506-18-102 Upgrade Electrical Swithgear Bid Set.pdf

PDF 21 MB Posted

Attached to
Z1DA--506-18-102 Upgrade Electrical Switchgear Distribution Federal contract opportunity
Solicitation number
36C25020B0057
Issued by
Department of Veterans Affairs Veterans Health Administration Veterans Integrated Service Network 10

About this file

This pre-solicitation announcement describes an upcoming Invitation for Bid for an electrical upgrade project. The Department of Veterans Affairs will replace the existing 4800V primary distribution system at the Ann Arbor VA Medical Center with a new 13.2kV system, reusing the existing 4800V cabling. A Firm Fixed Price contract valued between $2-5 million will be awarded within 120 days of bid receipt to furnish all labor, materials, equipment, permits and supervision necessary to upgrade the switchgear and distribution. Interested contractors must register at beta.SAM.gov and the solicitation containing specifications, forms and drawings will be available there on or around July 6th, with the bid due date specified in those documents. All work must comply with privacy training requirements and be completed within 570 days.

View the file

Other files for this federal contract opportunity

Other files attached to Z1DA--506-18-102 Upgrade Electrical Switchgear Distribution, newest first.
File Type Posted
36C25020B0057 0001.docx DOCX document
Pre-Bid Attendance 506-18-102.pdf PDF
506-18-102 - RFIs answers.docx DOCX document
Covid Instructions.docx DOCX document
RFI Form 506 18 102.docx DOCX document
506-18-102 Specs Vol 1 - Ann Arbor VA Upgrade Switchgear.pdf PDF
36C25020B0057_3.docx DOCX document
506-18-102 Specs Vol 2 - Ann Arbor VA Upgrade Switchgear.pdf PDF
_WD MI20200100 7-24-20.pdf PDF
506-18-102 Contractor EMR Certification Form 2020.docx DOCX document

On GovTribe

Work with this file on GovTribe

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

GUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46204

317.800.6388

ELECTRICAL ENGINEER:

GHAFARI ASSOCIATES

17101 MICHIGAN AVE.

DEARBORN, MI 48126

313.331.3000

UPGRADE ELECTRICAL

SWITCHGEAR & DISTRIBUTION

ANN ARBOR VAMC

506-18-102

N/A Project Director

11/19/19 SLP DSMRevisions: Date:

SUITE 200

S

T

A

T

E

O

F M

I

C

H

I

G

A

N

L I C

E

N

S

D

P

R

O

F

E

SS

I O

N

A

L

N

G

I

N

E

E R

GI000

COVER SHEET

PROJECT SITE

AREA MAP

VICINITY MAP

SHEET

NUMBER SHEET NAME

GENERAL

GI000 COVER SHEET

DEPARTMENT OF VETERANS AFFAIRS

ANN ARBOR VA MEDICAL CENTER

ANN ARBOR, MICHIGAN

UPGRADE ELECTRICAL SWITCHGEAR

AND DISTRIBUTION

Contact:

GHAFARI ASSOCIATES

ELECTRICAL

ENGINEER

GUIDON DESIGN INC.

CIVIL

ENGINEER

ANN ARBOR VA MEDICAL CENTER

Jeff Means Project COR

2215 Fuller Road Ann Arbor, MI 48105 p: 735.222.4345 e: Jeff.Means@va.gov

OWNER

17101 Michigan Avenue Dearborn, MI 48126 p:313.441.3000

1221 N. Pennsylvania Avenue Suite 200 Indianapolis, IN 46202 p: 317.800.6388

100% CONSTRUCTION DOCUMENTS

SHEET LIST

GI001 GENERAL NOTES SHEET

OVERALL SITE PLAN

SWITCHGEAR DEMOLITION PLAN

SWITCHGEAR SITE DEVELOPMENT PLAN

BUILDING 22 TRANSFORMER DEMOLITION AND SITE PLAN

BUILDING 28 TRANSFORMER DEMOLITION AND SITE PLAN

LINAC BUILDING TRANSFORMER DEMOLITION AND SITE PLAN

DETAIL SHEET

DETAIL SHEET

GRADING PLAN

CIVIL

CC001

CD101

CS101

CS102

CS103

CS104

CS501

CS502

CG101

ELECTRICAL SYMBOLS LIST

ELECTRICAL GENERAL NOTES AND ABBREVIATIONS

ELECTRICAL COMPOSITE SITE PLAN - DEMOLITION

ELECTRICAL ENLARGED PLAN BUILDING 1 - WEST

ELECTRICAL ONE LINE DIAGRAM - DEMOLITION

ELECTRICAL COMPOSITE SITE PLAN

ELECTRICAL ENLARGED PLAN BUILDING 1 - WEST

ELECTRICAL ENLARGED PLAN BUILDING 22

ELECTRICAL ENLARGED PLAN BUILDING 28

ELECTRICAL ENLARGED PLAN LINEAR ACCELERATOR

ELECTRICAL DETAILS

ELECTRICAL ONE LINE DIAGRAM MV POWER DISTRIBUTION

ELECTRICAL ONE LINE DIAGRAM SWITCHBOARDS 1-A & 1-B

ELECTRICAL ONE LINE DIAGRAM SWITCHBOARDS 2-A & 2-B

ELECTRICAL ONE LINE DIAGRAM SWITCHBOARDS 3-A & 3-B

ELECTRICAL

EE001

EE002

ED101

ED401

ED601

ES101

ES401

ES402

ES403

ES404

ES501

EP601

EP602

EP603

EP604

Contact:

Stacey Paul Project Manager

Contact:

Jeff Pedersen

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

GUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46204

317.800.6388

ELECTRICAL ENGINEER:

GHAFARI ASSOCIATES

17101 MICHIGAN AVE.

DEARBORN, MI 48126

313.331.3000

UPGRADE ELECTRICAL

SWITCHGEAR & DISTRIBUTION

ANN ARBOR VAMC

506-18-102

N/A Project Director

11/19/19 SLP DSMRevisions: Date:

SUITE 200

S

T

A

M

I

C

H

I

G

A

N

L I C

E

N

S

O

F

E

SS

I O

N

G

I

N

E

E R

GI001

GENERAL NOTES SHEET

BLDG. 1-W

BLDG. 22

BLDG. 1-W

BLDG. 28

AMBULANCE

ENTRANCE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

GUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46204

317.800.6388

ELECTRICAL ENGINEER:

GHAFARI ASSOCIATES

17101 MICHIGAN AVE.

DEARBORN, MI 48126

313.331.3000

UPGRADE ELECTRICAL

SWITCHGEAR & DISTRIBUTION

ANN ARBOR VAMC

506-18-102

N/A Project Director

11/19/19 SLP DSMRevisions: Date:

SUITE 200

S

T

A

M

I

C

H

I

G

A

N

L I C

E

N

S

O

F

E

SS

I O

N

G

I

N

E

E R

N

0 8040

CC001

OVERALL SITE PLAN

AMBULANCE

ENTRANCE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

GUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46204

317.800.6388

ELECTRICAL ENGINEER:

GHAFARI ASSOCIATES

17101 MICHIGAN AVE.

DEARBORN, MI 48126

313.331.3000

UPGRADE ELECTRICAL

SWITCHGEAR & DISTRIBUTION

ANN ARBOR VAMC

506-18-102

N/A Project Director

11/19/19 SLP DSMRevisions: Date:

SUITE 200

S

T

A

M

I

C

H

I

G

A

N

L I C

E

N

S

O

F

E

SS

I O

N

G

I

N

E

E R

N

0 105

CD101

SWITCHGEAR DEMOLITION PLAN

ENTRANCE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

GUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46204

317.800.6388

ELECTRICAL ENGINEER:

GHAFARI ASSOCIATES

17101 MICHIGAN AVE.

DEARBORN, MI 48126

313.331.3000

UPGRADE ELECTRICAL

SWITCHGEAR & DISTRIBUTION

ANN ARBOR VAMC

506-18-102

N/A Project Director

11/19/19 SLP DSMRevisions: Date:

SUITE 200

S

T

A

M

I

C

H

I

G

A

N

L I C

E

N

S

O

F

E

SS

I O

N

G

I

N

E

E R

N

0 105

CS101

SWITCHGEAR SITE DEVELOPMENT

PLAN

BLDG. 22

BLDG. 22

BLDG. 1-W

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

GUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46204

317.800.6388

ELECTRICAL ENGINEER:

GHAFARI ASSOCIATES

17101 MICHIGAN AVE.

DEARBORN, MI 48126

313.331.3000

UPGRADE ELECTRICAL

SWITCHGEAR & DISTRIBUTION

ANN ARBOR VAMC

506-18-102

N/A Project Director

11/19/19 SLP DSMRevisions: Date:

SUITE 200

S

T

A

M

I

C

H

I

G

A

N

L I C

E

N

S

O

F

E

SS

I O

N

G

I

N

E

E R

N

0 105

BUILDING 22 TRANSFORMER

DEMOLITION AND SITE PLAN

CS102

0 105

BLDG. 28

BLDG. 28

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

GUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46204

317.800.6388

ELECTRICAL ENGINEER:

GHAFARI ASSOCIATES

17101 MICHIGAN AVE.

DEARBORN, MI 48126

313.331.3000

UPGRADE ELECTRICAL

SWITCHGEAR & DISTRIBUTION

ANN ARBOR VAMC

506-18-102

N/A Project Director

11/19/19 SLP DSMRevisions: Date:

SUITE 200

S

T

A

M

I

C

H

I

G

A

N

L I C

E

N

S

O

F

E

SS

I O

N

G

I

N

E

E R

N

0 105

N

0 105

CS103

BUILDING 28 TRANSFORMER

DEMOLITION AND SITE PLAN

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

GUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46204

317.800.6388

ELECTRICAL ENGINEER:

