515-18-109 Bid Drawings - Signed_Part4.pdf
PDF 15 MB Posted
- Solicitation number
- 36C25020B0058
About this file
This federal contract opportunity solicitation is for renovation services for an outpatient pharmacy and urgent care facility located at the Battle Creek Healthcare System in Battle Creek, Michigan. The solicitation number is 36C25020B0058 and seeks bids to furnish all labor, materials, supervision, equipment, tools and other necessary resources for the project according to contract specifications, drawings, terms and conditions. Site visits are scheduled and bids must be submitted in sealed envelopes to the Department of Veterans Affairs Network 10 Contracting Office by September 10, 2020 at 2:00PM. The place of performance is 5500 Armstrong RD, Battle Creek, Michigan 49037. This procurement is fully set aside for Service Disabled Veteran Owned Small Businesses and has a $39.5 million small business size standard. The soliciting agency is the Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| Covid Instructions.docx | DOCX document | |
| 36C25020B0058 0002.docx | DOCX document | |
| 515-18-109 Pre-Bid Attendance Sheet.pdf | ||
| RFi Answers.docx | DOCX document | |
| 515-18-109 Bid Drawings - Signed_Part1 - reissue.pdf | ||
| 36C25020B0058 0001.docx | DOCX document | |
| 515-18-109 Bid Specifications_Part3.pdf | ||
| WD MI20200079 7-24-20.pdf | ||
| Contractor EMR Certification Form 2020.docx | DOCX document | |
| 515-18-109 Bid Drawings - Signed_Part1.pdf | ||
| 515-18-109 Bid Drawings - Signed_Part2.pdf | ||
| 515-18-109 Bid Drawings - Signed_Part5.pdf | ||
| 515-18-109 Bid Drawings - Signed_Part3.pdf | ||
| S02 - RFI Form 515-18-109.docx | DOCX document | |
| 515-18-109 Bid Specifications_Part1.pdf | ||
| 515-18-109 Bid Specifications_Part2.pdf | ||
| 36C25020B0058.docx | DOCX document | |
| 515-18-109 Bid Drawings - Signed_Part6.pdf |
Show all 18
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
REF.REF.
REF.
REF.
UP
H
J
L
M
M.4
N
M.1
13.3
A
B
13.2
HH
FF
JJ
GG
KK
12 3 4 5 6 7 8 9 10 11 12 13 14 15
FA401
FA402
FA403
FA404
FA402
10.8
TEMPORARY
PHARMACY
(PHASE 1) OPEN
OFFICE AND
AUDIOLOGY
(PHASE 3)
PHARMACY
(PHASE 2)
URGENT CARE
(PHASE 4)
SHADE INDICATES
APPROXIMATE
AREA OUT OF
SCOPE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
GUIDON DESIGN INC. | 1221 N PENNSYLVANIA SUITE 200 | INDIANAPOLIS, IN 46202
317.800.6388 | WWW.GUIDONDESIGN.COM
GHAFARI ASSOCIATES LLC. | 17101 MICHIGAN AVENUE | DEARBORN, MI 48126
313.441.3000 | WWW.GHAFARI.COM
C g h a fa ri l o c a l c a c h e \R e v it \1
E
C
E N
T R
A L rv t_ p h e ro h a lli .r v t
/1
/2
:2
:4
P
M
FA101
FIRE DETECTION AND ALARM
GROUND FLOOR COMPOSITE
RENOVATE PHARMACY &
URGENT CARE
5500 Armstrong Road, Battle Creek
515-18-109
05/20/2020 M. Sabapathy P. Herohalli
100% BID DOCUMENTS
PART. SPRINKLERED
SCALE:
NORTH
EP405 3/32" = 1'-0"
1 FIRE ALARM PLAN GROUND FLOOR COMPOSITE
GENERAL NOTES :
1. REFER TO SHEET FA000 FOR SYMBOLS AND
GENERAL NOTES.
187216
NOT TO SCALE
KEY PLAN - GROUND FLOOR
100% BID DOCUMENTS
Revisions: Date:
REF. REF.
P
P
P
P
P
W F
W F
W F
H
J
L
M
M.4
N
M.1
HH
JJ
GG
KK
2 3 4 5 6 7 8
15cd
15cd
30cd
CONFERENCE RM
BREAK RM
0225 STAFF TLT
HAC
PHARM. STORAGE
MECHANICAL
WORK STATIONS
OFFICE
OFFICE
RECEIVING
INV. CONTROL
MANAGER
MAIL-OUT
DISPENSING WINDOWS
FILLING
CALL ROOM
VAULT
PHARMACY WORK RM
MECH
(TYP)
(TYP)
75cd
15cd
15cd
75cd
15cd
75cd
75cd
(R)
(ER)(ER) (ER)
(ER)
(ER)(ER)
(ER)
(ER)
(ER)
(ER)
(ER)
(ER)
(ER)
(ER)
(R)
(R)
(R)
(R)
(R)
(TYP)
(TYP)
(ER)
(ER)
15cd
15cd
15cd
15cd
15cd
STAIR
S6
Space
021G
15cd
15cd
Space
021H
EXIT PASSAGEWAY
01228
HOUSE KEEPING
HVAC
0020E
EP405
LEGEND:
(ER) - EXISTING TO REMAIN
(R) - RELOCATED
AREA NOT IN SCOPE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
GUIDON DESIGN INC. | 1221 N PENNSYLVANIA SUITE 200 | INDIANAPOLIS, IN 46202
317.800.6388 | WWW.GUIDONDESIGN.COM
GHAFARI ASSOCIATES LLC. | 17101 MICHIGAN AVENUE | DEARBORN, MI 48126
313.441.3000 | WWW.GHAFARI.COM
C g h a fa ri l o c a l c a c h e \R e v it \1
E
C
E N
T R
A L rv t_ p h e ro h a lli .r v t
/1
/2
:2
:5
P
M
FA401
FIRE ALARM LARGE SCALE VIEW -
PHARMACY
RENOVATE PHARMACY &
URGENT CARE
5500 Armstrong Road, Battle Creek
515-18-109
05/20/2020 M. Sabapathy P. Herohalli
100% BID DOCUMENTS
PART. SPRINKLERED
SCALE:
NORTH
FA101 1/4" = 1'-0"
1 FIRE ALARM PLAN GROUND FLOOR - PHARMACY
187216
GENERAL NOTES :
1. REFER TO SHEET FA000 FOR SYMBOLS AND GENERAL
NOTES.
2. EXISTING WORK IS SHOWN WITH LIGHT LINE WEIGHT.
NEW WORK IS SHOWN WITH HEAVY LINE WEIGHT.
3. FIRE ALARM DEVICES ( NOTIFICATION AND INITIATION
DEVICES) SHALL BE ADDRESSABLE AND CONNECTED TO
EXISTING FIRE ALARM CONTROL PANEL THROUGH SIGNAL
LINE OF CIRCUIT (SLC).
4. SPEAKERS/HORN WITH STROBE SHALL BE 15db ABOVE
AMIENT NOISE LEVEL.
SHEET NOTES :
1. INSTALL FIRE ALARM PULL STATIONS NEXT TO EXIT DOOR.
CONNECT TO FIRE ALARM SYSTEM LOOP .
2. INSTALL FIRE ALARM NOTIFICATION DEVICES AS INDICATED.
CONNECT IT TO EXISTING AND/OR NEW ADDRESSABLE SYSTEM
LOOP PER NFPA 72.
3. CONTRACTOR SHALL EXTEND WIRING BRANCH CIRCUITRY TO NEW
LOCATION OF RELOCATED DEVICES AS NECESSARY.
NOT TO SCALE
KEY PLAN - PHARMACY
FACP
P
P
P
P
B
FF
GG
2 3 4 5 6 7 8
75cd
30cd
CONSULT
CONSULT
CONSULT
HALL
CONSULT / DISPENSING
PHARMACY WAITING
CONSULT
CORRIDOR
C02
VEST. / BOX BREAK
DOWN
NF AND PENDING
CORRIDOR
C014
ELEC.
15cd
15cd
(TYP)
(ER)
(R)
(TYP)
(R)
(R)
(ER)
(ER)
(ER)
(ER)
(ER)
(ER)
(ER)
(ER)
(ER)
(ER)
(ER)
(ER)
(ER)
(ER)
(ER) (ER) (ER)
(ER)
I.T.
EXISTING IT ROOM EXISTING IT ROOM
EXISTING ELECTRICAL ROOM
15cd
(ER)
(ER)
EXIT PASSAGEWAY
01228
STOR.
016A
STAIR
S1
ELEV. MACH.
0018E
ELEV.
E2
ELEV.
E1
HVAC
0017E
HOUSE KEEPING
15cd
30cd
(ER)
A
7 8 9 10
75cd
UC WAITING
GENERAL WAITING
WALK-IN ENTRANCE
30cd
(TYP)
(TYP)
(R)
(ER)
(R)
(TYP)
CORRIDOR
C014
(TYP)
LEGEND:
(ER) - EXISTING TO REMAIN
(R) - RELOCATED
AREA NOT IN SCOPE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
GUIDON DESIGN INC. | 1221 N PENNSYLVANIA SUITE 200 | INDIANAPOLIS, IN 46202
317.800.6388 | WWW.GUIDONDESIGN.COM
GHAFARI ASSOCIATES LLC. | 17101 MICHIGAN AVENUE | DEARBORN, MI 48126
313.441.3000 | WWW.GHAFARI.COM
C g h a fa ri l o c a l c a c h e \R e v it \1
E
C
E N
T R
A L rv t_ p h e ro h a lli .r v t
/1
/2
:2
:5
P
M
FA402
FIRE ALARM LARGE SCALE VIEW -
WAITING AND ENTRANCE
RENOVATE PHARMACY &
URGENT CARE
5500 Armstrong Road, Battle Creek
515-18-109
05/20/2020 M. Sabapathy P. Herohalli
100% BID DOCUMENTS
PART. SPRINKLERED
SCALE:
NORTH
FA101 1/4" = 1'-0"
1 FIRE ALARM PLAN GROUND FLOOR - PHARMACY WAITING
SCALE:
NORTH
FA101 1/4" = 1'-0"
2 FIRE ALARM PLAN GROUND FLOOR - SOUTH ENTRANCE
187216
SHEET NOTES :
1. INSTALL FIRE ALARM PULL STATIONS NEXT TO EXIT DOOR.
CONNECT TO FIRE ALARM SYSTEM LOOP .
2. INSTALL FIRE ALARM NOTIFICATION DEVICES AS INDICATED.
CONNECT IT TO EXISTING ADDRESSABLE SYSTEM LOOP.
3. CONTRACTOR SHALL EXTEND WIRING BRANCH CIRCUITRY TO NEW
LOCATION OF RELOCATED DEVICES AS NECESSARY.
GENERAL NOTES :
1. REFER TO SHEET FA000 FOR SYMBOLS AND GENERAL
NOTES.
2. EXISTING WORK IS SHOWN WITH LIGHT LINE WEIGHT. NEW
WORK IS SHOWN WITH HEAVY LINE WEIGHT.
3. FIRE ALARM DEVICES ( NOTIFICATION AND INITIATION
DEVICES) SHALL BE ADDRESSABLE AND CONNECTED TO
EXISTING FIRE ALARM CONTROL PANEL THROUGH SIGNAL
LINE OF CIRCUIT (SLC).
