5-YATB Reno Permit Set 2026-06-22.pdf
PDF 26 MB Posted
- Attached to
- Mailroom Infill Project
- Solicitation number
- Not on record
- Issued by
- York County, Pennsylvania
About this file
This document comprises permit-level architectural drawings and specifications for the York Adams Tax Bureau's Second Floor Office Expansion project located at 1405 North Duke Street, York, PA 17404. The project involves partial demolition and infill construction on both the first and second floors of an existing building, including removal of existing walls, doors, ceilings, and fixtures, followed by construction of new interior partitions, ceiling assemblies, flooring systems, and finishes. The scope encompasses architectural, structural, mechanical, electrical, and plumbing work coordinated by Core Design Group (architect), Paragon Engineering Services (MEP engineer), and Structural Engineering Resources LLC (structural engineer). Key project elements include new interior partitions with metal studs and gypsum wallboard, reflected ceiling plans with acoustical tile and gypsum board assemblies, floor assemblies with concrete and metal deck, new door and window openings, and accessibility compliance per 2009 and 2017 ANSI A117.1 standards. The general contractor is responsible for obtaining all building permits, coordinating inspections, securing a Certificate of Occupancy, verifying all dimensions and site conditions, and ensuring compliance with ADA requirements and all applicable local, state, and federal codes. A pre-bid meeting is scheduled for Wednesday, July 1, 2026 at 1:00 p.m. at the project site, with sealed bids due by 3:00 p.m. on Wednesday, July 22, 2026 via the PennBid system. Bidders must submit questions and substitution requests no later than 2:00 p.m. on Wednesday, July 8, 2026 through PennBid.
Bid security of ten percent (10%) of the maximum bid amount must accompany each bid in the form of a Bid Bond. The contractor must provide full and complete warranties for all HVAC, electrical, and plumbing equipment with a minimum one-year term from substantial completion. Upon project completion, a minimum of two cases or 5% of product finishes must be left at the job site. The general contractor bears sole responsibility for shoring, bracing, site safety, debris management, utility location verification, and coordination of all subcontractors and trades throughout construction. York Adams Tax Bureau reserves the right to waive any irregularities in bids and to reject any and all bids. No proposal may be withdrawn for sixty (60) days following bid opening without the consent of York Adams Tax Bureau. The drawings are issued for permit purposes only and are the exclusive property of Core Design Group; recipients warrant not to reproduce, distribute, or reuse the documents without written permission from the architect.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 2-Section 008700 Bid Form-General.pdf | ||
| 4-Prevailing Wage Rates.pdf | ||
| 1-Section 000300 Advertisement for Bids.pdf | ||
| 3-AIA A310-2010 Bid Bond.pdf |
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
FIRE ALARM SYSTEM
DETAILED DRAWINGS FULLY DEFINING THE FOLLOWING SYSTEMS HAVE NOT BEEN INCLUDED.
THE REQUIRED DRAWINGS, SHOP DRAWINGS, SCHEDULES AND FULL SPECIFICATIONS WILL BE
PROVIDED FOR REVIEW A MINIMUM OF THIRTY (30) DAYS PRIOR TO INSTALLATION. ACCEPTANCE
OF DEFERRED SUBMISSION OF THE FOLLOWING INFORMATION IS REQUESTED:
DEFERRED SUBMISSIONS
SPRINKLER SYSTEM
ALL PARTS OF THESE DOCUMENTS AND/OR SPECIFICATIONS ARE THE
EXCLUSIVE PROPERTY OF THE ARCHITECT AND WE RESERVE ALL
RIGHTS TO HAVE THIS WORK REPRODUCED, FABRICATED,
CONSTRUCTED, AND/OR MANUFACTURED. WE HAVE PLACED THESE
DOCUMENTS IN YOUR TEMPORARY CUSTODY, IN CONFIDENCE,
SOLELY FOR YOUR INSPECTION, AND/OR ESTIMATING THE COST OF
FABRICATING, CONSTRUCTING, AND/OR MANUFACTURING THE WORK
SHOWN. THE CONTRACTOR IS RESPONSIBLE FOR CHECKING ALL
DIMENSIONS AND CONDITIONS AT THE JOBSITE, AS WELL AS BUILDING
RULES AND REGULATIONS. THE CONTRACTOR IS RESPONSIBLE FOR
COORDINATING ALL INSPECTIONS AND OBTAINING THE CERTIFICATE
OF OCCUPANCY. THE RECIPIENT OF THESE DOCUMENTS WARRANTS
THAT THEY WILL NOT REPRODUCE, DISTRIBUTE, OR OTHERWISE
MAKE USE OF THE DOCUMENTS WITHOUT THE PERMISSION OF THE
ARCHITECT. THE USE OF THESE DESIGNS FOR ANY OTHER PURPOSE
IS UNAUTHORIZED. DO NOT SCALE THESE DOCUMENTS.
CORE DESIGN GROUP
SHEET NO:
PROJECT TEAM VICINITY MAP SITE LOCATION
SHEET NAME:
PROJECT NO: PROJECT MGR:
REVISIONS
CONSULTANT INFORMATION:
SEAL/STAMP:
155 WEST MARKET STREET, SUITE 200
YORK, PA 17401
PHONE 717.741.2046 FAX: 717.741.6836
WWW.CORE-DESIGNGROUP.COM
6/
/2
2:
:1
PM
Au to de sk
D oc s:
//Y
AT
B
M ai l R oo m
In fil l P ro je ct
/2 5.
- Y
AT
B
- M ai l I nf ill
Pr oj ec t.r vt
COVER SHEET
G000
25.147 M.A.S.
YO
RK
A
DA
M S
TA
X
BU
RE
AU
SE
CO
ND
F
LO
OR
O
FF
IC
E
EX
PA
NS
IO
N
N
OR
TH
D
UK
E
ST
RE
ET
YO
RK
, P
A
YORK ADAMS TAX BUREAU
SECOND FLOOR OFFICE EXPANSION
1405 NORTH DUKE STREET
YORK, PA 17404
ARCHITECT: STRUCTURAL ENGINEER:
OWNER: M.E.P. ENGINEER:
PARAGON ENGINEERING SERVICES
1620 S. QUEEN STREET
YORK, PA 17403
(717) 781-2264
YORK ADAMS TAX BUREAU
1405 NORTH DUKE STREET
YORK, PA 17405
(717) 845-1584
STRUCTURAL ENGINEERING RESOURCES, LLC.
26 NORTH FOURTH STREET
GETTYSBURG, PA 17325
(717) 337-1335
CORE DESIGN GROUP
155 WEST MARKET STREET, SUITE 200
YORK, PA 17401
(717) 741-2046
SHEET LIST AND REVISION DATE
SHEET NAME
GENERAL
G000 COVER SHEET
G100 DRAWING INDEX, SYMBOL LEGEND AND GENERAL NOTES
G201 FIRST FLOOR LIFE SAFETY PLAN
G202 SECOND FLOOR LIFE SAFETY PLAN
G300 ACCESSIBILITY DETAILS
G400 ACCESSIBILITY SIGNAGE
ARCHITECTURAL
AD101 PARTIAL FIRST FLOOR DEMOLITION PLAN
AD102 PARTIAL SECOND FLOOR DEMOLITION PLAN
AD200 PARTIAL FIRST FLOOR CEILING DEMOLITION PLAN
AD201 PARTIAL SECOND FLOOR CEILING DEMOLITION PLAN
A101 PARTIAL FIRST FLOOR NEW WORK PLAN
A102 PARTIAL SECOND FLOOR NEW WORK PLAN
A103 FIRST FLOOR REFLECTED CEILING PLAN
A104 SECOND FLOOR REFLECTED CEILING PLAN
A200 ENLARGED PLANS AND ELEVATIONS
A300 DOOR AND WINDOW SCHEDULE
STRUCTURAL
S1 FOUNDATION PLAN
S2 PARTIAL SECOND FLOOR NEW WORK PLAN
S3 SECTIONS AND DETAILS
MECHANICAL
D101 FIRST FLOOR - DEMO - SANITARY & VENT
D102 SECOND FLOOR - DEMO - SANITARY & VENT
M001 LEGENDS, SCHEDULES, SPECIFICATIONS AND DETAILS
M101 SECOND FLOOR - PLUMBING
M201 FIRST FLOOR - HVAC
M202 SECOND FLOOR - HVAC
ELECTRICAL
E001 SYMBOLS, ABBREVIATIONS & SPECIFICATIONS
E002 SCHEDULES
ED101 FIRST FLOOR - DEMO - LIGHTING AND POWER
ED102 SECOND FLOOR - DEMO - LIGHTING AND POWER
E101 FIRST FLOOR - LIGHTING
E102 SECOND FLOOR - LIGHTING
E201 SECOND FLOOR - POWER PLAN
NO. DATE DESCRIPTION
1 2026/06/05 ISSUED FOR PERMIT
SECTION CALLOUT
EXTERIOR ELEVATION CALLOUT
INTERIOR ELEVATION CALLOUT
ROOM NAME
ROOM NUMBER
DOOR TAG
REVISION DELTA
ELEVATION DESIGNATION
WALL / PARTITION TAG
COLUMN GRID DESIGNATION
REFERENCE LEVEL
DATUM
SCALE
NAME
LEVEL
VIEW TITLE WINDOW TAG
W#
CENTERLINE
CLDETAIL CALLOUT
VIEW NUMBER
SHEET NUMBER
ROOM TAG
ROOM NAME
P##
VIEW NUMBERS
SHEET NUMBER
VIEW NUMBER
SHEET NUMBER
A101
1 VIEW NUMBER
SHEET NUMBER
A101
SIM
A101
LEVEL NAME
X'-X"
STOREFRONT / CURTAINWALL TAG
CW#
PROPOSED EXISTING
A101
XX
TOILET ACCESSORY TAG
VIEW TITLE
SCALE: x/x" = x' - x"
A101
XX'-X" ELEVATION ABOVE
DATUM 0'-0"
TRUE NORTH
AB ANCHOR BOLT(S), AUGER BORING
ACI AMERICAN CONCRETE INSTITUTE
ACT ACOUSTICAL CEILING TILE
ADA AMERICANS WITH DISABILITIES ACT
ADDL ADDITIONAL
AFF ABOVE FINISH FLOOR
AFG ABOVE FINISHED GRADE
AHU AIR HANDLING UNIT
AISC AMERICAN INSTITUTE OF STEEL CONSTRUCTION
AJC ASPHALTIC CONCRETE
ALT ALTERNATE/ ALTERNATING
APPROX APPROXIMATE
ARCH ARCHITECT(URAL)
ASSOC ASSOCIATED/ ASSOCIATION
ASTM AMERICAN SOCIETY OF TESTING MATERIALS
ATC AUTOMATIC TEMPERATURE CONTROL
AWP ACOUSTICAL WALL PANEL
BC BOTTOM OF CURB
BFF BELOW FINISHED FLOOR
BFG BELOW FINISHED GRADE
BKT BRACKET
BLDG BUILDING
BLVD BOULEVARD
BM BENCH MARK
BOB BOTTOM OF BEAM
BOF BOTTOM OF FOOTING
BOJ BOTTOM OF JOIST
BOS BOTTOM OF STEEL
BOTT BOTTOM
BRG BEARING
BSMT BASEMENT
BUR BUILT-UP ROOF
CART CARTWAY
CCT CUBICLE CURTAIN TRACK
CF CUBIC (FOOT) FEET
CFM CUBIC FEET PER MINUTE
CFS CUBIC FEET PER SECOND
CI CAST IRON
CIP CAST IRON PIPE
CIRC CONTRACTION/ CONTROL JOINT
CL CENTER LINE
CLG CEILING
CLR CLEARANCE / CLEAR
CM CORRUGATED METAL
CMP CORRUGATED METAL PIPE ARCH
CMU CONCRETE MASONRY UNIT
CNTR COUNTER
CO CLEANOUT
COB CENTER OF BEAM
COL COLUMN
CONC CONCRETE
CONF CONFERENCE
CONST CONSTRUCTION
CONT CONTINUOUS
CORRG CORRUGATED
CPP CORRUGATED PLASTIC PIPE
CPT CARPET
CR CLASSROOM
CUH CABINET UNIT HEATER
DBL DOUBLE
DH DRILL HOLE
DIAG DIAGONAL
DIFF DIFFUSER
DIM DIMENSION
DP DAMPROOF(ING)
DS DOWN SPOUT
DWG DRAWING
EC ELECTRICAL CONTRACTOR
EF EACH FACE
EJ EXPANSION JOINT
EL ELEVATION
ELEC ELECTRICAL
ELEV ELEVATOR
ENGR ENGINEER(ING)
EOF EDGE OF FLOOR
EOS EDGE OF SLAB
EQUIP EQUIPMENT
EST ESTIMATE
EW EACH WAY
EX EXISTING
FBD FIBER BOARD
FCO FLOOR CLEAN OUT
FD FLOOR DRAIN
FDN FOUNDATION
FE FIRE EXTINGUISHER
FEC FIRE EXTINGUISHER CABINET
FFE FINISHED FLOOR ELEVATION
FIN FINISH(ED)
FIX FIXTURE
FM FACTORY MANUAL
FP FULL PENETRATION WELD
FPR FIRE PROOF(ING)
FTG FOOTING
FURN FURNITURE
GAL GALLON
GALV GALVANIZED
GC GENERAL CONTRACTOR
GFI GROUND FAULT INTERRUPTER
GLBLK GLAZED BLOCK
GPM GALLONS PER MINUTE
GYM GYMNASIUM
GWB GYPSUM WALLBOARD
H/ V HEATING AND VENTILATING
HB HOSE BIB
HC HEATING CONTRACTOR
HM HOLLOW METAL
HORIZ HORIZONTAL
HT HEIGHT
HVAC HEATING/ VENTILATING/ AIR CONDITIONING
HW HOT WATER
HYD HYDRANT
IBC INTERNATIONAL BUILDING CODE
INCL INCLUDE/ INCLUSIVE
INSUL INSULATE/ INSULATION
JAN JANITOR
KSI KIPS PER SQUARE INCH
LAB LABORATORY
LAV LAVATORY
LB(S) POUND(S)
LDY LAUNDRY
LF LINEAL FEET
LH LEFT HAND
LHR LEFT HAND REVERSE
LIB LIBRARY
LLH LONG LEG HORIZONTAL
LLV LONG LEG VERTICAL
MAS MASONRY
MAX MAXIMUM
MB MAILBOX
MC MECHANICAL CONTRACTOR
MECH MECHANIC(AL)
MED MEDICAL
MEP MECHANICAL, ELECTRICAL, PLUMBING
MFD MANUFACTURED
MFR MANUFACTURE(R)
MIN MINIMUM
MISC MISCELLANEOUS
MM MILLIMETER
MO MASONRY OPENING
MTD MOUNTED
MTG MOUNTING
NA NOT APPLICABLE
NEC NATIONAL ELECTRIC CODE
NFPA NATIONAL FIRE PROTECTION ASSOC.