GHAFARI ASSOCIATES

17101 MICHIGAN AVE.

DEARBORN, MI 48126

313.331.3000

UPGRADE ELECTRICAL

SWITCHGEAR & DISTRIBUTION

ANN ARBOR VAMC

506-18-102

N/A Project Director

11/19/19 SLP DSMRevisions: Date:

SUITE 200

S

T

A

M

I

C

H

I

G

A

N

L I C

E

N

S

O

F

E

SS

I O

N

G

I

N

E

E R

N 0 105

N

0 105

CS104

LINAC BUILDING TRANSFORMER

DEMOLITION AND SITE PLAN

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

GUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46204

317.800.6388

ELECTRICAL ENGINEER:

GHAFARI ASSOCIATES

17101 MICHIGAN AVE.

DEARBORN, MI 48126

313.331.3000

UPGRADE ELECTRICAL

SWITCHGEAR & DISTRIBUTION

ANN ARBOR VAMC

506-18-102

N/A Project Director

11/19/19 SLP DSMRevisions: Date:

SUITE 200

S

T

A

M

I

C

H

I

G

A

N

L I C

E

N

S

O

F

E

SS

I O

N

G

I

N

E

E R

CS501

DETAIL SHEET

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

GUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46204

317.800.6388

ELECTRICAL ENGINEER:

GHAFARI ASSOCIATES

17101 MICHIGAN AVE.

DEARBORN, MI 48126

313.331.3000

UPGRADE ELECTRICAL

SWITCHGEAR & DISTRIBUTION

ANN ARBOR VAMC

506-18-102

N/A Project Director

11/19/19 SLP DSMRevisions: Date:

SUITE 200

S

T

A

M

I

C

H

I

G

A

N

L I C

E

N

S

O

F

E

SS

I O

N

G

I

N

E

E R

CS502

DETAIL SHEET

ENTRANCE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

100% CONSTRUCTION

DOCUMENTS

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

GUIDON DESIGN, INC.

1221 N. PENNSYLVANIA STREET

INDIANAPOLIS, IN 46204

317.800.6388

ELECTRICAL ENGINEER:

GHAFARI ASSOCIATES

17101 MICHIGAN AVE.

DEARBORN, MI 48126

313.331.3000

UPGRADE ELECTRICAL

SWITCHGEAR & DISTRIBUTION

ANN ARBOR VAMC

506-18-102

N/A Project Director

11/19/19 SLP DSMRevisions: Date:

SUITE 200

S

T

A

M

I

C

H

I

G

A

N

L I C

E

N

S

O

F

E

SS

I O

N

G

I

N

E

E R

N

0 105

GRADING PLAN

CG101

EE001

ELECTRICAL SYMBOLS LIST

M.

SABAPATHY

F. KHAN11/18/19

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

GUIDON DESIGN, INC.

1221 N. PENNSYLVAINA STREET

INDIANAPOLIS, IN 46204

317.800.6388

STACEY PAUL

ELECTRICAL ENGINEER:

GHAFARI ASSOCIATES

17101 MICHIGAN AVE.

DEARBORN, MI 48126

UPGRADE ELECTRICAL

SWITCHGEAR & DISTRIBUTION

ANN ARBOR VAMC

506-18-102

N/A Project Director

Revisions: Date:

SUITE 200

PROJECT NUMBER: 187371

313.441.3000

JEFF PEDERSEN

J J

PANEL;CIRCUIT

SINGLE RECEPTACLE - WALL, CEILING, FLOOR

RECEPTACLE, 220V, 3 PHASE - SINGLE, DUPLEX

CONDUIT UP

GROUND ROD

CONDUIT HOME RUN TO PANEL

CONDUIT RUN

UNDERGROUND GROUND WIRE

UNDERGROUND TELECOMMUNICATIONS CONDUIT / DUCT BANK

UNDERGROUND ELECTRICAL CONDUIT / DUCT BANK

JUNCTION BOX

DUPLEX RECEPTACLE - WALL, CEILING, FLOOR

DOUBLE DUPLEX RECEPTACLE - WALL, CEILING, FLOOR

RECEPTACLE, 240/208V, 3 PHASE - WALL, FLOOR

RECEPTACLE, 480V, 3 PHASE - WALL, FLOOR

PULL BOX

GROUND TEST WELL

CADWELD CABLE CONNECTION

GROUND BUS

PB

GROUNDING SYMBOL LIST (ALL MAY NOT APPLY)

WIRING SYMBOL LIST (ALL MAY NOT APPLY)

POWER SYMBOL LIST (ALL MAY NOT APPLY)

G

T

E

GFR

CAPACITOR

VALUE AS

INDICATED

ON

DRAWINGS

V

G

A

MOUNTING HEIGHTS (ALL MAY NOT APPLY)

SINGLE LINE DIAGRAM SYMBOL LIST

(ALL MAY NOT APPLY)

TOGGLE SWITCHES - GENERAL 4'-0" AFF

RECEPTACLES - FINISHED AREAS 1'-6" AFF

RECEPTACLES - NON FINISHED AREAS 4'-0" AFF

PUSHBUTTONS 4'-6" AFF

DISCONNECT SWITCHES 5'-6" AFF

MOTOR STARTERS 5'-6" AFF

PANELS & CABINETS 6'-0" TO TOP

INDIVIDUAL CIRCUIT BREAKERS 5'-6" TO TOP

MOUNTING HEIGHT NOTES:

1. ALL ELEVATIONS ARE TO CENTER LINE OF DEVICE

UNLESS NOTED OTHERWISE.

2. PENDANT LIGHTING FIXTURE MOUNTING HEIGHTS ARE TO THE

BOTTOM OF THE FIXTURE UNLESS NOTED OTHERWISE.

3. CEILING SURFACE LIGHTING FIXTURE MOUNTING HEIGHTS ARE TO

THE TOP OF THE FIXTURE UNLESS NOTED OTHERWISE.

4. WALL LIGHTING FIXTURE MOUNTING HEIGHTS ARE TO THE BOTTOM

OF THE FIXTURE UNLESS NOTED OTHERWISE.

CONTACTOR - NORMALLY OPEN

CONTACTOR - NORMALLY CLOSED

LINE TERMINATOR

ELECTRICAL CONNECTOR

GROUND

FUSE

DISCONNECT SWITCH

TRANSFORMER

JAGGED RESISTOR

VOLTAGE REGULATOR

3-PHASE MOTOR

WYE CONNECTION

SERVICE WEATHERHEAD

METER

CONTROL TRANSFORMER

POTENTIAL TRANSFORMER

CURRENT TRANSFORMER

CABLE POT HEAD

CIRCUIT BREAKER

DELTA CONNECTION

BATTERY

SURGE ARRESTOR

DRAW OUT, LOW VOLTAGE CIRCUIT BREAKER

GROUND FAULT RELAY

AUTOMATIC TRANSFER SWITCH

H.R.C FUSE RATING AS INDICATED ON DRAWING

RATINGS AS INDICATED ON DRAWING

H.R.C FUSED CUT-OUT

SURGE PROTECTION DEVICE

LIGHTNING ARRESTOR

POWER FACTOR CORRECTION CAPACITOR BANK

POTENTIAL TRANSFORMER WITH PRIMARY

AND SECONDARY FUSES

FULL VOLTAGE NON-REVERSIBLE MOTOR

STARTER AND OVERLOAD RELAY,

MOUNTED IN MOTOR CONTROL CENTER

REDUCED VOLTAGE (STAR/DELTA) NON-REVERSIBLE

MOTOR STARTER AND OVERLOAD RELAY, MOUNTED

IN MOTOR CONTROL CENTER

OVERLOAD RELAY

KEY INTERLOCK

AMMETER, VOLTMETER

AMMETER, VOLTMETER SELECTOR SWITCH

INDICATOR LAMP

STAND-BY DIESEL GENERATOR SET

POWER METER

ADDRESSABLE ELECTRONIC MODULE

DRAW OUT, MEDIUM VOLTAGE VACUUM

CIRCUIT BREAKER (VCB)

M

SPD

ASS VSS

K

AEM

PP

CP

VFD

M

DCP

POWER POLE

ELECTRICAL EQUIPMENT (TYPE OF EQUIPMENT AS INDICATED ON DRAWINGS)

RECESSED ELECTRICAL PANEL

SURFACE MOUNTED ELECTRICAL PANEL

CONTROL PANEL

DOOR CONTROL PANEL

COMBINATION DISCONNECT SWITCH / MOTOR STARTER

FUSED DISCONNECT SWITCH

NON-FUSED DISCONNECT SWITCH

SINGLE-PHASE MOTOR

THREE-PHASE MOTOR

MOTOR STARTER

VARIABLE FREQUENCY DRIVE

PUSHBUTTON - 2 BUTTON, W/ PILOT LIGHT

PUSHBUTTON - 3 BUTTON, W/ PILOT LIGHT

PUSHBUTTON - EMERGENCY OFF

ELECTRICAL BUS DUCT WITH FUSIBLE BUS PLUGS

UTILITY METER

PUSHBUTTON - 1 BUTTON, W/ PILOT LIGHT

RECEPTACLE, 240/208V, 3 PHASE, W/DISCONNECT - FUSED,

W/DISCONNECT - NON-FUSED - WALL

RECEPTACLE, 480V, 3 PHASE, W/DISCONNECT - FUSED,

W/DISCONNECT - NON-FUSED - WALL

MANUAL MOTOR STARTER

HOT

CONDUCTOR

GROUND

CONDUCTOR

NEUTRAL

CONDUCTOR

RECEPTACLE IDENTIFIERS:

