRACKET BELOW
LINE OF WOOD
WALL BELOW
GLASS DIVIDER PANEL
WITH CONCEALED
COUNTER SUPPORT
BRACKET BELOW
WALL PANEL WITH
1/4" Z CLIP SYSTEM
1 5/8" MTL STUDS
1X3 WOOD PAINTED TRIM. (EXTEND
FROM SILL TO UNDERSIDE OF
TRACK)
6"
COORD. WALL OPENING &
FRAMING WITH WINDOW MANUF.
F1
AS-200
3"3"
2"
2" GLASS SUPPORT ABOVE
A Se rv ic e D i s a b le d Ve t e r an Owned
Sm a l l
B u s iness
SDVOSB
CVE
Location
Building Number
Miller-Remick LLC
1010 KINGS HIGHWAY SOUTH
CHERRY HILL, NEW JERSEY 08034
PHONE: (856)429-4000
FAX: (856)429-5002
M.E.P. & Structural Engineering A Service Disabled Veteran Owned Small Business
MR PROJECT NO: 0500-0016
o n e e ig h th i n c h o n e f o o t
B
A
C
D
E
F th re e i n c h e s o n e f o o t 6 o n e a n d o n e h a lf i n c h e s o n e f o o t o n e i n c h o n e f o o t th re e q u a rt e rs i n c h o n e f o o t o n e h a lf i n c h o n e f o o t th re e e ig h th s i n c h o n e f o o t o n e q u a rt e r in c h o n e f o o t
VA FORM 08-6231
1 2 3 4 5 6 87 9
97 8654321
B
A
C
D
E
F
Revisions Date
ACTUAL
NORTH
Date
Project No.
Drawing NO.
Project Title
Checked Drawn
Drawing Title
Approved:
DESIGN RENOVATION
FOR 4B CARDIOLOGY
SYRACUSE VAMC, SYRACUSE, NY
Project Director
MILLER-REMICK LLC
PROFESSIONAL ENGINEER
PRINTS OF THIS DRAWING SHALL NOT BE USED FOR ANY PURPOSE
WHATSOEVER WITHOUT THE SEAL AND SIGNATURE OF THE PROFESSIONAL ENGINEER.
Reviewed: Facility Manager
Reviewed: Facility Director
Reviewed:
Reviewed:
2020-10-26
528A7-18-726
BID DOCUMENTS
FULLY SPRINKLERED
KEYPLAN
SH AE
AREA
OF
WORK
UP
DN
Scientists | Engineers | Program Managers
Mabbett & Associates, Inc.
105 Central Street, Stoneham, MA 02180
T.
781-275-6050 www.mabbett.com AS-101
PARTIAL 4B FLOOR PLAN &
DETAILS
SCALE: 1/4" = 1'-0"
E1
PARTIAL 4B FLOOR PLAN - NORTH
SCALE: NO SCALE
F7
GENERAL PLAN NOTES
SCALE: 1 1/2" = 1'-0"
F5
PLAN DTL - RECEPTION WINDOW FRAMING
KEYED NOTES-PLAN
NUMBER COMMENT
01 ALIGN NEW WALL WITH WINDOW JAMB UNLESS CHASE
CAN BE SMALLER.
02 COAT RACK, PROVIDE BLOCKING, SEE ELEVATIONS.
03 (3) 12" x 18" LOCKERS PER EQUIPMENT PLAN.
04 (8) 12" x 18" LOCKERS PER EQUIPMENT PLAN.
05 ALIGN 1/2" RC-1 CHANNELS. SEE DTL F2/AS-100
06 EXISTING WALL TO REMAIN.
07 COORDINATE FINAL WALL LOCATION WITH EXISTING
CONDITIONS IN FIELD. NEW WALL TO BE LOCATED AS
TIGHT TO EXISTING PIPES/DUCTWORK AS POSSIBLE.
COORD W/ C.O.R.
08 PAINT EXISTING DOOR.
SCALE: NO SCALE
F1
GENERAL PLAN NOTES
4"
1'-0"
1"
2' -1
0" S
E E
E
LE
V A
T
IO
N
4"6"
S E
E E
LE
V
A T
IO
N
SSM-1 COUNTER SEE
FINISH SCHEDULE
SEE INTERIOR ELEVATION
AS TO FUNCTION OF BASE
CABINET SEE FINISH
SCHEDULE
PLYWOOD TOE
KICK W/
SCHEDULED BASE
FINISH
MELAMINE INTERIORS AND
ADJUSTABLE SHELVES
SCHEDULED
FLOORING
FIN FLOOR
+0"
+34"
AFF
UNDER CABINET LIGHT W/
CONCEALED WIRING (SEE
ELEC DWGS)
SEE ELEVATIONS
WALL CABINETS SEE
ELEVATIONS
+7'-1"
FILLER
BULK HEAD SEE DETAIL B8
/ AS-501 PNT
S E
E E
LE
V
A T
IO
N
S
6"
1 / 4
1"
1/
2"
2' -3
M
IN 2'
-1
0"
FIN FLOOR
+0"
+34"
AFF
SCHEDULED FLOORING
1/2" THICK 4" HEIGHT SSM
SEE FINISH SCHEDULE
SST SINK
SSM-1 COUNTER
SEE FINISH SCHEDULE
VB
FIXED FRONT PANEL
FACE SCREWED IN
PLACE.
+7'-1"
BULK HEAD SEE DETAIL B8
/ AS-501 PNT
UNDER CABINET LIGHT
(SEE ELEC DWGS)
WALL CABINETS SEE
ELEVATIONS
FILLER
PIPE COVERS ON
SUPPLIES AND DRAIN
RAKKS SYSTEM
BRACKETS
8' -0
VB-2
WALL PROTECTION WP-1
6" 2'
-6
5' -0
CHAIR RAIL
INPRO 2700, OATMEAL
WALL PROTECTION WP-1
8' -0
3' -0
5'
-0
VB-2
SSM-2 SSM-2
CHAIR RAIL
INPRO 2700, OATMEAL
A9
AS-400
B9
AS-400
C9
AS-400
GWB (PNT-2)
TYP.
TYP.
TYP.
WP-2
WP-1
WP-2
IMPACT RESISTANT
CORNER GUARD, PNT TO
MATCH PNT-2
FRY REGLET WCTOSC TRIM AT
OUTSIDE CORNERS OF WP-2
F1
AS-200
METAL REVEAL WALL BASE,
FRY REGLET MWCB75400
CLEAR ANNODIZED ALUM
(OR EQUIVALENT).
WOOD WALL
PANELS WD-1
7' -9
FLOATING TRANSACTION
COUNTER, SSM-1
3"
ACRYLIC PRIVACY PANEL, AR-1
WITH ALUMINUM CLIPS.
3/8" TEMPERED GLASS TRANSACTION
WINDOW. FRAMELESS GLASS IN
SYNCHRONIZED BI-PARTING POCKET
FRAME.
4' -2
2'
-1 0"
FRY REGLET MILLWORK
CHANNEL - OUTSIDE CORNER
WITH RETURN KEYS.
MWCOSC75 CLEAR
ANNODIZED ALUMINUM (OR
EQUIVALENT).
FRY REGLET MILLWORK
CHANN…