4. SPEAKERS/HORN WITH STROBE SHALL BE 15db ABOVE
AMIENT NOISE LEVEL.
NOT TO SCALE
KEY PLAN - WAITING AND ENTRANCE
P
AOM
P
P
H
J
L
M
M.4
N
M.1
13.3
HH
JJ
GG
KK
8 9 10 11 12 13 14 15
30cd
75cd
15cd
75cd
15cd
CORRIDOR
C05
CORRIDOR
C03
30cd
(R)
(ER)
(R)
(R)
(R)
(ER)
(ER)
(ER)
(ER)
(ER)
(ER) (ER)
(ER)
(ER)
(ER)
(ER)
(ER)
(ER) (ER)
(ER)
(ER)
(ER)
(ER)
15cd
15cd
15cd
15cd
15cd
CORRIDOR
C01
UC BREAK RM AND
LOCKERS
ON-CALL TLT / SHOWER
0097B
AUDIOLOGY CLEAN
STORAGE
CORRIDOR
C03
AUDIOLOGY EXAM
AUDIOLOGY AND UC
OFFICES
MECH
MECH
AGENT CASHIER
0051A
VAULT
0051B
HVAC
021E
PATIENT FUNDS
OFFICE
OFFICE
(ER)
LEGEND:
(ER) - EXISTING TO REMAIN
(R) - RELOCATED
AREA NOT IN SCOPE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
GUIDON DESIGN INC. | 1221 N PENNSYLVANIA SUITE 200 | INDIANAPOLIS, IN 46202
317.800.6388 | WWW.GUIDONDESIGN.COM
GHAFARI ASSOCIATES LLC. | 17101 MICHIGAN AVENUE | DEARBORN, MI 48126
313.441.3000 | WWW.GHAFARI.COM
C g h a fa ri l o c a l c a c h e \R e v it \1
E
C
E N
T R
A L rv t_ p h e ro h a lli .r v t
/1
/2
:2
:5
P
M
FA403
FIRE ALARM LARGE SCALE VIEW -
OPEN OFFICE AND AUDIOLOGY
RENOVATE PHARMACY &
URGENT CARE
5500 Armstrong Road, Battle Creek
515-18-109
05/20/2020 M. Sabapathy P. Herohalli
100% BID DOCUMENTS
PART. SPRINKLERED
SCALE:
NORTH
FA101 1/4" = 1'-0"
1 FIRE ALARM PLAN GROUND FLOOR - OPEN OFFICE AND AUDIOLOGY
187216
SHEET NOTES :
1. INSTALL FIRE ALARM NOTIFICATION DEVICES AS INDICATED.
CONNECT IT TO EXISTING ADDRESSABLE SYSTEM LOOP.
2. CONTRACTOR SHALL EXTEND WIRING BRANCH CIRCUITRY TO
NEW LOCATION OF RELOCATED DEVICES AS NECESSARY.
1(TYP)
(TYP)
GENERAL NOTES :
1. REFER TO SHEET FA000 FOR SYMBOLS AND GENERAL
NOTES.
2. EXISTING WORK IS SHOWN WITH LIGHT LINE WEIGHT. NEW
WORK IS SHOWN WITH HEAVY LINE WEIGHT.
3. FIRE ALARM DEVICES ( NOTIFICATION AND INITIATION
DEVICES) SHALL BE ADDRESSABLE AND CONNECTED TO
EXISTING FIRE ALARM CONTROL PANEL THROUGH SIGNAL
LINE OF CIRCUIT (SLC).
4. SPEAKERS/HORN WITH STROBE SHALL BE 15db ABOVE
AMIENT NOISE LEVEL.
NOT TO SCALE
KEY PLAN - OPEN OFFICE AND AUDIOLOGY
2 (TYP)
UP
P
P
P
P
P
P
P
13.3
A
B
13.2
FF
GG
8 9 10
11 12 13
14 15
CORRIDOR
C011
15cd
CORRIDOR
C011
NURSE MANAGER
EQUIP. STORAGE
LINEN
STOR.
CORRIDOR
C06
STAFF TLT
STAFF TLT
STORAGE
ON-CALL
0097A
HAC
EXAM / FLEX M.H.
M.H. TLT
EXAM / FLEX M.H.
EXAM
SOILED
EXIST. IT CLOSET
CORRIDOR
C010
CORRIDOR
C012
ELECTRICAL CLOSET
ELECTRICAL CLOSET
GAS - EMPTY AND
IN-USE
OFFICE
MECH
0112A
PROCEDURE
0111A
PROCEDURE
0110A
STOR.
0110B
EXAM
EXAM
EXAM
PATIENT TLT
CLEAN
MED
MH EXAM
MH EXAM
TRIAGE
RECEPTION
0103A
PHOTO
VAULT
0103B
TRIAGE
ISO / PATIENT TOILET
ISO EXAM
PROCEDURE ROOM
VESTIBULE
C09
2 (TYP)
2 (TYP)
30cd
3 (TYP)
GENERAL NOTES :
5. PROVIDE TAMPERED PROOF FIRE ALARM NOTIFICATION
DEVICES IN MENTAL HEALTH ROOMS / M.H. TOILET.
SHEET NOTES :
1. INSTALL FIRE ALARM PULL STATIONS NEXT TO EXIT DOOR.
CONNECT TO FIRE ALARM SYSTEM LOOP.
2. INSTALL FIRE ALARM NOTIFICATION DEVICES AS INDICATED.
CONNECT IT TO EXISTING ADDRESSABLE SYSTEM LOOP.
3. CONTRACTOR SHALL EXTEND WIRING BRANCH CIRCUITRY TO NEW
LOCATION OF RELOCATED DEVICES AS NECESSARY.
(TYP)
15cd
1. REFER TO SHEET FA000 FOR SYMBOLS AND GENERAL
NOTES.
2. EXISTING WORK IS SHOWN WITH LIGHT LINE WEIGHT. NEW
WORK IS SHOWN WITH HEAVY LINE WEIGHT.
3. FIRE ALARM DEVICES ( NOTIFICATION AND INITIATION
DEVICES) SHALL BE ADDRESSABLE AND CONNECTED TO
EXISTING FIRE ALARM CONTROL PANEL THROUGH SIGNAL
LINE OF CIRCUIT (SLC).
4. SPEAKERS/HORN WITH STROBE SHALL BE 15db ABOVE
AMIENT NOISE LEVEL.
(ER)
(R)
(R)
(R)
(ER)
(R)
(R)
(R)
(R)
30cd
15cd
(TYP)
(ER)
(ER)
(ER)
(ER)
(ER)
(ER)
(ER)
(ER)
(R)
(ER)
(ER)
(R)
EY407
15cd
15cd
15cd
15cd
15cd
15cd
15cd
15cd
15cd
15cd
15cd
15cd 15cd
15cd
15cd15cd
SHOWER
0106A
CORRIDOR
C013
NURSE
0135A
NURSE / DICTATION
GAS - FULL
CORRIDOR
C05
CORRIDOR
C06CORRIDOR
C06
CORRIDOR
C014
(TYP)
15cd 15cd
15cd
15cd
(ER)
(TYP)
1 (TYP)
(TYP)
LEGEND:
(ER) - EXISTING TO REMAIN
(R) - RELOCATED
AREA NOT IN SCOPE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
GUIDON DESIGN INC. | 1221 N PENNSYLVANIA SUITE 200 | INDIANAPOLIS, IN 46202
317.800.6388 | WWW.GUIDONDESIGN.COM
GHAFARI ASSOCIATES LLC. | 17101 MICHIGAN AVENUE | DEARBORN, MI 48126
313.441.3000 | WWW.GHAFARI.COM
C g h a fa ri l o c a l c a c h e \R e v it \1
E
C
E N
T R
A L rv t_ p h e ro h a lli .r v t
/1
/2
:5
:5
P
M
FA404
FIRE ALARM LARGE SCALE VIEW -
URGENT CARE
RENOVATE PHARMACY &
URGENT CARE
5500 Armstrong Road, Battle Creek
515-18-109
05/20/2020 M. Sabapathy P. Herohalli
100% BID DOCUMENTS
PART. SPRINKLERED
SCALE:
NORTH
FA101
1/4" = 1'-0"
1 FIRE ALARM PLAN GROUND FLOOR - URGENT CARE
187216
NOT TO SCALE
KEY PLAN - URGENT CARE
H
J
L
M
M.4
N
M.1
13.3
A
B
C
DD
3.8 4.9 5.3 5.7 6.5 11.9
EE
HH
FF
JJ
GG
KK
1 2 3 4 5 6
8 9
11 12 13 14 15
SHADED AREAS ARE NOT INCLUDED IN SCOPE OF WORK
RELOCATE 4" FP
PIPE UP TO
UNDERSIDE OF
STEEL, ROUTE
BETWEEN
JOISTS/BEAMS AS
MUCH AS
POSSIBLE
(E) FIRE MAIN
HATCHED AREA NOT CURRENTLY SPRINKLERED - EXTEND FIRE SUPPRESSION TO THESE AREA, PER NOTES
REMAINING AREA CURRENTLY SPRINKLERED - REWORK PER SCOPE OF WORK, SEE NOTES
MECH
STAFF TLT
CLOSET
0107A
PROC RM STOR.
0110B
GAS - FULL
STAFF TLT
ON-CALL
0097A
GENERAL WAITING
CONSULT
PROCEDURE
0110A
INV. CONTROL
MANAGER
RECEIVING
MAIL-OUT
HVAC
021E
HVAC
0017E
STAIR
S5
MECH
OFFICE
OFFICE
OFFICE
OFFICE
EXAM
OFFICE
OFFICE
0074A
OFFICE
STOR.
CUSTOMER SERVICE
OFFICE
STAIR
S3
HSK
ELEC.
TOILET
0078A
SECURITY OFFICE
ELEV.
E3
MALE
STOR.
016A ELEV. MACH.
0018E
HVAC
0020E
STOR.
CHIEF
HVAC
0042E
EXAM SOUND BOOTH
TREATMENT
PROSTHETICS
STOR.
NURSE MANAGER
TRIAGE
0105A
CLOSET
0111B
NEW VESTIBULE
C09
ELECTRICAL CLOSET
PATIENT FUNDS
HALL
DISPENSING WINDOWS
FEMALE
OFFICE
FEMALE
MALE
CONSULT
STAFF LOUNGE/
LOCKER ROOM
CORRIDOR
C04
OFFICE
I.T.
OFFICE
HOUSE KEEPING
STORAGE
OFFICE
OFFICE
EXAM SOUND BOOTH
STAIR
S6
AUDIOLOGY CLEAN
HAC
CONSULT
CONSULT
EXIST. IT CLOSET
SOILED
CORRIDOR
C08
ELECTRICAL CLOSET
GAS - EMPTY AND
IN-USE
TRIAGE
MH EXAM
WALK-IN ENTRANCE
SUB WAITING
CORRIDOR
C015
WAITING
PROCEDURE
0111A
OFFICE
EXIT PASSAGEWAY
01228
EXAM SOUND BOOTH
VAULT
MECH
ELEV.
E1
ELEV.
