50194091 - Cliffdale Library Boiler Replacement - Drawings.pdf
PDF 12 MB Posted
- Attached to
- Cliffdale Library Boiler Replacement
- Solicitation number
- 600600CLBoil
- Issued by
- Cumberland County, North Carolina
About this file
This file contains mechanical, electrical, and plumbing (MEP) construction drawings for the Cliffdale Library Boiler Replacement project in Cumberland County, North Carolina, prepared by Dewberry Engineers Inc. The project involves the replacement of a 1,000 MBTU natural gas boiler located at 6882 Cliffdale Road, Fayetteville, NC 28314. The scope of work includes demolition of the existing boiler, heating hot water pump, and associated controls; installation of a new 1,000 MBTU natural gas high-efficiency condensing boiler with integral pump; provision of new natural gas piping, stainless-steel vent and combustion air systems, electrical connections, and a new building automation system plant controller. The contractor must coordinate multiple work mobilizations to minimize outages, with whole-building air handling unit and cooling outages limited to less than two days during off-hours or weekends, and heating loss limited to weekdays during the cooling season with moderate outdoor temperatures and low dewpoint conditions to avoid reheat or dehumidification requirements.
The drawings include detailed specifications for piping, controls, electrical connections, and equipment installation, with symbols, abbreviations, and general notes provided for mechanical and electrical work. The project requires contractor responsibility for permitting costs and includes two preferred brand alternates: Johnson Controls Inc. for controls and Reillo for the boiler. The contractor must provide hydronic testing, adjusting, and balancing services with a final report, perform system flushing and chemical treatment, and ensure integration of the new controller into the countywide building automation system with graphics, trending, and alarms. All work must comply with applicable federal, state, and local codes, including the Energy Conservation Code, with coordination required between mechanical, electrical, and other trades to maintain existing systems operability and protect materials to be retained by the owner.
View the file
Other files
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
Sheet Number Sheet Title
G-001 COVER SHEET
G-002 BUILDING CODE SUMMARY
PME001 SYMBOLS ABBREVATIONS & GENERAL NOTES
PMED111 DEMOLITION PLAN
PME111 NEW WORK PLAN
PME501 DETAILS
PME601 SCHEDULES
PME701 CONTROLS
A
54321
B
C
D
E
F
ELECTRICAL SEAL
APPROVED BY
CHECKED BY
REVISIONS
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SCALE
MECHANICAL SEAL
NO. DESCRIPTION DATE
C U
M
BE
R
LA
N D
C O
U N
TY
C
LI
FF
D
AL
E
LI
BR
AR
Y
BO
IL
ER
R
EP
LA
C
EM
EN
T
C
LI
FF
D
AL
E
R D
FA
YE
TT
EV
IL
LE
, N
C
50194091
10/07/2026
/2
/2
3:
:0
PM
P:
\5
1\
C
AD
\P M
E\
G
-0
C O
VE
R
S H
EE
T.
D W
G
2610 Wycliff Road Suite 410 Raleigh, NC 27607-3073 919.881.9939 NC License No. F-0929
Dewberry Engineers Inc.
KRC
TW
WLH
G-001
COVER SHEET
MEP:
6882 CLIFFDALE RD, FAYETTEVILLE, NC 28314
CLIFFDALE LIBRARY BOILER REPLACEMENT
CUMBERLAND COUNTY
CAMPUS MAP
OWNER:
VICINITY MAP CONTACTS
DRAWING INDEX
DEWBERRY ENGINEERS, INC.
2610 WYCLIFF ROAD
SUITE 410
RALEIGH, NC 27607
CONTACT:
Weston Hockaday, PE, P: 984.255.7051
E-MAIL:
whockaday@dewberry.com
CUMBERLAND COUNTY
ENGINEERING DEPARTMENT
130 GILLESPIE ST,
FAYETTEVILLE, NC 28301
CONTACT:
ABU-BAKR FARRAKHAN
P: 910.678.7813
E-MAIL:
afarrakhan@cumberlandcountync.gov
REMOVE AHU DUCTWORK, PIPING, CONDUIT, PNEUMATIC TUBING, AND FIRE ALARM AS REQUIRED
TO CREATE ACCESS OPENING FOR BOILER AND PUMP RIGGING THROUGH PENTHOUSE
MECHANICAL ROOM. DEMOLISH CONDUITS AND PNEUMATIC TUBING THAT ARE ABANDONED
BLOCKING ACCESS. RELOCATE CONDUIT AND PNEUMATIC PIPING STILL IN USE THAT ARE
BLOCKING ACCESS. PROVIDE CRANE AND RIGGING UP TO ROOF AND THROUGH PENTHOUSE.
PROVIDE NEW AHU DUCTWORK AND PIPING WITH INSULATION INSTALLATION AFTER NEW BOILER
RIGGED INTO PLACE TO RETURN AIR AND CHILLED WATER SYSTEM TO NORMAL OPERATION AND
OTHER ITEMS MAY BE REUSED. PREFABRICATE WHERE POSSIBLE TO REDUCE OUTAGE
DURATION.
REMOVE 1,000 MBTU NATURAL GAS BOILER.
REMOVE BUILDING HEATING HOT WATER PUMP LOCATED IN THE PENTHOUSE MECHANICAL
ROOM.
REMOVE EXISTING HEATING HOT WATER AND CHILLED WATER PLANT SYSTEM DIGITAL JCI
METASYS DX9100 CONTROLLER. AHU CONTROLLERS AND PNEUMATIC SYSTEM TO REMAIN FOR
OPERATION OF AHU CONTROL VALVES.
PROVIDE 1000 MBTU NATURAL GAS HIGH EFFICIENCY CONDENSING BOILER WITH INTEGRAL
PUMP TO FIT INTO EXISTING SPACE IN PENTHOUSE. PROVIDE MANUFACTURER STARTUP.
PROVIDE NEW STEEL NATURAL GAS PIPING WITH PRESSURE AND YELLOW PAINT LABELING AND
NEW GAS REGULATORS TO NEW BOILER.
PROVIDE NEW STAINLESS-STEEL VENT AND COMBUSTION AIR INTAKE THROUGH EXISTING
PENTHOUSE BOILER VENT ROOF CURB PENETRATION. UTILIZE DOUBLE WALL VENT WHERE
ACCESSIBLE IN PENTHOUSE. PROVIDE NEW FLASHING ON EXISTING ROOF CURB FOR NEW
PENETRATIONS.
PROVIDE NEW ELECTRICAL CONNECTIONS TO BOILER AND PUMPS. BOILER PUMP TO BE
POWERED AND CONTROLLED BY BOILER.
PROVIDE NEW BASE MOUNTED END SUCTION BUILDING HOT WATER PUMP WITH NEW VARIABLE
FREQUENCY DRIVE (VFD) WITH DISCONNECT IN LOCATION OF EXISTING MOTOR STARTER
DISCONNECT. PROVIDE PUMP ALIGNMENT WITH REPORT AFTER INSTALLATION.
PROVIDE NEW HEATING HOT WATER PIPING WITH FIBERGLASS INSULATION TO ACCOMMODATE
NEW BOILERS AND PUMP SYSTEM.
PROVIDE NEW AIR/DIRT SEPARATOR (AS), EXPANSION TANK (ET), MAKEUP WATER (MW),
PRESSURE REDUCING VALVE, SYSTEM FLUSHING, AND CHEMICAL TREATMENT (CHEM) FOR HOT
WATER SYSTEM.
PROVIDE NEW BUILDING AUTOMATION SYSTEM PLANT CONTROLLER FOR COMPLETE PLANT
SYSTEM INCLUDING BUT NOT LIMITED TO AIR COOLED CHILLER, CHILLER PUMP, BOILER, AND
BOILER BUILDING PUMP. PROVIDE NEW CONTROL WIRING TO NEW BOILER AND PUMP. PROVIDE
NEW WIRING TO ALL PUMP STARTERS AND VARIABLE FREQUENCY DRIVES. PROVIDE NEW
SENSORS AND RELAYS. INCLUDE RELAYS WITH HOA SWITCH FOR EXISTING STARTERS WITHOUT
HOA SWITCH. SEE SCHEMATIC FOR POINTS AND SEQUENCING TO BE PROVIDED. INTEGRATE
NEW CONTROLLER INTO COUNTYWIDE BUILDING AUTOMATION SYSTEM WITH GRAPHIC,
TRENDING, AND ALARMS. EXISTING CONTROL PANEL MAY BE REUSED IF 3RD PARTY LISTED
ASSEMBLY SIMILAR TO UL.
PROVIDE NEW EMERGENCY SHUTOFF SWITCH AND HARDWIRE FOR BOILER SHUTDOWN.
PROVIDE HYDRONIC TESTING ADJUSTING, AND BALANCING FOR BOILER AND PUMPS. PROVIDE
TAB REPORT.
PROVIDE TWO PIECE REMOVABLE COVER FOR MECHANICAL ROOM PENTHOUSE DOOR LOUVER.
LOUVER IS NO LONGER REQUIRED FOR DEMOLISHED BOILER ROOM COMBUSTION AIR INTAKE
BUT MAY BE REMOVED FOR THERMOSTAT CONTROLLED PENTHOUSE EXHAUST FAN MAKEUP IF
NEEDED.
CONTRACTOR TO INCLUDE PERMITTING COSTS.