NIC NOT IN CONTRACT
NO NUMBER
NTS NOT TO SCALE
OC ON CENTER(S)
OPNG OPENING(S)
OPP OPPOSITE
PC PLUMBING CONTRACTOR
PCF POUNDS PER CUBIC FOOT
PLAM PLASTIC LAMINATE
PLBG PLUMBING
PLWD PLYWOOD
POLYISO POLYISOCYANURATE
PREFAB PREFABRICATED
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PTL PRESSURE TREATED LUMBER
PTD PAINTED
RA RETURN AIR
RC REINFORCED CONCRETE
RD ROOF DRAIN
REBAR REINFORCING BAR
REG REGISTER
REINF REINFORCED/REINFORCING
RH RIGHT HAND
RHR RIGHT HAND REVERSE
RL RAIN LEADER
RO ROUGH OPENING
RWC RAIN WATER CONDUCTOR
SA SUPPLY AIR
SECT SECTION(AL)
SJ SAW JOINT
SLV SHORT LEG VERTICAL
SOG SLAB ON GRADE
SP SOUNDPROOF
SPAND SPANDREL
SPECS SPECIFICATIONS
SPR SPRINKLER(ED)
SQ SQUARE
SF SQUARE FOOT/FEET
SI SQUARE INCH(ES)
SS STAINLESS STEEL
STC SOUND TRANSMISSION CLASS
STD STANDARD
STER STERILIZER
STOR STORAGE
STRUCT STRUCTURAL
SV SHEET VINYL
SW STORMWATER
T&B TOP AND BOTTOM
T&G TONGUE & GROOVE
TC TOP OF CURB
TEL TELEPHONE
TEMP TEMPERED
TG TOP OF GRATE
TH THICK/THICKNESS
THRU THROUGH
TOB TOP OF BEAM
TOF TOP OF FOOTING
TOJ TOP OF JOIST
TOS TOP OF STEEL
TW TOP OF WALL
TYP TYPICAL
UC UNDERCUT (DOORS)
UCC UNIFORM CONSTRUCTION CODE
UG UNDERGROUND
UNO UNLESS NOTED OTHERWISE
VB VINYL BASE
VCT VINYL COMPOSITION TILE
VERT VERTICAL
VEST VESTIBULE
VIF VERIFY IN FIELD
VOL VOLUME
VT VINYL TREAD
VWC VINYL WALL COVERING
WC WATER CLOSET
WCO WALL CLEAN OUT
WDW WINDOW
WGL WIRE GLASS
WM WOOD MOLDING
WP WEATHERPROOF
WP WORK POINT
WSL WATER SURFACE ELEVATION
WT WEIGHT
WWF WELDED WIRE FABRIC
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
27.
28.
29.
30.
31.
32.
33.
THE WORK INCLUDES ALL LABOR, MATERIALS, EQUIPMENT, AND SERVICES NECESSARY FOR THE COMPLETION OF ALL WORK AS ILLUSTRATED AND DESCRIBED ON THE DRAWINGS AS PREPARED BY CORE DESIGN GROUP. ALL SUCH WORK IS TO BE DONE BY THE GENERAL CONTRACTOR UNLESS
OTHERWISE NOTED.
GENERAL CONTRACTOR SHALL VERIFY ALL DIMENSIONS AND CONDITIONS SHOWN ON DRAWINGS AT THE JOB SITE AND SHALL NOTIFY THE ARCHITECT OF ANY OMISSIONS, DISCREPANCIES, AND / OR CONFLICTS PRIOR TO CONSTRUCTION / INSTALLATION. INTERIOR DIMENSIONS ARE TO FACE OF STUD
AND FACE OF PLYWOOD WHERE APPLICABLE.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE TO COMPLETE THIS PROJECT IN COMPLIANCE WITH THE AMERICANS WITH DISABILITIES ACT AND ALL CITIES, STATE AND LOCAL CODES, INCLUDING THE PREPARATION AND APPROVAL BY LOCAL AUTHORITIES OF ALL MECHANICAL, ELECTRICAL, PLUMBING, SPRINKLER PLANS AND SPECIFICATIONS.
GENERAL CONTRACTOR SHALL OBTAIN FULL AND COMPLETE WARRANTIES FOR ALL HVAC, ELECTRICAL, AND PLUMBING EQUIPMENT FROM THE CONTRACTOR PROVIDING SAID SERVICES. WARRANTIES WILL REMAIN IN EFFECT A MINIMUM OF ONE (1) YEAR FROM SUBSTANTIAL COMPLETION DATE.
WHERE COLOR AND DESIGN SELECTIONS ARE REQUIRED, THE GENERAL CONTRACTOR SHALL SUBMIT SAMPLES TO THE OWNER FOR SELECTION AND APPROVAL. AFTER COMPLETION OF THE PROJECT, A MINIMUM OF 2 CASES OR 5% OF PRODUCT FINISHES TO BE LEFT AT THE JOB SITE.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING AND REVIEWING ALL SHOP DRAWINGS BEFORE SUBMISSION AND PROVIDING ALL
NECESSARY SAMPLES TO THE ARCHITECT.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR OBTAINING AND REVIEWING ALL STRUCTURAL ERECTION DRAWINGS BEFORE SUBMISSION TO
THE ARCHITECT / STRUCTURAL ENGINEER.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR SECURING ALL REQUIRED BUILDING PERMITS AND OBTAINING A CERTIFICATE OF OCCUPANCY
FROM THE GOVERNING AUTHORITY.
GENERAL CONTRACTOR SHALL HAVE DIRECT CONTROL AND MANAGEMENT OF ALL CONSTRUCTION OPERATIONS AND BE RESPONSIBLE FOR THE SATISFACTORY OVERALL PERFORMANCE OF ALL HIS SUPPLIERS AND SUBCONTRACTORS AS WELL AS ALL ASSIGNED CONTRACTORS.
GENERAL CONTRACTOR IS TO RECEIVE, HANDLE, STORE (IF NECESSARY) AND BE RESPONSIBLE FOR ALL MATERIALS PROVIDED BY OTHERS.
ALL MATERIALS USED IN CONSTRUCTION SHALL BE NEW AND OF FIRST QUALITY UNLESS OTHERWISE INDICATED.
GYPSUM WALLBOARD SHALL BE INSTALLED WITH ALL CORNER BEADS, TRIM ACCESSORIES AND MOLDINGS, ETC. FOR A COMPLETE INSTALLATION.
GYPSUM WALLBOARD TO BE TAPED AND SANDED (READY FOR PAINT). DRYWALL CONTRACTOR TO INSTALL CONTROL JOINTS ACCORDING TO INDUSTRY STANDARDS. ALL FULL HEIGHT STEEL STUD PARTITIONS MUST INCLUDE A DEFLECTION TRACK IF WALL IS SECURED TO ROOF STRUCTURE.
GENERAL CONTRACTOR SHALL VERIFY THE LOCATION OF ALL UTILITIES PRIOR TO CONSTRUCTION.
GENERAL CONTRACTOR SHALL COORDINATE THE MECHANICAL, PLUMBING, AND ELECTRICAL DRAWINGS AND REPORT TO ARCHITECT ANY
UNFORESEEN CONFLICTS BETWEEN THE SUB TRADES.
ITEMS AND CONDITIONS NOTED ON DETAILS ARE APPLICABLE AND BINDING TO SIMILAR CONDITIONS ON ALL THE DRAWINGS. FOR CONDITIONS NOT NOTED OR DETAILED, CONTRACTOR SHALL PROVIDE MATERIALS OF EQUAL QUALITY AND PERFORMANCES TO OTHER SIMILAR CONDITIONS ON THE
JOB.
WALL AND CEILING FINISHES SHALL INCLUDE PROJECTIONS, BEAM ENCLOSURES, RECESSES, BULKHEADS, PILASTERS OR OTHER ENCLOSURES.
ALL APPURTENANCES BUILT INTO OR THROUGH WALLS, INCLUDING DOORS, DUCTS, WINDOWS, LOUVERS, GRILLES, MECHANICAL WORK, ETC., SHALL FIT SNUGLY AND BE THOROUGHLY SEALED AROUND PERIMETERS. WORK AT EXTERIOR WALLS SHALL BE FLASHED OR OTHERWISE WATERPROOF
SEALED.
