511.21337.CAK RENOVATE ARMORY - BIG RAPIDS Drawings CD volume b_Part1.pdf
PDF 4 MB Posted
- Solicitation number
- RFQ - 171 - 230000000114
- Issued by
- Mecosta County, Michigan
About this file
This document is a drawing set for a structural renovation project for the Big Rapids Armory in Mecosta County, Michigan. The project involves demolition and reconstruction of portions of the existing armory building, including upgrades to the floor slab, foundation walls, masonry walls, structural steel framing, steel joists and decking, and concrete vault construction. The drawings provide detailed plans, sections, and details for the structural work required. No specific bid due date or award date is provided, but the project is being managed by the Michigan Department of Military and Veterans Affairs, Construction and Facilities Management Office.
The structural design is based on the 2015 Michigan Building Code and specifies material strengths, dead/live loads, snow loads, wind loads, and seismic loads to be used. The drawings include a full set of typical construction details, including foundation, masonry wall, steel framing, and steel deck connections. Special inspection and testing requirements are also specified in accordance with the building code. No information is provided on pricing terms, set asides, incumbent contractors, funding sources, or contract term.
View the file
Other files
Show all 13
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
STRUCTURAL DESIGN CRITERIA
1. GOVERNING CODE MICHIGAN BUILDING CODE (MBC), 2015 EDITION
2. BUILDING RISK CATEGORY III
3. DESIGN SOIL BEARING PRESSURE 3000 PSF
4. MATERIAL STRENGTHS
STRUCTURAL STEEL:
ASTM A992 (Fy = 50 KSI) - ROLLED STEEL SHAPES UNLESS NOTED ON THE
DRAWINGS.
ASTM A36 (Fy = 36 KSI) - ROLLED STEEL PLATES, CHANNELS, ANGLES, BARS, AND RODS AS NOTED ON THE DRAWINGS.
ASTM A500, GRADE C - RECTANGULAR HSS
REINFORCING STEEL:
ASTM A615, GRADE 60
CONCRETE:
4000 PSI FOR ALL CONCRETE UNLESS SPECIFICALLY NOTED OTHERWISE
MASONRY:
1500 PSI FOR CLAY MASONRY
2000 PSI FOR CONCRETE MASONRY
5. DEAD LOADS
ROOF
ROOFING 1.0 PSF
INSULATION 4.0 PSF
METAL DECK 3.0 PSF
FRAMING 5.0 PSF
MEP ALLOWANCE 7.0 PSF
TOTAL ROOF DEAD LOAD 20.0 PSF
6. LIVE LOADS
ROOF 20 PSF
LIVE LOAD REDUCTIONS SHALL BE COMPUTED IN ACCORDANCE WITH THE MICHIGAN
BUILDING CODE. ROOF LIVE LOADS ARE NON-REDUCIBLE.
7. DESIGN SNOW LOAD AND SNOW DRIFTING PARAMETERS ARE AS FOLLOWS:
GROUND SNOW LOAD (Pg) 40.0 PSF
FLAT ROOF SNOW LOAD (Pf) 31.0 PSF + DRIFT
SNOW EXPOSURE FACTOR (Ce) 1.0
SNOW THERMAL FACTOR (Ct) 1.0
SNOW LOAD IMPORTANCE FACTOR 1.10
8. WIND LOAD DESIGN PARAMETERS ARE AS FOLLOWS:
BASIC WIND SPEED (V), (3 SECOND GUST) 120 MPH
WIND EXPOSURE CATEGORY C
INTERNAL PRESSURE COEFFICIENT ±0.18
9. SEE TABLE FOR COMPONENTS AND CLADDING LOAD CRITERIA. ALL ARCHITECTURAL AND
STRUCTURAL COMPONENTS SHALL CONFORM WITH THE MICHIGAN BUILDING CODE AND
ASCE 7 FOR COMPONENTS AND CLADDING DESIGN.
ROOF PRESSURES (PSF)
WALL PRESSURES (PSF)
NOTES:
- END ZONE WIDTH IN FEET = 10% OF LEAST HORIZONTAL DIMENSION OR .4h
WHICHEVER IS SMALLER BUT NOT LESS THAN EITHER, 4% OF LEAST HORIZONTAL
DIMENSION OR 3'-0"
h=MEAN ROOF HEIGHT, IN FEET, EXCEPT THAT EAVE HEIGHT SHALL BE USED FOR
ROOF ANGLES < 10
10. SEISMIC LOAD DESIGN PARAMETERS ARE AS FOLLOWS:
SOIL SITE CLASS D
MAPPED SPECTRAL RESPONSE ACCELERATION
(Ss) 0.058
(S1) 0.038
DESIGN SPECTRAL RESPONSE ACCELERATION
(Sds) 0.062
(Sd1) 0.061
SEISMIC DESIGN CATEGORY A
SEISMIC IMPORTANCE FACTOR (Ie) 1.25
SEISMIC LATERAL FORCE RESISTING SYSTEM - INTERMEDIATE REINFORCED MASONRY
SHEAR WALLS
RESPONSE MODIFICATION FACTOR (R) 3.5
DEFLECTION AMPLIFICATION FACTOR (Cd) 2.25
SEISMIC DESIGN METHOD EQUIVALENT LATERAL FORCE PROCEDURE
SEISMIC RESPONSE COEFFICIENT (Cs) 0.01
SEISMIC DESIGN STRUCTURE WEIGHT (W) 102 KIPS
SEISMIC DESIGN BASE SHEAR (V) 1.02 KIPS
FOUNDATIONS
1. FOUNDATIONS HAVE BEEN DESIGNED IN ACCORDANCE WITH THE SUBSURFACE
INVESTIGATION REPORT BY MATERIALS TESTING CONSULTANTS, INC. DATED APRIL 2022.
THE CONTRACTOR SHALL BECOME FAMILIAR WITH THE SURVEY AND SUBSURFACE
INVESTIGATION REPORT PRIOR TO BIDDING AND BEFORE BEGINNING CONSTRUCTION.
2. THE SUBSURFACE INVESTIGATION IS FOR INFORMATIONAL PURPOSES ONLY AND SHALL NOT
BE CONSIDERED PART OF THE CONTRACT DOCUMENTS. FURTHERMORE, NO WARRANTY IS
MADE BY THE OWNER WITH REGARD TO COMPLETENESS AND ACCURACY OF SUBSURFACE
INVESTIGATION DATA, STATEMENTS, AND INTERPRETATIONS GIVEN IN REPORT.
3. NOTIFY THE A/E AS SOON AS POSSIBLE OF ANY UNUSUAL SOIL CONDITIONS OR SOIL
CONDITIONS AT VARIANCE WITH TEST BORINGS, SUCH AS UNEXPECTED SPRING OR
SEEPAGE WATER, MATERIAL DIFFERING FROM TEST BORINGS, OR SOIL OF QUESTIONABLE
BEARING CAPACITY.
4. SET FOUNDATIONS AT THE ELEVATIONS SHOWN ON THE DRAWINGS ON FIRM SUBGRADE
PREPARED PER THE EARTHWORK SPECIFICATIONS. VERIFY THAT EACH FOOTING PLACED IS
BEARING ON MATERIAL WITH THE DESIGN BEARING CAPACITY PER THE SUBSURFACE
INVESTIGATIVE REPORT.
5. THE CONTRACTOR SHALL BE RESPONSIBLE FOR THE DESIGN, INSTALLATION, AND FINAL
CLEARANCE OF ANY REQUIRED NEEDLING, UNDERPINNING, SHORING, OR BRACING OF
EXISTING STRUCTURES.
GENERAL CONDITIONS
1. COORDINATE WITH ALL DRAWINGS FOR PERTINENT INFORMATION RELATED TO THE
STRUCTURAL WORK. ANY CHANGES TO THE STRUCTURAL SYSTEMS SHALL BE RE-DESIGNED
BY A REGISTERED PROFESSIONAL ENGINEER AT NO COST TO THE OWNER OR A/E AND
SUBMITTED TO THE A/E FOR REVIEW. SUBMITTAL SHALL BE ACKNOWLEDGED IN WRITING
BEFORE BEGINNING CONSTRUCTION
2. EQUIPMENT FRAMING LOADS, OPENINGS, AND STRUCTURE, IN ANY WAY RELATED TO HVAC,
PLUMBING, PROCESS, ELECTRICAL, ELEVATOR, OR ESCALATOR REQUIREMENTS ARE SHOWN
FOR BIDDING PURPOSES ONLY. CONTRACTOR SHALL OBTAIN APPROVAL OF THE PERTINENT
TRADES BEFORE PROCEEDING WITH SUCH PORTION OF THE WORK. EXCESS COST RELATED
TO VARIATION IN THESE REQUIREMENTS SHALL BE BORNE BY THE APPROPRIATE
CONTRACTOR.
3. IT IS SOLELY THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE THE ERECTION
PROCEDURE AND SEQUENCES TO ENSURE THE SAFETY OF THE BUILDING AND ITS
COMPONENTS DURING ERECTION. THIS INCLUDES, BUT IS NOT LIMITED TO, THE ADDITION
OF TEMPORARY BRACING, SHORING, GUYS, OR TIE-DOWNS THAT MAY BE NECESSARY.
4. THE STRUCTURE HAS BEEN DESIGNED FOR THE UNIFORM LOADS INDICATED IN ADDITION TO
THE CONCENTRATED LOADS REQUIRED BY THE BUILDING CODE. THE STRUCTURAL DESIGN
IS BASED SOLELY ON THE BUILDING IN ITS COMPLETED STATE. CONTRACTORS AND THEIR
SUB-CONTRACTORS SHALL TAKE NECESSARY PRECAUTIONS TO WITHSTAND ALL
HORIZONTAL AND VERTICAL LOADINGS THAT MAY BE ENCOUNTERED DURING
CONSTRUCTION PRIOR TO COMPLETION OF THE BUILDING. SUCH CONSTRUCTION
LOADINGS INCLUDE, BUT ARE NOT LIMITED TO, LOADS FROM CRANES, LIFTS, DOLLIES, AND
HOISTS. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR THE EVALUATION OF THE IMPACT
OF SUCH LOADS ON THE STRUCTURE AND PROVIDING TEMPORARY SHORING, BRACING, OR
REINFORCEMENT AS REQUIRED.
5. SEE THE ARCHITECTURAL DRAWINGS FOR ALL DIMENSIONS NOT SHOWN ON THE
STRUCTURAL DRAWINGS. ALL DIMENSIONS AND ELEVATIONS SHOWN ON THE STRUCTURAL
DRAWINGS SHALL BE VERIFIED BY THE CONTRACTOR AND SHALL CONFORM TO THOSE
SHOWN ON THE ARCHITECTURAL DRAWINGS. REPORT ALL DISCREPANCIES TO THE A/E FOR
RESOLUTION BEFORE PROCEEDING.
6. THE CONTRACTOR SHALL SUPPORT, BRACE, AND SECURE EXISTING STRUCTURES AS
REQUIRED. THE CONTRACTOR IS SOLELY RESPONSIBLE FOR THE SAFETY OF EXISTING
STRUCTURES DURING CONSTRUCTION. FIELD VERIFY ALL EXISTING DIMENSIONS WHICH
AFFECT THE NEW CONSTRUCTION PRIOR TO FINAL DETAILING AND FABRICATION OF NEW
STRUCTURAL ELEMENTS.
