506-25-104 Ann Arbor Emergent Garage Repair Revised Drawings R3.pdf
PDF 13 MB Posted
- Solicitation number
- 36C25026B0038
About this file
This document is a set of 100% Construction Documents for the Emergent Parking Structure Repairs project at the Veterans Affairs Ann Arbor Healthcare System, located at 2215 Fuller Road, Ann Arbor, Michigan 48105. The project number is 506-25-104 and the documents were prepared by Guidon Design Inc. as the Architect/Engineer of Record, with an issue date of March 25, 2026. The project involves comprehensive repairs to two parking structures (East and West garages) across multiple levels (AA through E for the East garage and A through E for the West garage).
The scope of work includes concrete delamination repairs, crack sealing, expansion joint replacement, polyurethane traffic coating application, floor drain installation and replacement, and waterproofing solutions to eliminate water pooling on Level D of the East garage. Construction is organized into phased work with a maximum of 30 parking spaces closed at any given time during business hours to maintain facility operations. The project mandates that elevator lobbies, stairs, and drive aisles remain open throughout construction. Work is anticipated to occur on a single floor per building at a time, proceeding from top deck downward. The contractor is responsible for providing a detailed phasing schedule with minimum two-week notice to the VA Contracting Officer Representative (COR) for parking outage coordination. Construction documents include architectural plans, structural repair details, plumbing plans showing floor drain locations, and specifications for cast-in-place concrete repairs with minimum compressive strengths of 4,500-5,000 PSI depending on application. The project is classified as a non-sprinklered, S-2 low-hazard storage facility with Type I-B construction.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C25026B0038 0004.docx | DOCX document | |
| 36C25026B0038 0003.docx | DOCX document | |
| 36C25026B0038 0002.docx | DOCX document | |
| S04 Pre-Bid Site Visit Agenda - 506-25-104 and Sign-in Sheet.pdf | ||
| 36C25026B0038 0001.docx | DOCX document | |
| Contractor EMR Certification Form - 506-25-104.docx | DOCX document | |
| Wage Determination MI20260100 1.02.2026.pdf | ||
| ATTACHMENT VAAR 852.219-75 DEVIATION Jan 2023 LIMITATIONS OF SUBCONTRACTING COMPLIANCE CERTIFICATION.docx | DOCX document | |
| 36C25026B0038_1.docx | DOCX document | |
| RFI Form - 506-25-104.doc | DOC document | |
| 506-25-104 Ann Arbor Emergent Garage Repair Revised Bid Specifications R3.pdf |
Show all 11
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
A u to d e s k D o c s /2
.1
V A
A n n A rb o r
E m e rg e n t
P a rk in g R e p a ir s /2
.1
A v
.r v t
/2
/2
:4
:4
P
M
GI000
COVER SHEET
GUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
317.800.6388
EMERGENT PARKING
STRUCTURE REPAIRS
2215 FULLER RD. ANN ARBOR, MI 48105
506-25-104
03/25/2026 DB CS
506-25-104
EMERGENT PARKING STRUCTURE REPAIRS
VETERANS AFFAIRS ANN ARBOR HEALTHCARE SYSTEM
2215 FULLER RD. ANN ARBOR, MI 48105
100% CONSTRUCTION DOCUMENTS
100% CONSTRUCTION
DOCUMENTS
NON-SPRINKLER
SHEET INDEX
SHEET NUMBER SHEET NAME
GENERAL
GI000 COVER SHEET
GI001 INFECTION CONTROL
GI002 PRELIMINARY PHASING PLAN
GI003 PRELIMINARY PHASING PLAN
GI101 LIFE SAFETY CODE DATA
CG101 EAST GARAGE ARCHITECTURAL SITE PLAN
STRUCTURAL
SI001 ABBREVIATIONS, SCHEDULES, & SYMBOLS
SI002 STRUCTURAL GENERAL NOTES
SF101 EAST LEVEL AA FRAMING PLAN
SF102 EAST LEVEL A FRAMING PLAN
SF103 EAST LEVEL B FRAMING PLAN
SF104 EAST LEVEL C FRAMING PLAN
SF105 EAST LEVEL D FRAMING PLAN
SF201 WEST LEVEL A FRAMING PLAN
SF202 WEST LEVEL B FRAMING PLAN
SF203 WEST LEVEL C FRAMING PLAN
SF204 WEST LEVEL D FRAMING PLAN
SF501 REPAIR DETAILS
ARCHITECTURAL
AE001 ARCHITECTURAL SYMBOLS AND ABBREVIATIONS
AD101 EAST GARAGE - DEMO PLANS
AE101 EAST GARAGE - LEVEL AA
AE102 EAST GARAGE - LEVEL A
AE103 EAST GARAGE - LEVEL B
AE104 EAST GARAGE - LEVEL C
AE105 EAST GARAGE - LEVEL D
AE106 WEST GARAGE ENLARGED PLANS
AE107 WEST GARAGE - LEVEL E
AE501 ARCHITECTURAL AND PARKING STRIPING DETAILS
PLUMBING
P000 PLUMBING SYMBOLS, ABBREVIATIONS, AND NOTES
P101 PLUMBING PLAN - EAST GARAGE LEVEL AA
P102 PLUMBING PLAN - EAST GARAGE LEVEL A
P103 PLUMBING PLAN - EAST GARAGE LEVEL B
P104 PLUMBING PLAN - EAST GARAGE LEVEL C
P105 PLUMBING PLAN - EAST GARAGE LEVEL D
P106 PLUMBING PLAN - WEST GARAGE LEVEL A
Contact:Contact:Contact: Contact:
GUIDON DESIGN INC.
Daniel Willeman
Plumbing Designer
MECHANICAL,
ELECTRICAL &
PLUMBING
GUIDON DESIGN INC.
Mukesh Poddar
Structural EIT
STRUCTURAL
ENGINEER
VA ANN ARBOR HEALTHCARE
SYSTEM
Terry Clark
Contracting Officer Representative
2215 Fuller Rd.
Ann Arbor, MI 48105 p: 734-972-2345 e: terry.clack@va.gov
OWNER
GUIDON DESIGN INC.
Christian Schmoll
Architectural Designer
1221 North Pennsylvania Street Indianapolis, IN 46202 p: 317.627.0450 e: cschmoll@guidon.com
ARCHITECT
1221 North Pennsylvania Street Indianapolis, IN 46202 p: 419.245.4418 e: mpoddar@guidon.com
1221 North Pennsylvania Street Indianapolis, IN 46202 p: 317.800.6388 x 144 e: dwilleman@guidon.com
Contact:
GUIDON DESIGN INC.
Andrew Kennedy
Project Manager
1221 North Pennsylvania Street Indianapolis, IN 46202 p: 317.800.6388 x 121 e: akennedy@guidon.com
PROJECT MANAGER
AREA MAP
CAMPUS MAP
N
N
EAST PARKING
GARAGE
WEST PARKING
GARAGE
FULLER RD
FULLER CT
VA MEDICAL CIR
HURON RIVER
FULLER CT
FULLER RD
PROJECT LOCATION:
EAST PARKING
GARAGE
HURON RIVER
FULLER RD
H U
R O
N P
K W
Y
PROJECT SITE
PROJECT LOCATION:
WEST PARKING
GARAGE
REVISION SCHEDULE
NUMBER DATE DESCRIPTION
I (green)
I (green)
I (green)
II (yellow)
II (yellow)
II (yellow)
II (yellow)
II (yellow)
III/IV (pink)
III/IV (pink)
III/IV (pink)
III/IV (pink)
III/IV (pink)
IV (red)
IV (red)
IV (red)
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
A u to d e s k D o c s /2
.1
V A
A n n A rb o r
E m e rg e n t
P a rk in g R e p a ir s /2
.1
A v
.r v t
/2
/2
:4
:5
P
M
GI001
INFECTION CONTROL
GUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
317.800.6388
EMERGENT PARKING
STRUCTURE REPAIRS
2215 FULLER RD. ANN ARBOR, MI 48105
506-25-104
03/25/2026 DB CS
100% CONSTRUCTION
DOCUMENTS
NON-SPRINKLER
SCALE: 6" = 1'-0"GI001
1 INFECTION CONTROL RISK ASSESSMENT MATRIX
UP
DN
UP
DN
UP
DN
DN
PHASING GENERAL NOTES
A. PHASING PLANS SHOW A PROPOSED CONCEPT, FINAL PHASING PLAN IS THE
RESPONSIBILITY OF THE CONTRACTOR. PLANS SHOWN ARE CONCEPTUAL.
B. EACH PHASE SHOULD ONLY SHUT DOWN A MAXIMUM OF 30 SPACES AND
SHOULD ALLOW DRIVE AISLES AND PEDESTRIAN PATHWAYS TO REMAIN
OPEN AS MUCH AS POSSIBLE. ACCESS TO THE ELEVATOR LOBBY AND
STAIRS MUST ALSO REMAIN OPEN DURING ALL PHASES OF CONSTRUCTION.
C. IF MORE THAN 30 SPACES WILL BE SHUT DOWN WORK MUST BE NIGHT /
WEEKEND WORK. WEEKEND WORK IS EXPECTED TO BEGIN ON FRIDAY'S AT
NOON. WEEKEND AND NIGHT WORK WILL NEED TO BE COORDINATED WITH
COR AND WORK MUST BE CLEARED SO THAT NO MORE THAN 30 SPACES ARE
SHUT DOWN BY 7 AM DURING WEEKDAYS.
D. ONCE ALL REPAIRS ARE FINISHED ON LEVEL D OF THE EAST GARAGE, TOP
DECK SHOULD BE CLOSED FOR THE WEEKEND TO APPLY POLYURETHANE
TRAFFIC COATING PER MANUFACTURER REQUIREMENTS. COORDINATE
SHUT DOWN WITH VA / COR
E. PHASING IS BROKEN OUT FOR EACH FLOOR. WORK SHALL ONLY BE DONE
ON ONE FLOOR IN EACH BUILDING AT A TIME. STARTING ON TOP DECK
PHASING AND WORK DOWN TO THE LOWER LEVELS IS PROPOSED.
F. CONTRACTOR TO PROVIDE PHASING SCHEDULE TO VA / COR WITH A
MINIMUM 2 WEEK NOTICE FOR ADJUSTMENTS IN SCHEDULE TO COORDINATE
PARKING OUTAGE.
G. PHASING SHALL OCCUR IN EAST AND WEST GARAGE CONCURRENTLY TO
MINIMIZE CONSTRUCTION TIME.