FIELD CHECK ROUGH AND / OR FINISHED DIMENSIONS FOR ACCURATE FITTING OF CABINETS, COUNTERS, LOCKERS, DOORS, WINDOWS, FIXTURES, SHELVING, GATES AND OTHER INSTALLATIONS PRIOR TO SHOP OR FACTORY FABRICATIONS. PROVIDE AND INSTALL NECESSARY FILLER STRIPS, SCRIBE STRIPS, BASES, CLOSURES, FINISHES AND TRIM TO COMPLETE SUCH INSTALLATIONS. PROVIDE AND INSTALL ALL NECESSARY CONCEALED
BLOCKING TO SECURELY ANCHOR WALL MOUNTED FIXTURES, CABINETS, EQUIPMENT, ETC.
GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR CLOSING-IN, SEALING AND PROTECTION OF EXISTING OR PUBLIC SPACES FROM THE WORK AREA INCLUDING NOISE, DUST AND POLLUTION CONTROL. THE CONTRACTOR SHALL MAINTAIN AT ALL TIMES ADEQUATE SAFETY BARRIERS AND CLEAR ACCESS IN AND OUT OF THE SITE AND FACILITY SO AS TO FACILITATE DAILY TRAFFIC MOVEMENT, DELIVERIES AND PUBLIC SAFETY. THE CONTRACTOR
SHALL BE RESPONSIBLE FOR KEEPING THE AREA CLEAN FROM DEBRIS DURING CONSTRUCTION.
GENERAL CONTRACTOR SHALL CONSULT WITH THE OWNER TO VERIFY THE SCOPE OF WORK; TO VERIFY OWNER FURNISHED ITEMS AND COORDINATE THOSE ITEMS INTO THE WORK; TO VERIFY ANY ITEMS TO BE RELOCATED. VERIFY ANY WORK TO BE PROVIDED BY THE OWNER AND TO COORDINATE
THAT WORK INTO THE PROGRESS OF THE SCHEDULED WORK.
GENERAL CONTRACTOR SHALL PROVIDE BLOCKING (FIRE RATED AS REQUIRED) WITHIN WALLS FOR ALL ACCESSORIES.
SECTIONS SHOWN ARE INTENDED TO SHOW THE SPECIFIC CONSTRUCTION WHERE INDEXED AS WELL AS ESTABLISH THE GENERAL CONSTRUCTION DETAILS FOR SECTIONS THROUGHOUT THE PROJECT WHICH DO NOT HAVE SPECIFIC SECTIONS DRAWN. THE MOST SIMILAR SECTION SHALL BE ADAPTED TO ANY SECTION NOT DETAILED. ANY SPECIFIC QUESTION CONCERNING CONSTRUCTION NOT ADEQUATELY COVERED BY THE ABOVE
SHOULD BE DIRECTED TO THE ARCHITECT.
OPENINGS FOR PIPES, DUCTS, CONDUIT, SLEEVES, ETC. SHALL BE SEALED AROUND THE COMPONENTS FULL THICKNESS OF THE DECK (FIRE RATED
SEALANT WHERE REQUIRED).
ARCHITECTURAL DRAWINGS INDICATE BEARING ELEVATION FOR INFORMATION PURPOSES ONLY. SEE STRUCTURAL DRAWINGS FOR ACTUAL
STRUCTURAL STEEL AND BEARING ELEVATIONS.
CONSULT PLUMBING, HVAC AND ELECTRICAL DRAWINGS FOR LOCATIONS AND DESCRIPTIONS OF ACCESS PANELS, LOUVER OPENINGS, VENTILATORS, GRILLES, VALVE CABINETS, FIRE DAMPERS OR OTHER APPURTENANCES AFFECTING WALLS, CEILING OR FLOORS AND PROVIDE NECESSARY LINTELS, SUPPORT OR ANCHORING. SEE STRUCTURAL NOTES FOR LINTEL REQUIREMENTS.
SEAL ALL SIDES OF FRAMES ABUTTING DISSIMILAR MATERIALS; TYPICAL, CONTINUOUSLY AT HEADS, JAMBS, AND SILLS (EXCEPT AT DOOR SILLS
UNLESS NOTED OTHERWISE).
FILL ALL HOLLOW METAL (HM) FRAMES ABUTTING MASONRY WITH GROUT. FILL INTERMEDIATE MEMBERS AS SHOWN IN DETAILS (TYPICAL).
GENERAL CONTRACTOR SHALL VERIFY ALL PENETRATIONS THROUGH CONCRETE FLOORS AND FORM ACCORDINGLY (PRIOR TO POURING SLAB).
FLASHING AT HEADS OF WALL OPENINGS SHALL INCLUDE END DAMS.
ALL MASONRY WALL PENETRATIONS TO BE SLEEVED OR CORE DRILLED. SUBCONTRACTORS ARE RESPONSIBLE FOR SEALING ALL OF THEIR
PENETRATIONS IN MASONRY WALLS.
BUILD ALL PARTITIONS IN THEIR ENTIRETY TO THE UNDERSIDE OF THE FLOOR OR ROOF DECK, UNLESS NOTED OTHERWISE. PROVIDE DEFLECTION TRACK AT ALL STUD TO DECK CONDITIONS. SEE DEFLECTION TRACK DETAILS. WHERE FIRE RATED PARTITIONS OR CMU WALLS ARE REQUIRED, SEE
FIRE SAFING DETAIL.
INSTALL ALL MATERIALS / PRODUCTS IN ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS AND SPECIFICATIONS.
GENERAL CONTRACTOR SHALL PROVIDE CAULKING WHERE ALL DISSIMILAR MATERIALS MEET.
34. MAINTAIN THE BUILDING IN A WATERTIGHT CONDITION AT ALL TIMES.
35. THE CONTRACTOR SHALL MAINTAIN (FOR THE ENTIRE LENGTH OF HIS CONTRACT) EXITS, EXIT LIGHTING, FIRE PROTECTIVE DEVICES AND ALARMS TO
CONFORM TO LOCAL BUILDING CODE REQUIREMENTS.
36. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ADEQUATELY BRACING AND PROTECTING WORK DURING CONSTRUCTION AGAINST DAMAGE, BREAKAGE, COLLAPSE, DISTORTION, AND/OR MISALIGNMENT IN ACCORDANCE WITH APPLICABLE CODE STANDARDS AND GOOD PRACTICE.
37. THE GENERAL CONTRACTOR SHALL BE SOLELY AND EXCLUSIVELY RESPONSIBLE FOR THE ADEQUACY OF ALL SHORING AND BRACING. THE CONTRACTOR SHALL PROVIDE TEMPORARY ERECTION SHORING AND BRACING OF ALL STRUCTURAL WORK AS REQUIRED FOR THE STABILITY OF THE STRUCTURE DURING ALL PHASES OF CONSTRUCTION. THE CONTRACTOR SHALL IMMEDIATELY INFORM THE ENGINEER OF ANY CONDITION WHICH, IN HIS OPINION, MIGHT ENDANGER THE STABILITY OF THE STRUCTURE OR CAUSE DISTRESS IN THE STRUCTURE.
GENERAL NOTES:
ALL PARTS OF THESE DOCUMENTS AND/OR SPECIFICATIONS ARE THE
EXCLUSIVE PROPERTY OF THE ARCHITECT AND WE RESERVE ALL
RIGHTS TO HAVE THIS WORK REPRODUCED, FABRICATED,
CONSTRUCTED, AND/OR MANUFACTURED. WE HAVE PLACED THESE
DOCUMENTS IN YOUR TEMPORARY CUSTODY, IN CONFIDENCE,
SOLELY FOR YOUR INSPECTION, AND/OR ESTIMATING THE COST OF
FABRICATING, CONSTRUCTING, AND/OR MANUFACTURING THE WORK
SHOWN. THE CONTRACTOR IS RESPONSIBLE FOR CHECKING ALL
DIMENSIONS AND CONDITIONS AT THE JOBSITE, AS WELL AS BUILDING
RULES AND REGULATIONS. THE CONTRACTOR IS RESPONSIBLE FOR
COORDINATING ALL INSPECTIONS AND OBTAINING THE CERTIFICATE
OF OCCUPANCY. THE RECIPIENT OF THESE DOCUMENTS WARRANTS
THAT THEY WILL NOT REPRODUCE, DISTRIBUTE, OR OTHERWISE
MAKE USE OF THE DOCUMENTS WITHOUT THE PERMISSION OF THE
ARCHITECT. THE USE OF THESE DESIGNS FOR ANY OTHER PURPOSE
SHEET NAME:
PROJECT NO: PROJECT MGR:
REVISIONS
CONSULTANT INFORMATION:
SEAL/STAMP:
155 WEST MARKET STREET, SUITE 200
YORK, PA 17401
PHONE 717.741.2046 FAX: 717.741.6836
WWW.CORE-DESIGNGROUP.COM
6/
/2
2:
:1
PM
Au to de sk
D oc s:
//Y
AT
B
M ai l R oo m
In fil l P ro je ct
/2 5.
- Y
AT
B
- M ai l I nf ill
Pr oj ec t.r vt
DRAWING INDEX,
SYMBOL LEGEND
AND GENERAL
NOTES
G100
25.147 M.A.S.
YO
RK
A
DA
M S
TA
X
BU
RE
AU
SE
CO
ND
F
LO
OR
O
FF
IC
E
EX
PA
NS
IO
N
N
OR
TH
D
UK
E
ST
RE
ET
YO
RK
, P
A
ASSEMBLY COMPOSITION LIST
TAG THUMBNAIL COMPOSITION STATUS
A INTERIOR PARTITION
THICKNESS: 4 7/8" (● CORE THICKNESS: 3 5/8")
○ 5/8" GYPSUM WALL BOARD
● 3 5/8" METAL STUD
○ 5/8" GYPSUM WALL BOARD
NEW WORK
B INTERIOR PARTITION
THICKNESS: 4 5/8" (● CORE THICKNESS: 3 5/8")
— TAG SIDE —
○ 5/8" GYPSUM WALL BOARD
● 3 5/8" METAL STUD
○ 3/8" AIR GAP
NEW WORK
C INTERIOR PARTITION
THICKNESS: 4 1/4" (● CORE THICKNESS: 3 5/8")
○ 5/8" GYPSUM WALL BOARD
● 3 5/8" METAL STUD
NEW WORK
D FLOOR ASSEMBLY
THICKNESS: 1' - 9" (● CORE THICKNESS: 1' - 4")
○ 3 1/2" CONCRETE
○ 1 1/2" METAL DECK
● 1' - 4" STEEL BEAMS, SEE STRUCTURAL DRAWINGS
NEW WORK
E CEILING ASSEMBLY
THICKNESS: 2 1/8" (● CORE THICKNESS: 1 1/2")
● 1 1/2" METAL FURRING
○ 5/8" GYPSUM BOARD
NEW WORK
F CEILING ASSEMBLY
THICKNESS: 3/4"
○ 3/4" ACOUSTICAL CEILING TILE 24" X 24"
NEW WORK
ASSEMBLY HEIGHTS LIST
TAG BOTTOM OF ASSEMBLY TOP OF ASSEMBLY
1 TOP OF FLOOR ASSEMBLY UNDERSIDE OF ROOF ASSEMBLY
2 TOP OF FLOOR ASSEMBLY SECOND FLOOR (+ 8' - 6")
3 SECOND FLOOR (+ 8' - 0") SECOND FLOOR (+ 8' - 2 1/8")
4 SECOND FLOOR (+ 8' - 0") SECOND FLOOR (+ 8' - 0 3/4")
5 FIRST FLOOR (+ 12' - 11") SECOND FLOOR
USE GROUP / CONSTRUCTION TYPE
CAPACITY REQUIRED
CAPACITY PROVIDED
NUMBER OF OCCUPANTS
OCCUPANTS PER GROSS FLOOR AREA SF
XXXX
EMERGENCY LIGHT FIXTURE
WALL MOUNTED FIRE EXTINGUISHERFE
EXIT LIGHT
EXIT LIGHT COMBO
105'
1341 SF
MAIL ROOM
173 SF
MACHINE ROOM
139 SF
STAIR
.825" 33.75"
2.625" 33.75"
326 SF
STORAGE
FE
FIRE EXTINGUISHER EQUIPMENT:
A.
