515-18-109 Bid Drawings - Signed_Part6.pdf

PDF 11 MB Posted

Attached to
Z1DA--Renovate Outpatient Pharmacy & Urgent Care 515-18-109
Solicitation number
36C25020B0058
Issued by

About this file

This solicitation is for renovations to the Outpatient Pharmacy and Urgent Care at the Battle Creek Healthcare System located in Battle Creek, Michigan. The solicitation number is 36C25020B0058 and seeks bids to furnish all labor, materials, supervision, equipment, tools and other necessary resources for the project according to contract specifications, drawings, terms and conditions. Bids are due by September 10, 2020 at 2:00PM and will be opened at the Department of Veterans Affairs Network 10 Contracting Office located in Ann Arbor, Michigan. The procurement is set aside entirely for Service Disabled Veteran Owned Small Businesses and has a $39.5 million small business size standard. The place of performance for the project is 5500 Armstrong Road in Battle Creek. The soliciting agency is the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10.

View the file

Other files

Show all 18

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

UP

GFCITP

TP

G F

C I

G F

C I

TP

GFCI

TP

G F

C I

TP

G F

C I

G F

C I

T P

T P

T P

T P

T P

T P

T P

T P

T P

T P

G F

C I

TP

GFCI

T P

GFCI

GFCI

GFCI

GFCI

J

J

J

J

J

TP

GFCI

G F

C I

GFCI

J

J

GFCI

13.3

A

B

13.2

FF

GG

8 9 10

11 12 13

14 15

L P

-C B

MDP-2 A-3

RP-CB7;18

RP-CB7;22

RP-CB7;22

RP-CB7;22

RP-CB7;22

R P

-C B

;1

RP-CB8;11

A -1

A

-2RP-CB8;22

RP-CB7;12

RP-CB7;20

RP-CB7;20

RP-CB7;22

RP-CB8;24

R P

-C B

;2

RP-CB8;22

A-2;29

RP-CB8;29

RP-CB8;30

RP-CB8;29 RP-CB8;31

R P

-C B

;3

R P

-C B

;3

RP-CB8;4

R P

-C B

;4

R P

-C B

;5

RP-CB8;5

RP-CB8;8

RP-CB8;9

R P

-C B

;9

RP-CB8;9

RP-CB8;16

RP-CB8;1

RP-CB8;1

RP-CB7;12 RP-CB7;23

RP-CB7;18

RP-CB7;18

RP-CB8;23

RP-CB8;30

RP-CB7;18

RP-CB7;20

RP-CB7;20

RP-CB7;20

RP-CB7;24 RP-CB7;24

RP-CB7;24

RP-CB7;24

RP-CB7;24RP-CB7;24

RP-CB8;9EP-CB6;3

RP-CB8;9

EP-CB6;4 RP-CB8;6

EP-CB6;4

RP-CB8;6

RP-CB8;6

R P

-C B

;2

R P

-C B

;2

RP-CB8;24

R P

-C B

RP-CB7;23

RP-CB8;4

RP-CB8;4

EP-CB6;1 RP-CB8;3

EP-CB6;1

RP-CB7;23 RP-CB7;23

R P

-C B

;3

EP-CB6;2 RP-CB8;5

EP-CB6;2

RP-CB8;5

R P

-C B

;8

R P

-C B

;8

EP-CB6;3

RP-CB8;6

RP-CB8;11

RP-CB8;11

RP-CB8;12

RP-CB8;12

RP-CB8;13

RP-CB8;13 RP-CB8;11

RP-CB8;11

R P

-C B

;1

R P

-C B

;1

RP-CB8;14

RP-CB8;14

RP-CB8;16

EP-CB6;11

EP-CB6;11RP-CB8;16

R P

-C B

;1

RP-CB8;18

EP-CB6;10

EP-CB6;10RP-CB8;18

RP-CB8;18

E P

-C B

;8

R P

-C B

;2

RP-CB8;22

EP-CB6;6

RP-CB8;22

R P

-C B

;2

RP-CB8;25

EP-CB6;7

EP-CB6;7

RP-CB8;25

RP-CB8;25

RP-CB8;32

RP-CB8;31

RP-CB8;31

RP-CB8;31

RP-CB8;1

RP-CB7;18 RP-CB7;20

RP-CB7;23

CUH-02

R P

-C B

;8

RP-CB8;27

RP-CB8;28

A-1;6

RP-CB8;33

RP-CB8;13

RP-CB8;30

NURSE MANAGER

EQUIP. STORAGE

LINEN

STOR.

CORRIDOR

C06

STAFF TLT

STAFF TLT

STORAGE

ON-CALL

0097A

HAC

EXAM / FLEX M.H.

M.H. TLT

EXAM / FLEX M.H.

EXAM

SOILED

EXIST. IT CLOSET

CORRIDOR

C010

CORRIDOR

C012

ELECTRICAL CLOSET

ELECTRICAL CLOSET

GAS - EMPTY AND

IN-USE

OFFICE

MECH

0112A

PROCEDURE

0111A

PROCEDURE

0110A

STOR.

0110B

EXAM

EXAM

EXAM

PATIENT TLT

CLEAN

MED

MH EXAM

MH EXAM

TRIAGE

RECEPTION

0103A

PHOTO

VAULT

0103B

TRIAGE

ISO EXAM

PROCEDURE ROOM

VESTIBULE

C09

RP-CB8;21

RP-CB8;37 RP-CB8;38

RP-CB8;5

RP-CB8;30

RP-CB7;35

R P

-C B

;1

E P

-C B

;8

RP-CB8;10

RP-CB8;17

RP-CB8;29

RP-CB8;29

RP-CB8;30

RP-CB8;30

RP-CB8;19

RP-CB8;19

RP-CB8;19

RP-CB8;19

EP-CB6;18

EP-CB6;18

EP-CB6;19

EP-CB6;20

EP-CB6;21

EP-CB6;22

RP-CB8;29

RP-CB8;23

RP-CB8;23

RP-CB8;23

RP-CB8;23

RP-CB8;26

RP-CB8;23

EP-CB6;23

EP-CB6;23 EP-CB6;5

EP-CB6;5

RP-CB8;32

RP-CB8;32

RP-CB8;19

RP-CB8;1

RP-CB8;1

(TYP)

(TYP)

(TYP)

(TYP)

A-1;7

ACU-01-EVAP

RP-CB8;20

(R

(R

(ER) (ER)

MEDICAL

GAS

ALARM PANEL

MEDICAL

GAS

ALARM

PANEL

A-2;20

A-2;22

(TYP)

EP405

EP405

RP-CB8;3

EP-CB6;6RP-CB8;24

EY407

NURSE

CALL

ALARM PANEL

A-2;24

NURSE

CALL ALARM

PANEL

A-2; 26

RP-CB8;8

RP-CB8;8

(ER)

(ER)

GAS - FULL

RP-CB8;6

A-1;1

ACU-01-COND

RP-CB8;35

RP-CB7;22

CATV, 66" AFF

CATV, 66" AFF

CATV, 66" AFF

CATV, 66" AFF

Rx, 66" AFF

RP-CB8;2

RP-CB8;2

CATV, 66" AFF

RP-CB8;39 SHOWER

0106A

ISO / PATIENT TOILET

CATV, 66" AFF

EP-CB6;3

LP-CB8;17

LP-CB8;10

LP-CB8;15

CATV, 66" AFF

RP-CB8;29

CATV, 66" AFF

CATV, 66" AFF

CATV, 66" AFF

RP-CB8;31

RP-CB8;31

CATV, 66" AFF

CATV, 66" AFF

R P

-C B

;4 CATV, 66" AFF

6(TYP)

(TYP)

(TYP)

LEGEND:

(ER) - EXISTING TO REMAIN

(R) - RELOCATED

AREA NOT IN SCOPE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

GUIDON DESIGN INC. | 1221 N PENNSYLVANIA SUITE 200 | INDIANAPOLIS, IN 46202

317.800.6388 | WWW.GUIDONDESIGN.COM

GHAFARI ASSOCIATES LLC. | 17101 MICHIGAN AVENUE | DEARBORN, MI 48126

313.441.3000 | WWW.GHAFARI.COM

C g h a fa ri l o c a l c a c h e \R e v it \1

E

C

E N

T R

A L rv t_ p h e ro h a lli .r v t

/1

/2

:5

:5

P

M

EP404

POWER LARGE SCALE VIEW -

URGENT CARE

RENOVATE PHARMACY &

URGENT CARE

5500 Armstrong Road, Battle Creek

515-18-109

05/20/2020 M. Sabapathy P. Herohalli

100% BID DOCUMENTS

PART. SPRINKLERED

SCALE:

NORTH

EP101

1/4" = 1'-0"

1 POWER PLAN GROUND FLOOR - URGENT CARE

GENERAL NOTES :

1. REFER TO SHEET EO000 AND EO001 FOR SYMBOLS, DEMOLITION

AND GENERAL NOTES.

2. REFER TO SHEET EP701, EP702 AND EP703 FOR THE PANEL

SCHEDULES.

3. REFER SHEET EP-405 FOR MOUNTING DETAILS OF ALL RECEPTACLES IN

EXAM ROOMS.

187216

SHEET NOTES :

1. RECEPTACLES OF DIFFRENT MOUNTING HEIGHTS AT

HEADBOARDS OF EXAM, PROCEDURE ROOM TO BE COORDINATED.

REFER SECTIONS IN SHEET EP405.

2. ELECTRICAL PANEL A-1 AND A-2 ARE RELOACTED PANEL.

RP-CB8 AND LP-CB8 ARE NEW PANELS.