H. WORK AREA SHALL BE CLEARLY IDENTIFIED AND FENCED IN BY 7' CHAIN LINK
FENCE TO ENSURE AREA IS SAFE AND SECURE WHILE UNDER
CONSTRUCTION. SIGNAGE SHALL BE PROVIDED CALLING OUT NO ENTRY /
CONSTRUCTION AREA REFERENCE SIGNAGE SPECIFICATIONS FOR
ADDITIONAL INFORMATION.
I. LEVEL E OF THE WEST GARAGE SHALL BE COMPLETED AS WEEKEND WORK
ONLY. CONCRETE REPAIR AND PREP SHOULD BE DONE PRIOR TO TRAFFIC
COATING BEING APPLIED. WORK SHOULD BEGIN AT NOON ON FRIDAY AND
SHOULD BE OPEN FOR TRAFFIC BY 7 AM ON MONDAY.
FLOOR PHASING LEGEND
PHASE 1
PHASE 2
PHASE 3
PHASE 4
PHASE 5
123456789101112131416 151718
C
D
E
F
STAIR 3
EAA107
MECHANICAL RM
III
2122232425
123456789101112
A
BB.1
C
D
E
F
11.212.1
RAMP UP
STAIR 3
EA107
ELEVATOR LOBBY
EA102
STAIR 1
EA101
ELEVATOR
EQUIPMENT RM
EA104
ELEVATORS
EA
STAIR
EA106
STORAGE
EA
N.I.C.
123456789101112
A
B
B.1
C
D
E
F
11.212.1
RAMP UP
STAIR 3
EB107
ELEVATOR LOBBY
EB102
ELECTRICAL RM
EB103
ELEVATORS
EB
STAIR 1
EB101
STAIR 2
EB106
N.I.C.
123456789101112
A
BB.1
C
D
E
F
11.212.1
RAMP UP
STAIR 3
EC107
ELEVATOR LOBBY
EC102
ELEVATORS
EC
STAIR 1
EC101
STAIR 2
EC106
N.I.C.
123456789101112
A
BB.1
C
D
E
F
11.212.1
RAMP DOWN
STAIR 3
EC107
ELEVATOR LOBBY
ED102
ELECTRICAL ROOM
ED103
ELEVATORS
ED
STAIR 1
ED101
STAIR 2
ED106
N.I.C.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
A u to d e s k D o c s /2
.1
V A
A n n A rb o r
E m e rg e n t
P a rk in g R e p a ir s /2
.1
A v
.r v t
/2
/2
:4
:5
P
M
GI002
PRELIMINARY PHASING PLAN
GUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
317.800.6388
EMERGENT PARKING
STRUCTURE REPAIRS
2215 FULLER RD. ANN ARBOR, MI 48105
506-25-104
EAST 29
03/25/2026 DB CS
100% CONSTRUCTION
DOCUMENTS
NON-SPRINKLER
EAST 29
SCALE: 1/32" = 1'-0"GI002
1 EAST GARAGE - LEVEL AA - PHASING PLAN
SCALE: 1/32" = 1'-0"GI002
2 EAST GARAGE - LEVEL A - PHASING PLAN
SCALE: 1/32" = 1'-0"GI002
3 EAST GARAGE - LEVEL B - PHASING PLAN
SCALE: 1/32" = 1'-0"GI002
4 EAST GARAGE - LEVEL C - PHASING PLAN
SCALE: 1/32" = 1'-0"GI002
5 EAST GARAGE - LEVEL D - PHASING PLAN
PHASING GENERAL NOTES
A. PHASING PLANS SHOW A PROPOSED CONCEPT, FINAL PHASING PLAN IS THE
RESPONSIBILITY OF THE CONTRACTOR. PLANS SHOWN ARE CONCEPTUAL.
B. EACH PHASE SHOULD ONLY SHUT DOWN A MAXIMUM OF 30 SPACES AND
SHOULD ALLOW DRIVE AISLES AND PEDESTRIAN PATHWAYS TO REMAIN
OPEN AS MUCH AS POSSIBLE. ACCESS TO THE ELEVATOR LOBBY AND
STAIRS MUST ALSO REMAIN OPEN DURING ALL PHASES OF CONSTRUCTION.
C. IF MORE THAN 30 SPACES WILL BE SHUT DOWN WORK MUST BE NIGHT /
WEEKEND WORK. WEEKEND WORK IS EXPECTED TO BEGIN ON FRIDAY'S AT
NOON. WEEKEND AND NIGHT WORK WILL NEED TO BE COORDINATED WITH
COR AND WORK MUST BE CLEARED SO THAT NO MORE THAN 30 SPACES ARE
SHUT DOWN BY 7 AM DURING WEEKDAYS.
D. ONCE ALL REPAIRS ARE FINISHED ON LEVEL D OF THE EAST GARAGE, TOP
DECK SHOULD BE CLOSED FOR THE WEEKEND TO APPLY POLYURETHANE
TRAFFIC COATING PER MANUFACTURER REQUIREMENTS. COORDINATE
SHUT DOWN WITH VA / COR
E. PHASING IS BROKEN OUT FOR EACH FLOOR. WORK SHALL ONLY BE DONE
ON ONE FLOOR IN EACH BUILDING AT A TIME. STARTING ON TOP DECK
PHASING AND WORK DOWN TO THE LOWER LEVELS IS PROPOSED.
F. CONTRACTOR TO PROVIDE PHASING SCHEDULE TO VA / COR WITH A
MINIMUM 2 WEEK NOTICE FOR ADJUSTMENTS IN SCHEDULE TO COORDINATE
PARKING OUTAGE.
G. PHASING SHALL OCCUR IN EAST AND WEST GARAGE CONCURRENTLY TO
MINIMIZE CONSTRUCTION TIME.
H. WORK AREA SHALL BE CLEARLY IDENTIFIED AND FENCED IN BY 7' CHAIN LINK
FENCE TO ENSURE AREA IS SAFE AND SECURE WHILE UNDER
CONSTRUCTION. SIGNAGE SHALL BE PROVIDED CALLING OUT NO ENTRY /
CONSTRUCTION AREA REFERENCE SIGNAGE SPECIFICATIONS FOR
ADDITIONAL INFORMATION.
I. LEVEL E OF THE WEST GARAGE SHALL BE COMPLETED AS WEEKEND WORK
ONLY. CONCRETE REPAIR AND PREP SHOULD BE DONE PRIOR TO TRAFFIC
COATING BEING APPLIED. WORK SHOULD BEGIN AT NOON ON FRIDAY AND
SHOULD BE OPEN FOR TRAFFIC BY 7 AM ON MONDAY.
FLOOR PHASING LEGEND
PHASE 1
PHASE 2
PHASE 3
PHASE 4
PHASE 5
G
G
F
F
E
E
D
D
C
C
B
B
7 7
6 6
5 5
4 4
3 3
2 2
1 1
A
A
D O
W N
U P
U P U
P
G
G
F
F
E
E
D
D
C
C
B
B
7 7
6 6
5 5
4 4
3 3
2 2
1 1
A
A
ONLY
D O
W N
U P
D O
W N
U P
U P
D O
W N
G
G
F
F
E
E
D
D
C
C
B
B
7 7
6 6
5 5
4 4
3 3
2 2
1 1
A
A
ONLY
D O
W N
U P
D O
W N
U P
U P
D O
W N
G
G
F
F
E
E
D
D
C
C
B
B
7 7
6 6
5 5
4 4
3 3
2 2
1 1
A
A
D O
W N
U P
D O
W N
U P
U P
D O
W N
ONLY
G
G
F
F
E
E
D
D
C
C
B
B
7 7
6 6
5 5
4 4
3 3
2 2
1 1
A
A
D O
W N
U P
D O
W N
D O
W N
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
A u to d e s k D o c s /2
.1
V A
A n n A rb o r
E m e rg e n t
P a rk in g R e p a ir s /2
.1
A v
.r v t
/2
/2
:4
:5
P
M
GI003
PRELIMINARY PHASING PLAN
GUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
317.800.6388
EMERGENT PARKING
STRUCTURE REPAIRS
2215 FULLER RD. ANN ARBOR, MI 48105
506-25-104
03/25/2026 DB CS
100% CONSTRUCTION
DOCUMENTS
NON-SPRINKLER
WEST
SCALE: 1/32" = 1'-0"GI003
1 WEST GARAGE - LEVEL A - PHASING PLAN
SCALE: 1/32" = 1'-0"GI003
2 WEST GARAGE - LEVEL B - PHASING PLAN
SCALE: 1/32" = 1'-0"GI003
3 WEST GARAGE - LEVEL C - PHASING PLAN
SCALE: 1/32" = 1'-0"GI003
4 WEST GARAGE - LEVEL D - PHASING PLAN
SCALE: 1/32" = 1'-0"GI003
5 WEST GARAGE - LEVEL E - PHASING
NPFA, NATIONAL FIRE PROTECTION ASSOCIATION FULL LISTING OF CURRENT CODES,
INCLUDING BUT NOT LIMITED TO:
NFPA 10 STANDARD FOR PORTABLE FIRE EXTINGUISHER 2022 ED.
NFPA 13 STANDARD FOR THE INSTALLATION OF SPRINKLER SYSTEMS 2022 ED.
NFPA 54, ANSI Z223.1 NATIONAL FUEL GAS CODE 2021 ED.
NFPA 70, NEC NATIONAL ELECTRICAL CODE 2023 ED.
NFPA 72 FIRE ALARM CODE 2022 ED.
NFPA 80 STANDARD FOR FIRE DOORS AND FIRE WINDOWS 2022 ED.
NFPA 90A STANDARD FOR INSTALLTION FOR THE INSTALLATION OF AIR-
CONDITIONING AND VENTILATING SYSTEMS 2021 ED.
NFPA 99 HEALTHCARE FACILITIES CODE 2024 ED.
NPFA 101 LIFE SAFETY CODE 2024 ED.
NFPA 220 STANDARD ON TYPES OF BUILDING CONSTRUCTION 2024 ED.
NFPA 241 STANDARD FOR SAFEGUARDING CONSTRUCTION, ALTERATION, AND
DEMOLITION OPERATIONS 2022 ED.
ICC CODES, INTERNATIONAL CODE COUNCIL FULL LISTING OF CURRENT
CODES, INCLUDING BUT NOT LIMITED TO:
INTERNATIONAL BUILDING CODE 2024 ED.
INTERNATIONAL PLUMBING CODE 2024 ED.
INTERNATIONAL MECHANICAL CODE 2024 ED.
INTERNATIONAL FUEL GAS CODE 2024 ED.
INTERNATIONAL ENERGY AND CONSERVATION CODE 2024 ED.
