5-Addendum 2.pdf

PDF 5 MB Posted

Attached to
Jefferson Avenue Water Main Replacement
Solicitation number
Not on record
Issued by
Lawrence County, Pennsylvania

About this file

This is Addendum 2 to the bidding documents for the Jefferson Avenue Water Main Replacement Project issued by the Myerstown Water Authority in Lebanon County, Pennsylvania. The project encompasses the replacement of water mains on Jefferson Avenue in Myerstown Borough, including the installation of approximately 1,020 linear feet of ductile iron pipe (495 linear feet of 12-inch pipe and 525 linear feet of 8-inch pipe), along with associated fittings, valves, hydrants, and service laterals. The work also includes excavation and removal of road material, restoration of driveways, sidewalks, curbs, and lawns, and pavement restoration on both borough and state roadways. A pre-bid conference was scheduled for July 1, 2026 at 9:00 a.m. at the Myerstown Water Authority's office located at 601 Stracks Dam Road, Myerstown, PA 17067. Sealed proposals were due by 11:00 a.m. prevailing time on July 10, 2026, to be opened and read aloud at Hanover Engineering Associates, Inc., 1438 West Main Street, Suite E, Ephrata, PA 17522. Final questions were due no later than 12:00 p.m. on July 6, 2026, with a final addendum issued by 3:00 p.m. on July 7, 2026. All bidders must submit proposals on all items listed in the bid form and provide a bid bond or other security in the amount of 10 percent of the total base bid, with bids remaining effective for 60 calendar days from the bid opening date.

The contract documents specify unit price work items for materials and labor, with payment based on actual quantities measured and verified by the engineer. Contingency items include additional sand, aggregate, concrete, sheeting and shoring, and pipe fittings, payable only upon engineer direction and verification of incorporation into the work. The project is subject to Pennsylvania Prevailing Wage Act conditions, Federal Occupational Safety and Health Act of 1970 requirements, Pennsylvania Act 287 of 1974 (as amended), the Trade Practices Act of July 23, 1968, and the Public Works Employment Verification Act. Change orders will be executed on a fixed unit price basis for predetermined unit costs, while work change directives may be issued for non-predetermined items with costs determined on a force account basis, allowing for direct costs plus 15 percent markup for contractor overhead and profit. All bid documents are available at no cost online through the PennBid Program at https://pennbid.bonfirehub.com.

View the file

Other files

On GovTribe

Work with this file

  • Download the original file
  • Contacts named in this file
  • Similar government files
  • Ask GovTribe AI about this file

Text version

W . M ai n

St re et , S ui te

E Ep hr at a, P

A

2-

P :71

7.

1.

F:

7.

1.

H an ov er

En g.

co m

La nc as te r- Le ba no n O ffi ce

JEFFERSON AVENUE WATER MAIN REPLACEMENT

MYERSTOWN WATER AUTHORITY

MYERSTOWN BOROUGH

LEBANON COUNTY, PENNSYLVANIA

GENERAL NOTESLIST OF DRAWINGS

Dial 8-1-1 or 1-800-242-1776 | www.paonecall.org

12 JUNE 2026 ERK

UTILITY LISTING

CABLE PROTECTION SERVICES INC

PENNSYLVANIA ELECTRIC CO

MYERSTOWN BOROUGH

LIST OF ABBREVIATIONS

20261630378

MYERSTOWN WATER AUTH

VERIZON NORTH

UGI UTILITIES INC

LOCATION MAP

SCALE: 1" = 1,000'

USGS 7.5' QUAD

BETHEL, PA 2025

PROPOSED WATER

MAIN REPLACEMENT

AutoCAD SHX Text THIS DOCUMENT IS THE PROPERTY OF HANOVER ENGINEERING ASSOCIATES, INC. ANY USE OF A COPY OF THIS DOCUMENT THAT DOES NOT CONTAIN AN ORIGINAL SEAL AND SIGNATURE IS STRICTLY PROHIBITED. THIS DOCUMENT IS NOT PUBLISHED AND ALL RIGHTS ARE RESERVED BY HANOVER ENGINEERING ASSOCIATES, INC. THIS PLAN HAS BEEN SEALED WITH EITHER A RED INK SEAL OR A CRIMP SEAL. IF NEITHER APPEARS ON THIS PLAN, POSSIBLE REPRODUCTIONS OR ALTERATIONS MAY HAVE BEEN MADE WITHOUT THE APPROVAL OR KNOWLEDGE OF THE SIGNATORY.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

NO.

AutoCAD SHX Text

REVISIONS

AutoCAD SHX Text

SEAL:

AutoCAD SHX Text

OF

AutoCAD SHX Text

ERK

AutoCAD SHX Text

FFF

AutoCAD SHX Text

25 JUNE 2026

AutoCAD SHX Text

MWA26-13

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

WATER MAIN REPLACEMENT

AutoCAD SHX Text

COVER SHEET

AutoCAD SHX Text 7/7/26

AutoCAD SHX Text

AutoCAD SHX Text

ADDENDUM 2

AutoCAD SHX Text

MYERSTOWN WATER AUTHORITY LEBANON COUNTY PENNSYLVANIA

AutoCAD SHX Text 1"=1000'

AutoCAD SHX Text

SHEET NO.

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CHECKED BY:

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 1 of 4: COVER SHEET of 4: COVER SHEET 4: COVER SHEET COVER SHEET 2 of 4: PLAN & PROFILE of 4: PLAN & PROFILE 4: PLAN & PROFILE PLAN & PROFILE 3 of 4: PLAN & PROFILE of 4: PLAN & PROFILE 4: PLAN & PROFILE PLAN & PROFILE 4 of 4: PLAN & PROFILE of 4: PLAN & PROFILE 4: PLAN & PROFILE PLAN & PROFILE 1 of 1: PADOT UTILITY PERMIT PLAN of 1: PADOT UTILITY PERMIT PLAN 1: PADOT UTILITY PERMIT PLAN PADOT UTILITY PERMIT PLAN C-55138: JEFFERSON AVENUE ROCK PROFILEJEFFERSON AVENUE ROCK PROFILE

AutoCAD SHX Text

1. THE CONTRACTOR SHALL FIELD VERIFY THE LOCATIONS AND THE CONTRACTOR SHALL FIELD VERIFY THE LOCATIONS AND DEPTH OF EXISTING WATER MAINS, WATER SERVICES, AND WATER MAIN CONNECTION POINTS BY HYDRO-EXCAVATION PRIOR TO THE START OF CONSTRUCTION. 2. THE CONTRACTOR SHALL RESTORE ALL DRIVEWAYS, SIDEWALKS, THE CONTRACTOR SHALL RESTORE ALL DRIVEWAYS, SIDEWALKS, CURBS AND LAWNS IN KIND. 3. ALL WORK IN BOROUGH STREETS AND STATE HIGHWAYS, ALL WORK IN BOROUGH STREETS AND STATE HIGHWAYS, INCLUDING RIGHT-OF-WAYS, SHALL CONFORM TO PENNDOT PUBLICATIONS 213 AND 408, AS APPLICABLE. 4. REQUIREMENTS FOR CONSTRUCTION ARE CONTAINED IN THE REQUIREMENTS FOR CONSTRUCTION ARE CONTAINED IN THE SPECIFICATIONS AND STANDARD DETAILS, AS WELL AS ON THE PLAN SHEETS FOR THIS PROJECT. 5. COPPERHEAD BRAND (OR APPROVED EQUAL), SOLID STRAND, COPPERHEAD BRAND (OR APPROVED EQUAL), SOLID STRAND, 12 GAUGE, BLUE VINYL COATED COPPER TRACER WIRE SHALL BE INSTALLED DIRECTLY ON TOP OF ALL WATER MAINS, HYDRANT SERVICE PIPING, AND BUILDING SERVICE PIPING. BRING THE WIRE UP TO THE GROUND SURFACE AT EACH VALVE BOX AND HYDRANT LOCATION WITH A MINIMUM OF 18-INCHES OF WIRE PROVIDED OUTSIDE OF THE BOX OR HYDRANT TO PERMIT CLAMP-ON OF PIPE DETECTION/LOCATING EQUIPMENT. TIE INTO EXISTING TRACER WIRE IF POSSIBLE. ALL TRACER WIRE CONNECTORS SHALL BE COPPERHEAD BRAND (OR APPROVED EQUAL) WATERPROOF CONNECTORS. 6. MEGA-LUG JOINT RESTRAINTS (OR APPROVED EQUAL) SHALL MEGA-LUG JOINT RESTRAINTS (OR APPROVED EQUAL) SHALL BE PROVIDED AT ALL MECHANICAL JOINTS. 7. ONLY MYERSTOWN WATER AUTHORITY PERSONNEL SHALL ONLY MYERSTOWN WATER AUTHORITY PERSONNEL SHALL OPERATE EXISTING GATE VALVES AND CURB STOPS WITHIN THE DISTRIBUTION SYSTEM. 8. NO DEPTHS FOR ANY GAS MAINS OR SERVICE LINES HAVE NO DEPTHS FOR ANY GAS MAINS OR SERVICE LINES HAVE BEEN PROVIDED VIA UGI UTILITIES, INC. DEPTHS SHALL BE FIELD VERIFIED PRIOR TO CONSTRUCTION.

AutoCAD SHX Text DATE:______________________ BY:____________________ SERIAL NUMBER:______________________________________

AutoCAD SHX Text PO BOX 4816 MIDLOTHIAN, VA. 23112 CONTACT:DEBBIE KING EMAIL:debbie_king@cableps.com PHONE:804-562-3409 341 WHITE POND DRIVE AKRON, OH. 44320 CONTACT:MELLYSSA ADAMS EMAIL:madams@firstenergycorp.com PHONE:330-252-4013 101 S. RAILROAD ST. MYERSTOWN, PA. 17067 CONTACT: BARRY LUDWIG EMAIL: LUDWIG@MYERSTOWNPA.ORG PHONE: 717-866-5826

AutoCAD SHX Text GV GATE VALVE GATE VALVE RDC REDUCER REDUCER DICL DUCTILE IRON CEMENT LINED PIPE DUCTILE IRON CEMENT LINED PIPE HYD HYDRANT HYDRANT EX EXISTING EXISTING MJ MECHANICAL JOINTMECHANICAL JOINT

AutoCAD SHX Text 601 STRACKS DAM RD. MYERSTOWN, PA. 17067 CONTACT: CHRIS STRAUSE EMAIL: CSTRAUSE@MTOWNWA.COM VERIZON NORTH 37 W. 8TH ST. WYOMING, PA. 18644 CONTACT:RONALD SILINSKIE EMAIL: RONALD.SILINSKIE@VERIZON.COM PHONE: 570-826-4263 UGI UTILITIES INC 1301 AIP DR. MIDDLETOWN, PA. 17057-5987 CONTACT: GEOFFREY FERGUSON EMAIL: GFERGUSON@UGI.COM PHONE: 610-807-3118

AutoCAD SHX Text

JEFFERSON AVENUE

AutoCAD SHX Text S.R. 0501

.4

.5

.4

.3

.1

.0

.8

.6

.3

.7

.1

.3

.6

.9

.2

.5

.7

.9

.3

.5

.8

.1

.4

.7

.0

.3

.0

W . M ai n

St re et , S ui te

E Ep hr at a, P

A

2-

7.