ALTERNATE 1 - PREFERRED BRAND CONTROLS - JOHNSON CONTROLS INC
ALTERNATE 2 - PREFERRED BRAND BOILER - REILLO
PROVIDE MULTIPLE WORK MOBILIZATIONS AND STAGING FOR DEMOLITION AND INSTALLATION OF
EQUIPMENT, PIPING, CONTROLS, AND ELECTRICAL AS REQUIRED TO MEET THE OWNER OUTAGE
REQUIREMENTS.
ACCESS AND RIGGING SCOPE OF WORK RESULTING IN WHOLE BUILDING AHU AND COOLING
OUTAGE MUST BE LIMITED TO LESS THAN 2 DAY OUTAGE DURING OFF HOURS, WEEKEND OR
HOLIDAY PERIOD DURING MODERATE OUTDOOR TEMPERATURES AND DEWPOINT (60F TO 80F).
BOILER REPLACEMENT SCOPE OF WORK RESULTING IN LOSS OF HEATING MUST BE LIMITED TO
WEEKDAYS DURING MODERATE OUTDOOR TEMPERATURES DURING COOLING SEASON FROM 65F
TO 80F AND DEWPOINT BELOW 55F TO AVOID NEED FOR REHEAT/DEHUMIDIFICATION NEEDS.
CHILLER AND AIR HANDLERS MUST REMAIN ACTIVE.
PROJECT SCOPE
10/07/2026
10/07/2026
Docusign Envelope ID: BA62D07C-0566-83AC-82E8-2AF9FB156B34
./50194091 G-001 COVER SHEET.DWG#,G-001 COVER SHEET
./50194091 G-001 COVER SHEET.DWG#,G-001 COVER SHEET
./50194091 G-002 BUILDING CODE SUMMARY.DWG#,G-002 BUILDING CODE SUMMARY
./50194091 G-002 BUILDING CODE SUMMARY.DWG#,G-002 BUILDING CODE SUMMARY
./50194091 PME001 SYMBOLS ABBREVATIONS & GENERAL NOTES.DWG#,PME001 SYMBOLS ABBREVATIONS & GENERAL NOTES ./50194091 PME001 SYMBOLS ABBREVATIONS & GENERAL NOTES.DWG#,PME001 SYMBOLS ABBREVATIONS & GENERAL NOTES
./50194091 PMED111 DEMOLITION PLAN.DWG#,PMED111 DEMOLITION PLAN
./50194091 PMED111 DEMOLITION PLAN.DWG#,PMED111 DEMOLITION PLAN
./50194091 PME111 NEW WORK PLAN.DWG#,PME111 NEW WORK PLAN
./50194091 PME111 NEW WORK PLAN.DWG#,PME111 NEW WORK PLAN
./50194091 PME501 DETAILS.DWG#,PME501 DETAILS
./50194091 PME501 DETAILS.DWG#,PME501 DETAILS
./50194091 PME601 SCHEDULES.DWG#,PME601 SCHEDULES
./50194091 PME601 SCHEDULES.DWG#,PME601 SCHEDULES
./50194091 PME701 CONTROLS.DWG#,PME701 CONTROLS
./50194091 PME701 CONTROLS.DWG#,PME701 CONTROLS
A
54321
B
C
D
E
F
ELECTRICAL SEAL
APPROVED BY
CHECKED BY
REVISIONS
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SCALE
MECHANICAL SEAL
NO. DESCRIPTION DATE
C U
M
BE
R
LA
N D
C O
U N
TY
C
LI
FF
D
AL
E
LI
BR
AR
Y
BO
IL
ER
R
EP
LA
C
EM
EN
T
C
LI
FF
D
AL
E
R D
FA
YE
TT
EV
IL
LE
, N
C
50194091
10/07/2026
/2
/2
3:
:1
PM
P:
\5
1\
C
AD
\P M
E\
G
-0
B U
IL
D
IN
G
C O
D E
SU
M
M
AR
Y.
D
W G
2610 Wycliff Road Suite 410 Raleigh, NC 27607-3073 919.881.9939 NC License No. F-0929
Dewberry Engineers Inc.
KRC
TW
WLH
G-002
BUILDING CODE
SUMMARY
10/07/2026
10/07/2026
Docusign Envelope ID: BA62D07C-0566-83AC-82E8-2AF9FB156B34
54321
B
C
D
E
F
ELECTRICAL SEAL
APPROVED BY
CHECKED BY
REVISIONS
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SCALE
MECHANICAL SEAL
NO. DESCRIPTION DATE
C U
M
BE
R
LA
N D
C O
U N
TY
C
LI
FF
D
AL
E
LI
BR
AR
Y
BO
IL
ER
R
EP
LA
C
EM
EN
T
C
LI
FF
D
AL
E
R D
FA
YE
TT
EV
IL
LE
, N
C
50194091
10/07/2026
/2
/2
3:
:2
PM
P:
\5
1\
C
AD
\P M
E\
P
M E0
S
YM
BO
LS
A
BB
R
EV
AT
IO
N
S
G
EN
ER
AL
N O
TE
S.
D W
G
2610 Wycliff Road Suite 410 Raleigh, NC 27607-3073 919.881.9939 NC License No. F-0929
Dewberry Engineers Inc.
KRC
TW
WLH
PME001
SYMBOLS
ABBREVATIONS &
GENERAL NOTES
ABBREVIATIONS - MECHANICAL
THIS IS A MASTER ABBREVIATIONS LIST. SOME ABBREVIATIONS MAY NOT APPLY
TO THIS PROJECT.
(E) EXISTING
AC AIR CONDITIONING
ADJ ADJUSTABLE
AF AIRFLOW
AFF ABOVE FINISHED FLOOR
AHU AIR HANDLING UNIT
AI ANALOG INPUT
AO ANALOG OUTPUT
AS AIR SEPARATOR
ASHRA
E
AMERICAN SOCIETY OF HEATING,
REFRIGERATING, AND AIR-CONDITIONING
ENGINEERS
ATC AUTOMATIC TEMPERATURE CONTROL
ATV ATMOSPHERIC VENT
B BOILER
BAS BUILDING AUTOMATION SYSTEM
BHP BRAKE HORSEPOWER
BI BINARY INPUT
BO BINARY OUTPUT
BT BUFFER TANK
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
CD CONDENSATE DRAIN
CFM CUBIC FEET PER MINUTE
CH CHILLER
CHWP CHILLED WATER PUMP
CO CARBON MONOXIDE
CO2 CARBON DIOXIDE
CONT CONTROLS, CONTINUED
CT COOLING TOWER
Cv VALVE COEFFICIENT
DB DRY BULB
DEG DEGREE
DI DIGITAL INPUT
DIA DIAMETER
DN DOWN
DO DIGITAL OUTPUT
DP DIFFERENTIAL PRESSURE
DPS DIFFERENTIAL PRESSURE (SENSOR)
DP DEW POINT
DWG DRAWING
EA EXHAUST AIR
EAT ENTERING AIR TEMPERATURE
ABBREVIATIONS - MECHANICAL
THIS IS A MASTER ABBREVIATIONS LIST. SOME ABBREVIATIONS MAY NOT APPLY
TO THIS PROJECT.
ECM ELECTRONICALLY COMMUTATED MOTOR
EF EXHAUST FAN
ELEC ELECTRICAL
ESP EXTERNAL STATIC PRESSURE
ET EXPANSION TANK
EWT ENTERING WATER TEMPERATURE
F DEGREES FAHRENHEIT
FD FIRE DAMPER OR FLOOR DRAIN
FLA FULL LOAD AMPS
FPM FEET PER MINUTE
FS FLOW SWITCH
FT FOOT/FEET
GA GAUGE
GAL GALLONS
GALV GALVANIZED
GC GENERAL CONTRACTOR
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
GR GRAINS
H HUMIDIFIER OR HEIGHT
H2O WATER
HD HEAD
HP HORSEPOWER
HVAC HEATING, VENTILATION, AND AIR-CONDITIONING
HWB HOT WATER BOILER
HWT HEATING WATER TEMPERATURE
IN INCH
KW KILOWATT
L LOUVER
LAT LEAVING AIR TEMPERATURE
LBS POUNDS
LF LINEAR FEET
LWT LEAVING WATER TEMPERATURE
M MOTOR OR MOTORIZED DAMPER OR METER
MA MIXED AIR
MAT MIXED AIR TEMPERATURE
MBH 1,000 BRITISH THERMAL UNITS PER HOUR
MCA MINIMUM CIRCUIT AMPACITY
MFR MANUFACTURER
MOCP MAXIMUM OVERCURRENT PROTECTION
NC NORMALLY CLOSED OR NOISE CRITERIA
NO NORMALLY OPEN OR NUMBER
ABBREVIATIONS - MECHANICAL
THIS IS A MASTER ABBREVIATIONS LIST. SOME ABBREVIATIONS MAY NOT APPLY
TO THIS PROJECT.
