523 19 602 Drawings Pages 31 to 68.pdf

PDF 10 MB Posted

Attached to
Z2DA--VISN 1 Construction MATOC Federal contract opportunity
Solicitation number
36C24123R0073
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 1

About this file

This file appears to contain technical drawings in support of a federal construction contract opportunity issued by the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 1. The solicitation seeks construction services under a multiple award task order contract (MATOC) for VISN 1, with an identification number 36C24123R0073. Awards will be made to multiple vendors to provide indefinite delivery indefinite quantity construction services on an as-needed basis. Response submission dates, initial and maximum contract terms, and other salient procurement details are not specified in the drawings appendix file.

View the file

Other files for this federal contract opportunity

Other files attached to Z2DA--VISN 1 Construction MATOC, newest first.
File Type Posted
36C24123R0073 0018.pdf PDF
36C24123R0073 0017.pdf PDF
SSJ Electronic Safety and Security_.pdf PDF
523-19-602 Seed Project Site Visit 2 Attendees.pdf PDF
WD MA20220001 Effective 10132023.pdf PDF
GENERAL CONTRACT REQUIREMENTS SECTIONS 01000 01001 01300 01451 01700 A0016.pdf PDF
523 19 602 Drawings Pages 31 to 68 A0016.pdf PDF
WD MA20230001 Effective 10202023 A0016.pdf PDF
SSJ Lock Systems A0016.pdf PDF
SSJ Fire Alarm System A0016.pdf PDF
SSJ Electronic Safety and Security A0016.pdf PDF
Exhibit B Past Performance Questionnaire A0016.pdf PDF
523 19 602 Drawings Pages 24 to 30 A0016.pdf PDF
523-19-602 523-19-602 Install Site Security Revised Specs A0016.pdf PDF
SSJ DDC BMS A0016.pdf PDF
523-19-602 Seed Project PCRA A0016.pdf PDF
Updated MATOC Solicitation Instructions.pdf PDF
Exhibit D Proposal Inquiry Form A0016.pdf PDF
Exhibit A Project Information Sheet for Contractors A0016.pdf PDF
36C24123R0073 0013.pdf PDF
36C24123R0073 0012.pdf PDF
36C24123R0073 0011.pdf PDF
SSJ Fire Alarm System.pdf PDF
WD MA20230001 Effective 09152023.pdf PDF
SSJ Electronic Safety and Security.pdf PDF
36C24123R0073 0010.pdf PDF
36C24123R0073 0009.pdf PDF
S02 36C24123R0073 0007.pdf PDF
S06 MATOC RFIs Amendment 6.pdf PDF
Amendment 5 MATOC RFIs.pdf PDF
Exhibit G VA PAY FORM w-Monthly checklist.docx DOCX document
MATOC RFIs.pdf PDF
Summary of changes to the RFP.pdf PDF
Seed Project 523-19-602 Install Site Security Site Visit Sign In Sheet.pdf PDF
36C24123R0073 0003.pdf PDF
Parking.PNG PNG image
36C24123R0073 0002.pdf PDF
WD MA20230001 Effective 07212023.pdf PDF
523 19 602 Project Manual Part 1.pdf PDF
523 19 602 Drawings Pages 24 to 30.pdf PDF
523 19 602 Drawings Pages 19 to 23.pdf PDF
Exhibit A Project Information Sheet for Contractors.pdf PDF
36C24123R0073 Solicitation.docx DOCX document
523 19 602 Drawings Pages 10 to 18.pdf PDF
523 19 602 Drawings Pages 1 to 9.pdf PDF
523 19 602 Task Order RFP.pdf PDF
Exhibit F Price Schedule Sheet.pdf PDF
SPECIAL MATOC REQUIREMENTS.pdf PDF
GENERAL CONTRACT REQUIREMENTS SECTIONS 01000 01001 01300 01451 01700.pdf PDF
523 19 602 Project Manual Part 2.pdf PDF
Show all 50

Z2DA--VISN 1 Construction MATOC has more files on GovTribe.

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

100% BID DOCUMENTSOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

17 MARCH 2023Revisions: Date:

CAMPUS

523-19-602

150 SOUTH HUNTINGTON AVENUE, BOSTON MA

VAMC BOSTON

JAMAICA PLAIN CAMPUS

SITE SECURITY UPGRADES

THINKFORM DESIGN ARCHITECT LLC

38 EAST BROAD STREET

HOPEWELL, NJ 08525

T:855.821.0274 F:609.644.4397 Russell DiNardo, AIA NY 031521-1

A/E:

WATSON ENGINEERING

4500 STATE ROUTE 434

APALACHIN, NY 13732

PHONE: (607) 223-4334

EMW MAK

E-001

ELECTRICAL NOTES AND SYMBOLS

GENERAL ELECTRICAL NOTES:

1. THE GENERAL ELECTRICAL NOTES ON THIS SHEET APPLY TO ALL THE ELECTRICAL DRAWINGS.

2. IT IS THE ELECTRICAL CONTRACTOR'S RESPONSIBILITY TO FIELD VERIFY ALL ASPECTS OF THE DESIGN, TO INCLUDE THE WORK OF SUB-TRADES, PRIOR

TO SUBMITTING A BID.

3. BECAUSE OF THE SMALL SCALE OF THE DRAWINGS, IT IS NOT POSSIBLE TO INDICATE ALL OFFSETS, TRANSITIONS, FITTINGS, CLEARANCES, POSSIBLES

CLASHES, AND ACCESSORIES THAT MAY BE REQUIRED. COORDINATE ALL THE WORK OF ALL THE TRADES TO ENSURE ALL DUCTS, PIPES, CONDUITS, ETC.

DO NOT CONFLICT AND CLEAR STRUCTURAL AND ARCHITECTURAL MEMBERS. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR DEVELOPING

COORDINATED SHOP DRAWINGS FOR REVIEW PRIOR TO STARTING INSTALLATION.

4. ELECTRICAL CONTRACTOR SHALL VISIT THE SITE AND BE FULLY COGNIZANT OF ALL CONDITIONS PRIOR TO SUBMITTING BID. REPORT ANY

DISCREPANCIES TO THE ENGINEER PRIOR TO SUBMITTAL OF BID.

5. THE WORK INCLUDES ALL ITEMS OF THE ELECTRICAL SPECIFICATIONS THAT ARE EITHER WRITTEN ON THE DRAWINGS OR SEPARATELY IN A

SPECIFICATIONS BOOK.

6. WHERE THERE IS A CONFLICT ON THE PLANS, SPECIFICATIONS, NOTES, GENERAL NOTES, REFERENCES, PUBLICATIONS, CODES, ETC. WITH RESPECT TO CONSTRUCTION, MATERIALS, PRODUCTS, METHODS, WORKMANSHIP, PROCEDURE, EXECUTION, ETC. THE MOST STRINGENT SHALL BE UTILIZED OR INSTALLED. THE MOST STRINGENT SHALL BE DEFINED AS THE SPECIFICATION OR REQUIREMENT THAT ALLOWS ALL SPECIFICATIONS OR REQUIREMENTS THAT ARE IN CONFLICT TO BE SATISFIED. NO RELIEF OR EXTRA PAYMENT SHALL BE MADE TO THE CONTRACTOR BECAUSE OF THIS INTERPRETATION.

7. ELECTRICAL CONTRACTOR SHALL NOT BEGIN FABRICATION, CUT ANY MEMBERS, OR BEGIN INSTALLATION UNTIL THE SUBMITTALS AND COORDINATED SHOP DRAWINGS HAVE BEEN APPROVED. ANY WORK CONSTRUCTED OR INSTALLED PRIOR TO THE APPROVAL OF SUBMITTALS AND COORDINATED SHOP DRAWINGS SHALL BE AT THE ELECTRICAL CONTRACTOR'S RISK AND SHALL BE REMOVED AND REINSTALLED OR RECONSTRUCTED AT THE ELECTRICAL CONTRACTOR'S EXPENSE AT THE REQUEST OF THE OWNER'S REPRESENTATIVE TO THE COMPLETE SATISFACTION OF THE OWNER'S REPRESENTATIVE.

8. UNLESS STATED OTHERWISE, ALL EXISTING MATERIAL AND EQUIPMENT SHALL REMAIN THE PROPERTY OF THE PROJECT OWNER.

9. THE ELECTRICAL CONTRACTOR SHALL DEVELOP AND PRESENT A CONSTRUCTION PLAN AND WORK SCHEDULE WITH ALL PHASING, STAGING, AND

SEQUENCING OF WORK FOR APPROVAL PRIOR TO THE COMMENCEMENT AND BEGINNING IMPLEMENTATION OF HIS WORK. THE ELECTRICAL CONTRACTOR SHALL DETERMINE PRIOR TO SUBMITTING HIS WORK SCHEDULE, THE SPECIFIC TIME AVAILABILITY OF ALL AREAS AND SPACES AND

DETERMINE WHAT WORK MUST BE DONE DURING "OFF HOURS".

10. WITH THE EXCEPTION OF SIGNIFICANT NOISE GENERATING ACTIVITIES SUCH AS CORE DRILLING, ETC., WORK OUTSIDE OF THE OCCUPIED SPACES, SUCH

AS ON THE ROOF, ETC., MAY BE PERFORMED DURING NORMAL WORKING HOURS.

11. UNLESS SPECIFICALLY NOTED AS EXISTING, ALL ITEMS, EQUIPMENT, AND WORK SHOWN IS NEW AND SHALL BE FURNISHED AND INSTALLED BY THE

ELECTRICAL CONTRACTOR.

12. DURING THE EXECUTION OF THIS CONTRACT, THE SITE AND BUILDINGS WILL BE OCCUPIED AND IN USE. WORK DONE UNDER THIS CONTRACT SHALL BE PERFORMED WITHOUT INCONVENIENCE TO THE OWNER INSOFAR AS POSSIBLE. ALL WORK SHALL BE COORDINATED WITH THE OWNER'S

REPRESENTATIVE AND IS SUBJECT TO THEIR CONTINUOUS APPROVAL.