"A" ABOVE COUNTER

"GFCI" GROUND FAULT CIRCUIT INTERRUPTER

"IG" ISOLATED GROUND

"PT" POKE THRU

"WP" WEATHERPROOF

"XP" EXPLOSION PROOF

SHUNT TRIP

ST

PM

1-PHASE MOTOR

EXISTING

NEW

LINETYPE LEGEND (ALL MAY NOT APPLY)

INSTANTANEOUS OVER CURRENT

OR DEFINITE TIME RELAY

INVERSE TIME OVER CURRENT RELAY

GROUND INSTANTANEOUS AND TIME

OVER CURRENT RELAY

50G/51G

ANSI RELAY DESIGNATIONS (ALL MAY NOT APPLY)

POWER FACTOR RELAY55

UNDERVOLTAGE RELAY27

OVERVOLTAGE PROTECTION RELAY59

FREQUENCY PROTECTION RELAY

74TC

LOCKOUT RELAY

DIFFERENTIAL PROTECTION RELAY87

DEMOLITION

CONDUIT DOWN

FIXED CAPACITOR

UNDERGROUND ELECTRICAL CONDUIT

CABLE TRAY (TYPE AND SIZE INDICATED ON DRAWINGS)

CABLE TRAY UP OR DOWN OR SECTION CUT

CR CORD REEL RECEPTACLE

COMBINATION FUSED DISCONNECT SWITCH / MOTOR STARTER

TB TEST BLOCK

TRIP CIRCUIT SUPERVISION

CIRCUIT BREAKER FAILURE PROTECTION

50BF

SENSITIVE GROUND CURRENT PROTECTION

50NS

CIRCUIT METER AND MONITORCMM

100% CONSTRUCTION

DOCUMENTS SUBMISSION

G

DATA OUTLET - WALL / FLOOR MOUNTED

AUXILIARY SYSTEMS SYMBOL LIST (ALL MAY NOT APPLY)

EWHITMAN

Image

EE002

ELECTRICAL GENERAL NOTES

AND ABBREVIATIONS

M.

SABAPATHY

F. KHAN

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

GUIDON DESIGN, INC.

1221 N. PENNSYLVAINA STREET

INDIANAPOLIS, IN 46204

317.800.6388

STACEY PAUL

ELECTRICAL ENGINEER:

GHAFARI ASSOCIATES

17101 MICHIGAN AVE.

DEARBORN, MI 48126

UPGRADE ELECTRICAL

SWITCHGEAR & DISTRIBUTION

ANN ARBOR VAMC

506-18-102

N/A Project Director

Revisions: Date:

SUITE 200

PROJECT NUMBER: 187371

313.441.3000

JEFF PEDERSEN

GENERAL NOTES:

ABBREVIATIONS

A

AFF

AFG

AHJ

AL

ATS

C

COMM

CP

CTRL

CU

DPM

ECC

EF

E.O

ER

ERR

FTV

G

GB

GFCI

HP

Hz

I.C

KA

KVA

LSIG

M

MAX

MCB

MIN

MLO

NC

NIC

NB

NO

P

PH

POS

PWR

RECEP

RGS

TR

TRU

UNO

V

W

WP

WAP

XP

AMPERES

ABOVE FINISHED FLOOR

ABOVE FINISHED GRADE

AUTHORITY HAVING JURISDICTION

ALUMINUM

AUTOMATIC TRANSFER SWITCH

CONDUIT

COMMUNICATIONS

CONTROL PANEL

CONTROL

COPPER

DIGITAL PANEL METER

EMPTY CONDUIT

EXHAUST FAN

ELECTRICALLY OPERATED

EXISTING REMOVE

EXISTING REMOVE REPLACE

FLIGHT TEST VEHICLE

GROUND

GROUND BUS

GROUND FAULT CIRCUIT INTERRUPTER

HORSEPOWER

HERTZ

INTERRUPTING CURRENT

KILO AMPERES

KILOVOLT-AMPERES

LONG TERM, SHORT TERM,

INSTANTANEOUS AND GROUND FAULT

PROTECTION RELAY

METER

MAXIMUM

MAIN CIRCUIT BREAKER

MINIMUM

MAIN LUGS ONLY

NORMALLY CLOSED

NOT IN CONTRACT

NEUTRAL BUS

NORMALLY OPEN

POLE

PHASE

POSITION

POWER

RECEPTACLE

RIGID GALVANIZED STEEL

TRANSFORMER

TRANSFORMER RECTIFIER UNIT

UNLESS NOTED OTHERWISE

VOLT

WIRE

WEATHER PROOF

WIRELESS ACCESS POINT

EXPLOSION PROOF

(ALL MAY NOT APPLY)

1. THE EXISTING SERVICE AGED CABLES THAT ARE BEING SLATED FOR RE-USE ARE RATED

FOR 15KV . THIS DETERMINATION HAS BEEN MADE BY VA.

2. ALL THE SERVICE AGED CABLES, SLATED FOR RE-USE, SHALL BE TESTED IN SITU USING

ONE OF THE FOLLOWING NON-DESTRUCTIVE TESTS:

a. ON-LINE PARTIAL DISCHARGE TESTING.

b. OFF-LINE PARTIAL DISCHARGE TESTING.

c. VERY LOW FREQUENCY (VLF) DISSIPATION FACTOR TESTING.

d. POWER FACTOR/DISSIPATION FACTOR TESTING.

3. ALL OR ANY PORTION OR PART OF THE SERVICE AGED CABLE THAT DOESN'T PASS ONE OF

THE ABOVE TESTS SHALL BE REPLACED IN KIND WITH PRIOR AND SPECIFIC WRITTEN

APPROVAL FROM THE COR AND CO THROUGH A FORMAL CONTRACT MODIFICATION. THE

NEW CABLE AND/OR SPLICE(S) SHALL COMPLY WITH THE SPECIFICATIONS.

4. THE CONTRACTOR SHALL COORDINATE ALL POWER OUTAGES WITH THE COR AT LEAST

TWO WEEKS IN ADVANCE. POWER OUTAGES SHALL BE RESTRICTED TO THE HOURS THAT

ARE NOT NORMAL BUSINESS HOURS. SEE NOTE #8 BELOW.

5. ONLY ONE OF THE THREE (3) 208Y/120V SWITCHBOARDS, #1, #2 AND #3, SHALL BE

REPLACED. AT A TIME, SO THAT BUILDING 1-WEST'S OPERATIONS AREN'T ADVERSELY

AFFECTED. ALSO, REFER TO NOTE #8 BELOW.

6. THE CONTRACTOR SHALL PROVIDE A SEQUENCE OF WORK SHOWING ALL PHASING, AS

NECESSARY, ALONG WITH THEIR BID, FOR THE COR'S AND ENGINEER'S APPROVAL.

7. ALL POWER OUTAGES SHALL BE COORDINATED TO MINIMIZE TO AN ABSOLUTE MINIMUM

HOW LONG AREAS OF THE FACILITY WILL BE WITHOUT NORMAL POWER. SEE NOTE #8

BELOW. ALSO, REFER TO NOTE #8 BELOW

8. WHERE ANY SCHEDULED POWER OUTAGE RESULTS IN A LOSS OF SERVICE FOR LONGER

THAN FOUR (4) HOURS, THE CONTRACTOR SHALL PROVIDE TEMPORARY POWER TO

SERVICE THE FACILITY SUCH THAT TOTAL POWER OUTAGE AT THE FACILITY SHALL NOT

EXCEED FOUR (4) HOURS.

IMPORTANT NOTES:

1. SCOPE OF WORK: ELECTRICAL DEMOLITION WORK SHALL INCLUDE DISCONNECTION OF

ELECTRICAL EQUIPMENT, WIRING, CONDUIT, BOXES, ETC. IN THE AREA OF NEW AND/OR

RENOVATION CONSTRUCTION.

2. SITE SURVEY: ELECTRICAL CONTRACTOR SHALL VISIT THE SITE PRIOR TO SUBMISSION

OF THEIR BID TO EXAMINE THE EXISTING CONDITIONS AND THE EXTENT OF THE

DEMOLITION WORK.

3. SITE UTILITIES: ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR LOCATING ALL EXISTING

UTILITIES. ELECTRICAL CONTRACTOR IS RESPONSIBLE FOR REQUESTING EXISTING

AVAILABLE AS-BUILT DRAWINGS FROM THE OWNER. ELECTRICAL CONTRACTOR IS FULLY

RESPONSIBLE FOR REPAIRING ALL DAMAGED UTILITIES RESULTING FROM

CONSTRUCTION RELATED ACTIVITIES.

4. COORDINATION WITH OTHER TRADES: EXAMINE ALL DRAWINGS BY OTHER TRADES TO BE

FAMILIAR WITH DEMOLITION REQUIREMENTS BY OTHER TRADES. PROVIDE ALL

INCIDENTAL ELECTRICAL DEMOLITION OF AND/OR RELOCATION OF ELECTRICAL SYSTEMS

TO FACILITATE THE DEMOLITION WORK FROM OTHER TRADES WHETHER OR NOT

INDICATED ON THE DRAWINGS.

5. COORDINATION: COORDINATE THE DEMOLITION WITH THE NEW WORK FOR THE EXTENT

OF DEMOLITION WORK.

6. RACEWAYS: REMOVE ALL UNUSED EXPOSED CONDUIT, WIRE, RACEWAY, JUNCTION

BOXES, HANGERS, AND CLAMPS BACK TO THE SOURCE. WHERE CONDUITS ARE

CONCEALED IN WALL CAVITIES, CUT AND REMOVE THE CONDUITS ABOVE EXISTING WALL

LEADING INTO AN ACCESSIBLE CEILING OR TRUSS SPACE. REMOVE SURFACE MOUNTED

ELECTRICAL DEVICES, BOXES, AND RELATED CONDUITS.