NPSH NET POSITIVE SUCTION HEAD
NTS NOT TO SCALE
OA OUTDOOR AIR
OAT OUTDOOR AIR TEMPERATURE
OD OUTSIDE DIAMETER
P PRESSURE OR PRESSURE SENSOR
PD PRESSURE DROP
PH PHASE
PHC PREHEAT COIL
PRV PRESSURE REDUCING VALVE
PSI POUNDS PER SQUARE INCH
PSIA POUNDS PER SQUARE INCH ABSOLUTE
PSIG POUNDS PER SQUARE INCH GAUGE
QTY QUANTITY
R RADIUS, RISE, OR REMOVE
RA RETURN AIR
RAT RETURN AIR TEMPERATURE
RH RELATIVE HUMIDITY, REHEAT
RPM REVOLUTIONS PER MINUTE
SCH SCHEDULE
SEC SECONDS
SF SUPPLY FAN OR SQUARE FOOT
SP STATIC PRESSURE
SS SPLIT SYSTEM OR STAINLESS STEEL
T, TEMP TEMPERATURE
T&P TEMPERATURE AND PRESSURE
T-STAT THERMOSTAT
TON COOLING TONS (12,000 BTUH)
TSP TOTAL STATIC PRESSURE
TYP TYPICAL
UH UNIT HEATER
V, VOLT VOLTAGE
VEL VELOCITY
VFD VARIABLE FREQUENCY DRIVE
W WIDTH OR WATTS
W/ WITH
WB WET BULB
WC WATER COLUMN
WCU WATER CHILLING UNIT
WG WATER GAUGE
WPD WATER PRESSURE DROP
1. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH APPLICABLE FEDERAL,
STATE AND LOCAL CODES AND REGULATIONS. MECHANICAL EQUIPMENT SHALL BE
SELECTED TO MEET OR EXCEED THE REQUIREMENTS OF THE ENERGY
CONSERVATION CODE. MECHANICAL WORK SHALL COMPLY WITH PROJECT
SPECIFICATIONS.
2. FURNISH AND INSTALL ALL INCIDENTAL ACCESSORIES REQUIRED TO MAKE THE
MECHANICAL WORK COMPLETE AND OPERATIONAL.
3. THESE DRAWINGS ARE DIAGRAMMATIC. EXACT EQUIPMENT LOCATIONS AND DUCT
AND PIPING ROUTING SHALL BE COORDINATED WITH THE BUILDING AND SITE
CONDITIONS. THE ACTUAL EQUIPMENT AND MINIMUM CLEARANCE DIMENSIONS
SHALL BE VERIFIED WITH THE SUPPLIERS.
4. EQUIPMENT, DUCTWORK, PIPING AND CONDUIT LAYOUT SHALL BE COORDINATED
WITH BUILDING COMPONENTS AND OTHER TRADES PRIOR TO INSTALLATION. THE
SYSTEM SHALL BE NEATLY ARRANGED TO MAXIMIZE SPACE. MAINTAIN MINIMUM
EQUIPMENT AND DEVICE MAINTENANCE CLEARANCES. DEVICES SHALL BE READILY
MAINTAINABLE. METERS AND GAGES SHALL BE ORIENTED FOR BEST VIEW.
INSTALLED MATERIALS NOT COORDINATED SHALL BE REMOVED AND REINSTALLED
AT NO ADDITIONAL COST TO THE OWNER.
5. WALL-MOUNTED CONTROL SENSORS SHALL BE INSTALLED AT 48-INCHES ABOVE THE
FLOOR TO THE TOP OF BACK-BOX. COORDINATE EXACT LOCATIONS WITH LIGHT
SWITCHES. WHEN BOTH ARE INDICATED ADJACENT TO A DOOR, LOCATE THE
SWITCH CLOSEST TO THE DOOR AND THE SENSOR WITHIN 12-INCHES OF THE
SWITCH.
6. CONTROL AND ALARM DEVICES SHALL BE INSTALLED IN BACK-BOXES WITHIN NEW
AND EXISTING WALLS. SURFACE-MOUNTED CONDUIT AND RACEWAY WILL NOT BE
ACCEPTED EXCEPT FOR EXISTING SOLID CONCRETE WALLS. DEVICE BACK-BOXES
IN FIRE-RATED WALLS SHALL HAVE FIRESTOP PUTTY PADS OR EQUIVALENT
UL-LISTED INSTALLATION.
7. HVAC PIPING SHALL BE NO LESS THAN 3/4-INCH.
8. ALL MOTORIZED EQUIPMENT SHALL BE CONNECTED TO DUCTWORK OR PIPING WITH
FLEXIBLE CONNECTIONS.
9. ROOF MODIFICATIONS AND REPAIRS SHALL MEET THE REQUIREMENTS OF THE ROOF
WARRANTY.
10. EXTEND POWER CONDUIT AND WIRING FROM DEDICATED POWER SOURCES TO
CONTROL EQUIPMENT AND DEVICES. COORDINATE POWER SOURCES WITH
ELECTRICAL CONTRACTOR.
11. MAINTAIN MINIMUM 36-INCH CLEARANCE FOR 120/208V POWER OR 42-INCH
CLEARANCE FOR 277/480V POWER AS REQUIRED BY THE NATIONAL ELECTRIC CODE
FOR ELECTRICAL EQUIPMENT AND TO PROVIDE MAINTENANCE ACCESS.
12. COORDINATE ALL CLEARANCES WITH OTHER TRADES. ENSURE ACCESS DOORS
CAN BE OPENED FULLY AND ALL VALVES, DAMPERS AND DEVICES CAN BE EASILY
REACHED AND ACTUATED.
13. FIELD VERIFY EXACT PIPING SIZES AND FLOW DIRECTIONS PRIOR TO CONNECTING
TO PIPING SYSTEM.
14. SCHEDULE ALL SERVICE DISRUPTIONS AND SHUTDOWNS WITH THE OWNER NO LESS
THAN 2 WEEKS IN ADVANCE. SHUT DOWNS IMPACTING CHILLED WATER SYSTEM
SHALL BE SCHEDULED OVERNIGHT TO MINIMIZE IMPACT TO LIBRARY HOURS.
MECHANICAL GENERAL
NEW WORK NOTES
1. VERIFY PROJECT SITE EXISTING CONDITIONS PRIOR TO BID. EXISTING CONDITIONS
INDICATED IN THESE DOCUMENTS ARE APPROXIMATE AND DO NOT INCLUDE EVERY
COMPONENT.
2. RECORD EXISTING CONDITIONS PRIOR TO THE START OF WORK. REPAIR DAMAGES
RESULTING FROM PROJECT WORK.
3. COORDINATE MATERIALS TO BE RETAINED BY THE OWNER PRIOR TO THE START OF
DEMOLITION WORK. RETAINED MATERIALS SHALL BE DELIVERED TO A POINT
DESIGNATED BY THE OWNER WITHIN A 10-MILE RADIUS OF THE PROJECT SITE.
PROPERLY DISPOSE OF ALL REMAINING DEMOLITION MATERIALS. COMPLY WITH
MATERIAL RECYCLING REQUIREMENTS. DO NOT ABANDON IN PLACE ANY ITEMS
IDENTIFIED TO BE REMOVED UNLESS OTHERWISE NOTED.
4. THE SCOPE OF DEMOLITION FOR ITEMS TO BE REMOVED INCLUDES ASSOCIATED
SUPPORTS, POWER CONNECTIONS, CONTROLS, ETC.
5. PERFORM ALL DEMOLITION INDICATED INCLUDING THAT REQUIRED TO INSTALL NEW
WORK. REMOVE AND REINSTALL MATERIALS TO REMAIN AS NEEDED WHERE
REQUIRED TO PERFORM DEMOLITION OR TO INSTALL NEW WORK. REPAIR DAMAGED
SURFACES TO MATCH EXISTING ADJACENT SURFACES.
6. REMOVE DUCT, PIPING AND CONDUIT BACK TO POINTS INDICATED. PREPARE OPEN
ENDS FOR CONNECTION TO NEW WORK INDICATED OR CAP.
MECHANICAL GENERAL
DEMOLITION WORK NOTES
ECCENTRIC TRANSITION
CONCENTRIC TRANSITION
RADIUS OFFSET (IN THE VERTICAL)
MITERED OFFSET (IN THE VERTICAL)
RADIUS ELBOW
MITERED ELBOW WITH TURNING VANES
SUPPLY DUCT
RETURN AIR DUCT
EXHAUST AIR DUCT
FLEX DUCT
DEMOLITION DUCTWORK OR EQUIPMENT
EXISTING DUCTWORK OR EQUIPMENT
NEW DUCTWORK OR EQUIPMENT
SYMBOL DESCRIPTION
HVAC SYMBOLS
CARBON MONOXIDE SENSOR
CARBON DIOXIDE SENSOR
OXYGEN SENSOR
TEMPERATURE SENSOR
HUMIDITY SENSOR
EMERGENCY POWER OFF SWITCH (E-STOP)
MANUAL MOTOR STARTER, FRACTIONAL HORSEPOWER
(SEE STARTER SCHEDULE FOR SIZE, ETC.)