13. THE CONTRACTOR IS COMPLETELY RESPONSIBLE FOR ALL CHARACTERISTICS OF THE EQUIPMENT THAT HE INTENDS TO INSTALL AND MUST FOLLOW MANUFACTURER RECOMMENDATIONS FOR PROPER INSTALLATION. IF THERE ARE ANY DIFFERENCES IN THE EQUIPMENT SHOWN ON THE DESIGN DRAWINGS AND THE EQUIPMENT TO BE INSTALLED, THE ELECTRICAL CONTRACTOR SHALL MAKE ALL CHANGES AND ADJUSTMENTS TO ACCOMMODATE THE PROPOSED EQUIPMENT AT NO ADDITIONAL COST TO THE OWNER. THIS APPLIES TO ALL SUPPORT SERVICES AND FACILITIES NECESSARY TO PROPERLY INSTALL THE EQUIPMENT TO FUNCTION ADEQUATELY AS PART OF THE SYSTEMS FOR WHICH THEY WERE DESIGNED AND SELECTED. THESE CHARACTERISTICS INCLUDE SUCH THINGS AS WEIGHT, CLEARANCE, DIMENSIONS, ELECTRICAL, MECHANICAL, PLUMBING, AND UTILITY SERVICES, ETC.

ACCOMMODATING SERVICES INCLUDE SUCH THINGS AS DIMENSIONS, LOCATIONS, AND SIZES OF SUPPORTING MEMBERS, PIPE, CONNECTION SIZES, ELECTRICAL SERVICE SIZE AND PROTECTION, ELECTRICAL CONNECTION LOCATION, UTILITY AND PLUMBING CONNECTION SIZES AND LOCATIONS, ETC.

ALL REQUIRED CHANGES TO THE CONTRACT DRAWINGS AND SPECIFICATIONS SHALL BE DESIGNED AND STAMPED BY REGISTERED ENGINEERS IN THE APPROPRIATE DISCIPLINE EMPLOYED BY THE ELECTRICAL CONTRACTOR AND SHALL BE INCLUDED AS PART OF THE EQUIPMENT SUBMITTALS. ALL CHANGES SHALL BE SUBJECT TO THE APPROVAL OF THE PROJECT A/E AND THE OWNER'S REPRESENTATIVE.

14. BEFORE ANY DEMOLITION OR CONSTRUCTION WORK IS BEGUN, THE ELECTRICAL CONTRACTOR AND THE OWNER'S REPRESENTATIVE SHALL SURVEY THE EXISTING BUILDING AREA TO BE MODIFIED AND/OR REPLACED TO ACCURATELY DOCUMENT EXISTING CONDITIONS. THIS SURVEY WILL BE USED BY THE OWNER'S REPRESENTATIVE AT JOB COMPLETION TO DETERMINE WHICH BUILDING/SITE COMPONENTS MUST BE REPLACED WITH NEW.

15. UNLESS STATED OTHERWISE, REQUEST APPROVAL FROM THE OWNER'S REPRESENTATIVE SEVEN DAYS IN ADVANCE FOR THE SHUTDOWN OF ANY

EXISTING SYSTEM.

16. UNLESS STATED OTHERWISE, FINAL ADVANCE NOTICE OF 48 HOURS SHALL BE GIVEN TO THE OWNER'S REPRESENTATIVE PRIOR TO THE PROPOSED

SHUTDOWN OF ANY SYSTEM.

17. PROVIDE ADEQUATE FIRE PROTECTION IN THE ENTIRE CONSTRUCTION AREA FOR THE DURATION OF THE CONSTRUCTION PERIOD. COORDINATE WITH

INSTALLING FIRE PROTECTION CONTRACTOR.

18. ELECTRICAL CONTRACTOR SHALL NOT PENETRATE OR CUT ANY STRUCTURAL MEMBERS NOT SPECIFICALLY SHOWN ON THE DRAWINGS (E.G., JOISTS, BEAMS, ETC.). IF STRUCTURAL MEMBERS CONFLICT WITH ROUTING, CONTACT THE OWNER'S REPRESENTATIVE FOR DIRECTION BEFORE PROCEEDING.

EXERCISE CAUTION IN CUTTING CONCRETE FLOORS AND WALLS TO AVOID EXISTING UTILITIES WHICH MAY BE LOCATED IN AND UNDER CONCRETE

SURFACES.

19. THE ELECTRICAL CONTRACTOR SHALL PROVIDE NEW OPENINGS IN WALLS, FLOOR, AND ROOF, AND PATCH EXISTING OPENINGS IN CONJUNCTION WITH THE DEMOLITION AND INSTALLATION OF THE NEW BUILDING COMPONENTS. ALL NECESSARY FRAMING, COUNTER-FLASHING, ETC. SHALL BE INCLUDED.

20. FOR ALL FLOOR, WALL, AND ROOF PENETRATION, VERIFY THE LOCATION OF THE EXISTING STRUCTURAL MEMBERS PRIOR TO DRILLING AND CUTTING, RELOCATE OPENINGS AS REQUIRED AND OFFSET DUCTS, PIPES, CONDUIT, ETC.

21. EXISTING DUCTWORK, DOMESTIC COLD WATER PIPING, DOMESTIC HOT WATER PIPING, CHILLED AND HEATING HOT WATER PIPING, WASTE, VENT, FIRE SPRINKLER LINES, FIRE ALARM EQUIPMENT, ELECTRICAL CONDUIT, TELEPHONE CONDUIT, COMMUNICATION CONDUIT, PNEUMATIC TUBING, ETC., MAY HAVE TO BE RELOCATED TO FACILITATE THE INSTALLATION OF THE NEW WORK. THE CONTRACTOR SHALL DETERMINE ALL EXISTING SERVICES THAT REQUIRE RELOCATION PRIOR TO SUBMITTING HIS BID AND INCLUDE ALL COSTS IN THE BID. THERE WILL BE NO EXTRA COMPENSATION TO THE

CONTRACTOR FOR THIS WORK.

22. THE CONTRACTOR IS HEREBY NOTIFIED THAT SOME WORK MAY BE REQUIRED OUTSIDE OF THE AREAS SHOWN ON THESE DRAWINGS. THIS COULD INCLUDE ELECTRICAL WORK, REFRIGERANT LINE ROUTING, CONTROL MODIFICATIONS OR CONNECTIONS AT REMOTE LOCATIONS, CONTROL PANELS, CPU'S, ETC.

23. THE CONTRACTOR SHALL PAY FOR ALL DAMAGE, INCLUDING WATER DAMAGE, TO PROPERTY AND EQUIPMENT CAUSED BY HIS WORK THROUGHOUT THE

CONSTRUCTION AND WARRANTEE PERIOD.

24. PATCH AND PAINT TO MATCH EXISTING, ALL SURFACES DAMAGED BY THE DEMOLITION AND ALL OPENINGS NOT TO BE REUSED.

25. REPAIR DAMAGE TO CEILING, WALLS, ETC. TO THE SATISFACTION OF THE OWNER'S REPRESENTATIVE.

26. WHEN A DETAIL OR NOTE IS IDENTIFIED AS TYPICAL, THE ELECTRICAL CONTRACTOR IS TO APPLY THE DETAIL OR NOTE TO EVERY SIMILAR CONDITION, WHETHER OR NOT THE REFERENCED DETAIL OR NOTE IS REPEATED OR REFERENCED.

27. WHERE NO CONSTRUCTION DETAIL IS INDICATED, SUCH WORK SHALL BE SIMILAR TO COMPARABLE WORK DETAILED OR NOTED ELSEWHERE OR TO

MATCH EXISTING CONDITIONS, SUBJECT TO THE APPROVAL OF THE OWNER'S REPRESENTATIVE.

28. THE DEMOLITION SHALL INCLUDE ALL ASSOCIATED ANCHORAGES, HANGERS, SUPPORTS, BRACES, FASTENERS, MASTIC, MORTAR, LATH, AND RELATED

ITEMS. THE EXISTING SUBSTRATE, INCLUDING CONCRETE, MASONRY, METAL FRAMING AND FURRING SHALL BE REPAIRED WHERE DAMAGE BY THE

CONTRACTOR'S WORK.

TIME CLOCK

R

RECTIFIER, CATHODIC PROTECTION SANITARY

ELECTRICAL STRIP MOLD (OUTLETS ON 2'-0" [610mm] CENTERS OR AS DESIGNATED ON DRAWINGS), MTD 3'-6" [1067mm] AFF OR AS

INDICATED.

3-GANG COMPARTMENT BOX IN FLOOR FOR TELEPHONE, DATA &

RECEPTACLE.

DISCONNECT SWITCH, FUSED

DISCONNECT SWITCH, UNFUSED

STARTER, COMBINATION WITH DISCONNECT SWITCH

STARTER OR MOTOR CONTROLLER

POTHEAD

STRESS CONE

VENTILATOR OR FAN COIL UNIT OUTLET

CONDUIT TERMINATED 6" AFF IN STANDARD BOX FOR

EXTENSION TO EQUIPMENT AS DIRECTED.

CONDUIT TERMINATED W/COUPLING (FLUSH W/FINISHED

FLOOR) FOR EXTENSION TO EQUIPMENT AS DIRECTED.

ELECTRICAL SYMBOLS - POWER PLAN

JUNCTION BOX

TRANSFORMER, PLAN

MOTOR, SINGLE-PHASE

MOTOR, THREE-PHASE

WYE CONNECTION

DUCT, CELL FLOOR HEADER

DUCT, TROLLEY

DUCT, UNDERFLOOR JUNCTION BOX

EARTH GROUND

LADDER CABLE TRAY

BRANCH CIRCUIT HOMERUN. LINES INDICATE NUMBER

OF CIRCUITS, NEUTRAL, AND SWITCH LEG CONDUCTORS.

ONE SEPARATE GREEN GROUNDING CONDUCTOR SHALL

BE PROVIDED FOR EACH HOMERUN; NOT SHOWN

PULL BOX

WIREWAY

RIGID CONDUIT LINE = RC

SUBSTATION

BUSWAY

FLOOR OUTLET, DATA COMMUNICATION

OUTLET, DATA COMMUNICATION

PUSH BUTTON

DISTRIBUTION PANEL

LIGHTING PANEL

PANELBOARD CABINET, FLUSH MOUNTED

PANELBOARD CABINET, SURFACE MOUNTED

RECEPTACLE, CLOCK HANGER

RECEPTACLE, DUPLEX

RECEPTACLE, DUPLEX ON EMERGENCY POWER

RECEPTACLE, DUPLEX WITH GROUND FAULT CIRCUIT INTERRUPTER

RECEPTACLE, QUADRAPLEX

RECEPTACLE, SINGLE

RECEPTACLE, SINGLE WITH SWITCH

RECEPTACLE, SPECIAL PURPOSE

A = 120V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 5-20R.

