5 - Architectural.pdf
PDF 33 MB Posted
- Solicitation number
- 36C26126R0007
About this file
This document is a comprehensive architectural drawing file for a Veterans Affairs (VA) construction project located at 3801 Miranda Ave., Palo Alto, CA. The drawing (A0.2.0) provides a life safety diagram for Level B of a facility for Centers for Ambulatory Care, Polytrauma and Blind Rehabilitation. The floor plan details multiple rooms including an exercise room (3,376 sq ft), designed for 68 occupants based on a 50 sq ft per person calculation, open workstations accommodating 21 business occupancy workers, interview rooms, an elevator lobby, and various support spaces like electrical rooms and storage areas. The drawing includes critical life safety information such as maximum travel distances, exit sign locations, fire extinguisher placements, and occupancy load calculations for different spaces, demonstrating detailed planning for emergency egress and building safety compliance.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C26126R0007 0001.pdf | ||
| 7 - Equipment.pdf | ||
| 15 - Existing Gymnasium Floor Detail.pdf | ||
| 12 - 2 - Electrical.pdf | ||
| 14 - Bleachers.pdf | ||
| Supplemental Price Breakdown by Division Sheet.docx | DOCX document | |
| REQUEST FOR INFORMATION FORM.docx | DOCX document | |
| 9 - Plumbing.pdf | ||
| 8 - Mechanical.pdf | ||
| 2 - Civil.pdf | ||
| 4 - Structural.pdf | ||
| 16 - Existing Elkay two level.pdf | ||
| 640-26-112 SPECS.pdf | ||
| 13 - Fire Alarm.pdf | ||
| 1 - General.pdf | ||
| 36C26126R0007 Replace Gymnasium Flooring.docx | DOCX document |
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
ABV
A
ABOVE
ACOUS ACOUSTICAL
ACP
AD
ACOUSTICAL CEILING PANEL
AREA DRAIN
ADDL ADDITIONALADDITIONAL
ADJ
AFF
ADJACENT
AFG
ABOVE FINISH FLOOR
ABOVE FINISH GRADE
AGGR
ALUM
AGGREGATE
ALT
ALUMINUM
ANOD
ALTERNATE
APPROX
ANODIZED
ARCH
APPROXIMATE(LY)
ARCHITECT(URAL)
ASPH ASPHALT
AUTO AUTOMATIC
BB
B
BULLETIN BOARD
BD BOARD
BTWN
BLDG
BETWEEN
BUILDING
BM
BOT
BEAM
BOTTOM
BITUM BITUMINOUS
BOS BOTTOM OF STEEL
BRG BEARING
BSMT BASEMENT
CAB
C
CABINET
CB CATCH BASIN
CCT
CG
CUBICLE CURTAIN TRACK
CORNER GUARD
CEM CEMENT, CEMENTITIOUS
CCTV CLOSED CIRCUIT TELEVISION
CH BD CHALKBOARD
CI CAST IRON
CJ CONTROL JOINT
CL
CLG
CLR
CMU
CNTR
COL
CONC
CONF
CONN
CONSTR
CONT
CONTR
CPT
CSK
CSP
CSWK
CW
CENTER LINE
CEILING
CLEAR
CONCRETE MASONRY UNIT
COUNTER
COLUMN
CONCRETE
CONFERENCE
CONNECTION
CONSTRUCTION
CONTINUOUS
CONTRACTOR
CARPET
COUNTERSUNK
COMBINATION STANDPIPE
CASEWORK
COLD WATER
D
D
DEPTH
DBL DOUBLE
DBL ACT DOUBLE ACTING
DEG DEGREE
DEMO DEMOLISH
DEPT DEPARTMENT
DET DETAIL
DF DRINKING FOUNTAIN
DIA DIAMETER
DIAG DIAGONAL
DIFF DIFFUSER
DIM DIMENSION
DIM PT DIMENSION POINT
DISP DISPENSER
DIST DISTANCE
DN DOWN
DR DRAIN
DS DOWNSPOUT
DSP DRY STANDPIPE
DT DRAPERY TRACK
DWG DRAWING
DWGS DRAWINGS
(E)
E
EXISTING
EA EACH
EDR EQUIPMENT DRAIN
EG EDGE GUARD
EIFS EXTERIOR INSULATION FINISH SYSTEM
EL ELEVATION
ELAST ELASTOMERIC
ELEC ELECTRICAL
ELEV ELEVATOR
EMER EMERGENCY
ENCL ENCLOSURE
ENGR ENGINEER
EOS EDGE OF SLAB
EP ELECTRICAL PANEL
EPDM ETHYLENE PROPYLENE DIENE MONOMER
EQ EQUAL
EQL SP EQUALLY SPACED
EQUIP EQUIPMENT
EQUIV EQUIVALENT
EST ESTIMATE(D)
EWC ELECTRIC WATER COOLER
EXP EXPANSION
EXP JT EXPANSION JOINT
EXT EXTERIOR
FURN FURNITURE
FXTR FIXTURE
G
G
GAS
H
H
HIGH
GA GAUGE, GAGE
GAL GALLON
GALV GALVANIZED
GB GRAB BAR
GC GENERAL CONTRACTOR
GFRC GLASS FIBER REINFORCED CONCRETE
GFRG GLASS FIBER REINFORCED GYPSUM
GL GLASS
GLU LAM GLUE LAMINATED
GLZ GLAZING
GR GRADE OR GRADING
GVL GRAVEL
GYP GYPSUM
GYP BD GYPSUM BOARD
GYP PLAS GYPSUM PLASTER
ID
I
INSIDE DIAMETER
JAN
J
JANITOR
KG
K
KILOGRAM
L L
LENGTH, LONG
M
M
METER (S)
(N)
N
NEW
P
QT
Q
QUARRY TILE
R
R
RISER
S SOUTH
T
T
TREAD
W
W
WEST
XFMR
X
TRANSFORMER
YD
Y
YARD
HB HOSE BIBB
HC HOLLOW CORE
HD HEAD
HDBD HARDBOARD
HDW HARDWARE
HDWD HARDWOOD
HGT HEIGHT
HM HOLLOW METAL
HNDRL HANDRAIL
HORIZ HORIZONTAL
HPT HIGH POINT
HR HOUR
HVAC HEATING-VENTILATION-AIR CONDITIONING
IN INCH
INCL INCLUDE, INCLUDING
INFO INFORMATION
INSUL INSULATION
INTR INTERIOR
INV INVERT
IVT INTRAVENOUS TRACK
JST JOIST
JT JOINT
KIT KITCHEN
KPL KICK PLATE
KS KNEE SPACE
LAB LABORATORY
LAM LAMINATE, LAMINATION
LAV LAVATORY
LB POUND
LED LIGHT EMITTING DIODE
LF LINEAR FOOT
LIN LINEAR
LL LEAD LINED
LPT LOW POINT
LT LIGHT
LT WT LIGHT WEIGHT
LTG LIGHTING
LVR LOUVER
HW HOT WATER
S
MACH MACHINE
MATL MATERIAL
MATV MASTER ANTENNA TELEVISION SYSTEM
MAX MAXIMUM
MB MACHINE BOLT
MC MEDICINE CABINET
MDF MEDIUM DENSITY FIBERBOARD
MECH MECHANICAL
MED MEDIUM
MEMB MEMBRANE
MFR MANUFACTURER
MH MANHOLE
MIN MINIMUM
MISC MISCELLANEOUS
MELD MOLDING
MM MILLIMETERS
MO MASONRY OPENING
MOD MODULE, MODULAR
MTD MOUNTED
MTG MOUNTING
MOVABLE MOVABLE
MULL MULLION
DNA NOT APPLICABLE
NAT NATURAL
NE NORTHEAST
NIC NOT IN CONTRACT
NO NUMBER
NOM NOMINAL
RC NOISE REDUCTION COEFFICIENT
NTS NOT TO SCALE
NW NORTHWEST
PLAS PLASTER
PLBG PLUMBING
PLF POUNDS PER LINEAR FOOT
PLYWD PLYWOOD
PNL PANEL
PNL BD PANEL BOARD
PNT PAINT
PORT PORTABLE
PP PUSH PLATE
PPM PARTS PER MILLION
PR PAIR
PRCST PRECAST
PREP PREPARATION / PREPARE
PREFAB PREFABRICATED
PRKG PARKING
PROJ PROJECT
PROP PROPERTY
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
PT POINT
PTN PARTITION
PTS PNEUMATIC TUBE STATION / SYSTEM
PVC POLYVINYL CHLORIDE
PVG PAVING
PVMT PAVEMENT
PWR POWER
QTR QUARTER
QTY QUANTITY
RA RETURN AIR
RAD RADIUS
RB RESILIENT BASE
RCP REFLECTED CEILING PLAN
RCPT RECEPTACLE
RD ROOF DRAIN
RECT RECTANGULAR
REF REFERENCE
REFR REFRIGERATOR
REG REGISTER
REINF REINFORCE (D) (ING) (MENT)
REQD REQUIRED
REQT REQUIREMENT
RESIL RESILIENT
RET RETURN
REV REVISION
RF RESILIENT FLOORING / RADIO FREQUENCY
RH RIGHT HAND
RHMS ROUND HEAD MACHINE SCREW
RHWS ROUND HEAD WOOD SCREW
RM ROOM
RND ROUND
RO ROUGH OPENING
ROW RIGHT OF WAY
RWL RAIN WATER LEADER
SB SPLASH BLOCK
SC SOLID CORE
SCHED SCHEDULE, SCHEDULED
SCRN SCREEN
SD STORM DRAIN
SE SOUTHEAST
SECT SECTION
SEG SEGMENT
SEP SEPARATION OR SEPARATE
SEP JT SEPARATION JOINT
SHT SHEET, SHEETING
SHWR SHOWER
SIM SIMILAR
SJ SEISMIC JOINT
SK SINK
SMS SHEET METAL SCREW
SP SPACE, SPACED, SPACING
SPEC SPECIFICATION
SPKLR SPRINKLER
SPKR SPEAKER
SQ SQUARE
SS SANITARY SEWER
SSK SERVICE SINK
SST STAINLESS STEEL
ST STREET
STA STATION
STAG STAGGERED
STC SOUND TRANSMISSION COEFFICIENT
STD STANDARD
STL STEEL
STOR STORAGE
STRUCT STRUCTURAL
STS SELF-TAPPING SCREW
SUSP SUSPENDED
SUSP CLG SUSPENDED CEILING
SW SOUTHWEST
SYMM SYMMETRICAL
SYST SYSTEM
T&B TOP AND BOTTOM
T&G TONGUE AND GROOVE
TC TOP OF CONCRETE, TOP OF CURB
TD TRENCH DRAIN