ASHRAE STANDARDS, AS REFERENCED WITHIN OTHER CODES INCLUDING,
BUT NOT LIMITED TO:
STANDARD 170-2024, VENTILATION OF HEALTHCARE FACILITIES
STANDARD 188-2018, LEGIONELLOSIS: RISK MANAGEMENT FOR BUILDING WATER
SYSTEMS
ACCESSIBILITY CODES
VA BARRIER FREE DESIGN GUIDE PG-18-13, ABAAS
FGI, THE FACILITY GUIDELINES INSTITUTE
GUIDELINES FOR DESIGN AND CONSTRUCTION OF HOSPITALS 2022 ED.
GUIDELINES FOR DESIGN AND CONSTRUCTION OF OUTPATIENT
FACILITIES 2022 ED.
BEHAVIORAL HEALTH DESIGN GUIDE 2019 ED.
SYSTEMS RELATING TO MAINTENANCE OF FACILITIES
OSHA, OCCUPATIONAL, SAFETY AND HEALTH ADMINISTRATION STANDARDS.
CODES AND GUIDELINES REFERENCED WITHIN NFPA AND ICC CODES ARE TO
ALSO BE FOLLOWED AND APPLIED TO ALL DESIGN AND CONSTRUCTION.
REFER TO VA MANUAL PG-18-3, SPECIFICATIONS FOR ADDITIONAL CODES,
STANDARDS, GUIDELINES AND REGULATIONS. CONTRACTOR IS RESPONSIBLE
FOR CONSTRUCTING WORK COMPLIANT WITH OSHA, OCCUPATIONAL, SAFETY
AND HEALTH ADMINISTRATION STANDARDS.
ARCHITECTURAL AUG-14
ASBESTOS ABATEMENT JULY-11
AUTOMATED TRANSPORT SYSTEMS NOV-20
COMMISSIONING AND RETRO COMMISSIONING NOV-13
ELECTRICAL DEC-19
ESTIMATING CES MAR-11
FIRE PROTECTION NOV-23
HVAC MAR-24
INTERIOR DESIGN NOV-20
LIGHTING DESIGN JAN-22
PHYSICAL SECURITY MAY-24
PLUMBING FEB-24
SIGNAGE MAR-23
SITE PARKING, SITE DEVELOPMENT, SITE APPENDIX NOV-16
STEAM, HEATING, HOT WATER, AND OUTSIDE DISTRIBUTION SYSTEMS MAY-24
STRUCTURAL JUL-24
SUSTAINABILITY
TELECOMMUNICATIONS
GOVERNING CODES
VA DESIGN MANUAL PG-18-10:
2215 FULLER RD. ANN ARBOR, MI 48105
NFPA 101 PRIMARILY ADDRESSES LIFE SAFETY AND FIRE PROTECTION FEATURES, WHILE THE IBC ADDRESSES A WIDE RANGE OF CONSIDERATIONS, INCLUDING, BUT NOT LIMITED TO, STRUCTURAL STRENGTH, SEISMIC STABILITY, SANITATION, ADEQUATE LIGHT AND VENTILATION, AND ENERGY CONSERVATION. VA BUILDINGS MUST MEET THE REQUIREMENTS OF NFPA 101 AND DOCUMENTS REFERENCED BY NFPA 101 IN ORDER TO COMPLY WITH THE ACCREDITATION REQUIREMENTS OF THE JOINT COMMISSION. THEREFORE, DESIGNS SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF NFPA 101 AND DOCUMENTS REFERENCED THEREIN. DESIGN FEATURES NOT ADDRESSED BY NFPA 101 OR DOCUMENTS REFERENCED THEREIN SHALL COMPLY WITH THE REQUIREMENTS OF THE LATEST EDITION OF THE IBC OR AS OTHERWISE ADDRESSED IN VA DESIGN MANUALS. FOR DESIGN FEATURES THAT ARE ADDRESSED BY BOTH THE IBC AS WELL AS NFPA 101 OR A DOCUMENT REFERENCED BY NFPA 101, THE REQUIREMENTS OF NFPA 101 OR THE DOCUMENT REFERENCED BY NFPA 101 SHALL BE USED EXCLUSIVELY (THIS APPLIES EVEN IF THE IBC REQUIREMENTS ARE DIFFERENT). SHOULD A CONFLICT EXIST BETWEEN VA REQUIREMENTS AND VA-ADOPTED NATIONALLY RECOGNIZED CODES AND STANDARDS, THE CONFLICT SHALL BE BROUGHT TO THE ATTENTION OF VA. THE RESOLUTION OF THE CONFLICT SHALL BE MADE BY THE AUTHORITY HAVING JURISDICTION (AHJ) FOR VA TO ENSURE CONSISTENCY SYSTEM WIDE. IN
ADDITION TO NFPA 101, NFPA 88A STANDARD FOR PARKING STRUCTURES IS REFERENCED.
BUILDING INFORMATION
BUILDING USE AND OCCUPANCY CLASSIFICATION: S-2 LOW HAZARD STORAGE FACILITIES PER NFPA 101 42.8.15
CONSTRUCTION TYPE: TYPE I-B
SPRINKLER SYSTEM: NON-SPRINKLERED
OCCUPANCY SEPARATION: NONE
SMOKE COMPARTMENT: NONE
ACTUAL ALLOWABLE
BUILDING HEIGHT ABOVE GRADE: 55' - 0" 160' - 0" (IBC 504.3)
BUILDING STORIES: 6 STORIES 11 STORIES (IBC 504.4)
BUILDING AREA: 57,633 SF 79,000 SF (IBC 506.2)
CONSTRUCTION RATING OF BUILDING ELEMENTS
THE GARAGE WAS DESIGNED AS STORAGE OCCUPANCY. INCIDENTAL USES ARE NOT USED, NO FIRE RATED SEPARATION IS REQUIRED BETWEEN FUNCTION FOR SPACES. INTERIOR BUILDING ELEMENTS THAT REQUIRE FIRE RESISTANCE RATINGS ARE LISTED BELOW:
BUILDING ELEMENT FIRE RESISTANCE RATING CODE REFERENCE
NON-ENCLOSED EXIT STAIRS 0 NFPA 88A 4.1.5
ENCLOSED EXIT STAIRS 1,2 NFPA 101 7.1.3.2.1
RAMPS 0 NFPA 101 42.8.3.1.2
SHAFTS WHICH CONNECT TWO (2) OR MORE STORIES
IN OPEN PARKING GARAGES 0 NFPA 101 42.8.3.1.2
NFPA 88A 5.4.8
ELEVATOR MACHINE ROOMS 2 NFPA 101 7.14.7.1
EMERGENCY GENERATOR 2 NFPA 70
WHERE NONRATED WALLS OR UNPROTECTED OPENINGS ENCLOSE THE EXTERIOR OF THE STAIRWAY AND THE WALLS OR OPENINGS ARE EXPOSED BY OTHER PARTS OF THE BUILDING AT AN ANGLE OF LESS THAN 180 DEGREES, THE BUILDING EXTERIOR WALLS WITHIN 3.048 M (10 FT) HORIZONTALLY OF A NONRATED WALL OR UNPROTECTED OPENING MUST HAVE A FIRE RESISTANCE RATING OF NOT LESS THAN 1-HOUR. OPENINGS WITHIN SUCH EXTERIOR WALLS MUST BE PROTECTED BY OPENING PROTECTIVE'S HAVING A FIRE PROTECTION RATING OF NOT LESS THAN ¾-HOUR. THIS CONSTRUCTION MUST EXTEND VERTICALLY FROM THE GROUND TO A POINT 3.048 M (10 FT) ABOVE THE TOP MOST LANDING OF THE STAIRWAY OR TO THE ROOF LINE, WHICHEVER IS LOWER.
THE ELECTRICAL, SECURITY AND IT ROOMS DO NOT HAVE A TOTAL AREA EXCEEDING 3,000 SF THEREFORE SHALL BE SEPARATED BY PARTITIONS BUILT TO
RESIST THE PASSAGE OF SMOKE. NFPA 88A 5.2.4.
FIRE BARRIERS WILL EXTEND FROM THE TOP OF THE FLOOR BELOW TO THE UNDERSIDE OF THE FLOOR OR ROOF DECK ABOVE. THE OPENINGS AND PENETRATIONS IN REQUIRED EXIT ENCLOSURES WILL BE PROTECTED WITH SELF-CLOSING OR AUTOMATIC-CLOSING OPENING PROTECTIVE'S. OPENINGS IN FIRE RESISTANCE RATED WALLS WILL BE PROTECTED IN ACCORDANCE WITH THE FOLLOWING:
COMPONENT WALLS AND PARTITIONS FIRE DOOR ASSEMBLIES
(HR) NFPA 101 8.3.4.2 (HR/MIN) NFPA 101 8.3.4.2
ELEVATOR HOISTWAYS 0 (OPEN) 0 MIN
2 (NON-OPEN) 90 MIN
ELEVATOR MACHINE ROOMS 2 90 MIN
VERTICAL SHAFTS 0 (OPEN) 0
EXTINGUISHER REQUIREMENTS
PORTABLE FIRE EXTINGUISHERS SHALL BE PROVIDED THROUGHOUT AS REQUIRED BY IFC SECTION 906.1 AND SPACED IN ACCORDANCE WITH NFPA 10, CODE ANALYSIS - NFPA 101, PARKING STRUCTURERS CHAPTER 42
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
A u to d e s k D o c s /2
.1
V A
A n n A rb o r
E m e rg e n t
P a rk in g R e p a ir s /2
.1
A v
.r v t
/2
/2
:4
:5
P
M
GI101
LIFE SAFETY CODE DATA
GUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
317.800.6388
EMERGENT PARKING
STRUCTURE REPAIRS
2215 FULLER RD. ANN ARBOR, MI 48105
506-25-104
03/25/2026 DB CS
100% CONSTRUCTION
DOCUMENTS
NON-SPRINKLER
SITE KEYNOTES
1. EXISTING SUMP PUMP WORK TO OCCUR IN THIS AREA. WORK TO INCLUDE
CUTTING AND CAPPING THE EXISTING DRAIN LINE AND GRADING / SOIL
REMEDIATION WHERE MINOR EROSION HAS OCCURRED. RE: PLUMBING
DRAWINGS FOR MORE INFORMATION.
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
A u to d e s k D o c s /2
.1
V A
A n n A rb o r
E m e rg e n t
P a rk in g R e p a ir s /2
.1
A v
.r v t
/2
/2
:4
:5
P
M
CG101
EAST GARAGE ARCHITECTURAL
SITE PLANGUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
317.800.6388
EMERGENT PARKING
STRUCTURE REPAIRS
2215 FULLER RD. ANN ARBOR, MI 48105
506-25-104
EAST 29
03/25/2026 AK CS
100% CONSTRUCTION
DOCUMENTS
NON-SPRINKLER
EAST 29
SCALE: 1" = 40'-0"CG101
1 EXTERIOR SITE REPAIRS
N
40 40 80 120 160 200 240
1" = 40'-0"
FEETSCALE
MISCELLANEOUS SYMBOLS
NORTH ARROW
SECTION NUMBER
SHEET NUMBER
S101
S101
CALLOUT NUMBER
SHEET NUMBER
F ## COLUMN FOOTING NOTATION
WF ## WALL FOOTING NOTATION
ROOF DRAIN
XS
T/SLAB ELEV.