STRUCTURAL STEEL
1. STRUCTURAL STEEL SHALL CONFORM TO THE AISC "SPECIFICATION FOR DESIGN,
FABRICATION, AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS".
2. THE STRUCTURE WAS DESIGNED USING LRFD APPROACH PER THE AISC "STEEL
CONSTRUCTION MANUAL"
3. WELDED CONNECTIONS SHALL CONFORM TO THE AWS D1.1.
4. ALL STRUCTURAL STEEL, BOLTS, ETC., SHALL BE DOMESTICALLY PRODUCED.
5. BOLTS AND BOLTED CONNECTIONS SHALL CONFORM TO THE REQUIREMENTS OF THE
"SPECIFICATION FOR STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS" AS
APPROVED BY THE COUNCIL ON RIVETED AND BOLTED JOINTS, UNO. USE BEARING-TYPE
BOLTS WITH THREADS INCLUDED IN THE SHEAR PLANE. ANCHOR BOLTS SHALL CONFORM TO
ASTM F-1554, GRADE 36, OR AS SPECIFIED ON THE DRAWINGS.
6. WELDING ELECTRODES SHALL BE E70XX (LOW HYDROGEN) OR BETTER, FOR WELDING
SYMBOLS WITH NO LENGTH DIMENSION GIVEN, THE WELDING SHALL BE CONTINUOUS
BETWEEN ABRUPT CHANGES IN DIRECTION. WELDS NOT OTHERWISE NOTED SHALL BE 1/4" IN
SIZE.
7. IN GENERAL, IT IS THE INTENT OF THESE PLANS AND SPECIFICATIONS THAT ALL SHOP
CONNECTIONS BE WELDED AND ALL FIELD CONNECTIONS BE BOLTED EXCEPT WHERE NOTED
OTHERWISE.
8. ALL BOLTS SHALL BE TIGHTENED TO A "SNUG-TIGHT" CONDITION, UNO. BOLTS IN MOMENT
CONNECTIONS SHALL BE DESIGNED "SLIP-CRITICAL" WITH A CLASS "A" FAYING SURFACE.
BOLTS IN BRACED CONNECTIONS AND COLUMN SPLICES SHALL BE FULLY PRE-TENSIONED,
BUT ARE REQUIRED TO BE SLIP CRITICAL.
9. UNLESS NOTED OTHERWISE, TYPICAL BEAM SHEAR CONNECTIONS SHALL BE DETAILED WITH
STANDARD DOUBLE ANGLE OR SHEAR PLATE CONNECTIONS, USING A325 BOLTS.
NON-COMPOSITE BEAM CONNECTIONS SHALL BE DESIGNED TO DEVELOP 55% OF THE
TOTAL LOAD CAPACITY DERIVED FROM THE AISC STEEL CONSTRUCTION MANUAL
MAXIMUM UNIFORM LOAD TABLES.
10. VERIFY THE EXACT SIZE AND LOCATION OF ALL OPENINGS PRIOR TO FABRICATION OF STEEL
FRAMING MEMBERS.
11. OPENINGS THROUGH STEEL BEAMS SHALL BE PROVIDED AS DETAILED ON THE DRAWINGS.
ALL SUCH OPENINGS SHALL BE MACHINE CUT. ALL RECTANGULAR OPENINGS SHALL HAVE A
CORNER RADIUS OF 2 TIMES THE WEB THICKNESS, 1/2" MINIMUM.
12. ALL STEEL EXPOSED TO WEATHER, EXPOSED TO EARTH, EXPOSED TO VIEW OUTSIDE THE
BUILDING ENVELOPE, OR DENOTED ON THE DRAWINGS TO BE GALVANIZED, SHALL BE HOT-
DIPPED GALVANIZED AFTER FABRICATION. GALVANIZING SHALL BE REMOVED PER AWS
D-19.0, "WELDING ZINC-COATED STEEL", PRIOR TO FIELD WELDING. WELDS SHALL BE
TOUCHED-UP WITH TWO COATS OF ZINC-RICH PAINT BRUSH APPLIED USING ZRC
GALVANIZING COMPOUND OR EQUAL. PROVIDE VENT/DRAINAGE HOLES IN HSS MEMBERS
(MINIMUM 3/4 DIAMETER, BOTTOM SIDE OF HORIZONTAL MEMBERS, WITHIN 2" OF BASE
FOR VERTICAL MEMBERS) PRIOR TO GALVANIZING.
13. ALL STEEL WITHIN UNCONDITIONED AREAS OUTSIDE THE BUILDING ENVELOPE (E.G.
EXTERIOR SOFFITS, CANOPIES, ETC) BUT NOT EXPOSED TO VIEW SHALL BE PRIMED AND
PAINTED UNLESS NOTED OTHERWISE.
14. THE FABRICATOR SHALL SUPPLY LOOSE LINTEL ANGLES OVER ALL MASONRY OPENINGS AND
RECESSES UNLESS OTHERWISE NOTED. LINTELS NOT SCHEDULED ON THE DRAWINGS SHALL
CONSIST OF A SINGLE ANGLE WITH A 3 1/2" HORIZONTAL LEG FOR EACH 4" OF WALL
THICKNESS. LINTELS SHALL BE SIZED PER THE MASONRY LINTEL SCHEDULE, UNO.
EXISTING CONDITIONS
1. ALL EXISTING STRUCTURAL ELEMENTS (SLABS, BEAMS, WALLS, COLUMNS, FOUNDATIONS,
ETC.) SHALL REMAIN INTACT UNLESS SPECIFICALLY NOTED TO BE REMOVED BY THE MOST
RECENT DEMOLITION DOCUMENTS OR OTHERWISE NOTED ON THE STRUCTURAL DRAWINGS.
2. INFORMATION PROVIDED ON THESE DRAWINGS RELATED TO EXISTING CONDITIONS IS
BASED ON AVAILABLE DESIGN DOCUMENTS AND LIMITED FIELD OBSERVATION. THE
CONTRACTOR SHALL IMMEDIATELY REPORT TO AND AWAIT DIRECTION FROM THE A/E IF ANY
DISCREPANCY BETWEEN THE CONTRACT DOCUMENTS AND THE EXISTING CONDITIONS IS
DISCOVERED.
3. THIS PROJECT REQUIRES A SIGNIFICANT AMOUNT OF DRILLING INTO THE EXISTING
REINFORCED CONCRETE STRUCTURE. THE CONTRACTOR WILL NOT RECEIVE ADDITIONAL
PAYMENT FOR DIFFICULTIES ENCOUNTERED IN DRILLING DUE TO HARDNESS OF MATERIALS,
HITTING OF EXISTING REINFORCING, ETC.. ALL COSTS ASSOCIATED WITH REDRILLING OF
HOLES DUE TO HITTING EXISTING REINFORCING STEEL SHALL BE BORNE BY THE
CONTRACTOR. THIS INCLUDES FILLING UNNECESSARY AND UNUSED HOLES WITH EPOXY
GROUT. DO NOT CUT REINFORCING STEEL DURING CONCRETE DRILLING OR CORING
OPERATIONS. LOCATE REINFORCING WITH A PACHOMETER OR OTHER NON-DESTRUCTIVE
TESTING DEVICE PRIOR TO DRILLING OR CORING OPERATIONS.
4. CORE DRILLS REQUIRED BY MECHANICAL OR ELECTRICAL TRADES, BUT NOT SHOWN ON THE
STRUCTURAL DRAWINGS SHALL BE DOCUMENTED IN SKETCH FORM SHOWING EXACT
DIMENSIONS AND LOCATIONS. THE SKETCH SHALL BE SUBMITTED TO THE A/E FOR
COMMENT PRIOR TO PROCEEDING WITH THE DRILLING OPERATION.
5. EXISTING SURFACE PREPARATION:
INTENTIONALLY ROUGHEN EXISTING CONCRETE SURFACES WHERE NEW CONCRETE IS BEING
PLACED AGAINST THE EXISTING CONCRETE AND CONNECTED BY DRILLING AND EPOXY
GROUTING. THE ENTIRE COMMON SURFACE WHERE THE EXISTING CONCRETE ABUTS THE
NEW SHALL BE COATED WITH AN EPOXY BONDING AGENT. FOLLOW ALL ADDITIONAL
REQUIREMENTS OF SURFACE PREPARATION AS REQUIRED BY THE BONDING AGENT
MANUFACTURER.
STEEL JOISTS AND JOIST GIRDERS
1. STEEL JOISTS SHALL CONFORM TO THE REQUIREMENTS OF THE STEEL JOIST INSTITUTE (SJI)
STANDARD SPECIFICATIONS, LOAD TABLES, AND WEIGHT TABLES FOR STEEL JOISTS AND
JOIST GIRDERS.
2. THE STEEL JOIST MANUFACTURER SHALL BE A MEMBER OF THE STEEL JOIST INSTITUTE.
3. VERIFY THE EXACT SIZE AND LOCATION OF ALL OPENINGS PRIOR TO FABRICATION OF JOISTS
AND HEADERS.
4. THE JOIST VENDOR SHALL PROVIDE HEADERS OF ADEQUATE STRENGTH FOR JOIST SUPPORT
AT OPENINGS.
5. ALL HANGERS TO SUPPORT MECHANICAL EQUIPMENT, ETC. SHALL BE SUPPORTED BY THE
BOTTOM CHORD OF JOISTS AND SHALL BE LOCATED AT THE PANEL POINTS. PROVIDE JOIST
STIFFENERS AS INDICATED IN DETAILS. ALL HANGERS SHALL BE LOCATED AT THE CENTERLINE
OF THE BOTTOM CHORD MEMBER.
6. EXTEND BOTTOM CHORDS OF ALL JOISTS CENTERED ON COLUMNS TO A STABILIZER PLATE
ON THE COLUMN AS SHOWN IN THE TYPICAL DETAILS. DO NOT CONNECT JOIST BOTTOM
CHORD TO THE STABILIZER PLATE UNLESS NOTED OTHERWISE.
7. JOIST BRIDGING SHALL BE FURNISHED AND INSTALLED TO MEET DESIGN AND SPACING
REQUIREMENTS OF THE SJI STANDARD SPECIFICATION FOR STEEL JOISTS AND JOIST
GIRDERS. USE HORIZONTAL BRIDGING FOR SHORT SPAN ROOF JOISTS. USE RIGID X-
BRIDGING FOR ALL LH AND DLH SERIES JOISTS. ALL BRIDGING AND BRIDGING ANCHORS
SHALL BE COMPLETELY INSTALLED BEFORE CONSTRUCTION LOADS ARE PLACED ON THE
JOISTS.
8. ENDS OF JOIST BRIDGING LINES SHALL BE ANCHORED TO MASONRY WALLS OR STEEL
BEAMS. ALL BRIDGING SHALL BE WELDED TO JOISTS IN SUCH A MANNER AS NOT TO IMPAIR
THE STRUCTURAL INTEGRITY OF THE JOIST.
9. RIGID X-BRACING AS SHOWN ON THE PLANS SHALL BE BOLTED OR WELDED AT THE
INTERSECTION OF THE TWO BRIDGING MEMBERS BETWEEN JOISTS.