B.
C.
D.
E.
A.
B.
1.
2.
3.
4.
a.
b.
c.
5.
FIRE PROTECTION:
EXTINGUISHING EQUIPMENT GUIDELINES:
PROVIDE EXTINGUISHERS PER NFPA 10
MINIMUM PLACEMENT OF ONE 10LB ABC PORTABLE FIRE EXTINGUISHER AND SHALL BE PROVIDED WITH A MAXIMUM OF 75FT OF TRAVEL
DISTANCE TO THE EXTINGUISHER.
FIRE EXTINGUISHERS SHALL BE CONSPICUOUSLY LOCATED WHERE THEY ARE READILY ACCESSIBLE AND IMMEDIATELY AVAILABLE IN THE EVENT
OF A FIRE.
FIRE EXTINGUISHERS SHALL BE LOCATED ALONG NORMAL PATHS OF TRAVEL, INCLUDING EXITS FROM AREAS.
SIGNS OR OTHER MEANS USED TO INDICATE FIRE EXTINGUISHER LOCATIONS SHALL BE LOCATED IN CLOSE PROXIMITY AND SHALL BE VISIBLE
FROM THE NORMAL PATH OF TRAVEL.
INSTALLATION:
BEFORE INSTALLING ANY FIRE-EXTINGUISHING EQUIPMENT, THE OWNER/RESIDENT SHALL READ AND UNDERSTAND THE INSTALLATION AND USE INSTRUCTIONS, INCLUDING THE LIMITATIONS, CAUTION, AND WARNINGS CONTAINED ON THE EQUIPMENT AND IN THE OWNERS MANUAL.
PORTABLE FIRE EXTINGUISHERS SHALL BE INSTALLED PER NFPA 10 AND AS FOLLOWS:
PROVIDE A MINIMUM OF 2 FIRE EXTINGUISHERS. LOCATION SHOWN ON DRAWINGS AND/ OR AS DIRECTED BY FIRE MARSHAL IN THE FIELD.
IN AN ACCESSIBLE LOCATION, FREE FROM BLOCKING BY STORAGE AND EQUIPMENT, AND NEAR ROOM EXITS THAT PROVIDE AN ESCAPE ROUTE.
SO THAT THE TOP OF THE EXTINGUISHER IS NOT MORE THAN 5FT ABOVE TO REACH AND REMOVE AND SHALL BE PLACED WHERE IT WILL NOT BE
DAMAGED.
PORTABLE FIRE EXTINGUISHERS SHALL BE INSTALLED USING ANY OF THE FOLLOWING MEANS:
SECURELY ON A HANGER INTENDED FOR THE FIRE EXTINGUISHER.
IN A BRACKET INCORPORATING RELEASING STRAPS OR BANDS SUPPLIED BY THE EXTINGUISHER MANUFACTURER.
ON A LISTED BRACKET INCORPORATING RELEASING STRAPS OR BANDS APPROVED FOR SUCH A PURPOSE.
PLACED SO THAT THE OPERATING INSTRUCTIONS ON THE EXTINGUISHER FACE OUTWARD.
EMERGENCY AND EXIT LIGHTING SYSTEM NOTES:
A.
B.
C.
D.
EMERGENCY LIGHTING SHALL BE PROVIDED IN ACCORDANCE WITH NFPA 101, SECTION 7.9. THE EMERGENCY LIGHTING SYSTEM SHALL BE ARRANGED TO PROVIDE THE REQUIRE ILLUMINATION AUTOMATICALLY IN THE EVENT OF ANY INTERRUPTION OF NORMAL LIGHTING. EMERGENCY LIGHTING UNITS SHALL CONSIST OF THE RECHARGEABLE BATTERY-OPERATED TYPE IN ACCORDANCE WITH NFPA 70.
EXIT LIGHTING SYSTEM AND MARKING OF MEANS OF EGRESS SHALL BE PROVIDED IN ACCORDANCE WITH NFPA 101, SECTION 7.10. THE EXIT SIGNS SHALL BE INTERNALLY ILLUMINATED BY CIRCUITING FROM THE NORMAL ELECTRICAL SYSTEMS AND SHALL BE FITTED WITH RECHARGEABLE BATTERY OPERATED BACK-UP CIRCUITING IN THE EVENT OF FAILURE OF THE NORMAL POWER SYSTEM.
ALL EXIT AND EMERGENCY LIGHTING SYSTEMS SHALL BE WIRED TO THE NORMAL ELECTRICAL DISTRIBUTION SYSTEM AHEAD OF ANY LOCAL
SWITCHING.
ALL EXIT AND EMERGENCY LIGHTING SYSTEMS SHALL BE PROVIDED IN ACCORDANCE WITH APPLICABLE SECTIONS OF NFPA 70.
ALL PARTS OF THESE DOCUMENTS AND/OR SPECIFICATIONS ARE THE
EXCLUSIVE PROPERTY OF THE ARCHITECT AND WE RESERVE ALL
RIGHTS TO HAVE THIS WORK REPRODUCED, FABRICATED,
CONSTRUCTED, AND/OR MANUFACTURED. WE HAVE PLACED THESE
DOCUMENTS IN YOUR TEMPORARY CUSTODY, IN CONFIDENCE,
SOLELY FOR YOUR INSPECTION, AND/OR ESTIMATING THE COST OF
FABRICATING, CONSTRUCTING, AND/OR MANUFACTURING THE WORK
SHOWN. THE CONTRACTOR IS RESPONSIBLE FOR CHECKING ALL
DIMENSIONS AND CONDITIONS AT THE JOBSITE, AS WELL AS BUILDING
RULES AND REGULATIONS. THE CONTRACTOR IS RESPONSIBLE FOR
COORDINATING ALL INSPECTIONS AND OBTAINING THE CERTIFICATE
OF OCCUPANCY. THE RECIPIENT OF THESE DOCUMENTS WARRANTS
THAT THEY WILL NOT REPRODUCE, DISTRIBUTE, OR OTHERWISE
MAKE USE OF THE DOCUMENTS WITHOUT THE PERMISSION OF THE
ARCHITECT. THE USE OF THESE DESIGNS FOR ANY OTHER PURPOSE
PROJECT NO: PROJECT MGR:
REVISIONS
CONSULTANT INFORMATION:
SEAL/STAMP:
155 WEST MARKET STREET, SUITE 200
YORK, PA 17401
PHONE 717.741.2046 FAX: 717.741.6836
WWW.CORE-DESIGNGROUP.COM
6/
/2
2:
:1
PM
Au to de sk
D oc s:
//Y
AT
B
M ai l R oo m
In fil l P ro je ct
/2 5.
- Y
AT
B
- M ai l I nf ill
Pr oj ec t.r vt
FIRST FLOOR LIFE
SAFETY PLAN
G201
25.147 M.A.S.
YO
RK
A
DA
M S
TA
X
BU
RE
AU
SE
CO
ND
F
LO
OR
O
FF
IC
E
EX
PA
NS
IO
N
N
OR
TH
D
UK
E
ST
RE
ET
YO
RK
, P
A
LIFE SAFETY PLAN LEGEND
SCALE: 1/4" = 1'-0"G201
FIRST FLOOR LIFE SAFETY1
UP
R ef rig er at or
USE GROUP / CONSTRUCTION TYPE
CAPACITY REQUIRED
CAPACITY PROVIDED
NUMBER OF OCCUPANTS
OCCUPANTS PER GROSS FLOOR AREA SF
XXXX
EMERGENCY LIGHT FIXTURE
WALL MOUNTED FIRE EXTINGUISHERFE
EXIT LIGHT
EXIT LIGHT COMBO
RO
OF
B
EL
OW
132 SF
STORAGE
CORRIDOR
283 SF
CONFERENCE
64 SF
TOILET ROOM
192 SF
STORAGE & ROOF
ACCESS
EXIST. ELEV.
1208 SF
DATA ENTRY
201 SF
KITCHENETTE
TOILET ROOM
TOILET ROOM
116 SF
OFFICE
129 SF
OFFICE
99 SF
SERVER
139 SF
STAIR
CO
RR
ID
OR
3A
65'
102'
FE
BOARD ROOM
FIRE EXTINGUISHER EQUIPMENT:
A.
B.
C.
D.
E.
A.
B.
1.
2.
3.
4.
a.
b.
c.
5.
FIRE PROTECTION:
EXTINGUISHING EQUIPMENT GUIDELINES:
PROVIDE EXTINGUISHERS PER NFPA 10
MINIMUM PLACEMENT OF ONE 10LB ABC PORTABLE FIRE EXTINGUISHER AND SHALL BE PROVIDED WITH A MAXIMUM OF 75FT OF TRAVEL
DISTANCE TO THE EXTINGUISHER.
FIRE EXTINGUISHERS SHALL BE CONSPICUOUSLY LOCATED WHERE THEY ARE READILY ACCESSIBLE AND IMMEDIATELY AVAILABLE IN THE EVENT
OF A FIRE.
FIRE EXTINGUISHERS SHALL BE LOCATED ALONG NORMAL PATHS OF TRAVEL, INCLUDING EXITS FROM AREAS.
SIGNS OR OTHER MEANS USED TO INDICATE FIRE EXTINGUISHER LOCATIONS SHALL BE LOCATED IN CLOSE PROXIMITY AND SHALL BE VISIBLE
FROM THE NORMAL PATH OF TRAVEL.
INSTALLATION:
BEFORE INSTALLING ANY FIRE-EXTINGUISHING EQUIPMENT, THE OWNER/RESIDENT SHALL READ AND UNDERSTAND THE INSTALLATION AND USE INSTRUCTIONS, INCLUDING THE LIMITATIONS, CAUTION, AND WARNINGS CONTAINED ON THE EQUIPMENT AND IN THE OWNERS MANUAL.
PORTABLE FIRE EXTINGUISHERS SHALL BE INSTALLED PER NFPA 10 AND AS FOLLOWS:
PROVIDE A MINIMUM OF 2 FIRE EXTINGUISHERS. LOCATION SHOWN ON DRAWINGS AND/ OR AS DIRECTED BY FIRE MARSHAL IN THE FIELD.
IN AN ACCESSIBLE LOCATION, FREE FROM BLOCKING BY STORAGE AND EQUIPMENT, AND NEAR ROOM EXITS THAT PROVIDE AN ESCAPE ROUTE.
SO THAT THE TOP OF THE EXTINGUISHER IS NOT MORE THAN 5FT ABOVE TO REACH AND REMOVE AND SHALL BE PLACED WHERE IT WILL NOT BE
DAMAGED.
PORTABLE FIRE EXTINGUISHERS SHALL BE INSTALLED USING ANY OF THE FOLLOWING MEANS:
SECURELY ON A HANGER INTENDED FOR THE FIRE EXTINGUISHER.
IN A BRACKET INCORPORATING RELEASING STRAPS OR BANDS SUPPLIED BY THE EXTINGUISHER MANUFACTURER.
ON A LISTED BRACKET INCORPORATING RELEASING STRAPS OR BANDS APPROVED FOR SUCH A PURPOSE.
PLACED SO THAT THE OPERATING INSTRUCTIONS ON THE EXTINGUISHER FACE OUTWARD.
EMERGENCY AND EXIT LIGHTING SYSTEM NOTES:
A.
B.
C.
D.
EMERGENCY LIGHTING SHALL BE PROVIDED IN ACCORDANCE WITH NFPA 101, SECTION 7.9. THE EMERGENCY LIGHTING SYSTEM SHALL BE ARRANGED TO PROVIDE THE REQUIRE ILLUMINATION AUTOMATICALLY IN THE EVENT OF ANY INTERRUPTION OF NORMAL LIGHTING. EMERGENCY LIGHTING UNITS SHALL CONSIST OF THE RECHARGEABLE BATTERY-OPERATED TYPE IN ACCORDANCE WITH NFPA 70.
