13 - Fire Alarm.pdf
PDF 8 MB Posted
- Solicitation number
- 36C26126R0007
About this file
These documents are fire alarm system design drawings for the Centers for Ambulatory Care, Polytrauma and Blind Rehabilitation Recreation Services Building 530 at 3801 Miranda Ave, Palo Alto, CA. The comprehensive set of drawings details a fully sprinklered fire alarm system installation across multiple building levels, including basement, level 1, level 2, and roof. The system utilizes a Notifier NFS2-640 addressable fire alarm control panel with digital audio amplifiers, network control annunciators, and includes specific programming requirements for monitoring fire alarm devices in both the Recreation Services and Aquatic Therapy buildings. Key components include smoke detectors, heat detectors, manual pull stations, strobes, speakers, and relay modules, with intricate wiring diagrams specifying device interconnections, voltage drop calculations, and battery backup requirements. The design also includes provisions for elevator recall, HVAC shutdown, and campus-wide fire alarm network integration with Building 100's fire alarm node.
View the file
Other files
| File | Type | Posted |
|---|---|---|
| 36C26126R0007 0001.pdf | ||
| 7 - Equipment.pdf | ||
| 15 - Existing Gymnasium Floor Detail.pdf | ||
| Supplemental Price Breakdown by Division Sheet.docx | DOCX document | |
| REQUEST FOR INFORMATION FORM.docx | DOCX document | |
| 9 - Plumbing.pdf | ||
| 8 - Mechanical.pdf | ||
| 2 - Civil.pdf | ||
| 4 - Structural.pdf | ||
| 16 - Existing Elkay two level.pdf | ||
| 12 - 2 - Electrical.pdf | ||
| 14 - Bleachers.pdf | ||
| 640-26-112 SPECS.pdf | ||
| 5 - Architectural.pdf | ||
| 1 - General.pdf | ||
| 36C26126R0007 Replace Gymnasium Flooring.docx | DOCX document |
Show all 16
On GovTribe
Work with this file
- Download the original file
- Contacts named in this file
- Similar government files
- Ask GovTribe AI about this file
Text version
JJ
IR
EOL
RM
MM
DM
SMOKE DETECTOR (AREA)
IN
D
IC
AT
E A
LA
R
M A
T
AL
L
SP
E
AK
ER
S
A N
D S
TR
O
BE
S
IN
D
IC
AT
E
SU
PE
R
VI
SO
R Y
AT
F
AC
P
AN
D
R
EM
O
TE
AN
N
U N
C
IA
TO
R
IN
D
IC
AT
E
TR
O U
BL
E
AT
F
AC
P
AN
D
R
EM
O
TE
AN
N
U N
C
IA
TO
R
R
EP
O R
T
AL
AR
M
T O
4H
R M
AN
N
ED
M
O N
IT
O
R
IN
G
ST
AT
IO
N
R
EP
O R
T
TR
O U
BL
E
TO
4H R
M
AN
N
ED
M O
N
IT
O R
IN
G
S
TA
TI
O
N
N O
TI
FY
F
IR
E D
EP
AR
TM
EN
T
C
LO
SE
A
SS
O
C
IA
TE
D
S M
O
KE
B
AR
R
IE
R D
O O
R S
O N
FL
O
O R
SH
U
T D
O W
N A
SS
O
C
IA
TE
D
H
VA
C U
N
IT
C
LO
S E
FI
R
E S
M O
KE
D
AM
PE
R
IN
D
IC
AT
E
SU
PE
R
VI
SO
R Y
SI
G
N
AL
T O
4H
R M
AN
N
ED
M
O N
IT
O
R
IN
G S
TA
TI
O N
ACTION
DEVICE
SMOKE DETECTOR (DOOR RELEASE)
IN
D
IC
AT
E
AL
AR
M
A T
FA
C
P
AN
D R
EM
O
TE
AN
N U
N C
IA
TO
R
R
EC
AL
L
EL
EV
AT
O
R T
O E
XI
TI
N G
F
LO
O R
AN
N
U N
C
IA
TE
S
O
LI
D
IL
LU
M
IN
AT
IO
N
IN
SI
D E
EL
EV
AT
O
R C
AB
AN
N
U N
C
IA
TE
F
LA
SH
IN
G
IL
LU
M
IN
AT
IO
N
IN
SI
D
E
EL
EV
AT
O R
C
AB
DUCT SMOKE DETECTOR AT FIRE SMOKE DAMPER
HVAC UNIT DUCT SMOKE DETECTOR SUPPLY AND/OR RETURN
BREAK IN SIGNALING LINE CIRCUIT
BREAK IN NOTIFICATION APPLIANCE CIRCUIT
GROUND IN SIGNALING LINE CIRCUIT
GROUND IN NOTIFICATION APPLIANCE CIRCUIT
WIRE TO WIRE SHORT IN SIGNALING LINE CIRCUIT
WIRE TO WIRE SHORT IN NOTIFICATION APPLIANCE CIRCUIT
MONITOR MODULE (SPRINKLER WATER FLOW SWITCH)
MONITOR MODULE (SPRINKLER VALVE TAMPER)
SMOKE DETECTOR (ELEVATOR MACHINE ROOM)
MANUAL PULL STATION
HEAT DETECTOR (ELEVATOR MACHINE ROOM)
IN
IT
IA
TE
E
LE
VA
TO
R S
H U
TD
O
W N
A N
D D
IS
C
O N
N
EC
T
EL
EV
AT
O R
P O
W
ER
SMOKE DETECTOR (ELEVATOR LOBBY)
MONITOR MODULE (LOSS OF POWER TO ELEV SHUNT TRIP CIRCUIT)
DH
DAA
FCPS
FATC
FACP
FS
HD
X X X
X
X X
X
X X
SEE NOTES:
#1, #2, #3, #5, #8, #9, #10, #12, #14, #16, #17
LEVEL B
SPECIFIC REMARKS
RELAY
MODULE (RM)VISUAL (V)
STROBEMANUALDUCT
DETECTOR (DD)(S)
FLOOR
CLG. SMOKE
STATION (M)
1.
2.
3.
PROVIDE COMPLETE FIRE ALARM SYSTEM PROGRAMMING AS REQUIRED TO ACTIVATE ALL DEVICES AND FUNCTIONS AS SHOWN ON PLANS.
VERIFY PROGRAMMING DESCRIPTION FOR ALL DEVICES WITH THE RESIDENT ENGINEER. SUBMIT COMPLETE PROGRAMMING SCHEDULE AND DESCRIPTIONS PRIOR TO PROGRAMMING NEW DEVICES INTO
SYSTEM.
PROGRAM INITIATING DEVICES, SUCH AS SMOKE DETECTORS, MANUAL PULL STATIONS, MONITOR MODULE (FOR WATER FLOW SWITCH) TO INITIATE NOTIFICATION DEVICES AND TO SEND AN ALARM TO THE
FACP AND 24 HOUR MANNED STATIONS.
NOTES RE: FIRE ALARM MATRIX OF OPERATIONS &
FIRE ALARM SYSTEM DEVICE SCHEDULE
LEVEL 1
FIRE ALARM SYSTEM DEVICE SCHEDULE
FIRE ALARM MATRIX OF OPERATIONS
MODEL, P/NDESCTRIPTION REMARKS
FIRE ALARM SYSTEM LEGEND SYMBOLS
ABBREV./
SYMBOL BACKBOX EQUIPMENT
DIGITAL AUDIO AMPLIFIER WITH POWER SUPPLY
BOARD AND CHASSIS.
ADDRESSABLE RELAY MODULE
DAA-5070
8.0 AMP REMOTE POWER SUPPLY WITH BUILT-IN
SYNC
FCPS-24S8
FRM-1
ADDRESSABLE SMOKE DETECTOR, CEILING
MOUNTED, PHOTOELECTRIC TYPE WITH
STANDARD MOUNTING BASE
FSP-851
B210LP
MAGNETIC DOOR HOLDER DEVICE
STROBE, WALL MOUNT
WATER FLOW SWITCH
ADDRESSABLE MANUAL PULL STATION, DUAL
ACTION WITH KEY LOCKING FEATURE.
DUCT DETECTOR REMOTE KEY TEST AND
ANNUNCIATOR STATION.
NBG-12LX
RST151 KEY
NOTIFIER
NOTIFIER
NOTIFIER
NOTIFIER
HVAC DUCT SMOKE DETECTOR AND HOUSING DNR
FSP-851
FSP-851R
NOTIFIER
VALVE TAMPER SWITCH
LOCATE IN #EQDR-D4 ENCLOSURE. NOTIFIER
PROVIDE TYPE PER MFR RQMT. FLUSH MOUNT BACKBOX AT
FINISHED SPACES, OTHERWISE SURFACE MOUNT WHERE
LOCATED IN CEILING SPACE, UTILITY SPACES AND OUTDOORS.
PROVIDE WITH WEATHERPROOF BACKBOX WHERE LOCATED IN
AN OUTDOOR ENVIRONMENT.
4"SQx21/8"D - FLUSH MOUNT BACKBOX. SURFACE MOUNT IS ONLY
ACCEPTABLE IN UTILITY SPACES. PROVIDE BACKBOX TYPE PER
MFR REQUIREMENTS.
SEE MANUFACTURER REQUIREMENTS.
SYSTEM SENSOR
SB-1
THRU
SB-10
ROOF
LEVEL
RELAY MODULES (RM2-5, RM1-10) SHALL DEACTIVATE DOOR HOLDERS WHEN MANUAL PULL STATIONS, WATERFLOW SWITCH, HEAT DETECTOR AND SMOKE DETECTORS ARE IN ALARM.
DUAL MONITOR
MODULE (DM)
SEE NOTES:
#1, #2, #3, #11, #13, #16, #17
4.
5. PROGRAM MONITOR MODULE (FOR VALVE TAMPER) TO SIGNAL A SUPERVISORY TO THE MAIN FACP AND 24 HOUR MANNED STATIONS.
ADDRESSABLE SINGLE MONITOR MODULE FMM-1 NOTIFIER
N/A
N/A PROVIDE MONITOR MODULE. COORDINATE WORK WITH DIVISION
21.
PROVIDE MONITOR MODULE. COORDINATE WORK WITH DIVISION
21.
ADDRESSABLE DUAL MONITOR MODULE FDM-1 UTILIZE FOR NEW VALVE TAMPER AND NEW WATER FLOW
SWITCHES. COORDINATE CONNECTIONS WITH DIVISION 21.
NOTIFIER
SR 4"SQx21/8"D - FLUSH MOUNT BACKBOX. SURFACE MOUNT IS ONLY
ACCEPTABLE IN UTILITY SPACES. PROVIDE BACKBOX TYPE PER
MFR REQUIREMENTS.
PROVIDE WEATHERPROOF TYPE, #DNRW WHERE LOCATED
OUTDOORS. PROVIDE SAMPLING TUBE TO SUIT DUCT WIDTH.