3. EMERGENCY RECEPTACLES IN URGENT CARE AREA IS CIRCUITED

EXISTING TO REMAIN CRITICAL BRANCH (ER)EP-EB2, AND NEW CRITICAL

BRANCH PANEL EP-CB6

4. PROVIDE DEDICATED CIRCUIT TO EMERGENCY RECEPTACLES IN

MENTAL HEALTH AND EXAM \ FLEX M.H ROOMS

5. PROVIDE TAMPER RESISTANT RECEPTACLES IN MENTAL

HEALTH ROOMS, EXAM / FLEX MENTAL HEALTH ROOMS

AND M.H TOILET.

6. COORDINATE HEIGHT OF TV RECEPTACLES, TYPE AND LEGEND

PRIOR TO ROUGH-IN. SEE ARCHITECTURAL DRAWINGS SHEET NUMBER

AF601.

7. CONNECT MEDICAL GAS ALARM PANEL AND NURSE CALL ALARM PANEL

TO RELOCATED PANEL A-1.

8. INSTALL DUPLEX (GFCI) RECEPTACLE AT THE SINKS .

9. PROVIDE JUNCTION BOX FOR CARD READER AUTO OPERATOR PUSH BUTTON.

COORDINATE WITH EY404 DRAWING.

10. PROVIDE JUNCTION BOX IN THE CEILING FOR SHUTTER. COORDINATE

WITH ARCHTECTURAL TRADES BEFORE INSTALLING.

11. CONTRACTOR TO PROVIDE 60A BREAKER FOR THE NEW SWITCH ADDED.

COORDINATE LOCATION WITH OWNER PRIOR TO INSTALLATION.

12. MECHANICAL CONTRACTOR TO PROVIDE DISCONNECTS.

REFER MECHANICAL SCHEDULES.

(TYP)

NOT TO SCALE

KEY PLAN - URGENT CARE

100% BID DOCUMENTS

Revisions: Date:

FIRST FLOOR

100' - 0"

TOP OF CONCRETE

WALL

104' - 0"

Level 6 100' - 0"

GRADE LEVEL

101' - 3"

FIRST FLOOR

100' - 0"

Level 6 100' - 0"

GRADE LEVEL

101' - 3"

RECEPTACLE MOUNTED AT 5'-6" AFF

TV COAX OUTLET MOUNTED AT 5'-6" AFF

TELEVISION, HDTV, 60" INCH

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

GUIDON DESIGN INC. | 1221 N PENNSYLVANIA SUITE 200 | INDIANAPOLIS, IN 46202

317.800.6388 | WWW.GUIDONDESIGN.COM

GHAFARI ASSOCIATES LLC. | 17101 MICHIGAN AVENUE | DEARBORN, MI 48126

313.441.3000 | WWW.GHAFARI.COM

C g h a fa ri l o c a l c a c h e \R e v it \1

E

C

E N

T R

A L rv t_ p h e ro h a lli .r v t

/1

/2

:2

:2

P

M

EP405

MOUNTING DETAILS RENOVATE PHARMACY &

URGENT CARE

5500 Armstrong Road, Battle Creek

515-18-109

05/20/2020 M. Sabapathy P. Herohalli

100% BID DOCUMENTS

PART. SPRINKLERED

RECEPTACLE

MOUNTED AT 3'-8"

RECEPTACLE

MOUNTED AT 1'-6"

RECEPTACLE

MOUNTED AT 5'-0"

SCALE:

NORTH

1" = 1'-0"

TYPICAL RECEPTACLE MOUNTING HEIGHTS - URGENT CARE

SCALE:

NORTH

1" = 1'-0"

TYPICAL RECEPTACLE MOUNTING HEIGHTS - URGENT CARE COUNTER

RECEPTACLE

MOUNTED AT 3'-8"

TV RECEPTACLE

MOUNTED AT 5'-6"

RECEPTACLE

MOUNTED AT 1'-6"

100% BID DOCUMENTS

Revisions: Date:

SCALE:

NORTH

1" = 1'-0"

TYPICAL POWER AND COAX MOUNTING DETAIL FOR TV

208Y/120V

3PH-4W

MDP-4 208/120V 3PH, 4W 600A MAIN DISTRIBUTION PANEL

(GROUND FLOOR)

PARTIAL SINGLE LINE DIAGRAM

4F12 4F094F09

MDP-5 208/120V 3PH, 4W

600A MAIN DISTRIBUTION PANEL

(GROUND FLOOR)

LP-CB8 RP-CB8

MDP-6 208Y/120V 3PH, 4W 3000A MAIN DISTRIBUTION PANEL

1600AF

1600AT

G

750KVA

EXISTING SWITCHBOARD (BLDG 137)

N E

ATS

1600 A

(BLDG 137)

A-1

208Y/120V

3PH-4W

MDP-2 (GROUND FLR)

A-2

208Y/120V

3PH-4W

208Y/120V

3PH-4W

(LIFE SAFTY BRANCH )

MDP-3 (ATTIC)

208Y/120V

3PH-4W

(CRITICAL BRANCH)

800A 125A

250A225A 225A

400A

208Y/120V

3PH-4W

(CRITICAL BRANCH)

250A

4F13

4F12

4F12

4F09

EP-CB1 EP-CB2 EP-CB6

208Y/120V

3PH-4W

208Y/120V

3PH-4W

208Y/120V

3PH-4W

208Y/120V

3PH-4W

208Y/120V

3PH-4W

150A 3P

225A 3P

LP-CB6 RP-CB6

150A 3P

225A 3P

150A 3P

225A 3P

600 AF

600 AT

600 AF

600 AT

600 AF

600 AT

600 AF

600 AT

LP-CB6 RP-CB6

4F12 4F12 4F13

4F08

OVERCURRENT

DEVICE RATING

(AMPS)

FEEDER

CODE

WIRE & CONDUIT SIZE (2 WIRE SYSTEM)

FEEDER

CODE

WIRE & CONDUIT SIZE (3 WIRE SYSTEM)

FEEDER

CODE

WIRE & CONDUIT SIZE (4 WIRE SYSTEM)

15 2F01 2#12 & 1#12GND IN 3/4"C 3F01 3#12 & 1#12GND IN 3/4"C 4F01 4#12 & 1#12GND IN 3/4"C

20 2F01 2#12 & 1#12GND IN 3/4"C 3F01 3#12 & 1#12GND IN 3/4"C 4F01 4#12 & 1#12GND IN 3/4"C

25 2F02 2#10 & 1#10GND IN 3/4"C 3F02 3#10 & 1#10GND IN 3/4"C 4F02 4#10 & 1#10GND IN 3/4"C

30 2F02 2#10 & 1#10GND IN 3/4"C 3F02 3#10 & 1#10GND IN 3/4"C 4F02 4#10 & 1#10GND IN 3/4"C

35 2F03 2#8 & 1#10GND IN 3/4"C 3F03 3#8 & 1#10GND IN 3/4"C 4F03 4#8 & 1#10GND IN 3/4"C

40 2F03 2#8 & 1#10GND IN 3/4"C 3F03 3#8 & 1#10GND IN 3/4"C 4F03 4#8 & 1#10GND IN 3/4"C

45 2F03 2#8 & 1#10GND IN 3/4"C 3F03 3#8 & 1#10GND IN 3/4"C 4F03 4#8 & 1#10GND IN 3/4"C

50 2F03 2#8 & 1#10GND IN 3/4"C 3F03 3#8 & 1#10GND IN 3/4"C 4F03 4#8 & 1#10GND IN 3/4"C

60 2F04 2#6 & 1#10GND IN 3/4"C 3F04 3#6 & 1#10GND IN 1"C 4F04 4#6 & 1#10GND IN 1"C

70 2F05 2#4 & 1#8GND IN 1"C 3F05 3#4 & 1#8GND IN 1"C 4F05 4#4 & 1#8GND IN 1-1/2"C

80 2F05 2#4 & 1#8GND IN 1"C 3F05 3#4 & 1#8GND IN 1"C 4F05 4#4 & 1#8GND IN 1-1/2"C

90 2F06 2#3 & 1#8GND IN 1"C 3F06 3#3 & 1#8GND IN 1-1/2"C 4F06 4#3 & 1#8GND IN 1-1/2"C

100 2F06 2#3 & 1#8GND IN 1"C 3F06 3#3 & 1#8GND IN 1-1/2"C 4F06 4#3 & 1#8GND IN 1-1/2"C

110 2F07 2#2 & 1#6GND IN 1"C 3F07 3#2 & 1#6GND IN 1-1/2"C 4F07 4#2 & 1#6GND IN 1-1/2"C

125 2F08 2#1 & 1#6GND IN 1-1/2"C 3F08 3#1 & 1#6GND IN 1-1/2"C 4F08 4#1 & 1#6GND IN 1-1/2"C

150 2F09 2#1/0 & 1#6GND IN 1-1/2"C 3F09 3#1/0 & 1#6GND IN 1-1/2"C 4F09 4#1/0 & 1#6GND IN 2"C

175 2F10 2#2/0 & 1#6GND IN 1-1/2"C 3F10 3#2/0 & 1#6GND IN 2"C 4F10 4#2/0 & 1#6GND IN 2"C

200 2F11 2#3/0 & 1#6GND IN 1-1/2"C 3F11 3#3/0 & 1#6GND IN 2"C 4F11 4#3/0 & 1#6GND IN 2"C

225 2F12 2#4/0 & 1#4GND IN 2"C 3F12 3#4/0 & 1#4GND IN 2"C 4F12 4#4/0 & 1#4GND IN 2-1/2"C

250 2F13 2-250 KCMIL & 1#4GND IN 2"C 3F13 3-250 KCMIL & 1#4GND IN 2-1/2"C 4F13 4-250 KCMIL & 1#4GND IN 2-1/2"C

300 2F14 2-350 KCMIL & 1#4GND IN 2-1/2"C 3F14 3-350 KCMIL & 1#4GND IN 3"C 4F14 4-350 KCMIL & 1#4GND IN 3"C

350 2F15 2-500 KCMIL & 1#3GND IN 3"C 3F15 3-500 KCMIL & 1#3GND IN 3"C 4F15 4-500 KCMIL & 1#3GND IN 3-1/2"C

400 2F15 2-500 KCMIL & 1#3GND IN 3"C 3F15 3-500 KCMIL & 1#3GND IN 3"C 4F15 4-500 KCMIL & 1#3GND IN 3-1/2"C

450 2F16 (2) 2#4/0 & 1#2GND IN 2"C 3F16 (2) 3#4/0 & 1#2GND IN 2"C 4F16 (2) 4#4/0 & 1#2GND IN 2-1/2"C

500 2F17 (2) 2-250 KCMIL & 1#2GND IN 2"C 3F17 (2) 3-250 KCMIL & 1#2GND IN 2-1/2"C 4F17 (2) 4-250 KCMIL & 1#2GND IN 2-1/2"C