10. WELD ALL STEEL JOISTS TO SUPPORTING STRUCTURAL STEEL MEMBERS AS SHOWN ON THE
DRAWINGS AND ACCORDING TO SJI AND AWS D1.1 AS A MINIMUM.
11. ANY SPLICES REQUIRED IN JOIST OR JOIST GIRDER WEB OR CHORD MEMBERS SHALL BE
DESIGNED BY THE JOIST MANUFACTURER AND SHALL BE IN ACCORDANCE WITH SJI
STANDARD SPECIFICATIONS.
12. ALL LH AND DLH SERIES JOISTS SHALL HAVE A MINIMUM LENGTH OF BEARING ON STEEL
BEAMS OF 5". MINIMUM BEARING LENGTH ON MASONRY AND CONCRETE SHALL BE:
- 6" FOR LH02 THROUGH LH11 AND DLH10 THROUGH DLH12.
- 8" FOR LH12 THROUGH LH14, DLH13 AND DLH14.
- 10" FOR LH15 THROUGH LH17, DLH15 AND DLH16.
- 12" FOR DLH17 THROUGH DLH19.
- IF THIS MINIMUM BEARING CANNOT BE MET, THE JOIST PLACEMENT MUST BE
STAGGERED TO ACHIEVE THIS MINIMUM REQUIRED BEARING.
13. JOISTS AND JOIST GIRDERS SHALL BE ERECTED STRAIGHT. SWEEPS SHALL BE A MAXIMUM
OF 1" MEASURED AT THE CENTER.
14. JOISTS AND JOIST GIRDERS SHALL BE DESIGNED FOR A MINIMUM NET UPLIFT LOAD EQUAL
TO 20 PSF.
STEEL DECK
1. STEEL DECK FABRICATION AND ERECTION SHALL CONFORM TO THE STEEL DECK INSTITUTE
SPECIFICATIONS.
2. DECK SHALL INCLUDE ANY MISCELLANEOUS CLOSURE PIECES, METAL SCREEDS, ROOF
CURBS, DRAIN SUMP PANS, REINFORCING AROUND OPENINGS, ETC. REQUIRED TO MAKE A
COMPLETE JOB. MISCELLANEOUS ITEMS SHALL BE GALVANIZED AND SHALL BE NO THINNER
THAN 18 GAGE.
3. ROOF DECK SHALL BE PRIME PAINTED (G-90), UNO.
4. NO LOAD SHALL BE HUNG FROM STEEL ROOF DECK.
CAST-IN-PLACE CONCRETE
1. CAST-IN-PLACE CONCRETE WORK SHALL CONFORM TO THE PROJECT MANUAL AND
AMERICAN CONCRETE INSTITUTE CODES AND STANDARDS, INCLUDING, BUT NOT LIMITED
TO, ACI 301, ACI 315, AND ACI 318.
2. WELDED WIRE FABRIC SHALL CONFORM TO ASTM A-185 DELIVERED IN FLAT SHEETS.
3. THE CONTRACTOR SHALL REVIEW ALL DRAWINGS FOR SIZE AND LOCATION OF ALL
EMBEDDED ITEMS, SLEEVES, SLAB DEPRESSIONS, OPENINGS, ETC. REQUIRED BY OTHER
TRADES. RECONCILE THEIR EXACT SIZES AND LOCATIONS BEFORE PROCEEDING WITH THE
WORK. ALL ITEMS SHALL BE FURNISHED AND INSTALLED PRIOR TO PLACEMENT OF
CONCRETE. SECURE THE APPROVAL OF THE STRUCTURAL ENGINEER PRIOR TO PLACING
OPENINGS NOT SHOWN ON THE STRUCTURAL DRAWINGS. DO NOT CORE DRILL THROUGH
BEAMS, JOISTS, GIRDERS, OR WALLS. NO CONDUIT SHALL BE PLACED IN CONCRETE SLABS
OR BEAMS UNLESS SPECIFICALLY SHOWN ON THE STRUCTURAL DRAWINGS.
4. BACKFILL AGAINST WALLS SHALL NOT BE PLACED UNTIL THE FLOOR CONSTRUCTION AT THE
FIRST FLOOR HAS BEEN COMPLETED TO BRACE THE WALL. AT THE CONTRACTORS OPTION,
WALLS MAY BE BRACED AND BACKFILL INSTALLED. ANY SUCH BRACING SHALL BE SOLELY
THE RESPONSIBILITY OF THE CONTRACTOR AND SHALL REMAIN IN PLACE UNTIL THE FIRST
FLOOR IS COMPLETED AND CONTINUOUSLY CONNECTED TO THE WALL.
5. WHERE BAR LENGTHS ARE GIVEN ON THE DRAWINGS, THE LENGTH OF ANY HOOK, IF
REQUIRED, IS NOT INCLUDED. USE STANDARD 90° BAR HOOK UNO.
6. PROVIDE HORIZONTAL CONTROL/CONSTRUCTION JOINTS IN SLABS AND VERTICAL
CONTROL/CONSTRUCTION IN WALLS AS SHOWN ON THE DRAWINGS. ALL BEAMS,
SPANDRELS, AND SLABS SHALL BE CAST MONOLITHICALLY, EXCEPT FOR REQUIRED
CONTROL/CONSTRUCTION JOINTS SHOWN ON THE DRAWINGS. CONTRACTOR SHALL SUBMIT
ALTERNATE AND ADDITIONAL CONSTRUCTION JOINT LOCATIONS AND DETAILS TO THE A/E
FOR APPROVAL PRIOR TO CONSTRUCTION. AT LEAST 48 HOURS SHALL ELAPSE BETWEEN
CASTING OF ADJOINING UNITS. REINFORCEMENT SHALL BE CONTINUOUS ACROSS
CONSTRUCTION JOINTS UNLESS DETAILED OTHERWISE ON THE DRAWINGS. SUBMIT ALL
CONSTRUCTION JOINT LOCATIONS WITH THE REINFORCING SHOP DRAWINGS.
7. WHERE CONSTRUCTION JOINTS ARE REQUIRED BUT ARE NOT INDICATED ON THE DRAWINGS,
THEY SHALL BE LOCATED AT THE MID-SPAN OF BEAMS, SLABS AND WALLS, AND SHALL BE
SUBJECT TO REVIEW BY THE A/E. UNO OR SHOWN ON THE DRAWINGS, PROVIDE A
CONTINUOUS SHEAR KEY IN SLABS AND WALLS, AND A MINIMUM OF (2) CONTINUOUS
HORIZONTAL KEYS IN BEAMS AND EACH JOIST. THE MINIMUM KEY SIZE SHALL BE 1-1/2"
DEEP X 1/3 THE DEPTH OR WIDTH OF THE MEMBER. AT COMPOSITE CONCRETE SLABS ON
STEEL DECK, SUPPORTED BY STEEL BEAMS AND GIRDERS, CONSTRUCTION JOINTS PARALLEL
TO BEAMS SHALL BE PLACED MID-WAY BETWEEN BEAMS NEAREST TO THE COLUMN
CENTERLINE AND CONSTRUCTION JOINTS PARALLEL TO GIRDERS SHALL BE PLACED 4 TO 6
FEET FROM THE GIRDER CENTERLINE. AT NON-COMPOSITE CONCRETE SLABS ON STEEL
DECK, SUPPORTED BY STEEL BEAMS AND GIRDERS, CONSTRUCTION JOINTS SHALL BE
PLACED AT MID-SPAN OF DECK AND MID-WAY BETWEEN GIRDERS. REFERENCE ACI 302 FOR
GUIDELINES AND ADDITIONAL INFORMATION.
8. THE CONTRACTOR SHALL PROVIDE 3/4" CHAMFERS ON ALL EXPOSED CORNERS OF
COLUMNS, BEAMS, AND WALLS UNO INDICATED ON THE ARCHITECTURAL DRAWINGS.
MINIMUM CLEARANCES FOR REINFORCING STEEL SHALL CONFORM WITH THE TYPICAL
REINFORCING BAR CLEARANCE TABLE.
9. THE HARDENED CONCRETE OF HORIZONTAL CONSTRUCTION JOINTS SHALL BE DAMPENED
AND THEN THOROUGHLY COVERED WITH A COAT OF CEMENT GROUT OF SIMILAR
PROPORTIONS TO THE MORTAR IN THE CONCRETE. THE FRESH CONCRETE SHALL BE PLACED
BEFORE THE GROUT HAS ATTAINED ITS INITIAL SET.
10. THE HARDENED CONCRETE OF CONSTRUCTION JOINTS SHALL BE THOROUGHLY COATED
WITH A BONDING AGENT (SIKA ARMATEC 110 OR EQUAL).
11. WELDING OF REINFORCING STEEL IS NOT PERMITTED.
12. COMPLY WITH THE ARCHITECTURAL DRAWINGS FOR LOCATION AND EXTENT OF SPECIAL
FINISHES OR TREATMENTS TO EXPOSED CONCRETE.
13. PROVIDE 6X6-W1.4XW1.4 WELDED WIRE FABRIC IN ALL TOPPING SLABS, UNO.
14. LAP WELDED WIRE FABRIC 1 SPACE (2 CROSS WIRES) + 2" AT ALL EDGES AND ENDS OF
SHEETS.
15. REINFORCING BAR LAP SPLICES AND ANCHORAGE LENGTHS SHALL CONFORM WITH
"MINIMUM LAP SPLICE AND ANCHORAGE DIMENSION TABLE"
16. PROVIDE A BOND-BREAKER AT MASONRY BEARING OF ALL CAST-IN-PLACE CONCRETE
SLABS, JOISTS, AND BEAMS.
MASONRY CONSTRUCTION
1. MASONRY WORK SHALL CONFORM TO THE ACI 530 AND 530.1.
2. CONCRETE MASONRY UNITS SHALL BE NORMAL WEIGHT UNITS
HOLLOW LOAD BEARING ASTM C90, WITH MINIMUM NET AREA COMPRESSIVE OF
2000 PSI. ALL LOAD BEARING BLOCK UNITS SHALL BE
MANUFACTURED SO THE CORES AND WEBS LINE UP WHEN
LAID IN RUNNING BOND.
SOLID LOAD BEARING PROVIDE UNITS COMPLYING WITH ASTM C145, GRADE
N-1, WITH A MINIMUM COMPRESSIVE STRENGTH OF 2000
PSI, EACH UNIT, NET CROSS-SECTIONAL AREA.
3. MORTAR FOR LOAD BEARING WALLS, EXTERIOR WALLS, SHEAR WALLS, AND VERTICALLY
REINFORCED MASONRY WALLS SHALL BE ASTM C270, TYPE S, WITH A MINIMUM
COMPRESSIVE STRENGTH OF 1800 PSI AT 28 DAYS.
4. WHERE VERTICAL BARS ARE TO BE GROUTED INTO CORES, THE FOLLOWING REQUIREMENTS
APPLY:
COARSE GROUT FOR REINFORCED MASONRY CONSTRUCTION SHALL CONFORM TO
ASTM C476 WITH A MAXIMUM AGGREGATE SIZE OF 3/8" AND A MINIMUM
COMPRESSIVE STRENGTH OF 3000 PSI.
PROVIDE DOWELS FROM FOOTING, SAME SIZE AND SPACING AS WALL BARS. LAP
WITH WALL BAR.