TEL TELEPHONE
TEMP TEMPORARY
THERM THERMAL
THK THICK, THICKNESS
THRES THRESHOLD
THRU THROUGH
TMPD GL TEMPERED GLASS
TO TOP OF
TOR TOP OF RAILING
TOS TOP OF STEEL
TOT TOTAL
TOW TOP OF WALL
TP TOP OF PAVEMENT
TV TELEVISION
UC
U
UNDER COUNTER
TYP TYPICAL
UL UNDERWRITERS LABORATORIES
UON UNLESS OTHERWISE NOTED
UPS UNINTERRUPTABLE POWER SUPPLY
UTIL UTILITY
W/ WITH
W/O WITHOUT
WC WATER CLOSET OR WALL COVERING
WD WOOD
WDW WINDOW
WGL WIRE GLASS
WCHR WHEELCHAIR
WM WIRE MESH
WO WHERE OCCURS
WPT WORKING POINT
WR WATER RESISTANT
WSCT WAINSCOT
WSP WET STANDPIPE
WT WEIGHT
WTHPRF WEATHERPROOF
WWF WELDED WIRE FABRIC
WWM WELDED WIRE MESH
CR CARD READER
BUR BUILT UP ROOFING SYSTEM
CT CERAMIC TILE / COMPUTED TOMOGRAPHY
F
FA FIRE ALARM
FBD FIBERBOARD
FCU FAN COIL UNIT
FD FLOOR DRAIN
FDC FIRE DEPARTMENT CONNECTION
FDN FOUNDATION
FEC FIRE EXTINGUISHER CABINET
FE FIRE EXTINGUISHER
FF FINISH FACE
FHC FIRE HOSE CABINET
FHMS FLAT HEAD MACHINE SCREW
FHWS FLAT HEAD WOOD SCREW
FHY FIRE HYDRANT
FLAM FLAMMABLE
FLASH FLASHING
FLEX FLEXIBLE
FLUOR FLUORESCENT
FO FACE OF
FSB FOLDING SHOWER BENCH
FSTNR FASTENER
FT FOOT, FEET
OC
O
ON CENTER
PA PUBLIC ADDRESS
OA OVERALL
OD OUTSIDE DIAMETER
OFCI
OFOI
OPP OPPOSITE
ORD OVERFLOW ROOF DRAIN
OVHD OVERHEAD
OZ OUNCE
PART PARTIAL
PBD PARTICLEBOARD
PCF POUNDS PER CUBIC FOOT
PCI POUNDS PER CUBIC INCH
PERF PERFORATED
PERIM PERIMETER
PERM PERMANENT
PERP PERPENDICULAR
PL PLATE OR PROPERTY LINE
PLAM PLASTIC LAMINATE
P
OWNER FURNISHED-CONTRACTOR INSTALLED
OWNER FURNISHED-OWNER INSTALLED
V
VB VALVE BOX
VCT VINYL COMPOSITION TYLE
VERT VERTICAL
VEST VESTIBULE
VIT VITREOUS
VP VENT PIPE
VOL VOLUME
VWC VINYL WALL COVERING
SYMBOLS AS
ABBREVIATIONS
ANGLE
@ AT
C CENTER LINEL
Ø DIAMETER
= EQUAL
> GREATER THAN
< LESS THAN
± PLUS OR MINUS (TOLERANCE)
# POUND(S)
' FOOT OR FEET
" INCH OR INCHES
FOF FACE OF FINISH
OH OPPOSITE HAND
HSS HOLLOW STRUCTURAL STEEL
SA SUPPLY AIR
A AIR
AB ANCHOR BOLT
ACT ACOUSTICAL CEILING TILE
AVG AVERAGE
BKG BACKING
BLW BELOW
BG BUMPER GUARD
EJ EXPANSION JOINT
EF EACH FACE
E EAST
FB FLAT BAR O OXYGEN
N NORTH
MRI MAGNETIC RESONANCE IMAGING
LVT LUXURY VINYL TILES
F
FHV FIRE HOSE VALVE
FTG FOOTING
WP WATERPROOF (ING)
UR URINAL
VIF VERIFY IN FIELD
VNR VENEER
DEGREE (S) OF ANGULAR
MEASURE
o
MTL METAL
VC VA PROVIDED, CONTRACTOR INSTALLED
VV VA PROVIDED AND INSTALLED
COORD COORDINATE
PL PLATE
AESS ARCHITECTURALLY EXPOSED STRUCTURAL STEEL
PCF POUNDS PER CUBIC FOOT
FLRG FLOORING
TRANS TRANSITION
LLV LONG LEG VERTICAL
FSK FOIL SCRIM KRAFT
THE FOLLOWING GENERAL NOTES APPLY TO ALL
A-SERIES DRAWINGS.
A.
B.
C.
FOR GENERAL NOTES APPLICABLE TO ALL
DRAWINGS REFER TO THE "PROJECT GENERAL
NOTES" ON SHEET GI0.2.1
FOR GENERAL NOTES, ABBREVIATION, AND
SYMBOLS APPLICABLE ONLY TO DRAWINGS OF A
DISCIPLINE OTHER THAN ARCHITECTURE, REFER
TO THE SPECIFIC DRAWINGS OF THAT DISCIPLINE
- SEE THE "INDEX OF DRAWINGS" ON SHEET
GI0.1.1
D. THE DRAWINGS ARE INTENDED TO
GRAPHICALLY ILLUSTRATE THE OVERALL
NATURE OF THE WORK; THE CONFIGURATION,
ARRANGEMENT, AND LOCATION OF THE WORK
AND ITS PARTS; AND THE PHYSICAL
DIMENSIONS OF THE WORK - THE DRAWINGS
TAKE PRECEDENCE OVER THE SPECIFICATIONS
WITH RESPECT TO INFORMATION OF THIS
NATURE.
E. THE SPECIFICATIONS ARE INTENDED TO
COMMUNICATE THE DETAILED PROPERTIES AND
QUALITY OF THE INDIVIDUAL MATERIALS,
ASSEMBLIES, AND SYSTEMS THAT COMPRISE
THE WORK; THE FUNCTIONAL AND
PERFORMANCE REQUIREMENTS FOR THE
INDIVIDUAL PARTS OF THE WORK; AND THE
FABRICATION AND INSTALLATION
REQUIREMENTS FOR INDIVIDUAL PARTS OF THE
WORK - THE SPECIFICATIONS TAKE
PRECEDENCE OVER THE DRAWINGS WITH
RESPECT TO INFORMATION OF THIS NATURE.
F. AS PART OF THE CONTRACTOR'S RESPONSIBILITY
TO COORDINATE THE WORK OF ALL SUB-
CONTRACTORS, TRADES, AND SUPPLIERS, THE
CONTRACTOR SHALL ENDEAVOR TO IDENTIFY AND
NOTIFY THE VA REPRESENTATIVE OF ANY
CONFLICTS AT THE EARLIEST POSSIBLE DATE SO
AS TO ALLOW REASONABLE AND ADEQUATE TIME
FOR THE CONFLICT TO BE RESOLVED WITHOUT
DELAYING THE WORK, ALL DEVIATIONS FROM
THAT WHICH IS REQUIRED BY THE CONTRACT
DOCUMENTS MUST BE APPROVED IN ADVANCE BY
THE VA REPRESENTATIVE.
G. THE ARCHITECTURAL DRAWINGS ARE A PART
OF A LARGER SET OF DRAWINGS WHICH, WHEN
COMPLETE, CONSISTS OF ALL DRAWINGS
LISTED BY THE INDEX OF DRAWINGS, THE WORK
DESCRIBED BY THE DRAWINGS OF ANY ONE
DISCIPLINE MAY BE AFFECTED BY THE WORK
DESCRIBED ON DRAWINGS OF ANOTHER
DISCIPLINE AND MAY REQUIRE REFERENCE TO
THE DRAWINGS OF ANOTHER DISCIPLINE.
PARTIAL SETS OF DRAWINGS ARE INCOMPLETE
AND SHOULD NOT BE DISTRIBUTED OR UTILIZED
BY THE CONTRACTOR. IT IS THE CONTRACTOR'S
RESPONSIBILITY TO REVIEW AND COORDINATE
THE WORK OF ALL SUB-CONTRACTORS,
TRADES, AND SUPPLIERS WITH ALL
REQUIREMENTS OF THE CONTRACT
DOCUMENTS BEFORE COMMENCING
CONSTRUCTION, AND TO ASSURE THAT ALL
PARTIES ARE AWARE OF ALL REQUIREMENTS,
REGARDLESS OF WHERE THE REQUIREMENTS
OCCUR IN THE CONTRACT DOCUMENTS, WHICH
MIGHT AFFECT THE WORK OF THAT PARTY.
THE ARCHITECTURAL DRAWINGS ESTABLISH
AND COORDINATE THE FINISHED APPEARANCE
AND EXACT LOCATION OF ALL EXPOSED
ELEMENTS OF THE WORK OF ALL TRADES,
INCLUDING THAT WORK WHICH IS ILLUSTRATED
PRIMARILY ON DRAWINGS OF OTHER
DISCIPLINES, LOCATIONS SHOWN ON OTHER
DRAWINGS ARE SCHEMATIC, UNLESS
OTHERWISE NOTED ON THE ARCHITECTURAL
DRAWINGS. THE ARCHITECTURAL DRAWINGS
TAKE PRECEDENCE FOR THE FINISHED
APPEARANCE AND EXACT LOCATION OF ALL
PARTS OF THE WORK,
EXCEPTION: DIMENSIONED LOCATIONS SHOWN
ON DRAWINGS OF OTHER DISCIPLINES SHALL
GOVERN ONLY WHERE:
1. SPECIFICALLY AND INDIVIDUALLY INDICATED
BY SYMBOL, KEYED NOTE, OR NOTATION ON
THE ARCHITECTURAL DRAWINGS.
2. OCCURRING WITHIN A ROOM OR OTHER
IDENTIFIED SPACE FOR WHICH ARCH SHEET OR
SCHEDULE NOTES INDICATE THAT DIMENSIONS
PROVIDED ELSEWHERE SHALL GOVERN.
H.
THE ARCHITECTURAL FLOOR PLANS, REFLECTED
CEILING PLANS, SECTIONS, AND ELEVATIONS
ILLUSTRATE THE EXACT LOCATION OF MANY, BUT
NOT ALL, EXPOSED PARTS OF THE WORK, APPLY
THE RULES INDICATED BY THE DRAWING "TYPICAL
MOUNTING HEIGHTS AND CONFIGURATION
DIAGRAMS" TO DETERMINE THE EXACT LOCATION
OF EACH EXPOSED PART OF THE WORK.
I.
REFER TO THE STRUCTURAL, MECHANICAL,
ELECTRICAL, AND PLUMBING DRAWINGS FOR
THE DETAILED DESIGN OF STRUCTURAL,
MECHANICAL, ELECTRICAL, AND PLUMBING
SYSTEMS, OF WHICH PORTIONS MAY BE
SHOWN ON THE ARCHITECTURAL DRAWINGS.
J.
FINISH FLOOR ELEVATIONS ARE TO TOP OF
CONCRETE FLOOR SLAB, UON. WHERE THE
CONCRETE IS DEPRESSED TO ACCOMMODATE
MORTAR BEDS, SETTING BEDS, RAISED ACCESS
FLOORS, AND OTHER SIMILAR FLOOR
ASSEMBLIES, FINISHED FLOOR ELEVATIONS ARE
TO TOP OF FINISH FLOOR ASSEMBLY INDICATED.
K.