EXIT LIGHTING SYSTEM AND MARKING OF MEANS OF EGRESS SHALL BE PROVIDED IN ACCORDANCE WITH NFPA 101, SECTION 7.10. THE EXIT SIGNS SHALL BE INTERNALLY ILLUMINATED BY CIRCUITING FROM THE NORMAL ELECTRICAL SYSTEMS AND SHALL BE FITTED WITH RECHARGEABLE BATTERY OPERATED BACK-UP CIRCUITING IN THE EVENT OF FAILURE OF THE NORMAL POWER SYSTEM.
ALL EXIT AND EMERGENCY LIGHTING SYSTEMS SHALL BE WIRED TO THE NORMAL ELECTRICAL DISTRIBUTION SYSTEM AHEAD OF ANY LOCAL
SWITCHING.
ALL EXIT AND EMERGENCY LIGHTING SYSTEMS SHALL BE PROVIDED IN ACCORDANCE WITH APPLICABLE SECTIONS OF NFPA 70.
ALL PARTS OF THESE DOCUMENTS AND/OR SPECIFICATIONS ARE THE
EXCLUSIVE PROPERTY OF THE ARCHITECT AND WE RESERVE ALL
RIGHTS TO HAVE THIS WORK REPRODUCED, FABRICATED,
CONSTRUCTED, AND/OR MANUFACTURED. WE HAVE PLACED THESE
DOCUMENTS IN YOUR TEMPORARY CUSTODY, IN CONFIDENCE,
SOLELY FOR YOUR INSPECTION, AND/OR ESTIMATING THE COST OF
FABRICATING, CONSTRUCTING, AND/OR MANUFACTURING THE WORK
SHOWN. THE CONTRACTOR IS RESPONSIBLE FOR CHECKING ALL
DIMENSIONS AND CONDITIONS AT THE JOBSITE, AS WELL AS BUILDING
RULES AND REGULATIONS. THE CONTRACTOR IS RESPONSIBLE FOR
COORDINATING ALL INSPECTIONS AND OBTAINING THE CERTIFICATE
OF OCCUPANCY. THE RECIPIENT OF THESE DOCUMENTS WARRANTS
THAT THEY WILL NOT REPRODUCE, DISTRIBUTE, OR OTHERWISE
MAKE USE OF THE DOCUMENTS WITHOUT THE PERMISSION OF THE
ARCHITECT. THE USE OF THESE DESIGNS FOR ANY OTHER PURPOSE
PROJECT NO: PROJECT MGR:
REVISIONS
CONSULTANT INFORMATION:
SEAL/STAMP:
155 WEST MARKET STREET, SUITE 200
YORK, PA 17401
PHONE 717.741.2046 FAX: 717.741.6836
WWW.CORE-DESIGNGROUP.COM
6/
/2
2:
:2
PM
Au to de sk
D oc s:
//Y
AT
B
M ai l R oo m
In fil l P ro je ct
/2 5.
- Y
AT
B
- M ai l I nf ill
Pr oj ec t.r vt
SECOND FLOOR
LIFE SAFETY
PLAN
G202
25.147 M.A.S.
YO
RK
A
DA
M S
TA
X
BU
RE
AU
SE
CO
ND
F
LO
OR
O
FF
IC
E
EX
PA
NS
IO
N
N
OR
TH
D
UK
E
ST
RE
ET
YO
RK
, P
A
LIFE SAFETY PLAN LEGEND
SCALE: 1/4" = 1'-0"G202
SECOND FLOOR LIFE SAFETY1
60" MIN - 2009 ANSI A117.1
67" MIN - 2017 ANSI A117.1
" M
AX
A
NS
I A
7.1
OVERLAP OF KNEE AND TOE CLEARANCE
CIRCULAR TURNING SPACE -
SIZE AND OVERLAP
" M
AX
A
NS
I A
7.1
SCALE: 1/2" = 1'-0"
FORWARD
APPROACH
CLEAR FLOOR SPACE
IN ALCOVE
SCALE: 1/4" = 1'-0"
CLEAR FLOOR SPACE GUIDELINES
" M
IN
X > 24"
48" MAX - 2009 ANSI A117.1
52" MAX - 2017 ANSI A117.1 60" MIN
X>
" M
IN
48" MIN - 2009 ANSI A117.1
52" MIN - 2017 ANSI A117.1
" M
IN
48" MIN - 2009 ANSI A117.1
52" MIN - 2017 ANSI A117.1
" M
IN
CLEAR FLOOR SPACE
IN ALCOVE
CLEAR FLOOR
SPACE
CLEAR FLOOR
SPACE
PARALLEL
APPROACH
1.
2.
3.
NO CHANGES IN LEVEL EXCEPT SLOPES 1:48 MAX
PERMITTED TO INCLUDE KNEE SPACE
ALCOVE CLEARANCES ALSO APPLY TO OTHER
CONFINEMENTS ON 3 SIDES OF THE CLEAR FLOOR SPACE
4" M
IN
" M
IN
4" MIN
28" MIN
36" MIN
" M
IN
40" MIN
" M
IN
OPTION (1)
CLEAR WIDTH AT 90 DEGREE TURN
SCALE: 1/4" = 1'-0"
36" MIN
" M
IN
OPTION (2)
8" MIN
8" M
IN
36" MIN - 2009 ANSI A117.1
X - 2017 ANSI A117.1
" M
IN
A
NS
I A
7.1
Y
- 2
7 A
NS
I A
7.1
OPTION (3)
X= 38" MIN IF Y= 42" MIN
X= 36" MIN IF Y= 44" MIN
1. WHERE AN ACCESSIBLE ROUTE MAKES
A 90-DEGREE TURN AT DOOR,
DOORWAYS, GATES, ELEVATOR OR
PLATFORM LIFTS THE ACCESSIBLE
ROUTE SHALL NOT BE REQUIRED TO
COMPLY WITH THIS SECTION
CLEAR WIDTH OF AN ACCESSIBLE ROUTE - INTERIOR
SCALE: 1/2" = 1'-0"
SLOPE
1"/20" MAX36
" M
IN
" M
IN
24" MAX
48" MIN - 2009 ANSI A117.1
52" MIN - 2017 ANSI A117.1 24" MAX
" M
IN
" M
IN
SL
OP
E 1"
/48 " M
AX
CLEAR WIDTH AT DOORWAYS
NOTE: DOUBLE LEAF DOORS AND GATES SHALL HAVE
AT LEAST ONE LEAF THAT COMPLIES
SCALE: 1/2" = 1'-0"
32" MIN
90°
32" MIN
HINGED DOOR
32" MIN 36" MIN
SLIDING DOOR
FOLDING DOOR DOORS AND DOORWAYS
WITHOUT DOORS
MANEUVERING CLEARANCES AT DOORWAYS
WITHOUT DOORS
SIDE APPROACHFRONT APPROACH
SCALE: 1/4" = 1'-0"
" M
IN
A
NS
I A
7.1
" M
IN
A
NS
I A
7.1
" M
IN
MANEUVERING CLEARANCES AT SWINGING DOORS
LATCH SIDE APPROACH HINGE SIDE APPROACH
PUSH SIDE:
X=12" IF DOOR HAS BOTH A
LATCH AND A CLOSER
FRONT APPROACH
SCALE: 1/4" = 1'-0"
1.
2.
FRONT APPROACH PROVIDED AT RECESSED DOORS WHERE AN OBSTRUCTION WITHIN 18" OF LATCH SIDE IS 8" DEEP MIN.
DOORS IN SERIES ARE SEPARATED BY 48" MIN PLUS THE WIDTH OF DOORS SWINGING BETWEEN THE TWO
" M
IN
" M
IN
A
NS
I A
7.1
" M
IN
A
NS
I A
7.1
MIN
18"
Y
" M
IN
Y
" M
INX
24" MIN
24" MIN 22" MIN
Y
" M
IN
YX
PULL SIDE:
Y=54" MIN. IF DOOR HAS CLOSER
PUSH SIDE:
Y=48" MIN. IF DOOR HAS CLOSER
PULL SIDE:
X=36" MIN. IF Y=60"
X=42" MIN. IF Y=54"
PUSH SIDE:
Y=48" MIN. IF DOOR HAS BOTH A LATCH AND
CLOSER
68" MIN
" M
IN
" M
IN
" M
IN8"
8"
16" MIN
36" MIN
16" MIN
2017 ANSI A117.1 - OPTION (1)
12" MIN (3)
11" MIN (2) 40" MIN (3)
42" MIN (2)
12" MIN (3)
11" MIN (2)
" M
IN
(3
" M
IN
(2
" M
IN
(3
" M
IN
(2
64" MIN
" M
IN
2017 ANSI A117.1 - OPTION (2) / OPTION (3)
OVERLAP OF KNEE AND TOE CLEARANCE 1.
2.
TURNING SPACE SHALL BE PERMITTED TO INCLUDE KNEE
& TOE CLEARANCE OF EITHER THE BASE OR ONE ARM.
UNLESS OTHERWISE SPECIFIED, DOORS SHALL BE
PERMITTED TO SWING INTO TURNING SPACES.
T-SHAPE TURNING SPACE
BASE
AR
M
BASE
AR
M
SCALE: 1/4" = 1'-0"
12" MIN
36" MIN
12" MIN
" M
IN
" M
IN
60" MIN
" M
IN
BASE
AR
M
2009 ANSI A117.1
SL
OP
E 6"
/1" M
IN
KNEE AND TOE CLEARANCES -
ELEVATION
SCALE: 1" = 1'-0"
1.
2.
APPLIES WHERE SPACE UNDER AN ELEMENT IS PART
OF CLEAR FLOOR SPACE OR TURNING SPACE
CLEARANCES SHALL BE 30" MIN. IN WIDTH
" M
IN
C
LE
AR
K
NE
E
SP
AC
E
AT 27" AFF
8" MIN
6" MAX
AT 9" AFF
11" MIN
TO
E
SP
AC
E
9" M
IN
C
LE
AR
17"-25"
KNEE AND TOE CLEARANCES - PLAN
SCALE: 1" = 1'-0"
" M
IN
25" MAX CLEAR KNEE SPACE
17-25" CLEAR TOE SPACE
PROTRUSION LIMITS
SCALE: 1/4" = 1'-0"
1.
2.
HANDRAILS PROTRUDE 4 1/2" MAX
PROTRUDING OBJECTS MAY NOT
OBSTRUCT REQUIRED CLEAR WIDTH
4" MAX
" M
IN
X
KNEE
SPACE
UNOBSTRUCTED
FORWARD REACH
1. X= 20" MAX IF Y= 48" MAX
X= 20"-25" IF Y= 44" MAX
2. REACH DEPTH NOT TO EXTEND
PAST CLEAR KNEE SPACE
REACH RANGES
SCALE: 1/2" = 1'-0"
" M
AX
" M
IN
Y
CO
UN
TE
R
HE
IG
HT
" M
AX
X
" M
AX
" M
IN
X
Y
" M
AX
OBSTRUCTED HIGH
FORWARD REACH
UNOBSTRUCTED
SIDE REACH
OBSTRUCTED
SIDE REACH
1. X= 10" MAX IF Y= 48" MAX
X= 10"-24" IF Y=46" MAX
OPERABLE
HARDWARE
NO PROJECTIONS INTO THE CLEAR OPENING
WIDTH LOWER THAN 34" ABOVE THE FLOOR
DOOR GUIDELINES
SCALE: 3/8" = 1'-0"
" M
AX
"-4
8"
" M
IN
VISION
LITE
SMOOTH
SURFACE
AREA
VIEWING
SURFACE
FINISHED FLOOR
DOOR WITHOUT SIDELITE
OPERABLE
HARDWARE
NO PROJECTIONS INTO THE CLEAR OPENING
WIDTH LOWER THAN 34" ABOVE THE FLOOR
" M
AX
" M
IN
VISION
LITE
SMOOTH
SURFACE
AREA
VIEWING
SURFACE
FINISHED FLOOR
DOOR WITH SIDELITE
VISION
LITE
SINGLE POST
POST-MOUNTED PROTRUDING OBJECTS
SCALE: 1/4" = 1'-0"
MULTIPLE POSTS
1.