INCLUDE ACCESSORIES REQUIRED FOR COMPLETE
INSTALLATION. PROVIDE #FSP-851R WHERE CONTROLLED BY
REMOTE TEST SWITCH.
PROVIDE EACH DIGITAL AUDIO AMPLIFIER WITH BATTERY
CHASSIS AND TWO 12.0AH BATTERIES.
FIRE ALARM ZONING/MONITORING
BUILDING 530 WILL CONSIST OF TWO BUILDING STRUCTURES - AQUATIC THERAPY AND RECREATIONAL SERVICES.
THE NEW FIRE ALARM PANEL FOR RECREATIONAL SERVICES WILL BECOME THE MAIN FIRE ALARM CONTROL PANEL FOR AQUATIC THERAPY AND RECREATION SERVICES. THE EXISTING FIRE ALARM PANEL IN
AQUATIC THERAPY WILL BE RETAINED TO MONITOR ONLY THE AQUATIC THERAPY BUILDING.
IN PROGRAMMING THE NEW FIRE ALARM PANEL IN RECREATION SERVICES, PROVIDE TWO FIRE ALARM ZONES. ONE FIRE ALARM ZONE SHALL MONITOR AND CONTROL FIRE ALARM DEVICES IN AQUATIC THERAPY WHILE THE OTHER FIRE ALARM ZONE SHALL MONITOR AND CONTROL FIRE ALARM DEVICES IN RECREATIONAL SERVICES. PROGRAM FIRE ALARM STROBES WITHIN THE LOBBY OF AQUATIC THERAPY
TO ALSO ACTIVATE UPON A FIRE ALARM EVENT IN THE RECREATION SERVICES BUILDING.
A NEW REMOTE ANNUNCIATOR PANEL FOR BUILDING 530 WILL BE PROVIDED AND LOCATED IN THE LOBBY OF AQUATIC THERAPY, AND WILL MONITOR THE TWO BUILDING STRUCTURES.
4"SQx21/8"D - FLUSH MOUNT BACKBOX. SURFACE MOUNT IS ONLY
ACCEPTABLE IN UTILITY SPACES. PROVIDE BACKBOX TYPE PER
MFR REQUIREMENTS.
MOUNT 7'-0"AFF, E.A.N.
PROVIDE MANUFACTURER SPECIFIED BACKBOX, FLUSH TYPE.
PROVIDE WITH WEATHERPROOF, SURFACE BACKBOX WHERE
LOCATED OUTDOORS.
ONLY LOCATE ON WALL WHERE INDICATED ON FIRE ALARM
PLANS.
PROVIDED IN ANOTHER DIVISION OF WORK. PROVIDE WIRING TO
CONNECT TO NEAREST 24VDC FIRE ALARM POWER SUPPLY,
U.O.N.
MFR
(NO SUBSTITUTIONS)
FIRE ALARM TERMINAL CABINET 24186 TCS
ADDRESSABLE CEILING MOUNTED HEAT
DETECTOR (57°C/135°F) RATE COMPENSATION
WITH DETECTOR BASE
FST-851
B210LP
PROVIDE WITH RED COLOR FINISH.SURFACE MOUNT TYPE. PROVIDE SIZE TO SUIT
INSTALLATION.
JUNCTION BOX - CEILING OR WALL MOUNT TYPE. _ PROVIDE WITH RED COLOR FINISH.PROVIDE WEATHERPROOF TYPE WHERE EXPOSED TO THE
OUTDOOR ENVIRONMENT. PROVIDE FLUSH TYPE WHERE
INSTALLED IN PUBLIC AREAS AND FINISHED SPACES.
FIRE ALARM CONTROL PANEL NFS2-640 ADDRESSABLE FIRE ALARM CONTROL PANEL. PROVIDE WITH
NCA-2 AND ASSOCIATED MOUNTING KIT.
PROVIDE ENCLOSURE SIZE TO ALLOW INSTALLATION OF
ANNUNCIATOR DISPLAY, DIGITAL VOICE
COMMUNICATION MODULE, DIGITAL AUDIO AMPLIFIERS
AND ASSOCIATED BATTERIES / COMPONENTS, POWER
SUPPLIES, ETC. FOR A COMPLETE AND OPERATIONAL
SYSTEM.
NOTIFIER
NOTIFIER
FIRE ALARM COMBINATION AUDIBLE/STROBE SPSR
SPSRH
4"SQx21/8"D - FLUSH MOUNT BACKBOX. SURFACE MOUNT IS ONLY
ACCEPTABLE IN UTILITY SPACES. PROVIDE BACKBOX TYPE PER
MFR REQUIREMENTS.
SYSTEM SENSOR
SPEAKER, WALL MOUNT. SPR
SPRV
SPRK
SPSRK
4"SQx21/8"D - FLUSH MOUNT BACKBOX. SURFACE MOUNT IS ONLY
ACCEPTABLE IN UTILITY SPACES. PROVIDE BACKBOX TYPE PER
MFR REQUIREMENTS. PROVIDE WEATHERPROOF TYPE WHERE
LOCATED IN AN OUTDOOR ENVIRONMENT.
SYSTEM SENSOR
LEVEL 2
6. RELAY MODULE (RM2-8) FOR SECURITY PANEL SHALL COMMUNICATE ALARM TO THE SECUIRTY ACCESS CONTROL SYSTEM.
7.
PROGRAM THE SMOKE DETECTORS AT THE ELEVATOR LOBBY OF LEVEL B AND IN THE ELEVATOR MACHINE ROOM TO ACTIVATE THE SUPERVISED CONTROL MODULE IN THE FIRE ALARM CONTROL PANEL TO
INITIATE ELEVATOR RECALL TO LEVEL 1 (ALTERNATE LEVEL RECALL).
8.
PROGRAM THE SMOKE DETECTOR AT ELEVATOR LOBBIES (EXCEPT AT THE DESIGNATED LEVEL RECALL) TO ACTIVATE THE SUPERVISED CONTROL MODULE IN THE FIRE ALARM CONTROL PANEL TO INITIATE
ELEVATOR RECALL TO LEVEL B (DESIGNATED LEVEL RECALL).
PROGRAM THE SMOKE DETECTOR IN THE ELEVATOR MACHINE ROOM TO ACTIVATE THE SUPERVISED CONTROL MODULE IN THE FIRE ALARM CONTROL PANEL TO INITIATE FLASHING OF THE FIRE FIGHTER'S HELMET SYMBOL IN THE ELEVATOR CAB. PROGRAM THE SMOKE DETECTOR IN THE ELEVATOR LOBBIES TO ACTIVATE THE SUPERVISED CONTROL MODULE IN THE FIRE ALARM CONTROL PANEL TO INITIATE
SOLID ILLUMINATION OF THE FIRE FIGHTER'S HELMET SYMBOL IN THE ELEVATOR CAB.
9.
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X X X X
X X
X X XXX
X X X
X X X
X
X
X
X
X
X
SPEAKER, CEILING MOUNT, SINGLE COIL TYPE,
70.7V, 8" DIAMETER
ATLAS SOUNDPROVIDE WITH COMPATIBLE UL APPROVED ENCLOSURE TO MEET
UL 1480 LISTING.
UKT70C-U51-8
PROVIDE TYPE PER MFR RQMT. FLUSH MOUNT BACKBOX AT
FINISHED SPACES, OTHERWISE SURFACE MOUNT WHERE
LOCATED IN CEILING SPACE, UTILITY SPACES AND OUTDOORS.
PROVIDE WITH WEATHERPROOF BACKBOX WHERE LOCATED IN
AN OUTDOOR ENVIRONMENT.
PROVIDE TYPE PER MFR RQMT. FLUSH MOUNT BACKBOX AT
FINISHED SPACES, OTHERWISE SURFACE MOUNT WHERE
LOCATED IN CEILING SPACE, UTILITY SPACES AND OUTDOORS.
PROVIDE WITH WEATHERPROOF BACKBOX WHERE LOCATED IN
AN OUTDOOR ENVIRONMENT.
X X X X
X
X
X
HEAT DETECTOR
(HD)
SPEAKER
(SP)
MONITOR
MODULE (MM)
SEE NOTES:
#1, #2, #3, #4, #5, #7, #9, #10, #11, #14, #15, #16, #17
SEE NOTES:
#1, #2, #3, #4, #5, #6, #7, #9, #11, #12, #14, #16, #17
S1-1 S1-2
S2-1
DDB-1
THRU
DDB-8
DD1-1
THRU
DD1-12
DD2-1
THRU
DD2-10
DDR-1
DDR-3
MB-1
THRU
MB-5
M1-1
THRU
M1-4
M2-1 M2-2
HDB-1 VB-1
THRU
VB-15
V1-1
THRU
V1-13
V2-1
THRU
V2-16
RMR--1
RMR-3
SPB-1
THRU
SPB-14
SP1-1
THRU
SP1-12
SP2-1
THRU
SP2-10
RMB-1
THRU
RMB-11
RM1-1
THRU
RM1-13
RM2-1
THRU
RM2-14
DMB-1
DMB-2
DM1-1
DM1-2
DM2-1
DM2-2
PROGRAM HEAT DETECTOR (HDB-1) TO ACTIVATE THE SUPERVISED CONTROL MODULE IN THE FIRE ALARM CONTROL PANEL TO DISCONNECT ELEVATOR POWER. SEE DETAIL 52 ON SHEET FA6.1.1.10.
PROGRAM DUCT DETECTORS (DD1-10, DD2-7, DD2-8) TO ACTIVATE ASSOCIATED RELAY MODULES TO CLOSE THE FIRE SMOKE DAMPER AND/OR ACTIVATE RELAY MODULE (RMR-2) TO SHUTDOWN THE RETURN FAN FOR AHU-1. PROGRAM DUCT DETECTOR (DDR-2) TO ACTIVATE RELAY MODULE (RMR-2 )TO SHUTDOWN THE RETURN FAN FOR AHU-1. COORDINATE ADDITIONAL REQUIREMENTS WITH DIVISION 23.
11.
RELAY MODULE (RMB-7, RM2-7, RM2-11) TO OVERRIDE OUTPUT OF AV/PAGING HEAD-END EQUIPMENT UPON FIRE ALARM.12.
PROGRAM DUCT DETECTORS (DDR-1, DDR3) TO ACTIVATE ASSOCIATED RELAY MODULES TO SHUTDOWN THE SUPPLY FAN.13.
PROGRAM DUCT DETECTORS TO ACTIVATE THE CLOSURE OF FIRE SMOKE DAMPERS UNLESS OTHERWISE NOTED.14.
4"SQx21/8"D - FLUSH MOUNT BACKBOX. SURFACE MOUNT IS ONLY
ACCEPTABLE IN UTILITY SPACES. PROVIDE BACKBOX TYPE PER
MFR REQUIREMENTS.
X
MMB-1
PROGRAM MONITOR MODULES (MM1-1, MM1-2) TO SIGNAL A SUPERVISORY TO THE MAIN FACP AND 24 HOUR MANNED STATIONS UPON LOSS OF POWER TO THE ELEVATOR SHUNT TRIP CIRCUIT. SEE DETAIL 52
ON SHEET FA6.1.1.