7. CONDUIT STATUS: FIELD VERIFY STATUS OF CONDUITS IN THE SPACE AND DETERMINE IF

CONDUITS ARE TO REMAIN OR BE REMOVED. WHERE APPLICABLE AND NOT

SPECIFICALLY INDICATED OTHERWISE, EXISTING IN-PLACE CONDUITS ABOVE CEILINGS

OR IN WALLS, JUNCTION BOXES, PULL BOXES, AND HANGERS ABOVE CEILINGS, TRUSS

SPACE, OR IN WALLS MAY BE RE-USED FOR NEW WIRING. COMPLY WITH CONDUIT FILL

REQUIREMENTS LISTED IN THE NEC.

8. ACTIVE CIRCUITS: EXISTING ACTIVE CIRCUITS IN WORK AREAS TO REMAIN. WHERE

REMOVAL OF CONDUIT AND WIRING AFFECTS THE OPERATION UPSTREAM AND/OR

DOWNSTREAM OF ELECTRICAL EQUIPMENT, WHICH IS NOT INDICATED TO BE REMOVED,

THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE TO MAINTAIN AND PROVIDE ALL

REQUIRED CONDUITS AND WIRING TO RESTORE THE UPSTREAM AND/OR DOWNSTREAM

CONNECTIONS OF ELECTRICAL EQUIPMENT TO ITS NORMAL OPERATION. ELECTRICAL

CONTRACTOR SHALL COORDINATE THIS WITH OWNER AND ASSOCIATED PARTIES.

9. FEEDERS: DISCONNECT AND REMOVE FEEDERS FROM THE ARCHITECTURAL AND

MECHANICAL EQUIPMENT TO BE REMOVED. COORDINATE WITH ARCHITECTURAL AND

MECHANICAL DRAWINGS AND CONTRACTORS FOR FULL SCOPE OF WORK. REMOVE ALL

DISCONNECTS, JUNCTION BOXES, AND CONTROL STATIONS.

10. LOW VOLTAGE CABLING: REMOVE UNUSED DATA/COMMUNICATION CONDUITS AND

CABLING COMING FROM TELEPHONE AND DATA CLOSETS. CONDUITS THAT ARE EXISTING

TO REMAIN SHALL BE TAGGED AS SUCH.COORDINATE WITH THE COR.

11. SUPPORT: RE-SUPPORT ITEMS WHERE WALLS AND SUPPORTS ARE SCHEDULED FOR

REMOVAL.

12. PROTECTION: PROTECT EXISTING ITEMS TO REMAIN FROM DAMAGE BY OTHER

DEMOLITION ACTIVITIES.

13. MATERIAL: MATERIAL INCLUDING, BUT NOT LIMITED TO, WIRING DEVICES, CONDUIT,

WIRING, JUNCTION BOXES, ETC. THAT IS REMOVED SHALL BECOME PROPERTY OF THE

ELECTRICAL CONTRACTOR, UNLESS OTHERWISE NOTED. THE ELECTRICAL CONTRACTOR

SHALL BE RESPONSIBLE FOR REMOVAL AND PROPER DISPOSAL OF THESE MATERIALS.

14. SALVAGED EQUIPMENT: ELECTRICAL EQUIPMENT INCLUDING, BUT NOT LIMITED TO,

PANELBOARD, TRANSFORMERS, LIGHT FIXTURES, DISCONNECT SWITCHES, CONTROL

PANELS, ETC. THAT IS REMOVED SHALL BE CLEANED AND RETURNED TO THE COR,

UNLESS THE COR ELECTS TO DISPOSE OF THIS EQUIPMENT.

DEMOLITION NOTES:

1. ALL ELECTRICAL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE

2017 WITH STATE OF MICHIGAN AMENDMENTS (PART 8).

2. DRAWINGS ARE DIAGRAMMATICAL AND INDICATE DESIGN INTENT.

3. DO NOT SCALE DRAWINGS.

4. CONTRACTOR SHALL FIELD VERIFY EXISTING CONDITIONS AND ACTUAL DIMENSIONS PRIOR TO START OF

WORK.

5. THOROUGHLY COORDINATE ELECTRICAL WORK WITH OTHER TRADES TO AVOID PHYSICAL CONFLICTS AND

CONFLICTS WITH WORK SEQUENCE.

6. ALL WIRING SHALL BE #12 AWG UNLESS OTHERWISE NOTED, BRANCH CIRCUITS WITH LENGTH EXCEEDING

150FT SHALL BE #10 AWG MINIMUM.

7. ALL CONDUITS SHALL CONTAIN GROUND WIRE, SIZED PER NEC 2017, ART. 250.

8. ALL CONDUIT AND WIRING SHALL BE CONCEALED IN WALL OR CEILING CAVITY EXCEPT FOR EXISTING

BLOCK WALLS, AREAS WITH EXPOSED CEILING CONSTRUCTION. EXPOSED CONDUIT SHALL BE RGS UP TO

10 FT HEIGHT ABOVE FINISHED FLOOR, WHERE MOUNTED EXPOSED.

9. THE ELECTRICAL CONTRACTOR MAY, AT THEIR OPTION, REUSE A PORTION OR ALL OF EXISTING

MULTI-BRANCH CIRCUIT WIRING AND/OR CONDUIT(S) PROVIDED THEY MEET ALL THE REQUIREMENTS OF

THE NEW INSTALLATIONS (I.E., APPROPRIATE ROUTING, CONDUIT SIZE, CONDUIT TYPE, WIRE SIZE FOR

LENGTH WITH DERATING, TESTING ETC.).

10. BRANCH CIRCUIT WIRING SHALL BE DERATED PER NEC 310-15. DUE TO HARMONIC LOADING, THE NEUTRAL

CONDUCTOR SHALL BE CONSIDERED AS A CURRENT CARRYING CONDUCTOR FOR DERATING PURPOSES.

11. MAIN BRANCH CIRCUIT CONDUIT RUNS SHALL BE EMT. REFER TO SPECIFICATIONS FOR ADDITIONAL

RACEWAY RESTRICTIONS.

12. ALL EMPTY DUCTS AND CONDUITS SHALL BE DEBURRED, CLEANED, TAGGED AND PROVIDED WITH A NYLON

PULL STRING.

13. MOUNTING HEIGHTS OF ELECTRICAL DEVICES ARE TO CENTER OF DEVICE UNLESS OTHERWISE NOTED.

14. IN GENERAL, ELECTRICAL EQUIPMENT, WHICH ARE INDICATED ON THE PLAN MAY NOT BE SCALED, EXCEPT

WHERE DIMENSIONED OR ADDITIONAL LAYOUT CRITERIA IS INDICATED AT CRITICAL LOCATIONS.

15. WHEREVER 'PROVIDE' IS USED IN THE DRAWINGS AND SPECIFICATIONS, IT SHALL MEAN 'PROVIDE AND

INSTALL'.

16. ALL EMERGENCY WIRING SHALL BE IN SEPARATE CONDUIT FROM NON-EMERGENCY WIRING.

17. REFER TO THE ONE LINE DIAGRAMS FOR CONDUIT AND WIRE SIZES.

18. EXISTING ONE LINE DIAGRAMS WERE CREATED FROM AVAILABLE DRAWINGS AND INFORMATION.

ELECTRICAL CONTRACTOR SHALL FIELD VERIFY ALL EXISTING CONDITIONS AND LOCATIONS PRIOR TO

START OF WORK.

19. ALL 120 VOLT BRANCH CIRCUITS SHALL BE PROVIDED WITH SEPARATE FULL SIZE NEUTRAL CONDUCTORS.

20. PROVIDE PULL BOXES AS REQUIRED TO INTERCEPT FEEDER AND BRANCH CIRCUITS AND EXTEND TO NEW

PANEL LOCATION. REFER TO SPECIFICATIONS FOR APPROVED SPLICING METHODS. LOCATE PULL BOXES IN

ACCESSIBLE LOCATIONS.

21. COORDINATE SEQUENCING AND TEMPORARY REQUIREMENTS TO MAINTAIN LIGHTING SYSTEM OPERATION

DURING CONSTRUCTION.

22. THE ELECTRICAL TRADES SHALL PROVIDE FIELD INVESTIGATION TO VISUALLY AND ELECTRICALLY TRACE

BRANCH CIRCUITS, WHICH ARE TO BE REMOVED. IF BRANCH CIRCUITS SERVE LIGHTING OR EQUIPMENT

OUTSIDE OF THE PROJECT SCOPE, THE EXISTING BRANCH CIRCUIT WIRING SHALL BE MAINTAINED TO

SERVE THESE LOADS.

23. FEEDER SIZES ARE BASED ON NEC 2017 ARTICLES 310.15, 310.60, 250.122, AND 110.14. CONDUIT SIZES

SELECTED ARE BASED ON RIGID METAL CONDUIT (UNLESS NOTED OTHERWISE) AND 40% CONDUIT FILL.

CONDUIT SIZE SHALL BE ADJUSTED AS REQUIRED FOR OTHER TYPES OF CONDUIT. UNLESS NOTED

OTHERWISE, THE CONDUCTOR SIZE IS BASED ON AN AMBIENT TEMPERATURE OF 60°C AND 600V

INSULATED COPPER CABLE APPLIED AT 60°C FOR TERMINATIONS RATED 100 AMPS AND LESS AND 75°C FOR

TERMINATIONS RATED MORE THAN 100 AMPS. CONDUCTOR SIZE IS A MINIMUM AND DOES NOT TAKE INTO

ACCOUNT VOLTAGE DROP OR DERATING. CONDUCTOR SIZE SHALL BE ADJUSTED AS REQUIRED PER NEC.