600 2F18 (2) 2-350 KCMIL & 1#1GND IN 2-1/2"C 3F18 (2) 3-350 KCMIL & 1#1GND IN 3"C 4F18 (2) 4-350 KCMIL & 1#1GND IN 3"C

700 2F19 (2) 2-500 KCMIL & 1#1/0GND IN 3"C 3F19 (2) 3-500 KCMIL & 1#1/0GND IN 3"C 4F19 (2) 4-500 KCMIL & 1#1/0GND IN 3-1/2"C

800 2F19 (2) 2-500 KCMIL & 1#1/0GND IN 3"C 3F19 (2) 3-500 KCMIL & 1#1/0GND IN 3"C 4F19 (2) 4-500 KCMIL & 1#1/0GND IN 3-1/2"C

1000 2F20 (3) 2-500 KCMIL & 1#2/0GND IN 3"C 3F20 (3) 3-500 KCMIL & 1#2/0GND IN 3"C 4F20 (3) 4-500 KCMIL & 1#2/0GND IN 3-1/2"C

1200 2F21 (4) 2-350 KCMIL & 1#3/0GND IN 2-1/2"C 3F21 (4) 3-350 KCMIL & 1#3/0GND IN 3"C 4F21 (4) 4-350 KCMIL & 1#3/0GND IN 3"C

1600 2F22 (5) 2-500 KCMIL & 1#4/0GND IN 3"C 3F22 (5) 3-500 KCMIL & 1#4/0GND IN 3"C 4F22 (5) 4-500 KCMIL & 1#4/0GND IN 3-1/2"C

2000 2F23 (6) 2-500 KCMIL & 1-250KCMIL GND IN 3"C 3F23 (6) 3-500 KCMIL & 1-250KCMIL GND IN 3"C 4F23 (6) 4-500 KCMIL & 1-250KCMIL GND IN 3-1/2"C

2500 2F24 (7) 2-500 KCMIL & 1-350KCMIL GND IN 3"C 3F24 (7) 3-500 KCMIL & 1-350KCMIL GND IN 3"C 4F24 (7) 4-500 KCMIL & 1-350KCMIL GND IN 3-1/2"C

3000 2F25 (8) 2-500 KCMIL & 1-500KCMIL GND IN 3"C 3F25 (8) 3-500 KCMIL & 1-500KCMIL GND IN 3"C 4F25 (8) 4-500 KCMIL & 1-500KCMIL GND IN 3-1/2"C

3200 2F26 (9) 2-500 KCMIL & 1-500KCMIL GND IN 3"C 3F26 (9) 3-500 KCMIL & 1-500KCMIL GND IN 3"C 4F26 (9) 4-500 KCMIL & 1-500KCMIL GND IN 3-1/2"C

4000 2F27 (11) 2-500 KCMIL & 1-500KCMIL GND IN 3"C 3F27 (11) 3-500 KCMIL & 1-500KCMIL GND IN 3"C 4F27 (11) 4-500 KCMIL & 1-500KCMIL GND IN 3-1/2"C

BRANCH WIRING SCHEDULE (LINEAR LOADS)

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

GUIDON DESIGN INC. | 1221 N PENNSYLVANIA SUITE 200 | INDIANAPOLIS, IN 46202

317.800.6388 | WWW.GUIDONDESIGN.COM

GHAFARI ASSOCIATES LLC. | 17101 MICHIGAN AVENUE | DEARBORN, MI 48126

313.441.3000 | WWW.GHAFARI.COM

C g h a fa ri l o c a l c a c h e \R e v it \1

E

C

E N

T R

A L rv t_ p h e ro h a lli .r v t

/1

/2

:2

:2

P

M

EP601

ELECTRICAL POWER SINGLE LINE

DIAGRAMS

RENOVATE PHARMACY &

URGENT CARE

5500 Armstrong Road, Battle Creek

515-18-109

05/20/2020 M. Sabapathy P. Herohalli

100% BID DOCUMENTS

PART. SPRINKLERED

187216

SHEET NOTES :

1 PANEL A-1 AND A-2 ARE EXISTING RELOCATED.

2. PANEL RP-CB8 AND LP-CB8 ARE NEW PANEL.

3. PANEL EP-CB6 IS NEW CRITICAL BRANCH

PANEL ADDED TO THE EXISTING SWITCHBOARD

(BLDG 137)

GENERAL NOTES :

1. REFER TO EO000 FOR GENERAL NOTES AND

LEGEND.

2. ALL INFORMATION IN THE DRAWINGS ARE BASED

ON EXISTING INFORMATION PROVIDED BY

OWNER.

100% BID DOCUMENTS

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

GUIDON DESIGN INC. | 1221 N PENNSYLVANIA SUITE 200 | INDIANAPOLIS, IN 46202

317.800.6388 | WWW.GUIDONDESIGN.COM

GHAFARI ASSOCIATES LLC. | 17101 MICHIGAN AVENUE | DEARBORN, MI 48126

313.441.3000 | WWW.GHAFARI.COM

C g h a fa ri l o c a l c a c h e \R e v it \1

E

C

E N

T R

A L rv t_ p h e ro h a lli .r v t

/1

/2

:2

:2

P

M

EP701

ELECTRICAL POWER PANEL

BOARD SCHEDULES

RENOVATE PHARMACY &

URGENT CARE

5500 Armstrong Road, Battle Creek

515-18-109

05/20/2020 M. Sabapathy P. Herohalli

100% BID DOCUMENTS

PART. SPRINKLERED

187216

ISOLATED GROUND BUS: NO NEUTRAL BUS RATING: 100% ISC = 10 KAIC

GROUND BUS: YES NEUTRAL BUS: YES INTEGRAL SPD: NO

TOTAL 20.4 kVA 16.290 kVA

NON-COINCIDENT 0% 0.0 kVA S - SUB-FED DEMAND 16.290 kVA 45 A

PROCESS N - NON-COINCIDENT CONNECTED 20.380 kVA 56.6 A

HEATING P - PROCESS TOTAL

EQUIPMENT 0.0 kVA Not Computed 0.0 kVA H - HEATING

LARGEST MOTOR E - EQUIPMENT

MOTORS 0.7 kVA 100% 0.7 kVA LM - LARGEST MOTOR PH C 0 VA

RECEPT (REMAINDER) 8.180 kVA 50% 4.090 kVA M - MOTOR PH B 0 VA

RECEPT (FIRST 10 kVA) 10.000 kVA 100% 10.000 kVA R - RECEPTACLE PH A 20380 VA

LIGHTING L - LIGHTING CONNECTED

LOAD DESCRIPTION CONNECTED D.F. DEMAND CODE

41 EXISTING LOAD -- 1 20 -- 0 0 -- 20 1 -- SPARE 42

39 EXISTING LOAD -- 1 20 -- 0 0 1-#10, 1-#10, 1-#10 GND IN 3/4" C 30 1 M ACU-02-COND 40

37 EXISTING LOAD -- 1 20 -- 500 540 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R FILLING 0209 38

35 R FILLING 0209 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 0 0 -- 20 1 -- EXISTING LOAD 36

33 R VEST. / BOX BREAK DOWN 016 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 0 0 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R FILLING 0209 34

31 R PHARMACY WAITING 0202 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 720 900 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R NF AND PENDING 017 32

29 R PHARMACY WAITING 0202 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 0 0 -- 20 1 -- EXISTING LOAD 30

27 EXISTING LOAD -- 1 20 -- 0 0 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R PHARMACY DISPENSING 0202 28

25 R CONSULT 0205 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 360 720 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R CONSULT 0205 26

23 R CONSULT 0208, 0207 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 0 0 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R CONSULT 0207, 0206, 0204 24

21 R MECH 0214, SERVER FOR ROBOT 0213 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 0 0 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R CONSULT 0208 22

19 MECH-EF-01 M 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 700 0 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 E ACU-01-EVAP 20

17 R VAULT 0212, CALL ROOM 0211 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 0 0 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 M ACU-02-EVAP 18

15 E FILLING 0209 E 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 0 0 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R RECP - MECH 0227 16

13 R PHRM STORAGE 0215 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 1080 720 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R DISPENSING WINDOWS 0210 14

11 R IVG CONTROL MANAGER 0218 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 0 0 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R MAIL OUT 0216 12

9 R OFFICE 0220, 0219 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 0 0 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R OFFICE 1219, RECEIVING 0217 10