CEILING HEIGHT DIMENSIONS ARE TO FINISHED
SURFACES, UNLESS OTHERWISE NOTED.L.
FOR TYP DIMENSIONING CONVENTIONS,
INCLUDING RULES FOR LOCATING DOORS
WHICH HAVE NOT BEEN DIMENSIONED, REFER
TO THE "ARCHITECTURAL DIMENSIONING
CONVENTIONS" NOTES ON THIS SHEET.
M.
FOR ILLUSTRATION AND DEFINITION OF TYPICAL
SYMBOLS USED ON THE ARCHITECTURAL
DRAWINGS, REFER TO THE "ARCHITECTURAL
SYMBOLS" ON SHEET AE0.1.2.
N.
ADDITIONAL SYMBOLS, NOT SHOWN OR DEFINED
ON THE DRAWING "ARCHITECTURAL SYMBOLS",
MAY OCCUR AND ARE DEFINED ON OTHER
ARCHITECTURAL DRAWINGS.
O.
BASIC FIRE PROTECTION AND EXITING
CONCEPTS ARE ILLUSTRATED BY AE0.2-SERIES
"LIFE SAFETY DIAGRAM" DRAWINGS.
P.
ARCHITECTURAL DIMENSIONING CONVENTIONS
- CONTINUED AT TOP OF NEXT COLUMN
D.
5.
DIMENSION, WHEN OCCURS
ALIGN
B.
C.
B.
A.
4.
3.
A.
F.
E.
D.
1.
2.
E.
NOTE NO 4 CONTINUED:4.
C.
EXCEPT WHERE DIRECTED TO PLACE ITEMS OF THE
WORK AT THE "APPROXIMATE LOCATION SHOWN,"
DO NOT SCALE DRAWINGS FOR DIMENSIONAL
INFORMATION.
ALL ELEMENTS OF THE DRAWINGS MAY NOT BE
DRAWN TO EXACT SCALE. ALL DIMENSIONS
REQUIRED ARE SHOWN (OR MAY BE DERIVED
FROM THOSE SHOWN OR NOTED) ON THE FLOOR
PLANS, DETAIL PLANS, ELEVATIONS, SECTIONS,
SCHEDULES, CONFIGURATION DETAILS, AND
SPECIFICATIONS. SEE THE NOTES BELOW AND
SYMBOLS ON SHEET A0.1.2 FOR DIMENSIONING
CONVENTIONS USED ON THIS PROJECT.
EXCEPT WHERE SPECIFICALLY NOTED TO THE
CONTRARY, ALL DIMENSIONS SHOWN ON THE
ARCHITECTURAL DRAWINGS CONFORM TO THE
FOLLOWING CONVENTIONS:
DIMENSIONS UTILIZING THE "CENTERLINE" SYMBOL
ARE MEASURED TO:
STRUCTURAL OR DIMENSIONAL GRID LINES.
CENTERLINE OF CONCRETE OR CONC
MASONRY UNIT WALLS (EXCLUSIVE OF
FURRING OR APPLIED FINISHES HAVING
THICKNESS). REFER TO THE ARCH PLANS
AND SECTIONS, THE STRUCT DRAWINGS,
OR PARTITION SCHEDULE TO DETERMINE
THE THICKNESS OF CONCRETE OR CONC
MASONRY UNIT WALLS.
CENTERLINE OF PARTITION ASSEMBLY
(EXCLUSIVE OF ANY APPLIED FINISHES
HAVING THICKNESS WHICH MAY BE
ADDED TO SUCH WALLS) AT PARTITIONS
FRAMED WITH METAL STUDS. REFER TO
"PARTITION SCHEDULE" TO DETERMINE
THICKNESS OF EACH PARTITION TYPE.
CENTERLINE OF DOOR, WINDOW, OR LOUVER
OPENING.
CENTERLINE OF EQUIPMENT OR
FURNISHING.
CENTERLINE OF OTHER FEATURES AS
INDICATED.
REFER TO SHEET A0.1.2 FOR SYMBOL USED
TO INDICATE CENTERLINE DIMENSION.
DIMENSIONS UTILIZING THE "FACE OF"
SYMBOL ARE MEASURED TO:
FACE OF CONCRETE OR CONC MASONRY
UNIT WALL (EXCLUSIVE OF APPLIED
FINISHES HAVING THICKNESS OR FURRING
WHICH MAY BE ADDED TO THE FACE OF
SUCH WALLS).
FACE OF PARTITION ASSEMBLY
(EXCLUSIVE OF ANY APPLIED FINISHES
HAVING THICKNESS WHICH MAY BE
ADDED TO SUCH WALL) AS DEFINED
BY THE PARTITION SCHEDULE.
UNLESS NOTED AS A "FACE OF
FINISH" OR "CLEAR" DIMENSION (SEE
NOTE 'E' BELOW), DIMENSIONS ARE
NOT MEASURED TO THE FACE OF
APPLIED FINISH. REFER TO THE
"PARTITION SCHEDULE" TO DETERMINE
THE THICKNESS OF EACH PARTITION
TYPE.
INSIDE EDGE OF FINISHED DOOR
OPENING. REFER TO THE "DOOR
SCHEDULE" FOR ADDITIONAL
DIMENSIONAL INFORMATION.
DIMENSION OR WORK POINT AS
INDICATED ON RELATED ARCH DETAIL
PLAN, SECTION, ELEVATION, LAYOUT
OR CONFIGURATION DETAIL, OR
CONSTRUCTION DETAIL.
REFER TO SHEET A0.1.2 FOR SYMBOL USED
TO INDICATE "FACE OF" DIMENSION.
WHERE "FACE OF FINISH" OR "CLEAR" DIMENSIONS
ARE SPECIFICALLY NOTED, THE DIM IS MEASURED
TO:
FINISH FACES AT THE MOST NARROW
OR CONSTRICTED POINTS OF SECTION
WHERE DIMENSION IS SHOWN, WHEN
THE DIMENSION OCCURS ACROSS AN
OPEN SPACE. THIS CASE, A "FACE
OF FINISH" DIMENSION IS EQUIVALENT
TO A "CLEAR" DIMENSION.
FINISH FACES AT THE WIDEST OR MOST
EXPANSIVE POINTS OF THE SECTION THE
DIMENSION IS SHOWN WHEN THE DIMENSION
OCCURS ACROSS AN OBJECT OR GROUP OF
OBJECTS.
WHERE "EQUAL" DIMENSIONS ARE USED
ON REFLECTED CEILING PLANS TO
LOCATE CEILING GRID WORK POINTS,
MEASURE DIMENSIONS TO:
EDGE OF THE INDICATED CEILING AT
THE FACE OF THE ADJACENT APPLIED
FINISH MEASURED AT THE PLANE OF
THE CEILING.
CAUTION: DUE TO THE POSSIBLE
APPLICATION OF APPLIED FINISHES -
THICKNESS OF WHICH MAY VARY
BETWEEN FLOOR AND CEILING AND IS
NOT ACCOUNTED FOR (EXCEPT AS
INDICATED BY "FOF" OR "CLEAR") BY
THE DIMENSION SHOWN ON THE FLOOR
PLANS - THE CONTRACTOR MUST
ADJUST, AS NECESSARY, THE FLOOR
PLAN DIMENSIONS TO REFLECT THE
ACTUAL DIMENSIONS FOUND AT PLANE
OF THE CEILING.
WHERE DIMENSIONS ARE NOT PROVIDED ON
FLOOR PLANS TO LOCATE DOOR OPENINGS,
APPLY THE FOLLOWING RULES, IN ORDER, TO
DETERMINE THE LOCATION OF DOOR OPENINGS:
DOOR OPENINGS MAY BE
DIMENSIONED ON DRAWINGS OTHER
THAN THE FLOOR PLANS. REFER TO
THE SECTIONS, ELEVATIONS, DETAILS,
AND DOOR SCHEDULE NOTES FOR
ADDITIONAL DIMENSIONAL
INFORMATION.
WHERE THE HINGE-SIDE OF A DOOR IS
SHOWN ADJACENT TO A WALL - OR WALLS
- PERPENDICULAR TO THE WALL IN WHICH
THE DOOR OPENING OCCURS:
AT DOORS OCCURRING IN METAL FRAMED
GYPSUM BOARD PARTITIONS, LOCATE THE
HINGE-SIDE OF THE DOOR FINISHED
OPENING 4 INCHES FROM THE FACE
(EXCLUSIVE OF APPLIED FINISHES) OF THE
CLOSEST PERPENDICULAR WALL OR
PARTITION ASSEMBLY.
AT DOORS OCCURRING IN WALLS OF CONC
MASONRY UNIT CONSTRUCTION, LOCATE
THE HINGE-SIDE OF THE DOOR FINISHED
OPENING 10 INCHES FROM THE FACE
(EXCLUSIVE OF APPLIED FINISHES) OF THE
CLOSEST PERPENDICULAR WALL OR
PARTITION ASSEMBLY.
WHERE DOOR OCCURS NOT ADJACENT TO A
PERPENDICULAR WALL AND EITHER "DIM E"
OR "DIM F" IS 16'-0" OR LESS, LOCATE
DOOR UTILIZING THE FOLLOWING MINIMUM
DIMENSIONS:
DIMENSION A = 18 INCHES MIN
DIMENSION B = 12 INCHES MIN
DIMENSION C = DOOR WIDTH + 2
INCHES MINIMUM
DIMENSION D = 4 INCHES MIN AT
METAL FRAMED GYP BD PARTITIONS
OR - EVEN MULTIPLE OF 1/2 CMU
MODULE PLUS 2 INCHES AT CONC
MASONRY UNIT WALLS
DIMENSIONS E AND F = AS SHOWN ON
PLANS
DIMENSION G = 36 INCHES MIN
DIMENSION H = 60 INCHES MIN
IF SPACE ALLOWS, CENTER DOOR IN
WALL SHOWN ON THE DRAWINGS SO
THAT EITHER "DIM A" EQUALS "DIM C"
OR "DIM B" EQUALS "DIM D".
IF "DIM E" IN DIAGRAMS BELOW IS LESS
THAN THE SUM OF 2 TIMES THE DOOR
WIDTH PLUS 20 INCHES, LOCATE DOOR
SO THAT MINIMUMS STATED BY NOTE
NO 4C ABOVE FOR "DIM A", "DIM B,"
AND "DIM D" ARE MET - MAXIMIZING
"DIM A" AND MINIMIZING "DIM D" TO
THE EXTENT POSSIBLE.
WHERE DOOR IS SHOWN LOCATED IN A
LARGE EXPANSE OF OPEN WALL ("DIM
E" AND "DIM F" IN DIAGRAM BELOW
BOTH EXCEED 16'-0"), PLACE DOOR
AT APPROXIMATE LOCATION SHOWN ON
THE PLANS. WHERE DOOR OCCURS IN
CMU WALL, PLACE DOOR AT
APPROXIMATE LOCATION SHOWN WHILE
MINIMIZING "CUT" OR PARTIAL CMU
MODULES ADJACENT TO THE JAMBS.