E2
CORRIDOR
C02
HAC
PHARMACY WAITING
VEST. / BOX BREAK
DOWN
SHOWER
0105B
UC BREAK RM AND
LOCKERS
CONSULT / DISPENSING
CORRIDOR
C01
VAULT
0051B
LINEN
EQUIP. STORAGE
PHOTO
VAULT
0103B
CORRIDOR
C06
CORRIDOR
C05
CORRIDOR
C014
UC WAITING
FILLING
CALL ROOM
AGENT CASHIER
0051A
ON-CALL TLT / SHOWER
0097B
STAFF TLT
PROCEDURE ROOM
WORK STATIONS
OFFICE
RECEPTION
0103A
ISO EXAM
ISO / PATIENT TOILET
BREAK RM
AUDIOLOGY EXAM
AUDIOLOGY AND UC
OFFICES
CORRIDOR
C012
PHARM. STORAGE
MECH
0112A
OFFICE
STAIR
S2
EXAM
PATIENT TLT
CONFERENCE RM
NURSE
EXAM
EXAM / FLEX M.H.
EXAM
EXAM
CLEAN
MH EXAM
STORAGE
EXAM / FLEX M.H.
M.H. TLT
NURSE
0135A
NURSE / DICTATION
CORRIDOR
C03
MECHANICAL
NF AND PENDING
SERVER FOR ROBOT
SECRETARY
H
J
L
M
M.4
N
A
B
C
DD
EE
HH
FF
JJ
GG
KK
1 2 3 4 5 6
8 9
11 12 13 14 15
AREAS WITH EXISTING FIRE SUPPRESSION
1.
2.
3.
4.
5.
6.
7.
8.
A.
B.
C.
FIRE PROTECTION NOTES
PRIOR TO START OF WORK, CONDUCT THROUGH FIELD SURVEY TO VERIFY EXISTING
CONDITIONS, INCLUDING DETERMINE SIZE, LOCATION AND DETAILS OF EXISTING FIRE
PROTECTION RISERS, MAINS, BRANCHES, COMPONENTS, ALARM VALVES, AND OTHER
SYSTEM ELEMENTS.
IN AREAS OF WORK WITH NO EXISTING FIRE PROTECTION, PROVIDE FIRE PROTECTION,
EXTENDED FROM EXISTING FIRE PROTECTION SYSTEMS.
IN AREAS OF WORK WITH EXISTING FIRE PROTECTION, REWORK EXISTING FIRE
PROTECTION PIPING SYSTEM TO MEET DESIGN DENSITY REQUIREMENTS AND TO
ACCOMMODATE RELOCATED, MODIFIED AND NEW PARTITIONS, AND RELOCATED,
MODIFIED AND NEW CEILINGS. RELOCATE SPRINKLER HEADS AS NEEDED TO
ACCOMMODATE OTHER CEILING ELEMENTS AS NECESSARY WITHIN AREAS OF NEW
WORK. "REWORK" INCLUDES ANY NECESSARY MODIFICATION, DEMOLITION OR
INSTALLATION OF NEW PIPING AND SPRINKLERS TO PROVIDE A COMPLETE AND
OPERATIONAL SYSTEM. WHERE PARTITIONS ARE RELOCATED, REVISED OR NEW,
VERIFY ADEQUATE SPRINKLER COVERAGE ON BOTH SIDES OF PARTITIONS, WHETHER
DENOTED AS WITHIN "AREA OF WORK" OR NOT. REFER TO ARCHITECTURAL FOR AREAS
OF WORK.
FIRE PROTECTION SYSTEMS SHALL BE HYDRAULICALLY DESIGNED IN ACCORDANCE
WITH APPLICABLE NFPA STANDARDS, INCLUDING NFPA 13, AND THE AUTHORITY HAVING
JURISDICTION.
REFER TO SHEET M-001 FOR GENERAL NOTES, ABBREVIATIONS AND SYMBOLS.
SUBMIT SHOP DRAWINGS, HYDRAULIC CALCULATIONS AND TECHNICAL DATA SHEETS
FOR ALL EQUIPMENT TO BE INSTALLED TO THE COR. DO NOT START ANY INSTALLATION
WORK UNTIL APPROVAL HAS BEEN RECEIVED.
MAINTAIN PROTECTION IN EXISTING AREAS ADJACENT TO AREAS OF NEW WORK. ANY
NECESSARY SHUTDOWN OF EXISTING SYSTEM SHALL BE COORDINATED AND APPROVED
BY THE VA.
DESIGN DENSITY SHALL BE AS FOLLOWS:
LIGHT HAZARD: 0.10 GPM/SF OVER THE MOST REMOTE 1,500 SF
- OFFICES
- CORRIDORS
- TREATMENT AREAS
- WAITING AREAS
- STORAGE ROOMS UNDER 100 SF
ORDINARY HAZARD GROUP 1: 0.15 GPM/SF OVER THE MOST REMOTE 1,500 SF
- ELECTRICAL ROOMS
- ELECTRICAL CLOSETS
- MECHANICAL EQUIPMENT ROOMS
- ELEVATOR MACHINE ROOMS
ORDINARY HAZARD GROUP 2: 0.20 GPM/SF OVER THE MOST REMOTE 1,500 SF
- STORAGE ROOMS
- LINEN ROOMS
- PHARMACY AND ASSOCIATED STORAGE ROOMS
9.
10.
A.
B.
C.
11.
12.
13.
14.
15.
16.
FURNISH NEW SPRINKLER HEADS, 165° F, ½” ORIFICE.
UNLESS NOTED OTHERWISE:
SPRINKLERS IN AREAS WITH LAY-IN OR HARD CEILINGS SHALL BE SEMI-
RECESSED. SPRINKLER HEADS SHALL BE CENTERED IN 2X2 CEILING TILES, OR
CENTERED IN THE HALF-PANEL OF 4X2 CEILING TILES.
SPRINKLERS IN AREAS OF EXPOSED CONSTRUCTION SHALL BE STANDARD
UPRIGHT.
COORDINATE WITH ARCHITECTURAL TRADES.
PROVIDE 1” AUX DRAIN VALVES WITH HOSE END CONNECTIONS WHERE TRAPPED
SECTIONS OF PIPING ARE INSTALLED.
OBTAIN HYDRANT FLOW TEST OR FIRE PUMP TEST REPORT FROM OWNER. IF A REPORT
FROM WITHIN THE LAST YEAR DOES NOT EXIST, CONTRACTOR IS RESPONSIBLE TO
ARRANGE FOR AND OBTAIN REPORT.
FIRE PROTECTION SYSTEMS, COMPONENTS AND LOCATIONS SHALL BE COORDINATED
THOROUGHLY WITH OTHER TRADES AND EXISTING CONDITIONS PRIOR TO START OF
INSTALLATION. COORDINATE INSTALLATION OF FIRE PROTECTION SYSTEMS, INCLUDING
SUPPORT SYSTEMS, WITH WORK OF MECHANICAL, ARCHITECTURAL AND ELECTRICAL
TRADES, OWNER'S PROCESS EQUIPMENT PROVIDERS, AND EXISTING SYSTEMS,
EQUIPMENT AND BUILDING TRADES.
HANGERS AND SUPPORTS SHALL BE PER NFPA 13. USE OF C-CLAMPS WITHOUT
RETAINING CLIPS IS PROHIBITED. SUPPORT FROM STRUCTURE ONLY.
OFFSET SPRINKLER PIPING AROUND OBSTRUCTIONS AND PROVIDE REQUIRED
CLEARANCE FROM OBSTRUCTIONS FOR ALL AUTOMATIC SPRINKLERS IN ACCORDANCE
WITH NFPA 13. LOCATE PIPING BETWEEN AND THROUGH JOISTS WHERE POSSIBLE.
CEILING SPACE IS EXCEEDINGLY CONGESTED - EXISTING FLOOR-TO-FLOOR HEIGHT IS
10'-0". THOROUGH COORDINATION WITH ALL TRADES IS ESSENTIAL.
THE FOLLOWING SPACES SHALL HAVE "INSTITUTIONAL" TYPE QUICK RESPONSE
SPRINKLER HEADS: EXAM/ FLEX MH ROOMS 0120 & 0121, MH EXAM ROOMS 0123 & 0124;
AND MH TOILET ROOM 0122.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
GUIDON DESIGN INC. | 1221 N PENNSYLVANIA SUITE 200 | INDIANAPOLIS, IN 46202
317.800.6388 | WWW.GUIDONDESIGN.COM
GHAFARI ASSOCIATES LLC. | 17101 MICHIGAN AVENUE | DEARBORN, MI 48126
313.441.3000 | WWW.GHAFARI.COM
C g h a fa ri l o c a l c a c h e
\R e v it \1
M
C
E N
T R
A L p e la y y a n .r v t
/1
/2
:4
:1
P
M
FX101
FIRE SUPPRESSION PLAN GROUND
FLOOR
RENOVATE PHARMACY &
URGENT CARE
5500 Armstrong Road, Battle Creek
515-18-109
05/20/20 MAP PME
100% BID DOCUMENTS
PART. SPRINKLERED
100% BID DOCUMENTS
SCALE:
NORTH
3/32" = 1'-0"
FIRE PROTECTION PLAN GROUND FLOOR
SCALE:
NORTH
3/64" = 1'-0"
FIRE PROTECTION PLAN GROUND FLOOR EXISTING
SCALE:
NORTH
1" = 50'-0"
KEY PLAN - GROUND FLOOR
1" PIPE (AS REQUIRED)
90° ELL
1" NIPPLE
2"x2"x1" TEE BRANCH
LINE (SIZE VARIES)
1/2"x1" REDUCER
165° PENDANT
SPRINKLER HEAD
CEILING PLATE
CEILING TILE
1" PIPE AS REQUIRED
90° ELL
6"
TYP
PLATE WASHER (TYP
TOP AND BOTTOM)
ADJ. SWIVEL
RING.
ANVIL FIG. 69
SEE PLAN FOR PIPE SIZE
THREADED
ROD
ANVIL FIG. 146
FLAT WASHERS FOR
THREADED ROD (TYP
TOP AND BOTTOM)
BEAM CLAMP
UNISTRUT MODEL NO.
DOUBLE HEX NUT
UNISTRUT CHANNEL
MODEL NO.
P2000KO
PURLIN SPACING (FIELD VERIFY)
EXISTING ROOF
PURLIN
(FIELD VERIFY SIZE)
THREADED ROD
ADJ. SWIVEL
RING
PIPE HANGER
EXTENSION PIECE
TOP BEAM CLAMP
DOUBLE HEX NUT
ADJUSTABLE
CLEVIS
TYPE PIPE HANGER
EXISTING ROOF
PURLIN
FIELD VERIFY SIZE
ADJUSTABLE BEAM CLAMP
EXTENSION PIECE
THREADED ROD
THREADED ROD
BEAM CLAMP UNISTRUT
MODEL NO. 2867
ADJ. SWIVEL RING.