B = 208V, 20A, 1 PHASE, 2-POLE, 3W, NEMA 6-20R.

C = 120V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 5-30R.

D = 208V, 30A, 1 PHASE, 2-POLE, 3W, NEMA 6-30R.

E = 208V, 60A, 1 PHASE, 3-POLE, 4W, NEMA 14-60R.

F = 208V, 30A, 3 PHASE, 3-POLE 4W, NEMA 15-30R.

G = 208V, 50A, 3 PHASE, 3 POLE, 4W, NEMA 15-30R.

H = 208V, 60A, 3 PHASE, 3 POLE, 4W, NEMA 15-60R.

RECEPTACLE, SWITCHED DUPLEX

DIRECT BURIAL CABLE = DB

POWER DUCT DIRECT BURIED

PVC CONDUIT MIN 18" DEPTH = P

HI VOLTAGE SWITCH ON CONCRETE PAD

LOW VOLTAGE SWITCH ON CONCRETE PAD

DUAL POWER AND TELECOMMUNICATIONS MANHOLE

DROP CORD, SINGLE CONVENIENCE OUTLET, 3-WIRE,

GROUNDING TYPE, 20A, W/#12 CONDUCTORS IN FLEXIBLE

CORD (CENTER LINE OF OUTLET: 6'-6" [1981mm] AFF. MINIMUM).

ELECTRICAL STRIP MOLD (OUTLETS ON 2'-0" [610mm] CENTERS OR AS DESIGNATED ON DRAWINGS), MTD 3'-6" [1067mm] AFF OR

AS INDICATED.

3-GANG COMPARTMENT BOX IN FLOOR FOR TELEPHONE, DATA &

RECEPTACLE.

RELAY; LETTER INDICATES RELAY TYPE

50 = INSTANTANEOUS OVERCURRENT OR RATE-OF-RISE

51 = AC-TIME OVERCURRENT

67 = AC-DIRECTIONAL OVERCURRENT

86 = LOCK OUT

ELECTRICAL SYMBOLS - POWER PLAN

SWITCH

F = FUSED SWITCH K = KEY OPERATED

L = LOCK LM= LOW VOLTAGE MASTER

M = MANUAL MOTOR STARTING MC= MOMENTARY CONTACT

MP= MOTOR SNAP WITH PILOT LIGHT P = WITH PILOT LIGHT

(THERMAL TYPE)

PB= PUSH BUTTON STATION RC= REMOTE CONTROL

WP= WEATHER PROOF X = EXPLOSION PROOF

VARIABLE FREQUENCY DRIVE

SWITCH, CEILING MOUNTED PULL

SWITCH (# SUBSCRIPT AS INDICATED BELOW):

BLANK = SINGLE POLE 2 = DOUBLE POLE

3 = THREE-WAY 4 = FOUR-WAY

D = DIMMER K = KEY OPERATED

LV= LOW VOLTAGE P = WITH PILOT LIGHT

LM= LOW VOLTAGE MASTER RC= REMOTE CONTROL

PB= PUSH BUTTON STATION WP= WEATHER PROOF

T = TIMER OPERATED Mo= OCCUPANCY SENSOR

RECESSED DOWNLIGHT FIXTURE, LETTER INDICATES TYPE.

LIGHT FIXTURE, RECESSED LED, 2'x4';

LETTER INDICATES TYPE.

LIGHT FIXTURE, RECESSED LED, 1'x4';

LETTER INDICATES TYPE.

ELECTRICAL SYMBOLS - LIGHTING PLAN

LIGHT FIXTURE, RECESSED LED, 1'x8';

LETTER INDICATES TYPE.

LIGHT FIXTURE, SURFACE MOUNTED LED, 2'x4';

LETTER INDICATES TYPE.

LIGHT FIXTURE, SURFACE MOUNTED LED, 1'x4';

LETTER INDICATES TYPE.

LIGHT FIXTURE, SURFACE MOUNTED LED, 1'x8';

LETTER INDICATES TYPE.

LIGHT FIXTURE, LED EMERGENCY;

LETTER INDICATES TYPE.

LIGHTING, ONE HEAD EMERGENCY BATTERY POWER

STREET LIGHT WITH BRACKET

LIGHT POLE, ONE LUMINAIRE

LIGHTING, EXTERIOR BUILDING

LIGHTING, TWO HEAD EMERGENCY BATTERY POWER

LIGHTING, THREE HEAD EMERGENCY BATTERY POWER

EXTERIOR FLOOD LIGHT

EXIT SIGN, WALL MOUNTED WITH DIRECTIONAL ARROWS AND FACES AS SHOWN

EXIT SIGN, CEILING MOUNTED WITH DIRECTIONAL ARROWS AND FACES AS SHOWN

LIGHT FIXTURE, RECESSED LED, 2'x2';

LETTER INDICATES TYPE.

LIGHT FIXTURE, SURFACE MOUNTED LED, 2'x2';

LETTER INDICATES TYPE.

LIGHT TRACK WITH HEADS AS SHOWN

LIGHT FIXTURE, STRIP/INDUSTRIAL LED; LETTER INDICATES TYPE.

LIGHT FIXTURE, WALL MOUNTED

LIGHT FIXTURE, BOLLARD

LIGHT FIXTURE, DIRECTIONAL

LIGHT POLE, TWO LUMINAIRES

RECEPTACLE, QUADRAPLEX, GFCI PROTECTED

GFCI

FUSE

SWITCH

VFD

E SITE LIGHTING DIRECT BURIED

PVC CONDUIT MIN 18" DEPTH = E

NUC UNDERGROUND CONTROLS

PVC CONDUIT 18" DEPTH = NUC

MISC SYMBOLS

NEW PERIMETER FENCE. REFER TO CIVIL

SHEETS FOR ADDITIONAL INFORMATION

FC1-01

C1-2

CORRIDOR

RESTROOM

LOBBY

C1-4 C1-5

C1-37

OFFICE LOCKER R

OFFICE

CORRIDOR

POLICE POLICE

ARMORY

POLICE

WINDOW C1-38

POLICE

C1-38

POLICE

POLICE STATION LIGHTING DEMOLITION PLAN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

100% BID DOCUMENTSOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

17 MARCH 2023Revisions: Date:

CAMPUS

523-19-602

150 SOUTH HUNTINGTON AVENUE, BOSTON MA

VAMC BOSTON

JAMAICA PLAIN CAMPUS

SITE SECURITY UPGRADES

THINKFORM DESIGN ARCHITECT LLC

38 EAST BROAD STREET

HOPEWELL, NJ 08525

T:855.821.0274 F:609.644.4397 Russell DiNardo, AIA NY 031521-1

A/E:

WATSON ENGINEERING

4500 STATE ROUTE 434

APALACHIN, NY 13732

PHONE: (607) 223-4334

EMW MAK

1/4" = 1'-0"ED-101

ED-101

POLICE STATION LIGHTING DEMOLITION

PLAN

KEY PLAN - FIRST FLOOR

GENERAL ELECTRICAL DEMOLITION NOTES:

1. ALL ELECTRICAL WORK SHALL CONFORM TO ALL STATE, LOCAL, AND NATIONAL ELECTRICAL CODES.

2. ELECTRICAL CHARACTERISTICS SHALL BE VERIFIED WITH EQUIPMENT MANUFACTURER.

3. THE CONTRACTOR SHALL FIELD VERIFY ALL LOCATIONS AND DIMENSIONS SHOWN ON DRAWINGS AND

COORDINATE THE INSTALLATION OF ALL EQUIPMENT WITH OTHER CONTRACTORS.

4. ALL AREAS DISTURBED BY WORK SHALL BE RESTORED TO A CONDITION EQUAL TO OR BETTER THAN ORIGINAL AS

DETERMINED BY THE COR.

5. ALL ELECTRICAL CONDUIT AND CONDUCTORS DISCONNECTED AND NOT TO BE REUSED SHALL BE REMOVED.

KEYED NOTES:

DEMOLISH EXISTING 2X2 LIGHT FIXTURE. CONTRACTOR SHALL REMOVE CONDUIT AND CIRCUIT BACK TO PANEL.1

1 1

ESTEY ST.

SOUTH HUNTINGTON AVE

E V

E R

G R

E E

N S

T

K E

N N

E Y

S T

N

IR

A A

V E

G R

O T

T O

G L

E N

R D

ESTEY ST.

H E

A T

H S

T R

E E

T

A R

C O

L A

S T

ELECTRICAL DEMOLITION PLAN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

100% BID DOCUMENTSOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

17 MARCH 2023Revisions: Date:

CAMPUS

523-19-602

150 SOUTH HUNTINGTON AVENUE, BOSTON MA

VAMC BOSTON

JAMAICA PLAIN CAMPUS

SITE SECURITY UPGRADES

THINKFORM DESIGN ARCHITECT LLC

38 EAST BROAD STREET

HOPEWELL, NJ 08525

T:855.821.0274 F:609.644.4397 Russell DiNardo, AIA NY 031521-1

A/E:

WATSON ENGINEERING

4500 STATE ROUTE 434

APALACHIN, NY 13732

PHONE: (607) 223-4334

EMW MAK

1" = 20'-0"

ED-102

ED-102

SITE ELECTRICAL DEMOLITION PLAN

KEY PLAN - CAMPUS

KEYED NOTES:

DEMOLISH EXISTING LIGHT POLE AND LIGHT. CONTRACTOR SHALL PULL

ASSOCIATED WIRING BACK.1

GENERAL ELECTRICAL DEMOLITION NOTES:

1. ALL ELECTRICAL WORK SHALL CONFORM TO ALL STATE, LOCAL, AND NATIONAL ELECTRICAL CODES.

2. ELECTRICAL CHARACTERISTICS SHALL BE VERIFIED WITH EQUIPMENT MANUFACTURER.

3. THE CONTRACTOR SHALL FIELD VERIFY ALL LOCATIONS AND DIMENSIONS SHOWN ON DRAWINGS AND

COORDINATE THE INSTALLATION OF ALL EQUIPMENT WITH OTHER CONTRACTORS.

4. ALL AREAS DISTURBED BY WORK SHALL BE RESTORED TO A CONDITION EQUAL TO OR BETTER THAN ORIGINAL AS

DETERMINED BY THE COR.