WHEN A FOUNDATION DOWEL DOES NOT LINE UP WITH A VERTICAL CORE, IT SHALL
NOT BE SLOPED MORE THAN ONE HORIZONTAL IN SIX VERTICAL. DOWELS SHALL BE
GROUTED INTO A CORE IN VERTICAL ALIGNMENT, EVEN THOUGH IT IS IN AN
ADJACENT CELL TO THE VERTICAL WALL REINFORCEMENT.
REINFORCING STEEL SHALL BE LAPPED IN ACCORDANCE WITH SCHEDULE WHERE
SPLICED. PROVIDE REINFORCING ALIGNMENT DEVICES AT A MAXIMUM SPACING OF
192 BAR DIAMETERS.
5. HORIZONTAL REINFORCEMENT SHALL BE PLACED IN CONTINUOUS MASONRY COURSES
CONSISTING OF BOND BEAM OR TROUGH BLOCK UNITS AND GROUTED IN PLACE. THE
CONTRACTOR SHALL PLACE ANCHOR BOLTS OR EMBEDDED ITEMS IN COARSE GROUT, UNO
ON DRAWINGS.
6. SPLICED WIRE REINFORCEMENT SHALL BE LAPPED AT LEAST 6" AND CONTAIN AT LEAST ONE
CROSS WIRE OF EACH PIECE OF REINFORCEMENT WITHIN THE 6".
7. WALL CONSTRUCTION UNDER MASONRY BEARING STRUCTURAL MEMBERS SHALL BE AS
FOLLOWS, UNO:
PROVIDE BOND BEAM AS DETAILED ON THE DRAWINGS UNDER WALL BEARING
STEEL JOISTS. BOND BEAM SHALL BE FILLED WITH 3000 PSI GROUT.
PROVIDE SOLID MASONRY, 32" LONG x 24" HIGH, CENTERED UNDER EACH WALL
BEARING STEEL BEAM.
PROVIDE CONTINUOUS SOLID MASONRY, 8" HIGH, UNDER WALLS BEARING
PRECAST OR CAST-IN-PLACE CONCRETE SLABS.
8. DO NOT CONSTRUCT MASONRY WALLS ON SUPPORTED CONCRETE DECKS UNTIL CONCRETE
HAS REACHED 28 DAY STRENGTH AND ALL SHORING HAS BEEN REMOVED.
9. ALL UNITS SHALL BE LAID WITH FULL MORTAR COVERAGE ON HEAD, BED (FACE SHELLS),
WEBS AND COLLAR JOINTS, UNO.
10. PROVIDE LINTELS OVER ALL OPENINGS WIDER THAN 8" IN MASONRY WALLS. REFER TO THE
ARCHITECTURAL AND MECHANICAL DRAWINGS FOR LOCATION, NUMBER, AND SIZES OF
OPENINGS.
11. PROVIDE CONTROL JOINTS IN ALL MASONRY WALLS AS SHOWN ON THE STRUCTURAL
DRAWINGS OR AS DEFINED IN THE SPECIFICATIONS. IF NO CONTROL JOINTS ARE SHOWN ON
THE DRAWINGS, PROVIDE CONTROL JOINTS AT A SPACING OF 25' OR 1.5 TIMES THE WALL
HEIGHT, WHICHEVER IS LESS. NO CONTROL JOINTS SHALL BE PROVIDED IN MASONRY
SHEAR WALLS, WHERE SHEAR WALLS ARE LONGER THAN MAXIMUM CONTROL JOINT SPACING
PROVIDE SINGLE COURSE CONTINUOUS HORIZONTAL BOND BEAM WITH (2) #6 BARS @ 6' -
0" OC MAX OVER THE FULL HEIGHT OF THE WALL.
12. BOND BEAM REINFORCING SHALL BE CONTINUOUS THROUGH CONTROL JOINTS AND
AROUND CORNERS AND AT WALL INTERSECTIONS. AT CORNERS AND WALL INTERSECTIONS,
PROVIDE BENT BARS OF SAME SIZE AND QUANTITY AS BOND BEAM REINFORCING AND LAP
SPLICE WITH BOND BEAM REINFORCING WITH LENGTHS AS REQUIRED BY MASONRY LAP
SPLICE SCHEDULE.
ZONE 1
16.0, -25.9
16.0, -25.0
16.0, -24.3
16.0, -23.7
16.0, -23.7
ZONE 2
16.0, -43.4
16.0, -37.3
16.0, -32.7
16.0, -28.1
16.0, -28.1
ZONE 3
16.0, -65.4
16.0, -50.5
16.0, -39.3
16.0, -28.1
16.0, -28.1
AREA
INTERIOR ZONE
23.7, -43.4
22.3, -37.3
21.3, -32.7
20.2, -28.1
17.8, -28.1
EDGE ZONE
23.7, -65.4
22.3, -50.5
21.3, -39.3
20.2, -28.1
17.8, -28.1
AREA
USE THIS TABLE FOR A615 GRADE 60 REINFORCING WHEN CONCRETE CLEAR COVER AND
CLEAR SPACING IS AT LEAST db AND CODE MINIMUM STIRRUPS ARE PROVIDED OR IF
MINIMUM STIRRUPS ARE NOT PROVIDED, CLEAR SPACING IS AT LEAST 2db.
CONCRETE MINIMUM LAP SPLICE AND
ANCHORAGE DIMENSION TABLE
(4000 PSI CONCRETE) (3000 PSI CONCRETE)
TOP BARS OTHER BARS TOP BARS OTHER BARSBAR SIZE BAR SIZE
DEVELOPMENT LENGTH
#3
#4
#5
#6
#7
#8
#10
#9
#11
#3
#4
#5
#6
#7
#8
#10
#9
#11
15"
20"
25"
30"
44"
50"
63"
56"
12"
16"
19"
23"
34"
38"
49"
43"
54"
18"
23"
29"
35"
50"
57"
73"
65"
81"
14"
18"
22"
27"
39"
44"
56"
50"
62"
NOTES:
• LAP LENGTHS SHALL BE 1.3 TIMES DEVELOPMENT LENGTH.
• FOR EPOXY COATED REINFORCING MULTIPLY THE TABLE VALUES ABOVE BY 1.5.
• (MC) DENOTES MECHANICAL COUPLER DEVELOPING 125% OF THE BAR YIELD STRENGTH.
NO OTHER SPLICE WILL BE ACCEPTED.
• WHEN LAPPING TWO DIFFERENT SIZE BARS, USE THE LAP DIMENSION OF THE SMALLER
BAR OR THE ANCHORAGE DIMENSION OF THE LARGER BARS. USE WHICHEVER DIMENSION
IS LARGER.
• TOP BARS SHALL BE DEFINED AS BEAM AND SLAB HORIZONTAL REINFORCEMENT SO
PLACED THAT MORE THAN 12" OF FRESH CONCRETE IS CAST IN THE MEMBER BELOW THE
TOP REINFORCEMENT. HORIZONTAL REINFORCING IN WALLS SHALL BE CONSIDERED TOP
BARS.
DEVELOPMENT LENGTH
MASONRY MINIMUM LAP SPLICE SCHEDULE
BAR SIZE
#3
#4
LAP LENGTH FOR BARS EACH FACE OF CMU
WALL (2 1/2" CLEAR MASONRY COVER)
LAP LENGTH FOR BARS CENTERED
IN CMU THICKNESS
12" 12"
13" 18"
#5 20" 28"
#6 38" 52"
#7 52" 70"
#8 79" 105"
NOTES:
MECHANICAL COUPLERS DEVELOPING 125% OF THE BAR YIELD STRENGTH ARE PERMITTED AT
ANY SPLICE LOCATION AT CONTRACTOR'S OPTION.
CONCRETE REINFORCING CLEAR COVER REQUIREMENTS
CONCRETE CAST AGAINST AND PERMANENTLY IN CONTACT WITH GROUND
CONCRETE EXPOSED TO WEATHER OR IN CONTACT WITH GROUND
#5 BAR AND SMALLER
#6 BAR AND LARGER
CONCRETE NOT EXPOSED TO WEATHER OR IN CONTACT WITH GROUND
SLABS, JOISTS, AND WALLS (NOT LARGER THAN #11 BAR)
BEAMS, COLUMNS, PIERS
NOTE:
CLEAR COVER DIMENSIONS LISTED ARE CODE-REQUIRED MINIMUMS. PROVIDE GREATER
COVER WHERE SPECIFICALLY REQUIRED BY DETAILS.
3"
1-1/2"
2"
3/4"
1-1/2"
NOTE:
1. ONLY DRIFTS ON AREAS OF NEW CONSTRUCTION OR DRIFTS ON EXISTING
CONSTRUCTION CAUSED BY THE NEW CONSTRUCTION ARE SHOWN ON THIS PLAN.
2. SCHEDULED DRIFT VALUES ARE IN ADDITION TO THE FLAT ROOF SNOW LOAD.
3. WHERE TWO OR MORE SNOW DRIFTS INTERSECT THE LARGER VALUE SNOW DRIFT
VALUE SHALL GOVERN. INTERSECTING SNOW DRIFTS SHALL BE CONSIDERED TO
OCCUR CONCURRENTLY, EXCEPT THAT THE SNOW DRIFT LOADS NEED NOT BE
SUPERIMPOSED.
Wd
P f
P d
FLAT ROOF SNOW LOAD PER GENERAL NOTES
SNOW DRIFT SCHEDULE
DRIFT Wd Pd (PSF) NOTES
A 17' - 2" 83
B 13' - 4" 62
EXISTING BUILDING
NEW ADDITION
A
B
1/32" = 1'-0"
SNOW DRIFT PLAN
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R D
A T
E
F
IL
E N
U M
B E
R
/2
.C A
K
A
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
T U E B O R
U S
Q U
E R
C I
UP
IS
R
C
S N I
E N
M
I S
K A B
E
R U
P L
S B U
I
A N
E O
E
I
M L A P
A M
C
M
M U
U N
P R E L
IM
IN
A R Y
C O N S T R U C T
IO
N
F
IN
A L
R E C O R D
D A T E
IS
S U E D
F O R
IN
D E X
C O D E
P R O J E C T
ID
E N T
IF
IC
A T
IO
N
N O
S H E E T
D E S
IG
N E D
D R A W N
C H E C K E D
A P P R O V E D
S T
A T
E O
F M
IC
H
IG
A
N D
E P
A R
T M
E N
T O
F M
IL
IT
A R
Y A
N D
V E
T E
R A
N S
A F
F A
IR
S
C
O N
S T
R U
C T
IO
N
A N
D F
A C
IL
IT
IE
S
M
A N
A G
E M
E N
T O
F F
IC
E
N
M
A R
T
IN
L U
T H
E R
K
IN
G J
R B
L V
D L A
N S
IN
G
M
IC
H
IG
A
N
-2
T
A T
E O
F M
IC
H
IG
A
N
D E P A R T M E N T
O F
T E C H N O L O G Y M A N A G E M E N T
A N D
B U D G E T
F A C
IL
IT
IE
S
A N D
B U S
IN
E S S
S E R V
IC
E S
A D M
IN
IS
T R A T
IO
N
A D A M
L A C H R A D
IR
E C T O R
G E
N E
R A
L N
O T
E S
S
D E
C E
M B
E R
D E
C E
M B
E R
JNJN R
E
R C
-5
.0
R E
N O
V A
T E
A R
M O
R Y
B
IG
R
A P
ID
S
B ig
R a p id s, M ic h ig a n
ISSUED FOR DATE
REQUIRED SPECIAL INSPECTIONS AND TESTS OF SOILS (MBC SECTION 1705.6)
SPECIAL INSPECTION TASK
CONTINUOUS SPECIAL
INSPECTION
PERIODIC SPECIAL
INSPECTION
1. VERIFY MATERIALS BELOW SHALLOW FOUNDATIONS ARE ADEQUATE TO ACHIEVE
THE DESIGN BEARING CAPACITY.