7 EXISTING LOAD -- 1 20 -- 500 540 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R WORK STATIONS 0221 8

5 EXISTING LOAD -- 1 20 -- 0 0 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R STF TLT 0223, HAC 0224, PS 0215 6

3 EXISTING LOAD -- 1 20 -- 0 0 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R BREAK RM LOCKERS 0225 4

1 EXISTING LOAD -- 1 20 -- 500 720 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R RECEPTACLES - CONFERENCE 0226 2

CKT

NO LOAD DESCRIPTION CODE POLE TRIP FEEDER

A B C A B C

FEEDER TRIP POLE CODE LOAD DESCRIPTION

CKT

NO

RP-CB6 SURFACE MDP-4 208/120 V, 3 PH, 4 W 225 A 225 A MCB

PANEL NAME LOCATION MOUNTING SUPPLIED FROM VOLTAGE BUS MAIN

ISOLATED GROUND BUS: NO NEUTRAL BUS RATING: 100% ISC = 10 KAIC

GROUND BUS: YES NEUTRAL BUS: YES INTEGRAL SPD: NO

TOTAL 2.6 kVA 2.636 kVA

NON-COINCIDENT 0% 0.0 kVA S - SUB-FED DEMAND 2.636 kVA 7 A

PROCESS N - NON-COINCIDENT CONNECTED 2.636 kVA 7.3 A

HEATING P - PROCESS TOTAL

EQUIPMENT H - HEATING

LARGEST MOTOR E - EQUIPMENT

MOTORS LM - LARGEST MOTOR PH C 500 VA

RECEPT (REMAINDER) 0.000 kVA 50% 0.000 kVA M - MOTOR PH B 910 VA

RECEPT (FIRST 10 kVA) 0.000 kVA 100% 0.000 kVA R - RECEPTACLE PH A 1226 VA

LIGHTING 1.1 kVA 100% 1.1 kVA L - LIGHTING CONNECTED

LOAD DESCRIPTION CONNECTED D.F. DEMAND CODE

41 SPACE -- -- -- -- 0 0 -- -- -- -- SPACE 42

39 SPACE -- -- -- -- 0 0 -- -- -- -- SPACE 40

37 SPACE -- -- -- -- 0 0 -- -- -- -- SPACE 38

35 SPACE -- -- -- -- 0 0 -- -- -- -- SPACE 36

33 SPACE -- -- -- -- 0 0 -- -- -- -- SPACE 34

31 SPACE -- -- -- -- 0 0 -- -- -- -- SPACE 32

29 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 30

27 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 28

25 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 26

23 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 24

21 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 22

19 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 20

17 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 18

15 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 16

13 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 14

11 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 12

9 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 10

7 L MECHANICAL 0227 L 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 0 0 -- 20 1 -- SPARE 8

5 EXISTING LOAD -- 1 20 -- 500 0 -- 20 1 -- SPARE 6

3 EXISTING LOAD -- 1 20 -- 500 410 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 L LIGHTS - PHARMACY WAITING, 016, 017 4

1 EXISTING LOAD -- 1 20 -- 500 726 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 L LIGHTS - PHARMACY 2

CKT

NO LOAD DESCRIPTION CODE POLE TRIP FEEDER

A B C A B C

FEEDER TRIP POLE CODE LOAD DESCRIPTION

CKT

NO

LP-CB6 SURFACE MDP-4 208/120 V, 3 PH, 4 W 100 A 100 A MCB

PANEL NAME LOCATION MOUNTING SUPPLIED FROM VOLTAGE BUS MAIN

ISOLATED GROUND BUS: NO NEUTRAL BUS RATING: 100% ISC = 10 KAIC

GROUND BUS: YES NEUTRAL BUS: YES INTEGRAL SPD: NO

TOTAL 0.9 kVA 0.940 kVA

NON-COINCIDENT 0% 0.0 kVA S - SUB-FED DEMAND 0.940 kVA 3 A

PROCESS N - NON-COINCIDENT CONNECTED 0.940 kVA 2.6 A

HEATING P - PROCESS TOTAL

EQUIPMENT H - HEATING

LARGEST MOTOR E - EQUIPMENT

MOTORS LM - LARGEST MOTOR PH C 0 VA

RECEPT (REMAINDER) 0.000 kVA 50% 0.000 kVA M - MOTOR PH B 419 VA

RECEPT (FIRST 10 kVA) 0.000 kVA 100% 0.000 kVA R - RECEPTACLE PH A 521 VA

LIGHTING 0.9 kVA 100% 0.9 kVA L - LIGHTING CONNECTED

LOAD DESCRIPTION CONNECTED D.F. DEMAND CODE

41 SPACE -- -- -- -- 0 0 -- -- -- -- SPACE 42

39 SPACE -- -- -- -- 0 0 -- -- -- -- SPACE 40

37 SPACE -- -- -- -- 0 0 -- -- -- -- SPACE 38

35 SPACE -- -- -- -- 0 0 -- -- -- -- SPACE 36

33 SPACE -- -- -- -- 0 0 -- -- -- -- SPACE 34

31 SPACE -- -- -- -- 0 0 -- -- -- -- SPACE 32

29 SPACE -- -- -- -- 0 0 -- -- -- -- SPACE 30

27 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 28

25 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 26

23 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 24

21 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 22

19 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 20

17 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 18

15 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 16

13 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 14

11 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 12

9 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 10

7 L AUDIOLOGY AND UC OFFICES 0048 L 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 411 0 -- 20 1 -- SPARE 8

5 LIGHTING - EMERGENCY EGRESS -- 1 20 -- 0 0 -- 20 1 -- SPARE 6

3 LIGHTING - MECH AREA -- 1 20 -- 0 419 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 L L AUDILGY & LCKRS 0052,0046,0047,0040 4

1 LIGHTING - UNFINISHED SHELL AREA -- 1 20 -- 0 110 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 L L CORRIDOR C01, AC 0051A, PF 0024 2

CKT

NO LOAD DESCRIPTION CODE POLE TRIP FEEDER

A B C A B C

FEEDER TRIP POLE CODE LOAD DESCRIPTION

CKT

NO

LP-CB7 SURFACE MDP-5 208/120 V, 3 PH, 4 W 150 A 150 A MCB

PANEL NAME LOCATION MOUNTING SUPPLIED FROM VOLTAGE BUS MAIN

ISOLATED GROUND BUS: NO NEUTRAL BUS RATING: 100% ISC = 10 KAIC

GROUND BUS: YES NEUTRAL BUS: YES INTEGRAL SPD: NO

TOTAL 19.0 kVA 16.460 kVA

NON-COINCIDENT 0% 0.0 kVA S - SUB-FED DEMAND 16.460 kVA 46 A

PROCESS N - NON-COINCIDENT CONNECTED 19.020 kVA 52.8 A

HEATING P - PROCESS TOTAL

EQUIPMENT 0.0 kVA Not Computed 0.0 kVA H - HEATING

LARGEST MOTOR E - EQUIPMENT

MOTORS 1.4 kVA 100% 1.4 kVA LM - LARGEST MOTOR PH C 8200 VA

RECEPT (REMAINDER) 5.120 kVA 50% 2.560 kVA M - MOTOR PH B 5680 VA

RECEPT (FIRST 10 kVA) 10.000 kVA 100% 10.000 kVA R - RECEPTACLE PH A 5140 VA

LIGHTING L - LIGHTING CONNECTED

LOAD DESCRIPTION CONNECTED D.F. DEMAND CODE

41 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 42

39 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 40

37 E AUDIOLOGY AND UC OFFICES 0048 E 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 0 0 -- 20 1 -- SPARE 38

35 MECH - CUH-02 M 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 700 700 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 M MECH -EF-02 36

33 E AUDIOLOGY AND UC OFFICES 0048 E 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 0 180 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R PATIENT FUNDS 0024 34

31 E AUDIOLOGY AND UC OFFICES 0048 E 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 0 0 -- 20 1 -- 32

29 E AUDIOLOGY AND UC OFFICES 0048 R; E 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 180 540 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R AGENT CASHIER 0051A 30

27 E AUDIOLOGY AND UC OFFICES 0048 E 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 0 0 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 E E AUDIOLOGY AND UC OFFICES 0048 28

25 E AUDIOLOGY AND UC OFFICES 0048 E 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 0 360 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R AUDIOLOGY AND UC OFFICES 0048 26

23 R NEW VESIBULE C09 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 900 1080 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R OFFICE 0112A 24

21 R AUDIOLOGY AND UC OFFICES 1044 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 1260 1080 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R PHYSICIAN AND SOCIAL WORK 416 22

19 R CORRIDOR C03 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 180 1080 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R STAFF TLT 150 20

17 R UC BREAK RM AND LOCKERS 1043 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 900 900 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R EQUIP. STORAGE 0091 18

15 R AUDIOLOGY AND UC OFFICES 0048 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 540 540 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R AUDIOLOGY AND UC OFFICES 0048 16

13 R AGENT CASHIER 1042 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 720 180 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R AUDIOLOGY AND UC OFFICES 0048 14

11 R AUDIOLOGY AND UC OFFICES 0048 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 360 360 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R UC WAITING 1002 12

9 EXISTING LOAD -- 1 20 -- 500 720 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R GENERAL WAITING 1001 10

7 EXISTING LOAD -- 1 20 -- 500 540 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R AUDIOLOGY EXAM 1048 8

5 EXISTING LOAD -- 1 20 -- 500 1080 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R AUDIOLOGY CLEAN 1049 6

3 EXISTING LOAD -- 1 20 -- 500 360 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R AUDIOLOGY AND UC OFFICES 0048 4