1.

F:

7.

1.

H an ov er

En g.

co m

La nc as te r- Le ba no n O ffi ce

WEST JEFFERSON AVENUE

PARK LANE

PARK LANE

N. RAILROAD STREET

N O

RW

ED

G E

L A

N E

VA

LE

N

TI

N E

A

LL

EY

N O

RT

H

C O

LL

EG

E S

TR

EE

T (S

R

WEST JEFFERSON AVENUE WATER MAIN

SCALE:

H: 1" = 20' V: 1=5'

AutoCAD SHX Text

6" STEEL

AutoCAD SHX Text

1.25" POLYETHYLENE

AutoCAD SHX Text

1 W. JEFFERSON AVE. MARTIN/SHIRK

AutoCAD SHX Text

HOUSE

AutoCAD SHX Text

8 W. JEFFERSON AVE. KELLER HOUSE

AutoCAD SHX Text

10 W. JEFFERSON AVE. MOYER/ANSPACH HOUSE

AutoCAD SHX Text

12 W. JEFFERSON AVE. HUIE HOUSE

AutoCAD SHX Text

140 N. COLLEGE ST. LAYSER HOUSE

AutoCAD SHX Text

GARAGE

AutoCAD SHX Text

2 W. JEFFERSON AVE. STAUFFER

AutoCAD SHX Text

4 W. JEFFERSON AVE. MOYER HOUSE

AutoCAD SHX Text

HOUSE 9 W. JEFFERSON AVE. GETTLE

AutoCAD SHX Text

HOUSE 11 W. JEFFERSON AVE. KELLER

AutoCAD SHX Text

HOUSE 15 W. JEFFERSON AVE. GETTLE

AutoCAD SHX Text

200 N. COLLEGE ST. LANG

AutoCAD SHX Text

HOUSE

AutoCAD SHX Text

HOUSE

AutoCAD SHX Text

CUT EX 10" AND INSTALL 10" CAP

AutoCAD SHX Text 45°

AutoCAD SHX Text 45°

AutoCAD SHX Text 45°

AutoCAD SHX Text

REMOVE EX VALVE BOX AND ABANDON VALVE IN PLACE

AutoCAD SHX Text 22.5°

AutoCAD SHX Text 45°

AutoCAD SHX Text

10" GV

AutoCAD SHX Text

REMOVE EX VALVE

AutoCAD SHX Text

CUT EX 6" AND INSTALL 6" CAP

AutoCAD SHX Text 45°

AutoCAD SHX Text ±11'

AutoCAD SHX Text ±11'

AutoCAD SHX Text

EX WATER SERVICE AND CURB BOX TO BE REMOVED (TYP)

AutoCAD SHX Text PROPOSED WATER SERVICE AND CURB BOX. CONCRETE CURB TO BE REPLACED AS NECCESSARY (TYP)

AutoCAD SHX Text

CONNECT NEW WATER SERVICE TO EX WATER SERVICE (TYP)

AutoCAD SHX Text

NOTE: SEWER LATERAL LOCATED ON NORTH RAILROAD ST.

AutoCAD SHX Text

NOTE: SEWER LATERAL LOCATED ON NORTH RAILROAD ST.

AutoCAD SHX Text

NOTE: SEWER LATERAL LOCATED ON NORWEDGE AVE,

AutoCAD SHX Text

NOTE: SEWER LATERAL LOCATED ON NORTH COLLEGE ST.

AutoCAD SHX Text ±11'

AutoCAD SHX Text

NOTE: SEWER LATERAL LOCATED ON NORTH COLLEGE ST.

AutoCAD SHX Text

1.25" GAS MAIN IN STEEL CASE (APPROXIMATE)

AutoCAD SHX Text

1.25" GAS MAIN IN STEEL CASE (APPROXIMATE)

AutoCAD SHX Text

GAS MAIN LOCATION BEYOND THIS POINT IS UNKNOWN

AutoCAD SHX Text

12"X10" RDC

AutoCAD SHX Text

8" GV

AutoCAD SHX Text

CUT EX 10" MAIN AND REMOVE TAPPING SLEEVE AND VALVE

AutoCAD SHX Text

10"X8" RDC

AutoCAD SHX Text

CONNECT TO EX 8" MAIN

AutoCAD SHX Text

8"X8" TEE

AutoCAD SHX Text

EX VALVE TO REMAIN IN PLACE

AutoCAD SHX Text

RESTORE DRIVEWAY WITH 6" 2A SUBBASE AND 3" SPAV 12.5MM SPAV 12.5MM WEARING MIX

AutoCAD SHX Text 8"x8" TEE INSTALLED ON EX 8" MAIN

AutoCAD SHX Text

8" GV

AutoCAD SHX Text 45°

AutoCAD SHX Text 8"x6" HYDRANT TEE

AutoCAD SHX Text 45°

AutoCAD SHX Text

REMOVE EX 6" ROMAC COUPLER AND 8"X6" REDUCER AND CONNECT TO EX 8" MAIN

AutoCAD SHX Text

48" COVER (MIN)

AutoCAD SHX Text

EX GRADE

AutoCAD SHX Text

PADOT LEGAL RIGHT-OF-WAY

AutoCAD SHX Text THIS DOCUMENT IS THE PROPERTY OF HANOVER ENGINEERING ASSOCIATES, INC. ANY USE OF A COPY OF THIS DOCUMENT THAT DOES NOT CONTAIN AN ORIGINAL SEAL AND SIGNATURE IS STRICTLY PROHIBITED. THIS DOCUMENT IS NOT PUBLISHED AND ALL RIGHTS ARE RESERVED BY HANOVER ENGINEERING ASSOCIATES, INC. THIS PLAN HAS BEEN SEALED WITH EITHER A RED INK SEAL OR A CRIMP SEAL. IF NEITHER APPEARS ON THIS PLAN, POSSIBLE REPRODUCTIONS OR ALTERATIONS MAY HAVE BEEN MADE WITHOUT THE APPROVAL OR KNOWLEDGE OF THE SIGNATORY.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

NO.

AutoCAD SHX Text

REVISIONS

AutoCAD SHX Text

SEAL:

AutoCAD SHX Text

OF

AutoCAD SHX Text

ERK

AutoCAD SHX Text

FFF

AutoCAD SHX Text

25 JUNE 2026

AutoCAD SHX Text

MWA26-13

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

WATER MAIN REPLACEMENT

AutoCAD SHX Text

PLAN AND PROFILE

AutoCAD SHX Text

MYERSTOWN WATER AUTHORITY LEBANON COUNTY PENNSYLVANIA

AutoCAD SHX Text 1"=20'

AutoCAD SHX Text

SHEET NO.

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CHECKED BY:

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

JEFFERSON AVENUE

AutoCAD SHX Text

SEE PADOT HIGHWAY OCCUPANCY PERMIT PLANS

AutoCAD SHX Text

MATCH LINE - SHT. 3

AutoCAD SHX Text

MATCH LINE - SHT. 2

AutoCAD SHX Text

PADOT LEGAL RIGHT-OF-WAY

AutoCAD SHX Text

PADOT LEGAL RIGHT-OF-WAY

AutoCAD SHX Text 7/7/26

AutoCAD SHX Text

ADDENDUM 2

.7

.2

.9

.6

.2

.8

.4

.0

.6

.1

.6

.1

.6

.0

.4

.8

.1

.3

.2

.0

.1

.9

.8

.5

.4

W . M ai n

St re et , S ui te

E Ep hr at a, P

A

2-

7.

1.

F:

7.

1.

H an ov er

En g.

co m

La nc as te r- Le ba no n O ffi ce

WEST JEFFERSON AVENUE

WEST JEFFERSON AVENUE WATER MAIN

SCALE:

H: 1" = 20' V: 1=5'

VALVE VAULT

NOT TO SCALE

N O

RT

H

C O

LL

EG

E S

TR

EE

T (S

R

AutoCAD SHX Text

MAILBOX

AutoCAD SHX Text

MAILBOX

AutoCAD SHX Text

199 N. COLLEGE ST.. BOROUGH OF MYERSTOWN

AutoCAD SHX Text

MYERSTOWN BOROUGH PUBLIC LIBRARY

AutoCAD SHX Text

201 N. COLLEGE ST.. MYERSTOWN WATER AUTHORITY

AutoCAD SHX Text

PUMP HOUSE FFE=519.61

AutoCAD SHX Text

AUTOMOTIVE BODY SHOP

AutoCAD SHX Text

110 W. LINCOLN AVE. WAGNER

AutoCAD SHX Text

UNITED STATES POST OFFICE MYERSTOWN BOROUGH

AutoCAD SHX Text

RETAIL SHOP

AutoCAD SHX Text

114 W. LINCOLN AVE. SMITH/HEMPRLY

AutoCAD SHX Text

APPROXIMATE LIMIT OF AERIAL WATER TANK

AutoCAD SHX Text

CONCRETE TANK PEDESTAL FOOTER (TYP)

AutoCAD SHX Text 22.5°

AutoCAD SHX Text 45°

AutoCAD SHX Text

12" GV

AutoCAD SHX Text 11.25°

AutoCAD SHX Text ±11.5'

AutoCAD SHX Text

NOTE: SEWER LATERAL LOCATED ON STATE ROUTE 422.

AutoCAD SHX Text

NOTE: SEWER LATERAL LOCATED ON STATE ROUTE 422.

AutoCAD SHX Text

NOTE: SEWER LATERAL LOCATION UNKNOWN

AutoCAD SHX Text

NOTE: SEWER LATERAL LOCATED ON NORTH COLLEGE ST.

AutoCAD SHX Text

NOTE: SEWER LATERAL LOCATED ON NORTH COLLEGE ST.