WHERE WALLS AND/OR PARTITIONS OF
UNEQUAL THICKNESS ABUT, ALIGN EXPOSED
FACES, UNLESS OTHERWISE NOTED.
3. NOTE NO 3 CONTINUED:
MEASURED AT CLG PLANE
"EQUAL" DIM AT CEILING
MEASURED TO FACE OF PTN
TYPICAL DIM ON CEILING PLAN
4"
4"
10"
10"
DIM E > 16'-0"
DIM F > 16'-0"
E
A
E
A D
B D B
E A C
F
B D
G
H
- CONTINUED AT TOP OF NEXT COLUMN
3. NOTE NO 3 CONTINUED: NOTE NO 4 CONTINUED:4.
- CONTINUED AT TOP OF NEXT COLUMN
- CONTINUED AT TOP OF NEXT COLUMN
SEE SHEET AE7.3.1 FOR LOCATION OF RESTROOM ACCESSORIES.
SEE SPECIFICATION SECTION 10 28 00 FOR MORE INFORMATION.
VV VA PROVIDED AND INSTALLED
VC VA PROVIDED, CONTRACTOR INSTALLED
CC CONTRACTOR PROVIDED AND INSTALLED
DISPENSER, SOAP, DISPOSABLE VV
DISPENSER, PAPER TOWEL, SURFACE MOUNTED VV
DISPOSAL, SANITARY NAPKIN, SURFACE MOUNTED VC
GRAB BAR, 1-1/4" DIA, SST, 2 WALL CC
HOOK, GARMENT, DOUBLE, SST, SURFACE MOUNTED CC
DISPENSER, TOILET TISSUE, SST, 2-ROLL, SURFACE MOUNTED VV
BASKET, WASTEPAPER, ROUND, METAL VV
DISPENSER, SURFACE MOUNTED, SEAT COVER VC
GRAB BAR, 1-1/4" DIA, SST CC
DISPENSER, SURFACE MOUNTED, SANITARY NAPKIN VC
3801 Miranda Ave., Palo Alto CA
CENTERS FOR AMBULATORY CARE,
POLYTRAUMA AND BLIND REHABILITATION
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management
Seals and Signatures on e e igh th inc h = on e f oo t
B
A
C
D
E
F thr ee in ch es on e f oo t
6"
6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t
6" 6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
301 BATTERY STREET, 7TH FLOOR
SAN FRANCISCO, CA 94111
T 415.227.0100 F 415.908.0862 www.smithgroup.com
The Design Partnership LLP Architects + Planners
1412 VAN NESS AVE., 2ND FLOOR
SAN FRANCISCO, CA 94109
T 415.777.3737 F 415.777.3476 www.dpsf.com
Associate Architect:
Department of Veterans Affairs
PR
IN
TE
D
ON
:8
/8 /2
5:
:1
PM ABBREVIATIONS, GENERAL NOTES
AND DIMENSIONING CONVENTIONS
A0.1.1
DO NW10 MAY 2013
640-424
Recreation Services
ARCHITECTURAL ABBREVIATIONS ARCHITECTURAL GENERAL NOTES RESTROOM ACCESSORIES
eaquino Rectangle eaquino Typewritten Text
AS-BUILT
eaquino Typewritten Text Halbert Const. Co., Inc.
eaquino Typewritten Text eaquino Typewritten Text
SECOND LEVEL
+10'-0"
BUILDING SECTION
WALL SECTION NUMBER
DIRECTION OF VIEW
SHEET WHERE DRAWN
WALL SECTION
WALL SECTION NUMBER
NORTH ARROW REFERENCE
PROJ NORTH
NEW GRID
IDENTIFICATION
LAYOUT GRID LINES
BASIC DRAWING TITLE
SHEET WHERE DRAWN
DIRECTION OF VIEW
LEVEL LINE
REVISION NUMBER AND EXTENT
ROOM NAME AND NUMBER
PLAN DETAIL REFERENCE
SECTION DETAIL REFERENCE
DETAIL REFERENCE
EXTERIOR ELEVATION
AE102 2
INTERIOR ELEVATION REFERENCE
SEE PARTITION SYMBOL
DESCRIPTION ON SHEET
AE9.2.1
PARTITION TYPE IDENTIFICATION MARK
ELEVATION NUMBER AND
DIRECTION
SHEET WHERE DRAWN
SHEET WHERE DRAWN
ELEVATION NUMBER AND
DIRECTION OF VIEW
SHEET WHERE DRAWN,
HYPHEN INDICATES DETAIL
ON SAME SHEET.
DETAIL NUMBER
DETAIL NUMBER
SHEET WHERE DRAWN,
DASH TEXT INDICATES
DETAIL ON SAME SHEET
SHEET WHERE DRAWN
ELEVATION NUMBER AND
DIRECTION
AX.X.X X
GLAZING AND LOUVER TYPE MARK
SEE ELEVATIONS AND
EXT WINDOW SCHEDULE
NAME OF LEVEL
INDICATES HEIGHT ABOVE
PROJECT DATUM
REVISION NUMBER - SEE
REVISION HISTORY ON THE
TITLE BLOCK OF EACH
SHEET
EXTENT OF CURRENT
REVISION
KEYED NOTE MARK
MATCH LINE REFERENCE
DRAWING TITLE SYMBOLS
SEE CORRESPONDING
NUMBERED KEY NOTE ON
SHEET WHERE
REFERENCE OCCURS
DRAWING SIDE
DRAWING WHERE
CONTINUATION IS FOUND
A
SCALE:
A101
SIM
A101
SIM
A101
SIM
A101
SIM
AE101
SIM
A101
Room Name
0A3X
1 View Name 1/8" = 1'-0"
SEE PLANS AND INTERIOR
GLAZING TYPES
X-1
X
F1-140
(120SF)
466SF
ROOM NUMBER
PROGRAM AREA
ACTUAL AREA
EXTERIOR
INTERIOR
AA
EXISTING GRID
IDENTIFICATION
TRUE NORTH
FINISH TAG
P1
SEE CORRESPONDING
NUMBERED KEY NOTE ON
SHEET WHERE REFERENCE
OCCURS. SEE SPECIFICATIONS
FOR FINISH INFORMATION
DETAILS ARE NUMBERED ACCORDING TO THEIR
LOCATION ON EACH SHEET AND ARE NOT NUMBERED
CONSECUTIVELY. EACH MODULE MAINTAINS THE
NUMBER ASSOCIATED WITH IT
THIS SYSTEM CAN BE APPLIED TO ANY DRAWING
THAT CONTAINS MULTIPLE IMAGES. THE IMAGES ARE
NUMBERED ACCORDING TO THE MODULE SYSTEM
SHOWN ILLUSTRATED TO THE LEFT
EACH DETAIL MAY OCCUPY ONE OR MORE WHOLE
MODULES. THE DETAIL MODULE IS USED TO
ESTABLISH THE IDENTIFYING LABEL FOR EACH
DETAIL, NOT TO LIMIT THE SIZE OF THE DETAIL
DETAIL MODULE LAYOUT
DETAIL NUMBERING EXAMPLE
THE NUMBER OF THE MODULE WHICH OCCURS IN THE
LOWER LEFT CORNER OF A SINGLE MODULE OR
SEVERAL MODULES GROUPED TOGETHER WILL
DEFINE THE FINAL DETAIL NUMBER AS SHOWN IN THE
ILLUSTRATION TO THE LEFT. ALTHOUGH THE MODULE
NUMBERS OCCUR IN CONSECUTIVE ORDER, NOT ALL
NUMBERS ARE NECESSARILY USED ON EACH SHEET
162228
OVERHEAD ROLLING DOOR
PAIR DOORS - UNEQUAL SIZES
DOUBLE ACTING DOOR
SINGLE OPENING DOOR 2 PANEL BI-FOLD DOOR
PAIR - BI FOLD DOOR
DOOR OPENING MARK
PAIR DOORS - EQUAL SIZES
PAIR DOORS - DOUBLE EGRESS
DOOR WITH SIDE LIGHT
SLIDING DOOR - BETWEEN JAMBS
SLIDING POCKET DOOR
INTERIOR GLAZED WINDOW
EARTH
AGGREGATE BASE COURSE
CONCRETE
CONCRETE MASONRY UNIT/
TERRA COTTA
BRICK MASONRY
PRECAST CONCRETE
LIMESTONE, SANDSTONE, GRANITE
MARBLE
STEEL, STAINLESS STEEL
(LARGE SCALE)
ALUMINUM (LARGE SCALE)
OTHER METALS (LARGE
SCALE)
WOOD FRAMING -
CONTINUOUS (LARGE SCALE)
WOOD FRAMING - DISCONTINUOUS
(LARGE SCALE)
PLYWOOD
(LARGE SCALE)
FINISH WOOD (LARGE SCALE)
EIFS INSULATION BOARD
(LARGE SCALE)
SEMI-RIGID INSULATION
(LARGE SCALE)
BATT INSULATION
(LARGE SCALE)
MORTAR, SAND, FIREPROOFING,
STUCCO, GYPSUM BOARD
TERRAZZO (LARGE SCALE)
COMPOSITE BOARD
(LARGE SCALE)
ACOUSTIC TILE (LARGE SCALE)
PROTECTION BOARD
(LARGE SCALE)
CERAMIC TILE (LARGE SCALE)
GLASS (LARGE SCALE)
PLASTER, CONCRETE
CERAMIC TILE
METAL SIDING (VERTICAL)
GLASS
ELEVATION
PLAN AND SECTION
TRAFFIC COATING
FRITTED GLASS, EXTERIOR
DETECTABLE WARNING FLOOR
SURFACING
SILKSCREENED GLASS, INTERIOR
ARCHITECTURAL
ACCESS PANEL
MECHANICAL
SUPPLY GRILLE
RETURN GRILLE
EXHAUST GRILLE
LINEAR DIFFUSER
SPRINKLER HEAD - CLG MOUNT
SPRINKLER HEAD - WALL MOUNT
ELECTRICAL
2'X4' FLUORESCENT RECESSED
MOUNTED LUMINAIRE
2'X4' FLUORESCENT RECESSED
MOUNTED LUMINAIRE FOR EMERGENCY
FLUORESCENT RECESSED MOUNTED
LUMINAIRE
2'X2' FLUORESCENT RECESSED
MOUNTED LUMINAIRE