1 EXISTING LOAD -- 1 20 -- 500 1080 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R HVAC 395 2

CKT

NO LOAD DESCRIPTION CODE POLE TRIP FEEDER

A B C A B C

FEEDER TRIP POLE CODE LOAD DESCRIPTION

CKT

NO

RP-CB7 SURFACE MDP-5 208/120 V, 3 PH, 4 W 225 A 225 A MCB

PANEL NAME LOCATION MOUNTING SUPPLIED FROM VOLTAGE BUS MAIN

ELEC ROOM 0F-020E ELEC ROOM 0F-020E

ELEC ROOM 0G-010E

ELEC ROOM 0G-010E(E)

(E)(E)

(E)

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

GUIDON DESIGN INC. | 1221 N PENNSYLVANIA SUITE 200 | INDIANAPOLIS, IN 46202

317.800.6388 | WWW.GUIDONDESIGN.COM

GHAFARI ASSOCIATES LLC. | 17101 MICHIGAN AVENUE | DEARBORN, MI 48126

313.441.3000 | WWW.GHAFARI.COM

C g h a fa ri l o c a l c a c h e \R e v it \1

E

C

E N

T R

A L rv t_ p h e ro h a lli .r v t

/1

/2

:2

:3

P

M

EP702

ELECTRICAL POWER PANEL

BOARD SCHEDULES

RENOVATE PHARMACY &

URGENT CARE

5500 Armstrong Road, Battle Creek

515-18-109

05/20/2020 M. Sabapathy P. Herohalli

100% BID DOCUMENTS

PART. SPRINKLERED

187216

ISOLATED GROUND BUS: NO NEUTRAL BUS RATING: 100% ISC = 10 KAIC

GROUND BUS: YES NEUTRAL BUS: YES INTEGRAL SPD: NO

TOTAL 2.2 kVA 2.241 kVA

NON-COINCIDENT 0% 0.0 kVA S - SUBFED DEMAND 2.241 kVA 6 A

PROCESS N - NON-COINCIDENT CONNECTED 2.241 kVA 6.2 A

HEATING P - PROCESS TOTAL

EQUIPMENT 0.0 kVA Not Computed 0.0 kVA H - HEATING

LARGEST MOTOR E - EQUIPMENT

MOTORS LM - LARGEST MOTOR PH C 354 VA

RECEPT (REMAINDER) 0.000 kVA 50% 0.000 kVA M - MOTOR PH B 712 VA

RECEPT (FIRST 10 kVA) 0.000 kVA 100% 0.000 kVA R - RECEPTACLE PH A 1175 VA

LIGHTING 2.2 kVA 100% 2.2 kVA L - LIGHTING CONNECTED

LOAD DESCRIPTION CONNECTED D.F. DEMAND CODE

41 SPACE -- -- -- -- 0 0 -- -- -- -- SPACE 42

39 SPACE -- -- -- -- 0 0 -- -- -- -- SPACE 40

37 SPACE -- -- -- -- 0 0 -- -- -- -- SPACE 38

35 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 36

33 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 34

31 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 32

29 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 30

27 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 28

25 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 26

23 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 24

21 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 22

19 L EXAM 0119, SOILED 0118 L 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 44 0 -- 20 1 -- SPARE 20

17 E PROCEDURE ROOM 0108 E 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 0 0 -- 20 1 -- SPARE 18

15 E PROCEDURE 0111A E 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 0 0 -- 20 1 -- SPARE 16

13 L MH EXAM 0124 L 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 128 128 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 L L EXAM / FLEX M.H. 0120 14

11 L EXAM / FLEX M.H. 0121 L 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 64 128 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 L L MH EXAM 0123 12

9 L CORRIDOR C06, VESTIBULE C09 L 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 242 0 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 E E PROCEDURE 0110A 10

7 L CLN 0133,EXM 0132,0128,0127,N/D... L 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 243 228 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 L L OFC 0112, PROCEDR RM 0110A, 0111A 8

5 L TRIAGE 0125, MH TLT 0122 L 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 59 103 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 L L RECP 0103A, PHOTO 0104, TRG 0105A 6

3 L CORRIDOR C012 L 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 286 184 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 L L ISO EXM 0107, PRDR RM 0108 4

1 L WALK-IN ENTRANCE 0100 L 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 72 332 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 L L CORRIDOR C014, SOUTH ENTRANCE 2

CKT

NO LOAD DESCRIPTION CODE POLE TRIP FEEDER

A B C A B C

FEEDER TRIP POLE CODE LOAD DESCRIPTION

CKT

NO

LP-CB8 ELECTRICAL CLOSET 0115 SURFACE MDP-5 208/120 V, 3 PH, 4 W 150 A 150 A MCB

PANEL NAME LOCATION MOUNTING SUPPLIED FROM VOLTAGE BUS MAIN

ISOLATED GROUND BUS: NO NEUTRAL BUS RATING: 100% ISC = 10 KAIC

GROUND BUS: YES NEUTRAL BUS: YES INTEGRAL SPD: NO

TOTAL 5.4 kVA 5.380 kVA

NON-COINCIDENT 0% 0.0 kVA S - SUB-FED DEMAND 5.380 kVA 15 A

PROCESS N - NON-COINCIDENT CONNECTED 5.380 kVA 14.9 A

HEATING P - PROCESS TOTAL

EQUIPMENT 0.0 kVA Not Computed 0.0 kVA H - HEATING

LARGEST MOTOR E - EQUIPMENT

MOTORS 0.7 kVA 100% 0.7 kVA LM - LARGEST MOTOR PH C 2500 VA

RECEPT (REMAINDER) 0.000 kVA 50% 0.000 kVA M - MOTOR PH B 2000 VA

RECEPT (FIRST 10 kVA) 0.180 kVA 100% 0.180 kVA R - RECEPTACLE PH A 880 VA

LIGHTING L - LIGHTING CONNECTED

LOAD DESCRIPTION CONNECTED D.F. DEMAND CODE

41 SPARE -- 1 20 -- 0 500 -- 20 1 -- EXISTING LOAD 42

39 SPARE -- 1 20 -- 0 500 -- 20 1 -- EXISTING LOAD 40

37 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 38

35 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 36

33 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 34

31 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 32

29 SPARE -- 1 20 -- 0 500 -- 20 1 -- EXISTING LOAD 30

27 SPARE -- 1 20 -- 0 500 -- 20 1 -- EXISTING LOAD 28

25 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 26

23 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 24

21 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 22

19 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 20

17 SPARE -- 1 20 -- 0 500 -- 20 1 -- EXISTING LOAD 18

15 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 16

13 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 14

11 SPARE -- 1 20 -- 0 500 -- 20 1 -- EXISTING LOAD 12

9 500 -- 20 1 -- EXISTING LOAD 10

7 R NURSE / DICTATION 0131 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 180 0 -- 20 1 -- SPARE 8

5 EXISTING LOAD -- 1 20 -- 500 0 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 E CORRIDOR C012 6

3 SPARE -- 1 20 -- 0 500 -- 20 1 -- EXISTING LOAD 4

1 IT SWITCH - IT CLOSET 0117 M 1 60 1-#6, 1-#6, 1-#10 GND IN 1" C 700 0 -- 20 1 -- SPARE 2

CKT

NO LOAD DESCRIPTION CODE POLE TRIP FEEDER

A B C A B C

FEEDER TRIP POLE CODE LOAD DESCRIPTION

CKT

NO

A-1 ELECTRICAL CLOSET 0114 SURFACE MDP-2 208/120 V, 3 PH, 4 W 100 A 100 A MCB

PANEL NAME LOCATION MOUNTING SUPPLIED FROM VOLTAGE BUS MAIN

ISOLATED GROUND BUS: NO NEUTRAL BUS RATING: 100% ISC = 10 KAIC

GROUND BUS: YES NEUTRAL BUS: YES INTEGRAL SPD: NO

TOTAL 10.1 kVA 10.080 kVA

NON-COINCIDENT 0% 0.0 kVA S - SUB-FED DEMAND 10.080 kVA 28 A

PROCESS N - NON-COINCIDENT CONNECTED 10.080 kVA 28.0 A

HEATING P - PROCESS TOTAL

EQUIPMENT H - HEATING

LARGEST MOTOR E - EQUIPMENT

MOTORS LM - LARGEST MOTOR PH C 2720 VA

RECEPT (REMAINDER) 0.000 kVA 50% 0.000 kVA M - MOTOR PH B 3680 VA

RECEPT (FIRST 10 kVA) 1.080 kVA 100% 1.080 kVA R - RECEPTACLE PH A 3680 VA

LIGHTING L - LIGHTING CONNECTED

LOAD DESCRIPTION CONNECTED D.F. DEMAND CODE

31 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 32

29 R NURSE 0135A R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 180 0 -- 20 1 -- SPARE 30

27 EXISTING LOAD -- 1 20 -- 500 0 -- 20 1 -- SPARE 28

25 EXISTING LOAD -- 1 20 -- 500 0 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 S NURSE CALL PANEL 26

23 EXISTING LOAD -- 1 20 -- 500 0 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 S NURSE CALL PANEL 24

21 EXISTING LOAD -- 1 20 -- 500 0 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 S MED GAS PANEL 22

19 EXISTING LOAD -- 1 20 -- 500 0 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 S MED GAS PANEL 20

17 EXISTING LOAD -- 1 20 -- 500 180 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R PHARM. STORAGE 0215 18

15 EXISTING LOAD -- 1 20 -- 500 500 -- 20 1 -- EXISTING LOAD 16

13 EXISTING LOAD -- 1 20 -- 500 500 -- 20 1 -- EXISTING LOAD 14

11 EXISTING LOAD -- 1 20 -- 500 500 -- 20 1 -- EXISTING LOAD 12

9 EXISTING LOAD -- 1 20 -- 500 500 -- 20 1 -- EXISTING LOAD 10

7 EXISTING LOAD -- 1 20 -- 500 500 -- 20 1 -- EXISTING LOAD 8

5 R SERVER FOR ROBOT 0213 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 180 180 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R MECH 0214 6