24. THE CONTRACTOR SHALL COMPLY WITH THE VA, LOCAL AND STATE RULES AND REGULATIONS WHILE

ACCESSING AND WORKING IN CONFINED SPACES, SUCH AS MANHOLES AND CABLE VAULTS.

THE CONTRACTOR IS FREE TO PROPOSE THEIR OWN SEQUENCE OF WORK SO AS TO KEEP THE

NUMBER AND DURATION OF POWER SHUTDOWNS TO THE LEAST NECESSARY.

THE PROPOSED SEQUENCE OF WORK BELOW ENVISIONS KEEPING THE EXISTING 13.2 KV, 4.8 KV

AND 208Y/120V POWER SYTSEMS OPERATIONAL, AS LONG AS IS PRACTICAL, WHILE INSTALLING

THE NEW 13.2 KV AND 208Y/120V SYSTEMS.

FEEDERS A#104 AND A#106 ORIGINATE IN THE MV SWITCHGEAR IN THE BASEMENT OF BUILDING

32 (ENERGY CENTER).

BUILDING 1-WEST

1. PHASE A:

A. PROVIDE THE 15 KV PRIMARY INCOMING AND TIE SWITCHGEAR (MVS-MAIN).

B. PROVIDE THE 15 KV FEEDER SWITCHGEAR (MVS-SWGR) ALONG WITH THE ASSOCIATED

UNDERGROUND DUCTS AND 15 KV CABLES.

C. TRANSFER BUILDINGS 1-WEST, #22, #28 AND THE LINAC BUILDING ON TO FEEDER /

SWITCH #A104.

D. LOCK OUT TAG OUT FEEDER #A106 IN THE MV SWITCHGEAR IN BUILDING 32 (ENERGY

CENTER). DISCONNECT THE 15 KV CABLES FROM FEEDER / SWITCH #A106 AND

RE-ROUTE, WITH ADDITIONAL CABLES, AS REQUIRED, TO MVS-MAIN. NEW CABLES

SHALL MATCH EXISTING. NEW CABLES SHALL BE CONNECTED TO THE EXISTING USING

DEADBREAK ELBOWS.

E. SHUTDOWN REQUIRED. DISCONNECT THE 208Y/120V SWITCHBOARD “SWBD-2” FROM

UNIT SUBSTATION #2 AND FEED IT FROM A SPARE 800A BREAKER IN 208Y/120V

SWITCHBOARD “SWBD-1”. USE DIESEL LOCOMOTIVE CABLE (DLO) RATED

FOR 600V, 90 DEG C, 4-1/C, 777.7 KCMIL AND 1-1/C 777.7 KCMIL GROUND.

F. SHUTDOWN REQUIRED. DISCONNECT THE 208Y/120V SWITCHBOARD “SWBD-3” FROM

UNIT SUBSTATION #3 AND FEED IT FROM A SPARE 800A BREAKER IN 208Y/120V

SWITCHBOARD “SWBD-1”. USE DIESEL LOCOMOTIVE CABLE (DLO) RATED

FOR 600V, 90 DEG C, 4-1/C, 777.7 KCMIL AND 1-1/C 777.7 KCMIL GROUND.

G. DISCONNECT UNIT SUBSTATIONS #2 AND #3 FROM THE 4.8 KV SOURCE AND REMOVE

FROM THE BUILDING.

2. PHASE B:

A. PROVIDE A MOBILE 500 KW, 208Y/120V DIESEL GENERATOR ALONG WITH AN ATS AND

THE NECESSARY CABLES AND CONTROL WIRING TO PROVIDE EMERGENCY POWER TO

THE BUILDING. THE GENERATOR SHALL BE CONNECTED TO ONE OF THE SPARE 1600A

BREAKERS IN THE UNIT SUBSTATION. THE MAIN BREAKERS, IN THE SUBSTATION SHALL

BE OPEN WHEN THE GENERATOR IS RUNNING.

B. PROVIDE THE RIGHT 15 KV AIR TERMINAL CHAMBER (ATC), ASSOCIATED 1000 KVA, 13.2

KV - 208Y/120V TRANSFORMER AND THE 208Y/120V SECONDARY DISTRIBUTION

SWITCHBOARD. CONNECT TO THE ASSOCIATED FEEDER IN MVS-SWGR.

C. SHUTDOWN REQUIRED. DISCONNECT SWBD-3 ON BOTH THE LINE SIDE AND THE LOAD

SIDE AND REMOVE FROM THE BUILDING. RETAIN LOAD SIDE FEEDERS FOR RE-USE.

D. PROVIDE SWITCHBOARDS #3-A AND #3-B. CONNECT THE LINE SIDE, OF EACH

SWITCHBOARD, TO THEIR FEEDERS IN THE UNIT SUBSTATION. CONNECT THE EXISTING

LOAD SIDE FEEDERS TO THE BREAKERS IN THE SWITCHBOARDS.

E. SHUTDOWN REQUIRED. DISCONNECT SWBD-2 ON BOTH THE LINE SIDE AND THE LOAD

SIDE AND REMOVE FROM THE BUILDING. RETAIN LOAD SIDE FEEDERS FOR RE-USE.

F. PROVIDE SWITCHBOARDS #2-A AND #2-B. CONNECT THE LINE SIDE, OF EACH

SWITCHBOARD, TO THEIR FEEDERS IN THE UNIT SUBSTATION. CONNECT THE EXISTING

LOAD SIDE FEEDERS TO THE BREAKERS IN THE SWITCHBOARDS.

G. SHUTDOWN REQUIRED. DISCONNECT SWBD-1 ON BOTH THE LINE SIDE AND THE LOAD

SIDE AND REMOVE FROM THE BUILDING. RETAIN LOAD SIDE FEEDERS FOR RE-USE.

H. PROVIDE SWITCHBOARDS #1-A AND #1-B. CONNECT THE LINE SIDE, OF EACH

SWITCHBOARD, TO THEIR FEEDERS IN THE UNIT SUBSTATION. CONNECT THE EXISTING

LOAD SIDE FEEDERS TO THE BREAKERS IN THE SWITCHBOARDS.

3. PHASE C:

A. DISCONNECT UNIT SUBSTATION #1 FROM THE 4.8 KV SOURCE AND REMOVE FROM THE

BUILDING.

B. PROVIDE THE LEFT 15 KV AIR TERMINAL CHAMBER (ATC) AND ASSOCIATED 1000 KVA,

13.2 KV - 208Y/120V TRANSFORMER. CONNECT TO THE ASSOCIATED FEEDER IN

MVS-SWGR.

C. PLACE BUILDINGS 1-WEST, #28 AND THE LINAC BUILDING ON THE NEW MVS-SWGR

SWITCH.

D. LOCK OUT TAG OUT FEEDER #A104 IN THE SWITCHGEAR IN BUILDING 32 (ENERGY

CENTER). DISCONNECT THE 15 KV CABLES FROM FEEDER / SWITCH #A104 AND

RE-ROUTE, WITH ADDITIONAL CABLES, AS REQUIRED, TO MVS-MAIN. NEW CABLES

SHALL MATCH EXISTING. CONNECT THE NEW CABLES, TO THE EXISTING, USING

DEADBREAK ELBOWS.

E. SHUTDOWN REQUIRED. REPLACE TRANSFORMER AT BUILDING #22 AND CONNECT

CABLES TO MVS-SWGR.

4. PHASE D:

A. PROVIDE THE GENERATOR TRANSFORMER (T-GEN) WITH ASSOCIATED CONDUITS AND

CABLES.

B. DISCONNECT THE GENERATOR DISTRIBUTION SWITCHGEAR ON BOTH THE LINE SIDE

AND THE LOAD SIDES AND REMOVE. RETAIN CABLES FOR RE-USE

C. PULL BACK THE MV CABLE FROM THE GENERATOR DISTRIBUTION SWITCHGEAR AND

TERMINATE AT THE 4800V TERMINALS OF THE GENERATOR TRANSFORMER (T-GEN).

D. PROVIDE 15KV CABLE, IN CONDUIT, BETWEEN T-GEN AND THE 15 KV SWITCHGEAR,

MVS-GEN.

E. PROVIDE THE 15 KV SWITCHGEAR, MVS-GEN, IN THE SAME LOCATION AS THE

GENERATOR DISTRIBUTION SWITCHGEAR AND RECONNECT TO BOTH THE ATS.

F. CONNECT THE LOAD SIDE OF BOTH THE ATS TO THE MV SWITCHGEAR, MVS-SWGR.

BUILDING 22

1. SHUTDOWN REQUIRED. DISCONNECT THE EXISTING PAD-MOUNTED TRANSFORMER

AND REMOVE. RETAIN THE ASSOCIATED MV AND 600V CABLES FOR RE-USE.

2. PROVIDE THE PAD-MOUNTED TRANSFORMER.

3. CONNECT THE EXISTING MV AND 600V CABLES TO THE PAD-MOUNTED TRANSFORMER.

BUILDING 28

1. PROVIDE THE 15 KV SWITCHGEAR AND PAD-MOUNTED TRANSFORMER.

2. PROVIDE THE ASSOCIATED UNDERGROUND DUCTS, FROM THE EXISTING MANHOLE TO

THE 15 KV SWITCHGEAR AND THE 15 KV CABLES.

3. PROVIDE THE 600V CABLES, IN CONDUIT, FROM THE PAD-MOUNTED TRANSFORMER

SECONDARY TO THE 480V SECTION IN THE ELECTRICAL ROOM.

4. PROVIDE A MOBILE 500 KW, 480Y/277V DIESEL GENERATOR ALONG WITH THE

NECESSARY CABLES AND CONTROL WIRING TO PROVIDE TEMPORARY POWER TO THE

BUILDING.