PLATE WASHER
(TYP TOP AND
BOTTOM)
DOUBLE HEX NUT
FLAT WASHERS FOR
THREADED ROD (TYP
TOP AND BOTTOM) UNISTRUT CHANNEL
MODEL NO. P2000KO
ADJ. CLEVIS
PURLIN SPACING (FIELD VERIFY)
THREADED ROD
ADJ. SWIVEL RING
PIPE HANGER
TOP BEAM CLAMP
C-CLAMP
RETAINING STRAP
EXISTING ROOF
PURLIN
(FIELD VERIFY SIZE)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
GUIDON DESIGN INC. | 1221 N PENNSYLVANIA SUITE 200 | INDIANAPOLIS, IN 46202
317.800.6388 | WWW.GUIDONDESIGN.COM
GHAFARI ASSOCIATES LLC. | 17101 MICHIGAN AVENUE | DEARBORN, MI 48126
313.441.3000 | WWW.GHAFARI.COM
C g h a fa ri l o c a l c a c h e
\R e v it \1
M
C
E N
T R
A L p e la y y a n .r v t
/1
/2
:4
:2
P
M
FX501
FIRE SUPPRESSION DETAILS RENOVATE PHARMACY &
URGENT CARE
5500 Armstrong Road, Battle Creek
515-18-109
05/20/20 MAP PME
100% BID DOCUMENTS
PART. SPRINKLERED
100% BID DOCUMENTS
NOT TO SCALE
SPRINKLER DROP
NOT TO SCALE
PIPING HANGER
NOT TO SCALE
UTILITY PIPING HANGER
NOT TO SCALE
UTILITY PIPING HANGER
NOT TO SCALE
UTILITY PIPING HANGER
NOT TO SCALE
UTILITY PIPING HANGER
HWR
W R
HWR
HW
H W
HW
CW
C W
CW
H
J
L
M
M.4
N
M.1
13.3
A
B
C
DD
3.8 4.9 5.3 5.7 6.5 10.6 10.8 11.3 11.8 11.9 13.2
EE
HH
FF
JJ
GG
KK
1 2 3 4 5 6
8 9
11 12 13 14 15
REMOVE PLUMBING IN HATCHED AREAS, CAP BRANCH
LINES AT MAIN, CAP SAN FLUSH WITH SLAB -
COORDINATE WITH SCOPE OF NEW WORK
AREA NOT IN SCOPE
REMOVE SINK,
PREPARE
BRANCH PIPING
FOR
RECONNECTION
CAP 4" DWC & 6" FP
STUB-UPS FLUSH
WITH SLAB, PROVIDE
FLOOR MARKER,
WORK TO BE DONE
ON WEEKENDS
(E) 4"ø DCW
(E) 6"ø FP
CAP FD FLUSH
WITH SLAB
CAP DCW LINE AT BRANCH
MAIN ABOVE CEILING
REWORK SANITARY
RISER TO BE WITHIN
NEW COLUMN
ENCLOSURE, CAP
ABANDONED PIPING
ABOVE CEILING
REWORK SANITARY
RISER, COORD W/
SCOPE OF NEW
WORK
(E) MAINS
TO REMAIN
(E) DCW, DHW,
DHWR BRANCH
MAINS TO REMAIN
(E) BRANCH
MAINS TO
REMAIN
(E) PIPING AND CONDUIT TO
BE REWORKED IN THIS AREA
TO COORDINATE WITH NEW
DUCT AND UTILITIES
1. WORK WHICH WILL AFFECT FIRST FLOOR ABOVE SHALL BE
DONE AT NIGHT OR ON WEEKENDS. COORDINATE WITH
THE COR.
2. REFER TO SHEET M-001 FOR GENERAL NOTES AND
ABBREVIATIONS.
3. CONTRACTOR TO PERFORM THOROUGH SURVEY OF
EXISTING PLUMBING SYSTEM AND COMPONENTS TO
VERIFY EXISTING CONDITIONS.
4. DEAD LEGS ARE PROHIBITED. ANY DCW OR DHWS BRANCH
LINES NOT SERVING FIXTURES SHALL BE CAPPED AT THE
MAIN.
NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
GUIDON DESIGN INC. | 1221 N PENNSYLVANIA SUITE 200 | INDIANAPOLIS, IN 46202
317.800.6388 | WWW.GUIDONDESIGN.COM
GHAFARI ASSOCIATES LLC. | 17101 MICHIGAN AVENUE | DEARBORN, MI 48126
313.441.3000 | WWW.GHAFARI.COM
C g h a fa ri l o c a l c a c h e
\R e v it \1
M
C
E N
T R
A L p e la y y a n .r v t
/1
/2
:4
:5
P
M
PD101
PLUMBING DEMOLITION PLAN
GROUND FLOOR
RENOVATE PHARMACY &
URGENT CARE
5500 Armstrong Road, Battle Creek
515-18-109
05/20/20 MAP PME
100% BID DOCUMENTS
PART. SPRINKLERED
100% BID DOCUMENTS
SCALE:
NORTH
3/32" = 1'-0"
PLUMBING DEMOLITION PLAN GROUND FLOOR
(E) DCW, DHW,
DHWR BRANCH
MAINS TO REMAIN
(E) DCW, DHW,
DHWR BRANCH
MAINS TO REMAIN
UG
SCALE:
NORTH
1" = 50'-0"
J
L
M
M.4
N
M.1
13.3
A
B
C
DD
3.8 4.9 5.3 5.7 6.5 10.6 10.8 11.3 11.8 11.9 13.2
EE
HH
FF
JJ
GG
KK
1 2 3 4 5 6
8 9
11 12 13 14 15
PP403
PP402
PP401
(E) 4"ø SAN
(E) 4"ø SAN
RELOCATE 4"
SAN RISER
1. REFER TO SHEET M-001 FOR GENERAL NOTES
AND ABBREVIATIONS.
2. REFER TO FIXTURE CONNECTION SCHEDULE ON
SHEET PP501.
3. GRAVITY PIPING SHALL BE SLOPED A MINIMUM OF
1/8" PER FOOT IN THE DIRECTION OF FLOW.
4. FINISHED FLOOR ELEVATION: 100'-0".
NOTES
AREA NOT IN SCOPE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
GUIDON DESIGN INC. | 1221 N PENNSYLVANIA SUITE 200 | INDIANAPOLIS, IN 46202
317.800.6388 | WWW.GUIDONDESIGN.COM
GHAFARI ASSOCIATES LLC. | 17101 MICHIGAN AVENUE | DEARBORN, MI 48126
313.441.3000 | WWW.GHAFARI.COM
C g h a fa ri l o c a l c a c h e
\R e v it \1
M
C
E N
T R
A L p e la y y a n .r v t
/1
/2
:4
:1
P
M
PP100
PLUMBING PLAN UNDERGROUND
COMPOSITE
RENOVATE PHARMACY &
URGENT CARE
5500 Armstrong Road, Battle Creek
515-18-109
05/20/20 MAP PME
100% BID DOCUMENTS
PART. SPRINKLERED
100% BID DOCUMENTS
SCALE:
NORTH
3/32" = 1'-0"
PLUMBING PLAN UNDERGROUND COMPOSITE
SCALE:
NORTH
1" = 50'-0"
J
L
M
M.4
N
M.1
13.3
A
B
C
DD
3.8 4.9 5.3 5.7 6.5 10.6 10.8 11.3 11.8 11.9 13.2
EE
HH
FF
JJ
GG
KK
1 2 3 4 5 6
8 9
11 12 13 14 15
PP411
PP412
PP413
REWORK SANITARY
AS REQ'D TO RE-
ROUTE SAN RISER
4" SAN DN
(E) 4"ø SAN
UP & DN
(E) 4"ø SAN
(E) 4"ø SAN
PP414
(E) DCW,
DHW, DHWR
TO REMAIN
(E) PIPING AND CONDUIT TO
BE REWORKED IN THIS AREA
TO COORDINATE WITH NEW
DUCT AND UTILITIES; COORD
WITH ALL TRADES PRIOR TO
START OF WORK
1. WORK WHICH WILL AFFECT FIRST FLOOR ABOVE SHALL BE
DONE AT NIGHT OR ON WEEKENDS. COORDINATE WITH
THE COR.
2. HOLD ALL UTILITIES UP AS HIGH AS POSSIBLE, LOCATING
BETWEEN AND THROUGH JOISTS WHERE POSSIBLE.
CEILING SPACE IS EXCEEDINGLY CONGESTED - EXISTING
FLOOR-TO-FLOOR HEIGHT IS 10'-0". THOROUGH
COORDINATION WITH ALL TRADES IS ESSENTIAL.
3. REFER TO SHEET M-001 FOR GENERAL NOTES AND
ABBREVIATIONS.
4. SANITARY PIPING SHALL SLOPE MINIMUM 1/8" PER FOOT IN
THE DIRECTION OF FLOW.
5. REFER TO FIXTURE CONNECTION SCHEDULE ON SHEET
PP501.
6. OFFSET PIPING AS REQUIRED TO AVOID INTERFERENCES
WITH STRUCTURE AND OTHER TRADES. NOT ALL
REQUIRED OFFSETS WHICH MAY BE REQUIRED ARE
INDICATED - CONTRACTOR TO COORDINATE WITH EXISTING
CONDITIONS AND ALL TRADES.
7. REFER TO ARCH GENERAL SERIES SHEETS FOR RATED
WALLS, TEMPORARY PARTITIONS, AND PHASING.
NOTES
AREA NOT IN SCOPE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
GUIDON DESIGN INC. | 1221 N PENNSYLVANIA SUITE 200 | INDIANAPOLIS, IN 46202
317.800.6388 | WWW.GUIDONDESIGN.COM
GHAFARI ASSOCIATES LLC. | 17101 MICHIGAN AVENUE | DEARBORN, MI 48126
313.441.3000 | WWW.GHAFARI.COM
C g h a fa ri l o c a l c a c h e
\R e v it \1
M
C
E N
T R
A L p e la y y a n .r v t
/1
/2
:4
:4
P
M
PP101
PLUMBING PLAN GROUND FLOOR
COMPOSITE
RENOVATE PHARMACY &
URGENT CARE
5500 Armstrong Road, Battle Creek
515-18-109
05/20/20 MAP PME
100% BID DOCUMENTS
PART. SPRINKLERED
100% BID DOCUMENTS
SCALE:
NORTH
3/32" = 1'-0"
PLUMBING PLAN GROUND FLOOR COMPOSITE
SCALE:
NORTH
1" = 50'-0"
J
L
M
M.4
N
M.1
HH
JJ
GG
KK
1 2 3 4 5 6 7 8
(E
"ø
S A
N
(E) 4"ø SAN
(E
"ø
S A
N
(E) 3"ø SAN
CAP VENT LINE
FLUSH WITH SLAB
(E) FD
3" SAN UP
1 1/2" SAN UP TO SINK
3"ø SAN
UP TO
WC
1 1/2" SAN UP TO LAV
UP TO SS
UP TO FD
3" SAN UP
UP TO
CO
4"ø SAN
"ø
S A
N
4"ø SAN
4" SAN UP
4"ø SAN
4" SAN UP
3"ø SAN
3" SAN UP
4"ø SAN
UP TO CO
3"ø SAN
3"ø SAN
4"ø V UP
(E) 4"ø SAN
(E) CAP
BACKWATER
VALVE
AREA NOT IN SCOPE
1. REFER TO SHEET M-001 FOR GENERAL NOTES
AND ABBREVIATIONS.
2. REFER TO FIXTURE CONNECTION SCHEDULE ON
SHEET PP501.
3. GRAVITY PIPING SHALL BE SLOPED A MINIMUM OF
1/8" PER FOOT IN THE DIRECTION OF FLOW.