5. ALL ELECTRICAL CONDUIT AND CONDUCTORS DISCONNECTED AND NOT TO BE REUSED SHALL BE REMOVED.

6. GENERAL CONTRACTOR IS REQUIRED TO PERFORM UTILITY SURVEY FOR ALL AREAS OF EXCAVATION. ANY OBSTRUCTIONS SHALL BE BROUGHT TO EOR AND VA COR FOR FURTHER INSTRUCTIONS PRIOR TO EXCAVATION.

N E

Y S

T

N

IR

A A

V E

G R

O T

T O

G L

E N

R D

A R

C O

L A

S T

SOUTH HUNTINGTON AVE

E V

E R

G R

E E

N S

T

K E

N N

E Y

S T

N

IR

A A

V E

G R

O T

T O

G L

E N

R D

ESTEY ST.

H E

A T

H S

T R

E E

T

A R

C O

L A

S T

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

100% BID DOCUMENTSOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

17 MARCH 2023Revisions: Date:

CAMPUS

523-19-602

150 SOUTH HUNTINGTON AVENUE, BOSTON MA

VAMC BOSTON

JAMAICA PLAIN CAMPUS

SITE SECURITY UPGRADES

THINKFORM DESIGN ARCHITECT LLC

38 EAST BROAD STREET

HOPEWELL, NJ 08525

T:855.821.0274 F:609.644.4397 Russell DiNardo, AIA NY 031521-1

A/E:

WATSON ENGINEERING

4500 STATE ROUTE 434

APALACHIN, NY 13732

PHONE: (607) 223-4334

EMW MAK

1" = 20'-0"

ED-103

ED-103

KEY PLAN - CAMPUS

SITE ELECTRICAL DEMOLITION PLAN

KEYED NOTES:

DEMOLISH EXISTING LIGHT POLE AND LIGHT. CONTRACTOR SHALL PULL

ASSOCIATED WIRING BACK.1

GENERAL ELECTRICAL DEMOLITION NOTES:

1. ALL ELECTRICAL WORK SHALL CONFORM TO ALL STATE, LOCAL, AND NATIONAL ELECTRICAL CODES.

2. ELECTRICAL CHARACTERISTICS SHALL BE VERIFIED WITH EQUIPMENT MANUFACTURER.

3. THE CONTRACTOR SHALL FIELD VERIFY ALL LOCATIONS AND DIMENSIONS SHOWN ON DRAWINGS AND

COORDINATE THE INSTALLATION OF ALL EQUIPMENT WITH OTHER CONTRACTORS.

4. ALL AREAS DISTURBED BY WORK SHALL BE RESTORED TO A CONDITION EQUAL TO OR BETTER THAN ORIGINAL AS

DETERMINED BY THE COR.

5. ALL ELECTRICAL CONDUIT AND CONDUCTORS DISCONNECTED AND NOT TO BE REUSED SHALL BE REMOVED.

6. GENERAL CONTRACTOR IS REQUIRED TO PERFORM UTILITY SURVEY FOR ALL AREAS OF EXCAVATION. ANY OBSTRUCTIONS SHALL BE BROUGHT TO EOR AND VA COR FOR FURTHER INSTRUCTIONS PRIOR TO EXCAVATION.

ELECTRICAL DEMOLITION PLAN

V

E R

G R

E E

N S

T

K E

N N

E Y

S T

SOUTH HUNTINGTON AVE

E V

E R

G R

E E

N S

T

K E

N N

E Y

S T

N

IR

A A

V E

G R

O T

T O

G L

E N

R D

ESTEY ST.

H E

A T

H S

T R

E E

T

A R

C O

L A

S T

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

100% BID DOCUMENTSOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

17 MARCH 2023Revisions: Date:

CAMPUS

523-19-602

150 SOUTH HUNTINGTON AVENUE, BOSTON MA

VAMC BOSTON

JAMAICA PLAIN CAMPUS

SITE SECURITY UPGRADES

THINKFORM DESIGN ARCHITECT LLC

38 EAST BROAD STREET

HOPEWELL, NJ 08525

T:855.821.0274 F:609.644.4397 Russell DiNardo, AIA NY 031521-1

A/E:

WATSON ENGINEERING

4500 STATE ROUTE 434

APALACHIN, NY 13732

PHONE: (607) 223-4334

EMW MAK

1" = 20'-0"

ED-104

ED-104

KEY PLAN - CAMPUS

SITE ELECTRICAL DEMOLITION PLAN

KEYED NOTES:

DEMOLISH EXISTING LIGHT POLE AND LIGHT. CONTRACTOR SHALL PULL

ASSOCIATED WIRING BACK.1

GENERAL ELECTRICAL DEMOLITION NOTES:

1. ALL ELECTRICAL WORK SHALL CONFORM TO ALL STATE, LOCAL, AND NATIONAL ELECTRICAL CODES.

2. ELECTRICAL CHARACTERISTICS SHALL BE VERIFIED WITH EQUIPMENT MANUFACTURER.

3. THE CONTRACTOR SHALL FIELD VERIFY ALL LOCATIONS AND DIMENSIONS SHOWN ON DRAWINGS AND

COORDINATE THE INSTALLATION OF ALL EQUIPMENT WITH OTHER CONTRACTORS.

4. ALL AREAS DISTURBED BY WORK SHALL BE RESTORED TO A CONDITION EQUAL TO OR BETTER THAN ORIGINAL AS

DETERMINED BY THE COR.

5. ALL ELECTRICAL CONDUIT AND CONDUCTORS DISCONNECTED AND NOT TO BE REUSED SHALL BE REMOVED.

6. GENERAL CONTRACTOR IS REQUIRED TO PERFORM UTILITY SURVEY FOR ALL AREAS OF EXCAVATION. ANY

H

A T

H S

T R

E E

T

SOUTH HUNTINGTON AVE

E V

E R

G R

E E

N S

T

K E

N N

E Y

S T

N

IR

A A

V E

G R

O T

T O

G L

E N

R D

ESTEY ST.

H E

A T

H S

T R

E E

T

A R

C O

L A

S T

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

100% BID DOCUMENTSOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

17 MARCH 2023Revisions: Date:

CAMPUS

523-19-602

150 SOUTH HUNTINGTON AVENUE, BOSTON MA

VAMC BOSTON

JAMAICA PLAIN CAMPUS

SITE SECURITY UPGRADES

THINKFORM DESIGN ARCHITECT LLC

38 EAST BROAD STREET

HOPEWELL, NJ 08525

T:855.821.0274 F:609.644.4397 Russell DiNardo, AIA NY 031521-1

A/E:

WATSON ENGINEERING

4500 STATE ROUTE 434

APALACHIN, NY 13732

PHONE: (607) 223-4334

EMW MAK

1" = 20'-0"

ED-105

ED-105

KEY PLAN - CAMPUS

SITE ELECTRICAL DEMOLITION PLAN

KEYED NOTES:

DEMOLISH EXISTING LIGHT POLE AND LIGHT. CONTRACTOR SHALL PULL

ASSOCIATED WIRING BACK.1

1 1

GENERAL ELECTRICAL DEMOLITION NOTES:

1. ALL ELECTRICAL WORK SHALL CONFORM TO ALL STATE, LOCAL, AND NATIONAL ELECTRICAL CODES.

2. ELECTRICAL CHARACTERISTICS SHALL BE VERIFIED WITH EQUIPMENT MANUFACTURER.

3. THE CONTRACTOR SHALL FIELD VERIFY ALL LOCATIONS AND DIMENSIONS SHOWN ON DRAWINGS AND

COORDINATE THE INSTALLATION OF ALL EQUIPMENT WITH OTHER CONTRACTORS.

4. ALL AREAS DISTURBED BY WORK SHALL BE RESTORED TO A CONDITION EQUAL TO OR BETTER THAN ORIGINAL AS

DETERMINED BY THE COR.

5. ALL ELECTRICAL CONDUIT AND CONDUCTORS DISCONNECTED AND NOT TO BE REUSED SHALL BE REMOVED.

6. GENERAL CONTRACTOR IS REQUIRED TO PERFORM UTILITY SURVEY FOR ALL AREAS OF EXCAVATION. ANY

E V

E R

G R

E E

N S

T

K E

N N

E Y

S T

N

IR

A A

V E

G R

O T

T O

G L

E N

R D

ESTEY ST.

H E

A T

H S

T R

E E

T

A R

C O

L A

S T

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

100% BID DOCUMENTSOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

17 MARCH 2023Revisions: Date:

CAMPUS

523-19-602

150 SOUTH HUNTINGTON AVENUE, BOSTON MA

VAMC BOSTON

JAMAICA PLAIN CAMPUS

SITE SECURITY UPGRADES

THINKFORM DESIGN ARCHITECT LLC

38 EAST BROAD STREET

HOPEWELL, NJ 08525

T:855.821.0274 F:609.644.4397 Russell DiNardo, AIA NY 031521-1

A/E:

WATSON ENGINEERING

4500 STATE ROUTE 434

APALACHIN, NY 13732

PHONE: (607) 223-4334

EMW MAK

1" = 20'-0"

ED-106

ED-106

KEY PLAN - CAMPUS

SITE ELECTRICAL DEMOLITION PLAN

KEYED NOTES:

DEMOLISH EXISTING LIGHT POLE AND LIGHT. CONTRACTOR SHALL PULL

ASSOCIATED WIRING BACK.

EXISTING GUARD HOUSE SHALL BE REMOVED (REFER TO CIVIL FOR

ADDITIONAL INFORMATION). CONTRACTOR SHALL REMOVE CIRCUITS AND

CONDUIT BACK TO PANEL. EXISTING CAMERAS EQUIPMENT SHALL BE

MAINTAINED AND OPERATIONAL.

GENERAL ELECTRICAL DEMOLITION NOTES:

1. ALL ELECTRICAL WORK SHALL CONFORM TO ALL STATE, LOCAL, AND NATIONAL ELECTRICAL CODES.

2. ELECTRICAL CHARACTERISTICS SHALL BE VERIFIED WITH EQUIPMENT MANUFACTURER.

3. THE CONTRACTOR SHALL FIELD VERIFY ALL LOCATIONS AND DIMENSIONS SHOWN ON DRAWINGS AND

COORDINATE THE INSTALLATION OF ALL EQUIPMENT WITH OTHER CONTRACTORS.