FLUORESCENT RECESSED WALLWASH
LUMINAIRE
LED COVE MOUNTED LUMINAIRE
WALL/CEILING SURFACE MOUNTED
LUMINAIRE
PENDANT MOUNTED LINEAR LUMINAIRE
FOR EMERGENCY
STRIPLIGHT LINEAR LUMINAIRE
UNDERCABINET LUMINAIRE
RECESSED DOWNLIGHT LUMINAIRE
RECESSED WALLWASH OR ACCENT
LUMINAIRE
SURFACE WALL MOUNTED LUMINAIRE
CEILING MOUNTED PENDANT LUMINAIRE
CEILING OR WALL MOUNTED EXIT SIGN
ACOUSTIC CEILING TILE
GYPSUM WALLBOARD CEILING,
PAINTED FINISH
2'X2' FLUORESCENT RECESSED
MOUNTED LUMINAIRE FOR EMERGENCY
MISCELLANEOUS
HEIGHT OF CEILING FINISH
ABOVE FINISH FLOOR
+12'-8"
RECESSED DOWNLIGHT LUMINAIRE
FOR EMERGENCY
FLUORESCENT RECESSED MOUNTED
LUMINAIRE FOR EMERGENCY
CEILING MOUNTED PENDANT LUMINAIRE
FOR EMERGENCY
SURFACE WALL MOUNTED LUMINAIRE
FOR EMERGENCY
PENDANT MOUNTED LINEAR LUMINAIRE
SURFACE CEILING MOUNTED LUMINAIRE
SURFACE CEILING MOUNTED
WALLWASH LUMINAIRE
FOR EMERGENCY
SURFACE CEILING MOUNTED LUMINAIRE
FOR EMERGENCY
SURFACE CEILING MOUNTED
WALLWASH LUMINAIRE
WALL/CEILING SURFACE MOUNTED
LUMINAIRE
FIRE ALARM COMBINATION
AUDIBLE/STROBE, WALL MOUNTED
ENCLOSED WRAPAROUND LUMINAIRE
CIRCULAR ACOUSTIC TILE CEILING
UNDERSIDE OF DECK
LINEAR WOOD CEILING
BASE CABINETS
BASE AND WALL CABINETS
WALL CABINETS
TOILET PARTITION AND DOOR
TOILET - WALL HUNG
URINAL - FLOOR/WALL
HUNG
LAVATORY -
COUNTERTOP
LAVATORY -
PEDESTAL/WALL HUNG
GENERAL SYMBOLS PLUMBING SYMBOLS
10' - 0"
EDGE GUARD
OVERHEAD ITEMS
UNDER-COUNTER ITEMS
NIC NOT-IN-CONTRACT
ITEMS
10' - 0"
10' - 0"
CLINIC SINK
DRINKING FOUNTAIN
DIMENSION SYMBOLS
SERVICE SINK
BATHTUB
SHOWER
STORM DRAIN AREA
DRAIN
FEC
FEC
FEXT FIRE EXTINGUISHER
BRACKET
FIRE EXTINGUISHER
CABINET
SURFACE MOUNTED
FIRE EXTINGUISHER
CABINET
SEMI-RECESSED
FIRE EXTINGUISHER
CABINET RECESSED
DIMENSION SHOWN TO:
- STRUCTURAL GRID
- LAYOUT GRID
GRID LINE TYPICAL
DIMENSION SHOWN TO:
- CENTERLINE OF ASSEMBLY
- CENTER OF OPENING
- CENTER OF EQUIP/ FURN
CENTER LINE TYPICAL
DIMENSION SHOWN TO:
- PARTITION ASSEMBLY
- EDGE OF DOOR OPENING
- OTHER BUILDING ELEMENT
- WPT INDICATED ON DETAIL
CORNER GUARD,
SEE DETAILS AE9.5.3 FOR DETAILS
SEE SCHEDULE OF FINISHES FOR
COLOR
CGXX TYPE DESIGNATION, SEE SPECS
FEC
FLOOR DRAIN IN
SLOPING FLOOR
HANDRAIL, HANDRAIL WITH
WALLGUARD
WALL GUARD
CRASHRAIL AND BUMPERGUARD
PUSH PLATE
PP
THE PURPOSE OF THIS SHEET IS TO ILLUSTRATE
AND DEFINE TYPICAL GRAPHIC SYMBOLS AND
SYSTEMS OF GRAPHIC SYMBOLS WHICH MAY
OCCUR ON THE ARCHITECTURAL DRAWINGS.
1.
2. THE ILLUSTRATION OF A SYMBOL OR SYSTEM OF
SYMBOLS ON THIS SHEET DOES NOT
NECESSARILY INDICATE THAT THE BUILDING ITEM
OR SYSTEM DESCRIBED BY THE SYMBOL IS
USED AS PART OF THE WORK OF THIS PROJECT.
REFER TO THE PLANS, ELEVATIONS, SECTIONS,
SCHEDULES, DETAILS, AND SPECIFICATIONS TO
DETERMINE THE SCOPE OF THE WORK.
3. MOUNTING HEIGHTS, WHERE INDICATED ADJACENT
TO SYMBOLS SHOWN ON THIS SHEET, ARE
PROVIDED ONLY FOR THE PURPOSE OF
ILLUSTRATING THE FORMAT OF THE SYMBOL ON
DRAWINGS OTHER THAN THIS SHEET, MOUNTING
HEIGHTS ARE INDICATED ADJACENT TO THE SYMBOL
ONLY WHERE THE MOUNTING HEIGHT IS NOT
TYPICAL WHERE THE MOUNTING HEIGHT IS TYPICAL,
NO HEIGHT IS SHOWN.
4. SYMBOLS ARE NOT DRAWN TO SCALE. TO DETERMINE
ACTUAL SIZES OF ELEMENTS REPRESENTED BY
SYMBOLS, REFER TO THE SPECIFICATIONS AND
OTHER DRAWINGS AS MAY APPLY.
5. FOR INFORMATION REGARDING SYMBOLS WHICH ARE
USED AS ABBREVIATIONS, REFER TO THE
ARCHITECTURAL ABBREVIATIONS SHOWN ON SHEET
A0.1.1
C
C 7'-0"
MOUNTING HEIGHT IS
OMITTED WHERE
HEIGHT IS TYPICAL.
HEIGHT IS SHOWN
WHERE HEIGHT IS NOT
TYPICAL.
6. CERTAIN SYMBOLS MAY INCORPORATE SPECIAL
ABBREVIATIONS AS PART OF THE SYMBOL, SUCH
ABBREVIATIONS ARE AS DEFINED ON THIS SHEET.
3801 Miranda Ave., Palo Alto CA
CENTERS FOR AMBULATORY CARE,
POLYTRAUMA AND BLIND REHABILITATION
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management
Seals and Signatures on e e igh th inc h = on e f oo t
B
A
C
D
E
F thr ee in ch es on e f oo t
6"
6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t
6" 6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
301 BATTERY STREET, 7TH FLOOR
SAN FRANCISCO, CA 94111
T 415.227.0100 F 415.908.0862 www.smithgroup.com
The Design Partnership LLP Architects + Planners
1412 VAN NESS AVE., 2ND FLOOR
SAN FRANCISCO, CA 94109
T 415.777.3737 F 415.777.3476 www.dpsf.com
Associate Architect:
Department of Veterans Affairs
PR
IN
TE
D
ON
:8
/8 /2
5:
:3
PM ARCHITECTURAL SYMBOLS
A0.1.2
DO HL10 MAY 2013
640-424
Recreation Services
ARCHITECTURAL FLOOR PLAN SYMBOLS AND REFERENCE SYMBOLS ARCH REFLECTED CEILING PLAN SYMBOLS
DOOR AND INTERIOR OPENING SYMBOLS
ARCHITECTURAL MATERIAL INDICATIONS
MODULAR LAYOUT / DETAIL NUMBER
eaquino Rectangle eaquino Typewritten Text Halbert Const. Co., Inc.
eaquino Typewritten Text
AS-BUILT
eaquino Typewritten Text
UP
1 2 3 7
A
RECREATION ROOM B100
EXERCISE ROOM
(WITH EQUIPMENT)
8600 SF / 50 SF PER
OCCUPANT =
172 OCCUPANTS
MECHANICAL ROOM
548 SF / 300 =
2 OCCUPANTS
RECREATION
ROOM
B100
WOMEN
B105
MEN
B103
ELEV MACH
B101A
ELEVATOR
LOBBY
B130
VIEWING STANDS
180 LF OF BENCHES /
1.5 LF PER PERSON =
120 OCCUPANTS
SEATING ALCOVE
115 SF / 1OO=
2 OCCUPANTS
MEP
B100B
STORAGE
B100A
D
F
ELEVATOR MACHINE
217 SF / 300 =
1 OCCUPANT
4 95 86
C
E
B
DRESSING
60 SF / 100 =
1 OCCUPANT
DRESSING
50 SF / 100 =
1 OCCUPANT
STORAGE
199 SF / 300 =
1 OCCUPANT
1.10.7
STAIR 2
BST2
ELEVATOR
BP02
ELEVATOR
BP01
VENDING
B101
VENDING ROOM
159 SF / 100 =
2 OCCUPANTS
UTILITY ROOM
68 SF / 300 =
1 OCCUPANT
M
AX
IM
UM
T
RA
VE
L
DI
ST
AN
CE
'-0
FEC
FEC
FEC
FEC
FEC
FEC
MAXIMUM TRAVEL DISTANCE 124'-0"
STAIR 3
BST3
EGRESS STAIR
TO LEVEL 1
LOBBY
FEC
HAC
B104
FEC
60 60
161' - 0 " 130' - 0"
106' - 10 1/2"
112' - 0"
UP
UP
SEATING
ALCOVE
CB01A
CORRIDOR
CB01
ELECTRICAL ROOM
17 SF / 300 =
1 OCCUPANT
ELEC
B101B
4"
0"
(E ) A
DJ
B
LD
G
(E ) A
DJ
B
LD
G
VESTIBULE
B105A
LEGEND
SMOKE BARRIER
XX EXIT LOAD
1 HR FIRE BARRIER
MAXIMUM TRAVEL DISTANCE
1. GREATEST OCCUPANT LOAD AT EXTERIOR DOOR IS WHEN
CONSIDERING THE LOBBY A POINT OF CONVERGENCE FOR
LEVEL B AND LEVEL 2 PER SECTION 7.3.1.5 OF NFPA 101.
2. FOR MOUNTING LOCATIONS OF EXIT SIGNS AT EXIT DOORS,
SEE GI1.1.2. FOR CEILING MOUNTED EXIT SIGNS, CENTER IN
CORRIDOR, TYPICAL.