2. VERIFY EXCAVATIONS ARE EXTENDED TO THE PROPER DEPTH AND HAVE REACHED
PROPER MATERIAL.
3. PERFORM CLASSIFICATION AND TESTING OF COMPACTED FILL MATERIALS.
4. VERIFY USE OF PROPER MATERIALS, DENSITIES, AND LIFT THICKNESSES DURING
PLACEMENT AND COMPACTION OF COMPACTED FILL.
5. PRIOR TO PLACEMENT OF COMPACTED FILL, INSPECT SUBGRADE AND VERIFY
THAT SITE HAS BEEN PREPARED PROPERLY.
X
X
X
X
X
REQUIRED SPECIAL INSPECTIONS AND TESTS OF CONCRETE CONSTRUCTION (MBC SECTION 1705.3)
SPECIAL INSPECTION TASK
CONTINUOUS SPECIAL
INSPECTION
PERIODIC SPECIAL
INSPECTION
1. INSPECT REINFORCEMENT AND VERIFY PLACEMENT.
2. REINFORCING BAR WELDING (PERMITTED ONLY WHEN SPECIFICALLY SHOWN IN THE
DETAILS OR WITH PERMISSION IN WRITING BY THE ENGINEER):
A. VERIFY WELDABILITY OF REINFORCING BARS OTHER THAN ASTM A706
B. INSPECT SINGLE-PASS FILLET WELDS UP TO AND INCLUDING 5/16"
C. INSPECT ALL OTHER WELDS
3. INSPECT ANCHORS CAST IN CONCRETE
4. INSPECT ANCHORS POST-INSTALLED IN HARDENED CONCRETE
A. ADHESIVE ANCHORS INSTALLED IN HORIZONTALLY OR UPWARDLY INCLINED
ORIENTATIONS TO RESIST SUSTAINED TENSION LOADS
B. ALL OTHER ANCHORS POST-INSTALLED IN HARDENED CONCRETE
5. VERIFY USE OF REQUIRED MIX DESIGN.
6. PRIOR TO CONCRETE PLACEMENT, FABRICATE SPECIMENS FOR STRENGTH TESTS,
PERFORM SLUMP AND AIR CONTENT TESTS, AND DETERMINE THE TEMPERATURE
OF THE CONCRETE.
7. INSPECT CONCRETE PLACEMENT FOR PROPER APPLICATION TECHNIQUES.
8. VERIFY MAINTENANCE OF SPECIFIED CURING TEMPERATURE AND TECHNIQUES.
9. INSPECT ERECTION OF PRECAST CONCRETE MEMBERS.
10. VERIFY IN-SITU CONCRETE STRENGTH PRIOR TO REMOVAL OF SHORES AND
FORMS FROM BEAMS AND STRUCTURAL SLABS.
11. INSPECT FORMWORK FOR SHAPE, LOCATION AND DIMENSIONS OF CONCRETE
MEMBER BEING FORMED.
X
X
X
X
X
X
X
X
X
X
X
X
X
X
EXCEPTIONS - THE ABOVE SPECIAL INSPECTIONS AND TESTS SHALL NOT BE REQUIRED FOR THE FOLLOWING BUILDING ELEMENTS:
1. ISOLATED SPREAD FOOTINGS OF BUILDINGS THREE STORIES OR LESS ABOVE GRADE THAT ARE FULLY SUPPORTED ON EARTH OR ROCK.
2. NONSTRUCTURAL SLABS SUPPORTED DIRECTLY ON THE GROUND.
REQUIRED SPECIAL INSPECTIONS AND TESTS OF MASONRY CONSTRUCTION (MBC SECTION 1705.4
AND TMS 402-13 LEVEL B QUALITY ASSURANCE)
SPECIAL INSPECTION TASK
CONTINUOUS SPECIAL
INSPECTION
PERIODIC SPECIAL
INSPECTION
1. VERIFY COMPLIANCE WITH THE APPROVED SUBMITTALS
2. AS MASONRY CONSTRUCTION BEGINS, VERIFY THAT THE FOLLOWING ARE IN
COMPLIANCE:
A. PROPORTIONS OF SITE-PREPARED MORTAR
B. CONSTRUCTION OF MORTAR JOINTS
C. LOCATION OF REINFORCEMENT AND CONNECTORS
3. PRIOR TO GROUTING, VERIFY THAT THE FOLLOWING ARE IN COMPLIANCE:
A. GROUT SPACE
B. GRADE, TYPE, AND SIZE OF REINFORCEMENT AND ANCHOR BOLTS
C. PLACEMENT OF REINFORCEMENT AND CONNECTORS
D. PROPORTIONS OF SITE-PREPARED GROUT
E. CONSTRUCTION OF MORTAR JOINTS
4. VERIFY DURING CONSTRUCTION:
A. SIZE AND LOCATION OF STRUCTURAL ELEMENTS
B. TYPE, SIZE, AND LOCATION OF ANCHORS, INCLUDING OTHER DETAILS OF
ANCHORAGE OF MASONRY TO STRUCTURAL MEMBERS, FRAMES, OR OTHER
CONSTRUCTION
C. WELDING OF REINFORCEMENT (PERMITTED ONLY WHEN SPECIFICALLY SHOWN
IN THE DETAILS OR WITH PERMISSION IN WRITING BY THE ENGINEER)
D. PREPARATION, CONSTRUCTION, AND PROTECTION OF MASONRY DURING
COLD WEATHER (TEMPERATURE BELOW 40°F) OR HOT WEATHER
(TEMPERATURE ABOVE 90°F)
E. PLACEMENT OF GROUT IS IN COMPLIANCE
5. OBSERVE PREPARATION OF GROUT SPECIMENS, MORTAR SPECIMENS, AND/OR
PRISMS
X
X
TESTING TASK
1. VERIFICATION OF SLUMP FLOW AND VISUAL STABILITY INDEX (VSI) AS DELIVERED TO THE PROJECT SITE IN ACCORDANCE WITH TMS
602-13 ARTICLE 1.5 B.1.b.3 FOR SELF-CONSOLIDATING GROUT.
2. VERIFICATION OF f'm IN ACCORDANCE WITH TMS 602-13 ARTICLE 1.4 B PRIOR TO CONSTRUCTION.
X
X
X
X
X
X
X
X
X
X
X
X
X
REQUIRED SPECIAL INSPECTIONS PRIOR TO WELDING OF STRUCTURAL STEEL (AISC 360 N5.4)
SPECIAL INSPECTION TASK PERFORM OBSERVE
1. WELDER QUALIFICATION RECORDS AND CONTINUITY RECORDS
2. WPS AVAILABLE
3. MANUFACTURER CERTIFICATIONS FOR WELDING CONSUMABLES AVAILABLE
4. MATERIAL IDENTIFICATION (TYPE/GRADE)
5. WELDER IDENTIFICATION SYSTEM
6. FIT-UP OF GROOVE WELDS (INCLUDING JOINT GEOMETRY)
A. JOINT PREPARATIONS
B. DIMENSIONS (ALIGNMENT, ROOT OPENING, ROOT FACE, BEVEL)
C. CLEANLINESS (CONDITION OF STEEL SURFACES)
D. TACKING (TACK WELD QUALITY AND LOCATION)
E. BACKING TYPE AND FIT (IF APPLICABLE)
7. CONFIGURATION AND FINISH OF ACCESS HOLES
8. FIT-UP OF FILLET WELDS
A. DIMENSIONS (ALIGNMENT, GAPS AT ROOT)
B. CLEANLINESS (CONDITION OF STEEL SURFACES)
C. TACKING (TACK WELD QUALITY AND LOCATION)
X
X
X
X
X
X
X
X
REQUIRED SPECIAL INSPECTIONS DURING WELDING OF STRUCTURAL STEEL (AISC 360 N5.4)
SPECIAL INSPECTION TASK
1. CONTROL AND HANDLING OF WELDING CONSUMABLES
A. PACKAGING
B. EXPOSURE CONTROL
2. NO WELDING OVER CRACKED TACK WELDS
3. ENVIRONMENTAL CONDITIONS
A. WIND SPEED WITHIN LIMITS
B. PRECIPITATION AND TEMPERATURE
4. WPS FOLLOWED
A. SETTINGS ON WELDING EQUIPMENT
B. TRAVEL SPEED
C. SELECTED WELDING MATERIALS
D. SHIELDING GAS TYPE/FLOW RATE
E. PREHEAT APPLIED
F. INTERPASS TEMPERATURE MAINTAINED (MIN./MAX.)
G. PROPER POSITION (F, V, H, OH)
5. WELDING TECHNIQUES
A. INTERPASS AND FINAL CLEANING
B. EACH PASS WITHIN PROFILE LIMITATIONS
C. EACH PASS MEETS QUALITY REQUIREMENTS
6. PLACEMENT AND INSTALLATION OF STEEL HEADED STUD ANCHORS
X
X
X
X
X
X
REQUIRED SPECIAL INSPECTIONS AFTER WELDING OF STRUCTURAL STEEL (AISC 360 N5.4)
SPECIAL INSPECTION TASK
1. WELDS CLEANED
2. SIZE, LENGTH, AND LOCATION OF WELDS
3. WELDS MEET VISUAL ACCEPTANCE CRITERIA
A. CRACK PROHIBITION
B. WELD/BASE-METAL FUSION
C. CRATER CROSS SECTION
D. WELD PROFILES
E. WELD SIZE
F. UNDERCUT
G. POROSITY
4. ARC STRIKES
5. k-AREA
6. WELD ACCESS HOLES IN ROLLED HEAVY SHAPES AND BUILT-UP HEAVY SHAPES
7. BACKING REMOVED AND WELD TABS REMOVED (IF REQUIRED)
8. REPAIR ACTIVITIES
9. DOCUMENT ACCEPTANCE OR REJECTION OF WELDED JOINT OR MEMBER
10. NO PROHIBITED WELDS HAVE BEEN ADDED WITHOUT THE APPROVAL OF THE EOR
X
X
X
X
X
X
X
X
X
X
REQUIRED SPECIAL INSPECTIONS PRIOR TO BOLTING OF STRUCTURAL STEEL (AISC 360 N5.6)
SPECIAL INSPECTION TASK PERFORM OBSERVE
1. MANUFACTURER'S CERTIFICATIONS AVAILABLE FOR FASTENER MATERIALS
2. FASTENERS MARKED IN ACCORDANCE WITH ASTM REQUIREMENTS
3. CORRECT FASTENERS SELECTED FOR THE JOINT DETAIL (GRADE, TYPE, BOLT
LENGTH IF THREADS ARE TO BE EXCLUDED FROM SHEAR PLANE)
4. CORRECT BOLTING PROCEDURE SELECTED FOR JOINT DETAIL
5. CONNECTING ELEMENTS, INCLUDING THE APPROPRIATE FAYING SURFACE
CONDITION AND HOLE PREPARATION, IF SPECIFIED, MEET APPLICABLE
REQUIREMENTS
6. PRE-INSTALLATION VERIFICATION TESTING BY INSTALLATION PERSONNEL
OBSERVED AND DOCUMENTED FOR FASTENER ASSEMBLIES AND METHODS USED
(REQUIRED ONLY FOR PRETENSIONED OR SLIP-CRITICAL JOINTS)
7. PROTECTED STORAGE PROVIDED FOR BOLTS, NUTS, WASHERS AND OTHER
FASTENER COMPONENTS
X
X
X
X
X
X
X
REQUIRED SPECIAL INSPECTIONS DURING BOLTING OF STRUCTURAL STEEL (AISC 360 N5.6)
SPECIAL INSPECTION TASK PERFORM OBSERVE
1. FASTENER ASSEMBLIES PLACED IN ALL HOLES AND WASHERS AND NUTS ARE
POSITIONED AS REQUIRED.