AutoCAD SHX Text

1.25" GAS MAIN IN STEEL CASE (APPROXIMATE)

AutoCAD SHX Text 22.5°

AutoCAD SHX Text 45°

AutoCAD SHX Text 45°

AutoCAD SHX Text

12"X10" RDC

AutoCAD SHX Text

REMOVE EX VALVE BOX AND ABANDON VALVE IN PLACE

AutoCAD SHX Text

EX WATER SERVICE AND CURB BOX TO BE REMOVED (TYP)

AutoCAD SHX Text PROPOSED WATER SERVICE AND CURB BOX. CONCRETE CURB TO BE REPLACED AS NECCESSARY (TYP)

AutoCAD SHX Text

EX FH TO BE REMOVED (TYP)

AutoCAD SHX Text

EX VALVE TO BE CLOSED AND VALVE BOX REMOVED

AutoCAD SHX Text

EX VALVE TO BE CLOSED AND VALVE BOX REMOVED

AutoCAD SHX Text

CONNECT NEW SERVICE TO EX METER PIT

AutoCAD SHX Text

CONNECT NEW WATER SERVICE TO EX WATER SERVICE (TYP)

AutoCAD SHX Text

FH

AutoCAD SHX Text

10'X14' VALVE VAULT. PERFORM SIDEWALK AND CURB RESTORATION

AutoCAD SHX Text

CONNECT TO TANK FEED LINE OUTSIDE OF FOOTER WALL WITH 12" COUPLING

AutoCAD SHX Text

12"X12" TEE

AutoCAD SHX Text

EX VALVE TO BE REMOVED

AutoCAD SHX Text

CUT EX 10" AND INSTALL 10" CAP

AutoCAD SHX Text

CONNECT TO EX 10" MAIN

AutoCAD SHX Text

12" GV TO BE INSTALLED OUTSIDE OF PADOT RIGHT-OF-WAY

AutoCAD SHX Text

EX CURB BOX TO BE REMOVED

AutoCAD SHX Text

6"FIRE HYDRANT LINE TO BE REMOVED

AutoCAD SHX Text

12"X6" HYDRANT TEE

AutoCAD SHX Text

6" GV

AutoCAD SHX Text

INSERT-A-VALVE

AutoCAD SHX Text

EX SIGN TO BE REINSTALLED AWAY FROM VAULT LOCATION

AutoCAD SHX Text

12" GV

AutoCAD SHX Text 12"x12" TEE

AutoCAD SHX Text 22.5°

AutoCAD SHX Text 45°

AutoCAD SHX Text

12" GV

AutoCAD SHX Text

12"X10" RDC

AutoCAD SHX Text 10"x10" TEE

AutoCAD SHX Text

CONNECT TO EX 10" DICL

AutoCAD SHX Text

EX GAS (UNKNOWN SIZE AND DEPTH)

AutoCAD SHX Text

EX DEPRESSED CURB/EDGE ROAD

AutoCAD SHX Text

PADOT LEGAL RIGHT-OF-WAY

AutoCAD SHX Text

CONNECT TO EX 10" DICL

AutoCAD SHX Text

12"X10" RDC

AutoCAD SHX Text 22.5°

AutoCAD SHX Text 45°

AutoCAD SHX Text

12" DICL

AutoCAD SHX Text

48" COVER (MIN)

AutoCAD SHX Text

EX GRADE

AutoCAD SHX Text

10" DICL

AutoCAD SHX Text

VALVE VAULT BEYOND

AutoCAD SHX Text THIS DOCUMENT IS THE PROPERTY OF HANOVER ENGINEERING ASSOCIATES, INC. ANY USE OF A COPY OF THIS DOCUMENT THAT DOES NOT CONTAIN AN ORIGINAL SEAL AND SIGNATURE IS STRICTLY PROHIBITED. THIS DOCUMENT IS NOT PUBLISHED AND ALL RIGHTS ARE RESERVED BY HANOVER ENGINEERING ASSOCIATES, INC. THIS PLAN HAS BEEN SEALED WITH EITHER A RED INK SEAL OR A CRIMP SEAL. IF NEITHER APPEARS ON THIS PLAN, POSSIBLE REPRODUCTIONS OR ALTERATIONS MAY HAVE BEEN MADE WITHOUT THE APPROVAL OR KNOWLEDGE OF THE SIGNATORY.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

NO.

AutoCAD SHX Text

REVISIONS

AutoCAD SHX Text

SEAL:

AutoCAD SHX Text

OF

AutoCAD SHX Text

ERK

AutoCAD SHX Text

FFF

AutoCAD SHX Text

25 JUNE 2026

AutoCAD SHX Text

MWA26-13

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

WATER MAIN REPLACEMENT

AutoCAD SHX Text

PLAN AND PROFILE

AutoCAD SHX Text

MYERSTOWN WATER AUTHORITY LEBANON COUNTY PENNSYLVANIA

AutoCAD SHX Text 1"=20'

AutoCAD SHX Text

SHEET NO.

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CHECKED BY:

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

JEFFERSON AVENUE

AutoCAD SHX Text

MATCH LINE - SHT. 3

AutoCAD SHX Text

MATCH LINE - SHT. 2

AutoCAD SHX Text

SEE PADOT HIGHWAY OCCUPANCY PERMIT PLAN AND SHEET 2 OF 4

AutoCAD SHX Text SEAL ALL TONGUE AND GROOVE JOINTS WITH TWO (2) RINGS OF CONSEAL CS-120 BUTYL RUBBER SEALANT OR APPROVED EQUAL. ALL EXTERIOR JOINTS TO BE SEALED WITH WRAPIDSEAL ENCAPSULATION SYSTEM OR APPROVED EQUAL. (TYP)

AutoCAD SHX Text

PIPE SUPPORT (TYP)

AutoCAD SHX Text 12"x12"x4" SUMP (SLOPE FLOOR TO SUMP)

AutoCAD SHX Text

GATE VALVE WITH WHEEL CONTROL

AutoCAD SHX Text ALUMINUM LADDER WITH EXTENDABLE 42" HANDLE BY HALLIDAY PRODUCTS OR APPROVED EQUAL.

AutoCAD SHX Text

ENTIRE PRECAST CONCRETE VAULT (INCLUDING TOP SLAB) TO BE HS-20 LOAD RATED

AutoCAD SHX Text

%%UPLAN VIEW

AutoCAD SHX Text ALUMINUM LADDER WITH EXTENDABLE 42" HANDLE BY HALLIDAY PRODUCTS OR APPROVED EQUAL.

AutoCAD SHX Text

%%USECTION VIEW

AutoCAD SHX Text

12" WATER TANK FEED LINE

AutoCAD SHX Text

PADOT LEGAL RIGHT-OF-WAY

AutoCAD SHX Text

PADOT LEGAL RIGHT-OF-WAY

AutoCAD SHX Text 7'

AutoCAD SHX Text

BOTTOM PIPE 12" WATER TANK FEED ELEV. = 511.60

AutoCAD SHX Text

TOP VAULT DOOR ELEV. = 519.45 (OR MATCH EXISTING SIDEWALK ELEV.)

AutoCAD SHX Text

TOP PAVING ELEV. = 518.80

AutoCAD SHX Text

NEW TOP CURB ELEV. = 519.45

AutoCAD SHX Text

BTM 6" SUBBASE/TOP VAULT ELEV. = ±517.80

AutoCAD SHX Text

INTERIOR TOP VAULT ELEV. = 516.60

AutoCAD SHX Text

INTERIOR BTM VAULT ELEV. =509.60

AutoCAD SHX Text 2'

AutoCAD SHX Text PROPOSED 72" x 60" SERIES W2R7260 ACCESS DOOR WITH SS PNEUMATIC ASSIST AUTOMATIC HOLD-OPEN ARM AND FLUSH MOUNTED LOCKABLE HANDLE BY HALLIDAY PRODUCTS OR APPROVED EQUAL

AutoCAD SHX Text

BUTTERFLY VALVE WITH REMOTE ACTUATOR

AutoCAD SHX Text

BUTTERFLY VALVE WITH REMOTE ACTUATOR

AutoCAD SHX Text

GATE VALVE WITH WHEEL CONTROL (TYP)

AutoCAD SHX Text

LINK SEAL (TYP)

AutoCAD SHX Text

LINK SEAL (TYP)

AutoCAD SHX Text

PIPE SUPPORT LOCATION (TYP)

AutoCAD SHX Text

12" WATER TANK FEED LINE

AutoCAD SHX Text

12" BYPASS PIPE

AutoCAD SHX Text

12" (COMPACTED DEPTH) #57 STONE LEVELING BED

AutoCAD SHX Text NOTE: ALL ELECTRICAL LAYOUT/INSTALLATION AND VALVE AUTOMATION LAYOUT/INSTALLATION SHALL BE PERFORMED BY OTHERS.

AutoCAD SHX Text TESTING TAP INSTALLED TOP CENTER OF PIPE; CORPORATION STOP WITH BRASS BALL VALVE WITH HANDLE

AutoCAD SHX Text 7/7/26

AutoCAD SHX Text

AutoCAD SHX Text

ADDENDUM 2

AutoCAD SHX Text

PIPE LENGTHS AND FITTINGS TO BE DETERMINED BY FIELD CONDITIONS

AutoCAD SHX Text PROPOSED 72" x 60" SERIES W2R7260 ACCESS DOOR WITH SS PNEUMATIC ASSIST AUTOMATIC HOLD-OPEN ARM AND FLUSH MOUNTED LOCKABLE HANDLE BY HALLIDAY PRODUCTS OR APPROVED EQUAL

AutoCAD SHX Text ±2.5'

AutoCAD SHX Text ±2.5'

AutoCAD SHX Text ±3'

AutoCAD SHX Text ±1.5'

ENTIRE PRECAST CONCRETE VAULT (INCLUDING TOP SLAB) TO BE HS-20 LOAD RATED

W . M ai n

St re et , S ui te

E Ep hr at a, P

A

2-

7.

1.

F:

7.

1.