4. ALL AREAS DISTURBED BY WORK SHALL BE RESTORED TO A CONDITION EQUAL TO OR BETTER THAN ORIGINAL AS

DETERMINED BY THE COR.

5. ALL ELECTRICAL CONDUIT AND CONDUCTORS DISCONNECTED AND NOT TO BE REUSED SHALL BE REMOVED.

6. GENERAL CONTRACTOR IS REQUIRED TO PERFORM UTILITY SURVEY FOR ALL AREAS OF EXCAVATION. ANY OBSTRUCTIONS SHALL BE BROUGHT TO EOR AND VA COR FOR FURTHER INSTRUCTIONS PRIOR TO EXCAVATION.

V

E R

G R

E E

N S

T

K E

N N

E Y

S T

N

IR

A A

V E

G R

O T

T O

G L

E N

R D

ESTEY ST.

H E

A T

H S

T R

E E

T

A R

C O

L A

S T

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

100% BID DOCUMENTSOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

17 MARCH 2023Revisions: Date:

CAMPUS

523-19-602

150 SOUTH HUNTINGTON AVENUE, BOSTON MA

VAMC BOSTON

JAMAICA PLAIN CAMPUS

SITE SECURITY UPGRADES

THINKFORM DESIGN ARCHITECT LLC

38 EAST BROAD STREET

HOPEWELL, NJ 08525

T:855.821.0274 F:609.644.4397 Russell DiNardo, AIA NY 031521-1

A/E:

WATSON ENGINEERING

4500 STATE ROUTE 434

APALACHIN, NY 13732

PHONE: (607) 223-4334

EMW MAK

1" = 20'-0"

ED-107

ED-107

KEY PLAN - CAMPUS

SITE ELECTRICAL DEMOLITION PLAN

KEYED NOTES:

DEMOLISH EXISTING LIGHT POLE AND LIGHT. CONTRACTOR SHALL PULL

ASSOCIATED WIRING BACK.1

GENERAL ELECTRICAL DEMOLITION NOTES:

1. ALL ELECTRICAL WORK SHALL CONFORM TO ALL STATE, LOCAL, AND NATIONAL ELECTRICAL CODES.

2. ELECTRICAL CHARACTERISTICS SHALL BE VERIFIED WITH EQUIPMENT MANUFACTURER.

3. THE CONTRACTOR SHALL FIELD VERIFY ALL LOCATIONS AND DIMENSIONS SHOWN ON DRAWINGS AND

COORDINATE THE INSTALLATION OF ALL EQUIPMENT WITH OTHER CONTRACTORS.

4. ALL AREAS DISTURBED BY WORK SHALL BE RESTORED TO A CONDITION EQUAL TO OR BETTER THAN ORIGINAL AS

DETERMINED BY THE COR.

5. ALL ELECTRICAL CONDUIT AND CONDUCTORS DISCONNECTED AND NOT TO BE REUSED SHALL BE REMOVED.

6. GENERAL CONTRACTOR IS REQUIRED TO PERFORM UTILITY SURVEY FOR ALL AREAS OF EXCAVATION. ANY

E

E

E

E

E

E

E

E

E

EE

E

E

E

E

E

E

E

E E

E

E

E

E

P P

P

P P

P

P

P

SOUTH HUNTINGTON AVE

E V

E R

G R

E E

N S

T

K E

N N

E Y

S T

N

IR

A A

V E

G R

O T

T O

G L

E N

R D

ESTEY ST.

H E

A T

H S

T R

E E

T

A R

C O

L A

S T

ELECTRICAL PLAN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

100% BID DOCUMENTSOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

17 MARCH 2023Revisions: Date:

CAMPUS

523-19-602

150 SOUTH HUNTINGTON AVENUE, BOSTON MA

VAMC BOSTON

JAMAICA PLAIN CAMPUS

SITE SECURITY UPGRADES

THINKFORM DESIGN ARCHITECT LLC

38 EAST BROAD STREET

HOPEWELL, NJ 08525

T:855.821.0274 F:609.644.4397 Russell DiNardo, AIA NY 031521-1

A/E:

WATSON ENGINEERING

4500 STATE ROUTE 434

APALACHIN, NY 13732

PHONE: (607) 223-4334

EMW MAK

1" = 20'-0" E-101

E-101

ELECTRICAL PLAN

KEY PLAN - CAMPUS

GENERAL ELECTRICAL NOTES:

1. ALL ELECTRICAL WORK SHALL CONFORM TO ALL STATE, LOCAL, AND NATIONAL ELECTRICAL CODES.

2. ELECTRICAL CHARACTERISTICS SHALL BE VERIFIED WITH EQUIPMENT MANUFACTURER.

3. THE CONTRACTOR SHALL FIELD VERIFY ALL LOCATIONS AND DIMENSIONS SHOWN ON DRAWINGS AND

COORDINATE THE INSTALLATION OF ALL EQUIPMENT WITH OTHER CONTRACTORS.

4. ALL AREAS DISTURBED BY WORK SHALL BE RESTORED TO A CONDITION EQUAL TO OR BETTER THAN ORIGINAL AS

DETERMINED BY THE COR.

5. ALL ELECTRICAL CONDUIT AND CONDUCTORS DISCONNECTED AND NOT TO BE REUSED SHALL BE REMOVED.

6. ANY WALL PENETRATIONS MADE FOR CONDUIT RUNS SHALL BE PROPERLY SEALED FOR FIRE RATING.

7. SEE DETAIL 5 ON SHEET E501 FOR DETAILS.

8. PROVIDE MEANS OF DISCONNECT FOR ALL NEW EQUIPMENT.

9. GENERAL CONTRACTOR IS REQUIRED TO PERFORM UTILITY SURVEY FOR ALL AREAS OF EXCAVATION. ANY OBSTRUCTIONS SHALL BE BROUGHT TO EOR AND VA COR FOR FURTHER INSTRUCTIONS PRIOR TO EXCAVATION

KEYED NOTES:

NEW SLIDING GATE OPERATOR TO BE POWERED BY EXISTING EMERGENCY POWER INFRASTRUCTURE.

INSTALL NEW 120 VOLT, 20 AMP, SINGLE-POLE CIRCUIT BREAKER. CONDUCTOR SIZE SHALL BE #10

AWG WITH 1" CONDUIT. USE PANEL LBR2, LOCATED ON WEST WALL OF BOILER PLANT.

NEW VEHICULAR ACCESS CONTROL GATE OPERATOR TO BE POWERED BY EXISTING EMERGENCY

POWER INFRASTRUCTURE. INSTALL NEW 120 VOLT, 20 AMP, SINGLE-POLE CIRCUIT BREAKER.

CONDUCTOR SIZE SHALL BE #10 AWG WITH 1" CONDUIT. USE PANEL LBR2 LOCATED ON WEST WALL OF

BOILER PLANT.

SG-1

LBR2

Y S

T

N

IR

A A

V E

G R

O T

T O

G L

E N

R D

A R

C O

L A

S T

E

E

E

E E

E E

E E

E E

E

E

E

EEEE

E

E

E

E

E E

E

E

E

E

E E

E

E

E

E E

E

E

E

SOUTH HUNTINGTON AVE

E V

E R

G R

E E

N S

T

K E

N N

E Y

S T

N

IR

A A

V E

G R

O T

T O

G L

E N

R D

ESTEY ST.

H E

A T

H S

T R

E E

T

A R

C O

L A

S T

ELECTRICAL PLAN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

100% BID DOCUMENTSOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

17 MARCH 2023Revisions: Date:

CAMPUS

523-19-602

150 SOUTH HUNTINGTON AVENUE, BOSTON MA

VAMC BOSTON

JAMAICA PLAIN CAMPUS

SITE SECURITY UPGRADES

THINKFORM DESIGN ARCHITECT LLC

38 EAST BROAD STREET

HOPEWELL, NJ 08525

T:855.821.0274 F:609.644.4397 Russell DiNardo, AIA NY 031521-1

A/E:

WATSON ENGINEERING

4500 STATE ROUTE 434

APALACHIN, NY 13732

PHONE: (607) 223-4334

EMW MAK

1" = 20'-0" E-102

E-102

ELECTRICAL PLAN

KEY PLAN - CAMPUS*ELECTRICAL WORK IN THIS AREA IS LIGHTING AND CAMERAS ONLY. REFER TO ADDITIONAL SHEETS

FOR INFORMATION. DRAWING SHOWN FOR CLARITY ONLY*

GENERAL ELECTRICAL NOTES:

1. ALL ELECTRICAL WORK SHALL CONFORM TO ALL STATE, LOCAL, AND NATIONAL ELECTRICAL CODES.

2. ELECTRICAL CHARACTERISTICS SHALL BE VERIFIED WITH EQUIPMENT MANUFACTURER.

3. THE CONTRACTOR SHALL FIELD VERIFY ALL LOCATIONS AND DIMENSIONS SHOWN ON DRAWINGS AND

COORDINATE THE INSTALLATION OF ALL EQUIPMENT WITH OTHER CONTRACTORS.

4. ALL AREAS DISTURBED BY WORK SHALL BE RESTORED TO A CONDITION EQUAL TO OR BETTER THAN ORIGINAL AS

DETERMINED BY THE COR.

5. ALL ELECTRICAL CONDUIT AND CONDUCTORS DISCONNECTED AND NOT TO BE REUSED SHALL BE REMOVED.

6. ANY WALL PENETRATIONS MADE FOR CONDUIT RUNS SHALL BE PROPERLY SEALED FOR FIRE RATING.

7. SEE DETAIL 5 ON SHEET E501 FOR DETAILS.

8. PROVIDE MEANS OF DISCONNECT FOR ALL NEW EQUIPMENT.

9. GENERAL CONTRACTOR IS REQUIRED TO PERFORM UTILITY SURVEY FOR ALL AREAS OF EXCAVATION. ANY OBSTRUCTIONS SHALL BE BROUGHT TO EOR AND VA COR FOR FURTHER INSTRUCTIONS PRIOR TO EXCAVATION

E R

G R

E E

N S

T

K E

N N

E Y

S T

E

E

E

E

E

E

E

E

E

E E E E E

SOUTH HUNTINGTON AVE

E V

E R

G R

E E

N S

T

K E

N N

E Y

S T

N

IR

A A

V E

G R

O T

T O

G L

E N

R D

ESTEY ST.