3. SEE GI0.2.1 FOR PROJECT INFORMATION
EXIT SIGN
FIRE EXTINGUISHER CABINET (FEC)
FEC
EXISTING 1 HR FIRE RESISTIVE
RATED PARTITION
GRAPHIC SCALE:
0'
1/8" = 1'-0"
8' 8' 16'
3801 Miranda Ave., Palo Alto CA
CENTERS FOR AMBULATORY CARE,
POLYTRAUMA AND BLIND REHABILITATION
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management
Seals and Signatures on e e igh th inc h = on e f oo t
B
A
C
D
E
F thr ee in ch es on e f oo t
6"
6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t
6" 6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
301 BATTERY STREET, 7TH FLOOR
SAN FRANCISCO, CA 94111
T 415.227.0100 F 415.908.0862 www.smithgroup.com
The Design Partnership LLP Architects + Planners
1412 VAN NESS AVE., 2ND FLOOR
SAN FRANCISCO, CA 94109
T 415.777.3737 F 415.777.3476 www.dpsf.com
SHEET NOTES
Associate Architect:
Department of Veterans Affairs
PR
IN
TE
D
ON
TRUE NORTH
PROJ NORTH
8/ 7/
:5
3:
P
M LIFE SAFETY DIAGRAM LEVEL B
A0.2.0
DO NW10 MAY 2013
640-424
Recreation Services
SCALE: 1/8" = 1'-0"54 LIFE SAFETY DIAGRAM LEVEL B
eaquino Rectangle eaquino Typewritten Text
AS-BUILT
eaquino Typewritten Text Halbert Const. Co., Inc.
eaquino Typewritten Text
DN
1 2 3 7
A
152 (FROM
LEVEL B)
OR 46
(FROM
LEVEL 1)
EXERCISE ROOM
(WITH EQUIPMENT)
3376 SF / 50 =
68 OCCUPANTS
BUSINESS OCCUPANCY
CALCULATED BASED
UPON NUMBER OF
WORKSTATIONS
21 OCCUPANTS
128 (FROM
LEVEL B &
LEVEL 2)
128 (FROM
LEVEL B &
LEVEL 2)
GAIT TRACK
ELEC
EC1
INTERVIEW
CHIEF
ELEVATOR
LOBBY
OPEN
WORKSTATIONS
ELEVATOR LOBBY
332 SF / 15 =
23 OCCUPANTS
106 (FROM
EXISTING
LEVEL 1)
D
F
INTERVIEW
CONFERENCE
KITCHEN
ELECTRICAL ROOM
200 SF / 300
1 OCCUPANT
4 95 86
C
E
B OFFICE
COPY
C01A
1.10.7
FEC
FEC
FEC
FEC
FEC
FEC
FEC
FEC
7' - 2"
MAXIMUM TRAVEL DISTANCE 151' - 6"
ELEVATOR 1
1P01
ELEVATOR 2
1P02
M
AX
IM
UM
T
RA
VE
L
DI
ST
AN
CE
8'
- 0
CO
M
M
ON
P
AT
H
OF
T
RA
VE
L
<1
F T
68 (FROM
LEVEL 2)
BUSINESS OCCUPANCY
262 SF / 15
18 OCCUPANTS
EXISTING LOBBY
STAIR 1
1ST1
EXTERIOR
(E) LOBBY
/4
M
AI
NT
AI
N (E
) E
XI
T W
ID
TH
(E) CANOPY ABOVE
STAIR 2
1ST2
STAIR 3
ST3
OPEN TO BELOW
(E)
(E
EXIT TO PUBLIC WAY
AT GRADE
1.7 2.2
(E)E
EXIT TO PUBLIC WAY
AT GRADE
EXISTING EXIT.
CONTINUE TO PUBLIC
WAY AT GRADE
EXISTING EXIT TO
PUBLIC WAY AT
GRADE
EXIT
EX
IT
161' - 0 " 130' - 0"
106' - 10"
113' - 3"
85' - 0"
79' - 9"
100 (FROM
EXISTING
LEVEL 1)
1.2
0"
(E ) A
DJ
B
LD
G
(E ) A
DJ
B
LD
G
(E) BLDG 530 AQUATIC CENTER
LEGEND
SMOKE BARRIER
XX EXIT LOAD
1 HR FIRE BARRIER
MAXIMUM TRAVEL DISTANCE
1. GREATEST OCCUPANT LOAD AT EXTERIOR DOOR IS WHEN
CONSIDERING THE LOBBY A POINT OF CONVERGENCE FOR
LEVEL B AND LEVEL 2 PER SECTION 7.3.1.5 OF NFPA 101.
2. FOR MOUNTING LOCATIONS OF EXIT SIGNS AT EXIT DOORS,
SEE GI1.1.2. FOR CEILING MOUNTED EXIT SIGNS, CENTER IN
CORRIDOR, TYPICAL.
3. SEE GI0.2.1 FOR PROJECT INFORMATION
EXIT SIGN
FIRE EXTINGUISHER CABINET (FEC)
FEC
EXISTING 1 HR FIRE RESISTIVE
RATED PARTITION
GRAPHIC SCALE:
0'
1/8" = 1'-0"
8' 8' 16'
3801 Miranda Ave., Palo Alto CA
CENTERS FOR AMBULATORY CARE,
POLYTRAUMA AND BLIND REHABILITATION
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management
Seals and Signatures on e e igh th inc h = on e f oo t
B
A
C
D
E
F thr ee in ch es on e f oo t
6"
6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t
6" 6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
301 BATTERY STREET, 7TH FLOOR
SAN FRANCISCO, CA 94111
T 415.227.0100 F 415.908.0862 www.smithgroup.com
The Design Partnership LLP Architects + Planners
1412 VAN NESS AVE., 2ND FLOOR
SAN FRANCISCO, CA 94109
T 415.777.3737 F 415.777.3476 www.dpsf.com
SHEET NOTES
Associate Architect:
Department of Veterans Affairs
PR
IN
TE
D
ON
TRUE NORTH
PROJ NORTH
8/
/2
5:
:5
PM LIFE SAFETY DIAGRAM LEVEL 1
A0.2.1
DO NW10 MAY 2013
640-424
Recreation Services
SCALE: 1/8" = 1'-0"54 LIFE SAFETY DIAGRAM LEVEL 1
eaquino Rectangle eaquino Typewritten Text Halbert Const. Co., Inc.
eaquino Typewritten Text
AS-BUILT
eaquino Typewritten Text
R.D.R.D.
R.D.
O.F.D.O.F.D. O.F.D.
DN
DN
1 2 3 7
A
EXERCISE ROOM
(WITH EQUIP)
3252 SF / 50
66 OCCUPANTS
EXERCISE ROOM
(NO EQUIP)
652 SF / 15 =
44 OCCUPANTS EXERCISE ROOM
(WITH EQUIP)
958 SF / 50 =
20 OCCUPANTS
ELEVATOR LOBBY /
CIRCULATION
280 SF / 100 =
3 OCCUPANTS
D
F
UTILITY ROOMS
499 SF / 300 =
2 OCCUPANTS
4 95 86
C
E
B
1.10.7
EXERCISE 2
MEN
WOMEN
CORRIDOR
C03
HAC
CO3A
ELEC
EC2
TELECOMMUNICATIONS
TC1
ELEVATOR
LOBBY
CORRIDOR
C02
STUDIO
EXERCISE 1
ELEC
EC3
AV/ STOR
AV1
ELEVATOR
2P02
ELEVATOR
2P01
TOILETS
150 SF / 100 =
2 OCCUPANTS
7' - 2"
FEC FEC
M
AX
IM
UM
T
RA
VE
L
DI
ST
AN
CE
9"
CORRIDOR
CO2A
EXISTING LOBBY
(E) CANOPY
VEGETATED ROOF
OPEN TO BELOW
TOILETS
150 SF / 100 =
2 OCCUPANTS
EXIT STAIR
FROM LEVEL 2
(E) EXIT DOORS
BELOW
MAXIMUM TRAVEL DISTANCE 110'-0"
FEC
1.7 2.2
(E)E
FEC
VEGETATED ROOF
65' - 9 1/32"
107' - 6"
170' - 10"
DN
COMMON PATH OF TRAVEL
61'-3", LESS THAN 75'-0"
COMMON PATH OF TRAVEL
50'-10", LESS THAN 75'-0"
1.2
(E ) A
DJ
B
LD
G
(E ) A
DJ
B
LD
G
(E) BLDG 530 AQUATIC CENTER
(E)
(E)
EXIT STAIR FROM
BASEMENT AND
LEVEL 1 BELOW
128' - 1 0"
LEGEND
SMOKE BARRIER
XX EXIT LOAD
1 HR FIRE BARRIER
MAXIMUM TRAVEL DISTANCE
1. GREATEST OCCUPANT LOAD AT EXTERIOR DOOR IS WHEN
CONSIDERING THE LOBBY A POINT OF CONVERGENCE FOR
LEVEL B AND LEVEL 2 PER SECTION 7.3.1.5 OF NFPA 101.
2. FOR MOUNTING LOCATIONS OF EXIT SIGNS AT EXIT DOORS,
SEE GI1.1.2. FOR CEILING MOUNTED EXIT SIGNS, CENTER IN
CORRIDOR, TYPICAL.
3. SEE GI0.2.1 FOR PROJECT INFORMATION
EXIT SIGN
FIRE EXTINGUISHER CABINET (FEC)
FEC
EXISTING 1 HR FIRE RESISTIVE
RATED PARTITION
GRAPHIC SCALE:
0'
1/8" = 1'-0"
8' 8' 16'
3801 Miranda Ave., Palo Alto CA
CENTERS FOR AMBULATORY CARE,
POLYTRAUMA AND BLIND REHABILITATION
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management
Seals and Signatures on e e igh th inc h = on e f oo t
B
A
C
D
E
F thr ee in ch es on e f oo t
6"
6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t
6" 6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
301 BATTERY STREET, 7TH FLOOR
SAN FRANCISCO, CA 94111
T 415.227.0100 F 415.908.0862 www.smithgroup.com
The Design Partnership LLP Architects + Planners
1412 VAN NESS AVE., 2ND FLOOR
SAN FRANCISCO, CA 94109
T 415.777.3737 F 415.777.3476 www.dpsf.com
SHEET NOTES
Associate Architect:
Department of Veterans Affairs
PR
IN
TE
D
ON
TRUE NORTH
PROJ NORTH
5/
/2
7:
:0
PM LIFE SAFETY DIAGRAM LEVEL 2
A0.2.2
DO NW10 MAY 2013
640-424
Recreation Services
SCALE: 1/8" = 1'-0"54 LIFE SAFETY DIAGRAM LEVEL 2
1 ASI # 01 05/16/2014
eaquino Rectangle eaquino Typewritten Text
AS-BUILT
eaquino Typewritten Text Halbert Const. Co., Inc.
eaquino Typewritten Text
D SD SD SD SD SD SD SD SD SD SD SD SD SD
ALIGN
AL
IG
N
1. CONTRACTOR SHALL VERIFY ALL EXISTING CONSTRUCTION
RELATED CONDITIONS PRIOR TO STARTING DEMOLITION AND NEW
CONSTRUCTION.
2. THE INFORMATION LISTED BY THE DEMOLITION KEYNOTES ARE NOT
INTENDED TO INCLUDE EVERY ITEM FOR DEMOLITION AND NEW
CONSTRUCTION. REFER TO AS-BUILT DRAWINGS OF EXISTING
ADJACENT AQUATIC THERAPY PROJECT FOR ADDITIONAL
INFORMATION.
3. SEE CIVIL, STRUCTURAL AND ELECTRICAL DRAWINGS FOR MORE
INFORMATION CONCERNING NEW CONSTRUCTION IN THIS AREA
4. ALL OPENINGS AND VOIDS LEFT BY THE REMOVAL OF EXISTING
CONSTRUCTION, EQUIPMENT, ETC. SHALL BE PROPERLY PATCHED
TO MATCH EXISTING CONDITIONS.
5. PROTECT FROM DAMAGE MATERIALS THAT ARE INDICATED TO
REMAIN. ANY MATERIAL DAMAGED DURING REMOVAL SHALL BE
REPAIRED OR REPLACED BY CONTRACTOR. PATCH TO MATCH
ADJACENT FINISHES.