15.
X X
MM1-1
MM1-2
16.
INTERPOSING RELAY
PROVIDE PER MANUFACTURER REQUIREMENTS.
SEE SHEET FA6.1.1 FOR ADDITIONAL REQUIREMENTS.
END OF LINE RESISTOR
24 HOUR MANNED STATIONS - THE ADDRESSABLE FIRE ALARM SYSTEM SHALL TRANSMIT ALARM, SUPERVISORY, AND TROUBLE SIGNALS VIA NETWORK CABLING TO ANNUNCIATOR PANELS LOCATED AT BUILDING 100 (POLICE DISPATCH), BUILDING 40 (BOILER PLANT) AND BUILDING 41 (ENGINEERING).
PROVIDE COMPLETE FIRE ALARM PROGRAMMING AT BUILDING 100 MAIN FIRE ALARM CONTROL PANEL AND AT ALL 24 HOUR MANNED STATION TO MONITOR AND ACCEPT RECREATION SERVICES INTO THE
EXISTING FIRE ALARM CAMPUS NETWORK LOOP AS A PART OF BUILDING 530.
17.
X
X
X
X
NOTIFIER
R-20T(A) NOTIFIER/
HONEYWELL
MINIMIZE OR AVOID DISRUPTION TO FIRE ALARM SYSTEMS.
DELINEATE PHASING OF CONSTRUCTION TO ENSURE THE
INSTALLATION OF NEW SYSTEMS ARE EXPEDITED, AND MAINTAIN
EXISTING SYSTEMS IN SERVICE AS REQUIRED UNTIL THE SYSTEM
IS OPERATIONAL.
1.
INSTALLATION OF THE FIRE ALARM SYSTEM SHALL NOT
COMMENCE UNTIL DETAILED SHOP DRAWINGS AND REQUIRED
SUBMITTALS ARE PROVIDED BY THE CONTRACTOR AND
REVIEWED BY THE RESIDENT ENGINEER PER SPECIFICATIONS.
2.
INSTALLATION OF FIRE ALARM SYSTEM SHALL BE PERFORMED
BY A FACTORY TRAINED AUTHORIZED REPRESENTATIVE.
3.
A SET OF APPROVED FIRE ALARM SHOP DRAWINGS SHALL BE AT
THE JOB SITE AT ALL TIMES. ANY DEVIATION FROM THE
APPROVED PLANS, INCLUDING SUBSTITUTION OF COMPONENTS
AND/OR DEVICES, SHALL BE REVIEWED WITH AND APPROVED BY
THE RESIDENT ENGINEER PRIOR TO IMPLEMENTATION.
4.
5. DO NOT INSTALL SMOKE DETECTORS UNTIL AFTER THE
CONSTRUCTION CLEAN UP OF ALL TRADES IS COMPLETE AND
FINAL, EXCEPT WHEN SMOKE DETECTORS COME WITH PLASTIC
COVERINGS FROM THE MANUFACTURER.
WHERE CONFLICTING INFORMATION IS FOUND BETWEEN THE
SPECIFICATIONS AND DRAWINGS, THE MOST STRINGENT
DIRECTION SHALL APPLY, UNLESS DIRECTED OTHERWISE BY
THE RESIDENT ENGINEER. SUBMIT INQUIRY TO THE RESIDENT
ENGINEER FOR CLARIFICATION AND RESOLUTION.
6.
PROVIDE TEMPORAL - THREE DISTINCTIVE FIRE ALARM SOUND
FOR AUDIBLE NOTIFICATION DEVICES WITHIN ZONE OF ALARM.
7.
AUDIBLE FIRE ALARM SOUND LEVEL SHALL BE AT LEAST 15dB ABOVE THE REDUCED AVERAGE AMBIENT SOUND LEVEL OR 5dB
ABOVE THE MAXIMUM SOUND LEVEL WITH A DURATION OF 60
SECONDS, AFTER REDUCTION OF AMBIENT SOUND LEVEL,
WHICHEVER IS GREATER PER IBC AND NFPA 72.
8.
VISUAL DEVICES SHALL NOT EXCEED 2 FLASHES PER SECOND
AND SHALL NOT BE SLOWER THAN 1 FLASH EVERY SECOND.
PROVIDE SYNCHRONIZED STROBES WHERE MULTIPLE STROBE
DEVICES ARE LOCATED WITHIN SIGHT OF EACH OTHER.
9.
INSTALL FIRE ALARM WIRING IN METAL RACEWAY. PAINT EXPOSED
FIRE ALARM CONDUITS, ENCLOSURES, JUNCTION BOXES AND COVER
PLATES WITH SPECIFIED RED PAINT, EXCEPT WHERE CONDUIT IS
INSTALLED UNDERGROUND OR RECESSED IN WALLS. SEE
SPECIFICATION SECTION 260533 RACEWAY AND BOXES FOR
ELECTRICAL SYSTEMS FOR ALLOWABLE CONDUIT TYPES.
10.
CONDUCTORS INSTALLED IN WET LOCATION EITHER ABOVE OR
BELOW GROUND SHALL BE MOISTURE-RESISTANT OR OF A TYPE
APPROVED FOR USE UNDER WET CONDITIONS.
11.
ALL NEW RACEWAY INSIDE BUILDINGS SHALL BE ROUTED TIGHT
TO THE STRUCTURE, PARALLEL AND PERPENDICULAR TO
BUILDING LINES. INSTALL RACEWAY IN A MANNER TO AVOID
CONFLICT WITH OTHER ELEMENTS.
12.
UNDERGROUND AND EXTERIOR CONDUITS SHALL HAVE WATER-
TIGHT FITTINGS. (NEC 110-11 AND 300-6).
13.
COORDINATE ROUTING OF CONDUITS WITH OTHER TRADES.
GROUP CONDUITS IN A NEAT AND ORGANIZED MANNER.
HOMERUNS AND MAJOR CONDUITS SHALL BE GROUPED AND
RACKED NEAR MAIN STRUCTURAL MEMBERS. REVIEW
PROPOSED METHOD OF WALL PENETRATIONS WITH VA RESIDENT
ENGINEER AND ARRANGE AS DIRECTED.
14.
DO NOT INSTALL CONDUIT OR RACEWAY THROUGH BEAMS OR
OTHER STRUCTURAL MEMBERS UNLESS SPECIFICALLY
PERMITTED BY VA RESIDENT ENGINEER.
15.
16. REFER TO ELECTRICAL DRAWINGS EP6.1.X SERIES FOR
ADDITIONAL REQUIREMENTS.
PROVIDE U.L. LISTED FIRESTOP SYSTEM THROUGH RATED
WALL AND FLOOR OPENINGS MADE BY NEW CONDUIT
PENETRATIONS.
17.
DO NOT LOCATE CEILING SMOKE DETECTORS WITHIN 3'-0" OF
SUPPLY DIFFUSERS.
18.
3801 Miranda Ave., Palo Alto CA
CENTERS FOR AMBULATORY CARE,
POLYTRAUMA AND BLIND REHABILITATION
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management
Seals and Signatures on e ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
301 BATTERY STREET, 7TH FLOOR
SAN FRANCISCO, CA 94111
T 415.227.0100 F 415.908.0862 www.smithgroup.com
The Design Partnership LLP Architects + Planners
1412 VAN NESS AVE., 2ND FLOOR
SAN FRANCISCO, CA 94109
T 415.777.3737 F 415.777.3476 www.dpsf.com
Associate Architect:
Department of Veterans Affairs
PR
IN
TE
D
O N
5/
/2
9:
:2
A
M GENERAL NOTES, SYMBOLS AND
SCHEDULES
FA0.1.0
MGC KG10 MAY 2013
640-424
Recreation Services
GENERAL NOTES
ABBREVIATIONS
AFF ABOVE FINISH FLOOR
AHU AIR HANDLING UNIT
ANN ANNUNCIATOR
BLDG BUILDING
cd CANDELA
CKT CIRCUIT
DAA DIGITAL AUDIO AMPLIFIER
DCP DIGITAL CONTROL PANEL
DED DEDICATED
DN DN
DPDT DOUBLE POLE DOUBLE THROW
DWG DRAWING
(E) EXISTING
E.A.N. EXCEPT AS NOTED
ELEV ELEVATOR
(ER) REMOVE, RELOCATE, REINSTALL -
CONNECT COMPLETE AND
REPROGRAM PER NEW WIRING
ARRANGEMENT
FA FIRE ALARM
FAAN FIRE ALARM ANNUNCIATOR PANEL
FACP FIRE ALARM CONTROLS PANEL
FATC FIRE ALARM TERMINAL CABINET
FCPS FIRE ALARM POWER SUPPLY
FFSD FAN FIRE SHUTDOWN
FSD FIRE SMOKE DAMPER
WIRING REQUIREMENTS
NEW FIRE ALARM SYSTEM SHALL CONSIST OF:
1. CLASS A WIRING FOR SPEAKERS' DIGITAL AUDIO AMPLIFIERS.
2. CLASS B WIRING FOR IDC, SLC AND NAC FOR LOCAL BUILDING USE.
3. STYLE 7, CLASS A WIRING (SINGLE MODE FIBER OPTIC TYPE) FOR SLC FOR COMMUNICATION BETWEEN BUILDINGS' FIRE ALARM PANEL.
PROVIDE SPECIFIC FIRE ALARM SYSTEM CABLING TYPE AND QUANTITY PER FIRE ALARM SHOP DRAWING SUBMITTAL AND PER FIRE ALARM EQUIPMENT
MANUFACTURER REQUIREMENTS.
PROVIDE 1-INCH CONDUIT MINIMUM BETWEEN FIRE ALARM DEVICES AND EQUIPMENT INSIDE THE BUILDING.
FOR NEW SINGLE MODE FIBER OPTIC CONNECTIONS TO EXISTING FIRE ALARM PANELS UTILIZING MULTI-MODE FIBER:
REPLACE THE NETWORK CARD IN EXISTING, AFFECTED FIRE ALARM PANEL(S). PROVIDE NEW NETWORK CARD TYPE COMPATIBLE WITH BOTH SINGLE MODE AND MULTI-MODE FIBER OPTIC CABLES TO ALLOW COMMUNICATION BETWEEN NEW AND EXISTING FIRE ALARM CONTROL PANELS.
SITE RELATED WORK:
PROVIDE TWO (2) 1.25" CONDUITS FROM THE MAIN FIRE ALARM CONTROL PANEL IN THE RECREATION SERVICES BUILDING TO THE EXISTING
FIRE ALARM PANEL IN THE AQUATIC THERAPY BUILDING. REFER TO SHEET FA3.1.1.
ESTABLISH A CONNECTION WITH THE EXISTING FIRE ALARM CAMPUS NETWORK. PROVIDE NEW NETWORKING CABLING BETWEEN BUILDING 530 (REC SER) AND EXISTING BUILDING 100 VIA BUILDING 530 (AQUATIC THERAPY). REFER TO SHEET FA5.1.1, DETAILS 14 AND 54.