2.
DOES NOT APPLY TO SLOPED PORTIONS OF STAIR AND RAMP HANDRAILS
PROTRUDING OBJECTS MAY NOT OBSTRUCT REQUIRED CLEAR WIDTH
"-8
0"
MAX
4"
MAX
4"
" M
AX X > 12"
" M
IN
X > 12"
4" MAX4" MAX
SIDE ELEVATION FRONT ELEVATION
ACCESSIBLE WATER CLOSET
IN WHEELCHAIR ACCESSIBLE COMPARTMENTS:
X= 59" IF WATER CLOSET IS FLOOR MOUNTED
SCALE: 1/2" = 1'-0"
TOILET PAPER
DISPENSER
LOCATION
X
56" CLEAR FLOOR SPACE
"-3
6"
" M
IN
"-4 1"
39" - 41"
MAX
12" 42" MIN
MI
N
1 1 /2"
54" MIN
6" MAX 36" MIN
MIN
12" 24" MIN
16"-18"
60" CLEAR FLOOR SPACE
42" MAX
" M
IN
"-1
9"
42" MIN
24" MIN
NOTE: FIXTURE IS SHOWN FOR REFERENCE ONLY.
CL
1. FORWARD APPROACH PROVIDED
CENTERED ON UNIT
DRINKING FOUNTAINS
SCALE: 1/2" = 1'-0"
KNEE
SPACE
15" MIN 5" MAX
" M
IN
X
A
NS
I A
7.1
A
NS
I A
7.1
30"
1. X= WIDTH VARIES PER ACTUAL UNIT
SIDE ELEVATION PLAN VIEW
1. FORWARD APPROACH PROVIDED
CENTERED ON UNIT
KNEE
SPACE
FRONT ELEVATION
30"
NOTE: FIXTURE IS SHOWN FOR REFERENCE ONLY.
FINISH FLOOR
FIRE EXTINGUISHER
WITHOUT CABINET
" M
AX
F
RO
M
FI
NI
SH
F
LO
OR
T O
HA
ND
LE
O
F
FI
RE
E
XT
IN
GU
IS
HE
R
SE
E
PL
AN
TO
M
EE
T
A.
D.
A.
OR
T O
4"
WALL MOUNTED FIRE
EXTINGUISHER WITH
BRACKET
FIRE EXTINGUISHER PLAN
WITHOUT CABINET
SCALE: 1" = 1' - 0"
SCALE: 1" = 1' - 0"
KNEE
SPACE
SINK AND MIRROR CLEARANCES
SCALE: 1/2" = 1'-0"
SU
RF
AC
E
OF
M
IR
RO
R
RE
FL
EC
TI
VE
X
" M
AX
" M
AX
" M
IN
R
EC
OM
ME
ND
ED
1. X= 35" MAX IF NOT ABOVE
SINK OR COUNTERTOP
2. FORWARD APPROACH
PROVIDED CENTERED ON UNIT
48" CLEAR- 2009 ANSI A117.1
52" CLEAR- 2017 ANSI A117.1
CL
EA
R
NOTE: FIXTURE IS SHOWN FOR REFERENCE ONLY.
4'
- 0
4'
- 0
3'
- 4
3'
- 8
" M
AX
2'
- 0
" M
IN
MIRROR SOAP DISPENSER PAPER TOWEL
DISPENSER
2'
- 0
" M
IN
4'
- 0
2'
- 6
TOILET PAPER
DISPENSER
TOILET PAPER
HOLDER
SANITARY NAPKIN
DISPOSAL
SANITARY NAPKIN
DISPENSER
MA
X.
MA
X.
MA
X.
MA
X.
TYPICAL TOILET ACCESSORIES MOUNTING HEIGHTS
SCALE: 3/8" = 1'-0"
MA
X.
MA
X.
MI
N.
BABY
CHANGING
STATION
" M
IN
" M
AX
3'
- 6
TOILET PARTITION
COAT HOOKS
FITTING ROOM COAT
HOOKS
NOTE: ALL ACCESSORIES ARE SHOWN FOR REFERENCE ONLY.
ALL PARTS OF THESE DOCUMENTS AND/OR SPECIFICATIONS ARE THE
EXCLUSIVE PROPERTY OF THE ARCHITECT AND WE RESERVE ALL
RIGHTS TO HAVE THIS WORK REPRODUCED, FABRICATED,
CONSTRUCTED, AND/OR MANUFACTURED. WE HAVE PLACED THESE
DOCUMENTS IN YOUR TEMPORARY CUSTODY, IN CONFIDENCE,
SOLELY FOR YOUR INSPECTION, AND/OR ESTIMATING THE COST OF
FABRICATING, CONSTRUCTING, AND/OR MANUFACTURING THE WORK
SHOWN. THE CONTRACTOR IS RESPONSIBLE FOR CHECKING ALL
DIMENSIONS AND CONDITIONS AT THE JOBSITE, AS WELL AS BUILDING
RULES AND REGULATIONS. THE CONTRACTOR IS RESPONSIBLE FOR
COORDINATING ALL INSPECTIONS AND OBTAINING THE CERTIFICATE
OF OCCUPANCY. THE RECIPIENT OF THESE DOCUMENTS WARRANTS
THAT THEY WILL NOT REPRODUCE, DISTRIBUTE, OR OTHERWISE
MAKE USE OF THE DOCUMENTS WITHOUT THE PERMISSION OF THE
ARCHITECT. THE USE OF THESE DESIGNS FOR ANY OTHER PURPOSE
PROJECT NO: PROJECT MGR:
REVISIONS
CONSULTANT INFORMATION:
SEAL/STAMP:
155 WEST MARKET STREET, SUITE 200
YORK, PA 17401
PHONE 717.741.2046 FAX: 717.741.6836
WWW.CORE-DESIGNGROUP.COM
6/
/2
2:
:2
PM
Au to de sk
D oc s:
//Y
AT
B
M ai l R oo m
In fil l P ro je ct
/2 5.
- Y
AT
B
- M ai l I nf ill
Pr oj ec t.r vt
ACCESSIBILITY
DETAILS
G300
25.147 M.A.S.
YO
RK
A
DA
M S
TA
X
BU
RE
AU
SE
CO
ND
F
LO
OR
O
FF
IC
E
EX
PA
NS
IO
N
N
OR
TH
D
UK
E
ST
RE
ET
YO
RK
, P
A
NOTE:
EXISTING CONSTRUCTION - 2009 ANSI A117.1
NEW CONSTRUCTION - 2017 ANSI A117.1
6" M
AX
" M
AX
4"
SCALE: 3" = 1'-0"
STANDARD
INTERNATIONAL
SYMBOL
PICTOGRAM
UPPERCASE
RAISED TEXT
CHARACTERS
GRADE 2
BRAILLE
AE
SCALE: 3" = 1'-0"
SIGNS HAVE A NON-GLARE FINISH AND A BACKGROUND WITH A HIGH LIGHT
TO DARK VISUAL CONTRAST TO THE PICTOGRAMS AND TEXT CHARACTERS
MISCELLANEOUS VISUAL SIGNS
ACCESSIBLE
ENTRANCE
AX ES
EXIT STAIRS
E X T I N G U I S H E R
FE
" M
AX
TACTILE / VISUAL SIGNS
NOTE:
REPLACE WHEELCHAIR ICON FOR
STATES AND CITIES AS REQUIRED.
ALTERNATIVE WHEELCHAIR ICON SYMBOL
1.
2.
3.
NOTES APPLY TO ALL TACTILE / VISUAL SIGNS:
SIGNS HAVE SMOOTH EDGES WITH A NON-GLARE FINISH AND A
BACKGROUND WITH A HIGH LIGHT TO DARK VISUAL CONTRAST TO
THE PICTOGRAMS AND TEXT CHARACTERS
TEXT CHARACTERS AND BRAILLE ARE SEPARATED FROM EACH
OTHER, RAISED BORDERS, AND DECORATIVE ELEMENTS BY 3/8" MIN
TEXT CHARACTER HEIGHT IS 5/8" TO 2" UNLESS SAME INFO IS
SEPARATELY PROVIDED IN VISUAL TEXT CHARACTERS THEN THE
TACTILE TEXT CHARACTER HEIGHT IS 1/2" TO 2"
ACCESSIBLE
EXIT
SIGN DESIGNATION
ON ARCHITECT'S
PLANS
AR AB AU
AREA OF
RESCUE
ASSISTANCE
ACCESSIBLE
BREAK ROOM
RESTROOM
NO STORAGE
ABOVE
NO ROOF
ACCESS
THIS DOOR TO REMAIN
UNLOCKED DURING
BUSINESS HOURS
ST
IN CASE
OF FIRE
USE STAIRS
E
EXIT
EEO
EMERGENCY
EXIT ONLY
MAXIMUM
OCCUPANCY
PERSONS
MO
CERAMIC TILE
SETTING BEDDIVIDER STRIP CONCRETE
SUB-FLOOR
TYPE 3
ALUMINUM
THRESHOLD
TYPE 1 TYPE 4
VCT VINYL
TRANSITION
CARPET
CONCRETE
SUB-FLOOR
CERAMIC TILE
SETTING BED
CARPET
CONCRETE SUB-FLOOR
TYPE 5
ALUMINUM TRANSITION
TYPE 2
VCT
FIRST FLOOR
0' - 0"
FIRST FLOOR
0' - 0"
FIRST FLOOR
0' - 0"
FIRST FLOOR
0' - 0"
1/2
4" - 10"
ALUMINUM
THRESHOLD
1/2
1/8
5" 3"
FIRST FLOOR
0' - 0"
ALL PARTS OF THESE DOCUMENTS AND/OR SPECIFICATIONS ARE THE
EXCLUSIVE PROPERTY OF THE ARCHITECT AND WE RESERVE ALL
RIGHTS TO HAVE THIS WORK REPRODUCED, FABRICATED,
CONSTRUCTED, AND/OR MANUFACTURED. WE HAVE PLACED THESE
DOCUMENTS IN YOUR TEMPORARY CUSTODY, IN CONFIDENCE,
SOLELY FOR YOUR INSPECTION, AND/OR ESTIMATING THE COST OF
FABRICATING, CONSTRUCTING, AND/OR MANUFACTURING THE WORK
SHOWN. THE CONTRACTOR IS RESPONSIBLE FOR CHECKING ALL
DIMENSIONS AND CONDITIONS AT THE JOBSITE, AS WELL AS BUILDING
RULES AND REGULATIONS. THE CONTRACTOR IS RESPONSIBLE FOR
COORDINATING ALL INSPECTIONS AND OBTAINING THE CERTIFICATE
OF OCCUPANCY. THE RECIPIENT OF THESE DOCUMENTS WARRANTS
THAT THEY WILL NOT REPRODUCE, DISTRIBUTE, OR OTHERWISE
MAKE USE OF THE DOCUMENTS WITHOUT THE PERMISSION OF THE
ARCHITECT. THE USE OF THESE DESIGNS FOR ANY OTHER PURPOSE
PROJECT NO: PROJECT MGR:
REVISIONS
CONSULTANT INFORMATION:
SEAL/STAMP:
155 WEST MARKET STREET, SUITE 200
YORK, PA 17401
PHONE 717.741.2046 FAX: 717.741.6836
WWW.CORE-DESIGNGROUP.COM
6/
/2
2:
:2
PM
Au to de sk
D oc s:
//Y
AT
B
M ai l R oo m
In fil l P ro je ct
/2 5.