X" THICK SLAB ON GRADE ON
15-MIL VAPOR BARRIER ON
6" COMPACTED AGGREGATE
5" THICK: USE MICROFIBER REINFORCEMENT
6" THICK: USE #4 @ 12" OC TOP W/
MICROFIBER REINFORCEMENT
12" THICK: USE MACROFIBER REINFORCEMENT
REF. TYP. HEAVY EQUIPMENT SLAB
SUPPORT DETAIL ON SHEET S50.02
18" THICK: USE #6 @ 9" OC TOP & BOTTOM
INDICATES SPAN DIRECTION OF:
4 ½" N.W. CONC. SLAB W/ 6x6 - W2.1 x W2.1
WWF ON 2", 20 GA. GALV. COMPOSITE STEEL
FLOOR DECK
TOTAL SLAB THICKNESS = 6 ½"
INDICATES SPAN DIRECTION OF:
1 1/2", 20 GA. GALVANIZED, WIDE-RIB STEEL
ROOF DECK
GRIDLINES
EARTH
A
ELEVATION REFERENCE
LIMIT OF EXTENT
CONTINUOUS EXTENT
GRAVEL
Name
Elevation
SNOW DRIFT LOAD
PEAK SNOW DRIFT LOAD
MINIMUM BALANCED UNIFORM SNOW
LOAD PER FLOOR LOAD SCHEDULE
INDICATES SPAN DIRECTION OF
4" N.W. CONC. SLAB W/ 6x6 - W2.1 x W2.1 WWF
ON 2", 20 GA. GALV. COMPOSITE STEEL
FLOOR DECK
TOTAL SLAB THICKNESS = 6"
EXISTING TO REMAIN
N
XX.X K ELEVATOR REACTIONS
PER FLOOR LOAD MAPS
PIPE PENETRATION THROUGH
FOUNDATION. COORDINATE EXACT
LOCATION & INVERT ELEVATION W/
APPROPRIATE TRADE. PROVIDE SLEEVE.
A
B
C
FD
OVERFLOW DRAIN
RD
FLOOR DRAIN
OD
SCHEDULE OF SPECIAL INSPECTIONS
MATERIAL / ACTIVITY SERVICE Y/N FREQUENCY
CONCRETE CONSTRUCTION
Y CONTINUOUSVERIFICATION OF REQUIRED CONCRETE MIX DESIGN REVIEW SUBMITTALS
Y
PERIODIC
FRESH CONCRETE SAMPLING FIELD TESTING
ONE TEST / 75 CYD. MINIMUM ONE TEST/DAY
TWO TEST FOR BEAM/ COLUMN REPAIRS
CONCRETE PLACEMENT
Y CONTINUOUSCONCRETE CURING OPERATIONS
YFIELD REVIEW
Y CONTINUOUSEVALUATION OF CONCRETE STRENGTH
FIELD TESTING AND REVIEW OF
LABORATORY REPORTS
REINFORCING AND PRESTRESSING STEEL
YREVIEW CERTIFIED MILL TEST REPORTS FIELD REVIEW CONTINUOUS
1. THE CONTRACTOR SHALL EMPLOY ONE OR MORE SPECIAL INSPECTOR(S) TO PROVIDE INSPECTIONS DURING CONSTRUCTION LISTED IN THIS SECTION. THE SPECIAL INSPECTOR SHALL BE A QUALIFIED PERSON WHO SHALL DEMONSTRATE COMPETENCE IN THE INSPECTIONS BEING PERFORMED TO THE SATISFACTION AND APPROVAL OF THE CONTRACTING OFFICER. THE SPECIAL INSPECTOR SHALL HAVE EXPERIENCE WITH AT LEAST FIVE OTHER PROJECTS SIMILAR IN NATURE. SEE PROJECT SPECIFICATIONS FOR FURTHER REQUIREMENTS RELATED TO
SPECIAL INSPECTORS
2. THE PURPOSE OF THE INSPECTIONS SHALL BE TO ENFORCE COMPLIANCE WITH THE CONSTRUCTION DRAWINGS, SPECIFICATIONS, AND STATE AND LOCAL BUILDING CODES IN EFFECT.
3. SPECIAL INSPECTORS SHALL KEEP RECORD OF INSPECTIONS. THE SPECIAL INSPECTOR SHALL FURNISH INSPECTION REPORTS TO THE COR AND TO THE ENGINEER OF RECORD.
REPORTS SHALL INDICATE THAT THE WORK INSPECTED WAS PERFORMED IN CONFORMANCE TO THE APPROVED CONSTRUCTION DOCUMENTS. DISCREPANCIES SHALL BE BROUGHT TO THE IMMEDIATE ATTENTION OF THE COR. THE COR SHALL THEN COMMUNICATE DISCREPANCIES TO THE CONTRACTOR. ANY CORRECTIONS THAT WERE NOT COMPLETED BY THE CONTRACTOR SHALL BE BROUGHT TO THE ATTENTION OF THE COR AND THE ENGINEER OF RECORD. IF DISCREPANCIES ARE NOT CORRECTED BY THE CONTRACTOR, SPECIAL INSPECTOR SHALL ISSUE A NOTIFICATION OF NON-COMPLIANCE (NNC) TO THE ENGINEER OR RECORD.
4. THE SPECIAL INSPECTOR SHALL VERIFY THAT THE FABRICATOR / MANUFACTER SUBMITTED QAQC PLAN AND PROCEDURES ARE FOLLOWED BY THE FABRICATOR / MANUFACTURER IF FABRICATOR IS ENROLLED IN A NATIONALLY ACCEPTED INSPECTIONS PROGRAM (SATISFACTORY TO THE CONTRACTING OFFICER), THIS IS NOT REQUIRED. ANY CORRECTIONS THAT WERE NOT COMPLETED BY THE CONTRACTOR SHALL BE BROUGHT TO THE ATTENTION OF THE CONTRACTING OFFICER.
5. THE SPECIAL INSPECTOR SHALL INSPECT THE CONCRETE FRAME INCLUDING BEARING WALLS, SHEAR WALLS, CONNECTION OF STRUCTURAL SLABS TO SHEAR WALLS, ELEVATED SLABS, BEAMS, COLUMNS, MAT FOUNDATIONS AND PIER CAPS.
NOTES:
FIELD REVIEW
MISCELLANEOUS
Y
SURFACE PREPARATION FOR DECK SEALANTS / MEMBRANES
FIELD REVIEW BY MANUFACTURERS
REPRESENTATIVE
PRIOR TO PRODUCT INSTALLATION
SURFACE WATER FLOW TEST FIELD REVIEW Y ONCE NEW TOPPING SLAB IS INSTALLED
AND CURED, SPRAY CONCRETE SURFACE
WITH WATER TO ENSURE SLOPES ARE
SUFFICIENT TO SHED WATER TO FIELD
DRAINS
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
A u to d e s k D o c s /2
.1
V A
A n n A rb o r
E m e rg e n t P a rk in g R e p a ir s /2
.1
S
V
V
A A n n
A rb o r
G a ra g e
G u id o n S tr u c t.
rv t
/2
/2
:5
:5
P
M
SI001
ABBREVIATIONS, SCHEDULES, &
SYMBOLSGUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
317.800.6388
EMERGENT PARKING
STRUCTURE REPAIRS
2215 FULLER RD, ANN ARBOR MI 48105
506-25-104
03/25/2026 AJK DSE
100% BID DOCUMENTS
NON-SPRINKLERED
STRUCTURAL ABBREVIATIONS
A/E ARCHITECT/ENGINEER
ACI AMERICAN CONCRETE INSTITUTE
ACP AUGER CAST PILE
ADDL ADDITIONAL
ADJ ADJACENT
AGGR AGGREGATE
AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION
ALT ALTERNATE
ANSI AMERICAN NATIONAL STANDARDS INSTITUTE
APPROX APPROXIMATE
AR ANCHOR ROD
ARCH ARCHITECTURAL
ASTM AMERICAN SOCIETY FOR TESTING AND MATERIALS
AWS AMERICAN WELDING SOCIETY
B/ BOTTOM OF
BAL BALANCE
BD BOARD
BLDG BUILDING
BLK BLOCK
BLKG BLOCKING
BM BEAM
BOTT BOTTOM
BRG BEARING
BRKT BRACKET
BTWN BETWEEN
C STANDARD CHANNEL
CANT CANTILEVER
CC CENTER TO CENTER
CF COLD FORMED
CG CENTER OF GRAVITY
CIP CAST-IN-PLACE
CJ CONTROL JOINT OR CONSTRUCTION JOINT
CJP COMPLETE JOINT PENETRATION
CL CENTERLINE
CLR CLEARANCE, CLEAR
CMU CONCRETE MASONRY UNIT
COL COLUMN
CONC CONCRETE
CONN CONNECTION
CONST CONSTRUCTION
CONT CONTINUOUS
CONTR CONTRACTOR
CTR CENTER
CTRD CENTERED
CU FT CUBIC FEET
CU IN CUBIC INCH
CYD CUBIC YARD
CW CONCRETE WALL
DBL DOUBLE
DEG DEGREE
DEMO DEMOLITION, DEMOLISH
DEPT DEPARTMENT
DET DETAIL
DIA DIAMETER
DIAG DIAGONAL
DIAPH DIAPHRAGM
DIM DIMENSION
DN DOWN
DO DITTO
DP DRILLED PIER OR DEEP
DWG DRAWING
DWL DOWELS
EA EACH
EF EACH FACE
EJ EXPANSION JOINT
EL, ELEV ELEVATION
ELEC ELECTRICAL
ENCL ENCLOSURE
ENGR ENGINEER
EOD EDGE OF DECK
EOJ EDGE OF JOIST
EOS EDGE OF SLAB
EQ EQUAL
EQPT EQUIPMENT
ES EACH SIDE
EW EACH WAY
EX EXISTING
EXP EXPANSION
EXT EXTERIOR
FAB FROM ADJACENT BEAM
FD FLOOR DRAIN
FDN FOUNDATION
FIN FINISH
FLG FLANGE
FLR FLOOR
FS FOOTING STEP
FT FEET
FTG FOOTING
FTGD FOOTING DRAIN
GA GAUGE
GALV GALVANIZED
GB GRADE BEAM
GRND GROUND
GT GIRDER TRUSS
HAS, HS HEADED ANCHOR STUD
HK HOOK
HORIZ HORIZONTAL
HP HIGH POINT
HSS HOLLOW STRUCTURAL SECTION
HVAC HEATING, VENTILATION, AIR CONDITIONING
ID INSIDE DIAMETER
IF INSIDE FACE
IN INCH
INCL INCLUDE
INFO INFORMATION
INSUL INSULATION
INT INTERIOR
J/BRG JOIST BEARING
JST JOIST
STRUCTURAL ABBREVIATIONS
JT JOINT
KB KNEE BRACE
KIP, K 1,000 POUNDS
KO KNOCK-OUT
KSI KIPS PER SQUARE INCH
L ANGLE OR LENGTH
LAB LABRATORY
LB POUND
LF LINEAL FOOT
LIN LINEAL, LINEAR
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
LONGIT LONGITUDINAL
LP LOW POINT
LSLT LONG SLOTTED HOLE
LTWT LIGHT WEIGHT
MAS MASONRY
MATL MATERIAL
MAX MAXIMUM
MB MACHINE BOLT
MC MISCELLANEOUS CHANNEL
MECH MECHANICAL
MEMB MEMBRANE
MEP MECHANICAL/ ELECTRICAL/ PLUMBING
MFR MANUFACTURER
MIN MINIMUM
MISC MISCELLANEOUS
MO MASONRY OPENING
MULT MULTIPLE
N/A NOT APPLICABLE
NO NUMBER
NOM NOMINAL
NS NEAR SIDE
NTS NOT TO SCALE
OC ON CENTER
OD OUTSIDE DIAMETER
OF OUTSIDE FACE
OFD OVERFLOW DRAIN
OH OVERHEAD
OPNG OPENING
OPP OPPOSITE
OPPHD OPPOSITE HAND
ORIG ORIGINAL
OVS OVERSIZED HOLE
P PIER
PC PIER CAP OR PRECAST
PERIM PERIMETER
PERM PERMANENT
PERP PERPENDICULAR
PJP PARTIAL JOINT PENETRATION
PL PLATE
PLF POUNDS PER LINEAL FOOT
PLYWD PLYWOOD
PREFAB PREFABRICATED
PREL PRELIMINARY
PREP PREPARATION, PREPARE
PROJ PROJECTION
PS PRESTRESSED
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT POST-TENSIONED
PW PRECAST WALL (REF. ARCH DWGS.)