ESTABLISH A NEW SUB-NETWORK FOR BUILDING 530 BETWEEN RECREATION SERVICES AND AQUATIC THERAPY BUILDINGS. PROVIDE A NEW REMOTE ANNUNCIATOR PANEL AT THE LOBBY ENTRANCE OF THE AQUATIC THERAPY BUILDING. PROVIDE NEW NETWORK CABLING BETWEEN
THE FIRE ALARM PANELS IN BOTH BUILDINGS AND THE REMOTE ANNUNCIATOR PANEL.
GENERAL NOTES
FOTC FIBER OPTIC TERMINAL CABINET
(ALSO KNOWN AS FIBER OPTIC PATCH
PANEL)
IBC INTERNATIONAL BUILDING CODE
IDC INITIATING DEVICE CIRCUIT
MFR MANUFACTURER
N/A NOT APPLICABLE
NAC NOTIFICATION APPLIANCE CIRCUIT
NFPA NATIONAL FIRE PROTECTION ASSOCIATION
PNL PANEL
(R) REMOVAL
REC SER RECREATION SERVICES
RQMT REQUIREMENTS
SLC SIGNALING LINE CIRCUIT
U.O.N. UNLESS OTHERWISE NOTED
VFD VARIABLE FREQUENCY DRIVE
WP WEATHERPROOF
1 ASI #01 05/16/2014
eaquino Typewritten Text eaquino Typewritten Text eaquino Typewritten Text
AS-BUILT
eaquino Typewritten Text eaquino Typewritten Text
19. Equivalent to drawing no. FA0.00 eaquino Typewritten Text eaquino Typewritten Text eaquino Typewritten Text eaquino Typewritten Text eaquino Polygon
Typewritten Text As-Built eaquino Typewritten Text eaquino Typewritten Text eaquino Typewritten Text eaquino Typewritten Text 01.31.2019 eaquino Typewritten Text eaquino Typewritten Text
UP
F S
FS
RM RM
F S
DMMM
FS
J
J
J
RM
RM
RM
RM
RM RM
RM
1 2 3 7
A
D
F
4 95 86
C
E
B
1.10.7
1.7 2.2
(E)E
FA6.1.1
135cd
MEP
B100B
STORAGE
B100A
WOMEN
B105
HAC
B104
CORRIDOR
CB01
STAIR 2
BST2
ELEVATOR
LOBBY
B130
ELEV MACH
B101A
VENDING
B101
MEN
B103
RECREATION
ROOM
B100
STAIR 3
BST3
ELEVATOR
BP02
ELEVATOR
BP01
VESTIBULE
B105A
ELEC
B101B
15cd
15cd
30cd 135cd
15cd
30cd
15cd
135cd
135cd
15cd
MB-4
MB-3
SPB-4
VB-6
SB-2
SPB-3
MB-2
VB-5
VB-2
VB-3
DDB-5
RMB-6 RMB-5
DDB-4
VB-4
SB-5
SPB-5 SB-6
SPB-8
SB-7
SB-8
VB-8
RMB-10
SB-9
SB-10
MMB-1 DMB-1
DMB-2
VB-9
SPB-7
VB-10
VB-12
SPB-9
SPB-10
VB-13
SPB-11
VB-14
SPB-12
MB-5
SPB-13
VB-15
SPB-14
NEW FAN COIL UNIT 3.03
3.03
3.03
3.02
3.04
RMB-7
SPB-2
15cd
VB-11
30cd
SB-3
VB-7
15cd
SPB-6
RMB-4
SB-4
DDB-3
DDB-6
RMB-9
RMB-8
DDB-7
RMB-11
DDB-8
NEW FAN COIL UNIT
RMB-3
3.01 NOT USED.
3.02 CONCEAL CONDUIT BEHIND AND FLUSH BACKBOX TO METAL
FURRING. WHERE THE BACKBOX IS INSTALLED ON THE SURFACE
OF THE COLUMN FLANGE, WELD BACKBOX AND CONDUIT STRAP
SUPPORTS TO THE COLUMN. WHERE THE BACKBOX IS INSTALLED
AT THE WEB OF THE COLUMN, PROVIDE COLUMN INSERTS TO
ALLOW INSTALLATION OF CHANNEL SUPPORTS FOR BACKBOX AND
CONDUIT. TYPICAL.
3.03 MOUNT BACKBOX AS HIGH AS POSSIBLE.
3.04 RELAY MODULE TO INTERFACE WITH AV HEAD-END EQUIPMENT -
COORDINATE LOCATION IN FIELD WITH AV/PAGING INSTALLER.
GRAPHIC SCALE:
0'
1/8" = 1'-0"
8' 8' 16'
3801 Miranda Ave., Palo Alto CA
CENTERS FOR AMBULATORY CARE,
POLYTRAUMA AND BLIND REHABILITATION
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management
Seals and Signatures on e ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
301 BATTERY STREET, 7TH FLOOR
SAN FRANCISCO, CA 94111
T 415.227.0100 F 415.908.0862 www.smithgroup.com
The Design Partnership LLP Architects + Planners
1412 VAN NESS AVE., 2ND FLOOR
SAN FRANCISCO, CA 94109
T 415.777.3737 F 415.777.3476 www.dpsf.com
SHEET NOTES
KEYNOTES
Associate Architect:
Department of Veterans Affairs
PR
IN
TE
D
O N
TRUE NORTH
PROJ NORTH
5/
/2
9:
:5
A
M FIRE ALARM FLOOR PLAN LEVEL B
FA3.1.0
MGC KG10 MAY 2013
640-424
Recreation Services
SCALE: 1/8" = 1'-0"
54 FIRE ALARM FLOOR PLAN LEVEL B
1. ALL CONDUIT IN RECREATION ROOM B100, EXERCISE1 250,
EXERCISE2 240, AND STUDIO 245 SHALL BE SURFACE MOUNTED TO
BOTTOM OF ACOUSTICAL DECKING IN ACCORDANCE WITH DECKING
MANUFACTURER’S INSTRUCTIONS AND RECOMMENDATIONS USING
DECKING MANUFACTURER’S APPROVED ATTACHMENT DEVICES.
2. ARRANGE ALL SURFACE MOUNTED CONDUIT IN A NEAT AND
ORDERLY MANNER, ROUTED PARALLEL AND PERPENDICULAR TO
BUILDING LINES. GROUP CONDUITS TOGETHER WHERE
PRACTICABLE.
3. FOR ADDITIONAL REQUIREMENTS, REFER TO SHEET FA6.1.X
DRAWINGS.
4. WIRING ARRANGEMENT SHOWN ON PLAN IS DIAGRAMMATIC.
PROVIDE ADDITIONAL BACKBOXES AND/OR ALTERNATE WIRE RUNS
AS REQUIRED TO SUIT INSTALLATION. REFER TO SHEET FA5.1.1 FOR
RISER DIAGRAM.
5. FOR CONTROLLING FIRE SMOKE DAMPER (FSD):
OPTION 1 - PROVIDE DUCT SMOKE DETECTOR WITHIN 5'-0" OF FSD.
OPTION 2 - PROVIDE IN-DUCT SMOKE DETECTOR WITHIN 5'-0" OF FSD
WHERE AIR VELOCITY AND/OR DUCT SIZE HINDERS THE
INSTALLATION OF DUCT SMOKE DETECTOR.
OPTION 3 - WHERE NEITHER OPTIONS 1 AND 2 ARE FEASIBLE, PROVIDE
CEILING SMOKE DETECTOR(S) TO PROVIDE AREA
COVERAGE IN ROOM(S) SERVED BY AFFECTED DUCTWORK RELATED
TO THE FIRE SMOKE DAMPER.
COORDINATE WORK WITH DIVISION 23 PRIOR TO IMPLEMENTATION.
1 ASI #01 05/16/2014
eaquino Typewritten Text
6. Equivalent to drawing no. FA1.0B eaquino Typewritten Text eaquino Polygon eaquino Typewritten Text
AS-BUILT
eaquino Typewritten Text
As-Built eaquino Typewritten Text 01.31.2019 eaquino Typewritten Text
DN
UP
FS
FS
F S
RM RM
RM
RM
RM
RM
F S
D H
D H
RM
RM
J
J
J
J
MM
MM
RM
RM
RM
RM RM
DM
1 2 3 7
A
D
F
4 95 86
C
E
B
1.10.7
1.7 2.2
(E)E
ELEVATOR 1
1P01
ELEVATOR 2
1P02
CHIEF
OFFICE
INTERVIEW
INTERVIEW
COPY
C01A
KITCHEN
CONFERENCE
STAIR 2
1ST2
OPEN
WORKSTATIONS
CORRIDOR
C01
ELEVATOR
LOBBY
GAIT TRACK
FIRE ALARM DAA
NEW
EXISTING
30cd
30cd
15cd
15cd
15cd 135cd
135cd
135cd
135cd
15cd
(RECREATION SERVICES)
(AQUATIC THERAPY)
3.01
MAIN FACP
FCPS
3.02
3.03
M1-4
DD1-10
RM1-11
M1-3
RM1-10
S1-2
RM1-9RM1-8
DD1-9
DD1-8
M1-1
S1-1
RM1-1
DD1-1
3.08
3.07
RM1-2
RM1-3
DD1-3DD1-2
3.05
OUTLINE OF SHAFT AT
FLOOR LEVEL ABOVE
V1-1
V1-2
SP1-2
V1-5
SP1-3
V1-4
SP1-4
V1-3
SP1-5
V1-8
SP1-6
V1-9
SP1-7
V1-10
SP1-8
SP1-9
V1-11
SP1-10
V1-12
SP1-11V1-13
SP1-12
FATC 3.06
M1-2
3.09
3.09
3.09
3.10
MM1-2
MM1-1
3.11
SP1-1
3.12
3.13
RM1-4
DD1-4
3.14
3.14
15cd
OUTLINE OF SHAFT AT
FLOOR LEVEL ABOVE
RM1-12
DD1-11
RM1-13
DD1-12
3.05
V1-7
RM1-5
DD1-5
DD1-6
DD1-7
RM1-7RM1-6
DM1-2
DM1-1
15cd V1-6
GRAPHIC SCALE:
0'
1/8" = 1'-0"
8' 8' 16'
3801 Miranda Ave., Palo Alto CA
CENTERS FOR AMBULATORY CARE,
POLYTRAUMA AND BLIND REHABILITATION
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management
Seals and Signatures on e ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
301 BATTERY STREET, 7TH FLOOR
SAN FRANCISCO, CA 94111
T 415.227.0100 F 415.908.0862 www.smithgroup.com
The Design Partnership LLP Architects + Planners
1412 VAN NESS AVE., 2ND FLOOR
SAN FRANCISCO, CA 94109
T 415.777.3737 F 415.777.3476 www.dpsf.com
SHEET NOTES
KEYNOTES
Associate Architect:
Department of Veterans Affairs
PR
IN
TE
D
O N
TRUE NORTH
PROJ NORTH
5/
/2
9:
:1
A
M FIRE ALARM FLOOR PLAN LEVEL 1
FA3.1.1
MGC KG10 MAY 2013
640-424
Recreation Services
SCALE: 1/8" = 1'-0"
54 FIRE ALARM FLOOR PLAN LEVEL 1
1. ALL CONDUIT IN RECREATION ROOM B100, EXERCISE1 250,
EXERCISE2 240, AND STUDIO 245 SHALL BE SURFACE MOUNTED TO
BOTTOM OF ACOUSTICAL DECKING IN ACCORDANCE WITH DECKING
MANUFACTURER’S INSTRUCTIONS AND RECOMMENDATIONS USING
DECKING MANUFACTURER’S APPROVED ATTACHMENT DEVICES.