H an ov er

En g.

co m

La nc as te r- Le ba no n O ffi ce

FIRE HYDRANT

NOT TO SCALE

PIPE BEDDING

NOT TO SCALE

PAVED TEMPORARY

TRENCH RESTORATION

NOT TO SCALE

MAXIMUM TRENCH &

REPAVEMENT WIDTHS

NOT TO SCALE

MECHANICAL RESTRAINING DEVICES

NOT TO SCALE

UTILITY LINE SEPARATION

NOT TO SCALE

WATER SERVICE TRENCH

NOT TO SCALE

WATER SERVICE CONNECTION

NOT TO SCALE

SHALLOW WATER SERVICE CONNECTION

NOT TO SCALE

CURB & SIDEWALK RESTORATION (SERVICES)

NOT TO SCALE

GATE VALVE

NOT TO SCALE

PAVED AND UNPAVED PERMANENT

TRENCH RESTORATION

NOT TO SCALE

CONCRETE SIDEWALK

NOT TO SCALE

CONCRETE CURB

NOT TO SCALE

AutoCAD SHX Text THIS DOCUMENT IS THE PROPERTY OF HANOVER ENGINEERING ASSOCIATES, INC. ANY USE OF A COPY OF THIS DOCUMENT THAT DOES NOT CONTAIN AN ORIGINAL SEAL AND SIGNATURE IS STRICTLY PROHIBITED. THIS DOCUMENT IS NOT PUBLISHED AND ALL RIGHTS ARE RESERVED BY HANOVER ENGINEERING ASSOCIATES, INC. THIS PLAN HAS BEEN SEALED WITH EITHER A RED INK SEAL OR A CRIMP SEAL. IF NEITHER APPEARS ON THIS PLAN, POSSIBLE REPRODUCTIONS OR ALTERATIONS MAY HAVE BEEN MADE WITHOUT THE APPROVAL OR KNOWLEDGE OF THE SIGNATORY.

AutoCAD SHX Text

DATE

AutoCAD SHX Text

NO.

AutoCAD SHX Text

REVISIONS

AutoCAD SHX Text

SEAL:

AutoCAD SHX Text

OF

AutoCAD SHX Text

ERK

AutoCAD SHX Text

FFF

AutoCAD SHX Text

25 JUNE 2026

AutoCAD SHX Text

MWA26-13

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

WATER MAIN REPLACEMENT

AutoCAD SHX Text

DETAILS

AutoCAD SHX Text

MYERSTOWN WATER AUTHORITY LEBANON COUNTY PENNSYLVANIA

AutoCAD SHX Text

NOT TO SCALE

AutoCAD SHX Text

SHEET NO.

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CHECKED BY:

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

JEFFERSON AVENUE

AutoCAD SHX Text

4'-0" MIN COVER

AutoCAD SHX Text

VARIABLE

AutoCAD SHX Text

VARIABLE - 4'-0" MIN COVER

AutoCAD SHX Text

CUSTOMER TO CONNECT AT THIS POINT

AutoCAD SHX Text

CUSTOMER SERVICE LINE

AutoCAD SHX Text

CURB STOP (SEE NOTE 5)

AutoCAD SHX Text

WATER DISTRIBUTION MAIN

AutoCAD SHX Text

SYSTEM SERVICE LINE

AutoCAD SHX Text

BRICK SUPPORT

AutoCAD SHX Text

MARKED "WATER" ON LID 12" FROM CURB 24" FROM EDGE OF PAVING

AutoCAD SHX Text

CURB BOX SHALL BE LOCATED IN R/W EASEMENTS

AutoCAD SHX Text

CAST IRON CURB BOX (SEE NOTE 6)

AutoCAD SHX Text NOTES: : 1. CORPORATION STOPS SHALL BE COMPRESSION TYPE AND BE AS MANUFACTURED CORPORATION STOPS SHALL BE COMPRESSION TYPE AND BE AS MANUFACTURED BY MUELLER CO #B-25008N OR AS MANUFACTURED BY FORD METER BOX CO #FB1100-X-G-NL. 2. SERVICE TO BE BEDDED IN SCREENINGS. SERVICE TO BE BEDDED IN SCREENINGS. 3. DO NOT LOCATE CURB BOX IN SIDEWALK OR DRIVEWAY. DO NOT LOCATE CURB BOX IN SIDEWALK OR DRIVEWAY. 4. THERE SHALL BE A MINIMUM 5 FOOT SPACING BETWEEN CORPORATION STOPS IN THERE SHALL BE A MINIMUM 5 FOOT SPACING BETWEEN CORPORATION STOPS IN A MAIN. 5. CURB STOPS SHALL BE COMPRESSION TYPE AND BE AS MANUFACTURED BY CURB STOPS SHALL BE COMPRESSION TYPE AND BE AS MANUFACTURED BY MUELLER CO #B-25209N OR AS MANUFACTURED BY FORD METER BOX CO #B44-XXX-Q-NL. 6. CURB BOXES AND COVERS SHALL BE AS MANUFACTURED BY BINGHAM & TAYLOR CURB BOXES AND COVERS SHALL BE AS MANUFACTURED BY BINGHAM & TAYLOR #93-E WITH COVER TYPE NO. 4901-B OR AS MANUFACTURED BY TYLER PIPE #93-E.

AutoCAD SHX Text

CORPORATION STOP (SEE NOTE 1)

AutoCAD SHX Text

1" COPPER OR POLYETHYLENE (CTS)

AutoCAD SHX Text

1" COPPER OR POLYETHYLENE (CTS)

AutoCAD SHX Text

4'-0" MIN COVER

AutoCAD SHX Text

VARIABLE

AutoCAD SHX Text

VARIABLE - 4'-0" MIN COVER

AutoCAD SHX Text

GRADE

AutoCAD SHX Text

CURB STOP

AutoCAD SHX Text

CUSTOMER SERVICE LINE

AutoCAD SHX Text

EXISTING CURB BOX

AutoCAD SHX Text

CURB BOX SHALL BE LOCATED IN R/W EASEMENTS

AutoCAD SHX Text

CAST IRON CURB BOX SHALL BE TWO-PIECE TYPE, TYLER MODEL #6500 OR APPROVED EQUAL

AutoCAD SHX Text

MARKED "WATER" ON LID 12" FROM CURB 24" FROM EDGE OF PAVING

AutoCAD SHX Text

SYSTEM SERVICE LINE

AutoCAD SHX Text

CUSTOMER TO CONNECT AT THIS POINT

AutoCAD SHX Text

WATER DISTRIBUTION MAIN

AutoCAD SHX Text

CORPORATION STOP

AutoCAD SHX Text

BRICK SUPPORT

AutoCAD SHX Text

18"-24" APPROX COVER

AutoCAD SHX Text

CUSTOMER TO CONNECT AT THIS POINT

AutoCAD SHX Text

LEAD SERVICES SHALL BE REPLACED

AutoCAD SHX Text

EX SIDEWALK (WIDTH VARIES)

AutoCAD SHX Text

BACK EDGE OF EX SIDEWALK OR BUILDING WALL

AutoCAD SHX Text

EX GRASS BUFFER STRIP

AutoCAD SHX Text 24"

AutoCAD SHX Text

SAWCUT AND REPLACE CONCRETE SIDEWALK

AutoCAD SHX Text

WATER SERVICE

AutoCAD SHX Text

REPLACE EX CURB (24" WIDTH)

AutoCAD SHX Text

TOPSOIL AND SEEDING

AutoCAD SHX Text

NO BUFFER STRIP

AutoCAD SHX Text

WITH BUFFER STRIP

AutoCAD SHX Text

WATER MAIN

AutoCAD SHX Text 8"

AutoCAD SHX Text O.D.

AutoCAD SHX Text 8"

AutoCAD SHX Text

12" (MIN)

AutoCAD SHX Text

O.D. 4 (6" MIN)

AutoCAD SHX Text

AASHTO #8 CRUSHED STONE

AutoCAD SHX Text

TRENCH SUBGRADE

AutoCAD SHX Text

SIGNAL WIRE

AutoCAD SHX Text

PAVED AREAS

AutoCAD SHX Text

EXISTING PAVED SURFACE

AutoCAD SHX Text

2A AGGREGATE BACKFILL COMPACTED IN 12" LIFTS

AutoCAD SHX Text

MAXIMUM PAYMENT WIDTH FOR REPAVING

AutoCAD SHX Text

4'-0" MIN COVER

AutoCAD SHX Text

TRENCH DEPTH

AutoCAD SHX Text 6"

AutoCAD SHX Text 8"

AutoCAD SHX Text 8"

AutoCAD SHX Text O.D.

AutoCAD SHX Text

MAX TRENCH WIDTH AT TOP OF PIPE

AutoCAD SHX Text

REPAVING, SEE WATER\W003, W007, W008, AND W009 FOR DETAILS

AutoCAD SHX Text

TRENCH DEPTH

AutoCAD SHX Text

MAXIMUM PAYMENT WIDTH - REPAVING

AutoCAD SHX Text 0' - 12'

AutoCAD SHX Text O.D. + 3'-4"

AutoCAD SHX Text 12' - 18'

AutoCAD SHX Text O.D. + 4'-4"

AutoCAD SHX Text 18' - 24'

AutoCAD SHX Text O.D. + 5'-4"

AutoCAD SHX Text 24' - 30'

AutoCAD SHX Text O.D. + 6'-4"

AutoCAD SHX Text L

AutoCAD SHX Text L

AutoCAD SHX Text L

AutoCAD SHX Text L

AutoCAD SHX Text L

AutoCAD SHX Text L

AutoCAD SHX Text L

AutoCAD SHX Text L

AutoCAD SHX Text L

AutoCAD SHX Text L

AutoCAD SHX Text L

AutoCAD SHX Text L

AutoCAD SHX Text L

AutoCAD SHX Text

MINIMUM LENGTH OF PIPE WITH RESTRAINED JOINTS (L) IN FEET

AutoCAD SHX Text

PIPE SIZE

AutoCAD SHX Text 4"

AutoCAD SHX Text 6"

AutoCAD SHX Text 8"

AutoCAD SHX Text 10"

AutoCAD SHX Text 12"

AutoCAD SHX Text 14"

AutoCAD SHX Text 16"

AutoCAD SHX Text 18"

AutoCAD SHX Text 20"

AutoCAD SHX Text 24"