5. SHUTDOWN REQUIRED. DISCONNECT THE EXISTING MV SWITCHGEAR AND DRY-TYPE

TRANSFORMER AND REMOVE FROM THE BUILDING. PROVIDE THE 480V SECTION AND

CONNECT IT TO THE EXISTING 480V SWITCHBOARD. TERMINATE 600V CABLES.

6.

LINAC BUILDING

1. SHUTDOWN REQUIRED. DISCONNECT THE EXISTING PAD-MOUNTED TRANSFORMER

AND REMOVE ALONG WITH THE ASSOCIATED MV CABLE FROM THE MANHOLE. RETAIN

600V CABLES FOR RE-USE.

2. PROVIDE A MOBILE 500 KW, 480Y/277V DIESEL GENERATOR ALONG WITH THE

NECESSARY CABLES AND CONTROL WIRING TO PROVIDE TEMPORARY POWER TO THE

BUILDING.

3. PROVIDE THE 15 KV SWITCHGEAR AND PAD-MOUNTED TRANSFORMER.

4. PROVIDE THE ASSOCIATED UNDERGROUND DUCTS, FROM THE EXISTING MANHOLE TO

THE 15 KV SWITCHGEAR AND THE 15 KV CABLES.

5. CONNECT THE 600V CABLES TO THE PAD-MOUNTED TRANSFORMER.

PROPOSED SEQUENCE OF WORK

11/18/19

100% CONSTRUCTION

DOCUMENTS SUBMISSION

BLDG. 22

BLDG. 1-W

BLDG. 28

AMBULANCE

ENTRANCE

LINAC

ED101

ELECTRICAL COMPOSITE SITE

PLAN - DEMOLITION

M.

SABAPATHY

I. ORTIZ

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

GUIDON DESIGN, INC.

1221 N. PENNSYLVAINA STREET

INDIANAPOLIS, IN 46204

317.800.6388

STACEY PAUL

ELECTRICAL ENGINEER:

GHAFARI ASSOCIATES

17101 MICHIGAN AVE.

DEARBORN, MI 48126

UPGRADE ELECTRICAL

SWITCHGEAR & DISTRIBUTION

ANN ARBOR VAMC

506-18-102

N/A Project Director

Revisions: Date:

SUITE 200

PROJECT NUMBER: 187371

313.441.3000

JEFF PEDERSEN

T-22

T-LINAC

T-28

(E) 480Y/277V

SWITCH BOARD

LINEWEIGHT LEGEND:

NEW ITEMS.

ITEMS TO BE REMOVED OR

RELOCATED.

EXISTING ITEMS TO REMAIN.

GENERAL NOTES:

1. THE DRAWINGS AND SPECIFICATIONS ARE FOR DESIGN INTENT.

ALTHOUGH INTENDED TO CONVEY INFORMATION AS ACCURATELY

AS POSSIBLE, THE DRAWING IS BASED MOSTLY ON EXISTING

AS-BUILT DRAWINGS AND SOME FIELD VERIFICATIONS.

CONTRACTOR SHALL VERIFY FIELD CONDITIONS BEFORE

COMMENCING WORK AND NOTIFY ENGINEER/ARCHITECT

CONCERNING MAJOR DISCREPANCIES.

2. REFER TO SHEET EE001 FOR ELECTRICAL SYMBOLS LIST.

3. REFER TO SHEET EE002 FOR GENERAL AND DEMOLITION NOTES

AND ABBREVIATIONS.

4. DISCONNECT POWER TO THE EXISTING ELECTRICAL EQUIPMENT

TO BE REMOVED. COORDINATE WITH CIVIL DRAWINGS AND

CONTRACTORS FOR THE FULL SCOPE OF DEMOLITION WORK.

5. (E) INDICATES EXISTING TO REMAIN.

6. ELECTRICAL CONTRACTOR SHALL CONFIRM BRANCH CIRCUIT

WIRING TO REMAIN DURING DEMOLITION WORK. ROUTE AND

EXTEND EXISTING CIRCUITS TO REMAIN TO NEW ELECTRICAL

EQUIPMENT.

7. FIELD VERIFY SIZES, LOCATIONS, ELEVATIONS, AND DETAILS OF

ALL EXISTING CONSTRUCTION AND CONDITIONS THAT AFFECT

THE WORK BEFORE PROCEEDING WITH THIS WORK.

8. PROVIDE SHORING, SHEETING, UNDERPINNING, AND ALL OTHER

MEANS REQUIRED TO PROTECT AND MAINTAIN THE SAFETY,

INTEGRITY, AND STABILITY OF ALL EXISTING AND NEW

CONSTRUCTION THAT MAY BE AFFECTED BY WORK.

9. VERIFY AND IDENTIFY ANY MISCELLANEOUS CONDUIT OR

EQUIPMENT NOT INDICATED ON THE DRAWINGS PRIOR TO

DEMOLITION.

10. SITE CLEAN-UP IS REQUIRED ON A DAILY BASIS.

11. WHERE FEASIBLE, EXISTING EQUIPMENT SHALL BE REMOVED

ONLY AFTER THE NEW EQUIPMENT HAS BEEN INSTALLED, TESTED

AND COMMISSIONED. REFER TO THE PROPOSED SEQUENCE OF

WORK ON SHEET EE002.

12. REFER TO THE ONE LINE DIAGRAM ON SHEET ED601.

ED401

MH-P2

MH-P6

MH-P102

MH-P4

MV SWITCH

KEY NOTES:

1. TRANSFORMER SHALL BE REPLACED. EXISTING PRIMARY AND

SECONDARY CABLES SHALL BE RETAINED FOR RE-USE.

2. TRANSFORMER SHALL BE REPLACED. EXISTING SECONDARY

CABLES SHALL BE RETAINED FOR RE-USE. REMOVE PRIMARY

CABLES BACK TO THE MANHOLE, MH-P2.

3. MV SWITCH AND TRANSFORMER SHALL BE REPLACED. REMOVE

PRIMARY CABLES BACK TO THE MANHOLE, MH-P4. THE 480Y/277V

SWITCHBOARD SHALL BE RETAINED FOR RE-USE.

4. EXISTING 1500KW/1875KVA GENERATOR AND SWITCHGEAR

LOCATED IN THE GENERATOR ROOM

IMPORTANT NOTE:

REFER TO PROPOSED SEQUENCE OF

WORK ON SHEET EE002

N

0 105

MV SWITCH

11/18/19

100% CONSTRUCTION

DOCUMENTS SUBMISSION

AutoCAD SHX Text 1W

AutoCAD SHX Text 1E

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text T2

AutoCAD SHX Text 3"G

AutoCAD SHX Text 3"G

AutoCAD SHX Text 3"G

AutoCAD SHX Text

SEE DETAIL FOR TUNNEL FACILITIES

AutoCAD SHX Text

TC

AutoCAD SHX Text

FO

AutoCAD SHX Text

TC

AutoCAD SHX Text

FO

AutoCAD SHX Text 4"G

AutoCAD SHX Text 4"G

AutoCAD SHX Text 4"G

AutoCAD SHX Text

1 1/2"OXY

AutoCAD SHX Text

1 1/2"OXY

AutoCAD SHX Text

2"OXY

AutoCAD SHX Text

4"FUEL

AutoCAD SHX Text

2"FUEL

AutoCAD SHX Text

2"FUEL

AutoCAD SHX Text

1/2"OXY

AutoCAD SHX Text

QLD

AutoCAD SHX Text T

AutoCAD SHX Text

SYMBOLS

AutoCAD SHX Text

SYMBOLS

AutoCAD SHX Text S

AutoCAD SHX Text P

AutoCAD SHX Text S

AutoCAD SHX Text P

AutoCAD SHX Text S

AutoCAD SHX Text P

AutoCAD SHX Text S

AutoCAD SHX Text P

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text S

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text

WALK

AutoCAD SHX Text

WALK

AutoCAD SHX Text

WALK

AutoCAD SHX Text

WALK

AutoCAD SHX Text 6"

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text S

AutoCAD SHX Text H

AutoCAD SHX Text H

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P&S

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text S

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text 3"G

AutoCAD SHX Text 3"G

AutoCAD SHX Text 3"G

AutoCAD SHX Text 3"G

AutoCAD SHX Text 3"G

AutoCAD SHX Text G

AutoCAD SHX Text G

AutoCAD SHX Text 6"G-100#

AutoCAD SHX Text 6"

AutoCAD SHX Text

1"STM

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text P

AutoCAD SHX Text

CONC.

AutoCAD SHX Text 1 1/2"G

AutoCAD SHX Text 2"G

AutoCAD SHX Text

CB-22

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text

NTS

AutoCAD SHX Text

%%USITE KEY MAP

ENTRANCE

ED401

ELECTRICAL ENLARGED PLAN

BUILDING 1 - WEST

M.

SABAPATHY

I. ORTIZ

(E) MV UNIT SUBSTATION

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

GUIDON DESIGN, INC.

1221 N. PENNSYLVAINA STREET

INDIANAPOLIS, IN 46204

317.800.6388

STACEY PAUL

ELECTRICAL ENGINEER:

GHAFARI ASSOCIATES

17101 MICHIGAN AVE.

DEARBORN, MI 48126

UPGRADE ELECTRICAL

SWITCHGEAR & DISTRIBUTION

ANN ARBOR VAMC

506-18-102

N/A Project Director

Revisions: Date:

SUITE 200

PROJECT NUMBER: 187371

313.441.3000

JEFF PEDERSEN

GENERAL NOTES:

1. THE DRAWINGS AND SPECIFICATIONS ARE FOR DESIGN INTENT.

ALTHOUGH INTENDED TO CONVEY INFORMATION AS ACCURATELY

AS POSSIBLE, THE DRAWING IS BASED MOSTLY ON EXISTING

AS-BUILT DRAWINGS AND SOME FIELD VERIFICATIONS.