CONTROLS
HVAC SYMBOLS CONTINUED
H
T
O2
CD
CO
M
24x24
DROPRISE
DROPRISE
DROPRISE
NON-FUSIBLE SAFETY SWITCH
FUSIBLE SAFETY SWITCH
COMBINATION MOTOR STARTER/SAFETY SWITCH,
ENCLOSED CIRCUIT BREAKER
VARIABLE FREQUENCY DRIVE (VFD)
DISCONNECT SWITCH
(FURNISHED BY OTHERS)
SYMBOL DESCRIPTION
BALL VALVE
STOP VALVE
3-WAY VALVE
BALANCING VALVE AUTOMATIC
BACKWATER VALVE
BUTTERFLY VALVE
CHECK VALVE
GATE VALVE
GLOBE VALVE
PIPE TURN UP
PIPE TURN DOWN
PIPE BOTTOM TAKE OFF
PIPE TOP TAKE OFF
PIPE CAP OR PLUG
PIPE UNION
AF
MECHANICAL PIPING SYMBOLS
PIPE GUIDE
BALANCING VALVE MANUAL
AV ATMOSPHERIC VENT
BBD BOILER BLOW DOWN
CA COMPRESSED AIR
CD CONDENSATE DRAIN
D DRAIN
CHWR CHILLED WATER RETURN
CHWS CHILLED WATER SUPPLY
HWR HEATING WATER RETURN
HWS HEATING WATER SUPPLY
MU MAKEUP WATER
NG NATURAL GAS
MECHANICAL PIPING SYSTEMS
SYMBOL DESCRIPTION
T
AFMS
FS
ES
HL
BASN
BAS
AI AO DI DO
R
VFD
STR
EP
EPT
PRESSURE REDUCING VALVE
BACK FLOW PREVENTER
TRIPLE DUTY
RELIEF (R) OR SAFETY (S) VALVE
PRESSURE GAGUE
TEMPERATURE GAUGE
TEMPERATURE SENSOR
DIFFERENTIAL PRESSURE SENSOR
MAGNEHELIC GAUGE
CURRENT TRANSDUCER (SENSOR)
AIR FLOW MONITORING STATION
FLOW SWITCH
END SWITCH
HUMIDITY - HIGH LIMIT SWITCH
NETWORK POINT FOR BAS
NETWORK BUILDING AUTOMATION SYSTEM CONTROL PANEL
DDC CONTROL POINTS
TRANSFORMER
RELAY
VARIABLE FREQUENCY DRIVE
STARTER
ELECTRONIC OR ELECTRIC TO PNEUMATIC SWITCH
ELECTRONIC OR ELECTRIC TO PNEUMATIC TRANSDUCER
R/S
PRV-1
VFD
CT
DP
MECHANICAL SCHEMATIC SYMBOLS
DESIGNATIONS
"AI" = ANALOG INPUT
"AO" = ANALOG OUTPUT
"DI" = DIGITAL INPUT
"DO" = DIGITAL OUTPUT
GAUGES/SENSORS
PIPE ACCESSORIES & SPECIALTIES
PNEUMATIC SYMBOLS
ELECTRONIC CONTROLS
AV
FLOW METER, INDICATE IF RATE OR TOTALING & UNITS
FLOW INDICATOR
FLEXIBLE CONNECTOR
AIR VENT, MANUAL
AIR VENT, AUTOMATIC
BTU METER, INDICATE IF RATE OR TOTALING & UNITS
UNIT/TIME
FM
UNIT/TIME
BTU
SUCTION DIFFUSER
FLOW ARROW
REDUCER CONCENTRIC
REDUCER ECCENTRIC STRAIGHT INVERT
REDUCER ECCENTRIC STRAIGHT CROWN
PT PORT (PEETS PLUG)
FLANGED CONNECTION
VALVES
BALL
THREE WAY
BUTTERFLY
GATE
END CAP
PIPE UNION
STRAINER, W/ OR W/ OUT VALVE.
STOP (HANDLE OPTIONAL)
CHECK
GLOBE
T TEMPERATURE SENSOR
STANDARDS DETAILING SYMBOLS
SYMBOL DESCRIPTION
SHEET REF.
PLAN / DETAIL
REF.
SECTION REF.
SHEET REF.
BUILDING / WALL
SECTION
SIM
SCALE:
VIEW TITLEVIEW NAMEVIEW DESIGNATION
VIEW SCALE
LEVEL NAME
LEVEL ELEVATION
GRID NUMBER
OR LETTER
GRID LINE
INDICATES
PLAN NORTH
INDICATES
TRUE NORTH
NORTH INDICATOR
ROOM NUMBER
ROOM TAG
REVISION NUMBER REVISION TAG
REVISION CLOUD
KEYNOTE TAG
(PER SHEET NUMBERS)
SPOT ELEVATION
SYMBOL
POINT OF
CONNECTION
POINT OF
DISCONNECTION
ELEVATION AT
POINT INDICATED
1' - 0"
Space Name
A
FIRST FLOOR
100' - 0"
1 View Name 1/8" = 1'-0"
A-101
A-101
AREA TO BE
ENLARGED
CALLOUT
LEVEL LINE
LINETYPES
BACKGROUND
EXISTING
DEMOLITION
NEW
FUTURE
HIDDEN/UNDER
OBSTRUCTION
WIRES DESCRIPTION
LC-1-1
HOME RUN. NUMERALS INDICATE PANELBOARD AND
CIRCUIT NUMBERS.
INDICATES CIRCUIT CONTINUATION
INDICATES CONDUIT RISER UP
INDICATES CONDUIT RISER DOWN
CIRCUIT SYMBOLS
SWBD1
WALL MOUNTED PANEL
RECESSED PANEL
POWER SYMBOLS
SYMBOL DESCRIPTION
JUNCTION BOX
C
EI
LI
N
G M
TD
W
AL
L M
TD
ST
U
B U
P
N O
R M
AL
FL
O
O R
M
TD
DUPLEX OUTLETS
EQUIPMENT CONNECTION
MANUAL MOTOR STARTER, FRACTIONAL HORSEPOWER (SEE
STARTER SCHEDULE FOR SIZE, ETC.)
NON-FUSIBLE SAFETY SWITCH
UTILITY METER
SUBSCRIPTS
"GF" = GROUND FAULT
"WP" = WEATHERPROOF BOX
"WR" = WEATHER RESISTANT
FUSIBLE SAFETY SWITCH
COMBINATION MOTOR STARTER/SAFETY SWITCH,
ENCLOSED CIRCUIT BREAKER
VARIABLE FREQUENCY DRIVE (VFD)
ELECTRICAL EQUIPMENT/GEAR
SIZE, TYPE, AND MOUNTING AS SHOWN AND/OR NOTED.
POWER DISTRIBUTION
/ C R
IT
IC
AL
EM
ER
G
EN
C
Y e
JJ
M
J
1. ELECTRICAL PLANS ARE GENERALLY DIAGRAMMATIC IN NATURE AND DO NOT CONVEY ALL
DETAILS REQUIRED FOR A COMPLETE INSTALLATION. HOWEVER, THESE PLANS SHALL BE
FOLLOWED AS CLOSELY AS POSSIBLE FOR GENERAL ARRANGEMENT AND LOCATION OF
EQUIPMENT. REFER TO ARCHITECTURAL PLANS FOR EXACT LOCATIONS, DIMENSIONS AND
MOUNTING METHODS. CONTRACTOR SHALL VERIFY ALL DIMENSIONS PRIOR TO COMMENCING
WORK. CONTRACTOR SHALL VERIFY STRUCTURAL AND FINISH CONDITIONS PRIOR TO
COMMENCING WORK. CONTRACTOR SHALL ARRANGE WORK TO MEET THESE CONDITIONS AND
PROVIDE SUCH EQUIPMENT AND ACCESSORIES AS MAY BE REQUIRED. IN THE EVENT OF A
CONFLICT, DEVIATION OR DISCREPANCY FOUND WITHIN THE PLANS OR SPECIFICATIONS,
CONTRACTOR SHALL PROVIDE WRITTEN NOTIFICATION TO ENGINEER OF RECORD FOR
CLARIFICATION PRIOR TO COMMENCING WORK.
2. ALL WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE PROJECT SPECIFICATIONS,
MANUFACTURERS' RECOMMENDED INSTALLATION PROCEDURES, THE AMERICANS WITH
DISABILITIES ACT, ANSI A117.1, NEC, NFPA AND ALL OTHER APPLICABLE LOCAL AND STATE
CODES AS ADOPTED AND MODIFIED BY THE AUTHORITIES HAVING JURISDICTION.
3. CONTRACTOR SHALL LABEL ALL COVERPLATES, EQUIPMENT, JUNCTION BOXES, AND PULL
BOXES WITH CIRCUIT AND PANEL DESIGNATIONS. REFER TO DETAILS AND SPECIFICATIONS
FOR SPECIFIC LABEL AND IDENTIFICATION REQUIREMENTS.
4. CONTRACTOR SHALL PROVIDE NEW, TWO COLUMN, TYPED, COMPLETED AND REMOVABLE
DIRECTORIES INDICATING CIRCUIT DESCRIPTIONS AND ROOM NUMBERS (AS INDICATED BY
FINAL ROOM SIGNAGE), FOR ALL AFFECTED CIRCUITS WITHIN ELECTRICAL DISTRIBUTION
EQUIPMENT. ALL SPACES SHALL BE INDICATED AS SUCH. ALL SPARES SHALL BE INDICATED AS
SUCH AND PLACED IN THE "OFF" POSITION.
5. MINIMUM RACEWAY SIZE OF 3/4", UNLESS NOTED OTHERWISE.ALL ELECTRICAL CONDUCTORS, EQUIPMENT AND TERMINALS SHALL BE 75°C RATED UNLESS NOTED OTHERWISE. MINIMUM
CONDUCTOR SIZE OF #12AWG, COPPER, THHN/THWN, FOR BRANCH CIRCUITS, UNLESS NOTED
OTHERWISE.
6. ALL RACEWAYS SHALL BE INSTALLED CONCEALED ABOVE CEILINGS, WITHIN WALLS EXCEPT
WITHIN UNFINISHED SPACES AND ON CEILINGS OF AREAS WITH EXPOSED STRUCTURE. WITHIN
PUBLIC SPACES, EXPOSED RACEWAY SHALL BE SURFACE MOUNT RACEWAY THAT IS FACTORY
OR FIELD PAINTED TO MATCH ADJACENT STRUCTURE.