4. FINISHED FLOOR ELEVATION: 100'-0".
NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
GUIDON DESIGN INC. | 1221 N PENNSYLVANIA SUITE 200 | INDIANAPOLIS, IN 46202
317.800.6388 | WWW.GUIDONDESIGN.COM
GHAFARI ASSOCIATES LLC. | 17101 MICHIGAN AVENUE | DEARBORN, MI 48126
313.441.3000 | WWW.GHAFARI.COM
C g h a fa ri l o c a l c a c h e
\R e v it \1
M
C
E N
T R
A L p e la y y a n .r v t
/1
/2
:4
:0
P
M
PP401
PLUMBING LARGE SCALE VIEW -
PHARMACY
RENOVATE PHARMACY &
URGENT CARE
5500 Armstrong Road, Battle Creek
515-18-109
05/20/20 MAP PME
100% BID DOCUMENTS
PART. SPRINKLERED
100% BID DOCUMENTS
SCALE:
PP100
1/4" = 1'-0"
1 PLUMBING PLAN UNDERGROUND - PHARMACY
SCALE:
NORTH
1" = 50'-0"
KEY PLAN - PHARMACY
L
M
M.4
N
M.1
13.3
HH
JJ
GG
KK
8 9 10 11 12 13 14 15
(E
"ø
S A
N
(E) 4"ø SAN
3" SAN UP
UP TO SINK
UP TO LAV
UP TO WC UP TO WCO
FD
FD
UP TO
SINK
3"ø SAN4"ø SAN
UP TO CO
3"ø SAN
"ø
S A
N
4"ø SAN
UP
UP TO
FCO
4"ø SAN
UP
"ø
S A
N
UP TO
FCO
4"ø SAN
UP
(E
"ø
S A
N
"ø
S A
N
4"ø SAN 4"ø SAN
I.E.: 98' - 3"
I.E.: 98' - 0"
I.E.: 98' - 1 3/4"
UP TO LAV
"ø
S A
N
I.E.: 98' - 10 1/2"
I.E.: 98' - 6"
(E) 4"ø SAN
UP
1 1/2"ø SAN 1 1/2"ø SAN
UP
1 1/2"ø SAN
1 1/2"ø SAN
1 1/2"ø SAN
(E) 4"ø SAN
UP
2"ø V UP
2"ø V
UP
(E) 4"ø SAN
(E) 4"ø SAN
(E) 4"ø SAN
AREA NOT IN SCOPE
1. REFER TO SHEET M-001 FOR GENERAL NOTES
AND ABBREVIATIONS.
2. REFER TO FIXTURE CONNECTION SCHEDULE ON
SHEET PP501.
3. GRAVITY PIPING SHALL BE SLOPED A MINIMUM OF
1/8" PER FOOT IN THE DIRECTION OF FLOW.
4. FINISHED FLOOR ELEVATION: 100'-0".
NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
GUIDON DESIGN INC. | 1221 N PENNSYLVANIA SUITE 200 | INDIANAPOLIS, IN 46202
317.800.6388 | WWW.GUIDONDESIGN.COM
GHAFARI ASSOCIATES LLC. | 17101 MICHIGAN AVENUE | DEARBORN, MI 48126
313.441.3000 | WWW.GHAFARI.COM
C g h a fa ri l o c a l c a c h e
\R e v it \1
M
C
E N
T R
A L p e la y y a n .r v t
/1
/2
:4
:1
P
M
PP402
PLUMBING LARGE SCALE VIEW -
OPEN OFFICE AND AUDIOLOGY
RENOVATE PHARMACY &
URGENT CARE
5500 Armstrong Road, Battle Creek
515-18-109
05/20/20 MAP PME
100% BID DOCUMENTS
PART. SPRINKLERED
100% BID DOCUMENTS
SCALE:
PP100
1/4" = 1'-0"
1 PLUMBING PLAN UNDERGROUND - OPEN OFFICE AND AUDIOLOGY
SCALE:
NORTH
1" = 50'-0"
KEY PLAN - OPEN OFFICE AND AUDIOLOGY
13.3
A
B
C
DD
10.6 10.8 11.3 11.8 11.9 13.2
EE
FF
GG
8 9 10
11 12 13
14 15
(E) 4"ø SAN
(E
"ø
S A
N
(E) 4"ø SAN
(E) 4"ø SAN
(E) 4"ø SAN
(E) 4"ø SAN
(E
"ø
S A
N
(E
"ø
S A
N
"ø
S A
N
"ø
S A
N
"ø
S A
N
3"ø SAN
"ø
S A
N "ø
S A
N
"ø
S A
N
3"ø SAN3"ø SAN
"ø
S A
N
3"ø SAN
(E
"ø
S A
N
(E
"ø
S A
N
"ø
S A
N
(E) 3"ø SAN(E) 4"ø SAN(E) 4"ø SAN
(E
"ø
S A
N (E
"ø
S A
N
(E) 4"ø SAN
4"ø SAN
UP TO WC
UP TO WC
UP TO
2 LAV
UP TO (E) CO -
SET TO NEW FIN
FLR AS REQ'D
(E
"ø
S A
N
UP TO (E) CO -
SET TO NEW FIN
FLR AS REQ'D
UP TO SINK
UP TO SINK
UP TO CLINICAL
SERVICE SINK
UP TO SINK
UP TO SINK
UP TO SINK
UP TO (E) CO -
SET TO NEW FIN
FLR AS REQ'D
UP TO FCO
UP TO SINK
UP TO LAV
FD
UP TO SINK
3"ø SAN
UP TO SS
UP TO CO
UP TO FD
1 1/2"ø SAN
(E) CO
(E) 4"ø SAN
CAPPED
AT FLR
(E) 1 1/2"ø SAN
CAPPED
AT FLR
(E) CO
(E) CO
(E) 1 1/2"ø SAN
(E) 1 1/2"ø SAN
(E) 4"ø SAN
(E) 1 1/2"ø SAN
(E) 1 1/2"ø SAN
CAPPED
FLUSH W/
SLAB
CAPPED
FLUSH W/
SLAB
CAPPED
FLUSH W/
SLAB
CAPPED
FLUSH W/
SLAB
CAPPED FLUSH
W/ SLAB
(E) 1 1/2"ø SAN
CAPPED
AT FLR
(E) 1 1/2"ø SAN
CAPPED AT FLR
(E) 4"ø SAN
(E) 1 1/2"ø SAN
(E) 4"ø SAN
(E) 1 1/2"ø SAN
CAPPED AT FLR
CAPPED FLUSH
W/ SLAB
CAPPED FLUSH
W/ SLAB
(E) 1 1/2"ø SAN
(E) 4"ø SAN (E) 1 1/2"ø SAN
CAPPED AT FLR
CAPPED AT FLRCAPPED
AT FLR
(E) CO
(E) 1 1/2"ø SAN
CAPPED AT FLR
(E) 4"ø SAN
UP
1 1/2"ø SAN
1 1/2"ø SAN
1 1/2"ø SAN
UP TO SINK
1 1/2"ø SAN
1 1/2"ø SAN
1 1/2"ø SAN
(E) 4"ø SAN
UP
1 1/2"ø SAN
1 1/2"ø SAN
1 1/2"ø SAN
INSTALL CO ON
(E) SAN LEVEL
WITH FIN FLR
CAPPED
BELOW FIN
FLR
4"ø SAN UP
FD
1 1/2"ø SAN
UP TO SINK
3"ø SAN
3"ø SAN
1 1/2"ø SAN
UP TO SINK
1 1/2"ø SAN
UP TO LAV
4"ø SAN
UP TO WC
4"ø SAN
3"ø SAN
CAPPED AS
REQ'D FOR
NEW WORK
1 1/2"ø SAN
4"ø SAN
UP TO LAV
UP TO WC
1 1/2"ø SAN
1 1/2"ø SAN
1 1/2"ø SAN
UP TO SINK
UP TO SINK
UP TO SINK
1 1/2"ø SAN
UP TO SINK
1 1/2"ø SAN
UP TO SINK
"ø
S A
N
3"ø SAN
4"ø SAN
3"ø SAN
3"ø SAN
UP TO WC
4"ø SAN
2"ø V
UP
1 1/2"ø V
UP
1 1/2"ø V
UP
(E) 1 1/2"ø SAN
TO SITE SANITARY
1 1/2"ø V UP
4"ø SAN
4"ø SAN
AREA NOT IN SCOPE
1. REFER TO SHEET M-001 FOR GENERAL NOTES
AND ABBREVIATIONS.
2. REFER TO FIXTURE CONNECTION SCHEDULE ON
SHEET PP501.
3. GRAVITY PIPING SHALL BE SLOPED A MINIMUM OF
1/8" PER FOOT IN THE DIRECTION OF FLOW.
4. FINISHED FLOOR ELEVATION: 100'-0".
NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
GUIDON DESIGN INC. | 1221 N PENNSYLVANIA SUITE 200 | INDIANAPOLIS, IN 46202
317.800.6388 | WWW.GUIDONDESIGN.COM
GHAFARI ASSOCIATES LLC. | 17101 MICHIGAN AVENUE | DEARBORN, MI 48126
313.441.3000 | WWW.GHAFARI.COM
C g h a fa ri l o c a l c a c h e
\R e v it \1
M
C
E N
T R
A L p e la y y a n .r v t
/1
/2
:4
:2
P
M
PP403
PLUMBING LARGE SCALE VIEW -
URGENT CARE
RENOVATE PHARMACY &
URGENT CARE
5500 Armstrong Road, Battle Creek
515-18-109
05/20/20 MAP PME
100% BID DOCUMENTS
PART. SPRINKLERED
100% BID DOCUMENTS
SCALE:
PP100
1/4" = 1'-0"
1 PLUMBING PLAN UNDERGROUND - URGENT CARE
5. FOR SINKS AND LAVATORIES WITH BASINS INTEGRAL TO
COUNTERS, MILLWORK OR FURNITURE SYSTEMS,
COORDINATE PLUMBING CONNECTION LOCATIONS WITH
SUPPLIER(S) AND ARCHITECTURAL TRADES.