2. ARRANGE ALL SURFACE MOUNTED CONDUIT IN A NEAT AND
ORDERLY MANNER, ROUTED PARALLEL AND PERPENDICULAR TO
BUILDING LINES. GROUP CONDUITS TOGETHER WHERE
PRACTICABLE.
3. FOR ADDITIONAL REQUIREMENTS, REFER TO SHEET FA6.1.1.
4. WIRING ARRANGEMENT SHOWN ON PLANS IS DIAGRAMMATIC. PROVIDE
ADDITIONAL BACKBOXES AND/OR ALTERNATE WIRE RUNS AS
REQUIRED TO SUIT INSTALLATION. REFER TO SHEET FA5.1.1 FOR
RISER DIAGRAM.
5. FOR CONTROLLING FIRE SMOKE DAMPER (FSD):
OPTION 1 - PROVIDE DUCT SMOKE DETECTOR WITHIN 5'-0" OF FSD.
OPTION 2 - PROVIDE IN-DUCT SMOKE DETECTOR WITHIN 5'-0" OF FSD
WHERE AIR VELOCITY AND/OR DUCT SIZE HINDERS THE
INSTALLATION OF DUCT SMOKE DETECTOR.
OPTION 3 - WHERE NEITHER OPTIONS 1 AND 2 ARE FEASIBLE, PROVIDE
CEILING SMOKE DETECTOR(S) TO PROVIDE AREA
COVERAGE IN ROOM(S) SERVED BY AFFECTED DUCTWORK RELATED
TO THE FIRE SMOKE DAMPER.
COORDINATE WORK WITH DIVISION 23 PRIOR TO IMPLEMENTATION.
3.01 EXISTING SEMI-FLUSHED FIRE ALARM CONTROL PANEL IN
AQUATICS THERAPY BUILDING LOBBY.
3.02 PROVIDE (2) 1.25" CONDUITS FROM THE FIRE ALARM CONTROL
PANEL IN RECREATION SERVICES BUILDING TO THE FIRE
ALARM CONTROL PANEL IN AQUATICS THERAPY BUILDING. IN
AQUATICS THERAPY BUILDING, RUN CONDUITS CONCEALED IN
20 TO 30 FEET HIGH GYPBOARD CEILING AND WALL. REPAIR
CEILING AND WALL BACK TO ORIGINAL CONDITION AND
PROVIDE FINISHES TO MATCH EXISTING AFTER NEW
INSTALLATIONS.
3.03 PROVIDE FLEX CONDUIT CONNECTION AT SEISMIC JOINT
BETWEEN BUILDINGS. SEAL ALL BUILDING PENETRATIONS.
3.04 NOT USED.
3.05 UP TO LEVEL 2. REFER TO SHEET FA3.1.2.
3.06 PROVIDE FATC ABOVE MAIN FIRE ALARM CONTROL PANEL.
3.07 TO DAA FOR SPEAKERS AND TO FCPS FOR STROBES.
3.08 TO FACP VIA FATC.
3.09 MOUNT BACKBOX AS HIGH AS POSSIBLE.
3.10 CONCEAL CONDUIT BEHIND AND FLUSH BACKBOX TO METAL
FURRING. PROVIDE COLUMN INSERTS TO ALLOW INSTALLATION
OF CHANNEL SUPPORTS FOR BACKBOX AND CONDUIT.
3.11 MONITOR MODULE AND RELAY MODULE FOR ELEVATOR SHUNT
TRIP - COORDINATE LOCATION AND INSTALLATION WITH THE
ELECTRICAL CONTRACTOR. REFER TO SHEET FA5.1.1, DETAIL 54
AND FA6.1.1, DETAIL 52 FOR ADDITIONAL REQUIREMENTS.
3.12 LOCATE NEW ANNUNCIATOR PANEL SEMI-FLUSHED IN LOBBY
WALL, ADJACENT TO THE EXISTING FIRE ALARM PANEL.
3.13 PROVIDE (1) 1" CONDUIT BETWEEN EQUIPMENT AND CONCEAL IN
WALL SPACE.
3.14 REPAIR WALL TO MATCH EXISTING WHERE DISTURBED BY NEW
INSTALLATIONS.
1 ASI #01 05/16/2014
eaquino Typewritten Text
6. Equivalent to drawing no. FA1.01 eaquino Polygon eaquino Typewritten Text
AS-BUILT
eaquino Typewritten Text
01.31.2019 eaquino Typewritten Text eaquino Typewritten Text eaquino Typewritten Text As-Built eaquino Typewritten Text
DN
RM
RM
F S
DM
RM
RMD
H
D H
RM
RM
RM
RM
RM
RM
RM
RM
RM
RM
FS
1 2 3 7
A
D
F
4 95 86
C
E
B
1.10.7
1.7 2.2
(E)E
1.2
NEW
EXISTING
15cd
V2-15
V2-14
SP2-9
75cd
75cd
15cd15cd
15cd
30cd
75cd 15cd
15cd
15cd 15cd
75cd
(RECREATION SERVICES)
(AQUATIC THERAPY)
V2-16
SP2-10
15cd
75cd
V2-1
SP2-1
DD2-1
DD2-2
RM2-3
DD2-3
SP2-2 SP2-5
V2-2
S2-1
RM2-4
DD2-4
RM2-5
M2-1
SP2-3
V2-3
RM2-8
SP2-4
V2-4
V2-5
V2-6
3.03
DM2-1
DM2-2
V2-7
V2-8
V2-10
SP2-6
SP2-7
V2-9
V2-12
3.04
V2-11
SP2-8
DD2-7
DD2-8
RM2-12
3.07
3.03
15cd V2-13
RM2-14
RM2-13 DD2-10
DD2-9
3.05
RM2-7
3.02
RM2-2
RM2-1
3.01
3.04
RM2-11
3.02
RM2-10
EXERCISE 1
AV/ STOR
AV1
ELEC
EC3
SHAFT C
EXERCISE 2
TELECOMMUNICATIONS
TC1
WOMEN
MEN
HAC
CO3A
ELEC
EC2
CORRIDOR
C03
ELEVATOR
LOBBY
ELEVATOR
2P01
ELEVATOR
2P02STUDIO
CORRIDOR
C02
CORRIDOR
CO2A
SHAFT B
SHAFT A
STAIR 1
2ST1
3.03
RM2-9
DD2-6
RM2-6
DD2-5
3.06 M2-2
3.07
GRAPHIC SCALE:
0'
1/8" = 1'-0"
8' 8' 16'
3801 Miranda Ave., Palo Alto CA
CENTERS FOR AMBULATORY CARE,
POLYTRAUMA AND BLIND REHABILITATION
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management
Seals and Signatures on e ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
301 BATTERY STREET, 7TH FLOOR
SAN FRANCISCO, CA 94111
T 415.227.0100 F 415.908.0862 www.smithgroup.com
The Design Partnership LLP Architects + Planners
1412 VAN NESS AVE., 2ND FLOOR
SAN FRANCISCO, CA 94109
T 415.777.3737 F 415.777.3476 www.dpsf.com
SHEET NOTES
KEYNOTES
Associate Architect:
Department of Veterans Affairs
PR
IN
TE
D
O N
TRUE NORTH
PROJ NORTH
5/
/2
9:
:4
A
M FIRE ALARM FLOOR PLAN LEVEL 2
FA3.1.2
MGC KG10 MAY 2013
640-424
Recreation Services
SCALE: 1/8" = 1'-0"
54 FIRE ALARM FLOOR PLAN LEVEL 2
1. ALL CONDUIT IN RECREATION ROOM B100, EXERCISE1 250,
EXERCISE2 240, AND STUDIO 245 SHALL BE SURFACE MOUNTED TO
BOTTOM OF ACOUSTICAL DECKING IN ACCORDANCE WITH DECKING
MANUFACTURER’S INSTRUCTIONS AND RECOMMENDATIONS USING
DECKING MANUFACTURER’S APPROVED ATTACHMENT DEVICES.
2. ARRANGE ALL SURFACE MOUNTED CONDUIT IN A NEAT AND
ORDERLY MANNER, ROUTED PARALLEL AND PERPENDICULAR TO
BUILDING LINES. GROUP CONDUITS TOGETHER WHERE
PRACTICABLE.
3. FOR ADDITIONAL REQUIREMENTS, REFER TO SHEET FA6.1.1.
4. WIRING ARRANGEMENT SHOWN ON PLANS IS DIAGRAMMATIC.
PROVIDE ADDITIONAL BACKBOXES AND/OR ALTERNATE WIRE RUNS
AS REQUIRED TO SUIT INSTALLATION. REFER TO SHEET FA5.1.1 FOR
RISER DIAGRAM.
5. FOR CONTROLLING FIRE SMOKE DAMPER (FSD):
OPTION 1 - PROVIDE DUCT SMOKE DETECTOR WITHIN 5'-0" OF FSD.
OPTION 2 - PROVIDE IN-DUCT SMOKE DETECTOR WITHIN 5'-0" OF FSD
WHERE AIR VELOCITY AND/OR DUCT SIZE HINDERS THE
INSTALLATION OF DUCT SMOKE DETECTOR.
OPTION 3 - WHERE NEITHER OPTIONS 1 AND 2 ARE FEASIBLE, PROVIDE
CEILING SMOKE DETECTOR(S) TO PROVIDE AREA COVERAGE IN
ROOM(S) SERVED BY AFFECTED DUCTWORK RELATED TO THE FIRE
SMOKE DAMPER.
COORDINATE WORK WITH DIVISION 23 PRIOR TO IMPLEMENTATION.
3.01 TO DAA FOR SPEAKERS AND TO FCPS FOR STROBES.
3.02 RELAY MODULE TO INTERFACE WITH AV/PAGING HEAD-END
EQUIPMENT - COORDINATE LOCATION IN FIELD WITH AV/PAGING
INSTALLER.
3.03 UP TO ROOF LEVEL. FOR CONTINUATION, REFER TO SHEET
FA3.1.3.
3.04 TO FIRE ALARM HEADEND EQUIPMENT AT LEVEL 1.
3.05 RELAY MODULE FOR SECURITY PANEL - COORDINATE LOCATION IN
FIELD WITH SECURITY WORK.