7. ALL CONDUITS SHALL BE ROUTED PARALLEL OR PERPENDICULAR TO BUILDING STRUCTURE.
ALL CONDUITS ROUTED IN PARALLEL SHALL UTILIZE CONCENTRIC BEND RADII FOR ALL TURNS.
8. ALL EMPTY RACEWAYS SHALL BE PROVIDED WITH PULL STRINGS INSTALLED PER
SPECIFICATIONS.
9. ALL EXPOSED RACEWAY ENDS SHALL BE PROVIDED WITH PLASTIC BUSHINGS.
10. ALL BRANCH AND FEEDER CIRCUITS SHALL ORIGINATE FROM PANELS AND SERVE DEVICES AND
EQUIPMENT AS INDICATED ON PLANS AND SCHEDULES. IN THE EVENT OF A CONFLICT,
DEVIATION OR DISCREPANCY, CONTRACTOR SHALL PROVIDE WRITTEN NOTIFICATION TO
ENGINEER OF RECORD FOR CLARIFICATION PRIOR TO COMMENCING WORK.
11. ALL BRANCH CIRCUITS SHALL HAVE A DEDICATED NEUTRAL CONDUCTOR, UNLESS NOTED
OTHERWISE. THE USE OF A COMMON NEUTRAL FOR MULTIPLE BRANCH CIRCUITS IS STRICTLY
PROHIBITED.
12. ALL RACEWAYS CONTAINING A FEEDER OR BRANCH CIRCUIT SHALL BE PROVIDED WITH AN
INSULATED EQUIPMENT GROUNDING CONDUCTOR. FOR RACEWAYS CONTAINING MORE THAN
ONE BRANCH CIRCUIT, SIZE OF EQUIPMENT GROUNDING CONDUCTOR SHALL BE BASED ON THE
LARGEST CIRCUIT'S OVERCURRENT PROTECTIVE DEVICE.
13. ORIENT VERTICALLY MOUNTED RECEPTACLES WITH GROUND PIN UP. ORIENT HORIZONTALLY
MOUNTED RECEPTACLES WITH GROUND PIN TO LEFT (NEUTRAL UP).
GENERAL NOTES - ELECTRICAL
1. NEW WORK SHOWN BOLD AND CONTINUOUS. EXISTING TO REMAIN WORK SHOWN LIGHT AND
CONTINUOUS.
2. NOT ALL ELECTRICAL DEVICES AND EQUIPMENT ARE SHOWN.
3. ALL EXISTING DEVICES AND EQUIPMENT SHALL REMAIN IN PLACE AND OPERATIONAL UNLESS
NOTED OTHERWISE.
4. CONTRACTOR SHALL BE RESPONSIBLE FOR CONTINUITY OF ALL EXISTING CIRCUITS AND
SYSTEMS TO REMAINING DEVICES AND EQUIPMENT WHICH MAY BE AFFECTED BY AREA OF
WORK. MATCH AND EXTEND CONDUIT, CONDUCTORS, CABLES, ETC. AS NECESSARY TO
MAINTAIN CIRCUIT INTEGRITY.
5. ALL EXISTING RACEWAY AND WIRING THAT ARE TO REMAIN IN THE AREA OF WORK SHALL BE
RELOCATED AS REQUIRED TO PROVIDE OR MAINTAIN ACCESSIBILITY AND TO ACCOMMODATE
THE PROPOSED CONSTRUCTION. CONTRACTOR SHALL FIELD VERIFY ALL RACEWAY AND
WIRING TO REMAIN PRIOR TO COMMENCING WORK. ALL RELOCATION SHALL BE COORDINATED
WITH THE OWNER OR OWNER'S REPRESENTATIVE. PROVIDE TEMPORARY CONNECTIONS TO
EQUIPMENT AND DEVICES TO MAINTAIN EQUIPMENT AND SYSTEMS IN SERVICE. ALL DOWNTIME
REQUIRED FOR INSTALLATION OF TEMPORARY CONNECTIONS SHALL BE COORDINATED WITH
THE OWNER OR OWNER'S REPRESENTATIVE.
6. CONTRACTOR SHALL VERIFY NO DEVICES OR EQUIPMENT ARE SERVED BY BREAKERS
CURRENTLY LABELED "SPARE" TO BE UTILIZED FOR NEW WORK WITHIN AFFECTED ELECTRICAL
DISTRIBUTION EQUIPMENT. IN THE EVENT OF A CONFLICT, DEVIATION OR DISCREPANCY,
CONTRACTOR SHALL TRACE AND IDENTIFY SUSPECT LOAD(S) AND PROVIDE WRITTEN
NOTIFICATION TO ENGINEER OF RECORD FOR CLARIFICATION PRIOR TO COMMENCING WORK.
RENOVATION NOTES - ELECTRICAL
10/07/2026
B-1
HWP-1
COMPRESSION
TANK
COMPRESSION
TANK
AS
HVAC CONTROLS PANEL HWP-1 DISC (D)
(E) AHU-1
(E) AHU-3
(E) AHU-2
(E)CHWP-1
(E)UH
FD
PANEL F (E)
(E ) A
IR
C
O M
PR
ES
SO
R
(E) AHU
CONTROLS PANEL
(E) AIR DRYER
(E) RELIEF VENT
(E) MAKEUP WATER
CONNECTION
2" NG, 2 PSI
1" NG
F-25,27,29 e
J
F-16 e
F-14
J e
11 12
A
54321
B
C
D
E
F
ELECTRICAL SEAL
APPROVED BY
CHECKED BY
REVISIONS
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SCALE
MECHANICAL SEAL
NO. DESCRIPTION DATE
C U
M
BE
R
LA
N D
C O
U N
TY
C
LI
FF
D
AL
E
LI
BR
AR
Y
BO
IL
ER
R
EP
LA
C
EM
EN
T
C
LI
FF
D
AL
E
R D
FA
YE
TT
EV
IL
LE
, N
C
50194091
10/07/2026
/2
/2
3:
:5
PM
P:
\5
1\
C
AD
\P M
E\
P
M
ED
D
EM
O
LI
TI
O
N P
LA
N
.D W
G
2610 Wycliff Road Suite 410 Raleigh, NC 27607-3073 919.881.9939 NC License No. F-0929
Dewberry Engineers Inc.
WALL RATING LEGEND:
GENERAL NOTES:
1. DEMOLISH BOILER.
2. DEMOLISH PUMP. DISCONNECT REMOVE LOAD SIDE BRANCH
CIRCUIT (WIRING AND CONDUIT) BETWEEN EQUIPMENT
CONNECTION AND DEMOLISHED DISCONNECT AND CONTROL
WIRE. RETAIN LINE SIDE WIRE AND CONDUIT FOR RECONNECTION
IN NEW WORK. CONCRETE PAD EXISTING TO REMAIN.
3. DEMOLISH COMPRESSION TANK INCLUDING EQUIPMENT
SUPPORTS.
4. DEMOLISH AIR SEPARATOR.
5. DEMOLISH PIPING BACK TO POINTS INDICATED.
6. DEMOLISH FLUE DUCT AND STACK. ROOF CURB TO BE REUSED.
7. DEMOLISH GAS PIPING BACK TO ISOLATION VALVE IN PIPE RISER.
8. REMOVE RETURN AIR PLENUM ON AHU-1 TO MAKE SPACE FOR
BOILER INSTALLATION. INTERNALLY LINED PLENUM TO BE
REATTACHED AFTER BOILER IS INSTALLED. IF DAMAGED,
CONTRACTOR SHALL REPLACE AT NO ADDITIONAL COST TO
OWNER.
9. DEMOLISH LOW SECTION OF CHILLED WATER PIPING TO MAKE
SPACE FOR BOILER INSTALLATION.
10. TEMPORARILY REMOVE AHU CONDENSATE DRAINS ROUTED TO
FLOOR DRAIN TO MAKE SPACE FOR BOILER INSTALLATION.
CONDENSATE PIPING SHALL BE REATTACHED AFTER BOILER IS
INSTALLED. IF DAMAGED, CONTRACTOR SHALL REPLACE AT NO
ADDITIONAL COST TO OWNER.
11. DEMO JCI METASYS DX9100 CONTROLLER FOR HW AND CHW
PLANT. DISCONNECT LOAD SIDE BRANCH CIRCUIT (WIRING AND
CONDUIT) BETWEEN EQUIPMENT CONNECTION AND NEAREST
UPSTREAM JUNCTION BOX. RETAIN LINE SIDE WIRE AND CONDUIT
FOR RECONNECTION IN NEW WORK.
12. CONTRACTOR TO SHALL DEMOLISH PUMP DISCONNECT SWITCH.
RETAIN ALL LINE SIDE WIRING AND CONDUIT BACK SOURCE FOR
USE IN NEW WORK. DEMOLISH ALL WIRING AND CONDUIT ON
LOAD SIDE OF DISCONNECT SWITCH TO PUMP.
13. PNEUMATIC CONTROLS CABINET FOR AHU'S IS EXISTING TO
REMAIN.
14. COMPRESSOR AND AIR DRYER ARE EXISTING TO REMAIN.
15. DEMOLISH WIRING AND CONDUIT FROM JUNCTION BOX SHOWN
TO BOILER. RETAIN ALL WIRING AND CONDUIT BETWEEN
JUNCTION BOX AND PANEL "F" FOR REUSE IN NEW WORK.
# KEYNOTES:
SCALE:1 DEMOLITION PLAN
1/2" = 1'-0"
1. NOT ALL EXISTING EQUIPMENT, ELECTRICAL PANELS,
DISCONNECTS, EQUIPMENT PADS, ETC, ARE SHOWN.