3 R FILLING 0209 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 180 500 -- 20 1 -- EXISTING LOAD 4

1 R PHARM. STORAGE 0215 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 180 500 -- 20 1 -- EXISTING LOAD 2

CKT

NO LOAD DESCRIPTION CODE POLE TRIP FEEDER

A B C A B C

FEEDER TRIP POLE CODE LOAD DESCRIPTION

CKT

NO

A-2 ELECTRICAL CLOSET 0114 SURFACE MDP-2 208/120 V, 3 PH, 4 W 100 A 100 A MCB

PANEL NAME LOCATION MOUNTING SUPPLIED FROM VOLTAGE BUS MAIN

ISOLATED GROUND BUS: NO NEUTRAL BUS RATING: 100% ISC = 10 KAIC

GROUND BUS: YES NEUTRAL BUS: YES INTEGRAL SPD: NO

TOTAL 26.2 kVA 19.160 kVA

NON-COINCIDENT 0% 0.0 kVA S - SUB-FED DEMAND 19.160 kVA 53 A

PROCESS N - NON-COINCIDENT CONNECTED 26.220 kVA 72.8 A

HEATING P - PROCESS TOTAL

EQUIPMENT 0.0 kVA Not Computed 0.0 kVA H - HEATING

LARGEST MOTOR E - EQUIPMENT

MOTORS 2.1 kVA 100% 2.1 kVA LM - LARGEST MOTOR PH C 9880 VA

RECEPT (REMAINDER) 14.120 kVA 50% 7.060 kVA M - MOTOR PH B 7000 VA

RECEPT (FIRST 10 kVA) 10.000 kVA 100% 10.000 kVA R - RECEPTACLE PH A 9340 VA

LIGHTING L - LIGHTING CONNECTED

LOAD DESCRIPTION CONNECTED D.F. DEMAND CODE

41 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 42

39 R CORRIDOR C011 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 180 360 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R GENERAL WAITING 0101 40

37 E EXAM / FLEX M.H. 0121 E 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 0 0 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 E E EXAM / FLEX M.H. 0120 38

35 R EXAM M 1 60 1-#4, 1-#4, 1-#10 GND IN 3/4" C 700 540 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R CORRIDOR C06 36

33 E NURSE / DICTATION 0131 E 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 0 540 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R Room-1 1047-1 34

31 R EXAM 0128 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 1080 720 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R EXAM 0128 32

29 R EXAM / MH 0126 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 1080 1080 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R CLEAN 0133 30

27 R EXAM E 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 0 0 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 E R EXAM 28

25 R EXAM 0119 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 1080 360 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R EXAM 0127 26

23 R EXAM 0127 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 1080 900 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R EXAM 0120 24

21 R EXAM 1029 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 180 1080 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R EXAM 0121 22

19 R EXAM 0132 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 1080 700 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 M ACU-01-EVAP 20

17 E NURSE 0135A E 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 0 1080 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R EXAM / OBS 0123 18

15 MECH- CUH-01 M 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 700 900 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R EXAM/ OBS 1032 16

13 R PHOTO 0104 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 720 720 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R TRIAGE 1033 14

11 R CORRIDOR 1004 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 900 360 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R; E R RECEPTION 0103A 12

9 R PROCEDURE ROOM 0108 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 1080 0 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 E E NURSE 0135A 10

7 R UC WAITING 1002 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 540 1080 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R PROCEDURE ROOM 0108 8

5 R TRAUMA 1013 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 1080 1080 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R TRAUMA 1013 6

3 R TRAUMA 1014 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 900 1080 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R TRAUMA 0111A 4

1 R CORRIDOR 1004 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 900 360 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R UC WAITING 0102 2

CKT

NO LOAD DESCRIPTION CODE POLE TRIP FEEDER

A B C A B C

FEEDER TRIP POLE CODE LOAD DESCRIPTION

CKT

NO

RP-CB8 ELECTRICAL CLOSET 0115 SURFACE MDP-5 208/120 V, 3 PH, 4 W 225 A 225 A MCB

PANEL NAME LOCATION MOUNTING SUPPLIED FROM VOLTAGE BUS MAIN

(ER) (ER)

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

GUIDON DESIGN INC. | 1221 N PENNSYLVANIA SUITE 200 | INDIANAPOLIS, IN 46202

317.800.6388 | WWW.GUIDONDESIGN.COM

GHAFARI ASSOCIATES LLC. | 17101 MICHIGAN AVENUE | DEARBORN, MI 48126

313.441.3000 | WWW.GHAFARI.COM

C g h a fa ri l o c a l c a c h e \R e v it \1

E

C

E N

T R

A L rv t_ p h e ro h a lli .r v t

/1

/2

:2

:3

P

M

EP703

ELECTRICAL POWER PANEL

BOARD SCHEDULES

RENOVATE PHARMACY &

URGENT CARE

5500 Armstrong Road, Battle Creek

515-18-109

05/20/2020 M. Sabapathy P. Herohalli

100% BID DOCUMENTS

PART. SPRINKLERED

ISOLATED GROUND BUS: NO NEUTRAL BUS RATING: 100% ISC = 10 KAIC

GROUND BUS: YES NEUTRAL BUS: YES INTEGRAL SPD: NO

TOTAL 12.5 kVA 12.456 kVA

NON-COINCIDENT 0% 0.0 kVA S - SUB-FED DEMAND 12.456 kVA 35 A

PROCESS N - NON-COINCIDENT CONNECTED 12.456 kVA 34.6 A

HEATING P - PROCESS TOTAL

EQUIPMENT H - HEATING

LARGEST MOTOR E - EQUIPMENT

MOTORS LM - LARGEST MOTOR PH C 3318 VA

RECEPT (REMAINDER) 0.000 kVA 50% 0.000 kVA M - MOTOR PH B 4567 VA

RECEPT (FIRST 10 kVA) 0.000 kVA 100% 0.000 kVA R - RECEPTACLE PH A 4071 VA

LIGHTING 0.7 kVA 100% 0.7 kVA L - LIGHTING CONNECTED

LOAD DESCRIPTION CONNECTED D.F. DEMAND CODE

29 EXISTING LOAD -- 1 20 -- 500 500 -- 20 1 -- EXISTING LOAD 30

27 EXISTING LOAD -- 1 20 -- 500 500 -- 20 1 -- EXISTING LOAD 28

25 EXISTING LOAD -- 1 20 -- 500 500 -- 20 1 -- EXISTING LOAD 26

23 SPARE -- 1 20 -- 0 500 -- 20 1 -- EXISTING LOAD 24

21 EXISTING LOAD -- 1 20 -- 500 500 -- 20 1 -- EXISTING LOAD 22

19 EXISTING LOAD -- 1 20 -- 500 500 -- 20 1 -- EXISTING LOAD 20

17 EXISTING LOAD -- 1 20 -- 500 0 -- 20 1 -- SPARE 18

15 EXISTING LOAD -- 1 20 -- 500 800 -- 20 1 -- EXISTING LOAD 16

13 EXISTING LOAD -- 1 20 -- 500 5 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 L L CORRIDOR C05 14

11 EXISTING LOAD -- 1 20 -- 500 154 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 L L CORRIDOR C05 12

9 EXISTING LOAD -- 1 20 -- 500 245 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 L L CORRIDOR C011 10

7 EXISTING LOAD -- 1 20 -- 500 500 -- 20 1 -- EXISTING LOAD 8

5 EXISTING LOAD -- 1 20 -- 500 164 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 L L PHARMACY WAITING, VEST BD 017 6

3 EXISTING LOAD -- 1 20 -- 500 22 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 L L TRAUMA STOR. 0110B 4

1 EXISTING LOAD -- 1 20 -- 500 66 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 L L MECH 0214, 0227, VAULT 0212, PWR... 2

CKT

NO LOAD DESCRIPTION CODE POLE TRIP FEEDER

A B C A B C

FEEDER TRIP POLE CODE LOAD DESCRIPTION

CKT

NO

EP-CB1 ELEC. 0069 SURFACE 208/120 V, 3 PH, 4 W 225 A 225 A MLO

PANEL NAME LOCATION MOUNTING SUPPLIED FROM VOLTAGE BUS MAIN

ISOLATED GROUND BUS: NO NEUTRAL BUS RATING: 100% ISC = 10 KAIC

GROUND BUS: YES NEUTRAL BUS: YES INTEGRAL SPD: NO

TOTAL 0.7 kVA 0.675 kVA

NON-COINCIDENT 0% 0.0 kVA S - SUB-FED DEMAND 0.675 kVA 2 A

PROCESS N - NON-COINCIDENT CONNECTED 0.675 kVA 1.9 A

HEATING P - PROCESS TOTAL

EQUIPMENT H - HEATING

LARGEST MOTOR E - EQUIPMENT

MOTORS LM - LARGEST MOTOR PH C 4000 VA

RECEPT (REMAINDER) 0.000 kVA 50% 0.000 kVA M - MOTOR PH B 4500 VA

RECEPT (FIRST 10 kVA) 0.000 kVA 100% 0.000 kVA R - RECEPTACLE PH A 4675 VA

LIGHTING 0.7 kVA 100% 0.7 kVA L - LIGHTING CONNECTED

LOAD DESCRIPTION CONNECTED D.F. DEMAND CODE

29 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 30

27 EXISTING LOAD -- 1 20 -- 500 500 -- 20 1 -- EXISTING LOAD 28

25 EXISTING LOAD -- 1 20 -- 500 500 -- 20 1 -- EXISTING LOAD 26

23 EXISTING LOAD -- 1 20 -- 500 500 -- 20 1 -- EXISTING LOAD 24

21 EXISTING LOAD -- 1 20 -- 500 500 -- 20 1 -- EXISTING LOAD 22

19 EXISTING LOAD -- 1 20 -- 500 500 -- 20 1 -- EXISTING LOAD 20

17 EXISTING LOAD -- 1 20 -- 500 500 -- 20 1 -- EXISTING LOAD 18

15 EXISTING LOAD -- 1 20 -- 500 500 -- 20 1 -- EXISTING LOAD 16

13 L TRIAGE 0125 L 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 357 318 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 L L PHARMACY AND PHARMACY WAITING 14