3.06 CONCEAL CONDUIT BEHIND AND FLUSH BACKBOX TO METAL
FURRING. PROVIDE COLUMN INSERTS TO ALLOW INSTALLATION
OF CHANNEL SUPPORTS FOR BACKBOX AND CONDUIT.
3.07 TO DUCT DETECTOR AT LEVEL 1. FOR CONTINUATION, REFER TO
SHEET FA3.1.1.
1 ASI #01 05/16/2014
eaquino Typewritten Text eaquino Typewritten Text
AS-BUILT
eaquino Typewritten Text eaquino Typewritten Text
6. Equivalent to drawing no. FA1.02 eaquino Typewritten Text eaquino Typewritten Text
As-Built eaquino Typewritten Text eaquino
01.31.2019
FS
RM
1 2 3 7
A
D
F
4 95 86
C
E
B
1.10.7
AHU-2
AHU-1
NEW
EXISTING
(RECREATION SERVICES)
(AQUATIC THERAPY)
WP
3.02
3.03
3.02
3.03
3.01
DDR-1
3.04
OUTLINE OF RATED
SHAFT AT FLOOR
LEVEL BELOW
OUTLINE OF RATED SHAFT
AT FLOOR LEVEL BELOW
RMR-1
OUTLINE OF RATED
SHAFT AT FLOOR LEVEL
BELOW
RMR-3
DDR-3
3.04
MR-1
3.04
3.05
3.05
OUTLINE OF HAC ROOM
BELOW
3.02
DDR-2
3.05 RMR-2
3.01 SURFACE MOUNT MANUAL PULL STATION TO METAL STUD.
3.02 COORDINATE INSTALLATION AND LOCATION OF DUCT SMOKE
DETECTOR WITH MECHANICAL DRAWINGS.
3.03 LOCATE RELAY MODULE ADJACENT TO CONTROL PANEL IN AHU
ENCLOSURE IF SPACE PERMITS. OTHERWISE, LOCATE RELAY AND
ITS ENCLOSURE OUTSIDE, NEAR CONTROL PANEL LOCATION AND
PROVIDE STRUT SUPPORT TO SUIT INSTALLATION.
3.04 DOWN TO LEVEL 2. FOR CONTINUATION, REFER TO SHEET FA3.1.1.
3.05 COORDINATE LOCATION OF CONDUIT RUN WITH OTHER TRADES
PRIOR TO INSTALLATION.
GRAPHIC SCALE:
0'
1/8" = 1'-0"
8' 8' 16'
3801 Miranda Ave., Palo Alto CA
CENTERS FOR AMBULATORY CARE,
POLYTRAUMA AND BLIND REHABILITATION
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management
Seals and Signatures on e ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
301 BATTERY STREET, 7TH FLOOR
SAN FRANCISCO, CA 94111
T 415.227.0100 F 415.908.0862 www.smithgroup.com
The Design Partnership LLP Architects + Planners
1412 VAN NESS AVE., 2ND FLOOR
SAN FRANCISCO, CA 94109
T 415.777.3737 F 415.777.3476 www.dpsf.com
SHEET NOTES
KEYNOTES
Associate Architect:
Department of Veterans Affairs
PR
IN
TE
D
O N
TRUE NORTH
PROJ NORTH
8/ 5/
:5
9:
P
M FIRE ALARM FLOOR PLAN ROOF
LEVEL
FA3.1.3
MGC KG10 MAY 2013
640-424
Recreation Services
SCALE: 1/8" = 1'-0"
54 FIRE ALARM FLOOR PLAN ROOF LEVEL
1. ALL CONDUIT IN RECREATION ROOM B100, EXERCISE1 250,
EXERCISE2 240, AND STUDIO 245 SHALL BE SURFACE MOUNTED TO
BOTTOM OF ACOUSTICAL DECKING IN ACCORDANCE WITH DECKING
MANUFACTURER’S INSTRUCTIONS AND RECOMMENDATIONS USING
DECKING MANUFACTURER’S APPROVED ATTACHMENT DEVICES.
2. ARRANGE ALL SURFACE MOUNTED CONDUIT IN A NEAT AND
ORDERLY MANNER, ROUTED PARALLEL AND PERPENDICULAR TO
BUILDING LINES. GROUP CONDUITS TOGETHER WHERE
PRACTICABLE.
3. FOR ADDITIONAL REQUIREMENTS, REFER TO SHEET FA6.1.1.
4. FOR CONTROLLING FIRE SMOKE DAMPER (FSD):
OPTION 1 - PROVIDE DUCT SMOKE DETECTOR WITHIN 5'-0" OF FSD.
OPTION 2 - PROVIDE IN-DUCT SMOKE DETECTOR WITHIN 5'-0" OF FSD
WHERE AIR VELOCITY AND/OR DUCT SIZE HINDERS THE
INSTALLATION OF DUCT SMOKE DETECTOR.
OPTION 3 - WHERE NEITHER OPTIONS 1 AND 2 ARE FEASIBLE, PROVIDE
CEILING SMOKE DETECTOR(S) TO PROVIDE AREA
COVERAGE IN ROOM(S) SERVED BY AFFECTED DUCTWORK
RELATED TO THE FIRE SMOKE DAMPER.
COORDINATE WORK WITH DIVISION 23 PRIOR TO IMPLEMENTATION.
eaquino Typewritten Text
5. Equivalent to drawing no. FA1.03 eaquino Typewritten Text eaquino Typewritten Text eaquino Polygon eaquino
AS-BUILT
01.31.2019 eaquino Typewritten Text eaquino Typewritten Text eaquino
As-Built
SCALE:
11111
5 5 5
1 1
2 11
RMRMRMRMMM DM
RMRMRMRMRM
RM
RMRMRMRMRM
RMRM
DH DH
RM
DH DH
DM
RM
RM
RM
MM
IR
EOL
EOL
IR
IR
EOL
EOL
IR
IR
EOL
EOL
IR
14 16
IR
EOL
IR
MM
IR
EOL
IR
RM
RM
RM RM RM
181617
RM
RM
RM
RM RM
RM DM RM
RMRMRM
RMRM
RM RMRM
6 14
SB-2RMB-4 SB-3SB-4RMB-5RMB-6SB-5SB-6SB-7RMB-10 SB-8MMB-1 DMB-1
RM1-1RM1-3RM1-4RM1-6RM1-7
RM1-11
RM2-1RM2-2RM2-3RM2-10RM2-12
SB-1
SB-9SB-10
RM1-2S1-2RM1-10
S2-1RM2-5DM2-1
DM2-2
RMR-3
RM2-8
RMR-1
DMB-2
V2-1V2-10V2-11V2-14V2-16
SP2-1SP2-6SP2-8SP2-9SP2-10
V1-1V1-6V1-10V1-11V1-12
SP1-1SP1-7SP1-9SP1-10
V1-13
SP1-11SP1-12
SPB-3SPB-8SPB-10SPB-11SPB-12
VB-2VB-7VB-9VB-10VB-12
SPB-13
VB-13VB-14
SPB-14
VB-15
BLDG 530
(RECREATION
SERVICES)
S1-1MM1-1MM1-2RM1-8
SPB-2
VB-11 VB-1
RMB-7
RM2-11 RM2-7 RM2-4RM2-13
RMR-2
RM2-14
RM1-12 RM1-13
DM1-1
DM1-2
RM1-5
V1-8
ELEV #2
ELEV #1
ELEV #1
ELEV #2
RMB-8RMB-9RMB-11
RM1-9
RM2-6RM2-9
RMB-3 RMB-1RMB-2
BLDG 530
(AQUATIC THERAPY)
FS
FS FS
HD
FSFSFS
FSFS
FS
FS
FS
GENERAL NOTES: RE: DETAIL FIRE ALARM BUILDING RISER DIAGRAM:
1. UTILIZE MORE THAN ONE NOTIFICATION DEVICE CIRCUIT IN THE FACP WHERE CALCULATIONS
DEEM IT NECESSARY.
2. PROVIDE END OF LINE RESISTOR OHM VALUE TO MEET FIRE ALARM MANUFACTURER
REQUIREMENTS.
3. PROVIDE BAR CODE LABEL ON NEW FIRE ALARM DEVICES PER CAMPUS STANDARDS.
4. PROVIDE LOOP/CIRCUIT ADDRESS LABEL ON NEW FIRE ALARM DEVICES TO MATCH CAMPUS
STANDARDS.
5. ALL CABLES SHALL BE CLEARLY LABELED AT EACH TERMINATED END WITH ITS OWN
INDIVIDUAL AND DISTINCT NUMBER OR MARKING PER CAMPUS STANDARDS.
6. RISER SHOWN IS DIAGRAMMATIC. REFER TO FLOOR PLANS ON FA3.1.x SERIES SHEETS AND WIRING DIAGRAM DETAILS ON FA6.1.x SERIES SHEET FOR ADDITIONAL REQUIREMENTS.
KEYNOTES: RE: DETAIL FIRE ALARM BUILDING RISER DIAGRAM:
TO FSD VIA INERPOSING RELAY - WIRING PROVISION BY FIRE
ALARM WORK. COORDINATE INSTALLATION WITH DIVISIONS 23
& 26.
TO FIRE ALARM CONNECTION POINT AT EQUIPMENT
CONTROLLER FOR FFSD - WIRING PROVISION BY FIRE ALARM
WORK. COORDINATE INSTALLATION WITH OTHER DIVISIONS
OF WORK.
TO SECURITY POWER SUPPLY - WIRING PROVISION BY FIRE
ALARM WORK. COORDINATE INSTALLATION WITH SECURITY
WORK.
PROVIDE HIGH SPEED NETWORK COMMUNICATIONS MODULE
IN THE FIRE ALARM CONTROL PANEL TO ALLOW FIRE ALARM
COMMUNICATION WITH OTHER BUILDINGS VIA FIBER OPTIC
CABLING.
14 PART FIRE ALARM CAMPUS RISER DIAGRAM
NO SCALE
NOTES RE:DETAIL PART FIRE ALARM CAMPUS RISER DIAGRAM:
1. FIRE ALARM CAMPUS RISER SCHEMATIC IS DIAGRAMMATIC AND IS INTENDED TO SHOW A GENERAL IDEA OF THE EXISTING FIRE ALARM INFRASTRUCTURE.
2. REMOVE EXISTING STYLE 7 FIRE ALARM NETWORK CABLING BETWEEN THE FIRE ALARM NODE IN BUILDING 100 AND THE FACP IN BUILDING 530 (AQUATIC
THERAPY). PRIOR TO REMOVAL, REFER TO NOTE 3.
3. MAXIMUM DOWNTIME FOR THE FIRE ALARM NETWORK IS FOUR HOURS. DO NOT DISCONNECT AND/OR REMOVE EXISTING FIBER OPTIC CABLES UNTIL ALL
NEW FIBER OPTIC CABLES HAVE BEEN INSTALLED AND TESTED FOR PROPER OPERATION.
4. EXISTING FIRE ALARM CAMPUS RISER DIAGRAM CONNECTIONS SHOWN ARE APPROXIMATE AND DIAGRAMMATIC. VERIFY IN FIELD ALL EXISTING
INTERBUILDING CAMPUS NETWORK CONNECTIONS.