AutoCAD SHX Text

HORIZONTAL BEND

AutoCAD SHX Text 11.25°

AutoCAD SHX Text 22.5°

AutoCAD SHX Text 45°

AutoCAD SHX Text 90°

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

VERTICAL BEND UP

AutoCAD SHX Text 11.25°

AutoCAD SHX Text 22.5°

AutoCAD SHX Text 45°

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

VERTICAL BEND DOWN

AutoCAD SHX Text 11.25°

AutoCAD SHX Text 22.5°

AutoCAD SHX Text 45°

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

DEAD END OR VALVE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

UNIFORM SIZE TEE OR WYE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

UNIFORM SIZE TEE OR WYE

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text NOTES: : 1. RESTRAINING DEVICES OR RESTRAINED JOINTS SHALL HAVE A WORKING PRESSURE OF 250 PSI WITH A MINIMUM SAFETY FACTOR OF 2.0. RESTRAINING DEVICES OR RESTRAINED JOINTS SHALL HAVE A WORKING PRESSURE OF 250 PSI WITH A MINIMUM SAFETY FACTOR OF 2.0. 2. RESTRAINED LENGTH SHOWN IS BASED ON 3' OF COVER, SOIL TYPE CL, TRENCH TYPE 2, 2:1 SAFETY FACTOR, AND DUCTILE IRON PIPE AT A TEST RESTRAINED LENGTH SHOWN IS BASED ON 3' OF COVER, SOIL TYPE CL, TRENCH TYPE 2, 2:1 SAFETY FACTOR, AND DUCTILE IRON PIPE AT A TEST PRESSURE OF 150 PSI. IF FIELD CONDITIONS DIFFER FROM THOSE LISTED, CONTACT ENGINEER TO DETERMINE REQUIRED RESTRAINED LENGTH. 3. RESTRAINED LENGTHS SHOWN IN CHART WERE CALCULATED USING METHODOLOGY DEVELOPED BY THE DUCTILE IRON PIPE RESEARCH ASSOCIATION (DIPRA) RESTRAINED LENGTHS SHOWN IN CHART WERE CALCULATED USING METHODOLOGY DEVELOPED BY THE DUCTILE IRON PIPE RESEARCH ASSOCIATION (DIPRA) AND ARE INTENDED AS A GENERAL GUIDE BASED ON CONDITIONS SHOWN IN NOTE 2. FOR FITTINGS AND/OR FIELD CONDITIONS NOT SHOWN, ENGINEER SHALL SUBMIT CALCULATIONS USING DIPRA METHODOLOGY TO THE TOWN FOR APPROVAL. 4. EXISTING PIPE ADJACENT TO PROPOSED BENDS, WYES, VALVES, TEES, AND PLUGS SHALL BE UNCOVERED AND THE JOINTS RESTRAINED FOR THE LENGTHS EXISTING PIPE ADJACENT TO PROPOSED BENDS, WYES, VALVES, TEES, AND PLUGS SHALL BE UNCOVERED AND THE JOINTS RESTRAINED FOR THE LENGTHS INDICATED. IF THE EXISTING PIPE IS UNABLE TO ACCEPT THE MECHANICAL JOINT RESTRAINING MECHANISM, THE EXISTING PIPE SHALL BE REPLACED WITH DUCTILE IRON WATER MAIN IN ACCORDANCE WITH THE SPECIFICATIONS AND RESTRAINED LENGTH INDICATED. IN LIEU OF RESTRAINING JOINTS OF EXISTING PIPE, A BULKHEAD ANCHOR AS SHOWN IN DETAILS CA-1 AND CA-2 MAY BE USED. 5. FIRE HYDRANTS SHALL BE RESTRAINED AT EACH JOINT IN THE ASSEMBLY. FIRE HYDRANTS SHALL BE RESTRAINED AT EACH JOINT IN THE ASSEMBLY. 6. ALL JOINTS WITHIN CASING PIPES SHALL BE RESTRAINED. ALL JOINTS WITHIN CASING PIPES SHALL BE RESTRAINED. 7. IF A CASING PIPE FALLS WITHIN THE RESTRAINED LENGTH "L", THE REQUIRED RESTRAINED LENGTH SHALL BE INCREASED BY THE LENGTH OF THE CASING. IF A CASING PIPE FALLS WITHIN THE RESTRAINED LENGTH "L", THE REQUIRED RESTRAINED LENGTH SHALL BE INCREASED BY THE LENGTH OF THE CASING. 8. THRUST RESTRAINTS SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS AND SHALL CONFORM TO THE FOLLOWING THRUST RESTRAINTS SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS AND SHALL CONFORM TO THE FOLLOWING TABLE OR APPROVED EQUAL. SHOP DRAWINGS FOR ALTERNATE RESTRAINTS SHALL BE SUBMITTED TO THE TOWN FOR APPROVAL PRIOR TO CONSTRUCTION.

AutoCAD SHX Text L

AutoCAD SHX Text L

AutoCAD SHX Text

VALVE

AutoCAD SHX Text

BEND

AutoCAD SHX Text

TEE

AutoCAD SHX Text

DEAD END

AutoCAD SHX Text

REDUCER

AutoCAD SHX Text

WYE

AutoCAD SHX Text

CONNECTION TO EXISTING MAIN

AutoCAD SHX Text

IF LESS THAN "L" RESTRAIN ALL JOINTS

AutoCAD SHX Text

RESTRAIN ALL JOINTS WITHIN DISTANCE "L" FROM FITTING

AutoCAD SHX Text

EXISTING MAIN

AutoCAD SHX Text

RESTRAIN ALL JOINTS WITHIN DISTANCE "L" FROM FITTING

AutoCAD SHX Text PIPE SIZE JOINT TYPE SPECIFICATION JOINT TYPE SPECIFICATION SPECIFICATION 4"-12" MECHANICAL JOINT ROMAC INDUSTRIES GRIP RING, ROMAGRIP OR MEGALUG SERIES 1100 MECHANICAL JOINT ROMAC INDUSTRIES GRIP RING, ROMAGRIP OR MEGALUG SERIES 1100 ROMAC INDUSTRIES GRIP RING, ROMAGRIP OR MEGALUG SERIES 1100 4"-12" PUSH-ON OR COUPLING ROMAC INDUSTRIES 611 OR MEGALUG SERIES 1700 PUSH-ON OR COUPLING ROMAC INDUSTRIES 611 OR MEGALUG SERIES 1700 ROMAC INDUSTRIES 611 OR MEGALUG SERIES 1700 4"-12" COUPLING ROMAC INDUSTRIES ALPHA COUPLING COUPLING ROMAC INDUSTRIES ALPHA COUPLING ROMAC INDUSTRIES ALPHA COUPLING

AutoCAD SHX Text

18" (MIN) VERTICAL SEPARATION

AutoCAD SHX Text

18" (MIN) VERTICAL SEPARATION

AutoCAD SHX Text

WATER MAIN

AutoCAD SHX Text

WATER MAIN

AutoCAD SHX Text

18" (MIN) VERTICAL SEPARATION

AutoCAD SHX Text

3'-0" (MIN) HORIZONTAL SEPARATION

AutoCAD SHX Text

18" (MIN) VERTICAL SEPARATION

AutoCAD SHX Text

10'-0" (MIN) HORIZONTAL SEPARATION

AutoCAD SHX Text

OVER SEWER OR DRAIN LINE

AutoCAD SHX Text

WATER MAIN CROSSING UNDER SEWER OR DRAIN LINE

AutoCAD SHX Text NOTES: : 1. IF MINIMUM HORIZONTAL SEPARATION CANNOT BE IF MINIMUM HORIZONTAL SEPARATION CANNOT BE MAINTAINED, THE WATER MAIN SHALL BE CONSTRUCTED SO AS TO MAINTAIN MINIMUM VERTICAL SEPARATION.

AutoCAD SHX Text

GAS MAIN

AutoCAD SHX Text

WATER MAIN

AutoCAD SHX Text

SANITARY SEWER

AutoCAD SHX Text

BUILDING DRAIN, SANITARY SEWER OR STORM SEWER

AutoCAD SHX Text

BUILDING DRAIN, SANITARY SEWER OR STORM SEWER

AutoCAD SHX Text 6"

AutoCAD SHX Text 12"

AutoCAD SHX Text

PIPE

AutoCAD SHX Text

48" MIN COVER

AutoCAD SHX Text

OD+12" MINIMUM 18" MAXIMUM TRENCH WIDTH

AutoCAD SHX Text

MARKING TAPE

AutoCAD SHX Text

STONE DUST OR SAND

AutoCAD SHX Text

SEE RESTORATION DETAILS

AutoCAD SHX Text

REQUIRED BACKFILL (SEE DETAILS)

AutoCAD SHX Text

PIPE

AutoCAD SHX Text

ROAD SAWCUT (TYP)

AutoCAD SHX Text

EXISTING ROAD OR SHOULDER

AutoCAD SHX Text

SIGNAL WIRE

AutoCAD SHX Text

4'-0" MIN

AutoCAD SHX Text

6" DIP

AutoCAD SHX Text 2'-0"

AutoCAD SHX Text

2'-0" MIN: IF LESS THAN 10', RODS ARE REQ'D

AutoCAD SHX Text

FINISHED GRADE

AutoCAD SHX Text 1'-6"

AutoCAD SHX Text

UNDISTURBED EARTH

AutoCAD SHX Text

#AASHTO #57 CRUSHED STONE

AutoCAD SHX Text

AVOID BLOCKING HYDRANT DRAIN HOLE

AutoCAD SHX Text

TEE IN WATER MAIN

AutoCAD SHX Text

(2) 2-1/2" HOSE NOZZLES

AutoCAD SHX Text

(1) 4-1/2" PUMPER NOZZLE W/ 5" STORZ NOZZLE

AutoCAD SHX Text

CAST IRON

AutoCAD SHX Text

6" GATE VALVE

AutoCAD SHX Text

1. HYDRANT USE MAY BE RESTRAINED WITH TIE RODS, CLAMPS, OR MEGA-LUGS IN HYDRANT USE MAY BE RESTRAINED WITH TIE RODS, CLAMPS, OR MEGA-LUGS IN A MANNER APPROVED BY THE AUTHORITY. 2. FIRE HYDRANT SHALL BE LOCATED 2.5' BEHIND THE FACE OF CURB WHERE FIRE HYDRANT SHALL BE LOCATED 2.5' BEHIND THE FACE OF CURB WHERE ESTABLISHED. OTHERWISE, FIRE HYDRANT SHALL BE LOCATED 2.5' FROM THE EDGE OF ROAD R/W. (MEASURED FROM TIP OF PUMPER NOZZLE) OR AS DIRECTED BY THE WATER AUTHORITY. THE MAXIMUM DISTANCE THAT WILL BE ALLOWED BY THE AUTHORITY IS 6' BEHIND CURB. 3. NO PART OF HYDRANT SHALL PROJECT BEYOND THE FACE OF CURB. NO PART OF HYDRANT SHALL PROJECT BEYOND THE FACE OF CURB. 4. SEE SECTION 15180 OF THE STANDARD SPECIFICATIONS AND ITS AMENDMENTS. SEE SECTION 15180 OF THE STANDARD SPECIFICATIONS AND ITS AMENDMENTS. 5. MANUFACTURER SHALL PAINT HYDRANT BODY RED. BONNET AND CAPS WHITE. MANUFACTURER SHALL PAINT HYDRANT BODY RED. BONNET AND CAPS WHITE. 6. NO OBSTRUCTIONS OF ANY KIND SHALL BE PERMITTED WITHIN 3' OF A HYDRANT. NO OBSTRUCTIONS OF ANY KIND SHALL BE PERMITTED WITHIN 3' OF A HYDRANT. 7. LIST OF APPROVED FIRE HYDRANTS: LIST OF APPROVED FIRE HYDRANTS: WATEROUS COMPANY: PACER MODEL PACER MODEL MUELLER COMPANY : SUPER CENTURION 250: SUPER CENTURION 250SUPER CENTURION 250

AutoCAD SHX Text

NOTES::

AutoCAD SHX Text

%%UELEVATION

AutoCAD SHX Text %%uSECTION A-A

AutoCAD SHX Text 3-PIECE SCREW TYPE VALVE BOX DARLING VALVE & MFG CO #1321, MUELLER CO #H-10357, TYLER #6860 SERIES, OR APPROVED EQUAL.