H E

A T

H S

T R

E E

T

A R

C O

L A

S T

ELECTRICAL PLAN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

100% BID DOCUMENTSOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

17 MARCH 2023Revisions: Date:

CAMPUS

523-19-602

150 SOUTH HUNTINGTON AVENUE, BOSTON MA

VAMC BOSTON

JAMAICA PLAIN CAMPUS

SITE SECURITY UPGRADES

THINKFORM DESIGN ARCHITECT LLC

38 EAST BROAD STREET

HOPEWELL, NJ 08525

T:855.821.0274 F:609.644.4397 Russell DiNardo, AIA NY 031521-1

A/E:

WATSON ENGINEERING

4500 STATE ROUTE 434

APALACHIN, NY 13732

PHONE: (607) 223-4334

EMW MAK

1" = 20'-0" E-103

E-103

ELECTRICAL PLAN

KEY PLAN - CAMPUS*ELECTRICAL WORK IN THIS AREA IS LIGHTING ONLY. REFER TO ADDITIONAL SHEETS FOR

INFORMATION. DRAWING SHOWN FOR CLARITY ONLY*

GENERAL ELECTRICAL NOTES:

1. ALL ELECTRICAL WORK SHALL CONFORM TO ALL STATE, LOCAL, AND NATIONAL ELECTRICAL CODES.

2. ELECTRICAL CHARACTERISTICS SHALL BE VERIFIED WITH EQUIPMENT MANUFACTURER.

3. THE CONTRACTOR SHALL FIELD VERIFY ALL LOCATIONS AND DIMENSIONS SHOWN ON DRAWINGS AND

COORDINATE THE INSTALLATION OF ALL EQUIPMENT WITH OTHER CONTRACTORS.

4. ALL AREAS DISTURBED BY WORK SHALL BE RESTORED TO A CONDITION EQUAL TO OR BETTER THAN ORIGINAL AS

DETERMINED BY THE COR.

5. ALL ELECTRICAL CONDUIT AND CONDUCTORS DISCONNECTED AND NOT TO BE REUSED SHALL BE REMOVED.

6. ANY WALL PENETRATIONS MADE FOR CONDUIT RUNS SHALL BE PROPERLY SEALED FOR FIRE RATING.

7. SEE DETAIL 5 ON SHEET E501 FOR DETAILS.

8. PROVIDE MEANS OF DISCONNECT FOR ALL NEW EQUIPMENT.

A T

H S

T R

E E

T

E

E

E

E

E E

E

E

E

E

E

E

E

E

E E

E

E

E

E

E

E E

E E

E

E

E

E

E

E

E E E E E E E

E

E

E

E

E

P

P

P

P

P

SOUTH HUNTINGTON AVE

E V

E R

G R

E E

N S

T

K E

N N

E Y

S T

N

IR

A A

V E

G R

O T

T O

G L

E N

R D

ESTEY ST.

H E

A T

H S

T R

E E

T

A R

C O

L A

S T

ELECTRICAL PLAN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

100% BID DOCUMENTSOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

17 MARCH 2023Revisions: Date:

CAMPUS

523-19-602

150 SOUTH HUNTINGTON AVENUE, BOSTON MA

VAMC BOSTON

JAMAICA PLAIN CAMPUS

SITE SECURITY UPGRADES

THINKFORM DESIGN ARCHITECT LLC

38 EAST BROAD STREET

HOPEWELL, NJ 08525

T:855.821.0274 F:609.644.4397 Russell DiNardo, AIA NY 031521-1

A/E:

WATSON ENGINEERING

4500 STATE ROUTE 434

APALACHIN, NY 13732

PHONE: (607) 223-4334

EMW MAK

1" = 20'-0" E-104

E-104

ELECTRICAL PLAN

KEY PLAN - CAMPUS

KEYED NOTES:

NEW SLIDING GATE OPERATOR TO BE POWERED FROM SUBPANEL 7EPH LOCATED WITHIN BLDG 7.

INSTALL NEW 120 VOLT, 20 AMP, SINGLE-POLE CIRCUIT BREAKER. CONDUCTOR SIZE SHALL BE #10 AWG

WITH 1" CONDUIT.

EXISTING PANEL NEP SHALL BE UPSIZED. CONTRACTOR SHALL REPLACE EXISTING TRANSFORMER WITH NEW DRY-TYPE TRANSFORMER. RE-FEED EXISTING CIRCUITS FROM EXISTING PANEL NEP TO NEW

60-SPACE PANEL WITH NEW CIRCUIT BREAKERS. REFER TO ELECTRICAL DETAIL SHEETS FOR

ADDITIONAL INFORMATION.

NEW GUARD HOUSE LIGHTS AND RECEPTACLES TO BE POWERED FROM PANEL NEP LOCATED WITHIN BLDG 1 GENERATOR ROOM. INSTALL NEW 120 VOLT, 20 AMP, SINGLE-POLE CIRCUIT BREAKER.

CONDUCTOR SIZE SHALL BE #10 AWG WITH 1" CONDUIT.

NEW GUARD HOUSE HVAC TO BE POWERED FROM PANEL NEP LOCATED WITHIN BLDG 1 GENERATOR ROOM. INSTALL NEW 120 VOLT, 30 AMP, SINGLE-POLE CIRCUIT BREAKER. CONDUCTOR SIZE SHALL BE

#10 AWG WITH 1" CONDUIT.

NEW RETRACTABLE ANTI-RAM WEDGES TO BE POWERED FROM PANEL NEP LOCATED WITHIN BLDG 1 GENERATOR ROOM. INSTALL NEW 208 VOLT, 35 AMP, TWO-POLE CIRCUIT BREAKER. CONDUCTOR SIZE

SHALL BE #10 AWG WITH 1" CONDUIT.

NEW SLIDING GATE OPERATOR TO BE POWERED FROM PANEL NEW PANEL NEP LOCATED WITHIN BLDG 1 GENERATOR ROOM. INSTALL NEW 120 VOLT, 20 AMP, SINGLE-POLE CIRCUIT BREAKER. CONDUCTOR

SIZE SHALL BE #10 AWG WITH 1" CONDUIT.

SG-1

SG-1

WG-1

7EPH

NEP

GENERAL ELECTRICAL NOTES:

1. ALL ELECTRICAL WORK SHALL CONFORM TO ALL STATE, LOCAL, AND NATIONAL ELECTRICAL CODES.

2. ELECTRICAL CHARACTERISTICS SHALL BE VERIFIED WITH EQUIPMENT MANUFACTURER.

3. THE CONTRACTOR SHALL FIELD VERIFY ALL LOCATIONS AND DIMENSIONS SHOWN ON DRAWINGS AND

COORDINATE THE INSTALLATION OF ALL EQUIPMENT WITH OTHER CONTRACTORS.

4. ALL AREAS DISTURBED BY WORK SHALL BE RESTORED TO A CONDITION EQUAL TO OR BETTER THAN ORIGINAL AS

DETERMINED BY THE COR.

5. ALL ELECTRICAL CONDUIT AND CONDUCTORS DISCONNECTED AND NOT TO BE REUSED SHALL BE REMOVED.

6. ANY WALL PENETRATIONS MADE FOR CONDUIT RUNS SHALL BE PROPERLY SEALED FOR FIRE RATING.

7. SEE DETAIL 5 ON SHEET E501 FOR DETAILS.

8. PROVIDE MEANS OF DISCONNECT FOR ALL NEW EQUIPMENT.

C O

C O

E

EEEEEEEEE

E E E E E E

E

E

E

E

E E

E

E

E

E

E

E

E E

E E

E E

E E

PP

P P

P P

P P

PP

P

P

P P P P P P P P P P

SOUTH HUNTINGTON AVE

E V

E R

G R

E E

N S

T

K E

N N

E Y

S T

N

IR

A A

V E

G R

O T

T O

G L

E N

R D

ESTEY ST.

H E

A T

H S

T R

E E

T

A R

C O

L A

S T

ELECTRICAL PLAN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

100% BID DOCUMENTSOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

17 MARCH 2023Revisions: Date:

CAMPUS

523-19-602

150 SOUTH HUNTINGTON AVENUE, BOSTON MA

VAMC BOSTON

JAMAICA PLAIN CAMPUS

SITE SECURITY UPGRADES

THINKFORM DESIGN ARCHITECT LLC

38 EAST BROAD STREET

HOPEWELL, NJ 08525

T:855.821.0274 F:609.644.4397 Russell DiNardo, AIA NY 031521-1

A/E:

WATSON ENGINEERING

4500 STATE ROUTE 434

APALACHIN, NY 13732

PHONE: (607) 223-4334

EMW MAK

1" = 20'-0" E-105

E-105

ELECTRICAL PLAN

KEY PLAN - CAMPUS

KEYED NOTES:

NEW SLIDING GATE OPERATOR TO BE POWERED FROM PANEL P2G WITHIN EMPLOYEE PARKING

GARAGE. INSTALL NEW 120 VOLT, 20 AMP, SINGLE-POLE CIRCUIT BREAKER. CONDUCTOR SIZE SHALL BE

#10 AWG WITH 1" CONDUIT.

INSTALL NEW 100A, 40 SPACE 120/208V SUBPANEL (DPS21C) FED FROM SPARE IN DPS21. NEW SUBPANEL

WILL REQUIRE A NEW DRY-TYPE TRANSFORMER FROM SPARE. INSTALL NEW SUBPANEL AND

TRANSFORMER WITHIN ROOM F1-11. REFER TO DETAILS SHEET FOR ADDITIONAL INFORMATION.

NEW GUARD HOUSE LIGHTS AND RECEPTACLES TO BE POWERED FROM PANEL DPS21C IN ROOM F1-11.

INSTALL NEW 120 VOLT, 20 AMP, SINGLE-POLE CIRCUIT BREAKER. CONDUCTOR SIZE SHALL BE #10 AWG

WITH 1" CONDUIT.

NEW GUARD HOUSE HVAC TO BE POWERED FROM PANEL DPS21C IN ROOM F1-11. INSTALL NEW 120 VOLT, 30 AMP, SINGLE-POLE CIRCUIT BREAKER. CONDUCTOR SIZE SHALL BE #10 AWG WITH 1" CONDUIT.

EXACT CONNECTION LOCATIONS TO BE COORDINATED WITH VA.

NEW RETRACTABLE ANTI-RAM WEDGES TO BE POWERED FROM PANEL DPS21C IN ROOM F1-11. INSTALL NEW 208 VOLT, 35 AMP, TWO-POLE CIRCUIT BREAKER. CONDUCTOR SIZE SHALL BE #8 AWG WITH 1"

CONDUIT EACH.