SCALE:
NORTH
1" = 50'-0"
KEY PLAN - URGENT CARE
L
M
M.4
N
M.1
HH
JJ
GG
KK
1 2 3 4 5 6 7 8
1 1/2"ø SAN
(E
/2 "ø
S A
N
(E) 1 1/2"ø SAN
2"ø SAN
1 1/2"ø SAN
(E) 4"ø SAN
(E) 1 1/2"ø SAN
(E) 1 1/2"ø SAN
(E) 1 1/2"ø SAN
P-528
P-101
2" SAN DN
CO
FD
3/4"ø DHWS
3/4"ø DCW
(E) 1 1/2"ø SAN UP
P-418
1 1/2"ø DCW
3/4"ø DHWS 3/4"ø DHWR
3/4"ø DHWS
3/4"ø DCW
P-502
CO
(E) 1 1/2"ø SAN
(E) 1 1/2"ø SAN
(E) 4"ø SAN
(E) 3"ø SAN
(E) 1 1/2"ø SANUP
4"ø SAN
P-TRAP
UP
UP
3/4"ø DHWR
3/4"ø DHWS
1 1/2"ø DCW
3/4"ø DHWR
1"ø DHWS
2"ø DCW
(E) 1"ø DHWR
(E) 2"ø DHWS
(E) 3"ø DCW
(E) 2"ø DHWS
(E) 1"ø DHWR (E) 3"ø DCW
4"ø SAN
DN
4"ø SAN
DN
(E) 4"ø SAN
(E) 1 1/2"ø SAN
(E) 3"ø SAN
UP
UP UP
CO
P-TRAP
(E) 3"ø SAN
(E) 4"ø SAN
(E) 1 1/2"ø SAN
UP
UP
P-TRAP
CO4"ø SAN
DN
CO
(E) 1 1/2"ø SAN
3"ø SAN
DN
CO
P-531 & P-712, CONNECT TO (E) DCW,
DHW, SAN & V
(E) FD
(E) 4"ø V
UP
4"ø V
4"ø V DN
1 1/2"ø V 2"ø V 2"ø V
2"ø V
(E) 2"ø V
(E) 3"ø V
UP
PROVIDE A 3/4" VALVED OUTLET
AT WALL ADJACENT TO SINK FOR
FUTURE COFFEE MAKER
UP
AREA NOT IN SCOPE
1. WORK WHICH WILL AFFECT FIRST FLOOR ABOVE SHALL BE
DONE AT NIGHT OR ON WEEKENDS. COORDINATE WITH
THE COR.
2. HOLD ALL UTILITIES UP AS HIGH AS POSSIBLE, LOCATING
BETWEEN AND THROUGH JOISTS WHERE POSSIBLE.
CEILING SPACE IS EXCEEDINGLY CONGESTED - EXISTING
FLOOR-TO-FLOOR HEIGHT IS 10'-0". THOROUGH
COORDINATION WITH ALL TRADES IS ESSENTIAL.
3. REFER TO SHEET M-001 FOR GENERAL NOTES AND
ABBREVIATIONS.
4. SANITARY PIPING SHALL SLOPE MINIMUM 1/8" PER FOOT IN
THE DIRECTION OF FLOW.
5. REFER TO FIXTURE CONNECTION SCHEDULE ON SHEET
PP501.
6. OFFSET PIPING AS REQUIRED TO AVOID INTERFERENCES
WITH STRUCTURE AND OTHER TRADES. NOT ALL
REQUIRED OFFSETS WHICH MAY BE REQUIRED ARE
INDICATED - CONTRACTOR TO COORDINATE WITH EXISTING
CONDITIONS AND ALL TRADES.
7. REFER TO ARCH GENERAL SERIES SHEETS FOR RATED
WALLS, TEMPORARY PARTITIONS, AND PHASING.
NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
GUIDON DESIGN INC. | 1221 N PENNSYLVANIA SUITE 200 | INDIANAPOLIS, IN 46202
317.800.6388 | WWW.GUIDONDESIGN.COM
GHAFARI ASSOCIATES LLC. | 17101 MICHIGAN AVENUE | DEARBORN, MI 48126
313.441.3000 | WWW.GHAFARI.COM
C g h a fa ri l o c a l c a c h e
\R e v it \1
M
C
E N
T R
A L p e la y y a n .r v t
/1
/2
:4
:4
P
M
PP411
PLUMBING LARGE SCALE VIEW -
PHARMACY
RENOVATE PHARMACY &
URGENT CARE
5500 Armstrong Road, Battle Creek
515-18-109
05/20/20 MAP PME
100% BID DOCUMENTS
PART. SPRINKLERED
100% BID DOCUMENTS
SCALE:
PP101
1/4" = 1'-0"
1 PLUMBING PLAN GROUND FLOOR - PHARMACY
SCALE:
NORTH
1" = 50'-0"
KEY PLAN - PHARMACY
L
M
M.4
N
M.1
13.3
HH
JJ
GG
KK
8 9 10 11 12 13 14 15
P-528
3/4"ø DHWS 3/4"ø DCW
P-532
WCO
P-101
P-711
FD
FD
P-418
3/4"ø DCW 3/4"ø DHWS
1"ø DCW 1"ø DHWS
1 1/2"ø DCW
P-532
3/4"ø DCW
3/4"ø DHWS
3/4"ø DHWS
3/4"ø DCW
3/4"ø DCW
3/4"ø DHWS
(E) 4"ø SAN
UP & DN
FCO
FCO
(E) 1 1/2"ø SAN
UP
1 1/2"ø SAN
DN TO UG
(E) 1 1/2"ø SAN
1 1/2"ø SAN
UP
DN TO UG
(E) 1 1/2"ø SAN
UP
4"ø SAN
DN TO UG
(E) 3"ø SAN
(E) 4"ø SAN
UP TO FD
UP
(E
"ø
S A
N
(E) 3"ø SAN
(E) 1 1/2"ø SAN
(E) 3"ø SAN
(E) 4"ø SAN
(E) 1 1/2"ø SAN
UP
UP
UP
UP TO FD
CO
4"ø SAN
DN TO UG
(E) 1 1/2"ø SAN
(E) 3"ø SAN
(E) 4"ø SAN
(E) 1 1/2"ø SAN
4"ø SAN
UP
UP
UP TO FD
UP
DN TO UG
2"ø V2"ø V
DN TO UG
2"ø V
DN TO UG
PROVIDE A 3/4" VALVED
OUTLET AT WALL
ADJACENT TO SINK FOR
FUTURE COFFEE MAKER
(E) 3"ø DCW
(E) 3"ø DHWR
(E) 3"ø DHWS
FCO
AREA NOT IN SCOPE
1. WORK WHICH WILL AFFECT FIRST FLOOR ABOVE SHALL BE
DONE AT NIGHT OR ON WEEKENDS. COORDINATE WITH
THE COR.
2. HOLD ALL UTILITIES UP AS HIGH AS POSSIBLE, LOCATING
BETWEEN AND THROUGH JOISTS WHERE POSSIBLE.
CEILING SPACE IS EXCEEDINGLY CONGESTED - EXISTING
FLOOR-TO-FLOOR HEIGHT IS 10'-0". THOROUGH
COORDINATION WITH ALL TRADES IS ESSENTIAL.
3. REFER TO SHEET M-001 FOR GENERAL NOTES AND
ABBREVIATIONS.
4. SANITARY PIPING SHALL SLOPE MINIMUM 1/8" PER FOOT IN
THE DIRECTION OF FLOW.
5. REFER TO FIXTURE CONNECTION SCHEDULE ON SHEET
PP501.
6. OFFSET PIPING AS REQUIRED TO AVOID INTERFERENCES
WITH STRUCTURE AND OTHER TRADES. NOT ALL
REQUIRED OFFSETS WHICH MAY BE REQUIRED ARE
INDICATED - CONTRACTOR TO COORDINATE WITH EXISTING
CONDITIONS AND ALL TRADES.
7. REFER TO ARCH GENERAL SERIES SHEETS FOR RATED
WALLS, TEMPORARY PARTITIONS, AND PHASING.
NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
GUIDON DESIGN INC. | 1221 N PENNSYLVANIA SUITE 200 | INDIANAPOLIS, IN 46202
317.800.6388 | WWW.GUIDONDESIGN.COM
GHAFARI ASSOCIATES LLC. | 17101 MICHIGAN AVENUE | DEARBORN, MI 48126
313.441.3000 | WWW.GHAFARI.COM
C g h a fa ri l o c a l c a c h e
\R e v it \1
M
C
E N
T R
A L p e la y y a n .r v t
/1
/2
:4
:5
P
M
PP412
PLUMBING LARGE SCALE VIEW -
OPEN OFFICE AND AUDIOLOGY
RENOVATE PHARMACY &
URGENT CARE
5500 Armstrong Road, Battle Creek
515-18-109
05/20/20 MAP PME
100% BID DOCUMENTS
PART. SPRINKLERED
100% BID DOCUMENTS
SCALE:
PP101
1/4" = 1'-0"
1 PLUMBING PLAN GROUND FLOOR - OPEN OFFICE AND AUDIOLOGY
KEYNOTES
FIELD ROUTE VENT BRANCH LINE AND CONNECT TO
(E) 2" VENT MAIN.
SCALE:
NORTH
1" = 50'-0"
KEY PLAN - OPEN OFFICE AND AUDIOLOGY
A
B
C
DD
10.6 10.8 11.3 11.8 11.9 13.2
EE
FF
GG
8 9 10
11 12 13
14 15
(E) 3"ø DCW
(E) 3"ø DHWS
(E) 2"ø DCW
(E) 2"ø DHWS
(E) 2 1/2"ø DHWS
(E) 2 1/2"ø DCW
(E) 1 1/2"ø DHWS
(E) 2"ø DCW
1 1/4"ø DHWS
2"ø DCW
1"ø DHWS
1 1/2"ø DCW
3/4"ø DHWS 3/4"ø DCW
3/4"ø DHWS
3/4"ø DCW
1"ø DHWS
1 1/2"ø DCW
1"ø DHWS
1 1/2"ø DCW
3/4"ø DHWS
1 1/2"ø DCW
P-502
3/4"ø DCW 3/4"ø DHWS
3/4"ø DHWR
CIRCUIT SETTER
SET TO 0.5 GPM
1 1/2"ø DCW 1 1/4"ø DHWS
P-101
P-418
1 1/2"ø DCW
3/4"ø DHWS
2"ø DCW
(E) 3"ø DHWR
3/4"ø DHWR
(E) 2 1/2"ø DHWR
(E) 2 1/2"ø DHWR
P-418
(E) 1"ø DHWR
3/4"ø DCW 3/4"ø DHWS
P-418 P-404
3/4"ø DCW
3/4"ø DHWS
P-505
P-532
3/4"ø DHWS
3/4"ø DCW
P-404
3/4"ø DCW 3/4"ø DHWS
(E) 1"ø DHWR
(E) 1 1/2"ø DHWS
(E) 2"ø DCW
P-404
P-935
P-910
3/4"ø DHWR
(E) 1 1/2"ø DCW
(E) 1"ø DHWS
(E) 1"ø DHWR
(E) 2"ø DCW
(E) 2"ø DHWS
(E) 2"ø DHWR
P-533
P-404
P-711
FD
P-418
P-101
P-404
3/4"ø DHWS
3/4"ø DCW
1"ø DHWS
1 1/2"ø DCW
P-404
P-404
3/4"ø DCW
3/4"ø DHWS
P-404
3/4"ø DCW
3/4"ø DHWS
3/4"ø DHWS
3/4"ø DCW
1 1/2"ø DCW
1 1/4"ø DHWS
CIRCUIT SETTER,
SET TO 0.5 GPM
FCO
FD
(E)FCO
(E) 2 1/2"ø DHWS
(E) 2 1/2"ø DCW
P-101
P-418
P-404
P-533
P-404
(E) 4"ø SAN
(E) 2"ø SAN
(E) 3"ø SAN
4"ø SAN
(E) 3"ø SAN
UP
UP
UP
DN TO UG
FD
1 1/2"ø V
FCO
1 1/2"ø V
1 1/2"ø V
2"ø V
2"ø V
DN TO
UG
1 1/2"ø V
1 1/2"ø V
1 1/2"ø V
1 1/2"ø V
1 1/2"ø V
1 1/2"ø V
1 1/2"ø V
1 1/2"ø V
1 1/2"ø V
1 1/2"ø V
1 1/2"ø V
1 1/2"ø V
11 1/2"ø V
1 1/2"ø V
SHUT-OFF
VALVE (TYP)
PROVIDE BFP AND PIPING TO
ICE MAKER/ BEVERAGE
DISPENSER, REFER TO
DETAIL
(E)FCO
(E)FCO
(E)FCO
(E)FCO
(E)FCO
1"ø DCW
3/4"ø DCW1 1/2"ø DCW
1 1/2"ø DCW
3/4"ø DHWS
1"ø DHWS
1"ø DHWS
AREA NOT IN SCOPE
1. WORK WHICH WILL AFFECT FIRST FLOOR ABOVE SHALL BE
DONE AT NIGHT OR ON WEEKENDS. COORDINATE WITH
THE COR.