AutoCAD SHX Text

COVER MARKED "WATER"

AutoCAD SHX Text A

AutoCAD SHX Text A

AutoCAD SHX Text

5 " SHAFT14" SHAFT

AutoCAD SHX Text

AASHTO #8 CRUSHED STONE BEDDING AND BACKFILL MATERIAL

AutoCAD SHX Text

PROVIDE 2" RISER FOR VALVE BOXES LOCATED IN PAVED SURFACES

AutoCAD SHX Text

12" MIN

AutoCAD SHX Text

6" MIN

AutoCAD SHX Text

MARKING TAPE

AutoCAD SHX Text NOTES: : 1. BOTH THE WATER AND SEWER LINE SHALL BE BOTH THE WATER AND SEWER LINE SHALL BE CONSTRUCTED OF CAST IRON OR DUCTILE IRON HAVING MECHANICAL JOINTS. 2. THE LENGTH OF THE WATER LINE PIPE SHALL BE THE LENGTH OF THE WATER LINE PIPE SHALL BE CENTERED AT THE POINT OF THE CROSSING SO THAT THE JOINTS ARE EQUIDISTANT AND AS FAR AS POSSIBLE FROM THE SEWER. 3. THE SANITARY SEWER SHALL BE CONCRETE THE SANITARY SEWER SHALL BE CONCRETE ENCASED FOR 10 FEET ON EITHER SIDE OF THE WATER CROSSING WHEN LESS THAN 18" VERTICAL SEPARATION IS MAINTAINED.

AutoCAD SHX Text NOTES: : 1. BOTH THE WATER AND SEWER LINE SHALL BE BOTH THE WATER AND SEWER LINE SHALL BE CONSTRUCTED OF CAST IRON OR DUCTILE IRON HAVING MECHANICAL JOINTS. 2. THE SEWER SHALL HAVE ADEQUATE THE SEWER SHALL HAVE ADEQUATE STRUCTURAL SUPPORT TO PREVENT EXCESSIVE DEFLECTION OF THE JOINTS AND THE SETTLING ON AND BREAKING OF THE WATER LINE. 3. THE LENGTH OF THE WATER LINE PIPE SHALL THE LENGTH OF THE WATER LINE PIPE SHALL BE CENTERED AT THE POINT OF THE CROSSING SO THAT THE JOINTS ARE EQUIDISTANT AND AS FAR AS POSSIBLE FROM THE SEWER. 4. THE WATER MAIN SHALL BE CONCRETE THE WATER MAIN SHALL BE CONCRETE ENCASED FOR 10 FEET ON EITHER SIDE OF THE SEWER CROSSING WHEN LESS THAN 18" VERTICAL SEPARATION IS MAINTAINED.

AutoCAD SHX Text SUPERPAVE HMA BINDER COURSE, PG64S-22, 0 to 0.3 MILLION ESALs, 19mm MIX, 2-1/2" DEPTH

AutoCAD SHX Text NOTE: 1. CURB TO CURB PERMANENT PAVING ACTIVITIES ON WEST JEFFERSON CURB TO CURB PERMANENT PAVING ACTIVITIES ON WEST JEFFERSON AVENUE FROM NORTH RAILROAD STREET TO NORTH COLLEGE STREET (S.R. 501) IS TO BE COMPLETED BY MYERSTOWN BOROUGH IN SEPTEMBER 2026. 2. PERMANENT TRENCH RESTORATION PAVING ON WEST JEFFERSON AVENUE PERMANENT TRENCH RESTORATION PAVING ON WEST JEFFERSON AVENUE FROM NORTH COLLEGE STREET (S.R. 501) WESTWARD TO THE DEAD END OF WEST JEFFERSON AVENUE SHALL BE COMPLETED BY THE WATER MAIN CONTRACTOR.

AutoCAD SHX Text

SEE PIPE BEDDING DETAIL, THIS SHEET

AutoCAD SHX Text NOTES: : 1. ALL BACK FILL MATERIAL IS SUBJECT TO ENGINEER APPROVAL. ALL BACK FILL MATERIAL IS SUBJECT TO ENGINEER APPROVAL. * COMPACT IN ACCORDANCE W/MOST RECENT REVISION OF PENNDOT PUBLICATION 408, "STANDARD SPECIFICATIONS"

AutoCAD SHX Text NOTES: : 1. CORPORATION STOPS SHALL BE COMPRESSION TYPE AND BE AS MANUFACTURED CORPORATION STOPS SHALL BE COMPRESSION TYPE AND BE AS MANUFACTURED BY MUELLER CO #B-25008N OR AS MANUFACTURED BY FORD METER BOX CO #FB1100-X-G-NL. 2. SERVICE TO BE BEDDED IN SCREENINGS. SERVICE TO BE BEDDED IN SCREENINGS. 3. DO NOT LOCATE CURB BOX IN SIDEWALK OR DRIVEWAY. DO NOT LOCATE CURB BOX IN SIDEWALK OR DRIVEWAY. 4. THERE SHALL BE A MINIMUM 5 FOOT SPACING BETWEEN CORPORATION STOPS IN THERE SHALL BE A MINIMUM 5 FOOT SPACING BETWEEN CORPORATION STOPS IN A MAIN. 5. CURB STOPS SHALL BE COMPRESSION TYPE AND BE AS MANUFACTURED BY CURB STOPS SHALL BE COMPRESSION TYPE AND BE AS MANUFACTURED BY MUELLER CO #B-25209N OR AS MANUFACTURED BY FORD METER BOX CO #B44-XXX-Q-NL. 6. CURB BOXES AND COVERS SHALL BE AS MANUFACTURED BY BINGHAM & TAYLOR CURB BOXES AND COVERS SHALL BE AS MANUFACTURED BY BINGHAM & TAYLOR #93-E WITH COVER TYPE NO. 4901-B OR AS MANUFACTURED BY TYLER PIPE #93-E.

AutoCAD SHX Text

UNPAVED AREAS

AutoCAD SHX Text APPROVED SUITABLE BACKFILL IN ACCORDANCE WITH THE SPECIFICATIONS TAMPED IN 12" LIFTS

AutoCAD SHX Text

6" (MIN) TOPSOIL

AutoCAD SHX Text

12" (MIN)

AutoCAD SHX Text

12" (MIN)

AutoCAD SHX Text

7" 2A SUBBASE

AutoCAD SHX Text NOTES: : 1. ALL BACK FILL MATERIAL IS SUBJECT TO ENGINEER APPROVAL. ALL BACK FILL MATERIAL IS SUBJECT TO ENGINEER APPROVAL. * COMPACT IN ACCORDANCE W/MOST RECENT REVISION OF PENNDOT PUBLICATION 408, "STANDARD SPECIFICATIONS"

AutoCAD SHX Text SUPERPAVE ASPHALT BINDER COURSE 25 MM, PG64S-22, 30 MILLION ESALs, 5.5" DEPTH. NOTE: BINDER COURSE SHALL BE INSTALLED IN TWO (2) SEPARATE LIFTS WITH THE FIRST LIFT NOT EXCEEDING THREE (3) INCHES COMPACTED DEPTH.

AutoCAD SHX Text

SAWCUT (TYP)

AutoCAD SHX Text

PENNDOT 2A STONE

AutoCAD SHX Text

SEE PIPE BEDDING DETAIL, THIS SHEET

AutoCAD SHX Text

PAVED AREAS

AutoCAD SHX Text

SEE PIPE BEDDING DETAIL, THIS SHEET

AutoCAD SHX Text

BACKFILL COMPACTED IN 12" LIFTS

AutoCAD SHX Text

MATCH EXISTING

AutoCAD SHX Text NOTES: : 1. SIDEWALK SHALL HAVE A MINIMUM THICKNESS OF 4" WHERE SIDEWALK SHALL HAVE A MINIMUM THICKNESS OF 4" WHERE USED SOLELY FOR PEDESTRIAN TRAFFIC. 2. MAXIMUM LENGTH OF SECTIONS SHALL BE 10'. MAXIMUM LENGTH OF SECTIONS SHALL BE 10'. 3. TO MINIMIZE OR PREVENT VERTICAL SEPARATION WHERE NEW TO MINIMIZE OR PREVENT VERTICAL SEPARATION WHERE NEW SIDEWALK ADJOINS EXISTING CONCRETE STRUCTURES, CURBING, OR SIDEWALK, 12" LONG 5/8" REBAR DOWELS SHALL BE INSTALLED (6" DEPTH) INTO THE EXISTING CONCRETE TO TIE THE NEW SIDEWALK TO THE EXISTING.

AutoCAD SHX Text CLASS A CEMENT CONCRETE (3000 PSI) WITH BROOM FINISH, 4" MIN THICKNESS-SEE NOTE 1

AutoCAD SHX Text

AASHTO NO. 57 (2B) COARSE AGGREGATE 4" DEPTH (SEE NOTE 2)

AutoCAD SHX Text

14" PER FOOT

AutoCAD SHX Text

20'-0" MAX. TO 4'-0" MIN.