R RADIUS
RD ROOF DRAIN
REF REFERENCE
REINF REINFORCEMENT, REINFORCE
REQD REQUIRED
RO ROUGH OPENING
SCH SCHEDULE
SECT SECTION
SF SQUARE FEET
SHT SHEET
SIM SIMILAR
SL SLOPE
SL-DN SLOPE DOWN
SL-UP SLOPE UP
SOG SLAB-ON-GRADE
SP SHEET PILING
SPA SPACES, SPACE
SPECS SPECIFICATIONS
SQ SQUARE
SS STAINLESS STEEL
SSLT SHORT SLOTTED HOLE
STD STANDARD
STIFF STIFFENER
STL STEEL
STRUC STRUCTURAL
SYM SYMMETRICAL
T & B TOP AND BOTTOM
T/ TOP OF
T/GB TOP OF GRADE BEAM
TBS MECHANICAL TENSION BUTT SPLICE
TEMP TEMPERATURE
TF TRENCH FOOTING
THRU THROUGH
TRANS TRANSVERSE
TYP TYPICAL
UL UNDERWRITERS' LABORATORY INC.
UNO UNLESS NOTED OTHERWISE
UT ULTRA-SONIC TEST
VERT VERTICAL
VIF VERIFY IN FIELD
W WIDE FLANGE
W/ WITH
W/O WITHOUT
WD WOOD
WF WALL FOOTING
WP WORK POINT
WWF WELDED WIRE FABRIC
STRUCTURAL SHEET LIST
SHEET NUMBER SHEET NAME
SI001 ABBREVIATIONS, SCHEDULES, & SYMBOLS
SI002 STRUCTURAL GENERAL NOTES
SF101 EAST LEVEL AA FRAMING PLAN
SF102 EAST LEVEL A FRAMING PLAN
SF103 EAST LEVEL B FRAMING PLAN
SF104 EAST LEVEL C FRAMING PLAN
SF105 EAST LEVEL D FRAMING PLAN
SF201 WEST LEVEL A FRAMING PLAN
SF202 WEST LEVEL B FRAMING PLAN
SF203 WEST LEVEL C FRAMING PLAN
SF204 WEST LEVEL D FRAMING PLAN
SF501 REPAIR DETAILS
Revisions: Date:
Project Number
Building Number
Drawing Number
Project Title
Location
Issue Date Checked Drawn
Drawing Title
Approved:
VA FORM 08 - 6231
A
Office of Construction and Facilities Management
U.S. Department of Veterans Affairs
B
C
D
E
F
A
B
C
D
E
F
21 4 5 6 7 8 9 10
Phase
ARCHITECT/ENGINEER OF RECORD
A/E:
STAMPCONSULTANT
321 4 5 6 7 8 9 10
Consultant:
A u to d e s k D o c s /2
.1
V A
A n n A rb o r
E m e rg e n t P a rk in g R e p a ir s /2
.1
S
V
V
A A n n
A rb o r
G a ra g e
G u id o n S tr u c t.
rv t
/2
/2
:5
:5
P
M
SI002
STRUCTURAL GENERAL NOTES
GUIDON
1221 N. PENNSYLVANIA STREET
INDIANAPOLIS, IN 46202
317.800.6388
EMERGENT PARKING
STRUCTURE REPAIRS
2215 FULLER RD, ANN ARBOR MI 48105
506-25-104
03/25/2026 AJK DSE
100% BID DOCUMENTS
NON-SPRINKLERED
GENERAL
THE STRUCTURE HAS BEEN DESIGNED FOR THE IN-SERVICE LOADS ONLY. THE METHODS, MEANS, PROCEDURES, AND SEQUENCES OF CONSTRUCTION ARE THE RESPONSIBILITY OF THE CONTRACTOR. THE STRUCTURE IS DESIGNED TO BE SELF-SUPPORTING AND STABLE AFTER THE BUILDING IS COMPLETE. IT IS THE CONTRACTOR'S RESPONSIBILITY TO DETERMINE ERECTION PROCEDURES AND SEQUENCE TO ENSURE SAFETY OF THE BUILDING AND ITS COMPONENTS DURING ERECTION. THIS INCLUDES THE ADDITION OF
NECESSARY SHORING, SHEETING, TEMPORARY BRACING, GUYS, TIEDOWNS, ETC.
THE STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION ALL OTHER DISCIPLINE DRAWINGS AS APPLICABLE TO THE PROJECT
THE GENERAL NOTES ON THE DRAWINGS ARE TO BE USED IN CONJUNCTION WITH THE FULL WRITTEN MATERIAL SPECIFICATIONS (IF ANY) FOR THE PROJECT. IF A DISCREPANCY OCCURS BETWEEN THE NOTES AND THE FULL SPECIFICATIONS, THE MORE STRINGENT
REQUIREMENT SHALL APPLY.
NO PENETRATIONS THROUGH STRUCTURAL ELEMENTS, OTHER THAN THOSE SHOWN ON THE DRAWINGS, SHALL BE MADE WITHOUT
THE REVIEW OF THE STRUCTURAL ENGINEER AND APPROVAL OF THE COR.
CONTRACTOR TO COORDINATE ALL EQUIPMENT, ROOF DRAINS, CHASES, AND OTHER ITEMS CONNECTED TO THE STRUCTURE BEFORE
FABRICATION BEGINS.
CONTRACTOR SHALL PRINT ALL DISCIPLINE DRAWINGS IN COLOR
SHOP DRAWING SUBMITTALS
THE CONTRACTOR SHALL PREPARE DETAILED SHOP DRAWINGS TO ENABLE HIM TO FABRICATE, ERECT AND CONSTRUCT ALL PARTS OF THE WORK IN ACCORDANCE WITH THE DRAWINGS AND SPECIFICATIONS. THESE SHOP DRAWINGS WILL BE REVIEWED FOR GENERAL COMPLIANCE WITH THE DESIGN INTENT ONLY. THE CONTRACTOR IS RESPONSIBLE FOR ALL DIMENSIONS, ACCURACY AND FIT OF WORK.
ALL SHOP DRAWINGS SHALL BE REVIEWED BY THE CONTRACTOR PRIOR TO SUBMITTAL TO THE STRUCTURAL ENGINEER. DRAWINGS
SUBMITTED WITHOUT CONTRACTOR'S REVIEW WILL BE RETURNED UNCHECKED.
SUBMIT ELECTRONIC VERSIONS OF SHOP DRAWINGS. SUBMIT SHOP DRAWINGS IN PDF FORMAT.
SUBMIT SHOP DRAWINGS FOR EACH OF THE FOLLOWING ITEMS:
1. CONCRETE REINFORCEMENT
2. SHORING DRAWINGS AND CALCULATIONS AS NEEDED SIGNED AND SEALED BY A PROFESSIONAL ENGINEER REGISTERED IN
THE STATE THE PROJECT IS LOCATED IN
PRODUCT DATA SUBMITTALS
THE CONTRACTOR SHALL SUBMIT FOR APPROVAL PRODUCT DATA FOR THE SPECIFIC ITEMS LISTED BELOW. CONTRACTOR SHALL NOT USE PRODUCTS OTHER THAN THOSE SUBMITTED WITHOUT THE APPROVAL OF THE STRUCTURAL ENGINEER.
MANUFACTURER'S TRADE NAMES AND NUMBERS USED HEREIN ARE ONLY TO IDENTIFY COLORS, FINISHES, TEXTURES, AND PATTERNS AS A BASIS OF DESIGN. PRODUCTS OF AUTHORIZED EQUAL MANUFACTURER'S EQUIVALENT TO COLORS, FINISHES, TEXTURES, AND PATTERNS OF MANUFACTURERS LISTED THAT MEET REQUIREMENTS OF TECHNICAL SPECIFICATIONS IN EVERY RESPECT MAY BE ACCEPTABLE WITH SUBMITTAL OF A COMPLETED SUBSTITUTION REQUEST CONTAINING ALL PRODUCT DATA, TESTING AND ACTUAL
SAMPLES, AND UPON APPROVAL IN WRITING BY CONTRACTING OFFICER.
SUBMIT ELECTRONIC VERSIONS OF PRODUCT DATA IN PDF FORMAT TO THE STRUCTURAL ENGINEER AND COR FOR REVIEW.