2. JOINT BROUGHT INTO THE SNUG-TIGHT CONDITION PRIOR TO THE PRETENSIONING
OPERATION.
3. FASTENER COMPONENT NOT TURNED BY THE WRENCH PREVENTED FROM
ROTATING.
4. FASTENERS ARE PRETENSIONED IN ACCORDANCE WITH THE RCSC SPECIFICATION,
PROGRESSING SYSTEMATICALLY FROM THE MOST RIGID POINT TOWARD THE FREE
EDGES (REQUIRED ONLY FOR PRETENSIONED OR SLIP-CRITICAL JOINTS)
X
X
X
X
REQUIRED SPECIAL INSPECTIONS AFTER BOLTING OF STRUCTURAL STEEL (AISC 360 N5.6)
SPECIAL INSPECTION TASK
1. DOCUMENT ACCEPTANCE OR REJECTION OF BOLTED CONNECTIONS X -
OTHER REQUIRED SPECIAL INSPECTIONS OF STRUCTURAL STEEL (AISC 360 N5.7 AND N5.8)
SPECIAL INSPECTION TASK
1. VISUALLY INSPECT EXPOSED CUT SURFACES OF GALVANIZED STRUCTURAL STEEL MAIN MEMBERS AND EXPOSED CORNERS OF
RECTANGULAR HSS FOR CRACKS SUBSEQUENT TO GALVANIZING.
2. DURING PLACEMENT OF ANCHOR RODS AND OTHER EMBEDMENTS SUPPORTING STRUCTURAL STEEL, VERIFY AND DOCUMENT THE
DIAMETER, GRADE, TYPE AND LENGTH OF THE ANCHOR ROD OR EMBEDDED ITEM, AND THE EXTENT OR DEPTH OF EMBEDMENT INTO
THE CONCRETE PRIOR TO PLACEMENT OF CONCRETE.
3. INSPECT THE FABRICATED STEEL OR ERECTED STEEL FRAME, AS APPLICABLE, TO VERIFY COMPLIANCE WITH THE DETAILS SHOWN ON
THE CONSTRUCTION DOCUMENTS. THIS INCLUDES SUCH ITEMS AS BRACES, STIFFENERS, MEMBER LOCATIONS, AND THE CORRECT
APPLICATION OF JOINT DETAILS AT EACH CONNECTION.
REQUIRED NONDESTRUCTIVE TESTING OF WELDED JOINTS IN STRUCTURAL STEEL (AISC 360 N5.5)
TESTING TASK
1. ULTRASONIC TESTING OF COMPLETE-JOINT-PENETRATION (CJP) GROOVE WELDS SUBJECT TO TRANSVERSELY APPLIED TENSION
LOADING IN BUTT, T- AND CORNER JOINTS, IN MATERIAL 5/16" THICK OR GREATER
A. ULTRASONIC TESTING SHALL BE PERFORMED ON 10% OF SUCH WELDS IN STRUCTURES IN RISK CATEGORY II
B. ULTRASONIC TESTING SHALL BE PERFORMED ON 100% OF SUCH WELDS IN STRUCTURES IN RISK CATEGORY III OR IV
C. REFER TO AISC 360 SECTION N5.5 FOR CONDITIONS WHERE THE RATE OF ULTRASONIC TESTING IS PERMITTED TO BE REDUCED
D. REFER TO AISC 360 SECTION N5.5 FOR CONDITIONS WHERE THE RATE OF ULTRASONIC TESTING IS REQUIRED TO BE INCREASED
PERFORM OBSERVE
PERFORM OBSERVE
PERFORM OBSERVE
REQUIRED SPECIAL INSPECTIONS OF OPEN WEB STEEL JOISTS (MBC SECTION 1705.2.3)
SPECIAL INSPECTION TASK
CONTINUOUS SPECIAL
INSPECTION
PERIODIC SPECIAL
INSPECTION
1. INSPECT JOIST AND JOIST GIRDER END CONNECTIONS - WELDED OR BOLTED
2. INSPECT INSTALLATION OF JOIST BRIDGING
X
X
REQUIRED SPECIAL INSPECTIONS PRIOR TO STEEL DECK PLACEMENT (SDI QA/QC)
SPECIAL INSPECTION TASK PERFORM OBSERVE
1. VERIFY COMPLIANCE OF MATERIALS (DECK AND ALL DECK ACCESSORIES) WITH
CONSTRUCTION DOCUMENTS, INCLUDING PROFILES, MATERIAL PROPERTIES, AND
BASE METAL THICKNESS
2. DOCUMENT ACCEPTANCE OR REJECTION OF DECK AND DECK ACCESSORIES
X
X
REQUIRED SPECIAL INSPECTIONS AFTER STEEL DECK PLACEMENT (SDI QA/QC)
SPECIAL INSPECTION TASK PERFORM OBSERVE
1. VERIFY COMPLIANCE OF DECK AND ALL DECK ACCESSORIES INSTALLATION WITH
CONSTRUCTION DOCUMENTS
2. VERIFY DECK MATERIALS ARE REPRESENTED BY THE MILL CERTIFICATIONS THAT
COMPLY WITH THE CONSTRUCTION DOCUMENTS
3. DOCUMENT ACCEPTANCE OR REJECTION OF INSTALLATION OF DECK AND DECK
ACCESSORIES
X
X
X
REQUIRED SPECIAL INSPECTIONS PRIOR TO WELDING OF STEEL DECK (SDI QA/QC)
SPECIAL INSPECTION TASK PERFORM OBSERVE
1. WELDING PROCEDURE SPECIFICATIONS (WPS) AVAILABLE
2. MANUFACTURER CERTIFICATIONS FOR WELDING CONSUMABLES AVAILABLE
3. MATERIAL IDENTIFICATION (TYPE/GRADE)
4. CHECK WELDING EQUIPMENT
X
X
X
X
REQUIRED SPECIAL INSPECTIONS DURING WELDING OF STEEL DECK (SDI QA/QC)
SPECIAL INSPECTION TASK PERFORM OBSERVE
1. USE OF QUALIFIED WELDERS
2. CONTROL AND HANDLING OF WELDING CONSUMABLES
3. ENVIRONMENTAL CONDITIONS (WIND SPEED, MOISTURE, TEMPERATURE)
4. WPS FOLLOWED
X
X
X
X
REQUIRED SPECIAL INSPECTIONS AFTER WELDING OF STEEL DECK (SDI QA/QC)
SPECIAL INSPECTION TASK PERFORM OBSERVE
1. VERIFY SIZE AND LOCATION OF WELDS, INCLUDING SUPPORT, SIDELAP, AND
PERIMETER WELDS
2. WELDS MEET VISUAL ACCEPTANCE CRITERIA
3. VERIFY REPAIR ACTIVITIES
4. DOCUMENT ACCEPTANCE OR REJECTION OF WELDS
X
X
X
X
REQUIRED SPECIAL INSPECTIONS PRIOR TO MECHANICAL FASTENING OF STEEL DECK (SDI QA/QC)
SPECIAL INSPECTION TASK PERFORM OBSERVE
1. MANUFACTURER INSTALLATION INSTRUCTIONS AVAILABLE FOR MECHANICAL
FASTENERS
2. PROPER TOOLS AVAILABLE FOR FASTENER INSTALLATION
3. PROPER STORAGE FOR MECHANICAL FASTENERS
X
X
X
REQUIRED SPECIAL INSPECTIONS DURING MECHANICAL FASTENING OF STEEL DECK (SDI QA/QC)
SPECIAL INSPECTION TASK PERFORM OBSERVE
1. FASTENERS ARE POSITIONED AS REQUIRED
2. FASTENERS ARE INSTALLED IN ACCORDANCE WITH MANUFACTURER'S
INSTRUCTIONS
X
X
REQUIRED SPECIAL INSPECTIONS AFTER MECHANICAL FASTENING OF STEEL DECK (SDI QA/QC)
SPECIAL INSPECTION TASK PERFORM OBSERVE
1. CHECK SPACING, TYPE, AND INSTALLATION OF SUPPORT FASTENERS
2. CHECK SPACING, TYPE, AND INSTALLATION OF SIDELAP FASTENERS
3. CHECK SPACING, TYPE, AND INSTALLATION OF PERIMETER FASTENERS
4. VERIFY REPAIR ACTIVITIES
5. DOCUMENT ACCEPTANCE OR REJECTION OF MECHANICAL FASTENERS
X
X
X
X
X
GENERAL NOTES REGARDING SPECIAL INSPECTIONS AND TESTS
1. SPECIAL INSPECTIONS ARE IN ADDITION TO INSPECTIONS BY THE BUILDING OFFICIAL THAT ARE IDENTIFIED IN SECTION 110 OF THE
MICHIGAN BUILDING CODE. SPECIAL INSPECTIONS DO NOT RELIEVE THE CONTRACTOR FROM COMPLYING WITH THE CONTRACT
DOCUMENTS.
2. CONTINUOUS SPECIAL INSPECTION IS DEFINED AS SPECIAL INSPECTION BY THE SPECIAL INSPECTOR WHO IS PRESENT
CONTINUOUSLY WHEN AND WHERE THE WORK TO BE INSPECTED IS BEING PERFORMED.
3. PERIODIC SPECIAL INSPECTION IS DEFINED AS SPECIAL INSPECTION BY THE SPECIAL INSPECTOR WHO IS INTERMITTENTLY PRESENT
WHERE THE WORK TO BE INSPECTED HAS BEEN OR IS BEING PERFORMED. THE FREQUENCY OF THESE SPECIAL INSPECTION TASKS
SHALL BE ADEQUATE TO DETERMINE THAT WORK HAS BEEN PERFORMED IN ACCORDANCE WITH THE APPROVED CONSTRUCTION
DOCUMENTS.
4. WHERE A SPECIAL INSPECTION TASK IS NOTED AS "OBSERVE," THE SPECIAL INSPECTOR SHALL OBSERVE THESE ITEMS ON A RANDOM
BASIS. OPERATIONS NEED NOT BE DELAYED PENDING THESE INSPECTIONS. THE FREQUENCY OF THESE SPECIAL INSPECTION TASKS
SHALL BE ADEQUATE TO DETERMINE THAT THE WORK HAS BEEN PERFORMED IN ACCORDANCE WITH THE APPROVED CONSTRUCTION
DOCUMENTS.