11 EXISTING LOAD -- 1 20 -- 500 500 -- 20 1 -- EXISTING LOAD 12

9 EXISTING LOAD -- 1 20 -- 500 0 -- 20 1 -- SPARE 10

7 EXISTING LOAD -- 1 20 -- 500 500 -- 20 1 -- EXISTING LOAD 8

5 EXISTING LOAD -- 1 20 -- 500 500 -- 20 1 -- EXISTING LOAD 6

3 EXISTING LOAD -- 1 20 -- 500 500 -- 20 1 -- EXISTING LOAD 4

1 EXISTING LOAD -- 1 20 -- 500 500 -- 20 1 -- EXISTING LOAD 2

CKT

NO LOAD DESCRIPTION CODE POLE TRIP FEEDER

A B C A B C

FEEDER TRIP POLE CODE LOAD DESCRIPTION

CKT

NO

EP-CB2 ELEC. 0069 SURFACE 208/120 V, 3 PH, 4 W 100 A 100 A MLO

PANEL NAME LOCATION MOUNTING SUPPLIED FROM VOLTAGE BUS MAIN

ISOLATED GROUND BUS: NO NEUTRAL BUS RATING: 100% ISC = 10 KAIC

GROUND BUS: YES NEUTRAL BUS: YES INTEGRAL SPD: NO

TOTAL 8.2 kVA 8.189 kVA

NON-COINCIDENT 0% 0.0 kVA S - SUB-FED DEMAND 8.189 kVA 23 A

PROCESS N - NON-COINCIDENT CONNECTED 8.189 kVA 22.7 A

HEATING P - PROCESS TOTAL

EQUIPMENT H - HEATING

LARGEST MOTOR E - EQUIPMENT

MOTORS 0.0 kVA Not Computed 0.0 kVA LM - LARGEST MOTOR PH C 2885 VA

RECEPT (REMAINDER) 0.000 kVA 50% 0.000 kVA M - MOTOR PH B 2577 VA

RECEPT (FIRST 10 kVA) 7.200 kVA 100% 7.200 kVA R - RECEPTACLE PH A 2727 VA

LIGHTING 1.0 kVA 100% 1.0 kVA L - LIGHTING CONNECTED

LOAD DESCRIPTION CONNECTED D.F. DEMAND CODE

41 SPACE -- -- -- -- 0 0 -- -- -- -- SPACE 42

39 SPACE -- -- -- -- 0 0 -- -- -- -- SPACE 40

37 SPACE -- -- -- -- 0 0 -- -- -- -- SPACE 38

35 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 36

33 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 34

31 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 32

29 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 30

27 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 28

25 SPARE -- 1 20 -- 0 0 -- 20 1 -- SPARE 26

23 R EXAM 0127 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 540 0 1-#10, 1-#10, 1-#10 GND IN 3/4" C 30 1 M SWITCH I.T. 0076 24

21 R MED 0130 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 180 180 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R MED 0130 22

19 R MED 0130 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 180 180 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R MED 0130 20

17 L EXAM / FLEX M.H. 0120 L 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 64 540 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R EXAM 0132 18

15 L MH EXAM 0123 L 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 64 128 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 L L EXAM / FLEX M.H. 0121 16

13 L AUDIOLOGY CLEAN 0046 L 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 143 64 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 L L MH EXAM 0124 14

11 R EXAM/ OBS 0124 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 540 301 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 L L AUDIOLOGY AND UC OFFICES 0048 12

9 L PATIENT FUNDS 0024 L 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 225 540 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R EXAM / OBS 0123 10

7 R EXAM 0119 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 540 540 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R EXAM 0121 8

5 R EXAM 0128 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 540 360 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R EXAM 0120 6

3 R PROCEDURE ROOM 0108 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 720 540 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R ISO EXAM 0107 4

1 R TRAUMA 1014 R 1 20 1-#12, 1-#12, 1-#12 GND IN 3/4" C 540 540 1-#12, 1-#12, 1-#12 GND IN 3/4" C 20 1 R R TRAUMA 0110A 2

CKT

NO LOAD DESCRIPTION CODE POLE TRIP FEEDER

A B C A B C

FEEDER TRIP POLE CODE LOAD DESCRIPTION

CKT

NO

EP-CB6 ELEC. 0069 SURFACE 208/120 V, 3 PH, 4 W 250 A 250 A MLO

PANEL NAME LOCATION MOUNTING SUPPLIED FROM VOLTAGE BUS MAIN

187216

MDP-3 SWBD 137

SWBD 137

100% BID DOCUMENTS

(ER) (ER)

MM

S S

4-PORT DATA OUTLET - WALL / FLOOR MOUNTED

MICROPHONE OUTLET - WALL / FLOOR MOUNTED

SPECIAL SYSTEMS SYMBOL LIST

PP

VC

TV

DC

MD

CR

B

SS

SCP

DOOR CONTACT

COAXIAL CABLE TV OUTLET (ONE F-TYPE CONNECTOR)

SPEAKER - WALL / CEILING MOUNTED

VOLUME CONTROL

PAGING SPEAKER - WALL / CEILING MOUNTED

CLOSED CIRCUIT TV CAMERA, FIXED

SECURITY CONTROL PANEL

MOTION DETECTOR

STANDARD CARD READER

DOOR BUZZER

SPEAKER - WALL / CEILING MOUNTED

F

360 DEGREE CAMERA F

CR CARD READER WITH PIN

CARD READER - AUTO OPERATORCR

P

AO

NEW WIRELESS ACCESS POINT

CR SCRAMBLE PROX CARD READERSP

R WIRELESS ACCESS POINT TO BE REMOVED AND RELOCATED

AUDIO STATION BED CONNECTOR

STAFF CONTROL - DESK MOUNT

SRS PATIENT STATION WITH CODE

REMOTE PULL SWITCH, BATH SWITCH WITH CANCEL SUPERVISED

DOME LIGHT - SINGLE - CEILING MOUNTED

NURSE CALL SYMBOL LIST

BC

SCDM

SR

CB

DSC

Es

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

Phase

ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT

321 4 5 6 7 8 9 10

GUIDON DESIGN INC. | 1221 N PENNSYLVANIA SUITE 200 | INDIANAPOLIS, IN 46202

317.800.6388 | WWW.GUIDONDESIGN.COM

GHAFARI ASSOCIATES LLC. | 17101 MICHIGAN AVENUE | DEARBORN, MI 48126

313.441.3000 | WWW.GHAFARI.COM

C g h a fa ri l o c a l c a c h e \R e v it \1

E

C

E N

T R

A L rv t_ s p a n d y a E

Y G

X .r v t

/1

/2

:3 :4

P

M

EY000

ELECTRICAL AUXILIARY SYSTEMS

SYMBOLS

RENOVATE PHARMACY &

URGENT CARE

5500 Armstrong Road, Battle Creek

515-18-109

05/20/2020 M. Sabapathy P. Herohalli

100% BID DOCUMENTS

PART. SPRINKLERED

100% BID DOCUMENTS

187216

GENERAL NOTES

1. ALL NOTES ON THE DRAWINGS INDICATED AS 'TYPICAL' SHALL APPLY TO THE ENTIRE

PROJECT, WHETHER OR NOT SPECIFICALLY INDICATED ON EACH DRAWING.

2. REFER TO ARCHITECTURAL DRAWINGS FOR EXACT LOCATIONS AND MOUNTING

HEIGHTS OF TECHNOLOGY INFRASTRUCTURE DEVICES.

3. REFER TO MECHANICAL, ELECTRICAL, PLUMBING AND FIRE PROTECTION DRAWINGS

FOR EXACT LOCATIONS OF RELATED EQUIPMENT.

4. ELECTRICAL FEEDS AND CIRCUITS SHALL NOT BE RUN PARALLEL WITH ANY

TECHNOLOGY INFRASTRUCTURE CABLING OR RACEWAYS.

5. IF PARALLEL RUNS ARE UNAVOIDABLE, A MINIMUM OF 2'-0" SEPARATION FOR HIGH-

VOLTAGE (240VAC OR GREATER) AND 1'-0" SEPARATION FOR MEDIUM VOLTAGE

(120VAC) MUST BE MAINTAINED.

6. FOR EVERY "T.O." THE CONTRACTOR MUST SUPPLY TWO PATCH CORDS. 50% OF THE

TOTAL NUMBER OF PATCH CORDS MUST BE 7'-0" AND 50% MUST BE 10'-0".

7. FOR EVERY "T.O." THAT IS TERMINATED TO JACK ONLY OR BISCUIT JACK, INTENDED

FOR CONNECTION INSIDE A BACK BOX OR ENCLOSURE (SUCH AS CLOCKS), THE

CONTRACTOR MUST SUPPLY ONE PATCH CORD THAT IS 6" (SIX INCHES) IN LENGTH

8. ALL PATCH CORDS MUST MATCH CABLE SYSTEM, I.E. CAT 6A PATCH CORDS FOR A CAT

6A INSTALLATION.