CONTRACTOR SHALL REVIEW EXISTING CONDITIONS AND
COORDINATE NEW WORK WITH ELEMENTS THAT ARE EXISTING TO
REMAIN.
NO RATED WALLS IN PROJECT AREA.
PMED111
DEMOLITION PLAN
WLH
TW
KRC & KMS
0' 2' 4'1'
10/07/2026
(E) RELIEF VENT
6Ø
FL
U
E
6Ø
C O
M B.
A
IR
(E) MAKEUP WATER
CONNECTION
2" NG, 2 PSI
3" HWR
3" HWS
3" HWR
3" HWS
1" MAKEUP WATER
1-1/2" NGAS
F-25,27,29
J
F-16
F-14
J e
SB
J e e e
INTEGRAL
PWHP-1
CONNECTIONM
BOILER
CONNECTION M
B-1 DISC (N)
(E) AHU-1
(E) AHU-3
(E) AHU-2
(E)CHWP-1
(E)UH
FD
PANEL F (E)
(E ) A
IR
C
O M
PR
ES
SO
R
(E) AHU
CONTROLS PANEL
(E) AIR DRYER
B-1
AS-1
HWP-1
XT-1
BAS PLANT CONTROLLER
BOILER
MAINTENANCE
CLEARANCE
HWP-1 VFD (N)
A
54321
B
C
D
E
F
ELECTRICAL SEAL
APPROVED BY
CHECKED BY
REVISIONS
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SCALE
MECHANICAL SEAL
NO. DESCRIPTION DATE
C U
M
BE
R
LA
N D
C O
U N
TY
C
LI
FF
D
AL
E
LI
BR
AR
Y
BO
IL
ER
R
EP
LA
C
EM
EN
T
C
LI
FF
D
AL
E
R D
FA
YE
TT
EV
IL
LE
, N
C
50194091
10/07/2026
/2
/2
3:
:5
PM
P:
\5
1\
C
AD
\P M
E\
P
M E1
N
EW
W
O R
K
PL
AN
.D
W G
2610 Wycliff Road Suite 410 Raleigh, NC 27607-3073 919.881.9939 NC License No. F-0929
Dewberry Engineers Inc.
KRC
TW
WLH
PME111
NEW WORK PLAN
SCALE:1 NEW WORK PLAN
1/2" = 1'-0"
WALL RATING LEGEND:
GENERAL NOTES:
1. PROVIDE BOILER AND SNAP SWITCH DISCONNECT WITH
WEATHER PROOF COVER.
2. PROVIDE PUMP, MOUNT TO EXISTING CONCRETE PAD.
PROVIDE NEW VFD.
3. PROVIDE EXPANSION TANK. SUSPEND FROM ROOF
STRUCTURE.
4. PROVIDE AIR SEPARATOR.
5. PROVIDE PIPING AS SHOWN COMPLETE WITH ALL REQUIRED
SUPPORTS, ACCESSORIES, AND INSULATION. CONNECT
BACK TO EXISTING PIPING AS INDICATED.
6. PROVIDE FLUE AND COMBUSTION AIR DUCT TO EXISTING
ROOF CURB. PROVIDE FLUE STACK AND GOOSENECK
INTAKE. SEE DETAILS FOR MORE INFORMATION.
7. PROVIDE GAS PIPING AND REGULATOR. PROVIDE AT LEAST
10 FT OF PIPE DOWNSTREAM OF REGULATOR. VENT
REGULATOR TO EXTERIOR.
8. REATTACH EXISTING RETURN AIR PLENUM TO AHU-1. IF
DAMAGED, CONTRACTOR SHALL REPLACE AT NO
ADDITIONAL COST TO OWNER.
9. REROUTE CHILLED WATER PIPING UP CLOSER TO ROOF
STRUCTURE TO MAKE SPACE FOR BOILER INSTALLATION.
10. REATTACH AHU CONDENSATE PIPING. IF DAMAGED,
CONTRACTOR SHALL REPLACE AT NO ADDITIONAL COST TO
OWNER.
11. ELECTRICAL CONTRACTOR TO PROVIDE NEW 3#12, #12G IN
3/4" C LOAD SIDE BRANCH CIRCUIT (WIRING AND CONDUIT)
BETWEEN BAS CONNECTION AND NEAREST UPSTREAM
JUNCTION BOX. SPLICE AND RECONNECT BAS TO LINE SIDE
WIRE RETAINED DURING DEMOLITION. COORDINATE WITH
DIVISION 23 ON FINAL DISCONNECT LOCATION.
12. PROVIDE INSULATED PANEL TO CLOSE LOUVERS IN
MECHANICAL ROOM DOOR. MOUNT TO INTERIOR SIDE OF
DOOR.
13. PROVIDE EPO SWITCH AT PENTHOUSE DOORS. PROVIDE
ROUGH-IN FOR NEW EPO BUTTONS AS REQUIRED. IF OLD
ROUGH-IN ARE NOT AVAILABLE FOR USE, PROVIDE
JUNCTION BOX AT 48"AFF TO TOP OF BOX WITH 3/4"C TO
MECHANICAL CONTROLS, BAS. CABLING AND BUTTON
PROVIDED UNDER DIVISION 23 CONTRACT.
14. PROVIDE EPO SWITCH AT THE BASE OF LADDER IN
CONTROLS ROOM BELOW MECHANICAL PENTHOUSE.
MOUNT 48" AFF. PROVIDE JUNCTION BOX AT 48" AFF TO TOP
OF BOX WITH 3/4"C TO MECHANICAL CONTROLS, BAS.
CABLING AND BUTTON PROVIDED UNDER DIVISION 23
CONTRACT.
15. PROVIDE HONEYWELL #CO1224 SERIES OR APPROVED
EQUAL. DEVICE SHALL PROVIDE LOCAL CARBON MONOXIDE
DETECTION WITH AUDIO/VISUAL ALARM NOTIFICATION.
PROVIDE 4 CONDUCTOR CABLE IN 3/4"C FOR POWER AND
ALARM SIGNAL TO BAS.
16. PROVIDE BAS PLANT CONTROLLER. SEE CONTROLS
SCHEMATIC FOR ADDITIONAL INFORMATION.
17. SPLICE AND EXTEND EXISTING BRANCH CIRCUIT RETAINED
DURING DEMOLITION USING 2#12, #12G IN 3/4"C TO NEW
BOILER. PROVIDE NEW JUNCTION BOX FOR NEW BOILER
DISCONNECTING MEANS, COORDINATE LOCATION WITH
DIVISION 23.
18. EXTEND BRANCH CIRCUIT USING 3#12, #12G IN 3/4" C FROM
THE LOAD SIDE OF DISCONNECT TO NEW PUMP. DIVISION 26
SHALL INSTALL DISCONNECT SWITCH AND RECONNECT LINE
SIDE WIRE RETAINED DURING DEMOLITION.
# KEYNOTES:
0' 2' 4'1'
1. NOT ALL EXISTING EQUIPMENT, ELECTRICAL PANELS,
DISCONNECTS, EQUIPMENT PADS, ETC, ARE SHOWN.
CONTRACTOR SHALL REVIEW EXISTING CONDITIONS AND
COORDINATE NEW WORK WITH ELEMENTS THAT ARE EXISTING TO
REMAIN.
2. NOTE TO REVIEWER: NO ADDITIONAL ELECTRIC LOADS ADDED OR
REMOVED FROM THIS PROJECT.
NO RATED WALLS IN PROJECT AREA.
0' 2' 4'1'
10/07/2026
54321
B
C
D
E
F
ELECTRICAL SEAL
APPROVED BY
CHECKED BY
REVISIONS
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SCALE
MECHANICAL SEAL
NO. DESCRIPTION DATE
C U
M
BE
R
LA
N D
C O
U N
TY
C
LI
FF
D
AL
E
LI
BR
AR
Y
BO
IL
ER
R
EP
LA
C
EM
EN
T
C
LI
FF
D
AL
E
R D
FA
YE
TT
EV
IL
LE
, N
C
50194091
10/07/2026
/2
/2
3:
:1
PM
P:
\5
1\
C
AD
\P M
E\
P
M E5
D
ET
AI
LS
.D
W G
2610 Wycliff Road Suite 410 Raleigh, NC 27607-3073 919.881.9939 NC License No. F-0929
Dewberry Engineers Inc.
KRC
TW
WLH
PME501
DETAILS
CONDENSING BOILER SCALE: NTS
235216-004
DUCTED COMBUSTION AIR.
SEE PLANS FOR SIZE AND
ROUTING
BOILER BURNER
CONTROLS
PAINT 4" HIGH EQUIPMENT
PAD WITH OSHA APPROVED
YELLOW PAINT
GAS PRESSURE REGULATOR (TYP.) FOR
EACH BOILER NEAR FLOOR. VERIFY
INCOMING GAS PRESSURE AT METER.