5. WHERE A SPECIAL INSPECTION TASK IS NOTED AS "PERFORM," THE TASK SHALL BE PERFORMED FOR EACH MEMBER, JOINT, OR
ELEMENT PRIOR TO FINAL ACCEPTANCE.
6. THE SPECIAL INSPECTOR SHALL BE A QUALIFIED PERSON EMPLOYED OR RETAINED BY AN APPROVED AGENCY AND APPROVED BY THE
BUILDING OFFICIAL AS HAVING THE COMPETENCE NECESSARY TO INSPECT A PARTICULAR TYPE OF CONSTRUCTION REQUIRING
SPECIAL INSPECTION.
7. PRIOR TO THE START OF CONSTRUCTION, THE APPROVED SPECIAL INSPECTION AGENCY SHALL SUBMIT WRITTEN DOCUMENTATION
TO THE BUILDING OFFICIAL DEMONSTRATING THE COMPETENCE AND RELEVANT EXPERIENCE OR TRAINING OF THE SPECIAL
INSPECTORS WHO WILL PERFORM THE SPECIAL INSPECTIONS AND TESTS DURING CONSTRUCTION.
8. THE CONSTRUCTION OR WORK FOR WHICH SPECIAL INSPECTION OR TESTING IS REQUIRED SHALL REMAIN ACCESSIBLE AND EXPOSED
FOR SPECIAL INSPECTION OR TESTING PURPOSES UNTIL COMPLETION OF REQUIRED SPECIAL INSPECTIONS OR TESTS. SEE
SPECIFICATION FOR ADDITIONAL REQUIREMENTS, INCLUDING CONTRACTOR'S RESPONSIBILITY TO PROVIDE ACCESS FOR SPECIAL
INSPECTIONS AND CONTRACTOR'S RESPONSIBILITY TO PROVIDE DUE NOTICE TO SPECIAL INSPECTOR PRIOR TO THE TIME THAT
SPECIAL INSPECTION IS REQUIRED.
9. SPECIAL INSPECTION AGENCY SHALL KEEP RECORDS OF SPECIAL INSPECTIONS AND TESTS AND SHALL SUBMIT REPORTS OF SPECIAL
INSPECTIONS AND TESTS TO THE BUILDING OFFICIAL AND TO THE ENGINEER. REPORTS SHALL INDICATE THAT WORK INSPECTED OR
TESTED WAS OR WAS NOT COMPLETED IN CONFORMANCE TO APPROVED CONSTRUCTION DOCUMENTS. DISCREPANCIES SHALL BE
BROUGHT TO THE IMMEDIATE ATTENTION OF THE CONTRACTOR FOR CORRECTION. IF THEY ARE NOT CORRECTED, THE
DISCREPANCIES SHALL BE BROUGHT TO THE ATTENTION OF THE BUILDING OFFICIAL AND TO THE ENGINEER PRIOR TO THE
COMPLETION OF THAT PHASE OF THE WORK. A FINAL REPORT DOCUMENTING REQUIRED SPECIAL INSPECTIONS AND TESTS, AND
CORRECTION OF ANY DISCREPANCIES NOTED IN THE INSPECTIONS AND TESTS, SHALL BE SUBMITTED TO THE BUILDING OFFICIAL.
10. WHERE SPECIAL INSPECTION OF STRUCTURAL MEMBERS OR ASSEMBLIES IS BEING CONDUCTED ON THE PREMISES OF A
FABRICATOR'S SHOP, SPECIAL INSPECTION OF THE FABRICATED ITEMS SHALL BE PERFORMED DURING FABRICATION.
11. SPECIAL INSPECTIONS DURING FABRICATION ARE NOT REQUIRED WHERE THE WORK IS DONE ON THE PREMISES OF A FABRICATOR
REGISTERED AND APPROVED BY THE BUILDING OFFICIAL TO PERFORM SUCH WORK WITHOUT SPECIAL INSPECTION. UPON THE
COMPLETION OF FABRICATION, THE APPROVED FABRICATOR SHALL SUBMIT A CERTIFICATE OF COMPLIANCE TO THE OWNER OR THE
OWNER'S AUTHORIZED AGENT FOR SUBMITTAL TO THE BUILDING OFFICIAL STATING THAT THE WORK WAS PERFORMED IN
COMPLIANCE WITH THE APPROVED CONSTRUCTION DOCUMENTS.
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R D
A T
E
F
IL
E N
U M
B E
R
/2
.C A
K
A
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
T U E B O R
U S
Q U
E R
C I
UP
IS
R
C
S N I
E N
M
I S
K A B
E
R U
P L
S B U
I
A N
E O
E
I
M L A P
A M
C
M
M U
U N
P R E L
IM
IN
A R Y
C O N S T R U C T
IO
N
F
IN
A L
R E C O R D
D A T E
IS
S U E D
F O R
IN
D E X
C O D E
P R O J E C T
ID
E N T
IF
IC
A T
IO
N
N O
S H E E T
D E S
IG
N E D
D R A W N
C H E C K E D
A P P R O V E D
S T
A T
E O
F M
IC
H
IG
A
N D
E P
A R
T M
E N
T O
F M
IL
IT
A R
Y A
N D
V E
T E
R A
N S
A F
F A
IR
S
C
O N
S T
R U
C T
IO
N
A N
D F
A C
IL
IT
N
A G
E M
E N
T O
F F
IC
E
N
M
A R
T
IN
L U
T H
E R
K
IN
G J
R B
L V
D L A
N S
IN
G
M
IC
H
IG
A
N
-2
A T
E O
F M
IC
H
IG
A
N
D E P A R T M E N T
O F
T E C H N O L O G Y M A N A G E M E N T
A N D
B U D G E T
F A C
IL
IT
IE
S
A N D
B U S
IN
E S S
S E R V
IC
E S
A D M
IN
IS
T R A T
IO
N
A D A M
L A C H R A D
IR
E C T O R
S P
E C
IA
L
I N
S P
E C
T
IO
N S
S
D E
C E
M B
E R
D E
C E
M B
E R
J N
J N
R E
R C
-5
.0
R E
N O
V A
T E
A R
M O
R Y
B
IG
R
A P
ID
S
B ig
R a p id s, M ic h ig a
SEE PLAN
TOP OF SLAB
SEE ARCHITECTURAL
DRAWINGS FOR SIZE AND
LOCATION OF NON-BEARING
WALLS
WWF
C
LR2W
W
(2) #5 BOTTOM
CONTINUOUS
SLAB ON GRADE,
SEE PLAN
CONCRETE SLAB
ON GRADE
WWF, SEE PLANS VAPOR BARRIER,
SEE SPECIFICATIONS
DRAINAGE COURSE
(FREE DRAINING
POROUS FILL)
COMPACTED
SUBGRADE
NOTES:
1. SUBGRADE SHALL BE PREPARED PER THE GEOTECHNICAL REPORT PRIOR TO SLAB PLACEMENT.
UNSUITABLE SUBGRADE SHALL BE REMOVED AND REPLACED WITH AN ENGINEERED FILL OR
ADEQUATE BORROW MATERIAL AND COMPACTED PER THE EARTHWORK SPECIFICATIONS AND
GEOTECHNICAL REPORT RECOMMENDATIONS.
2. SEE GEOTECHNICAL REPORT FOR ADDITIONAL SUBGRADE PREPARATION REQUIREMENTS.
3. SLAB SHALL BE PLACED A MINIMUM OF 90 DAYS PRIOR TO INSTALLATION OF FLOOR FINISHES.
4. WET CURE ALL SLABS ON GRADE, REFER TO SPECIFICATIONS.
/3
T
S E E P
LA
N
T
SEE PLANS
TOP OF SLAB
D E P
TH
FT
G
TY
P
M
A X
TYP
STD HK
4' - 0" MIN UNO
C
LR
2" CLR
DEPTH TYP
FTG
3" CLR
"C
LR
SEE PLAN FOR FOOTING
SIZE & REINFORCING
INDICATES FOOTING STEP
LOCATION ON PLAN
NEW CONCRETE SLAB ON GRADE 5/8" DIA GREASED SMOOTH BAR
X 1'-6" LONG @ 24" OC. DRILL
AND GROUT TO EXISTING SLAB W/
8" MIN EMBED
INSTALL VAPOR
BARRIER PER
SPECIFICATIONS
RECOMPACT EXISTING
FILL PRIOR TO
INSTALLATION OF NEW
SLAB ON GRADE INFILL
SEE PLAN
TOP OF SLAB
TY
P (3
S
ID
E S
M
IN
3" PREFABRICATED VOID
FORM BENEATH SLAB
8"
COORDINATE WITH CIVIL & LANDSCAPE DRAWINGS
PLAN
SEE
FOUNDATION WALL AND
FOOTING REINFORCEMENT
OMITTED FOR CLARITYCOMPACTED
SUBGRADE
#4@12" EACH WAY,
TYP. THREE SIDES
ISOLATION JOINT
#4 BENT BARS
@12" OC
SLOPE
#4@12" EACH WAY
C L R
/2
NOTE: PLACE APRON AT ALL EXTERIOR
DOOR LOCATIONS. SEE ARCH
DRAWINGS FOR DOOR LOCATIONS.
ISOLATION JOINT WITH BONDBREAKER
ALONG WALL, TYP
COLUMN, SEE PLAN
CONTROL JOINT MAX SPAN
SHALL CONFORM WITH
SPECIFICATIONS
ISOLATION JOINT WITH
BONDBREAKER AROUND
DIAMOND, TYP
CAST DIAMOND AFTER
SLAB ON GRADE HAS BEEN
CAST SHALL CONFORM
WITH SPECIFICATIONS
1 LAYER OF REINFORCING
PROVIDE ADDITIONAL
VERTICAL BAR AT CORNER
CORNER BARS TO MATCH
SIZE AND SPACING OF WALL
HORIZONTAL REINFORCING
REINFORCING IN CENTER
OF WALL, U.N.O.
CONSTRUCTION JOINT
DOWEL TO MATCH
SIZE & SPACING OF
WALL HORIZONTAL
REINFORCING
S
TD
H K
LA
P
LAP
LAP
2 LAYERS OF REINFORCING
CONSTRUCTION JOINT
DOWEL TO MATCH SIZE &
SPACING OF WALL
HORIZONTAL REINFORCING
S
TD
H K
LAP
LAP
LA
P
TY
P
C
LE
A R C
O V E R
,PROVIDE ADDITIONAL
VERTICAL BAR AT CORNER
CORNER BARS TO MATCH
SIZE AND SPACING OF WALL
HORIZONTAL REINFORCING
BOND BEAM WITH (2)#4 CONTINUOUS
AT FIRST FULL COURSE BELOW JOIST
BEARING. GROUT SOLID ANY PARTIAL
COURSES BETWEEN BOND BEAM AND
JOIST BEARING.