NEW ICE MELT SYSTEM TO BE POWERED FROM PANEL 1C2 IN ROOM C1-21. INSTALL NEW 120 VOLT, 50 AMP, SINGLE-POLE CIRCUIT BREAKER. CONDUCTOR SIZE SHALL BE #10 AWG WITH 1" CONDUIT.

CONTRACTOR SHALL PERFORM A 30-DAY LOAD STUDY ON PANEL TO ENSURE CAPACITY. IF

INSUFFICIENT CAPACITY EXISTS, CONTRACTOR SHALL ALERT EOR AND VA COR FOR FURTHER

INSTRUCTIONS.

3 5

E-301

SG-1

SG-1

WG-1 WG-1

DPS21C

DPS21

F1-11

C1-21

P2G

WG-1

WG-15

GENERAL ELECTRICAL NOTES:

1. ALL ELECTRICAL WORK SHALL CONFORM TO ALL STATE, LOCAL, AND NATIONAL ELECTRICAL CODES.

2. ELECTRICAL CHARACTERISTICS SHALL BE VERIFIED WITH EQUIPMENT MANUFACTURER.

3. THE CONTRACTOR SHALL FIELD VERIFY ALL LOCATIONS AND DIMENSIONS SHOWN ON DRAWINGS AND

COORDINATE THE INSTALLATION OF ALL EQUIPMENT WITH OTHER CONTRACTORS.

4. ALL AREAS DISTURBED BY WORK SHALL BE RESTORED TO A CONDITION EQUAL TO OR BETTER THAN ORIGINAL AS

DETERMINED BY THE COR.

5. ALL ELECTRICAL CONDUIT AND CONDUCTORS DISCONNECTED AND NOT TO BE REUSED SHALL BE REMOVED.

6. ANY WALL PENETRATIONS MADE FOR CONDUIT RUNS SHALL BE PROPERLY SEALED FOR FIRE RATING.

7. SEE DETAIL 5 ON SHEET E501 FOR DETAILS.

8. PROVIDE MEANS OF DISCONNECT FOR ALL NEW EQUIPMENT.

E E

E

E

E

E

E

E

E

E

E E

E

E

E

E

E

E

SOUTH HUNTINGTON AVE

E V

E R

G R

E E

N S

T

K E

N N

E Y

S T

N

IR

A A

V E

G R

O T

T O

G L

E N

R D

ESTEY ST.

H E

A T

H S

T R

E E

T

A R

C O

L A

S T

ELECTRICAL PLAN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

100% BID DOCUMENTSOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

17 MARCH 2023Revisions: Date:

CAMPUS

523-19-602

150 SOUTH HUNTINGTON AVENUE, BOSTON MA

VAMC BOSTON

JAMAICA PLAIN CAMPUS

SITE SECURITY UPGRADES

THINKFORM DESIGN ARCHITECT LLC

38 EAST BROAD STREET

HOPEWELL, NJ 08525

T:855.821.0274 F:609.644.4397 Russell DiNardo, AIA NY 031521-1

A/E:

WATSON ENGINEERING

4500 STATE ROUTE 434

APALACHIN, NY 13732

PHONE: (607) 223-4334

EMW MAK

1" = 20'-0" E-106

E-106

ELECTRICAL PLAN

KEY PLAN - CAMPUS*ELECTRICAL WORK IN THIS AREA IS LIGHTING AND CAMERAS ONLY. REFER TO ADDITIONAL SHEETS

FOR INFORMATION. DRAWING SHOWN FOR CLARITY ONLY*

GENERAL ELECTRICAL NOTES:

1. ALL ELECTRICAL WORK SHALL CONFORM TO ALL STATE, LOCAL, AND NATIONAL ELECTRICAL CODES.

2. ELECTRICAL CHARACTERISTICS SHALL BE VERIFIED WITH EQUIPMENT MANUFACTURER.

3. THE CONTRACTOR SHALL FIELD VERIFY ALL LOCATIONS AND DIMENSIONS SHOWN ON DRAWINGS AND

COORDINATE THE INSTALLATION OF ALL EQUIPMENT WITH OTHER CONTRACTORS.

4. ALL AREAS DISTURBED BY WORK SHALL BE RESTORED TO A CONDITION EQUAL TO OR BETTER THAN ORIGINAL AS

DETERMINED BY THE COR.

5. ALL ELECTRICAL CONDUIT AND CONDUCTORS DISCONNECTED AND NOT TO BE REUSED SHALL BE REMOVED.

6. ANY WALL PENETRATIONS MADE FOR CONDUIT RUNS SHALL BE PROPERLY SEALED FOR FIRE RATING.

7. SEE DETAIL 5 ON SHEET E501 FOR DETAILS.

8. PROVIDE MEANS OF DISCONNECT FOR ALL NEW EQUIPMENT.

PPP

E V

E R

G R

E E

N S

T

K E

N N

E Y

S T

N

IR

A A

V E

G R

O T

T O

G L

E N

R D

ESTEY ST.

H E

A T

H S

T R

E E

T

A R

C O

L A

S T

C O

C O

ICE MELT ENLARGED PLAN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

100% BID DOCUMENTSOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

17 MARCH 2023Revisions: Date:

CAMPUS

523-19-602

150 SOUTH HUNTINGTON AVENUE, BOSTON MA

VAMC BOSTON

JAMAICA PLAIN CAMPUS

SITE SECURITY UPGRADES

THINKFORM DESIGN ARCHITECT LLC

38 EAST BROAD STREET

HOPEWELL, NJ 08525

T:855.821.0274 F:609.644.4397 Russell DiNardo, AIA NY 031521-1

A/E:

WATSON ENGINEERING

4500 STATE ROUTE 434

APALACHIN, NY 13732

PHONE: (607) 223-4334

EMW MAK

1/2" = 1'-0"E-301

E-301

ENLARGED ICE MELT PLAN

ICE MELT NOTES:

1. NEW ICE MELT SYSTEM SHALL BE INSTALL IN NEW CONCRETE SIDEWALK AND ASPHALT ROADWAY. SEE CIVIL FOR

ADDITIONAL INFORMATION.

2. REFER TO SHEET E-501 & E-105 FOR ELECTRICAL REQUIREMENTS.

3. SYSTEM SHALL BE CONTROLLED UTILIZING WATTS CONTACTORPRO PANEL PM-L3 CAPABLE OF AUTOMATIC OR

MANUAL OPERATION, ADJUSTABLE TRIGGER TEMPERATURE AND ADJUSTABLE DRYING CYCLE. PLACE NEW

CONTROL PANEL WITHIN ROOM C1-21.

PM-2

PM-1

PM-1

PM-2

10'

2'

2'

6"

20'2'

2'

6"

KEY PLAN - CAMPUS

CORRIDOR

RESTROOM

LOBBY

C1-4 C1-5

C1-37

OFFICE LOCKER R

OFFICE

CORRIDOR

POLICE POLICE

ARMORY

POLICE

WINDOW C1-38

POLICE

C1-38

POLICE

POLICE STATION LIGHTING PLAN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

100% BID DOCUMENTSOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

17 MARCH 2023Revisions: Date:

CAMPUS

523-19-602

150 SOUTH HUNTINGTON AVENUE, BOSTON MA

VAMC BOSTON

JAMAICA PLAIN CAMPUS

SITE SECURITY UPGRADES

THINKFORM DESIGN ARCHITECT LLC

38 EAST BROAD STREET

HOPEWELL, NJ 08525

T:855.821.0274 F:609.644.4397 Russell DiNardo, AIA NY 031521-1

A/E:

WATSON ENGINEERING

4500 STATE ROUTE 434

APALACHIN, NY 13732

PHONE: (607) 223-4334

EMW MAK

1/4" = 1'-0"EL-101

EL-101

POLICE STATION LIGHTING PLAN

GENERAL ELECTRICAL NOTES:

1. ALL ELECTRICAL WORK SHALL CONFORM TO ALL STATE, LOCAL, AND NATIONAL ELECTRICAL CODES.

2. ELECTRICAL CHARACTERISTICS SHALL BE VERIFIED WITH EQUIPMENT MANUFACTURER.

3. THE CONTRACTOR SHALL FIELD VERIFY ALL LOCATIONS AND DIMENSIONS SHOWN ON DRAWINGS AND

COORDINATE THE INSTALLATION OF ALL EQUIPMENT WITH OTHER CONTRACTORS.

4. ALL AREAS DISTURBED BY WORK SHALL BE RESTORED TO A CONDITION EQUAL TO OR BETTER THAN ORIGINAL AS

DETERMINED BY THE COR.

5. ALL ELECTRICAL CONDUIT AND CONDUCTORS DISCONNECTED AND NOT TO BE REUSED SHALL BE REMOVED.

6. ANY WALL PENETRATIONS MADE FOR CONDUIT RUNS SHALL BE PROPERLY SEALED FOR FIRE RATING.

7. SEE DETAIL 5 ON SHEET E501 FOR PENETRATION DETAIL.

8. PROVIDE MEANS OF DISCONNECT FOR ALL NEW EQUIPMENT.

KEYED NOTES:

INSTALL NEW 2X2 LIGHT LED FIXTURE. REFER TO LIGHT FIXTURE SCHEDULE ON SHEET E-501.1

KEY PLAN - FIRST FLOOR

A A

A

A

E

E

E

E

E

E

E

E

E

EE

E

E

E

E

E

E

E

E E

E

E

E

E

P P

P

P P

P

P

P

SOUTH HUNTINGTON AVE

E V

E R

G R

E E

N S

T

K E

N N

E Y

S T

N

IR

A A

V E

G R

O T

T O

G L

E N

R D

ESTEY ST.