- Y
AT
B
- M ai l I nf ill
Pr oj ec t.r vt
ACCESSIBILITY
SIGNAGE
G400
25.147 M.A.S.
YO
RK
A
DA
M S
TA
X
BU
RE
AU
SE
CO
ND
F
LO
OR
O
FF
IC
E
EX
PA
NS
IO
N
N
OR
TH
D
UK
E
ST
RE
ET
YO
RK
, P
A
SCALE: 3" = 1'-0"G400
ACCESSIBLE / STANDARD TRANSITION TYPES2
A B C
4.5
6'
4"
4' - 0" 4' - 0" 4' - 0" 4' - 0" 4' - 0" 4' - 0" 4' - 0" 8' - 0"
MAIL ROOM
MACHINE ROOM
STORAGE
STAIR
D06
D06D06D06D06
AD101
A300
EXISTING WALL
EXISTING DOOR
LEGEND
DEMO WALL
DEMO DOOR
EXISTING ACT GRID
EXISTING PENDANT LIGHT
EXISTING HVAC DIFFUSER
EXISTING 2X2 CEILING LIGHT
EXISTING PENDANT CEILING LIGHT
EXISTING ACT GRID
TO BE REMOVED
EXISTING PENDANT LIGHT
TO BE REMOVED
EXISTING HVAC DIFFUSER
TO BE REMOVED
EXISTING TO REMAIN(E)
EXISTING TO BE REMOVED(ER)
EXISTING HVAC SUPPLY TO BE REMOVED
GENERAL ALTERATION NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
THESE DEMOLITION PLANS INDICATE MAJOR AREAS TO BE REMOVED OR ALTERED. ANY ITEMS NOT NOTED SHALL
BE CONSIDERED EXISTING TO REMAIN.
THE EXTENT OF DEMOLITION WORK IS TO INCLUDE ALL WORK REQUIRED TO COMPLETE THE OVERALL INTENT OF
THE PROJECT WHETHER INDICATED ON THE DRAWINGS OR NOT.
THESE RENOVATIONS SHALL BE CONSTRUCTED IN COMPLIANCE WITH ALL GOVERNING CODES. IT WILL BE THE RESPONSIBILITY OF THE CONTRACTOR TO REPORT ANY DISCREPANCIES TO THE ARCHITECT PRIOR TO CONSTRUCTION. ANY COMPLETED WORK REQUIRING REMOVAL OR ALTERATIONS SHALL BE THE CONTRACTOR'S
RESPONSIBILITY.
ALL WORK TO BE COORDINATED WITH EACH RESPECTIVE CONTRACTOR. EACH CONTRACTOR SHALL THOROUGHLY REVIEW ALL PLANS AND SPECIFICATIONS PRIOR DEMOLITION AND CONSTRUCTION.
THE RESPECTIVE CONTRACTOR FOR EACH TRADE SHALL VERIFY LOCATION OF ALL UTILITIES PRIOR TO
DEMOLITION AND CONSTRUCTION.
THE RESPECTIVE CONTRACTOR FOR EACH TRADE SHALL VERIFY THAT ALL BUILDING PERMITS, ZONING, PLUMBING AND ELECTRICAL CODES HAVE BEEN MET PRIOR TO BEGINNING OF DEMOLITION AND CONSTRUCTION.
THE CONTRACTORS SHALL ADVISE THE ARCHITECT OF ANY ITEMS WHICH DO NOT MEET WITH LOCAL APPROVALS.
ALL PERMITS SHALL BE OBTAINED AND FEES PAID BY THE RESPECTIVE SUBCONTRACTOR.
ALL DEMOLITION WORK SHALL BE COORDINATED AND SCHEDULED ACCORDINGLY WITH THE NEW
CONSTRUCTION BY THE GENERAL CONTRACTOR.
ALL USABLE ITEMS SHALL BE STORED OR REMOVED AS DIRECTED BY THE OWNER.
DISPOSAL OF ITEMS SHALL BE DONE IN ACCORDANCE WITH ALL 'ENVIRONMENTAL PROTECTION AGENCIES' AND
THE 'DEPARTMENT OF ENVIRONMENTAL RESOURCES' STANDARDS.
ALL EXISTING EQUIPMENT HAVING PLUMBING, HVAC OR ELECTRICAL CONNECTIONS AND NOTED TO BE REMOVED
SHALL BE DISCONNECTED BY THE APPROPRIATE CONTRACTOR.
ALL DISTURBED OR DAMAGED AREAS (EXTERIOR OR INTERIOR) SHALL BE REPAIRED AND FINISHED WITH MATERIALS TO MATCH EXISTING ADJACENT SURFACES OR AS NOTED ON THE ROOM FINISH SCHEDULE.
ALL RESPECTIVE CONTRACTORS SHALL BE RESPONSIBLE FOR UNREASONABLE DAMAGE TO ITEMS THAT ARE
EXISTING AND TO REMAIN.
WHERE EXISTING FLOORS, WALLS, CEILINGS, DOOR FRAMES, WINDOWS, CABINETS, SINKS, PIPING, LIGHTS, ETC.
ARE REMOVED, THE EXISTING OPENING SHALL BE CLOSED OR REPAIRED WITH MATERIALS TO MATCH EXISTING
ADJACENT SURFACES OR AS NOTED ON THE ROOM FINISH SCHEDULE.
WHERE NEW OPENINGS ARE REQUIRED IN AN EXISTING WALL, THE CONTRACTOR SHALL PROVIDE THE REQUIRED
LINTEL, WHETHER INDICATED ON THE DRAWING OR NOT.
WHERE NEW WALLS, FLOORS OR CEILINGS ABUT EXISTING WALLS, FLOORS OR CEILINGS, THE TWO SURFACES
SHALL ALIGN.
ALL RESPECTIVE CONTRACTORS SHALL BE RESPONSIBLE FOR CLEAN-UP AND REMOVAL OF CONSTRUCTION
DEBRIS WITHIN THE LIMITS OF THE CONTRACT TO DUMPSTERS PROVIDED BY THE OWNER.
PERMITS AND FEES THAT ARE NOT TO BE OBTAINED AND PAID FOR BY THE SUBCONTRACTORS SHALL BE
OBTAINED AND PAID FOR BY THE GENERAL CONTRACTOR.
18. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ADEQUATELY BRACING AND PROTECTING WORK DURING CONSTRUCTION AGAINST DAMAGE, BREAKAGE, COLLAPSE, DISTORTION, AND/OR MISALIGNMENT IN ACCORDANCE
WITH APPLICABLE CODE STANDARDS AND GOOD PRACTICE.
FIRST FLOOR
0' - 0"
SECOND FLOOR
14' - 8"
ABC
2'
8" 4'
8"
4' - 0"12' - 0"4' - 0"
2'
8" 4'
8"
4' - 0"4' - 0"4' - 0"4' - 0"4' - 0"4' - 0"4' - 0"
D06 D06 D06 D06
A300
D06 D06
ALL PARTS OF THESE DOCUMENTS AND/OR SPECIFICATIONS ARE THE
EXCLUSIVE PROPERTY OF THE ARCHITECT AND WE RESERVE ALL
RIGHTS TO HAVE THIS WORK REPRODUCED, FABRICATED,
CONSTRUCTED, AND/OR MANUFACTURED. WE HAVE PLACED THESE
DOCUMENTS IN YOUR TEMPORARY CUSTODY, IN CONFIDENCE,
SOLELY FOR YOUR INSPECTION, AND/OR ESTIMATING THE COST OF
FABRICATING, CONSTRUCTING, AND/OR MANUFACTURING THE WORK
SHOWN. THE CONTRACTOR IS RESPONSIBLE FOR CHECKING ALL
DIMENSIONS AND CONDITIONS AT THE JOBSITE, AS WELL AS BUILDING
RULES AND REGULATIONS. THE CONTRACTOR IS RESPONSIBLE FOR
COORDINATING ALL INSPECTIONS AND OBTAINING THE CERTIFICATE
OF OCCUPANCY. THE RECIPIENT OF THESE DOCUMENTS WARRANTS
THAT THEY WILL NOT REPRODUCE, DISTRIBUTE, OR OTHERWISE
MAKE USE OF THE DOCUMENTS WITHOUT THE PERMISSION OF THE
ARCHITECT. THE USE OF THESE DESIGNS FOR ANY OTHER PURPOSE
PROJECT NO: PROJECT MGR:
REVISIONS
CONSULTANT INFORMATION:
SEAL/STAMP:
155 WEST MARKET STREET, SUITE 200
YORK, PA 17401
PHONE 717.741.2046 FAX: 717.741.6836
WWW.CORE-DESIGNGROUP.COM
6/
/2
2:
:2
PM
Au to de sk
D oc s:
//Y
AT
B
M ai l R oo m
In fil l P ro je ct
/2 5.
- Y
AT
B
- M ai l I nf ill
Pr oj ec t.r vt
PARTIAL FIRST
FLOOR
DEMOLITION
PLAN
AD101
25.147 M.A.S.
YO
RK
A
DA
M S
TA
X
BU
RE
AU
SE
CO
ND
F
LO
OR
O
FF
IC
E
EX
PA
NS
IO
N
N
OR
TH
D
UK
E
ST
RE
ET
YO
RK
, P
A
4SCALE: 1/4" = 1'-0"AD101
PARTIAL FIRST FLOOR DEMOLITION PLAN1
NOT TO SCALE
AREA OF WORK
NO WORK THIS AREA
KEYPLAN
DEMOLITION NOTES
MARK DESCRIPTION
D01 DEMOLISH EXISTING WALL AND ANY ASSOCIATED ACCESSORIES - COMPLETE.
D02 REMOVE EXISTING DOOR, FRAME, AND HARDWARE - COMPLETE.
D03 REMOVE EXISTING CEILING AND ASSOCIATED FIXTURES - COMPLETE.
D04 REMOVE EXISTING STOREFRONT AND FRAME TO ACCOMMODATE NEW CONSTRUCTION.
D06 REMOVE PORTION OF EXISTING WALL TO ACCOMMODATE NEW WINDOW. - SEE NEW WORK PLANS
D07 SALVAGE EXISTING LIGHTS FOR RELOCATION. - SEE NEW WORK PLANS
D08 SALVAGE EXISTING HVAC DIFFUSERS FOR RELOCATION. - SEE NEW WORK PLANS
D09 REMOVE EXISTING CEILING TILES. EXISTING GRID TO REMAIN.
D10 REMOVE PORTION OF EXISTING GRID & CEILING TILES A REQUIRED FOR NEW CONSTRUCTION.
SCALE: 1/4" = 1'-0"AD101
WEST DEMOLITION ELEVATION2
4.5
3.5
RO
OF
B
EL
OW
D01
D02
D01
D01
D01
D04
D03
DATA ENTRY
STORAGE & ROOF
ACCESS
TOILET ROOM
KITCHENETTE
TOILET ROOM
SERVER
STAIR
D04
4' - 0" 12' - 0" 4' - 0" 8' - 0"
9' - 2 5/8"
D06 D06
EXISTING WALL
EXISTING DOOR
LEGEND
DEMO WALL
DEMO DOOR
EXISTING ACT GRID
EXISTING PENDANT LIGHT
EXISTING HVAC DIFFUSER
EXISTING 2X2 CEILING LIGHT
EXISTING PENDANT CEILING LIGHT
EXISTING ACT GRID
TO BE REMOVED
EXISTING PENDANT LIGHT
TO BE REMOVED
EXISTING HVAC DIFFUSER
TO BE REMOVED
EXISTING TO REMAIN(E)
EXISTING TO BE REMOVED(ER)
EXISTING HVAC SUPPLY TO BE REMOVED
GENERAL ALTERATION NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
THESE DEMOLITION PLANS INDICATE MAJOR AREAS TO BE REMOVED OR ALTERED. ANY ITEMS NOT NOTED SHALL
BE CONSIDERED EXISTING TO REMAIN.