BEARING PLATE 3/8"x7"x9" WITH (2)1/2"x5"
HEADED STUDS (5" GAUGE)
1/2" MAX
6" MIN
1/8 2-1/2
1/8 2-1/2
TOP OF JOIST
EL. SEE PLAN
SEE PLAN FOR JOIST SPACING
1/4" PLATE WELDED TO
BEAM FOR CONNECTION
OF BRIDGING
DIAGONAL BRIDGING SIZE &
SPACING SHALL CONFORM
WITH SJI SPECIFICATIONS
U.N.O.
BEAM
WELD PER NOTE 'A' - TYPICAL
JOIST
SEE PLAN FOR JOIST SPACING
NOTE 'A': ALL WELDING TO STEEL JOIST SHALL BE DONE SO AS
NOT TO IMPAIR THE STRENGTH OF THE JOIST
CONTINUOUS L4x4x1/4" TOP WITH 3/4"Ø
EXPANSION BOLTS AT 4'-0" O.C. (WHERE
SHOWN ON PLAN ONLY)
STEEL DECK
HORIZONTAL
BRIDGING
100% SOLID BLOCK
OR GROUT FILLED AT
ALL EXPANSION BOLT
LOCATIONS TYP
L4x4x1/4" WITH (2) 1/2"Ø EXPANSION
BOLTS AT EACH BRIDGING LINE (100%
SOLID BLOCK OR GROUT FILLED
AT EXPANSION BOLTS)
CONTINUOUS L4x4x1/4", BOTTOM WITH
3/4"Ø EXPANSION BOLTS AT 4'-0" O.C.
(WHERE SHOWN ON PLAN ONLY)
TYP
CONCENTRATED
LOAD
CONCENTRATED
LOAD
JOIST DEPTH ANGLE SIZE
8" TO 24" L1 1/2x1 1/2x3/16
26" TO 48" L2x2x3/16
52" TO 72" L2 1/2x2 1/2x1/4
TYP
WHERE CONCENTRATED LOAD DOES NOT OCCUR
AT A JOIST PANEL POINT, ADD (2) ANGLES IN THE
FIELD FROM THE CONCENTRATED LOAD LOCATION
TO THE NEAREST PANEL POINT ON THE OPPOSITE
CHORD (1 ANGLE EACH SIDE OF JOIST CHORDS).
REQUIRED ANGLE SIZES ARE AS FOLLOWS:
IN ADDITION TO CONCENTRATED LOADS NOTED ON FRAMING
PLANS, VERIFY LOCATION AND QUANTITY OF OTHER
CONCENTRATED LOADS WITH ARCHITECTURAL, MECHANICAL,
PLUMBING, AND ELECTRICAL DRAWINGS.
FIELD INSTALLED ANGLES ARE NOT REQUIRED WHERE THE
SUM OF THE CONCENTRATED LOADS WITHIN A CHORD PANEL
DOES NOT EXCEED 100 LBS AND THE ATTACHMENTS ARE
CONCENTRIC TO THE CHORD.
JOIST OR BEAM, TYPICAL
MC6x12 LOCATED BENEATH RTU CURB
OUTLINE OF RTU AND CURB
SEE ROOF OPENING FRAME DETAIL
RTU CURB
MC6x12 NESTED IN DECK RIBS. SPAN TO NEXT
JOIST BEYOND END OF RTU (MINIMUM 2 SPANS).
IF SPLICING IS REQUIRED, SPLICE ONLY OVER THE
CENTERLINE OF A SUPPORTING JOIST/BEAM.
WELD TO JOIST/BEAM THROUGH DECK.
ADD ANGLES IN FIELD PER TYPICAL DETAIL IF
RTU LOAD IS NOT APPLIED AT A TOP CHORD
PANEL POINT.
3/16
TYP AT
EA. JOIST
3/16
ROOF OPENING FRAME, SEE TYPICAL DETAIL
A A
PLAN VIEW
SECTION A-A
1. SEE ARCHITECTURAL FOR BLOCKING AND FLASHING REQUIREMENTS AT RTU
CURB.
2. COORDINATE MC6x12 LOCATIONS WITH MECHANICAL CONTRACTOR.
3. COORDINATE SIZE AND LOCATION OF ROOF OPENING FRAMES WITH
MECHANICAL CONTRACTOR. OPENING QUANTITY, SIZES, AND LOCATIONS
SHOWN IN THIS DETAIL ARE NOT REPRESENTATIVE OF ACTUAL OPENINGS
REQUIRED.
4. IN THE CASE THAT THE RTU IS ORIENTED WITH THE LONG DIMENSION
PARALLEL TO JOISTS/BEAMS, PROVIDE MC6x12 BENEATH EACH END OF THE
RTU AND @4'-0" MAX SPACING BETWEEN ENDS (COORDINATE PLACEMENT
WITH OPENING LOCATIONS). MC6x12 SHALL SPAN TO NEXT JOIST BEYOND
SIDES OF RTU.
5. WHERE RTU CURB LOCATION RELATIVE TO ROOF DECK RIBS IS SUCH THAT A
SINGLE MC6x12 NESTED IN THE DECK RIBS DOES NOT FULLY SUPPORT THE
RTU CURB OR DOES NOT PROVIDE AN ADEQUATE SURFACE FOR CONNECTION
OF THE RTU CURB, PROVIDE DOUBLE MC6x12 AT NO ADDITIONAL COST.
COORDINATE WITH MECHANICAL CONTRACTOR.
6. MECHANICAL CONTRACTOR SHALL BE RESPONSIBLE FOR CONNECTIONS OF
ROOFTOP EQUIPMENT TO CURBS AND CURBS TO THE SUPPORTING
STRUCTURE. DESIGN OF CONNECTIONS SHALL CONSIDER ALL APPLICABLE
LOADS IN ACCORDANCE WITH THE BUILDING CODE, INCLUDING WIND AND
SEISMIC LOADS.
NOTES:
SCALE: NONE
TYPICAL NON-BEARING WALL FOOTING
SCALE: NONE
TYPICAL SOG CONSTRUCTION
SCALE: NONE
TYPICAL FOOTING STEP
SCALE: NONE
TYPICAL SLAB ON GRADE INFILL DETAIL
SCALE: NONE
TYPICAL FROST-FREE DOOR APRON DETAIL
SCALE: NONE
TYPICAL SOG JOINT PATTERN
SCALE: NONE
TYPICAL CONCRETE WALL CORNER DETAILS
SCALE: NONE
LH- JOIST BEARING ON CMU
SCALE: NONE
TYPICAL JOIST BRDG-LH SERIES
SCALE: NONE
TYPICAL BRIDGING ANCHORAGE
SCALE: NONE
TYPICAL JOIST MODIFICATION AT CONCENTRATED LOADS
SCALE: NONE
TYPICAL RTU SUPPORT
T O
W E
R P
IN
K
S T
E R
.C O
M
A L L R
IG
H
T S
R E
S E
R V
E D
S H
E E
T T
IT
L
E
S H
E E
T N
U M
B E
R D
A T
E
F
IL
E N
U M
B E
R
/2
.C A
K
A
D E
S
IG
N A
N D
C O
N S
T R
U C
T
IO
N D
IV
IS
IO
N
T U E B O R
U S
Q U
E R
C I
UP
IS
R
C
S N I
E N
M
I S
K A B
E
R U
P L
S B U
I
A N
E O
E
I
M L A P
A M
C
M
M U
U N
P R E L
IM
IN
A R Y
C O N S T R U C T
IO
N
F
IN
A L
R E C O R D
D A T E
IS
S U E D
F O R
IN
D E X
C O D E
P R O J E C T
ID
E N T
IF
IC
A T
IO
N
N O
S H E E T
D E S
IG
N E D
D R A W N
C H E C K E D
A P P R O V E D
S T
A T
E O
F M
IC
H
IG
A
N D
E P
A R
T M
E N
T O
F M
IL
IT
A R
Y A
N D
V E
T E
R A
N S
A F
F A
IR
S
C
O N
S T
R U
C T
IO
N
A N
D F
A C
IL
IT
N
A G
E M
E N
T O
F F
IC
E
N
M
A R
T
IN
L U
T H
E R
K
IN
G J
R B
L V
D L A
N S
IN
G
M
IC
H
IG
A
N
-2
A T
E O
F M
IC
H
IG
A
N
D E P A R T M E N T
O F
T E C H N O L O G Y M A N A G E M E N T
A N D
B U D G E T
F A C
IL
IT
IE
S
A N D
B U S
IN
E S S
S E R V
IC
E S
A D M
IN
IS
T R A T
IO
N
A D A M
L A C H R A D
IR
E C T O R
T Y
P
IC
A L D
E T
A
IL
S
S
D E
C E
M B
E R
D E
C E
M B
E R
J N
J N
R E
R C
-5
.0
R E
N O
V A
T E
A R
M O
R Y
B
IG
R
A P
ID
S
B ig
R a p id s, M ic h ig a
END OF WALL, CORNER, OR CONTROL JOINT
LOCATE JOINT REINFORCEMENT IN FIRST
MORTAR JOINT BELOW OPENING AND
EXTEND THE ENTIRE LENGTH OF THE WALL
PANEL
LINTEL REINFORCING, SEE LINTEL SCHEDULE
1'-0" MIN. TYP
A
WHERE DISTANCE 'A' IS LESS THAN OR
EQUAL TO 1'-4", PROVIDE JOINT
REINFORCING IN EVERY BED JOINT IN
THE HEIGHT OF THE OPENING
NOTES:
1. VERTICAL REINFORCING BARS SHALL BE LOCATED AS FOLLOWS:
A. AT WALL CORNERS
B. WITHIN 6" OF THE ENDS OF A WALL
C. WITHIN 6" OF EACH SIDE OF A CONTROL JOINT
D. AT JAMBS OF OPENINGS AS SHOWN, WITHIN 6" OF EACH SIDE OF ALL OPENINGS GREATER THAN 16" WIDE, AND
E. AT SPACING NOT TO EXCEED MAXIMUM SPACING IN CMU WALL SCHEDULE.
2. SEE CMU WALL SCHEDULE FOR VERTICAL REINFORCING BAR SIZE.
3. VERTICAL REINFORCING BARS SHALL BE CENTERED IN CMU WALL THICKNESS, UNLESS NOTED OTHERWISE.
4. EXTEND ALL VERTICAL REINFORCING THE FULL HEIGHT OF THE WALL OR UNTIL REACHING AN OPENING, THEN CONTINUE SAME VERTICAL REINFORCING ABOVE THE OPENING.
5. JOINT REINFORCEMENT SHALL CONSIST OF LADDER-TYPE 9 GAGE JOINT REINFORCING @1'-4" UNLESS NOTED OTHERWISE.
6. REFER TO DETAILS AND SECTIONS FOR REQUIRED LOCATIONS OF CONTINUOUS HORIZONTAL REINFORCING BARS, SUCH AS AT BOND BEAMS. HORIZONTAL REINFORCING BARS, IF ANY, SHALL BE IN ADDITION TO THE
JOINT REINFORCING NOTED HERE. CONTINUOUS HORIZONTAL REINFORCING BARS SHALL BE LAP SPLICED WITH CORNER BARS OF THE SAME SIZE AND QUANTITY AS THE HORIZONTAL BARS.
7. GROUT CMU CELLS AS FOLLOWS:
A. ALL CELLS CONTAINING REINFORCING BARS
B. BELOW LINTEL BEARING, DOWN TO FOUNDATION
C. WHERE REQUIRED FOR…