AutoCAD SHX Text

CONTRACTION JOINT SPACING

AutoCAD SHX Text

(SEE NOTE 5)

AutoCAD SHX Text NOTES: : 1. MATERIALS AND CONSTRUCTION SHALL MEET THE REQUIREMENTS OF PUBLICATION 408, SECTION 630. MATERIALS AND CONSTRUCTION SHALL MEET THE REQUIREMENTS OF PUBLICATION 408, SECTION 630. 2. USE ACCEPTABLE METAL FORMS, EXCEPT ON SHARP CURVES AND SHORT TANGENT SECTIONS, WHERE WOOD FORMS MAY BE USE ACCEPTABLE METAL FORMS, EXCEPT ON SHARP CURVES AND SHORT TANGENT SECTIONS, WHERE WOOD FORMS MAY BE USED. USE FORMS WHICH WILL NOT DISCOLOR THE CONCRETE. 3. PLACE CONCRETE IN THE FORMS IN LAYERS NOT EXCEEDING 5" IN DEPTH WHEN SPADING, OR LAYERS NOT EXCEEDING 15" IN PLACE CONCRETE IN THE FORMS IN LAYERS NOT EXCEEDING 5" IN DEPTH WHEN SPADING, OR LAYERS NOT EXCEEDING 15" IN DEPTH WHEN USING A VIBRATOR TO ELIMINATE VOIDS. PROVIDE DRAINAGE OPENINGS THROUGH THE CURB, AT THE ELEVATION AND OF THE SIZE REQUIRED, WHERE INDICATED OR DIRECTED. SMOOTHLY AND EVENLY FINISH THE TOP SURFACE OF THE CURB, USING A WOOD FLOAT. 4. THE CONCRETE CURB MAY BE PLACED WITH AN ACCEPTABLE, SELF PROPELLED MACHINE. THE CONCRETE CURB MAY BE PLACED WITH AN ACCEPTABLE, SELF PROPELLED MACHINE. 5. SPACE CONTRACTION JOINTS IN UNIFORM LENGTHS OR SECTIONS. SPACE CONTRACTION JOINTS IN UNIFORM LENGTHS OR SECTIONS. 6. PLACE 3/4" PREMOLDED EXPANSION JOINT FILLER MATERIAL AT STRUCTURES AND AT THE END OF THE WORK DAY. CUT PLACE 3/4" PREMOLDED EXPANSION JOINT FILLER MATERIAL AT STRUCTURES AND AT THE END OF THE WORK DAY. CUT MATERIAL TO CONFORM TO AREA ADJACENT TO CURB OR TO CONFORM TO CROSS SECTIONAL AREA OF CURB. 7. CURB SHALL BE PLACED AT A DEPTH OF 24" ALONG THE SOUTHERN CURB LINE OF RAILROAD AVENUE, EXCEPT AS APPROVED CURB SHALL BE PLACED AT A DEPTH OF 24" ALONG THE SOUTHERN CURB LINE OF RAILROAD AVENUE, EXCEPT AS APPROVED BY THE BOROUGH ENGINEER.

AutoCAD SHX Text

%%UTYPICAL CROSS SECTION

AutoCAD SHX Text

DETAIL A CONTRACTION JOINT

AutoCAD SHX Text

CLASS A CEMENT CONCRETE (3000 PSI)

AutoCAD SHX Text

CONTRACTION JOINT (SEE DETAIL A)

AutoCAD SHX Text

MATCH EXISTING CURB HEIGHT AND PROFILE

AutoCAD SHX Text 24"

AutoCAD SHX Text NOTE: : 1. THE CONTRACTOR SHALL BE RESPONSIBLE FOR SUPPLYING THE CONTRACTOR SHALL BE RESPONSIBLE FOR SUPPLYING ANY ADDITIONAL FITTINGS NEEDED TO CONNECT THE CURB STOP TO THE CUSTOMER SERVICE LINE IF THE LINE IS NOT 1" CTS PIPE. ALL ADDITIONAL FITTINGS SHALL BE APPROVED BY THE WATER AUTHORITY OR THEIR ASSIGNED DELEGATE PRIOR TO INSTALLATION. THE INSTALLATION OF ANY FITTINGS SHALL BE DOCUMENTED AND SUBMITTED TO THE AUTHORITY FOR THEIR RECORDS WITHIN 10 BUSINESS DAYS AFTER THE SUBSTANTIAL COMPLETION DATE OF THE PROJECT. 2. THE WATER SERVICE LINE FROM THE MAIN TO THE CURB STOP THE WATER SERVICE LINE FROM THE MAIN TO THE CURB STOP SHALL BE A CONTINUOUS LENGTH OF PIPE. NO COUPLERS ARE PERMITTED TO BE INSTALLED ON THE SERVICE LINE.

AutoCAD SHX Text 7/7/26

AutoCAD SHX Text

ADDENDUM 2

.5

.4

.3

.4

W. JEFFERSON AVE.

SR

(N . C

O

LL

EG

E

S T.

SR 0501 (N. COLLEGE ST.) WATER MAIN

SCALE:

H: 1" = 20' V: 1=5'

W . M ai n

St re et , S ui te

E Ep hr at a, P

A

2-

7.

1.

F:

7.

1.

H an ov er

En g.

co m

La nc as te r- Le ba no n O ffi ce

W. JEFFERSON AVE.

PIPE BEDDING

NOT TO SCALE

TEMPORARY RESTORATION

NOT TO SCALE

MAXIMUM TRENCH &

REPAVEMENT WIDTHS

NOT TO SCALE

TRENCH BACKFILL & RESTORATION

(UNPAVED AREAS)

NOT TO SCALE

TRENCH BACKFILL & RESTORATION

STATE HIGHWAY

NOT TO SCALE

LOCATION MAP

SCALE: 1" = 1,000'

USGS 7.5' QUAD

BETHEL, PA 2025

PROPOSED WATER

MAIN REPLACEMENT

HOP LOCATION

N. COLLEGE STREET

SR 0501

AutoCAD SHX Text

140 N. COLLEGE ST. LAYSER HOUSE

AutoCAD SHX Text

200 N. COLLEGE ST. LANG

AutoCAD SHX Text

HOUSE

AutoCAD SHX Text

201 N. COLLEGE ST.. MYERSTOWN WATER AUTHORITY

AutoCAD SHX Text

PUMP HOUSE FFE=519.61

AutoCAD SHX Text

APPROXIMATE LIMIT OF AERIAL WATER TANK

AutoCAD SHX Text

CONCRETE TANK PEDESTAL FOOTER (TYP)

AutoCAD SHX Text

NOTE: SEWER LATERAL LOCATED ON NORTH COLLEGE ST.

AutoCAD SHX Text

NOTE: SEWER LATERAL LOCATION UNKNOWN

AutoCAD SHX Text

NOTE: SEWER LATERAL LOCATED ON NORTH COLLEGE ST.

AutoCAD SHX Text

1.25" GAS MAIN IN STEEL CASE (APPROXIMATE)

AutoCAD SHX Text

PADOT LEGAL RIGHT-OF-WAY LINE

AutoCAD SHX Text

PADOT LEGAL RIGHT-OF-WAY LINE

AutoCAD SHX Text

11.8' LANE

AutoCAD SHX Text

14.4' LANE

AutoCAD SHX Text

16.2' LANE

AutoCAD SHX Text 50'

AutoCAD SHX Text 25'

AutoCAD SHX Text 25'

AutoCAD SHX Text 22.5°

AutoCAD SHX Text 45°

AutoCAD SHX Text

12" GV

AutoCAD SHX Text

12"X10" RDC

AutoCAD SHX Text 10"x10" TEE

AutoCAD SHX Text

CONNECT TO EX 10" DICL

AutoCAD SHX Text

PADOT LEGAL RIGHT-OF-WAY

AutoCAD SHX Text

10" DICL

AutoCAD SHX Text

EX 10"X8" RDC

AutoCAD SHX Text

EX 90°

AutoCAD SHX Text 8"x8" TEE

AutoCAD SHX Text

PADOT LEGAL RIGHT-OF-WAY

AutoCAD SHX Text

SR 0501 (N. COLLEGE ST.)

AutoCAD SHX Text

CONNECT TO EX 8" DICL

AutoCAD SHX Text

8" GV

AutoCAD SHX Text 45°

AutoCAD SHX Text

8" DICL

AutoCAD SHX Text

10" DICL

AutoCAD SHX Text

12" DICL

AutoCAD SHX Text

WATER MAIN REPLACEMENT

AutoCAD SHX Text

JEFFERSON AVENUE

AutoCAD SHX Text

DATE

AutoCAD SHX Text

NO.

AutoCAD SHX Text

REVISIONS

AutoCAD SHX Text THIS DOCUMENT IS THE PROPERTY OF HANOVER ENGINEERING ASSOCIATES, INC. ANY USE OF A COPY OF THIS DOCUMENT THAT DOES NOT CONTAIN AN ORIGINAL SEAL AND SIGNATURE IS STRICTLY PROHIBITED. THIS DOCUMENT IS NOT PUBLISHED AND ALL RIGHTS ARE RESERVED BY HANOVER ENGINEERING ASSOCIATES, INC. THIS PLAN HAS BEEN SEALED WITH EITHER A RED INK SEAL OR A CRIMP SEAL. IF NEITHER APPEARS ON THIS PLAN, POSSIBLE REPRODUCTIONS OR ALTERATIONS MAY HAVE BEEN MADE WITHOUT THE APPROVAL OR KNOWLEDGE OF THE SIGNATORY.

AutoCAD SHX Text

SEAL:

AutoCAD SHX Text

OF

AutoCAD SHX Text

ERK

AutoCAD SHX Text

FFF

AutoCAD SHX Text

25 JUNE 2026

AutoCAD SHX Text

MWA26-13

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text 1"=20'

AutoCAD SHX Text

SHEET NO.

AutoCAD SHX Text

PROJECT NO.

AutoCAD SHX Text

DRAWN BY:

AutoCAD SHX Text

CHECKED BY:

AutoCAD SHX Text

SCALE:

AutoCAD SHX Text

DATE:

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

AutoCAD SHX Text

MYERSTOWN WATER AUTHORITY LEBANON COUNTY PENNSYLVANIA

AutoCAD SHX Text

UTILTY PERMIT PLAN

AutoCAD SHX Text

HIGHWAY OCCUPANCY

AutoCAD SHX Text

O.D. 4 (6" MIN)

AutoCAD SHX Text

AASHTO #8 CRUSHED STONE

AutoCAD SHX Text

TRENCH SUBGRADE

AutoCAD SHX Text

PAVED AREAS

AutoCAD SHX Text

UNPAVED AREAS

AutoCAD SHX Text

EXISTING PAVED SURFACE

AutoCAD SHX Text

BACKFILL THE TRENCH WITH 2A AGGREGATE AND THOROUGHLY COMPACT.

AutoCAD SHX Text

AASHTO NO. 8 CRUSHED STONE BEDDING AND BACKFILL (SEE WATER\W002)

AutoCAD SHX Text APPROVED SUITABLE BACKFILL IN ACCORDANCE WITH THE SPECIFICATIONS TAMPED IN 6" LAYERS

AutoCAD SHX Text

2A CRUSHED STONE BACKFILL TAMPED IN 6" LAYERS

AutoCAD SHX Text

6" TOPSOIL

AutoCAD SHX Text PLACE AND COMPACT 2" OF 25mm SUPERPAVE MATERIAL, PG 64-22, 0.3 to < 3.0 MILLION ESALs TO MATCH EXISTING GRADE.