2. HOLD ALL UTILITIES UP AS HIGH AS POSSIBLE, LOCATING
BETWEEN AND THROUGH JOISTS WHERE POSSIBLE.
CEILING SPACE IS EXCEEDINGLY CONGESTED - EXISTING
FLOOR-TO-FLOOR HEIGHT IS 10'-0". THOROUGH
COORDINATION WITH ALL TRADES IS ESSENTIAL.
3. REFER TO SHEET M-001 FOR GENERAL NOTES AND
ABBREVIATIONS.
4. SANITARY PIPING SHALL SLOPE MINIMUM 1/8" PER FOOT IN
THE DIRECTION OF FLOW.
5. REFER TO FIXTURE CONNECTION SCHEDULE ON SHEET
PP501.
6. OFFSET PIPING AS REQUIRED TO AVOID INTERFERENCES
WITH STRUCTURE AND OTHER TRADES. NOT ALL
REQUIRED OFFSETS WHICH MAY BE REQUIRED ARE
INDICATED - CONTRACTOR TO COORDINATE WITH EXISTING
CONDITIONS AND ALL TRADES.
7. REFER TO ARCH GENERAL SERIES SHEETS FOR RATED
WALLS, TEMPORARY PARTITIONS, AND PHASING.
NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
GUIDON DESIGN INC. | 1221 N PENNSYLVANIA SUITE 200 | INDIANAPOLIS, IN 46202
317.800.6388 | WWW.GUIDONDESIGN.COM
GHAFARI ASSOCIATES LLC. | 17101 MICHIGAN AVENUE | DEARBORN, MI 48126
313.441.3000 | WWW.GHAFARI.COM
C g h a fa ri l o c a l c a c h e
\R e v it \1
M
C
E N
T R
A L p e la y y a n .r v t
/1
/2
:4
:1
P
M
PP413
PLUMBING LARGE SCALE VIEW -
URGENT CARE
RENOVATE PHARMACY &
URGENT CARE
5500 Armstrong Road, Battle Creek
515-18-109
05/20/20 MAP PME
100% BID DOCUMENTS
PART. SPRINKLERED
100% BID DOCUMENTS
SCALE:
PP101
1/4" = 1'-0"
1 PLUMBING PLAN GROUND FLOOR - URGENT CARE
KEYNOTES
FIELD ROUTE VENT BRANCH LINE AND CONNECT TO
(E) 2" MIN VENT MAIN.
SCALE:
NORTH
1" = 50'-0"
A
B
C
DD
10.6 10.8 11.3 11.8 11.9 13.2
EE
FF
GG
8 9 10
11 12 13
14 15
(E) 3/4"ø O2
3/4"ø O2 3/4"ø MVAC
MED GASES
DN TO ZONE
VALVE BOX
3/4"ø MVAC
3/4"ø O2
MED GASES DN TO
(1) O2 OUTLET AND
(1) MVAC INLET IN
EXAM ROOM
(E) 3/4"ø O2
3/4"ø O2
3/4"ø MVAC
MED GASES DN TO
ZONE VALVE BOX
MED GAS
ALARM PANEL
MED GAS
ALARM PANEL
(E) 3/4"ø O2
3/4"ø MVAC
3/4"ø O2
3/4"ø MVAC
3/4"ø O2
3/4"ø O2 3/4"ø MVAC
3/4"ø MVAC 3/4"ø O2
MED GASES DN
TO (1) O2 OUTLET
AND (1) MVAC
INLET IN EACH
EXAM ROOM
MED GASES DN TO
(1) O2 OUTLET AND
(1) MVAC INLET IN
EXAM ROOM
MED GASES DN TO
(1) O2 OUTLET AND
(1) MVAC INLET IN
EXAM ROOM
MED GASES DN TO
(1) O2 OUTLET AND
(2) MVAC INLETS IN
PROCEDURE ROOM
MED GASES DN TO
(1) O2 OUTLET AND
(2) MVAC INLETS IN
PROCEDURE ROOM
MED GASES DN TO
(1) O2 OUTLET AND
(2) MVAC INLETS IN
PROCEDURE ROOM
MED GASES DN TO
(1) O2 OUTLET AND
(1) MVAC INLET IN ISO
ROOM
(E) 1"ø MVAC
FIELD VERIFY LOCATION OF
EXISTING VACUUM PIPING
MAIN
FIELD VERIFY LOCATION OF
EXISTING OXYGEN PIPING
MAIN
(E) 1" MVAC,
CONTINUES TO
SOURCE
(E) 3/4" O2, CONTINUES TO
SOURCE
(E) 1" MVAC,
CONTINUES TO
OTHER LOADS
(E) 3/4" O2, CONTINUES TO
OTHER LOADS
(E) 3/4" O2, CONTINUES TO
OTHER LOADS
AREA NOT IN SCOPE
1. WORK WHICH WILL AFFECT FIRST FLOOR ABOVE SHALL BE
DONE AT NIGHT OR ON WEEKENDS. COORDINATE WITH
THE COR.
2. HOLD ALL UTILITIES UP AS HIGH AS POSSIBLE, LOCATING
BETWEEN AND THROUGH JOISTS WHERE POSSIBLE.
CEILING SPACE IS EXCEEDINGLY CONGESTED - EXISTING
FLOOR-TO-FLOOR HEIGHT IS 10'-0". THOROUGH
COORDINATION WITH ALL TRADES IS ESSENTIAL.
3. REFER TO SHEET M-001 FOR GENERAL NOTES AND
ABBREVIATIONS.
4. OFFSET PIPING AS REQUIRED TO AVOID INTERFERENCES
WITH STRUCTURE AND OTHER TRADES. NOT ALL
REQUIRED OFFSETS WHICH MAY BE REQUIRED ARE
INDICATED - CONTRACTOR TO COORDINATE WITH EXISTING
CONDITIONS AND ALL TRADES.
5. IN NO CASE SHALL ANY MEDICAL GAS PIPING BE LESS THAN
1/2". IN NO CASE SHALL ANY MEDICAL VACUUM PIPING BE
LESS THAN 3/4".
NOTES
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
GUIDON DESIGN INC. | 1221 N PENNSYLVANIA SUITE 200 | INDIANAPOLIS, IN 46202
317.800.6388 | WWW.GUIDONDESIGN.COM
GHAFARI ASSOCIATES LLC. | 17101 MICHIGAN AVENUE | DEARBORN, MI 48126
313.441.3000 | WWW.GHAFARI.COM
C g h a fa ri l o c a l c a c h e
\R e v it \1
M
C
E N
T R
A L p e la y y a n .r v t
/1
/2
:4
:2
P
M
PP414
PLUMBING LARGE SCALE VIEW -
URGENT CARE - MEDICAL GAS
RENOVATE PHARMACY &
URGENT CARE
5500 Armstrong Road, Battle Creek
515-18-109
05/20/20 MAP PME
100% BID DOCUMENTS
PART. SPRINKLERED
100% BID DOCUMENTS
SCALE:
PP101
1/4" = 1'-0"
1 PLUMBING PLAN GROUND FLOOR - URGENT CARE - MEDICAL GASES
KEYNOTES
Medical Gases NO Smoking or Open Flame
PROVIDE LABEL FOR THE GAS BOTTLE STORAGE
ROOM. COORDINATE WITH THE GOVERNMENT'S
SIGNAGE PROVIDER. SIGN SHALL READ:
SCALE:
NORTH
1" = 50'-0"
INSTALL ZONE VALVE BOXES PER MANUFACTURER'S RECOMMENDATIONS.
FRONT VIEW
WALL
FIN. FLR.
SIDE VIEW
50"
SHUT-OFF
VALVE (TYP)
PRESSURE
GAUGE (TYP)
CL
NOTE:
REFER TO PLANS FOR PIPE
SIZES & DESIGNATIONS.
MEDICAL
GASES FROM
SOURCE
BRANCHES
MEDICAL
GASES TO
ROOMS
DOUBLE ZONE
VALVE BOX
SINGLE COMPARTMENT SINK
LAV 1/2" 1/2" 1 1/2" 1 1/2"
1 1/2"1/2"1/2" 1 1/2"
3" 1 1/2"SS SERVICE SINK 2" 3/4"
LAVATORY
FS -- -FLOOR SINK
NOTES:
1.
2.
3.
4.
PLUMBING FIXTURE SCHEDULE
VENTWASTE
HOT WATER/
TEMPERED
(DHW)
COLD
WATER
(DCW)
POINT CONNECTION
PLUMBING FIXTUREMARK
WC 1 1/4" 2"4"-
4"
NOTE 2
SK
WATER CLOSET
FD FLOOR DRAIN - -
3"
NOTE 2
3" 1 1/2"CSS CLINICAL SERVICE SINK 1 1/4" 3/4"
WH -3/4" -FREEZELESS
WALL HYDRANT
INSTALL FIXTURES PER MANUFACTURER'S INSTRUCTIONS TO MEET
BARRIER FREE REQUIREMENTS, AND PER CODE.
FURNISH AND INSTALL A DEEP SEAL TRAP WITH 4" SEAL AND 1/2" TRAP
PRIMER PIPING.
PROVIDE EACH LAVATORY, SINK AND SHOWER WITH POINT-OF-USE
THERMOSTATIC MIXING VALVE. ALL POINT-OF-USE MIXING VALVES
SHALL BE IN ACCORDANCE WITH APPLICABLE ASSE STANDARD.
PROVIDE SHUT-OFF VALVE ON SUPPLY LINES TO EACH FIXTURE
GROUP.
EWC -1/2" 1 1/2"ELECTRIC WATER
COOLER
1 1/2"
SH SHOWER 3/4" 3/4" --
STEAM, GAS, OR AIR PIPING
BRANCH SECTIONALIZING
VALVE, OR EQUIPMENT
SHUT-OFF VALVE
SUPPLY MAIN
BRANCH PIPING
OFF TOP OF MAIN
WATER PIPING
BRANCH SECTIONALIZING
VALVE, OR EQUIPMENT
SHUT-OFF VALVE
SUPPLY OR
RETURN MAIN
BRANCH PIPING OFF
BOTTOM OF MAIN
NOTE: BRANCHES MAY BE 45 OR 90 DEGREES ABOVE/BELOW MAIN
STEEL PIPE
SLEEVE AS
REQUIRED
FIRE RATED
PARTITION
UNINSULATED PIPE
REFER TO UL APPROVED
MFG LITERATURE FOR
SPECIFIC PRODUCT
LIMITATIONS.