CONTRACTOR SHALL VERIFY FIELD CONDITIONS BEFORE

COMMENCING WORK AND NOTIFY ENGINEER/ARCHITECT

CONCERNING MAJOR DISCREPANCIES.

2. REFER TO SHEET EE001 FOR ELECTRICAL SYMBOLS LIST.

3. REFER TO SHEET EE002 FOR GENERAL AND DEMOLITION NOTES

AND ABBREVIATIONS.

4. DISCONNECT POWER TO THE EXISTING ELECTRICAL EQUIPMENT

TO BE REMOVED. COORDINATE WITH CIVIL DRAWINGS AND

CONTRACTORS FOR THE FULL SCOPE OF DEMOLITION WORK.

5. (E) INDICATES EXISTING TO REMAIN.

6. ELECTRICAL CONTRACTOR SHALL CONFIRM BRANCH CIRCUIT

WIRING TO REMAIN DURING DEMOLITION WORK. ROUTE AND

EXTEND EXISTING CIRCUITS TO REMAIN TO NEW ELECTRICAL

EQUIPMENT.

7. FIELD VERIFY SIZES, LOCATIONS, ELEVATIONS, AND DETAILS OF

ALL EXISTING CONSTRUCTION AND CONDITIONS THAT AFFECT

THE WORK BEFORE PROCEEDING WITH THIS WORK.

8. PROVIDE SHORING, SHEETING, UNDERPINNING, AND ALL OTHER

MEANS REQUIRED TO PROTECT AND MAINTAIN THE SAFETY,

INTEGRITY, AND STABILITY OF ALL EXISTING AND NEW

CONSTRUCTION THAT MAY BE AFFECTED BY WORK.

9. VERIFY AND IDENTIFY ANY MISCELLANEOUS CONDUIT OR

EQUIPMENT NOT INDICATED ON THE DRAWINGS PRIOR TO

DEMOLITION.

10. SITE CLEAN-UP IS REQUIRED ON A DAILY BASIS.

11. WHERE FEASIBLE, EXISTING EQUIPMENT SHALL BE REMOVED

ONLY AFTER THE NEW EQUIPMENT HAS BEEN INSTALLED, TESTED

AND COMMISSIONED. REFER TO THE PROPOSED SEQUENCE OF

WORK ON SHEET EE002.

12. REFER TO THE ONE LINE DIAGRAM ON SHEET ED601.

UNIT SUBSTATION-1

UNIT SUBSTATION-3

UNIT SUBSTATION-2

SWBD-1

SWBD-3

SWBD-2

(E) ATS

(E) ATS-3

(E) ATS-5-6

(E) ATS-5-5

(E) ATS

(E) BLDG 26

EMER LTG

ATS

(E) (E)

(E) CC-B2

FLAGPOLE TO

BE RELOCATED

(BY OTHERS)

LINEWEIGHT LEGEND:

NEW ITEMS.

ITEMS TO BE REMOVED OR

RELOCATED.

EXISTING ITEMS TO REMAIN.

SITE LTS.

WEST (E) LP-A (E) PP-A

EXH. FAN #1

EXH. FAN #2

EXH. FAN #3

(E) ASCO

LIGHTING

CONTACTOR

SWBD (E) PUMP

CONTROLLER

(E) AMBULANCE

GARAGE X-FMR

(E) AUTOMATIC TRANSFER

SWITCHES

GENERATOR DISTRIBUTION

SWITCHGEAR

MH-P7

KEY NOTES:

1. REMOVE ASSOCIATED MV CABLE BACK TO THE POWER SOURCE.

2. EXISTING LOW VOLTAGE (LV) FEEDER CABLE SHALL BE RETAINED

FOR RE-USE.

2 2

IMPORTANT NOTE:

REFER TO PROPOSED SEQUENCE OF

WORK ON SHEET EE002

MV

FUSE

FDR

# A106

FDR

# A104

1500 KVA

TRANSFORMER

CABLE

# 14

CABLE

# 4

ISOLATION BANK 'A' ISOLATION BANK 'A'

SECONDARY

SELECTOR SWITCHES

ISOLATION BANK 'B'

SECONDARY

SELECTOR SWITCHES

CABLE

# 15

CABLE

# 3

1000 KVA

TRANSFORMER

MV

FUSE

FDR

# A104

FDR

# A106

ISOLATION BANK 'B'

BAY A BAY B I/C

ISOLATION BANK 'A' ISOLATION BANK 'B'

(E) PULL BOX

N

0 105

11/18/19

100% CONSTRUCTION

DOCUMENTS SUBMISSION

AutoCAD SHX Text B3-15

AutoCAD SHX Text B3-16

AutoCAD SHX Text P

AutoCAD SHX Text D

AutoCAD SHX Text

NTS

AutoCAD SHX Text

%%USITE KEY MAP

100E

125E

200E

125E

125E

500KVA

30KVA

LINEAR

ACCELERATOR

500KVA

750KVA

NURSING

HOME

BUILDING #28

480Y/277V

3Ø, 4w

SWITCHBOARD

MANHOLE MH-P3

MANHOLE MH-P4

MANHOLE MH-P2

MANHOLE P6

MANHOLE MH-P5

BUILDING #22

DISTRIBUTION

CENTER #2

SOUTH

METER

HOUSE

125E

250E

EXISTING 3-1/C - 350Kcmil, EPR, 15KV, SHIELDED

133% INSULATION

133% INSULATION

EXISTING

3-1/C - 350KCMIL,

EPR, 15KV,

SHIELDED

EXISTING

3-1/C - 350KCMIL,

EPR, 15KV,

SHIELDED

133% INSULATION

WIRE LEGEND:

3 - 1/C - 15KV, 133% SHIELDED INSULATION, 350Kcmil EPR &

1 - #350Kcmil XHHW GRD IN 5" PVC DUCTBANK

3 - 1/C - 15KV, 133% SHIELDED INSULATION, 500Kcmil EPR &

1 - #500Kcmil XHHW GRD IN 5" PVC DUCTBANK

600A

3P

600A

3P

300E

300E

600A

3P

600A

3P

BUILDING 1-W

ISOLATION BANK "A"

1200A/

300A

SITE GENERATOR

1500KW/1875KVA, 4800V, 3P, 4W

600A

3P

600A

3P

125E

BUILDING 1-W

ISOLATION BANK "B"

1500KVA

WITH FAN COOLING

13,200-4800V, 3PH, 3W

250E

600A

3P

600A

3P

600A

3P

600A

3P

1000KVA

WITH FAN COOLING

13,200-4800V, 3 , 3W

600A

3P

600A

3P

250E

ISOLATION BANK B

MOTORIZED OPERATED

AUTOMATIC TRANSFER SWITCH

ISOLATION BANK A

MOTORIZED OPERATED

AUTOMATIC TRANSFER SWITCH

K

K

K

ISOLATION BANK B

SECONDARY SELECTOR

SWITCHES

ISOLATION BANK A

SECONDARY SELECTOR

SWITCHES

ISOLATION BANK A

PRIMARY SELECTOR

SWITCHES

ISOLATION BANK B

PRIMARY SELECTOR

SWITCHES

KEY INTERLOCK

SO ONLY ONE

SWITCH CAN BE

CLOSED AT A TIME

TYPICAL

PRIMARY FEEDER #A-106

13200V, 3PH, 3W FROM MANHOLE, PS102

PRIMARY FEEDER #A-104

13200V, 3PH, 3W FROM MANHOLE, PS102

750KVA

4800-208/120V

3PH, 4W

750KVA

4800-208/120V

3 , 4W

750KVA

4800-208/120V

3PH, 4W

GENERATOR DISTRIBUTION

SWITCHGEAR

COPPER

BUS LINK

COPPER

BUS LINK

CABLE #4

CABLE #3

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

GUIDON DESIGN, INC.

1221 N. PENNSYLVAINA STREET

INDIANAPOLIS, IN 46204

317.800.6388

STACEY PAUL

ELECTRICAL ENGINEER:

GHAFARI ASSOCIATES

17101 MICHIGAN AVE.

DEARBORN, MI 48126

UPGRADE ELECTRICAL

SWITCHGEAR & DISTRIBUTION

ANN ARBOR VAMC

506-18-102

N/A Project Director

Revisions: Date:

SUITE 200

PROJECT NUMBER: 187371

313.441.3000

JEFF PEDERSEN

LINEWEIGHT LEGEND:

NEW ITEMS.

ITEMS TO BE REMOVED OR

RELOCATED.

EXISTING ITEMS TO REMAIN.

ED601

ELECTRICAL ONE LINE

DIAGRAM - DEMOLITION

M. SABAPATHY I. ORTIZ07/31/19

GENERAL NOTES:

1. REFER TO SHEET EE001 FOR ELECTRICAL SYMBOLS LIST.

2. REFER TO SHEET EE002 FOR GENERAL AND DEMOLITION NOTES,

ABBREVIATIONS AND PROPOSED SEQUENCE OF WORK.