AutoCAD SHX Text

MAXIMUM PAYMENT WIDTH FOR REPAVING

AutoCAD SHX Text

4'-0" MIN COVER

AutoCAD SHX Text

TRENCH DEPTH

AutoCAD SHX Text 6"

AutoCAD SHX Text 8"

AutoCAD SHX Text 8"

AutoCAD SHX Text O.D.

AutoCAD SHX Text

MAX TRENCH WIDTH AT TOP OF PIPE

AutoCAD SHX Text

REPAVING, SEE WATER\W003, W007, W008, AND W009 FOR DETAILS

AutoCAD SHX Text

TRENCH DEPTH

AutoCAD SHX Text

MAXIMUM PAVEMENT WIDTH - REPAVING

AutoCAD SHX Text 0' - 12'

AutoCAD SHX Text O.D. + 3'-4"

AutoCAD SHX Text 12' - 18'

AutoCAD SHX Text O.D. + 4'-4"

AutoCAD SHX Text 18' - 24'

AutoCAD SHX Text O.D. + 5'-4"

AutoCAD SHX Text 24' - 30'

AutoCAD SHX Text O.D. + 6'-4"

AutoCAD SHX Text

LAWN AREAS

AutoCAD SHX Text

NOTE 4

AutoCAD SHX Text

STONE/EARTH DRIVES OR PARKING AREAS

AutoCAD SHX Text 12"

AutoCAD SHX Text 12"

AutoCAD SHX Text

SEE PIPE BEDDING DETAILS

AutoCAD SHX Text

ORDINARY BACKFILL

AutoCAD SHX Text

4" MIN TOPSOIL WHERE REQUIRED

AutoCAD SHX Text

NOTE 4

AutoCAD SHX Text

SEE PIPE BEDDING DETAILS

AutoCAD SHX Text

2A STONE

AutoCAD SHX Text

2A STONE

AutoCAD SHX Text

12" (MIN)

AutoCAD SHX Text

12" (MIN)

AutoCAD SHX Text

8" 2A SUBBASE OR MATCH EXISTING WHICHEVER IS GREATER

AutoCAD SHX Text NOTES: : 1. ALL BACK FILL MATERIAL IS SUBJECT TO ENGINEER APPROVAL. ALL BACK FILL MATERIAL IS SUBJECT TO ENGINEER APPROVAL. 2. SHOP DRAWINGS SHALL BE SUBMITTED FOR ALL COMPACTION SHOP DRAWINGS SHALL BE SUBMITTED FOR ALL COMPACTION EQUIPMENT. 3. COMPACT IN ACCORDANCE W/MOST RECENT REVISION OF COMPACT IN ACCORDANCE W/MOST RECENT REVISION OF PENNDOT PUBLICATION 408, "STANDARD SPECIFICATIONS"

AutoCAD SHX Text SPAV, BASE PG64S-22, 25mm 3.0 to 30.0 MILLION ESALs, 5.0" OR MATCH EXISTING WHICHEVER IS GREATER

AutoCAD SHX Text SPAV, WRG, PG 64S-22, 12.5mm 3.O to 30.0 MILLION ESALs, 2.0" DEPTH, SRL-H

AutoCAD SHX Text

SEAL W/ PG64S-22 ASPHALT CEMENT (TYP)

AutoCAD SHX Text

SAWCUT (TYP)

AutoCAD SHX Text

PENNDOT 2A STONE

AutoCAD SHX Text

SEE PIPE BEDDING DETAIL

AutoCAD SHX Text

EXISTING PAVEMENT

AutoCAD SHX Text

EXISTING PAVEMENT

AutoCAD SHX Text

1. MAINTENANCE AND PROTECTION OF TRAFFIC DURING MAINTENANCE AND PROTECTION OF TRAFFIC DURING CONSTRUCTION SHALL BE IN ACCORDANCE WITH PENNDOT PUB. 213, "TEMPORARY TRAFFIC CONTROL GUIDELINES," APRIL 2022 OR MOST CURRENT. 2. ALL WZTC SIGNING IS TO BE TYPE III OR TYPE IV ALL WZTC SIGNING IS TO BE TYPE III OR TYPE IV SHEETING. 3. USE "ROAD WORK" LEGEND IN LIEU OF "ROAD USE "ROAD WORK" LEGEND IN LIEU OF "ROAD CONSTRUCTION" LEGEND ON ALL APPLICABLE SIGNS. 4. REMOVE ALL SHORT-TERM WZTC SIGNING UPON REMOVE ALL SHORT-TERM WZTC SIGNING UPON COMPLETION OF THAT DAY'S WORK PERIOD. 5. NO TRAFFIC RESTRICTIONS OR LANE CLOSURES ARE NO TRAFFIC RESTRICTIONS OR LANE CLOSURES ARE PERMITTED ON LEGAL HOLIDAYS OR WEEKENDS ASSOCIATED WITH LEGAL HOLIDAYS. 6. NOTIFY THE LOCAL MUNICIPALITY WHEN A SIGNALIZED NOTIFY THE LOCAL MUNICIPALITY WHEN A SIGNALIZED INTERSECTION FALLS WITHIN THE WORK ZONE. DO NOT FLAG A SIGNALIZED INTERSECTION WITHOUT THE MUNICIPALITY PLACING A SIGNAL ON FLASH. 7. DO NOT STOP TRAFFIC FLOW WITHIN THE WORK AREA DO NOT STOP TRAFFIC FLOW WITHIN THE WORK AREA FOR MORE THAN A 5-MINUTE PERIOD AT ANY ONE TIME. 8. THE FOLLOWING CONSTITUTES THE REQUIRED WZTC WHEN THE FOLLOWING CONSTITUTES THE REQUIRED WZTC WHEN CONDUCTING ANY CONSTRUCTION ACTIVITIES WITHIN THE DEPARTMENT RIGHT-OF-WAY. A. SHORT TERM SIGNING: PUBLICATION 213 PATA SHORT TERM SIGNING: PUBLICATION 213 PATA FIGURES 106, 107, AND 110 SERIES (AS APPLICABLE TO SITE CONDITIONS).

AutoCAD SHX Text

1. THIS WORK CONSISTS OF THE MAINTENANCE AND PROTECTION THIS WORK CONSISTS OF THE MAINTENANCE AND PROTECTION OF TRAFFIC AND THE PROTECTION OF THE PUBLIC WHEN APPROACHING AND DEPARTING THE CONSTRUCTION AREA AND WITHIN THE LIMITS OF CONSTRUCTION. 2. FURNISH, ERECT, PLACE AND MAINTAIN TRAFFIC CONTROL FURNISH, ERECT, PLACE AND MAINTAIN TRAFFIC CONTROL SIGNS AND DEVICES. MAINTAIN TRAFFIC DURING HOURS OF CONSTRUCTION AND AT ALL OTHER TIMES CONSISTENT WITH THE METHODS INDICATED ON THESE DRAWINGS AND THE FOLLOWING: A. PENNDOT PUBLICATION 35 PENNDOT PUBLICATION 35 B. PENNDOT PUBLICATION 46 PENNDOT PUBLICATION 46 C. PENNDOT PUBLICATION 72M PENNDOT PUBLICATION 72M D. PENNDOT PUBLICATION 111 PENNDOT PUBLICATION 111 E. PENNDOT PUBLICATION 212 PENNDOT PUBLICATION 212 F. PENNDOT PUBLICATION 213 PENNDOT PUBLICATION 213 G. PENNDOT PUBLICATION 236 PENNDOT PUBLICATION 236 H. PENNDOT PUBLICATION 408 PENNDOT PUBLICATION 408 I. MUTCD, CURRENT EDITION MUTCD, CURRENT EDITION 3. REMOVE THESE DEVICES IMMEDIATELY UPON COMPLETION OF REMOVE THESE DEVICES IMMEDIATELY UPON COMPLETION OF THE WORK. PENNDOT WILL REMOVE ANY TRAFFIC CONTROL DEVICES ERECTED BY DEPARTMENT FORCES. 4. COVER OR REMOVE ALL CONFLICTING SIGNS AND ERADICATE COVER OR REMOVE ALL CONFLICTING SIGNS AND ERADICATE ALL CONFLICTING PAVEMENT MARKINGS. 5. MOUNT ALL LONG-TERM ADVANCE WARNING SIGNS ON TYPE III MOUNT ALL LONG-TERM ADVANCE WARNING SIGNS ON TYPE III BARRICADES UNLESS OTHERWISE NOTED OR INSTRUCTED BY DISTRICT OFFICE. 6. ALL SIGNS AND DEVICES TO BE MAINTAINED IN NEW OR ALL SIGNS AND DEVICES TO BE MAINTAINED IN NEW OR LIKE NEW CONDITION. 5. NOTIFY PROPERTY OWNERS 72 HOURS PRIOR TO ANY NOTIFY PROPERTY OWNERS 72 HOURS PRIOR TO ANY INTERRUPTIONS TO DRIVEWAY ACCESS. (COORDINATE WITH OWNERS AND MINIMIZE ACCESS CLOSURE). 6. LOCATE ALL SIGNS SO THAT SIGHT DISTANCES WILL NOT BE LOCATE ALL SIGNS SO THAT SIGHT DISTANCES WILL NOT BE OBSTRUCTED AT DRIVEWAYS AND LOCAL ROADS. 7. ALL CHANNELIZING DEVICES, BARRICADES, AND SIGNS ALL CHANNELIZING DEVICES, BARRICADES, AND SIGNS SHALL HAVE TYPE III OR BETTER PRISMATIC RETROREFLECTIVE SHEETING. SHEETING SHALL BE APPROVED AND LISTED IN PENNDOT PUBLICATION 35 (BULLETIN 15). 8. NO TRAFFIC RESTRICTIONS OR LANE CLOSURES ARE NO TRAFFIC RESTRICTIONS OR LANE CLOSURES ARE PERMITTED BETWEEN 6:00AM AND 9:00 AM BETWEEN 3:00 PM AND 7:00 PM MONDAYS THROUGH FRIDAYS OR ON LEGAL HOLIDAYS AND WEEKENDS ASSOCIATED WITH LEGAL HOLIDAYS. ALL RESTRICTIONS AND CLOSURES ARE TO BE REMOVED BY NOON ON THE DAY PRIOR TO THE LEGAL HOLIDAY. 9. PERMITTEE SHALL NOTIFY LOCAL EMERGENCY AUTHORITIES PERMITTEE SHALL NOTIFY LOCAL EMERGENCY AUTHORITIES (E.G., POLICE, FIRE, MEDICAL).

This is the start of the file's text. The full file is on GovTribe.

File details come from the government source that posted it. Updated .