6. PORTIONS OF WALLS, FLOORS AND CEILINGS THAT ARE REMOVED
FOR NEW CONSTRUCTION OF MECHANICAL AND ELECTRICAL
COMPONENTS SHALL BE REPLACED OR PATCHED TO MATCH
EXISTING CONSTRUCTION
7. THE CONTRACTOR IS RESPONSIBLE FOR THE SAFE OFFSITE
REMOVAL AND DISPOSAL OF ALL DEMOLISHED MATERIALS.
8. PRIOR TO BEGINNING DEMOLITION WORK, TRACE AND IDENTIFY
EXISTING UNDERGROUND UTILITIES WITHIN AND PASSING BELOW
THE AREA OF WORK.
9. MAINTAIN CODE COMPLIANT EXITING DURING DEMOLITION. PROVIDE
TEMPORARY SIGNAGE. MAINTAIN EMERGENCY LIGHTING AND FIRE
ALARM AND SUPPRESSION SYSTEMS
10. PROVIDE CONSTRUCTION BARRIERS TO ALLOW FOR ACCESS,
EGRESS AND CONTAIN CONSTRUCTION DUST AND DEBRIS.
11. AT PRE-CONSTRUCTION CONFERENCE FOR WATERPROOFING:
CONTRACTOR AND MANUFACTURER’S REPRESENTATIVE TO EXAMINE
EXISTING CONDITIONS, CONFIRM CONFORMANCE WITH AS-BUILT
DRAWINGS, BRING DISCREPANCIES TO ATTENTION OF RESIDENT
ENGINEER, AND VERIFY COMPATIBILITY OF NEW WATERPROOFING
SYSTEM WITH EXISTING TO MAINTAIN INTEGRITY OF THE
WATERPROOFING SYSTEM AND APPLICABLE WARRANTY
12. CONTRACTOR SHALL SEAL THE MECHANICAL DIFFUSERS SERVING
THE AREA OF WORK IN THE (E) LOBBY DURING DEMOLITION AND NEW
CONSTRUCTION, IN ORDER TO COMPLETELY STOP THE MOVEMENT
OF SYSTEM AIR. CONTRACTOR TO REQUEST INFORMATION ABOUT (E)
BUILDING MECHANICAL SYSTEMS FROM THE RESIDENT ENGINEER
AND USE THIS INFORMATION FOR PROPER BLOCKAGE OF THE
AFFECTED DIFFUSERS WITHOUT NEGATIVELY IMPACTING THE
OPERATION OF THE ENTIRE MECHANICAL SYSTEM. DIFFUSERS
SHALL BE PROPERLY SEALED TO PREVENT DUST CREATED FROM
CONSTRUCTION ACTIVITIES ENTERING INTO THE BUILDING
MECHANICAL SYSTEM. PROVIDE TEMPORARY VENTILATION SYSTEM
SUFFICIENT TO EXHAUST THE DEBRIS AND DUST CREATED BY
CONSTRUCTION ACTIVITIES FROM THE AREA OF THE WORK TO THE
OUTSIDE. RESTORE (E) VENTILATION SYSTEM UPON COMPLETION OF
ALL CONSTRUCTION ACTIVITIES.
1 2 3
F
1.1
AD1.1.1
AD1.1.1
1.09
1.02
1.09
1.27
1.32
1.29
1.28
1.16
1.26
1.04
1.01
1.7 2.2
(E)E
1.06
5'- 0"
M
IN
C
LR
5'
- 3
/2
0Q6-
1.59
1.66 1.67
5'-0 " M
IN CLR
5' - 1 7
/16
1.68
1.2
1.26
LEVEL 1
0"
LEVEL 2
14' - 0"
ROOF
28' - 0"
1 2 31.1 51
AD1.1.1
AD1.1.2
AD1.1.2
1.02
1.04
1.08
1.05
1.7 2.2
1.24
1.26
AD1.1.2
/4 " V
IF
TYP
TYP
AD1.1.2
NOTE MAXIMUM OPENING
FOR MATERIAL ACCESS
(+/-) VIF
7' - 4"
V
IF
1/
2"
1.611.61
1.2
1.151.60
1.26
LEVEL 1
0"
LEVEL 2
14' - 0"
ROOF
28' - 0"
F 42
AD1.1.1
1.06
1.04
1.05
1.06
1.08
1.02
1.09
1.26
(E)E
AD1.1.2
1.24
/4 " V
IF
/4 " V
IF
AD1.1.2
1.19
1.18
1.17
1.30
1 2 3
F
1.1
AD1.1.1
AD1.1.11.7 2.2
(E)E
1.04
1.05
1.05
1.26
1.62
1.63
1.65
1.64
1.2
1.19
1.18
1.17
1.17 FLOORING TO BE REMOVED
EXISTING TO BE REMOVED
DEMOLITION LEGEND
GRAPHIC SCALE:
4' 0' 4' 8'
1/4" = 1'-0"
3801 Miranda Ave., Palo Alto CA
CENTERS FOR AMBULATORY CARE,
POLYTRAUMA AND BLIND REHABILITATION
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management
Seals and Signatures on e e igh th inc h = on e f oo t
B
A
C
D
E
F thr ee in ch es on e f oo t
6"
6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t
6" 6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
301 BATTERY STREET, 7TH FLOOR
SAN FRANCISCO, CA 94111
T 415.227.0100 F 415.908.0862 www.smithgroup.com
The Design Partnership LLP Architects + Planners
1412 VAN NESS AVE., 2ND FLOOR
SAN FRANCISCO, CA 94109
T 415.777.3737 F 415.777.3476 www.dpsf.com
SHEET NOTES
KEYNOTES
Associate Architect:
Department of Veterans Affairs
PR
IN
TE
D
ON
TRUE NORTH
PROJ NORTH
8/
/2
5:
:1
PM DEMOLITION PLAN AND ELEVATIONS
AT EXISTING LEVEL 1 LOBBY 101
AD1.1.1
DO RM10 MAY 2013
640-424
Recreation Services
1.01 (E) BUILDING 530 AQUATIC SERVICES
1.02 DEMOLISH (E) SLAB AS REQUIRED FOR INSTALLATION OF LOBBY
STAIR 1. SEE STRUCTURAL DWGS FOR INFILL AND REPAIR TO MATCH
(E). SEE AE6.1.1 AND AE6.1.4. EXTENTS SHOWN HATCHED
1.04 DEMOLISH (E) CURTAIN WALL
1.05 DEMOLISH (E) ALUMINUM COMPOSITE BEAM COVER, (E) BEAM TO
REMAIN
1.06 DEMOLISH (E) CLADDING PANELS
1.08 DEMOLISH (E) CONCRETE CURB TO BELOW FINISH FLOOR.
COORDINATE WITH NEW FLOOR FINISH.
1.09 DEMOLISH (E) FLOOR FINISH. EXTENTS SHOWN HATCHED
1.15 COVER AND PROTECT EXISTING FINISHES TO REMAIN
1.16 EXTENT OF CANOPY ABOVE
1.17 (E) CEILING SYSTEM. GYP BD AND METAL STUDS. TYPE A.
1.18 (E) CEILING SYSTEM. ACOUSTICAL TILE. TYPE B.
1.19 (E) CEILING SYSTEM. SUSPENDED ACOUSTICAL PANEL. TYPE C.
1.24 OVEREXCAVATE TO ALLOW FOR CONTINUATION OF BELOW-GRADE
WATERPROOFING SYSTEM. PROTECT (E) PROTECTION BOARD AND
MEMBRANE FOR (N) WORK.
1.26 BARRICADE AFFECTED AREA DURING CONSTRUCTION
1.27 (E) STORM DRAIN LINE BELOW. PROTECT DURING CONSTRUCTION.
SEE CIVIL DWGS.
1.28 DEMOLISH (E) WALK-OFF MAT.
1.29 (E) EXIT DOORS. MAINTAIN OPERABILITY DURING CONSTRUCTION
1.30 EXISTING HVAC TO REMAIN
1.32 OPEN AND LOCK (E) ENTRY DOORS AND PROTECT OPENING FOR USE
AS CONSTRUCTION ENTRY. PROVIDE TEMPORARY CONTRACTORS
DOOR IN BARRICADE, ALIGNED TO (E) OPENING. RESTORE TO
OPERATION AT COMPLETION OF LOBBY CONSTRUCTION. REPAIR AND
REPLACE ANY DAMAGE TO MATCH EXISTING.
1.59 (E) BRACED FRAME AND FOOTING TO REMAIN
1.60 (E) STEEL AND ALUMINUM CANOPY
1.61 DISCONNECT AND REMOVE (E) ELECTRICAL FIXTURES
1.62 MAINTAIN OPERATION OF (E) FIRE SPRINKLER HEADS
1.63 MAINTAIN OPERATION OF (E) CONCEALED SPRINKLER HEADS
1.64 MAINTAIN OPERATION OF (E) MECHANICAL DIFFUSERS
1.65 MAINTAIN OPERATION OF (E) CONCEALED MECHANICAL DIFFUSERS
1.66 MAINTAIN OPERATION OF (E) PULL BOX
1.67 (E) FIRE ALARM CONTROL PANEL. SEE FIRE ALARM DRAWING FA3.1.1
1.68 (E) BENCH
SCALE: 1/4" = 1'-0"30 DEMOLITION PLAN (E) LEVEL 1 LOBBY 101
SCALE: 1/4" = 1'-0"42 DEMOLITION SECTION (E) INTERIOR LOBBY 101 NORTH
SCALE: 1/4" = 1'-0"51 DEMOLITION SECTION (E) INTERIOR LOBBY 101 EAST
SCALE: 1/4" = 1'-0"54 DEMOLITION RCP (E) LEVEL 1 LOBBY 101
DEMOLITION SEQUENCING
1. ERECT TEMPORARY PARTITION BARRICADE. SEE AD1.1.2
2. INSTALL TEMPORARY PROTECTION SHEETING UNDER (E) FINISH
CEILINGS
3. PROTECT (E) MECHANICAL DIFFUSERS AND ASSOCIATED DUCTING
FROM DAMAGE DURING DEMOLITION AND NEW CONSTRUCTION
4. MAINTAIN OPERATION OF (E) FIRE SPRINKLER HEADS AND
ASSOCIATED FIRE ALARM PULL BOXES
5. DISCONNECT AND REMOVE (E) WALL MOUNTED ELECTRICAL
FIXTURES
6. DEMOLISH (E) CURTAINWALL.
7. DEMOLISH ALUMINUM CLADDING PANELS AROUND (E) BEAM
8. DEMOLISH (E) CONCRETE CURB BELOW CURTAINWALL
9. REMOVE (E) INTERIOR WALL CLADDING PANELS AND WALL BASES
10. DEMOLISH (E) FINISH FLOOR TILES AND CONCRETE SLAB ON GRADE
11. PROVIDE TEMPORARY EXIT SIGNAGE
eaquino Rectangle eaquino Typewritten Text Halbert Const. Co., Inc.
eaquino Typewritten Text
AS-BUILT
eaquino Typewritten Text eaquino Typewritten Text
LEVEL 1
0"
EXISTING ALUMINUM AND GLASS
CURTAINWALL SYSTEM TO REMAIN
EXISTING FLASHING TO REMAIN
EXISTING WATERPROOFING TO REMAIN
EXISTING FOOTING TO REMAIN
EXISTING CONCRETE MOW STRIP
WHERE OCCURS AND ADJACENT
GRADE TO REMAIN
REMOVE EXISTING STONE
TILE FINISH FLOOR
MATERIAL AND STOCKPILE
FOR RE-INSTALLATION
TEMPORARY CONSTRUCTION
PARTITION- 6" METAL STUDS, 16
GA, 16" O.C. W/ 3/4" PLYWOOD
MAINTAIN (E) UNDERSLAB
VAPOR BARRIER. REPLACE
WITH NEW VAPOR BARRIER
FOLLOWING SLAB
DEMOLITION
3/8" DIA EXPANSION
ANCHOR W/ 2" MIN
EMBEDMENT INTO (E) SLAB EXISTING PORTION OF SLAB ON GRADE
TO REMAIN
LEVEL 1
0"
1.7
TEMPORARY CONSTRUCTION
PARTITION- 6" METAL STUDS, 16 GA,
16" O.C. W/ 5/8" GYP. BD. PAINTED.