REDUCE TO 14" W.C. PIPE RELIEF TO
BUILDING EXTERIOR
UNION
GAS SUPPLY
6" DIRT LEG
SEE PLUMBING
DRAWINGS FOR
GAS PIPING
DETAILS
PIPE TO
FLOOR DRAIN
CONDENSATE DRAIN
WITH CONDENSATE
NEUTRALIZATION KIT
HARD PIPED
BYPASS PIPE WITH VALVE
ASME PRESSURE
RELIEF VALVE
AL-29-4C STAINLESS
STEEL VENT STACK
FLOW CONTROL VALVE
HOT WATER SUPPLY
DIAL THERMOMETER
P
P
BOILER
DRAIN
NOTES:
1. VERIFY GAS PRESSURE RANGE
2. PREFER COMBUSTION AIR & VENT TO SAME WALL OR ROOF
TO MINIMIZE PRESSURE IMPACT ON EXTERIOR SURFACE
P
DIAL THERMOMETER
PRESSURE GAUGE
HOT WATER RETURN
10' MIN
MAINTAIN MINIMUM 10 FT FROM
REGULATOR OUTLET TO BOILER
CONNECTION. PIPE SIZE SHALL BE
ONE NOMINAL SIZE LARGER THAN
BOILER CONNECTION SIZE.
ELECTRICAL TO MECHANICAL EQUIPMENT SCALE: NTS
ME002-01
STARTER
OR VFD
PANELBOARD
GENERAL NOTES:
1. IT IS THE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO COORDINATE BETWEEN THE ELECTRICAL AND OTHER
TRADES.
2. ELECTRICAL CONTRACTOR PROVIDES DISCONNECT SWITCH IF NEEDED FOR ELEVATORS, KITCHEN EQUIPMENT, OR
OWNER FURNISHED EQUIPMENT.
3. IN ALL CASES THE CONTRACTOR SUPPLYING THE EQUIPMENT SHALL MAKE FINAL CONNECTIONS, START UP, AND TEST
EQUIPMENT.
KEYNOTES:
1. EQUIPMENT BY TRADES OTHER THAN ELECTRICAL.
2. CONDUIT & WIRING BY ELECTRICAL CONTRACTOR.
3. IF AN ADDITIONAL DISCONNECT IS REQUIRED BY NEC IT SHALL BE PROVIDED AND INSTALLED BY ELECTRICAL
CONTRACTOR.
4. A COMBINATION STARTER OR VFD MAY BE USED IN LIEU OF A SEPARATE DISCONNECT SWITCH AND STARTER / VFD.
DISCONNECT SWITCH AND STARTER/VFD PROVIDED BY ELECTRICAL CONTRACTOR. LOCATE DISCONNECT SWITCH
ADJACENT TO VFD.
5. FEEDER CIRCUIT WIRING AND CONDUIT IN ELECTRICAL WORK. SEE PANELBOARD SCHEDULE FOR BREAKER SIZES AND
BRANCH OR FEEDER SCHEDULES FOR WIRE/CONDUIT SIZES.
6. EQUIPMENT PROVIDED WITH INTEGRAL DISCONNECTING MEANS.
TYPICAL PIPE HANGERS SCALE: NTS
230529-003
ADJUSTABLE CLEVIS HANGERADJUSTABLE ROLLER HANGER
SIDE VIEW
TRAPEZE HANGER FOR UP TO 1000
LBS. UNIFORM LOAD
1/2" DIA. HANGER RODS
WITH 36" MAX. SPACING
ON EACH CHANNEL
BAND
PROVIDE INSULATION
SHIELD AND INSERT
FOR ALL PIPING
1-5/8" 12 GAGE
CHANNEL OR 2" X
2" X 1/4" ANGLE
HANGER ROD HANGER ROD
INSULATION
PIPE
SADDLE
INSULATION (VAPOR BARRIER
TYPE IS REQUIRED FOR LOW
TEMPERATURE PIPE)
PROVIDE HIGH COMPRESSIVE
STRENGTH INSULATION INSERT
UNDER INSULATION SHIELD
INSULATION SHIELD AT HANGER
4GAS PIPING PRESSURE REGULATOR SCALE: NTS
231123-002
PRESSURE
REGULATING
VALVE. PRV
TO
UNIT
GROUND JOINT UNION
GAS COCK
6'' TRAP
UTILIZATION
PRESSURE
GAS PIPING SUPPLY
GROUND JOINT UNION
MANUAL SHUTOFF VALVE WITH 1/8''
NPT PLUGGED TAPPING ACCESSIBLE
FOR TEST GAUGE CONNECTION
PIPE RELIEF TO
BUILDING EXTERIOR
SCALE: NTS
232116-002
AIR SEPARATOR / EXPANSION TANK
DRAIN WITH CAP
LOCK SHIELD VALVE
4" HIGH REINFORCED CONCRETE HOUSEKEEPING PAD
AUTOMATIC AIR VENT
BLADDER TYPE
EXPANSION
TANK
AIR
SEPARATOR
FINISHED
FLOOR
REMOVABLE STRAINER
DISCHARGE TO
FL.D.
AUTOMATIC AIR VENT
FLANGE CONNECTION
(TYPICAL)
CLEVIS
HANGER (TYP.)
DRAIN VALVE WITH HOSE THREAD
AND CAP
SKIM VALVE
PRE-CHARGING AIR
CONNECTION
TANK PURGE VALVE
TO PUMP
SUCTION
CONNECTION TO ADDITIONAL EXPANSION
TANK AS REQUIRED
NOTE:
1. REFER TO SCHEDULE FOR EXPANSION TANK CHARGE PRESSURE.
2. WHERE MAKEUP WATER CONNECT CANNOT BE MADE DIRECTLY TO AIR
SEPARATOR, CONNECT ON INLET SIDE OF PIPING.
UNION (TYP.)
SYSTEM
RETURN
RELIEF VALVE REFER TO
SCHEDULE
AV
AV
MAKEUP WATER
CONNECTION
BASE MOUNTED END SUCTION PUMP SCALE: NTS
232123-012
BUTTERFLY ISOLATION VALVE (LUG STYLE)
PUMP FLEX CONNECTOR. REFER TO
SPECS FOR ACCEPTABLE TYPES.
PROVIDE "SPOOL PIECE" SPACER IF NECESSARY TO
PROVIDE ADEQUATE PIPE SEPARATION FOR
INSTALLATION.
PIPE 1/2" GAUGE PRESSURE RELIEF
TO FLOOR DRAIN.
PUMP SUCTION DIFFUSER WITH STRAINER.
MAINTAIN MANF. SUGGESTED SERVICE
CLEARANCE FOR SUCTION FITTING AND
STRAINER REMOVAL.
PROVIDE ADJUSTABLE FOOT SUPPORT
FOR SUCTION FITTING
(E) FLOOR DRAIN
PROVIDE DRIP PAN. PIPE TO NEAREST FLOOR DRAIN.
PROVIDE PUMP WITH INTEGRAL GAUGE PORT TAPS ON
SUCTION & DISCHARGE.
PROVIDE CONCENTRIC REDUCERS WHERE REQUIRED.
PROVIDE BALL VALVES ON GAUGE PIPING (GAUGE COCKS
ARE NOT ACCEPTABLE). MOUNT GAUGE VALVES OUTSIDE
OF PUMP INSULATION COVER.
PIPE GAUGES WITH 1/2" BLACK STEEL PIPE. PAINT WITH
RUST INHIBITOR PAINT.
4" MIN. DIAL GLYCERINE FILLED PRESSURE GAUGE.
SPRING CHECK VALVE
BUTTERFLY ISOLATION VALVE (LUG STYLE). PROVIDE POSITION
LOCK OPERATOR. BALANCE SHALL SET POSITION STOP.
PUMP FLEX CONNECTOR. REFER TO SPECS FOR
ACCEPTABLE TYPES.
(E) CONCRETE EQUIPMENT PAD.
BLOWDOWN VALVE WITH 3/4" HOSE END
AND CAP
NOTE :
MAINTAIN REQUIRED CLEARANCE TO COMBUSTABLES PER CODE
AND FLUE MANUFACTURER.
BOILER STACK AND INTAKE SCALE: NTS
235216-005
2X FLUE
DIA. MIN.
30°
HEIGHT AS REQ'D BY LOCAL
CODE. 24" MINIMUM ABOVE
HIGHEST POINT OF ROOF OR
OBSTRUCTION WITHIN 10FT OF
VENT
RAIN CAP
12"
6"
1 1/2"
ROOF THIMBLE
GALVANIZED SLEEVE
WITH WELDED BASE
ROOF
WEATHER SHIELD, WELD
OR POP RIVIT TO FLUE
BOILER FLUE STACK
EMERGENCY PUSH OFF STATION (EPO) SCALE: NTS
250100-001
WHITE LETTERING
CLEAR PLASTIC COVER
BLACK LETTERING ON
CLEAR PLASTIC COVER.
BLACK LETTERING
DESIGNATING AHU ON
WHITE BACKGROUND
RED PUSH BUTTON
BLUE BACKGROUND
WHITE LETTERING
CONTINUOUS
MASTIC SEAL
ALUMINUM
BIRD SCREEN
18 GA. GALV. DUCT WELD ALL
JOINTS TO BE WATERTIGHT -
SEE PLANS FOR SIZE
30°
BOILER COMBUSTION
AIR INTAKE
WIRE COLOR CODING 120/208V SCALE: NTS
E002-07
BLACK
PHASE-C BLUE
PHASE-B RED
PHASE-A BLACK
DODO
BLACK
BLUE
RED
BLUE
RED
DO
120/208 VOLTS
DO
BLACK
BLACK
BLUE
RED
BLUE
RED
GROUND BUS
NEUTRAL BUS
WHITE
120/208 VOLTS
GREEN
TOP OR BOTTOM FEED
(SEE RISER DIAGRAM)
10/07/2026
54321
B
C
D
E
F
ELECTRICAL SEAL
APPROVED BY
CHECKED BY
REVISIONS
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SCALE
MECHANICAL SEAL
NO. DESCRIPTION DATE
C U
M
BE
R
LA
N D
C O
U N
TY
C
LI
FF
D
AL
E
LI
BR
AR
Y
BO
IL
ER
R
EP
LA
C
EM
EN
T
C
LI
FF
D
AL
E
R D
FA
YE
TT
EV
IL
LE
, N
C
50194091
10/07/2026
/2
/2
3:
:3
PM
P:
\5
1\
C
AD
\P M
E\
P
M E6
S
C H
ED
U
LE
S.