FIRESTOP SEALANT
SEE MANUFACTURER
LITERATURE FOR DEPTH
FIRESTOP SEALANT OF
SLEEVE PENETRATION BY
OTHERS WHERE
REQUIRED
FIRESTOP SEALANT
SEE MANUFACTURER
LITERATURE FOR DEPTH
STEEL PIPE
SLEEVE WHERE
REQUIRED
FIRE RATED
PARTITION
REFER TO UL APPROVED
MFG LITERATURE FOR
SPECIFIC PRODUCT
LIMITATIONS.
PIPING
PIPE INSULATION
FIRESTOP SEALANT OF
SLEEVE PENETRATION BY
OTHERS WHERE REQUIRED
ENTENTES TO SEWER LINE
NOTE:
PIPING AND JOINT TYPE PER SPECIFICATIONS
EXTERIOR
PROVIDE NICKEL BRONZE FLOOR
PLATE TO BE COMPATIBLE
W/ TYPE FLOOR INSTALLED
EXTENSION TO
SOIL OR WASTE
LINE
JOINT TYPE
PER SPECS
FINISHED FLOOR OR PAVED
AREA. PROVIDE 18"x18"x8"
CONCRETE PAD WHEN
FINISHING AT GRADE
FLOOR WALL
SOIL OR WASTE
CLEANOUT TEE
CHROME PLATED
BRONZE WALL PLATE
JOINT TYPE
PER SPECS
BRASS PLUG
CLEANOUT
ACCESS
COVER
SANITARY OR
STORM PIPING,
SLOPED IN
DIRECTION OF FLOW
AT SLOPE NOTED
ON PLANS
CAST IRON
CLEANOUT FERRULE
AND PLUG
FINISHED FLOOR OR PAVED
AREA PROVIDE 18" x 18"x 6"
CONCRETE PAD WHEN
FINISHING AT GRADE.
BALL VALVES
1 1/2" VENT
1/2" DHWS
3/4" DCW
1/2" DCW
1/2" DHWS &
DCW TO SINK
1 1/2" SAN
FILTER WITH
GAUGES AND
BALL VALVE
INSTALL TRAP PRIMER
BEHIND 8" SQUARE
STAINLESS STEEL
ACCESS PANEL
M
IN
SECURE TUBING DRAIN
LINES TO UNDERSIDE OF
COUNTER TOP & TERMINATE
OF TRAPPED SAN INLET
1 1/2" SAN
FIN FLR
CEILING
WALL
3/4" DCW
1 1/2" VENT
ICE
MAKER
ICE MAKER
FILTER
TUBING DRAINS
2" AIR GAP
1 1/2" SAFE WASTE
DRAIN WITH TRAP,
CONNECT TO VENTED
SAN RISER IN WALL
1 1/2" VENTED
SAN RISER
FIN FLR
CEILING
FOOT PEDAL
FLUSH VALVE
1 1/2" VENT
3/4" DHWS
1 1/4" DCW
1 1/4"
3/4"
1/2"
PEDAL VALVE
SUPPORT
BRACKET
VACUUM
BREAKER
FIN FLR
CEILING
FIXTURE
SUPPORT
3" WASTE
NOTES:
INSTALL FIXTURE AND COMPONENTS PER MANUFACTURER'S GUIDELINES AND INSTRUCTIONS.
RINSE UNIT TO
DRIP OVER SINK
AND BE LONG
ENOUGH TO
EXTEND TO
SINK RIM
SERVICE
SINK FAUCET
PEDAL VALVE
FOOT PEDAL
FLUSH VALVE
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD STAMPCONSULTANT
321 4 5 6 7 8 9 10
GUIDON DESIGN INC. | 1221 N PENNSYLVANIA SUITE 200 | INDIANAPOLIS, IN 46202
317.800.6388 | WWW.GUIDONDESIGN.COM
GHAFARI ASSOCIATES LLC. | 17101 MICHIGAN AVENUE | DEARBORN, MI 48126
313.441.3000 | WWW.GHAFARI.COM
C g h a fa ri l o c a l c a c h e
\R e v it \1
M
C
E N
T R
A L p e la y y a n .r v t
/1
/2
:4
:4
P
M
PP501
PLUMBING PIPING DETAILS RENOVATE PHARMACY &
URGENT CARE
5500 Armstrong Road, Battle Creek
515-18-109
05/20/20 MAP PME
100% BID DOCUMENTS
PART. SPRINKLERED
100% BID DOCUMENTS
NOT TO SCALE
MEDICAL GASES ZONE VALVE BOX
NOT TO SCALE
PLUMBING BRANCH CONNECTIONS
NOT TO SCALE
PENETRATION - FIRESTOPPED UNINSULATED PIPE THRU RATED PARTITION
NOT TO SCALE
PENETRATION - FIRESTOPPED INSULATED PIPE THRU RATED WALL
NOT TO SCALE
CLEANOUTS
NOT TO SCALE
CLEANOUT DETAIL
NOT TO SCALE
COUNTER-TOP BEVERAGE DISPENSER OR ICE MAKER PIPING
NOT TO SCALE
CLINICAL SERVICE SINK PIPING DIAGRAM - WALL MOUNT PEDAL FLUSH
F
T
TS
H
S
PD
SP
TS
FS
1.
2.
3.
4.
5.
6.
7.
GENERAL MECHANICAL NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
GENERAL HVAC NOTES
1.
2.
3.
4.
5.
6.
7.
8.
9.
A.
B.
GENERAL HVAC PIPING NOTES
FINAL ELECTRICAL POWER CONNECTIONS TO ALL MECHANICAL EQUIPMENT SHALL BE BY
ELECTRICAL TRADE.
FINAL GAS CONNECTIONS TO ALL MECHANICAL EQUIPMENT SHALL BE PROVIDED BY
PLUMBING TRADE.
ALL FIELD CONTROL WIRING AND INTERLOCK WIRING SHALL BE FURNISHED AND
INSTALLED BY TEMPERATURE CONTROL TRADES. FOR EXAMPLE, WIRING FROM
CONTROL PANEL TO CONTROLLED DEVICE SHALL BE SHOWN AND INSTALLED BY
TEMPERATURE CONTROL TRADES.
KEEP ALL EXHAUST AIR AND SANITARY VENTS AWAY FROM OUTSIDE AIR INTAKE, AT
LEAST A MINIMUM OF 10 FEET.
MECHANICAL CONTRACTOR SHALL COORDINATE ALL OPENINGS IN MASONRY/PRE-CAST
WALLS WITH MASON/PRE-CAST CONTRACTOR.
MECHANICAL CONTRACTOR SHALL COORDINATE WITH ARCHITECTURAL TRADES
PAINTING OF ALL EXPOSED DUCTWORK, DIFFUSERS AND PIPING/INSULATION.
ACCESS DOORS: PROVIDE ACCESS DOORS FOR ALL EQUIPMENT THAT REQUIRES
ROUTINE MAINTENANCE OR SERVICE; AND THAT IS CONCEALED BEHIND NON-
ACCESSIBLE WALL OR CEILING CONSTRUCTION. TYPICALLY ACCESS PANELS ARE NOT
SHOWN ON THE DRAWINGS. THE CONTRACTOR SHALL BE RESPONSIBLE FOR LOCATING
AND SIZING OF ACCESS DOORS TO PERMIT REQUIRED ACCESS FOR ROUTINE
MAINTENANCE OPERATIONS.
1.
2.
3.
4.
5.
6.
GENERAL DEMOLITION NOTES
DEMOLITION OF EACH SYSTEM SHALL INCLUDE ALL ACCESSORIES (DAMPERS, VALVES,
AND OTHER COMPONENTS), PIPE, DUCT AND EQUIPMENT SUPPORTS, AS WELL AS ALL
EXISTING ABANDONED EQUIPMENT AND MATERIALS WHERE SUCH ITEMS ARE NOT
REQUIRED FOR THE PROPER OPERATION OF THE REVISED SYSTEMS.
REMOVE ALL ITEMS INDICATED FOR DEMOLITION. REMOVE ASSOCIATED SUPPORTS,
ACCESSORIES, INSULATION, CONDUIT, WIRING AND CONTROLS. POWER AND CONTROL
WIRING SHALL BE REMOVED BACK TO SOURCE. PIPING AND DUCTWORK SHALL BE
CAPPED AT MAIN, UNLESS SHOWN OTHERWISE.
DURING DEMOLITION AND CONSTRUCTION, PROTECT EQUIPMENT, PIPING, DUCTWORK,
ACCESSORIES, SUPPORTS, AND OTHER EXISTING SYSTEMS THAT ARE TO REMAIN.
PROTECT ALL EQUIPMENT, DUCT, AND PIPE ENDS OF COMPONENTS TO REMAIN WITH
TEMPORARY CLOSURES DURING DEMOLITION WORK.
EXCEPT FOR ITEMS IDENTIFIED AS BEING TURNED OVER TO THE OWNER, ALL
DEMOLISHED ITEMS SHALL BE COMPLETELY REMOVED FROM THE SIDE AND PROPERLY
DISPOSED OF BY CONTRACTOR.
SERVICES TO ADJACENT AREAS SHALL BE MAINTAINED DURING DEMOLITION AND
CONSTRUCTION. PROVIDE MEANS FOR TEMPORARY SERVICES IF REQUIRED IN ORDER
TO PROVIDE FOR CONTINUOUS OPERATIONS.
GENERAL NOTES
1. CONTRACTOR IS RESPONSIBLE TO COMPLETE A THOROUGH FIELD SURVEY OF THE AREA
OF WORK. CONTRACTOR MUST CONDUCT A SITE SURVEY DURING BID PERIOD TO CONFIRM
EXISTING CONDITIONS AND EXTENTS OF SCOPE.
2. VERIFY EXACT SIZE AND LOCATION OF EXISTING UTILITIES BEFORE START OF
CONSTRUCTION.
3. CONNECTIONS TO AND SHUT-DOWNS OF EXISTING SYSTEM SHALL BE COORDINATED WITH
THE VA TO ALLOW MINIMUM INTERFERENCE WITH THE VA'S OPERATIONS AND DOWN TIME
OF EXISTING SERVICES. CONTRACTOR SHALL SUBMIT TO VA FOR REVIEW AND APPROVAL
THE PROPOSED PHASING PLAN FOR CONNECTING NEW SERVICES.
4. IT IS MANDATORY FOR CONTRACTOR TO COORDINATE WITH ALL OTHER MECHANICAL AND
ELECTRICAL TRADES IN REGARDS TO ROUTING OF PIPING IN MECHANICAL ROOMS, SHAFTS,
ABOVE CEILINGS AND ATTIC SPACES.
5. ALL ITEMS THAT REQUIRE ACCESS, SUCH AS FOR OPERATING, CLEANING, SERVICING,
MAINTENANCE, AND CALIBRATION, SHALL BE EASILY AND SAFELY ACCESSIBLE BY PERSONS
STANDING AT FLOOR LEVEL, OR STANDING ON PERMANENT PLATFORMS, WITHOUT THE USE
OF PORTABLE LADDERS. EXAMPLES OF THESE ITEMS INCLUDE, BUT ARE NOT LIMITED TO:
ALL TYPES OF VALVES, FILTERS AND STRAINERS, TRANSMITTERS, CONTROL DEVICES.
PRIOR TO COMMENCING INSTALLATION WORK, REFER CONFLICTS BETWEEN THIS
REQUIREMENT AND…