1. WELDED WIRE FABRIC MESH
2. CONCRETE REINFORCEMENT
3. CONCRETE CURING COMPOUND
4. CONCRETE JOINT SEALANT
5. EXPANSION ANCHORS
6. ADHESIVE ANCHORS
7. NON-SHRINK GROUT
8. CONCRETE REPAIR MORTARS
SHORING/RE-SHORING
ANY SHORING AND/OR RE-SHORING DESIGN FOR EXISTING STRUCTURAL SYSTEMS AS NEEDED FOR ANY STRUCTURAL REPAIR WORK IS THE RESPONSIBILITY OF THE CONTRACTOR. TEMPORARY SHORING FOR SLABS, BEAMS, AND GIRDERS SHALL BE ADEQUATE TO CARRY THE TOTAL WEIGHT OF THE SLAB-BEAM-GIRDER SYSTEM AND ANY TEMPORARY CONSTRUCTION LOADS TO BE IMPOSED ON THE STRUCTURAL SYSTEM. SHORING SHALL NOT BE REMOVED UNTIL ANY REPAIRS OR WORK PERFORMED IS ADEQUATELY IN PLACE TO SUPPORT EXISTING LOADS. REMOVAL OF SHORING AND/OR RESHORING SHALL NOT CAUSE OVERSTRESSING OF ANY STRUCTURAL
ELEMENTS.
THE FOLLOWING DESIGN LOADS FOR THE EXISTING GARAGE ARE TAKEN FROM THE DRAWING SET TITLED "CLINICAL ADDTION AND RENOVATION" AND DATED 01/18/94. REFRENCE DRAWINGS FOR ADDTIONAL EXISTING ASSUMED LOADING FOR THE THE STRUCTURE.
LIVE LOAD: LEVEL D - 80 PSF INCLUDING SNOW (NO LL REDUCTION PERMITEED)
LEVELS B & C - 50 PSF
CONCENTRATED WHEEL LOAD OVER 20 SQ IN - 2,000 LBS
REINFORCING STEEL
REINFORCING STEEL SHALL BE DEFORMED BARS CONFORMING TO ASTM A615 AND SHALL HAVE A MINIMUM YIELD STRENGTH OF 60,000
PSI.
REINFORCING BAR DETAILING, FABRICATING, AND PLACING SHALL CONFORM TO THE LATEST EDITION OF THE FOLLOWING STANDARDS:
ACI 301, ACI 315, ACI 318 AND ACI DETAILING MANUAL (SP66).
UNLESS A GREATER AMOUNT OF COVER IS INDICATED ON THE DRAWINGS, PROVIDE THE FOLLOWING MINIMUM CONCRETE COVER
OVER REINFORCEMENT AS FOLLOWS:
CONCRETE CAST AGAINST AND PERMANENTLY EXPOSED TO EARTH: 3 INCHES
#6 BARS AND LARGER EXPOSED TO EARTH OR WEATHER: 2 INCHES
#5 BARS AND SMALLER EXPOSED TO EARTH OR WEATHER: 1-1/2 INCHES
BEAM AND COLUMN TIES, STIRRUPS AND SPIRALS: 1-1/2 INCHES
ELEVATED SLAB BARS NOT EXPOSED TO EARTH OR WEATHER: 3/4 INCH
REINFORCING STEEL SHALL NOT BE TACK WELDED, WELDED, HEATED OR CUT UNLESS INDICATED ON THE CONTRACT DOCUMENTS OR
APPROVED BY THE STRUCTURAL ENGINEER.
WHERE LAP SPLICE LENGTHS ARE NOT SHOWN OR NOTED, PROVIDE A CLASS "B" LAP.
ALL 90 DEGREE AND 180 DEGREE BENDS SHOWN ON THE DRAWINGS SHALL BE STANDARD HOOKS, UNLESS NOTED OTHERWISE.
PROVIDE CORNER BARS OF SAME SIZE AND SPACING AS HORIZONTAL BARS AT CORNERS OF ALL WALLS AND GRADE BEAMS. LAP
SPLICE CORNER BARS WITH STRAIGHT BARS.
UNLESS OTHERWISE SHOWN OR NOTED, PROVIDE 2-#5 BARS (ONE EACH FACE) AROUND UNFRAMED OPENINGS IN CONCRETE WALLS AND GRADE BEAMS. PLACE BARS PARALLEL TO THE SIDES OF THE OPENING AND EXTEND 24" BEYOND CORNERS.
WELDABLE REINFORCING STEEL
REINFORCING STEEL WHICH IS TO BE WELDED SHALL CONFORM TO ASTM A706. WELDING OF REINFORCING STEEL, WHEN APPROVED BY THE STRUCTURAL ENGINEER, SHALL CONFORM TO THE LATEST EDITION OF AMERICAN WELDING SOCIETY STANDARD D1.4.
ELECTRODES FOR SHOP AND FIELD WELDING OF REINFORCING STEEL SHALL CONFORM TO ASTM A233, CLASS E90XX.
EPOXY-COATED REINFORCING STEEL
EPOXY COATED REINFORCING STEEL SHALL CONFORM TO ASTM A775 AND SHALL BE USED ONLY WHERE SHOWN OR NOTED ON THE
DRAWINGS.
WELDED WIRE FABRIC
WELDED WIRE FABRIC SHALL BE SMOOTH WIRE FABRIC CONFORMING TO ASTM A185. FABRIC SHALL BE SUPPLIED IN FLAT SHEETS AND
LAPPED A MINIMUM OF ONE SPACE PLUS 2 INCHES.
WELDED WIRE FABRIC SHALL BE PLACED CENTERED WITHIN THE TOPPING SLAB
CONCRETE TESTING
MAKE ONE SET OF TEST CYLINDERS IN ACCORDANCE WITH ASTM C31 FOR EACH DAY'S POUR AND FOR EACH 100 CUBIC YARDS. EACH SET SHALL INCLUDE ONE SPECIMEN TESTED AT 7 DAYS, 2 SPECIMENS TESTED AT 28 DAYS AND ONE SPECIMEN RETAINED IN RESERVE TO BE TESTED AT THE DIRECTION OF THE STRUCTURAL ENGINEER. SPARE CYLINDER MAY BE DISCARDED 90 DAYS AFTER CASTING
UNLESS
DIRECTED OTHERWISE BY THE STRUCTURAL ENGINEER. THIS SET OF TEST CYLINDERS SHALL BE PROTECTED AGAINST FREEZING.
WHEN THE AMBIENT TEMPERATURE IS EXPECTED TO FALL BELOW 40 DEGREES DURING THE COURSE OF A CONCRETE POUR OR SUBSEQUENT CURING PROCESS, AN ADDITIONAL SET OF CONCRETE TEST CYLINDERS SHALL BE MADE AND TESTED. THESE CYLINDERS SHALL BE STORED IMMEDIATELY ADJACENT TO, AND CURED UNDER THE SAME CONDITIONS AS THE BUILDING CONCRETE. SPECIAL
CURING BOXES ARE NOT PERMITTED FOR THESE TEST CYLINDERS.
FORWARD COPIES OF TEST RESULTS TO THE ARCHITECT, STRUCTURAL ENGINEER, READY-MIX SUPPLIER AND CONTRACTOR WITHIN 24
HOURS AFTER TESTING.
EXPANSION ANCHORS
EXPANSION ANCHORS SHALL BE CARBON STEEL ANCHORS AS MANUFACTURED BY HILTI FASTENING SYSTEMS OR AN EQUIVALENT SUBSTITUTE APPROVED BY THE STRUCTURAL ENGINEER AND SHALL BE INSTALLED IN CONFORMANCE WITH THE MANUFACTURER'S
RECOMMENDATIONS.
EXPANSION ANCHORS SHALL NOT BE INSTALLED IN CONCRETE UNTIL IT HAS ATTAINED ITS SPECIFIED MINIMUM 28 DAY COMPRESSIVE
STRENGTH.
ADHESIVE ANCHORS
ADHESIVE ANCHORS SHALL BE HILTI "HIT HY200" FOR SOLID SUBSTRATE AND HILTI "HIT HY270" FOR HOLLOW SUBSTRATE OR AN EQUIVALENT SUBSTITUTE APPROVED BY THE STRUCTURAL ENGINEER, UNLESS NOTED OTHERWISE ON PLANS. ANCHORS SHALL BE INSTALLED IN CONFORMANCE WITH THE MANUFACTURER'S RECOMMENDATIONS BY INSTALLERS TRAINED BY THE MANUFACTURER'S
REPRESENTATIVE.
MINIMUM EMBEDMENT DEPTH SHALL BE 8 BOLT DIAMETERS UNLESS NOTED OTHERWISE.
NON-SHRINK GROUT
GROUT SHALL BE A NON-METALLIC, SHRINKAGE RESISTANT (WHEN TESTED IN ACCORDANCE WITH THE LATEST EDITION OF ASTM C827 OR CRD-C621), PREMIXED, NON-CORROSIVE, NON-STAINING PRODUCT CONTAINING PORTLAND CEMENT, SILICA SANDS, SHRINKAGE COMPENSATING AGENTS AND FLUIDITY IMPROVING COMPOUNDS. GROUT SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH (F'C) OF
5,000 PSI IN 28 DAYS.
RENOVATION (EXISTING CONDITIONS)
INFORMATION SHOWN FOR THE EXISTING STRUCTURE ON THESE DRAWINGS WAS TAKEN FROM DRAWINGS THAT WERE PREPARED FOR VAMC ANN ARBOR, MICHIGAN, ENTITLED CLINICAL ADDITION AND RENOVATION, AND DATED 1/18/1994 AND RECORD DRAWINGS
ENTITLED REPAIR PARKING STRUCTURES DATED 08/05/2025.
WORK SHOWN ON THESE PLANS ASSUMES THAT THE ORIGINAL CONSTRUCTION WAS PERFORMED IN ACCORDANCE WITH THE ABOVE INDICATED ORIGINAL DRAWINGS INCLUDING (BUT NOT LIMITED TO) DIMENSIONS, ELEVATIONS, MEMBER SIZES, MATERIALS, DETAILS, ETC. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO VERIFY THE CONDITIONS RELATING TO THE EXISTING STRUCTURE AND TO
NOTIFY THE COR IMMEDIATELY OF ANY DISCREPANCIES OR CONFLICTS.
WHERE NEW WORK IS TO BE FITTED TO OLD WORK, THE CONTRACTOR SHALL CHECK ALL DIMENSIONS AND CONDITIONS IN THE FIELD, AND REPORT ANY ERRORS OR DISCREPANCIES TO THE COR TO THE FABRICATION AND ERECTION OF ANY NEW MEMBERS.