THE EXTENT OF DEMOLITION WORK IS TO INCLUDE ALL WORK REQUIRED TO COMPLETE THE OVERALL INTENT OF
THE PROJECT WHETHER INDICATED ON THE DRAWINGS OR NOT.
THESE RENOVATIONS SHALL BE CONSTRUCTED IN COMPLIANCE WITH ALL GOVERNING CODES. IT WILL BE THE RESPONSIBILITY OF THE CONTRACTOR TO REPORT ANY DISCREPANCIES TO THE ARCHITECT PRIOR TO CONSTRUCTION. ANY COMPLETED WORK REQUIRING REMOVAL OR ALTERATIONS SHALL BE THE CONTRACTOR'S
RESPONSIBILITY.
ALL WORK TO BE COORDINATED WITH EACH RESPECTIVE CONTRACTOR. EACH CONTRACTOR SHALL THOROUGHLY REVIEW ALL PLANS AND SPECIFICATIONS PRIOR DEMOLITION AND CONSTRUCTION.
THE RESPECTIVE CONTRACTOR FOR EACH TRADE SHALL VERIFY LOCATION OF ALL UTILITIES PRIOR TO
DEMOLITION AND CONSTRUCTION.
THE RESPECTIVE CONTRACTOR FOR EACH TRADE SHALL VERIFY THAT ALL BUILDING PERMITS, ZONING, PLUMBING AND ELECTRICAL CODES HAVE BEEN MET PRIOR TO BEGINNING OF DEMOLITION AND CONSTRUCTION.
THE CONTRACTORS SHALL ADVISE THE ARCHITECT OF ANY ITEMS WHICH DO NOT MEET WITH LOCAL APPROVALS.
ALL PERMITS SHALL BE OBTAINED AND FEES PAID BY THE RESPECTIVE SUBCONTRACTOR.
ALL DEMOLITION WORK SHALL BE COORDINATED AND SCHEDULED ACCORDINGLY WITH THE NEW
CONSTRUCTION BY THE GENERAL CONTRACTOR.
ALL USABLE ITEMS SHALL BE STORED OR REMOVED AS DIRECTED BY THE OWNER.
DISPOSAL OF ITEMS SHALL BE DONE IN ACCORDANCE WITH ALL 'ENVIRONMENTAL PROTECTION AGENCIES' AND
THE 'DEPARTMENT OF ENVIRONMENTAL RESOURCES' STANDARDS.
ALL EXISTING EQUIPMENT HAVING PLUMBING, HVAC OR ELECTRICAL CONNECTIONS AND NOTED TO BE REMOVED
SHALL BE DISCONNECTED BY THE APPROPRIATE CONTRACTOR.
ALL DISTURBED OR DAMAGED AREAS (EXTERIOR OR INTERIOR) SHALL BE REPAIRED AND FINISHED WITH MATERIALS TO MATCH EXISTING ADJACENT SURFACES OR AS NOTED ON THE ROOM FINISH SCHEDULE.
ALL RESPECTIVE CONTRACTORS SHALL BE RESPONSIBLE FOR UNREASONABLE DAMAGE TO ITEMS THAT ARE
EXISTING AND TO REMAIN.
WHERE EXISTING FLOORS, WALLS, CEILINGS, DOOR FRAMES, WINDOWS, CABINETS, SINKS, PIPING, LIGHTS, ETC.
ARE REMOVED, THE EXISTING OPENING SHALL BE CLOSED OR REPAIRED WITH MATERIALS TO MATCH EXISTING
ADJACENT SURFACES OR AS NOTED ON THE ROOM FINISH SCHEDULE.
WHERE NEW OPENINGS ARE REQUIRED IN AN EXISTING WALL, THE CONTRACTOR SHALL PROVIDE THE REQUIRED
LINTEL, WHETHER INDICATED ON THE DRAWING OR NOT.
WHERE NEW WALLS, FLOORS OR CEILINGS ABUT EXISTING WALLS, FLOORS OR CEILINGS, THE TWO SURFACES
SHALL ALIGN.
ALL RESPECTIVE CONTRACTORS SHALL BE RESPONSIBLE FOR CLEAN-UP AND REMOVAL OF CONSTRUCTION
DEBRIS WITHIN THE LIMITS OF THE CONTRACT TO DUMPSTERS PROVIDED BY THE OWNER.
PERMITS AND FEES THAT ARE NOT TO BE OBTAINED AND PAID FOR BY THE SUBCONTRACTORS SHALL BE
OBTAINED AND PAID FOR BY THE GENERAL CONTRACTOR.
18. THE CONTRACTOR SHALL BE RESPONSIBLE FOR ADEQUATELY BRACING AND PROTECTING WORK DURING CONSTRUCTION AGAINST DAMAGE, BREAKAGE, COLLAPSE, DISTORTION, AND/OR MISALIGNMENT IN ACCORDANCE
WITH APPLICABLE CODE STANDARDS AND GOOD PRACTICE.
ALL PARTS OF THESE DOCUMENTS AND/OR SPECIFICATIONS ARE THE
EXCLUSIVE PROPERTY OF THE ARCHITECT AND WE RESERVE ALL
RIGHTS TO HAVE THIS WORK REPRODUCED, FABRICATED,
CONSTRUCTED, AND/OR MANUFACTURED. WE HAVE PLACED THESE
DOCUMENTS IN YOUR TEMPORARY CUSTODY, IN CONFIDENCE,
SOLELY FOR YOUR INSPECTION, AND/OR ESTIMATING THE COST OF
FABRICATING, CONSTRUCTING, AND/OR MANUFACTURING THE WORK
SHOWN. THE CONTRACTOR IS RESPONSIBLE FOR CHECKING ALL
DIMENSIONS AND CONDITIONS AT THE JOBSITE, AS WELL AS BUILDING
RULES AND REGULATIONS. THE CONTRACTOR IS RESPONSIBLE FOR
COORDINATING ALL INSPECTIONS AND OBTAINING THE CERTIFICATE
OF OCCUPANCY. THE RECIPIENT OF THESE DOCUMENTS WARRANTS
THAT THEY WILL NOT REPRODUCE, DISTRIBUTE, OR OTHERWISE
MAKE USE OF THE DOCUMENTS WITHOUT THE PERMISSION OF THE
ARCHITECT. THE USE OF THESE DESIGNS FOR ANY OTHER PURPOSE
PROJECT NO: PROJECT MGR:
REVISIONS
CONSULTANT INFORMATION:
SEAL/STAMP:
155 WEST MARKET STREET, SUITE 200
YORK, PA 17401
PHONE 717.741.2046 FAX: 717.741.6836
WWW.CORE-DESIGNGROUP.COM
6/
/2
2:
:2
PM
Au to de sk
D oc s:
//Y
AT
B
M ai l R oo m
In fil l P ro je ct
/2 5.
- Y
AT
B
- M ai l I nf ill
Pr oj ec t.r vt
PARTIAL SECOND
FLOOR
DEMOLITION
PLAN
AD102
25.147 M.A.S.
YO
RK
A
DA
M S
TA
X
BU
RE
AU
SE
CO
ND
F
LO
OR
O
FF
IC
E
EX
PA
NS
IO
N
N
OR
TH
D
UK
E
ST
RE
ET
YO
RK
, P
A
NOT TO SCALE
NO WORK THIS AREA
AREA OF WORK
KEYPLAN
SCALE: 1/4" = 1'-0"AD102
PARTIAL SECOND FLOOR DEMOLITION PLAN1
DEMOLITION NOTES
MARK DESCRIPTION
D01 DEMOLISH EXISTING WALL AND ANY ASSOCIATED ACCESSORIES - COMPLETE.
D02 REMOVE EXISTING DOOR, FRAME, AND HARDWARE - COMPLETE.
D03 REMOVE EXISTING CEILING AND ASSOCIATED FIXTURES - COMPLETE.
D04 REMOVE EXISTING STOREFRONT AND FRAME TO ACCOMMODATE NEW CONSTRUCTION.
D06 REMOVE PORTION OF EXISTING WALL TO ACCOMMODATE NEW WINDOW. - SEE NEW WORK PLANS
D07 SALVAGE EXISTING LIGHTS FOR RELOCATION. - SEE NEW WORK PLANS
D08 SALVAGE EXISTING HVAC DIFFUSERS FOR RELOCATION. - SEE NEW WORK PLANS
D09 REMOVE EXISTING CEILING TILES. EXISTING GRID TO REMAIN.
D10 REMOVE PORTION OF EXISTING GRID & CEILING TILES A REQUIRED FOR NEW CONSTRUCTION.
EXISTING WALL
EXISTING DOOR
LEGEND
DEMO WALL
DEMO DOOR
EXISTING ACT GRID
EXISTING PENDANT LIGHT
EXISTING HVAC DIFFUSER
EXISTING 2X2 CEILING LIGHT
EXISTING PENDANT CEILING LIGHT
EXISTING ACT GRID
TO BE REMOVED
EXISTING PENDANT LIGHT
TO BE REMOVED
EXISTING HVAC DIFFUSER
TO BE REMOVED
EXISTING TO REMAIN(E)
EXISTING TO BE REMOVED(ER)
EXISTING HVAC SUPPLY TO BE REMOVED
A B C
4.5
D07
D07
D07
D07
D07
(ER)(ER)
(ER) (ER)
(ER) (ER)
(ER) (ER)
(ER) (ER)
(ER) (ER)
(ER) (ER)(E)
(E)
(E)
(E)
(E)
(E)
GENERAL ALTERATION NOTES:
1.
2.
3.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
16.
17.
THESE DEMOLITION PLANS INDICATE MAJOR AREAS TO BE REMOVED OR ALTERED. ANY ITEMS NOT NOTED SHALL
BE CONSIDERED EXISTING TO REMAIN.
THE EXTENT OF DEMOLITION WORK IS TO INCLUDE ALL WORK REQUIRED TO COMPLETE THE OVERALL INTENT OF
THE PROJECT WHETHER INDICATED ON THE DRAWINGS OR NOT.
THESE RENOVATIONS SHALL BE CONSTRUCTED IN COMPLIANCE WITH ALL GOVERNING CODES. IT WILL BE THE RESPONSIBILITY OF THE CONTRACTOR TO REPORT ANY DISCREPANCIES TO THE ARCHITECT PRIOR TO CONSTRUCTION. ANY COMPLETED WORK REQUIRING REMOVAL OR ALTERATIONS SHALL BE THE CONTRACTOR'S
RESPONSIBILITY.
ALL WORK TO BE COORDINATED WITH EACH RESPECTIVE CONTRACTOR. EACH CONTRACTOR SHALL THOROUGHLY REVIEW ALL PLANS AND SPECIFICATIONS PRIOR DEMOLITION AND CONSTRUCTION.
THE RESPECTIVE CONTRACTOR FOR EACH TRADE SHALL VERIFY LOCATION OF ALL UTILITIES PRIOR TO
DEMOLITION AND CONSTRUCTION.
THE RESPECTIVE CONTRACTOR FOR EACH TRADE SHALL VERIFY THAT ALL BUILDING PERMITS, ZONING, PLUMBING AND ELECTRICAL CODES HAVE BEEN MET PRIOR TO BEGINNING OF DEMOLITION AND CONSTRUCTION.
THE CONTRACTORS SHALL ADVISE THE ARCHITECT OF ANY ITEMS WHICH DO NOT MEET WITH LOCAL APPROVALS.
ALL PERMITS SHALL BE…