5. PROVIDE NEW CONTINUOUS FIBER OPTIC CABLING BETWEEN THE FACP IN BUILDING 530 (REC SER) AND BUILDING 100'S FIRE ALARM NODE. PROVIDE NEW CONTINUOUS FIBER OPTIC CABLING BETWEEN THE FACP IN BUILDING 530 (AQUATIC THERAPY) AND BUILDING 100'S FIRE ALARM NODE. INSTALL CABILING BETWEEN RECREATION SERVICES AND AQUATIC THERAPY IN NEW CONDUIT AND UTILIZE EXISTING CONDUIT BETWEEN BUILDINGS 530 (AQUATIC THERAPY)
AND BUILDING 100.
6. PROVIDE ADDITIONAL FIBER OPTIC PATCH PANEL AS REQUIRED TO SUIT TEMPORARY/INTERIM INSTALLATIONS.
54 FIRE ALARM BUILDING RISER DIAGRAM
NO SCALE
TO ELEVATOR CONTROLLER - WIRING PROVISION BY FIRE
ALARM WORK. COORDINATE INSTALLATION WITH ELEVATOR
WORK.
PROVIDE TERMINAL BLOCKS FOR WIRING TERMINATIONS.
ARRANGE TERMINAL BLOCKS IN AN ORGANIZED MANNER.
LABEL ALL TERMINATIONS WITH DEVICE AND LOOP/CIRCUIT
IDENTIFICATION.
CONNECT TO 24VDC POWER SOURCE IN FACP.
* REFER TO THE FIRE ALARM SYSTEM DEVICE SCHEDULE ON SHEET FA0.1.0
FOR REFERENCE.
COORDINATE LOCATION AND INSTALLATION WITH DIVISION 21.
PROVIDE QUANTITY OF DIGITAL AUDIO AMPLIFIER ASSEMBLY
TO SUIT INSTALLATION AND PROVIDE SPARE CAPACITY.
TO SHUNT TRIP ACCESSORY IN ELEVATOR'S CIRCUIT
BREAKER - 120V WIRING PROVISION IN ELECTRICAL WORK.
COORDINATE INSTALLATION WITH DIVISION 26. REFER TO
DETAIL 52 ON SHEET FA6.1.1.
TO SUPERVISED CONTROL MODULE OUTPUT IN THE FACP.
CKT E11-1 CKT E11-5
PROVIDE ADDITIONAL FIRE ALARM POWER SUPPLY PANELS TO
SUIT INSTALLATION AND PROVIDE SPARE CAPACITY.
PROVIDE NEW CONTINUOUS FIBER OPTIC WIRING FROM THE
FIRE ALARM PANEL IN RECREATION SERVICES TO THE
ANNUCIATOR PANE IN AQUATIC THERAPY. PROVIDE NEW
CONTINUOUS FIBER OPTIC WIRING FROM THE FIRE ALARM
PANEL IN RECREATION SERVICES TO THE FIRE ALARM NODE IN
BUILDING 100. SEE DETAIL 14 ON THIS SHEET.
PROVIDE SIX - OUTPUT SUPERVISED CONTROL MODULES FOR
USE BY ELEVATOR FUNCTIONS. PROVIDE QUANTITY OF
MODULES AS REQUIRED TO SUIT NEW INSTALLATION. OBTAIN
24V SUPPLY FROM 24VDC AUXILIARY POWER SUPPLY IN THE
FACP TO SERVE THE SUPERVISED CONTROL MODULE
CIRCUITS.
PROGRAM THE FIRE ALARM CONTROL PANEL AND REMOTE
ANNUNCIATOR PANEL TO MONITOR FIRE ALARM IN REC SER
AND AQUATIC THERAPY BUILDINGS.
PROVIDE NEW ANNUNCIATOR PANEL COMPLETE WITH HIGH
SPEED NETWORK CARD, SEMI-RECESSED ENCLOSURE,
ANNUNCIATOR DISPLAY EQUIPMENT, MOUNTING HARDWARE,
ETC. TO PROVIDE A COMPLETE AND OPERATIONAL
INSTALLATION.
PROVIDE ALL COMPONENTS/HARDWARE REQUIRED TO SUIT
NEW INSTALLATIONS BETWEEN THE REC SER BUILDING AND
THE NEW ANNUNCIATOR PANEL, AND TO MAINTAIN THE
FUNCTIONALITY OF EXISTING BUILDING FIRE ALARM DEVICES.
CKT E11-3
TO AV/PAGING HEAD-END EQUIPMENT - WIRING PROVISION BY
FIRE ALARM WORK. COORDINATE INSTALLATION WITH
AV/PAGING INSTALLER.
PROVIDE NEW CONTINUOUS FIBER OPTIC WIRING BETWEEN
THE REMOTE ANNUCIATOR AND THE FIRE ALARM PANEL IN
AQUATIC THERAPY.
PROVIDE 24VDC POWER TO THE ANNUNCIATOR PANEL
UTILIZING THE POWER SUPPLY IN THE EXISTING FIRE ALARM
PANEL.
FACP
(E)
BLDG 530
(E)
FACP
(E)
(E)
(E)(E)
(E)
(E)
FOTC
(E)
FACP
(E)
(E)
FOTC
(E)
FOTC
(E)
FAAN
(E)
FOTC
(E)
FAAN
(E)
TO (E) FOTC IN
BLDG 615
(E)
GUTTER (E)
TO CAMPUS FA INFRASTRUCTURE
FACP
(AQUATIC)
(E)
(E)
MAIN
FACP
FCPS
FACP
(REC SER)
DAA
CABINET
MB-2
DDB-3DDB-4DDB-5
DD1-1DD1-3DD1-4DD1-6DD1-7
M1-2
DD1-10
M1-1
DD2-1DD2-2DD2-3DD2-7DD2-8
V2-2V2-3V2-4V2-5V2-6V2-7V2-8
DDR-3
V1-1
FLOOR LEVEL
DEVICE *
SEQUENTIAL NO.
NOTIFICATION DEVICES:
M1-1
FLOOR LEVEL
DEVICE *
INITIATING DEVICES:
SEQUENTIAL NO.
HDB-1
MB-1MB-3MB-4
DD1-2
M1-3M1-4
M2-1
DD2-9
DDR-1
FATC
V2-9V2-12V2-13V2-15
E O L
SP2-2SP2-3SP2-4SP2-5SP2-7
E O L
DESIGNATIONS: RE: DETAIL FIRE
ALARM BUILDING RISER DIAGRAM
V1-2V1-3V1-4V1-5V1-7
E O L
SP1-2SP1-3SP1-4SP1-5SP1-8
E O L
SPB-4SPB-5SPB-6SPB-7SPB-9
E O L
VB-3VB-4VB-5VB-6VB-8
E O L
SEE NOTE 2.
NOTE 6.
SEE NOTE 5.
DD1-8
SP1-6
SPB-1
DD2-4
ANN
PANEL
(2) CONDUITS - SEE SHEET FA3.1.1.
DDR-2
DD2-10
DD1-11
DD1-5
V1-9
FAAN
(AQUATIC)
DD1-12
DDB-6DDB-7DDB-8
DD1-9
DD2-5DD2-6
DDB-1DDB-2
M2-2
MB-5
LEVEL 2
ROOF
LEVEL 1
ELEVATOR MACHINE RM B101A
LOBBY OF
AQUATIC
THERAPYMAIN ELEC ROOM
BASEMENT
LEVEL 2
ROOF
LEVEL 1
BASEMENT
3801 Miranda Ave., Palo Alto CA
CENTERS FOR AMBULATORY CARE,
POLYTRAUMA AND BLIND REHABILITATION
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management
Seals and Signatures on e ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
301 BATTERY STREET, 7TH FLOOR
SAN FRANCISCO, CA 94111
T 415.227.0100 F 415.908.0862 www.smithgroup.com
The Design Partnership LLP Architects + Planners
1412 VAN NESS AVE., 2ND FLOOR
SAN FRANCISCO, CA 94109
T 415.777.3737 F 415.777.3476 www.dpsf.com
Associate Architect:
Department of Veterans Affairs
PR
IN
TE
D
O N
5/
/2
9:
:0
A
M FIRE ALARM RISER DIAGRAMS
FA5.1.1
MGC KG10 MAY 2013
640-424
Recreation Services
1 ASI #01 05/16/2014
eaquino Typewritten Text
AS-BUILT
eaquino Typewritten Text Note:
eaquino Typewritten Text Equivalent to drawing no. FA2.00 eaquino Typewritten Text eaquino Typewritten Text
As-Built eaquino Typewritten Text 01.31.2019 eaquino Typewritten Text
FS
HD
RM
RM
SCALE:
SCALE:
SCALE:
RM
MM
EOL EOL EOL
IRIRIR
IR
EOL
IR
NH
120V-1PH
(UTILIZE SAME CIRCUIT
AS ASSOCIATED FSD)
TO ADDRESSABLE FA DEVICESTO ADDRESSABLE FA
DEVICES
FIRE ALARM WIRING FIRE ALARM WIRING
TO FIRE SMOKE DAMPER
H
N
FIRE ALARM WIRING
F F
120V-1PH
CIRCUIT E11-7 FOR ELEVATOR #1
CIRCUIT E11-9 FOR ELEVATOR #2
TO ADDRESSABLE FA
DEVICES
TO ADDRESSABLE HEAT
DETECTOR
TO SUPERVISED
CONTROL MODULE
IN FACP
TO ELEVATOR CONTROLLER
(FOR FIRE FIGHTER'S HELMET IN ELEVATOR CAB)
TO ELEVATOR CONTROLLER
(DESIGNATED LEVEL RECALL)
TO ELEVATOR CONTROLLER
(ALTERNATE LEVEL RECALL)
2#12 FOR EACH RELAY IN COMMON 3/4" CONDUIT WITH 1#12G
TO SUPERVISED
CONTROL MODULE
IN FACP
TO SUPERVISED
CONTROL MODULE
IN FACP
H N
3/4"-2#12, 1#12G
TO SUPERVISED CONTROL
MODULE IN FACP
32 WIRING DIAGRAM: FIRE ALARM SYSTEM, FIRE SMOKE DAMPER INTERFACE
NO SCALE
52 WIRING DIAGRAM: FIRE ALARM SYSTEM, ELEVATOR SHUNT TRIP INTERFACE
NONE
54 WIRING DIAGRAM: FIRE ALARM SYSTEM, ELEVATOR CONTROL PANEL INTERFACE
NONE
NO NC
C
FIRE ALARM FSD ENCLOSURE
12"SQ.x4"D NEMA 1 ENCLOSURE
WITH SCREW COVER. PROVIDE
NAMEPLATE ON COVER TO READ
"FSD FIRE ALARM". LOCATE
ENCLOSURE IN ACCESSIBLE CEILING
NEAR ASSOCIATED FSD AND DUCT
DETECTOR LOCATION.