H E

A T

H S

T R

E E

T

A R

C O

L A

S T

SITE LIGHTING PLAN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

100% BID DOCUMENTSOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

17 MARCH 2023Revisions: Date:

CAMPUS

523-19-602

150 SOUTH HUNTINGTON AVENUE, BOSTON MA

VAMC BOSTON

JAMAICA PLAIN CAMPUS

SITE SECURITY UPGRADES

THINKFORM DESIGN ARCHITECT LLC

38 EAST BROAD STREET

HOPEWELL, NJ 08525

T:855.821.0274 F:609.644.4397 Russell DiNardo, AIA NY 031521-1

A/E:

WATSON ENGINEERING

4500 STATE ROUTE 434

APALACHIN, NY 13732

PHONE: (607) 223-4334

EMW MAK

1" = 20'-0"

EL-102

EL-102

SITE LIGHTING PLAN

KEY PLAN - CAMPUS

KEYED NOTES:

INSTALL NEW LIGHT POLE. REFER TO LIGHT FIXTURE SCHEDULE ON

SHEET E-501 FOR ADDITIONAL INFORMATION.1

GENERAL ELECTRICAL NOTES:

1. ALL ELECTRICAL WORK SHALL CONFORM TO ALL STATE, LOCAL, AND NATIONAL ELECTRICAL CODES.

2. ELECTRICAL CHARACTERISTICS SHALL BE VERIFIED WITH EQUIPMENT MANUFACTURER.

3. THE CONTRACTOR SHALL FIELD VERIFY ALL LOCATIONS AND DIMENSIONS SHOWN ON DRAWINGS AND

COORDINATE THE INSTALLATION OF ALL EQUIPMENT WITH OTHER CONTRACTORS.

4. ALL AREAS DISTURBED BY WORK SHALL BE RESTORED TO A CONDITION EQUAL TO OR BETTER THAN ORIGINAL AS

DETERMINED BY THE COR.

5. ALL ELECTRICAL CONDUIT AND CONDUCTORS DISCONNECTED AND NOT TO BE REUSED SHALL BE REMOVED.

6. ANY WALL PENETRATIONS MADE FOR CONDUIT RUNS SHALL BE PROPERLY SEALED FOR FIRE RATING.

7. NEW CIRCUITS FOR SITE LIGHTING SHALL BE INSTALLED, CONNECTING TO THE EXISTING LIGHTING CIRCUITS.

CONDUCTOR SIZE SHALL BE #10 AWG. CONDUITS SHALL BE 1" RIGID SCH. 80 PVC AND SHALL BE DIRECT BURIED IN

ACCORDANCE WITH PROJECT SPECIFICATIONS.

8. PROVIDE MEANS OF DISCONNECT FOR ALL NEW EQUIPMENT.

9. SITE LIGHTING BID INFORMATION:

9.1. BASE BID: PROVIDE COMPLETE SITE LIGHTING SYSTEM INCLUDING, BUT NOT LIMITED TO, LIGHT POLES, LIGHT

FOUNDATIONS, LIGHT FIXTURES, CONDUITS, CONDUCTORS, CIRCUITS, SITE TRENCHING AND PATCHING

ASSOCIATED WITH SITE LIGHT SYSTEM SHOWN ON PLANS AND IN SPECIFICATIONS.

9.2. DEDUCT ALTERNATE #1: PROVIDE COST FOR ELIMINATING COMPLETE SITE LIGHTING SYSTEM, INCLUDING ALL COMPONENTS AND WORK ASSOCIATED WITH LIGHT SYSTEM SHOWN ON PLANS AND IN SPECIFICATIONS.

10. GENERAL CONTRACTOR IS REQUIRED TO PERFORM UTILITY SURVEY FOR ALL AREAS OF EXCAVATION. ANY OBSTRUCTIONS SHALL BE BROUGHT TO EOR AND VA COR FOR FURTHER INSTRUCTIONS PRIOR TO EXCAVATION

NEW ELECTRICAL DIRECT-BURIED PVC CONDUIT FOR LIGHTING

NEW POLE MOUNTED SITE LIGHT FIXTURE

E

LEGEND

SL-1

1SL-1

1SL-1

Y S

T

N

IR

A A

V E

G R

O T

T O

G L

E N

R D

A R

C O

L A

S T

E

E

E

E E

E E

E E

E E

E

E

E

EEEE

E

E

E

E

E E

E

E

E

E

E E

E

E

E

E E

E

E

E

SOUTH HUNTINGTON AVE

E V

E R

G R

E E

N S

T

K E

N N

E Y

S T

N

IR

A A

V E

G R

O T

T O

G L

E N

R D

ESTEY ST.

H E

A T

H S

T R

E E

T

A R

C O

L A

S T

SITE LIGHTING PLAN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

100% BID DOCUMENTSOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

17 MARCH 2023Revisions: Date:

CAMPUS

523-19-602

150 SOUTH HUNTINGTON AVENUE, BOSTON MA

VAMC BOSTON

JAMAICA PLAIN CAMPUS

SITE SECURITY UPGRADES

THINKFORM DESIGN ARCHITECT LLC

38 EAST BROAD STREET

HOPEWELL, NJ 08525

T:855.821.0274 F:609.644.4397 Russell DiNardo, AIA NY 031521-1

A/E:

WATSON ENGINEERING

4500 STATE ROUTE 434

APALACHIN, NY 13732

PHONE: (607) 223-4334

EMW MAK

1" = 20'-0"

EL-103

EL-103

SITE LIGHTING PLAN

KEY PLAN - CAMPUS

1SL-1

1SL-1

1SL-1

SL-1

SL-1

1SL-1

NEW ELECTRICAL DIRECT-BURIED PVC CONDUIT FOR LIGHTING

NEW POLE MOUNTED SITE LIGHT FIXTURE

E

LEGEND

KEYED NOTES:

INSTALL NEW LIGHT POLE. REFER TO LIGHT FIXTURE SCHEDULE ON

SHEET E-501 FOR ADDITIONAL INFORMATION.

NEW SITE LIGHTING CIRCUIT SHALL BE POWERED FROM EXISTING PANEL

PRL1A WITHIN THE PARKING GARAGE. PROVIDE NEW CIRCUIT BREAKERS,

CONDUCTORS AND CONDUIT TO PROVIDE A COMPLETE, OPERATIONAL

SYSTEM.

GENERAL ELECTRICAL NOTES:

1. ALL ELECTRICAL WORK SHALL CONFORM TO ALL STATE, LOCAL, AND NATIONAL ELECTRICAL CODES.

2. ELECTRICAL CHARACTERISTICS SHALL BE VERIFIED WITH EQUIPMENT MANUFACTURER.

3. THE CONTRACTOR SHALL FIELD VERIFY ALL LOCATIONS AND DIMENSIONS SHOWN ON DRAWINGS AND

COORDINATE THE INSTALLATION OF ALL EQUIPMENT WITH OTHER CONTRACTORS.

4. ALL AREAS DISTURBED BY WORK SHALL BE RESTORED TO A CONDITION EQUAL TO OR BETTER THAN ORIGINAL AS

DETERMINED BY THE COR.

5. ALL ELECTRICAL CONDUIT AND CONDUCTORS DISCONNECTED AND NOT TO BE REUSED SHALL BE REMOVED.

6. ANY WALL PENETRATIONS MADE FOR CONDUIT RUNS SHALL BE PROPERLY SEALED FOR FIRE RATING.

7. NEW CIRCUITS FOR SITE LIGHTING SHALL BE INSTALLED, CONNECTING TO THE EXISTING LIGHTING CIRCUITS.

CONDUCTOR SIZE SHALL BE #10 AWG. CONDUITS SHALL BE 1" RIGID SCH. 80 PVC AND SHALL BE DIRECT BURIED IN

ACCORDANCE WITH PROJECT SPECIFICATIONS.

8. PROVIDE MEANS OF DISCONNECT FOR ALL NEW EQUIPMENT.

9. SITE LIGHTING BID INFORMATION:

9.1. BASE BID: PROVIDE COMPLETE SITE LIGHTING SYSTEM INCLUDING, BUT NOT LIMITED TO, LIGHT POLES, LIGHT

FOUNDATIONS, LIGHT FIXTURES, CONDUITS, CONDUCTORS, CIRCUITS, SITE TRENCHING AND PATCHING

ASSOCIATED WITH SITE LIGHT SYSTEM SHOWN ON PLANS AND IN SPECIFICATIONS.

9.2. DEDUCT ALTERNATE #1: PROVIDE COST FOR ELIMINATING COMPLETE SITE LIGHTING SYSTEM, INCLUDING ALL COMPONENTS AND WORK ASSOCIATED WITH LIGHT SYSTEM SHOWN ON PLANS AND IN SPECIFICATIONS.

10. GENERAL CONTRACTOR IS REQUIRED TO PERFORM UTILITY SURVEY FOR ALL AREAS OF EXCAVATION. ANY

E R

G R

E E

N S

T

K E

N N

E Y

S T

E

E

E

E

E

E

E

E

E

E E E E E

SOUTH HUNTINGTON AVE

E V

E R

G R

E E

N S

T

K E

N N

E Y

S T

N

IR

A A

V E

G R

O T

T O

G L

E N

R D

ESTEY ST.

H E

A T

H S

T R

E E

T

A R

C O

L A

S T

SITE LIGHTING PLAN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Fi le

P at h 6/

/2

:3

9:

P M

100% BID DOCUMENTSOffice of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

Project Director

17 MARCH 2023Revisions: Date:

CAMPUS

523-19-602

150 SOUTH HUNTINGTON AVENUE, BOSTON MA

VAMC BOSTON

JAMAICA PLAIN CAMPUS

SITE SECURITY UPGRADES

THINKFORM DESIGN ARCHITECT LLC

38 EAST BROAD STREET

HOPEWELL, NJ 08525

T:855.821.0274 F:609.644.4397 Russell DiNardo, AIA NY 031521-1

A/E:

WATSON ENGINEERING

4500 STATE ROUTE 434

APALACHIN, NY 13732

PHONE: (607) 223-4334

EMW MAK

1" = 20'-0"

EL-104

EL-104

SITE LIGHTING PLAN

KEY PLAN - CAMPUS

1SL-1

1SL-1

1SL-1

KEYED NOTES:

INSTALL NEW LIGHT POLE. REFER TO LIGHT FIXTURE SCHEDULE ON

SHEET E-501 FOR ADDITIONAL INFORMATION.1

NEW ELECTRICAL DIRECT-BURIED PVC CONDUIT FOR LIGHTING

NEW POLE MOUNTED SITE LIGHT FIXTURE

E

LEGEND

GENERAL ELECTRICAL NOTES:

1. ALL ELECTRICAL WORK SHALL CONFORM TO ALL STATE, LOCAL, AND NATIONAL ELECTRICAL CODES.

2. ELECTRICAL CHARACTERISTICS SHALL BE VERIFIED WITH EQUIPMENT…