D W
G
2610 Wycliff Road Suite 410 Raleigh, NC 27607-3073 919.881.9939 NC License No. F-0929
Dewberry Engineers Inc.
KRC & KMS
TW
WLH
PME601
SCHEDULES
10/07/2026
54321
B
C
D
E
F
ELECTRICAL SEAL
APPROVED BY
CHECKED BY
REVISIONS
SHEET NO.
TITLE
DRAWN BY
DATE
PROJECT NO.
SCALE
MECHANICAL SEAL
NO. DESCRIPTION DATE
C U
M
BE
R
LA
N D
C O
U N
TY
C
LI
FF
D
AL
E
LI
BR
AR
Y
BO
IL
ER
R
EP
LA
C
EM
EN
T
C
LI
FF
D
AL
E
R D
FA
YE
TT
EV
IL
LE
, N
C
50194091
10/07/2026
/2
/2
3:
:4
PM
P:
\5
1\
C
AD
\P M
E\
P
M E7
C
O N
TR
O
LS
.D
W G
2610 Wycliff Road Suite 410 Raleigh, NC 27607-3073 919.881.9939 NC License No. F-0929
Dewberry Engineers Inc.
KRC & KMS
TW
WLH
PME701
CONTROLS
SCALE:1 BOILER CONTROLS SCHEMATIC
N.T.S. SCALE:2 CHILLER CONTROLS SCHEMATIC
N.T.S.
B-1
PHWP-1
DO START/STOP
DI STATUS
DI ALARM
MSD DO START/STOP
DI STATUS
ASBLDG
SHWP-1
VFD DO START/STOP
AO SPEED CONTROL
VP STATUS
(E) 3" HWR
(E) 3" HWS
T
AI
T
AIBLDG HWR
TEMP
DO COMPRESSOR 1 STATUS
DO COMPRESSOR 2 STATUS
AI AMPS
T
AICH-1 EWT
T
AI CH-1 LWT
VFDDOSTART/STOP
AOSPEED CONTROL
AIAMPS
DO START/STOP
CH-1
4" CHWS
4" CHWR
1. GENERAL: THE BAS SHALL FULLY CONTROL THE HEATING AND COOLING SYSTEMS AND
EQUIPMENT.
1.1. SYSTEM ENABLE: WHEN THE BUILDING IS OCCUPIED BASED ON THE TIME SCHEDULE, OR THE
SPACE TEMPERATURE SETPOINTS HAVE NOT BEEN MET FOR 10 MINUTES (ADJ), OR IF
MANUALLY ENABLED BY THE BAS.
1.2. SYSTEM DISABLE: WHEN THE BUILDING IS UNOCCUPIED BASED ON THE TIME SCHEDULE, OR
THE TEMPERATURE SET POINTS HAVE BEEN MET FOR AT LEAST 30 MINUTES (ADJ), OR IF
MANUALLY DISABLED BY THE BAS.
1.3. OCCUPIED TIME SCHEDULE (ADJ):
MONDAY THROUGH THURSDAY, 8 AM TO 9 PM
FRIDAY, 8 AM TO 7 PM
SATURDAY, 8 AM TO 6 PM
SUNDAY, 12 PM TO 6 PM
2. HOT WATER PUMP CONTROL
2.1. START/STOP: WHENEVER THE SYSTEM IS ENABLED, THE HOT WATER PUMP WILL BE
ENABLED. WHENEVER DISABLED, THE PUMP SHALL BE DISABLED AFTER A 3 MINUTE DELAY.
2.2. PROOF: UPON FAILURE OF THE HOT WATER PUMP, THE BAS SHALL ENUNCIATE AN ALARM.
2.3. VFD CONTROL: ON START AND STOP, THE VFD SHALL RAMP TO SPEED AND SLOW DOWN
WITHIN AN ADJUSTABLE ACCELERATION AND DECELERATION LIMIT. CONSTANT SPEED
SETTING SHALL BE ESTABLISHED BY PRETAB OF EXISTING PUMP OPERATION.
3. BOILER PUMP CONTROL
3.1. ENABLE/DISABLE: THE BOILER SHALL CONTROL ITS PRIMARY PUMP. WHENEVER DISABLED, THE PUMP SHALL BE DISABLED AFTER A 1 MINUTE DELAY.
3.2. PROOF: BOILER SHALL PROVE ITS PRIMARY PUMP OPERATION. UPON FAILURE OF THE PUMP, THE BAS SHALL RECEIVE AND ENUNCIATE AN ALARM.
4. BOILER CONTROL
4.1. ENABLE/DISABLE: WHENEVER THE SYSTEM IS ENABLED AND THE HOT WATER SUPPLY
TEMPERATURE FALLS BELOW THE SETPOINT, 180 DEG F (ADJ), AND THE HOT WATER PUMP IS
PROVEN ON, THE BAS SHALL ENABLE THE BOILER. THE BOILER SHALL OPERATE UNDER ITS
PACKAGED CONTROLS TO MAINTAIN HEATING WATER SETPOINT.
4.2. PROOF: UPON FAILURE OF THE BOILER, THE BAS SHALL ENUNCIATE AN ALARM.
5. CHILLED WATER PUMP CONTROL
5.1. START/STOP: WHENEVER THE SYSTEM IS ENABLED, THE CHILLED WATER PUMP WILL BE
ENABLED. WHENEVER DISABLED, THE PUMP SHALL BE DISABLED AFTER A 3 MINUTE DELAY.
5.2. PROOF: UPON FAILURE OF THE CHILLED WATER PUMP, THE BAS SHALL ENUNCIATE AN
ALARM.
5.3. VFD CONTROL: ON START AND STOP, THE VFD SHALL RAMP TO SPEED AND SLOW DOWN
WITHIN AN ADJUSTABLE ACCELERATION AND DECELERATION LIMIT. CONSTANT SPEED
SETTING SHALL BE ESTABLISHED BY PRETAB OF EXISTING PUMP OPERATION.
6. CHILLER CONTROL
6.1. ENABLE/DISABLE: WHENEVER THE SYSTEM IS ENABLED AND THE CHILLED WATER SUPPLY
TEMPERATURE FALLS BELOW SETPOINT, 44 DEG F (ADJ), AND THE CHILLED WATER PUMP
STATUS IS PROVEN ON, THE BAS SHALL ENABLE THE CHILLER. THE CHILLER SHALL OPERATE
UNDER ITS PACKAGED CONTROLS TO MAINTAIN THE CHILLED WATER SETPOINT.
6.2. UPON FAILURE OF THE CHILLER, THE BAS SHALL ENUNCIATE AN ALARM.
SEQUENCE OF OPERATIONS: CHILLED WATER AND HOT WATER PLANT
CONTROLS
BLDG HWS
TEMP
VP ALARM
CO
DIBOILER ROOM CO
VP EWT (BACNET)
VP BACNET IT
DI EPO STATUS
EPO
DI E-STOP
VP LWT (BACNET)
KEY NOTES:
1. HW SUPPLY HEADER TEMPERATURE SENSOR FURNISHED BY BOILER MANUFACTURER.
GENERAL NOTES:
1. CONTRACTOR SHALL VERIFY ALL NEW AND EXISTING TO REMAIN DEVICES ARE CALIBRATED AND
OPERATING PROPERLY. EXISTING DEVICES WHICH ARE BROKEN OR MALFUNCTIONING SHALL BE
INVENTORIED AND BROUGHT TO THE OWNER'S ATTENTION FOR REPLACEMENT.
2. MIGRATE ALL BALANCED STATES (VFD SPEED, ETC) FOR EXISTING TO REMAIN SYSTEMS.
GENERAL NOTES:
1. END DEVICES AND SENSORS ARE EXISTING TO REMAIN. EXISTING WIRING AND CONDUIT BETWEEN CONTROLLER AND DEVICES SHALL BE REUSED. MIGRATE EXISTING POINTS TO NEW CONTROLLER.
2. CONTRACTOR SHALL VERIFY ALL NEW AND EXISTING TO REMAIN DEVICES ARE CALIBRATED AND
OPERATING PROPERLY. EXISTING DEVICES WHICH ARE BROKEN OR MALFUNCTIONING SHALL BE
INVENTORIED AND BROUGHT TO THE OWNER'S ATTENTION FOR REPLACEMENT.
3. MIGRATE ALL BALANCED STATES (VFD SPEED, ETC) FOR EXISTING TO REMAIN SYSTEMS.
T
AI TO BOILER 2
X
10/07/2026
| Sheets and Views |
| G-001 COVER SHEET |
| G-002 BUILDING CODE SUMMARY |
| PME001 SYMBOLS ABBREVATIONS & GENERAL NOTES |
| PMED111 DEMOLITION PLAN |
| PME111 NEW WORK PLAN |
| PME501 DETAILS |
| PME601 SCHEDULES |
| PME701 CONTROLS |
| 2026-10-07T05:27:07-0700 | |
| Digitally verifiable PDF exported from www.docusign.com |
File details come from the government source that posted it. Updated .