9. ALL PENETRATIONS IN WALLS OR FLOORS SHALL BE FIRE STOPPED TO MEET LOCAL

CODES. FIRE STOP SHALL MATCH OR EXCEED THE ORIGINAL FIRE RATING OF THE

WALL OR FLOOR.

10. TELECOMMUNICATION OUTLETS SHALL BE MOUNTED WITHIN 12" OF POWER OUTLETS.

TELECOMMUNICATION OUTLETS SHALL BE MOUNTED AT THE SAME HEIGHT AS

ADJACENT POWER OUTLETS UNLESS OTHERWISE NOTED.TELECOMMUNICATION

OUTLETS MOUNTING HEIGHT TO BE COORDINATED WITH OWNER BEFORE

INSTALLATION.

11. CONTRACTOR SHALL COORDINATE FLOOR BOX LOCATIONS WITH ELECTRICAL

CONTRACTOR AND WITH FURNITURE INSTALLER PRIOR TO INSTALLATION.

HORIZONTAL CONDUITS

1. LOCATIONS ON THESE DRAWINGS INDICATE ONLY THE INTERCONNECTION BETWEEN

TERMINATION POINTS. THE EXACT PATH OF HORIZONTAL CONDUITS WILL BE DICTATED

BY ACTUAL FIELD CONDITIONS AND SHALL BE COORDINATED WITH THE ARCHITECT.

2. ALL CONDUIT MUST BE EMT. PROVIDE (1) CONDUIT FROM EACH T.O. TO THE CABLE

TRAY.

3. ALL CONDUITS SHALL BE DEBURRED, CLEANED, CAPPED, TAGGED AND FURNISHED

WITH PULL LINES.

4. ALL CONDUIT BENDS MUST BE A MINIMUM OF 6X INTERNAL CONDUIT DIAMETER FOR

50MM OR SMALLER CONDUIT AND A MINIMUM OF 10X INTERNAL CONDUIT DIAMETER

FOR CONDUIT LARGER THAN 50MM.

5. NO MORE THAN TWO 90° BENDS IN ANY ONE RUN ARE ALLOWED. IF MORE THAN TWO

90° BENDS ARE REQUIRED, A PULL BOX MUST BE USED.

6. REVERSE BENDS (180°) ARE NOT ACCEPTABLE.

7. IF A CONDUIT RUN EXCEEDS 30M, INSTALL PULL BOXES EVERY 30M.

8. PULL BOXES ARE NOT ALLOWED TO FORM A CORNER. PULL BOXES ARE TO BE USED

FOR STRAIGHT-LINE PULLS ONLY AND MUST BE LOCATED IN ACCESSIBLE LOCATION.

9. MINIMUM PULL BOX SIZE FOR SINGLE CONDUIT RUNS IS A 12MM SQUARE BOX.

10. FOR CONDUIT RUNS SERVING MULTIPLE TO'S, THE MINIMUM PULL BOX SIZE IS 100MM W

X 200MM L X 100MM D.

11. INSTALLATION OF TELECOMMUNICATIONS CABLING AND OUTLETS SHALL BE

COORDINATED WITH ARCHITECT, DESIGN-BUILDER AND FURNITURE SYSTEM.

12. ALL CABLE BEND RADIUS RULES SHALL BE OBSERVED IN ALL FURNITURE SYSTEM

PATHWAYS.

13. NO T.O. SHALL EXCEED CAT. 6A ALLOWABLE DISTANCE.

14. CONDUIT ROUTE AND CABLE FILL QUANTITIES MUST FOLLOW CURRENT CABLING

STANDARDS (ANSI/TIA/EIA AND BICSI TDMM) AND THE FOLLOWING TABLE(S):

BACKBONE CONDUITS AND SLEEVES

1. ALL CONDUIT BENDS MUST BE A MINIMUM OF 6X INTERNAL CONDUIT DIAMETER FOR

50MM OR SMALLER CONDUIT AND A MINIMUM OF 10X INTERNAL CONDUIT DIAMETER FOR

CONDUIT LARGER THAN 50MM.

2. PRIMARY CONDUIT RISER 100MM CONDUITS SHALL HAVE A MINIMUM OF 1220MM SWEEP

RADIUS.

3. NO MORE THAN TWO 90° BENDS IN ANY ONE RUN ARE ALLOWED. IF MORE THAN TWO 90°

BENDS ARE REQUIRED, A PULL BOX MUST BE USED.

4. REVERSE BENDS (180°) ARE NOT ACCEPTABLE.

5. IF A CONDUIT RUN EXCEEDS 100', INSTALL PULL BOXES EVERY 100'.

6. PULL BOXES ARE NOT ALLOWED TO FORM A CORNER. PULL BOXES ARE TO BE USED

FOR STRAIGHT-LINE PULLS ONLY AND MUST BE LOCATED IN ACCESSIBLE LOCATIONS.

7. CONDUIT SLEEVES SHALL PROTRUDE PAST FLOOR/CEILING BY NOT LESS THAN 100MM

AND NOT MORE THAN 150MM.

8. THE MINIMUM SIZE FOR A PULL BOX WITH 100MM CONDUITS IS 813MM PER SIDE.

GROUNDING AND BONDING

1. ALL TELECOMMUNICATIONS GROUNDING BUSBARS (TGB) IN TELECOMMUNICATION

CLOSET (TC) SHALL BE BONDED TO THE TELECOMMUNICATIONS MAIN GROUNDING

BUSBAR (TMGB) WITH A MINIMUM 4/0. SEE ELECTRICAL DRAWINGS FOR DIAGRAM.

2. ALL BACKBONE AND HORIZONTAL PATHWAYS AND CABLE MANAGEMENT COMPONENTS

INCLUDING CONDUITS, SLEEVES, LADDER RACK AND RELAY RACKS SHALL BE BONDED

TO THE TELECOMMUNICATIONS GROUNDING BUSBAR (TGB) IN THE TECHNOLOGY ROOM

THEY SERVE WITH A MINIMUM #6 AWG.

3. ALL CONNECTIONS TO BUSBARS AND FLAT METALLIC SURFACES SHALL BE MADE WITH

EXOTHERMIC WELDS OR LISTED TWO-HOLE COMPRESSION LUGS.

4. ALL SURFACES ARE TO BE CLEANED OR SANDED TO ACHIEVE METAL-TO-METAL

CONTACT, AND PROTECTED WITH NO-OX-ID GREASE.

5. ALL GROUND/BOND CONDUCTOR-TO-CONDUCTOR CONNECTIONS SHALL BE MADE WITH

H-TAPS WITH PROPER DIRECTIONAL TURNS IN THE DIRECTION OF THE TMGB.

6. A "DO NOT DISCONNECT" BRASS TAG SHALL BE AFFIXED TO BOTH ENDS OF ALL

GROUND/BOND CONDUCTORS AS NEAR AS POSSIBLE TO THE CONNECTION TO THE

GROUND BUS.

7. BOTH ENDS OF ALL GROUND/BOND CONDUCTORS SHALL HAVE LAMICOID DESTINATION

TAGS AFFIXED ADJACENT TO THE "DO NOT DISCONNECT" TAGS.

8. ALL GROUND/BOND CONDUCTORS SHALL BE FREE OF SHARP BENDS; THE NOMINAL

BEND RADIUS OF ALL GROUND/BOND CONDUCTORS SHALL BE NOT LESS THAN 8".

CODES, REGULATIONS AND STANDARDS

1. THE INSTALLATION SHALL BE IN COMPLIANCE WITH THE REQUIREMENTS

OF THE NATIONAL ELECTRICAL CODE, STANDARD BUILDING CODE, OSHA,

ANSI/TIA/EIA, IEEE, CDA, THE RECOMMENDATIONS AND THE RULES,

REGULATIONS AND REQUIREMENTS OF FEDERAL COMMUNICATIONS

COMMISSION.

2. ALL EQUIPMENT SHALL BE EQUAL TO OR EXCEED THE MINIMUM

REQUIREMENTS OF NEMA, IEEE, ASME, ANSI AND UNDERWRITERS'

LABORATORIES.

3. MATERIAL AND EQUIPMENT SHALL BEAR THE UL LABEL EXCEPT WHERE

UL DOES NOT LABEL SUCH TYPES OF MATERIAL AND EQUIPMENT.

4. IF A CONFLICT EXISTS BETWEEN APPLICABLE DOCUMENTS, THEN THE

ORDER IN THE LIST BELOW SHALL DICTATE THE ORDER OF PRECEDENCE

IN RESOLVING CONFLICTS. THIS ORDER OF PRECEDENCE SHALL BE

MAINTAINED UNLESS A LESSER ORDER DOCUMENT HAS BEEN ADOPTED

AS CODE BY A LOCAL, STATE OR FEDERAL ENTITY, AND IS THEREFORE

ENFORCEABLE AS LAW BY A LOCAL, STATE OR FEDERAL INSPECTION

AGENCY.

5. IF THIS DOCUMENT AND ANY OF THE DOCUMENTS LISTED BELOW ARE IN

CONFLICT, THEN THE MORE STRINGENT REQUIREMENT SHALL APPLY.

ALL DOCUMENTS LISTED ARE BELIEVED TO BE THE MOST CURRENT

RELEASES OF THE DOCUMENTS. THE VENDOR IS RESPONSIBLE TO

DETERMINE AND ADHERE TO THE MOST RECENT RELEASE WHEN

DEVELOPING…