SEAL W/ POLYPROPYLENE SHEET
TO RESTRICT CONSTRUCTION DUST
IN NON-CONSTRUCTION AREA
EXISTING FINISH FLOOR TO REMAIN
EXISTING SLAB ON GRADE
TO REMAIN
MAINTAIN EXISTING
WATERPROOFING MEMBRANE
REMOVE EXISTING STONE TILE FINISH
FLOOR MATERIAL ALONG TILE JOINTS
AND STOCKPILE FOR RE-INSTALLATION
DEMOLISH EXISTING MORTAR
AND SLAB ON GRADE
VERIFY (E) FLOOR LEVELVI
F3"
3/8" DIA EXPANSION ANCHOR W/ 2"
EMBEDMENT AT 2'-0" OC
94' - 0"
TWO ROWS 16P NAILS AT 24" OC
TWO LAYERS OF 3/4" PLYWOOD,
MIN. STAPLE LAYERS TOGETHER
AT 2'-0" OC, MAX.
VARIES, SEE PLAN
(E)E
EXISTING HORIZONTAL RAINSCREEN PANEL
SYSTEM TO REMAIN
EXISTING INSULATION TO REMAIN
EXISTING FLASHING MEMBRANES TO
REMAIN
REMOVE EXISTING RAINSCREEN PANELS
REMOVE EXISTING RIGID INSULATION.
COORD WITH (N) SEISMIC EXPANSION JOINT.
SEE AE5.1.2
EXISTING STUD FRAMING TO REMAIN
1. CONTRACTOR SHALL VERIFY ALL EXISTING CONSTRUCTION
RELATED CONDITIONS PRIOR TO STARTING DEMOLITION AND NEW
CONSTRUCTION.
2. THE INFORMATION LISTED BY THE DEMOLITION KEYNOTES ARE NOT
INTENDED TO INCLUDE EVERY ITEM FOR DEMOLITION AND NEW
CONSTRUCTION. REFER TO AS-BUILT DRAWINGS OF EXISTING
ADJACENT AQUATIC THERAPY PROJECT FOR ADDITIONAL
INFORMATION.
3. SEE CIVIL, STRUCTURAL AND ELECTRICAL DRAWINGS FOR MORE
INFORMATION CONCERNING NEW CONSTRUCTION IN THIS AREA
4. ALL OPENINGS AND VOIDS LEFT BY THE REMOVAL OF EXISTING
CONSTRUCTION, EQUIPMENT, ETC. SHALL BE PROPERLY PATCHED
TO MATCH EXISTING CONDITIONS.
5. PROTECT FROM DAMAGE MATERIALS THAT ARE INDICATED TO
REMAIN. ANY MATERIAL DAMAGED DURING REMOVAL SHALL BE
REPAIRED OR REPLACED BY CONTRACTOR. PATCH TO MATCH
ADJACENT FINISHES.
6. PORTIONS OF WALLS, FLOORS AND CEILINGS THAT ARE REMOVED
FOR NEW CONSTRUCTION OF MECHANICAL AND ELECTRICAL
COMPONENTS SHALL BE REPLACED OR PATCHED TO MATCH
EXISTING CONSTRUCTION
7. THE CONTRACTOR IS RESPONSIBLE FOR THE SAFE OFFSITE
REMOVAL AND DISPOSAL OF ALL DEMOLISHED MATERIALS.
8. PRIOR TO BEGINNING DEMOLITION WORK, TRACE AND IDENTIFY
EXISTING UNDERGROUND UTILITIES WITHIN AND PASSING BELOW
THE AREA OF WORK.
9. MAINTAIN CODE COMPLIANT EXITING DURING DEMOLITION. PROVIDE
TEMPORARY SIGNAGE. MAINTAIN EMERGENCY LIGHTING AND FIRE
ALARM AND SUPPRESSION SYSTEMS
10. PROVIDE CONSTRUCTION BARRIERS TO ALLOW FOR ACCESS,
EGRESS AND CONTAIN CONSTRUCTION DUST AND DEBRIS.
11. AT PRE-CONSTRUCTION CONFERENCE FOR WATERPROOFING:
CONTRACTOR AND MANUFACTURER’S REPRESENTATIVE TO EXAMINE
EXISTING CONDITIONS, CONFIRM CONFORMANCE WITH AS-BUILT
DRAWINGS, BRING DISCREPANCIES TO ATTENTION OF RESIDENT
ENGINEER, AND VERIFY COMPATIBILITY OF NEW WATERPROOFING
SYSTEM WITH EXISTING TO MAINTAIN INTEGRITY OF THE
WATERPROOFING SYSTEM AND APPLICABLE WARRANTY
12. CONTRACTOR SHALL SEAL THE MECHANICAL DIFFUSERS SERVING
THE AREA OF WORK IN THE (E) LOBBY DURING DEMOLITION AND NEW
CONSTRUCTION, IN ORDER TO COMPLETELY STOP THE MOVEMENT
OF SYSTEM AIR. CONTRACTOR TO REQUEST INFORMATION ABOUT (E)
BUILDING MECHANICAL SYSTEMS FROM THE RESIDENT ENGINEER
AND USE THIS INFORMATION FOR PROPER BLOCKAGE OF THE
AFFECTED DIFFUSERS WITHOUT NEGATIVELY IMPACTING THE
OPERATION OF THE ENTIRE MECHANICAL SYSTEM. DIFFUSERS
SHALL BE PROPERLY SEALED TO PREVENT DUST CREATED FROM
CONSTRUCTION ACTIVITIES ENTERING INTO THE BUILDING
MECHANICAL SYSTEM. PROVIDE TEMPORARY VENTILATION SYSTEM
SUFFICIENT TO EXHAUST THE DEBRIS AND DUST CREATED BY
CONSTRUCTION ACTIVITIES FROM THE AREA OF THE WORK TO THE
OUTSIDE. RESTORE (E) VENTILATION SYSTEM UPON COMPLETION OF
ALL CONSTRUCTION ACTIVITIES.
LEVEL 1
0"
LEVEL 2
14' - 0"
ROOF
28' - 0"
123 1.151
AD1.1.1
1.06
1.04
1.38 1.38
1.07
1.07
1.07
1.72.2
VERIFY (E) FLR LEVEL
VERIFY (E) FLR LEVEL
VERIFY (E) LEVEL
1.59
1.59
1.60
1.2
ROOF
28' - 0"
1.7
TEMPORARY CONSTRUCTION BARRIER- 6"
METAL STUDS, 16 GA, 16" O.C. W/ 5/8" GYP. BD.
PAINTED. PROVIDE COMPENSATION TRACK AS
REQUIRED
(E) METAL STUD FRAMED CEILING
SOFFIT SYSTEM TYPE A TO REMAIN
PROTECT (E) CEILING FINISH. RESTORE TO (E)
CONDITION WHEN REMOVING BARRICADE
PROTECT (E) ELECTRICAL FIXTURES DURING
DEMO AND NEW CONSTRUCTION
(E) SUSPENDED CEILING
SYSTEM TYPE B TO REMAIN
TEMPORARY CONSTRUCTION BARRIER-
6" METAL STUDS, 16 GA, 16" O.C. W/ 3/4"
PLYWOOD
(E) METAL STUD FRAMED
CEILING SOFFIT SYSTEM
TYPE A TO REMAIN
PROTECT (E) CEILING FINISH. RESTORE
TO (E) CONDITION WHEN REMOVING
BARRICADE
EXISTING ALUMINUM AND GLASS
CURTAINWALL SYSTEM TO REMAIN
TEMPORARY CONSTRUCTION
BARRIER- 6" METAL STUDS, 16 GA,
16" O.C. W/ 5/8" GYP. BD. PAINTED.
(E) SUSPENDED CEILING
SYSTEM TYPE C TO REMAIN
3/4" PLYWD TO PROTECT (E)
CEILING FINISH. PATCH AND
PAINT TO RESTORE TO (E)
CONDITION WHEN REMOVING
BARRICADE
(E) METAL STUD AND GYP BD
SOFFIT SYSTEM TYPE A TO
REMAIN
(E) SUSPENDED CEILING
SYSTEM TYPE B
SCREW FASTEN TEMP METAL
STUD FRAMING INTO (E)
SOFFIT FRAMING
30°
3801 Miranda Ave., Palo Alto CA
CENTERS FOR AMBULATORY CARE,
POLYTRAUMA AND BLIND REHABILITATION
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management
Seals and Signatures on e e igh th inc h = on e f oo t
B
A
C
D
E
F thr ee in ch es on e f oo t
6"
6" on e a nd on e h alf in ch es on e f oo t on e i nc h = on e f oo t
6" 6" thr ee qu ar ter s i nc h = on e f oo t on e h alf in ch on e f oo t thr ee ei gh ths in ch on e f oo t on e q ua rte r in ch on e f oo t
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
301 BATTERY STREET, 7TH FLOOR
SAN FRANCISCO, CA 94111
T 415.227.0100 F 415.908.0862 www.smithgroup.com
The Design Partnership LLP Architects + Planners
1412 VAN NESS AVE., 2ND FLOOR
SAN FRANCISCO, CA 94109
T 415.777.3737 F 415.777.3476 www.dpsf.com
SHEET NOTES
KEYNOTES
Associate Architect:
Department of Veterans Affairs
PR
IN
TE
D
ON
:8
/7 /2
2:
:2
PM DEMOLITION WALL SECTIONS AND
DETAILS
AD1.1.2
DO RM10 MAY 2013
640-424
Recreation Services
SCALE: 1 1/2" = 1'-0"42 DEMOLITION AT (E) FOOTING
SCALE: 1 1/2" = 1'-0"54 DEMOLITION AT (E) SLAB ON GRADE
SCALE: 1 1/2" = 1'-0"38 DEMOLITION AT (E) PARAPET
1.04 DEMOLISH (E) CURTAIN WALL
1.06 DEMOLISH (E) CLADDING PANELS
1.07 REMOVE (E) CLADDING PANELS SHADED AND RESERVE FOR
This is the start of the file's text. The full file is on GovTribe.