INTER-POSING RELAY -
PROVIDE DPDT RELAY WITH 10A, 120VAC
RATED CONTACTS, 115VAC COIL,
TERMINAL STRIP, MOUNTING TRACK
AND HARDWARE
SHUNT TRIP AT CIRCUIT BREAKER
OF ELEVATOR SERVICE.a
ST
C
C
ELEVATOR SHUNT TRIP ENCLOSURE
NEMA 1 ENCLOSURE WITH SCREW COVER. PROVIDE BOX SIZE TO
SUIT INSTALLATION. NAMEPLATE ON ENCLOSURE COVER TO READ
"FA ELEVATOR SHUNT TRIP ASSEMBLY". LOCATE ENCLOSURE WITHIN
3'-0" OF PANEL E11.
INTER-POSING RELAY:
PROVIDE DPDT RELAY WITH
7A, 24VDC RATED CONTACTS,
120VAC COIL, TERMINAL STRIP,
MOUNTING TRACK AND
HARDWARE. PROVIDE
IDENTIFICATION INDICATING
FUNCTION.
FIRE ALARM ADDRESSABLE
MONITOR MODULE
(FOR SHUNT TRIP POWER LOSS)
C
FIRE ALARM ELEVATOR RELAY ENCLOSURE
NEMA 1 ENCLOSURE WITH SCREW COVER. PROVIDE BOX
SIZE TO SUIT INSTALLATION. PROVIDE NAMEPLATE ON
ENCLOSURE COVER TO READ, "FA ELEVATOR RELAYS."
LOCATE ENCLOSURE WITHIN 3'-0" OF ITS ASSOCIATED THE
ELEVATOR CONTROLLER.
CC INTER-POSING RELAY -
PROVIDE DPDT RELAY WITH 7A, 24VDC
RATED CONTACTS, 18--35VDC COIL, TERMINAL
STRIP, MOUNTING TRACK AND HARDWARE,
TYPICAL OF 3. PROVIDE IDENTIFICATION FOR
EACH RELAY INDICATING ITS FUNCTION.
TERMINAL BLOCK CONNECTION
(TYPICAL)
INTERPOSING RELAY - PROVIDE DPDT RELAY WITH 10A, 120VAC
RATED CONTACTS, 18-35VDC COIL, TERMINAL STRIP, MOUNTING
TRACK AND HARDWARE. PROVIDE IDENTIFICATION INDICATING
FUNCTION.
F
E
1.1
6.01
6.04
6.03
6.05
HDB-1
SB-1
MB-1
SB-2
6.02
6.05
6.01
6.05
VB-1
SPB-1
6.02
RMB-2
DDB-2
DDB-1
RMB-1
6.01 FIRE ALARM ELEVATOR ENCLOSURE - PROVIDE ONE FOR EACH
ELEVATOR CONTROL PANEL. COORDINATE LOCATION IN FIELD
ADJACENT TO ITS ASSOCIATED ELEVATOR CONTROL PANEL. FOR
SCHEMATIC DIAGRAM, REFER TO SHEET FA6.1.1, DETAIL 54.
6.02 REFER TO SHEET FA3.1.0 FOR CONTINUATION.
6.04 SURFACE MOUNT FIRE ALARM DEVICE.
6.05 TO FACP IN THE ELECTRICAL ROOM AT LEVEL 1 ABOVE.
6.03 TO FCPS IN THE ELECTRICAL ROOM AT LEVEL 1 ABOVE.
3801 Miranda Ave., Palo Alto CA
CENTERS FOR AMBULATORY CARE,
POLYTRAUMA AND BLIND REHABILITATION
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management
Seals and Signatures on e ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
301 BATTERY STREET, 7TH FLOOR
SAN FRANCISCO, CA 94111
T 415.227.0100 F 415.908.0862 www.smithgroup.com
The Design Partnership LLP Architects + Planners
1412 VAN NESS AVE., 2ND FLOOR
SAN FRANCISCO, CA 94109
T 415.777.3737 F 415.777.3476 www.dpsf.com
SHEET NOTES
KEYNOTES
Associate Architect:
Department of Veterans Affairs
PR
IN
TE
D
O N
TRUE NORTH
PROJ NORTH
8/ 9/
0:
:4
AM FIRE ALARM DETAILS
FA6.1.1
MGC KG10 MAY 2013
640-424
Recreation Services
SCALE: 1/2" = 1'-0"24 ENLARGED PLAN LEVEL B - ELEVATOR MACHINE ROOM
GRAPHIC SCALE:
0'1' 4'2' 2'
1/2" = 1'-0" eaquino Typewritten Text
1. Equivalent to drawing no. FA3.00 eaquino Typewritten Text eaquino Polygon eaquino
AS-BUILT
01.31.2019 eaquino Typewritten Text eaquino
As-Built
3'-8" (44")
6" *
6'-8" (80") * 7'-0" (84") E.A.N.
SLC-LOOP -
TO NEXT
INITIATING DEVICE
SLC-LOOP -
FROM FACP OR
INITIATING DEVICE
OUTPUT TO NEXT
DEVICE OR EOL
INPUT FROM
FACP OR
PRIOR DEVICE
SLC-LOOP -
FROM FACP OR
INITIATING DEVICE
SLC-LOOP -
TO NEXT
INITIATING DEVICE
AUDIBLE/STROBE
MANUAL PULL STATION
SMOKE DETECTOR
18 FIRE ALARM DEVICE - SCHEMATIC WIRING DIAGRAM
NONE
NOTE: RE: DETAIL FIRE ALARM DEVICE - SCHEMATIC WIRING DIAGRAM:
1. WIRING DIAGRAM SHOWN IS DIAGRAMMATIC AND APPROXIMATE. REFER TO MANUFACTURER'S
DEVICE WIRING DIAGRAMS FOR ACTUAL INSTALLATION REQUIREMENTS.
14 MOUNTING ELEVATIONS
NONE
NOTE: RE: DETAIL MOUNTING ELEVATIONS:
1. REFER TO FLOOR PLANS WHERE SPECIFIC MOUNTING HEIGHTS ARE REQUIRED OTHER THAN
WHAT IS INDICATED.
1(-)
2(+)
STRIP
GAUGE
1 2 3 4
WALL STROBE
OR WALL
AUDIBLE/STROBE
MANUAL PULL STATION
REMOTE KEY TEST SWITCH
WITH ANNUNCIATION
* USE WHICHEVER IS LOWER
FROM CENTER OF HANDLE
CEILING
FLOOR
3801 Miranda Ave., Palo Alto CA
CENTERS FOR AMBULATORY CARE,
POLYTRAUMA AND BLIND REHABILITATION
CONSTRUCTION DOCUMENTS
FULLY SPRINKLERED
Drawing Title
Approved: Project Director
Project Title
Date
Location
Checked
Building Number
Project Number
Drawing Number
Drawn
Revisions: Date
CONSULTANTS: ARCHITECT/ENGINEERS: Office of Construction and Facilities Management
Seals and Signatures on e ei gh th in ch o ne fo ot
B
A
C
D
E
F th re e in ch es o ne fo ot 6"
6" on e an d on e ha lf in ch es o ne fo ot on e in ch o ne fo ot
6" 6" th re e qu ar te rs in ch o ne fo ot on e ha lf in ch o ne fo ot th re e ei gh th s in ch o ne fo ot on e qu ar te r i nc h on e fo ot
VA FORM 08-6231
1 2 3 4 5 6 87 9
F
E
D
C
B
A
97 8654321
301 BATTERY STREET, 7TH FLOOR
SAN FRANCISCO, CA 94111
T 415.227.0100 F 415.908.0862 www.smithgroup.com
The Design Partnership LLP Architects + Planners
1412 VAN NESS AVE., 2ND FLOOR
SAN FRANCISCO, CA 94109
T 415.777.3737 F 415.777.3476 www.dpsf.com
Associate Architect:
Department of Veterans Affairs
PR
IN
TE
D
O N
8/
5/
:0 5:
P
M FIRE ALARM DETAILS
FA6.1.2
MGC KG10 MAY 2013
640-424
Recreation Services eaquino Typewritten Text
AS-BUILT
eaquino Typewritten Text eaquino Typewritten Text Note:
eaquino Typewritten Text Equivalent to drawing no. FA4.00 eaquino Typewritten Text eaquino Typewritten Text
FCPS BATTERY CALCULATION
24.0 HOURS SUPERVISION FCPS
QTY. MANUFACTURER MODEL NUMBER DESCRIPTION CURRENT EXTENSION
1 Notifier FCPS-S8 0.0650 0.0650
1 NAC 1-ST5 0.0000 0.0000
1 NAC 2-ST6 0.0000 0.0000
1 NAC 3-ST7 0.0000 0.0000
1 NAC 4-ST8 0.0000 0.0000
TOTAL : 0.0650
15.0 MIN ALARM
QTY. MANUFACTURER MODEL NUMBER DESCRIPTION CURRENT EXTENSION
1 Notifier FCPS-S8 Remote Power Supply, 8A 0.1450 0.1450 1 NAC 1-ST5 Circuit #1 Alarm Current Draw 0.8000 0.8000 1 NAC 2-ST6 Circuit #2 Alarm Current Draw 0.9780 0.9780 1 NAC 3-ST7 Circuit #3 Alarm Current Draw 0.9920 0.9920 1 NAC 4-ST8 Circuit #4 Alarm Current Draw 0.6720 0.6720
TOTAL : 3.5870
SUPERVISION CURRENT : 24.0 X 0.0650 1.5600
ALARM CURRENT : 0.2500 X 3.5870 0.8968
SAFETY MARGIN : 20.0% 0.4914
STANDBY REQUIRED : 2.9481
BATTERY PROVIDED : 7.0000
RESERVE - AMP HOURS : 4.0519
RESERVE - PERCENTAGE : 57.88%
Remote Power Supply, 8A
Circuit #1 Alarm Current Draw
Circuit #2 Alarm Current Draw
Circuit #3 Alarm Current Draw
Circuit #4 Alarm Current Draw
FACP BATTERY CALCULATION
24.0 HOURS SUPERVISION FACP
QTY. MANUFACTURER MODEL NUMBER DESCRIPTION CURRENT EXTENSION
1 Notifier CPU2-640 0.2500 0.2500
2 Notifier NCA2 0.2000 0.4000
1 Notifier DVCEM 0.4400 0.4400
2 Notifier DVC-KD 0.0600 0.1200
2 Notifier HS-NCM-SF 0.4000 0.8000
1 Notifier 0.4000 0.4000
1 Notifier ACPS-610 0.1300 0.1300
1 NAC 1-ST1 0.0000 0.0000
1 NAC 2-ST2 0.0000 0.0000
NAC 3-ST7-spare 0.0000
NAC 4-ST8-spare 0.0000
TOTAL : 2.5400
15.0 MIN ALARM
QTY. MANUFACTURER MODEL NUMBER DESCRIPTION CURRENT EXTENSION
1 Notifier CPU2-640 NFS2-640 CPU 0.2500 0.2500 2…