125E

95% CONSTRUCTION

DOCUMENTS

PULL BOX IN CABLE

VAULT BELOW

SUBSTATION ROOM

PULL BOX IN

BUILDING 1-W

CRAWL SPACE

T-22

CABLE #15

CABLE #3

CABLE #4

CABLE #14

CABLE #15

CABLE #15

CABLE #15

CABLE #14

CABLE #14

CABLE #14

CABLE #14

CABLE #15

CABLE #14

MV SWITCH

T-28

B

B

B

B

B

B

B

B

B

A

MV SWITCH

ABOVE GROUND

PULL BOX

UNIT SUBSTATION 3

UNIT SUBSTATION 2

UNIT SUBSTATION 1

208Y/120V

SWITCHBOARD #3

SWBD - 3

208Y/120V

SWITCHBOARD #2

SWBD - 2

208Y/120V

SWITCHBOARD #1

SWBD - 1

ABOVE GROUND

PULL BOX

DEAD BREAK

JUNCTION (TYPICAL)

T - LINCA

AutoCAD SHX Text

AutoCAD SHX Text G

AutoCAD SHX Text K

AutoCAD SHX Text K

AutoCAD SHX Text K

AutoCAD SHX Text K

AutoCAD SHX Text K

AutoCAD SHX Text 80E

AutoCAD SHX Text 80E

BLDG. 22

BLDG. 1-W

BLDG. 28

AMBULANCE

ENTRANCE

LINAC

ES101

ELECTRICAL COMPOSITE SITE

PLAN

M.

SABAPATHY

I. ORTIZ

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

GUIDON DESIGN, INC.

1221 N. PENNSYLVAINA STREET

INDIANAPOLIS, IN 46204

317.800.6388

STACEY PAUL

ELECTRICAL ENGINEER:

GHAFARI ASSOCIATES

17101 MICHIGAN AVE.

DEARBORN, MI 48126

UPGRADE ELECTRICAL

SWITCHGEAR & DISTRIBUTION

ANN ARBOR VAMC

506-18-102

N/A Project Director

Revisions: Date:

SUITE 200

PROJECT NUMBER: 187371

313.441.3000

JEFF PEDERSEN

LINEWEIGHT LEGEND:

NEW POWER

CONTROL

EXISTING POWER

ES403

ES404

ES402

ES401

GENERAL NOTES:

1. THE DRAWINGS AND SPECIFICATIONS ARE FOR DESIGN INTENT.

ALTHOUGH INTENDED TO CONVEY INFORMATION AS ACCURATELY

AS POSSIBLE, THE DRAWING IS BASED MOSTLY ON EXISTING

AS-BUILT DRAWINGS AND SOME FIELD VERIFICATIONS.

CONTRACTOR SHALL VERIFY FIELD CONDITIONS BEFORE

COMMENCING WORK AND NOTIFY ENGINEER/ARCHITECT

CONCERNING MAJOR DISCREPANCIES.

2. REFER TO SHEET EE001 FOR ELECTRICAL SYMBOLS LIST.

3. REFER TO SHEET EE002 FOR GENERAL AND DEMOLITION NOTES

AND ABBREVIATIONS.

4. DISCONNECT POWER TO THE EXISTING ELECTRICAL EQUIPMENT

TO BE REMOVED. COORDINATE WITH CIVIL DRAWINGS AND

CONTRACTORS FOR THE FULL SCOPE OF DEMOLITION WORK.

5. (E) INDICATES EXISTING TO REMAIN.

6. ELECTRICAL CONTRACTOR SHALL CONFIRM BRANCH CIRCUIT

WIRING TO REMAIN DURING DEMOLITION WORK. ROUTE AND

EXTEND EXISTING CIRCUITS TO REMAIN TO NEW ELECTRICAL

EQUIPMENT.

7. FIELD VERIFY SIZES, LOCATIONS, ELEVATIONS, AND DETAILS OF

ALL EXISTING CONSTRUCTION AND CONDITIONS THAT AFFECT

THE WORK BEFORE PROCEEDING WITH THIS WORK.

8. PROVIDE SHORING, SHEETING, UNDERPINNING, AND ALL OTHER

MEANS REQUIRED TO PROTECT AND MAINTAIN THE SAFETY,

INTEGRITY, AND STABILITY OF ALL EXISTING AND NEW

CONSTRUCTION THAT MAY BE AFFECTED BY WORK.

9. VERIFY AND IDENTIFY ANY MISCELLANEOUS CONDUIT OR

EQUIPMENT NOT INDICATED ON THE DRAWINGS PRIOR TO

DEMOLITION.

10. SITE CLEAN-UP IS REQUIRED ON A DAILY BASIS.

11. WHERE FEASIBLE, EXISTING EQUIPMENT SHALL BE REMOVED

ONLY AFTER THE NEW EQUIPMENT HAS BEEN INSTALLED, TESTED

AND COMMISSIONED. REFER TO THE PROPOSED SEQUENCE OF

WORK ON SHEET EE002.

12. REFER TO THE ONE LINE DIAGRAMS ON SHEETS EP601, EP602,

EP603 AND EP604.

13. REFER TO THE CIVIL DRAWINGS FOR THE CONCRETE PAD

DETAILS.

IMPORTANT NOTE:

REFER TO PROPOSED SEQUENCE OF

WORK ON SHEET EE002

N

0 105

MH-PS102

MH-P6

11/18/19

100% CONSTRUCTION

DOCUMENTS SUBMISSION

AutoCAD SHX Text 1W

AutoCAD SHX Text 1E

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text T2

AutoCAD SHX Text

SEE DETAIL FOR TUNNEL FACILITIES

AutoCAD SHX Text

TC

AutoCAD SHX Text

FO

AutoCAD SHX Text

TC

AutoCAD SHX Text

FO

AutoCAD SHX Text 4"G

AutoCAD SHX Text 4"G

AutoCAD SHX Text 4"G

AutoCAD SHX Text

1 1/2"OXY

AutoCAD SHX Text

1 1/2"OXY

AutoCAD SHX Text

2"OXY

AutoCAD SHX Text

4"FUEL

AutoCAD SHX Text

2"FUEL

AutoCAD SHX Text

2"FUEL

AutoCAD SHX Text

1/2"OXY

AutoCAD SHX Text

QLD

AutoCAD SHX Text T

AutoCAD SHX Text

SYMBOLS

AutoCAD SHX Text

SYMBOLS

AutoCAD SHX Text S

AutoCAD SHX Text P

AutoCAD SHX Text S

AutoCAD SHX Text P

AutoCAD SHX Text S

AutoCAD SHX Text P

AutoCAD SHX Text S

AutoCAD SHX Text P

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text S

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text 6"

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text S

AutoCAD SHX Text H

AutoCAD SHX Text H

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P&S

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text S

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text P

AutoCAD SHX Text

1"STM

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text S

AutoCAD SHX Text P

AutoCAD SHX Text

CB-22

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text E

AutoCAD SHX Text

NTS

AutoCAD SHX Text

%%USITE KEY MAP

AMBULANCE

ENTRANCE

ES401

ELECTRICAL ENLARGED PLAN

BUILDING 1 - WEST

M.

SABAPATHY

I. ORTIZ

UNIT SUBSTATION- SS1W

13.2KV - 208Y/120V

15 KV

SWITCHGEAR #1

15 KV PRIM.

FEEDER AND TIE

Project Number

Building Number

Drawing Number

Project Title

Location

Issue Date Checked Drawn

Drawing Title

Approved:

VA FORM 08 - 6231

A

Office of Construction and Facilities Management

U.S. Department of Veterans Affairs

B

C

D

E

F

A

B

C

D

E

F

21 4 5 6 7 8 9 10

PhaseARCHITECT/ENGINEER OF RECORD A/E:

STAMPCONSULTANT

321 4 5 6 7 8 9 10

GUIDON DESIGN, INC.

1221 N. PENNSYLVAINA STREET

INDIANAPOLIS, IN 46204

317.800.6388

STACEY PAUL

ELECTRICAL ENGINEER:

GHAFARI ASSOCIATES

17101 MICHIGAN AVE.

DEARBORN, MI 48126

UPGRADE ELECTRICAL

SWITCHGEAR & DISTRIBUTION

ANN ARBOR VAMC

506-18-102

N/A Project Director

Revisions: Date:

SUITE 200

PROJECT NUMBER: 187371

313.441.3000

JEFF PEDERSEN

SWITCHBOARD #3-A

(E) FLAGPOLE

TEST

WELL

SWITCHBOARD #3-B SWITCHBOARD #2-A SWITCHBOARD #2-B

SWITCHBOARD #1-A SWITCHBOARD #1-B

T-GEN

TEST WELL

LINEWEIGHT LEGEND:

NEW POWER

CONTROL

EXISTING POWER

15KV

MVS-GEN

ATS EQUIPMENT

BY OTHERS

FRONT

FRONT

FRONT

FRONT

FRONT

SITE LTS.

WEST

(E) LP-A (E) PP-A

EXH. FAN #1

EXH. FAN #2

EXH. FAN #3

(E) ASCO

LIGHTING

CONTACTOR

SWBD (E) PUMP

CONTROLLER

(E) AMBULANCE

GARAGE X-FMR

(E) PANEL

(E) PANEL

CC-B2

(E) POWER

LOGIC PANEL

FRONT

FRONT

3'-0" MINIMUM

INSTALL IN PHASE A

INSTALL IN PHASE B

TO EXISTING GROUND

BUS IN THE CABLE VAULT

TO EXISTING GROUND

BUS IN THE CABLE VAULT

KEY NOTES:

1. BOLT WITH LUGS, TO EXISTING BUS BAR (TYPICAL TO PRIMARY AND

SECONDARY SIDES OF TRANSFORMERS)

2. BOLLARDS ( SEE CIVIL DRAWINGS ).

3. OPENINGS IN THE FLOOR SLAB SHALL BE COVERED WITH STEEL PLATES OF

ADEQUATE STRENGTH AND SIZE.

4. INSTALL A 4" SQUARE, 2 1/8 " DEEP OUTLET BOX WITH A SINGLE GANG

ADJUSTABLE MUD RING AND 1" CONDUIT, STUBBED 6" INTO THE CEILING

SPACE. ELECTRICAL CONTRACTOR SHALL INSTALL (4) DATA OUTLETS, FACE

PLATE AND…