EXISTING MATERIALS TO BE REMOVED AND REINSTALLED AS PART OF THE PROJECT, THAT BECOME DAMAGED, SHALL BE REPLACED
WITH NEW MATERIAL OF EQUAL QUALITY AND APPEARANCE, AT THE CONTRACTORS EXPENSE.
ALL WORK SHALL BE PERFORMED WITHOUT DAMAGE TO ADJACENT RETAINED WORK. ADJACENT EXISTING CONSTRUCTION SHALL BE
PROTECTED FROM DUST, DIRT, AND DEBRIS ACCUMULATION AT ALL TIMES.
SPECIAL CONSIDERATION SHALL BE MADE TO LIMIT MATERIAL STORAGE ON THE STRUCTURE. ASSUMED LIVE LOAD ON THE EXISTING
DECK SURFACE IS 40 PSF
GENERAL NOTES
GENERAL
1. ALL REPAIRS SHALL BE IN ACCORDANCE WITH THE FOLLOWING:
A. INTERNATIONAL BUILDING CODE (IBC), 2024 EDITION, OR MOST CURRENT
B. ACI 318-22, OR MOST CURRENT
2. EXISTING BUILDING CLASSIFICATION
A. IBC USE AND OCCUPANCY CLASSIFICATION: LOW - HAZARD STORAGE, GROUP S-2 PARKING GARAGES, ENCLOSED.
B. TYPE OF CONSTRUCTION: TYPE 1B
3. THE DRAWINGS SHALL BE USED IN CONJUNCTION WITH SPECIFICATIONS.
4. THE GENERAL NOTES ON THE DRAWINGS ARE TO BE USED IN CONJUNCTION WITH THE FULL WRITTEN MATERIAL
SPECIFICATIONS (IF ANY) FOR THE PROJECT.
5. NO PENETRATIONS THROUGH STRUCTURAL ELEMENTS, OTHER THAN THOSE SHOWN ON THE DRAWINGS, SHALL BE MADE
WITHOUT THE APPROVAL OF THE COR.
6. CONTRACTOR TO COORDINATE ALL EQUIPMENT, ROOF DRAINS, CHASES, AND OTHER ITEMS CONNECTED TO THE
STRUCTURE BEFORE FABRICATION BEGINS.
CONSTRUCTION NOTES
1. GENERAL
A. WHERE DIMENSIONS ARE INDICATED FOR EXISTING COMPONENTS, THEY ARE APPROXIMATE AND FOR REFERENCE ONLY.
CONTRACTOR SHALL VERIFY IN FIELD (VIF) ALL DIMENSIONS/ELEVATIONS PRIOR TO CONSTRUCTION. ANY VARIATIONS BETWEEN EXISTING DIMENSIONS/ELEVATIONS ON DRAWINGS AND EXISTING CONDITIONS SHALL BE REPORTED TO COR.
B. ALL OMISSIONS OR CONFLICTS AMONG VARIOUS ELEMENTS OF DRAWINGS AND/OR SPECIFICATIONS SHALL BE REPORTED TO
ENGINEER BEFORE PROCEEDING WITH ANY WORK.
C. VERIFY LOCATION OF SLAB DEPRESSIONS, FLOOR DRAINS, INSERTS AND OTHER RELATED ITEMS AS THEY AFFECT REPAIR
AREAS.
D. NO STRUCTURAL MEMBERS SHALL BE CUT UNLESS SPECIFICALLY DETAILED OR APPROVED IN WRITING BY COR AND ENGINEER.
E. FIELD VERIFY THE LOCATIONS OF EXISTING STRUCTURES, UTILITIES, ETC., AND NOTIFY ENGINEER OF INTERFERENCES NOT
NOTED ON DRAWINGS.
F. RESTRICTIONS MAY BE REQUIRED BY VA AS TO NOT IMPACT CERTAIN EFFORTS. LOCAL NOISE ORDINANCE MAY GOVERN
OPERATIONS.
G. DURING JOB SITE VISITS BY THE ENGINEER OF RECORD, ENGINEER SHALL IDENTIFY ANY NON-CONFORMANCE NOTED AND
INCLUDE SAME IN THE FIELD INSPECTION REPORT FOR THAT DAY/DATE.
H. FIRE SUPPRESSION SYSTEM MUST BE MAINTAINED IN THE STRUCTURE AT ALL TIMES EXCEPT IN WORK AREAS. IF FIRE
SUPPRESSION SYSTEM IS TO BE TAKEN OFFLINE IN THE WORK AREA, FIRE HOSES MUST BE INSTALLED WITHIN THE WORK AREA
PRIOR TO BEGINNING CONSTRUCTION.
I. TAKE EXTREME CAUTION NOT TO DAMAGE IN ANY WAY THE EXISTING ELECTRICAL SERVICE, TELECOMMUNICATION LINES, COMPUTER LINES, ETC. LOCATE AND MARK ALL SERVICE LINES. CONCRETE SLAB HAS EMBEDDED CONDUIT. TAKE PRECAUTIONS SO AS NOT TO INTERRUPT ELECTRICAL SERVICE WITHOUT NOTICE. IT IS THE CONTRACTORS RESPONSIBILITY TO RESTORE ANY
DAMAGE TO ORIGINAL CONDITION.
J. ALL TEMPORARY SIGNS TO BE 24" x 24" MINIMUM. CONSTRUCTED OF RIGID MATERIAL (1/2" PLYWOOD OR SIMILAR). TEXT TO BE 10" HIGH STENCILED BLACK HELVETICA LETTERS. NO HANDWRITTEN TEXT WILL BE PERMITTED. SIGN BACKGROUND TO BE ORANGE
WITH 1/2" BLACK BORDER.
K. DO NOT SCALE DRAWINGS.
L. REMOVE AND REINSTALL ANY ITEMS/COMPONENTS THAT INTERFERE WITH THE CONCRETE REPAIR WORK REQUIRED. IF ANY
DAMAGE OCCURS TO THESE MATERIALS, CONTRACTOR TO REPLACE AT NO ADDITIONAL COST WITH EQUAL OR BETTER
MATERIALS ACCEPTABLE TO THE COR.
M. CLEANING OF UTENSILS, EQUIPMENT, CHUTES, ETC. SHALL BE CONTAINED IN A BAG OR CONTAINER SO AS TO NOT CONTAMINATE
THE STORM DRAINS WITH CONCRETE. CONCRETE TRUCKS MUST BE CLEANED OFFSITE.
N. IF THE CONTRACTOR HAS POL (PETROLEUM, OILS, LUBRICANTS), IN QUANTITIES OF 55 GALLONS OR GREATER, THE CONTRACTOR MUST COMPLY WITH THE SPILL PREVENTION CONTROL AND COUNTERMEASURE PLAN. THIS WILL INCLUDE A MONTHLY
INSPECTION AND A SECONDARY CONTAINMENT WHILE IN STORAGE.
2. CONSTRUCTION PHASING
A. CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATION OF ALL CONSTRUCTION ACTIVITY AND SHALL COOPERATE FULLY
WITH OWNER FOR ALL CONSTRUCTION PHASING.
B. COORDINATE WITH THE COR MOVING MATERIALS IN STORAGE OR OTHER OCCUPIED ROOMS AS REQUIRED TO PERFORM
REPAIRS.
C. IT WILL BE NECESSARY TO SCHEDULE CONTRACTOR DELIVERIES AND WASTE HAULING TO MINIMIZE INTERFERENCE WITH EXISTING BUILDING OPERATIONS. CONTRACTOR SHALL COORDINATE DELIVERIES AND WASTE REMOVAL WITH OWNER.
D. PARKING WILL NOT BE ALLOWED IN AREAS WITH SHORING.
E. A PRE-EXISTING CONDITIONS WALK-THROUGH MUST BE DONE IN THE PRESENCE OF THE COR IMMEDIATELY PRIOR TO BEGINNING
WORK.
F. SEE SPEC SECTION 01 00 00 1.6-G FOR DETAILS REGARDING HOSPITAL BUSINESS HOURS AND THE AMOUNT OF PARKING SPACES
ALLOWED TO BE SHUT DOWN AT A TIME.
G. IF MORE THAN THIRTY (30) PARKING SPACES ARE REQUIRED TO BE TAKEN OUT OF SERVICE AT ANY ONE TIME, THE CONTRACTOR
SHALL COORDINATE WITH THE OWNER AND THE DEPARTMENT OF VETERANS AFFAIRS (VA) TO SCHEDULE SUCH WORK DURING NIGHTTIME HOURS AND/OR WEEKENDS, AS DIRECTED. WORK IMPACTING MORE THAN THIRTY (30) SPACES SHALL NOT PROCEED
WITHOUT PRIOR WRITTEN APPROVAL. SEE ARCH FOR ADDITIONAL INFORMATION ON PHASING.
H. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ALL ARRANGEMENTS NECESSARY TO PERFORM WORK DURING SEASONAL CONDITIONS. NO SCHEDULE DELAYS WILL BE GRANTED DUE TO LACK OF PLANNING FOR WORK DURING COLD OR HOT WEATHER
CONDITIONS. SEE DIVISION 1 SPECIFICATIONS FOR FURTHER REQUIREMENTS.
3. FORMWORK AND SHORING
A. DRAWINGS DO NOT INCLUDE NECESSARY COMPONENTS FOR SAFETY OF BUILDING OR EQUIPMENT DURING CONSTRUCTION.
CONTRACTOR IS RESPONSIBLE FOR ALL WORK RELATING TO CONSTRUCTION, ERECTION METHODS, BRACING, SHORING, RIGGING, GUYS, SCAFFOLDING, FORMWORK, AND OTHER WORK AIDS REQUIRED TO SAFELY PERFORM WORK INDICATED.
B. CONTRACTOR IS RESPONSIBLE FOR PROVIDING APPROPRIATE STRUCTURAL SHORING ADJACENT TO REPAIR AREAS.
C. CONTRACTOR TO PROVIDE PROFESSIONAL ENGINEERED SEALED CALCULATIONS (PER STATE OF MICHIGAN REQUIREMENTS).
D. SHORING AND FORMWORK FOR OVERHEAD REPAIRS SHALL BE MAINTAINED UNTIL CONCRETE REPAIR AREAS HAVE ACHIEVED A
MINIMUM STRENGTH OF 4,000 PSI.
4. CONCRETE DELAMINATION REPAIR
A. MARK PERIMETER OF ALL VISIBLE CONCRETE DELAMINATION AS INDICATED ON THE DRAWINGS.
B. SAWCUT AND CHIP AT PERIMETER OF DELAMINATED AREAS AS INDICATED IN DETAILS
C. REMOVE EXISTING CONCRETE BEYOND DELAMINATION TO SOUND CONCRETE, EXPOSING EXISTING REINFORCEMENT STEEL
PERIMETER AS INDICATED IN DETAILS
D. PROVIDE UNIFORM HORIZONTAL SURFACE BETWEEN ADJACENT BARS OR WIRES WHEN PARTIAL DEPTH CAVITY ENCOMPASSES
MORE THAN ONE BAR OR WIRE.
E. MECHANICALLY CLEAN ALL EXPOSED REINFORCEMENT STEEL AND OTHER EMBEDDED STEEL AND APPLY EPOXY MODIFIED
COATING TO STEEL AND OTHER METALS.
F. PROVIDE SPRAY OR BRUSH APPLIED BONDING AGENT TO EXCAVATED CAVITY SURFACE.
G. PROVIDE PATCH MATERIAL AS INDICATED IN REPAIR MATERIAL TABLE THIS SHEET.
H. FINISH OF UNFORMED CONCRETE PATCH SURFACES TO MATCH ADJACENT AREAS.
I. WHERE APPLICABLE, CHAMFER CORNERS TO MATCH ADJACENT AREAS.
J. CONCRETE PATCHES IN PAINTED SURFACES SHALL BE PAINTED TO MATCH ADJACENT AREAS. COST OF PAINTING TO BE
INCLUDED IN REPAIR COST.
K. NOMINAL SIZES OF MEMBERS ARE INDICATED ON DETAILS, ACTUAL SIZES MAY VARY.
L. NOMINAL PATCH DEPTHS ARE INDICATED ON DETAILS, ACTUAL DEPTH MAY VARY.
M. IF ANY OTHER PRE-EXISTING ITEMS ARE DAMAGED, THEY SHALL BE REPAIRED TO AN EQUAL OR BETTER CONDITION AS
ACCEPTABLE TO THE COR.
5. SPRAY WASH
A. SPRAY WASH THE FLOOR SURFACE TO REMOVE DUST, GRIME, DEBRIS, OIL, AND OTHER STAINS PRIOR TO PAINTING.
6. PAINTING TRAFFIC MARKINGS
A. PREPARATION OF SUBSTRATE SURFACES FOR PAINTING, BOTH EXISTING AND NEW SURFACES, ARE TO MEET THE
REQUIREMENTS OF THE SPECIFICATION AND THE MATERIAL MANUFACTURER.
B. SEE SPECIFICATIONS FOR SUBSTRATE REQUIREMENTS.
C. CONTRACTOR SHALL TAKE NECESSARY CARE TO PREVENT OVERSPRAY AND SPILLAGE.
CAST-IN-PLACE CONCRETE
1. ALL DESIGN AND REPAIRS SHALL BE IN ACCORDANCE WITH ACI 318-19, AND ACI GUIDE 362.1R-12. REFER TO SPECIFICATION
SECTION (03 30 00), CAST-IN-PLACE CONCRETE, FOR INFORMATION NOT LISTED HEREIN.
2. CONCRETE-ACI 362.1R TABLE 3.2 (ZONE 2)
A. READY MIXED/SITE BATCHED CONCRETE REPAIR MATERIAL
NOTES:
1. AVERAGE AIR-ENTRAINED VALUES ARE FOR IN-PLACE CONCRETE. TOLERANCE ON TOTAL AIR CONTENT IS 2% PER ACI.
ALL NORMAL WEIGHT CONCRETE TO HAVE A DENSITY OF APPROXIMATELY 145 PCF UNLESS NOTED.
2. SPA: DESIGNATES A CONCRETE MIX DESIGN IN ACCORDANCE WITH SPECIFICATION SECTION 033000 WHICH CONTAINS
GGBS BY WEIGHT OF CEMENT AND/OR FLY ASH BY WEIGHT OF CEMENT
3. CEMENT
A. ASTM C 150 TYPE I OR II
4. AGGREGATES
A. ASTM C 33
5. MILD REINFORCEMENT (ZONE 3/CC-2)
A. MILD REINFORCEMENT, ASTM A 615 GRADE 60
B. WELDED PLAIN WIRE FABRIC SHEETS, ASTM A 185, GRADE 65
C. CONCRETE PROTECTION SHALL BE PER ACI 362.1R, EXCEPT AS NOTED ON DRAWINGS AND SPECIFIED HEREIN.
6. GROUT / BONDING AGENT
A. PREMIXED, PACKAGED, NON-SHRINK, CHLORIDE-FREE, NON- STAINING, F'C = 6000 PSI MINIMUM, ASTM C 1107.
DESCRIPTION F'C PSI, MIX MAX W/C RATIO AVERAGE ENTRAINED AIR
VERTICAL REPAIRS 5000 SPA 0.45 6.5%
BEAM PATCH 5000 SPA 0.45 6.5%
SLAB PATCH 4500 SPA 0.50 6.5%
REPAIR MATERIAL TABLE
GENERAL CAST-IN-PLACE CONCRETE
1. REINFORCEMENT
A. MINIMUM LENGTH OF LAP SPLICES SHALL BE BASED ON ACI 318. CHAPTER 12 CLASS B OR A MINIMUM 36 X BAR
DIAMETER FOR UNCOATED BARS AND 54 X BAR DIAMETER FOR COATED BARS UNLESS NOTED OTHERWISE ON
DRAWINGS.
B. EXISTING REINFORCING STEEL SHALL NOT BE BENT OR STRAIGHTENED UNLESS APPROVED BY ENGINEER OR AS
INDICATED ON DRAWINGS.
C. FIELD CUTTING OF EXISTING REINFORCEMENT NOT CALLED OUT ON THE DRAWINGS IS PROHIBITED UNLESS
REVIEWED BY ENGINEER AND APPROVED BY COR.
D. WELDING OF REINFORCEMENT IS PROHIBITED UNLESS SPECIFICALLY CALLED FOR ON DRAWINGS OR REVIEWED
BY ENGINEER AND APPROVED BY COR.
2. ACCESSORIES
A. INSTALL INSERTS AND ANCHORS IN CONCRETE FOR SUSPENDING MECHANICAL AND ARCHITECTURAL ITEMS
WHERE FEASIBLE. IF ADDITIONAL FASTENERS ARE NEEDED IN CONVENTIONALLY REINFORCED CONCRETE, USE
DRILLED-IN TYPE ANCHORS LOCATED TO AVOID CONFLICT WITH REINFORCEMENT.
B. NO ALUMINUM CONDUIT OR PRODUCTS CONTAINING ALUMINUM OR ANY OTHER MATERIAL INJURIOUS TO THE
CONCRETE SHALL BE EMBEDDED IN CONCRETE.
3. JOINTS
A. PROVIDE A 3/4 INCH CHAMFER ON EXPOSED CORNERS OF CONCRETE UNLESS OTHERWISE INDICATED ON
DRAWINGS.
B. TOOL SLAB JOINTS AT TIME OF FINISHING. WET SAW CUTTING IS NOT ALLOWED UNLESS REVIWED BY ENGINEER
AND APPROVED BY COR AND PROVIDED WATER IS PROMPTLY VACUUMED/COLLECTED BELOW.
C. CONSTRUCTION JOINTS FOR REPAIR WORK ON SUPPORTED SLABS SHALL MATCH EXISTING JOINT LOCATIONS OR
AS REVIEWED BY THE ENGINEER AND APPROVED BY COR.
4. USE OF CHLORIDES SUCH AS DEICING SALTS ARE PROHIBITED FOR USE OF MELTING ICE PRIOR TO PLACEMENT OF
CONCRETE.
THERMAL AND MOISTURE PROTECTION
1. JOINT SEALANTS
A. ALL JOINTS BETWEEN DISSIMILAR STRUCTURAL MEMBERS SHALL BE PROPERLY PREPARED AND FILLED WITH
JOINT SEALANT UNLESS NOTED OTHERWISE. ALL JOINT EDGES, INCLUDING TOP AND BOTTOM SURFACES AND VERTICAL AND HORIZONTAL SURFACES, SHALL BE FORMED OR TOOLED AS REQUIRED. JOINT SEALANT SHALL BE APPLIED ONLY TO TOP, VERTICAL, AND HORIZONTAL SURFACES UNLESS NOTED OTHERWISE ON DRAWINGS.
B. JOINTS TO BE PREPARED AND FILLED WITH JOINT SEALANT SHALL INCLUDE, BUT ARE NOT LIMITED TO, EXISTING CONSTRUCTION JOINTS, NEW FULL DEPTH PATCH PERIMETERS, AND NEW CONSTRUCTION JOINTS. SPECIFIC LOCATIONS MAY BE INDICATED ON DRAWINGS OR MAY OCCUR DUE TO CONSTRUCTION SEQUENCE SELECTED BY
CONTRACTOR.
SPECIALTY STRUCTURAL ENGINEERING (SSE)
A SPECIALTY STRUCTURAL ENGINEER IS DEFINED AS A PROFESSIONAL ENGINEER LICENSED IN THE STATE THAT THE PROJECT IS LOCATED, NOT THE STRUCTURAL ENGINEER OF RECORD, WHO PERFORMS STRUCTURAL ENGINEERING FUNCTIONS NECESSARY FOR THE STRUCTURE TO BE COMPLETED AND WHO HAS SHOWN EXPERIENCE AND/OR TRAINING IN THE SPECIFIC SPECIALITY.
IT IS THE SPECIALTY STRUCTURAL ENGINEER'S RESPONSIBILITY TO REVIEW THE CONSTRUCTION DRAWINGS AND SPECIFICATIONS TO
DETERMINE THE APPROPRIATE SCOPE OF ENGINEERING.
IT IS THE INTENT OF THE DRAWINGS AND SPECIFICATIONS TO PROVIDE SUFFICIENT INFORMATION FOR THE SPECIALTY STRUCTURAL ENGINEER (SSE) TO PERFORM THEIR DESIGN AND ANALYSIS. IF THE SSE DETERMINES THERE ARE DETAILS, FEATURES, OR UNANTICIPATED PROJECT LIMITS WHICH CONFLICT WITH THE ENGINEERING REQUIREMENTS AS DESCRIBED IN THE PROJECT DOCUMENTS, THE SSE SHALL IN A TIMELY MANNER, CONTACT THE STRUCTURAL ENGINEER OF RECORD FOR RESOLUTION OF
CONFLICTS.
THE SPECIALTY STRUCTURAL ENGINEER (SSE) SHALL FORWARD DOCUMENTS TO THE STRUCTURAL ENGINEER OF RECORD FOR
REVIEW. SUCH DOCUMENTS SHALL BEAR THE STAMP OF THE SSE AND INCLUDE:
1. DRAWINGS INTRODUCING ENGINEERING INPUT, SUCH AS DEFINING THE CONFIGURATION OR STRUCTURAL CAPACITY
OF STRUCTURAL COMPONENTS AND/OR THEIR ASSEMBLY INTO STRUCTURAL…